You are on page 1of 128

INDEX

Sl. No Drawing Description Drg No. Total Sheets Rev

1 110/33kV, 12.5/15MVA TRANSFORMER CONTROL & RELAY PANEL

a) General Arrangement YN1M302310-AAB R0


b) Bill of Material YN1M302310-AB 54 R0
c) Schematic drawings YN1M302310-CAB R0

2 SUBSTATION AUTOMATION SYSTEM PANEL

a) General Arrangement YN1M302310-ASA R0


b) Bill of Material YN1M302310-SA 16 R0
c) Schematic drawings YN1M302310-CSA R0

3 SUBSTATION AUTOMATION SYSTEM COMMUNCATION CONNECTIVITY DIAGRAM


COMMUNCATION CONNECTIVITY
YN1M302310-CZN 1 R0
DIAGRAM
4 FACTORY ACCEPTANCE TEST SPRCIFICATION

FACTORY ACCEPTANCE TEST


YN1M302310-ZFA 17 -
SPRCIFICATION

5 FUNCTION DESIGN SPECIFICATION

FUNCTION DESIGN SPECIFICATION YN1M302310-ZAA 39 -

CLIENT:

DGGT DELEGATION GENERALE DES GRANDS TRAVAUX


CONTRACTOR:

OVERSEAS INFRASTRUCTURE ALLIANCE


OIA (INDIA) PVT. LIMITED. MUMBAI
PROJECT:

Prepared by: Checked by: Approved by:


110/33kV TRANSFORMER BAY EXTENSION AT EXISTING
RMS RMS/MNG UKD MOUKOUKOULOU SUBSTATION IN REPULIC OF CONGO
Date: Rev. Date: Rev. Date: Rev. TITLE:
Total Sheet

30.05.2014 0 10.06.2014 1
CONTROL & PROTECTION PANELS
AND SCADA SYSTEM 128

Doc. No. REV

ABB INDIA LIMITED 3VIN 14 0573 D4 906 1


ABB India Title page A3 - Version 2 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

A A
Customer : Extension of Mokoulou Substation

Customer Ref.
SAP Project PO.No NO.:
Definition : IN56414054

B
ABB Ref.NO : 3100053172 B

Substation : Mokokoulou Substation


We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Equipment : 110kV Transformer Control & Relay panel

C Drawing Ref. : General Arrangement : YN1M302310 -AAB C

Bill of Material : YN1M302310 -AB


Schematic Drawings : YN1M302310 -CAB

Standard Bay Ref. : 1CR1A


C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

D APPLICABLE FOR FOLLOWING BAYS D

SL.No BAY REF. PANEL REF. BAY DESCRIPTION


Transformer Control & Relay Panel
1 101 1CR1A

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Title page Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 1


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-AAB No.sheets 54
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
Report ABB India List of contents A3 - Version 2 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
Sheet n.sh. Description 1 Description 2 Rev. Revision note Sheet n.sh. Description 1 Description 2 Rev. Revision note

A 1 2 For Transformer bay Title page 44 45 For Transformer bay Master Blocks_REC670 A

2 11 For Transformer bay List of contents 45 46 For Transformer bay Master Blocks_REC670

11 12 Cubicle layout Front view with door 46 47 For Transformer bay Master Blocks_REC670

12 13 Cubicle layout Section view incl. location designation 47 48 For Transformer bay Master Blocks_REC670

13 14 Cubicle layout Hinged frame view 48 49 For Transformer bay Power supply Circuit_RET650

14 21 Cubicle layout Inside view 49 50 For Transformer bay Analog Input Circuit_RET650
B B
21 22 For Transformer bay List of symbols 50 51 For Transformer bay Analog Input Circuit_RET650

22 23 For Transformer bay Single Line Diagram 51 52 For Transformer bay Binary Input Circuit_RET650
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

23 24 For Transformer bay Control Logics 52 53 For Transformer bay Binary Input Circuit_RET650

24 25 For Transformer bay Trip Logic 53 54 For Transformer bay Binary Input Circuit_RET650

25 26 For Transformer bay DC Distribution 54 55 For Transformer bay Master Blocks_RET650

26 27 For Transformer bay DC Distribution 55 56 For Transformer bay Master Blocks_RET650


C C
27 28 For Transformer bay AC Distribution 56 57 For Transformer bay Trafo Troubles

28 29 For Transformer bay Metering Circuit 57 58 For Transformer bay GRP-A Master Trip Relay Circuit

29 30 For Transformer bay Metering Circuit 58 59 For Transformer bay 3Ph Trip Relay Circuit For LBB Protn

30 31 For Transformer bay Power Supply Circuit_REC670 59 60 For Transformer Bay Trip Coil-I Circuit
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

31 32 For Transformer bay Analog Input Circuit_REC670 60 61 For Transformer Bay Trip Coil-II Circuit

32 33 For Transformer bay Analog Input Circuit_REC670 61 62 For Transformer Bay CB Closing Circuit
D D
33 34 For Transformer bay Analog Input Circuit_REC670 62 63 For Transformer Bay Contacts Distribution

34 35 For Transformer bay Binary Input Circuit_REC670 63 64 For Transformer Bay Spare TB's

35 36 For Transformer bay Binary Input Circuit_REC670 64 1001 For Transformer Bay CB Closing Circuit

36 37 For Transformer bay Binary Input Circuit_REC670 1001 1002 Parts list Part List

37 38 For Transformer bay Binary Input Circuit_REC670 1002 1003 Parts list Part List

38 39 For Transformer bay Binary Input Circuit_REC670 1003 1004 Parts list Part List

E 39 40 For Transformer bay Binary Input Circuit_REC670 1004 Parts list Part List E

40 41 For Transformer bay Binary Input Circuit_REC670

41 42 For Transformer bay Isolator Control Circuit

42 43 For Transformer bay mA Input Circuit_REC670

43 44 For Transformer bay Binary Output Circuit_REC670

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. List of contents Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation List of contents Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 2


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 11
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Layout A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB Front view with door
>+CC01 Technical data:
-C2

A
ABB Height 2312mm (47mm Base Frame+15mm AV)
A
Width 800mm
Depth 800mm
Weight 400 kg Approx.
Thickness of material
: Swing frame 3mm
: Rear cover 2mm
: Roof plate 2mm
: Bottom plate 2mm
: Side covers 2mm
: Base frame 3mm

B Protection class IP54 B


Cubcile Illumination 11W Compact Flourescent lamp
Earth Bar Tinned Copper Strip of 25 x 6mm
Bottom Plate With two opening of size 275x550mm
Gland Plate 2 nos of plates of size 315x590mm
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Cubicle Colour
Powder Coating : Exterior RAL7032,Texture finish
: Interior Glossy white
: Base frame Black
: Thickness 80 microns for powder coating

Wires & Ferrules


C Wire size for CT Circuits 2.5mm², Phase : RYB, Neutral : Black C
Wire size for PT Circuits 1.5mm², Phase : RYB, Neutral : Black
Wire size for DC Circuits 1.5mm², Grey
2250

Wire size for Aux.AC Circuit 1.5mm², Grey


Wire size for Earthing 2.5mm², Green
Ferrules
Wire directly connected to TRIP COIL Red Coloured "T"
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

All other ferrules White Sleeve with Nos.marked in Black letters


Terminal blocks ( 20% spare terminal blocks )
Terminal Make
Terminal CT / VT Disconnecting type
D Terminal AC/DC incoming Disconnecting type
D
Terminal Earthing Non-Disconnecting type
Terminal Trip Non-Disconnecting type
Terminal Interpanel,General Disconnecting ,Non-Disconnecting type
LABELS DIMENSIONS(mm) LETTER HEIGHT(mm)
1:Main Label(Front) 200 x 40 10
MATERIAL : Lamicoid TYPE OF INSCRIPTION : Engraving-white letters on black background
2A : Apparatus Label (Inside) 33 x 80 3
MATERIAL : Aluminium anodised TYPE OF INSCRIPTION : Engraving-white letters on black background
2B : Apparatus Label (Front) 48 x 14 3
MATERIAL : Aluminium anodised TYPE OF INSCRIPTION : Engraving-white letters on black background
E E
3:Item Desgination Stickers(Inside) 20 x 10 5
MATERIAL : Aluminium anodised TYPE OF INSCRIPTION : Black letters
4:Flag Relay Labels 29 x 29 2

MATERIAL : Aluminium anodised TYPE OF INSCRIPTION : Engraving-white letters on black background

5:PB/Lamp Labels 30 x 40 3
MATERIAL : Aluminium anodised TYPE OF INSCRIPTION : Engraving-white letters on black background
15
47

800

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Assembly drawing Ref.Des. =1R
Approved AHV Cubicle layout DCC ELU +1A
F F
Project Extension of Mokoulou Substation Front view with door Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Rev. Revision note Date Name


Mokokoulou Substation
3100053172 ABB ABB
Doc. no. YN1M302310-AAB
Sheet
n. sheet
11
12
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Layout A3 - Version 1 1
Cross 2sectional view I - I 3 4 5 6 7 8
© Copyright 2010 ABB

A A

800

65 670 65

25
50
275 275

B B

CABLE OPENING
CABLE OPENING

275 x 550 mm
275 x 550 mm

550

800
770

720
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

max. 90°
C C
+V

30

25
max. 120°

+U +W

X
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

NOTE:

D 1. ALL DIMENSIONS ARE IN MM. D

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Assembly drawing Ref.Des. =1R
Approved AHV Cubicle layout DCC ELU +1A
F F
Project Extension of Mokoulou Substation Section view incl. location designation Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Rev. Revision note Date Name


Mokokoulou Substation
3100053172 ABB ABB
Doc. no. YN1M302310-AAB
Sheet
n. sheet
12
13
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Layout A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB +U Front view hinged frame +W Side view hinged frame +V Back view hinged frame
-1CR1A -1CR1A -1CR1A

A A
U W V
0 0 0
1 1 1
2 2 2
3 3 3
-D03.01 -D03.02
4 4 4
5 5 5
-D07.01 -X31 -X41 -X51 -X61 -X71 -X81
>+CC01
-X301 -X311 -X321 -X401 -X401

6 6 6 Length of cable duct=200 mm


1 1 1 1 1 1 -X311
-X11PE -X31 -X41 -X51 -X61 -X71 -X81 -X91 -X101 -X111 -X121 -X131 -X401 -X411
2 2 2 2 2 2
-X11
3 3 3 3 3 3
A AA A
1 1 1
4 4 4 4 4 4
2 2 2
5 5 5 5 5 5

3 6 6 6 6 6 6 3 3

7 7 7 7 7 7 B BB B
4 4 4
8 8 8 8 8 8

7 7 7
5 5 5

P1
9 9 9 9 9 9

10 10 10 10 10 10 6 6

-D07.01
11 11 11 11 11 11
7 7
12 12 12 12 12 12
C C C
13 13 13 13 13 13 8 8

14 14 14 14 14 14
9 9
15 15 15 15 15 15
10 10
16 16 16 16 16 16

B 8 8 8 B
17 17 17 17 17 17
D D D
11 11
18 18 18 18 18 18
12 12

13 13
-X32 -X42 -X52 -X62 -X72 -X302 -X312 -X322

REC670 1
-X32
2

3
1
-X42
2

3
1
-X52
2

3
1
-X62
2

3
1
-X72
2

3
-X82 -X92 -X102 -X112 -X122 -X132
A A A
14

15
14

15

9 9 9
4 4 4 4 4 16 16

5 5 5 5 5
17 17
6 6 6 6 6
18 18
7 7 7 7 7 B B B
8 8 8 8 8 19 19
9 9 9 9 9
20 20
10 10 10 10 10 -X303 -X313 -X323
11 11 11 11 11 21 21

10 10 10 12

13

14

15

16
12

13

14

15

16
12

13

14

15

16
12

13

14

15

16
12

13

14

15

16
A A A 22

23

24
22

23

24

B B B

P10

P11

P12

P13

P40

P41
17 17 17 17 17

P3

P4

P5

P6

P7

P8

P9
18 18 18 18 18

11 11 11
12 12 12
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

13 13 13
14 14 14
15 15 15
>+CC01 >+CC01
16 16 16 Length of cable duct=200 mm

-D17.01
17 ABB Ready Start Trip 17-D17.01 17
18 18 18 -D17.01
19 19 19
C -X0
-X321

X321

X331
X326

X336
1
-X101

X0
HMI 2

X101
1 3

ESC Clear 2
4

20 20
5

20
-X307
3 6

X1

X307
1
7
2 4

? -X4
1
3
4
5
8
9
10
5 6
2 11

X4
R 3
6
7
12
7
L 4
8
13

21 21
8 14

21
9
15
10 9
16
11

X9
10 17
12
18
13
14
15
16
-X304 -X102 -X324

22 22
17

22

X304

X324

X329

X334

X339
X102
1 18 1 1
2 2
3 2 3
4 4
3
5 5

RET650
-X309
6 4 6

X309
1
7 7
2 5
8 8
3

23 23
9 6 9

23
10 10
11 7 11
12 12
8
13 -X410 13
14 9 14

X410
1
15 15
PE 10
16 16
3
17 17

24 24
18 18

24
25 -TNC 25 25
-ASS -A/M >+CC01 >+CC01
-PB01 Length of cable duct=200 mm
26 26 26
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

27 27 27
28 28 28
-D29.131.101

-D29.137.101

-D29.143.301

-D29.155.101

29 29 -D29.155.101
-D29.143.301
-D29.137.101
-D29.131.101
-D29.119.101
-D29 29 -D29 -D29.113.101
-D29.107.101
-D29.101.101
21 11 21 11 21 11 21 11
221 211 121 111
1B 1A 1B 1A 1B 1A
22 12 22 12 22 12 22 12
222 212 122 112
2B 2A 2B 2A 2B 2A

30 30
23 13 23 13 23 13 23 13

30
223 213 123 113
24 14 24 14 24 14 24 14 3B 3A 3B 3A 3B 3A
224 214 124 114
25 15 25 15 25 15 25 15 4B 4A 4B 4A 4B 4A
225 215 125 115
-D29.101.101

-D29.107.101

-D29.113.101

-D29.119.101

-D29.131.301

-D29.143.101

D D
26 16 26 16 26 16 26 16 5B 5A 5B 5A 5B 5A
226 216 126 116
27 17 27 17 27 17 27 17
227 217 127 117 6B 6A 6B 6A 6B 6A
28 18 28 18 28 18 28 18
228 218 128 118 7B 7A 7B 7A 7B 7A

-D29.143.101
-D29.131.301
31 31 31
8B 8A 8B 8A 8B 8A

9B 9A 9B 9A 9B 9A

10B 10A 10B 10A 10B 10A

11B 11A 11B 11A 11B 11A


21 11 21 11 421 411 321 311
12B 12A 12B 12A 12B 12A
22 12 22 12 422 412 322 312

23 13 23 13 423 413 323 313 13B 13A 13B 13A 13B 13A

32 32 32 24

25

26
14

15

16
24

25

26
14

15

16
424

425

426
414

415

416
324

325

326
314

315

316
14B

15B
14A

15A
14B

15B
14A

15A
14B

15B
14A

15A
-D33.101.101

-D33.113.101

-D33.119.101

-D33.125.101

16B 16A 16B 16A 16B 16A


27 17 27 17 427 417 327 317
17B 17A 17B 17A 17B 17A
28 18 28 18 428 418 328 318
18B 18A 18B 18A 18B 18A

33 -D33 33 33 -D33.125.101
-D33.119.101
-D33.113.101
-D33.101.101
-D33 21 11 21 11 21 11 221 211 121 111

22 12 22 12 22 12 222 212 122 112

34 34 34 23

24

25
13

14

15
23

24

25
13

14

15
23

24

25
13

14

15
223

224

225
213

214

215
123

124

125
113

114

115
-D33.101.301

-D33.101.307

-D33.119.301

26 16 26 16 26 16 226 216 126 116

27 17 27 17 27 17 227 217 127 117

28 18 28 18 28 18 228 218 128 118

35 35 35 -D33.119.301
-D33.101.307
-D33.101.301
21 11 21 11 21 11

22 12 22 12 22 12

36 36 36 23

24

25

26
13

14

15

16
23

24

25

26
13

14

15

16
23

24

25

26
13

14

15

16

27 17 27 17 27 17

28 18 28 18 28 18

37 -D37.01 37 37
-D37.01 >+CC01 >+CC01
38 38 Length of cable duct=200 mm
38 N2 N1 9 8 7 7 B2 B1 6 5

39 39 39 4 4 Y2 Y1 3 2 1 1 R2 R1

40 40 40
41 41 41
E 42 42
E
42
43 43 43
44 44 44

Sheet-Origin

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Assembly drawing Ref.Des. =1R
Approved AHV Cubicle layout DCC ELU +1A
F F
Project Extension of Mokoulou Substation Hinged frame view Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Rev. Revision note Date Name


Mokokoulou Substation
3100053172 ABB ABB
Doc. no. YN1M302310-AAB
Sheet
n. sheet
13
14
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
Print: 5/30/2014 C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s ABB India Layout A3 - Version 1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © Copyright 2010 ABB

F
A

E
D
C

Rev.
Sheet-Origin

Based on

1
1

Revision note
1MYN691003-102(A3)REV01
125x100x9999
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Top/Left

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
100x75x9999

2
-XX1 -XX2
2

-1CR1A

Date
75x50x1800
+A Left side

-LIU

RESTRICTED AREA

Name

3
3

Prepared
Approved

3100053172
26.05.2014
RESTRICTED AREA

4
4

75x50x1800
Top/Left Top/Left Top/Left Top/Left Top/Left Top/Left Top/Left Top/Left
1

Mokokoulou Substation
1

E
1

2
2

1
1
1

2
-DS

-FS09
E
2 -FS17
2

E
-FS01
E

1
1
1
1

E
2

E
2
2

3
3

E
E
3
3

-X02

2
2
E

E
4
4

4
4
E
5
5

E
-SR

E
6
6

3
3
1

E
1

E
7
7

5
5

-X01
E

E
8
8
1

4
4
E

-FS18
E
9
9

-FS10
-X04

6
6

40x40x500
40x40x500
40x40x500
40x40x500
40x40x500
40x40x500

40x40x500
40x40x500
40x40x500

-FS02

5
5
E
E

7
7
E

E
E

6
6
E
E

8
8
1

E
1

E
2

7
7
E

E
1

9
9
E

-FS11

E
-FS19
E

8
8
E
E

-FS03
10
10
E

E
9
9
E

E
E

11
11

E
E

10
10
1

E
2

12
12
E

E
E
1

11
11
E

-FS12
1

E
2

13
13

E
E
-E1

-FS21

12
12
E

-FS04
E

14
14

Project Extension of Mokoulou Substation


E
E

13
13
E
E

15
15
E

E
1

14
14
E

E
E

15
-FS13
15
1
1

E
2
2

E
E

16
16
E

-FS05 -FS22
1
1

1
1

E
E
E

17
17
E

E
2
2

2
2
AFS660

E
E
E

18
18
E
3
3

-FS14
3
3
E

E
1

2
-X13

-NLR
-1CR1A

19
19
-X03
1

E
4
4

E
2

4
4

-FS06
E
E

20
20
E

E
5
5

-FS23
5
5
E

E
E

E
L N PE

21
21
E
6
6

6
6
1

E
2

ETHERNET SWITCH

E
E

22
22
E

E
7
7

7
7
1

-FS15
E
E

23
23
E
8
8

E
1

8
8

-FS07
E

E
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

24
24

-FS24
E
25
25

E
26
26
1

E
1

27
27

-FS16
E

-FS08 -FS25
28
28

E
+B Rear plane

29
29

E
30
30
1

-LK01 -FS26

AHV
Sonam
1

5
-LK02 -LK03
5

75x50x1800

RESTRICTED AREA

ABB
100x75x999

Inside view
Cubicle layout

6
6

Title 110kV Control & Relay Panel

ABB

RESTRICTED AREA
Doc. no.

>+CC01
75x75x9999
Resp. dept.

E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E

120 119 118 117 116 115 114 113 112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97 96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 185 184 183 182 181 180 179 178 177 176 175 174 173 172 171 170 169 168 167 166 165 164 163 162 161 160 159 158 157 156 155 154 153 152 151 150 149 148 147 146 145 144 143 142 141 140 139 138 137 136 135 134 133 132 131 130 129 128 127 126 125 124 123 122 121 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Top/Left

120 119 118 117 116 115 114 113 112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97 96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 185 184 183 182 181 180 179 178 177 176 175 174 173 172 171 170 169 168 167 166 165 164 163 162 161 160 159 158 157 156 155 154 153 152 151 150 149 148 147 146 145 144 143 142 141 140 139 138 137 136 135 134 133 132 131 130 129 128 127 126 125 124 123 122 121 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
7
7

-X04 -52X04 -89X04


-C3
>+CC01

125x100x9999
DCC

-MCB01
2
1
3

16A
+C Right side

Doc. kind. Assembly drawing


N

ELU
PE
-A01.01

P
1
2

YN1M302310-AAB
-S1

Ref.Des.

00- Rev. ind.

