* THESE ARE GENERAL NOTES TO BE FOLLOWED IN
SYMBOL IN SYMBOL SYMBOL IN SYMBOL CONJECTION WITH SPECIFIC ELECTRICAL DRAWINGS
ELEVATION IN PLAN DESCRIPTION ELEVATION IN PLAN DESCRIPTION & INSTRUCTION ISSUED FOR PROJECT.
ELECTRICAL DISTRIBUTION * ALL WIRING SHALL BE CONCEALED IN GOOD QUALITY
TRACK LIGHT P.V.C. CONDUITS (BETA / POPULAR OR EQUIVALENT)
BOARD
IN WALLS & CEILING OR AS REQUIRED.
TELEPHONE DISTRIBUTION 4FT
TEL. BD. TUBE LIGHT * THE MINIMUM SIZE OF P.V.C. CONDUIT SHALL NOT BE LESS
BOARD
THEN 3/4" DIA. IN WALL & 1" DIA. IN FLOOR & CEILING.
2FT * LIGHT CIRCUIT WIRING SHALL BE 7/.029 AND LIGHT POINT
TEL.EXCH. TELEPHONE EXCHANGE TUBE LIGHT
WIRING SHALL BE WITH 3/.036 P.V.C. SINGLE CORE.
TV.
TV. / CABLE DISTRIBUTION FLOOR MOUNTED * ALL POWER PLUGS WIRING SHALL HAVE INDEPENDENT
BOARD FLOOD LIGHT CIRCUIT FROM POWER DISTRIBUTION BOARD.
3P-15 AMP POWER PLUG * ALL POWER PLUGS WIRING SHALL BE WITH 7/.034 OR
(0'-6" A.F.FL.)
EARTH SET COMPLETE
AS REQUIRED P.V.C. SINGLE CORE WIRE.
3P-5 AMP LIGHT PLUG * SUPERIOR QUALITY CIRCUIT BREAKERS,
GARDEN W.P. SPOT LIGHT
(0'-6" A.F.FL.)
(TERASAKI / AEG / LEGRAND) WITH EARTH PROTECTION
SWITCH / SWITCH PLATE PREMIUM QUALITY MAIN SWITCH, INDICATORS, CHANGE
GATE LIGHT OVER ETC. WILL BE USED IN THE DISTRIBUTION BOARD.
(3'-6" A.F.FL.)
* NO HORIZONTAL CHASING IN WALL WILL BE DONE.
TWO WAY SWITCH
STEP LIGHT / FOOT LIGHT
(3'-6" A.F.FL.) * NO STRUCTURE ELEMENT LIKE SLAB, COL,
BEAM WILL BE CHASED.
TEL. TELEPHONE/INTERCOM POINT GEN. GENERATOR
(0'-6" A.F.FL.) * ONLY GRINDER DISK CUTTER WILL BE USED
FOR CHASING IN WALL.
1'x4' TUBE LIGHT FIXTURE
TV. TV. OUTLET POINT * 1/44 P.V.C. SINGLE CORE COPPER EARTH WIRE SHALL
2x40 WATTS
RUN ALONG POWER PLUG WIRING 15 AMP, & LIGHT PLUG
EXTERNAL WALL 2'x2' TUBE LIGHT FIXTURE WIRING 5 AMP./ ALL POINTS.
BRACKET LIGHT (W.P)
6'-6" (A.F.FL.)
4x20 WATTS
* ALL CONDUIT, MAIN / SUB DISTRIBUTION BOARD, MAIN
WALL BRACKET LIGHT LED WATER PROOF SWITCH, BACK BOXES AND ENERGY METER WILL HAVE
6'-6" (A.F.FL.) FLOOR LIGHT FULL ELECTRIC CONTINUITY & WILL BE BOUND TO EARTH.
* THE MOUNTING HEIGHT ABOVE FINISHED FLOOR LEVEL
BUZZER POINT C COMPUTER POINT FOR VARIOUS ELECTRIC POINTS, SHALL BE AS FOLLOWS,
OR AS OTHER WISE INDICATED ON DRAWING.
FANCY DOOR BELL CCTV CAMERA
* ALL DIMENSIONS FOR MOUNTING OF ELECTRIC POINT ARE
TO BE TAKEN FROM FINISHED FLOOR LEVEL TO THE
CAT SIX CABLE BOTTOM OF POINT.
CEILING FAN C-6
FOR NETWORKING
* SWITCH PLATE WILL HAVE CLEAR DISTANCE
SD.
SMOKE DETECTOR FACADE LIGHT OF 1" BETWEEN PLATE.
