STRUCTURAL PLAN

GENERAL NOTES:
1.0 GENERAL : GCpi = PRODUCT OF INTERNAL PRESSURE
1.1 & GUST EFFECT FACTOR IN NSCP TABLE 207-4.
UNLESS NOTED OTHERWISE, ALL DIMENSIONS SHOWN ARE IN MILLIMETERS
AND ELEVATIONS SHOWN ARE IN METERS. 3.4. SEISMIC LOAD , E 4.2.2 ALL REINFORCING BARS SHALL BE CLEANED OF RUST, GREASE OR OTHER 6.2 IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS , USE SEPARATORS OF SIZE
1.2 THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SEISMIC LOADS FOR BUILDING STRUCTURES ARE CALCULATED BASED ON MATERIALS WHICH TEND TO IMPAIR BOND. NOT LESS THAN 25mm BARS SPACED ABOUT 1.00m ON CENTER AND PLACED DIAGONALLY.
SITE, AND SHALL NOTIFY THE ENGINEER OF DISCREPANCIES BETWEEN ACTUAL THE FOLLOWING: IN NO CASE SHALL THERE BE LESS TWO (2) SEPARATORS BETWEEN LAYERS OF BARS.
4.2.3 ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED
CONDITIONS AND INFORMATION SHOWN ON THE DRAWINGS BEFORE PROCEEDING E = rEh + Ev BEFORE POURING CONCRETE OR APPLYING MORTAR OR GROUT. 6.3 WHEN A BEAM CROSSES A GIRDER, REST BEAM BARS ON TOP OF GIRDER BARS.
WITH THE WORK. THIS SHALL INCLUDE THE LOCATION AND DIMENSIONS OF Em = Vo Eh REINFORCING BARS SHALL BE SYMMETRICAL ABOUT THE CENTER LINE WHENEVER POSSIBLE.
GROOVES, REGLETS, SLEEVES, CURBS, OPENINGS, EMBEDDED OR ATTACHED 4.2.4 LAPPED SPLICES SHALL BE STAGGERED WHERE POSSIBLE.
WHERE: UPPER LAYER SHALL BE PLACED DIRECTLY ABOVE THOSE IN THE BOTTOM LAYER.
ITEMS, ETC. (REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING.) 4.2.5 UNLESS INDICATED OTHERWISE, SPLICING OF REINFORCEMENT SHALL BE IN SPACING OF BARS IN LAYER SHALL NOT BE LESS THAN 0.025m NOR ONE BAR DIAMETER.
E = EARTHQUAKE LOAD ON THE STRUCTURE ACCORDANCE WITH ACI 318-2005.
1.3 ALL FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS, Eh = THE EARTHQUAKE LOAD DUE TO THE BASE SHEAR, V, OR THE 6.4 GENERALLY, NO SPLICE SHALL BE PERMITTED ON BEAM AT POINT WHERE CRITICAL
SECTIONS OR DETAILS. SPECIFIC NOTES AND DETAILS ON DRAWINGS SHALL TAKE DESIGN LATERAL FORCE Fp. 4.2.6 UNLESS SHOWN OTHERWISE ON PLANS, SPLICES SHALL BE AS FOLLOWS : BENDING STRESSES OCCUR. WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125%
PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. Em = THE ESTIMATED MAXIMUM EARTHQUAKE FORCE THAT CAN BE A. BEAMS AND FOOTING TIE BEAMS : TOP AND BOTTOM BARS SHALL NOT OF THE SPECIFIED STRENGTH OF THE BAR, NOT MORE THAN 50% OF THE BARS AT ANY
DEVELOPED IN THE STRUCTURE. BE SPLICED WITHIN THE COLUMN OR WITHIN A DISTANCE OF TWICE THE ONE SECTION SHALL BE ALLOWED TO BE SPLICED THEREIN.
1.4 THE STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED Ev = THE LOAD EFFECT RESULTING FROM THE VERTICAL COMPONENT MEMBER DEPTH FROM THE FACE OF THE COLUMN ; AT LEAST TWO EXTRA 6.5 FOR BAR TERMINATIONS OF TOP BARS AT SUPPORT AND MIDSPAN BARS, CUT-OFF ONLY
STRUCTURES. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION OF THE EARTHQUAKE GROUND MOTION AND IS EQUAL TO AN STIRRUP - TIES SHALL BE PROVIDED AT ALL SPLICES. THE SPLICE LENGTH TWO BARS AT EVERY 0.3m INTERVAL (UNLESS REQUIRED IN SPECIFICATIONS, OR
UNLESS SO STATED. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY ADDITIONAL OF 0.5 Ca I D TO THE DEAD LOAD EFFECT. D, FOR SHALL NOT BE LESS THAN THE LENGTH IN ITEM 4.2.9 BELOW. NOTED OTHERWISE.)
MEASURES TO PROTECT THE STRUCTURES, ADJACENT PROPERTIES, WORKMEN STRENGTH DESIGN, AND MAY BE TAKEN AS ZERO FOR ALLOWABLE
AND OTHER PERSONS DURING ALL PHASES OF CONSTRUCTION. STRESS DESIGN. B. COLUMNS : SPLICES WHEN PERMITTED SHALL BE MADE WITHIN THE CENTER
Vo = THE SEISMIC FORCE AMPLIFICATION FACTOR THAT IS REQUIRED HALF OF COLUMN HEIGHT, AND LAP SPLICE SHALL NOT BE LESS THAN
1.5 THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN CHARGE 40 BAR DIAMETERS. THE USE OF APPROVED MECHANICAL DEVICES MAY BE
7.0 FOUNDATIONS :
TO ACCOUNT FOR STRUCTURAL OVERSTRENGTH.
OF ANY CONDITION WHICH IN HIS OPINION MIGHT ENDANGER THE STABILITY PERMITTED PROVIDED THAT NOT MORE THAN ALTERNATE BARS ARE 7.1 FOOTINGS WERE DESIGNED USING AN ASSUMED ALLOWABLE SOIL BEARING
OF THE STRUCTURES OR CAUSE DISTRESS IN THE STRUCTURES. r = RELIABILITY / REDUNDANCY FACTOR WHICH SHALL NOT BE TAKEN SPLICED AT ANY LEVEL AND THE MINIMUM VERTICAL DISTANCE CAPACITY OF 150 kPa AT DEPTHS INDICATED IN THE DRAWING. IN CASE THE
LESS THAN 1.0 AND GREATER THAN 1.5, IS GIVEN BY THE BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600mm. ACTUAL SOIL BEARING CAPACITY IS FOUND LESS THAN THE ASSUMED 150 kPa,
1.6 THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION BRACINGS AND
FOLLOWING FORMULA: C. CONCRETE MASONRY UNIT (CMU) WALLS : VERTICAL BARS SHALL BE SPLICED NOTIFY THE STRUCTURAL ENGINEER FOR PROPER REVISION OF FOOTINGS.
SHORINGS FOR ALL THE STRUCTURAL MEMBERS AS REQUIRED FOR STRUCTURE
STABILITY DURING ALL PHASES OF CONSTRUCTION. r =2- 6.1 AT THE TOP OF WALL FOOTING OR TIE BEAM AND AT THE BOTTOM OF RC LINTEL 7.2 CONFIRMATION OF ACTUAL SOIL BEARING CAPACITY SHALL BE PERFORMED