8
8

+1A
=1R

Sheet
n. sheet
Language
14
21
en
F
A

E
D
C
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

A A

TERMINAL BLOCK DESIGNATION FOR


EXTERNAL WIRING TERMINAL BLOCKS SYMBOL LIST

X01 CT CIRCUITS NON DISCONNECTING TB


B MCB B
X02 PT CIRCUITS DIS CONNECTING TB

X03 DC/AC INCOMING CIRCUITS CT/PT JUNCTION BOX TERMINAL


FUSE
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

X04 CONTROL CIRCUITS BREAKER TERMINAL LINK

ISOLATOR TERMINAL
RELAY COIL

C MARSHALLING KIOSK TB C

REVERSE FLAG
TERMINAL BLOCK DESIGNATION FOR PLCC TERMINALS
INTERPANEL BUS WIRING

X11 CT CIRCUITS ACDB/DCDB TERMINALS MANUAL RESET FLAG


C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

X12 PT CIRCUITS
PUSH BUTTON ON CONTACT

X13 DC/AC INCOMING CIRCUITS


D NO CONTACT D

X14 CONTROL CIRCUITS


NC CONTACT

CURRENT TRANSFORMER

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation List of symbols Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 21


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 22
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
© Copyright 2010 ABB

110kV MAIN BUS


A A

101-89A
ISO
101-89AE

B B
101-52CB

RET650
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

P1
87T DR
101-CT CORE-1
CTR:100/1A
\\10.140.6.9\PowerSystems\PS-SAS\Engineering\01 CRP PROJECTS\Sonam\19.Mokoulou Substation\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

64R ER
CL:PS
REC670
101-CT CORE-2 50/51 50/51N 67 DR
CTR:100/1A FROM EXISTING BUS PT

C CL:5P20 C
50LBB 67N ER
20VA
101-CT CORE-3
FROM EXISTING BUS PT
CTR:100/1A ASS A MFM
CL:0.2
20VA 30AB 30CD 30EF 80 95 86
101-CT CORE-4 SPARE
CTR:100/1A
CL:5P20
P2

101-LA
D D
64R
101-HV BCT
CTR:100/1A
CL:PS 101-NCT
CTR:100/1A
CL:PS
POWER TRFR-1
12.5/15 MVA
ONAN/ONAF
Z=10%
110/33kV, YNd11

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Single Line Diagram Resp. dept. - Rev. ind. 00 Language en
Mokokoulou Substation
Print: 6/9/2014

Sheet 22
Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 23
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
REC670

A A

89AE E/S OPEN


& 89A ISOLATOR I/L OK
52CB OPEN

B BUS E/S IF ANY B


We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

89A ISO CLOSED


C C
TRIP COIL-1 HEALTHY

TRIP COIL-2 HEALTHY & 52 CB INTERLOCK OK

86A & B TRIP RELAY RESET


C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

CB SPRING CHARGED

SF6 GAS PRESSURE OK


D D

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Control Logics Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 23


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 24
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

A A

TRANSFORMER PROTECTION

HV-3PH GRP-B MASTER TRIP RELAY


HV-3PH GRP-A MASTER TRIP RELAY

BREAKER FAIL PROTECTION


B B
PROTECTION FUNCTION Remark

TO HV CB TC-1

TO HV CB TC-2

CLOSE HV CB
OUTPUT

GROUP
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

DIFFERENTIAL PROTECTION (87T) 3 PH IP A RET 650

OVERFLUXING PROTECTION 3 PH IP
A RET 650
C C
3 PH IP A REC 670
DIR. O/C & E/F PROTECTION (67/67N)

3 PH IP A RET 650
HV REF PROTECTION (64R)

3Ph TRIP RELAY_LBB PROTN IP TP TP RS RXMVB2

3 PH IP
TRAFO TROUBLE TRIP IP A
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

TRAFO TROUBLE ALARM 3 PH A

GRP-A MASTER TRIP RELAY 3 PH IP TP TP RS A RXMVB4


D D

TP INDICATES TRIP FROM PROTECTION FUNCTION. INDICATES INITIATION FROM PROTECTION FUNCTION. INDICATES RESET STATUS FOR CB CLOSING.
IP RS

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Trip Logic Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 24


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 25
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

+DCDB +1A
A DC Source-1 A

-X03 -FS01
1 J1 1 2 #5.1
/26.A2
-FS03:1
110V DC +ve 16A
-X03 -FS02
2 J2 1 2 #6.2
/26.B2
-FS04:1
-ve 16A
-X13
1

B B
-X13
2 -D29.155.101
80A
TSR

11 13
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

12 21
/25.E3

C C
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

+1A

D D

-D29.155.101
80A
TSR

11
* /25.C5 12

21

13

E 15 16 E
17
25 26
27

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation DC Distribution Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 25


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 26
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A A

-FS03
#5.1 1 2 K101.1
/25.A7 /30.A1
-FS01:2 -D29.101.101:1A
6A TO BAY CONTROL UNIT-REC670
-FS04
#6.2 1 2 K102.2
/25.B7 /30.A1
-FS02:2 -D29.101.101:18A
6A

B -FS05 B
1 2 K201.1
/57.B3
-XX1:7
6A TO GRP-A TRIP RELAY CIRCUIT
-FS06
1 2 K202.2
/57.A8
-D29.131.101:18
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

6A

-FS07
1 2 K51.1
/59.A5
-52X04:10
10A TO TRIP COIL-I CIRCUIT
-FS08
1 2 K52.2
/59.B5
C 10A
-52X04:11 C

-FS09
1 2 K401.1
/28.B2
-D03.02:L
2A TO METERING CIRCUIT
-FS10
1 2 K402.2
/28.B2
-D03.02:N
2A
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-FS11
1 2 K301.3
/48.A1
-D29.113.101:1B
D 6A D
-FS12 TO PROTN RELAY-RET650
1 2 K302.4
/48.A1
-D29.113.101:18B
6A

-FS13
1 2 K501.1
/58.A3
-D33.101.307:16
6A TO 3PH TRIP RELAY CIRCUIT
-FS14 FOR LBB PROTN
1 2 K502.2
/58.A8
-D33.101.301:14
6A

E E
-FS15
1 2 K601.3
/56.A4
-X04:130
10A TO TRAFO TROUBLE CIRCUIT
-FS16 AND ISOL. CONTROL CKT
1 2 K602.4
/56.A2
-D33.119.101:12
10A

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation DC Distribution Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 26


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 27
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

+ACDB +1A
A Ac Source -E1 A
-MCB01 Lamp
CFL
-X03 -DS
3 H1 2 1 H3 1 2 H4 L

230V 1PH 50HZ AC /27.D3

CUBICLE & SOCKET -X03


POWER SUPPLY 4 H2 4 3 H5
/27.E3 N
PE

B -X13 B
3

-X13
4 -A01.01
Outlet
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

SW

AC
3

C N C

H6 PE

-TH
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

Thermostat
TH

-S1 <ϑ
1 2 H7 1
2
D D

-MCB01

H8
-B37
2 1 Heating
/27.A4 SPHT
4 3
/27.B4
1

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation AC Distribution Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 27


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 28
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A -D03.01 A

Rish Master 3430


3Ph, 3Ele, 4W

K401.1 13 P/+
/26.C5
-FS09:2

K402.2 14 N/-
/26.D5
-FS10:2

B B
-D03.02
1
AMM-D-DM_Var1 Current R-ph
Direct meter /29.B2
3
#I1 CT: 0–1A
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

L L/+ 4
Current Y-ph
/29.B2
N N/- 6
#I2 CT: 0–1A

7
Current B-ph
I1
Current /29.C2
9
Range:0-100A /28.E2 #I3 CT: 0–1A
C I2 C
2
Voltage R-ph /29.D2

#U1 VT:

5
Voltage Y-ph /29.D2

#U2 VT:
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

8
Voltage B-ph
/29.E2
11
#U3 VT:
D D

-D03.02 -ASS -D29.101.101:4A


/32.B5
D16.4
4 4-pos. contacts with 0 position

I1 A1 R
Current
Y D36.5
Range:0-100A /32.B5
I2 A2 B -D29.101.101:6A
/28.C4
E E
D56.6
/32.C5
-D29.101.101:8A
#343.1
-X01:4
/29.C5

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Metering Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 28


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 29
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A
+CT JB +CT CORE
A A
CT CORE-3
CT RATIO:100/1A
-D03.01 -D37.01 CL:0.2
BURDEN:20 VA
ISF<5
-X01 P1 P1 P1
1 1 1 1
D11 D10
Current R-ph

3 2 3S1
D13
#I1 CT: 0–1A /28.B8

3 3S2
D12
B B
/62.B8
-X01
4 4 4 2 3S1
D31 D30
Current Y-ph

6 5 3S2
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

D33
#I2 CT: 0–1A /28.C8
-X01
6 3
D32 D50
3S1
/62.B8
-X01
7 7 7 4 3S2
D51
Current B-ph

-D03.02:I2, -ASS:A2
-D29.101.101:7A

-D29.101.101:5A

-D29.101.101:3A
9 8
#I3 CT: 0–1A /28.C8
D53 -X01
C 5 P2 P2 P2
C

#343.1
9

D13.1
D53.3

D33.2
D52
/62.C8

/32.B5

/32.B5

/32.B5

/28.E3
-FS21 -X02
2 R1 R2 1 2 1
E13 E12 E11
Voltage R-ph
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

/62.C8 2A

#U1 VT: /28.C8

From exsisting Bus PT


-FS22 -X02
Y1 Y2

metering core
5 E33 E32 1 2 E31 2
D Voltage Y-ph D
/62.C8 2A

#U2 VT: /28.C8

-FS23 -X02
8 B1 B2 1 2 3
E53 E52 E51
Voltage B-ph
/62.C8 2A
11 -LK02 -X02
#U3 VT: /28.D8 N1 N2
E73 E72 1 2 E71 4

/62.C8

-D29.101.101:10A

-D29.101.101:11A

-D29.101.101:12A

-D29.101.101:13A
E E
E12.1

E32.2

E52.3

E72.4
/32.C5

/32.D5

/32.D5

/32.D5

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Metering Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 29


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 30
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

-D07.01 >-D07.01
-D05.01 -D07.01

/26.B5

/26.A5
A Power supply module 1MRK002239-BB Communication interface module 1MRK002266-AA Indication HMI 1MRK000008-PB A
-D07.01 PSM OEM LED

K101.1
-FS04:2
K102.2

-FS03:2
90-250VDC
Power supply module
PSM -X11 -X311
-D29.101.101 -D29.107.101 -X11 4 + A Tx
1A 1B K103 1A 1B K104 4 +
/30.B6 IEC61850
/62.B2 -D29.107.101 5 - B Rx
/30.B3
18A 18B K105 18A 18B K106 5 -
90-250VDC
/62.C2 PE -X11
90-250VDC
PE 2
/30.B4
B B
3 >-D07.01 -X311
/51.D4
Tx A
-89X04:1

Relay fail
K102.1

K101.2
-XX1:1

1
IEC61850
Rx B 1 89A ISOL. OPEN
/30.B5
/34.B3

/34.A5
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

2 89A ISOL. CLOSE

3 89AE E/S. OPEN

4 89AE E/S CLOSE

5 52CB OPEN

6 52CB CLOSE
C C
7 DIR. O/C PROTN OPTD

8 DIR. E/F PROTN OPTD

9 TC-1 FAULTY

10 TC-2 FAULTY

11 86A OPTD
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

12 86B OPTD

13
D - Dir. O/C & E/F protn (67/67N)
14 D
- Disturbance Recorder(RDRE)
- Event Recorder (RDRE)
- LBB Protn 15
- Residual o/c protection &
Local HMI
-Integrated HMI with 4 line display
-15 freely configurable LEDs O: Open
-Settings and disturbance Information
-Front port for communication I: Closed
with indication
C: Cancel/Clear

E: Enter/Select/Execute

L/R: Local/Remote/off
E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Power Supply Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 30


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 31
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +CT JB +CT CORE

A -D07.01 CT CORE-1
A
Dir. o/c & e/f Protn-REC670 CT RATIO:100/1A
CL:PS
Vk=150 P1 P1 P1
-D29.107.101 -X01 Rct=2
-X401 3A C111 6
+ 1 3B 1S1
C112
Current R-ph
Protection 1S2
- 2
P40#AI.01 CT: 1A /44.B2
-D29.107.101 -X01
-X401 4A C131 7
+ 3 4B 1S1
C132
B Current Y-ph B
Protection 1S2
- 4
P40#AI.02 CT: 1A /44.B2
-D29.107.101 -X01
-X401 5A C151 8
+ 5 5B 1S1
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

C152
Current B-ph
Protection 1S2
- 6 -D29.107.101 -X01
P40#AI.03 CT: 1A /44.B2
6A C171 9
C172 6B P2 P2 P2
-X01
10

C C

-X401 -D29.107.101 -FS17 -X02


+ 13 E113 7B 7A E112 1 2 E111 5
Voltage R-ph
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

Protection 2A
- 14
P40#AI.07 VT: 0-340V /44.D2

From existing bus PT


-X401 -D29.107.101 -FS18 -X02
+ 15 E133 8B 8A E132 1 2 E131 6
D Voltage Y-ph D

Protn core
Protection 2A
- 16
P40#AI.08 VT: 0-340V /44.D2

-X401 -D29.107.101 -FS19 -X02


+ 17 E153 9B 9A E152 1 2 E151 7
Voltage B-ph
Protection 2A
- 18
P40#AI.09 VT: 0-340V /44.D2
-D29.107.101 -LK01 -X02
E173 10B 10A E172 1 2 E171 8

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Analog Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 31


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 32
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

+1A
A A

-D07.01
Metering-REC670

-D29.101.101
-X401 3A D13.1
/29.C5
+ 7 D14 3B /62.B2 -D37.01:2
Current R-ph
4A D16.4
Metering /28.D5
- 8 D15 4B /62.B2 -ASS:R
P40#AI.04 CT: 1A /44.C2

-X401 5A D33.2
B /29.C5 B
+ 9 D34 5B /62.B2 -D37.01:5
Current Y-ph
6A D36.5
Metering /28.E5
- 10 D35 6B /62.B2 -ASS:Y
P40#AI.05 CT: 1A /44.C2

7A
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X401 D53.3
/29.C4
+ 11 D54 7B /62.B2 -D37.01:8
Current B-ph
8A D56.6
Metering /28.E5
- 12 D55 8B /62.C2 -ASS:B
P40#AI.06 CT: 1A /44.C2

C C

-X401 -D29.101.101
+ 19 E18 10B 10A E12.1
Voltage R-ph /29.E4
/62.C2 -FS21:1, -D37.01:R2
Metering
- 20
P40#AI.10 VT: 0-340V /44.D2
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X401 -D29.101.101
+ 21 E38 11B 11A E32.2
Voltage Y-ph /29.E5
/62.C2 -FS22:1, -D37.01:Y2
Metering
- 22
P40#AI.11 VT: 0-340V /44.E2
D D
-X401 -D29.101.101
+ 23 E58 12B 12A E52.3
Voltage B-ph /29.E5
/62.C2 -FS23:1, -D37.01:B2
Metering
- 24
P40#AI.12 VT: 0-340V /44.E2
-D29.101.101
E78 13B 13A E72.4
/29.E5
/62.C2 -LK02:1, -D37.01:N2

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Analog Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 32


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 33
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A A
-D07.01
Dir. o/c & e/f Protn-REC670

-X401 -D29.107.101 -FS24 -X02


+ 13 E213 11B 11A 1 2 E211 9
Voltage R-ph
2A
- 14
P40#AI.07 VT: 0-340V /47.C3
B B
-X401 -D29.107.101 -FS25 -X02 FROM 33kV Bus PT
+ 15 E233 12B 12A E232 1 2 E231 10 Metering core
Voltage Y-ph
2A core-1
- 16 CL:0.2
P40#AI.08 VT: 0-340V /47.D3
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X401 -D29.107.101 -FS26 -X02


+ 17 E253 13B 13A E252 1 2 E251 11
Voltage B-ph
2A
- 18
P40#AI.09 VT: 0-340V /47.D3
-D29.107.101 -LK03 -X02
E273 14B 14A E272 1 2 E271 12

C C
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

D D

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Analog Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 33


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 34
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

/30.B1
A A

/30.B1

K101.2
-D29.101.101:1A
+89A ISOL

K102.1
-D29.101.101:18A
-D07.01 -89X04
Dir. o/c & e/f Protn-REC670 1

-X31 -89X04
+ 1 K107 2
89A Isol. Open
-XX1
- 2 1 -89X04
B P3#BI.01 110-125VDC /44.B4 B
3

-X31
+ 3
89A Isol. Close

- 4 +52CB
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

P3#BI.02 110-125VDC /44.B4


-52X04
-X31 1
+ 5 K108
CB open
-52X04 -X3 -X3
- 6 2 101 102
P3#BI.03 110-125VDC /44.B4

-X31 -52X04 -X3 -X3


C + 7 K109 3 103 104 C
CB close

- 8
P3#BI.04 110-125VDC /44.C4

-X31 -D29.119.101
+ 9 315 316
86A Optd
/62.C3
- 10 86A
P3#BI.05 110-125VDC /44.C4
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X31
+ 11
Spare

- 12
D P3#BI.06 110-125VDC /44.C4 D
-D29.137.101
-X31 15 16
+ 13 K110 17 /62.E4
86A Trip Relay faulty
95/86A
- 14
P3#BI.07 110-125VDC /44.D4
-D33.113.101
-X31 15 16
+ 15 K111 17 /62.E6
86B Trip Relay faulty
95/50LBB
- 16
P3#BI.08 110-125VDC /44.D4

E E
K102.19
-XX1:2
/35.B3

K101.4
-X04:1
/35.B5

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 34


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 35
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A A

/34.E3

/34.E5
-XX1:1
K102.19

-D33.113.101:16
K101.4
-D07.01 -X04
Dir. o/c & e/f Protn-REC670 1

-X32 -X04
+ 1 K112 2
Spare
B -XX1 B
- 2 2
P3#BI.09 110-125VDC /44.B6
-D29.143.101
-X32 25 26
+ 3 K113 27 /62.E2
TC-I Faulty
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

195
- 4
P3#BI.10 110-125VDC /44.B6
-D29.143.301
-X32 25 26
+ 5 K114 27 /62.E3
TC-II Faulty
-D18.01 295
- 6 -X309 >-D17.01
P3#BI.11 110-125VDC /44.B6
3
C -X32 C
+ 7 K115 2 +89AE E/S
RET650 Relay Fail Self-supervision
Internal fail -89X04
- 8 1 4
P3#BI.12 110-125VDC /44.C6 /48.B5 P1#IRF

-X32 -89X04
+ 9 K116 5
89AE Earthswitch open
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

- 10 -89X04
P3#BI.13 110-125VDC /44.C6
6

-X32
+ 11 K117 +TRAFO
89AE Earthswitch Close
D -X04 -X1 -X1 D
- 12 3 729 30
P3#BI.14 110-125VDC /44.C6

-X32 -X04
+ 13 K118 4
Spare
-X04 -X1 -X1
- 14 5 31 32
P3#BI.15 110-125VDC /44.D6

-X32 -X04
+ 15 K119 6
Spare

- 16
P3#BI.16 110-125VDC /44.D6

-52X04:4
E E

K101.6
K102.20
-XX1:3

/36.A5
/36.A3

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 35


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 36
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

/35.E3

/35.E5
A A
+52CB

-XX1:2
K102.20

-X04:5
K101.6
-52X04
-D07.01 4
Dir. o/c & e/f Protn-REC670

-X51 -52X04 -X1 CB Spring Charged Indication


-X1
+ 1 K120 5 31 32
CB Spring Charged Indication
-XX1
- 2 3
B P5#BI.01 110-125VDC /44.B8 B

-X51 -52X04 -X1 Remote Indication -X1


+ 3 K121 6 33 34
Remote Indication

- 4
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

P5#BI.02 110-125VDC /44.B8

-X51 -52X04 -X1 SF6 Pressure Blocking


-X1
+ 5 K122 7 29 30
SF6 Pressure Blocking

- 6
P5#BI.03 110-125VDC /44.B8

-X51 -52X04 -X1 Dc Failure Indication


-X1
C + 7 K123 8 44 45 C
Dc Failure Indication

- 8
P5#BI.04 110-125VDC /44.C8

-X51 -52X04 -X1 SF6 Gas replenishment


-X1 alarm
+ 9 K124 9 18 19
SF6 Gas replenishment alarm

- 10
P5#BI.05 110-125VDC /44.C8
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

+TRAFO
-X51 -X04 -X2 -X2
+ 11 K125 7 7 8
Buchholz alarm

- 12 -X04
D P5#BI.06 110-125VDC /44.C8 D
8

-X51 -D33.119.101
+ 13 K126 23 24
OLTC PRV Trip
/56.B8
- 14
P5#BI.07 110-125VDC /44.D8

-X51 -D33.119.301
+ 15 K127 13 14
OTI Trip
/56.B8
- 16
P5#BI.08 110-125VDC /44.D8

E E
K102.21

K101.20
-XX1:4

-X04:9
/37.A3

/37.A5

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 36


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 37
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

/36.E3

/36.E5
A A

K102.21
-XX1:3

-D33.119.301:14
K101.20
+TRAFO
-D07.01
Dir. o/c & e/f Protn-REC670 -X04 -X2 -X2
9 15 16

-X52 -X04
+ 1 K128 10
LV winding alarm
-XX1
- 2 4
B P5#BI.09 110-125VDC /45.B3 B

-X52 -D33.119.301
+ 3 K129 23 24
OLTC OSR Trip
/56.B8 -X04 -X2 -X2
- 4 11 11 12
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

P5#BI.10 110-125VDC /45.B3

-X52 -X04
+ 5 K130 12
Oil Temp alarm

- 6 -X04
P5#BI.11 110-125VDC /45.B3
13

-X52 -X04
C + 7 K131 14 C
Spare

- 8 -X04
P5#BI.12 110-125VDC /45.C3
15

-X52 -X04
+ 9 16
Spare
-X04
- 10 17
P5#BI.13 110-125VDC /45.C3
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X52 -X04
+ 11 K132 18
Spare
-X04
- 12 19
D P5#BI.14 110-125VDC /45.C3 D

-X52 -X04
+ 13 K133 20
Spare

- 14 -X04
P5#BI.15 110-125VDC /45.D3
21

-X52 -X04
+ 15 22
Spare

- 16
P5#BI.16 110-125VDC /45.D3

E E
K101.8
K102.7
-XX1:5

/38.A5
/38.B3

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 37


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 38
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +RTCC

A **Customer to identify the terminal numbers. A

/37.E5
/37.E3

-X04:21
K101.8
-X04

-XX1:4
K102.7
-D07.01 23 +ve
Dir. o/c & e/f Protn-REC670

-X61 -X04
+ 1 K134 24 Master
Trafo Master
-XX1
- 2 5
P6#BI.01 110-125VDC /46.B2
B B
-X61 -X04
+ 3 K135 25 Follower
Trafo follower

- 4
P6#BI.02 110-125VDC /46.B2
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X61 -X04
+ 5 26 Independent
Independent

- 6
P6#BI.03 110-125VDC /46.B2
-A/M
-X61 1P1
+ 7 K136 1P2
TC auto
C /62.B7 C
- 8 Auto
P6#BI.04 110-125VDC /46.B2
AUTO/MANUAL
-A/M
-X61
+ 9 K137 1P4
Tc manual
/62.B7 1P3
- 10 Manual
P6#BI.05 110-125VDC /46.C2
AUTO/MANUAL
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X61 -PB01
+ 11 K138 3(1) 4(1)
Emergency stop

- 12 Emergency stop
P6#BI.06 110-125VDC /46.C2
D +RTCC D
-X61 -X04
+ 13 K139 27 Remote
Remote

- 14
P6#BI.07 110-125VDC /46.C2

-X61 -X04
+ 15 28 Manual
Local

- 16
P6#BI.08 110-125VDC /46.D2
-X04
29 +ve

E E
K101.21
-X04:30
K102.3
-XX1:6
/39.A3

/39.A5

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 38


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 39
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +RTCC

/38.E3

/38.E5
A ** A
Customer to identify these terminals.

