SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED : ROOM:CBAA EXTENSION BUILDING ROOM: CBAA EXT ROOM 4
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 30A
IT: (TOTAL x DF) CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
I = 30 AMPS x 0.80 DESCRIPTION QTY CONDUCTORS CONDUIT
IT: (8.78 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire NO. (VA) (V) (A) AT AF P
I = 24 AMPS
IT: 7.02 AMPERES 1 LIGHTING OUTLET 6 600 230 2.61 15 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC
2 CONVENIENCE OUTLET 22 3960 230 17.22 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC
SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR MINIMUM AMPACITY OF MAIN PANEL:
IT: (TOTAL x DF) FOR MAIN PANEL PROTECTION USED :
I = 30 AMPS x 0.80 230V, 60Hz, 2P CB - 30A
IT: (19.83 x 0.80)
I = 24 AMPS 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
IT: 15.86 AMPERES
SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED :
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 3P CB - 125 A
IT: (TOTAL x DF) I = 125 AMPS x 0.80
IT: (124.08 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
I = 100 AMPS
IT: 99.26 AMPS
Group Assigned: PROJECT TITLE COURSE AND SECTION SHEET CONTENT SEM. AY SHEET NO
POWER DISTRIBUTION SCHEDULE OF
Group 2 & LOAD DIAGRAM BSEE 4B LOAD
1ST 2023