Single Family Dwelling Unit, 156.

75 Square Meters Floor Area, 400/230 Volts Three Phase 4-Wire


Service

Total Load:
(A)General Lighting and Convenience Receptacle Load: [Table 2.20.2.23]
19 x 100 VA = 1900 VA
Provide two 20-ampere lighting circuits.

17 x 100 VA = 1700 VA
Provide three 20-ampere spare lighting circuit.

8 x 180 VA = 1440 VA
Provide two 20-convenience receptacle circuits.

8 x 180 VA = 1440 VA
Provide two 20-convenience spare receptacle circuit.

A= 408(24) = 9792 VA
Total Load =11232 VA

(B) Air Conditioning Load: (Section 2.20.3.23)


Three 6-kVA package type air-conditioning units =18000 VA
Provide three 40-ampere 3-pole package ACU circuits

Five 1.5-Hp room air-conditioning units


10 A x 230 V x 5 =11500 VA
Provide five 30-ampere room ACU circuits

Total Load =29500 VA

(C) Cooking Load: (Section 2.20.3.16)


Two 4-kW wall mounted ovens
4000 VA x 2 =8000 VA
Provide two 30-ampere wall mounted oven circuits.

One 8kW electric range =8000 VA


Provide one 40-ampere electric range circuit

Subtotal Load =16000 VA

Application of Demand Factor: (Table 2.20.3.16 Column C)


16000 VA x 0.55 =8800 VA

One 1.5-kW microwave oven circuit


(Table 2.20.3.16 Column B) =1200 VA
Provide one 20-ampere microwave oven circuit

One 12kW electric range =8000 VA


(Table 2.20.3.16 Column A)
Provide one 40-ampere electric range circuit
Total Load =18000 VA

(D) Other Load: (Table 2.20.3.16)

One refrigerator @ 5000 VA = 5000 VA


Provide one 30-ampere laundry circuit
One 5-kW clothes dryer = 5000 VA
Provide one 30-ampere clothes dryer circuit

Five 5-kW water heater


5000 x 5 =25000 VA
Provide five 30-ampere water heater circuits

One 1.5-Hp water pump =2300 VA


10 A x 230 V
Provide one 30-ampere clothes dryer circuit

Four spares
2000 x 4 =8000 VA
Provide four 30-ampere for spare
Subtotal =45300 VA

Application of Demand Factors: (Section 2.20.3.23)


(37300 x 40%) = 14920 VA

Total Net Computed Load = 72212 VA

Branch Circuit Arrangement:


A 3-phase fusible or circuit breaker type panelboard shall be provided for balanced distribution of
single-phase loads.

Circuit Requirement:
Use four 40-ampere 3-wire branch circuits, sixteen 20-ampere 2-wire branch circuits, fifteen 30-ampere
2-wire branch circuits, one 50-ampere 2-wire branch circuit, and one 70-ampere 2-wire branch circuits.

Main Service Entrance Conductors:


Total Full Load Current: (Section 4.30.2.4 and 4.40.1.7)
[72212 VA + 25% (6000 VA)] ÷ (400V)(√3) = 106.39 A
Use: 3C-60 mm2 + 1C-6O mm2 (NEUTRAL) THHN WIRE

Main Service Equipment:


Non-time Delay Fuse
[(6000VA) + 72212] ÷ (400V)(√3) = 112.89 A
Inverse Time Circuit Breaker
[250%(6000VA) + 72212] ÷ (400V)(√3) = 125.88 A

Service Equipment:
USE ONE 159 AMPERE, 3-POLE, 415VOL MOLDED CASE CIRCUIT