K101.21
-XX1:5
K102.3

-X04:29
-X04
-D07.01 30
Dir. o/c & e/f Protn-REC670

-X62 -X04 TC main supply undervoltage


+ 1 K140 31
TC main supply undervoltage
-XX1
- 2 6 -X04
P6#BI.09 110-125VDC /46.B4
32
B B
-X62 -X04 TC ac motor supply fail
+ 3 K141 33
TC ac motor supply fail

- 4 -X04
P6#BI.10 110-125VDC /46.B4
34
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X62 -X04 Tap change in progress


+ 5 K142 35
Tap change in progress
-X04
- 6 36
P6#BI.11 110-125VDC /46.B4

TC control supply fail


-X62 -X04
+ 7 K143 37
TC control supply fail
C -X04 C
- 8 38
P6#BI.12 110-125VDC /46.B4

Tap change error


-X62 -X04
+ 9 39
Tap change error

- 10 -X04
P6#BI.13 110-125VDC /46.C4
40
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X62 -X04 TC high Indication


+ 11 K144 41
TC high Indication

- 12 -X04
P6#BI.14 110-125VDC /46.C4
42
D D
-X62 -X04 TC low indication
+ 13 K145 43
TC low indication

- 14 -X04
P6#BI.15 110-125VDC /46.C4
44

-X62 -X04
+ 15 45
Spare

- 16
P6#BI.16 110-125VDC /46.D4

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 39


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 40
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

-D07.01
A Dir. o/c & e/f Protn-REC670 A
-X71 -X04
5 U1 46
Spare
-X04
4 U2 47
P7#BO.03 /46.B6

Spare
-X71 -X04
6 U3 48
P7#BO.04 /46.C6
B B
-X71 -X04
8 U4 49
Spare
-X04
7 U5 50
P7#BO.05 /46.C6
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Spare
-X71 -X04
9 U6 51
P7#BO.06 /46.C6

-X71 -X04
11 U7 52
Spare
C -X04 C
10 U8 53
P7#BO.07 /46.C6

Spare
-X71 -X04
12 U9 54
P7#BO.08 /46.D6
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X71 -X04
14 U10 55
Spare
-X04
13 U11 56
P7#BO.09 /46.D6
D D

Spare
-X71 -X04
15 U12 57
P7#BO.10 /46.D6

-X71 -X04
17 U13 58
Spare
-X04
16 U14 59
P7#BO.11 /46.E6

E Spare E
-X71 -X04
18 U15 60
P7#BO.12 /46.E6

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary output Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 40


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 41
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +BMK +89A ISOL

A A
-89X04
K601.20 7 +VE DC SUPPLY
/56.D4
-X04:130

-89X04
K602.19 8
/56.D2 -VE DC SUPPLY
-D33.125.101:22

-89X04
-D07.01 K608 9 COMMON
Dir. o/c & e/f Protn-REC670
B B
-X41 -89X04
2 K609 10 REMOTE OPEN
89A Isol. Open Command
-89X04
1 K610 11 REMOTE CLOSE
P4#BO.01 /45.B4
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

89A Isol. Close Command


-X41
3
P4#BO.02 /45.B4

C +89A ISOL C

-X41 -89X04
5 K611 12
89A Isol. I/L Ok
-89X04 I/L OK
4 K612 13
P4#BO.03 /45.B4
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

Spare
-X41 -89X04
6 K613 14
P4#BO.04 /45.C4
+89AE E/S
D D

-X42 -89X04
14 K614 15
E/S I/L Ok
-89X04 I/L OK
13 K615 16
P4#BO.21 /45.D6

Spare
-X42 -89X04
15 K616 17
P4#BO.22 /45.E6

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Isolator Control Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 41


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 42
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

A A
+1A +RTCC

** Customer to identify the terminals.


-D07.01
Dir. o/c & e/f Protn-REC670

-X81 -X04
+ 7 K146 61
Tap Position Indicator D
-X04
A
- 8 62 Tap Position Indicator
K147
P8#MI.01 0-20mA /45.B8
B B
-X81 -X04
+ 9 K148 63
Trafo Oil Temperature D
-X04
A
- 10 64 Trafo Oil Temperature
K149
P8#MI.02 0-20mA /45.B8
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X81 -X04
+ 11 K150 65
OLTC Oil temperature D
-X04 OLTC Oil temperature
A
- 12 K151 66
P8#MI.03 0-20mA /45.B8

-X81 -X04
+ 13 K152 67
Winding Temperature
C D
-X04 Winding Temperature
C
A
- 14 K153 68
P8#MI.04 0-20mA /45.C8

-X81 -X04
+ 15 U16 69
Spare D
-X04
A
- 16 U17 70
P8#MI.05 0-20mA /45.C8
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X81 -X04
+ 17 U18 71
Spare D
-X04
A
- 18 U19 72
P8#MI.06 0-20mA /45.C8
D D

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation mA Input Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 42


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 43
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A -D07.01 A
Dir. o/c & e/f Protn-REC670

-X42 -X04
17 U20 73
Spare
-X04
16 U21 74
P4#BO.23 /45.E6

Spare
-X42 -X04 +RTCC
B B
18 U22 75
P4#BO.24 /45.E6

-X04
157
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X71 -A/M
2 -X04
Tap Lower command
2P4 158
1 2P3 /62.B7 -A/M
P7#BO.01 /46.B6 Manual 2P1
AUTO/MANUAL 2P2
/62.B7
Tap raise command Auto
-X71 -A/M -X04
C 3 3P2 AUTO/MANUAL 159 C
P7#BO.02 /46.B6
3P1 /62.B7
Off
Manual

AUTO/MANUAL -A/M
3P3
3P4
/62.C7
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

Auto
Off
AUTO/MANUAL
+RTCC

D D
-X04
76

-PB01 -X04
3(2) 4(2) 77

Emergency stop

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Output Circuit_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 43


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 44
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A -D07.01 -D07.01 -D07.01 -D07.01 A


Transformer input module 1MRK002247-AG Binary input module 1MRK000508-BD Binary input module 1MRK000508-BD Binary input module 1MRK000508-BD
TRM BIM BIM BIM
1A, 0-340V, 50/60Hz 110-125VDC, 50ma 110-125VDC, 50ma 110-125VDC, 50ma
-X401 -X31 -X32 -X51
+ 1 + 1 + 1 + 1
Current R-ph 89A Isol. Open Spare CB Spring Charged Indication
Protection /31.B2 /34.B2 /35.B2 /36.B2
- 2 - 2 - 2 - 2
P40#AI.01 CT: 1A P3#BI.01 110-125VDC P3#BI.09 110-125VDC P5#BI.01 110-125VDC

+ 3 + 3 + 3 + 3
Current Y-ph 89A Isol. Close TC-I Faulty Remote Indication
Protection /31.B2 /34.B2 /35.B2 /36.B2
- 4 - 4 - 4 - 4
B P40#AI.02 CT: 1A P3#BI.02 110-125VDC P3#BI.10 110-125VDC P5#BI.02 110-125VDC B
+ 5 + 5 + 5 + 5
Current B-ph CB open TC-II Faulty SF6 Pressure Blocking
Protection /31.C2 /34.C2 /35.C2 /36.C2
- 6 - 6 - 6 - 6
P40#AI.03 CT: 1A P3#BI.03 110-125VDC P3#BI.11 110-125VDC P5#BI.03 110-125VDC
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

+ 7 + 7 + 7 + 7
Current R-ph CB close RET650 Relay Fail Dc Failure Indication
Metering /32.B2 /34.C2 /35.C2 /36.C2
- 8 - 8 - 8 - 8
P40#AI.04 CT: 1A P3#BI.04 110-125VDC P3#BI.12 110-125VDC P5#BI.04 110-125VDC

+ 9 + 9 + 9 + 9
Current Y-ph 86A Optd 89AE Earthswitch open SF6 Gas replenishment alarm
Metering /32.B2 /34.D2 /35.D2 /36.D2
- 10 - 10 - 10 - 10
P40#AI.05 CT: 1A P3#BI.05 110-125VDC P3#BI.13 110-125VDC P5#BI.05 110-125VDC
C C
+ 11 + 11 + 11 + 11
Current B-ph Spare 89AE Earthswitch Close Buchholz alarm
Metering /32.C2 /34.D2 /35.D2 /36.D2
- 12 - 12 - 12 - 12
P40#AI.06 CT: 1A P3#BI.06 110-125VDC P3#BI.14 110-125VDC P5#BI.06 110-125VDC

+ 13 + 13 + 13 + 13
Voltage R-ph 86A Trip Relay faulty Spare OLTC PRV Trip
Protection /31.D2 /34.D2 /35.D2 /36.D2
- 14 - 14 - 14 - 14
P40#AI.07 VT: 0-340V P3#BI.07 110-125VDC P3#BI.15 110-125VDC P5#BI.07 110-125VDC
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

+ 15 + 15 + 15 + 15
Voltage Y-ph 86B Trip Relay faulty Spare OTI Trip
Protection /31.D2 /34.E2 /35.E2 /36.E2
- 16 - 16 - 16 - 16
P40#AI.08 VT: 0-340V P3#BI.08 110-125VDC P3#BI.16 110-125VDC P5#BI.08 110-125VDC
D D
+ 17
Voltage B-ph
Protection /31.E2
- 18
P40#AI.09 VT: 0-340V

+ 19
Voltage R-ph
Metering /32.D2
- 20
P40#AI.10 VT: 0-340V

+ 21
Voltage Y-ph
Metering /32.D2
- 22
P40#AI.11 VT: 0-340V
E + 23
E
Voltage B-ph
Metering /32.D2
- 24
P40#AI.12 VT: 0-340V

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Master Blocks_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 44


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 45
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A -D07.01 -D07.01 -D07.01 -D07.01 A


Binary input module 1MRK000508-BD Binary output module 1MRK000614-AB Binary output module 1MRK000614-AB mA input module 1MRK000284-AB
BIM BOM BOM MIM
110-125VDC, 50ma 0-20, 4-20, ±20mA
-X52 -X41 -X42 -X81
+ 1 2 2 + 7
LV winding alarm 89A Isol. Open Command Dir.o/c & e/f Protn optd Tap Position Indicator
D
/37.B2 /41.B2 GRP-A /57.B5 /42.B2
- 2 1 1 A - 8
P5#BI.09 110-125VDC P4#BO.01 P4#BO.13 P8#MI.01 0-20mA

+ 3 + 9
OLTC OSR Trip 89A Isol. Close Command Spare Trafo Oil Temperature
D
/37.B2 /42.B2
- 4 3 3 A - 10
B P5#BI.10 110-125VDC P4#BO.02 /41.C2 P4#BO.14 P8#MI.02 0-20mA B
+ 5 5 5 + 11
Oil Temp alarm 89A Isol. I/L Ok Spare OLTC Oil temperature
D
/37.C2 /41.C2 /42.C2
- 6 4 4 A - 12
P5#BI.11 110-125VDC P4#BO.03 P4#BO.15 P8#MI.03 0-20mA
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

+ 7 + 13
Spare Spare Spare Winding Temperature
D
/37.C2 /42.C2
- 8 6 6 A - 14
P5#BI.12 110-125VDC P4#BO.04 /41.D2 P4#BO.16 P8#MI.04 0-20mA

+ 9 8 8 + 15
Spare Trip TC-II 86A Reset command Spare
D
/37.D2 /60.C3 /57.A4 /42.D2
- 10 7 7 A - 16
P5#BI.13 110-125VDC P4#BO.05 P4#BO.17 P8#MI.05 0-20mA
C C
+ 11 + 17
Spare Spare Spare Spare
D
/37.D2 /42.D2
- 12 9 9 A - 18
P5#BI.14 110-125VDC P4#BO.06 P4#BO.18 P8#MI.06 0-20mA

+ 13 11 11
Spare Trip TC-I Spare
/37.D2 /59.C3
- 14 10 10
P5#BI.15 110-125VDC P4#BO.07 P4#BO.19
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

+ 15
Spare Spare Spare
/37.E2
- 16 12 12
P5#BI.16 110-125VDC P4#BO.08 P4#BO.20
D D
14 14
CB Close command E/S I/L Ok
/61.D2 /41.D2
13 13
P4#BO.09 P4#BO.21

Synch check ok Spare

15 15
P4#BO.10 /61.D2 P4#BO.22 /41.E2

17 17
LBB Protn Optd Spare
/58.C5 /43.B2
16 16
P4#BO.11 P4#BO.23
E E
Spare Spare

18 18
P4#BO.12 /58.C5 P4#BO.24 /43.B2

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Master Blocks_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 45


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 46
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

-D07.01 -D07.01 -D07.01 -D07.01


A Binary input module 1MRK000508-BD Binary input module 1MRK000508-BD Binary output module 1MRK000614-AB Binary output module 1MRK000614-AB A
BIM BIM BOM BOM
110-125VDC, 50ma 110-125VDC, 50ma
-X61 -X62 -X71 -X72
+ 1 + 1 2 2
Trafo Master TC main supply undervoltage Tap Lower command Spare
/38.B2 /39.B2 /43.C2
- 2 - 2 1 1
P6#BI.01 110-125VDC P6#BI.09 110-125VDC P7#BO.01 P7#BO.13

+ 3 + 3
Trafo follower TC ac motor supply fail Tap raise command Spare
/38.B2 /39.B2
- 4 - 4 3 3
P6#BI.02 110-125VDC P6#BI.10 110-125VDC P7#BO.02 /43.C2 P7#BO.14
B B
+ 5 + 5 5 5
Independent Tap change in progress Spare Spare
/38.C2 /39.C2 /40.B2
- 6 - 6 4 4
P6#BI.03 110-125VDC P6#BI.11 110-125VDC P7#BO.03 P7#BO.15

+ 7 + 7
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

TC auto TC control supply fail Spare Spare


/38.C2 /39.C2
- 8 - 8 6 6
P6#BI.04 110-125VDC P6#BI.12 110-125VDC P7#BO.04 /40.B2 P7#BO.16

+ 9 + 9 8 8
Tc manual Tap change error Spare Spare
/38.D2 /39.D2 /40.B2
- 10 - 10 7 7
P6#BI.05 110-125VDC P6#BI.13 110-125VDC P7#BO.05 P7#BO.17

C + 11 + 11 C
Emergency stop TC high Indication Spare Spare
/38.D2 /39.D2
- 12 - 12 9 9
P6#BI.06 110-125VDC P6#BI.14 110-125VDC P7#BO.06 /40.C2 P7#BO.18

+ 13 + 13 11 11
Remote TC low indication Spare Spare
/38.D2 /39.D2 /40.C2
- 14 - 14 10 10
P6#BI.07 110-125VDC P6#BI.15 110-125VDC P7#BO.07 P7#BO.19
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

+ 15 + 15
Local Spare Spare Spare
/38.E2 /39.E2
- 16 - 16 12 12
P6#BI.08 110-125VDC P6#BI.16 110-125VDC P7#BO.08 /40.D2 P7#BO.20

14 14
D Spare Spare D
/40.D2
13 13
P7#BO.09 P7#BO.21

Spare Spare

15 15
P7#BO.10 /40.D2 P7#BO.22

17 17
Spare Spare
/40.E2
16 16
P7#BO.11 P7#BO.23

E Spare Spare E
18 18
P7#BO.12 /40.E2 P7#BO.24

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Master Blocks_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 46


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 47
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A
-D07.01
A Transformer input module 1MRK002247-AG A
TRM
1A, 0-340V, 50/60Hz
-X401
+ 1
Spare

- 2
P40#AI.01 CT: 1A

+ 3
Spare

- 4
P40#AI.02 CT: 1A
B B
+ 5
Spare

- 6
P40#AI.03 CT: 1A

+ 7
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Spare

- 8
P40#AI.04 CT: 1A

+ 9
Spare

- 10
P40#AI.05 CT: 1A

C + 11 C
Spare

- 12
P40#AI.06 CT: 1A

+ 13
Voltage R-ph
/33.B2
- 14
P40#AI.07 VT: 0-340V
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

+ 15
Voltage Y-ph
/33.B2
- 16
P40#AI.08 VT: 0-340V

+ 17
D Voltage B-ph D
/33.C2
- 18
P40#AI.09 VT: 0-340V

+ 19
Spare

- 20
P40#AI.10 VT: 0-340V

+ 21
Spare

- 22
P40#AI.11 VT: 0-340V

+ 23
E Spare E
- 24
P40#AI.12 VT: 0-340V

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Master Blocks_REC670 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 47


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 48
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

/26.D5

/26.D5
-D17.01 -D17.01
A -D17.01 Power supply module Communication interface module A

K302.4
-FS12:2

K301.3
-FS11:2
PSM COM
Power supply module 110-250VDC, 100-240VAC 24-250VDC
PSM
-D29.113.101 -X410 -X410 Ethernet -X0
1B 1A K303 3 + 3 + RJ45 HMI
Time synchronization module
/62.B2
#HMI
18B 18A K304 1 - 1 - -X4
/48.B2
/62.D2 GNDC 1
110-250VDC 110-250VDC
PE 100-240VAC PE 100-240VAC -X309
/48.B3 3 NC 2

B B
2 IRIG-B- 3
Self-supervision /35.C4 Time synchronisation
K301.11
K302.10

-X04:82

Internal fail
-XX2:1

1 IRIG-B+ 4
P1#IRF #IRIG-B
/51.A3

/51.A5
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

C C

- Differential Protection (87T)


- Restricted E/F Protection (64R)
- Tripping Logic(PTRC,94)
- Disturbance Recorder(RDRE)
- Fault Locator(RFLO)
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

- Event Recorder (RDRE)


tection &
Local HMI
-Integrated HMI with 4 line display
-15 freely configurable LEDs
-Settings and disturbance Information
D -Front port for communication D
with indicatio

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Power supply Circuit_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 48


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 49
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +CT JB +CT CORE HV Side

A A
CT CORE-1
-D17.01 CTR:100/1A
Diff.Protn Optd-RET650 CL:PS

-D29.113.101 -X01
-X101 3A A111 11
1 A112 3B /62.B2
Current R-ph
HV Side
2
P2#CH.01 CT: 1/5A /54.B2
B -D29.113.101 -X01 B
-X101 4A A131 12
3 A132 4B /62.B2
Current Y-ph
HV Side
4
P2#CH.02 CT: 1/5A /54.B2
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-D29.113.101 -X01
-X101 5A A151 13
5 A152 5B /62.B2
Current B-ph
HV Side
6 -D29.113.101 -X01
P2#CH.03 CT: 1/5A /54.B2
6A A171 14
A172 6B /62.B2

-X01
C 15 C

CT core:

33kV LV Side
+CT CORE
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

CT CORE-1
CTR:400-200/1A
CL:PS
-D29.113.101 -X01
-X101 7A A211 16
D D
7 A212 7B /62.B2
Current R-ph
LV side
8
P2#CH.04 CT: 1/5A /54.C2
-D29.113.101 -X01
-X101 8A A231 17
9 A232 8B /62.B2
Current Y-ph
LV side
10
P2#CH.05 CT: 1/5A /54.C2
-D29.113.101 -X01
-X102 9A A251 18
1 A252 9B /62.C2
Current B-ph
E LV side E
2 -D29.113.101 -X01
P2#CH.06 CT: 1/5A /54.C2
10A A271 19
A272 10B /62.C2

-X01
20

CT core:

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Analog Input Circuit_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 49


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 50
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
>>
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +CT JB +CT CORE

A HV BCT A
CT RATIO:100/1A
CL:PS

-D17.01
REF Protn Optd-RET650 -D29.113.101 -X01
-X102 -SR 11A A81 21
3 1 2 A82 11B /62.C2
Current
6.8k Ohm -NLR -D29.113.101 -X01
4 1 2 12A A83 22
P2#CH.07 CT: 1/5A /54.D2
12B /62.C2
U
B -X01 B
23
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

C CT core:
C

HV NCT
CT RATIO:100/1A
CL:PS
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

D D

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Analog Input Circuit_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 50


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 51
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

