GENERAL NOTES AND SPECIFICATION NEMA 3R - ECB 6 TO ECB 7 POWER PANEL AC (PPAC)

CKT. VOLT AMPERES CIRCUIT BREAKER CONDUIT CKT. VOLT AMPERES CIRCUIT BREAKER CONDUIT
C.O. DESCRIPTION VOLTS PHASE C.O. DESCRIPTION VOLTS PHASE
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE NO. LIGHTS AMPERE AB CA BC ABC AT AF P KAIC SIZE AND TYPE OF WIRE SIZE NO. LIGHTS AMPERE AB CA BC ABC AT AF P KAIC SIZE AND TYPE OF WIRE SIZE
PHILIPPINE ELECTRICAL CODE, THE LAWS AND ORDINANCES OF THE LOCAL CODE ENFORCING AUTHORITIES AND 1 1/2 HP - SPLIT TYPE ACCU 466 2.02 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC 1 NEMA 3R - ECB 6 466 2.02 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
THE REQUIREMENTS OF THE LOCAL POWER AND TELEPHONE COMPANIES. TOTAL 466 2.02 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC 2 NEMA 3R - ECB 7 466 2.02 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
3 NEMA 3R - ECB 5 700 3.04 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
2. THE CONTRACTOR SHALL SECURE ALL PERMITS AND PAY ALL FEES REQUIRED FOR THE WORK AND SHALL FURNISH LOCATION: ROOF DECK LOAD ANALYSIS COMPUTATION: USE FEEDER SIZE:
4 NEMA 3R - ECB 1 932 5.40 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
THE OWNER THROUGH THE ENGINEERS. FINAL CERTIFICATES OF ELECTRICAL INSPECTION AND APPROVAL FROM ENCLOSURE: NEMA 3R IT = (2.02 x 100% DF) 2 - 3.5 mm² THHN WIRE (P) + 1 - 2.0 mm² THHN WIRE (G) IN
5 NEMA 3R - ECB 2 932 5.40 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
PROPER GOVERNMENT AUTHORITIES FOR COMPLETE WORK. MOUNTING: WALL MOUNTING IT = 2.02 AMPERES 20mmØ PVC PIPE
6 NEMA 3R - ECB 3 932 5.40 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
AMPERES: CIRCUIT PROTECTION:
7 NEMA 3R - ECB 4 932 5.40 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
VOLTS: 230 V ICB = (2.02 x 175%) ALSO USE 20AT, 10 KAIC, 2 POLE BOLT-ON CIRCUIT BREAKER
3. POWER SUPPLY TO THE PANEL BOARD MUST BE 1Ø, 2 WIRE + GROUNDING. 230V LINE TO LINE. 8 NEMA 3R - ECB 8 1540 7.10 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
FED FROM: PPAC ICB = 3.53 AMPERES WITH GROUNDING TERMINAL LUGS
9 NEMA 3R - ECB 9 1540 7.10 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
4. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION 10 NEMA 3R - ECB 10 2150 10.00 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
TO THE POWER SUPPLY. 11 NEMA 3R - ECB 11 2150 10.00 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
NEMA 3R - ECB 12 2150 10.00 2 20mm PVC
NEMA 3R - ECB 5 12
13 NEMA 3R - ECB 13 2150 10.00
230
230


