A.

GENERAL LOADS
LIGHTING OUTLET
CONVENIENCE OUTLET
REFRIGERATOR
WACHING MACHINE
SPARE
SUB - TOTAL

=
=
=
=
=
=

615 W
4140 W
600 W
1500 W
4000 W
10855 W

3000 W

2749.25 W

SERVICE ENTRANCE CONDUCTORS


TOTAL FULL LOAD CURRENT:
[ 9755.65 + 25% (1500) ]
= 44.05 A

230

THEREFORE, USE 2 - 30 mm THW on 25 mm

RSC

DEMAND FACTOR (D.F.):


FIRST 3000 W @100% D.F.
REMAINDER @ 35% D.F.
( 8405 - 3000) x 0.35

SERVICE EQUIPMENT
INVERSE TIME CIRCUIT BREAKER:

[ 3000 + 2749.25 + 6400 + 3355.65 + 250% (1500) + 1500 ]


230

B. OTHER LOADS
1 - 8-kW RANGE @ 80% D.F.

6400 W

2 - 1-HP ACU @ 100%

3355.65 W

= 90.24 A
THEREFORE, USE 125 AT CB

TOTAL NET COMPUTED LOAD: 16811.75 W

Certified by:

Owner:

Perez, Daniel S.

Engr. Paulo Tindogan


PRC # 032106
PTR # 000011

Content:

Location:
Lot13 Blk47, Southfairway, Landayan,
San Pedro, Laguna

Sheet Number

DESIGN ANALYSIS
R.A. 9266 SEC. 12 THESE DRAWINGS AS INSTRUMENT OF
SERVICE ARE PROPERTY AND DOCUMENTS OF THE AUTHOR.
IT SHALL BE UNLAWFUL FOR ANY PERSON WITHOUT WRITTEN
OR PRIOR CONSENT OF THE AUTHOR OF DUPLICATE OR COPY
THE SAID DOCUMENT

10
E-9