PROJECT TEAM PROJECT LOCATION GENERAL NOTES RESIDENTIAL PLAN NOTES SYMBOLS LEGEND DRAWING INDEX

1. ALL PRODUCTS LISTED BY AN EVALUATION SERVICE REPORT (ESR) SHALL BE INSTALLED PER THE
DESIGNER 1. THE GENERAL CONTRACTORS IS THE RESPONSIBLE PARTY TO VERIFY REPORT AND THE MANUFACTURES WRITTEN INSTRUCTIONS. PRODUCT SUBSTITUTIONS SHALL ALSO GENERAL:
ALL DIMENSIONS IN FIELD PRIOR TO EXCAVATING, PLACING BE LISTED BY AN ESR.
EPTA CONSTRUCTION, LLC CONCRETE, ROUGH FRAMING, PENETRATIONS, CUT-OUTS, 1. A1.0 COVER SHEET
INSTALLING ANY FINISHES, FIXTURES OR EQUIPMENT. 2. SEPARATE PERMITS REQUIRED: POOLS, SPAS, FENCES, SITE WALLS, RETAINING WALLS, AND GAS 2. A2.0 FLOOR PLAN & BUILDING ELEVATIONS
19392 N TAFT AVE STORAGE TANKS.
COLUMN GRID
7725 W ODEUM LN, REFERENCE 3. A2.1 SHOWER DETAILS
MARICOPA, AZ 85139 2. ALL SUB-CONTRACTORS PERFORMING WORK ON THIS DETAIL NUMBER 4. A2.2 ROOF FRAMING PLAN
PHOENIX, AZ 85043 PROJECT/SITE WILL BE RESPONSIBLE FOR REVIEWING THE 3. FOUNDATION AND FOOTING DEPTH SHALL BE A MINIMUM OF 18 INCHES BELOW GRADE (OR PER 1 CROSS REFERENCE 5. A2.3 BUILDING SECTIONS
COMPLETE SET OF APPROVED STAMPED BUILDING PLANS AND PROPERTY SOIL REPORT), PROVIDE A MINIMUM OF 3 INCH CLEARANCE BETWEEN REBAR AND SOIL, A8.1 6. A3.0 COVERED PATIO EXTENSION PLAN
COORDINATING THEIR TRADE WITH OTHER TRADES ON THE SITE, (R403.1 AMENDED) SHEET NUMBER 6. A3.1 COVERED PATIO EXTENSION PLAN
GENERAL CONTRACTOR ANY CONTRACTOR WHICH FAILS TO MEET THIS STANDARD SHALL 7. S1.0 GENERAL STRUCTURAL NOTES
BARE THE FULL FINANCIAL RESPONSIBILITY OF CORRECTING THE 4. DOORS BETWEEN THE GARAGE AND RESIDENCE SHALL BE SELF-CLOSING MINIMUM 1 83" THICK SOLID 8. S1.1 FOUNDATION PLAN
WORK TO MEET THE DESIGN INTENT WITHIN THIS SET OF CORE OR 20 MINUTE FIRE RATED (R302.5.1) 9. S2.0 SHEAR WALL PLAN
EPTA CONTRUCTION LLC DOCUMENTS. 10. P1.0 PLUMBING WASTE PLAN

7725 W ODEUM LN, PHOENIX, AZ 85043


5. EXTERIOR WALL PENETRATIONS BY PIPES, DUCTS OR CONDUITS SHALL BE SEALED. (R703..1) 11. E1.0 ELECTRICAL PLAN
3. ALL WORK ON THIS PROJECT SHALL BE IN ACCORDANCE WITH ALL
CODES, SUB CODES AND BUILDING DEPARTMENTS HAVING 6. WOOD SILL PLATES SHALL BE PRESSURE TREATED OR DECAY RESISTANT, EXTERIOR SILL PLATES SHALL
1
A5.1
ELEVATION
REFERENCE ROC # 318489
JURISDICTION. THE GENERAL CONTRACTOR WILL COORDINATE BEAR A MINIMUM OF 6 INCHES ABOVE FINISH GRADE. (R317.1)
GOVERNING CODE

EPTA CONSTRUCTION
WITH LOCAL BUILDING OFFICIALS FOR SPECIFIC REQUIREMENTS.
7. GYPSUM BOARD APPLIED TO A CEILING SHALL BE 12" WHEN FRAMING MEMBERS ARE 24" O.C. OR USE 1 1
4. THE GENERAL CONTRACTOR IS TOTALLY RESPONSIBLE FOR ALL BUILDING SECTION
"HOLD" DIMENSIONS AND IS TO CONTACT THE DESIGNER FIRST, LABELED 12" SAG-RESISTANT GYPSUM CEILING BOARD, (TABLE R702.3.5(D)) A7.1 A7.1 REFERENCE
PRIOR TO BUILDING WALLS, IF THERE IS A QUESTION.

NEW CONDITIONED STUDIO


8. SHOWERS AND TUB-SHOWER COMBINATIONS SHALL BE PROVIDED WITH INDIVIDUAL CONTROL ALL CONSTRUCTION SHALL COMPLY WITH THE FOLLOWING BUILDING CODES:
5. ALL SUB-CONTRACTORS SHALL BE LICENSED CONTRACTORS VALVES OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. (P2708.4)
ENERGY COMPLIANCE REQUIREMENTS DOOR AND FRAME
POSSESSING GOOD LABOR RELATIONS AND MUST BE CAPABLE OF NUMBER 2018 INTERNATIONAL BUILDING CODE
Using Prescriptive method CERTIFICATE (MANDATORY) (N1101.14) QUALITY WORKMANSHIP IN HARMONY WITH OTHER 9. SHOWER AREA WALLS SHALL BE FINISHED WITH A SMOOTH, HARD NON-ABSORBENT SURFACE, SUCH
SUBCONTRACTORS WORKING ON THE PROJECT. AS CERAMIC TILE TO A HEIGHT OF NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. CEMENT, 2018 INTERNATIONAL RESIDENTIAL CODE
(Mandatory requirements N1101.13) A permanent certificate shall be completed by the builder FIBER-CEMENT OR GLASS MAT GYPSUM BACKERS INSTALLED IN ACCORDANCE WITH
or other approved party and posted on a wall in the space MANUFACTURERS' RECOMMENDATIONS SHALL BE USED AS BACKERS FOR WALL TILES IN TUB AND WINDOW DESIGNATION 2018 INTERNATIONAL MECHANICAL CODE
· Certificate, N1101.14. 6. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS OR
where the furnace is located, a utility room or SHOWER AREAS AND WALL PANELS IN SHOWER AREAS. (R702.4.2)
· Air leakage, N1102.4. (Third-party testing) an approved location inside the building. Where located OUTSIDE SERVICES COMPLETING WORK ON THIS PROJECT SHALL
2018 INTERNATIONAL PLUMBING CODE

WITH BATHROOM
on an electrical panel, the certificate shall not cover or COMPLY WITH ALL THE PROVISIONS OF O.S.H.A. (OCCUPATIONAL
· Controls, 1103.1.1 (Programmable thermostat/s) SAFETY AND HEALTH ACT). 10. PLUMBING FIXTURES SHALL COMPLY WITH THE FOLLOWING CONSERVATION REQUIREMENTS: WATER LEGEND NOTE
obstruct the visibility of the circuit directory label, service CLOSETS-TANK TYPE 1.28 GAL./FLUSH. SHOWER HEADS-2.0 GPM, SINKS-2.2 GPM, LAVATORY-1.5 GPM 2018 INTERNATIONAL FUEL GAS CODE
· Duct sealing, N1103.3 (Third-party testing) disconnect label or other required labels. The certificate (TABLE P2903.2 AMENDED).
shall indicate the following. 7. THE G/C SHALL POST THE BUILDING PERMIT AT THE JOB SITE AND
· Building cavities, N1103.3.5
2018 INTERNATIONAL ENERGY CONSERVATION CODE
MAKE IT VISIBLE TO ALL WHO VISIT AND WILL KEEP APPROVED WALL SECTION OR DETAIL
The predominant R-values of insulation installed in or on PERMIT DRAWINGS ON-SITE AT ALL TIMES UNTIL THE CERTIFICATE 11. STORAGE-TANK TYPE WATER HEATERS SHALL BE INSTALLED WITH A DRAIN PAN AND DRAIN LINE.
· Circulation hot water system, N1103.6 (P2801.6) REFERENCE 2017 NATIONAL ELECTRIC CODE
ceilings, roofs, walls, foundation components such as OF OCCUPANCY IS ISSUED.
· Mechanical Ventilation, N1103.7 slabs, basement walls, crawl space walls and floors, and
ducts outside conditioned spaces. U-factors of 8. ALL PRODUCT SUBSTITUTIONS MUST BE APPROVED BY THE 12. A DEMAND CONTROLLED HOT WATER CIRCULATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE
· Equipment sizing, N1103.7 WITH AMENDED SECTIONS N1103.5.1.1 AND N1103.5.1.2
fenestration and the solar heat gain coefficient (SHGC) of ARCHITECT. THE G/C IS RESPONSIBLE FOR SUBMITTING SAMPLES FINISHED FLOOR
· Lighting Equipment, N1104.1
Note: Builder shall provide third-party inspection
fenestration. OF EACH SUBSTITUTION FOR APPROVAL BY ARCHITECT AND THE
OWNER. 13. PROVIDE ROOF/ATTIC VENTILATION UNLESS INSULATION IS APPLIED DIRECTLY TO UNDERSIDE OF
ROOF SHEATHING OR THE DIMENSIONS IS 24 INCHES OR LESS BETWEEN THE CEILING AND BOTTOM
ELEVATION
IECC MATERIAL REPORTS
reports for duct sealing (at framing inspection) and 9. THE G/C AND ALL SUBCONTRACTORS PERFORMING WORK ON THIS OF ROOF SHEATHING. (R806.1 AMENDED)
air leakage (before final inspection) SPOT PRODUCT DESCRIPTION ICC-ESR #
PROJECT SHALL MAINTAIN CONTINUOUS PROTECTION OF
14. THE BUILDING THERMAL ENVELOPE SHALL COMPLY WITH CLIMATE ZONE 2. ENERGY COMPLIANCE ELEVATION
ADJACENT PREMISES IN SUCH MANNER AS TO PREVENT ANY
DAMAGE, LITTER OR MISCELLANEOUS DEBRIS FROM POLLUTING SHALL BE DEMONSTRATED BY UA TRADEOFF (RESCHECK) OR PERFORMANCE (REM/RATE) 1-KOTE STUCCO ESR-2729
ADJACENT BUSINESSES IN OPERATION. COMPLIANCE PATH OR BY THE FOLLOWING PRESCRIPTIVE VALUES (TABLE N1102.1.2): DATUM REFERENCE OR
I. PRESCRIPTIVE MINIMUM R-VALUES: <CEILING=R-30>/<WALLS=R-13> WORK POINT SPRAY FOAM INSULATION ESR-2847
10. WHEN BIDDING THIS PROJECT, EACH CONTRACTOR SHALL BE II. PRESCRIPTIVE MAXIMUM WINDOW FRENESTRATION VALUES: <U-FACTOR=0.40>/<SHGC=0.25>
RESPONSIBLE FOR VISITING THE SITE PRIOR TO BIDDING AND LaPOLLA FOAM-LOK 2000 ESR-2629
VERIFYING EXISTING CONDITIONS AS REFLECTED IN THESE 15. PROVIDE MINIMUM R-3 INSULATION ON HOT WATER PIPES. (N1103.5.3)
CONTRACT DOCUMENTS. ANY EXTRA WORK REQUIRED BUT NOT SOIL
INCLUDED IN THE DOCUMENTS SHALL BE REPORTED TO THE 16. SUPPLY AND RETURN DUCTS IN ATTICS SHALL BE INSULATED TO A MINIMUM R-8. DUCTS IN OTHER HARDI BUILDING PRODUCTS ESR-2658
THIRD PARTY ENERGY TESTING & INSPECTION N1103.1.1(R403.1.1) PROGRAMMABLE THERMOSTAT. ARCHITECT IMMEDIATELY. PORTIONS OF THE BUILDING SHALL BE INSULATED TO MINIMUM R-6. DUCTS AND AIR HANDLERS
LOCATED COMPLETELY INSIDE THE BUILDING THERMAL ENVELOPE ARE EXEMPT (N1103.3.1) GRAVEL THERMAL BATT INSULATION ESR-3398
* BUILDING ENVELOPE - THIRD PARTY INSPECTION (MANDATORY)
11. REQUEST CLARIFICATION OF ANY UNCLEAR DIMENSIONS NOT
OF INSULATION & AIR BARRIER The thermostat controlling the primary heating or cooling NOTED. DO NOT SCALE FOR DRAWINGS. 17. REGISTERS, DIFFUSERS AND GRILLES SHALL BE MECHANICALLY FASTENED TO RIGID SUPPORTS OR EXTERIOR INSULATION FINISH SYSTEM ESR-1720
* AIR LEAKAGE RATE - THIRD PARTY TESTING TO system of the dwelling unit shall be capable of controlling STRUCTURAL MEMBERS ON AT LEAST TWO OPPOSITE SIDES. SAND
VERIFY AIR LEAKAGE RATE the heating and cooling system on a daily schedule to 12. FOR ALL SURVEY/STACKING REQUESTS THE CONTRACTOR SHALL CULTURE STONE VENEER ESR-1215
maintain different temperature set points at different COORDINATE WITH THE ARCHITECT. THE ARCHITECT WILL SUPPLY 18. EXHAUST AIR FROM BATHROOMS, KITCHENS AND TOILET ROOMS SHALL BE EXHAUSTED DIRECTLY TO
* DUCTS TESTING - THIRD PARTY TESTING TO VERIFY CONCRETE
DUCT AIR LEAKAGE
times of the day and different days of the week. This AUTOCAD FILES NECESSARY TO COMPLETE ALL REQUESTS RELATED THE OUTDOORS, NOT RECIRCULATED OR DISCHARGED INDOORS. (M1507.2 AMENDED)
thermostat shall include the capability to set back or TO ANY SITE OR STRUCTURAL ELEMENTS SHOWN ON THESE PLANS. PREFORMED METAL ROOFING PANELS ESR-3486
WRITTEN REPORTS OF THE TESTING & INSPECTION SHALL temporarily operate the system to maintain zone 19. EXHAUST FANS IN BATHROOMS WITH A SHOWER OR TUB SHALL BE PROVIDED WITH A DELAY TIMER
BE SIGNED BY THE PARTY AND PROVIDED TO THE temperatures of not less than 55°F (13°C) to not greater OR HUMIDITY/CONDENSATION CONTROL SENSOR. EXHAUST FANS SHALL BE SWITCHED SEPARATELY WOOD (FRAMING/BLOCKING SCALE) ASPHALT ROOFING SHINGLES ESR-1475
BUILDING OFFICIAL. than 85°F (29°C). FROM LIGHTNING SYSTEMS. (R303.3)

20. PROVIDE A WALL MOUNTED GFCI PROTECTED RECEPTACLE OUTLET WITHIN 36" OF A BATHROOM OR WOOD (TRIM/FINISH) LARGE SCALE
POWDER ROOM LAVATORY. (E3901.6)

21. RECEPTACLES SERVING KITCHENS, COUNTERTOPS INSTALLED IN BATHROOMS, GARAGES, UNFINISHED


ACCESSORY BUILDINGS, OUTDOORS AND LOCATED WITHIN 6 FEET OF SINKS SHALL HAVE GFCI
WOOD (NON-CONT. BLOCKING) DEFERRED SUBMITTALS
PROTECTION FOR PERSONNEL. (E3902)
EXTEND TO EXTERIOR AND TERMINATE WITH BACKDRAFT
DAMPER M1502.3 22. ALL BRANCH CIRCUITS THAT SUPPLY 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
STEEL (LARGE SCALE) PRODUCT DESCRIPTION PROJECT NO.
35' LENGTH MAX M1502.4.5
REDUCE IN ACCORDANCE WITH M1502.4.5.1
ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
RECREATION ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL GLUE LAMINATED WOOD
(LARGE SCALE)
PREFAB ROOF TRUSSES 012423
BE PROTECTED BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER (AFCI) INSTALLED TO
DUCT TERMINATION MIN 3' IN ANY DIRECTION FROM PROVIDE PROTECTION OF THE BRAND CIRCUIT. (E3902.12)
OPENINGS INTO BUILDING M1502.3
23. GENERAL PURPOSE 15- AND 20-AMPERE RECEPTACLES SHALL BE LISTED
TAMPER-RESISTANT.(E4002.14)
PLYWOOD
(LARGE SCALE) ISSUE: DATE:
24. PROVIDE SMOKE ALARMS IN NEW AND EXISTING AREAS OF HOME. (R314)
GYPSUM WALL BOARD
25. APPROVED CARBON MONOXIDE ALARMS SHALL BE INSTALLED OUTSIDE OF EACH SEPARATE SLEEPING (LARGE SCALE)
AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS IN DWELLING UNITS WITHIN WHICH
FUEL-FIRED APPLIANCES ARE INSTALLED AND IN DWELLING UNITS THAT HAVE ATTACHED GARAGES.
(R315) BATT INSULATION

