1. ALL ELECTRICAL WORKS HEREUNDER SHALL CONFORM WITH THE LATEST EDITION OF PHILIPPINE ELECTRICAL CODE AND PLDT EE
TECHNICAL SPECIFICATIONS, RULES AND REGULATION OF NATIONAL, LOCAL CONCERNED AUTHORITIES, REQUIREMENTS OF LOCAL
MUNICIPALITY AND LOCAL POWER COMPANY.
2. CONTRACTOR SHALL CONDUCT SITE INSPECTION, VERIFICATION AND CHECKING BEFORE SUBMISSION OF BID IN ORDER TO
FAMILIARIZE THE ACTUAL CONDITION VERSUS EE PLANS. ANY CONFLICT BETWEEN PLANS AND ACTUAL CONDITION, ACTUAL
CONDITION SHALL PREVAIL. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR PLDT EVALUATION AND APPROVAL. ANY REVISION
HAS NO COST ADDITION TO PLDT.
3. CONSTRUCTOR SHALL PROVIDE ALL MATERIALS NOT MENTIONED ON THE PLANS AND BOQ AND ANY CONFLICT BETWEEN PLANS AND
ACTUAL CONDITION, CONTRACTOR SHALL REVISE WITHOUT AND COST ADDITION TO PLDT OR PLDT WILL NOT ISSUE ANY ADDITIONAL
WORK/ CONSTRUCTION BULLETIN.
4. ALL CONSTRUCTION PERMITS AND FEES INCLUDING THE SIGN AND SEAL OF ELECTRICAL PLANS, PROVIDING OF DESIGN ANALYSIS,
SPECIFICATIONS AND OTHER MAY REQUIRE FOR THIS WORK SHALL BE OBTAINED AT THE EXPENSE OF THE CONTRACTOR. THE
CONTRACTOR SHALL FURNISH PLDT THE FINAL CERTIFICATE OF INSPECTION AND APPROVAL FROM THE GOVERNMENT AUTHORITIES
AFTER THE COMPLETION OF THE WORK.
5. PROPOSED CIRCUIT BREAKERS SHALL BE INDUSTRIAL TYPE
6. CONTRACTOR SHALL PROVIDE ALL MATERIALS NOTMENTIONED ON THE PLANS AND BOQ ANY CONFLICT BETWEEN PLANS AND
ACTUAL CONDITION CONTRACTOR WILL REVISE WITHOUT ANY COST ADDITION TO PLDT OR PLDT WILL NOT ISSUE ANY ADDITIONAL
WORKS/CONSTRUCTION BULLETIN.
