LEGENDS
1. ALL ELECTRICAL WORKS HEREIN SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
PHILIPPINE ELECTRICAL CODE (PEC). THE EXISTING LOCAL ORDINANCES RULES & REGULATIONS OF
THE MUNICIPAL ELECTRICIAN & REQUIREMENTS OF THE UTILITY COMPANY.
2. THE TYPE OF ELECTRICAL SERVICE TO BE SUPPLIED SHALL BE THREE PHASE, 3 WIRE, 230 V, 60 Hz.
3. ALL WIRE SHALL BE COPPER WITH AT LEAST 99% CONDUCTIVITY, 600 VOLTS INSULATION, THERMOPLASTIC
INSULATED TYPE "THHN" & "THW" UNLESS OTHERWISE INDICATED, AND COLUMBIA OR PHELPS DODGE
BRAND. THE MINIMUM SIZE FOR POWER AND LIGHTING SHALL BE 3.5 sq. mm.
4. THE ELECTRICAL WIRING INSULATION SHALL BE DONE IN RIGID METALLIC CONDUIT (RMC), OR RIGID PVC
CONDUIT AS SPECIFIED, CONCEALED IN CEILING, CONCRETE AND MASONRY WORKS AND IN DOUBLE
WOOD WALLS. FLEXIBLE METALLIC CONDUITS SHALL BE USED WHERE REQUIRED MINIMUM SIZE FOR ALL
CONDUIT SHALL BE 20 mm Ø ELECTRICAL TRADE SIZE.
6. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANEL BOARDS, LIGHTING FIXTURES AND ALL NON-CURRENT
CARRYING METAL PARTS SHALL BE PROPERLY CONDUCTED. GROUND WIRE MUST BE CONTINUOUS WITH
GREEN INSULATION OR BARE UNINSULATED.
7. ALL 20 AMPERE CIRCUIT HOMERUNS TO PANEL BOARDS OF MORE THAN 30 METERS IN LENGTH SHALL BE 5.5
sq. mm. UNLESS OTHERWISE SPECIFIED.
8. WIRE SPLICES SHALL BE MECHANICALLY AND ELECTRICALLY SECURED JOINTS, TAPS AND SPLICES LARGER
THAN 5.5 mm. SHALL BE MADE WITH THE USE OF SOLDERLESS COPPER CONNECTION. THEY SHALL BE
COVERED WITH ELECTRICAL TAPE EQUAL TO THE THICKNESS OF THE WIRE INSULATION.
9. CIRCUIT BREAKERS SHALL BE MOLDED CASE, NEMA STANDARD, QUICK MAKE, QUICK BREAK, THERMAL
MAGNETIC WITH INVERSE TIME CHARACTERISTICS SHALL BE FUJI OR GE BRAND. PANEL BOARDS SHALL BE
FUJI-HAYA OR EDISON ELECTRICAL BRAND. BOXES SHALL BE CODE GALVANIZED SHEET WITH BLUE GRAY
LACQUERED VARNISH TRIM
10. WALL SNAP SWITCHES AND DUPLEXCONVINIENCE OUTLETS SHALL BE 10 AMPS, 230 VOLTS, NATIONAL BRAND
WITH MODERN PLATE. SWITCHES SHALL BE INSTALLED 1.20 M. ABOVE FINSHED FLOOR, FLUSH WITH THE
WALL CONVINIENCE OUTLETS SHALL BE INSTALLED 0.30 M. ABOVE COUNTER TOP OR AS DIRECTED BY THE
ARCHITECT.
11. FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED PLANS. INDIVIDUAL BRANCH CIRCUIT
HOMERUN SHALL NOT BE COMBINED IN THE SAME CONDUITS UNLESS EXPLICITLY PROVIDED.
12. CONDUIT ROUTING SHOWN IS ESENTIALLY DRAMMATICAL. CONTRACTOR SHALL LAYOUT RUNS TO SUIT THE
FIELD CONDITIONS AND THE COORDINATION REQUIREMENTS OF UTILITIES AND OTHER TRADES.
13. ANY DISCREPANCY IN LOCATION AND RATING OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED WITH THE
ENGINEER/OWNER OR ANY OF HIS REPRESENTATIVES AND CHANGES SHALL BE MADE ACCORDINGLY.