26. A MINIMUM OF 90 PERCENT OF THE PERMANENTLY INSTALLED LIGHTNING FIXTURES SHALL CONTAIN
ONLY HIGH-EFFICACY LAMPS. (N1104.1 AMENDED) RIGID INSULATION

27. RECESSED LUMINARIES INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC-RATED AND
LABELED AS HAVING AN AIR LEAKAGE RATE NOT MORE THAN 2.0 CFM. ALL RECESSED LUMINARIES ACOUSTIC TILE
SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR WALL OR (LARGE SCALE)
CEILING COVERING. (N1102.4.5)

28. PROVIDE ILLUMINATION WITH WALL SWITCHES FOR STAIRWAYS WHEN THERE ARE 6 OR MORE TILE
RISERS. (E303.7) (LARGE SCALE)

29. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE FLOOR LINE IN ANY WALL
SPACE IS MORE THAN 6 FEET, MEASURED HORIZONTALLY, FROM AN OUTLET IN THAT SPACE,
INCLUDING ANY WALL SPACE 2 FEET OR MORE IN WIDTH.(E3901.2)

30. PROVIDE A MINIMUM OF TWO 20-AMP SMALL APPLIANCE BRANCH CIRCUITS FOR THE
KITCHEN/DINING/BREAKFAST. (E3703.2)

31. BOTH METAL PIPING SYSTEMS AND GROUNDED METAL PARTS IN CONTACT WITH THE CIRCULATING
WATER ASSOCIATED WITH A HYDRO MASSAGE TUB SHALL BE BONDED TOGETHER USING AN
INSULATED, COVERED, OR BARE SOLID COPPER BONDING JUMPER NOT SMALLER THAN 8 AWG.
(E4209)
COVER SHEET
CITY OF PHOENIX
32. PROVIDE OUTSIDE COMBUSTION AIR TO ALL INDOOR FIREPLACES WITH AIR INTAKE LOCATED NOT Planning and Development Department
HIGHER THAN THE FIREBOX. (R1006.1) BY: Gary D. Swinford
33. AT LEAST ONE THERMOSTAT SHALL BE PROVIDED FOR EACH SEPARATE HEATING AND COOLING
01/16/2024

A1.0
SYSTEM. (N1103.1)

This set of plans has been reviewed for PHOENIX


CONSTRUCTION CODE requirements prior to
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
the plans where such errors are subsequently found
to be in violation of any law or ordinance.
12'-0"
4'-2" 7'-10" 2
NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
10 11 5.- INSTALL TOP
FLAHING LAST PROJECT INFORMATION

1'-0"

1'-0"
9 8

OWNER INFORMATION

WH
NICHE
8'-1"

7'-6"
NAME: ANDERSON CHRISTOPHER JON/CRUZ LUS MARIA

4'-4"
4.- POSITION ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
2'-10" 1'-4" 2'-3" 11" 2.- INSTALL WINDOW 3.- INSTALL

24
IN
PROPERTY INFORMATION

68
BATHROOM SIDE SIDE
FLASHING OPENING FLASHING
6 11 ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
2668

NICHE ASESOR PARCEL NUMBER No: 104-52-698


3'-11" 7'-9"

1'-5"
LOT NUMER: N/A

5'-3"
3

7725 W ODEUM LN, PHOENIX, AZ 85043


1 1.- INSTALL ROC # 318489

4'-7"

4'-0"

4'-0"
BOTTOM
FLAHING LAST DOOR SCHEDULE

EPTA CONSTRUCTION
6
20'-0"

HEAD

2'-4"
WINDOW FLASHING DETAIL SYMBOL ROOM QUANTITY UNIT ID^
HEIGHT
TYPE

24
1 3-0 / 8-0 8'-2 12 " IN SWING

68
NEW STORAGE 1 BATHROOM
A NEW STORGE
B 1 2-4 / 6-8 6'-10 12 " OUT SWING
A/C

NEW CONDITIONED STUDIO


9' CEILING BATHROOM

5050XO
C 1 2-6/ 6-8 6'-10 12 " SLIDING

5'-0"
MAXIMUM U-FACTOR SHALL BE 0.40
WATER BARRIER - TWO LAYERS MAXIMUM SHGC SHALL BE 0.25
OF GRADE "D" BLDG PAPER OR
APPROVED EQUIVALENT
2668
WINDOW SCHEDULE
STUCCO FINISH SYMBOL ROOM QUANTITY UNIT ID^ SILL HEAD TYPE OPERATION COLOR
3'-2" 2'-6" 1'-10" HEIGHT HEIGHT

WITH BATHROOM
WEEP SCREED PER IBC 2512.1.2 CONCRETE SLAB - SEE 1 NEW STORGE 1 5-0 / 5-0 1'-10 12 " 6'-10 12 " SLIDING XO -
FOUNDATION PLAN
MAXIMUM U-FACTOR SHALL BE 0.40
8'-1" MAXIMUM SHGC SHALL BE 0.25
FINISH GRADE per R401.3

6" MIN
5'-5" TABLE R702.4.2. PLAN AREA CALCULATIONS
SHOWER WALLS TO BE TILE OVER VAPOR BARRIER AND
2
CEMENTITIOUS, GLASS MAT BACKING OR DESCRIPTION AREA SQFT
FIBER-REINFORCED GYPSUM PANELS.
LIVEABLE CONDITIONED SPACE 2,375
DAM TEST REQUIRED. FOOTING - SEE
VERIFY DOOR OR CURTAIN AT SHOWER AS THIS IS A ROLL FOUNDATION PLAN COVERED ENTRY -
IN SHOWER. GARAGE -
WEEP SCREED DETAIL
30
3'-0"

3'-0"
80

4
A 7
2018 IRC R311.3.1 LANDING REQUIRED AT ALL EXTERIOR
COVERED PATIO -
DOORS . SCALE 3/8":1' NEW CONDITIONED STUDIO
WITH BATHROOM 276
3'-6" 5'-0" 3'-6"
2018 IRC R702.3.7.1 MOISTURE RESISTANT BOARD
5 SHALL NOT BE INSTALLED IN HIGH HUMIDITY AREA'S . NEW COVERED PATIO EXTENSION 174
FLOOR P L A N TOTAL AREA UNDER ROOF 2,825
SCALE 3/8":1' ELEV= 12'-0"
TOP OF ROOF

LOT
ELEV= 12'-0"
TOP OF ROOF DESCRIPTION AREA SQFT
ELEV= 8'-2 12 " TOTAL AREA UNDER ROOF 2819.5
TOP OF DOOR
LOT SQUARE FOOTAGE 8,169
ELEV= 9'-0"
HEIGTH CEILING LOT COVERAGE 34.52%
CITY OF PHOENIX
Planning and Development Department
KEY NOTES - ARCHITECTURAL
BY: Gary D. Swinford
1. 2X4 STUD WALL AT 16" CTS. W/ 3/8" WOOD SHEATHING AND 12" PROJECT NO.
01/16/2024 STUCCO FINSIH 2.
3.
GYP. BD. SPRAY FOAM.
12" OVERHANG
USE SIMPSON MASA MUDSILL ANCHORS FOR STANDARD FORMS -
012423
This set of plans has been reviewed for PHOENIX G90 GALVANIZED AT 32" CTS. AT ALL OUTER WALLS.
CONSTRUCTION CODE requirements prior to 4. WIDE EGRESS DOOR per R311.2
ELEV= 2'-0"
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
5.
6.
7.
CONCRETE PAD 2500 psi
5/8 IN. FIRE RATED TYPEN X DRYWALL .
2018 IRC R311.3.1 LANDING REQUIRED AT ALL EXTERIOR DOORS .
ISSUE: DATE:
Building Official from requiring correction of errors in
the plans where such errors are subsequently found
A to be in violation of any law or ordinance. KEY NOTES - BATHROOM
8. WALL MOUNTED SINK
9. TINY ROUNDED TOILET
10. TILE FLOOR SHOWER
ELEV= 0'-0" ELEV= 0'-0" 11. SHOWER GLASS DOOR -
TOP OF FOUNDATION TOP OF FOUNDATION 3.- LEFT VIEW GLASS STRENGTH: FULL TEMPERED
1.- FRONT VIEW 5
SCALE 3/8":1' 5
*NO STEP INTO THE SHOWER.

SCALE 3/8":1'
GENERAL NOTES - ARCHITECTURAL
A. FINISH FLOOR ELEVATION = 100'-0"
B. *TG* SOWN ON PLANS INDICATES "TEMPERED GLASS"
ELEV= 12'-0" C. "F" SHOWN ON PLANS INDICATES "FIXED" WINDOW UNIT; NO
ELEV= 12'-0" TOP OF THE ROOF OPERABLE PANEL
TOP OF ROOF D. "SH" SHOWN ON ARCH PLANS INDICATES "SINGLE HUNG" OPERABLE
WINDOW PANEL
E. "XO" SHOWN ON ARCH PLANS INDICATES "SLIDER" OPERABLE
WINDOW PANEL.
ELEV= 9'-0" ELEV= 9'-0" F. "1R & 1S" SHOWN ON ARCH PLANS INDICATES (1) CLOTHS ROD & (1)
HEIGTH CEILING HEIGTH CEILING 12" SHELF.
G. "MC" SHOWN ON ARCH PLANS INDICATES A SEMI-RECESSED MEDICINE
CABINET.
H. SLOPE GARAGE FLOOR DOWN 3" TOWARD OHD FOR DRAINAGE
ELEV= 6'-10 12 " I. USE SAG RESISTANT DRYWALL AT ALL CEILINGS U.N.O. ON PLANS
J. GYPSUM BACKER BD. FOR ADHESIVE APPLICATIONS of CERAMIC TILE or FLOOR PLAN &
HEAD HEIGH
OTHER NON-ABSORBENT FINISH MATERIAL SHALL CONFORM WITH
ASTM C630 or C1178. 12" M.R. GYPSUM BD. SHALL BE PERMITTED AT
BUILDING ELEVATIONS
STUCCO FINSIH CEILINGS WITH FRAMING MEMBERS SPACED at 12" CTS., and 85" WHERE
1 FRAMING MEMBERS ARE SPACED at 16" CTS. M.R. GYPSUM BD. SHALL
NOT BE INSTALLED OVER A VAPOR RETARDER IN A SHOWER or TUB
COMPARTMENT. ALL CUTS or EXPOSED EDGES, INCLUDING THOSE at
WALL INTERSECTIONS SHALL BE SEALED AS RECOMMENDED BY THE
MFR. M.R. GYPSUM BD. TO BE INSTALLED IN BATHROOMS, KITCHEN,

A2.0
LAUNDRY ROOM and GARAGE, TYP.
K. UNLESS NOTED OTHERWISE ON THE PLANS THE BOTTOM OF ALL
ELEV= 1'-10 12 " B DOORS AND WINDOW HEADERS TO BE 82 12" ABOVE FLOOR SLAB.
SILL HEIGH L. PROVIDE SOLID WOOD BLOCKING IN WALLS FOR PROPER
5 INSTALLATION OF ALL CABINETS, TOWEL BARS, SHELF STANDARDS,
MIRRORS, WALL MOUNTED ITEMS, ETC.
ELEV= 0'-0"
TOP OF FOUNDATION
2.- REAR VIEW ELEV= 0'-0" 4.- RIGHT VIEW
5
SCALE 3/8":1' TOP OF FOUNDATION SCALE 3/8":1' NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
GENERAL NOTES - ARCHITECTURAL PROJECT INFORMATION
A. FINISH FLOOR ELEVATION = 100'-0"
B. *TG* SOWN ON PLANS INDICATES "TEMPERED GLASS"
C. "F" SHOWN ON PLANS INDICATES "FIXED" WINDOW UNIT; NO OWNER INFORMATION
OPERABLE PANEL
D. "SH" SHOWN ON ARCH PLANS INDICATES "SINGLE HUNG" OPERABLE
WINDOW PANEL NAME: ANDERSON CHRISTOPHER JON/CRUZ LUS MARIA
E. "XO" SHOWN ON ARCH PLANS INDICATES "SLIDER" OPERABLE ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
WINDOW PANEL.
8'-1"
F. "1R & 1S" SHOWN ON ARCH PLANS INDICATES (1) CLOTHS ROD & (1)
12" SHELF. PROPERTY INFORMATION
7'-6" G. "MC" SHOWN ON ARCH PLANS INDICATES A SEMI-RECESSED MEDICINE
CABINET.
ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
2'-10" 1'-4" 2'-3" 11" TABLE R702.4.2. H. SLOPE GARAGE FLOOR DOWN 3" TOWARD OHD FOR DRAINAGE
SHOWER WALLS TO BE TILE OVER VAPOR BARRIER AND I. USE SAG RESISTANT DRYWALL AT ALL CEILINGS U.N.O. ON PLANS ASESOR PARCEL NUMBER No: 104-52-698
CEMENTITIOUS, GLASS MAT BACKING OR J. GYPSUM BACKER BD. FOR ADHESIVE APPLICATIONS of CERAMIC TILE or
OTHER NON-ABSORBENT FINISH MATERIAL SHALL CONFORM WITH
FIBER-REINFORCED GYPSUM PANELS. ASTM C630 or C1178. 12" M.R. GYPSUM BD. SHALL BE PERMITTED AT LOT NUMER: N/A
DAM TEST REQUIRED. CEILINGS WITH FRAMING MEMBERS SPACED at 12" CTS., and 85" WHERE
VERIFY DOOR OR CURTAIN AT SHOWER AS THIS IS A ROLL FRAMING MEMBERS ARE SPACED at 16" CTS. M.R. GYPSUM BD. SHALL
IN SHOWER. NOT BE INSTALLED OVER A VAPOR RETARDER IN A SHOWER or TUB
ROC # 318489

1'-5"
COMPARTMENT. ALL CUTS or EXPOSED EDGES, INCLUDING THOSE at
WALL INTERSECTIONS SHALL BE SEALED AS RECOMMENDED BY THE
2018 IRC R311.3.1 LANDING REQUIRED AT ALL EXTERIOR MFR. M.R. GYPSUM BD. TO BE INSTALLED IN BATHROOMS, KITCHEN,
9 LAUNDRY ROOM and GARAGE, TYP. DOOR SCHEDULE
DOORS . K. UNLESS NOTED OTHERWISE ON THE PLANS THE BOTTOM OF ALL
SYMBOL ROOM QUANTITY UNIT ID^ HEAD TYPE
DOORS AND WINDOW HEADERS TO BE 82 12" ABOVE FLOOR SLAB. HEIGHT
4'-7"

4'-0"

4'-0"
8
10 2018 IRC R702.3.7.1 MR BOARD SHALL NOT BE L. PROVIDE SOLID WOOD BLOCKING IN WALLS FOR PROPER NEW STORGE 1 3-0 / 8-0 8'-2 12 " IN SWING

7725 W ODEUM LN, PHOENIX, AZ 85043


INSTALLED IN HIGH HUMIDITY AREA'S . INSTALLATION OF ALL CABINETS, TOWEL BARS, SHELF STANDARDS, 1 2-4 / 6-8 6'-10 12 " OUT SWING
MIRRORS, WALL MOUNTED ITEMS, ETC. BATHROOM

2'-4"
1 2-6/ 6-8 6'-10 12 " SLIDING
MAXIMUM U-FACTOR SHALL BE 0.40

EPTA CONSTRUCTION
BATHROOM
MAXIMUM SHGC SHALL BE 0.25

NEW CONDITIONED STUDIO


11

WINDOW SCHEDULE
SILL HEAD

WITH BATHROOM
SYMBOL ROOM QUANTITY UNIT ID^ TYPE OPERATION COLOR
3'-2" 2'-6" 1'-10" HEIGHT HEIGHT
NEW STORGE 1 5-0 / 5-0 1'-10 12 " 6'-10 12 " SLIDING XO -
MAXIMUM U-FACTOR SHALL BE 0.40
8'-1"
MAXIMUM SHGC SHALL BE 0.25

