ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE PROPER IDENTIFICATION AND LABELING OF ALL CIRCUIT
GENERAL NOTES & SPECIFICATIONS
BREAKERS. EACH PANEL WILL BE PROVIDED WITH A TYPEWRITTEN CIRCUIT DIRECTORY.
1. ALL ELECTICAL WORKS SHALL CONFORM TO THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. TO THE RULES
15. THE JOB SHALL BE EXECUTED IN THE MOST THOROUGH, AND WORKMAN-LIKE MANNER, EMPLOYING STANDARD TOOLS,
AND REGULATIONS OF THE LOCAL AND NATIONAL AUTHORITIES CONCERNED WITH THE REQUIREMENTS OF LOCAL UTILITY
EQUIPMENT, METHODS AND GOOD ENGINEERING PRACTICES. THE JOB SHALL BE DONE COMPLETE ALL ASPECTS AS
COMPANIES.
REQUIRED IN PLANS AND SPECIFICATIONS AND READY FOR OPERATION.
2. WIRING METHOD SHALL BE AS FOLLOWS:
16. THE DRAWINGS SPECIFICATIONS ARE INTENDED TO PRESENT A GENERAL LAYOUT AND BROAD OUTLINE AND
A. MAIN SERVICE ENTRANCE---------------- THWN THRU EXPOSED IMC & OPEN OVERHEAD
DESCRIPTION OF THE PROJECT AND NOT NECESSARILY INDICATED OR DESCRIBE ACTUAL LOCATION LEVELS AND
B. RACEWAYS FOR POWER----------------THHN/THWN NO. 12 AWG THRU EXPOSED IMC (AFTER PANEL BOARD)
DISTANCES OF EQUIPMENT. THE CONTRACTOR IS HEREBY REQUIRED TO MAKE ADJUSTMENTS AT THE JOBSITE AS
C. AUXCILLIARY SYSTEM ----------------THHN/THWN NO. 12 AWG THRU EXPOSED IMC (AFTER PANEL BOARD)
LOCATIONS, LEVELS, AND DISTANCES ARE GOVERNED BY ACTUAL FIELD CONDITIONS.
D. RACEWAYS FOR LIGHTING----------------THHN/THWN NO. 12 AWG THRU EXPOSED IMC (AFTER PANEL BOARD)
17. WIRES SHALL BE COLOR CODED:
3. MINIMUM SIZE OF WIRE SHALL BE 3.5 mm2 THHN/THWN & 15>> (1/2") NOMINAL DIAMETER RESPECTIVELY UNLESS OTHERWISE
LINE 1 ------------------------RED/BLUE COMMON------------WHITE
SPECIFIED ON THE PLANS.
LINE 2 -----------------------YELLOW GROUND ------------GREEN
4. NO BRANCH CIRCUIT WIRING IN LIGHTING AND POWER SHALL HAVE A LOAD MORE THAN 80% OF ITS RATING.
18. NO REVISION IN THE DESIGN SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE & APPROVAL OF THE DESIGNER AND
5. LIGHT CONTROL SWITCHES SHALL BE RATED 20 AMPERES, 230 V.
THE OWNER. ANY OF SUCH REVISION DONE WITHOUT THE APPROVAL SHALL CAUSE RESPONSIBILITY OF THE DESIGNER TO
6. UNLESS OTHERWISE SPECIFIED, PULL BOXES OR JUNCTION BOXES SHALL BE PROVIDED WHENEVER REQUIRED AND
CEASED AS A WHOLE.
NECESSARY, ALTHOUGH SUCH BOXES ARE NOT INDICATED ON PLANS.
19. ALL EQUIPMENT, WIRES, ROYAL CORDS, SPECIAL TYPE PLUGS, AND RECEPTACLES AS REQUIRED SHALL BE
7. FOR EACH SPARE CIRCUIT PLANELBOARDS, PROVIDE AN EMPTY CONDUIT 15mm (1/2") DIA.. TERMINATING TO A
PROVIDED BY THE ELECTRICAL CONTRACTOR.
COVERED SQUARE BOX.
20. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL
8. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW OF APPROVED TYPE FOR BOTH LOCATION AND
ENGINEER AND/OR MASTER ELECTRICIAN.
PURPOSES.