20
20
60
60 2
10
10
2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G)
2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
5. ALL MATERIALS TO BE USED SHALL BE NEW AND INSTALLED IN APPLICATION FOR WHICH THEY ARE INTENDE. CKT. VOLT AMPERES CIRCUIT BREAKER CONDUIT 2150 20 60 2 10 20mm PVC
DESCRIPTION VOLTS PHASE 14 NEMA 3R - ECB 14 10.00 230 1Ø 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G)
C.O.
NO. LIGHTS AMPERE AB CA BC ABC AT AF P KAIC SIZE AND TYPE OF WIRE SIZE
TOTAL 19190 92.88 230 1Ø 150 200 2 18 2-50.0 mm² THHN (P) + 1-22.0 mm² THHN (G) 40mm RSC
6. ALL METALLIC CONDUITS, CABINETS AND EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED, BY MEANS OF 1 3/4 HP - SPLIT TYPE ACCU 700 3.04 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
COPPER STRAPS. LOCATION: LOCKER ROOM LOAD ANALYSIS COMPUTATION: USE FEEDER SIZE:
TOTAL 700 3.04 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC ENCLOSURE: NEMA 1 IT = (92.88 x 100% DF) + (10.00 x 25%) 2 - 50.0 mm² THHN WIRE (P) + 1 - 22.0 mm² THHN WIRE (G) IN
LOCATION: ROOF DECK LOAD ANALYSIS COMPUTATION: USE FEEDER SIZE: MOUNTING: WALL MOUNTING IT = 95.38 AMPERES 40mmØ RSC PIPE
7. ADEQUATE AND EFFECTIVE GROUNDING SHALL BE PROVIDED. ENCLOSURE: NEMA 3R IT = (3.04 x 100% DF) 2 - 3.5 mm² THHN WIRE (P) + 1 - 2.0 mm² THHN WIRE (G) IN AMPERES: CIRCUIT PROTECTION:
MOUNTING: WALL MOUNTING IT = 3.04 AMPERES 20mmØ PVC PIPE VOLTS: 230 V ICB = (92.88 x 175%) ALSO USE 150AT, 18 KAIC, 2 POLE BOLT-ON CIRCUIT BREAKER
8. LIGHTING BRANCH CIRCUITS WITHOUT DESIGNATION SHALL BE 2-WIRE, AND 1-GROUND WIRE IN 15mm Ø EMT AMPERES: CIRCUIT PROTECTION: FED FROM: DP1 ICB = 143.07 AMPERES WITH NEUTRAL TERMINAL & GROUNDING TERMINAL BUS
CONDUIT UNLESS NOTED OTHERWISE. VOLTS: 230 V ICB = (3.04 x 175%) ALSO USE 20AT, 10 KAIC, 2 POLE BOLT-ON CIRCUIT BREAKER
FED FROM: PPAC ICB = 5.32 AMPERES WITH GROUNDING TERMINAL LUGS
9. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN" OR "THWN" UNLESS OTHERWIES
INDICATED. MINIMUM SIZE OF WIRE SHALL BE 3.5 mm² STRANDED WIRE IN 15mm Ø CONDUIT UNLESS NOTED ON
PLANS. USE PHILPLEX / DURAPLEX OR PHELPS DODGE THHN WIRES ONLY.
DISTRIBUTION PANEL 1 (DP1)
NEMA 3R - ECB 1 TO ECB 4 CKT.
C.O. DESCRIPTION
VOLT AMPERES
VOLTS PHASE
CIRCUIT BREAKER CONDUIT
CKT. VOLT AMPERES CIRCUIT BREAKER CONDUIT NO. LIGHTS AMPERE AB CA BC ABC AT AF P KAIC SIZE AND TYPE OF WIRE SIZE
10. CONVENIENCE OUTLET CIRCUITS IN GENERAL SHALL BE 2-WIRE, 3.5mm² STRANDED THHN IN EMT CONDUIT UNLESS C.O. DESCRIPTION VOLTS PHASE
OTHERWISE NOTED. NO. LIGHTS AMPERE AB CA BC ABC AT AF P KAIC SIZE AND TYPE OF WIRE SIZE 1 POWER PANEL AC 19190 92.88 230 1Ø 150 150 2 18 2-50.0 mm² THHN (P) + 1-22.0 mm² THHN (G) 40mm PVC
1 1 HP - SPLIT TYPE ACCU 932 5.40 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC 2 ELECTRIC RANGE 4000 17.39 230 1Ø 30 60 2 10 2-5.5 mm² THHN (P) + 1-3.5 mm² THHN (G) 20mm PVC
3 1 INDUCTION COOKER @ KITCHEN 3500 15.22 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
TOTAL 932 5.40 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
11. MOUNTING HEIGHT NOT SHOWN ON SCHEDULE ARE AS FOLLOWS: 4 1 COFFEE MACHINE @ BAR AREA 3200 13.91 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
