Professional Documents
Culture Documents
ENERGY CONSERVING
DESIGN OF BUILDINGS
BRIEF OVERVIEW
GUIDELINES FOR ENERGY CONSERVING DESIGN OF BUILDINGS
Section 1. Purpose
Section 2. Scope
Section 3. Lighting
Section 4 Electric Power & Distribution
Section 5. Building Envelope
Section 6. Air Conditioning & Ventilating
Systems
Section 7. Steam & Hot Water Systems
SECTION 1 - PURPOSE
To encourage and promote energy conserving design of
buildings and their services to reduce the use of energy
with due regard to the cost effectiveness, building
function, and comfort, health, safety and productivity of
the occupants.
3.1 Scope
Roads grounds and other exterior areas where lighting is required and is
energized through the building’s electrical service
Section 3 – Lighting
3.1 Exemptions
General Requirements
luminous efficacy
lamp control gear loss
lighting power density
General Requirements
General Requirements
Lighting Controls
Section 3 – Lighting
All Motors shall have full load efficiencies not less than the
values shown in Table 4.1.
The nameplates of these motors shall include not only all the
informations required by the Philippine Electrical Code, Part 1, but
also the rated full load efficiency and full load power factor as
determined by Philippine National Standard [PNS IEC
61972:2005 (IEC published 2002) Methods for Determining
Losses and Efficiency of Three Phase Cage Induction Motors].
Section 4 – Electrical Power and Distribution
4.3 Transformers
The electrical power feeders/ branch circuits for each facility of the
building for which sub-metering is required should be subdivided but
not limited to he following categories:
Lighting Load
Chillers
Air Handling Units, Unitary Air
Conditioning Systems, etc.
Other Motor Loads (Exhaust Fan,
Pumps, etc.)
Section 4 – Electrical Power and Distribution
Electrical Appliances
SECTION 5 – BUILDING ENVELOPE
5.1 Scope
The OTTV
OTTV Formula :
Where,
OTTV : overall thermal transfer value (W/m2)
Aw : opaque wall area (m2)
Uw : thermal transmittance of opaque wall (W/m2 oK)
TDeq : equivalent temperature difference (oK)
Af : fenestration area (m2)
Uf : thermal transmittance of fenestration (W/m2 oK)
∆T : temperature difference between exterior and interior
SC : shading coefficient of fenestration
SF : solar factor (W/m2)
Ao : gross area of exterior wall (m2)
= Aw + Af
Section 5 – Building Envelope
Solar Factor
The Solar Factor for vertical surfaces has been experimentally
determined to be at 130 W/m2. This figure has to be modified by
a correction factor when applied to a particular orientation and
also if the fenestration component is sloped at an angle skyward.
For the purpose of the building regulations, any construction
having a slope angle of more than 70o with respect to the
horizontal shall be treated as a wall. For a given orientation and
angle of slope, the Solar Factor is to be calculated from the
following formula:
SF = 130 x CF (W/m2)
Section 5 – Building Envelope
CORRECTION FACTORS
Slope Orien
Angle tation
N NE E S ES SW W NW
700 1.32 1.63 1.89 1.65 1.32 1.65 1.89 1.63
The correction factors for other orientations and other pitch angles can be found
by interpolation.
Section 5 – Building Envelope
Calculation of OTTVs
SECTION 6 – AIR CONDITIONING AND
VENTILATING SYSTEMS
6.1 Scope
Calculation Procedures
6.2.4 Ventilation
The quality and quantity of air used to ventilate
air-conditioned spaces shall always be sufficient and
acceptable to human occupation and comply with
applicable health and/or air quality requirements.
Ventilation requirements shall conform to the following
design criteria (Table 6.2.4)
Exception:
Outdoor air quantities may exceed those shown in Table
6.1 because of special occupancy or process
requirements, source control, air contamination or local
regulations.
Section 5 – Air Conditioning and Ventilating Systems
Individual VAV fans with motors rated at 7.5 KW and larger shall include controls and
devices such as variable speed drive necessary to make the fan motor operate
efficiently even at flow rates of as low as 40% of the rated flow.
Section 6 – Air Conditioning and Ventilating Systems
Design criteria for all pumping systems used for comfort air
conditioning. The energy demand of a pumping system is the sum of
the demand of all pumps that are required to operate at design
conditions to supply fluid from the cooling source to the conditioned
space(s) and return it back to the source.
Variable flow
control valves ,variable speed, multiple stage pumps
6.6.1 General
Exception:
Areas requiring comfort cooling only that are served by a system primarily
used for process temperature and humidity control, need not be served by
a separate system if the total supply air to these areas is no more than 25%
of the total system supply air or the total conditioned area is less than 100
sq .m.
Section 5 – Air Conditioning and Ventilating Systems
6.7 Controls
6.7.5 Location
Thermostats in controlled zones should be located where
they measure a condition representative of the whole
space and where they are not affected by direct
radiation, drafts, or abnormal thermal conduction or
stratification.
Section 5 – Air Conditioning and Ventilating Systems
The system with the lowest overall energy usage (considering the
heat losses in the calorifier and the circulating loop of a
centralized system and the total heat losses from a system of
individual storage heaters) should be chosen.
Where steam is available, it is definitely more economical to use
steam to generate hot water as compared to the use of electricity.
7.5 Controls
Section 7 – Steam and Hot water Systems
The insulation of steam, condensate and hot water lines shall conform to the requirements:
Subscript 1 refers to values quoted in Table 7.2; subscript 2 refers to values corresponding to
alternate insulating, material.
Section 7 – Steam and Hot water Systems