Professional Documents
Culture Documents
CHAPTER 1
EXAMPLE
EXAMPLE
CHAPTER 2
Example
CIRCUIT DIAGRAM
SLnew = PL + jQLnew
-jQC PLnew = PL
V C
SL = PL + jQL
SLnew QLnew
= 5.263 kVA = 1.6434 kVAR
QL=3.75 KVAr
QC
SL = - 2.1066 kVAR
= 6.25kVA
192
5
V2
V1 = 120/0o
j6
n
Example
a
Ia a
Wan
In Z
3-phase n
208 V n Z = 2.6667 + j2
60 Hz Ib Z Z
Supply b Wbn c
LL Ic b
c
Wcn
(a) Determine all V ' s (Van , Vbn , Vcn , Vab , Vbc , and Vca ).
(b) Determine all I ' s ( I a , I b , I c , and I n ).
(c) Determine all S ' s ( S an , Sbn , Scn , and STOTAL ).
(d) Determine the wattmeter readings Wan, Wbn, and Wcn.
(e) Draw the phasor diagram for all the V ' s and I ' s .
193
(e)
194
CHAPTER 3
Example
Example
Consider that a transmission line between two buses “1” and “3” in
a power system is at 500 kV and two 345/500 kV transformers are
used at both ends, as shown in the one-line diagram of Fig. 1. In the
per-unit study, if the system base voltage is 345 kV, then the line
impedance and the transformer leakage impedances are all
calculated on the 345-kV voltage base, and 100 MVA base. The
transmission line impedance parameters are given in Fig. 1. Neglect
line susceptances. Each transformer has a leakage reactance of 0.2
pu on the 345-kV and 100 MVA base. The 500-kV transmission line
is 200-km long.
345/500 kV 500/345 kV
Fig. 1
197
j0.15 j0.15
Vg Vm
Eg Em
198
#4(c)
V = 20000;
Xd = 13.5;
Xq = 9.333;
theta = acos(0.8);
Ia = 20E06/20000;
delta = atan(Xq*Ia*cos(theta)/(V + Xq*Ia*sin(theta)));
deltadg = delta*180/pi;
E = V*cos(delta) + Xd*Ia*sin(theta + delta);
% Excitation voltage in KV
E_KV = E/1000;
fprintf('Power angle = %g Degree \n', deltadg)
fprintf(' E = %g KV \n\n', E_KV)
deltadg = (0:.25:180)';
delta = deltadg*pi/180;
P = 3*E*V/Xd*sin(delta) + 3*V^2*(Xd -
Xq)/(2*Xd*Xq)*sin(2*delta);
% Power in MW
P = P/1000000;
plot(deltadg, P), grid
xlabel('Delta - Degree'), ylabel('P - MW')
[Pmax, k] = max(P);
delmax = deltadg(k);
140
P - MW
120
100
80
60
40
20
0
0 50 100 150 200
Delta - Degree
201
Example
SOLUTION
(a)
I1= I1rated Req1 jXeq1
V1
480:120
Gc -jBm V2 = 120/0o
V1
480:120
202
Example
SOLUTION
(a) Y – Y Transformer
Ia jXeq1 IA = 0.8333/-25.84o p.u.
(b) - Y Transformer
o
1: e j 30
203
90 V 100 A
175 A
210 V
120 V 75 A
120 V
204
CHAPTER 4
Example
x y
D = 7.5 cm
Dxy = 7 m
205
a b c
D12 = 8 m D23 = 8 m
D13 = 16 m
a b c
40 cm
D12 = 8 m D23 = 8 m
D13 = 16 m
206
a b c
45 cm
D12 = 14 m D23 = 14 m
D13 = 28 m
207
Example
Consider a 345-kV transmission line that consists of 3L3 type towers
shown in Fig. 1. This transmission system consists of a single-
conductor per phase which is Bluebird ACSR with diameter of
1.762 inches. Ignore the effect of ground, ground wires and
conductor sags.
(a) Calculate L(/km).
(b) Calculate C(S/km).
(c) Compare the results with those given in Table 1.
