Volm 4 Dwgs Adm 3

The document provides electrical symbols and general notes for an electrical one-line diagram. It includes symbols for outlets, panels, and devices. The general notes specify that all dimensions are approximate, locations must be verified in the field, and work must comply with relevant electrical codes. Connections subject to movement must use flexible metal conduit between 12 and 36 inches long, and penetrations through fire-rated walls must be sealed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
178 views35 pages

Volm 4 Dwgs Adm 3

The document provides electrical symbols and general notes for an electrical one-line diagram. It includes symbols for outlets, panels, and devices. The general notes specify that all dimensions are approximate, locations must be verified in the field, and work must comply with relevant electrical codes. Connections subject to movement must use flexible metal conduit between 12 and 36 inches long, and penetrations through fire-rated walls must be sealed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

ELECTRICAL SYMBOLS: GENERAL NOTES:

COMBINATION CAT 6 TELEPHONE (VOIP)/DATA 2-PORT OUTLET SINGLE ONE-LINE DIAGRAM SYMBOLS:
* GANG. FOR EACH DEVICE 1-DATA/1-TELEPHONE (VOIP) JACK WITHIN THAT A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE APPROXIMATE. ALL
VV DUPLEX RECEPTACLE, 125V, 20A. INSTALL DEVICE WITH BOTTOM AT +16" A.F.F.
MUTOA. INSTALL WITHIN A 4" x 4" EXTRA DEEP BOX. PROVIDE (2) CAT 6 LOCATIONS SHALL BE FIELD VERIFIED.
USB ASTERISK '*' = VANDALPROOF STYLE RECEPTACLE FACEPLATE. MAIN LUG ONLY PANELBOARD. "PANEL" INDICATES PANEL DESIGNATION.
CABLES U.O.N. PANEL
WP VV = VIDEO VISITATION / IPAD CHARGING STATION, INSTALL DEVICE WITH BOTTOM AT +16" "120/208" INDICATES PANEL OPERATING VOLTAGE. "3∅, 4W" INDICATES
INSTALL DEVICE WITH BOTTOM AT +16" AFF., U.O.N. 200 AMP B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE
GFCI A.F.F. PHASE AND WIRE. "200A 3P" INDICATES 3 POLE MAIN LUGS AND BUS RATED
* ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE. 120/208V LATEST EDITION ADOPTED BY INDIANA, THE INDIANA ELECTRICAL CODE
USB = 125V, 20A, USB CHARGING DUPLEX RECEPTACLE. 3∅, 4W FOR 200A.

DLZ INDIANA, LLC


TV
WP = WEATHERPROOF "WHILE-IN-USE" ENCLOSURE. CAT 6 TELEPHONE (VOIP) 1-PORT OUTLET SINGLE GANG. PROVIDE A WALL MLO AMENDMENTS, LOCAL/MUNICIPAL CODES, AND THE AUTHORITY HAVING
COPIER
TV = TELEVISION OUTLET, INSTALL DEVICE WITH BOTTOM AT +84" A.F.F. TELEPHONE FACEPLATE WITH MOUNTING STUDS FOR MOUNTING PHONE JURISDICTION.
C-I *
C-G GFCI = GROUND FAULT CIRCUIT INTERRUPTING TYPE DEVICE. +48" HANDSET ON FACEPLACE. INSTALL DEVICE AT +48" AFF., U.O.N.
COPIER = COPER OUTLET, FIELD VERIFY NEMA CONFIGURATION WITH OWNER PRIOR TO PROVIDE (1) CAT 6 CABLE U.O.N. C. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE
SUR
CONSTRUCTION, INSTALL DEVICE WITH BOTTOM AT +16" A.F.F. ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE. LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT LESS THAN 12" IN LENGTH, NOR
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. GREATER THAN 36" IN LENGTH.
TABLE CHARGING STATION SINGLE GANG 2-PORT DATA OUTLET. FOR EACH MAIN CIRCUIT BREAKER PANELBOARD. "PANEL" INDICATES PANEL
C-I = RECEPTACLE INDIVIDUALLY CONTROLLED BY SECURITY ELECTRONIC RELAY CABINET. PANEL
C-G = RECEPTACLE GROUP CONTROLLED BY SECURITY ELECTRONIC RELAY CABINET. * TCS DEVICE 2-DATA JACKS WITHIN THAT MUTOA. INSTALL WITHIN A 4" x 4" EXTRA 200 AMP DESIGNATION. "120/208" INDICATES PANEL OPERATING VOLTAGE. "3∅, 4W" D. ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE SEALED WITH THE
SUR = DEVICE TO BE SURFACE MOUNTED. DEEP BOX. PROVIDE (2) CAT 6 CABLES U.O.N. 120/208V INDICATES PHASE AND WIRE. "200A 3P" INDICATES 3 POLE MAIN LUGS AND APPROPRIATE FIRE STOPPING MATERIAL TO MAINTAIN WALL FIRE RATING. SEE
ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE 3∅, 4W BUS RATED FOR 200A. ARCHITECTURAL DRAWING #A-051 FOR FIRE RATED WALL LOCATIONS.
DUPLEX RECEPTACLE, 125V, 20A. INSTALL DEVICE WITH TOP AT +40" A.F.F. COORDINATE EXACT LOCATION WITH OWNER PROVIDED EQUIPMENT. MCB
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. E. SEE MECHANICAL AND PLUMBING SCHEDULES FOR MECHANICAL EQUIPMENT
PROJECT INPUT 3-PORT OUTLET SINGLE GANG. FOR EACH DEVICE 1- RATINGS AND SIZES.
PROJ DATA/TELEPHONE (VOIP) JACK, 1-USB JACK AND 1-HDMI INTERFACE WITHIN
DUPLEX RECEPTACLE ON UNINTERRUPTIBLE POWER SUPPLY CIRCUIT, 125V, 20A. THAT MUTOA. INSTALL WITHIN A 4" x 4" EXTRA DEEP BOX. PROVIDE (1) CAT 6 F. ALL 120V POWER AND LIGHTING CIRCUITS SHALL BE MINIMUM (2 )#12, AND (1) #12 G,
INSTALL DEVICE WITH BOTTOM AT +16", A.F.F. RECEPTACLE TO BE COLOR CABLE, (1) PRE-TERMINATED USB CABLE AND (1) PRE-TERMINATED HDMI 200 FUSED SWITCH. TOP NUMBER INDICATES SWITCH RATING IN AMPERES.
IN 3/4" CONDUIT UNLESS OTHERWISE NOTED. ALL BRANCH CIRCUIT WITH 20A AND
"ORANGE". U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. CABLE BETWEEN CEILING INTERFACE LOCATION AND ASSOCIATED WALL 200 BOTTOM NUMBER INDICATES FUSE RATING IN AMPERES.
BELOW BREAKER(S) SHALL USE THE FOLLOWING MINIMUM CABLE SIZE TO
INTERFACE LOCATION IN 1-1/4"C. INSTALL WALL DEVICE AT +16" AFF, U.O.N. ACCOMMODATE VOLTAGE DROP UNLESS OTHER WISE NOTED: LESS THAN 100'-0": #12
DUPLEX RECEPTACLE ON UNINTERRUPTIBLE POWER SUPPLY CIRCUIT, 125V, 20A.
INSTALL DEVICE WITH TOP AT +40" A.F.F., RECEPTACLE TO BE COLOR "ORANGE". THERMAL MAGNETIC CIRCUIT BREAKER. TOP NUMBER INDICATES TRIP RATING AWG; 100'-0" TO 170'-0": #10 AWG; 170'-0" TO 250'-0": #8 AWG.
COMBINATION TELEPHONE (VOIP)/DATA 2-PORT OUTLET SINGLE GANG. FOR 200AT
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. EACH DEVICE 1-DATA/TELEPHONE (VOIP) JACK AND (1) USB JACK WITHIN THAT IN AMPERES. BOTTOM NUMBER INDICATES FRAME RATING IN AMPERES. "80%
* USB 200AF RATED" INDICATES BREAKER RATING. "LSIG" INDICATES BREAKER WITH G. ALL CONTROL WIRING SHALL BE NOT LESS THAN (2) #14, (1) #14G, 3/4"C, UON.
DUPLEX RECEPTACLE CEILING MOUNTED 125V, 20A. REFER TO SPECIFICATIONS MUTOA. INSTALL WITHIN A 4" x 4" EXTRA DEEP BOX. PROVIDE (1) CAT 6 CABLE 80% RATED
AND (1) USB CABLE U.O.N. ADJUSTABLE LONG TIME, SHORT TIME, INSTANTANEOUS, AND GROUND FAULT
AND DRAWINGS FOR FURTHER DETAILS. LSIG TRIP SETTINGS. "SS" INDICATES SOLID STATE, 3-POLE, U.O.N. H. ALL CABLES INSTALLED IN AIR HANDLING PLENUMS SHALL BE PLENUM RATED CABLE. R
ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE EE
SS CK IN
INSTALL DEVICE WITH BOTTOM AT +16" AFF., U.O.N
DUPLEX RECEPTACLE CEILING MOUNTED ON UNINTERRUPTIBLE POWER SUPPLY CO