+TRAFO

/48.B1

/48.B1
A A

K301.11
K302.10
-D29.113.101:18B

-D29.113.101:1B
-D17.01
-X04 -X2 -X2
82 5 6

-X304 -X04
+ 2 K305 83
Tank MOLG alarm
-X04
- 84
P0#BI.01 24-250VDC /54.B4
B B
-X304 -X04
+ 3 K306 85
Spare

-
P0#BI.02 24-250VDC /54.B4
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X304 -D33.119.101
+ 4 K307 17 18
Buchholz Trip
/56.B8
-
P0#BI.03 24-250VDC /54.B4

-X304 -D33.125.101
+ 5 K308 17 18
LV Winding Trip
C -XX2 /56.C8 C
- 1 1
P0#BI.04 24-250VDC /54.C4

-X304 -D33.125.101
+ 7 K309 27 28
Tank PRV Trip
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-D07.01 /56.C8
- -X11
P0#BI.05 24-250VDC /54.C4
2

-X304
+ 8 K310 3
D Internal relay Fail D
REC670 Relay fail -X04
- 1 78
P0#BI.06 24-250VDC /54.C4 /30.B5

-X304 -X04
+ 9 K311 79
Spare
-X04
- 80
P0#BI.07 24-250VDC /54.C4

-X304 -X04
+ 10 81
Spare
-XX2
- 6 2
E P0#BI.08 24-250VDC /54.D4 E
K302.15

K301.12
-X04:86
-XX2:4
/52.B3

/52.A5

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 51


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 52
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A A

/51.E5
/51.E3

K301.12
-X04:80
K302.15
-XX2:2
-D17.01
-X04
86

-X304 -X04
+ 12 U23 87
B Spare B
-
P0#BI.09 24-250VDC /54.B6

-X304 -X04
+ 13 88
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

U24
Spare

-
P0#BI.10 24-250VDC /54.B6

-X304 -X04
+ 14 U25 89
Spare
-XX2 -X04
- 11 4 90
P0#BI.11 24-250VDC /54.B6
C C
-X304 -X04
+ 16 U26 91
Spare

-
P0#BI.12 24-250VDC /54.B6

-X304 -X04
+ 17 U27 92
Spare
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-
P0#BI.13 24-250VDC /54.C6

-X304 -X04
+ 18 U28 93
D Spare D
-XX2
- 15 3
P0#BI.14 24-250VDC /54.C6
K302.17

K301.14
-X04:94
-XX2:5

E E
/53.A3

/53.A4

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Ref.Des.
Doc. kind. Binary Input Circuit_RET650 =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 52


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 53
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

/52.E3

/52.E5
A A

K302.17
-XX2:3

K301.14
-X04:90
-X04
-D17.01 94

-X324 -X04
+ 2 U29 95
Spare
-XX2
- 1 5 -X04
P3#BI1 24-250VDC /55.B5
96

B -X324 -X04 B
+ 5 U30 97
Spare

-
P3#BI2 24-250VDC /55.B5
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X324 -X04
+ 6 U31 98
Spare
-XX2
- 4 6 -X04
P3#BI3 24-250VDC /55.B5
99

-X324 -X04
+ 9 U32 100
Spare

C - C
P3#BI4 24-250VDC /55.B5

-X324 -X04
+ 10 U33 101
Spare
-XX2
- 8 7 -X04
P3#BI5 24-250VDC /55.C5
102

-X324 -X04
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

+ 13 U34 103
Spare

-
P3#BI6 24-250VDC /55.C5

D -X324 -X04 D
+ 14 U35 104
Spare
-XX2
- 12 8 -X04
P3#BI7 24-250VDC /55.D5
105

-X324 -X04
+ 17 U36 106
Spare

-
P3#BI8 24-250VDC /55.D5

-X324 -X04
+ 18 U37 107
Spare
-XX2
E - 16 9
E
P3#BI9 24-250VDC /55.D5

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Binary Input Circuit_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 53


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 54
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A -D17.01 -D17.01 -D17.01 -D17.01 A


Transformer input module Communication interface module Communication interface module Power supply module
TRM COM COM PSM
1/5A, 100-220V, 50/60Hz 24-250VDC 24-250VDC 110-250VDC, 100-240VAC
-X101 -X304 -X304 -X307
1 + 2 + 12 + 2
Current R-ph Tank MOLG alarm /51.B2 Spare /52.B2
HV Side /49.B2 TCS
2 - - - 1
P2#CH.01 CT: 1/5A P0#BI.01 24-250VDC P0#BI.09 24-250VDC P1#BO01

3 + 3 + 13 + 4
Current Y-ph Spare /51.B2 Spare /52.C2
HV Side /49.B2 TCS
4 - - - 3
B P2#CH.02 CT: 1/5A P0#BI.02 24-250VDC P0#BI.10 24-250VDC P1#BO02 B
5 + 4 + 14 + 6
Current B-ph Buchholz Trip /51.C2 Spare
HV Side /49.C2 /52.C2 TCS
6 - - 11 - 5
P2#CH.03 CT: 1/5A P0#BI.03 24-250VDC P0#BI.11 24-250VDC P1#BO03
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

7 + 5 + 16 7
Current R-ph LV Winding Trip Spare /52.C2
LV side /49.D2 /51.C2
8 - 1 - 8
P2#CH.04 CT: 1/5A P0#BI.04 24-250VDC P0#BI.12 24-250VDC P1#BO04

9 + 7 + 17 9
Current Y-ph Tank PRV Trip /51.D2 Spare /52.D2 Differential Protn Optd
LV side /49.E2 GRP-A /57.C5
10 - - 10
P2#CH.05 CT: 1/5A P0#BI.05 24-250VDC P0#BI.13 24-250VDC P1#BO05
C C
-X102 + 8 + 18 11
Internal relay Fail /51.D2 Spare REF Protn Optd
1
Current B-ph REC670 /52.D2 GRP-A /57.D5
- - 15 12
LV side /49.E2 P0#BI.06 24-250VDC P0#BI.14 24-250VDC P1#BO06
2
P2#CH.06 CT: 1/5A
+ 9 13
Spare /51.E2 Spare
3
Current
- 14
/50.B2 P0#BI.07 24-250VDC P1#BO07
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

4
P2#CH.07 CT: 1/5A
+ 10 15
Spare Spare
5
Spare /51.E2
- 6 16
P0#BI.08 24-250VDC P1#BO08
6
D P2#CH.08 CT: 1/5A D
17
Spare
7
SPare
18
P1#BO09
8
P2#CH.09 VT: 100-220V

10
P2#CH.10 VT: 100-220V

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Master Blocks_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 54


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 55
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A -D17.01 -D17.01 A
Binary input/output module Binary input/output module
BIO BIO
24-250VDC 24-250VDC
-X321 -X324 -D17.01
1 + 2
Spare Spare
/53.B2 -X321 -X04
2 - 1 3 U38 108
P3#BO1_PO P3#BI1 24-250VDC Spare
-X04
3 + 5 4 U39 109
Spare Spare /53.B2 P3#BO2_PO /55.B3
/55.B6
4 -
B P3#BO2_PO P3#BI2 24-250VDC B
-X321 -X04
5 + 6 5 U40 110
Spare Spare Spare
/55.B6 /53.C2 -X04
6 - 4 6 U41 111
P3#BO3_PO P3#BI3 24-250VDC P3#BO3_PO /55.B3
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

7 + 9
Spare Spare /53.C2
/55.C6 -X321 -X04
8 - 7 U42 112
P3#BO4_SO P3#BI4 24-250VDC Spare
-X04
9 + 10 8 U43 113
Spare Spare P3#BO4_SO /55.C3
/55.C6 /53.C2
10 - 8
P3#BO5_SO P3#BI5 24-250VDC
C -X321 -X04 C
11 + 13 9 U44 114
Spare Spare /53.D2 Spare
/55.D6 -X04
12 - 10 U45 115
P3#BO6_SO P3#BI6 24-250VDC P3#BO5_SO /55.C3

15 + 14
Spare Spare
/53.D2 -X321 -X04
13 - 12 11 U46 116
P3#BO7_SO P3#BI7 24-250VDC Spare
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-X04
+ 17 12 U47 117
Spare Spare /53.E2 P3#BO6_SO /55.C3

14 -
P3#BO8_SO P3#BI8 24-250VDC
D D
18 + 18
Spare
/53.E2
16 - 16
Spare P3#BI9 24-250VDC

17
P3#BO9_SO

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Master Blocks_RET650 Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 55


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 56
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

/26.E5
/26.E5
A A

K601.3
-FS15:2
+TRAFO +1A

K602.4
-FS16:2
-X04
130
-D33.119.101 -D33.119.101
/56.B3 /56.B3
BUCHHOLZ TRIP -D33.119.101 -X04 BUCHHOLZ TRIP 23 24 13 14
/36.D4 /56.E2
12 11 K603 131 3 4 25 26 15 16
/57.D5 /57.D4
/56.B8 27 28 17 18
/56.E4 /51.C4

B B
OLTC PRV TRIP -D33.119.101 -X04 OLTC PRV TRIP
22 21 K604 132 1 2
-D33.119.301
/56.B7 /56.C3 -D33.119.301
13 14 /56.C3
/36.E4
15 16 23 24
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

/57.E4 /37.B4
OTI TRIP -D33.119.301 -X04 OTI TRIP 17 18 25 26
/56.E4 /57.E5
12 11 K605 133 3 4 27 28
/56.E4
/56.B7

OLTC OSR TRIP -D33.119.301 -X04 OLTC OSR TRIP -D33.125.101 -D33.125.101
22 21 134 1 2 /56.C3 /56.D3
C /56.B8 13 14 23 24 C
/56.E2 /56.E2
15 16 25 26
/57.D5 /57.D4
17 18 27 28
/51.C4 /51.D4
LV WDG. TRIP -D33.125.101 -X04 LV WDG. TRIP
12 11 K606 135 3 4
/56.C7
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

TANK PRV TRIP -D33.125.101 -X04 TANK PRV TRIP


22 21 K607 136 1 2
/56.C8
-89X04:8

-89X04:7
D D
K602.19

K601.20
/41.B4

/41.A4
BUCHHOLZ TRIP OLTC OSR TRIP
-X04 -D33.119.101 -X04 -X04 -D33.119.301 -X04
118 U48 13 14 U49 121 124 U54 27 28 U55 127
/56.B8 /56.C8

LV WDG. TRIP OTI TRIP


-X04 -D33.125.101 -X04 -X04 -D33.119.301 -X04
E 119 13 14
E
U52 U50 122 125 U56 17 18 U57 128
/56.C8 /56.B8

TANK PRV TRIP OLTC PRV TRIP


-X04 -D33.125.101 -X04 -X04 -D33.119.101 -X04
120 U53 23 24 U51 123 126 U58 27 28 U59 129
/56.C8 /56.B8

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation Trafo Troubles Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 56


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 57
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

-D07.01

/26.B5
A -X42 A
8

/26.B5

K202.2
-FS06:2
86A Reset command

K201.1
-FS05:2
/45.C6 P4#BO.17

-XX1 -D29.131.301 -D29.119.101 -D29.131.101


7 16 26 K204 211 212 K203 11 21 K207
/62.B4 /62.B3

86A 12 22
B B
-D29.119.101
K205 121 122 13 23 K208
-D07.01 -X42 /62.B3
2 111 86A 14 24
Dir.o/c & e/f Protn optd
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

GRP-A -XX1
-X04 1 8 K209 15 25
P4#BO.13 /45.B6
139

-X04 16 26
140

-D29.113.101 K210 17 27
2A 2B K213
/62.B2 18 28
C -D17.01 C
-X307
-XX2
9 10
Differential Protn Optd
GRP-A -XX2
10 11
P1#BO05 /54.C8
-X307
11
REF Protn Optd
GRP-A -XX2
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

Trafo LV Side 12 12
P1#BO06 /54.C8
-X04 -D29.119.101
137 K211 313 314 K212 -D33.119.101
/62.B3 15 16 BUCHHOLZ TRIP
86A /56.B8
D Inter Trip to LV side -X04 -D33.125.101 D
138 15 16 LV WDG. TRIP
-X04 -D29.119.101 -X04
-D33.125.101 /56.C8 141 U60 227 228 U61 143
25 26 TANK PRV TRIP /62.B3
/56.C8 86A
-D33.119.101
25 26 OLTC PRV TRIP
-D33.119.301 /56.B8 -X04 -D29.119.101 -X04
15 16 OTI TRIP 142 U62 311 312 U63 144
/56.B8 -D33.119.301 /62.B3
OLTC OSR TRIP 25 26 86A

/56.B8
-D29.137.101
95/86A
E TSR E
11 13

12 21 K206
/62.D4

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation GRP-A Master Trip Relay Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 57


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 58
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

/26.E5
A A

/26.E5

K502.2
-FS14:2
K501.1
-FS13:2
-D33.101.307 -D33.101.101 -D33.101.301
16 26 K503 122 121 K504 11 21 K505
/62.B6 111 /62.B5
50LBB 12 22
B B
-D33.101.101
K508 212 211 K506 13 23
221 /62.A5
-D07.01 50LBB 14 24 K507
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-X41
17
LBB Protn Optd
-XX1
16 9
P4#BO.11 /45.E4

Spare
-X41 -X04 -D33.101.101 -X04
C 18 151 U64 213 214 U65 153 C
P4#BO.12 /45.E4
/62.B5
50LBB

-X04 -X04 -D33.101.101 -X04


149 152 U66 225 226 U67 154
/62.B5
50LBB
-X04
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

150

D D

-X04 -D33.101.101
145 117 118 K511 -D33.113.101
/62.B5 95/50LBB
50LBB TSR
Trip to adjacent bays -X04
146 11 13

-X04 -D33.101.101
147 123 124 K510
Trip to adjacent bays /62.B5 12 21 K509
50LBB /62.D5
-X04
E 148
E

-ETH:N (-P1)
K502.3
-ETH:L (-P1)
K501.2

/64.B2
/64.B2

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer bay DCC EFS
F F
Project Extension of Mokoulou Substation 3Ph Trip Relay Circuit For LBB Protn Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 58


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 59
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +52CB

A A

-52X04 -X1
-FS07:2 10 1 +VE
/26.C5
K51.1

-52X04 -X1
-FS08:2 11 2 _VE
/26.C5
K52.2

B B

-52X04 -X1
K53 12 22 COMMON
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-TNC
1P3 -52X04 -X1
1P4 K534 13 10 REMOTE TRIP CKT-I
/62.B7
Trip

-D07.01 TNC

-X41 -XX1
C 11 10 C
Trip TC-I

10
P4#BO.07 /45.D4

-D29.119.101 -52X04 -X1


113 114 K55 14 40 PROTECTION TRIP-I
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

/62.B3
86A
-D33.101.101
113 114
/62.B5
50LBB
D D
-D29.143.101
195
TSR
-52X04 -X1
11 13 K56 15 12 PRECLOSE SUPERVISION

-52X04 -X1
12 21 K57 16 13 POSTCLOSE SUPERVISION
/62.D1

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer Bay DCC EFS
F F
Project Extension of Mokoulou Substation Trip Coil-I Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 59


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 60
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A +52CB

A A

-52X04 -X1
TC-I & TC-II are fed from same DC supply. 19 3 _VE

-52X04 -X1
K63 20 22 COMMON

B -TNC B
2P3 -52X04 -X1
2P4 K64 21 11 REMOTE TRIP CKT-II
/62.B7
Trip

TNC
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-D07.01
-X41 -XX1
8 11
Trip TC-II

7
P4#BO.05 /45.C4

C C

-D29.119.101 -52X04 -X1


223 224 K65 22 41 PROTECTION TRIP-II
/62.B3
86A
-D33.101.101
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

115 116
/62.B5
50LBB

D D
-D29.143.301
295
TSR
-52X04 -X1
11 13 K66 17 15 PRECLOSE SUPERVISION

-52X04 -X1
12 21 K67 18 14 POSTCLOSE SUPERVISION
/62.D2

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer Bay DCC EFS
F F
Project Extension of Mokoulou Substation Trip Coil-II Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 60


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 61
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

+BB
A A

+1A

B B

-X04
155

-X04
156
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-D29.143.301 -D29.143.101 -D33.101.101 -D29.119.101


15 16 K70 15 16 K69 223 224 K68 115 116
17 /62.E3 17 /62.E2 /62.B5 /62.B3
50LBB 86A +52CB
295 195

C -52X04 -X1 C
-D07.01 K71 23 22 COMMON

-X41 -XX1
14 12
CB Close command
-52X04 -X1
13 K72 24 9 REMOTE CLOSE
P4#BO.09 /45.D4
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

-TNC
Synch check ok
-X41 1P2
15 K73 1P1 /62.B7
P4#BO.10 /45.E4 Close
D D
TNC

+89AE E/S -X1


42

-X1 CB LOCAL INTERLOCK


43

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer Bay DCC EFS
F F
Project Extension of Mokoulou Substation CB Closing Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 61


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 64
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

-ETH
A Ethernet switch A
-ETH
Ethernet switch

-P1 -P1
K501.2 L + L +
/58.E3
-D33.113.101:12

K502.3 N - N -
/58.E8
-D33.101.301:14
77-300VDC /64.B2 77-300VDC
GND 90-265VAC GND 90-265VAC

PE PE
B B
/64.B4

Ethernet port
RJ45
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

#Diagnosis
-R1
1
Internal fail

2
#ALARM2

C C
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

D D

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer Bay DCC EFS
F F
Project Extension of Mokoulou Substation CB Closing Circuit Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 64


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 62
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
+1A

A A

-D37.01
-D33.101.101
-D29.113.101 /58.B6 -A/M -TNC
-D29.119.101 1P1 1 1
-D29.101.101 Test /57.B6 /58.B6 1P2 1P2
113 114 /38.C4 /61.D4
Test Normal /57.B6 /59.D5 -D33.101.307 DC-1 1P1 J
1B 1A 113 114 115 116 15 25 2
Normal /48.B2 /59.D5 -D29.131.301 /60.D5 1P4 1P3 1P4
1B 1A 2B 2A 15 25 117 118 16 26 1P3 /38.C4 /59.C5 /29.B4
/30.B1 /57.C4 115 116 /58.D3 /58.B5 DC-2 M
2B 2A 3A /61.C4 16 26 123 124 2P1 3
/49.B4 117 118 /57.B5 /58.E3 17 27 2P2 2P2
3A 3B /43.C4 2P1
/32.B4 4A 221 222 17 27 18 28 DC-1 J
3B /49.B4 213 214 2P3 4 4
B 4A 4B 223 224 18 28 /58.C7 2P4 2P4 B
/32.B4 5A /60.C4 2P3 /43.C3 /60.B5
4B /49.C4 223 224 DC-2 M
5A 5B 225 226 /61.C3 5
/32.B4 6A 225 226 3P2 3P2
5B /49.C4 227 228 /58.C7 3P1 3P1 /29.C4
6A 6B /57.D7 227 228 IND DC-2 J
/32.B4 7A 3P3 6
6B /49.D4 3P3 3P4
7A 7B 311 312 50LBB 3P4
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

/32.B4 8A /57.E7 /43.C3 M


7B /49.D4 313 314 DC-1 IND 7 7
8A 8B /57.D3 4P2
/32.C4 9A 315 316 4P2 4P1
8B /49.E4 /34.C4 4P1 /43.D4 J
9B 317 318 IND DC-2 4P3 8
9B 9A 10A 4P4
/49.E4 423 424 4P3 /29.C4
10B 10A 10B 4P4 M
/32.C4 11A 425 426 5P2 9
11B 11A /50.B4 DC-1 IND
/32.D4 11B 427 428 5P1 J
12B 12A 12A 5P3 R1 R2
/32.D4 /50.B4 Auto 1 5P4
13B 13A 12B 86A Off 0 /29.D4
C /32.E4 13A M C
14B 14A Manual 2 Y1 Y2
13B 6P2
15B 15A 14A 6P1 /29.D4
AUTO/MANUAL J
16B 16A 14B 6P3 B1 B2
6P4
17B 17A /29.D4
15B 15A M
18B 18A N1 N2
/30.B1 16B 16A 7P2
17B 17A 7P1 J /29.E4

18B 18A 7P3 7P4


/48.B2
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

M
8P2
8P1 A

8P3 8P4
D M D
-D29.137.101 -D33.113.101
9P2
-D29.143.101 -D29.143.301 95/86A 95/50LBB 9P1
TSR TSR AJ
195 295
TSR TSR 11 11 9P3 9P4
11 11 /57.E5 12 /58.E5 12 MA
/59.E5 12 /60.E5 12 10P2
21 21 10P1 AJ
21 21 10P3 10P4
13 13
MA
13 13
15 16 15 16
/34.D4 /34.E4 Trip
15 16 15 16 17 17 N
/61.C3 /61.C2 Close
E 17 17 25 26 25 26 E
25 26 25 26 27 27
/35.B4 /35.C4 TNC
27 27

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer Bay DCC EFS
F F
Project Extension of Mokoulou Substation Contacts Distribution Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 62


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 63
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Frame A3 - Version 1 1 2 3 4 5 6 7 8
© Copyright 2010 ABB

+1A
A A

-52X04 -89X04 -X01 -X02 -X03 -X04 -X04 -X04 -X13 -XX1 -XX2
25 18 24 13 5 160 166 176 5 13 13

-52X04 -89X04 -X01 -X02 -X03 -X04 -X04 -X04 -X13 -XX1 -XX2
26 19 25 14 6 161 167 177 6 14 14

-52X04 -89X04 -X01 -X02 -X03 -X04 -X04 -X04 -X13 -XX1 -XX2
27 20 26 15 7 162 168 178 7 15 15
B B

-52X04 -89X04 -X01 -X03 -X04 -X04 -X04 -X13


28 21 27 8 163 169 179 8
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-52X04 -89X04 -X01 -X04 -X04 -X04


