You are on page 1of 1

ESAMELCO

M
60AT
15 AT 15 AT
1. Total load current of all circuits. C1 C2
I = 3.04 + 2.17 + 2.61 + 3.04 + 9.39 + 9.39 + 1.52 15 AT 15 AT
9.39 + 6.26 + 6.49 C3 C4
I = 53.30 A 20AT 20 AT
C5 C6
2. Apply 80% demand factor. 20 AT 20 AT
C7 C8
20AT 30 AT
3. Size of 2conductor C9 C10
8.0mm
4.Size of2conduit SPARE
20mm Ø
5. Size of circuit breaker
60 Amp.

RISER DIAGRAM
SCALE: NTS
EYEBOLT OVAL GALVANIZED
25mm

POWER SERVICE ENTRANCE


230 BOLTS, 2" 0.60
2-8.0mm
0.60

2X80.0mm

5.40
KW/HR METER
M
SERVICE ENTRANCE
POST
2.13

GROUND FLOOR LEVEL

GROUNDING

SINGLE LINE DIAGRAM


SCALE: NTS

DRAWN BY: PROJECT TITLE: INSTRUCTOR: SHEET N0.

DILAO, ROJIM A. PROPOSED TWO STOREY THREE BEDROOM


ENGR.ROMEL JUSTIN MADRIAGA E
RESIDENTIAL BUILDING
5
BSCE-3B