A. LIGHT CONTROLLED SWITCHES 1.37M ABOVE FINISHED FLOOR TO THE CENTER OF DEVICE LOCATION: ROOF DECK LOAD ANALYSIS COMPUTATION: USE FEEDER SIZE: 5 WATER HEATER @ GROOMING AREA 2500 10.87 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
B. DUPLEX CONVENIENCE OUTLETS 0.30M ABOVE FINISHED FLOOR TO THE CENTER OF DEVICE ENCLOSURE: NEMA 3R IT = (5.40 x 100% DF) 2 - 3.5 mm² THHN WIRE (P) + 1 - 2.0 mm² THHN WIRE (G) IN 6 WATER HEATER @ GROOMING AREA 2500 10.87 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
0.15M ABOVE WORKING COUNTER TO THE CENTER OF DEVICE MOUNTING: WALL MOUNTING IT = 5.40 AMPERES 20mmØ PVC PIPE 7 1 HOT WATER DISPENSER @ BAR AREA 2000 8.70 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
AMPERES: CIRCUIT PROTECTION: 8 9 C.O. @ MOVIE AREA 2F 1620 7.04 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
C. TELEPHONE / CATV OUTLET 0.30M ABOVE FINISHED FLOOR TO THE CENTER OF DEVICE
VOLTS: 230 V ICB = (5.40 x 175%) ALSO USE 20AT, 10 KAIC, 2 POLE BOLT-ON CIRCUIT BREAKER 9 9 C.O. @DINING AREA 2F 1620 7.04 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
D. PASTEBOARD / DISCONNECT 1.80M ABOVE FINISHED FLOOR TO TOP OF THE PANEL
FED FROM: PPAC ICB = 9.45 AMPERES WITH GROUNDING TERMINAL LUGS 10 8 C.O. @ GROOMING AREA 1440 6.26 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
E. MANUAL PULL STATIONS 1.37M ABOVE FINISHED FLOOR TO THE CENTER OF DEVICE
F. ALARM BELL / HORNS 1.80M ABOVE FINISHED FLOOR TO TOP OF THE PANEL 11 8 C.O. @ DISPLAY AREA 1440 6.26 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
12 8 C.O. @ RECEPTION & STORAGE AREA 1440 6.26 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
13 8 C.O. @ BAR AREA 1440 6.26 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
12. ALL CONDUIT PIPES SHALL BE POLYVINYL CHLORIDE (PVC) UNLESS OTHERWISE NOTED. NEMA 3R - ECB 8 TO ECB 9 14 8 EMERGENCY LIGHTING OUTLETS 1440 6.26 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
CKT. VOLT AMPERES CIRCUIT BREAKER CONDUIT 15 6 C.O. @ PET DORM 1080 4.70 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
13. BOLT ON TYPE CIRCUIT BREAKER SHALL BE USE. C.O. DESCRIPTION VOLTS PHASE
NO. LIGHTS AMPERE AB CA BC ABC AT AF P KAIC SIZE AND TYPE OF WIRE SIZE 16 5 C.O. @ KITCHEN 900 3.91 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
1 2 HP - SPLIT TYPE ACCU 1540 7.10 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC 17 5 C.O @ BATHROOM & BAR AREA 900 3.91 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
14. EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL TO OR PERPENDICULAR WITH THE BUILDING LINE AND 720 3.13
TOTAL 1540 7.10 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC 18 4 C.O. @ CAT AREA & LOUNGE AREA 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
SUPPORTED BY CONDUIT CLAMPS EVERY 1.5M. DIAGONAL CONDUIT RUNS SHALL NOT BE ACCEPTED. EXHAUST AIR BLOWER 3.13 2 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
LOCATION: ROOF DECK LOAD ANALYSIS COMPUTATION: 19 720 230 1Ø 20 60 10
USE FEEDER SIZE:
20 2 WATER PROOF C.O. @ GARDEN 360 1.57 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
