2/21/2022

CODE REFERENCE:
PROJECT DESCRIPTION:
· 2019 CEC Adopts 2017 NEC
SCOPE OF WORK: · 2019 CRC Adopts 2018 IRC
2019 CMC Adopts 2018 UMC

16530 Ventura Blvd Suite 104


Encino, CA 91436
818.784.2300
CSLB: Gen-B; 1006535
·

SIGNATURE:_____________________________
Equisolar
Roof-mounted , transformerless
· 2019 CPC Adopts 2018 UPC
photovoltaic system and new · 2019 CBC Adopts 2018 IBC
electrical components, including · 2019 CFC Adopts 2018 IFC
modules, mounting hardware, · 2019 Edition of the California
inverter, load center, disconnects and Energy Efficiency Standards
metering devices as required. · Underwriters Laboratories (UL) Standards
· OSHA Guidelines
· All AHJ Requirements
PROPERTY:
SINGLE FAMILY RESIDENTIAL
Zoning: UNKNOWN
1 VICINITY MAP 2 AERIAL VIEW
Bldg Square Feet: 4020 NTS NTS
T-01 T-01
Year built: 2009
APN: 4305014065
GENERAL NOTES: CLIENT INFORMATION
UTILITY PROVIDER:
LADWP · All electrical equipment shall be labeled, listed, or certified by a Nationally Recognized Testing Laboratory accredited by the United
HOMEOWNER HARRIS, AGNES
PV SYSTEM: States Occupational Safety Health Administration.

7.200 kW DC · Local Utility provider shall be notified prior to use and activation of any solar photovoltaic installation. 8856 SATURN STREET,
MODULE TYPE: LOS ANGELES, CA 90035
· The System will not be interconnected until approval from the local jurisdiction and utility is obtained. ADDRESS
(18 ) QCELL: Q.PEAK DUO BLK
ML-G10+ 400W · A ladder shall be in place for the inspection in compliance with CAL-OSHA Regulations. PHONE ---
PTC Rating: 373.5 W · Proper access and working clearance shall be provided as per section 110.26 CEC. CONTRACTOR INFORMATION
PV INVERTER:
· PV equipment, systems, and all associated wiring and interconnections shall only be installed by qualified persons. CONTRACTOR Equisolar, Inc
(1) SOLAREDGE: SE6000H-US [240V]
CEC Efficiency Rating: 99.0 % 16530 Ventura Blvd Suite 104

7.200
· All outdoor equipment shall be minimum NEMA 3R rated, including all roof mounted transition boxes and switches.
(18 ) SOLAREDGE: P400 OPTIMIZERS ADDRESS Encino, CA 91436
· All exterior conduit, fittings, and boxes shall be rain tight and approved for use in wet locations.
ARRAY PLACEMENT: PHONE 818.784.2300
· All conductors exposed to weather shall be listed and identified for use in direct sunlight.
FLUSH MOUNTED CSLB 1006535; Gen-B
ROOF TYPES: · The module conductors must be type USE-2 or listed for Photovoltaic (PV) Wire (UL 4703 & 854 Listed).
SHEET INDEX
COMP SHINGLE · All conductors must be copper and 90° Rated.

LOS ANGELES, CA 90035


8856 SATURN STREET,
FRAMING TYPE: T-01 TITLE SHEET
· All equipment shall be properly grounded and bonded in accordance with NEC Article 250.

HARRIS, AGNES
TRUSSES
PV.01 SITE PLAN
- 2x4 TRUSSES, 24" on center. · All applicable PV equipment listed and compliant with UL2703 and UL1703.