G1 10.12 m G2
9.63 m
C1 C2 C3
7.5 m 7.5 m
17 m
Fig. 1
Table 1 Line Parameters with Balanced with Bundled Conductors (except at 230
kV) at 60 Hz
Nominal Voltage R (/km) L (/km) C (S/km)
230 kV 0.055 0.489 3.373
345 kV 0.037 0.376 4.518
500 kV 0.029 0.326 5.220
765 kV 0.13 0.339 4.988
208
CHAPTER 6
In polar form
36.7539/275.62o 21.0022/95.62o 15.751/95.62o
Ybus = 21.0022/95.62o 41.8027/275.62o 21.0022/95.62o
15.751/95.62o 21.0022/95.62o 36.7539/275.62o
Pi Pi
(i) Find partial derivatives and
k Vk
for i = 2; and k = 2, 3
P2 = |V2||V1||Y21|cos(21 - 2 + 1)
+|V2||V2||Y22|cos(22)
+ |V2||V3||Y23|cos(23 - 2 + 3)
P2
| V2 || V1 || Y21 | sin( 21 2 1 )
2
211
| V2 || V3 || Y23 | sin( 23 2 3 )
P2
| V2 || V3 || Y23 | sin( 23 2 3 )
3
P2
0 (V2mag is constant – controlled bus)
| V2 |
P2
| V2 || Y23 | cos( 23 2 3 )
| V3 |
for i = 3; and k = 2, 3
P3 = |V3||V1||Y31|cos(31 - 3 + 1)
+|V3||V2||Y32|cos(32 - 3 + 2)
+ |V3||V3||Y33|cos(33)
P3
| V3 || V2 || Y32 | sin( 32 3 2 )
2
P3
| V3 || V1 || Y31 | sin( 31 3 1 )
3
| V3 || V2 || Y32 | sin( 32 3 2 )
P3
0 (V2mag is constant – controlled bus)
| V2 |
P3
| V1 || Y31 | cos( 31 3 1 )
V3
| V2 || Y32 | cos( 32 3 2 ) 2V3Y33 cos( 33 )
Qi Qi
(i) Find partial derivatives and
k Vk
for i = 2; and k = 2, 3
Q2
| V2 || V1 || Y21 | cos( 21 2 1 )
2
| V2 || V3 || Y23 | cos( 23 2 3 )
Q2
| V2 || V3 || Y23 | cos( 22 2 2 )
3
V2
0 (V2mag is constant – controlled bus)
| V2 |
Q2
| V2 || Y23 | sin( 23 2 3 )
| V3 |
for i = 3; and k = 2, 3
Q3
| V3 || V2 || Y32 | cos( 32 3 2 )
2
Q3
| V3 || V1 || Y31 | cos( 31 3 1 )
3
| V3 || V2 || Y32 | cos( 32 3 2 )
Q3
0 (V2mag is constant – controlled bus)
| V2 |
Q3
| V1 || Y31 | sin( 31 3 1 )
| V3 |
| V2 || Y32 | sin( 32 3 2 ) 2 | V3 || Y33 | sin( 33 )
P J1 J2
= (6.54)
Q J3 J4 |V|
213
P
= (6.54)
Q |V|
Similarly,
P2
J (1,2) ( 0 ) | V2 || V3( 0 ) || Y23 | sin( 22 2( 0 ) 1 )
3
J(1, 2)(0) = -21.9464 pu
P2
J (1,3) ( 0 ) | V2 || Y23 | sin( 23 2( 0 ) 3( 0 ) )
| V3 |
J(1, 3)(0) = -2.596 pu
P3
J ( 2,1) ( 0 ) | V3( 0 ) || V2 || Y32 | sin( 32 3( 0 ) 2( 0 ) )
2
J(2, 1)(0) = -21.9464 pu
P3
J ( 2,2) ( 0 ) | V3( 0 ) || V1 || Y31 | sin( 31 3( 0 ) 1 )
3
| V3( 0 ) || V2 || Y32 | sin( 32 (30 ) (20 ) )
J(2, 2)(0) = 37.6224 pu
P3
J ( 2,3) ( 0 ) | V1 || Y31 | cos( 31 3( 0 ) 1 )
V3
| V2 || Y32 | cos( 32 (30 ) (20 ) )
2V3Y33 cos( 33 )
J(2, 3)(0) = 3.4965 pu
215
Q3
J (3,1) ( 0 ) | V3( 0 ) || V2 || Y32 | cos( 32 3( 0 ) 2( 0 ) )
2
J(3, 1)(0) = -21.9464 pu
Q3
J (3,2) ( 0 ) | V3( 0 ) || V1 || Y31 | cos( 31 3( 0 ) 1 )
3
| V3( 0 ) || V2 || Y32 | cos( 32 3( 0 ) 2( 0 ) )
J(3, 2)(0) = -3.7022 pu
Q3
J (3,3) ( 0 ) | V1 || Y31 | sin( 31 3( 0 ) 1 )
| V3 |
| V2 || Y32 | sin( 32 3( 0 ) 2 ) 2 | V3( 0 ) || Y33 | sin( 33 )
J(3, 3)(0) = 35.5323 pu
(f) Obtain the new bus voltages in this first iteration as:
2(1) 2( 0 ) 2(1)
3(1) 3( 0 ) 3(1)
| V3(1) | V3( 0 ) | V3(1) |
V1 = 1.0/0o V3 = 0.978/-8.79o
2.39 + j0.29 pu
0.69 – j1.11 pu
(5.0 + j1.0)
P1 + j Q1 = (3.8 - j0.82) pu
2.68 + j1.48 pu
o
V2 = 1.05/-2.07
P2 + j Q2 = (2.0 + j2.67) pu
Fig. 1
218
Example
4 – x2 = 0 (1)
where c = 4 and f(x) = x2. Solve for x which satisfies the equation (1)
with an error below a tolerance of 0.0002.