CEILING MOUNTED
* ALL PHASE / LIVE WIRES WILL BE RED IN COLOR
SPK. SPK.
SPEAKER LAWN LIGHT ALL NEUTRAL WIRES WILL BE BLACK IN COLOR
CEILING MOUNTED ALL EARTH WIRES WILL BE GREEN IN COLOR
* UPS WIRES WILL BE YELLOW IN COLOR
BELL PUSH SWITCH UPS UPS NEUTRAL WIRES WILL BE BLUE IN COLOR
UPS WILL HAVE INDEPENDED NEUTRAL WIRES ALL ALONG.
WALL BRACKET FAN
(AT 8'-0" A.F.FL.)
GENERATOR PAD
HANGING LIGHT = 8'-0"
SUB TITLE.
GENERAL NOTES. ARCHITECT. MAZHAR MUNIR PROJECT NO.
THE INFORMATION CONTAINED IN THIS DRAWING IS PROPRIETARY TO
MAZHAR MUNIR ARCHITECTURAL FIRM. IT IS SUBMITTED IN
DRAWN BY. JUNAID TARIQ GENERAL NOTES:
CLIENT.
CONFIDENCE AND IS NOT TO BE REPRODUCED, TRANSMITTED
DISCLOSED OR USED OTHERWISE IN WHOLE OR IN PART, OTHER
THAN WHAT IS HAS BE ORIGINAL FURNISHED FOR, WITHOUT THE THE
DATE ISSUED. 04 / 07 / 2023
REVISED DRAWING NO.
MR. UMER WAHID CHEENA Architectural Firm
PROJECT TITLE.
SCALE. N.T.S.
WRITTEN AUTHORIZATION OF MAZHAR MUNIR ARCHITECTURAL FIRM.
Address: mobile #:
NOTE:- DRAWING NO. PROPOSED DESIGN OF RESIDENCE 49 Fairway 0315 4345307
THE CONTRACTORS SHALL VERIFY ALL THE DIMENSIONS AT SITE.
AND REPORT ANY ERRORS OR OMISSIONS TO THE ARCHITECT. DO
· ALL BATHS ROOM & KITCHEN EXHAUST FAN
AT PLOT No.418 SECTOR M, PHASE VI DHA Raya ph.VI 0310 8555551
NOT SCALE THE DRAWINGS. THE DRAWING SHALL NOT BE USED ·
DUCT AS PLACED IN DRAWING
ALL BATH ROOM 1" DOWN FROM F.F.LEV. E-00 Email address :
FOR CONSTRUCTION UNTIL ISSUED FOR CONTRACTION. · ALL TERRACES 2" DOWN FROM F.F.LEV. D.H.A LAHORE CANTT. mdtworks@gmail.com
· SUNKEN AREA STEEL STEPS & BRIDGE
SUMP
02 2' X 2' X 2'
01
UP
VANITY
TOILET
BUZZER FROM
MAIN GATE
WARDROBE
SD. D/BATH
S.QTR 2
KITCHEN
W.C. P.T
BENCH
c-6
S.QTR 1 SD.
MEDIA WALL
BED ROOM
W.P.FLOOR
A.C
LIGHT
SD.
SPK.
SD.
OVEN
LOBBY
VANITY
KITCHEN
SHOWER
D/BATH
WARDROBE
c-6
SUMP
MEDIA WALL / FIRE PLACE BELL PUSH
2' X 2' X 2' W.C. P.T
INTERCOM
BENCH
LOUNGE
c-6
W.P.FLOOR
LIGHT
MEDIA WALL
SPK.
BED ROOM
CONSOLE
SPK. SD.
LIGHT
A.C
SD.
SUNKEN 2'-0" WIDE
STEP UP
17 18 19 20 21 SD.
PDR 16
15
VOID SPK.
VANITY 14 ABOVE UP
13 SPK.
CEILING 12 01 COLLECTION TANK
FAN STEPS 4'-0"X4'-0"X5'-0"
11 10 09 08 07 06 05 04 03 02 LIGHT
STEPS
P.T
W.C. LIGHT
SD.
STUDY
A.C
SPK.
CEILING
FAN
STORE
BASEMENT PLAN
SUB TITLE.
GENERAL NOTES. ARCHITECT. MAZHAR MUNIR PROJECT NO.
THE INFORMATION CONTAINED IN THIS DRAWING IS PROPRIETARY TO
MAZHAR MUNIR ARCHITECTURAL FIRM. IT IS SUBMITTED IN
DRAWN BY. JUNAID TARIQ BASEMENT ELECTRICAL PLAN
CLIENT.
