1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST
EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE LAWS AND ORDINANCES OF THE LOCAL CODE
ENFORCING AUTHORITIES AND THE REQUIREMENTS OF THE LOCAL POWER AND TELEPHONE
COMPANIES.
2. THE CONTRACTOR SHALL SECURE ALL PERMITS AND PAY ALL FEES REQUIRED FOR THE WORK AND
SHALL FURNISH THE OWNER THROUGH THE ENGINEERS. FINAL CERTIFICATES OF ELECTRICAL
INSPECTION AND APPROVAL FROM PROPER GOVERNMENT AUTHORITIES FOR COMPLETE WORK.
3. POWER SUPPLY TO THE PANEL BOARD MUST BE 3Ø, 4 WIRE + GROUNDING. 400V LINE TO LINE. 230V
LINE TO NEUTRAL.
4. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR
CONNECTION TO THE POWER SUPPLY.
5. ALL MATERIALS TO BE USED SHALL BE NEW AND INSTALLED IN APPLICATION FOR WHICH THEY ARE
INTENDED
6. ALL METALLIC CONDUITS, CABINETS AND EQUIPMENT SHALL BE PROPERLY GROUNDED AND
BONDED, BY MEANS OF COPPER STRAPS.
8. LIGHTING BRANCH CIRCUITS WITHOUT DESIGNATION SHALL BE 2-WIRE, AND 1-GROUND WIRE IN
15mm Ø EMT CONDUIT UNLESS NOTED OTHERWISE.
9. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN" OR "THWN" UNLESS
OTHERWIES INDICATED. MINIMUM SIZE OF WIRE SHALL BE 3.5 mm² STRANDED WIRE IN 15mm Ø
CONDUIT UNLESS NOTED ON PLANS. USE PHILPLEX / DURAPLEX OR PHELPS DODGE THHN WIRES
ONLY.
10. CONVENIENCE OUTLET CIRCUITS IN GENERAL SHALL BE 2-WIRE, 3.5mm² STRANDED THHN IN EMT
CONDUIT UNLESS OTHERWISE NOTED.
12. ALL CONDUIT PIPES SHALL BE ELECTRIC METALLIC TUBING (EMT) UNLESS OTHERWISE NOTED.
14. EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL TO OR PERPENDICULAR WITH THE BUILDING
LINE AND SUPPORTED BY CONDUIT CLAMPS EVERY 1.5M. DIAGONAL CONDUIT RUNS SHALL NOT BE
ACCEPTED.
15. ALL RECEPTACLE OUTLETS SHALL BE PROPERLY GROUNDED TO THE BOX BY MEANS OF GROUNDING
LUGS.
16. FOR SWITCH BOXES WITH MORE THAN FOUR (4) WIRES ENTERING THEM USE 0.10M. x 0.10M. SQUARE CAM 12 CAM 11 CAM 10 CAM 09 CAM 8
BOX WITH ONE (1) ADAPTER RING. (TYPICAL FOR RECEPTACLE BOXES). 2F
18. PULLBOXES SHALL BE PROVIDED BY THE CONTRACTOR WHENEVER NECESSARY TO FACILITATE WIRE
PULLING EVEN IF THESE ARE NOT INDICATED ON THE PLANS.
19. ALL REVISION OR ADDITIONAL WORKS ON ELECTRICAL PLANS SHOULD BE CONSULTED TO THE MONITOR
DESIGNER (P.E.E) PROFESSIONAL ELECTRICAL ENGINEER.
DP1
25
20. THE ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A DULY LICENSED
ELECTRICAL ENGINEER OR MASTER ELECTRICIAN AUTHORIZED FOR EACH GRADE.