An equipment draws from the supply system a 1000 kVA load with a 0.8 power
factor lagging. Find the real and reactive power of the system.
[800 W, 600 kvar]
2.
In the power triangle of figures below, calculate the missing parameters; the
reactive power (Q), real power (P) or apparent power (S).
For the given voltages and current below, calculate the complex power S,
apparent power S, real power P and reactive power Q. Determine also whether
the power factor is leading or lagging.
I = 560
a) V = 24030
b) V = 22030
I = 520
c) V = 2400
I = 520
d) V = 11030
I = 820
[1200-30VA, 1200 VA, 1.04 kW, -600var, 0.866 leading]
4.
5.
6.
Two loads connected in parallel are supplied from a single-phase 240-V rms
source. The two loads draw a total real power of 400 kW at a power factor of 0.8
lagging. One of the loads draws 120 kW at a power factor of 0.96 leading. Find
the complex power of the other load.
[436.650.1 kVA]
7.
[60 , 80 , 125016.26 V]
8.
a) Find the complex power S1, S2 for the two impedances, and S3 for the motor.
b) Determine the total power taken from the supply, the supply current, and the
overall power factor.
c) A capacitor is connected in parallel with the loads. Find the kVAR and the
capacitance in F to improve the overall power factor to unity. What is the
new line current?
9.