6 kV OUTGOING MOTOR FEEDER: IPCC-3B-M1 200 kW Motor


MOTOR FEEDER: BC OLBC9 200 kW motor Panel No: P12
Relay type: 7SK8042-5EB90-1HEO-LOA Relay Point : R:BC OLBC9
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting Primary value
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Function 66
Function 27
Function 60
Function 49
Function 46
Other functions are disabled
• Power System Data
Description Range Setting
CTs
CT rated primary 10..50000 A 50 A
CT rated secondary 1A/5A 1A
PTs
PT rated primary 0~132000 V 6600 V
PT rated Secondary 110 V 110 V
•Motor Data 200 kW Motor
Sl No Description Value units
1.01 Power 200 kW kW
1.02 Rated voltage 6.6 kV kV
1.03 Motor rated current IA 22.5 A A
1.04 Motor No load current 9 A A
1.05 Max. starting (at 100 % Vn) 123.75 A A
1.06 Max. starting (at minimum allowable Volts) 93.8
1.07 Starting time at full load 2 s s
1.08 Max. blocked rotor time hot/cold 10/26 s s
1.09 Locked rotor Current 123.75 A A
1.10 No of hot starts 3
1.11 No of Cold starts 4
1.12 Thermal Constant 55 min min
1.13 Cooling constant 220 min min
•Thermal Over Load protection 49
Address Setting name Range Setting Units Primary value
4201 FCT 49 OFF/ON/ALARM ON
4202 49k factor 0.10…4.00 0.45
4203 Time Constant 1.0….999.9 mins 55 mins
4204 49ϴ Alarm 50-100% 90 %
4205 I Alarm 0.1-4.0 0.5 Amps
4208A T Emergency 10-15000 sec 100 sec
4209 49 Temp Rise 40-200 deg C 100 deg C
Negative-sequence (unbalanced-load) protection 46
Address Setting name Range Setting Units Primary value
4001 FCT 46 OFF/ON ON
4002 46-1 PICK UP 0.05-3.0 0.09 A
4003 46-1 Delay 0-60 sec 20 sec
4004 46-2 PICK UP 0.05-3.0 0.23 A
4005 46-2 Delay 0-60 sec 3 sec
Time Over current protection 50/51
Address √ Range Setting Units Primary value
1201 FCT 50/51 OFF/ON ON
1204 50-1 PICKUP 0.10-35 3.2 A
1205 50-1 DELAY 0-60 sec 0.05 SEC
1207 51-1 PICKUP 0.1-4.0 0.5 A
1208 51 TIME DIAL 0.05-3.2 0.6
1211 IEC CURVE NI,VI,EI,LI VERY INVERSE
Earth-fault Detection 50N/51N
Address Setting name Range Setting Units Primary value
1301 FCT 50N/51N OFF/ON ON
1304 50N-1 PICKUP 0.10-35 0.5 A
1305 50N-1 DELAY 0-60 sec 0.05 SEC
1307 51N-1 0.1-4.0 0.05 A
1308 51N TIME DIAL 0.05-3.2 0.1
1311 IEC CURVE NI,VI,EI,LI NORMAL INVERSE
Under Voltage Protection 27
Address Setting name Range Setting Units Primary value
5101 FCT 27 UV PROT OFF/ON ON
5102 27-1 PICK UP 10-210 V 75 V 4500
5106 27-1 DELAY 1-50 SEC 5 SEC
5110 27-2 PICK UP 10-210 V 70 V 4200
5112 27-2 DELAY 1-50 SEC 1 SEC
MOTOR START PROTECTION 66
Address Setting name Range Setting Units Primary value
4301 FCT 66 OFF/ON ON
4302 I Start/ Imotnom 1-10 5.5
4303 T Start Max 1-320 sec 2 SEC
4305 I Mot nominal 0.20-1.20 0.45 A
4306 Max warm starts 1-4 3
4307 Cold-Warm starts 1-2 1
4308 kt at Stop 2-100 220 mins
4309 kt at Running 2-100 55 mins
4310 t Min Inhibit 0.2-120 mins 6 mins
4401 Load jam Prot OFF/ON ON
4402 Load Jam I> 0.5-12 0.9 A
4403 Trip delay 0-600 sec 0.5 sec
4404 I Alarm 0.5-12 0.675 A
4405 Alarm Delay 0-600 sec 0.5 sec