14. ALL MATERIAL TO BE USED AND EQUIPMENT INSTALLED SHALL BE BRAND NEW AND MUST BE OF APPROVED
TYPE FOR PARTICULAR LOCATION AND PURPOSE.
16. FOR EACH SPARE BRANCH CIRCUIT IN THE PANEL BOARD, PROVIDE ONE 20 mm INSIDE DIAMETER EMPTY
CONDUIT TERMINATED TO A 100 mm OCTAGONAL BOX ABOVE CELING PROVIDE PULL WIRES IN ALL SPARE
EMPTY CONDUITS.
17. THE JOB SHALL BE EXECUTED IN THE MOST THOROUGH, PROMPT AND WORKMANLIKE MANNER, EMPLOYING
STANDAR TOOLS, EQUIPMENT, METHODS AND GOOD ENGINEERING PRACTICES. THE JOB SHALL BE COMPLETE
IN ALL ASPECTS A REQUIRED IN PLAN AND SPECIFICATIONS AND READY FOR OPERATION.
18. ALL RECEPTACLE OUTLETS SHALL BE TAGGED WITH PANEL AND CIRCIOT NUMBER SUPPLYING THEM.
19. THE ELECTRICAL CONTRACTOR IS RESPONSIBE FOR THE PROPER IDENTIFICATION AND LABELLING OF ALL
CIRCUIT BREAKERS. EACH PANEL BOARD SHALL BE PROVIDED WITH TYPEWRITTTEN CIRCUIT DIRECTORY.
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
MARK JOSHUA T. PEDRO ENGR. GILBERT B. HOLLMAN
PROPOSED ELECTRICAL DESIGN OF A DANN MATTHEW S. DALINO PEE 3009
PTR. NUMBER
E
THREE-STOREY FOOD DRESSING PLANT
UNILEVER FOOD DRESSING COMPANY LEGENDS & GENERAL NOTES PLACE/DATE OF ISSUE:
DRAWN BY: SCALE:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
ELECTRICAL NOTES SITE LOCATION
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
6875
9000
6000
9000
6000
A1
6000
9000
3200
6000
2800
2800
9000
6000
XAF
3200
6000
9000
6000
500
6000
3575
3275
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
MARK JOSHUA T. PEDRO ENGR. GILBERT B. HOLLMAN
PROPOSED ELECTRICAL DESIGN OF A
UNILEVER FOOD DRESSING COMPANY LIGHTING LAYOUT-GF
DANN MATTHEW S. DALINO PEE 3009
PTR. NUMBER
E
THREE-STOREY FOOD DRESSING PLANT DRAWN BY: SCALE: PLACE/DATE OF ISSUE:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
9000 9000 9000 9000 9000 9000 9000 9000 9000 9000
6875
1000
5825
9000
6000
9000
6000
6000
9000
3200
6000
2800
2800
9000
6000
3200
6000
9000
6000
500
6000
3575
3275
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
MARK JOSHUA T. PEDRO ENGR. GILBERT B. HOLLMAN
PROPOSED ELECTRICAL DESIGN OF A
UNILEVER FOOD DRESSING COMPANY LIGHTING LAYOUT-1F
DANN MATTHEW S. DALINO PEE 3009
PTR. NUMBER
E
THREE-STOREY FOOD DRESSING PLANT DRAWN BY: SCALE: PLACE/DATE OF ISSUE:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
6875 9000 9000 9000 9000 9000 9000 9000 9000 9000
9000
6000
9000
6000
6000
9000
3200
2 3
6000
NLP-306
2800
2
2800
9000
E2-PM
6000
NLP-306 A1-SM
NLP-SB2-4
A1-SM
NLP-SB2-4
A1-SM
NLP-SB2-4
A1-SM
NLP-SB2-4
A1-SM
NLP-SB2-4
A1-SM
ELP-SB4-4
NLP-SB1-4
ELP-303
6
SB-1
3200
SB-2G
SB-1 SB-2
NLP-306 5
SB-1A
E2-PM
NLP-SB1-4
E2-PM
NLP-SB2-4
F1-PM F1-PM
F1-PM
ELP-SB5
F1-PM
ELP-SB5 F1-PM F1-PM
NLP-SB3
E2-PM
NLP-SB3-4
NLP-306 1
NLP-306
FUTURE
NLP-SB3 NLP-SB3 E2-PM
6000
9000
E2-PM
E2-PM NLP-SB1A-4
