1.0 GENERAL REQUIREMENTS 5.0 NOTES ON CONCRETE MIXES AND PLACEMENT
1.1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. 1.2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEEL, MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. SHALL BE SUBMITTED FOR ENGINEER'S APPROVAL BEFORE FABRICATION. 1.3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN, CHECK WITH MECHANICAL AND ELECTRICAL CONTRACTORS FOR CONDUITS, PIPE SLEEVES, ETC. TO BE EMBEDDED IN CONCRETE. 8.3. IF SLABS ARE REINFORCED BOTHWAYS, BARS ALONG THE SHORTER SPAN 1.4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING SHALL BE PLACED BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND BRACING OF THE STRUCTURE FOR ALL LOADS THAT MAYBE IMPOSED DURING AND OVER THE LONGER SPAN FOR REINFORCING BARS NEAR THE CONSTRUCTION. SUPPORTS, THE SPACING OF THE BARS AT THE COLUMN STRIPS SHALL NOT BE MORE THAN ONE AND A HALF (1 1/2) OF THE SLAB THICKNESS. 2.0 STANDARDS AND REFERENCES 8.4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE 2.1. THE DESIGN, FABRICATION AND CONSTRUCTION OF THE PROJECT SHALL BE FACE IN TENSION AND SHALL NOT BE LESS THAN 0.0025 X GROSS-SECTIONAL GOVERNED BY NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (N.S.C.P.). VOL 1, AREA (Ag) OF THE SLAB (SEE SCHEDULE BELOW) 7TH EDITION 2015
3.0 DESIGN CRITERIA
3.1. LOADINGS A. DEAD LOAD CONCRETE 23.544 kN/m³ STEEL 76.93 kN/m³ 150MM THK. CHB WALL 3.11 kPa 100MM THK. CHB WALL 2.89 kPa B. LIVE LOAD TYPICAL TO ROOMS 1.90 kPa EXTERIOR CORRIDORS 2.90 kPa ROOF LIVE LOAD 0.60 kPa C. WIND LOAD DESIGN WIND SPEED 270 kPh E. SEISMIC LOAD IMPORTANCE FACTOR =1, NUMERICAL FACTOR = 8.5 SEISMIC COEFFICIENT: Cv = 0.44Nv, Ca = 0.64Na NEAR SOURCE FACTOR: Nv = 1.0, Na = 1.0 SEISMIC ZONE: Z = 0.40 (ZONE 4) SOIL TYPE: S = D 3.2. DESIGN STRESSES A. CONCRETE FOR FOOTING, COLUMNS, BEAMS, WALLS AND SLABS COMPRESSIVE STRENGTH @ 28 DAYS fc' = 21 MPa (3,000 psi) B. REINFORCING STEEL BARS FOR BARS 16MMØ AND GREATER INTERMEDIATE GRADE DEFORMED BAR fy = 276 MPa (40,000 psi) FOR BARS LESS THAN 16MMØ fy = 235 MPa (33,000 psi) C. STRUCTURAL STEEL, ASTM-A36 FOR PURLINS, TRUSSES, BRACING AND STRUTS fy = 248 MPa (36,000 psi) D. MASONRY UNIT (CHB) NON-LOAD BEARING WALLS fm' = 3.45 MPa (500 psi) E. WELDS: USED E-60XX ELECTRODES F. STRUCTURAL BOLTS, ASTM-A307 fy = 620 MPa (90,000 PSI); Fnv = 372 mpA (54,000 si)
4.0 OTHER NOTES
4.1. IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN AND DISTANCES SHALL BE SCALED FOR CONSTRUCTION PURPOSES. 11.0 NOTES ON FOUNDATION 11.1.ALL FOUNDATION WORKS SHALL BE PROVIDED WITH A "LEAN CONCRETE" HAVING THICKNESS OF 50MM (2") AND CONCRETE STRENGTH FC' = 13.8 MPA (2000 PSI).
12.0 MISCELLANEOUS NOTES
RA 544, ARTICLE 5, SECTION 33
PREPARED BY: SEAL: MISCELLANEOUS PROVISIONS, SPECIFICATION AND OTHER CONTRACT PROJECT TITLE: SHEET CONTENT: CONFORME: DOCUMENTS.
MAC Structural Designs IT SHALL BE UNLAWFUL FOR ANY PERSON TO ORDER
OR OTHERWISE CAUSE THE CONSTRUCTION, AS SHOWN and Engineering Services RECONSTRUCTION, OR ALTERATION OF ANY BUILDING OR STRUCTURE INTENDED FOR PUBLIC GATHERING OR ASSEMBLY SUCH AS THEATERS, CINEMATOGRAPHS, PROPOSED CONSTRUCTION OF STADIA, CHURCHES OR STRUCTURES OF LIKE NATURE,
ENGR. MARK HEINTJE A. CUANAN
AND ANY OTHER ENGINEERING STRUCTURES MENTIONED IN SECTION TWO OF THIS ACT UNLESS THE DESIGNS, PLANS, AND SPECIFICATIONS OF SAME HAVE TWO-STOREY RESIDENTIAL MRS. WARDA PANONDI OWNER BEEN PREPARED UNDER THE RESPONSIBLE CHARGE Services Offered: Building Designs, CAD Drafting, Structural Designs and other Engineering Services CIVIL ENGINEER/STRUCTURAL DESIGNER OF, AND SIGNED AND SEALED BY A REGISTERED CIVIL ENGINEER, AND UNLESS THE CONSTRUCTION, RECONSTRUCTION AND/OR ALTERATION THEREOF ARE BUILDING SHEET NO. 6 Address: B11, L24, Summerville Subdivision, Lumbia, Cagayan de Oro City PRC: VALIDITY: EXECUTED UNDER THE RESPONSIBLE CHARGE AND DIRECT SUPERVISION OF A CIVIL ENGINEER. PLANS AND Mobile No: 09482110174/09352839502 PTR: PLACE: CDOC DESIGNS OF STRUCTURES MUST BE APPROVED AS LOCATION: BAGUA II, COTABATO CITY, MAGUINDANO Email: markcuanan@gmail.com DATE: 11/20/2021 TIN: PROVIDED BY LAW OR ORDINANCE OF A CITY OR PROVINCE OR MUNICIPALITY WHERE THE SAID STRUCTURE IS TO BE CONSTRUCTED. OWNER: MRS. WARDA PANONDI DRAWING NO. S1