15. ALL RECEPTACLE OUTLETS SHALL BE PROPERLY GROUNDED TO THE BOX BY MEANS OF GROUNDING LUGS. ENCLOSURE: NEMA 3R IT = (7.10 x 100% DF) 2 - 3.5 mm² THHN WIRE (P) + 1 - 2.0 mm² THHN WIRE (G) IN
21 1 ICE MAKER 360 1.57 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
MOUNTING: WALL MOUNTING IT = 7.10 AMPERES 20mmØ PVC PIPE
22 1 WORK TOP CHILLER 250 1.09 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
AMPERES: CIRCUIT PROTECTION:
16. FOR SWITCH BOXES WITH MORE THAN FOUR (4) WIRES ENTERING THEM USE 0.10M. x 0.10M. SQUARE BOX WITH ONE VOLTS: 230 V ICB = (7.10 x 175%) 23 1 REFRIGERATOR 360 1.57 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
ALSO USE 20AT, 10 KAIC, 2 POLE BOLT-ON CIRCUIT BREAKER
(1) ADAPTER RING. (TYPICAL FOR RECEPTACLE BOXES). FED FROM: PPAC ICB = 12.43 AMPERES WITH GROUNDING TERMINAL LUGS 24 1 REFRIGERATOR 430 1.87 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
25 2 C.O FOR CCTV & SPEAKER SYSTEM 360 1.57 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
17. MINIMUM SIZE OF CONDUIT SHALL BE 20mm Ø FOR PVC. 26 1 FACP @ LOCKER ROOM 500 2.17 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
27 1 CAKE CHILLER @ BAR AREA 360 1.57 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
28 12 12 - 200w SIGNAGES/LOGO 2400 10.43 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
18. PULLBOXES SHALL BE PROVIDED BY THE CONTRACTOR WHENEVER NECESSARY TO FACILITATE WIRE PULLING EVEN IF
THESE ARE NOT INDICATED ON THE PLANS.
NEMA 3R - ECB 10 TO ECB 14 29 LIGHTINGS @ GROUND FLOOR 1200 5.22 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
CKT. VOLT AMPERES CIRCUIT BREAKER CONDUIT 30 LIGHTINGS @ 2F 600 2.61 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC
C.O. DESCRIPTION VOLTS PHASE
NO. LIGHTS AMPERE AB CA BC ABC AT AF P KAIC SIZE AND TYPE OF WIRE SIZE 31 8 C.O. @ LOCKER ROOM & OFFICE 1440 6.26 230 1Ø 20 60 2 10 20mm PVC
19. ALL REVISION OR ADDITIONAL WORKS ON ELECTRICAL PLANS SHOULD BE CONSULTED TO THE DESIGNER (P.E.E) 1 3 HP - SPLIT TYPE ACCU 2150 10.00 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC 32 SPARE 1800 7.83 230 1Ø 20 60 2 10 20mm PVC
PROFESSIONAL ELECTRICAL ENGINEER. 63mm RSC
TOTAL 2150 10.00 230 1Ø 20 60 2 10 2-3.5 mm² THHN (P) + 1-2.0 mm² THHN (G) 20mm PVC TOTAL 280.90 230 1Ø 250 300 2 18 2-125.0 mm² THHN (P) + 1-30.0 mm² THHN (G)
LOCATION: ROOF DECK LOAD ANALYSIS COMPUTATION: USE FEEDER SIZE: LOCATION: LOCKER ROOM LOAD ANALYSIS COMPUTATION: USE FEEDER SIZE:
20. THE ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.
ENCLOSURE: NEMA 3R IT = (10.00 x 100% DF) 2 - 3.5 mm² THHN WIRE (P) + 1 - 2.0 mm² THHN WIRE (G) IN ENCLOSURE: NEMA 1 IT = (280.90 x 65% DF) + (17.39 x 25%) 2 - 125.0 mm² THHN WIRE (P) AND 1 - 50.0 mm² THHN WIRE
MOUNTING: WALL MOUNTING IT =10.00 AMPERES 20mmØ PVC PIPE MOUNTING: WALL MOUNTING IT = 186.93 AMPERES (G) IN 63mmØ RSC PIPE
AMPERES: CIRCUIT PROTECTION: AMPERES: CIRCUIT PROTECTION:
VOLTS: 230 V ICB = (10.00 x 175%) ALSO USE 20AT, 10 KAIC, 2 POLE BOLT-ON CIRCUIT BREAKER VOLTS: 230V IFL = 186.93 x 125% ALSO USE 250AT, 22 KAIC, 2 POLE BOLT-ON CIRCUIT BREAKER
FED FROM: PPAC ICB = 17.50 AMPERES FED FROM: MERALCO IFL = 233.67 AMPERES WITH GROUNDING TERMINAL BUS
WITH GROUNDING TERMINAL LUGS