BATHROOM PLAN
NOT TO SCALE
PLAN AREA CALCULATIONS
DESCRIPTION AREA SQFT
LIVEABLE CONDITIONED SPACE 2,375
COVERED ENTRY -
GARAGE -
COVERED PATIO -
NEW CONDITIONED STUDIO
WITH BATHROOM 276

NEW COVERED PATIO EXTENSION 174


Shower Pan Liner TOTAL AREA UNDER ROOF 2,825
APPLICATION INSTRUCTIONS
SUGGESTED BRAND
DAM CORNERS– FOR OUTSIDE CORNERS AND
Tile Shower Drain

Strainer
Tile Shower Drain– PVC for PVC drain
pipe or ABS for ABS drain pipe. Each is
OVER THE CURB PREFORMED DAM CORNERS ARE
AVAILABLE, WHICH CAN BE USED FOR PVC OR CPE PAN
LOT
available with stainless steel, polished
brass or white plastic strainer. LINER APPLICATIONS.
DESCRIPTION AREA SQFT
Adjustable
Drain Barrel
X-15 or CPE (Oateyweld) bonding
adhesive– For use on dam corners or
seaming use X-15 for PVC and Oateyweld
NOTE: OATEY PAN LINER INSTRUCTIONS ASSUME THE
SHOWER FRAMING HAS BEEN CONSTRUCTED AND THE
TOTAL AREA UNDER ROOF 2819.5
PROJECT NO.
012423
Collar for CPE.
Bolts FLOORING IS PLYWOOD. GENERALLY THE SAME PRINCIPLES
PVCor ABS solvent cement– PVC solvent APPLY TO CONCRETE FLOORING WHERE THE SLOPED
cement and primer for PVC drainage
systems or ABS solvent cement for ABS MORTAR BED IS APPLIED BENEATH THE PAN LINER. ALSO
LOT SQUARE FOOTAGE 8,169
Reversible drainage systems. Use the appropriate
Clamping Ring cement (and primer for PVC) to solvent THE INSTRUCTIONS APPLY TO EITHER PVC PAN LINER OR LOT COVERAGE 34.52%
weld tile shower drain to the drain pipe. CPE PAN LINER WHICH ARE INSTALLED THE SAME WITH

Drain Base
THE EXCEPTION OF THE BONDING ADHESIVE USED FOR
SEAMING AND DAM CORNER APPLICATIONS. IF YOU HAVE
QUESTIONS REGARDING PAN LINER INSTALLATION THAT
ISSUE: DATE:
ARE NOT COVERED IN THESE INSTRUCTIONS, CONTACT
Shower Pan Installation OATEY CUSTOMER SERVICE AT 800-321-9532 AND YOU
SUGGESTED BRAND
WILL BE REFERRED TO SOMEONE WHO CAN ASSIST YOU. KEY NOTES - ARCHITECTURAL
1. 2X4 STUD WALL AT 16" CTS. W/ 3/8" WOOD SHEATHING AND 12"
GYP. BD. SPRAY FOAM.
1. FOR TYPICAL WOOD SUBFLOOR CUT A 4.5" DIAMETER 2. 12" OVERHANG
Figure A
HOLE IN THE CENTER OF THE SHOWER FLOOR WHERE 3. USE SIMPSON MASA MUDSILL ANCHORS FOR STANDARD FORMS -
THE TILE SHOWER DRAIN WOULD NORMALLY BE G90 GALVANIZED AT 32" CTS. AT ALL OUTER WALLS.
Studding
POSITIONED. DISASSEMBLE THE TILE SHOWER DRAIN. 4. WIDE EGRESS DOOR per R311.2
Water Proof Drywall
Upper Section LAY THE TILE SHOWER DRAIN BASE IN THE OPENING 5. CONCRETE PAD 2500 psi
Thin Set (Setting Bed) of Drain SO THE FLANGE OF THE DRAIN BASE RESTS ON TOP OF 6. 5/8 IN. FIRE RATED TYPEN X DRYWALL .
Adjusts to
Tile Height of Tile Locking Ring THE SUBFLOOR. SOLVENT WELD THE DRAIN BASE TO 7. 2018 IRC R311.3.1 LANDING REQUIRED AT ALL EXTERIOR DOORS .
of Drain
Concrete Mortar (Bolts to Hold THE DRAIN PIPE USING THE APPROPRIATE SOLVENT
Down Liner) CEMENT. SEE FIGURE A.

2. COVER THE DRAIN BASE OPENING WITH DUCT TAPE


TO KEEP DEBRIS FROM ENTERING THE DRAIN. BEGIN KEY NOTES - BATHROOM
BY APPLYING PORTLAND SAND/ CEMENT MIXTURE
MORTAR BED OVER THE SUBFLOOR AT 1/4" PER FOOT 8. WALL MOUNTED SINK
Subfloor
(Wood or Concrete)
Tile Shower Drain
Mounted on Top
Pea Drain Pipe Shower
SLOPE FROM THE WALL FRAMING TO THE TOP OF, BUT 9. TINY ROUNDED TOILET
Gravel Pan Liner
of Subfloor to Cover NOT OVER, THE DRAIN BASE. AFTER THIS STEP THE 10. TILE FLOOR SHOWER
Weep Holes
SLOPED MORTAR BED SHOULD BE FLUSH WITH THE 11. SHOWER GLASS DOOR -
TOP SURFACE OF THE DRAIN BASE. GLASS STRENGTH: FULL TEMPERED
*NO STEP INTO THE SHOWER.
SHOWER DETAILS
CITY OF PHOENIX
Planning and Development Department

WATER RPOOFING MEMBRANE BY: Gary D. Swinford

NOT TO SCALE 01/16/2024

A2.1
This set of plans has been reviewed for PHOENIX
CONSTRUCTION CODE requirements prior to
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
the plans where such errors are subsequently found
to be in violation of any law or ordinance.
7725 W ODEUM LN, PHOENIX, AZ 85043
PLAN AREA CALCULATIONS ROC # 318489
14'-6"
DESCRIPTION AREA SQFT

EPTA CONSTRUCTION
LIVEABLE CONDITIONED SPACE 2,375
COVERED ENTRY -

NEW CONDITIONED STUDIO


GARAGE -
COVERED PATIO -
NEW CONDITIONED STUDIO

BUILT IN SITE TRUSSES @24" O.C. MAX.


WITH BATHROOM 276

WITH BATHROOM
NEW COVERED PATIO EXTENSION 174
TOTAL AREA UNDER ROOF 2,825

12'-0"
BUILT IN SITE TRUSSES @ 24" O.C. MAXIMUM

LOT
O'HAGIN TILE FIELD
SLOPE 5:12 SLOPE 5:12 DESCRIPTION AREA SQFT VENT - MODEL 'S'
TOTAL AREA UNDER ROOF 2819.5
HDR (2) 2X6's
A/C

LOT SQUARE FOOTAGE 8,169


LOT COVERAGE 34.52%

ROOF TILE TYPE


SCALE 3/8":1'
ADDRESS 7725 W ODEUM LN
PHOENIX, AZ 85043

DIVISION CONCRETE
TILE WEIGHT STANDRADWEIGHT
PROFILE GROUP MISSION S
PRODUCT COLOR MARBLED TERRA COTTA
ENVIROPRO NO

TRUSSES SHALL BE DESIGNED BY AN ARIZONA


REGISTERED ENGINEER. (P.E.)
1'-0"

PROJECT NO.
1'-0" 1/2" EXTERIOR RATED GYP. BD. AT PATIO/PORCH 012423
OVERHANG ROOF PLAN CEILING ICC ESR-1338
SCALE 3/8":1'
ISSUE: DATE:

ATTIC VENT CALCULATIONS


ROOF AREA 'SF' / 300
SUBJECT ROOF AREA REQUIRED VENT AREA AREA PER VENT IN # OF VENTS
CITY OF PHOENIX
SQFT IN SQ INCHES SQ INCHES REQUIRED ROOF PLAN
Planning and Development Department COVERED PATIO 174 84 98.75 1
BY: Gary D. Swinford
TOTAL 174 647 1
01/16/2024
This set of plans has been reviewed for PHOENIX

A2.2
CONSTRUCTION CODE requirements prior to
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
the plans where such errors are subsequently found NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
TRUSS AT WALL to be in violation of any law or ordinance.
NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
HOUSE COLORS
CATEGORY SELECTED COLOR

MAIN BODY SW7517 CHINA DOLL

SECONDARY BODY N/A

GARAGE DOOR SW7520 PLANTATION SHUTTERS


ELEV= 12'-0"
TOP OF ROOF TRIM SW6101 SANDS OF TIME
ATTIC
ACCES RAIL SW7020 BLACK FOX

FASCIA SW6048 TERRA BRUN


ELEV= 7'-2"
TOP OF DOOR SHUTTER SW6048 TERRA BRUN

7725 W ODEUM LN, PHOENIX, AZ 85043


FRONT DOOR SW6048 TERRA BRUN
5.- INSTALL TOP CORBELS/BRACKETS N/A
ROC # 318489
FLAHING LAST

A/C

EPTA CONSTRUCTION
DECORATIVE SW7020 BLACK FOX

ROOF SW7020 BLACK FOX

NEW CONDITIONED STUDIO


STONE MARBLED TERRA COTTA MSCS6129

GRUTTER AUTUMN BLEND -TUMBLED CAST BRIC

DOWNSPOUT ROYAL BROWN

OPTIONAL ROOF N/A

WITH BATHROOM
B-4 B-4 OPTIONAL STONE N/A
ELEV= 0'-0"
TOP OF FOUNDATION
4.- POSITION
2.- INSTALL WINDOW 3.- INSTALL
SIDE IN SIDE
FLASHING OPENING FLASHING
SECTION B-4
1/2" EXTERIOR RATED GYP. BD. AT PATIO/PORCH
CEILING ICC ESR-1338

ELEV= 12'-0"
TOP OF THE ROOF TRUSSES SHALL BE DESIGN BY ARIZONA REGISTERED
ATTIC ENGINEER.
ACCES
ELEV= 9'-0"
HEIGTH CEILING
1.- INSTALL
ELEV= 7'-2" BOTTOM
HEAD HEIGH
FLAHING LAST

WINDOW FLASHING DETAIL


PROJECT NO.
ELEV= 2'-2"
SILL HEIGH
012423
WATER BARRIER - TWO LAYERS
ELEV= 0'-0" OF GRADE "D" BLDG PAPER OR ISSUE: DATE:
TOP OF FOUNDATION
APPROVED EQUIVALENT
SECTION A-4
STUCCO FINISH
WEEP SCREED PER IBC 2512.1.2 CONCRETE SLAB - SEE
FOUNDATION PLAN
A/C
FINISH GRADE per R401.3

6" MIN
BUILDING
ACCES
ATTIC

CITY OF PHOENIX
Planning and Development Department
SECTIONS
BY: Gary D. Swinford FOOTING - SEE
FOUNDATION PLAN
01/16/2024

A2.3
This set of plans has been reviewed for PHOENIX
A-4 A-4 CONSTRUCTION CODE requirements prior to
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
WEEP SCREED DETAIL
the plans where such errors are subsequently found
to be in violation of any law or ordinance.
12"X12" FRAMED COLUMN
2 SIMPSON 14'-6" 2 SIMPSON 12"X12" FRAMED COLUMN
STDH14 STDH14
14'-6"
PROJECT INFORMATION
OWNER INFORMATION
ROOF TILE TYPE
ADDRESS 7725 W ODEUM LN NAME: ANDERSON CHRISTOPHER JON/CRUZ LUS MARIA
PHOENIX, AZ 85043 ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
FULLY SHEATH COLUMN W/ 83"
A.P.A. SHTG W/ 8d NAILS @3" DIVISION CONCRETE
O.C. TILE WEIGHT STANDRADWEIGHT PROPERTY INFORMATION

BUILT IN SITE TRUSSES @24" O.C. MAX.


PROFILE GROUP MISSION S
3-1/8"X12" 3-1/8"X12" PRODUCT COLOR MARBLED TERRA COTTA ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
30" SQX12" THICK FTG W/#4 GLULAM BEAM GLULAM BEAM ENVIROPRO NO
BARS @ 8" O.C. EACH WAY OR EQ. OR EQ. ASESOR PARCEL NUMBER No: 104-52-698
J

12'-0"

12'-0"
LOT NUMER: N/A
O'HAGIN TILE FIELD
VENT - MODEL 'S'
CAN LIGHT

7725 W ODEUM LN, PHOENIX, AZ 85043


NEW 4" CONCRETE
2 SIMPSON SLAB OVER 4" ABC 12"X12" FRAMED COLUMN ATTIC VENT CALCULATIONS ROC # 318489
STDH14 FILL- SLOPE 14" PER ROOF AREA 'SF' / 300

EPTA CONSTRUCTION
FOOT TO DRAIN SUBJECT ROOF AREA REQUIRED VENT AREA AREA PER VENT IN # OF VENTS
18"X18" SLOPE 4:12 SQFT IN SQ INCHES SQ INCHES REQUIRED
18"X18"
EXISTING EXISTING

NEW CONDITIONED STUDIO


FRAMED COVERED PATIO 174 84 98.75 1
FRAMED
COLUMN COLUMN TOTAL 174 647 1
EXISTING COVERED PATIO
EGRESS
SLIDING DOOR COVERED PATIO EXTENSION 1/2" EXTERIOR RATED GYPSUM BOARD AT
COVERED PATIO EXTENSION FRAMING PLAN PATIO/PORCH CEILING ICC ESR-1338

WITH BATHROOM
SCALE 3/8":1'
FOUNDATION & ELECTRICAL *TRUSSES SHALL BE DESIGN BY ARIZONA REGISTERED ENGINEER.
SCALE 3/8":1'
*EXTERIOR LIGHTING SHALL BE DAMP PROOF.
WHERE POST OCCURS IN CENTER: USE
SIMP. ABU SIZED FOR POST W/ 1/2" DIA.
TITEN HD W/ 6" EMBED EXISTING BEAM SIMP. CS20 STRAP W/ (10) 8d
INTO BEAM & (10) 8d INTO TOP
2x WOOD STUDS @ 16" O.C.
PLATE
MIN. 3/8" APA RATED SHTG. ON ALL SIDES
W/ 8d @ 3" O.C. ON ALL FOUR SIDES OF
FRAMED COLUMN

2x CONT. PRESSURE TREATED PLATE W/


5/8" DIA. x 12" LONG (EMBEDDED 8" MIN. W/
2 X 2 X 3/16" PLATE WASHER , MIN. (1)
4" NOM. CONC. SLAB BOLT PER PIECE.
O/ 4" A.B.C.
8" MIN.

BEAM - SEE FRAMING PLAN


HHUS 26-2

FINISH GRADE
SIMP. CS20 STRAP W/ (8) 8d NAILS
1'-6" MIN.

