M

LPP

MDS

1800mm

1400mm
FFL

1200mm
LPP Main: 60AT, 10kAIC, 60AF, 2P ,230V ,60HZ Flush Mounting Enclosure ( BOLT - ON )
LOADS: NO. OF OUTLETS - VA RATINGS SWITCHES VA / CURRENT FRAME BRANCH RACEWAY
CKT POLE TRIP TYPE
OUTLETS OTHERS LIGHTS Sa Sab Sabc S3W CIRCUIT (A) (AF) WIRE SIZE CONDUIT SIZE

23 - 40va LED Mini Downlight,


1 1 2 2 960 4.2 50 2 15AT BOLT - ON 3.5 mm2 THHN Cu.Con + G 20mmØ PVC Pipe
4 - 10va LED Downlight Swivel

17 - 40va LED Mini Downlight,


2 1 4 1 2 800 3.5 50 2 15AT BOLT - ON 3.5 mm2 THHN Cu.Con + G 20mmØ PVC Pipe
12 - 10va LED Downlight Swivel

3 9 - 180VA 1620 7.0 50 2 20AT BOLT - ON 3.5 mm2 THHN Cu.Con + G 20mmØ PVC Pipe

4 12 - 180VA 2160 9.4 50 2 20AT BOLT - ON 3.5 mm2 THHN Cu.Con + G 20mmØ PVC Pipe

5 RANGE 2500 10.9 50 2 30AT BOLT - ON 2


5.5 mm THHN Cu.Con + G
2
20mmØ PVC Pipe E SINGLE LINE RISER DIAGRAM
6 REF 1000 4.3 50 2 20AT BOLT - ON 5.5 mm THHN Cu.Con + G 20mmØ PVC Pipe
10 SCALE NTS
2
7 1 HP ACU 1000 4.3 50 2 20AT BOLT - ON 5.5 mm THHN Cu.Con + G 20mmØ PVC Pipe
2
8 1 HP ACU 1000 4.3 50 2 30AT BOLT - ON 5.5 mm THHN Cu.Con + G 20mmØ PVC Pipe

9 1 HP ACU 1000 4.3 50 2 30AT BOLT - ON 5.5 mm2 THHN Cu.Con + G 20mmØ PVC Pipe

10 SPACE
11 SPACE
11 SPACE
TOTAL CONNECTED LOAD 2 6 3 2 12040 52.3
LOAD DESIGN ANALYSIS COMPUTATIONS

LOADS CONN. VA DF DEMAND VA Current = (12040 / 230) = 52.35 A


M
1 LIGHTS 1760 100 1760 Demand Factor = (10150/12040) * 100% = 84.30 %
2 RECEPTACLES 3780 50 1890 Demand Current = (52.35 * 84.3% ) = 44.13 A

3 ACU 3000 100 3000 Feeder Sizing = (34.92 + 1.2 Spare + 25% largest motor) = 54.03 A

4 OTHERS 3500 100 3500 Capacity = 54.03 / 70


2 2
MAXIMUM DEMAND VA 10150 Use : 2-14mm THHN Cu. Con + 1-8.0mm TW Ground in 1-32mmØ Conduit

E SCHEDULE OF LOADS
9 SCALE NTS

E SINGLE LINE PANEL DIAGRAM


11 SCALE NTS

ENGINEER : PRO ECT TITLE: SHEET CONTENTS : REVISION DATE SHEET NO.
OWNER :
SCHEDULE OF LOADS
PROPOSED TWO STOREY RESIDENTIAL MR. RYAN S. ACOSTA VICINITY MAP
SINGLE LINE RISER DIAGRAM 8
SINGLE LINE PANEL DIAGRAM
LOCATION: ADDRESS:
PRC NO. PTR NO.
BALLIGI 2, BINTAWA NORTE, VILLAVERDE, BALLIGI 2, BINTAWA NORTE, VILLAVERDE, 8
T.I.N. DATE/PLACE: NUEVA VIZCAYA NUEVA VIZCAYA