7. USE L1= RED, L2= YELLOW, AND L3= BLUE POWER CABLES FOR GROUNDING WIRES USE GREEN.
8. ALL CONDUITS RUN SHALL BE INSTALLED PARALLEL TO OR PERPENDICULAR WITH THE BUILDING WALL AND SUPPORTED FOR EVERY
1.0 METER OR LESS.
9. CONDUIT ROUTE SHALL BE BASED ON ACTUAL CONDITION.
10. PROPOSED NEMA1 ENCLOSURE SHALL BE GAUGE #14 ANDGAUGE#16 FOR NEMA4X.
11. SUBMIT SHOP DRAWING OF PROPOSED ECB/PANELBOARD AND CIRCUIT BREAKER BROCHURES, PROPOSED BRANCH BUSBAR
REPLACEMENT FOR PLDT EVALUATION AND APPROVAL PRIOR TO FABRICATION
12. RESTORE ALL AFFECTED AREAS TO ITS ORIGINAL CONDITION
13. TO PROVIDE DESIGN ANALYSIS. PAYMENT OF PERMITS AND ALL LEG WORKS FOR THE APPLICATION.
VICINITY MAP
A B C D E F G H I J
11430 8780 4065 7090 1675 5825 6195 13450 2850
1 ECB
PANEL
MTS 3P
SMART MCB
SMART
MTS
SMART
2700
ECB 250-AT
100kVA
1170 1833 FUEL
MTS 1700
PUMP
MDP 785
100kVA
MCB 585
4055
GENSET
9695
EMDP 785
585 RP 2K19
ACU
600
100kVA 1400
FUEL RECTI
800 600
TANK 950
MTS BATTERY
BANK
780
600
GP
TRANSFORMER
MOBILE BOX
(PLDT SMART)
SMART 1550 635
ACBEL
RECTI
600
RECTI
GP
600
BUSINESS
ACBEL
OFFICE
BATTERY 600
780 RECTI
BANK
ACBEL
600
RECTI
2
600
ALC REC B
GP REC B
BATTERY
BANK 1
880
BATTERY
PPR
BANK 2 RECTIFIER
3360
TANK
DAY
GENSET
DECOMMISION OF
EXTG. RECTIFIER
8959
5625
7560
TELEPHONE
PLAZA
3
GUARD
HOUSE
FACP
3515
4
7050
5
PLDT CAUAYAN
EXISTING SITE DEVELOPMENT PLAN
CONTRACTOR: OPERATOR: PROJECT NAME: TNT PROJECT DRAWN BY: SHEET CONTENT: SHEET NO.
SUPPLY & INSTALLATION OF 2x5TR &
PROJECT DESCRIPTION:
1x7.5TR ACU
PROFESSIONAL ELECTRICAL ENGINEER CHECKED BY:
EXISTING SITE DEVELOPMENT PLAN
EE-01
CORPORATION
SITE NAME: PLDT CAUAYAN PRC No: PTR No: REVIEWED BY:
135 PAN-PHILIPPINE HWY, CAUAYAN CITY
SITE ADDRESS: DATE ISSUE: TIN: DATE SUBMITTED: APPROVED BY:
3305 ISABELA SCALE: REVISION NUMBER.: EE-06
LONGITUDE: 121°46'1.51" LATITUDE:16°58'8.37'' PLACE ISSUE: DATE APPROVED: 1 : 280
C D E F G H I
4065 7090 1675 5825 6195 13450
1
PROP. 3x100mm² THHN & 1x22mm²
THHN GW IN 65mmØ IMC
MCB
SMART MTS
ECB MTS 3P
SMART
SMART PROP. ACU
PANEL MAIN PANEL
MTS TYPE, NEMA 1
2700
ECB 250-AT
100kVA
1170 1833 FUEL
MTS 1700
100kVA 600
MCB 585
4055
GENSET 600
PROP.
1000AH
BATTERY
PROP.
1000AH
BATTERY
PROP.
1000AH
BATTERY
PROP.
1000AH
BATTERY
PROP.
1000AH
BATTERY
PROP.
1000AH
BATTERY
9695
EMDP 785 400 600 600 600 600 600 600
585 RP 2K19
ACU
600
100kVA 1400
TRANSFORMER
MOBILE BOX
(PLDT SMART)
SMART 1550 635
ACBEL
RECTI
600
RECTI
GP
600
600
BUSINESS
OFFICE
BATTERY 600
780 RECTI
BANK 600
ACBEL
600
RECTI
600
600
ALC REC B
GP REC B
BATTERY
2
BANK 1 600
880
BATTERY
PPR
BANK 2
3360
20AT, 230V, 2P
20AT, 230V, 2P
NEMA 1 ECB
NEMA 1 ECB
PROP. PROP.
STACU 5 288 STACU 5
GF 2ND FLOOR
PROP. 2x3.5mm² THHN &
1x3.5mm² THHN GW +1x2.0mm² Control
Wire IN 15mmØ IMC
5625
7560
PROP. 3x8.0mm² THHN & 1x3.5mm²
THHN GW +1x2.0mm² Control Wire IN
25mmØ IMC
PROP. 3x5.5mm² THHN & 1x3.5mm²
THHN GW +1x2.0mm² Control Wire IN
20mmØ IMC
3
936 1130
PLDT CAUAYAN
PROPOSED ACU ELECTRICAL LAYOUT
CONTRACTOR: OPERATOR: PROJECT NAME: TNT PROJECT DRAWN BY: SHEET CONTENT: SHEET NO.