CONFIDENCE AND IS NOT TO BE REPRODUCED, TRANSMITTED
DISCLOSED OR USED OTHERWISE IN WHOLE OR IN PART, OTHER
THAN WHAT IS HAS BE ORIGINAL FURNISHED FOR, WITHOUT THE THE
DATE ISSUED. 04 / 07 / 2023
REVISED DRAWING NO.
MR. UMER WAHID CHEENA Architectural Firm
PROJECT TITLE.
SCALE. N.T.S.
WRITTEN AUTHORIZATION OF MAZHAR MUNIR ARCHITECTURAL FIRM.
Address: mobile #:
NOTE:- DRAWING NO. PROPOSED DESIGN OF RESIDENCE 49 Fairway 0315 4345307
THE CONTRACTORS SHALL VERIFY ALL THE DIMENSIONS AT SITE.
AND REPORT ANY ERRORS OR OMISSIONS TO THE ARCHITECT. DO
· ALL BATHS ROOM & KITCHEN EXHAUST FAN
AT PLOT No.418 SECTOR M, PHASE VI DHA Raya ph.VI 0310 8555551
NOT SCALE THE DRAWINGS. THE DRAWING SHALL NOT BE USED ·
DUCT AS PLACED IN DRAWING
ALL BATH ROOM 1" DOWN FROM F.F.LEV. E-00 Email address :
FOR CONSTRUCTION UNTIL ISSUED FOR CONTRACTION. · ALL TERRACES 2" DOWN FROM F.F.LEV. D.H.A LAHORE CANTT. mdtworks@gmail.com
· SUNKEN AREA STEEL STEPS & BRIDGE
DN.
CEILING A.C
SHOWER
EX.FAN TUB
SHOWER
CEILING
EX.FAN
WARDROBE
CAMERA CAMERA
VANITY
POINT POINT
MEDIA WALL
D/BATH P.T M.BATH
CEILING CEILING
W.C. W.C.
FAN FAN
P.T
VANITY
MEDIA WALL
WARDROBE
SPK.
SPK.
BED ROOM
SUNKEN
A.C
WARDROBE
CONSOLE
LOBBY
FIRE PLACE
c-6
MEDIA WALL BELL PUSH
OVEN FRIDGE
CONSOLE
INTERCOM
CEILING FAN
UP
01 02 03
H
S.KIT.
LOUNGE
SPK. SD.
D/W
H
SUNKEN 2'-0" WIDE
A.C
CEILING
FAN
M.KITCHEN
90'
DINING
CAMERA
DN.
VANITY
POINT 04 03 02 01 SPK. SD.
PDR.
05
W.C. HT
06 EIG
P.T CEILING VOID L EH
FAN 07
BELOW UB
DO
08
STEPS
LIGHT SPK.
ENT.LOBBY
CAR PORCH
A.C
DRAWING ROOM
W.P FLOOR LIGHT PODIUM
CAMERA
SD.
POINT
03
02
01
LIGHT
POINT
UP
FLOOR MOUNTED
2'
FLOOD LIGHT
CAMERA
CAMERA POINT
POINT
5'-6"
LIGHT POINT
EARTH
W. GATE
INTER COM
RAMP UP
GROUND FLOOR PLAN
STEP UP
SUB TITLE.
GENERAL NOTES. ARCHITECT. MAZHAR MUNIR PROJECT NO.
THE INFORMATION CONTAINED IN THIS DRAWING IS PROPRIETARY TO
MAZHAR MUNIR ARCHITECTURAL FIRM. IT IS SUBMITTED IN
DRAWN BY. JUNAID TARIQ GROUND FLOOR ELECTRICAL PLAN
CLIENT.
CONFIDENCE AND IS NOT TO BE REPRODUCED, TRANSMITTED
DISCLOSED OR USED OTHERWISE IN WHOLE OR IN PART, OTHER
THAN WHAT IS HAS BE ORIGINAL FURNISHED FOR, WITHOUT THE THE
DATE ISSUED. 04 / 07 / 2023
REVISED DRAWING NO.
MR. UMER WAHID CHEENA Architectural Firm
PROJECT TITLE.
SCALE. N.T.S.
WRITTEN AUTHORIZATION OF MAZHAR MUNIR ARCHITECTURAL FIRM.
Address: mobile #:
NOTE:- DRAWING NO. PROPOSED DESIGN OF RESIDENCE 49 Fairway 0315 4345307
THE CONTRACTORS SHALL VERIFY ALL THE DIMENSIONS AT SITE.
