Professional Documents
Culture Documents
FAULTS
SYMMETRICAL COMPONENTS
I2b
I1c
I1a I2c
Current:
I a1 I a10o I a1
I c1 I a1120o aI a1
3 1
Note - a = 1120o = j = -0.5 + j0.866
2 2
1 3
a2 = 1240o = j = -0.5 - j0.866 (10.2)
2 2
a3 = 1360o = 1 + j0
and 1 + a + a2 = 0. (10.3)
Negative-Sequence (a-c-b) Phasor Equations:
I a2 I a20o I a2
I b2 I a2120o aI a2 (10.4)
I c2 I a2 240o a 2 I a2
Phase a current: I a I a0 I a1 I a2
Phase c current: I c I c0 I c1 I c2
Phase a current: I a I a0 I a1 I a2
Phase c current: I c I a0 aI a1 a 2 I a2
In matrix notation
Ia 1 1 1 I a0
1 a2 a (10.8)
Ib I a1
Ic 1 a a2 I a2
where
1 1 1
1 a2 a (10.10)
A
1 a a2
where
1 1 1
1
A-1 1 a a2 (10.12)
3
1 a2 a
And
1 *
A 1 A (10.13)
3
Express the three-phase currents in the phase a components
I a0 1 1 1 Ia
1
I 1 1 a a2 Ib
a 3 (10.14)
I a2 1 a2 a Ic
or
I a0
1
Ia Ib Ic
3
1
I a1 I a aI b a 2 I c
3
(10.15)
1
I a2 I a a 2 I b aI c
3
Voltage:
Similarly,
In matrix notation
Va 1 1 1 Va0
1 a2 a
Vb Va1
Vc 1 a a2 Va2
1 1 1
1 a2 a
A
1 a a2
where
1 1 1
1
A-1 1 a a2
3
1 a2 a
And
1 *
A 1 A
3
Express the three-phase voltages in the phase a components
Va0 1 1 1 Va
1
V 1 1 a a2
a 3 Vb
Va2 1 a2 a Vc
or
Va0
1
Va Vb Vc
3
1
Va1 Va aVb a 2Vc
3
(10.18)
1
Va2 Va a 2Vb aVc
3
Complex Power:
S V I
*
abc T abc *
( 3 ) (10.20)
S 3V I ;
( 3 ) a
012 T 012 *
a with AT = A and ATA* = 3
(10.22)
leading to
A three-phase line feeding a balanced-Y load has one of its phases (phase-b)
open. The load neutral is grounded, and unbalanced line currents are:
Ia = 10/0o A; Ib = 0 A; Ic = 10/+120o A;
Ic = 10/120o
In
Ib = 0 A
I2b
I1c
I1a I2c
SEQUENCE NETWORKS
Y-Connected Loads:
Zs + 3Zn + 2Zm 0 0
Z 012 0 Zs - Zm 0
0 0 Zs - Zm
Zs + 3Zn 0 0
Z 012 0 Zs 0
0 0 Zs
Transmission Line:
Dn
- Zero-sequence: X0 = X1 + 3Xn where X n 2f 0.2 ln
D
- The zero-sequence is more than three times larger than positive- or
negative-impedance.
Synchronous Machine:
Transformer:
Modeled with the leakage impedance. The leakage impedance does not
change even if the phase sequence is changed. The positive- and negative-
sequence impedances are the same. If the transformer permits the zero-
sequence to flow at all, the phase impedance to zero-sequence is equal to the
leakage impedance.
Z0 = Z1 = Z2 = ZT.