SS D I A N G
I. HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN ON THE

I ON A L E N
BUS BAR.

PE60018676
D

A
CIRCUIT 125V, 20A. REFER TO SPECIFICATIONS AND DRAWINGS FOR FURTHER

STATE OF
CONTRACT DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME RUNS MAY BE

L . H I TC
COMBINATION TELEVISION/DATA 2-PORT OUTLET SINGLE GANG. FOR EACH

E
I ST ER
DETAILS. RECEPTACLE TO BE COLOR "ORANGE". * DEVICE 1-DATA/1-TELEVISION JACK WITHIN THAT MUTOA. INSTALL WITHIN A 4" COMBINED AT THE CONTRACTOR'S DISCRETION NOT GREATER THAN (3) PHASE
+84" TV

No.
x 4" EXTRA DEEP BOX. PROVIDE (1) CAT 6 CABLE AND (1) COAX CABLE FEEDER CIRCUIT. CONDUCTORS, (3) NEUTRAL CONDUCTORS, AND REQUIRED GROUNDING
DUPLEX RECEPTACLE FLOOR BOX 125V, 20A. REFER TO SPECIFICATIONS AND CONDUCTOR(S). CONTRACTOR MUST INCREASE WIRE SIZE AND DERATE

EG
INSTALL DEVICE AT +84" AFF., U.O.N

IN
DRAWINGS FOR DETAILED ELECTRICAL REQUIREMENTS.