AND REPORT ANY ERRORS OR OMISSIONS TO THE ARCHITECT. DO
· ALL BATHS ROOM & KITCHEN EXHAUST FAN
AT PLOT No.418 SECTOR M, PHASE VI DHA Raya ph.VI 0310 8555551
NOT SCALE THE DRAWINGS. THE DRAWING SHALL NOT BE USED ·
DUCT AS PLACED IN DRAWING
ALL BATH ROOM 1" DOWN FROM F.F.LEV. E-00 Email address :
FOR CONSTRUCTION UNTIL ISSUED FOR CONTRACTION. · ALL TERRACES 2" DOWN FROM F.F.LEV. D.H.A LAHORE CANTT. mdtworks@gmail.com
· SUNKEN AREA STEEL STEPS & BRIDGE
SHOWER
EX.FAN
TUB
CEILING
EX.FAN
WARDROBE
VANITY
MEDIA WALL
D/BATH P.T M.BATH
CEILING CEILING
W.C. W.C.
FAN FAN
P.T
VANITY
A.C
WARDROBE
SPK.
BED ROOM
MEDIA WALL
WARDROBE
SD.
SD.
LOBBY
MEDIA WALL
W.P.FLOOR
LIGHT
TERRACE
LOUNGE
SPK. SD.
TERRACE
KITCHEN
W.P.FLOOR
LIGHT
CEILING
FAN
FRIDGE
A.C
ELE. DB.
LIGHT JN.DB. 6" A.FFL.
TEL.EXCH. 10"x15" TV./TEL.
STEPS
DN.
W.P.FLOOR
PASSAGE 4'-6" WIDE LIGHT
16 17 18 19 20 21
15
14 A.C
13 LOOKING BELOW
STAIR HALL SD.
12
11
BED ROOM
10 09 08 07 06 05 04 03 02 01
STEPS
LIGHT
MEDIA WALL
CEILING JACUZZI
EX.FAN SPK.
SHOWER
WARDROBE
DRESS
CEILING
FAN BATH
WARDROBE
VANITY
DRESSER
W.C. P.T
VOID SLAB
LIGHT
TERRACE POINT
FLOOR MOUNTED
FLOOR MOUNTED FLOOD LIGHT
FLOOD LIGHT
TERRACE
TERRACE
15'-6" X 25'-9"
FLOOD LIGHT
FLOOR MOUNTED
FLOOR MOUNTED
FLOOD LIGHT
FLOOR MOUNTED
FLOOD LIGHT
LOOKING BELOW
TERRACE
SUB TITLE.
GENERAL NOTES. ARCHITECT. MAZHAR MUNIR PROJECT NO.
THE INFORMATION CONTAINED IN THIS DRAWING IS PROPRIETARY TO
MAZHAR MUNIR ARCHITECTURAL FIRM. IT IS SUBMITTED IN
DRAWN BY. JUNAID TARIQ TOP ROOF ELECTRICAL PLAN
CLIENT.
CONFIDENCE AND IS NOT TO BE REPRODUCED, TRANSMITTED
DISCLOSED OR USED OTHERWISE IN WHOLE OR IN PART, OTHER
THAN WHAT IS HAS BE ORIGINAL FURNISHED FOR, WITHOUT THE THE
DATE ISSUED. 04 / 07 / 2023
REVISED DRAWING NO.
MR. UMER WAHID CHEENA Architectural Firm
PROJECT TITLE.
SCALE. N.T.S.
WRITTEN AUTHORIZATION OF MAZHAR MUNIR ARCHITECTURAL FIRM.
Address: mobile #:
NOTE:- DRAWING NO. PROPOSED DESIGN OF RESIDENCE 49 Fairway 0315 4345307
THE CONTRACTORS SHALL VERIFY ALL THE DIMENSIONS AT SITE.
AND REPORT ANY ERRORS OR OMISSIONS TO THE ARCHITECT. DO
· ALL BATHS ROOM & KITCHEN EXHAUST FAN
AT PLOT No.418 SECTOR M, PHASE VI DHA Raya ph.VI 0310 8555551
NOT SCALE THE DRAWINGS. THE DRAWING SHALL NOT BE USED ·
DUCT AS PLACED IN DRAWING
ALL BATH ROOM 1" DOWN FROM F.F.LEV. E-00 Email address :
FOR CONSTRUCTION UNTIL ISSUED FOR CONTRACTION. · ALL TERRACES 2" DOWN FROM F.F.LEV. D.H.A LAHORE CANTT. mdtworks@gmail.com
· SUNKEN AREA STEEL STEPS & BRIDGE
BOTTOM OF CEILING
9"
SWITCH PLATE
8'
1"
3'-6"
4"
TYPICAL PLACEMENT
DIMENSION FOR SPLIT
POWER SUPPLY
TYPE A.C
EQ. EQ.