SYSTEM WEIGHT: PV.02 ROOF PLAN

---
· All NEC required warning signs, markings, and labels shall be posted on equipment and disconnects.
963.00 LBS PV.03 SINGLE LINE DIAGRAM
· All circuits connected to more than one source shall have over current devices located so as to provide over current protections from
PV ARRAY AREA: all sources. PV.04 WARNING LABELS & SIGNAGE
364.17 ft².
· The PV Power source circuit breaker shall be located at the opposite end of the main service disconnect. PV.05 RACKING AND ATTACHMENTS
PSF PRESSURE:
2.64 lbs/ft² · Flexible, fine-stranded cables shall be terminated only with terminals, lugs, devices, or connectors that are identified and listed for such PV.06 PV MODULE DATA SHEET
use.
INTERCONNECTION METHOD: PV.07 INVERTER DATA SHEET Paper Size

Interconnect via ( 1) 240V circuit · Connectors shall be of latching or locking type. Connectors that are readily accessible and operating over 300 volts shall require a tool
PV.08 RAPID SHUTDOWN DATA SHEET Scale
to open and shall me marked "Do Not Disconnect under load".
breaker(s) in main service panel. Drawn by
· The roof mounted photovoltaic modules, panels, or solar photovoltaic roll roofing material shall have the same or better listed PV.09 UL
fire-resistance rating than the building roof-covering material. Title
PV.010 GROUNDING
Project Number
· Smoke alarms and carbon monoxide alarms are required to be retrofitted onto the existing dwelling as per the 2016 CRC. These
smoke alarms are required to be in all bedrooms, outside each bedroom, and a least one on each floor of the house.
Sheet
· Smoke alarms and carbon monoxide alarms are to be verified and inspected by the IHE inspector in the field.
2/21/2022
THIS IS NOT A LEGAL SURVEY. DESIGNER/ENGINEER ASSUMES NO LIABILITY SYSTEM INFORMATION
FOR PROPERTY LINE OR SETBACK LOCATIONS. SURVEY PROPERTY LINES
AND LOCATION OF STRUCTURE ON PROPERTY ARE APPROXIMATE .
ROOF ARRAY MAGNETIC TRUE
ARRAY MOUNT
PITCH TILT ORIENTATION ORIENTATION

SATURN 1 AR-01 FLUSH 4/12 18.43° 88° 100°


S

16530 Ventura Blvd Suite 104


Encino, CA 91436
818.784.2300
CSLB: Gen-B; 1006535

SIGNATURE:_____________________________
TREET

Equisolar
2 AR-02
AR-03

PROPER AR-04
TY LINE
AR-05

APE
AY/
DRIVEW
27'

HARDSC
MAIN RE
S IDENCE

TY LINE 4'

Y LINE
PROPER

7.200
125'

PROPER
1
3'

LOS ANGELES, CA 90035


8856 SATURN STREET,
HARRIS, AGNES

---
30'
Paper Size

Scale
1/16" = 1'-0"
PROPER Drawn by
TY LINE
Title

55' 1 SITE PLAN Project Number


PV-02 SCALE: 1/16" = 1'-0"
Sheet
CONSTRUCTION NOTES ATTACHMENT DETAIL 2/21/2022

· PRIOR TO COMMENCING WORK, CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND SHALL NOTIFY ENGINEER OF ANY SCALE: NTS Ironridge
DISCREPANCIES, INCLUDING BUT NOT LIMITED TO DIMENSIONS, STRUCTURE, ELECTRICAL SERVICE, CONDUIT PATHS, UNDERGROUND UTILITIES,
OBSTRUCTIONS, ACCESSIBILITY ISSUES AND WORKING CLEARANCES. FlashVue
· THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE STARTING ANY OF THE WORK.
· ALL LOCATIONS ARE APPROXIMATE AND REQUIRE FIELD VERIFICATION.