IN
ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE. CONDUCTOR CAPACITY ACCORDING TO NEC. R
20 MOTOR WITH HORSEPOWER INDICATED. RV
(1) HDMI INTERFACE OUTLET. PROVIDE 2-GANG BOX WITH ADAPTER RING FOR
MA FE
QUAD RECEPTACLE, 125V, 20A. INSTALL DEVICE WITH BOTTOM AT +16" A.F.F. J. EACH SINGLE PHASE BRANCH CIRCUIT CONDUCTOR SHALL HAVE A DEDICATED P RO
SINGLE GANG PLATE AND 1-1/4" EMT UP ABOVE CEILING AND STUBBED OUT NEUTRAL BACK TO THE PANELBOARD.
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN.
WITH BUSHING. INSTALL DEVICE AT HEIGHT INDICATED ON PLANS. FURNISH 208V
QUAD RECEPTACLE, 125V, 20A. INSTALL DEVICE WITH TOP AT +40" A.F.F. AND INSTALL PRE-TERMINATED HDMI CABLE BETWEEN LAPTOP/COMPUTER 30KVA TRANSFORMER. PRIMARY VOLTAGE, SECONDARY VOLTAGE, RATING IN KVA AS K. SUPPORTING WIRE FOR THE SUSPENDED CEILING GRID SHALL NOT BE USED AS
* HD INTERFACE MUTOA AND TV INTERFACE MUTOA WITH 1"C. AS INDICATED ON
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. 208/120 INDICATED. K FACTOR AS INDICATED. RACEWAY SUPPORT.
PLANS. K13
QUAD RECEPTACLE ON UNINTERRUPTIBLE POWER SUPPLY CIRCUIT, 125V, 20A. INSTALL DEVICE WITH BOTTOM AT +16" AFF., U.O.N L. DISCONNECT SWITCH RATINGS SHALL BE AS INDICATED ON THE DRAWINGS.
INSTALL DEVICE WITH BOTTOM AT +16" A.F.F. RECEPTACLE TO BE COLOR "ORANGE". ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE.
GROUND.
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. M. MAJOR FEEDERS FROM THE SWITCHBOARD TO PANELBOARDS, TRANSFORMERS,
VIDEO VISITATION 2-PORT DATA OUTLET, SINGLE GANG. FOR EACH DEVICE 1-
* VV DATA JACK WITHIN THAT RECEPTACLE. INSTALL WITHIN A 4" x 4" EXTRA DEEP MOTORS AND OTHER LARGE EQUIPMENT ARE NOT SHOWN ON THE FLOOR PLAN
QUAD RECEPTACLE ON UNINTERRUPTIBLE POWER SUPPLY CIRCUIT, 125V, 20A.
BOX. PROVIDE (1) CAT 6 CABLES U.O.N. DRAWINGS. THESE FEEDERS ARE INCLUDED WITHIN THE SCOPE OF THE ELECTRICAL
INSTALL DEVICE WITH TOP AT +40" A.F.F. RECEPTACLE TO BE COLOR "ORANGE". 100A NON-FUSED DISCONNECT SWITCH. NUMBER INDICATES RATING IN AMPERES.
ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE WORK AND ARE SHOWN ON THE ONE-LINE DIAGRAMS.
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN.
DEVICE TO BE LOCATED BEHIND VIDEO VISITATION MONITOR, VERIFY EXACT
SPECIAL RECEPTACLE, REFER TO MANUFACTURER REQUIREMENTS. LOCATION BEFORE ROUGH-IN. N. ALL FIRE ALARM CABLING SHALL BE RED, PLENUM RATED, AND INSTALLED IN RED
INSTALL CONDUIT. ALL ASSOCIATED JUNCTION/PULL BOXES SHALL BE "RED".
PLAIN OLD TELEPHONE SYSTEM OUTLET. PROVIDE (1) CAT 6 CABLE WITH (1) ENCLOSURE OUTLINE.
DEVICE WITH BOTTOM AT +16" A.F.F.
* RJ11 JACK. O. HVAC CONTROL WIRING FURNISHED AND INSTALLED BY OTHERS. PROVIDE POWER
U.O.N. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. POTS
INSTALL DEVICE WITH BOTTOM AT +16" AFF., U.O.N. TO EACH TEMPERATURE CONTROL PANELS AND EQUIPMENT AS INDICATED ON
SPECIAL RECEPTACLE ON UNINTERRUPTIBLE POWER SUPPLY CIRCUIT, ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE. 100 PLANS.
REFER TO MANUFACTURER REQUIREMENTS. INSTALL DEVICE WITH CABLE/CONDUIT NUMBER.
CONDUIT CONCEALED IN GROUND OR FLOOR.
BOTTOM AT +16" A.F.F., RECEPTACLE TO BE COLOR "ORANGE". U.O.N. P. INDOOR CONTROL EQUIPMENT ENCLOSURES SHALL BE NEMA 1 RATED U.O.N. ALL
COORDINATE EXACT LOCATION BEFORE ROUGH-IN. CONDUIT TURN UP AND TURN DOWN RESPECTIVELY. EXTERIOR ENCLOSURES SHALL BE NEMA 3R UNLESS OTHERWISE NOTED. ALL
ENCLOSURES LOCATED IN KITCHEN SHALL BE NEMA 4X STAINLESS STEEL UNLESS
J J J JUNCTION BOX A L1# OTHERWISE NOTED.
LIGHT FIXTURE. "A" INDICATES FIXTURE TYPE. "a" INDICATES SWITCH LEG. N E
"L1#" INDICATES CIRCUIT NUMBER FIXTURE IS CONNECTED TO. REFER TO AUTOMATIC TRANSFER SWITCH
R RELAY a LIGHT FIXTURES SCHEDULE ON DRAWING E-604. Q. ALL CONDUITS CROSSING EXPANSION JOINTS SHALL BE INSTALLED WITH EXPANSION
L FITTINGS, UNLESS THE CONDUIT IS BELOW SLAB IN THE COMPACTED GRANULAR
a TOGGLE SWITCH, 120/277V, 1-POLE, 20A. LIGHT FIXTURES WITH HALF SOLID SHADING INDICATES FIXTURE IS USED FILL. EXPANSION FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC AND
S* ASTERISK '*' = VANDALPROOF STYLE DEVICE FACEPLATE. FOR EMERGENCY EGRESS LIGHTING. "A" INDICATES FIXTURE TYPE MANUFACTURER'S WRITTEN RECOMMENDATIONS. REFER TO STRUCTURAL
WP WP=WEATHERPROOF ENCLOSURE, "a" INDICATES SWITCH LEG. A L1#
N.L. = NIGHT LIGHT, CONTINUOUS OPERATION, NON-CONTROLLED. DRAWINGS FOR EXPANSION JOINT LOCATIONS.
S 3a TOGGLE SWITCH, THREE WAY TYPE, 120/277V, 20A, "a" INDICATES SWITCH LEG. a EM = FIXTURE SUPPLIED WITH EMERGENCY POWER CONTROL MODULE,
CONTROLLED. SB SWITCHBOARD R. THE CONTRACTOR SHALL COORDINATE RECEPTACLE HEIGHTS AND LOCATIONS
S 4a REFER TO LIGHT FIXTURE SCHEDULE ON DRAWING E-604. WITH THE CASEWORK SHOP DRAWINGS TO DETERMINE EXACT LOCATIONS AND
TOGGLE SWITCH, FOUR WAY TYPE, 120/277V, 20A, "a" INDICATES SWITCH LEG. HEIGHTS FOR OUTLET INSTALLATION. REFER TO SHEET A-003 FOR ADA MOUNTING
HEIGHTS FOR WIRING DEVICES. FIELD VERIFY EXACT HEIGHTS FOR WIRING DEVICES
S Da DIMMABLE SWITCH, 120/277V, 20A, "a" INDICATES SWITCH LEG. PC PHOTOCELL
ABBREVIATIONS: PRIOR TO CONSTRUCTION AND INSTALL IN ACCORDANCE WITH ADA REQUIREMENTS.
a a DUAL TECHNOLOGY OCCUPANCY SENSOR, CEILING OR WALL MOUNT COVERAGE POE WIRELESS ACCESS POINT (WAP). PROVIDE TWO (2) CAT 6A CABLES S. CONTROL WIRING FOR HVAC EQUIPMENT FURNISHED AND INSTALLED BY OTHERS.
OC OR OC OF SENSOR DEPENDENT ON ROOM SIZE, "a" INDICATES SWITCH LEG, "WG" PER IEEE 802.11ac. CEILING MOUNT AND/OR SURFACE/FLUSH MOUNT AS PROVIDE POWER TO EQUIPMENT AS INDICATED ON PLANS.
WG WG INDICATES WIRE GUARD INCLUDED. POWER PACKS NOT SHOWN - FIELD LOCATE INDICATED ON DRAWINGS. A AMPERES MC MECHANICAL CONTRACTOR
AND RECORD ON RECORD DRAWINGS. AF AMPERE FRAME MCA MINIMUM CIRCUIT AMPACITY T. TO REDUCE NOISE BETWEEN WALLS, CONTRACTOR SHALL:
a DISTRIBUTION PANELBOARD, SEE SCHEDULE FOR DETAILED REQUIREMENTS. 1. AVOID INSTALLING POWER RECEPTACLES OR DATA OUTLETS LOCATED BACK TO
PIR HIGH BAY OCCUPANCY SENSOR. PROVIDE POWER PACK(S) AS REQUIRED PER AFC ABOVE FINISHED COUNTER MCB MAIN CIRCUIT BREAKER
OC BACK.
MANUFACTURER'S RECOMMENDATION, "a" INDICATES SWITCH LEG.
PANELBOARD, SEE SCHEDULE FOR DETAILED REQUIREMENTS. AFF ABOVE FINISHED FLOOR MCC MOTOR CONTROL CENTER 2. WHERE OUTLETS ARE REQUIRED TO BE LOCATED BACK TO BACK CONTRACTOR
4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR MOUNTING EMERGENCY SHALL PROVIDE SOUNDPROOFING MATERIAL BETWEEN JUNCTION BOXES (AND
AFG ABOVE FINISHED GRADE MDF MAIN DISTRIBUTION FRAME FIRE RATED PUTTY AROUND JUNCTION BOXES FOR FIRE RATED WALLS).
POWER CONTROL MODULE. MOUNT WHERE INDICATED ON PLANS. PROVIDE
C PERMANENT LABEL ON MODULE FACEPLATE INDICATING ROOM/AREA(S) WHERE NON-FUSED DISCONNECT SWITCH, SEE DRAWINGS FOR DETAILED REQUIREMENTS.
J AIC AMPERES INTERRUPTING CAPACITY MFR MANUFACTURER U. THE WORD "PROVIDE" IS TO BE DEFINED AS "FURNISH AND INSTALL".
W CONTROLLED LIGHTS ARE LOCATED. "C" INDICATES DEVICE FLUSH MOUNTED IN
FUSED DISCONNECT SWITCH, SEE DRAWINGS FOR DETAILED REQUIREMENTS. AT AMPERE TRIP MLO MAIN LUG ONLY
CEILING, "W" INDICATES DEVICE FLUSH MOUNTED IN WALL. COORDINATE EXACT
LOCATION WITH OWNER BEFORE ROUGH-IN. V. ALL ELECTRICAL DEVICES IN RECREATION ROOMS TO BE PROVIDED WITH
NON-COMBINATION STARTER, SEE DRAWINGS FOR DETAILED REQUIREMENTS. ATS AUTOMATIC TRANSFER SWITCH MOCP MAXIMUM OVERCURRENT PROTECTION WIREGUARD UNLESS INSTALLED IN CUSTOM BOX.
* o ADDRESSABLE FIRE ALARM HEAT DETECTOR. CEILING MOUNT COMBINATION RATE-
F 135 OF-RISE (15 DEGREES PER MINUTE) AND FIXED TEMPERATURE (135 DEGREES F) AS AWG AMERICAN WIRE GAUGE MTS MANUAL TRANSFER SWITCH
W. COORDINATE VIDEO VISITATION REQUIREMENTS WITH OWNER'S VIDEO VISITATION
COMBINATION STARTER/DISCONNECT, SEE DRAWINGS FOR DETAILED REQUIREMENTS.
NOTED IN SPECIFICATION 284621.11. BACnet BUILDING AUTOMATION AND MUTOA MULTI-USER TELECOMMUNICATIONS VENDOR BEFORE CONSTRUCTION. FURNISH AND INSTALL POWER AND SYSTEMS
ASTERISK '*' = VANDALPROOF STYLE DEVICE GUARD. CONTROL NETWORKING PROTOCOL OUTLET ASSEMBLY CABLING AS REQUIRED. PROVIDE WIRIGN DEVICES, BOXES, RACEWAYS, CABLING,
VARIABLE FREQUENCY DRIVE, SEE DRAWINGS FOR DETAILED REQUIREMENTS. SUPPORTS, ETC. AS REQUIRED.

