You are on page 1of 1

GENERAL NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE


SPECIFIED.
2. POWER SUPPLY SECURITY SYSTEM TO BE TAKEN FROM
NEAREST POWER SOURCES (UPS) (UN-INTERRUPTED
POWER SUPPLY).
3. MINIMUM SIZE OF PVC / EMT / RGS FLEXIBLE CONDUIT
SHALL BE 3/4 INCH.
4. ALL CABLES AND DEVICES SHALL BE LABELED IN
ACCORDANCE WITH THE RELEVANT EIA/TIA
SPECIFICATIONS.
5. MAXIMUM 3 DATA CABLE TO BE PULL FROM 3/4" CONDUIT.
6. NETWORK SWITCH SHALL BE PLACED IN IT & FILED
EQUIPMENT CABINET.
7. ALL OUTDOOR UNDER GROUND CABLES SHOULD BE
WAREHOUSE # 8 POWER SOURCE FEEDER BREAKER INSTALLED IN PVC SLEEVES.
CCTV SYSTEM:
1. ALL CAMERAS AND ACCESS CONTROL PANEL SHALL BE
CONNECTED TO POE NETWORK SWITCH.
2. ALL DATA CABLING WILL BE DONE WITH CAT-6 CABLE FOR
30AT/50AF CCTV AND SEPARATE CABLES TO BE CONSIDER FOR
EQUIPMENT CONNECTION.
3. MAXIMUM DISTANCE OF CAMERA FROM NETWORK SWITCH
3P, MCCB SHALL BE MAXIMUM 90 METERS.
POWER LOAD CALCULATION: 4. CCTV IP CAMERA WILL BE POWERED THROUGH IP BASED
POE SWITCH.
5. OUTDOOR FIXED CAMERA SHALL BE INSTALLED WITHIN 5
SWITCH 1 = 715W METER FROM THE FLOOR LEVEL.
6. OUTDOOR RATED CABLE TO BE USED IN OUTDOOR AREA.
SWITCH 2 = 715W 7. FIBER OPTIC CABLING TO BE DONE FOR NETWORK
3CX 4 Sq.mm+1CX 2 Sq.mm COMMUNICATION.
SECURITY EQUIPMENT ROOM:
SWITCH 3 = 715W
1. 2ALL SECURITY EQUIPMENT SHALL BE PLACED IN
EQUIPMENT ROOM.
2. 3 DISPLAY OF VIDEOS AND ALARMS EVENTS SHALL BE
PROVIDED IN GUARD ROOM.

SECURITY SYSTEM LEGENDS


IT CABINET
TOTAL LOAD CALCULATION: 2681VA. BULLET CAMERA
DOME CAMERA

DOME CAMERA
PROPOSED UPS 6 KVA
CAT-6

POWER CABLE

LOCATION : IT ROOM FOC SENSING CABLE

SWITCH (PoE Switch)

NETWORK SWITCH 48P (INDOOR)

CORE SWITCH
UPS-6 KVA FILED CABINET (PoE Switch)

REFERENCE DRAWING:
SL
NO DRAWING NUMBER DESCRIPTION
CAT-6 CABLE CONDUIT EXTERNAL NETWORK
1 EX00-CCTV-CN-XX0001 -001005
GENERAL LAYOUT
CAT-6 CABLE CONDUIT EXTERNAL NETWORK
2 EX00-CCTV-CN-XX0002 -001005
GENERAL LAYOUT

3 EX00-CCTV-GN-XX0001 -001005 EXTERNAL NETWORK GENERAL LAYOUT


3CX 4 Sq.mm+1C X 2 Sq.mm
4 EX00-CCTV-FV-XX0001 -001005 EXTERNAL NETWORK FIELD VIEW LAYOUT

5 EX00-CCTV-RD-XX0001 -001001 EXTERNAL NETWORK RISER DIAGRAM LAYOUT

EX00-CCTV-TN-XX0001 -001001 EXTERNAL NETWORK TOPOLOGY LAYOUT


UPS-DB-01 6

7 EX00-CCTV-ED-XX0001 -001001 EXTERNAL ELECTRICAL SINGLE LINE DIAGRAM


LOCATION : WAREHOUSE # 08 IT ROOM WAREHOUSE 07 CCTV - CONDUIT LAYOUT
8 WH07-CCTV-CN-XX0001-001003
ESSENTIAL LOAD LOWER LEVEL 0.00 FFL
WAREHOUSE 07 CCTV - CONDUIT LAYOUT
9 WH07-CCTV-CN-XX0002-001003
HIGH LEVEL 2.30 FFL

Rated Voltage 250V 10 WH08-CCTV-CN-XX0001-001003 WAREHOUSE 08 CCTV - CONDUIT LAYOUT

11 WH10-CCTV-CN-XX0001-001003 WAREHOUSE 10 CCTV - CONDUIT LAYOUT

PDU PDU U.T.M.

WAREHOUSES GRID

8 OUTLET / 15 AMP 8 OUTLET / 15 AMP


NORTH

LOCATION

15°
PROJECT
NORTH

42 41 40 39 38 37 36 35 34

MA
KK
AH
L
K
J
I
H
G
F
3CX 2.5 Sq.mm 3CX 2.5 Sq.mm 3CX 2.5 Sq.mm
E
D
C
B

KEY PLAN
ACCESS SWITCH # 3

ACCESS SWITCH # 2

ACCESS SWITCH # 1
REVISION:

00 05/05/2022 ISSUED FOR APPROVAL. -

REV. DATE DESCRIPTION OF REVISION APP.

DRAWN BY: DESIGNED BY: REVIEW BY: APPROVED BY: DATE:

AQM AQM SAM/MM AMH 05/05/2022

PROJECT

CCTV CAMERA FOR


WALL MOUNT CABINET 42U CABINET DACO WAREHOUSES
CLIENT:

WAREHOUSE # 8 SECURITY SYSTEM ELECTRICAL INTER CONNECTION DIAGRAM


NTS
CONTRACTOR:

DRAWING TITLE:

WAREHOUSE CCTV ELECTRICAL INTER


CONNECTIVITY DIAGRAM LAYOUT FOR
UPS
PROJECT NUMBER DRAWING NUMBER SHEET REV.
DACP-SS01
001
SCALE (A1)
WH08-CCTV-UPS-XX0002 00
N.T.S 001