NLP-SB1A-4 SB-4-2G
E2-PM
16 F1-PM
E2-PM
ELP-SB5-4
E2-PM
NLP-SB3-4
E2-PM
NLP-SB3-4 SB-2-3G
2000
A1-SM
ELP-SB4-4
700
A1-SM
ELP-SB4-4 4
SB-3-3G
F1-PM
NLP-304 ELP-SB5 ELP-SB5 NLP-SB3-4
NLP-306
SB-2
SB-1-2G
6000
E2-PM
SB-5
E2-PM
NLP-SB5-4 ELP-SB5-4
500
A1-SM A1-SM
3
A1-SM NLP-SB1-4
E2-PM NLP-SB1-4 ELP-SB2-4
NLP-SB1-4 E2-SM NLP-306 ELP-304
ELP-SB6-4
E2-PM
ELP-304 ELP-304 SB-3 A1-SM
6000
NLP-SB1-4 E2-PM ELP-SB4-4 A1-SM
NLP-SB3 NLP-SB1-4 A1-SM
E2-PM E2-PM A1-SM A1-SM
3575
1
3275
ELP-304
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
MARK JOSHUA T. PEDRO ENGR. GILBERT B. HOLLMAN
PROPOSED ELECTRICAL DESIGN OF A DANN MATTHEW S. DALINO PEE 3009
PTR. NUMBER
E
THREE-STOREY FOOD DRESSING PLANT
UNILEVER FOOD DRESSING COMPANY LIGHTING LAYOUT-2F SCALE: PLACE/DATE OF ISSUE:
DRAWN BY:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
9900 9900 9900 9900 9900 9900 9900 9900 9900 9900
6875
9000
6600
9000
6600
XX
6600
9000
3520
6600
2800
2800
9000
6600
REIPOC
3520
6600
9000
6600
500
6000
3933
3602
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
MARK JOSHUA T. PEDRO ENGR. GILBERT B. HOLLMAN
PROPOSED ELECTRICAL DESIGN OF A
UNILEVER FOOD DRESSING COMPANY POWER LAYOUT-GF
DANN MATTHEW S. DALINO PEE 3009
PTR. NUMBER
E
THREE-STOREY FOOD DRESSING PLANT DRAWN BY: SCALE: PLACE/DATE OF ISSUE:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
9000 9000 9000 9000 9000 9000 9000 9000 9000 9000
6875
1000
5825
9000
6000
9000
6000
6000
9000
3200
6000
2800
2800
9000
6000
3200
6000
9000
6000
500
6000
3575
3275
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
MARK JOSHUA T. PEDRO ENGR. GILBERT B. HOLLMAN
PROPOSED ELECTRICAL DESIGN OF A
UNILEVER FOOD DRESSING COMPANY POWER LAYOUT-1F
DANN MATTHEW S. DALINO PEE 3009
PTR. NUMBER
E
THREE-STOREY FOOD DRESSING PLANT DRAWN BY: SCALE: PLACE/DATE OF ISSUE:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
6875 9000 9000 9000 9000 9000 9000 9000 9000 9000
9000
6000
9000
6000
6000
9000
6000 3200
2800
2800
9000
6000 3200
6000
9000
6000
500
6000
3575
3275
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
MARK JOSHUA T. PEDRO ENGR. GILBERT B. HOLLMAN PTR. NUMBER
PROPOSED ELECTRICAL DESIGN OF A DANN MATTHEW S. DALINO PEE 3009
THREE-STOREY FOOD DRESSING PLANT
UNILEVER FOOD DRESSING COMPANY POWER LAYOUT-2F SCALE: PLACE/DATE OF ISSUE:
DRAWN BY:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
PLACE/DATE OF ISSUE:
E
DRAWN BY: SCALE:
GROUND MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
PLACE/DATE OF ISSUE:
E
DRAWN BY: SCALE:
FIRST LEVEL MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO
MOTOR LOAD COMPUTATION
PROJECT NAME: NAME & LOCATION OF OWNER: DESIGNED BY: CHECKED BY: NAME OF PEE: PRC REG. NUMBER
PLACE/DATE OF ISSUE:
E
DRAWN BY: SCALE:
MARK JOSHUA T. PEDRO NTS TIN NUMBER:
DANN MATTHEW S. DALINO