GENERAL NOTES AND SPECIFICATIONS

ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL BUILDING CODE, PROVISIONS OF THE LATEST APPROVED
S2 PHILIPPINE ELECTRICAL CODE, THE LAWS AND ORDINANCES OF THE LOCAL CODE ENFORCING AUTHORITIES AND REQUIREMENTS OF THE LOCAL
ELECTRIC, TELEPHONE COMPANY AND BUILDING ADMINISTRATION.

1. PRIOR TO BEGINNING OF ANY WORK, SECURE NECESSARY PERMITS OR CLEARANCES FROM THE AUTHORITIES HAVING JURISDICTION. PROVIDE ALL
LABOR AND MATERIALS FOR A COMPLETE INSTALLATION. WORK SHALL BE EXECUTED BY EXPERIENCED ELECTRICIANS.
1 2. IN CASE OF DISCREPANCY BETWEEN PLANS AND SITE CONDITION, SPECIFICATIONS AND REVISIONS CHANGES, THE CONTRACTOR SHOULD
IMMEDIATELY SEEK APPROVAL OF THE OWNER AND VERIFY AND CONSULT WITH A MASTER ELECTICIAN/ REGISTERED ELECTRICAL ENGINEER OR
PROFESSIONAL ELECTRICAL ENGINEER.

3. ALL LOCATION AND MOUNTING HEIGHT ARE SUBJECT TO APPROVAL OF OWNER AND ELECTRICAL ENGINEER.

4. FINAL LIGHTING FIXTURES AND WIRING DEVICES SHALL BE APPROVED BY THE OWNER AND ELECTRICAL ENGINEER.

5. CONTRACTOR SHALL LOCATE ALL SPLICING BOXES TO ACCESSIBLE PLACE OR WITH ACCESS PANELS.

6. ALL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSE DULY REGISTERED ELECTRICAL ENGINEER OR REGISTERED MASTER
ELECTRICIAN.

7. POWER SUPPLY TO THE BUILDING SHALL BE 230V, SINGLE PHASE, 2 WIRE, LINE TO GROUND SYSTEM.
S1 S2 S1 8. CONDUIT EMBEDDED WITHIN CONCRETE WALL SHALL HAVE A MINIMUM CEMENT PLASTERED OF 20 MM THICK.

9. THIS DRAWING IS A DIAGRAMMATIC LAYOUT ONLY. ANY MATERIALS AND FITTINGS NOT SHOWN ON THIS PLANS BUT NEEDED TO COMPLETE THE
SYSTEM AND OPERATION SHALL BE INCLUDED WITH THE CONTRACTORS SCOPE OF WORKS.

LIGHTING LAYOUT 11. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR PURPOSE AND LOCATION. ALL WIRES AND CABLE SHALL BE BRAND NEW AND
APPROVED TYPE.
SCALE 1:65MTS
12. ALL CONDUCTORS SHALL BE IDENTIFIED. ALL CIRCUIT BREAKERS SHALL BE USED WITH TYPED LABEL BELOW IDENTIFYING THE CIRCUIT
DESIGNATION AND CIRCUIT NUMBER WHICH THEY ARE FED.

13. ALL CONDUCTORS SHALL BE COPPER. MINIMUM SIZE SHALL BE #12 AWG. CONDUCTOR SHALL HAVE THHN/THWN INSULATION.

14. ALL CONDUITS AND JUNCTION BOXES SHALL BE CONCEALED IN FINISHED AREAS. PRIOR TO CONCEALMENT OF NEW CONSTRUCTION, ALL WORK
BEHIND FINISHED SURFACES SHALL BE INSPECTED BY THE OWNER OR OWNER'S REPRESENTATIVE.
3
2 ACU
2
2 COMPUTATION OF LOAD LEGEND
TOTAL LOAD: 3172 W SYMBOL DESCRIPTION
230 V LED BULB
= 13.79 AMPERES 2 DUPLEX CONVENIENCE OUTLET
#
CIRCUIT HOMERUN NO.
AT 100% DF:
= 13.79 A (100%) SWITCH LINE
= 13.79 A PANEL BOARD

-USE 40AMPS MCCB FOR MAIN CIRCUIT BREAKER


S1 ONE GANG SWITCH
2 -USE 2-5.5 SQ. MM THHN CU WIRE AT 20MM Ø CONDUIT S2 TWO GANG SWITCH

SERVICE ENTRANCE

230 V, SINGLE PHASE


2 WIRE, 60 HZ
M

POWER LAYOUT
MAIN
SCALE 1:65MTS 40 AT 30 AT

15 AT 20 AT
3

SCHEDULE OF LOADS 1 2
CKT. CKT.
LOAD DESCRIPTION NO. OF OUTLETS VOLTS WATTS AMP WIRE & CONDUIT
NO. PROTECTION
1 LIGHTING LOAD 6 230 600 2.61 15 AT 2-2.0 SQ. MM THHN CU WIRE AT 20MM Ø PVC PIPE
2 CONVENIENCE OUTLET 3 230 1080 9.39 20 AT 2-2.0 SQ. MM THHN CU WIRE AT 20MM Ø PVC PIPE GND
3 ACU 1 230 1492 8.11 30 AT 2-3.5 SQ. MM THHN CU WIRE AT 20MM Ø PVC PIPE
TOTAL 10 230 3172 20.11 40 AT 2-3.5 SQ. MM THHN CU WIRE AT 20MM Ø PVC PIPE RISER DIAGRAM
SCALE NTS

PROJECT TITLE AND LOCATION: IMPORTANT: SIGNED AND SEALED BY: OWNER: SHEET CONTENT: SHEET NO.: REV.:
THESE DRAWINGS AS INSTRUMENTS
OF SERVICE ARE THE PROPERTY
1
AS BUILT: CONSTRUCTION OF ONE-STOREY AND DOCUMENTS OF THE CIVIL
ENGINEER. IT SHALL BE UNLAWFUL ENGR. ABEL C. SABULARSE E 1
RESIDENTIAL BUILDING FOR ANY PERSON WITHOUT THE
WRITTEN CONSENT OF THE CIVIL PROFESSIONAL ELECTRICAL ENGINEER ELSA T. ABENOJA AS SHOWN