DATE
ADDRESSABLE FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR. CEILING MOUNT. BE BURIED ELECTRIC NEC NATIONAL ELECTRICAL CODE
S * VARIABLE FREQUENCY DRIVE AND DISCONNECT COMBINATION, SEE DRAWINGS
P ASTERISK '*' = VANDALPROOF STYLE DEVICE COVER, REFER TO DETAIL #9, DRAWING E-801. BFG BELOW FINISH GRADE NL NON-SWITCHED NIGHT LIGHT X. THE TRADE CONTRACTOR SHALL COORDINATE LOCATIONS OF ALL PENETRATIONS
FOR DETAILED REQUIREMENTS.
WITH STRUCTURAL DRAWING REQUIREMENTS. ADDITIONALLY, THE TRADE
ADDRESSABLE FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR. WALL MOUNT ON BFO BURIED FIBER OPTIC NO2 NITROGEN DIOXIDE CONTRACTOR SHALL COORDINATE ALL PENETRATIONS REQUIRED THROUGH
S * 3
RECESSED DEVICE BOX. NON-COMBINATION MAGNETIC MOTOR STARTER NUMBER INDICATES NEMA RATING, SIZE 1 U.O.N. PRECAST CONCRETE UNITS WITH THE HOLLOW CORE PRECAST CONCRETE
P ASTERISK '*' = VANDALPROOF STYLE DEVICE COVER, REFER TO DETAIL #9, DRAWING E-801. BMS BUILDING MANAGEMENT SYSTEM NO/NC NORMALLY OPEN/NORMALLY CLOSED
MANUFACTURER TO PRODUCE A SHOP DRAWING SUBMITTAL NOTING ALL
ADDRESSABLE FIRE ALARM DUCT MOUNTED SMOKE DETECTOR, HOUSING , AND
MOTOR. BSMT BASEMENT NTRL NEUTRAL PENETRATIONS AND THEIR SIZES. TRADE CONTRACTOR AND PRECAST
SMOKE DAMPER. CONNECT TO LEGALLY REQUIRED 120VAC BRANCH CIRCUIT. MANUFACTURER SHALL PROVIDE DOCUMENTATION WITH SHOP DRAWING
SAMPLING TUBE ON RETURN SIDE. INTERLOCK WITH DAMPER/FAN MOTOR CONTROL TO

REVISION
DAMPER SHALL OPEN UPON ENERGIZATION (OR FAIL CLOSED UPON DE- BT BURIED TELEPHONE NTS NOT TO SCALE SUBMITTAL INDICATING THAT ALL TRADES HAVE SIGNED OFF ON ALL
S SHUTDOWN UNIT UPON DETECTION. PROVIDE AND WIRE AN ILLUMINATED REMOTE TEST
ENERGIZATION). POWER TO SMOKE DAMPER(S) ASSOCIATED WITH AHU SHALL BE AFOREMENTIONED COORDINATION. IN ADDITION, ANCHORING TO HOLLOW CORE
D STATION INTERLOCKED TO THE EQUIPMENT; CENTRALLY LOCATE IN THE MASTER C CONDUIT OCP OVERCURRENT PROTECTIVE DEVICE
CONTROLLED BY THE FIRE ALARM CONTROL PANEL - I.E. THE 120VAC CIRCUIT SHALL PRECAST SHALL BE APPROVED AND SIGNED OFF BY ALL TRADES.
CONTROL #B1016, LOCATION SHALL BE READILY ACCESSIBILE TO FIREMAN FOR SMOKE FD BE WIRED VIA DRY, FORM C ISOLATION CONTACT (IN THE IAM). UPON DUCT DETECTOR CAT CATEGORY OCPD OVERCURRENT PROTECTIVE DEVICE
MANAGEMENT CONTROL/TESTING.
SMOKE DETECTION AT AHU, ASSOCIATED DAMPER(S) SHALL CLOSE (BE DE- Y. ALL DEVICES SURFACE MOUNTED ON BOTTOM OF PRECAST HOLLOW-CORE CEILING
ILLUMINATED REMOTE TEST STATION INTERLOCKED TO SHUTDOWN AIR HANDLING ENERGIZED). REFER TO DETAIL 7 ON DRAWING E-801 FOR SMOKE DAMPER WIRING CATV CABLE TELEVISION/COMMUNITY OL OVERLOADS SHALL BE SUPPLIED FROM ABOVE. EXPOSED CONDUITS OR WIREMOLD SHALL NOT
RTS ANTENNA TELEVISION
EQUIPMENT. DETAIL. REFER TO DRAWINGS E-203 AND E-204 FOR LOCATIONS OF AHU(S) REQUIRING BE INSTALLED ON, OR ANCHORED TO, THE BOTTOM OF PRECAST HOLLOW-CORE
DUCT SMOKE DETECTOR(S). P POLE
CB CIRCUIT BREAKER CEILING. BOXES SHALL BE ACCESSIBLE FROM BELOW PRECAST HOLLOW CORE.
WP NON-ADDRESSABLE FIRE ALARM HORN.
PC PERSONAL COMPUTER

NO.
WP = WEATHERPROOF STYLE DEVICE. P PULLBOX. CO CARBON MONOXIDE Z. CONDUITS SHALL NOT BE ROUTED IN OR THROUGH, OR ANCHORED TO, THE
F * ASTERISK '*' = VANDALPROOF STYLE DEVICE GUARD. PH PHASE PRECAST HOLLOWCORE CEILING. FIELD COORDINATE PRIOR TO CONSTRUCTION
DED DEDICATED WITH PRECAST VENDOR TO DETERMINE DROP-IN ANCHOR LOCATIONS FOR
WP NON-ADDRESSABLE FIRE ALARM HORN WITH VISUAL STROBE. BRANCH CIRCUIT HOME-RUN SYMBOLOGY: POE POWER OVER ETHERNET
WP = WEATHERPROOF STYLE DEVICE. DFA DROP FROM ABOVE MOUNTING OF RACEWAYS OR OTHER ELECTRICAL ITEMS UNDERNEATH THE
F * SOLID CIRCLE INDICATES GROUND CONDUCTOR POTS PLAIN OLD TELEPHONE SYSTEM PRECAST HOLLOWCORE CEILING. REFER TO DRAWING S-500, DETAIL #7.
ASTERISK '*' = VANDALPROOF STYLE DEVICE GUARD.