818.784.2300
16530 Ventura Blvd Suite 104
Encino, CA 91436

CSLB: Gen-B; 1006535

SIGNATURE:_____________________________
Equisolar
· ALL EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
Ironridge Rail
· ALL OUTDOOR EQUIPMENT SHALL BE RAIN TIGHT WITH MINIMUM NEMA 3R RATING.
· ALL EXPOSED CONDUIT SHALL BE EMT AND SHALL BE MOUNTED AT MIN 3.5” OFF SURFACE OFF ROOF SURFACE.
· ALL FIELD INSTALLED JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND MODULES OR PANEL SHALL BE ACCESSIBLE DIRECTLY OR BY
DISPLACEMENT OF MODULE(S) OR PANEL(S) SECURED BY REMOVABLE FASTENERS. pv module
· LIVE PARTS IN PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150 VOLTS TO GROUND SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED COMP SHINGLE
PERSONS WHILE ENERGIZED.
· IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL
A SUPPLEMENTAL GROUNDING ELECTRODE.
· THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. flashing
· PROVIDE MINIMUM 4" CLEARANCE BETWEEN SOLAR AND ANY VENT.
· THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCE WITH THE CBC SECTION 1609 TO WITHSTAND A MINIMUM 110MPH WIND LOAD. 18.43°
2x4 TRUSSES
@24" OC, TYP
5/16"x 4.75" SS Lag Bolt
3" Min Embedment

MODULE SPECS
MODEL: QCELL: Q.PEAK DUO BLK
ML-G10+ 400W
STC: 400W
PTC: 373.5 W
8' 8' WEIGHT: 48.50LBS
LENGTH: 74.00"
41.10"
WIDTH:

ARRAY SPECS

7.200
24'
NUMBER OF MODULES: 18
SYSTEM WEIGHT (LBS): 963.00
ARRAY AREA (SQ.FT.): 364.17
NUMBER OF MOUNTS: 40
LOAD PER MOUNT (LBS): 24.08

LOS ANGELES, CA 90035


8856 SATURN STREET,
LOAD PER SQ.FT. (LBS): 2.64

HARRIS, AGNES
BUILDING SPECS

---
(E) 200A MAIN SERVICE PANEL
(E) 2X4 TRUSSES STORIES: 2
& UTILITY METER, 120/240VAC, 1ɸ
@24" OC, TYP BUILDING HEIGHT: 25'
(N) 60A AC DISCONNECT BUILDING FT²: 4020ft²
2P, 240V, NON-FUSED FRAMING TYPE: TRUSSES
RAFTER SIZE: 2X4
(N) SOLAREDGE: SE6000H-US [240V]
RAFTER SPACING: 24" O.C. Paper Size
INVERTER SPAN: Scale
24' MAX
Drawn by
SLOPE OF ROOF: 4/12
MIN LAG BOLT Title

EMBEDMENT: 3" MIN


Project Number
1 ROOF PLAN ROOFING MATERIAL: COMP SHINGLE
PV-02 SCALE: 1/8" = 1'-0" STANDOFF DISTANCE: 4' MAX Sheet
RACKING CO: IRONRIDGE
2/21/2022

818.784.2300
16530 Ventura Blvd Suite 104
Encino, CA 91436

CSLB: Gen-B; 1006535

SIGNATURE:_____________________________
Equisolar
120/240 VAC
1
SINGLE PHASE SERVICE
(E) 200A MAIN PANEL 3/4" EMT: SOLAR
(E) 200A MAIN BREAKER (2) #8 AWG THWN-2 CONDUCTORS
(1) #8 AWG THWN-2 NEUTRAL
MODULE
STRING 1
(1) #8 AWG THWN-2 GROUND
(9) QCELL: Q.PEAK DUO BLK ML-G10+ 400W
CONNECT MODULE OUTPUT MODULES AND
CONDUCTORS EXPOSED TO FREE AIR: CONDUCTORS TO SOLAR EDGE (9) SOLAREDGE: P400 DC-DC POWER
UTILITY (4) #10 AWG PV-WIRE CONDUCTORS INPUT LEADS OPTIMIZERS.
METER
(1) #6 AWG BARE COPPER GROUND
OPTIMIZERS ARE WIRED IN SERIES
· 380V FIXED STRING VOLTAGE DURING
SOLAREDGE: SE6000H-US [240V] DC DC DC
2 OPERATION (CONTROLLED BY INVERTER).
200A,2P

