DESIGN ANALYSIS

I. LIGHTHING AND CONVENIENCE RECEPTACLE LOAD:


(SEE SEC. 2.20.3.23, PEC 2017)

LIGHTING & CONVENIENCE RECEPTACLE LOAD:


(SEE SEC. 2.20.3.23, PEC-2017)
1020 sq. m x 24 VA/sq. m = 26400 VA
PROVIDE 20-15A & 17-20A FOR LIGHTING
& CONVENIENCE RECEPTACLE CIRCUITS
TOTAL ACTUAL LOAD: =26400 VA

II. AIR CONDITIONING LOAD


10-1.0HP ROOM AIR CONDITIONING UNIT
(SEE SEC. 2.20.3.23 & TABLE 4.30.14.2, PEC-2017)
8 A x 230V x 10 = 18400 VA
PROVIDE 9-30A ROOM ACU CIRCUITS
TOTAL = 18400 VA

III. OTHER LOADS


1 REFRIGERATOR = 1500 VA
PROVIDE 1-30A REF CIRCUIT

1 WATER DISPENSER = 5000 VA


PROVIDE 1-30A REF CIRCUIT

1 - 5KW WATER HEATER = 5000 VA


PROVIDE 2-30A WATER HEATER CIRCUIT

1 -1.5 HP WATER PUMP = 2300 VA


PROVIDE 1 -30 A WATER PUMP CIRCUIT

1 DISH WASHER = 400 VA


PROVIDE 1 -30 A WATER PUMP CIRCUIT

1 LAUNDRY WASHING MACHINE


(SEE SEC. 2.20.1.11(C)(2)) = 1500 VA
PROVIDE 1-20A WASHING MACHINE CIRCUIT

1-1500 SPARE = 1500 VA


TOTAL = 17 200 VA
APPLICATION OF DEMAND FACTOR:
(SEE SECTION 2.20.3.23)
17 200 VA x 0.40 = 6 880 VA

TOTAL NET COMPUTED LOADS


26400 + 18400 + 6880 = 51 680VA
CIRCUIT REQUIREMENT:
USE 20 - 15A 2-WIRE BRANCH CIRCUIT, 17 - 20A 2-WIRE BRANCH CIRCUIT, 19 -
30A 2-WIRE BRANCH CIRCUIT

SERVICE ENTRANCE CONDUCTORS


TOTAL FULL LOAD CURRENT: (SEE SECS,. 4.30.2.4 AND 4.40.1.7)
[51 680 VA + 25% (2300 VA)]/230V = 227.2 A
USE TWO 80 mm² THW WITH AN AMPACITY OF 220 A

SERVICE EQUIPMENT:
(A) MAXIMUM CURRENT RATING OF PROTECTIVE DEVICE
(SEE SEC. 4.30.4.4 & TABLE 4.30.2)

1. NONTIME DELAY FUSE


[300% (2300 VA) + 26400 + 18400 + 6880]/230 = 254.7 A

2. INVERSE TIME CIRCUIT BREAKER


[250% (2300 VA) + 26400 + 18400 + 6880]/230 = 249.7 A

(B) SERVICE EQUIPMENT RATING


USE 1-300 A, 1PST, 250 V SAFETY SWITCH WITH 1-300A FUSE OR USE 1-400A TRIP,
2 POLE, 240V 10 KAIC MOLDED CASE CIRCUIT BREAKER (SEE SECTION 2.40.2.3)