9" 9"
BOTTOM OF CEILING
1'-6"
F.F.L.
11'-0"
5'-6" 5'-6"
EQ. 2 EQ. EQ.
SUB TITLE.
GENERAL NOTES. ARCHITECT. MAZHAR MUNIR PROJECT NO.
THE INFORMATION CONTAINED IN THIS DRAWING IS PROPRIETARY
TO MDT. IT IS SUBMITTED IN CONFIDENCE AND IS NOT TO BE
DRAWN BY. JUNAID TARIQ TYPICAL LAYOUT OF ELECTRICAL POINTS
CLIENT.
REPRODUCED, TRANSMITTED DISCLOSED OR USED OTHERWISE IN
07 / 07 / 2023
DRAWING NO.
MR. UMER WAHID CHEENA
Architectural Firm
WHOLE OR IN PART, OTHER THAN WHAT IS HAS BE ORIGINAL DATE ISSUED.
PROJECT TITLE.
ALL RIGHTS RESERVED. SCALE. NTS.
Address: mobile #:
THE CONTRACTORS SHALL VERIFY ALL THE DIMENSIONS AT SITE
NOTE:- PROPOSED DESIGN OF RESIDENCE AT 49 Fairway 0315 4345307
AND REPORT ANY ERRORS OR OMISSIONS TO THE ARCHITECT.
DHA Raya ph.VI 0310 8555551
DO NOT SCALE THE DRAWING. ALL BATHS ROOM & KITCHEN EXHAUST FAN E-06 PLOT NO.418 SECTOR.M , PHASE - VI
THE DRAWING SHALL NOT BE USED FOR CONSTRUCTION UNTIL DUCT AS PLACED IN DRAWING Email address :
ALL BATH ROOM 1" DOWN FROM F.F.LEV. DHA LAHORE CANTT. mdtworks@gmail.com
Z:\NEW PROJECTS\P472 418-M -6\01 PLAN\WORKING\TYPICAL DETAIL FOR ELECTRICAL.dwg Jul 07, 2023 - 12:24pm
F.F.L
9"
9"
1"1"
8"
2'-10"
3'-6"
TUBE LIGHT
UNDER CABINET
CONT. TOP
5'-2"
9"
SPLASH
MIRROR FRAME
EQ.
2'
A
MIRROR
EQ.
MIRROR LIGHT
POINT FOR
5'
2'
F.F.L
6"
2'-9" 9"
SPLASH
1"
9"
3'-6"
SWITCH PLATE &
LIGHT PLUG
5'
F.F.L
SUB TITLE.
GENERAL NOTES. ARCHITECT. MAZHAR MUNIR PROJECT NO.
THE INFORMATION CONTAINED IN THIS DRAWING IS PROPRIETARY
TO MDT. IT IS SUBMITTED IN CONFIDENCE AND IS NOT TO BE
DRAWN BY. JUNAID TARIQ TYPICAL LAYOUT OF ELECTRICAL POINTS
CLIENT.
REPRODUCED, TRANSMITTED DISCLOSED OR USED OTHERWISE IN
07 / 07 / 2023
DRAWING NO.
MR. UMER WAHID CHEENA
Architectural Firm
WHOLE OR IN PART, OTHER THAN WHAT IS HAS BE ORIGINAL DATE ISSUED.
PROJECT TITLE.
ALL RIGHTS RESERVED. SCALE. NTS.
Address: mobile #:
THE CONTRACTORS SHALL VERIFY ALL THE DIMENSIONS AT SITE
NOTE:- PROPOSED DESIGN OF RESIDENCE AT 49 Fairway 0315 4345307
AND REPORT ANY ERRORS OR OMISSIONS TO THE ARCHITECT.
DHA Raya ph.VI 0310 8555551
DO NOT SCALE THE DRAWING. ALL BATHS ROOM & KITCHEN EXHAUST FAN E-07 PLOT NO.418 SECTOR.M , PHASE - VI
THE DRAWING SHALL NOT BE USED FOR CONSTRUCTION UNTIL DUCT AS PLACED IN DRAWING Email address :
ALL BATH ROOM 1" DOWN FROM F.F.LEV. DHA LAHORE CANTT. mdtworks@gmail.com