6000WATT INVERTER OPTIMIZER OPTIMIZER OPTIMIZER · 480V DC MAXIMUM STRING VOLTAGE


3
4 SOME MODULE/OPTIMIZER (LIMITED BY INVERTER).
INVERTER PAIRS NOT SHOWN FOR
AC OUT CLARITY
(N) 35 AMP A
B
PV BREAKER C C DC IN

MANUAL OPTIMIZER GROUNDING DETAILS


JUNCTION BOX
LOCKABLE STRING 2
NEUTRAL (AS NEEDED)
DISCONNECT WIRING IDENTICAL TO STRING 1
BUS
3R, 60A, (9) QCELL: Q.PEAK DUO BLK ML-G10+
120/240VAC LOAD RATED DC DISCONNECT 400W
GROUND MAX DC INPUT VOLTAGE: 480V (9) SOLAREDGE: P400 POWER
BUS 3/4" EMT CONDUIT:
OPTIMIZERS
(4) #10 AWG THWN-2 WIRE CONDUCTORS
*INSTALLER TO VERIFY EXISTING GROUNDING SYSTEM* (1) #8 AWG THWN-2 COPPER GROUND

SUPPLEMENTAL FACILITY GEC COMPLIANT WITH NEC ARTICLES 250 AND 690.
GROUND IF GROUND 6AWG BARE COPPER GROUND RUN OUTSIDE RACEWAY OR 8AWG THWN-2 IN CONDUIT
NECESSARY (690.47, 250.30, 250.33, 250.66, 250.64 & ANY OTHER APPLICABLE SECTIONS)

7.200
MAIN PANEL
PV BACKFEED BREAKER SIZE 35A
MAIN BREAKER SIZE: 200A, MAIN BUS RATING: 200A
TOTAL AMPS ON BUS 200A + 35A = 235A ≤ 120% OF 200A (240A)
DC WIRE SIZING CALCULATIONS: AC WIRE SIZING CALCULATIONS:
OCPD CALCULATIONS PER INVERTER: ELECTRICAL NOTES:

LOS ANGELES, CA 90035


ASSUMPTIONS

8856 SATURN STREET,


1. GROUNDING WIRE WILL BE BONDED DIRECTLY TO FACILITY GROUND.
HIGH TEMP AMBIENT = 39°C MAX AC OUTPUT CURRENT = (Inverter Output Circuit Current)[690.8(A)(3)] x (Safety)[690.9(B)] = 2. ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2017 NEC 250.
HIGH TEMP ROOF = 56°C C. INVERTER TO MAIN SERVICE PANEL

HARRIS, AGNES
(25.00A) x (1.25) = 31.25A --> 35A OVERCURRENT PROTECTION. 3. MODULE CONNECTIONS TO BE MADE WITH #10 PV WIRE PER 690.35(D).
LOW TEMP = -7°C SOLAREDGE: SE6000H-US [240V]: 4. MODULE CONDUCTORS ARE SIZED FOR DERATED CURRENT.
90°C RATED WIRE MAX OUTPUT CURRENT: 25.00A 11.14 AMPS SHORT CIRCUIT CURRENT
CONDUIT MOUNTED MIN 3.5" ABOVE ROOF per 690.8(B)(1): 25.00A x 1.25 = 31.25A 125% DERATING FOR EXTREME IRRADIANCE CONDITIONS [NEC 690.8(A)(1)]
SURFACE 125% DERATING, CONTINUOUS PHOTOVOLTAIC SOURCE CURRENT [NEC 690.8(B)(1)].
EQUIPMENT