CHK'D: MLH
DIV DIVISION

SEPTEMBER 5, 2019
S LONG LINE INDICATES NEUTRAL CONDUCTOR(S) ∅ PHASE AA. ADJUST DEVICE BOX MOUNTING HEIGHT TO TOP OR BOTTOM OF BLOCK COURSING

1663-1190-90
NON-ADDRESSABLE FIRE ALARM VISUAL STROBE ANNUNCIATOR.
F * SHORT LINE INDICATES PHASE CONDUCTOR(S) D.S DISCONNECT SWITCH AS NEEDED SO BOXES DO NOT CROSS A MORTAR JOINT.
ASTERISK '*' = VANDALPROOF STYLE DEVICE GUARD. RCPT RECEPTACLE
ETR EXISTING TO REMAIN
ADDRESSABLE FIRE ALARM MANUAL PULL STATION. RECEPT RECEPTACLE BB. SECURITY CAULKING/SEALANT SHALL BE INSTALLED IN CREVICES IN ALL DETENTION
F *

PROJECT NUMBER
ASTERISK '*' = VANDALPROOF STYLE DEVICE COVER. OVERHEAD DOOR SAFETY INTERLOCKS. REFER TO SPECIFICATION
083613 FOR MORE INFORMATION. EX EXISTING TO REMAIN SPACES (I.E. AROUND DEVICE PLATES, LIGHTING FIXTURES, ETC.). REFER TO

DESIGNED: RDW
MLH
RLA RUNNING LOAD AMPERES SPECIFICATION 079200 FOR DETAILED REQUIREMENTS. A CREVICE SHALL BE

DRAWN: RDW
FAAP REMOTE FIRE ALARM ANNUNCIATOR PANEL. EC ELECTRICAL CONTRACTOR
LOCAL KEYED OPEN-STOP-CLOSE OVERHEAD SECTIONAL DOOR RM. ROOM CONSIDERED SPACE WHERE A RAZOR BLAD COULD BE CONCEALED/STORED OR AS
FACP PUSHBUTTON CONTROL STATION. REFER TO SPECIFICATION 083613 (F) FUTURE OTHERWISE DETERMINED BY ENGINEER/ARCHITECT PRIOR TO CONSTRUCTION

APPRV'D:
FIRE ALARM/DETECTION MAIN CONTROL PANEL.
"SECTIONAL DOORS" FOR DETAILED REQUIREMENTS. INSTALL DEVICE SE SERVICE ENTRANCE COMPLETION.

DATE:
AT +48" AFF U.O.N. FAAP FIRE ALARM ANNUNCIATOR PANEL
FA-GAP FIRE ALARM/DETECTION GRAPHIC ANNUNCIATOR WORKSTATION AND PRINTER. SP. SPARE CC. TORX HEAD SCREWS WITH A CENTER PIN SHALL BE INSTALLED IN ALL DETENTION
GAA FACP FIRE ALARM CONTROL PANEL
FA-NAC FIRE ALARM/DETECTION REMOTE NOTIFICATION APPLIANCE CABINET. GENERATOR REMOTE ALARM ANNUNCIATOR PANEL. SPEC SPECIFICATIONS SPACES (I.E. DEVICE FACEPLATES, LIGHTING FIXTURE ACCESS PLATES, ETC.). REFER
FLA FULL LOAD AMPERES TO SPECIFICATION 050553 FOR DETAILED REQUIREMENTS.
BUILDING OR TELECOMM GROUND BUS BAR. REFER TO DETAILS #2 AND #3 ON SS SOLID STATE (ELECTRONIC) BREAKER
PIV POST INDICATOR VALVE. DRAWING E-803. F/SD FIRE/SMOKE DAMPER DD. PER NEC ARTICLE 700, "LEGALLY REQUIRED", "EMERGENCY", "OPTIONAL" AND "UPS"

GENERAL NOTES, SYMBOLS & ABBREVIATIONS


SSOL SOLID STATE OVERLOADS POWERED CIRCUITS SHALL BE ROUTED IN SEPARATE CONDUITS FROM ONE
BF FIRE ALARM MONITOR POINT, BACKFLOW PREVENTOR/PRESSURE INDICATING SWITCH.

* ASTERISK '*' = VANDALPROOF STYLE DEVICE. G GROUND

VIGO COUNTY SECURITY CENTER


ST SAFETY TYPE ANOTHER. PAINT COVER OF JUNCTION BOXES FOR "OPTIONAL" CIRCUITS SILVER.
WP FIRE ALARM MONITOR POINT, TAMPER SWITCH. GFI GROUND FAULT INTERRUPT PAINT COVER OF JUNCTION BOXES FOR "EMERGENCY" CIRCUITS PURPLE. PAINT
TS SW SWITCH COVER OF "LEGALLY" REQUIRED CIRCUITS ORANGE. PAINT COVER OF JUNCTION
WP = WEATHERPROOF STYLE DEVICE.
GFCI GROUND FAULT CIRCUIT INTERRUPT BOXES FOR "UPS" CIRCUITS YELLOW.
FS FIRE ALARM MONITOR POINT, FLOW SWITCH. TBI TO BE INSTALLED
GRND GROUND
TBR TO BE REMOVED EE. ALL DEVICES IN FINISHED AREAS SHALL BE FLUSH MOUNTED UNLESS OTHERWISE
ANSUL KITCHEN HOOD FIRE SUPPRESSION. HDMI HIGH DEFINITION MULTIMEDIA NOTED.
TCC TEMPERATURE CONTROLS CONTRACTOR
WP FIRE ALARM INTERMEDIATE ADDRESSABLE MODULE. IAM LOOP POWERED BY FACP HMI HUMAN MACHINE INTERFACE FF. SMOKE CONTROL SYSTEM SHALL BE CONTROLLED BY THE BUILDING MANAGEMENT
IAM (SEPARATE POWER SUPPLY NOT REQUIRED UNLESS OTHERWISE INDICATED BY MFR). TTB TELEPHONE TERMINAL BOARD
HOA HAND OFF AUTOMATIC SYSTEM (BMS). FIRE ALARM CONTROL PANEL SHALL COMMUNICATE SMOKE
WP = WEATHERPROOF STYLE DEVICE. DETECTION AND ALARMING WITH BMS USING BACnet COMMUNICATION PROTOCOL
TV TELEVISION
ZAM ZONE ADDRESSABLE MODULE. HLOA HIGH LOW OFF AUTOMATIC VIA UL 864 COMPLIANT COMMUNICATION DEVICES AND ACCESSORIES.
TWSHPR TWISTED SHIELDED PAIR

TERRE HAUTE, INDIANA


HNDLR HANDLER GG. PROVIDE A "VESDA" SMOKE DETECTOR HEAD INSIDE EACH OF THE RETURN DUCTS
VESDA VERY EARLY SMOKE DETECTION APPARATUS CONTROL PANEL (SUITABLE UP TO 40 PORTS). TWPR TWISTED PAIR
IAM INTERMEDIATE ADDRESSABLE MODULE LEADING FROM EACH SLEEPING CELL (I.E. CELL WITH A BED). THESE CELLS SHALL BE
"VESDA" SMOKE DETECTION, REFER TO SPECIFICATION 284621.11 FOR DETAILED TYP. TYPICAL INDIVIDUALLY MONITORED (ADDRESSABLE) AT THE "VESDA" SMOKE DETECTION
SD SD
REQUIREMENTS. DEDICATED TUBE FOR EACH SAMPLING PORT/DETECTOR. IDF INTERMEDIATE DISTRIBUTION FRAME PANEL. ROUTE "VESDA" AIR SAMPLING TUBING FROM EACH DETECTOR HEAD BACK

ELECTRICAL SITE LEGEND: UON UNLESS OTHERWISE NOTED TO THE "VESDA" SMOKE DETECTION PANEL. PER FIRE ALARM SPECIFICATION,

A NEW
VESDA ASPIRATING SMOKE DETECTOR SAMPLING PORT. FLUSH MOUNT, TAMPER-RESISTANT IP INTERNET PROTOCOL PROVIDE ADDRESSABLE RELAY(S) FOR EACH OF THE 40 +/- TUBING PORTS LOCATED
S * SAMPLING PORT. UPS UNINTERRUPTABLE POWER SOURCE
V KAIC KILO-AMPERES INTERRUPTING CAPACITY IN THE "VESDA" SMOKE DETECTION PANEL (ALTERNATIVELY, PROVIDE
ASTERISK '*' = VANDALPROOF STYLE DEVICE COVER, REFER TO DETAIL #9, DRAWING E-801. COMMUNICATION PROTOCOL WITH WIRING BACK TO THE FIRE ALARM CONTROL
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