9. ALL METAL FRAMES SHALL BE PROPERLY AND ADEQUATELY GROUNDED. GROUND WIRE SHALL BE PROVIDED ON ALL

EQUIPMENT FEEDER.

10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: SERVICE ENTRANCE M


A. LIGHT SWITCHES ---------------- 1.40m FROM THE FINISHED FLOOR LINE (FFL)
FROM ELECTRIC 2 - 22.0 sq.mm. THWN / THHN
B. RECEPTACLES ---------------- 0.30m FROM THE FINISHED FLOOR LINE (FFL) SERVICE PROVIDER 1 - 5.5 sq.mm. TW GROUND(G)
IN A 30mm DIA. RIGID CONDUIT
C. TELEPHONE/INTERCOM OUTLETS ------- 0.30m FROM THE FINISHED FLOOR LINE (FFL)

D. PLANE BOARDS ---------------- 1.80m FROM THE FINISHED FLOOR LINE (FFL)

E. COUNTER TOP OUTLETS ---------------- 1.10m FROM THE FINISHED FLOOR LINE (FFL) PB1
11. THERE SHALL BE ONLY ONE SERVICE DROP SECONDARY TO THE PROPOSED BUILDING. 60 A

12. SECONDARY SERVICE SHALL BE 230V. SINGLE PHASE, 60Hz, FOR POWER & LIGHTING. ALL 20-AMPERE CIRCUIT
15 A 15 A
HOMERUN TO PLANE BOARDS MORE THAN 30m IN LENGTH SHALL BE 5.5mm2 THAN (10AWG), UNLESS OTHERWISE C1 C2
SPECIFIED ON THE PLANS. 15 A 15 A
C3 C4
13. ADDITIONAL MATERIAL SPECIFICATION:
15 A 20 A
A. INTERMEDIATE METALLIC CONDUIT (IMC) PIPE----NICHE OR APPROVED EQUIVALENT C5 C6

B. WIRES AND CABLES-----------------------------------------AMERICAN WIRES & CABLES OR 20 A 20 A


C7 C8
APPROVED EQUIVALENT
30 A 30 A
C. CIRCUIT BREAKER--------------------------------------------BOLT-ON TYPE FOR MAIN C9 C10
BREAKER & BOLT-ON FOR ALL 30 A 30 A
C11 C12
(BOLT-ON TYPE) PLANEBOARDS OR APPROVED EQUIVALENT SPARE
30 A
D. WIRING DEVICES-----------------------------------------AMERICAN STANDARD DEVICES OR C13 C14
APPROVED EQUIVALENT

E. JUCTION/PULL BOXES (GAUGE 16)---------------------FUMACO OR FABRICATED ON SITE. ZINC

CHROMATE FINISH.

SINGLE LINE DIAGRAM


GROUND
sign & seal

project title: owner: SHEET CONTENT/S: sheet no.


-
engineer A PROPOSED BUNGALOW
RESIDENTIAL BUILDING
ENGR. DANIEL A. PIOQUINTO FLOOR PLAN E2
prc no: date:
-
ptr no:
ctc no.:
place:
LOCATION: BRGY. AMBAGO, EMINVIL SUBDIVISION, BUTUAN CITY LOCATION: BRGY. AMBAGO, EMINVIL SUBDIVISION, BUTUAN CITY
PROJECT CODE:
DATE:
- -
DRAWN CHECK APPV. DESCRIPTION:
SCHEMATIC -
DATE:
E3
IRR 9266: SECTION 20 ARCTICLE 4: Drawings & Specifications duly signed or sealed as instruments of service are the intellectual properties and documents of the ARCHITECT, whether for they are made are executed or not. It shall be unlawful for any person, without the consent of the ARCHITECT or author of the documents to duplicate, or to make copies of said documents, for use or repetition or and for other projects or buildings, whether executed partly or whole.