TO MERALCO
230V,1Ø
2-250.0 mm² THHN (P) + 2W + G, 60 HZ
1-50.0 mm² THHN (G) in
63mm Ø RSC PIPE
LEGENDS AND SYMBOLS 2-50.0 mm² THHN (P) +
1-22.0 mm² THHN (G) in
40mm Ø RSC PIPE MERALCO
METER
(DIGITAL)
M 2-125.0 mm² THHN (P) +
1-50.0 mm² THHN (G) in
63mm Ø RSC PIPE
ECB NEMA 3R
250AT/2P
22kAIC, 60 HZ

SPO
150AT/2P 250AT/2P

REF PP1
20AT/2P 20AT/2P 150AT/2P 30AT/2P
2A
1 2 2
20AT/2P 20AT/2P 20AT/2P 20AT/2P
FR
Sabc 3 4 3 4
20AT/2P 20AT/2P 20AT/2P 20AT/2P
Sa 5 6 5 6
J J
SFS EL 20AT/2P 20AT/2P 20AT/2P 20AT/2P
7 8 7 8
20AT/2P 20AT/2P 20AT/2P 20AT/2P
9 10 9 10
20AT/2P 20AT/2P 20AT/2P 20AT/2P
11 12 11 12
20AT/2P 20AT/2P 20AT/2P 20AT/2P
13 14 13 14
20AT/2P 20AT/2P
GTB
15 16
20AT/2P 20AT/2P
17 18
PPAC, 20AT/2P 20AT/2P
150AT, 60 HZ, 18 KAIC, 19 20
NEMA 1 ENCLOSURE 20AT/2P 20AT/2P
21 22
20AT/2P 20AT/2P
23 24
20AT/2P 20AT/2P
25 26
20AT/2P 20AT/2P
27 28
20AT/2P 20AT/2P
29 30
20AT/2P SPARE
31 32
GTB

DISTRBUTION PANEL 1,
250AT, 60 HZ, 22 KAIC,
NEMA 1 ENCLOSURE

REVISION DESIGNED/ CHECKED REMARKS


DESIGNED & DRAWN BY/DATE: CERTIFIED BY: OWNER'S APPROVAL PROJECT TITLE DATE DRAWN SHEET CONTENT SHEET NO.

GENERAL NOTES
DEYU CAI 1-STOREY COMMERCIAL BLDG. 1/
MEZZANINE
SPECIFICATION

EE-1
LEGEND & SYMBOLS
SCHEDULE OF LOADS
"DRAWINGS, AS INSTRUMENTS OF SERVICE ARE THE SOLE OWNER: WONG CHU KING PROPERTIES INC. RISER DIAGRAM
JAN. 07, 2022
PROPERTIES OF CDY, WHETHER THE OBJECT FOR WHICH THEY
ARE MADE IS EXECUTED OR NOT. ALL RIGHTS RESERVED,
INCLUDING DETAILS, DESIGNS AND PORTIONS THEREIN." LOCATION: LT 39 BLK8, JUPITER ST., BRGY.
BEL-AIR, MAKATI
327
505 2118 459 2872 350 3541 3262 550 3820 505
562

办公室

贮存
更衣室

接待区

1939
厨房

猫区
C.R.

562
5108

休息区
酒吧区
To Lights def @ 2F
C.R.

C.R.

UP
3Sefg
2470 459 6041

Sh
RU

6095
UP

展示区
美容区
花园
5771

550
宠物宿舍

2645
B31

B23
430

459 2657 459 6041 459 2567 459 2371 459 3396 550 3150 550 3820 505 900
REVISION DESIGNED/ CHECKED REMARKS
DESIGNED & DRAWN BY/DATE: OWNER'S APPROVAL PROJECT TITLE DATE DRAWN SHEET CONTENT SHEET NO.
GF LIGHTING LAYOUT
DEYU CAI 1-STOREY COMMERCIAL BLDG. 1/
MEZZANINE
2F LIGHTING LAYOUT
GF POWER LAYOUT
JAN. 07, 2022
"DRAWINGS, AS INSTRUMENTS OF SERVICE ARE THE SOLE
PROPERTIES OF CDY, WHETHER THE OBJECT FOR WHICH THEY
ARE MADE IS EXECUTED OR NOT. ALL RIGHTS RESERVED,

OWNER: WONG CHU KING PROPERTIES INC.


2F POWER LAYOUT
EE-2
INCLUDING DETAILS, DESIGNS AND PORTIONS THEREIN." LOCATION: LT 39 BLK8, JUPITER ST., BRGY.
BEL-AIR, MAKATI
327
505 2118 459 2872 350 3541 3262 550 3820 505
562

1939
DOWN
用餐区

562
5108

To Sefg & Sh @ GF
2470 459 6041

RD

6095
h
g

g
h

h
d

g
c
3Sabc

f

Sd
5771

电影室

550
e
b

1912
a

483
430

459 2657 459 6041 459 2567 459 2371 459 3396 550 3150 550 3820 505
REVISION DESIGNED/ CHECKED REMARKS
DESIGNED & DRAWN BY/DATE: OWNER'S APPROVAL PROJECT TITLE DATE DRAWN SHEET CONTENT SHEET NO.
GF LIGHTING LAYOUT
DEYU CAI 1-STOREY COMMERCIAL BLDG. 1/
MEZZANINE
2F LIGHTING LAYOUT
GF POWER LAYOUT
JAN. 07, 2022
"DRAWINGS, AS INSTRUMENTS OF SERVICE ARE THE SOLE
PROPERTIES OF CDY, WHETHER THE OBJECT FOR WHICH THEY
ARE MADE IS EXECUTED OR NOT. ALL RIGHTS RESERVED,

OWNER: WONG CHU KING PROPERTIES INC.