SUPPLY & INSTALLATION OF 2x5TR &
PROJECT DESCRIPTION:
1x7.5TR ACU
PROFESSIONAL ELECTRICAL ENGINEER CHECKED BY:
PROPOSED ACU ELECTRICAL LAYOUT
EE-02
CORPORATION
SITE NAME: PLDT CAUAYAN PRC No: PTR No: REVIEWED BY:
135 PAN-PHILIPPINE HWY, CAUAYAN CITY
SITE ADDRESS: DATE ISSUE: TIN: DATE SUBMITTED: APPROVED BY:
3305 ISABELA SCALE: REVISION NUMBER.: EE-06
LONGITUDE: 121°46'1.51" LATITUDE:16°58'8.37'' PLACE ISSUE: DATE APPROVED: 1 : 130
C D E F G H I
4065 7090 1675 5825 6195 13450
20AT, 230V, 2P
NEMA 1 ECB
STACU FCU1
PROP. 3x3.5mm² THHN &
1x3.5mm² THHN GW +1x2.0mm² Control
Wire IN 15mmØ IMC
300 300 300 300
QCI
FUTURE
FUTURE
DCPDB
DCPDB
DCPDB
PROP.
PROP.
PCM 600 600
ROOM
ROOM 600
PROP.
CISCO
LOT1 900
EXISTING
PROP.
ACCU
600 CISCO
LOT1 PROP. CISCO
600
FUTURE CEN
600 EQUIPMENT
PROP. CISCO
600
FUTURE CEN
600
9695
EQUIPMENT
EXISTING
ACCU
FUTURE
600 EQUIPMENT
PROP. CISCO
600
LOT 3
FUTURE
600 EQUIPMENT
PROP. CISCO
600
LOT 2
EXISTING
EXISTING
EXISTING
FUTURE
600
ACCU
ACCU
ACCU
EQUIPMENT FUTURE 9345
600
EQUIPMENT
FUTURE 12340
600 FUTURE
EQUIPMENT
CONFERENCE STORAGE EQUIPMENT
600
1200
FUTURE
EQUIPMENT
600
1200
2 7.5 TR
FCU2
DEP 12
PP-REC 2 COLUMN DCPDB
WIRES
760 1000 520 600
8959
(WORKING)
ACU
C.R
ACU
LOCKER
600 600 600 600 600 600 900 ROOM
WATO
FIBER
DCPDB HUAWEI HUAWEI HUAWEI
STORAGE PANTRY
600 HOME HUAWEI
HUAWEI HUAWEI HUAWEI ODF OFFICE
OFFICE
ROOM MALE
C.R
UP
3
GT
ACU ACU
ACU (NOT WORKING) (WORKING)
PLDT CAUAYAN
PROPOSED ACU ELECTRICAL LAYOUT
CONTRACTOR: OPERATOR: PROJECT NAME: TNT PROJECT DRAWN BY: SHEET CONTENT: SHEET NO.
SUPPLY & INSTALLATION OF 2x5TR &
PROJECT DESCRIPTION:
1x7.5TR ACU
PROFESSIONAL ELECTRICAL ENGINEER CHECKED BY:
PROPOSED ACU ELECTRICAL LAYOUT
EE-03
CORPORATION
SITE NAME: PLDT CAUAYAN PRC No: PTR No: REVIEWED BY:
135 PAN-PHILIPPINE HWY, CAUAYAN CITY
SITE ADDRESS: DATE ISSUE: TIN: DATE SUBMITTED: APPROVED BY:
3305 ISABELA SCALE: REVISION NUMBER.: EE-06
LONGITUDE: 121°46'1.51" LATITUDE:16°58'8.37'' PLACE ISSUE: DATE APPROVED: 1 : 130
G2
G1
800AT,3P 250AT,3P
RECTIFIER - B RECTIFIER - A
800AT,3P 30AT,3P
SPARE TVSS
30AT,3P
TVSS
PLDT CAUAYAN
EXISTING SINGLE LINE DIAGRAM
CONTRACTOR: OPERATOR: PROJECT NAME: TNT PROJECT DRAWN BY: SHEET CONTENT: SHEET NO.
SUPPLY & INSTALLATION OF 2x5TR &
PROJECT DESCRIPTION:
1x7.5TR ACU
PROFESSIONAL ELECTRICAL ENGINEER CHECKED BY:
EXISTING SINGLE LINE DIAGRAM
EE-04
CORPORATION
SITE NAME: PLDT CAUAYAN PRC No: PTR No: REVIEWED BY:
135 PAN-PHILIPPINE HWY, CAUAYAN CITY
SITE ADDRESS: DATE ISSUE: TIN: DATE SUBMITTED: APPROVED BY:
3305 ISABELA SCALE: REVISION NUMBER.: EE-06
LONGITUDE: 121°46'1.51" LATITUDE:16°58'8.37'' PLACE ISSUE: DATE APPROVED: NTS
ATS
(NORMALLY CLOSED)
MDP ATS
(1600AT, 3P) (LOAD SIDE)
PLDT CAUAYAN
PROPOSED SINGLE LINE DIAGRAM
CONTRACTOR: OPERATOR: PROJECT NAME: TNT PROJECT DRAWN BY: SHEET CONTENT: SHEET NO.