INTO BEAM & (8) INTO


HHUS210-2Z TRIMMER / POST @ EA. SIDE OF
12"

BEAM TO POST @ BEAM SPANS 10'-0" &


TRUSS AT WALL CITY OF PHOENIX
GREATER
(1)#4 VERT. EA. CORNER & @ 24" O.C.
Planning and Development Department
THEREAFTER W/ #3 TIES @ 8" O.C., (3)
FRAMED COLUMN FOUNDATION
3"
IN TOP 5"
SECTION BY: Gary D. Swinford PROJECT NO.
BOTTOM OF FOOTING SHALL BE MIN. 01/16/2024 012423
1'-6" MIN. BELOW TOP OF This set of plans has been reviewed for PHOENIX BUILT-UP OR SOLID WOOD
UNDISTURBED SOIL W/IN 5'-0' OF SLO
PE 5 CONSTRUCTION CODE requirements prior to POST/TRIMMER & KING STUD
:12
A
FOUNDATION EDGE issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
ISSUE: DATE:
the plans where such errors are subsequently found
to be in violation of any law or ordinance. HOUSE COLORS
CATEGORY SELECTED COLOR
SLOP
E 4:1 MAIN BODY SW7517 CHINA DOLL
ELEV= 11'-9"
2
TOP OF GABLE SECONDARY BODY N/A

GARAGE DOOR SW7520 PLANTATION SHUTTERS

TRIM SW6101 SANDS OF TIME


ELEV= 9'-0"
HEIGTH CEILING TRUSSES @24" O.C. MAX. RAIL SW7020 BLACK FOX

12"X12" FASCIA SW6048 TERRA BRUN


FRAMED
COLUMN COVERED PATIO EXTENSION EXISTING HOUSE SHUTTER SW6048 TERRA BRUN

FRONT DOOR SW6048 TERRA BRUN

CORBELS/BRACKETS N/A

DECORATIVE SW7020 BLACK FOX


COVERED PATIO
12"X12" FRAMED COLUMN ROOF SW7020 BLACK FOX
EXTENSION PLAN
14'-6"
STONE MARBLED TERRA COTTA MSCS6129

GRUTTER AUTUMN BLEND -TUMBLED CAST BRIC

COVERED PATIO EXTENSION ELEVATION

A3.0
ELEV= 0'-0" DOWNSPOUT ROYAL BROWN
TOP OF FOUNDATION
SCALE 3/8":1' OPTIONAL ROOF N/A
A
OPTIONAL STONE N/A

FRONT ELEVATION NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
PROJECT INFORMATION
OWNER INFORMATION
ROOF TILE TYPE
ADDRESS 7725 W ODEUM LN NAME: ANDERSON CHRISTOPHER JON/CRUZ LUS MARIA
PHOENIX, AZ 85043 ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
DIVISION CONCRETE
TILE WEIGHT STANDRADWEIGHT PROPERTY INFORMATION
PROFILE GROUP MISSION S
PRODUCT COLOR MARBLED TERRA COTTA ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043
ENVIROPRO NO
ASESOR PARCEL NUMBER No: 104-52-698

LOT NUMER: N/A

HOUSE COLORS ROC # 318489


CATEGORY SELECTED COLOR

MAIN BODY SW7517 CHINA DOLL

7725 W ODEUM LN, PHOENIX, AZ 85043


SECONDARY BODY N/A

EPTA CONSTRUCTION
GARAGE DOOR SW7520 PLANTATION SHUTTERS

TRIM SW6101 SANDS OF TIME

NEW CONDITIONED STUDIO


RAIL SW7020 BLACK FOX

1 ROOF TO WALL FASCIA SW6048 TERRA BRUN


ISOMETRIC DETAIL SHUTTER SW6048 TERRA BRUN

WITH BATHROOM
NO SCALE
FRONT DOOR SW6048 TERRA BRUN

CORBELS/BRACKETS N/A

DECORATIVE SW7020 BLACK FOX

ROOF SW7020 BLACK FOX

STONE MARBLED TERRA COTTA MSCS6129

GRUTTER AUTUMN BLEND -TUMBLED CAST BRIC


2 ROOF TO ROOF
DOWNSPOUT ROYAL BROWN
EXISTING TILE ISOMETRIC DETAIL
OPTIONAL ROOF N/A
NO SCALE
OPTIONAL STONE N/A

FIELD VERIFY FLASHING AT NEW TO EXISTING WALL


AND ROOF TO ROOFL

PROJECT NO.
012423

ISSUE: DATE:
BREAK THE
EXISTING STUCCO
TO INSTALL NEW
UNERLAYMENT

PLACE A NEW UNDERLAYMET ASTM


40 UNDER THE EXISTING ONE

FLASHING AND METALS DETAIL 1 ROOF TO WALL


TO MATCH WITH
EXISTING CITY OF PHOENIX
COVERED PATIO
Planning and Development Department
BY: Gary D. Swinford
EXTENSION PLAN
TILE TO
MATCH WITH 01/16/2024
EXISTING DETAIL 2 ROOF TO ROOF This set of plans has been reviewed for PHOENIX
CONSTRUCTION CODE requirements prior to

A3.1
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
the plans where such errors are subsequently found
NEW COVERED PATIO to be in violation of any law or ordinance.
DETAIL NEW ROOF TO EXISTING STRUCTURE
NO SCALE
1. ANCHOR BOLTS 6. A HOLE NOT GREATER IN DIAMETER THAN 40% OF THE STUD WIDTH MAY BE BORED
GENERAL STRUCTURAL NOTES 2. CONCRETE MIXES SHALL BE DESIGNED BY A CERTIFIED LABORATORY AND IN ANY WOOD STUD. BORED HOLES NOT GREATER THAN 60% OF THE WIDTH OF THE STRAP TYPE HOLDOWN BOLT TYPE HOLDOWN
1 PAHD42 HTT16, PHD2
APPROVED BY THE ENGINEER. MIX DESIGNS SHOULD INCLUDE THE AMOUNT OF 1. SILL PLATE ANCHORAGE AT CONCRETE OR MASONRY SHALL BE DIAMETER 2"
STUD ARE PERMITTED IN NONBEARING PARTITIONS OR IN ANY WALL WHERE EACH
HPAHD22 HTT22, PHD5
GENERAL CEMENT, AGGREGATE (FIRE & COARSE), WATER AND ANG ADMIXTURES. MIX EMBEDDED ANCHOR BOLTS. ALL ANCHOR BOLTS (OTHER THAN BOLTS FOR BORED STUD IS DOUBLE PROVIDED NOT MORE THAN TWO SUCH SUCCESSIVE
LSTHD8 HTT16, HD2A, PHD2
DESIGNS SHALL BE PROVIDED A MINIMUM 2 WEEKS PRIOR TO PLACEMENT TO HOLDOWNS) SHALL BE EMBEDDED 7 INCHES MINIMUM INTO THE CONCRETE. ANCHOR DOUBLED STUDS ARE SO BORED. IN NO CASE SHALL THE EDGE OF THE BORED HOLE STHD8 HTT16, HD5A, PHD2
1. THE STRUCTURES DEPICTED HEREIN HAVE BEEN DESIGNED PRIMARILY TO ALLOW FOR REVIEW. MIX DESIGNS FOR CONCRETE SLABS SHALL BE BOLTS FOR HOLDOWNS SHALL NOT BE CONSIDERED AS PART OF THE REQUIRED SILL BE NEARER THAN 58" IN TO THE EDGE OF THE STUD. BORED HOLES SHALL NOT BE STHD10 HTT22, MTT28B, HD5A
SAFEGUARD AGAINST MAJOR STRUCTURAL DAMAGE AND LOSS OF LIFE, NOT TO PROPORTIONED SO AS TO MINIMIZE SHRINKAGE. PLATE ANCHOR BOLTS AS SPECIFIED IN THE SHEARWALL SCHEDULE OR GSN. LOCATED AT THE SAME SECTION OF STUD AS A CUT OR NOTCH. (2308.5.10 IBC 2018) DO STHD14 PHD6, HD8A
LIMIT DAMAGE OR MAINTAIN FUNCTION. (2018 INTERNATIONAL BUILDING CODE INTERIOR WALLS MAY BE ANCHORED TO THE CONCRETE WITH EMBEDDED ANCHOR NOT NOTCH JOISTS, RAFTERS OR BEAMS, EXCEPT WHERE SHOWN IN DETAILS. OBTAIN PA18, PA23, & PA28 HTT16
101.3) 3. ADMIXTURES THAT CONTAIN CHLORIDE WILL NOT BE PERMITTED TO BE USED BOLTS, EXPANSION ANCHORS OR POWDER DRIVEN FASTENERS AS SPECIFIED BELOW, ENGINEER'S APPROVAL FOR ANY HOLES OR NOTCHES NOT DETAILED. HPA28 HTT22
U.N.O. SPECIFICALLY ON THE PLANS. HPA35 PHD6, HD6A
2. THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL 4. CONCRETE TEST CYLINDERS MUST BE TAKEN AND TESTED IN ACCORDANCE WITH 1
7. ALL BOLTS SHALL BE INSTALLED IN HOLES BORED WITH A BIT 16 INCH LARGER THAN
CARE AND COMPLETENESS NORMALLY EXERCISED UNDER SIMILAR ACI STANDARDS FOR ALL POURS OF 50 YARDS OR MORE. 2. ALL SHEARWALLS SHALL BE ANCHORED TO THE CONCRETE PER THE SHEARWALL 4. ANCHOR BOLT HOLDOWN ANCHORAGE SHALL HAVE STANDARD HEX HEAD AT
THE DIA. OF THE BOLT. BOLTS AND NUTS SEATING ON WOOD SHALL HAVE CUT STEEL
CIRCUMSTANCES BY REPUTABLE STRUCTURAL ENGINEERS IN THIS OR SIMILAR SCHEDULE, GSN OR DETAILS. EMBEDDED END. THE EMBEDDED ANCHOR BOLT DIAMETER AND DEPTH OF EMBEDMENT
WASHERS UNDER HEADS AND NUTS. DING THREADS TO PREVENT LOOSENING. LAG
LOCALITIES. THESE DRAWINGS ASSUME THAT THE WORK DEPICTED WILL BE 5. DO NOT ADD WATER TO CONCRETE AFTER PLACEMENT. OR RETROFIT EMBEDMENT SHALL BE AS FOLLOWS:
BOLTS SHALL BE INSTALLED IN PRE-DRILLED HOLES BY TURNING WITH A WRENCH.
PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKMEN WHO HAVE 3. WHERE EXTERIOR WALL EMBEDDED ANCHOR BOLTS HAVE BEEN MISSED, DAMAGED
A WORKING KNOWLEDGE OF THE APPLICABLE CODE STANDARDS AND 6. ALL CONCRETE THAT MAY CONTACT WATER ARE O BE AIR-ENTRAINED PER ASTM SIMPSON MINIMUM BOLT MINIMUM ALL-THREAD MIN. EMBED SIMPSON SSTB ALT
OR MISLOCATED, ONE OF THE FOLLOWING RETROFIT OPTIONS MAY BE USED ST THE 8. ALL NAILS EXCEPT 16d NAILS SHALL BE COMMON NAILS U.N.O. 16d NAILS MAY BE 16d HOLDOWN DIA. EMBED DIAMETER EPOXY GROUT MONO POUR TWO POUR
REQUIREMENTS AND OF INDUSTRY ACCEPTED STANDARD GOOD PRACTICE. AS C260, C494, & C618. CONTRACTORS DISCRETION: SINKER, 16d BOX, PNEUMATIC (P-NAIL), OR 12d COMMON U.N.O. NAILS SHALL BE DRIVEN HTT4 5/8 " 8" 5/8 " 7 1/4" SSTB16 SSTB20
NOT EVERY CONDITION OR ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN ON SO THAT HEADS ARE FLUSH WITH WOOD SURFACE. OVER-OR UNDER-DRIVEN NAILS HTT5 5/8 " 10" 5/8 " 10" SSTB24 ---
THESE DRAWINGS, IT IS UNDERSTOOD THAT THE CONTRACTOR WILL USE 7. ALL CONCRETE SHALL BE NORMAL WEIGHT OF 145 POUNDS PER CUBIC FOOT 3.1 21" DIAMETER EXPANSION BOLTS, PROVIDE (2) 21" DIAMETER EXPANSION ANCHORS WILL NOT BE ACCEPTABLE. MISC. NAILING SHALL BE PER IBC TABLE 2304.10.1 NAILING MTT28B 5/8 " 8 3/4" 5/8 " 8 3/4" SSTB20 SSTB24
INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR ALL MISCELLANEOUS USING HARDROCK AGGREGATES. HD3B 5/8 " 7" 5/8 " 7" SSTB16 SSTB20
FOR EACH 21" DIAMETER EMBEDDED ANCHOR BOLT. EXPANSION ANCHORS SHALL BE SCHEDULE.
WORK NOT EXPLICITLY SHOWN ON THE DRAWINGS. HD5B 5/8 " 8" 5/8 " 8" SSTB20 SSTB24
8. MAXIMUM SLUMP SHALL BE 4.5 INCHES, AND THE WATER SHALL BE CLEAN AND INSTALLED NOT CLOSER THAN 6 21" O.C. AND SHALL BE INSTALLED WITH A MINIMUM OF HD7B 7/8 " 12" 7/8 " 14" SSTB28 SSTB24
NAIL SIZE SHANK DIAMETER LENGTH
3. CALCULATIONS AND DESIGN OF MISCELLANEOUS NON-STRUCTURAL ITEMS, SUCH POTABLE. 4 81" EMBEDMENT AND SPACED 1 34" FROM THE EDGE OF THE SLAB, EXPANSION 16d COMMON .162" 3 21"
HD9B 7/8 " 14" 7/8 " 18" SSTB28 SSTB34
HD12 1 1/8 " 17" 1 1/8 " 20" --- ---
AS STAIRS, RAILINGS, NON-STRUCTURAL WALLS AND PREFABRICATED ANCHORS BEING INSTALLED LESS THAN 2" FROM THE EDGE OF THE CONCRETE SHALL 16d SINKER .148" 3 41" HD19B 1 1/4 " 24" 1 1/4 " 24" --- ---
STRUCTURAL ITEMS, FOR EXAMPLE, FLOOR AND ROOF TRUSSES, ARE NOT 9. PORTLAND CEMENT SHALL CONFORM TO IBC 19. TYPE V CEMENT SHALL BE USED BE TRUEBOLT EXPANSION ANCHORS AS MANUFACTURED BY ITW RAMSET/REDHEAD 3 21"

7725 W ODEUM LN, PHOENIX, AZ 85043


16d BOX .135" HDU4 5/8 " 8" 5/8 " 8" SSTB16 SSTB20
INCLUDED AND ARE TO BE PROVIDED BY OTHERS UNLESS SPECIFICALLY NOTED FOR CONCRETE IN CONTACT WITH THE SOIL. TYPE II CEMENT MAY BE USED PER ICC ESR-2251 OR HILTI KWIK-BOLT 7Z (CONCRETE) OR KWIK BOLT 3 (MASONRY) PNEUMATIC (P-NAIL) .131" 3 41" HDU5 5/8 " 10" 5/8 " 10" SSTB16 SSTB24

4.
ON THESE DRAWINGS.

THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT


ELSEWHERE. CEMENT SHALL BE TYPE V WITH POZZOLAN WHERE CONCRETE IS IN
CONTACT WITH SOIL CONTAINING VERY SEVERE SULFATE EXPOSURE.
PER ICC ESR 1917/1385. SUBSTITUTIONS SHALL ONLY BE WITH THE EXPRESS WRITTEN
MASONRY APPROVAL OF THE STRUCTURAL ENGINEER.
12d COMMON
10d
8d
.148"
.148"
.131"
3 41"
3"
2 21"
HDU8
HDQ8
7/8 "
7/8 "
14"
14"
7/8 "
7/8 "
14"
24"
SSTB28
SSTB28
SSTB34
SSTB34 ROC # 318489
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY 10. FLY ASH SHALL COMPLY WITH ASTM C-618, AND SHALL BE APPROVED BY THE 3.2 EPOXY BOLTS OF THE SAME DIAMETER AND SPACING MAY BE USED IN LIEU OF THE NOTE:

EPTA CONSTRUCTION
RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, ENGINEER PRIOR TO BEING USED IN A PROJECT. EMBEDDED 80LTS. A 7" MINIMUM EMBEDMENT SHALL BE PROVIDED FOR EPOXY A. AT 3X SILL PLATE LOCATIONS (SEE PLAN AND SHEARWALL SCHEDULE) SIMPSON
9. ALL PLYWOOD LAYED WITH FACE GRAIN PERPENDICULAR TO SUPPORTS SHALL BE
SEQUENCES AND PROCEDURES. IT SHALL BE THE CONTRACTOR'S GROUTED BOLTS. SSTBL TYPE ANCHORS SHALL BE USED IN LIEU OF THE SPECIFIED SSTB TYPE
C-D OR C-C SHEATHING STRUCTURAL II OR BETTER, EXPOSURE I CONFORMING TO IBC
RESPONSIBILITY TO DESIGN AND PROVIDE ADEQUATE SHORING, BRACING, 10.1.CEMENT CONTENT MAY BE REDUCED A MINIMUM OF 15 PERCENT UP TO A ANCHOR.
STANDARD SECTION 2304 AND SHALL CONFORM TO THE FOLLOWING NOMINAL
FORMWORK, ETC... AS REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY MAXIMUM OF 25 PERCENT WHEN COMPARED TO AN EQUIVALENT CONCRETE 3.3 AS AN OPTION SIMPSON LMA OR MAS ANCHORS MAY BE USED IN LIEU OF THE B. FOOTING DEPTH SHALL BE INCREASED AS REQUIRED TO PROVIDE 3" OF COVER
THICKNESS SPAN RATING AND NAILING PATTERN U.N.O.
MIX DESIGN WITHOUT FLY ASH. FLY ASH CONTENT SHALL NOT COMPRISE MORE EMBEDDED ANCHOR BOLTS. THE ANCHORS SPACING SHALL BE AS FOLLOWS: BELOW ANCHOR.