Va0 0 Z 0 I a0
Va1 Ea Z 1 I a1
Va2 0 Z 2 I a2
Sequence Phase Shifts Through Wye-Delta (Y-) Transformer Banks:
IA = n(Ia – Ic)
and
Va = n(VA – VB)
For positive-sequence:
I 1A n I a1 aI a1 n 1 a ) I a1
where a = 1120o
Va1 n VA1 aVA1 n 1 aVA1
Va1 3nV A1 30o NV A1 30o
For negative-sequence:
I A2 n I a2 a 2 I a2 n 1 a 2 I a2
where a = 1240o
Va2 n V A2 aVA2 n 1 aVA2
Va2 3nV A2 30o NV A2 30o
FAULT
Sequence Networks:
simplified diagram
Note –
Vk (0)
Ik ( F )
Z kk Z f
3 Ea
I a 3 I a0
Z 1 Z 2 Z 0 3Z f
Vk (0)
I 0k I 1k I 1k
Z 1kk Z kk
2
Z 0kk 3 Z f
where Z 1kk , Z kk
2
, and Z 0kk are the diagonal elements in the k axis of the
corresponding bus impedance matrix and Vk(0) is the prefault voltage
at bus k.
I kabc AI k012
Double Line-to-Ground (2LG) Faults:
Simplified
Ea
I a1
Z 2 ( Z 0 3Z f )
Z
1
Z 2 Z 0 3Z f
I f I b I c 3 I a0
Vk (0)
I k1
Z 2kk ( Z 0kk 3Z f )
Z kk
1
Z 2kk Z 0kk 3 Z f
where Z 1kk , Z kk
2
, and Z 0kk are the diagonal elements in the k axis of the
corresponding bus impedance matrix and Vk(0) is the prefault voltage
at bus k.
Vk (0) Z 1kk I k1
I k2 2
Z kk
Vk (0) Z 1kk I k1
I k0
Z 0kk 3 Z f
Ea
I a1
Z1 Z 2 Z f
I b I c a 2 a I a1 j 3I a1
I k0 0
Vk (0)
I k1 I k1
Z 1kk Z 2kk 3Z f
where Z 1kk , Z kk
2
, and Z 0kk are the diagonal elements in the k axis of the
corresponding bus impedance matrix and Vk(0) is the prefault voltage
at bus k.
EXAMPLE
Bus 1 X1 = X2 = 20 Bus 2
X0 = 60
M
0 I0m j0.1 pu
I L
j0.05 pu
j0.15 pu
o Em = 1.05/0o pu
Eg = 1.05/0 pu
(b)
Zero-sequence Network (Thevenin’s Equivalent)
2
VTh = 0
(No voltage Source)
I0m j0.1 pu
ZTh
I1L I1m
j0.15 pu ZTh
j0.2 pu
j 0.455 x0.2
Z TH j 0.138931 pu
0.655
I2L I2m
j0.17 pu ZTh
j0.21 pu
j 0.475 x0.21
Z TH j 0.14562 pu
0.685
0
j0.250 pu I a I1a
j0.13893 pu
Z0 Z1
V0a VF = 1.05/0 puo V1a
Z2
V2a
(c) 0
j0.250 pu I a
Z0
V0a
1
j0.13893 pu I a
Z1
o
VF = 1.05/0 pu V1a
2
j0.14562 pu I a
Z2
V2a
EXAMPLE Continue Example ON FAULT-1
Faults at buses 1 and 2 for the three-phase power system given in example
above are of interest. The prefault voltage is 1.05 pu. Prefault load current is
neglected.
(a) Determine the per-unit zero-, positive-, and negative-sequence bus
impedance matrices.
(b) Find the subtransient fault current in per-unit for a bolted single line-
to-ground fault current from phase a to ground at bus 1.
(c) Find the subtransient fault current in per-unit for a bolted single line-
to-ground fault current from phase a to ground at bus 2.
(d) Find the per-unit line-to-ground voltages at bus 1 during the single line-
to-ground fault at bus 1.
(e) Find the per-unit line-to-ground voltages at bus 2 during the single line-
to-ground fault at bus 1.
(a) 2
1 j0.1 pu j0.315 pu j0.1 pu
0 I0m j0.1 pu
I L
j0.05 pu
j0.15 pu
o Em = 1.05/0o pu
Eg = 1.05/0 pu
2 I2m
I L j0.21 pu
j0.17 pu