SUPPLY & INSTALLATION OF 2x5TR &
PROJECT DESCRIPTION:
1x7.5TR ACU
PROFESSIONAL ELECTRICAL ENGINEER CHECKED BY:
PROPOSED SINGLE LINE DIAGRAM
EE-05
CORPORATION
SITE NAME: PLDT CAUAYAN PRC No: PTR No: REVIEWED BY:
135 PAN-PHILIPPINE HWY, CAUAYAN CITY
SITE ADDRESS: DATE ISSUE: TIN: DATE SUBMITTED: APPROVED BY:
3305 ISABELA SCALE: REVISION NUMBER.: EE-06
LONGITUDE: 121°46'1.51" LATITUDE:16°58'8.37'' PLACE ISSUE: DATE APPROVED: NTS
PANEL / TYPE: PROPOSED ACU MAIN PANEL
PROP. 3x100mm² THHN & 1x22mm² THHN GRND. WIRE IN 65mmØ IMC
PROP. MAIN PROTECTION: 225AT,230V,60HZ,3P,MCCB, MTS TYPE
PANEL / TYPE: EXISTING MTS (1600AT)
3 SETS OF 3x250mm² THHN & 1x60mm² THHN GRND. WIRE IN 90mmØ IMC GENERATOR UTILIZATION: EXISTING 250KW GENERATOR (312.5KVA)
MAIN PROTECTION: 1600AT,230V,60HZ,3P,MCCB EXISTING LOAD (KVA) = (230V x 244.50 A x 1.732) / 1000 = 97.40KVA
ADDITIONAL LOAD (KVA) = (230V x (76.27A+(24 x 25%) x 1.732) / 1000 = 32.77KVA
TRANSFORMER UTILIZATION: EXISTING 300KVA TRANSFORMER TOTAL LOAD (KVA) = 130.17KVA
EXISTING LOAD (KVA) = (230V x 244.50 A x 1.732) / 1000 = 97.40KVA
ADDITIONAL LOAD (KVA) = (230V x (76.27A+(24 x 25%) x 1.732) / 1000 = 32.77KVA UTILIZATION = (130.17KVA / 312.5KVA) x 100% = 41.65% (SUFFICIENT)
TOTAL LOAD (KVA) = 130.17KVA
UTILIZATION = (130.17KVA / 300KVA) x 100% = 43.39% (SUFFICIENT) GENERATOR UTILIZATION: EXISTING 300KW GENERATOR (375KVA)
EXISTING LOAD (KVA) = (230V x 244.50 A x 1.732) / 1000 = 97.40KVA
ADDITIONAL LOAD (KVA) = (230V x (76.27A+(24 x 25%) x 1.732) / 1000 = 32.77KVA
TOTAL LOAD (KVA) = 130.17KVA
PLDT CAUAYAN
PROPOSED SCHEDULE OF LOADS
CONTRACTOR: OPERATOR: PROJECT NAME: TNT PROJECT DRAWN BY: SHEET CONTENT: SHEET NO.
SUPPLY & INSTALLATION OF 2x5TR &
PROJECT DESCRIPTION:
1x7.5TR ACU
PROFESSIONAL ELECTRICAL ENGINEER CHECKED BY:
PROPOSED SCHEDULE OF LOADS
EE-06
CORPORATION
SITE NAME: PLDT CAUAYAN PRC No: PTR No: REVIEWED BY:
135 PAN-PHILIPPINE HWY, CAUAYAN CITY
SITE ADDRESS: DATE ISSUE: TIN: DATE SUBMITTED: APPROVED BY:
3305 ISABELA SCALE: REVISION NUMBER.: EE-06
LONGITUDE: 121°46'1.51" LATITUDE:16°58'8.37'' PLACE ISSUE: DATE APPROVED: NTS