BC DIRECT BURIED CONDUIT FOR COMMUNICATIONS CABLES. USB UNIVERSAL SERIAL BUS
KVA KILO-VOLT-AMPS PANEL; PROTOCOL SELECTED SHALL BE COMPATIBLE WITH FIRE ALARM CONTROL
F/SD FIRE AND SMOKE DAMPER. REFER TO DETAIL #7 ON DRAWING E-801. V VOLTS PANEL).
BE DIRECT BURIED CONDUIT FOR ELECTRICAL POWER CABLES. KW KILOWATTS
CO BFO VESDA VERY EARLY SMOKE DETECTION
CARBON MONOXIDE GAS DETECTION SENSOR BY OTHERS. DIRECT BURIED CONDUIT FOR SECURITY FIBER OPTIC CABLES. LSIG LONG TIME, SHORT TIME, HH. FURNISH AND INSTALL ELECTRICAL CONNECTIONS AS REQUIRED FOR ALL
APPARATUS
INSTANTANEOUS, GROUND EQUIPMENT IN KITCHEN, LAUNDRY AND MEDICAL/DENTAL AREA THAT REQUIRE
G DIRECT BURIED GROUND CONDUCTOR.
NO2 NITROGEN DIOXIDE GAS DETECTION SENSOR BY OTHERS. VFD VARIABLE FREQUENCY DRIVE POWER. CONFIRM POWER REQUIREMENTS WITH EQUIPMENT PROVIDER. FURNISH
LTG LIGHTING AND INSTALL BOXES, RACEWAYS, CABLING, SUPPORTS, DISCONNECTS, STARTERS,
HIGH-LEVEL-INTERFACE BOX FOR VESDA COMMUNICATION NETWORK. LOCATED ADJACENT ELECTRICAL HANDHOLE VOIP VOICE OVER INTERNET PROTOCOL
HLI ETC. AS REQUIRED.
TO EACH AIR SAMPLING SMOKE DETECTOR ALARM/MONITORING PANEL. (OR 'HH-E1' INDICATES ELECTRICAL HANDHOLE #1 MATV MASTER ANTENNA TELEVISION
HH-E1 'HH-C1' INDICATES COMMUNICATION HANDHOLE #1 W WIRE
ALTERNATIVELY WHERE FACP-1 IS NOT SUPPORTED BY THE VESDA COMMUNICATIONS II. FURNISH AND INSTALL ELECTRICAL CONNECTION AS REQUIRED FOR ALL SECURITY
NETWORK, PROVIDE ZAM(S) AT EACH VESDA AIR SAMPLING SMOKE DETECTOR WAP WIRELESS ACCESS POINT ELECTRONICS, MECHANICAL AND COMMUNICATIONS EQUIPMENT THAT REQUIRE
ALARM/MONITORING CABINET FOR ALARMING/MONITORING AS NOTED IN SPECIFICATION SITE LIGHTING FIXTURE/POLE. 'SA' INDICATES FIXTURE TYPE. REFER
POWER. CONFIRM POWER REQUIREMENTS WITH EQUIPMENT PROVIDER. PROVIDE
SECTION 284621.11 AND/OR AS OTHERWISE NOTED. SA TO LIGHT FIXTURE SCHEDULE ON DRAWING E-604. WP WEATHERPROOF CONNECTION TO POWER PANEL IN ROOM/AREA AS NEEDED. FURNISH AND INSTALL
POWER SUPPLY CABINET WITH BATTERY CHARGER/BATTERIES (120VAC INPUT POWER, ZAM ZONE ADDRESSABLE MODULE BOXES, RACEWAYS, CABLING, SUPPORTS, DISCONNECTS, STARTERS, ETC. AS
PWR REQUIRED.
24VDC OUTPUT POWER). LOCATED ADJACENT TO EACH AIR SAMPLING SMOKE DETECTOR
ALARM/MONITORING PANEL.
JJ. SEISMIC REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS: SITE CLASS: D;
BUILDING RISK CATEGORY: III; SEISMIC DESIGN CATEGORY: C; COMPONENT
IMPORTANCE FACTOR: 1.5; AMPLIFICATION FACTORS AND COMPONENT RESPONSE
9/25/2019 5:18:24 PM

MODIFICATION FACTORS: AS REQUIRED IN ASCE 7-10 TABLE 13.6.-1 (MECHANICAL AND


ELECTRICAL) FOR COMPONENTS AND RACEWAYS AND SUPPORTS. REFER TO
ELECTRICAL SPECIFICATION 260548.16 SEISMIC CONTROLS FOR ELECTRICAL
SYSTEMS. REFER TO ELECTRICAL SPECIFICATIONS FOR SEISMIC REQUIREMENTS
FOR ELECTRICAL EQUIPMENT, SUPPORTS, ETC.

DRAWING NUMBER

E-001

ELECTRICAL
KK. ALL CONDUIT SHALL BE CONCEALED UNLESS OTHERWISE APPROVED BY ENGINEER
ON A CASE-BY-CASE BASIS.
3
SITE KEYNOTES 2656## 2657##
SITE KEYNOTES 2656## 2657##

GENERAL NOTES 2705## 2805## 2705## 2805##

265630 SMOKERS HUT SHALL BE NON-ILLUMINATED (LIGHTING/POWER 265640 TOP OF CONCRETE BASE FOR LIGHT POLE SHALL BE 0'-6" AFG.
A. FOR LIGHTING FIXTURE SCHEDULE, SEE DRAWING E-606. L. BURY COMMUNICATIONS CONDUITS A MINIMUM OF 3'-0" BFG (I.E. FOR HUT SHALL NOT BE REQUIRED). LIGHT POLE SHALL BE 15'-0"H. FOR LIGHTING POLE FOUNDATION
BELOW FROSTLINE) U.O.N. 265631 ILLUMINATE NORTH FACE OF MONUMENT SIGN. REFER TO DETAIL DETAIL, REFER TO SHEET E-802, DETAIL #5. PROVIDE 2'-0"
B. (TYPICAL) CONDUIT DEPTH SHALL BE A MINIMUM 3'-6" BFG (I.E. 3 ON SHEET SD-803 FOR SIGN DETAILS. SPACING BETWEEN EDGE OF SIDEWALK AND EDGE OF CONCRETE
BELOW FROSTLINE) U.O.N., COORDINATE DEPTH WITH PAVING M. PRIOR TO CONSTRUCTION, COORDINATE WITH CIVIL CONTRACTOR POLE FOUNDATION.
265632 SURFACE MOUNT TYPE 'EE1' LIGHTING FIXTURES ON TOP OF
DETAILS. WHERE NECESSARY TO PROVIDE FINAL GRADING COVER AT POLE CONCRETE FOUNDATION. FOR LIGHTING INSTALLATION AND 265641 TOP OF CONCRETE BASE FOR LIGHT POLE SHALL BE 0'-0" AFG (I.E.