29 22 28 164 170 180

-52X04 -X01 -X04 -X04 -X04


30 29 165 171 181

-X01 -X04 -X04


30 172 182
C C
-X04 -X04
173 183

-X04 -X04
174 184

-X04 -X04
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

175 185

D D

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Circuit diagram Ref.Des. =1R
Approved AHV For Transformer Bay DCC EFS
F F
Project Extension of Mokoulou Substation Spare TB's Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 63


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 1001
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Parts list A3 - Version 2 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
Pos. Location Device Device Type designation Technical data Remark Article number Manufacturer Manufacturer number Qty. Document / sheet
designation description
A A

1 -52X04 Feed-through terminal 280-833 800V,20A 0.08-2.5mm², max 4 wire Wago 280-833 30 YN1M302310 / 34, 36, 59, 60, 61,
63

2 -89X04 Feed-through terminal 280-833 800V,20A 0.08-2.5mm², max 4 wire Wago 280-833 22 YN1M302310 / 34, 35, 41, 63

3 -A01.01 5 Pin Socket with Switch SW 230VAC, 05-15A Box type, Indian standard 1MYN538103-001 Anchor 1 YN1M302310 / 27

4 -A/M Rotary switch 8 3-pos. contacts with 0 position 32A Stayput, Wing knob type, 90 degre 1MYN533018-003 Switron 1 YN1M302310 / 38, 62
B switching B

5 -ASS Ammeter selector switch 4 4-pos. contacts with 0 position 440/250V, 10A Wing Type Knob, Size:75x75mm 1MYN533015-001 Switron 1 YN1M302310 / 28

6 -B37 Heating SPHT 230V AC, 50W IN6677-3001-2 *Reputed* 1 YN1M302310 / 27


We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

7 -D03.01 Multi function meter Rish Master 3430 3Ph, 3Ele, 4W with aux.supply Rishab 1 YN1M302310 / 28, 29

8 -D03.02 Digital Ammeter AMM-D-DM_Var1 Direct meter 96x96mm Rishab 1 YN1M302310 / 28

9 -D07.01 Mounting kit 19" mounting kit For 3/4x19" case 1MRK002420-BA ABB 1MRK002420-BA 1
15 LED indication module LED Small size 1MRK000008-PB ABB 1MRK000008-PB 1 YN1M302310 / 30
C 15 LED indication module LED Medium size 1MRK000008-MB ABB 1MRK000008-MB 1 C
mA input module MIM 0-20, 4-20, ±20mA 6 channels 1MRK000284-AB ABB 1MRK000284-AB 1 YN1M302310 / 42, 45
Communication interface module OEM 1 glass interface 1MRK002266-AA ABB 1MRK002266-AA 1 YN1M302310 / 30
Transformer input module TRM 1A, 0-340V, 50/60Hz 6I+6U 1MRK002247-AG ABB 1MRK002247-AG 2 YN1M302310 / 31, 32, 33, 44, 47
Binary input module BIM 110-125VDC, 50ma 16 inputs 1MRK000508-BD ABB 1MRK000508-BD 3 YN1M302310 / 34, 35, 36, 37, 38,
39, 44, 45, 46
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

Binary output module BOM 24 output relays 1MRK000614-AB ABB 1MRK000614-AB 2 YN1M302310 / 40, 41, 43, 45, 46,
57, 58, 59, 60, 61
Power supply module PSM 90-250VDC 50/60Hz 1MRK002239-BB ABB 1MRK002239-BB 1 YN1M302310 / 30, 51

D 10 -D17.01 Rack casing Rack casing 6U 1/2x19" rack casing ABB Supplied with main device 1 D
Communication interface module COM 24-250VDC 14 binary inputs ABB Supplied with main device 1 YN1M302310 / 48, 51, 52, 54
Transformer input module TRM 1/5A, 100-220V, 50/60Hz 8I+2U ABB Supplied with main device 1 YN1M302310 / 49, 50, 54
Binary input/output module BIO 24-250VDC 9 binary inputs, 9 binary outputs ABB Supplied with main device 1 YN1M302310 / 53, 55
Power supply module PSM 110-250VDC, 100-240VAC 9 outputs, for 6U rack casing ABB Supplied with main device 1 YN1M302310 / 35, 48, 54, 57

11 -D29 Mounting case RHGT20 4U60C 1MRK000137-PA ABB 1MRK000137-PA 1

12 -D29.101.101 Test switch RTXP18-AS 20A INRK926-015-AS ABB INRK926-015-AS 1 YN1M302310 / 30, 32, 62

13 -D29.107.101 Test switch RTXP18-BP 20A RK 926115-BP ABB RK 926115-BP 1 YN1M302310 / 30, 31, 33
E E
14 -D29.113.101 Test switch RTXP18-CP 20A INRK926-015-CP ABB INRK926-015-CP 1 YN1M302310 / 48, 49, 50, 57, 62

15 -D29.119.101 Bistable relay RXMVB4 24VDC 9NO, 5NC INRK251-402-AD ABB INRK251-402-AD 1 YN1M302310 / 34, 57, 59, 60, 61,
62

16 -D29.131.101 Resistor unit RXTMA1 8x47ohms,5W resistors 4 resistor place INRK711-008-AA ABB INRK711-008-AA 1 YN1M302310 / 57

17 -D29.131.301 Push button RXT 2NC, 2NO IN5396-3001-AC ABB RK 723001-AA 1 YN1M302310 / 57, 62

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Parts list Ref.Des. =1R
Approved AHV Parts list DCC EPB +1A
F F
Project Extension of Mokoulou Substation Part List Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 1001


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 1002
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Parts list A3 - Version 2 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
Pos. Location Device Device Type designation Technical data Remark Article number Manufacturer Manufacturer number Qty. Document / sheet
designation description
A A

18 -D29.137.101 Trip circuit supervision relay TSR 110/220V DC 2CO IN352-001-AS ABB IN 352-001-AS 1 YN1M302310 / 34, 57, 62

19 -D29.143.101 Trip circuit supervision relay TSR 110/220V DC 2CO IN352-001-AS ABB IN 352-001-AS 1 YN1M302310 / 35, 59, 61, 62

20 -D29.143.301 Trip circuit supervision relay TSR 110/220V DC 2CO IN352-001-AS ABB IN 352-001-AS 1 YN1M302310 / 35, 60, 61, 62

21 -D29.155.101 Trip circuit supervision relay TSR 110/220V DC 2CO IN352-001-AS ABB IN 352-001-AS 1 YN1M302310 / 25

B 22 -D33 Mounting case RHGT20 4U60C 1MRK000137-PA ABB 1MRK000137-PA 1 B

23 -D33.101.101 Bistable relay RXMVB2 24VDC, 220VAC 5NO, 3NC RK 251206-AD ABB RK 251206-AD 1 YN1M302310 / 58, 59, 60, 61, 62

24 -D33.101.301 Resistor unit RXTMA1 4x150ohms,5W resistors 4 resistor place INRK711-004-AA ABB INRK711-004-AA 1 YN1M302310 / 58
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

25 -D33.101.307 Push button RXT 2NC, 2NO IN5396-3001-AC ABB RK 723001-AA 1 YN1M302310 / 58, 62

26 -D33.113.101 Trip circuit supervision relay TSR 110/220V DC 2CO IN352-001-AS ABB IN 352-001-AS 1 YN1M302310 / 34, 58, 62

27 -D33.119.101 Auxiliary relay RXSF1 110-125VDC 6NO RK 271018-AN ABB RK 271018-AN 1 YN1M302310 / 36, 51, 56, 57

28 -D33.119.301 Auxiliary relay RXSF1 110-125VDC 6NO RK 271018-AN ABB RK 271018-AN 1 YN1M302310 / 36, 37, 56, 57
C C
29 -D33.125.101 Auxiliary relay RXSF1 110-125VDC 6NO RK 271018-AN ABB RK 271018-AN 1 YN1M302310 / 51, 56, 57

30 -D37.01 Test terminal block TTB 1100 V, 10 A Flush mounting 1MYN266015-001 Industrial Meters Pvt. Ltd 1 YN1M302310 / 29, 62

31 -DS Door limit switch DLS 230V AC, 5A Single pole, 1NO IIN5374-3001-1 Kaycee 1 YN1M302310 / 27

32 -E1 Compact FL lamp CFL 240AC, 11W 3BYN591500-001 Philips 1 YN1M302310 / 27


C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

33 -ETH Ethernet switch AFS660 Single PS 77-300VDC/90-265VAC no slots, screw terminals ABB To be customized: AFS670-EEEE__ 1 YN1M302310 / 64

34 -FP1 Line interface unit LIU 12 Ports wall mounted ,Front door type Besnet/equivalent 1
D D
35 -FS01 Fuse OFFNF1GG16 16A 1SCA107790R1001 ABB 1SCA107790R1001 1 YN1M302310 / 25
Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

36 -FS02 Fuse OFFNF1GG16 16A 1SCA107790R1001 ABB 1SCA107790R1001 1 YN1M302310 / 25


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

37 -FS03 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

38 -FS04 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1
E E
39 -FS05 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26
Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

40 -FS06 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

41 -FS07 Fuse OFFNF1GG10 10A 1SCA107789R1001 ABB 1SCA107789R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1
Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Parts list Ref.Des. =1R
Approved AHV Parts list DCC EPB +1A
F F
Project Extension of Mokoulou Substation Part List Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 1002


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 1003
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Parts list A3 - Version 2 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
Pos. Location Device Device Type designation Technical data Remark Article number Manufacturer Manufacturer number Qty. Document / sheet
designation description
A A

42 -FS08 Fuse OFFNF1GG10 10A 1SCA107789R1001 ABB 1SCA107789R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

43 -FS09 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

44 -FS10 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1
B B
45 -FS11 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26
Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

46 -FS12 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

47 -FS13 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

48 -FS14 Fuse OFFNF1GG6 6A 1SCA107788R1001 ABB 1SCA107788R1001 1 YN1M302310 / 26


C Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1 C

49 -FS15 Fuse OFFNF1GG10 10A 1SCA107789R1001 ABB 1SCA107789R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

50 -FS16 Fuse OFFNF1GG10 10A 1SCA107789R1001 ABB 1SCA107789R1001 1 YN1M302310 / 26


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

51 -FS17 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 31


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

52 -FS18 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 31


D D
Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

53 -FS19 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 31


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

54 -FS21 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 29


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

55 -FS22 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 29


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

E 56 -FS23 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 29 E


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

57 -FS24 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 33


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

58 -FS25 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 33


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Parts list Ref.Des. =1R
Approved AHV Parts list DCC EPB +1A
F F
Project Extension of Mokoulou Substation Part List Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 1003


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet 1004
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
ABB India Parts list A3 - Version 2 1 2 3 4 5 6 7 8
© Copyright 2010 ABB
Pos. Location Device Device Type designation Technical data Remark Article number Manufacturer Manufacturer number Qty. Document / sheet
designation description
A A

59 -FS26 Fuse OFFNF1GG2 2A 1SCA107786R1001 ABB 1SCA107786R1001 1 YN1M302310 / 33


Control Fuse Base BS type 32A 1SYN833001R2009 ABB 1SYN833001R2009 1

60 -LK01 Fuse Base with Neutral Link FA, Link 15A Fuse Base with Neutral Link 1MYN567004-C ABB 1MYN567004-C 1 YN1M302310 / 31

61 -LK02 Fuse Base with Neutral Link FA, Link 15A Fuse Base with Neutral Link 1MYN567004-C Bussmann 1MYN567004-C 1 YN1M302310 / 29

62 -LK03 Fuse Base with Neutral Link FA, Link 15A Fuse Base with Neutral Link 1MYN567004-C Bussmann 1MYN567004-C 1 YN1M302310 / 33
B B
63 -MCB01 Miniature circuit breaker S 272-C 16 16A 2 pole, 400VAC/125VDC 2CDS272001R0164 ABB GHS2721016R0164 1 YN1M302310 / 27

64 -NLR Varistor Metrosil 600A/S1/Spec.6368 1 phase 1MRK002059-B ABB 1MRK002059-B 1 YN1M302310 / 50


We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

65 -PB01 Auxiliary contact block 1 YN1M302310 / 38, 43

66 -S1 Toggle Switch TGLSW 230V AC,5A 1pole, ON/OFF Switch IN5399-3002-1 *Reputed* 1 YN1M302310 / 27

67 -SR Stabilising resistor SR 6.8k Ohm 100W Variable IN5245-3014-468 Nandalal 1 YN1M302310 / 50

68 -TH Thermostat TH 230VAC, 15A, 50 Hz Range : 20-85°C IN7635-3001 GIRISH EGO 1 YN1M302310 / 27
C C
69 -TNC Rotary Switch 20-3-pos. contacts with 0 position 32A, 660V Spring return & lost motion device with 1MYN533020-006 Switron 1 YN1M302310 / 59, 60, 61, 62
Pistol grip handle 45 degree Switching

70 -X01 Disconnect terminal CATD M4 800V, 41A 2.5-6mm² 1MYN266003-002 Elmex 30 YN1M302310 / 29, 31, 49, 50, 63

71 -X02 Disconnect terminal CATD M4 800V, 41A 2.5-6mm² 1MYN266003-002 Elmex 15 YN1M302310 / 29, 31, 33, 63
C:\MY DRAWINGS\12.Sonam\18.Republic of Congo\2.Detailed Design\2.CRP\1.YN1M302310-AAB_110kV Trafo.e3s

72 -X03 Disconnect terminal CATD M4 800V, 41A 2.5-6mm² 1MYN266003-002 Elmex 8 YN1M302310 / 25, 27, 63

73 -X04 Feed-through terminal 280-833 800V,20A 0.08-2.5mm², max 4 wire Wago 280-833 185 YN1M302310 / 35, 36, 37, 38, 39,
40, 42, 43, 51, 52, 53, 55, 56, 57,
D 58, 61, 63 D

74 -X13 Disconnect terminal CATD M4 800V, 41A 2.5-6mm² 1MYN266003-002 Elmex 8 YN1M302310 / 25, 27, 63

75 -XX1 Feed-through terminal 280-833 800V,20A 0.08-2.5mm², max 4 wire Wago 280-833 15 YN1M302310 / 34, 35, 36, 37, 38,
39, 57, 58, 59, 60, 61, 63

76 -XX2 Feed-through terminal 280-833 800V,20A 0.08-2.5mm², max 4 wire Wago 280-833 15 YN1M302310 / 51, 52, 53, 57, 63

E E

Based on Prepared 26.05.2014 Sonam Title 110kV Control & Relay Panel Doc. kind. Parts list Ref.Des. =1R
Approved AHV Parts list DCC EPB +1A
F F
Project Extension of Mokoulou Substation Part List Resp. dept. - Rev. ind. 00 Language en
Print: 5/30/2014

Mokokoulou Substation Sheet 1004


Rev. Revision note Date Name 3100053172
ABB
Doc. no. YN1M302310-CAB n. sheet
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
BILL OF MATERIAL

Document Name Identity


SAS Bill of Material YN1M302310-SA

REVISION TABLE

Rev.No. Revision Note Approved Week


00 First submission PM 23/2014

Design Checked by
KANNAN R SAS PANEL 3100053172
110/33kV BAY EXTN. MOKOUKOULOU SUBSTATION
Drawing Checked by Rev
PM Panel: Station Automation YN1M302310-SA 00

Drawn by Issued by Year Week Sheet


AHV SASE 14 23 BILL OF MATERIALS 1 of 5
Sl. Description
Make/Model Article No. Qty (No.)
No.
1. Frame Type with Fixed frame, front Glass door, 1No.
Rear side single Metallic door,
(W=800mm,D=800mm,H=2250mm+15mm
AVP+47mm BF)
with space heater, tinned copper earth bus
25x6mm;
Paint shade:
Exterior: RAL7032, TEXTURE FINISH
Interior: GLOSSY WHITE
2. AC MOUNTING PLATE: Mounting plate for 1 1No
MCB, universal socket and Rotary switch
3. MCB FOR 240V AC. Make: ABB, 2pole, GHS2721016R0164 1No
Rating: 16A 240V AC, S272 C16
4. Make: Anchor, Universal Socket (Box type) 1MYN538103-001 1No.
With switch Rating:5A/15A 230V AC
5. ROTARY SWITCH: Switron make ON/OFF, 1-
1MYN533014-001 1No.
Pole, 6A, 240V AC
6. Make: ABB 1SCA107789R1001
2NO.
Type: Fuse Base NSH15 with HRC Fuse +1SYN833001R20
NS10 Rating:10A 09
7. Make: Kaycee, DOOR SWITCH: Single pole,
IN5374-3001-1 1No.
Rating:5A,230 V AC
8. MAKE: THERMO, Space heater Rating 50W
IN6677-3001-2 1No.
230 V AC
9.
Make: OSRAM DULUX, COMPACT 3BYN591500-001 1No.
Fluorescent LAMP
Rating: 40W 230V AC
10.
Disconnecting type terminal blocks 1MYN266003-002 1 set
Elmex/connectwell make

Design Checked by
KANNAN R SAS PANEL 3100053172
110/33kV BAY EXTN. MOKOUKOULOU SUBSTATION
Drawing Checked by Rev
PM Panel: Station Automation YN1M302310-SA 00

Drawn by Issued by Year Week Sheet


AHV SASE 14 23 BILL OF MATERIALS 2 of 5
Sl. Description
Make/Model Article No. Qty (No.)
No.
I. Substation Automation System BOM mounted in respective Panel

11. KC1, Bay Level Ethernet switch for 1 to 11 ABB / AFS660 YN1M302310-TB 2 Nos.
KC2 100 Mbps Redundant managed
Ethernet switches. (location as per the
system architecture) 7 FO (LC type)
and 4 RJ45 ports
II. Substation Automation System BOM of SAS Panel

12.KD2 Time Synchronization SERTEL / T- YN1M302310-TFA 1No


Equipment GPS-300-S09
a) GPS Receiver with SNTP
protocol Input Aux. Supply - 90-
260 V AC, LCD Display 2X20
character, 2 XLAN interface on
RJ45 connector, 1XRS232
interface, Connection of Antenna-
Via BNC connector,
b) Antenna - T-GPS-014-S09 1 No.
c) Antenna cable-Coaxial cable 1 No.
RG58 (50 Mtrs.)
d) Slave Clock – T-SL-300-100-6D YN1M302310-TDU 1No.

13. KC101 Station Ethernet switch ABB/AFS660 YN1M302310-TA 1 No.


100 Mbps Redundant managed
Ethernet switches (Station Level
mounted SAS panel) 3 FO (LC type)
port and 8 RJ45 port.
14. KA1 Station HMI cum Gateway ADVANTECH 1MYN900010-GW 1 No.
19” Rack Mountable Industrial Grade
PC
Intel C2D 2.93GHz Processor or higher,
4GB DDR2 RAM, Minimum 160GB
HDD, CD & DVD Read \ Write drive
(24x – CD & 40x –DVD), 2-Serial port,
3-USB Ports, 1-VGA Port, 2xOn Board
RJ45,
1xRJ45 Dual Port Intel PRO 1000MT
Server Adapter

Windows 7 (32 bit)

Design Checked by
KANNAN R SAS PANEL 3100053172
110/33kV BAY EXTN. MOKOUKOULOU SUBSTATION
Drawing Checked by Rev
PM Panel: Station Automation YN1M302310-SA 00

Drawn by Issued by Year Week Sheet


AHV SASE 14 23 BILL OF MATERIALS 3 of 5
15. DR Evaluation LAPTOP HP/Dell/Lenovo 1MYN900010-DL 1No.
Intel core i3 processor> 2GHz /Equivalent
• 4 GB DDR3 RAM make
• At Least 250GB HDD
• DVD +/- RW Optical drive
• 3 Nos. USB 2.0 Ports
• 1 No. VGA port for External Monitor
• 1 No. RJ45 10/100 Mbps Ethernet Port
Windows 7
16. USB KVM Extender. ATEN CE750R 1MYN900010-KE 1 No.

