1. ALL ELECTRICAL INSTALLATION WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH DITO
SPECIFICATIONS, THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE RULES AND
125 AMP /Single Phase REGULATION OF THE LOCAL MUNICIPALITY AND POWER UTILITY COMPANY.
2. WIRING METHOD:
SERVICE ENTRANCEPEDESTAL 2 - 38mm² THW (BLACK/RED) + A. INTERMEDIATE METAL CONDUIT (IMC) FOR SERVICE ENTRANCE AND ALL EXPOSED PORTIONS.
1-25 mm² THW GROUND (GREEN) B. UNDERGROUND CONDUITS SHALL BE PVC, ENCASED IN CONCRETE .
IN 50mmØ IMC OR 50mm PVC PIPE
C. GROUNDING WIRES SHALL BE INSULATED.
CIRCUIT BREAKERS
CKT. LOAD DESCRIPTION
VOLTS_V LOAD_VA LOAD_AMP Computation: KVA LOAD SINGLE PHASE:
NO. AT POLE WIRE SIZE GROUND SIZE CONDUIT = (230 x 64.14) / 1000
LOAD_AMP = LOAD_VA / LOAD_V
= 14.8 kVA
1 RECTIFIER 1 230 9000 39.13 125 2P 2 - 35mm², THW 1-25mm², THW 50.8mm Ø IMC Pipe(2"), or 50mm Ø PVC DEMAND FACTOR (%) = 100
= 25 kVA, which is still minimum allowable transformer
TOTAL AMP = 51.31 A
2 SPARE 230 0 0 125 2P - - - PROTECTION AMP = TOTAL AMP * 1.25 = 64.14 capacity of COOP.
A
3 SPACE - - - - - - - -
4 Perimeter Light 230 400 1.74 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC
LEGEND
C. OUTLETS
Feeder:
5 230 600 2.61 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC
2-38mm² THW (Black/Red)+ 1-25 mm² THW GROUND
6 SPARE 230 600 2.61 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC (GREEN) IN 50 mmØ IMC or 50mm Ø PVC
M KILOWATT HOUR METER
7 SPARE 230 600 2.61 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC
8 SPARE 230 600 2.61 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC Protection: MECB MAIN ENCLOSED CIRCUIT BREAKER
125 AT, 1-Phase MECB 2P, 230 V, 25 kAIC (EZD), MTS MANUAL TRANSFER SWITCH
9 SPACE - - - - - - - -
in NEMA 3R or 4x Enclosure. ACPDB AC PANEL DISTRIBUTION BOARD
10 SPACE - - - - - - - -
GROUND
SERVICE ENTRANCE