REVISION 0
GENERATOR PARAMETERS
RATING : 45 MVA
IMPEDANCE, ZHV-LV (AT 25 MVA BASE) : 10% + 10% TOL. AT PRINCIPAL TAP
VOLTAGE RATIO : 21/11.5 kV
TAP CHANGER RANGE : + 7.5% TO –12.5% OLTC
RATED HV SIDE CURRENT : 1237.21 A
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-270-510-E018
FOR GRP REV NO. : 0 DATE : 02.12.2009
(UNIT # 1 & 2) SHEET : Page 2 of 14
RELAY DETAILS:-
This protection is provided to protect the Generator against operation at very low voltage
This relay is provided to change regulation of AVR from Auto to manual in case Auto Channel of
AVR fails at stage-1 and protection against overvoltages at stage-2
SETTING RANGE
V>1, V>2 VOLTAGE SET : 60 – 185 V
V>1, V>2 TIME DELAY : 0 – 100 SECOND
V>1(Stage-1) VOLTAGE SET : 115.5 V
V>1 TIME DELAY : 1.0 SECOND
V>2 (Stage-2) VOLTAGE SET : 132 V
V>2 TIME DELAY : 0 SECOND
SETTING RANGE
I>1 CURRENT SET : 0.08 In – 4 In A
I>1 TIME DELAY : 0 – 100 SECOND
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
GENERATOR OUTPUT : 500 MW
GENERATOR FULL LOAD CURRENT AT 95% OF = 500 × 1000
RATED VOLTAGE A
3 × 21 × 0.95 x 0.85
= 17023.94 A
CT SECONDARY CURRENT CORRESPONDING TO = 17023.94 x5
17023.94 A A
20000
= 4.25 A
GENERATOR OVERLOAD CAPABILITY : 10% FOR 3 MINUTES
RECOMMENDED SETTING
I>1 CURRENT SET = 0.85 In A
I>1 TIME DELAY = 5.0 SECOND
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-270-510-E018
FOR GRP REV NO. : 0 DATE : 02.12.2009
(UNIT # 1 & 2) SHEET : Page 4 of 14
From the capability and safety of TG set, trip setting is recommended at 47.5 Hz. Alarm setting
are to be made at 1 Hz interval to alert the operator for corrective action and load management.
Hence, follwing settings are recommended.
SETTING RANGE
F<1, F<2 SETTING : 45 – 65 Hz
F<1, F<2 TIME DELAY : 0.1 – 100 SECOND
FIRST STAGE – ALARM
F<1 SETTING : 48.5 Hz
F<1 TIME DELAY : 2.5 SECOND
SECOND STAGE – TRIPPING
F<2 SETTING : 47.5 Hz
F<2 TIME DELAY : 2 SECOND
This protection is provided to protect Generator against unbalanced loads and as a backup for
uncleared unsymmetrical faults.
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
GENERATOR RATED CURRENT, Ig : 16172.750 A
MAXIMUM CONTINUOUS NEGATIVE PHASE : 8%
SEQUENCE CURRENT (I2)
MAXIMUM VALUE OF I22t : 9
RELAY SETTING RANGE, ALARM STAGE
I2>1 CURRENT SET : 0.03 In – 0.5 In A
I2>1 TIME DELAY : 2 – 60 SECOND
TRIP STAGE, I2>2 CURRENT SET : 0.05 In – 0.5 In A
I2>2 K SETTING : 2 – 40
I2>2 KRESET : 2 – 40
ALARM SETTING
8 16172.75
I2>1 CURRENT SET = 65% x × x In A
100 20000
= 0.042 In A
I2>1 TIME DELAY = 20 SECOND
TRIP SETTING
8 16172.75
I2>2 CURRENT SET = × x In A
100 20000
= 0.064 In A
2
⎛ 16172.75 ⎞
I2>2 Thermal capability Constant (Heating)K = 9x ⎜ ⎟
⎝ 20000 ⎠
= 5.88
I2> KRESET = 5.88
This protection is provided to protect the Generator during the condition when ratio of voltage to
frequency exceeds certain limits.
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
RATED RELAY CURRENT, In : 5A
SETTING RANGE, FFAIL1 –Xa1 : 0/In – 40/In Ω
FFAIL1 Xb1 : 25/In – 325/In Ω
FFAIL1 TIMEDELAY : 0 – 100 SECOND
SETTING RANGE, FFAIL2 –Xa2 : 0/In – 40/In Ω
FFAIL2 Xb2 : 25/In – 325/In Ω
FFAIL2 TIMEDELAY : 0 – 100 SECOND
BASE IMPEDANCE OF THE GENERATOR = kV2/MVA Ω
= 212/588.23 Ω
= 0.749 Ω
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-270-510-E018
FOR GRP REV NO. : 0 DATE : 02.12.2009
(UNIT # 1 & 2) SHEET : Page 7 of 14
This protection is provided to prevent accidental energisation of Generator when the machine is
not running and the breaker is closed when the Generator is at standstill.