17. A4 Colour laser Printer Canon/ 1MYN900010-TE 1 No.


HP/LBP9100

18. MO 21`` Monitor DELL / HP 1MYN900010-MO 1No.

19. - MicroSCADA Station HMI cum ABB YN1M302310-LIC 1 Nos


Gateway License

20. - SNMP – OPC Gateway for supervision Oberimeir 1MYN900010-ZNA 1 No

21. - AFS View License for Network ABB YN1M302310 – AFS 1 No


monitoring system.
22. - Speaker set for SAS servers for
audible alarm. Logitech/Creative 1MYN900010-SPS 1 Nos.
/Philip

Design Checked by
KANNAN R SAS PANEL 3100053172
110/33kV BAY EXTN. MOKOUKOULOU SUBSTATION
Drawing Checked by Rev
PM Panel: Station Automation YN1M302310-SA 00

Drawn by Issued by Year Week Sheet


AHV SASE 14 23 BILL OF MATERIALS 4 of 5
23. a) Multimode FO Patch chords 1set.
with ST/LC connectors for
connecting IED to Ethernet
switch
b) Multimode FO Patch chords 1set.
with LC/LC connectors for
connecting IED to Ethernet
switch

c) Multimode FO Patch chords 3Nos.


with LC/LC connectors for
connecting Station Ethernet
switches to Bay Ethernet
switches (50m each)

d) Multimode FO Patch chords 1set.


with LC/LC connectors for
connecting Station Ethernet
switches to Bay Ethernet
switches (10m each)

e) CAT 5 FTP cable with RJ45 1set.


connectors at both ends.
(Station Ethernet switch to
station level devices)

f) RS485 cable for MFM meter 1set.


looping

24. Dot matrix printer. (LQ-1150- 1MYN900010-TJ 1 No.


II/MSP355,
Make: EPSON;
Model: LQ1150-II;
25. KC1 Printer Server for Dot matrix printer DIGISOL 1MYN900010-TY 1 No

26. RS485 / RS232 converter for MFM CMS YN1M302310-TC 1No..


connection to HMI
Aux supply: 230V AC
27. Inverter 1kVA,(I/P: 110/220V DC, O/P: ALAN YN1M302310-TD 1No.
230V AC)

Design Checked by
KANNAN R SAS PANEL 3100053172
110/33kV BAY EXTN. MOKOUKOULOU SUBSTATION
Drawing Checked by Rev
PM Panel: Station Automation YN1M302310-SA 00

Drawn by Issued by Year Week Sheet


AHV SASE 14 23 BILL OF MATERIALS 5 of 5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A
110/33kV TRANSFORMER BAY EXTENSION AT EXISTING MOUKOUKOULOU SUBSTATION IN REPUBLIC OF CONGO A

COMMUNICATION CONNECTIVITY DIAGRAM

CONTROL ROOM STATION HMI cum GATEWAY

B IEC 60870-5-104 PROTOCOL


B
(REMOTE CONTROL CENTRE)

GPS RECEIVER -P2 KVM-EXTENDER


-P1
DOT-MATRIX PRINTER LAPTOP-DR EVALUATION
A4 LASER COLOR PRINTER -KA1 (AA1KA1)
-KD2 (AA1KD2)
2001
2101 SUBSTATION AUTOMATION SYSTEM
GPS Receiver -KC11 (AA1KC11) LAPTOP
C SNTP 16 C

172.16.0.101
Printer 172.16.0.161
Server 172.16.0.160
172.16.0.140 IEC61850 // 1

IEC61850

RS232
// 2

//
RS485 TO RS232

RS485
//RS232 CONVERTER

//
D D
-KC101 (AA1KC101) 11 10 9 8 7 6 5 4 2
15 17
14 13 121819 20
16 Root / 1
1
Station Ethernet Switch 3
ABB INDIA LTD 2014

172.16.201.0
FAULT TOLERANT RING NETWORK ON IEC61850 STATION ETHERNET SWITCH – KC101
STATION ETHERNET SWITCH KC101 WILL BE
IED RING SPARE TOTAL
MOUNTED IN SAS PANEL PORT PORT PORT PORT
1 FO 3 FO
4 RJ45 2 FO + +
4 RJ45 8 RJ45

E E
BAY ETHERNET SWITCH KC1 WILL BE MOUNTED
CONTROL ROOM 33kV SWITCHGEAR ROOM
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

IN TRAFO PANEL BAY ETHERNET SWITCH KC2 WILL BE MOUNTED


-KC1 (AA1KC1) -KC2 (AA1KC2) IN 33kV SWITCHGEAR PANEL
18 20
12 13 14 1516 17 19 7 12 13 141516 17 19 1820 3
1 Bay Ethernet Switch 3 1 Bay Ethernet Switch 3
172.16.1.0 172.16.2.0
2 4 5 6 7 8 9 10 11 2 4 5 6 7 8 9 10 11

F BAY ETHERNET SWITCH – KC1 BAY ETHERNET SWITCH – KC2


F
1CR1A BAY-101 IED RING SPARE TOTAL IED RING SPARE TOTAL
PORT PORT PORT PORT PORT PORT PORT PORT
110/33kV TRAFO-1 3 FO 7 FO 33kV INCOMER FROM 33kV OUTGOING FEEDER-1 7 FO
2 FO 2 FO + + TRAFO-1 5 FO 2 FO 4 RJ45 +
-E1Q01KF1 (AA1E1Q01KF1) 4 RJ45 4 RJ45 4 RJ45
-H1Q01KF1 (AA1H1Q01KF1) -H1Q13KF1 (AA1H1Q13KF1)
6
9 10
172.16.1.5 IEC61850
172.16.2.2 IEC61850 IEC61850 172.16.2.7

G -E1Q01FN1 (AA1E1Q01FN1)
8
G
172.16.1.6 IEC61850
C:\Data\3.Projects\2014\CONGO_MOUKOUKOULOU\CONGO_MOUKOUKOULOU\CONGO_MOUKOUKOULOU\AA1\SCD - AA1.vsd / 14-05-30

33kV STATION TRAFO-1


33kV EARTHING TRAFO-1
-H1Q11KF1 (AA1H1Q11KF1)
-H1Q14KF1 (AA1H1Q14KF1)
2
5
172.16.2.4 IEC61850
IEC61850 172.16.2.6

H H

33kV OUTGOING FEEDER-1


-H1Q12KF1 (AA1H1Q12KF1)
4
172.16.2.5 IEC61850

I I

MFM-1 MFM-2 MFM-3 MFM-4 MFM-5 MFM-6

J J
110/33kV TRAFO-1 33kV INCOMER FROM 33kV STATION TRAFO-1 33kV OUTGOING 33kV OUTGOING 33kV EARTHING
TRAFO-1 FEEDER-1 FEEDER-1 TRAFO-1

LEGEND:
NAMING CONVENTION
CAT5 - RJ45 Cable
K Unarmored Fibre Optic Cable
E1/H1 Q01 KF1/FN1 CUSTOMER : DELEGATION GENERALE DES GRANDS TRAVAUX- (DGGT) K
KF1-CONTROL IED CONTRACTOR : OVERSEAS INFRASTRUCTURE ALLIANCE (INDIA) PVT LTD., -(OIA), MUMBAI, INDIA
RS232 Cable FN1-PROTECTION IED Based on: SALE ORDER NO:3100053172 Title SUBSTATION AUTOMATION SYSTEM
Note : 1. Numerical Relay for 33kV Bays – REF615 is supplied by
Switchgear Panel Vendor Twisted Pair cable for RS485 Communication BAY NUMBER Prepared: M. PREM KUMAR COMMUNICATION CONNECTIVITY DIAGRAM
Approved: R. KANNAN
Multi Function Meter VOLTAGE LEVEL
MFM Ex: E1-132kV & H1-33kV Project Doc. des.: Ref. des.:
With Reference Number 110/33kV TRANSFORMER BAY EXTENSION AT EXISTING
MOUKOUKOULOU SUBSTATION IN REPUBLIC OF CONGO
L Resp. dept.: PSAC-SAS Rev. ind.: 00 Lang.: English: L
Rev

Rev

Sheet: 01
ABB INDIA LTD Doc. No.: YN1M302310-CZN
No. of sh.: 01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Factory Acceptance Test Specification – Substation Automation System

REPUBLIC OF CONGO
110/33kV MOUKOUKOULOU
SUBSTATION

Substation Automation System

Factory Acceptance Test


Specification

REVISION TABLE

Rev. No Revision Note Approved Week


00 Original Document KR 22/2014

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. Copyright © by ABB Limited

110/33kV TRANSFORMER BAY EXTENSION AT EXISTING


MOUKOUKOULOU SUBSTATION IN REPUBLIC OF CONGO

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 1 (17)
Factory Acceptance Test Specification – Substation Automation System

Table of Contents:
1 General ............................................................................................................... 5

2 FAT Set Up ......................................................................................................... 6

2.1 System Architecture ..................................................................................... 6

2.2 Single Line Diagram..................................................................................... 6

2.3 Physical check FAT setup ............................................................................ 6

3 Start-up behaviour............................................................................................... 6

3.1 Start-up SAS system .................................................................................... 6

3.1.1 Windows 7 Start-up............................................................................... 6

3.1.2 Start-up MicroSCADA ........................................................................... 7

3.1.3 General interrogation ............................................................................ 7

3.1.4 MicroSCADA user login ........................................................................ 7

4 System Functions................................................................................................ 8

4.1 User authority management ......................................................................... 8

4.2 Blocking list .................................................................................................. 8

4.3 Time synchronization ................................................................................... 8

4.3.1 Synchronizing an external GPS clock ................................................... 8

4.3.2 Time synchronization at the MicroSCADA level .................................... 8

4.3.3 Time synchronization at device level .................................................... 9

4.4 Gateway for RCC ......................................................................................... 9

4.5 Printers......................................................................................................... 9

4.5.1 Event printer ......................................................................................... 9

4.5.2 Hardcopy printer ................................................................................... 9

5 SAS Graphical User Interface ........................................................................... 10


Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 2 (17)
Factory Acceptance Test Specification – Substation Automation System

5.1 Main menu ................................................................................................. 10

5.1.1 Process pictures ................................................................................. 10

5.1.2 Control system pictures ...................................................................... 10

5.2 Basic window functions .............................................................................. 10

5.2.1 Menus ................................................................................................. 10

5.3 Basic Monitoring Functions ........................................................................ 10

5.3.1 Event list ............................................................................................. 10

5.3.2 Alarm list ............................................................................................. 10

5.4 Basic control functions ............................................................................... 11

5.4.1 Single-line diagram ............................................................................. 11

5.4.2 Bay functions ...................................................................................... 12

5.4.3 Switch control handling ....................................................................... 12

5.4.4 Protection Functions ........................................................................... 13

5.4.5 Control handling SAS/RCC ................................................................. 13

5.4.6 Control priority SAS or RCC ............................................................... 13

5.4.7 Control by RCC (will be shown during SAT) ....................................... 14

5.5 Advanced Monitoring Functions ................................................................. 14

5.5.1 Uploading disturbance fault records from IED’s .................................. 14

5.5.2 Uploading manually ............................................................................ 14

5.5.3 Uploading automatically (cyclically) .................................................... 14

5.5.4 Disturbance recorder analysis ............................................................ 15

5.6 Parameter setting and reading of IED’s ..................................................... 15

5.6.1 Uploading settings from a device ........................................................ 15

5.6.2 Downloading settings to a device ....................................................... 15


Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 3 (17)
Factory Acceptance Test Specification – Substation Automation System

5.7 Measured Value Trends ............................................................................. 16

5.8 Advanced Control Functions ...................................................................... 16

5.8.1 Busbar Coloring .................................................................................. 16

6 Point-to-point test (to be done during SAT) ....................................................... 16

6.1 SAS Datapoint test bay level...................................................................... 16

6.2 Datapoint test SAS - RCC (to be done during SAT) ................................... 16

7 Reliability test (to be done during SAT) ............................................................. 17

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 4 (17)
Factory Acceptance Test Specification – Substation Automation System

1 General
Basically, this Test Instructions describe the various tests that would be carried out during the
system factory acceptance test.

Before commencing with the tests, bay units must be configured and tested; all the other
components of the control system must be installed and configured. Additional the
communication between the various units must work correctly. The station switchgear has to be
simulated with the aid of a process simulator.

To fulfil all ABB quality standards it is necessary that the test engineer has relative experience
about ABB SAS Systems and their functionality.

The following abbreviations are used in the document.

SAS – Substation Automation System


IED – Intelligent Electronic Device
HMI – Human Machine Interface
PC – Personal Computer
LAN – Local Area Network
DR – Disturbance Recorder
DMP – Dot Matrix Printer
SCADA – Supervisory Control and Data Acquisition System
RCC – Remote Control Centre
SLDC– State Load Dispatch Centre
LN – Logical Node
BCU – Bay Control Unit
GOOSE – Generic Object Oriented Substation Events
SNMP – Simple Network Management Protocol
SNTP – Simple Network Time Protocol
SLD – Single Line Diagram
DCS – Distributed Control System
GPS – Global Positioning System
LDU – Local Display Unit
SAT – Site Acceptance Test

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 5 (17)
Factory Acceptance Test Specification – Substation Automation System

2 FAT Set Up
The Factory Acceptance Tests are to be performed using IEDs of transformer bays of 110/33kV with
configurations loaded as per REPUBLIC OF CONGO-110/33kV MOUKOUKOULOU SUBSTATION
system. All protection IEDs and the Bay Control IEDs of 110.33kV transformer bay are connected to
the SAS as per the system architecture during the FAT, so that the control functions with interlocks
will be tested.

2.1 System Architecture


The system for Factory Acceptance Test shall consist of all components/Protection IEDs and Bay
control IEDs as per the system architecture. Physical connections of all components shall be
connected as per the approved system architecture. 33kV switchgear panel IED’s REF615 as per the
system architecture will be tested during SAT.

Please refer (Drawing no.YN1M302310-CZM) for the System Architecture.

2.2 Single Line Diagram


The single line diagram considered for the setup covers 110kV and 33kV switchyard.

Refer 3VIN-14-573-D2-001 Rev. 00 document for SLD.

2.3 Physical check FAT setup


Þ Check the specification of all components as per approved bill of material

Þ Check the physical connection of all components as per approved system architecture.
(33kV switchgear panel IED’s REF615 as per the system architecture will be tested during
SAT)

3 Start-up behaviour

3.1 Start-up SAS system


This section has to be repeated for each computer in the project.

3.1.1 Windows 7 Start-up


Windows 7 operating system is installed in Station HMI workstation, after switching on the
power; the following steps are processed and can be observed on the screen:

ð RAM is installed as per the BOM.


ð The BIOS is started.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 6 (17)
Factory Acceptance Test Specification – Substation Automation System

ð The operating system Windows 7 is started.

Important: No error messages may appear during the start-up process.

3.1.2 Start-up MicroSCADA


Start MicroSCADA from the SYS600 Control panel as a service, then MicroSCADA logon
screen appears on the Station HMI workstation.

The start menu provides facility for opening a large MicroSCADA monitor (window).

ð Check the entry for the license holder using the tools menu.

3.1.3 General interrogation


The general interrogation updates all the data points. This can be seen on the process displays
when the switchgear states that were previously not up to date changes to agree with the
current status of the process.

3.1.4 MicroSCADA user login


The logon and logoff procedure has to be checked for every access rights level. What functions
can be performed by the various levels is tested in the respective windows.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 7 (17)
Factory Acceptance Test Specification – Substation Automation System

4 System Functions

4.1 User authority management


With the user authority management, new MicroSCADA users can be created. For testing
reasons generate test users for each group (User Levels 0, 1 and 2).

User/Password
MicroSCADA-user level 0 ->view User0/user0
MicroSCADA-user level 1 ->control User1/user1
MicroSCADA-user level 2 ->engineering User2/user2
MicroSCADA-user level 5 ->system Manager CONGO/CONGO
ð Check the authority levels of each user mentioned above.

4.2 Blocking list


With the blocking list, events can be blocked in different ways. Check that the list is available
and do some random samples.

ð Blocking of general update for a device or a specific signal


ð Blocking of print out for a device or a specific signal
ð Blocking of Event list for a device or a specific signal
ð Blocking of alarming for a device or a specific signal
ð Blocking of control for a device or a specific signal

4.3 Time synchronization

4.3.1 Synchronizing an external GPS clock


ð Check that the aerial is connected to the GPS receiver.
ð The LED marked as “Time service” lights in Green as soon as NTP has been synchronised
to reference clock.
ð The LED marked as “Reference Time” lights in Green as soon as reference clock produce
valid time.

4.3.2 Time synchronization at the MicroSCADA level


Check the following on a system comprising Station HMI computers:

ð Change the Time on Window 7 level. The time must be corrected automatically, if Time
synchronisation is working correctly.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 8 (17)
Factory Acceptance Test Specification – Substation Automation System

4.3.3 Time synchronization at device level


The bay level devices are also synchronized directly from the GPS Clock.

ð The time synchronisation of the individual IED can be verified by as follows:

ð Change the time to different time in the LHMI. The time should be restored back to the
correct time if the IED is time synchronised with GPS receiver.

4.4 Gateway for RCC


(Full functionality will be shown during SAT)

ð Check the analog parameters and switchgear status and general tripping signal or alarm for
one of the bay with IEC- 60870-5-104 master simulator.
Note: - This test will be done with only one bay to simulate the capabilities of the gateway.
Complete test and integration with RCC will be done at site (SAT).

4.5 Printers
The SAS system has two printers connected to the Ethernet over a print server or built-in
Ethernet card. The matrix line printer is for printing alarms and logs on continuous paper.
Another printer is a laser printer to print out graphics or disturbance evaluation files. For FAT
DMP and Laser Printer will be configured and tested.

4.5.1 Event printer


ð Create an event and check that the event printer prints the event.

4.5.2 Hardcopy printer


A key combination enables hardcopies of the screen or open window to be printed.

ð Press the key combination Alt + PrtScrn to print the currently active window on the
hardcopy printer.
ð Press the key combination Ctrl + PrtScrn to print the complete screen on the hardcopy
printer.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 9 (17)
Factory Acceptance Test Specification – Substation Automation System

5 SAS Graphical User Interface

5.1 Main menu


The first thing to check is whether the distribution, marking and arrangement of the buttons and
the general appearance of the main menu corresponds to the FDS.

Check the functions of the individual buttons.

5.1.1 Process pictures


ð Check that every button opens the correct process window.

5.1.2 Control system pictures


ð Check that every overview button opens the correct overview window.

5.2 Basic window functions

5.2.1 Menus
ð Does the menu contain all the items?
ð Does the menu item open the correct windows, and do they perform the correct functions
(e.g. logoff)?
ð Do the effective access rights conform to those entered for the particular users (e.g. no
access below user level 2 for “Engineering” to “Tool manager”)?

5.3 Basic Monitoring Functions

5.3.1 Event list


The event list is an important feature of a MicroSCADA system and therefore special attention
has to be paid to it. The basic event list functions are tested in this section.

ð Initiate several events in a bay unit and check that they all appear in the event list and are
presented as specified.
ð Check the effectiveness of the most important event filter functions (perform filter operations
according to time, bay designation and alarm class).

5.3.2 Alarm list


The alarm list is also another important feature of a MicroSCADA system. Two different types
are existing:

One type is divided into two horizontal parts, the upper one called “Persisting alarms” with the
active alarms and the lower one called “Fleeting alarms” with the alarms that are no longer
Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 10 (17)
Factory Acceptance Test Specification – Substation Automation System

active, but were not acknowledged. An alarm that is no longer active and has been
acknowledged is deleted automatically from the list.

The other type of alarm list is not divided into two parts. All the alarms are entered in this list.
Whether an alarm is still active or has already been acknowledged can be seen from the colour
of the respective alarm text. The difference is that inactive and acknowledged alarms do not
disappear automatically, but only after clicking on the reset button.

Check the naming convention followed for alarms of typical bays.

Persisting and unacknowledged alarms

ð Generate events on a bay unit that have been configured as alarms and check that they
appear in the alarm list as specified.
Persisting and acknowledged alarms

ð Acknowledge a single alarm and then all alarms firstly by clicking on the corresponding
button and then via a pull-down menu.
ð Check that the alarms are presented in the alarm list as specified.
Fleeting and unacknowledged alarms

ð Generate events on a bay unit that have been configured as alarms and then reset them at
the bay unit (i.e. the alarm is not active any more).
ð Check that the alarms are presented in the alarm list as specified.
Fleeting and acknowledged alarms

ð Acknowledge the inactive alarms.


ð Check that the alarms disappear from the alarm list.

5.4 Basic control functions


It is important when checking process windows to make sure that they meet the customer’s
functional requirements.

5.4.1 Single-line diagram


ð Check both, the steady state (distribution, layout, designations and colours) and dynamic
(measurements, switching status of circuit-breakers and isolators, bus bar colours etc.)
features of the single-line diagrams and compare them with the specification.
ð Other aspects have to be compared with the specification when checking the analogue
values:
à Is the layout of the measurements correct?
à Are the units correct (e.g. A, kV, MVA)?
à Is the resolution (decimal places) of the values shown correct?
ð Generally the system includes a visual representation of control responsibility, the
appearance, layout and function of which is to be checked.
Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 11 (17)
Factory Acceptance Test Specification – Substation Automation System

5.4.2 Bay functions


A bay function refers to the signals and buttons which are defined for each feeder. Clicking on
the buttons opens a small dialogue for the particular feeder. The procedure for checking the bay
functions is as follows:

ð There is a signal below the bay local/remote button, which indicates whether control is
switched to “Local” (bay level) or “Station” (SAS). Use the Local/Remote switch on the bay
unit to check that the signal indicates the respective status correctly.
ð Provision is made in the bay for displaying a few measurements and these must also be
checked with regard to their presentation (number of places of decimals, units, order etc.)
their choice (function description) and their function.
ð Check the updating time for analogue values; any change in an analogue value has to be
updated in the SAS database within 2 seconds.
ð Check the operation of the limit monitors for which upper and lower limits and alarm settings
for the analogue signals have been set. Analogue signals in the bay control dialogue must
change to yellow colour upon exceeding the warning level and to red colour upon
exceeding the alarm level. Their colour at normal load values is white.
ð The next step is to check the correct operation of the functions in the bay control dialogue.
This involves checking the short event and alarm lists for the respective feeder.

5.4.3 Switch control handling


Selecting the symbol of a circuit-breaker or an isolator opens a “Switch control dialogue”. The
SAS always performs a switching operation in two steps, i.e. after selecting the element; the
interlocking conditions at bay level are checked first, before it is actually switched.

ð Check the operation of the switch control dialogue for typical switchgear (earth switches,
isolators and circuit-breakers) under all operating conditions.
à Check that the control is possible only when all the interlock conditions are satisfied.
Change the position of the switches in the process simulator to check this for various
conditions.
ð Check the operation of all options in the switch control dialogue for typical switchgear.
ð Check the system response time for control commands from the event list, by comparing
the time when the command was issued and when the output contact of BCU operated.
Check that the feedback on screen is within the response time specified.
ð Check the closing of the circuit breaker with synchrocheck function.
ð Check the double command blocking (Bay reservation) for switch gear.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 12 (17)
Factory Acceptance Test Specification – Substation Automation System

5.4.4 Protection Functions


These tests are carried out basically to check the integration of protection into the Substation
Automation System.