rmax AB BEAM OR BEAMS. SPLICE LENGTHS SHALL BE 600mm MIN. PRIOR TO THE CONSTRUCTION OF THE FOUNDATION.
1.7 THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE WHERE:
4.2.7 UNLESS INDICATED OTHERWISE, ALL BEAMS TERMINATING AT THE COLUMN 7.3 WHERE LOOSE/SOFT MATERIAL IS ENCOUNTERED AT DEPTH OF FOOTING/FOUNDATION
PROPER ALIGNMENT OF THE STRUCTURES DURING AND AFTER THE INSTALLATION rmax = THE MAXIMUM ELEMENT-STORY SHEAR RATIO. FOR A GIVEN SHALL HAVE TOP AND BOTTOM BARS EXTENDING TO THE FAR FACE OF
OF ALL STRUCTURAL AND FINISH MATERIALS. INDICATED, EXCAVATE TO FIRM LAYER AND REPLACE LOOSE/SOFT MATERIALS
DIRECTION OF LOADING, THE ELEMENT-STORY SHEAR RATIO IS THE COLUMN, TERMINATING IN A STANDARD 90° HOOK LENGTH OF
THE RATIO OF THE DESIGN OF STORY SHEAR IN THE HEAVILY UNDERNEATH THE FOOTING WITHIN THE FOOTING AREA PLUS 1/2 DEPTH OF SOIL
1.8 THE CONTRACTOR SHALL INFORM THE SUB-CONTRACTORS THAT NO CONSTRUCTION ANCHORAGE NOT LESS THAN 600mm. MATERIAL ON ALL SIDES WITH SELECTED BACKFILL. COMPACT SELECTED BACKFILL
LOADED SINGLE ELEMENT DIVIDED BY THE TOTAL DESIGN
MATERIALS SHALL BE STORED ON POURED FLOORS, AND SHALL ENSURE THAT THE STORY SHEAR. 4.2.8 SHOP DRAWINGS FOR BENDING AND CUTTING OF REINFORCEMENT SHALL TO 95% MAXIMUM DRY DENSITY ( ASTM D1557).
SUB-CONTRACTORS DO NOT VIOLATE THIS IMPORTANT REQUIREMENT. FOR MOMENT FRAMES, IT SHALL BE TAKEN AS THE MAXIMUM BE SUBMITTED FOR APPROVAL TO THE ENGINEER PRIOR TO FABRICATION. 7.4 ALL COLUMN FOOTINGS SHALL REST ON 100mm THK COMPACTED GRAVEL
OF THE SUM OF THE SHEARS IN ANY TWO ADJACENT COLUMNS 4.2.9 SPLICE LENGTH OF REINFORCING BARS SHALL BE AS SHOWN IN THE TABLE BELOW. BASE COURSE, UNLESS OTHERWISE STATED.
1.9 TYPICAL DETAILS AND GENERAL NOTES ON S-1 AND S-2 SHALL APPLY TO ALL PARTS IN A MOMENT FRAME BAY DIVIDED BY THE STORY SHEAR. FOR
OF THE WORKS UNLESS OTHERWISE SHOWN ON THE DRAWINGS. COLUMNS COMMON TO TWO BAYS, 70 PERCENT OF THE SHEAR 7.5 FILL/BACKFILL SHALL BE PLACED IN 200mm LAYERS AND EACH LAYER SHALL BE
IN THAT COLUMN MAY BE USED IN THE COLUMN SHEAR SUMMATION. 4.3 STRUCTURAL STEEL/ANCHOR BOLTS/BOLTS/WELDS & WELDMENTS COMPACTED TO 95% MAXIMUM DRY DENSITY BEFORE SUBSEQUENT LAYERS
AB = THE GROUND FLOOR AREA OF THE STRUCTURE. ARE TO BE LAID.
2.0 STANDARDS AND REFERENCES : 4.3.1 ALL STRUCTURAL STEEL SHALL HAVE A MINIMUM YIELD STRENGTH,
THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND CONSTRUCTION EARTHQUAKE BASE SHEAR, (V) : Fy = 248 MPa (36 KSI) AND SHALL CONFORM TO ASTM A 36
OF THE PROJECT: SPECIFICATIONS.
THE TOTAL DESIGN BASE SHEAR IN A GIVEN DIRECTION SHALL
BE DETERMINED FROM THE FOLLOWING FORMULA: 4.3.2 ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN
2.1 AMERICAN CONCRETE INSTITUTE ( ACI PUBLICATIONS ) ;
ACI 318-05 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE V = Cv I (W) ACCORDANCE WITH THE AISC SPECIFICATIONS (9TH EDITION) AND LAP SPLICE & ANCHORAGE LENGTH TABLE
ACI 315-94 MANUAL OF STANDARD PRACTICE FOR DETAILS AND DETAILING RT CODE OF STANDARD PRACTICE AS AMENDED TO DATE.
OF CONCRETE REINFORCEMENT. STANDARD HOOK LAP SPLICE (m) MIN. LAP SPLICE
AND NEED NOT EXCEED THE FOLLOWING: 4.3.3 ALL COLD FORMED STEEL SHALL HAVE A MINIMUM STRENGTH, LENGTH OF COL. REINF.
Fy = 230 MPa (33 KSI) BAR ANCHORAGE UNIT
2.2 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) PUBLICATION: V = 2.5 Ca I (W) DIAMETER LENGTH (m) TENSION BAR COMP. BAR WEIGHT INDIVIDUAL BARS
MANUAL OF STEEL CONSTRUCTION, NINTH EDITION. R 4.3.4 NO STEEL SHALL BE FABRICATED OR ERECTED UNTIL SHOP DRAWINGS (mm) (m) (kg/m)
"ALLOWABLE STRESS DESIGN" (ASD) HAVE BEEN APPROVED BY THE STRUCTURAL ENGINEER. 90° 180° 135° TOP BAR OTHERS TOP BAR OTHERS W/ TIES W/ SPIRAL
BUT SHALL NOT BE LESS THAN THE FOLLOWING:
2.3 AMERICAN WELDING SOCIETY (AWS) PUBLICATION D.1.1-2000. 4.3.5 ALL SHOP AND FIELD WELDING SHALL BE IN ACCORDANCE WITH AWS 10 0.50 0.15 0.13 0.10 0.42 0.30 0.42 0.30 0.617 0.30 0.30
V = 0.11 Ca I W
2.4 AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM) D.1.1-2000 AND PERFORMED BY QUALIFIED WELDERS.
IN ADDITION FOR SEISMIC ZONE 4, THE TOTAL BASE SHALL ALSO 12 0.50 0.20 0.15 0.12 0.42 0.30 0.42 0.30 0.889 0.30 0.30
2.5 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP) VOL. 1, BE NOT LESS THAN THE FOLLOWING: 4.3.6 UNLESS INDICATED OTHERWISE, WELDING ELECTRODES SHALL BE E70XX,
MINIMUM THICKNESS OF WELD SHALL BE 3mm. 16 0.60 0.25 0.18 0.14 0.73 0.52 0.87 0.62 1.580 0.52 0.47
SIXTH EDITION 2010.
V = 8.5 Z Nv I (W) 20 0.60 0.30 0.20 0.20 0.91 0.65 1.10 0.78 2.469 0.65 0.58
2.6 ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES (ASEP) 4.3.7 UNLESS OTHERWISE INDICATED ALL ANCHOR
R BOLTS SHALL CONFORM TO ASTM A307 SPECIFICATIONS.
HANDBOOK OF STRUCTURAL STEEL SHAPES AND SECTIONS, 2004 WHERE: 25 0.68 0.40 0.28 0.26 1.15 0.82 1.40 1.00 3.858 0.80 0.73
SEISMIC ZONE FACTOR, Z = 0.40 4.3.8 BOLTS FOR MEMBER CONNECTIONS SHALL BE HIGH STRENGTH BOLTS,
2.7 UNIFORM BUILDING CODE (UBC), VOL. 2 1997 EDITION 28 0.86 0.48 0.38 - 1.45 1.03 1.53 1.09 4.840 0.90 0.82