NEW CONDITIONED STUDIO


DURING CONSTRUCTION. CONSTRUCTION MATERIALS STACKED ON FLOOR OR
ROOF FRAMING SHALL BE UNIFORMLY SPREAD OUT SUCH THAT DESIGN LIVE THAN 35 PERCENT OF THE TOTAL CEMENTOUS CONTENT. THE WATER-CEMENT THICKNESS SPAN RATING EDGE NAILING FIELD NAILING
LOAD PER SQUARE FOOT AS STATED HEREIN IS NOT EXCEECED. VISITS TO THE RATIO SHALL BE CALCULATED BASED ON THE TOTAL CEMENTOUS MATERIAL IN LMA OR MAS LMA OR MAS 5. SPECIAL INSPECTION IS REQUIRED FOR ALL EPOXY INSTALLATIONS PER I.B.C. CHAPTER
SHEARWALL MARK SHEARWALL MARK 3
8" 24 / 0 8d AT 6" O.C. 8d AT 12" O.C.
THE MIX. SPACING SPACING 17.
SITE BY THE STRUCTURAL ENGINEER SHALL NOT BE CONSIDERED AN 1-6 2'-8" 10 1'-2" 7
16" 24 /16 8d AT 6" O.C. 8d AT 12" O.C.
INSPECTION, BUT AS A RESOURCE FOR THE CONTRACTOR. 7 2'-4" 11 1'-3" 15
32" 32 /16 8d AT 6" O.C. 8d AT 12" O.C.
10.2.CLASS "F" FLY ASH SHALL BE USED IN SULFATE RESISTANT CONCRETE 8 1'-6" 12 1'-4" 3
48 / 24
6. EPOXY SHALL BE HILTI HIT HY 150 (ICC ESR#1967) OR SIMPSON SET (ICC ESR #1772) OR
4" 10d AT 6" O.C. 10d AT 12" O.C.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXCAVATION PROCEDURES WITH f'c EQUAL TO OR GREATER THAN 4000 PSI. CLASS "C" FLY ASH MAY BE 9 1'-4" 13 1'-5" 1" 60 / 48 10d AT 6" O.C. 10d AT 12" O.C.
APPROVED EQUAL. EPOXY IS TO BE INSTALLED PER THE MFR. SPECIFICATIONS.
INCLUDING SHORING AND PROTECTION OF ADJACENT PROPERTY, STRUCTURES, USED IN LIEU OF CLASS "F" FLY ASH WHERE CONCRETE NOT IN CONTACT WITH 1 81" 48" O.C. 10d AT 6" O.C. 10d AT 12" O.C.
STREETS AND UTILITIES IN ACCORDANCE WITH THE LOCAL BUILDING CODES, SOIL. 4. WHERE INTERIOR ANCHOR BOLTS HAVE BEEN MISSED, DAMAGED OR MISLOCATED, 7. WHERE TRUSS MFR. REQUIRES ADDITIONAL BEARING AND APPROPRIATELY SIZED
REGULATIONS AND SAFETY REQUIREMENTS. ONE OF THE FOLLOWING RETROFIT OPTIONS MAY BE USED AT THE CONTRACTORS SIMPSON TBE CONNECTION SHALL BE PROVIDED. THE HARDWARE SHALL BE INSTALLED
10. A.P.A. PERFORMANCE RATED SHEATHING (OSB) MAY BE USED AS AN ALTERNATE TO

WITH BATHROOM
10.3.SHOULD THE CONTRACTOR ELECT TO USE EARLY STRENGTH CONCRETE DISCRETION. INTERIOR ANCHOR BOLTS ARE DEFINED AS ANCHOR BOLTS THAT ARE PER MFR. SPECIFICATIONS.
PLYWOOD WITH PRIOR APPROVAL OF OWNER AND ARCHITECT. RATED SHEATHING
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL TO ACHIEVE THE SPECIFIED COMPRESSIVE STRENGTH, f'c, AT LESS THAN LOCATED A MINIMUM OF 6 INCHES FROM SLAB EDGES, STEPS, TURN DOWNS, SHALL COMPLY WITH ICC REPORT NO. NER-108, EXPOSURE I, AND SHALL HAVE A SPAN
DIMENSIONS, CONDITIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS 28-DAY COMPRESSIVE STRENGTH AT THE REQUIRED AGE. THE CONTRACTOR OPENINGS, OR SIMILAR DISCONTINUITIES. 8. WHERE TRUSS MFR. REQUIRES A HARDWARE CONNECTION AT THE TOP PLATE TO
RATING EQUIVALENT TO OR BETTER THAN THE PLYWOOD IT REPLACES. ATTACHMENT
PRIOR TO START OF CONSTRUCTION. THE CONTRACTOR SHALL INFORM THE SHALL SUBMIT TEST DATA FOR REVIEW BY THE STRUCTURAL ENGINEER TO 1 RESIST UPLIFT EXCEEDING 250#, THE FOLLOWING STRAPS SHALL BE USED:
4.1 EXPANSION BOLTS OF EQUAL OR GREATER DIAMETER SHALL BE INSTALLED PER AND THICKNESS (WITHIN 32 ") SHALL BE THE SAME AS THE PLYWOOD IT REPLACES.
ARCHITECT IN WRITING OF ANY DISCREPANCIES OR OMISSIONS NOTED ON THE SUBSTANTIATE THE CONCRETE STRENGTH AT THE REQUIRED AGE.
THE MANUFACTURER. THE BOLTS SHALL BE ONE OF THE FOLLOWING: HILTI KWIK INSTALL PER MFR'S RECOMMENDATIONS. DOUG-FIR-LARCH SPRUCE-PINE-FIR
DRAWINGS. ANY SUCH DISCREPANCY, OMISSION, OR VARIATION NOT REPORTED
BOLTZ TZ (CONCRETE) /3 (MASONRY) - ICC REPORT NO. 1917 / 1385, RAMSET TRUB0LT - SO. PINE HEM FIR
BEFORE START OF CONSTRUCTION SHALL BE THE RESPONSIBILITY OF THE 11. NO MORE THAN 90 MINUTES SHALL ELAPSE BETWEEN CONCRETE BATCHING AND
ICC REPORT NO. 2251. EQUIVALENT EXPANSION BOLTS USED SHALL HAVE EQUAL OR 11. SHEAR PANEL BLOCKING NOTED ON PLANS OR DETAILS SHALL BE CONSTRUCTED LAT. TIES AT TOP LOADS LOADS LOADS LOADS
CONTRACTOR. WHERE DISCREPANCIES OCCUR IN THESE DRAWINGS, NOTES AND CONCRETE PLACEMENT, AND CAN NOT EXCEED A TEMPERATURE OF 90°F P2
UNLESS APPROVED BY THE ENGINEER IN WRITING. GREATER SHEAR AND PULLOUT VALUES AT EQUAL EMBEDMENT TO THOSE SPECIFIED OF 2x SOLID FRAMING WITH 38" MIN. PLYWOOD WITH 8d AT 6" O.C.U.N.O. AND SHALL BE PLATE HORIZ. P1 VERT. P2 HORIZ. P1 VERT. P2 P1
DETAILS ON DRAWINGS TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES H1 165# 490# 140# 400#
ABOVE. THE EXPANSION BOLTS SHALL HAVE MINIMUM EMBEDMENT DEPTHS PER THE NAILED TO ADJACENT TRUSSES WITH MIN. (2)16d TOP AND BOTTOM. H2.5A 110# 600# 110# 520#
AND TYPICAL DETAILS.
12. CONCRETE MIXING, PLACEMENT AND QUALITY SHALL BE PER IBC 1905 AND FOLLOWING: LTS12 --- 720# --- 620#
LATEST EDITION OF ACI. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED. 12. CONVENTIONALLY FRAMED ROOFS: A. PROVIDE 2X SOLID BLOCKING AT BEARING MTS12 --- 840# --- 730# 19.4590

7. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE 2018 HTS16 --- 1005# --- 865#
BOLT DIAMETER MINIMUM EMBEDMENT POINTS BETWEEN RAFTERS/TRUSSES. NAIL W/(3)16d TO TOP PLATES. B. ROOF
INTERNATIONAL BUILDING CODE AND ANY OTHER REGULATORY AGENCIES SLABS ON GRADE NEED BE VIBRATED ONLY AROUND AND UNDER FLOOR DUCTS, HTS20 --- 1450# --- 1245#
EMBEDDED ITEMS OR SIMILAR ELEMENTS. REMOVE ALL DEBRIS FROM FORMS
1
2" 2 41" SHEATHING (UNDER OVER-FRAMING) SHALL EXTEND TO ENDS OF RAFTERS/TRUSSES LGT2 --- 2150# --- 1850#
WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK, AND THOSE CODES
5
2 34" AND BE BOUNDARY NAILED. C. PROVIDE VALLEY PLATES WHERE ROOF SHAPES ARE
AND STANDARDS LISTED IN THESE NOTES AND SPECIFICATIONS. BEFORE PLACING CONCRETE. CONCRETE SHALL NOT BE DROPPED THROUGH 8"
REINFORCING STEEL SO AS TO NOT CAUSE SEGREGATION OF AGGREGATES. 3
3 41"
BUILT-UP OFF OF ROOF DECKING. NOTE: 8d X 1/" NAILS MAY NOT BE USED FOR HI & H2.5A
4"
8. OPENINGS, POCKETS, ETC... LARGER THAN 6 INCHES SHALL NOT BE PLACED IN UNCONFINED FALL OF CONCRETE SHALL NOT EXCEED FIVE FEET.
4.2 EPOXY BOLTS OF THE SAME DIAMETER AND SPACING MAY BE USED IN LIEU OF THE 13. AT TRUSSED FLOOR AND/OR HIGH HEEL ROOF SYSTEMS, PROVIDE FULL HEIGHT DEFERRED SUBMITTALS
SLABS, DECKS, BEAMS, JOISTS, COLUMNS WALLS, ETC., UNLESS SPECIFICALLY
13. ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCING, DOWELS, BOLTS, EMBEDDED BOLTS. A 7" MINIMUM EMBEDMENT SHALL BE PROVIDED FOR EPOXY PANEL BLOCKING PER G.S.N.
DETAILED ON THE STRUCTURAL DRAWINGS. NOTIFY THE STRUCTURAL ENGINEER
WHEN DRAWINGS BY OTHERS SHOW OPENINGS, POCKETS, ETC., NOT SHOWN ON ANCHORS, SLEEVES, ETC. SHALL BE SECURELY POSITIONED IN THE FORMS GROUTED BOLTS. 1. PREFABRICATED COMPONENTS, SPECIALTY ITEMS, OR DESIGN-BUILD ELEMENTS
PRIOR TO PLACEMENT OF THE CONCRETE. 14. TYPICAL NAILING SCHEDULE NOTED ON THE STRUCTURAL DRAWINGS, BUT WHICH REQUIRE THE MFR. OR
THE STRUCTURAL DRAWINGS, BUT WHICH ARE LOCATED ON STRUCTURAL
MEMBERS SPECIFIED ON THE APPROVED STRUCTURAL DRAWINGS. 4.3 SHOT PINS MAY BE USED EITHER RAMSET 3500 SERIES (ICC REPORT NO. 1799) OR SUPPLIER TO PROVIDE THE DESIGN, MAY BE SUBMITTED TO THE ARCHITECT
14. CONCRETE SLAB ON GRADE CONTROL JOINTS SHALL BE PER TABLE BELOW OR HILTI (ICC REPORT NO. 1663) OR ANY OTHER ICC APPROVED POWDER DRIVEN TYPE OF CONNECTIONS TYPE OF CONNECTIONS AND/OR ENGINEER FOR REVIEW AS A DEFERRED SUBMITTAL. DEFERRED
9. ASTM SPECIFICATIONS NOTED ON THESE CONSTRUCTION DOCUMENTS SHALL BE AS NOTED ON THE FOUNDATION PLAN OR STANDARD DETAIL. KEYED OR FASTENER WITH AT LEAST 200 POUNDS ALLOWABLE SHEAR RESISTANCE IN 2000 PSI (3) 16d, TOENAIL
SUBMITTALS REQUIRED BY THE STRUCTURAL ENGINEER OF RECORD SHALL
JOIST OR TRUSS TO TOP PLATE, SILL, ETC.
THE LATEST ACCEPTED VERSION. DOWELED CONTROL JOINTS NEED ONLY OCCUR AT EXPOSED EDGES DURING CONCRETE PER THE SCHEDULE BELOW. INSTALL ALL FASTENERS PER ICBO REPORT INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
BRIDGING TO JOIST (2) 8d, TOENAIL EACH END
PLACEMENT OF THE CONCRETE ALL OTHER JOINTS MAY BE SAW CUT. AND MANUFACTURERS RECOMMENDATIONS. EMBEDMENT SHALL BE 1 41" MINIMUM AND SOLE PLATE TO JOIST OR BLOCKING 16d AT 16" O.C.
10. STANDARD ABBREVIATIONS POST-TENSIONED CONCRETE SLABS ON GRADE SHALL NOT HAVE CONTROL THE SHOT PINS SHALL BE INSTALLED SUCH THAT THE SILL PLATE WOOD DOES NOT - WOOD TRUSSES
TOP PLATE TO STUD (2) 16d, END NAIL
JOINTS UNLESS SPECIFICALLY NOTED ON THE PLANS. SAW CUT JOINTS ARE TO SPLIT. IF SPLITTING OCCURS, EQUIVALENT EXPANSION BOLTS SHALL BE INSTALLED STUD TO SOLE PLATE (2X OR 3X) (2) 16d END NAIL (2X) OR (2)20d END NAIL (3X)
BE MADE IN SLAB PRIOR TO THE DEVELOPMENT OF VISIBLE SHRINKAGE CRACKS, PER THE REQUIREMENTS ABOVE. 2. DEFERRED SUBMITTALS SHALL INCLUDE CALCULATIONS AND DRAWINGS PREPARED
A.C.I. AMERICAN CONCRETE INSTITUTE MFR. MANUFACTURER DOUBLE OR MULTIPLE BUIILT-UP STUDS 16d AT 16" O.C. STAGGERED, EACH PIECE
A.F.F. ABOVE FINISH FLOOR MAX MAXIMUM WITHOUT CAUSING SPALLING OR CHIPPING OF THE CONCRETE SURFACE. AND STAMPED BY AN APPROPRIATELY LICENSED ENGINEER (SPECIALTY ENGINEER)
DOUBLE OR MULTIPLE TOP PLATES 16d AT 16" O.C. STAGGERED, EACH PIECE SHOWING LOCATION AND MAGNITUDE OF LOADS, CONFIGURATION AND SIZE OF
A.I.S.C. AMERICAN INSTITUTE OF STEEL CONSTRUCTION MIN MINIMUM REQUIRED ANCHOR BOLT SHOT PIN
MAXIMUM JOINT SPACING BLKING BETWEEN JOIST OR RAFTERS TO TOP
A.I.S.I. AMERICAN IRON AND STEEL INSTITUTE MISC. MISCELLANEOUS SLAB THICKNESS SPACING PLATE
(3) 16d, TOENAIL MEMBERS, AND COMPATIBILITY OF SUBMITTAL ITEM WITH THE PRIMARY
(EACH DIRECTION) 0.170 DIA. 0.140 DIA.
A.N.S.I. AMERICAN NATIONAL STANDARDS INSTITUTE N.T.S. NOT TO SCALE 1 RIM JOIST TO TOP PLATE 16d AT 8" O.C., TOENAIL STRUCTURAL SYSTEM.
4" 10' 2" DIAMETER AT 72" O.C. 13"
ARCH'L ARCHITECTURAL PLANS AND SPECIFICATION O.C. ON CENTER 5" TOP PLATE, LAPS AND INTERSECTIONS (2) 16d
12.5' 1
2" DIAMETER AT 60" O.C. 11" 0'-10"
ALT ALTERNATE OPP OPPOSITE 6" CONTINOUS HEADER, TWO OR MORE 3. IF A TRUSS WAIVER IS SUBMITTED AT THE TIME OF PLAN REVIEW THE ENGINEER
15' 1 16d AT 16" O.C. ALONG EACH EDGE, EACH PIECE
A.S.T.M. AMERICAN SOCIETY FOR TESTING AND MATERIALS plf POUNDS PER LINEAR FOOT 2" DIAMETER AT 48" O.C. 9" 0'-8" LAMINATIONS REVIEWED AND APPROVED TRUSS DESIGNS SHALL BE ATTACHED TO THE FIELD SET
CEILING JOIST TO PLATE (3) 16d, TOENAIL
B.F.F. BELOW FINISH FLOOR psf POUNDS PER SQUARE FOOT 15. PROTECT CONCRETE FROM DAMAGE OR REDUCED STRENGTH DUE TO COLD OR
1
2" DIAMETER AT 40" O.C. 7" 0'-6" OF CITY APPROVED PLANS BEFORE ANY ROOF, SHEATHING, OR FRAMING
CONTINUOUS HEADER TO STUD (3) 16d, TOENAIL
B.O.B. BOTTOM OF BEAM psi POUNDS PER SQUARE INCH HOT WEATHER IN ACCORDANCE WITH ACI 305 AND 306. CONTRACTOR SHALL 1
2" DIAMETER AT 36" O.C. 6" --- INSPECTION.
B.O.D. BOTTOM OF DECK SIM SIMILAR CEILING JOIST, LAP OVER PARTITIONS (3) 16d
TAKE SPECIAL CURING PRECAUTIONS TO MINIMIZE SHRINKAGE CRACKING OF 5
8" DIAMETER AT 72" O.C. 8 21" 0'-6"
C.J. CONTROL JOINT SPEC. SPECIFICATION CEILING JOIST TO PARALLEL RAFTERS (3) 16d 4. THE PURPOSE OF THE STRUCTURAL ENGINEER'S REVIEW SHALL BE LIMITED TO
CONCRETE SLABS. 5
CONT. CONTINUOUS STD STANDARD 8" DIAMETER AT 60" O.C. 7" --- RAFTER ON TRUSS TO PLATE (3) 16d, TOENAIL
16. CONSTRUCTION JOINTS OR POUR JOINTS IN STRUCTURAL ELEMENTS (BEAMS, 5
DETERMINING THAT THE DRAWINGS AND CALCULATIONS HAVE BEEN PROPERLY
DIA DIAMETER T&G TONGUE AND GROOVE 8" DIAMETER AT 48" O.C. 5 21" --- BUILT-UP CORNER STUDSS 16d AT 16" O.C. STAGGERED, EACH PIECE SEALED, THAT THE LOAD CRITERIA IS IN GENERAL CONFORMANCE WITH THE
COLUMNS, ELEVATED SLABS, ETC.) NOT SPECIFICALLY SHOWN OR NOTED ON 3
E.F. EACH FACE T.O. TOP OF 4" DIAMETER AT 72" O.C. 6" --- BUILT-UP CHANNEL BLOCKING AT WALL CONTRACT DOCUMENTS AND WITH THE INTENTIONAL BUILDING CODE, THAT
THE DRAWINGS REQUIRE PRIOR APPROVAL OF THE ENGINEER. CONTRACTOR 16d AT 3" O.C., EACH PIECE
EQ. EQUAL T.O.B. TOP OF BEAM INTERSECTING SHEARWALL
SHALL SUBMIT SHOP DRAWINGS SHOWING PROPOSED JOINTS TO ENGINEER FOR KING STUD TO BEAM (END) (2) 16d AT 3" O.C. (4 MIN) CONNECTIONS TO THE PRIMARY STRUCTURE ARE COMPATIBLE WITH THE PRIMARY
E.W. EACH WAY T.O.D. TOP OF DECK
APPROVAL. 5. INTERIOR NON-SHEAR LOADED PARTITION WALLS MAY BE ANCHORED TO THE SLAB DESIGN, AND THAT THE PRIMARY STRUCTURE IS CAPABLE OF SUPPORTING THE
F.F. FINISH FLOOR T.O.F. TOP OF FOOTING
17. PIPES, SLEEVES, CONDUITS, ETC. OF ANY MATERIAL SHALL NOT BE EMBEDDED IN WITH A MINIMUM 0.140 INCH DIAMETER SHOT PINS AT 32" O.C. MAXIMUM SPACING. IMPOSED LOADS.
ft FOOT T.O.J. TOP OF JOIST
GA GAUGE T.O.L. TOP OF LEDGER STRUCTURAL CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED BY THE
NOTES: 5. THE STRUCTURAL ENGINEER WILL RELY UPON THE SPECIALTY ENGINEER'S SEAL AS
GLB
G.S.N.
HSS
GLULAM BEAM
GENERAL STRUCTURAL NOTES
HOLLOW STRUCTURAL SECTION
T.O.M.
T.O.S.
T.O.W.
TOP OF MASONRY
TOP OF STEEL
TOP OF WALL
ENGINEER. EMBEDDED ITEMS SHALL NOT IMPAIR THE STRENGTH OF THE
MEMBER.
6. WOOD PLATES OR SILLS SHALL BE BOLTED TO THE FOUNDATION OR FOUNDATION
WALL. STEEL BOLTS SHALL HAVE A MINIMUM NOMINAL DIAMETER OF 21" UNLESS NOTED
OTHERWISE. BOLTS SHALL BE EMBEDDED AT LEAST 7 INCHES INTO THE CONCRETE OR
A.
B.
MINIMUM NAILING PER THIS SCHEDULE U.N.O. ON PLANS OR DETAILS
ALL NAILING IS FACE NAILING U.N.O. ON PLANS OR DETAILS.
CERTIFICATION THAT THE DEFERRED SUBMITTAL ITEMS DESIGNED BY THE
SPECIALTY ENGINEER COMPLY WITH THE CRITERIA SET FORTH IN THE CONTRACT
PROJECT NO.
I.B.C.
k
K.O.
INTERNATIONAL BUILDING CODE
KIP (1,000 LBS)
KNOCKOUT
T.W.I.
TYP
U.B.C.
TOP OF WROUGHT IRON
TYPICAL
UNIFORM BUILDING CODE
REINFORCING STEEL