---
WIRE CHOICE: #8 AWG THWN-2
156% TOTAL DERATING (COMBINATION OF ABOVE)
per 310.15(B)(16): #8 THWN-2 = 50A @75°C
17.38 AMPS TOTAL CAPACITY
per 310.15(B)(2)(a): 50A x 0.91[CORRECTION] = 45.5A
(AMPS TOTAL CAPACITY = STRING SHORT CIRCUIT CURRENT MULTIPLIED BY TWO ABOVE DERATES, 1.25 X 1.25 X SHORT
A. OPTIMIZER TO JUNCTION BOX (OPEN AIR)
SOLAREDGE: P400 POWER OPTIMIZER
per 310.15(B)(3)(a): 45.5A x 100% [ADJUSTMENT] = 45.5A ID QTY ITEM CIRCUIT CURRENT)
per 690.8(A)(5): 15A (max output current) 31.25A ≤ 45.5A ===> OK 5. INVERTER PROVIDES NECESSARY GROUND FAULT PROTECTION AS REQUIRED BY 2017 NEC 690.5 GROUND FAULT PROTECTION
AND 690.35 UNGROUNDED SYSTEMS.
per 690.8(B)(1): 15A x 1.25 = 18.75A 1 18 (N) QCELL: Q.PEAK DUO BLK ML-G10+ 400W 6. PHOTOVOLTAIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES
WIRE CHOICE: #10 AWG PV-WIRE MODULE WITH 690.35.
per 310.15(B)(16): #10 PV-WIRE = 40A @90°C 7. WHERE DC PHOTOVOLTAIC OUTPUT CIRCUITS ARE RUN INSIDE A BUILDING THEY SHALL BE CONTAINED IN A METALLIC
per 310.15(B)(3)(C): 39°C + 17°C[3.5" ABOVE ROOF] = 56°C RACEWAY OR ENCLOSURE FROM THE POINT OF PENETRATION TO THE FIRST READILY ACCESSIBLE DISCONNECTING MEANS -
per 310.15(B)(2)(a): 40A x 0.71[CORRECTION] = 28.4A
2 18 (N) SOLAREDGE: P400 DC-DC OPTIMIZERS 2017 NEC 690.31 (E).
per 310.15(B)(3)(a): 28.4A x 100% [ADJUSTMENT] = 28.4A 8. USE UL APPROVED BONDING FITTINGS AT ALL CONDUIT/BOX JUNCTIONS. Paper Size
9. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
18.75A ≤ 28.4A ===> OK 10. INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
Scale
B. JUNCTION BOX TO INVERTER
INVERTER 1 (N) SOLAREDGE: SE6000H-US [240V] INVERTER 11. INSTALLER TO IDENTIFY THE EXISTING GROUNDING ELECTRODE TYPE (I.E. DRIVEN ROD, UFER, WATER PIPE, OR COMBINATION
OF SOME OR ALL OF THE PREVIOUSLY MENTIONED). IN EXISTING ELECTRICAL SYSTEMS THAT USE ONLY A WATER PIPING
SOLAREDGE: P400 POWER OPTIMIZER GROUNDING ELECTRODE SYSTEM, AN ADDITIONAL GROUNDING ELECTRODE (I.E DRIVEN ROD) SHALL BE PROVIDED. (NEC 250.50) Drawn by
per 690.8(A)(5): 15A (max output current) 12. PER NEC 250.53(2), A SINGLE ROD, PIPE OR PLATE ELECTRODE SHALL BE SUPPLEMENTED BY AN ADDITIONAL ELECTRODE OF
per 690.8(B)(1): 15A x 1.25 = 18.75A
3 1 (N) NEMA 3R 60A NON-FUSED AC DISCONNECT TYPE SPECIFIED IN 250.52(A)(2) THROUGH (A)(8) SPACED NO LESS THAN 6FT APART. EXCEPTION, IF A SINGLE ROD, PIPE OR PLATE Title
WIRE CHOICE: #10 AWG THWN-2 GROUNDING ELECTRODE HAS A RESISTANCE TO EARTH OF 25 OHMS OR LESS, THE SUPPLEMENTAL ELECTRODE SHALL NOT BE
per 310.15(B)(16): #10 THWN-2 = 35A @75°C
240VAC, 10KAIC RATING. REQUIRED.
13. #4 AWG CU TO UNDERGROUND METAL WATER PIPE THAT IS A MINIMUM 10 FOOT BURIAL IN PIPE LENGTH. CONNECT GROUNDING Project Number
per 310.15(B)(3)(C): 39°C + 17°C[3.5" ABOVE ROOF] = 56°C
ELECTRODE CONDUCTOR WITHIN FIVE FEET OF WHERE IT ENTERS BUILDING. 250.52(A)(1), 250.68(C).
per 310.15(B)(2)(a): 35A x 0.71[CORRECTION] = 24.85A
14. ADDITIONAL #4 AWG CONNECTION TO UFER IF AVAILABLE PER 250.66. IF UFER NOT AVAILABLE THEN TWO #6 AWG CU
per 310.15(B)(3)(a): 24.85A x 80% [ADJUSTMENT] = 19.88A Sheet
CONNECTIONS TO GROUND RODS SEPARATED BY AT LEAST 6 FT IS NEEDED PER 250.33.
18.75A ≤ 19.88A ===> OK
2/21/2022
GENERAL FIRE GUIDELINES & MARKING REQTS: REQUIRED WARNING LABELS
SEC. 5. MARKINGS, LABELS, AND WARNING SIGNS.