DLZ INDIANA, LLC


BASE FOUNDATIONS, BURIED CONDUITS, ETC. FOR SUFFICIENT CONCRETE FOUNDATION DETAILS, SEE SHEET E-806 DETAILS 9 & FLUSH WITH CONCRETE WALKWAY). LIGHT POLE SHALL BE 15'-6"H.
C. ELECTRIC UTILITY COMPANY IS DUKE ENERGRY, CONTACT: TYLER GROUND COVER WHERE TOPOGRAPHY DROPS OFF STEEPLY AT 10. EMBEDDED JUNCTION BOX SHALL BE LOCATED FOR A FOR LIGHTING POLE FOUNDATION DETAIL, REFER TO SHEET E-802,
ANGLE - PHONE: 812-231-8721 - EMAIL: Tyler.Angle@duke-energy.com. EDGES OF ROADWAYS FOR DETENTION BASINS, ETC. CONCEALED WIRING CONNECTION. FOLLOW MANUFACTURER DETAIL #3. ALIGN CENTER OF POLE WITH CENTER OF ADJACENT
INSTRUCTIONS FOR EXACT PLACEMENT OF BOX PRIOR TO LINE OF PROTECTIVE CONCRETE BOLLARDS (I.E. IN LOCATION AS
D. REFER TO SITE-CIVIL DRAWINGS FOR TELEPHONE AND N. FOR DIRECT BURIED CONDUIT DETAIL, REFER TO SHEET E-XXX, CONSTRUCTION OF THE FOUNDATION. INDICATED AND SPACED AS INDICATED).
COMMUNICATIONS COMPANY CONTACT INFORMATION DETAIL X.
265633 LOCATE THE CENTERLINE OF TYPE 'EE1' FIXTURES 12'-0" FROM 265642 TOP OF CONCRETE BASE FOR LIGHT POLE SHALL BE 0'-6" AFG.
THE FRONT (NORTH) FACE OF THE MONUMENT SIGH. FIELD AIM LIGHT POLE SHALL BE 30'-0"H. FOR LIGHTING POLE FOUNDATION
E. USE RIGID GALVANIZED SLEEVES UNDER VEHICLE TRAFFIC AREAS. O. ORIENT LIGHTING POLES HANDHOLES ON THE OPPOSITE SIDE (NON- DETAIL, REFER TO SHEET E-802, DETAIL #5. LOCATE CENTERLINE
EXTEND SLEEVES 5'-0" BEYOND THE PAVED VEHICLE TRAFFIC TRAFFIC SIDE) OF PAVED ROADWAYS/PARKING AREAS U.O.N. TYPE 'EE1' LIGHTING FIXTURES TO PROVIDE EVEN ILLUMINATION
OF THE ENTIRE FACE OF THE MOMUMENT SIGN. FIELD AIM EACH OF LIGHTING POLE FOUNDATION 5'-0" FROM THE EDGE OF THE
AREAS. PAVED PARKING LOT.
P. FOR BUILDING EXTERIOR, PERIMETER/COURTYARD/CANOPY FIXTURE AT THE CENTER HEIGHT OF THE LOWER PORTION OF THE
SIGN FOR INITIAL AIMING; FIELD ADJUST AS NECESSARY TO 265643 PROVIDE 2'-0" SPACING BETWEEN EDGE OF SIDEWALK (I.E.
F. CONTRACTOR SHALL FIELD COORDINATE (ON-SITE) PRIOR TO LIGHTING, REFER TO SHEET E-301-A THROUGH E-301-E. ALSO REFER
OBTAIN EVEN ILLUMINATION ON THE ENTIRE SIGN FACE SIDEWALK ADJACENT TO THE EAST SIDE OF THE CONCRETE POLE
CONSTRUCTION WITH ELECTRIC UTILITY, TELEPHONE UTILITY AND TO ARCHITECTURAL FACADE ELEVATION PLANS.
(APPROXIMATELY 25-30 FC AVERAGE VERTICAL). ADJUST AIM TO FOUNDATION) AND EDGE OF CONCRETE POLE FOUNDATION.
CABLE TV UTILITY TO FIELD COORDINATE EXACT UTILITY
MAXIMIZE DARK SKIES, USE LIGHT METER AND MEASURE/RECORD 265644 LIGHTING POLE SHALL BE CONFIGURED FOR TWO (2) LIGHTING
REQUIREMENTS. Q. REFER TO SECURITY ELECTRONICS DRAWINGS FOR DETAILED POINT BY POINT MEASUREMENTS ON SIGN FACE. SUBMIT TO
SECURITY ELECTRONICS (SE) CABLING REQUIREMENTS FOR SE FIXTURES [I.E. ONE (1) ARM/LIGHTING FIXTURE AS INDICATED AND
ENGINEER FOR FINAL APPROVAL OF AIMING PRIOR TO ONE (1) FUTURE ARM/FUTURE LIGHTING FIXTURE ORIENTED 180
G. REFERENCE DRAWING SD-401 FOR LOCATIONS OF INCOMING CONDUIT ROUTINGS INDICATED THIS SHEET (I.E. FIBER OPTIC CONSTRUCTION COMPLETION.
UTILITIES. CABLING FOR CAMERAS, CARD READERS, INTERCOMS, ETC). REFER DEGREES APART FOR ILLUMINATION OF FUTURE VISITOR PARKING
TO SHEET ES-300 AND ES-301 FOR SE RISER DIAGRAMS AND SHEET 265635 FURNISH AND INSTALL CONDUIT SLEEVE 5'-0" BEYOND THE LOT]. PROVIDE POLE WITH ALL NECESSARY PROVISIONS TO
H. ROUTINGS ARE DIAGRAMMATIC. FIELD COORDINATE EXACT ES-400 FOR SE CABLE SCHEDULE. LIGHTING POLE FOUNDATION FOR FUTURE USE (I.E. FUTURE ACCOMODATE THE FUTURE ARM/FUTURE LIGHTING FIXTURE.
ROUTINGS WITH SITE CIVIL CONTRACTOR, PRIOR TO LIGHTING/POLES). CAP CONDUIT END AND FLAG; RECORD 265645 TOP OF CONCRETE BASE FOR LIGHT POLE SHALL BE 0'-6" AFG.
CONSTRUCTION, TO AVOID UNDERGROUND UTILITIES, OBSTACLES, R. CONTRACTOR SHALL USE LONG RADIUS BENDS FOR ALL LOCATION ON ELECTRICAL RECORD DRAWINGS. FURNISH WITH LIGHT POLE SHALL BE 30'-0"H. FOR LIGHTING POLE FOUNDATION
ETC. AS REQUIRED. COMMUNICATION/SECURITY ELECTRONICS (I.E. FIBER OPTIC PULLSTRING IN CONDUIT SLEEVE. DETAIL, REFER TO SHEET E-802, DETAIL #5. LOCATE CENTERLINE R
EE
CABLING) CONDUITS. MINIMIZE BENDS BETWEEN PULL POINTS TO 265636 FURNISH AND INSTALL ELECTRICAL HANDHOLE. HANDHOLE COVER OF LIGHTING POLE FOUNDATION IN THE CENTER OF THE SHRUB CK IN
CO

SS D I A N G
I. REFER TO SITE CIVIL PLANS FOR UNDERGROUND UTILITIES, PIPING, NO MORE THAN THREE (3) 90 DEGREE BENDS; SHALL BE LABELED "ELECTRICAL". FOR ELECTRICAL HANDHOLE BED IN LOCATION AS INDICATED.

I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC
STRUCTURES, RIGHT OF WAYS, PROPERTY LINES, ETC. COORDINATE/COMPLY WITH CABLING MANUFACTURERS PULLING DETAIL, REFER TO SHEET E-802, DETAIL 2. MINIMIZE SPLICES

E
265646 PROVIDE 2'-0" SPACING BETWEEN EDGE OF SIDEWALK (I.E.