1. REINFORCING STEEL SHALL CONFORM TO REQUIREMENTS OF ASTM A615 AND


MASONRY AND SHALL BE SPACED NOT MORE THAN 48 INCHES APART. THERE SHALL
BE A MINIMUM OF TWO BOLTS PER PIECE WITH ONE BOLT LOCATED NOT MORE THAN
12 INCHES OR LESS THAN SEVEN BOLT DIAMETERS FROM EACH END OF THE PIECE. A
C.
D.
SEE FRAMING PLAN NOTES FOR TOP PLATE SPLICE CONNECTION.
SEE IBC TABLE 2304.10.1 FOR CONDITIONS NOT LISTED.
DOCUMENTS AND APPLICABLE CODES AND STANDARDS. THE STRUCTURAL
ENGINEER SHALL NOT BE RESPONSIBLE FOR THE ADEQUACY OF DESIGNS
PROVIDED BY OTHERS.
012423
ksi KIPS PER SQUARE INCH U.N.O. UNLESS NOTED OTHERWISE CRSI SPECIFICATIONS AND HANDBOOK. REINFORCING SHALL BE GRADE 60 (Fy = PROPERLY SIZED NUT AND WASHER SHALL BE TIGHTENED ON EACH BOLT TO THE
L.L.H. LONG LEG HORIZONTAL VERT VERTICAL 60 KSI) DEFORMED BARS FOR ALL BARS #5 AND LARGER AND ALL BARS USED FOR WOOD TRUSSES 6. ALLOW SEVEN (7) WORKING DAYS FOR THE ENGINEER'S REVIEW. ONE COPY OF
3
PLATE. FOR SEISMIC DESIGN CATEGORIES D-F, WASHERS SHALL BE A MINIMUM OF 16 "
L.L.V. LONG LEG VERTICAL CONCRETE WALLS, BEAMS ELEVATED SLABS AND COLUMN PRIMARY EACH SUBMITTAL WILL BE RETAINED FOR THE ENGINEER'S RECORDS.

BASIS FOR DESIGN


REINFORCING. REINFORCING MAY BE GRADE 40 (Fy = 40 KSI) DEFORMED BARS
FOR ALL BARS #4 AND SMALLER U.N.O. ON PLANS OR DETAILS. ALL REINFORCING
TO BE WELDED SHALL BE ASTM A706, GRADE 60 LOW ALLOY WELDABLE STEEL.
THICK BY 2" SQUARE PLATE WASHERS (REFER TO "BASIS FOR DESIGN/SEISMIC
DESIGN" THIS SHEET FOR SEISMIC DESIGN CATEGORY) AT EXTERIOR WALLS,
SHEARWALLS, AND INTERIOR BEARING WALLS WHERE 2x SILL PLATES ARE SPECIFIED.
1. ALL PREFAB ROOF TRUSSES TO BE BY CITY APPROVED MANUFACTURER. IT IS
THE RESPONSIBILITY OF THE SUB-CONTRACTOR SUPPLYING ROOF TRUSSES TO
PROVIDE ADEQUATE SPECIFICATIONS AND/OR OTHER INFORMATION TO SATISFY
SPECIAL INSPECTION NOTES ISSUE: DATE:
FOUNDATION PLATES AND SILLS SHALL BE THE KIND OF WOOD SPECIFIED IN APPROVING AUTHORITIES. (UNLESS WAIVER IS USED).
1. 2018 INTERNATIONAL BUILDING CODES (IBC) / 2018 INTERNATIONAL RESIDENTIAL NONE
SECTION2304.11.4 OF THE 2018 IBC.
CODE (IRC) & GOVERNING MUNICIPALITY AMMENDMENTS 2. WELDED WIRE FABRIC SHALL CONFORM TO THE REQUIREMENTS OF ASTM A185.
LAPS IN WELDED WIRE FABRIC SHALL BE MADE SUCH THAT THE OVERLAP, 2. PREFABRICATED WOOD TRUSSES SHALL BE DESIGNED TO SUPPORT THEIR SELF
7. ANCHORAGE INTO CONCRETE MASONRY UNITS OR BRICK SHALL BE INTO SOLID WEIGHT, PLUS LIVE LOAD AND SUPERIMPOSED DEAD LOADS INCLUDING, BUT NOT
2. ROOF LOADS MEASURED BETWEEN OUTERMOST CROSS-WIRE OF EACH FABRIC SHEET, IS NOT END OF GENERAL STRUCTURAL NOTES
GROUTED CELLS ONLY. LIMITED TO, ALL MECHANICAL AND OTHER EQUIPMENT, AND SHALL BE DESIGNED
PITCHED ROOF LESS THAN THE SPACING OF CROSS WIRES PLUS 2 INCHES.
TO RESIST ALL DRAG FORCES, SHEARWALL UPLIFT AND DOWNWARD LOADS, AND
DEAD LOAD = 24 PSF WOOD OTHER SPECIAL LOADS NOTED ON THE DRAWINGS OR CALCULATIONS.
LIVE LOAD = 20 PSF (REDUCIBLE) 3. ALL DIMENSIONS SHOWING THE LOCATION OF REINFORCING STEEL NOT NOTED
FLAT ROOF AS "CLEAR" OR "CLR" ARE TO CENTER OF STEEL. MINIMUM, COVER FOR
1. STRUCTURAL SAWN LUMBER DESIGN VALUES SHALL COMPLY WITH THE LATEST 3. TRUSS MFR. SHALL DESIGN FOR SPAN/240 TOTAL LOAD DEFLECTION AND
DEAD LOAD = 18 PSF NON-PRESTRESSED CONCRETE REINFORCING SHALL BE AS FOLLOWS: (U.N.O. ON
EDITION OF THE GRADING RULES OF THE WESTERN WOOD PRODUCTS ASSOCIATION SPAN/360 LIVE LOAD DEFLECTION.
LIVE LOAD = 20 PSF (REDUCIBLE) THESE PLANS OR PLAN DETAILS).
(WWPA) OR THE WEST COAST LUMBER INSPECTION BUREAU (WCLIB). ALL SAWN
MINIMUM
EXPOSURE TOLERANCES LUMBER SHALL BE STAMPED WITH THE GRADE MATCH OF AN APPROVED LUMBER 4. BRIDGING SIZE AND SPACING SHALL BE AS DESIGNED BY TRUSS MFR. U.N.O.
COVER
3. WIND DESIGN 3 GRADING AGENCY. STRUCTURAL SAWN LUMBER COMPONENTS SHALL HAVE THE
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3" 8"
BASIC WIND SPEED (3-SECOND GUST) = 115 (VULT) FOLLOWING MIN. GRADE U.N.O. 5. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, ERECTION DRAWINGS, AND
EXPOSED TO EARTH OR WEATHER
IMPORTANCE FACTOR = 1.0 DESIGN CALCULATIONS SEALED BY AN APPROPRIATELY REGISTERED ENGINEER.
1 3
WIND EXPOSURE =C #5 AND SMALLER 1 2" 8" USE MATERIAL
3
SHOP DRAWINGS SHALL SHOW ANY SPECIAL DETAILS REQUIRED AT BEARING
#6 AND LARGER 2" 8" 2X4 TOP PLATES DOUGLAS FIR NO. 2 POINTS. ALL CONNECTORS SHALL HAVE CURRENT I.C.B.O. APPROVAL.
4. SEISMIC DESIGN NOT EXPOSED TO EARTH OR WEATHER 2X6 STUDS (UP TO 10'-0") BLOCKING,
DOUGLAS FIR NO. 2
NOT REQUIRED PER IBC 1614.1, EXCEPTION 2. ROOF SLABS 1" 1 TOP PLATES
8" 6. TRUSSES MAY BE OVERSPANNED TO ACCOMMODATE 30"x30" ATTIC ACCESS
3 1
2X6 STUDS (OVER 10'-0") DOUGLAS FIR NO. 2
STRUCTURAL SLABS AND WALLS 4" 8" PROVIDED ROOF SHEATHING PANEL EDGES ARE BLOCKED AND EDGE NAILED AT
BEAMS AND COLUMNS (PRIMARY REINFORCEMENT, JOISTS AND OTHER SAWN LUMBER DOUGLAS FIR NO. 2
FOUNDATION 1 21" 3
8"
OVERSPAN.
TIES, STIRRUPS, AND SPIRALS)
6X AND LARGER BEAMS AND POSTS DOUGLAS FIR NO. 2
SLABS ON GRADE 1 21" 1
4"
1. FOUNDATIONS WERE DESIGNED PER THE 2018 INTERNATIONAL BUILDING CODE CONNECTION HARDWARE
MINIMUM REQUIREMENTS. IT IS RECOMMENDED BUT NOT REQUIRED THAT A 2. GLUE-LAMINATED BEAMS (GLULAM) SHALL BE DOUGLAS FIR COMBINATION 24F-V4 FOR
4. LAP SPLICES OF REINFORCING STEEL IN CONCRETE BEAMS, SLABS AND
SOILS REPORT BE ACQUIRED PRIOR TO US COMPLETING THE STRUCTURAL ALL SIMPLY SUPPORTED SPANS AND SHALL BE 24F-V8 FOR ALL MULTIPLE SPAN OR 1. UNLESS NOTED OTHERWISE, ALL HANGERS, CLIPS, STRAPS, HOLDOWNS, MISC.
FOOTINGS SHALL BE ACCORDING TO ACI 318 CHAPTER 12 OR LAP SCHEDULE
DESIGN FOR THIS PROJECT. IN THE EVENT THAT A GEOTECHNICAL REPORT IS CANTILEVERED U.N.O. ON THE PLANS. THE GLB BEAMS SHALL HAVE THE FOLLOWING STRUCTURAL CONNECTORS, ETC. SHOWN ON PLANS OR DETAILS SHALL BE
WHERE PRESENT OR 48 BAR DIAMETERS, U.N.O. STAGGER SPLICES A MINIMUM
NOT PROVIDED BY A REPUTABLE BY A GEOTECHNICAL ENGINEER QUANTUM MINIMUM PROPERTIES: E=1,800,000psi, Fb=2,400psi, Fv=240psi, Fc(PARALLEL)=1650psi, SIMPSON STRONG-TIE OR EQUAL. ALL HARDWARE SHALL BE INSTALLED WITH
OF ONE LAP LENGTH. NO TACK WELDING OF REINFORCING BARS ALLOWED.
CONSULTING ENGINEERS WILL NOT ASSUME THE LIABILITY FOR THE Fc(PERPENDICULAR)=650psi. FABRICATION AND HANDLING SHALL CONFORM WITH THE FASTENERS PER MFR'S SPECIFICATIONS.
LATEST ACI CODE AND DETAILING MANUAL APPLY. PROVIDE BENT CORNER BARS
ENGINEERING EXPERTISE NORMALLY PROVIDED BY THE GEOTECHNICAL LATEST AITC AND AST STANDARDS. BEAMS SHALL BEAR AN APPROPRIATE GRADE
TO MATCH AND LAP WITH HORIZONTAL BARS AT ALL CORNERS AND
ENGINEER. INTERSECTIONS PER TYPICAL DETAILS. VERTICAL WALL BARS SHALL BE SPLICED
STAMP CLEARLY NOTING ITS DESIGN PROPERTIES. BEAMS SHALL BE MFR'D WITH
INDUSTRY STANDARD MINIMUM CAMBER UNLESS CAMBER IS SPECIFICALLY NOTED ON
2. MANUFACTURED HARDWARE SHALL BE AS NOTED ON THE DRAWINGS. GENERAL
2. ALL FOOTING SHALL EXTEND 18 INCHES MINIMUM BELOW GRADE (UNDISTURBED AT OR NEAR FLOOR LINES. SPLICE TOP BARS AT CENTER LINE OF SPAN AND ADDITIONAL ALTERNATIVES NOT LISTED BELOW MAY BE USED PROVIDED THEY
SOIL). GRADE IS DEFINED AS TOP OF SLAB FOR INTERIOR FOOTINGS, LOWEST
ADJACENT COMPACTED SUBGRADE (BUILDING PAD PRIOR TO PLACEMENT OF
BOTTOM BARS AT THE SUPPORT IN SPANDRELS, BEAMS, GRADE BEAMS, ETC.
3.
THE DRAWINGS.
ALL SILL PLATES RESTING ON CONCRETE OR MASONRY SHALL BE PRESSURE TREATED
HAVE EQUIVALENT CAPACITY FOR THE INTENDED APPLICATION AND A CURRENT
ICBO APPROVAL. ONE MANUFACTURER SHALL BE USED EXCLUSIVELY FOR EACH
STRUCTURAL
U.N.O. ON THE PLANS.
LANDSCAPE) OR NATURAL GRADE WITHIN 10 FEET OF BUILDING PERIMETER
FOOTINGS. WHERE PERMANENT CONCRETE OR PAVING EXTENDS AT LEAST 10 FT
5. ALL REINFORCING SHALL BE BENT COLD, ONE TIME ONLY. FIELD BENDING OF
REBAR SHALL NOT BE ALLOWED UNLESS SPECIFICALLY NOTED ON THE PLANS.
4.
DOUGLAS FIR.
ALL BEAMS SHALL BE CONSIDERED FLUSH BOTTOM U.N.O. ON THE PLANS. GIRDER
PROJECT. THE CONNECTOR FABRICATORS LISTED BELOW MAY BE USED AT THE
CONTRACTORS DISCRETION: CITY OF PHOENIX NOTES
FROM THE BUILDING AND IS LOCATED DIRECTLY ADJACENT TO THE BUILDING. 6. WELDING OF REINFORCING BARS, METAL INSERTS, AND CONNECTIONS SHALL
TRUSSES AND BEAMS SHALL HAVE FULL BEARING (2) 2X STUDS MINIMUM. NAIL STUDS Planning and Development Department
THE TOP OF FINISHED SURFACE MAY BE CONSIDERED GRADE. FOOTING TOGETHER PER TYPICAL NAILING SCHEDULE. BEAMS OR TWO PLY (OR LARGER)
CONFORM WITH AWS D1.4, AND SHALL BE MADE ONLY AT LOCATIONS SHOWN ON
GIRDER TRUSSES BEARING ON TOP PLATES SHALL BE ATTACHED TO TOP PLATES
A) SIMPSON STRONG-TIE COMPANY INC., BREA CALIFORNIA, SEE CURRENT
BY: Gary D. Swinford
EXCAVATIONS SHALL BE CLEAN AND FREE FROM LOOSE DEBRIS, STANDING PLANS OR DETAILS. CATALOGS FOR ALL CURRENT ICC REPORTS
WATER, OR UNCOMPACTED MATERIAL AT THE TIME OF CONCRETE PLACEMENT. WITH A34 ONE SIDE AND (2)16d TOENAILS ON THE OTHER SIDE. B) USP LUMBER CONNECTORS, 2150 KITTY HAWK ROAD, LIVERMORE, CALIFORNIA
7. REINFORCING BAR SPACING SHOWN ON PLANS REPRESENT THE MAXIMUM ON
3. ALLOWABLE DEAD PLUS LIVE LOAD SOIL PRESSURE = 1500 PSF. CENTER SPACING. ALL BARS SHALL BE DETAILED AND PLACED PER CRSI
5. AT EXTERIOR WALLS AND INTERIOR BEARING WALLS AND SHEARWALLS, ANY WOOD 94550, SEE CURRENT CATALOGS FOR ALL CURRENT ICC REPORTS. 01/16/2024

