You are on page 1of 1

REPUBLIC OF THE PHILIPPINES

GENERAL NOTES: OFFICE OF THE BUILDING OFFICIAL


-ELECTRICAL MUNICIPALITY OF DALAGUETE
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF THE
4800 4800 PHILIPPINES ELECTRICAL CODE, EXISTING APPLICABLE
RECOMMENDING APPROVAL:
ORDINANCES, RULES AND REGULATIONS OF THE LOCAL
GOVERNMENT AND WITH THE REQUIREMENTS OF THE LOCAL
POWER COMPANY.
2. THE TYPE OF POWER SUPPLY SHALL BE SINGLE PHASE, 230 V, 2
2 POLE, 2 WIRE, 60Hz. HEAD ELECTRICAL SECTION DATE
REF
3. ALL WIRING SHALL BE INSTALLED IN STANDARD PVC
4
CONDUIT RUN EMBEDDED INSIDE THE CONCRETE AND
1 HOLLOW BLOCK STRUCTURES, GLASS, COLUMN, WALL
S2 3 APPROVED:
PARTITIONS, AND/OR CONCEALED BETWEEN DOUBLE WALL
ELEV.+0.18M S3 ELEV.+0.18M
WOODEN PARTITIONS AND INSIDE THE CEILING.
4800

4800
ELEV.+0.17M ELEV.+0.17M 4. UNLESS OTHERWISE INDICATED ON THE PLAN, THE
S1
MINIMUM SIZE OF WIRES AND PVC CONDUIT TO BE USED
S2 BUILDING OFFICIAL DATE
6650

6650
ELEV. +0.08M ELEV. +0.08M
SHALL BE 3.5mm^2 AND 20mmØ RESPECTIVELY.
5. ALL LIGHTING CIRCUIT HOMERUN AND CONVENIENCE
OUTLET SHALL BE WIRED WITH NOT LESS THAN 3.5mm^2 TW
S3 IN SIZE UNLESS OTHERWISE INDICATED ON THE PLAN.
6. WHEREVER REQUIRED AND NECESSARY, PULL BOXES AND
JUNCTION BOXES OF PROPER SIZES SHALL BE INSTALLED AT
THE CONVENIENT LOCATION ALTHOUGH SUCH BOXES ARE
1850

1850
NOT SHOWN ON THE PLANS NOR MENTIONED ON THE
ELEV.+0.18M
SPECIFICATIONS.
7. ALL NON-CURRENT CARRYING EQUIPMENT/DEVICES SUCH AS
ELEV.+0.18M

PANEL BOARD SHALL BE PROPERLY GROUNDED IN


ELEV.+0.08M ELEV.+0.08M

ACCORDANCE WITH THE PROVISIONS OF ARTICLE 4 OF THE


2500 PHILIPPINE ELECTRICAL CODE.
8. ALL WALL OUTLETS SHALL BE INSTALLED AT THE
FOLLOWING HEIGHT ABOVE THE FINISHED FLOOR LEVEL,
LIGHTING LAYOUT POWER LAYOUT UNLESS OTHERWISE INDICATED ON THE PLAN: (a) WALL
SCALE 1:50 METERS SCALE 1:50 METERS SWITCHES - 1.4METERS; (b) CONVENIENCE OUTLET - 0.40
E-1 E-1 METERS; AND, (c) PANEL BOARD - 1.8METERS.
9. ALL ELECTRICAL WORKS SHALL BE DONE IN STANDARD
WORKMANSHIP MANNER WITH SKILLED MANPOWER DULY
SUPERVISED BY A LICENSED ELECTRICAL ENGINEER.

LEGEND & SYMBOLS:


USE: 2-8.0mm^2 THHN M
TOTAL POWER TOTAL CURRENT CIRCUIT BR. SIZE OF WIRE SIZE OF CONDUIT
CIRCUIT NO. LOAD DESCRIPTION + 1-5.5mm^2 TW(G) IN
(WATTS) (AMPERES)
A 25MMØ uPVC
2 FLUORESCENT LAMP, S1 SINGLE GANG SWITCH
1 700 3.04 15AT, 2P 2-2.0mm^2 STRANDED, THHN WIRE 20mm∅ PVC
4 WALL LIGHTS, 1 CIRCULAR LIGHT S2 TWO GANG SWITCH
2 9 PIN LIGHTS 900 3.91 15AT, 2P 2-2.0mm^2 STRANDED, THHN WIRE 20mm∅ PVC
S3 THREE GANG SWITCH
3 6 DUPLEX CONVENIENCE OUTLETS 2,160 9.39 20AT, 2P 2-3.5mm^2 STRANDED, THHN WIRE 20mm∅ PVC 100AT,2P DUPLEX CONVENIENCE OUTLET
4 1 REFRIGERATOR 1,500 6.52 30AT, 2P 2-5.5mm^2 STRANDED, THHN WIRE 30mm∅ PVC

5 SPARE 1,000 4.35 30AT, 2P 2-5.5mm^2 STRANDED, THHN WIRE 30mm∅ PVC PANEL BOARD
20AT,2P 20AT,2P
6 SPARE 1,000 4.35 30AT, 2P 2-5.5mm^2 STRANDED, THHN WIRE 30mm∅ PVC
1 2 PIN LIGHT
TOTAL 7,260 31.57 100AT, 2P
20AT,2P 30AT,2P
3 4 WALL LIGHT
COMPUTATIONS: 30AT,2P 30AT,2P
FLUORESCENT LAMP
SIZE OF MAIN WIRE: SIZE OF MAIN CIRCUIT BREAKER: 5 6
Ic = (IT + (IH)*25%)*(DF) Ic = (IT + (IH)*2.0)*(DF)
Ic = (31.57 + (9.39)*25%)*(80%) Ic = (31.57 + (9.39)*2.0)*(80%) CIRCULAR LIGHT
Ic = 27.13 AMPERES Ic =40.28 AMPERES
USE: 2-8.0mm^2 THHN + 1-5.5mm^2 TW(G) IN A 25MM∅ uPVC USE: 100AT, 2P 230V PLUG IN TYPE GROUND

1 CIRCUIT HOME RUN

SCHEDULE OF LOADS M KWH METER


E-1 SCHEMATIC DIAGRAM
E-1
SERVICE ENTRANCE

REG NO : 2583 SEAL PROJECT TITLE: PROJECT OWNER: SHEET CONTENTS: SHEET NO:

1
1. LIGHTING LAYOUT
ALAN T. ALVEZ DATE : 12/20/1991

E
2. POWER LAYOUT

E
PTR NO : 1525190 PROPOSED ONE-STOREY RESIDENCE ALLAN R. CARITERO 3. SCHEDULE OF LOADS
ELECTRICAL ENGINEER
1
4. SCHEMATIC DIAGRAM
DATE : 1/03/2020
5. LEGEND AND SYMBOLS
ADDRESS: GORORDO, LAHUG, CEBU CITY TIN NO : 153-872-532 LOCATION: LUMBANG, DALAGUETE, CEBU ADDRESS: LUMBANG, DALAGUETE, CEBU 6. GENERAL NOTES (ELECTRICAL)