MAX SYSTEM VOLTAGE: 480V

818.784.2300
16530 Ventura Blvd Suite 104
Encino, CA 91436

CSLB: Gen-B; 1006535

SIGNATURE:_____________________________
Equisolar
MAX CIRCUIT CURRENT: 11.14A
MAX RATED OUTPUT CURRENT OF 15A
WARNING: PHOTOVOLTAIC POWER SOURCE THE CHARGE CONTROLLER OR DC-TO-DC
CONVERTER (IF INSTALLED)

CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED

WARNING
“ ”

THE DISCONNECTION OF THE ∕


GROUNDED CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGE
ON THE EQUIPMENT

CAUTION: SOLAR CIRCUIT


WARNING
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDE MAY BE ENERGIZED
IN THE OPEN POSITION
SEC. 7. DIRECT CURRENT (DC) CONDUCTOR LOCATIONS.
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM

7.200
THIS LABEL TO BE INSTALLED AT THE
MAIN ELECTRICAL SERVICE PANEL

CAUTION
POWER TO THIS BUILDING IS ALSO

LOS ANGELES, CA 90035


SUPPLIED FROM THE FOLLOWING

8856 SATURN STREET,


SEC. 8. GROUND MOUNTED PHOTOVOLTAIC ARRAYS.
SOURCES WITH DISCONNECTS

HARRIS, AGNES
LOCATED AS SHOWN.

WARNING

---
SEC. 9. OVERHEAD ARRAYS ON ROOFTOPS (E.G. TRELLIS SYSTEMS).
POWER SOURCE OUTPUT
CONNECTIONDO NOT
RELOCATE THIS
OVERCURRENT DEVICE

(18) TOTAL Paper Size


PV MODULES

Scale
INTERACTIVE PHOTOVOLTAIC POWER SOURCE
SOLAR D/C
RATED AC OUTPUT CURRENT (A): 25.00A DISCONNECT Drawn by
MAIN ELECTRIC
NOMINAL OPERATING AC VOLTAGE (V): 240V PV SYSTEM DISCONNECT
SERVICE
DISCONNECT
FOR UTILITY OPERATION
Title

Project Number

8856 SATURN STREET LOS ANGELES, CA 90035


Sheet
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________
Title

Equisolar
Scale

Sheet

7.200 16530 Ventura Blvd Suite 104


Drawn by

HARRIS, AGNES
Paper Size

Encino, CA 91436
8856 SATURN STREET, 818.784.2300
Project Number

LOS ANGELES, CA 90035 CSLB: Gen-B; 1006535


2/21/2022

---
SIGNATURE:_____________________________