SCHEDULE OF LOADS: PANEL BOARD - 1

2-14 mm ² THHN/2.0mm²
CKT NO. OF LOAD DESCRIPTION VA VOLTS AMPS CB RATING TAPED TO 20mm Ø PVC CONDUIT
SIZE AND DIAMETER OF CONDUIT
NO. OUTLET AT EXISTING BLDG.
M KILOWATT-HOUR
METER
01 MAIN 3520 230 15.30 70 32mm Ø PVC
02 11 LIGHTING OUTLET 1100 230 4.78 15 20mm Ø PVC 40AT/50AF
03 8 LIGHTING OUTLET 800 230 3.48 15 20mm Ø PVC 2P,21 Ø
04 9 CONVENIENCE OUTLET 1620 230 7.04 20 20mm Ø PVC 15 AT .2P 15 AT .2P
05 L.O. 1 2 L.O.
06 20 AT .2P 20 AT .2P
TOTAL : 3520 CB RATING C.O. 3 4 C.O.
AMPACITY= =2.5[7.04] + [15.30-7.04][100%DF] 20 AT .2P 20 AT .2P
=0.25[7.04] + 15.3[100%DF]
=1.76 + 15.30
=17.6 + 8.26
= 25.86 AMP
SPARE 5 6 SPARE
=17.06 AMP USE 70AT, 230V 1Ø MOLDED CABLE CASE
GROUND BUS
USE: 2-14.00 SQ.MM THHN CUT 1-8.00SQ.MM THHN
CU STRANDED IN 32MM Ø PVC PIPE PB GROUND
PANEL BOARD DETAIL
SCALE NTS
2-14.0 mm² THHN Cu. WIRE @
20mmØ PVC PIPE MAIN FEEDER
70A 2P,1/2 Ø
MAIN
LIGHTING OUTLET 1 15A 15A
2 LIGHTING OUTLET
UTILITY SERVICE ENTRANCE
230VAC, 1Ø, 2W+G, 60Hz CONVENIENCE OUTLET 3 20A 4 SPARE
54.7A
UTILITY M
KWHr METER GROUND BUS
GROUND 1-8.0 mm² THHN Cu. WIRE
PANEL BOARD DETAIL
SCALE NTS
RISER DIAGRAM
SCALE NTS
Republic of the Philippines PREPARED BY: RECOMMENDING APPROVAL: NOTED BY: APPROVED BY: SHEET CONTENT: SHEET NO.
DEPARTMENT OF SOCIAL WELFARE & DEVELOPMENT
KALAHI- CIDSS: NCDDP Additional Financing
Construction of Quarantine Facility cum Evacuation REXTER S. PANGANIBAN ENGR. ROSENDO E. VELASCO ENGR. RAYMOND B. LIBARRA AS SHOWN E- 2
Center and Purchase of Medical Supply and Equipment Technical Facilitator Municipal Engineer PDO IV for Infrastructure BDC TWG- Chairperson
Location: Brgy. Rumbang, Rizal, Occidental, Mindoro NOTE: All units are in meters unless otherwise stated