TAGANITO HPAL PROJECT

TAGANITO, SURIGAO DEL NORTE

DESIGN ANALYSIS

I. BRANCH CIRCUIT COMPUTATION

A. Circuit No. 1 - Lighting 0


Capacity = 3.45 kVA
Voltage = 230 V
Phase = 1Ph, 2W
P. F. = 1.00
Capacity (KVA) = 3.45 kVA

FULL LOAD CURRENT:


= 3.45 kVA X 1000
$ 1 X 230 V
FLC = 15.00 A

CB RATING: = 15.00 X 1.25 = 18.75 A


Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 20 AT 1P
50 AF MCCB
CABLE SIZE AMPACITY:

15.00 X 1.25 = 18.8 A


Article 2.10 .2.2 (A)(1)(a) Overcurrent Protection PEC 1 2017 page 43
1 SET/S 2 3.5 mm² THHN

VOLTAGE DROP CALCULATION:


* Allowable Voltage Drop for Branch Circuit say 3%

VD = 35.6 X 15.00 X 50 LM
= 7.63 Volts
1000 X 3.5 X 1 SET/S
%VD = 7.63 Volts
230 Volts
%VD = 3.32 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN

FOR BRANCH CIRCUIT NO 1 :


USE: 1 SET/S 2- 3.5 mm² THHN

FOR GROUND WIRE:


Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 1- 3.5 mm² Copper Wire

FOR CONDUIT SIZING:


Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 20.0 mmØ IMC