SETTING RANGE
DEAD MACH I> : 0.08 In – 4 In A
DEAD MACH V< : 10 – 120 V
DEAD MACH tPU : 0 – 10 SECOND
DEAD MACH tDO : 0 – 10 SECOND
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
BASE MVA = 588.23 MVA
GENERATOR TRANSIENT REACTANCE = 24.1%
(SATURATED) (Xd’)
MAXIMUM VALUE OF Xd’ CONSIDERING TOL. = 1.15×24.1
= 27.7%
GENERATOR TRANSFORMER MAXIMUM = 13.4%
IMPEDANCE
400kV SYSTEM FAULT LEVEL = 40kA
= √3x40x420 MVA
= 29097 MVA
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-270-510-E018
FOR GRP REV NO. : 0 DATE : 02.12.2009
(UNIT # 1 & 2) SHEET : Page 8 of 14
SETTING RANGE:
VN>1 VOLTAGE SET : 1 – 80V
VN>1 TIME DELAY : 0 – 100 SECOND
= 11V
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
RATED RELAY CURRENT, In : 5A
SETTING RANGE, SEN -P>1 : 0.3 x In – 100 x In W
POWER1 TIME DELAY : 0 – 100 SECOND
0.5% OF RATED POWER = (0.5/100) x 500000000 W
= 2500000 W
0.5% POWER REFFERED TO RELAY = 2500000 x (5/20000) x (110/√3)/(21000/√3) W
= 3.27 W
= 0.654 x In W
SETTINGS SELECTED :
RECOMMENDED POWER SETTING : 0.6 x In W
TIME SETTING : 0 SECONDS
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-270-510-E018
FOR GRP REV NO. : 0 DATE : 02.12.2009
(UNIT # 1 & 2) SHEET : Page 9 of 14
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
RATED RELAY CURRENT, In : 5A
SETTING RANGE, SEN -P>1 : 0.3 x In – 100 x In W
POWER1 TIME DELAY : 0 – 100 SECOND
0.5% OF RATED POWER = (0.5/100) x 500000000 W
= 2500000 W
0.5% POWER REFFERED TO RELAY = 2500000 x (5/20000) x (110/√3)/(21000/√3) W
= 3.27 W
= 0.654 x In W
SETTINGS SELECTED :
RECOMMENDED POWER SETTING : 0.7 x In W
TIME SETTING : 3 SECONDS
SETTING RANGES
WARNING STAGE R< : 10 – 700 OHM
TRIPPING STAGE R<< : 10 – 700 OHM
CURRENT STAGE I>> : 0.02 – 1.50 A
20 Hz VOLTAGE FAILURE SUPERVISION
BLOCK U20< : 0.3 – 25.0 V
BLOCK I20< : 5 – 40 mA
TRANSFORMER ANGLE ERROR CORRECTION : -60 TO +60
CT ANGLE W1
TRIP DELAY : 0 – 100 SECOND
ALARM DELAY : 0 – 100 SECOND
SETTINGS
TRANSFORMATION FACTOR, S/E/F -FACTOR = TRETr2 x (TRVD / TRICT)
TRETr TRANSFORMATION RATIO OF
THE NGT = (21000 / SQRT3 ) / 220 V
TRVD TRANSFORMATION RATIO OF
THE VOLTAGE DIVIDER = 500/200 V
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-270-510-E018
FOR GRP REV NO. : 0 DATE : 02.12.2009
(UNIT # 1 & 2) SHEET : Page 10 of 14
SETTING RANGES
WARNING STAGE RE< WARN AND RE<TEST : 1 – 80 KOHM
TRIPPING STAGE RE<< TRIP AND RE<< TEST : 1 – 80 KOHM
PICK-UP VALUE OF MEAS. CIRCUIT : 0.00 – 20.00mA
SUPERVISION Qc<
TRIP DELAY : 0 – 600 SECOND
ALARM DELAY : 0 – 600 SECOND
ALARM SETTING : 40 KOHM
TRIP SETTING : 5 KOHM
TIME DELAY SETTING FOR WARNING STAGE : 10 SECOND
TIME DELAY SETTING FOR TRIPPING STAGE : 1 SECOND
A. DIFFERENTIAL PROTECTION:
MVA × 1000
UAT HV SIDE CURRENT :
3 × HV VOLTAGE
: 1237.21 A
CT SECONDARY CURRENT : 1237.21/1600 A
CORRESPONDING TO 1237.21 A
: 0.77 In A
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-270-510-E018
FOR GRP REV NO. : 0 DATE : 02.12.2009
(UNIT # 1 & 2) SHEET : Page 13 of 14
A. DIFFERENTIAL PROTECTION:
RECOMMENDED SETTINGS:
DIFFRENTIAL CURRENT (Id) : 0.2In
INITIAL SLOPE (m1) : 30%
FINAL SLOPE (m2) : 70%
CT RATIO : 1000/1 A
L = 550 M
RL (10 MM SQUARE) = (2.2 X 0.550)
≅ 1.21 OHM
VK ≥ 6.51(5 + 2X1.21)
≅ 48.3 V
SET THE RELAY AT 20% 0F 1A
PLUG SETTING CURRENT : 0.20In A
RELAY VA BURDEN = 1.4 VA
RELAY RESISTANCE AT 20% SETTING = 1.4/(0.2)2 OHM
RELAY RESISTANCE AT 20% SETTING = 35 OHM
CURRENT REQUIRED FOR RELAY OPERATION = 0.20 A
VALUE OF STABILISING RESISTOR = 48.3
− 35
0.2
= 206.5 OHM
RANGE OF STABILISING RESISTOR : 0-1000 OHM