IMPORTANCE FACTOR I = 1.5 CONFORMING TO ASTM A325 FRICTION TYPE WITH WASHERS.
GLOBAL DUCTILITY CAPACITY R = 8.5 (SMRF) 32 1.12 0.56 0.43 - 1.90 1.35 1.74 1.24 6.327 1.03 0.93
3.0 BASIC DESIGN LOADS : SEISMIC FORCE OVERSTRENGTH FACTOR Vo = 2.8 4.4 CONCRETE MASONRY UNITS (CMU)
3.1. DEAD LOADS (DL) : SEISMIC SOURCE TYPE =A 36 1.43 0.61 0.48 - 2.40 1.70 2.00 1.40 8.00 1.20 1.05
NEAR - SOURCE FACTOR, Nv = 1.6 4.4.1 CMU USED IN THESE WORKS SHALL HAVE A MINIMUM ULTIMATE
3.1.1 CONCRETE 24.00 kN/m3 COMPRESSIVE STRENGTH @ 28 DAYS AS FOLLOWS :
COLUMN/WALL
3.1.2 STEEL 77.00 kN/m3
NEAR - SOURCE TYPE, Na = 1.2 NOTES: FACE
ANCHORAGE
100mm THICK NON-LOAD BEARING CMU, f'm = 2.4 MPa (350 PSI) LENGTH
3.1.3 SOIL 18.00 kN/m3 1. ACI SECTION 12.4 STATES THAT DEVELOPMENT LENGTH OF INDIVIDUAL BARS W/IN A BUNDLE,
4.0 MATERIALS : 150mm THICK NON-LOAD BEARING CMU, f'm = 2.4 MPa (350 PSI)
3.1.4 CEILING 200 Pa IN TENSION OR COMPRESSION, SHALL BE THAT FOR THE INDIVIDUAL BAR, INCREASED 20%
3.1.5 MISCELLANEOUS 200 Pa 4.4.2 ALL CELLS SHALL BE SOLIDLY FILLED WITH GROUT. CONCRETE SHALL FOR THREE BAR BUNDLE, AND 33% FOR FOUR BAR BUNDLE. 180°
3.1.6 100mm THK.CHB WALL 4.1 NORMAL WEIGHT CONCRETE : HAVE A MINIMUM COMPRESSIVE STRENGTH OF 13.80 MPa HOOK
2107 Pa 2. FOR COLUMNS, AT ANY LEVEL NO MORE THAN ALTERNATE BARS SHOULD BE SPLICED. NOT
3.1.7 150mm THK.CHB WALL 2730 Pa (2,000 PSI) @ 28 DAYS.
4.1.1 CONCRETE USED IN THIS WORK SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH MORE THAN 33% OF THE BARS SHALL BE SPLICED W/IN THE REQUIRED LAP LENGTH. 135°
3.1.8 FLOOR TILES PLUS MORTAR 1100 Pa @ 28 DAYS AS FOLLOWS: 4.4.3 UNLESS INDICATED OTHERWISE, CMU REINFORCEMENT SHALL BE 10mmØ HOOK
MINIMUM DISTANCE BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600mm. 90°
HOR. BARS SPACED @ 600mm AND 10mmØ VERT. BARS SPACED @ 600mm. HOOK
3.2. LIVE LOADS (LL) : COLUMN, BEAM, SLAB, & OTHERS fc' = 28MPa (4,000 PSI) 3. TOP BARS ARE HORIZONTAL BARS W/ MORE THAN 300mm DEPTH OF CONCRETE CAST BELOW
4.4.4 ALL WALLS SHALL BE CONSTRUCTED IN CONVENTIONAL RUNNING BOND,
3.2.1 BASIC FLOOR AREA
HALLWAYS ABOVE GROUND FLOOR
1900
3800
Pa
Pa
FOOTING fc' = 21MPa (3,000 PSI) UNLESS NOTED OTHERWISE.
THE REINFORCEMENT. 1 DETAIL
3.2.2 4.4.5 GROUT MASONRY IN 2.4m MAXIMUM LIFTS. REINFORCING SHALL BE 4. AS MUCH AS POSSIBLE, SPLICES SUBJECTED TO TENSILE STRESSES ARE DISCOURAGE, THESE SCALE NTS
3.2.3 STAIRS, HALLWAYS, AND ASSEMBLY 4800 Pa 4.1.2 ALL CONCRETE SHALL BE DEPOSITED, VIBRATED AND CURED IN ACCORDANCE SHOULD BE AVOIDED OR PROVIDED W/ STANDARD HOOKS. S-1
SECURED AGAINTS DISPLACEMENT PRIOR TO GROUTING BY WIRE
3.2.4 ROOF 900 Pa WITH ACI STANDARD 318-2005.
POSITIONERS AT INTERVALS NOT EXCEEDING 200 BAR DIAMETERS
4.1.3 MINIMUM CONCRETE COVER FOR REINFORCING BARS SHALL BE AS FOLLOWS: NOR 3m.
A. FOOTINGS & BOT. OF FOOTING TIE BEAM = 75mm (CAST AGAINST EARTH) 4.4.6 IF WORK IS STOPPED ONE (1) HOUR OR LONGER, PROVIDE HORIZONTAL
3.3. WIND LOAD (WL) B. BEAMS AND COLUMNS = 40mm (TO STIRRUPS AND TIES) CONSTRUCTION JOINTS BY STOPPING THE GROUT 50mm BELOW THE TOP
WIND LOADING ON MWFRS (MAIN WIND FORCE RESISTING SYSTEM) : C. SLABS AND WALLS = 20mm (CAST AGAINST FORMS) OF THE BLOCK.
P = qh[(GCpf)-(GC pi )] 4.1.4 BEFORE CONCRETE IS POURED, CHECK WITH ALL TRADES TO ENSURE PROPER
PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, ETC. RELATIVE TO 5.0 CONSTRUCTION JOINTS :
WHERE :
THE WORK. 5.1 CONTRUCTION JOINTS NOT INDICATED ON PLANS SHALL BE MADE SO AS
P = DESIGN WIND PRESSURE, KN/m2 TO LEAST IMPAIR THE STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT
4.1.5 WHEN CONCRETE WILL BE EXPOSED TO EXTERNAL SOURCES OF CHLORIDES IN
q = VELOCITY PRESSURE, KN/m 3
SERVICES, SUCH AS DEICING SALTS, BRACKISH WATER, SEAWATER OR SPRAY FROM TO APPROVAL OF THE ENGINEER.
-6 2
= 47.3 x 10 Kz Kzt V Iw THESE SOURCES, CONCRETE MUST BE PROPORTIONED TO SATISFY THE SPECIAL 5.2 UNLESS SHOWN OTHERWISE, SLAB ON GRADE SHALL HAVE CONTROL JOINTS
EXPOSURE REQUIREMENTS OF ACI 318-2005. @ 6.00m MAXIMUM CENTER TO CENTER.
WHERE :
Kz = VELOCITY PRESSURE COEFFICIENT GIVEN IN NSCP TABLE 207.3 4.1.6 ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF 7 CONSECUTIVE DAYS
EXPOSURE B. IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP. 6.0 NOTES ON BEAMS AND GIRDERS :
Kzt = TOPOGRAPHIC FACTOR = 1.0
4.2 REINFORCING BARS : 6.1 UNLESS OTHERWISE NOTED IN PLANS OR SPECIFICATIONS, CAMBER ALL BEAMS AND
V = BASIC WIND SPEED SHOWN IN NSCP FIG. 207-1 = 250kph
GIRDERS AT LEAST 0.006m FOR EVERY 4.50m OF SPAN EXCEPT CANTILEVERS FOR WHICH
I = IMPORTANCE FACTOR = 1.15 4.2.1 UNLESS OTHERWISE SPECIFIED ON PLANS, ALL REINFORCING BARS SHALL BE THE CAMBERS SHALL BE AS NOTED IN THE PLANS OR AS ORDERED BY THE DESIGNERS.
G = GUST EFFECT FACTOR SHOWN = 0.85 DEFORMED WITH A MINIMUM YIELD STRENGTH, fy = 414 MPa (60,000 PSI). BUT IN NO CASE LESS THAN .019m FOR EVERY 3.00m OF FREE SPAN.
FOR DIAMETER 12mm AND BELOW, USE fy = 275 Mpa (40,000 PSI)
Cp = EXTERNAL PRESSURE COEFFICIENT SHOWN IN NSCP FIG. 207-3
STANDARD DETAIL CONNECTION