Create a fault using the test kit and check for the following:

ð Trip command is sent to the connected bay CB


ð Carrier send command
ð DR is initiated (refer section 5.5 for uploading)
ð Protection trip is in the event list

5.4.5 Control handling SAS/RCC


(Full functionality will be shown during SAT)

The control responsibility button determines whether control is being performed in the station
itself or at the network control centre. Every process window displays this button and the
associated signal.

ð Click on the control responsibility button to open the station dialogue.


ð The dialogue enables control responsibility to be switched from the station to the power
system control centre and back again.
ð Any change in the status of control responsibility must be recorded in the event list.

5.4.6 Control priority SAS or RCC


(Full functionality will be shown during SAT)

If control responsibility is set to Station, the SAS exercises full control:

ð The control responsibility signal indicates “Station”.


ð In this mode, switching operations can be initiated by the SAS, therefore check that this is
so by operating a typical switch.
ð Providing that a suitable RCC simulator (protocol simulator) is available, check that
switching operations cannot be carried out from the RCC.

If control responsibility is set to Remote, the RCC exercises full control:

ð The control responsibility signal indicates “Remote”.


ð In this mode, switching operations can be initiated by the RCC, therefore check that this is
so by operating a typical switch.
ð It must not be possible for the SAS to perform switching operations, therefore check this by
trying to operate a typical switch from SAS.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 13 (17)
Factory Acceptance Test Specification – Substation Automation System

5.4.7 Control by RCC (will be shown during SAT)


Control by the RCC can only be checked, if there is an RCC or a simulator available.

Check the switching sequence of isolators and circuit-breakers under all operating
configurations when controlled by the RCC.

5.5 Advanced Monitoring Functions

5.5.1 Uploading disturbance fault records from IED’s


Disturbance recorder data are only recorded if the bay units have been configured to do so.
There are two ways of uploading disturbance recorder data from a bay unit to PCM600, i.e. to
the hard disc of the DR Laptop

5.5.2 Uploading manually


ð Generate a protection trip by injecting an input variable into a protection relay (REL670).
ð Open the PCM600 Open Disturbance Handling (DRH) tool in PCM600
ð Click Get Recordings Information to start the dialog with the IED.
ð A list of all actual available DRs in the IED is displayed.
ð Select the desired recording and then right-click and choose read from the IED.
ð The recording is now read from the IED to the DR system.
ð As soon as the upload operation finishes you can refresh the list of recordings in the tool.
ð Now the file is available in the DRH tool and you can generate a report or choose to export
the recording.

5.5.3 Uploading automatically (cyclically)


A sequence to create a list of jobs to monitor IEDs would be as follow:

ð Start a project or it might be already started


ð Start Scheduler tool
ð Select Task Manager icon and choose Add Task
ð To add a task is always possible
ð Do the task configuration in the configuration window to your demand
ð Select Task icon and choose Add Object Job
ð Do job configuration. Select job variant and tool for the job
ð Choose Enable Task
ð Now generate a disturbance in the IED and verify that the operation specified in the Job is
done.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 14 (17)
Factory Acceptance Test Specification – Substation Automation System

ð Check the settings in the “Automatic upload” dialogue and if necessary reset the interval for
cyclically uploading disturbance recorder files.

5.5.4 Disturbance recorder analysis


The disturbance recorder data can be evaluated and graphically presented with the aid of an
evaluation program (e.g. Wavewin).

ð On an uploaded recording, select Open with…


ð Now specify with what tool you want to open the recording (Wavewin ), specify the path to
Wavewin
ð Click OK, The specified Tool should start opening the selected recording.

5.6 Parameter setting and reading of IED’s


The DR Laptop is used for reading and setting the parameters of the relays.

5.6.1 Uploading settings from a device


ð Start PCM600
ð Browse down to the IED in the plant structure
ð Right-click and choose Parameter Setting
ð In the plant structure, you can browse the functions of the IED
ð On any level, you can read settings from the IED. Choose a suitable function and Choose
Read from IED.
ð The Settings for the selected function are now read from the IED.

5.6.2 Downloading settings to a device


ð Change some of the settings read in test case above.
ð Select Write to IED, Choose all parameters in the dialog window.
ð All settings for the function are now written to the IED.
ð Upload the set of settings again (see above) and check whether the setting is really
changed.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 15 (17)
Factory Acceptance Test Specification – Substation Automation System

5.7 Measured Value Trends


ð Check that all required measurements (according customer’s specification) are configured.
ð Check the scaling by injecting the corresponding analog value to the BCU.
ð Measurement reports will be shown during SAT
ð Check the Trends for one analog measurement of one bay.

5.8 Advanced Control Functions

5.8.1 Busbar Coloring


With this additional feature, the busbar segment changes its colour depending on the state (e.g.
earthed, energized, de-energized). The colours have to be defined

ð Check the defined colours.


ð Check the functionality with random samples (Switching operations and injecting voltages)

6 Point-to-point test (to be done during SAT)


6.1 SAS Datapoint test bay level
The point-to-point test checks every single data point in the bay units. Each can influence one
or several of the listed functions or MicroSCADA components and therefore has to be tested.

ð Screens: All dynamic states must reflect the actual status of the process.
ð Event list: All items of process plant with defined HA and HE attributes must appear in the
event list.
ð Printers: The event printer must print all items of process plant with defined LD and PA
attributes.
ð Alarm list: All items of process plant with defined AC and AG attributes must appear in the
alarm list. Important: The status values 0 and 1 correspond to the status messages
“Normal” and “Alarm” respectively.
ð Analogue values: The scaling and resolution of all analogue process values must
accurately reflect the respective analogue process data.
ð Event channel: Check that all items of process plant with an event channel attached can
execute the attached command procedures.

6.2 Datapoint test SAS - RCC (to be done during SAT)


A database point test requires a connection to the respective protocol converter and an RCC or
simulator. The purpose of the test is to check the transfer of the various database point types in
both directions between the RCC and bay levels, i.e. not every signal is checked as is the case
with a full point-to-point test.

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 16 (17)
Factory Acceptance Test Specification – Substation Automation System

The communication is tested first from the bay level to the power system control level:

ð Change the positions of a number of switches and check that the new positions are
transmitted to the RCC (DB).
ð Change a few analogue input variables in steps (0%, 50%, 100%, 110%, 20%, 5%, 0%)
and check that the new values are properly scaled and transmitted to the RCC (AO).
ð Generate a few events at bay level, e.g. a protection trip, and check that the corresponding
events are transmitted to the RCC (BO).
ð Now check the communication from the system control level to the bay level.
ð Send a few switching commands from the RCC and check that the correct switching
operations are carried out at bay level. Repeat the test for other items of switchgear (BI).

7 Reliability test (to be done during SAT)


The purpose of this test is to observe the system in state of rest. The duration of the test should
be at least 48 hours. practically the test is carried out over the weekend (Friday evening until
Monday morning). During this test measurement values must be injected (one field unit).

No disturbance on communication level should appear.

ð No wrong or inexplicable signals in alarm list, event list or on printer.


ð Communication to bay level without any disturbance.
ð Communication to RCC without any disturbance.

End of the document

Document
FAT Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
29-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZFA 17 (17)
Functional Design Specification – Substation Automation System

REPUBLIC OF CONGO
110/33kV MOUKOUKOULOU
SUBSTATION

Substation Automation System

Functional Design Specification


REVISION TABLE

Rev. No Revision Note Approved Week


00 Original Document KR 22/2014

110/33kV TRANSFORMER BAY EXTENSION AT EXISTING


MOUKOUKOULOU SUBSTATION IN REPUBLIC OF CONGO

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. Copyright © by ABB Limited

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 1 (39)
Functional Design Specification – Substation Automation System

Table of Contents:
Table of Contents: .................................................................................................... 2

1 About This Document ........................................................................................... 5

1.1 General ................................................................................................. 5

1.2 Abbreviations ........................................................................................ 6

2 Introduction ........................................................................................................... 7

3 System Design ...................................................................................................... 8

3.1 System Architecture .............................................................................. 8

3.1.1 Station Level ......................................................................................... 8

3.1.2 Bay Level .............................................................................................. 9

3.2 110/33kV Transformer bays................................................................ 10

3.3 33kV Feeder bays ............................................................................... 12

3.5 Bay Level human machine interface (IHMI) ........................................ 13

3.6 Station Level Functions....................................................................... 14

3.6.1 Application server (Station HMI) cum Gateway .................................. 15

3.6.2 Communication Infrastructure ............................................................. 15

3.6.3 Time Synchronization ......................................................................... 16

3.6.4 Disturbance Evaluation Laptop ........................................................... 16

3.7 Operator Interface functions ............................................................... 16

3.7.1 User login............................................................................................ 17

3.7.2 Logout ................................................................................................. 17

3.7.3 Application Settings ............................................................................ 18

3.7.4 User Management .............................................................................. 20


Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 2 (39)
Functional Design Specification – Substation Automation System

3.7.5 Process Display .................................................................................. 21

3.7.6 Event List ............................................................................................ 28

3.7.7 Alarm List ............................................................................................ 31

3.7.8 Blocking List........................................................................................ 34

3.7.9 Trend Application ................................................................................ 36

3.7.10 System Self Supervision ..................................................................... 39

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 3 (39)
Functional Design Specification – Substation Automation System

Table of Figures:
Figure 1: Bay Level HMI ........................................................................................... 13

Figure 2: Monitor Pro Login dialog (Typical)............................................................. 17

Figure 3: Application setting dialog........................................................................... 19

Figure 4: Example of Authorization profile................................................................ 20

Figure 5: SLD Typical ............................................................................................... 22

Figure 6: Station Local / Remote control dialog........................................................ 23

Figure 7: Bay Local / Remote control dialog............................................................. 24

Figure 8: Switch control dialog (Select Before Operate)........................................... 25

Figure 9: Switch control dialog (expanded) .............................................................. 26

Figure 10: Tap changer control dialog ...................................................................... 27

Figure 11: Event List ................................................................................................ 28

Figure 12: Event list settings .................................................................................... 30

Figure 13: Event list filter settings............................................................................. 30

Figure 14: Alarm List (Template 1) ........................................................................... 31

Figure 15: Alarm List (Template 2) ........................................................................... 32

Figure 16: Alarm list settings .................................................................................... 33

Figure 17: Blocking List ............................................................................................ 35

Figure 18: Trend picture (Graphical Form) ............................................................... 36

Figure 19: Trend picture (Tabular Form) .................................................................. 37

Figure 20: Trend basket ........................................................................................... 38

Figure 21: Example of System Supervision picture .................................................. 39

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 4 (39)
Functional Design Specification – Substation Automation System

1 About This Document


1.1 General
This document describes the features of the Substation Automation System
(SAS) for REPUBLIC OF CONGO-110/33kV MOUKOUKOULOU
SUBSTATION.

The SAS provides facility to control and monitor all the equipment in the
substation locally as well as remotely. The software or hardware described in
this document is furnished under a license and may be used, copied, or
disclosed only in accordance with the terms of such license.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 5 (39)
Functional Design Specification – Substation Automation System

1.2 Abbreviations
The following abbreviations are used in the document.
SAS – Substation Automation System
IED – Intelligent Electronic Device
HMI – Human Machine Interface
PC – Personal Computer
LAN – Local Area Network
DR – Disturbance Recorder
DMP – Dot Matrix Printer
SCADA – Supervisory Control and Data Acquisition System
RCC – Remote Control Centre
SLDC – State Load Dispatch Centre
LN – Logical Node
BCU – Bay Control Unit
GOOSE – Generic Object Oriented Substation Events
SNMP – Simple Network Management Protocol
SNTP – Simple Network Time Protocol
SCIL – Supervisory Control Implementation Language
SLD – Single Line Diagram

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 6 (39)
Functional Design Specification – Substation Automation System

2 Introduction
The SAS is based on ABB make MicroSCADA Pro software running in a
industrial PCs with Microsoft Windows 7 Operating System.

The SAS conforms to IEC 61850 standards and has a decentralized


architecture consisting of the following main functional parts:

§ Application server (Station-HMI) cum Gateway (Gateway for remote


communication to Remote Control Centre (RCC) communicating on
IEC 60870-5-104)

§ Intelligent Electronic Devices (IED) for bay control and monitoring

§ Intelligent Electronic Devices (IED) for bay and station protection

§ Managed switched fiber-optic Ethernet LAN in single fault tolerant ring


architecture

§ Laptop for Disturbance Recorder (DR) evaluation.

§ Dot Matrix Printer for alarms and events printing.

§ A4 Laser color printer.

§ One GPS receiver is provided to synchronize the time of SAS including


the IEDs for protection and control.

The SAS provides an extensive range of Supervisory Control and Data


Acquisition (SCADA) functions.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 7 (39)
Functional Design Specification – Substation Automation System

3 System Design
The SAS is designed considering the functional requirements of Technical
Specification, along with the pre-bid clarifications and the deviations we had
taken in our offer with relevant sections of specification.

The SAS is suitable for operation and monitoring of the complete 110/33 kV
Moukoukoulou substation. It supports remote control and monitoring from
RCC through Communication Gateways using IEC 60870-5-104 protocol.

The SAS comprises full station and bay protection as well as control,
monitoring and communication functions and provides all functions required
for the safe and reliable operation of the 110/33 kV Moukoukoulou Substation.

3.1 System Architecture


For safety and availability reasons the SAS is based on a decentralized
architecture and on a concept of bay-oriented, distributed intelligence.
Functions are decentralized, object-oriented and located as close to the
process as possible.

The SAS layout is structured in two levels:

§ Station level

§ Bay level.

Please refer the system architecture YN1M302310-CZM.

3.1.1 Station Level


A PC based HMI enables local station control through the software package
MicroSCADA Pro, which contains an extensive range of SCADA functions.

The communication inbuilt gateway enables the information exchange with


RCC. The inter-bay bus provides independent station-to-bay and bay-to-bay
data exchange.

The system can be extended both physically and functionally without affecting
the original application. It has a unique user-friendly definition language
(SCIL) that facilitates integration of the system by the users themselves,
without detailed knowledge of real-time systems.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 8 (39)
Functional Design Specification – Substation Automation System

An authorization mechanism prevents system access to unauthorized users


and allows assignment of a number of authorization levels. This makes
certain functions accessible only to those users who have the required level of
authorization.

All alarm and event logs will be printed out on the dot matrix printer. The
reports and graphics will be printed on the Laser printer connected to the
system over the Ethernet LAN.

A dedicated GPS master clock is provided for the synchronization of the entire
system. This master clock is independent of the station computers and
gateways, and it synchronizes all devices via the inter-bay bus.

3.1.2 Bay Level


A bay comprises of one circuit breaker and associated disconnectors, earth
switches and instrument transformers. At bay level, the IEDs provide all bay
level functions like control (command outputs), monitoring (status indications,
measured values) and protection. The IEDs are directly connected to the
switchgear without any need for additional interposing or transducers.

Each bay control IED is independent of the others and its functioning is not
affected by any fault occurring in any of the other bay control units of the
station.

The data exchange among bay level IEDs, and between bay level and station
level take place via the fiber-optic inter bay bus according to IEC 61850-8-1
standard. The use of fiber-optic LAN guarantees disturbance-free
communication.

Though, at station level, the entire station is controlled and supervised from
the station HMI, it is possible to control and monitor the bay from the bay level
equipment, whenever required. The decentralized architecture ensures that
station wide interlocking is available even when the station computer fails.

Clear control priorities prevent the initiation of simultaneous operation of a


single switch from more than one of the various control levels, i.e. RCC,
station, bay level or apparatus level. The priority is on the lowest enabled
control level. The operation also depends on the status of other functions like
interlocking, synchrocheck, etc., as applicable.

Ethernet switches are provided for connecting the IEDs in the bay level
catering the specification requirements. The connection from each IED to the
switch is by a single fiber optic link. The switches are connected in a ring for
single fault tolerance.
Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 9 (39)
Functional Design Specification – Substation Automation System

In a decentralized architecture the functionality is provided as close to the


process as possible. In this respect, the following functions are allocated at
bay level:

§ Bay control and monitoring functions

§ Bay protection functions

A process bus is not used and the connections from the bay level to the
process are hardwired. The details of the functions provided for the individual
bays and at the station level are described below.

3.2 110/33kV Transformer bays


The following functions (Logical Nodes, or LN, as defined in IEC 61850) are
required for Transformer bay

1. ABB Make REC670 will be used as a Bay Control Unit cum Protection
(BCPU) with the following functions

§ Breaker and isolator control (CSWI,XSWI,XCBR)

§ Bay level and inter bay interlocks (CILO)

§ Measurement of voltages, currents, active and reactive power (MMXU)

§ Local HMI (LHMI)

§ Trip Circuit Supervision

§ Fuse failure supervision (RFUF, 60)

§ Instantaneous Over current Protection (PIOC, 50)

§ Instantaneous Earth Fault Protection (PIEF, 50N).

§ IDMT Over current Protection (PTOC, 51)

§ IDMT Earth Fault Protection (PTEF, 51N)

§ Directional Over current Protection (PDOC, 67)

§ Directional Earth Fault Protection (PDEF, 67N).

§ Breaker Failure Protection (RBRF, 50BF)

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 10 (39)
Functional Design Specification – Substation Automation System

§ Disturbance Recording, bay level acquisition (RDRE), with 8 analog


and 16 digital

§ Sequential event recorder (RDRE) with time resolution of 1 ms

2. ABB Make RET650 will be used for Transformer protection with the
following functions

§ Transformer differential protection (PDIF, 87T)

§ Restricted Earth Fault Protection (PDIF, 64R)

§ Disturbance Recording, bay level acquisition (RDRE), Sequential event


recorder (RDRE) with time resolution of 1 ms

As per IEC 61850, the primary equipment’s are also represented as LNs, and
the ones used in this bay are:

§ Circuit breaker (XCBR)

§ Isolators (XSWI)

§ Earth switches (XSWI)

§ Current Transformer (TCTR)

§ Voltage Transformer (TVTR)

Since process bus (IEC 61850-9-2) is not used, these LNs are hardwired
inputs and outputs of the control and protection IEDs. XCBR and XSWI
represent the status inputs from, and command outputs to the breaker and
isolators. TCTR and TVTR are the current and voltage inputs respectively
from the instrument transformers.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 11 (39)
Functional Design Specification – Substation Automation System

3.3 33kV Feeder bays


The following functions (Logical Nodes, or LN, as defined in IEC 61850) are
required for 33kV Incomer bays

ABB Make REF615 will be used as a Bay Control Unit cum Protection (BCPU)
with the following functions. (Supply of REF615 is part of 33kV switchgear
panels)

§ Breaker and isolator control (CSWI,XSWI,XCBR)

§ Bay level and inter bay interlocks (CILO)

§ Measurement of voltages, currents, active and reactive power (MMXU)

§ Local HMI (LHMI)

§ Directional Over current Protection (PDOC, 67)

§ Directional Earth Fault Protection (PDEF, 67N).

§ IDMT Over current Protection (PTOC, 51)

§ IDMT Earth Fault Protection (PTEF, 51N)

§ Disturbance Recording, bay level acquisition (RDRE), with 8 analog


and 16 digital

§ Sequential event recorder (RDRE) with time resolution of 1 ms

As per IEC 61850, the primary equipment’s are also represented as LNs, and
the ones used in this bay are:

§ Circuit breaker (XCBR)

§ Isolators (XSWI)

§ Earth switches (XSWI)

§ Current Transformer (TCTR)

§ Voltage Transformer (TVTR)

Since process bus (IEC 61850-9-2) is not used, these LNs are hardwired
inputs and outputs of the control and protection IEDs. XCBR and XSWI
represent the status inputs from, and command outputs to the breaker and

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 12 (39)
Functional Design Specification – Substation Automation System

isolators. TCTR and TVTR are the current and voltage inputs respectively
from the instrument transformers.

3.5 Bay Level human machine interface (IHMI)


The local human machine interface is equipped with an LCD that can display
the single line diagram with up to 9 objects. The local human-machine
interface is simple and easy to understand – the whole front plate is divided
into zones, each of them with a well-defined functionality:

§ Status indication LEDs

§ Alarm indication LEDs consisting of 6 red LEDs and 9 yellow LEDs with
user printable sticker. All LEDs are configurable from the PCM600 tool.

§ Liquid crystal display (LCD).

§ Keypad with push buttons for control and navigation purposes, switch
for selection between local and remote control, reset and an isolated
RJ-45 communication port.

Figure 1: Bay Level HMI

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 13 (39)
Functional Design Specification – Substation Automation System

3.6 Station Level Functions


The hardware of the station level system provided for the control room
consists of the following:

§ Application server (Station HMI) cum Gateway (Remote


Communication to RCC)

§ Fiber optic Ethernet LAN for station level and inter bay communication

§ A GPS receiver as the time master

§ Disturbance evaluation workstation (Laptop)

§ Dot matrix printer (DMP) for alarms and events printing

§ Laser Printer for printing graphics and reports

The station level functions (Logical Nodes) provided are:

§ Operator Interface (IHMI)

§ Remote Control Interface (ITCI)

§ Archiving (IARC) for long term historical data

§ Disturbance data evaluation (RDRS)

§ Time Master (STIM)

§ System supervision (SSYS)

Full station level HMI include full graphic screens, special user functions such
as station single line diagram, overviews, control of circuit breakers and
isolators, alarm lists and event lists, logging of historical data for trends and
reports.

The system will be controlled with the help of a mouse and keyboard. If
required, system engineering can also be done from the Station HMI. All
alarm and event logs will be printed out on the dot matrix printer. The reports
and graphics will be printed on the Laser printer.

The communication to the RCC uses IEC 60870-5-104 protocol, with the
remote control center as the master and the local gateway as the slave. It is
possible to control and monitor the local station from the remote control
center, with no priority being assigned to either of them. The communication
Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 14 (39)
Functional Design Specification – Substation Automation System

media from Moukoukoulou substation to the Remote control centers is to be


provided by customer.

