SCHEDULE OF LOADS & COMPUTATION

ROOM:CBAA EXTENSION BUILDING ROOM: CBAA EXT ROOM 2


CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
DESCRIPTION QTY CONDUCTORS CONDUIT
NO. (VA) (V) (A) AT AF P
ROOM:CBAA EXTENSION BUILDING ROOM: CBAA DEAN OFFICE AND FACULTY ROOM 1 LIGHTING OUTLET 4 400 230 1.74 15 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC
CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING 2 CONVENIENCE OUTLET 6 1080 230 4.70 15 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC
DESCRIPTION QTY CONDUCTORS CONDUIT
NO. (VA) (V) (A) AT AF P 1480 6.44
TOTAL CONNECTION LOAD
1 100W L.O. and 75W CEILING FAN 11 + 5 1475 230 6.41 15 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC
2 CONVENIENCE OUTLET 12 2160 230 9.39 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR MINIMUM AMPACITY OF MAIN PANEL: FOR MAIN PANEL PROTECTION USED :
IT: (TOTAL x DF) I = 60 AMPS x 0.80 230V, 60Hz, 2P CB - 60A
3 CONVENIENCE OUTLET 16 2880 230 12.52 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC
IT: (6.44 x 0.80) I = 48 AMPS
4 ACU 2HP 1 2760 230 12 30 50 2 2-3.5mm² THHN, Cu wire 20mmØ PVC 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
IT: 5.15 AMPERES
5 ACU 2HP 1 2760 230 12 30 50 2 2-3.5mm² THHN, Cu wire 20mmØ PVC

TOTAL CONNECTION LOAD


12035 52.32 ROOM:CBAA EXTENSION BUILDING ROOM: CBAA EXT ROOM 3
CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
DESCRIPTION QTY CONDUCTORS CONDUIT
SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED : NO. (VA) (V) (A) AT AF P
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 60A 4 400 230 1.74 15 50 2
IT: (TOTAL x DF) + (25% OF HIGHEST RATED MOTOR) 1 LIGHTING OUTLET 2-2.0mm² THWN, Cu wire 20mmØ PVC
I = 60 AMPS x 0.80
IT: (52.32 x 0.80) + (0.25 x 12) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire 2 CONVENIENCE OUTLET 14 2520 230 10.96 15 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC
I = 48 AMPS
IT: 44.86 AMPERES 3 ACU 2HP 1 2760 230 12 30 50 2 2-3.5mm² THHN, Cu wire 20mmØ PVC
4 ACU 2HP 1 2760 230 12 30 50 2 2-3.5mm² THHN, Cu wire 20mmØ PVC
ROOM:CBAA EXTENSION BUILDING ROOM: CBAA EXT ROOM 1 TOTAL CONNECTION LOAD
8440 36.7
CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
DESCRIPTION QTY CONDUCTORS CONDUIT
NO. (VA) (V) (A) AT AF P SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED :
1 LIGHTING OUTLET 4 400 230 1.74 15 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 30A
IT: (TOTAL x DF) + (25% OF HIGHEST RATED MOTOR) I = 30 AMPS x 0.80
2 CONVENIENCE OUTLET 9 1620 230 7.04 15 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC IT: (36.7 x 0.80) + (0.25 x 12) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
I = 24 AMPS
IT: 32.36 AMPERES
TOTAL CONNECTION LOAD 2020 8.78

SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED : ROOM:CBAA EXTENSION BUILDING ROOM: CBAA EXT ROOM 4
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 30A
IT: (TOTAL x DF) CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
I = 30 AMPS x 0.80 DESCRIPTION QTY CONDUCTORS CONDUIT
IT: (8.78 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire NO. (VA) (V) (A) AT AF P
I = 24 AMPS
IT: 7.02 AMPERES 1 LIGHTING OUTLET 6 600 230 2.61 15 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC
2 CONVENIENCE OUTLET 22 3960 230 17.22 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC

TOTAL CONNECTION LOAD 4560 19.83

SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR MINIMUM AMPACITY OF MAIN PANEL:
IT: (TOTAL x DF) FOR MAIN PANEL PROTECTION USED :
I = 30 AMPS x 0.80 230V, 60Hz, 2P CB - 30A
IT: (19.83 x 0.80)
I = 24 AMPS 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
IT: 15.86 AMPERES

SCHEDULE OF LOADS & COMPUTATION


CBAA EXTENSION BUILDING
MAIN DISTRIBUTION PANEL
CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
DESCRIPTION QTY CONDUCTORS CONDUIT
NO. (VA) (V) (A) AT AF P
1 CBAA DEAN OFFICE AND FACULTY ROOM 1 12035 230 52.33 60 50 3 2-14mm² THWN, Cu wire 20mmØ PVC
2 CBAA EXT ROOM 1 1 2020 230 8.78 30 50 3 2-14mm² THWN, Cu wire 20mmØ PVC
3 CBAA EXT ROOM 2 1 1480 230 6.44 60 50 3 2-14mm² THWN, Cu wire 20mmØ PVC
4 CBAA EXT ROOM 3 1 8440 230 36.70 30 50 3 2-14mm² THWN, Cu wire 20mmØ PVC
5 CBAA EXT ROOM 4 1 4560 230 19.83 30 50 3 2-14mm² THWN, Cu wire 20mmØ PVC
28535 124.08
TOTAL CONNECTION LOAD

SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED :
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 3P CB - 125 A
IT: (TOTAL x DF) I = 125 AMPS x 0.80
IT: (124.08 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
I = 100 AMPS
IT: 99.26 AMPS

Group Assigned: PROJECT TITLE COURSE AND SECTION SHEET CONTENT SEM. AY SHEET NO
POWER DISTRIBUTION SCHEDULE OF
Group 2 & LOAD DIAGRAM BSEE 4B LOAD
1ST 2023
- 2024 ?