10mm Ø AS SHOWN 6mm


150 SAWED JOINT
10mm Ø @ 400mm O.C. TOOLED
JOINT WITH SEALANT

SLAB THICKNESS, T

T/5
25mm-75mm

T/3
TYP.
h<600

T/3

T
NOTE:

T/2
250mm Ø

T/3
2-10mmØ TYP.
6t OR 1. REINF. TO BE SAME BAR SIZE AND SPACING AS
MAX. ADJACENT REINF. BARS ON SLABS.
450 MIN

DE
2. FOR CLOSURE SLABS AT OPENINGS AND BLOCKS OUT, 50mm

PR
REBARS TO BE THE SAME SIZE, AND 2/3 THE SPACING

t SION
ES
100
OF BARS AS ADJACENT SLABS. CONSTRUCTION JOINT WEAKENED PLANE JOINT
25mm-75mm TYP. NOTE:
PROVIDE 90° HOOK WHERE 1. CONTROL JOINTS CAN BE EITHER CONSTRUCTION JOINTS OR
t EXCEEDS 50mm WEAKENED PLANE JOINTS.

DEPRESSED SLAB & TYP. PIPE SLEEVE CONTROL JOINTS


1 SLAB EDGE DETAILS 2 OPENING FOR SLABS 3 FOR SLAB-ON GRADE
S-2 SCALE NTS
S-2 SCALE NTS S-2 SCALE NTS

250
150 100 R.C. WALL NOTE:
10mm Ø TIES/
UNLESS OTHERWISE NOTED IN THE PLAN, PROVIDE STIRRUPS
CHB WALL
16mm Ø VERT. BARS FRAMING STIFFENER COLUMNS & STIFFENER BEAMS @ 200mm O.C. L
@ 400mm O.C. NOT MORE THAN 3.0m APART. CL OF COLUMN

100
10mm Ø HOR. BARS
1000 < H < 3500

@ 400mm O.C. L/3 L/3 L/3


H < 1000

10mm Ø HOR. BARS


@ 300mm O.C.
2-10mmØ MAIN BARS

h<3000
16mm Ø VERT. BARS 16mm Ø VERT. BARS
@ 400mm O.C. @ 200mm O.C.
H/2

D
DECK SLAB 300
DECK SLAB 10mm Ø TIES/
STIRRUPS
@ 200mm O.C.

h<3000
R.C. EDGE R.C. EDGE WALL BASE 2D STIRRUPS @ 100mm O.C.

150
BEAM BEAM TOP BARS MAX. SPACING

NOTE:
(UNLESS OTHERWISE BOTTOM BARS
4-12mm Ø MAIN BARS NO SPLICE
CASE 1 CASE 2 NOTED ON PLANS) t<3000 t<3000

TYPICAL DETAIL TYPICAL DETAIL OF TYP. SPLICE DETAILS FOR


4 SECTION OF PARAPET 5 STIFFENER BEAMS & COLUMNS 6 BEAMS FRAMING INTO COLUMN
S-2 SCALE NTS S-2 SCALE NTS S-2 SCALE MTS

LINTEL IN BLOCK WALLS (SAME THICKNESS AS CMU) 12mm THK. COMPRESSIBLE


DOWELS JOINT FILLER W/ SEALANT 12 STIFFENER/
CLEAR SPAN TOTAL MIN. fc' HEIGHT OF LINTEL REINFORCEMENT (TYP.) S-2 BOND BEAM
L (mm) LENGTH Mpa BEAM (mm) STIRRUPS BOT. OF STIFFENER/
mm BOTTOM TOP
LINTEL BEAM BOND BEAM
1200 1800 13.8 200 2-10mm Ø 2-10mm Ø 10mm Ø @ 200
BEAM
1500 2100 13.8 225 2-12mm Ø 2-12mm Ø 10mm Ø @ 200

12mm
1800 2400 13.8 250 2-16mm Ø 2-16mm Ø 10mm Ø @ 200 12mm THK.
COMPRESSIBLE PLASTER
2100 2700 17.2 250 2-16mm Ø 2-16mm Ø 10mm Ø @ 200 JOINT FILLER
2400 3000 17.2 300 2-16mm Ø 2-16mm Ø 10mm Ø @ 200 W/ SEALANT
10mm Ø @ 200 (TYP.) LINTEL BEAM
2700 3300 17.2 300 2-16mm Ø 2-16mm Ø
3000 3800 17.2 350 3-16mm Ø 2-16mm Ø 10mm Ø @ 200 BOT. OF
3300 4100 17.2 400 3-16mm Ø 2-16mm Ø 10mm Ø @ 200 BEAM
200 200
3600 4400 17.2 450 4-16mm Ø 2-16mm Ø 10mm Ø @ 200
13
TOP BARS
S-2
HORIZONTAL
BARS
DOOR
CHB WALL
OPENING
BOT. BARS VERTICAL
LINTEL BEAM

BARS
DEPTH OF

OPENING

100
TYP.
FINISH
CLEAR SPAN 450 FLOOR LINE FFL
1-16mm Ø VERT. BAR
TOTAL LENGTH DOWELS
DOWELS

REINF. CONCRETE LINTEL


7 BEAM IN CHB WALLS 8 TYP. CHB WALL ELEVATION 9 SECTION 10 SECTION
S-2 SCALE MTS S-2 SCALE MTS S-2 SCALE MTS S-2 SCALE MTS
W

SCHEDULE OF FOOTINGS
REINFORCEMENT BARS ``A''
D t L W (TOP BAR ALONG L) FGL
MARK (DEPTH) (THICK.) (LENGTH) (WIDTH) TOP BOTTOM REMARKS
mm mm mm mm

+- 600
BARS ``B''
''A'' ''B'' ''C'' ''D'' NGL
(TOP BAR ALONG W)
F1 700 300 1800 1800 - - 9-20mm Ø 9-20mm Ø ISOLATED FOOTING

L
F2 700 300 2000 2000 - - 9-20mm Ø 9-20mm Ø ISOLATED FOOTING 0.25L1 0.3L1 0.3L2 0.3L2 B BARS ``C'' FTB
TOP BARS
(BOT. BAR ALONG L)

D
F3 700 300 2000 2000 - - 9-20mm Ø 9-20mm Ø ISOLATED FOOTING

500
F4 300 - - ISOLATED FOOTING
BARS ``D''
700 2500 2500 15-20mm Ø 15-20mm Ø
(BOT. BAR ALONG W)

t
WEB BAR 100mm THK.

H
WELL-COMPACTED
GRAVEL BASE BOTTOM BARS

SCHEDULE OF FOOTING TIE BEAMS (FTB) L1 L2 PLAN SECTION FOR THICKNESS, t 500mm
BOT. BARS
REINFORCING BARS ARRANGEMENT ELEVATION SECTION
STIRRUPS 2 DETAIL REFERENCE OF FOOTINGS
MARK SIZES AT SUPPORT AT MID - SPAN AT AT AT SIZE REMARKS NOT TO SCALE
( mm ) EXT. MID
SUPP. SPAN
INT.
SPACING ST-3
TOP BOTTOM TOP BOTTOM SUPP.
6 TYPICAL FOOTING TIE BEAM DETAIL
10mm Ø STIRRUPS 1@ 50mm, NOT TO SCALE
FTB1 250x350 4-20mm Ø 4-20mm Ø 3-20mm Ø 3-20mm Ø 3@100mm, 3@150mm, REST@ ST-3
200mm O.C.
10mm Ø STIRRUPS 1@ 50mm, 100mm THK.
150mm THK. CHB WALL
FTB2 300x450 5-20mm Ø 5-20mm Ø 3-20mm Ø 3-20mm Ø 3@100mm, 5@150mm, REST@ CHB WALL 10mm Ø HOR. BARS
200mm O.C. 10mm Ø HOR. BARS @ EVERY 3RD
@ EVERY 3RD COURSE
COURSE 10mm Ø VERT. BARS
10mm Ø VERT. BARS
@ 400mm O.C.
@ 400mm O.C.
NGL
1 2 3 4 5 6 7 8 9 10 11
10mm Ø BARS SPACED
3300 3980 4100 4100 4100 4100 4100 4100 3980 3000 3-10mm Ø LONG. TO MATCH SLAB
10mm Ø @ BARS REINFORCING BARS
250mm O.C.

600
ALTERNATE FFL
3-10mm Ø LONG.
90° BEND BARS

100 100
C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2

200
D 1
2 2
1
LEAN CONCRETE
BASE 100mm THK
F1 F1
F2 F2 F2 F3 F3 F3 F3
400
WF2 300
COMPACTED
GRAVEL BASE
FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2
5010

3 WALL FOOTING DETAIL


NOT TO SCALE
ST-3
C2 FTB-2 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-2 C2
C
SHAFT

SHAFT
F1 F1
F4 F4 F4 F4 F4 F4 F4 F4 F4
WF1
WF1
FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2
5330

WF1
WF1 150MM (EXTERIOR)
100MM (INTERIOR)
SHAFT

SHAFT
FACE OF WALL

CHB WALL 12mm THK


B 10mm Ø @ 600mm O.C.
PRE-FORMED ELASTOMERIC
JOINT FILLER WITH SEALANT
C2 FTB-2 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-1 C1 FTB-2 C2
VERTICAL BARS

t/3
F1 F1
F4 F4 F4 F4 F4 F4 F4 F4 F4 10mm Ø @ EVERY 3rd LAYER,

t
HORIZONTAL BARS
FTB-2

200
FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2
5010

WF2
REBARS OF SLAB ON FILL
G.F.L. 100mm THK COMPACTED

125
GRAVEL BASE
200 100
A 100mm THK.
C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 FTB-1 C2 N.G.L. COMPACTED
GRAVEL FILL ON
F1 F2 F2 F2 F3 F3 F3 F3 F1
A COMPACTED TYP. SLAB ON
EARTH FILL 5 TYPICAL SLAB ON GRADE DET.
NOT TO SCALE
USE: 125mm THK SLAB ON FILL WITH 10mm Ø BARS FTB ST-3
SPACED @ 250mm O.C. BOTHWAYS

4 WALL ON FOOTING TIE BEAM


1 LOWER GROUND FOUNDATION & FRAMING PLAN ST-3
NOT TO SCALE
SCALE 1:100 M.
ST-3
40
2-Ø16 @ 75 db
SCHEDULE OF SLABS BEAM DIAGONALS AT
1 MID-DEPTH OF 4
REINFORCING BARS 2 "Ø GROOVE SLAB AT EACH (T 0 db
YP
CORNER .)
THICKNESS BAR

(TYP.)
FLOOR

40db
MARK LOCATION BAR DIA. SHORT SPAN LONG SPAN REMARKS 0.60
LEVEL (mm)
END MIDDLE END MIDDLE 1-Ø16 TOP &
BOT. BARS
TOP Ø10 200 200 200 200

0.12
(TYP. ALL AROUND)

0.10
ALL S-1 125 TWO-WAY 38MM CLR.
BOT. Ø12 300 300 300 300
75MM MAX.
10mmØ BAR @ 0.3m O.C
GRID GRID GRID 12mmØ BAR @ 0.3m O.C

40db
S1 S2 EXTEND BARS UP
TO BEAM SUPPORT
S1/3 (FOR ONE-WAY SLAB) S1/3 S2/3 S2/3
S1/4 (FOR TWO-WAY SLAB) S1/4 S2/4 S2/4 NOTE (1) AT
NOTES: 75MM SPACING
5 TYPICAL CANOPY DETAIL
NOT TO SCALE
1. ALL TOP AND BOTTOM SLAB BARS INTERRUPTED BY OPENING SHALL BE REPLACED BY
ST-4
ADDITIONAL REINFORCING EQUAL TO THAT INTERRUPTED. PLACE HALF OF THE
DISCONTINUOUS END CONTINUOUS END ADDITIONAL REINFORCING ON EACH SIDE OF OPENING AND EXTEND SAME LENGTH AS
REQUIRED OR BAR LAP OF INTERRUPTED REINFORCING.
S1/7 S1/5 S2/5 S2/5
2. SEE ARCHITECTURAL & MECHANICAL PLANS FOR SLAB OPENING LOCATION.
2 TYPICAL SLAB DETAIL
NOT TO SCALE 3. OMIT TRIMMER BARS WHERE OPENING IS FRAMED BY BEAMS.
ST-4
4. BOXED OUT OPENINGS, RECESSES AND PIPE SLEEVE CLUSTERS SHALL BE TREATED AS
FRAMED SLAB OPENING.
5. MAXIMUM DIMENSION FOR EACH SIDE OF OPENING SHALL BE 1200MM. OPENINGS
1 2 3 4 5 6 7 8 9 10 11 BEYOND THE SAID DIMENSION ARE SUBJECT TO THE APPROVAL OF THE ENGINEER.
3300 3980 4100 4100 4100 4100 4100 4100 3980 3000

3 TYPICAL SLAB OPENING DETAIL


NOT TO SCALE
ST-4
150 150 150
D G2 G2 G2 G2 G2 G2 G2 G2 UPPER LEVEL UPPER GROUND LEVEL UPPER GROUND LEVEL
5010

G1

G1

G1

G1

G1

G1

G1

G1

G1
S-1 S-1 S-1 S-1 S-1 S-1 S-1 S-1 WF1
BB2 BB2 BB2

G3 G3 G3 G3 G3 G3 G3 G3 G3 G3 Ø12 @ 200 Ø12 @ 200 10mm Ø @ 600mm O.C.


C VERT. BARS VERT. BARS VERTICAL BARS
SHAFT

SHAFT
CHB WALL

VARIES

GREATER THAN H/2


Ø10 @ 300 Ø10 @ 300
5330

HOR. BARS HOR. BARS


STAIRS STAIRS
G2

G1

G1

G1

G1

G1

G1

G1

G1

G1

G2
S-1 S-1 S-1 S-1 S-1 S-1 S-1 S-1

Ø12 @ 200
SHAFT

SHAFT
VERT. BARS
Ø10 @ 300

LESS THAN H/2


HOR. BARS

B
G3 G3 G3 G3 G3 G3 G3 G3 G3 G3

S-1 LOWER GROUND LOWER GROUND LOWER GROUND


FLOOR LEVEL FLOOR LEVEL FLOOR LEVEL
5010

G1

B
G1

G1

G1

G1

G1

G1

G1

G1
S-1 S-1 S-1 S-1 S-1 S-1 S-1 S-1 WF1
Ø100MM PERFORATED Ø100MM PERFORATED Ø100MM PERFORATED
FTB PIPE TAP TO FTB PIPE TAP TO FTB PIPE TAP TO
NEAREST DRAIN NEAREST DRAIN NEAREST DRAIN

G2 G2 G2 G2 G2 G2 G2
A VERIFY VERIFY VERIFY
G2
B S-1 S-1 S-1 S-1 S-1 S-1 S-1

B B B B B B B
4 TYPICAL RETAINING WALL DETAIL
1 UPPER GROUND FRAMING PLAN NOT TO SCALE
SCALE 1:100 M. ST-4
ST-4
SCHEDULE OF COLUMNS
COL. MARK COL. MARK
C1 C2 C1 C2
FLOOR LEVEL FLOOR LEVEL
TOP OF BEAM
FOUNDATION THIRD FLOOR
CANTILEVER BEAM CANTILEVER BEAM
TO
TO L 200
ROOF BEAM 2-16mmØ
SECOND FLOOR

300
SIZE (mm) 400X400 350X350 SIZE (mm) 300X300 300X300
VERT. REINF. 4-25mm Ø & 4-20mmØ 8-20mm Ø VERT. REINF. 8-16mm Ø 8-16mm Ø 2-16mmØ
TIES 1@50mm,2@100mm,3@150mm, rest @ 200mm TIES 1@50mm,2@100mm, 3@150mm, rest @ 200mm
10mm Ø STIRRUPS 1@ 50mm,

ELEVATION
3@100mm, 4@150mm,REST@
200mm O.C. SECTION VERT. BARS
SECOND FLOOR

TO 3 TYPICAL BEAM DETAIL (B)

H2
NOT TO SCALE
THIRD FLOOR ST-5

SIZE (mm) 350X350 300X300


VERT. REINF. 8-20mm Ø 8-20mm Ø
TIES 1@50mm,2@100mm,3@150mm, rest @ 200mm

TOP OF BEAM
1 2 3 4 5 6 7 8 9 10 11
3300 3980 4100 4100 4100 4100 4100 4100 3980 3000

H1/4
D G2 G2 G2 G2 G2 G2 G2 G2

SPLICE
5010

G1

G1

G1

G1

G1

G1

G1

G1

G1
S-1 S-1 S-1 S-1 S-1 S-1 S-1 S-1

LAP
G3 G3 G3 G3 G3 G3 G3 G3 G3 G3

SPLICE
H1
C

H1/2

LAP
SHAFT

SHAFT
TIES
5330

STAIRS STAIRS
G2

G1

G1

G1

G1

G1

G1

G1

G1

G1

G2
S-1 S-1 S-1 S-1 S-1 S-1 S-1 S-1
SHAFT

SHAFT

H1/4
B
G3 G3 G3 G3 G3 G3 G3 G3 G3 G3
5010

G1

G1

G1

G1

G1

G1

G1

G1

G1
S-1 S-1 S-1 S-1 S-1 S-1 S-1 S-1

G2 G2 G2 G2 G2 G2 G2 G2
A

100mm THK COMPACTED


1 TYPICAL SECOND & THIRD FLOOR FRAMING PLAN
SCALE 1:100 M.
2 TYPICAL COLUMN DETAIL GRAVEL BASE
NOT TO SCALE
ST-5 ST-5
L1 L2 B
0.25L1 0.3L1 0.3L2 TOP BARS SEE TYP. BEAM (B) DEATILS SEE SCHEDULE OF BEAMS AND
GIRDERS
L1 L2 L3
CANTILEVER BEAM
L 2 /3 L 2 /3 L 3 /3 L 3 /3
LAP SPLICES ARE ALLOWED LAP SPLICES ARE ALLOWED
1200 2D ONLY IN THIS POINT 2D 2D ONLY IN THIS POINT 2D
BUNDLED BARS ADDITIONAL TOP BARS ADDITIONAL TOP BARS CONT. TOP BARS

300

h
600
WEB BARS

600
0.125L1 0.15L2 0.15L2 SEE SECTION OF
CANTILEVER BEAM L 2 /5
ADDITIONAL BOT. BARS
2 - 12mm Ø STIFF. BARS L 2 /5 L 3 /5 L 3 /5
CONTINUOUS BOT. BARS b
TOP BARS STIFF. BARS
BOT. BARS
ELEVATION SECTION B

3-25mmØ MAIN BARS

H
3-16mmØ MAIN BARS

SECTION (CANTILEVER BEAM)


2 TYPICAL BEAM DETAIL 3 TYPICAL BEAM DETAIL WITH CUT-OFF BARS
NOT TO SCALE NOT TO SCALE
ST-6 ST-6

1 2 3 4 5 6 7 8 9 10 11
3300 3980 4100 4100 4100 4100 4100 4100 3980 3000
SCHEDULE OF BEAMS AND GIRDERS
REINFORCING BARS ARRANGEMENT
STIRRUPS
MARK SIZES AT SUPPORT AT MID - SPAN AT AT AT SIZE REMARKS
D ( mm ) EXT. MID INT.
SUPP. SPAN SPACING
RG1 RG1 RG1 RG1 R.C. GUTTER RG1 RG1 RG1 RG1 TOP BOTTOM TOP BOTTOM SUPP.

RB1 RB1 RB1 RB1 RB1 RB1 RB1 RB1 GROUND FLOOR
10mm Ø STIRRUPS 1@ 50mm,
G1 350X450 5-25mm Ø 3-25mm Ø 3-25mm Ø 3-25mm Ø 3@100mm, 4@150mm,REST@
RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1
5010

200mm O.C.

10mm Ø STIRRUPS 1@ 50mm,


G2 300X400 4-20mm Ø 2-20mm Ø 2-20mm Ø 3-20mm Ø 3@100mm, 4@150mm,REST@
200mm O.C.

10mm Ø STIRRUPS 1@ 50mm,


RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 G3 5-20mm Ø 3-20mm Ø 3-20mm Ø
350X450 4-20mm Ø 3@100mm, 4@150mm,REST@
C 200mm O.C.
SHAFT

SHAFT
SECOND FLOOR
10mm Ø STIRRUPS 1@ 50mm,
G1 350X450 5-25mm Ø 3-25mm Ø 3-25mm Ø 3-25mm Ø 3@100mm, 4@150mm,REST@
200mm O.C.
RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1
5330

10mm Ø STIRRUPS 1@ 50mm,


G2 300X400 4-20mm Ø 2-20mm Ø 2-20mm Ø 3-20mm Ø 3@100mm, 4@150mm,REST@
200mm O.C.

10mm Ø STIRRUPS 1@ 50mm,


SHAFT

SHAFT
G3 350X450 5-20mm Ø 3-20mm Ø 3-20mm Ø 4-20mm Ø 3@100mm, 4@150mm,REST@
200mm O.C.

B THIRD FLOOR
RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 RG1 10mm Ø STIRRUPS 1@ 50mm,
G1 300X400 6-20mm Ø 3-20mm Ø 3-20mm Ø 4-20mm Ø 3@100mm, 4@150mm,REST@
200mm O.C.

10mm Ø STIRRUPS 1@ 50mm,


RG1

G2 300X400 4-16mm Ø 3-16mm Ø 2-16mm Ø 3-16mm Ø 3@100mm, 4@150mm,REST@


5010

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1
200mm O.C.

10mm Ø STIRRUPS 1@ 50mm,


G3 300X400 3-20mm Ø 2-20mm Ø 2-20mm Ø 3-20mm Ø 3@100mm, 4@150mm,REST@
RB1 RB1 RB1 RB1 RB1 RB1 RB1 RB1 200mm O.C.

RG1 RG1 RG1 RG1 R.C. GUTTER RG1 RG1 RG1 RG1 ROOF BEAM LEVEL
A RG1 3-16mm Ø 2-16mm Ø 2-16mm Ø
10mm Ø STIRRUPS 1@ 50mm,
250X300 3-16mm Ø 3@100mm, 4@150mm,REST@
200mm O.C.

10mm Ø STIRRUPS 1@ 50mm,


RB1 250X300 2-16mm Ø 2-16mm Ø 2-16mm Ø 3-16mm Ø 3@100mm, 4@150mm,REST@
200mm O.C.

1 ROOF BEAM FRAMING PLAN


SCALE 1:100 M.
ST-6
2000

b
a a a a

a a a
STRUT1 STRUT1 a
300

TOP CHORD : 2L 50X50X6MM


BP1 BOT CHORD : 2L 50X50X6MM a : 2L 50X50X3MM BP1
WEB MEMB : L 50X50X3MM b : 2L 50X50X6MM 1133 1133 1133 1133 1133 1133 1133 1133
6800 6800

2 TRUSS 1 DETAIL VERIFY


NOT TO SCALE
ST-7

10
1 2 3 4 5 6 7 8 9 10 11

0
VERIFY
0
45 Ø10 @ 400 E.W.
3300 3980 4100 4100 4100 4100 4100 4100 3980 3000
(UNLESS NOTED
OTHERWISE)
12mmØ ROUND BAR CROSS
BRACING W/ 12mm TURN BUCKLE

D R.C. GUTTER
COMPACTED SELECT
BORROW SUBBASE

300
RB1 RB1
2-Ø10 CONT. W/ Ø10 TRANSV.

55
BARS @ 400 O.C. MAX.
5010

60cm X 60cm MANHOLE WITH 250


200mm HEIGHT CONCRETE UPSTAND
3 RAMP ON-FILL DETAIL
6800

NOT TO SCALE
RG1 ST-7
C
CONCRETE HOLLOW BLOCKS 6'' THK
WITH PLASTER FINISH
TRUSS 1

TRUSS 1

TRUSS 1

TRUSS 1

TRUSS 1
TRUSS 1

TRUSS 1

TRUSS 1

TRUSS 1

12mmØ VERTICAL BARS SPACE @ 300mm O.C.

13600
5330

S -1 S -1
10mmØ HORIZONTAL BARS @ EVERY 3RD LAYER

2000
B 680 100 150
RG1
6800
5010

0
10
450

400
RB1 RB1

R.C. GUTTER

150
A

300
RG1 10mmØ REINF. BARS RB1
SPACE @ 300mm O.C.
USE LC 90X45X15X3.0MM THICK
PURLINS SPACED @ 500MM O.C. 12mmØ REINF. BARS
SPACE @ 300mm O.C. 250
WITH 10MMØ SAG RODS

1 ROOF FRAMING PLAN 4 TYP. CON. GUTTER DETAILS


SCALE 1:100 M. NOT TO SCALE
ST-7 ST-7
RIDGE LINE
GUSSET PLATE MEMBER SIZE OF FILLET
THICKNESS (mm) THICKNESS (mm) WELD, t (mm) 150 150 2-12mm Ø x40 LONG PURLIN
SAG ROD W/STD BOLTS W/ STD.NUTS
3.O 3.O NUTS & WASHER RIDGE PURLIN & WASHERS (EACH SIDE) 2-12mm Ø x40 LONG
6 BOLTS W/ STD.NUTS
5.0 3.0
ROOF PURLINS 4 6 THK STEEL & WASHERS (EACH SIDE)
6.O 4.5 - BENT PLATE W/ 6
10 6 THK STEEL
8.O 6.O SAG ROD THK STIFF. PLATE
SAGROD 80 BENT PLATE W/ 6 THK
WP LINE
W/ STD NUTS STIFF. PLATE

70 50
NOTE: & WASHER t

30
1. GUSSET PLATE DIMENSION (WHERE REQ'D.) SHALL BE t

50
DICTATED BY THE MINIMUM REQUIRED

30
LENGTH OF WELD.

70
2. COLUMN JOINT GUSSET AND CONTINUITY PLATES SHALL TOP CHORD
HAVE 100% ULTRASONIC INSPECTION FOR DELAMINATION
OF TRUSS 2 PURLIN
50
BEFORE AND AFTER WELDING. - 60 TOP CHORD OF TRUSS TOP CHORD OF TRUSS
GUSSET PLATE
PURLIN
(MIN.)

(MIN.)
90

120

FILLET WELD
TYPICAL SAGROD TYPICAL PURLIN
WEB MEMBER
1 CONNECTION DETAIL 2 SECTION 3 CONNECTION DETAIL 4 SECTION
S- SCALE NTS S- SCALE NTS S- SCALE NTS S- SCALE NTS

1 SCHEDULE OF WELDS
S-12 SCALE NTS
TOP CHORD WEB MEMBERS
TOP CHORD
WEB
GUSSET GUSSET PLATE MEMBERS
TOP CHORD WEB MEMBERS
PLATE
WP
WP
GUSSET PLATE
TYP WP GUSSET
t TYP PLATE
t TYP
TYP t TYP
t t t
t t PER REQ'D t
GUSSET PLATE LENGTH WP GUSSET PLATE
t WP
WEB MEMBERS
WEB MEMBER BOTTOM WP
PER TYP
REQ'D LENGTH t t PER REQUIRED CHORD BOTTOM
t LENGTH CHORD
WEB MEMBERS PER REQ'D.
LENGTH

5 DETAIL 6 DETAIL 7 DETAIL 8 DETAIL 9 DETAIL 10 DETAIL


S- SCALE NTS S- SCALE NTS S- SCALE NTS S- SCALE NTS S- SCALE NTS S- SCALE NTS

GUSSET PLATE
PER REQUIRED
WEB MEMBERS LENGTH
TOP CHORD TYP TOP CHORD
WEB MEMBER
t
GUSSET PLATE WP
WP t

TYP GUSSET PLATE TYP


TYP t
t TYP
t t
t L50x50x5

75
20
t GUSSET PLATE

t
WP
BOTTOM CHORD
50x100x6 THK. 75
PER REQ'D. WP WEB MEMBERS STEEL PLATE
BOTTOM PER REQ'D.
LENGTH
CHORD LENGTH
WEB MEMBERS

11 DETAIL 12 DETAIL 13 DETAIL 14 DETAIL 15 ANGULAR BUCKLE DETAIL


S- SCALE NTS S- SCALE NTS S- SCALE NTS S- SCALE NTS S- SCALE NTS

1 TRUSS CONNECTION DETAIL


NOT TO SCALE
ST-8
Ø12 @ 250
TOP & BOT BARS

Ø16 @ 125

Ø16 @ 125

MAIN ENTRANCE
PORCH LVL
GRADIENT =1:12

± 456
Ø10 NOSING BAR
450

100
Ø10 @ 300 Ø12 @ 250 SIDEWALK LVL
Ø16 @ 125
Ø10 @ 400 E.W.
Ø16 @ 125 Ø16 @ 125 (UNLESS NOTED

300
TOP BAR

0
15
3-Ø16 OTHERWISE)
COMPACTED
LANDING

150
SELECT BORROW
LEVEL 2-Ø10 CONT. W/ SUBBASE
L/4 Ø10 TRANSV. BARS
@ 400 O.C. MAX.

400
Ø10 STIRRUPS,

50
SPACED 1@50,
4@100, REST
@ 200 TO CL
2 SECTION
DETAIL SECTION OF PWD RAMP
NOT TO SCALE
3-Ø16
Ø16 @ 125 ST-9
175

250
Ø16 @ 150
SEE ARCH DWG.
MAIN/SERVICE/ REAR
Ø12 @ 250
VERIFY STEPS
300 ENTRANCE LVL
TOP & BOT. BARS
Ø10 NOSING BARS W/ Ø10
3-Ø16
CHAIR BARS @ 450 O.C. (TYP.)

150
Ø10 BAR CHAIRS
@ 450 (BOTH ENDS)
LANDING

SEE ARCH DWG.


(TYP. AT ALL STEPS)

15
VERIFY RISER
LEVEL

0
0
Ø16 @ 125 45

400
Ø10 @ 400 E.W.
(UNLESS NOTED
OTHERWISE)
Ø10 BAR CHAIRS L/4
3-Ø16
@ 450 (BOTH ENDS)
(TYP. AT ALL STEPS) Ø10 STIRRUPS,
15

COMPACTED SELECT
0

SPACED 1@50,
Ø10 NOSING BAR 4@100, REST 250
(TYP. AT ALL STEPS)
@ 200 TO CL
BORROW SUBBASE

300
2-Ø10 CONT. W/ Ø10 TRANSV.

55
L
Ø10 @ 300 BARS @ 400 O.C. MAX.
Ø16 @ 150

250
FFL L/4

NGL
TYPICAL3 STAIR ON GRADE DETAIL
300

Ø16 @ 150
VERT. BARS E.F. DETAIL OF STAIR ON-FILL
200 NOT TO SCALE
ST-9
3-Ø10 LONG.
250

BARS

Ø10 @ 300
TRANS BARS
600
100mm THK. WELL-
COMPACTED GRAVEL
BASE 1 DETAIL OF FIRE ESCAPE STAIR
NOT TO SCALE
ST-9