10
y
0
1 2 3 4 5 6 7 8 x
-10
-20
-30
-40
-50
220
CHAPTER 9
Example
CIRCUIT DIAGRAM
R X i(t)
t=0
2Vsin(wt + ) SW
e(t)
221
CIRCUIT DIAGRAM
V1(f) = 1.0 pu V 2
3 j0.1 pu
1 j0.1 pu
I1(f)
Ig1 Ig2
j0.1 pu j0.2 pu
j0.08 pu
In parallel
I1(f)
1 V1(f) = 1.0 pu V
j0.12 pu
j0.08 pu
222
CIRCUIT DIAGRAM
1 j0.1 pu j0.06 pu 3
Zeq
j0.0.06 pu
I4(F) j0.19 pu
1.0 pu V V4(F)
j0.25 pu
223
Example 4
IF1 Ig2
=I g1 VF
+ Eg VF Em
IF2
IF1 = IF j0.15 pu
=I g1 VF
+ Eg Em
Example 6
CIRCUIT DIAGRAM
1 j0.305 pu 2
1 j0.1 pu j0.1 pu 2
Em Eg Em
Eg
1 -j3.2787 pu 2
1. Find the admittance of
individual line
-j6.6667 pu -j5.0 pu 2. Use Power Flow method
to assemble [Ybus]
Eg Em
CHAPTER 10
Example
Example 3
Athree-phase line feeding a balanced-Y load has one of its phases
(phase-b) open. The load neutral is grounded, and unbalanced line
currents are:
Ia = 10/0o A; Ib = 0 A; Ic = 10/+120o A;
CIRCUIT DIAGRAM
Ia = 10/0o A
Ic = 10/120o
In
Ib = 0 A
I2b
I1c
I1a I2c
j3Xn= j0.1 pu
Example FAULT-1
Bus 1 X1 = X2 = 20 Bus 2
X0 = 60
M
2
(a) 1 j0.1 pu j0.315 pu j0.1 pu
0 I0m j0.1 pu
I L
j0.05 pu
j0.15 pu
o Em = 1.05/0o pu
Eg = 1.05/0 pu
(b)
Zero-sequence Network (Thevenin’s Equivalent)
2
VTh = 0
(No voltage Source)
I0m j0.1 pu
ZTh
I1L I1m
j0.15 pu ZTh
j0.2 pu
j 0.455 x0.2
Z TH j 0.138931 pu
0.655
I2L I2m
j0.17 pu ZTh
j0.21 pu
j 0.475 x0.21
Z TH j 0.14562 pu
0.685
234
0
j0.250 pu I a I1a
j0.13893 pu
Z0 Z1
V0a VF = 1.05/0o pu V1a
Z2
V2a
(c) 0
j0.250 pu I a
Z0
V0a
1
j0.13893 pu I a
Z1
o
VF = 1.05/0 pu V1a
2
j0.14562 pu I a
Z2
V2a
235
Z1 Z2
1
VF = 1.05/0o pu V a V2a
Calculate
(f) the subtransient fault current in each phase,
(g) neutral current, and
(h) contributions to the fault current from the motor and from the
transmission line,
for a bolted double line-to-ground fault from phase b to c to ground
at bus 2. Neglect the -Y transformer phase shift.
j0.13893 pu I1a
I2a I0a
Z1
VF = 1.05/0o pu V1a V2a j0.14562 pu V0a j0.250 pu
Z2 Z0
238
(a) 2
1 j0.1 pu j0.315 pu j0.1 pu
0 I0m j0.1 pu
I L
j0.05 pu
j0.15 pu
o Em = 1.05/0o pu
Eg = 1.05/0 pu
2 I2m
I L j0.21 pu
j0.17 pu