NORTH
U.T.M.
GRID
GENERAL NOTES:
NORTH
15°
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
SPECIFIED.
2. POWER SUPPLY SECURITY SYSTEM TO BE TAKEN FROM
NEAREST POWER SOURCES (UPS) (UN-INTERRUPTED
POWER SUPPLY).
3. MINIMUM SIZE OF PVC / EMT / RGS FLEXIBLE CONDUIT
SHALL BE 3/4 INCH.
AH 4. ALL CABLES AND DEVICES SHALL BE LABELED IN
KK
MA
ACCORDANCE WITH THE RELEVANT EIA/TIA
SPECIFICATIONS.
5. MAXIMUM 3 DATA CABLE TO BE PULL FROM 3/4" CONDUIT.
6. NETWORK SWITCH SHALL BE PLACED IN IT & FILED
EQUIPMENT CABINET.
7. ALL OUTDOOR UNDER GROUND CABLES SHOULD BE
INSTALLED IN PVC SLEEVES.
CCTV SYSTEM:
1. ALL CAMERAS AND ACCESS CONTROL PANEL SHALL BE
CONNECTED TO POE NETWORK SWITCH.
2. ALL DATA CABLING WILL BE DONE WITH CAT-6 CABLE FOR
CCTV AND SEPARATE CABLES TO BE CONSIDER FOR
EQUIPMENT CONNECTION.
3. MAXIMUM DISTANCE OF CAMERA FROM NETWORK SWITCH
SHALL BE MAXIMUM 90 METERS.
4. CCTV IP CAMERA WILL BE POWERED THROUGH IP BASED
POE SWITCH.
5. OUTDOOR FIXED CAMERA SHALL BE INSTALLED WITHIN 5
METER FROM THE FLOOR LEVEL.
6. OUTDOOR RATED CABLE TO BE USED IN OUTDOOR AREA.
7. FIBER OPTIC CABLING TO BE DONE FOR NETWORK
COMMUNICATION.
SECURITY EQUIPMENT ROOM:
1. 2ALL SECURITY EQUIPMENT SHALL BE PLACED IN
EQUIPMENT ROOM.
2. 3 DISPLAY OF VIDEOS AND ALARMS EVENTS SHALL BE
PROVIDED IN GUARD ROOM.
SMOKE DETECTOR
L-1
SMOKE DETECTOR
ADDRESS BUTTON
MAIN CYLINDER
FIRE BELL
U.T.M.
WAREHOUSES GRID
NORTH
LOCATION
15°
PROJECT
NORTH
L-1 42 41 40 39 38 37 36 35 34
MA
KK
AH
L
K
J
I
H
G
F
E
D
C
B
KEY PLAN
REVISION:
PROJECT
CONTRACTOR:
DRAWING TITLE: