SHT. NO. REV NO DRAWING NO. INDEX PLANT NO. CRM ORDER NO.

1. THE CONTRACTOR SHALL CHECK AND VERIFY THE 4. PROVIDE AND INSTALL NEW FLOOR FLUSH MOUNTED 18.THE CONTRACTOR SHALL INFORM AND COORDINATE
EXISTING ELECTRICAL INSTALLATION BEFORE THE RAISED FLOOR OUTLET BOX WITH THREE WITH THE INSTALLER OF WALL PANEL FOR THE SIZE
START OF THE CONSTRUCTION. COMPARTMENT OR APPROVED EQUAL. OF CONDUITS TO BE CONCEALED ON WALL AND THE
CUT OUT FOR THE NECESSARY BOX NEEDED FOR
2. TERMINATION AT BOTH ENDS, PROVISION, 5. PROVIDE AND INSTALL NEW WALL FLUSH MOUNTED OUTLETS.
INSTALLATION AND PULLING OF DATA & DUPLEX POWER OUTLET 13 AMP., 230 VOLTS, RATED
COMMUNICATION OUTLETS AND CABLES SHALL BE 19.BORE HOLE ON THE CONCRETE FLOOR SLAB TO
SASO 2203 (BS1363) AS SHOWN ON THE LAYOUT. USE
DONE BY CERTIFIED/APPROVED SAUDI ARAMCO ACCOMODATE 3/4" DIA. RSC CONDUIT AND
3/4" DIA. EMT CONDUIT CONCEALED ON WALL,
CONTRACTOR UNDER THE SUPERVISION OF CHIP OFF/CUT OFFCONCRETE FLOOR SCREED TO
IT/COMMUNICATION DEPARTMENT. RIGIDLY SUPPORTED AND ROUTED ABOVE CEILING
RPB-12
EMBED THE RAISED FLOOR OUTLET BOX WITH THREE
AND FEED TO DESIGNATED ELECTRICAL PANEL BOARD
COMPARTMENT, 1" AND 3/4" DIA. RSC CONDUIT.
3. TRANSFER EXISTING LOADS OF CIRCUITS 4 TO 22 AND AND CIRCUIT.
RPB-C1 MA-163 SECURE NECCESSARY PERMIT BEFORE START OF
21 TO 19.
6. PROVIDE AND INSTALL NEW FLOOR DUPLEX POWER WORK.
OUTLET 13 AMP., 230 VOLTS, RATED SASO 2203
(BS1363) ON NEW HOLE AS SHOWN ON THE LAYOUT
MA-161 MA-162 INCLUDING ALL ACCESSORIES AND FEED TO LEGEND:
STAIR-1B DN TO DESIGNATED ELECTRICAL PANEL BOARD AND CIRCUIT.
C O R R I D O R EXISTING ELECTRICAL PANEL BOARD
BSMT.
7. PROVIDE AND INSTALL NEW FLOOR DUPLEX POWER
PROPOSED WALL FLUSH MOUNTED
OUTLET 13 AMP., 230 VOLTS, RATED SASO 2203 220 VOLTS (BS TYPE) DUPLEX POWER
(BS1363) ON FLOOR FLUSH MOUNTED RAISED FLOOR OUTLET
2W W3 OUTLET BOX WITH THREE COMPARTMENT AS SHOWN
RPB-12
MA-175 ON THE LAYOUT INCLUDING ALL ACCESSORIES AND FEED TO PROPOSED FLOOR MOUNTED 220 VOLTS
1, 3 (BS TYPE) DUPLEX POWER, TEL./DATA
DESIGNATED ELECTRICAL PANEL BOARD AND CIRCUIT. N
OUTLET ON NEW HOLE
MOUNTING HEIGHT
8. PROVIDE AND INSTALL NEW WALL FLUSH MOUNTED N - DENOTES NO. OF TEL./DATA OUTLET
SHALL BE 700MM AFFL
MGR SEC. FOURPLEX AND DUPLEX TELEPHONE/DATA OUTLET AS
PROPOSED FLOOR MOUNTED 220 VOLTS
MA-174 RPB-12 SHOWN ON THE LAYOUT. FOR EVERY DUPLEX/FOURPLEX
(BS TYPE) DUPLEX POWER AND FOURPLEX
2, 4 OUTLET SHALL USE 1" DIA. EMT CONDUIT CONCEALED ON TEL./DATA OUTLET ON FLOOR FLUSH
RPB-24 4
MANAGER WALL, RIGIDLY SUPPORTED AND ROUTED ABOVE CEILING MOUNTED RAISED FLOOR OUTLET BOX
6, 8
3
2W MA-173 AND FEED TO DATA ROOM. WITH THREE COMPARTMENT
B RPB-12 W2 9. PROVIDE AND INSTALL NEW FLOOR FOURPLEX AND PROPOSED WALL FLUSH MOUNTED
MOUNTING HEIGHT 2, 4 DUPLEX TELEPHONE/DATA OUTLET ON NEW HOLE AND WN TEL./DATA OUTLET
W2 W2 W2
SHALL BE 700MM AFFL FEED TO DATA ROOM. N - DENOTES NO. OF OUTLET
2
FOCUSBOOTH RPB-12
10.PROVIDE AND INSTALL NEW FLOOR FOURPLEX CIRCUIT HOMERUN FOR 220 VOLTS
1, 3
GREENWALL TELEPHONE/DATA OUTLETS ON FLOOR FLUSH MOUNTED
2W C B A RAISED FLOOROUTLET BOX WITH THREE COMPARTMENT
MA-172 C-1
C-4 AS SHOWN ON THE LAYOUT INCLUDING ALL ACCESSORIES
C-2 AND FEED TO DATA ROOM. EXISTING FLOOR POWER AND
MOUNTING HEIGHT B A TELECOMMUNICATION GRID
SHALL BE 700MM AFFL 11.PROVIDE AND INSTALL NEW BRANCH CIRCUIT BREAKER
RPB-12 RPB-12 RATED 20 AMPS, 240 VAC, 60 HZ, 2 POLE WITH GROUND
21, 23 21, 23 FAULT CIRCUIT INTERRUPTER TO REPLACE THE EXISTING
BRANCH CIRCUIT BREAKER FOR CIRCUITS (1, 3), (2, 4) AND
2W 2
(21, 23) IN ELECTRICAL PANEL BOARD RPB-12 LOCATED IN
MA-171 4 4 ELECTRICAL CLOSET MA-163.
0 0.5 1 2 3 4 5
COLLABORATI
ONBOOTH
12.PROVIDE AND INSTALL NEW 24 PORTS BOARD CARD
MOUNTING HEIGHT
AS REQUIRED (CARD PART NUMBER HP J8702A OR GRAPHIC SCALE METERS
SHALL BE 700MM AFFL
APPROVED EQUAL) AT DATA ROOM TO BE CONNECTED
D C TO THE SAME EXISTING UNIT. TERMINATION AND
INSTALLATION IN THE COMMUNICATION ROOM INCLUDING
C-3
TESTING AND COMMISSIONING SHALL BE DONE BY
B A CERTIFIED/APPROVED SAUDI ARAMCO CONTRACTOR
WATERWALL RPB-24
RPB-12 UNDER THE SUPERVISION OF IT/COMMUNICATION
2, 4
MA-170 1, 3 DEPARTMENT.
REV.
COFFEESTATI
ON
2W 13.PROVIDE AND INSTALL NEW 3/4" DIA. EMT/RSC
W2 NO DATE DESCRIPTION CH'K'D CERT. APP'D
CONDUIT, LIQUIDTIGHT FLEXIBLE CONDUIT FOR THE
POWER OUTLET TO BE CONNECTED IN ELECTRICAL DESIGN CERTIFICATION

PANEL BOARD RPB-24 AT ELECTRICAL ROOM MA-248


BERLIN 1 : 100 M.
14.PROVIDE EXTENSION CABLE FOR POWER WITH POWER DESIGNED BY SCALE

STRIPS (BS 1363 TYPE). AMIR IQBAL


CHECKED BY

15.PROVIDE EXTENDED TEL. AND DATA PATCH CABLE UP APR. 2022 APR. 2022
DATE STARTED DATE COMPLETED
MOUNTING HEIGHT TO THE EQUIPMENT TERMINAL.
SHALL BE 800MM AFFL
16.OPEN POWER GRID WITHOUT OUTLET SHALL BE
CAPPED OR PATCHED WITH CEMENT.

17.MOUNTING HEIGHT FOR THE WALL POWER, TEL./DATA SAUDI ARABIAN OIL COMPANY
OUTLET SHALL BE 300 MM AFFL ULESS OTHERWISE THIS DRAWING IS NOT TO BE USED FOR
CERTIFIED BY:
CONSTRUCTION OR FOR ORDERING
SPECIFIED. MATERIAL UNTIL CERTIFIED AND DATED
DATE

1 PROPOSED POWER LAYOUT PROPOSED POWER LAYOUT

04/02 MODIFY EXISTING OFFICE SPACE


SCALE: 1 : 100 M.
RM# 170, FLR 01, MAIN ADMIN
DHAHRAN SAUDI ARABIA
CRM ORDER NO. PLANT NO. INDEX DRAWING NO. SHT. NO. REV NO

CRM# 4044013439 P 04 02
CADD