APPROVED SERVICE

HEAD FITTING

VOICE
DATA
VIDEO

CONDUIT PIPE
InT InT InT InT InT InT InT InT InT InT InT InT LEGEND :
PIPE BRACKET CLAMP TYPE DROP WIRE BED 1 BED 2 BED 3 BED 4 BED 5 BED 6 BED 7 BED 8 BED 9 BED 10 BED 11 BED 12
NCS - NURSE CALL SYSTEM
HOOK- TO BE PROVIDED
BY THE OWNER
NCS
CONSOLE C
C NCS INTERCOM CONSOLE
InT InT InT InT InT InT InT InT InT InT InT InT InT InT InT InT (MASTER STATION)
NURSE BED 26 BED 25 BED 24 BED 23 BED 22 BED 21 BED 20 BED 19 BED 18 BED 17 BED 16 BED 15 BED 14 BED 13
STATION PATIENT BED STATION (CALL PANEL)
InT
CORRIDOR / DOME LIGHTS
RIGHT WING NURSE CALL SYSTEM RISER DIAGRAM
NDTS

CONCRETE POST 1. WIRING SHALL BE CONCEALED CONDUIT UNLESS OTHERWISE SPECIFIED.


2. MAINTAIN 40% FILL FOR EACH CONDUIT.
3. THE POSITION OF ALL DATA/VOICE/CATV CCTV OUTLETS AS SHOWN IN THE DRAWINGS ARE APPROXIMATE ONLY.
THE EXACT POSITIONS SHALL BE DETERMINED ON SITE.
4. THE SPECIALTY SUB-CONTRACTOR SHALL BE RESPONSIBLE FOR THE LABELING OF ALL EQUIPMENT
THROUGHOUT THE INSTALLATION.
5. THE OVER-ALL RESISTANCE FOR THE EARTHING SYSTEM SHALL COMPLY WITH THE LATEST EDITION OF THE
SERVICE ENTRANCE INSTALLATIONS ELECTRICAL AND ELECTRONICS CODE.
NDTS. 6. THE SPECIALTY SUB-CONTRACTOR SHALL BE RESPONSIBLE SEALING OF ALL CABLE/CONDUIT PENETRATION
OPENINGS BETWEEN FLOOR SLAB AND WALLS WITH THE APPROVED FIRE RATING MATERIALS/SEALANT.
7. DON'T COMBINE ELECTRONICS OUTLET TO ELECTRICAL OUTLET.
1. CONDUIT SHALL BE PERMANENTLY 8. ALL MATERIALS USED SHALL BE IN GOOD STANDARD AND QUALITY.
AND EFFECTIVELY GROUNDED. 8. ALL ELECTRONICS PLAN SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ELECTRONICS ENGINEER UNDER RA 9292.
2. THIS ARRANGEMENT LIMITED TO DROP
WIRE ATTACHMENTS OF UP TO 5 LINES. TELECOMMUNICATIONS (DATA/VOICE/WIFI) OUTLETS.
1. ELECTRONICS OUTLET MUST BE 0.3 METER ABOVE THE FINISH FLOOR LEVEL UNLESS SPECIFIED BY THE OTHER PURPOSES.
3. SPAN TO FIXTURE SHALL BE NOT 2. ALL INFORMATION OUTLETS SHALL BE IN CATEGORY 6 OR OTHERWISE STATED.
EXCEED 45.7 MTS. 3. TELECOMMUNICATION OUTLETS ARE INDICATIVE AND APPROXIMATE.
4. ALL WIFI ACCESS POINTS SHALL BE CONFIGURED TO HAVE ONE SSID.
4. SERVICE MUST SHALL BE SUFFICIENTLY 5. CONSULT DESIGNING PROFESSIONAL ELECTRONICS ENGINEER FOR MORE DETAILS AND SPECIFICATIONS.
HIGH TO PROVIDE PROPER DROP WIRE
CLEARANCE OVER SIDEWALK, STREETS,
OR ROADWAYS IN COMPLIANCE WITH THE CABLE TELEVISION (CATV):
CODES AND REGULATIONS. 1. CATV OUTLETS SHALL BE RG-6 COAXIAL CABLE OR OTHERWISE STATED.
2. CATV OUTLETS ARE INDICATIVE AND APPROXIMATE.
3. CATV OUTLETS MUST BE 0.3 METER ABOVE THE FINISH FLOOR LEVEL UNLESS SPECIFIED BY THE OTHER PURPOSES.
4. CONSULT DESIGNING PROFESSIONAL ELECTRONICS ENGINEER FOR MORE DETAILS AND SPECIFICATIONS.

NURSE CALL SYSTEM


1. ALL WIRING SHALL COMPLY WITH THE SAME STANDARDS AS THE NURSE CALL EQUIPMENT AND WITH THE
RECOMMENDATION OF THE SYSTEM MANUFACTURER.