S1.0
4. TRENCHES AND EXCAVATIONSUNDER OR ADJACENT TO FOUNDATIONS SHALL BE STUD MAY BE CUT OR NOTCHED TO A DEPTH NOT EXCEEDING 25% OF ITS WIDTH.
SPECIFICATIONS AND HANDBOOK. DOWEL ALL VERTICAL REINFORCING TO
PROPERLY BACKFILLED AND COMPACTED. CUTTING OR NOTCHING OF THE STUDS TO A DEPTH NOT GREATER THAN 40% OF THE 3. HOLDOWNS SHALL BE INSTALLED WHERE SPECIFIED ON THE FOUNDATION AND
FOUNDATION, AS SPECIFIED ON PLANS OR DETAILS. MINIMUM CLEAR SPACING This set of plans has been reviewed for PHOENIX
WIDTH OF THE STUD IS PERMITTED IN NONBEARING PARTITIONS SUPPORTING NO THE ROOF FRAMING PLANS. THE FOLLOWING EQUIVALENT HOLDOWN
BETWEEN PARALLEL REINFORCEMENT SHALL BE THE LARGER OF 1 21 TIMES LOADS OTHER THAN THE WEIGHT OF THE PARTITION. (2308.9.10 IBC 2006) REINFORCE CONSTRUCTION CODE requirements prior to
CONCRETE SUBSTITUTIONS MAY BE USED AT THE CONTRACTORS DISCRETION: (HD TYPE
1. 28-DAY CONCRETE COMPRESSIVE STRENGTH, f'c, SHALL BE 2500 PSI FOR ALL NOMINAL BAR DIAMETER, 1 31 TIMES MAXIMUM AGGREGATE SIZE. STUD PER STANDARD DETAIL. HOLDOWNS MAY BE 8E REPLACED WITH EQUIVALENT PHD HOLDOWNS)
issuance of Building Permit and shall be kept at the
CONCRETE IN CONTACT WITH SOIL. construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
the plans where such errors are subsequently found
to be in violation of any law or ordinance.
KEY NOTES
1. FINISH FLOOR TO BE 6" MIN. ABOVE FIN. GRADE
2. FINISH GRADE SHALL SLOPE 5% FOR A DISTANCE OF

7725 W ODEUM LN, PHOENIX, AZ 85043


10' TO APPROVED WATER DISPOSAL AREA
3. LANDINGS AT DOOR AREAS SHALL HAVE A 1/4"/FT.
PREFAB TRUSSES -
SEE TRUSSES PLAN 4.
MAX. SLOPE
THERE SHALL BE A LANDING @ EACH DOOR WITH A ROC # 318489
WIDTH NOT LESS THAN THE WIDTH OF THE DOOR

12'-0" AND LENGTH OF 36" MIN

EPTA CONSTRUCTION
5. SPECIFY FLOOR LEVELS @ DOORS. THE LANDING
SHALL BE NOT MORE THAN 1" LOWER THAN THE
THRESHOLD OF THE DOOR. EXEMPTION 1.1
ALLOWS THE LANDING TO BE MAX. 8" LOWER
THAN THE DOOR THRESHOLD WHEN THE DOOR

NEW CONDITIONED STUDIO


DOES NOT SWING OVER THE LANDING
6. CONTROL JOINTS TO BE PROVIDED AND LOCATIONS
DETERMINED BY THE CONCRETE SUBCONTRACTOR
AT THE SITE
7. ALL SOLE PLATES TO BE PRESSURE TREATED. ALL
FIELD CUT ENDS, NOTCHES, AND DRILLED HOLES
ARE TO BE RETREATED IN THE FIELD IN
ACCORDANCE WITH AWPA M4.
2X4S @ 16" O.C.

WITH BATHROOM
FINISH STUCCO FOAM INSULATION

PLAN AREA CALCULATIONS

9'-0" HEIGHT
ALL EXTERIOR WALLS TO SHEATHED
DESCRIPTION AREA SQFT
W/3/8" OSB, , ALL EDGES BLOCKED LIVEABLE CONDITIONED SPACE 2,375
COVERED ENTRY -
ANCHORAGE BY #4
GARAGE -
VERTICAL REBARS @24" O.C. COVERED PATIO -
MASA MUDSIL ANCHOR
A CHEMICAL TERMITICIDE IS TO @ 32" O.C. MESH CONCRETE SHEET NEW CONDITIONED STUDIO
BE APPLIED BY A LICENSED 6" x 6" GRID 10/10 WITH BATHROOM 276
23'-0"

PROFESSIONAL BEFORE WEEP SCREED


FOUNDATION IS POURED. FINISHED 2'-0' 4" CONCRETE NEW COVERED PATIO EXTENSION 174
FLOOR OVER 4" ABC
TOTAL AREA UNDER ROOF 2,825

12"
4#4 REBARS
CONTINUE LOT
12"

GENERAL WALL SECTION DESCRIPTION AREA SQFT


TOTAL AREA UNDER ROOF 2819.5
LOT SQUARE FOOTAGE 8,169
LOT COVERAGE 34.52%

PROJECT NO.
WATER BARRIER - TWO LAYERS
OF GRADE "D" BLDG PAPER OR
FINISHED GRADE SHALL SLOPE AWAY
FROM FOUNDATION A MINUMUM OF 6"
012423
APPROVED EQUIVALENT WITHIN THE FIRST 10 FEET PER THE INTIL
RESIDENTIAL CODE **R401.3
STUCCO FINISH
WEEP SCREED PER IBC 2512.1.2 CONCRETE SLAB - SEE
ISSUE: DATE:
FOUNDATION PLAN FOUNDATION PLAN

ALL UNDERSLAB AREAS & FOUNDATION


SCALE 3/8":1' FINISH GRADE per R401.3 SHALL BE CHEMICALLY TREATED FOR

6" MIN
TERMINATES BY AN ARIZONA LICENSED
APPLICATOR. **R318.1. & PCBO.

FOOTING - SEE
FOUNDATION PLAN
2018 IRC R703.7.2.1 WEEP SCREED IN IRC.
WEEP SCREED DETAIL 2018 IRC R106.1.1 NOTE STRUCTURE IS
CONDITIONED STRUCTURE SLAB.

SPRAY FOAM INSULATION PER ESR-3225.

CITY OF PHOENIX
Planning and Development Department
BY: Gary D. Swinford FOUNDATION
01/16/2024 PLAN
This set of plans has been reviewed for PHOENIX
CONSTRUCTION CODE requirements prior to
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the

S1.1
Building Official from requiring correction of errors in
the plans where such errors are subsequently found
to be in violation of any law or ordinance.

NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
PROJECT INFORMATION
OWNER INFORMATION

NAME: ANDERSON CHRISTOPHER JON/CRUZ LUS MARIA


ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043

PROPERTY INFORMATION
ADRESS: 7725 W ODEUM LN, PHOENIX AZ 85043

ASESOR PARCEL NUMBER No: 104-52-698

7725 W ODEUM LN, PHOENIX, AZ 85043


LOT NUMER: N/A ROC # 318489

EPTA CONSTRUCTION
DOOR SCHEDULE
1 1 SHEAR WALL SCHEDULE
SYMBOL ROOM QUANTITY UNIT ID^ HEAD
HEIGHT
TYPE
A NEW STORGE 1 3-0 / 8-0 8'-2 12 " IN SWING

NEW CONDITIONED STUDIO


WALL WALL WALL NAILING
SCHED BRACING MATERIAL BLOCKED B 1 2-4 / 6-8 6'-10 12 " OUT SWING
BATHROOM
METHOD NAIL EDGE FIELD C 1 2-6/ 6-8 6'-10 12 " SLIDING
1 WSP 3
8" OSB 8d 6" 12" YES MAXIMUM U-FACTOR SHALL BE 0.40
MAXIMUM SHGC SHALL BE 0.25

1 WINDOW SCHEDULE
SILL HEAD

WITH BATHROOM
SYMBOL ROOM QUANTITY UNIT ID^ TYPE OPERATION COLOR
1 1 NEW STORGE 1 5-0 / 5-0
HEIGHT
1'-10 12 "
HEIGHT
6'-10 12 " SLIDING XO -
MAXIMUM U-FACTOR SHALL BE 0.40
MAXIMUM SHGC SHALL BE 0.25

EVERY FOURTH BLOCK SPACE


SHEATHING - SEE PLAN TO BE OPEN FOR VENTILATION
2x BLOCK'G & NAILING PLAN AREA CALCULATIONS
PREFAB WOOD TRUSSESS
/ JOISTS - SEE PLAN
8d COMMON at 6" CTS. DESCRIPTION AREA SQFT
LIVEABLE CONDITIONED SPACE 2,375
DOUBLE STUDS AT SHEARWALL ENDS "SIMP" CONNECTOR,
COVERED ENTRY -
A/C

(BOTH STUDS TO BE NAILED, SEE SEE PLAN


SCHEDULE) & SPIKE STUDS TOGETHER GARAGE -
WITH 10d COMMON AT 6" CTS. 8d COMMON at 6" CTS.
ALONG PANEL EDGES COVERED PATIO -
8d COMMON NEW CONDITIONED STUDIO
at 12" CTS. WITH BATHROOM 276
SHEARWALL SHEATHING,
SEE PLAN FOR LOCATION CRIPPLE WALL
NEW COVERED PATIO EXTENSION 174
HEADER, SEE PLAN
TOTAL AREA UNDER ROOF 2,825
1 1
BLOCKING FOR PANEL EDGES
(ALL EDGES ARE REQ'D TO BE
SUPPORTED BY BLOCKING OR
STUDS) LOT
7/16" PLYWOOD OR TYP. OPENING
OSB BOARD DESCRIPTION AREA SQFT
8d COMMON FIELD TOTAL AREA UNDER ROOF 2819.5
NAILING at 12" CTS.
LOT SQUARE FOOTAGE 8,169
1 1 MASA MUDSIL G90 & SPACING, SEE
SHEARWALL SCHEDULE (OUTSIDE OF LOT COVERAGE 34.52% PROJECT NO.
SHEARWALL at 36" CTS.) 012423
CONCRETE WALL
ISSUE: DATE:
SHEAR WALL P L A N CONCRETE FOOTING, SEE PLAN
SCALE 3/8":1'

S1 TYPICAL BRACED WALL PANEL ELEVATION

CITY OF PHOENIX
Planning and Development Department
BY: Gary D. Swinford
SHEAR WALL
01/16/2024
PLAN
This set of plans has been reviewed for PHOENIX
CONSTRUCTION CODE requirements prior to
issuance of Building Permit and shall be kept at the

S2.0
construction site. Such review shall not prevent the
Building Official from requiring correction of errors in
the plans where such errors are subsequently found
to be in violation of any law or ordinance.

NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
IRC 2018 TABLE P3004.1 UNIT FIXTURE SHEDULE

WH
DRAINAGE FIXTURE UNIT (d.f.u.) VALUES EXISTING
TYPE OF FIXTURE (d.f.u.) VALUE
MASTER BATHROOM
WHATER HEATERS REQUIREMENTS: TYPE OF FIXTURE NUMBER of WATER FIXTURE TOTAL FIXTURE
FIXTURES UNIT VALUE UNITS
BATHTUB 2
DRIP PAN SIZE -1-1/2"DEEP & Full Bath Group 1 3.6 3.6
LAVATORY 1
LAVATORY
SUFFICIENT SIZE TO FIT W/H WITH Shower 1 1.4 1.4
1
WATER CLOSET (1.6 gal.) 3
3/4" DRAIN ROUTED TO THE
Lavatory 1 0.7 0.7
TOTAL
EXTERIOR P2801.6.1; W/H IN THE
7
KITCHEN
GARAGE TO BE A MIN. 18" ABOVE Totals 3 5.7 5.7
FLOOR, P2801.7; Notes: Pressure regulator to be installed if pressure exceeds 80psi
DISHWASHER 2

7725 W ODEUM LN, PHOENIX, AZ 85043


PRESSURE/TEMPERATURE RELIEF
KITCHEN SINK 2
VALVE SHALL COMPLY WITH P2804
Total developed length of the water line from the water meter to the furtherest water using outlet = 175 feet
ROC # 318489
TOTAL 4 Meter size (3/4") and Water Supply Size (3/4")
& THE DISCARGE PIPE TO COMPLY

A/C

EPTA CONSTRUCTION
BATHROOM #2
WITH P2804.6. Water Meter and Service shall be sized in accordance with UPC Table #6-4 and water pressure available at point of
LAVATORY 1 connection at job site.

NEW CONDITIONED STUDIO


SHOWER STALL 2
3
Tankless water heater is shown on
WATER CLOSET (1.6 gal.)
6
exterior of structure. Pan not required.
TOTAL
BATHROOM #3
T&P built in. Will need a recirculation KEY NOTES - PLUMBING
system. Field verify

WITH BATHROOM
BATHTUB 2
1. THE POTABLE WATER SUPPLY TO LOAN IRRIGATION SYSTEMS SHALL BE PROTECTED AGAINST BACKFLOW BY AN
LAVATORY 1
LAVATORY 1 ATMOSPHERIC-TYPE VACUUM BREAKER, A PRESSURE-TYPE VACUUM BREAKER OR A REDUCED PRESSURE PRINCIPLE
WATER CLOSET (1.6 gal.) 3 BACKFLOW PREVENTER. A VALVE SHALL NOT BE INSTALLED DOWNSTREAM FROM AN ATMOSPHERIC VACUUM BREAKER.
TOTAL 7
WHERE CHEMICALS ARE INTRODUCED INTO THE SYSTEM, THE POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST
LAUNDRY
CLOTHES WASHER 2 BACKFLOW BY A REDUCED PRESSURE BACKFLOW PREVENTER per IRC SECTION P29002.5.3

2. THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE POSIBILITY OF WATER
TOTAL 2 PLUMBING WASTE AND HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE WUICK CLOSING VALVES ARE USED. WATER-HAMMER
GRAND TOTAL (d.f.u.) VALUES 26 DIRECTION OF FLOW TO
VENTILE PLAN EXISTING SEWER ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. WATER-HAMMER ARRESTERS

SHALL CONFORM TO ASSE 1010. IRC SECTION P2903.5

IRC 2018 TABLE P3004.1 3. SEE PLUMBING FLOOR PLAN SHOWING ALL PLUMBING FIXTURES, SUPPLY, WASTE AND VENT LINES per IRC SECTION
DRAINAGE FIXTURE UNIT (d.f.u.) VALUES NEW 2"Ø VTR R106.1.1.
CONDITIONED STUDIO WITH BATHROOM
TYPE OF FIXTURE 4. DRAINAGE PIPING SERVING FIXTURES WHICH HAVE FLOOD LEVEL RIMS LOCATED BELOW THE ELEVATION OF THE NEXT
(d.f.u.) VALUE
BATHROOM 2" UPSTREAM MANHOLE COVER THE PUBLIC SEWER SHALL BE PROTECTED FROM BACKFLOW OR SEWAGE BY A BACKWATER
LAVATORY 1
VALVE. IRC AMENDED SECTION P3008.1
SHOWER STALL 2
WATER CLOSET (1.6 gal.) 3 2"
5. ALL APPLIANCES AND EQUIPMENT ARE ELECTRIC (SEE SHEET A2.1) PROJECT NO.
TOTAL 6 2" 6. WATER METER WORKSHEET per TABLE E201.1 SHALL BE PROVIDED AS A SEPARATE DOCUMENT. 012423
SINK
LAV 7. INSULATION FOR HOT WATER PIPE WITH A MINIMUM THERMAL RESISTANT (R-VALUE) OF R-3 SHALL BE APPLIED TO THE
KITCHEN SINK 2
FOLLOWING:
ISSUE: DATE:
2"
2" TOILET PIPING LARGER THAN 43" NOMINAL DIAMETER
3"
4" PIPING FROM THE WATER HEATER TO THE KITCHEN OUTLETS
2" 3"
2" PIPING LOCATED OUTSIDE THE CONDITIONED SPACE
6"

TANKLESS
WATER HEATER
SINK 2" 3" PIPING FROM THE WATER HEATER TO A DISTRIBUTION MANIFOLD
T&P
VALVE
3"
DETAIL PIPING RUNS LENGHTS GREATER THAN THE MAXIMUM RUN LENGHTS FOR THE NOMINAL PIPE DIAMETER GIVEN IN TABLE
2X6 EXTERIOR WALL FIELD VERIFY SHOWER N1103.4.2
EXTERIOR 3"
INSTALLATION.
3/4" COPPER
PIPE
2"
NOTICE:
DIRECTION OF FLOW TO 3" 2 PLUMBING
CITY OF PHOENIX WAY CLEANOUT. THE SCHEMATICS ARE ONLY AN ISOMETRIC REPRESENTATION SHOWING RELATIVE FIXTURE
Planning and Development Department WASTE PLAN
BY: Gary D. Swinford
TEMPERATURE AND POSITIONING, THE ACTUAL LOCATION AND ROUTING OF PIPING MAY VARY. ANY CHANGE
PRESSURE VALVE DETAIL 01/16/2024
WASTE AND VENT IN THE SEQUENCE OF FIXTURES THAT EFFECTS THE PIPING SIZE, MUST BE APPROVED BY
This set of plans has been reviewed for PHOENIX
THE BUILDING OFFICIAL.
P1.0
CONSTRUCTION CODE requirements prior to
issuance of Building Permit and shall be kept at the
construction site. Such review shall not prevent the
ISOMETRIC
Building Official from requiring correction of errors in
the plans where such errors are subsequently found NON SCALE
to be in violation of any law or ordinance.
NOTE : ALL THE MATERIALS WILL BE THE SAME AS THOSE OF THE EXISTING HOUSE TO UNIFY.
ELECTRICAL SYMBOLS MAIN PANEL -ELECTRICAL LOAD CALCULATION FOR
ELECTRICAL SERVICE 2 OF 3 PANEL SCHEDULE SINGLE - FAMILY DWELLING OR DUPLEX

WH

GFCI
WP
DUPLEX CONVENIENCE OUTLET
GFCI GFCI GENERAL LIGHTING LOAD 7,125
180 AMPS 240 VLTS 1Ø, 3-WIRE 200 ,000 AIC 220V OUTLET
(LIVABLE AREA @ 3 WATTS PER SQ. FT. )
MAIN BREAKER (YES) (NO) NEMA 1 3R (CHOOSE ONE)
SUB-PANEL LIGHT - RECESSED CAN DOWN SMALL APPLIANCE LOAD 3,000
LOAD
CKT.# AMPS POLES AREA SERVED AREA SERVED AMPS POLES CKT.# (MINIMUN OF 2 CIRCUITS @ 1,500 WATTS EACH)
EXTERIOR LIGHT - WALL MOUNTED
AØ BØ FIXTURE WEATHERPROOF
1 20 1 RECEPTACLE RECEPTACLE 20 1 2 LAUNDRY LOAD 1,500
3 20 1 WASHER MASTER BEDROOM BATHROOM 15 1 4 SWITCH (MINIMUN OF 1 CIRCUITS @ 1,500 WATTS EACH)
5 20 1 WASHER BED 2- LAUNDRY 15 1 6
ATTIC INTERIOR WALL MOUNTED LIGHT (VANITY)
APPLIANCE LOADS @ NAMEPLATE RATING
7 20 1 DISPONSAL/DISHWASHER BEDS BATH 2 HALL 15 1 8
ACCES 9 20 1 MICRO KITCHEN GREAT ROOM PATIO 15 1 10 DRYER 5,000
11 20 1 KITCHEN GFCI NOOK ENTRY GARAGE NOOK 15 1 12 EXHAUST FAN RANGE 3,400

13 20 1 KITCHEN GFCI ICELAND FRIDGE 15 1 14 COOKTOP 8,000

7725 W ODEUM LN, PHOENIX, AZ 85043


SMOKE/CO DETECTOR - DUAL ALARM OVEN/ DOUBLE OVEN 3,400

A/C MINISPLIT
15
17
45
/
2
/
COOK
TOP
A/C
/
50
/
2
/
16
18
THERMOSTAT
WATER HEATER
DISHWASHER 1,500 ROC # 318489
19 20 1 OVEN EXT GFCI 15 1 20 DISPOSAL 1,600
MICROWAVE

EPTA CONSTRUCTION
1,500
J 21 / / / AIR HANDLER 15 / 22
SECTION N1104 (R404) TRASH COMPACTOR 1,800
A/C

23 20 1 DEDICATED GARAGE BATH GFCI 20 1 24 ELECTRICAL POWER AND LIGHTING SYSTEMS SPA/ HYDROMASSAGE BATHTUB
25 20 1 GARAGE GFCI LANDSCAPE 20 1 26 (MANDATORY) GARAGE DOOR OPENER 540

NEW CONDITIONED STUDIO


BATHROOM HEAT /VENT /LIGHT
27 20 1 DRYER NEW SUBPANEL 100 2 28 N1104.1 (R404.1) LIGHTING EQUIPMENT. WATER SOFTENER
SERVICE PLEASE NOTE: A MINIMUM OF 75% OF THE LAMPS IN SWIMING POOL EQUIPMENT
DISCONECT REFRIGERATOR 1,800
PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL AIR HANDLING UNIT(S) 1,200
PLAN AREA CALCULATIONS A MINIMUM OF ONE 20 AMP, GFCI PROTECTED BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF
CIRCUIT REQUIRED IN BATHROOMS. THE PERMANENTLY INSTALLED LIGHTING FIXTURES
DESCRIPTION AREA SQFT

WITH BATHROOM
A SEPARATE 20 AMP, GFCI PROTECTED CIRCUIT SHALL CONTAIN ONLY HIGH-EFICACY LAMPS. SUBTOTAL OF GENERAL LOAD 20,706
LIVEABLE CONDITIONED SPACE 2,375 REQUIRED IN THE LAUNDRY AREA. EXEMPTION: LOW-VOLTAGE LIGHTING SHALL NOT BE FIRST 10,000 WATTS @ 100% 10,000

COVERED ENTRY - A SEPARATE 20 AMP, GFCI PROTECTED CIRCUIT REQUIRED TO UTILIZE HIGH-EFFICIENCY LAMPS. REMAINDER OF GENERAL LOAD @ 40% 10,706
REQUIRED IN GARAGES AND EACH VEHICLE BAY
GARAGE - REQUIRED TO HAVE RECEPTALES. TOTAL GENERAL LOAD 20,706

COVERED PATIO - LARGER OF AIR CONDITIONING OR HEAT 7,800


A MINIMUM OF ONE 20 AMP, GFCI PROTECTED
NEW CONDITIONED STUDIO CIRCUIT ALL BRABCH CIRCUITS THAT SUPPLY 120
WITH BATHROOM 276 VOLT, SINGLE PHASE 15/20 AMP OUTLETS SHALL BE
NET COMPUTED LOAD IN WATTS
PROTECTED BY A COMBINATION TYPE ARC-FAULT
CIRCUIT-INTERRUPTER INCLUDING KITCHENS AND NET COMPUTE LOAD IN AMPS 119
GFCI NEW COVERED PATIO EXTENSION 174
WP LAUNDRY AREAS.
TOTAL AREA UNDER ROOF 2,825
PROVIDE TAMPER RESISTANT RECEPTACLE AS
REQUIRED BY E4002.14 SUBPANEL -ELECTRICAL LOAD CALCULATION FOR
SINGLE - FAMILY DWELLING OR DUPLEX
ELECTRICAL PLAN LOT
GENERAL LIGHTING LOAD 828
CITY OF PHOENIX
Planning and Development Department
SCALE 3/8":1' DESCRIPTION AREA SQFT (LIVABLE AREA @ 3 WATTS PER SQ. FT. )
BY: Gary D. Swinford
29
TOTAL AREA UNDER ROOF 2819.5 SMALL APPLIANCE LOAD 1,500
01/16/2024 20 (MINIMUN OF 2 CIRCUITS @ 1,500 WATTS EACH)
LOT SQUARE FOOTAGE 8,169 24"

This set of plans has been reviewed for PHOENIX


CONSTRUCTION CODE requirements prior to LOT COVERAGE 34.52% LAUNDRY LOAD 1,500
issuance of Building Permit and shall be kept at the 21
construction site. Such review shall not prevent the 28 22 (MINIMUN OF 1 CIRCUITS @ 1,500 WATTS EACH)
Building Official from requiring correction of errors in
the plans where such errors are subsequently found 26
to be in violation of any law or ordinance. APPLIANCE LOADS @ NAMEPLATE RATING
27
30"
23
27 DRYER
MAIN ELECTRICAL PANEL 24 20 RANGE
COOKTOP
OVEN/ DOUBLE OVEN
WATER HEATER
MAXIMUM AVAILABLE FAULT CURRENT 200 AMPS DISHWASHER
NOTE THIS SYSTEM IS AN ALL ELECTRICAL UNIT. NO GAS DETAILS DISPOSAL
PROVIDED. FIELD VERIFY. ALL WORK PER 2018 IRC MICROWAVE
TRASH COMPACTOR
PROJECT NO.
M 100 AMP SUBPANEL RATED SAME AS SES SPA/ HYDROMASSAGE BATHTUB
GARAGE DOOR OPENER
012423
BATHROOM HEAT /VENT /LIGHT
WATER SOFTENER
SWIMING POOL EQUIPMENT
MP
27
NOTE:
WATER HEATER
AIR HANDLING UNIT(S)
4,500
1,200
ISSUE: DATE:
SP IF FURNACE IS LOCATED BELOW SCISSOR TRUSS THE RECOMMENDED INSULATING PROCEDURE IS
ALONG THE CEILING LINE BELOW THE FURNACE NOT ALONG THE SCISSOR ABOVE TO PROVIDE
POOL PUMP
POOL LIGHT
3,840
396
PROPER COMBUSTION AIR WITHOUT COMPROMISING THE INTEGRITY OF THE THERMAL ENVELOPE
BY PENETRATING IT WITH COMBUSTION DUCTS. THE SPECIFICATIONS ABOVE MEET THE MINIMUM POOL HEATER ELECTRIC 5,040
REQUIREMENTS ESTABLISHED IN THE 1988,1991,1994 & 1997 U.B.C. and U.M.C. MANUALS.

A.H.U. LOCATED IN ATTIC SPACE No Scale SUBTOTAL OF GENERAL LOAD 18,804

#4 CUB #4 CUB FIRST 10,000 WATTS @ 100%


REMAINDER OF GENERAL LOAD @ 40%
10,000
3,522

WATER/GAS WATER/GAS KEY NOTES TOTAL GENERAL LOAD 13,522


BOND BOND
21 LARGER OF AIR CONDITIONING OR HEAT 3,000

2 12 " CONDUIT FROM 22 NET COMPUTED LOAD IN WATTS

TRANSFORMER PER 23 NET COMPUTE LOAD IN AMPS 69

UTILITY COMPANY 24

25
2018 IRC N1104.1 LIGHTING EQUIPMENT (MANDATORY). NOT LESS THAN ELECTRICAL
90% OF PERMANENTLY INSTALLED INSTALLED LIGHTING FIXTURE.
#4 BARE COPPER UFER MIN.
26

PLAN
20' LONG 27

28

29

NOTE : ALL THE MATERIALS WILL BE THE SAME


AS THOSE OF THE EXISTING HOUSE TO UNIFY.
E1.0