3.6.1 Application server (Station HMI) cum Gateway


The Application server consists of industrial PCs running with Windows 7
operating system.

The station HMI’s consists of industrial PCs with Window 7 operating system.
Monitoring and controlling of the station is through 22” TFT monitors by the
use of project specific pictures. A mouse is used to move the cursor and thus
navigate on and between picture pages. The PCs work on 230 V AC power
supply.

The operator interface is based upon a hierarchical set of menu pages, which
provide access to overview, alarm list, event list and other pages. An
authorization mechanism prevents system access of unauthorized users and
also allows assignment of a number of authorization levels. This makes
certain functions accessible only to users who have been granted the required
level of authorization.

3.6.2 Communication Infrastructure


The communication infrastructure consists of a fiber optic, managed, switched
Ethernet LAN in a fault tolerant ring configuration. This LAN is used for both
station level and inter-bay communications. The communication protocol
conforms to IEC 61850-8-1 standard. Ethernet switch is provided, with the
IEDs connected to the switch using fiber optic cables. The main features of
the Ethernet switches used are listed below:

§ High speed (100 Mbps) operation

§ Glass fiber optic cables with LC connectors

§ Designed for harsh environment – exceeds IEC 61850-3 requirements


for use in electrical substations

§ Operates up to a temperature of 60°C without the use of fans

§ Full compliance with IEEE 802.3 and IEEE 802.3u Ethernet standards
for universal interoperability

§ Rapid Spanning Tree (IEEE 802.1w) for fault tolerance with fast
recovery times (<5ms)

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 15 (39)
Functional Design Specification – Substation Automation System

§ Quality of service / Class of service (IEEE 802.1p) for prioritization of


traffic (real time traffic for software interlocks)

§ Virtual LAN (IEEE 802.1Q) for traffic segregation

§ SNMP for network management

§ SNTP for time synchronization of the Ethernet switches

3.6.3 Time Synchronization


The time master is a GPS receiver provided in the SAS. The GPS receiver is
connected to the Ethernet LAN and it synchronizes all the IEDs, the
redundant HMIs and the remote communication gateways directly. In
conformance with the IEC 61850 standards, SNTP protocol is used for time
synchronization function.

3.6.4 Disturbance Evaluation Laptop


A Laptop running Windows 7 operating system along with the disturbance
evaluation software acts as the DR workstation. The application server
automatically downloads the DR data from the IEDs. The downloading of DR
data can also be done manually on operator’s request.

The operator or protection engineer can access these DR files and analyze
them using the DR evaluation software. The disturbance waveforms are
printed on the color laser printer.

3.7 Operator Interface functions


The operator interface is based on MicroSCADA Pro (SYS600) software that
runs on Windows 7 operating system. SYS 600 software consists of the basic
functions needed to monitor and control substations.

Application pictures are used to visualize the supervised processes. There are
many different types of application pictures: single line diagrams, process
pictures, system supervision, lists, application tools, measurement reports and
trend reports. Generally, only one application picture is presented within one
monitor (Monitor Pro). The opening of another function closes or hides the
previous one. However, several monitors can be opened to the same
application. Each user can modify the layout of Monitor Pro. The user specific
layout is saved when the user logs out and it is loaded when the user logs into
the application.
Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 16 (39)
Functional Design Specification – Substation Automation System

The system specific start picture is the first picture displayed when Monitor
Pro is started. When Monitor Pro starts, it requires login before the session
can continue, The Close button in the login dialog closes the login dialog but
not Monitor Pro.

Figure 2: Monitor Pro Login dialog (Typical)

3.7.1 User login


In the login dialog, there is a combo box, in which the current "HOT"
applications are shown. The start picture requests a user name and
password. Each user is associated with a certain user profile defined by the
system manager.

The password is not displayed on the screen. If the user name and the
password do not match, or the user name does not exist, the login dialog
reappears and you can make a new attempt. Each attempt to log in is
registered by the system, even those that are failed.

If the login succeeds, the substation overview picture is produced on the


screen. All operations subsequently performed on the Monitor Pro, are related
to the authority profile associated with the user name. The user name is also
included in as an identifier in the event register when certain manual
operations are performed.

3.7.2 Logout
In Monitor Pro, logout means that the user name and user authority are
cleared. The user is logged out when:

§ The user logs out using the Main/Logout menu item

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 17 (39)
Functional Design Specification – Substation Automation System

§ Monitor Pro is closed down by using the Close button or the Main/Exit
menu item

§ Automatic time based logout is done by Monitor Pro

§ The MicroSCADA application state is changed from "HOT" to "WARM"


or "COLD"

§ The MicroSCADA OPC DA server or MicroSCADA service is stopped

3.7.2.1 Time Base Logout


After a certain predefined time, e.g. 8 hours, an automatic logout is done. The
logout duration is defined in the Application Settings, i.e. the setting is user
specific. The user has to login again via the Login dialog.

3.7.3 Application Settings


An Application Settings picture can be given new settings by selecting
Options-Settings in the main menu bar. Only a user with rights on level 5
(system manager) can change the application settings. It is used to create
some application specific settings such as:

§ Application owner: the name of the customer to whom this product is


licensed (in this case – REPUBLIC OF CONGO). The name of the
application owner cannot be changed in the Application settings
picture.

§ First picture shown after login: defines the first picture that pops up
after a user logs in.

§ System location: this defines whether the MicroSCADA is running as a


Remote Control Centre (RCC) or a Substation Control System (SCS).

§ Lockout duration: this sets the session length. When the lockout
duration time expires, the authorization level is reset to View (0). The
lockout duration time is given in hours (from 1 to 254). The session
duration can be activated or deactivated.

§ Show object ID: this defines the parts of the Object Identity attributes
that are to be shown in Alarm lists, Event lists and dialogs.

§ HD space alarm: Hard Disk Supervision function supervises the free


Hard Disk space. This function gives the operator an early warning if

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 18 (39)
Functional Design Specification – Substation Automation System

there is a risk of running out of space on the hard disk. The supervision
function is stopped when the limit is set to zero.

§ Report Settings: this is used to define, among others, the base period
for the reports (15, 30 or 60 minutes) and the history length (1 year to 5
years). These settings are valid for the entire application and changing
these later will erase the existing history data.

The application settings being used for this project are:

§ Application owner – REPUBLIC OF CONGO

§ First picture – Substation overview (110/33 kV)

§ System location – Substation Control System

§ Lockout duration – 8 hours

§ HD space alarm – 100 MB

§ Report settings – base period: 60 minutes, history length: 2 years

Figure 3: Application setting dialog

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 19 (39)
Functional Design Specification – Substation Automation System

3.7.4 User Management


The user with rights on level 5 (system manager) can make changes in the User
Management function. In the SYS600 applications the standard functions in the
process pictures can be freely grouped into authorization groups. This means that a
user can have different authorization levels for different apparatus. Users can also
be defined to have different authorization levels for different tools, substations etc.

Figure 4: Example of Authorization profile

§ View (0) level: The user is allowed to view the substation status, but is
not authorized to make any control operations, or to use the
programming and system configuration tools.

§ Control (1) level: The user is allowed to make control operations, but
he has no access to the engineering and system configuration tools.

§ Engineering (2) level: The user is granted all rights for control,
engineering and system configuration, except system management.

§ System management (5) level: The user is granted all rights including
the rights to add and remove users. Only one user can be granted this
authorization level.

The number of users and their authorization levels will be decided during the
detailed engineering stage. The system manager can add and remove users
and user groups as well as change the authorization levels. All users can
change their own passwords.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 20 (39)
Functional Design Specification – Substation Automation System

3.7.5 Process Display


The Process Display is a view, which is displayed when the user is logged
into an application. The process displays appear on the MicroSCADA Pro
Monitor. They contain information on the status of the process in the form of
Single Line Diagrams (SLD) having graphical objects with dynamic behavior.
Process displays in the MicroSCADA Pro Monitor contain the functionality for
zooming, panning and de-cluttering of displays.

The user interacts with the MicroSCADA system through the control dialogs
accessed from the process display. Only those users, who belong to certain
user groups, are allowed to execute control operations towards the process
devices of the MicroSCADA system.

The SAS will have the 110/33kV substation SLD as the main process display.
The substation SLD will have the following information.

§ Status of all circuit breakers and isolators

§ Bus voltages and frequency

§ Line current, voltage, active power, reactive power and power factor

§ Transformer tap position

§ Control mode (Station/Remote) of the substation

§ Control mode (Local/Remote) of each bay

§ Bus bar coloring to identify powered, non-powered and earthed


segments of the SLD

It is also possible to control the switchgears and the transformer tap position
from this picture. Further, it provides access to other pictures like event list,
alarm list, trends and reports.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 21 (39)
Functional Design Specification – Substation Automation System

Figure 5: SLD Typical

3.7.5.1 Display Builder


Display Builder is the picture editor in MicroSCADA that is used to create
complete graphical interfaces. You can define the graphical appearance of
objects in your interface, describe the data they will display, and specify their
dynamic behavior. The drawing process requires no programming. Drawings
are easy to create and edit directly in the drawing area, and dialogs let you
control all aspects of the editing process, including assigning display
characteristics and specifying how your data is stored. Display Builder
provides default values for every dynamic element of a drawing so you can
quickly construct a complete dynamic drawing that can monitor and control
substations as well as electrical power transmission and distribution systems.

3.7.5.2 Station Local/Remote control


The station local/remote control shows whether the control is authorized from
the station locally or from an external control centre.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 22 (39)
Functional Design Specification – Substation Automation System

Figure 6: Station Local / Remote control dialog

This control dialog has three tabs; Main tab, Message tab and Blocking tab.
Main tab lets you select the Local/Remote option. The options available
depend on object configuration. Unavailable options are dimmed. In
Messages tab, different messages concerning the object are shown. In
Blocking tab, different blockings concerning the process object are shown and
controlled.

3.7.5.3 Bay Local/Remote control


The Bay L/R control shows the whether the control of the bay is authorized
from the bay unit locally or remotely over a communication link. If the Bay L/R
switch is remotely controllable, it is possible to change the switch state from
the control dialog.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 23 (39)
Functional Design Specification – Substation Automation System

Figure 7: Bay Local / Remote control dialog

This control dialog has three tabs; Main tab, Message tab and Blocking tab.
Main tab lets you select the Local/Remote option. The options available
depend on object configuration. Unavailable options are dimmed. In
Messages tab, different messages concerning the object are shown. In
blocking tab, different blockings concerning the process object are shown and
controlled.

3.7.5.4 Switch control


Switch control dialogs can be used to show current state and status of a
switch device object. It is also used for operating the switch device. The same
dialog is used for circuit breakers and isolators. There are several tabs on this
dialog. Navigate between the tabs navigation by using the arrow buttons on
the upper-right corner of the dialog.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 24 (39)
Functional Design Specification – Substation Automation System

Figure 8: Switch control dialog (Select Before Operate)

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 25 (39)
Functional Design Specification – Substation Automation System

Figure 9: Switch control dialog (expanded)

Main tab

The upper field of the main tab shows the object identification: station, bay
and the object. The lower field of the tab shows the object status. If control is
not blocked, the Close button or Open button is active. If, based on the
interlock conditions, the selection of the control command is successful, the
Execute or Cancel symbol buttons become active. Confirm the control
operation by clicking the Execute button. Cancel the selection by clicking the
Cancel symbol button. Possible errors during operation appear in the Object
status field of the Switch state tab. Close the dialog by clicking Exit or click
the icon on the upper-right corner of the dialog.

Blocking tab

In the Blocking tab of the Switch control dialog, different blockings concerning
the process objects are displayed.

Forced operation tab

In the Forced operation tab, the internal blockings and control blockings can
be bypassed. After this, the Open and Close buttons are enabled. However,
Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 26 (39)
Functional Design Specification – Substation Automation System

this does not disable any interlocking’s or other IED measures, that is, no
special bypass messages are sent to the IEDs.

3.7.5.5 Transformer voltage control


Transformer Tap changer control dialog shows the current state of the
transformer tap position, and can be used for operating it as well.

Figure 10: Tap changer control dialog

The identification information (station, bay, object) is shown on the upper field
of the Main tab. The options available depend on object configuration, while
the unavailable options are dimmed. Voltage or tap position can be controlled,
if the configuration and status allow it. You can control the voltage and tap
value by using the Lower and Raise buttons. In this dialog, you can see the
current values of tap position and voltage as well. Close the dialog by clicking
the Exit button or by clicking the icon on the upper-right corner of the dialog.

In the Messages tab, different messages concerning the object are shown. In
blocking tab, different blockings concerning the process objects are shown
and controlled.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 27 (39)
Functional Design Specification – Substation Automation System

3.7.6 Event List


Event is a wide term that also comprises alarms. The event activation and
consequential actions are defined in the process database separately for each
individual object.

Figure 11: Event List

The purpose of the Event List is to provide the user with information about
events occurring in the system. It is also provides information about activities
carried out by other users, operations of objects, acknowledging of alarms,
editing of limit values, logging in and so on.

The Event List presents the data in a structured way for the user’s
convenience. Each event is presented by displaying an event text line, which
consists of a time stamp, object identification, a signal text and a text
indicating the status.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 28 (39)
Functional Design Specification – Substation Automation System

3.7.6.2 Features of Event List


§ Scroll intervals are configurable from 10 to 100 pages, in steps of 10

§ Fast navigation using the scroll bar: jump to the last page, one page
back or forward and so on.

§ Possibility to navigate to the previous day or next day or to a day typed


into the input dialog

§ User-friendly filters and color settings

§ Updating/Frozen presentation modes

§ Additional comments can be given to the events (up to 250 characters


per event)

§ Printing of Events on demand

§ Possibility to display events either in log order or event order

§ Color settings

§ Find

§ Column sort

If the Event List is in the updating mode, the list will be updated when a new
event occurs in the system. When the list is in the frozen mode (non-
updating), a message will be displayed informing the user to change the mode
to the updating mode and view the latest events.

When the Event List is in the updating mode, half a page will be shown when
the list is presented on the screen. All the new events are presented on the
remaining half a page until the page is full. When the page is full, it scrolls up
a half page and new events begin to fill the page again.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 29 (39)
Functional Design Specification – Substation Automation System

Figure 12: Event list settings

When the Event List is in the updating mode, the events are sorted in the
order which they were written into history database, i.e. logging order. The
order defined in the Settings dialog is applied in the frozen mode.

It is possible to configure certain events to use different colors in the Event


List. This improves the possibility to locate certain system events. E.g.
important events, which cause alarms in the system, can be defined to use
the red color in the Event List.

Figure 13: Event list filter settings

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 30 (39)
Functional Design Specification – Substation Automation System

Filters are used when the user wants to display or concentrate on specific
information. It is possible to change the existing filters or add new filters that
can be stored and reused by other operators.

By clicking the left mouse button on a column header in the event list, the
event list is sorted on the column clicked. If the same column is clicked twice,
the sorting is descending. After the data is sorted, the list is set to Frozen
mode. Column sort is reset when the list mode is changed back to Update.

The Find tool allows the user to search for text within the current event list
view. The Find tool searches the list from the start to the end. If an event line
contains the desired text, it is selected. A message box appears when find
has reached the end point of the search or when searched text is not found.

3.7.7 Alarm List


The Alarm List displays a summary of the present alarm situation of the
supervised process. Each alarm is presented as an alarm text line, which has
a time stamp, an object id, an object text, a text indicating the alarm status, as
well as a number ranging from 1-7 indicating the alarm class.

Figure 14: Alarm List (Template 1)

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 31 (39)
Functional Design Specification – Substation Automation System

Figure 15: Alarm List (Template 2)

The process alarms are alarms that are related to the supervised process, for
example, measurement values exceeding or going below the preset alarm
limits, breakers tripping or getting into a faulty position and so on.

The internal alarms are alarms caused by the network control system itself.
Reasons for these alarms include communication problems between a
communication unit and substation, printer device errors, substation getting
suspended, etc.

3.7.7.2 Features of Alarm List


§ Two types of Alarm List templates

§ User-friendly filters

§ Alarm List setting tool for colors and text layout

§ Color and text layout settings

§ Updating/Frozen presentation modes

§ Alarm acknowledgement

§ Alarm reset function

§ Locate Object

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 32 (39)
Functional Design Specification – Substation Automation System

§ Column sort

§ Find

Figure 16: Alarm list settings

3.7.7.3 Alarm acknowledgement


An acknowledgement of an alarm is a way to show that the operator has
registered and identified the alarm. Generally, acknowledging an alarm does
not affect the alarm state. An unacknowledged alarm remains in the alarm
buffer until it is acknowledged, even if the alarm state has passed.

3.7.7.4 Alarm Blocking


Alarm blocking blocks a signal in such a way that it cannot generate an alarm.
(The same implies for history blocking, printout blocking and reprocessing
blocking.) Since the alarm is blocked, it is not registered in the process
database when the process object gets into an alarm generating state.

3.7.7.5 Alarm classes


The alarms can be grouped into seven equally significant alarm classes. This
feature can be used when the user wants to group alarms caused by process
objects with common properties. From the system point of view there is no
internal priority between the different alarm classes. The alarm classes can
Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 33 (39)
Functional Design Specification – Substation Automation System

also be used when searching alarms from the alarm buffer. By setting the
alarm class to 0, the alarm function of a process object is set off.

Filters are used when the user wants to concentrate on certain information in
the alarm buffer. This is done by defining criteria to filter out unwanted
information. A single criterion or multiple criteria can be used for filtering. The
alarm list filter settings are identical to the event list filter set.

3.7.7.6 Alarm List presentation modes


The alarm buffer is updated every time the alarm state of a process object
changes. Basically, the Alarm List should be updated at each update of the
alarm buffer to give correct and up-to-date information. However, if the list is
updated frequently, it is almost impossible to concentrate on a single alarm
line. This is the reason why the Alarm List has two presentation modes: frozen
and updating. When the list is in the frozen mode, it is not updated, and the
alarm information can be read easily. If the alarm buffer is updated while the
Alarm List is in the frozen mode, the operator is notified with an informative
text on the status bar. When in the updating mode, the Alarm List is updated
at every update of the alarm buffer. The frozen mode is automatically selected
when the list is scrolled or when a tool affecting the alarm buffer is used. The
current mode is always indicated.

By clicking the left mouse button on a list column header, the alarm list is
sorted. The column that is used for sorting is the column that was clicked. If
the same column is clicked twice, the sorting is in descending order. After the
data is sorted, the list is set to the Frozen mode. The column sort is reset
when the list mode is changed back to Update.

The Find function allows you to search for text within the current alarm list
view. Find searches through the list from the beginning point down. The alarm
line that contains searched text is set selected. A message box appears when
Find has reached the end point of the search or when searched text does not
exist.

Acknowledgement of a single alarm is done by selecting the alarm text line of


the desired alarm on the list. If the selected alarm is unacknowledged,
selecting Acknowledge from the pop-up menu can open the
Acknowledgement dialog. At the same time the Alarm List is set to the frozen
mode to prevent unwanted scrolling.

3.7.8 Blocking List


The Blocking List summarizes the present blocking situation of the signals of
the supervised process. Each signal is presented as a signal text line, which
Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 34 (39)
Functional Design Specification – Substation Automation System

describes the signal in the process. The signal text line normally consists of a
signal text and a group of check boxes indicating the blocking state.

Figure 17: Blocking List

The following blocking types are provided by the Blocking List:

§ Alarm blocking: alarms are not raised, regardless of the object state.

§ Update blocking: indications are not updated by the process.

§ Control blocking: operation commands are not sent to the process.

§ Event blocking: event registrations are not made, events are not shown
in the Event List.

§ Printout blocking: events are not sent to the printer.

§ Action blocking: event channel activation is blocked.

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 35 (39)
Functional Design Specification – Substation Automation System

3.7.9 Trend Application


MicroSCADA Monitor Pro includes the new Trend Application. Trend
Application is used for trend analyses and for showing measured values in the
form of a curve or a table.

Figure 18: Trend picture (Graphical Form)

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 36 (39)
Functional Design Specification – Substation Automation System

Figure 19: Trend picture (Tabular Form)

3.7.9.2 Features of Trend Application


§ Graphic or tabular view modes

§ Hairline function

§ Zooming graphic view

§ Scrolling with scroll bars and panning

§ Configurable axes and line properties

· Using legend

· Update interval options from 30 seconds to 10 minutes

· Clearing trend data by user

· Save, Open and Delete pre configurations


Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 37 (39)
Functional Design Specification – Substation Automation System

· Printout option

· Update/Frozen modes

3.7.9.3 Trend Basket


A trend is a time-related follow-up of process data. All types of process
objects, e.g. analogue and digital data can be illustrated as trends.

When the trend picture is shown, the user can select the data from the trend
basket. When the trend basket is closed, the selected trends are brought to
the trend picture. Trend view configuration includes a set of parameters such
as colors, fonts, etc., which are called trend pre-configurations. Users can
create, delete or apply existing pre-configuration to the trend picture

Figure 20: Trend basket

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 38 (39)
Functional Design Specification – Substation Automation System

3.7.10 System Self Supervision


The SYS 600 System Self Supervision (SSS) is used with the MicroSCADA
systems for supervising and monitoring the system. It provides status
information of hardware and software, as well as picture functions for the
supervision of system objects.

Figure 21: Example of System Supervision picture

Document
Functional Design Specification - SAS Sale Order :
Prepared
M. Prem Kumar 3100053172
Approved
R. Kannan
Dept Lang En
PS-SASE Created
26-05-2014 Revision 00 Yr 14 Wk 22
Page
ABB India Ltd YN1M302310-ZAA 39 (39)