2F POWER LAYOUT
EE-2
INCLUDING DETAILS, DESIGNS AND PORTIONS THEREIN." LOCATION: LT 39 BLK8, JUPITER ST., BRGY.
BEL-AIR, MAKATI
GENERAL NOTES AND SPECIFICATIONS
THE DESIGN SCHEME HEREIN USES THE MODERN AND CONCISE DESIGN LANGUAGE
"CONCISE BUT NOT SIMPLE DECORATION STYLE" TO MEET THE DEMAND FOR
FUNCTIONAL REQUIREMENT. THE HANDLING OF INTERIOR SPACE IS STRIVING FOR
NATURAL AND RELAXED CONTEXT. THE EXPRESSIVENESS OF EXCESSIVE SPACE IS
ENHANCED THROUGH THE RELATIONSHIP OF COLOR.

SPACE: THE USAGE OF STAINLESS STEEL, GLASS TO FORM A SPRIGHTLY AND


TRANSPARENT SEPARATION AND THEN TO BUILD THE FLOW OF INDOOR SPACE. THROUGH
THE OVERLAPPING OF PERSPECTIVE POINT AND DISAPPEARANCE POINTS WHEN PEOPLE
MOVE, MANY SPACES ARE COMPARED AND LINKED TOGETHER TO FORM AN ABUNDANT
SPATIAL LEVEL.

INTERFACE: THE DIFFERENT MATERIAL AND INTERFACE ARE ABSTRACTED AS BASIC


MODELING ELEMENTS, THE COMPREHENSIVE APPLICATION OF MODELING ELEMENTS
(CHANGE AND CONTRAST) ARE USAGE TO FORM A CONCISE AND ABUNDANT SPACE.

MATERIAL: TAKING THE LARGE AREA OF WHITE MATERIAL AS THE BACKGROUND,


SIMPLICITY AND ELEGANCE AS THE COMMON CHARACTERISTICS OF MATERIALS,
DIFFERENT MATERIALS SUCH AS GLASS, STAINLESS STEEL AND STONE ARE
COMPREHENSIVELY APPLIED IN SPACE TO FORM A RHYTHMIC SENSE SPACE.

COLOR: THE APPLICATION OF COLOR IN SPACE IMPROVES THE IDENTIFIABILITY OF


THE ROUTE, AND EMPHASIZES THE INTERPENETRATION AND CONTRAST BETWEEN
DIFFERENT SPACE AND THE SPACE ITSELF. THE BLACK,WHITE AND ASH IS THE MAIN
KEYNOTE, SUPPLEMENTED WITH COLOR. THE DESIGN CONCEPTION EMPHASIZES
ORIGINALITY AND HIGHLIGHTS THE MODERN SENSE.

Fitting
Room Studio 1
8.5 flat

Room number 2204 Dressing


23.8 level Room Studio 2
Rest area
(8 people) 8.5 flat
Personnel Office Personnel
manager room
77.6 level (27 people)
15.9 flat Studio 3
8.5 flat

Room number 2203


Interview room 1 39.6 level (12 people)
committee room committee
Semi open office Storeroom Waiting Receptionist
8 people room
(32 people) circle 8 people
The
Manager Interview room 2 manager
room 2 room
32.3 flat 10 level
Room number 2202
77.4 level (28 people)

760
Finance room 1 Room number 2201
153.6 level (53 people) 115.2 level (37 people) 929
Assistant
Manager room 1 room
49.3 flat 8.5 flat 1774

Finance Director
Room Marketing
10.5 flat department
manager room
11.5 flat

ARCHITECTURAL PLAN
INTERIOR ENGINEER : PROJECT TITEL : PROJECT OWNER : SHEET CONTENTS : One REVISIONS : SHEET NO.

PROPOSED 22TH FLOOR


OFFICE LAYOUT WISHLAND
PROFESSIONAL INTERIOR ENGINEER
AS-SHOWN A-1
PRC NO.
SOFTWARE TECHNOLOGY
DATE ISSUE: LOCATION: 22TH
FLOOR TECHZONE CONDOMINIUM CORPORATION,
PTR NO. PLACE ISSUE: 213 BUENDIA AVE. MAKATI CITY PHILIPPINES