Sa Sh GENERAL NOTES :

1. ALL GENERAL ELECTRICAL WORKS SHALL BE EXECUTED IN ACCORDANCE WITH THE PROVISIONS OF
Sb Sg THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, LAWS AND ORDINANCES OF THE LOCAL
MUNICIPALITY, RULES AND REGULATIONS OF THE LOCAL POWER COMPANY.
2. POWER SERVICE TO THE BUILDING SHALL BE 230V, SINGLE PHASE, THREE WIRES, 60Hz.
3. WIRING SHALL BE AS FOLLOWS:
a) SERVICE ENTRANCE
Scd Sij b) FOR LIGHTINGS
c) FOR POWER
d) FOR AUXILLARY
4. SMALLEST CONDUCTOR TO BE USED SHALL BE NO. 3.5mm(12) AWG AND SMALLEST RACEWAY SHALL
BE 15mm(1/2) DIAMETER TRADE SIZE CONDUIT. CONDUCTORS SHALL BE INSULATED FOR 600 VOLTS
THHN OR THW OR AS INDICATED IN THE PLANS, PHELPS DODGE, OR APPROVED EQUAL.
5. FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED IN THE PLANS. HOMERUN SHALL
NOT BE COMBINED IN THE SAME RACEWAY UNLESS SO NOTED.
6. NO BRANCH CIRCUIT CONDUCTOR SHALL HAVE A LOAD OF MORE THAN 80% OF ITS RATING.

7. WIRE GUTTERS, SQUARE BOXES AND PULL BOXES SHALL BE PROVIDED ON CIRCUITS AND HOMERUN
IN EXCESS OF 30 METERS OR WHERE NECESSARY.
8. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR CODED AS PER REQUIREMENT OF PEC
GROUNDED CONDUCTOR SHALL BE IDENTIFIED BY A CONTINUOS COLOR WHITE. GROUNDING CONDUCTOR
OF BRANCH CIRCUITS SHALL BE IDENTIFIED BY A CONTINUOS GREEN COLOR UNLESS IT IS BARE.
LINE 1 - RED
LINE 2 - BLUE
GROUND - GREEN
9. EXPOSE WIRING FOR LIGHTING AND CONVENIENCE OUTLETS SHALL BE IN RIGID STEEL CONDUIT (RSC) OR
ELECTRICAL METALLIC TUBING (EMT) PIPE RUN PARALLEL TO BEAM AND TRUSSES.

10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS :


Sef Skl
a) LIGHT CONTROL SWITCHES
3 LOAD SCHEDULE b)
c)
CONVENIENCE OUTLET
STANDARD CAMERA WALL MTD.
1 2
LPP LPP E-1 SCALE NTS 11. ALL FLOURESCENT LIGHTING FIXTURES SHALL BE PROVIDED WITH RAPID START OR HIGH POWER FACTOR
BALLASTS WITH SPRING LOADED LAMP HOLDERS.

1 LIGHTING LAY-OUT 12. CONDUITS AND METAL FRAMES OF EQUIPMENT SHALL BE BONDED TOGETHER BY MEANS OF COPPER
STRAPS. CONDUITS OF SYSTEM SHALL BE PROPERLY GROUNDED TO THE WATER SUPPLY SERVICE
PIPES WHENEVER POSSIBLE OR GROUND ROD INSTALLED FOR THE PURPOSE. GROUND ROD
E-1 SCALE 1:100 SHALL BE 20mm DIA x 3000mm. COPPER CLAD STEEL EMBEDDED TO THE GROUND WITH ITS
TOP ACCESSIBLE FOR INSPECTION.
13. RECEPTACLES IN GENERAL SHALL BE RATED AS 15A, 250V NATIONAL IN BRAND.

14. PANELBOARDS AND BREAKERS


a) ALL MAIN CIRCUIT BREAKERS SHALL BE MOLDED CASE INTERRUPTING
CAPACITY AS SHOWN IN THE SCHEDULE OF LOADS.

b) ALL BRANCH CIRCUIT BREAKERS SHALL BE BOLT-ON INTERRUPTING


M M CAPACITY AS SHOWN IN THE SCHEDULE OF LOADS.

c) PROVIDE ACTUAL SCHEDULES OF LOADS AND DIRECTORIES FOR EACH


INDIVIDUAL PANELBOARD. PROVIDE NAMEPLATES (MICARTA) FOR EACH PANELS.

d) ALL CIRCUIT BREAKERS SHALL BE "GE", "ABB", "SQUARE D" OR MITSUBISHI IN BRAND OR APPROVED EQUAL.
15. THE CONTRACTOR SHALL CONDUCT TEST TOGETHER WITH OWNERS REPRESENTATIVE SUCH AS
INSULATION TEST, GROUND RESISTANCE TEST, PHASE SEQUENCE TEST AND OPERATING TEST.
ALL TEST RESULT SHALL BE SUBMITTED TO THE OWNERS REPRESENTATIVE. MINIMUM INSULATION
TEST SHALL BE 250,000 OHMS. MINIMUM GROUND RESISTANCE TEST SHALL BE 25 OHMS.
5 6 16. ALL MATERIALS SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSE IN
PP PP WHICH THEY ARE INTENDED TO BE INSTALLED.

17. ANY DISCREPANCY IN LOCATION AND RATINGS OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED
WITH THE OWNER OR ANY OF HIS REPRENTATIVES AND CHANGES SHALL BE MADE ACCORDINGLY.

18. FOR EACH SPARE BRANCH CIRCUIT OF PANEL BOARDS, PROVIDE 20mm(3/4") DIA. EMPTY
CONDUIT TERMINATED TO 100mm x 100mm SQUARE BOX ABOVE THE CEILING.

19. PROVIDE ENOUGH SUPPORT CONDUITS, PIPE STRAPS, WALL BRACKETS, HANGERS OR CEILING
TRAPEZE. FASTEN BY MACHINE SCREWS, WELDED THREADED STUDS, OR SPRING TENSION CLAMPS
ON STEEL WORKS.
20. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE SUPERVISION OF AN EXPERIENCED,
DULY LICENSED ELECTRICAL ENGINEER.

3 4
PP PP

2 POWER LAY-OUT 4 POWER SYSTEM DIAGRAM


E-1 SCALE 1:100 E-1 SCALE NTS

LIGHTING LAYOUT
POWER LAYOUT E
LOAD SCHEDULE
POWER SYSTEM DIAGRAM 1 1