GENERAL NOTES LEGEND AND SYMBOLS PB

1. ALL ELECTRICAL INSTALLATION HEREIN ARE DONE IN ACCORDANCE


WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE LOAD CURRENT CONDUCTOR SIZE
ELECTRICAL CODE, THE RULES, REGULATIONS AND REQUIREMENTS CCT No. LOAD DESCRIPTION VA RATING VOLTAGE CB RATING CONDUIT
IN AMPERES SET LINE GROUND
OF THE LOCAL POWER COMPANY AND THE LAWS AND ORDINANCES
OF THE LOCAL ENFORCING AUTHORITY. S1 - 1 GANG SWITCH
2. THE TYPE OF POWER SERVICE SUPPLIED IS 230V, 3Ø, 60Hz
1 CONVIENIENCE OUTLETS 2,200 230 9.57 20AT, 2P 1 2 x 3.5mm² THHN 3.5mm² E 20mmØ PVC
3. ALL CONDUCTORS ARE COPPER, MINIMUM SIZE SHALL BE 3.5mm²,
2 REFRIGERATOR 1,500 230 6.52 20AT, 2P 1 2 x 3.5mm² THHN 3.5mm² E 20mmØ PVC
UNLESS OTHERWISE SPECIFIED. S2/Sab - 2 GANG SWITCH
4. ALL MATERIALS ARE NEW AND OF THE APPROVED TYPE FOR THE 2,300 20AT, 2P
LOCATION INTENDED.
3 AIRCON OUTLETS 230 10.00 1 2 x 3.5mm² THHN 3.5mm² E 20mmØ PVC
5. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL
EQUIPMENT AND LIGHTING FIXTURE ARE EFFECTIVELY GROUNDED.
S3/Sabc - 3 GANG SWITCH 4 AIRCON OUTLETS 2,300 230 10.00 20AT, 2P 1 2 x 3.5mm² THHN 3.5mm² E 20mmØ PVC
6. MOUNTING HEIGHTS FOR SWITCHES IS 1.37M (ON CENTER OF BOX) AND 5 LIGHTING OUTLETS 480 230 2.09 15AT, 2P 1 2 x 3.5mm² THHN 3.5mm² E 20mmØ PVC
0.30M FOR CONVENIENCE OUTLETS, UNLESS OTHERWISE SPECIFIED. - PANEL BOARD
7. PULLBOXES ARE PROVIDED BY THE CONTRACTOR WHEN EVER 6 LIGHTING OUTLETS 560 230 2.43 15AT, 2P 1 2 x 3.5mm² THHN 3.5mm² E 20mmØ PVC
NECESSARY. TO FACILITATE WIRE PULLING EVEN IF THESE ARE NOT
INDICATED ON THE PLANS, PULL BOXES WERE SIZED IN 7 SPARE 230 - 20AT, 2P
ACCORDANCE WITH THE PEC.
- CENTER LIGHT
8. NO BRANCH CIRCUIT CONDUCTOR SHALL HAVE A LOAD MORE THAN 80% 8 SPARE 230 - 20AT, 2P
OF ITS RATING.
9. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT TOTAL 9,340 40.61 60AT, 2P 1 2 x 14mm² THHN 5.5mm² E 32mmØ PVC
SUPERVISION OF A DULY LICENSED AND COMPETENT PROFESSIONAL
- PIN LIGHT
OR REGISTERED ELECTRICAL ENGINEER.
10. TO PROVIDE EFFECTIVE GROUNDING SYSTEM FOR EQUIPMENT TOTAL CURRENT: MAIN CIRCUIT BREAKER PROTECTION
PROTECTION, USING MINIMUM 1,500mm x 20mmØ GROUNDING - CONVENIENCE OUTLETS
ELECTRODE DIRECTLY BURIED.
IT= [40.61 + (10 x 0.25)] x 95% D.F. ICB = [40.61 + (10 x 1.25)]
- AIRCON OUTLET
= 40.95 AMP. = 53.11 AMP.

Main Feeder Conductors: Main Circuit Breaker:

2 x 14mm² THHN + 5.5mm² E in 32mmØ PVC 60AT, 2P, 230V, 60Hz

LOAD SCHEDULES and COMPUTATION


M
A B C A B C
Incoming CASURECO Power Supply ECB
Single Phase, 230V, 60 Hz, 16300 16300

60AT, 2P 8150 8150 8150 8150

l q

1 1
j j o
o
n
2 x 14mm² THHN + 5.5mm² E PB PB
in 32mmØ PVC 2 3
PB 6000 k m p 6000
d
Smn
PB Sjkl Sopq

60AT, 2P 6
CONVIENIENCE OUTLETS 20AT, 20AT, REFRIGERATOR j j o o

2P 2P 2 2
b b
AIRCON OUTLETS 20AT, 20AT, AIRCON OUTLETS 14000 14000

2P 2P i

f
LIGHTING OUTLETS 15AT, 15AT, LIGHTING OUTLETS Sfg
Shi
PB
2P 2P 4 REF
c
8000
SPARE 20AT, 20AT, SPARE a 8000

2P 2P
Sab
Scde
PB
5 g

PB
SINGLE LINE DIAGRAM b PB PB
1
b
3 3
e h

LIGHTING LAYOUT POWER LAYOUT


SCALE 1 : 50 MTS SCALE 1 : 50 MTS

PROJECT TITLE: ENGINEER: SHEET CONTENTS: OWNER: SHEET NO.

GENERAL NOTES, LEGEND & SYMPBOL, LIGHTING and


RESIDENTIAL POWER LAYOUT, LOAD SCHEDULES and SINGLE LINE
JOYCE D. FESICO E-1
DIAGRAM
DESIGNED BY: CADD BY: I. N. D. OF 1
LOCATION : SAN ISIDRO, IRIGA CITY, CAMARINES SUR CHECKED BY: DATE DRAWN: MAY 20, 2022