I S T ER
TENSION REQUIREMENTS PRIOR TO INSTALLATION. WITHIN HANDHOLE UNLESS OTHERWISE APPROVED BY ENGINEER. SIDEWALK ADJACENT TO THE WEST SIDE OF THE CONCRETE POLE

No.
265632 265633 265690 J. CONTRACTOR SHALL PATCH AND REPAIR ALL SURFACES 265637 LOCATE THE CENTERLINE OF TYPE 'SH' FIXTURES 1/3 OF THE FOUNDATION) AND EDGE OF CONCRETE POLE FOUNDATION.
DISTURBED TO MATCH NEW, ADJACENT SURFACES UNLESS S. FOR SITE ELECTRICAL DEMOLITION WORK, REFER TO SHEETS

EG
HEIGHT OF THE FLAG POLE AWAY FROM FLAG POLE. FIELD AIM

IN
EE1 265647 PROVIDE 2'-0" SPACING BETWEEN EDGE OF BENCH (I.E. BENCH

IN
E2HA-20 OTHERWISE NOTED. FIELD COORDINATE UNDERGROUND ROUTINGS SD-102 AND SD-103 FOR DETAILED REQUIREMENTS. FIXTURE TO PROVIDE EVEN ILLUMINATION ON THE FLAG AT
R
ADJACENT TO THE SOUTH SIDE OF THE CONCRETE POLE RV
WITH STIE CIVIL CONTRACTOR, PRIOR TO CONSTRUCTION, TO HALF-STAFF AND FULL-STAFF HEIGHT. MOUNT FIXTURE ON FOUNDATION) AND EDGE OF CONCRETE POLE FOUNDATION. MA FE

BE
MINIMIZE PATCH AND REPAIR WORK. T. AT BASE OF EACH LIGHTING POLE HANDHOLE, CONTRACTOR SHALL CONCRETE FOOTER; INSTALL FOOTER PER MANUFACTURER P RO
S PROVIDE BAYONET BUSE(S), INSULATING LINK, AND INSULATED 265650 FURNISH AND INSTALL COMMUNICATION HANDHOLE. HANDHOLE
RECOMMENDATIONS. LIGHT FIXTURE MANUFACTURER SHALL
MONUMENT SIGN K. BURY GROUNDING ELECTRODE CABLE A MINIMUM OF 30" B.F.G. PER COMPRESSION FITTING ASSEMBLY. REFER TO DETAILS #3, #7, #11 COVER SHALL BE LABELED "FIBER OPTIC". FOR COMMUNICATION
PROVIDE LIGHTING CALCULATION INDICATING EXACT FIXTURE
NEC. AND #12 ON DRAWING E-806. HANDHOLE DETAIL, REFER TO SHEET E-802, DETAIL 2. SPLICES
LOCATION AND AIMING REQUIREMENTS PRIOR TO FIXTURE
265631 SHALL NOT BE ACCEPTABLE WITHIN HANDHOLE.
PROCUREMENT. REFER TO SHEET SD-802, DETAIL 7 FOR FLAG FI
C
POLE DETAIL. 265651 CAP CONDUIT END AND PROVIDE PULLSTRING IN CONDUIT. FLAG
265635 BE BE BE BE LOCATION AND RECORD ON RECORD DRAWINGS. CONDUIT
BE 265638 TOP OF CONCRETE BASE FOR LIGHT POLE SHALL BE 2'-6" AFG. RESERVED FOR FUTURE NORTHEAST PARKING LOT (I.E. FUTURE
SB 265638 #8 SB 265638 #8 SB 265638 LIGHT POLE SHALL BE 30'-0"H. FOR LIGHTING POLE FOUNDATION FIBER OPTIC CABLE FOR FUTURE SECURITY CAMERAS).
E2HA-22 E2HA-22 E2HA-22 DETAIL, REFER TO SHEET E-802, DETAIL #5. PROVIDE 3'-0"
265691 265691 265691
SPACING BETWEEN EDGE OF PAVED ROADWAY/PARKING LOT AND 265652 ROUTE CONDUIT UP TO NEMA 4X SECURITY ELECTRONICS
EDGE OF CONCRETE POLE FOUNDATION. ENCLOSURE. REFER TO SE RISER DIAGRAM REFER TO SECURITY
#8 ELECTRONICS (SE) RISER ON SHEET ES-300 FOR DETAILED
BE REQUIREMENTS. FURNISH AND INSTALL ALL NECESSARY
RACEWAYS, SLEEVES, J-BOXES, AND ELECTRICAL

BE
265635 APPURTENANCES AS REQUIRED FOR SE EQUIPMENT (I.E.
CAMERAS, CARD READERS, INTERCOMS) LOCATED AT ENTRY/EXIT
FUTURE GATE. REFER TO SE SERIES SHEETS FOR DETAILED
SA REQUIREMENTS. FIELD COORDINATE EXACT LOCATIONS FOR ALL
E3H-7 265651 NORTHEAST
SB PARKING LOT SE/GATE EQUIPMENT WITHIN THIS AREA WITH SE/GATE VENDORS
BE

265638 E2HA-22 PRIOR TO CONSTRUCTION.


265685 #10
265638 265653 ROUTE CONDUITS FOR SECURITY ELECTRONICS (SE) CABLES (I.E.
265691 FIBER OPTIC CABLES) UP TO SQE#1 (IN SECURITY ROOM C1079).
265666 CAP SPARE CONDUITS (WITH PULLSTRINGS) AND LABEL. REFER
TO SE RISER DIAGRAM ON SHEET ES-300 FOR DETAILED SE

O
HH-E2 CABLING REQUIREMENTS.

BF
DETENTION 265656 #1/0 CU GROUND LOOP IN FOOTING TRENCH FOR BUILDING
3 265636
BASIN

BE
GROUND. LOCATE 2'-6" BELOW FINISHED GRADE. BOND TO
265636 265724 BUILDING REBAR.
BE

#8 HH-E14 265650 265652 BE 265657 GROUND TEST WELL, REFER TO DETAIL #5, DRAWING E-803.
#8 HH-C2 265658 #1/0 CU GROUNDING ELECTRODE CABLE FROM GENERATOR TO
BE 265692 MAIN BUILDING GROUND BUS BAR #1 IN MECHANICAL #C1056.
SB 265725

O
265635 3 265644 BF LOCATE 2'-6" BELOW FINISH GRADE.
E2HA-22

BF
265636 #10 265642 #8 O ENTRY/EXIT 265659 POST INDICATOR VALVE (P.I.V.) REFER TO DRAWING SD-401-D FOR
BE

BE
265638 HH-E1 GATE #2 EXACT LOCATION. FURNISH AND INSTALL 3/4"C. BETWEEN P.I.V.
265691 SC BE AND ELECTRICAL #C1054 FOR FIRE ALARM CONNECTION BETWEEN
265692 E2HA-24 SB P.I.V. AND FIRE ALARM CONTROL PANEL (FACP-1), PROVIDE
265642 E1HA-12 CABLES AS REQUIRED.
BE

265638

BE
BE 265638 265660 (3)-4"C. FROM EXISTING UTILITY POLE TO MAIN DATA FRAME ROOM
SC 265703

O
BE

BF 265691 #B1060 FOR UTILITY COMMUNICATIONS FEEDS, ONE FIBER OPTIC 3

BF
265685 E2HA-24 O
SB VOIP/DATA, ONE FOR CATV AND ONE FOR 100-PAIR POTS LINES.
SB 265638

BE
280541 E2HA-22 COORDINATE EXACT LOCATION WITH OTHER TRADES BEFORE
E3H-7 265692 280541 #10 ROUGH-IN. FURNISH WITH PULLSTRINGS AND MARKER TAPES.

O
265645

BF
265661 RACEWAY #10A, REFER TO ONE-LINE DIAGRAM, DRAWING E-601.
265646
265652 FURNISH WITH PULLSTRING AND MARKER TAPE. COORDINATE

BE
HH-C5 BFO 280540 EXACT ROUTING WITH UTILITY.
265724 #10 280542 SC
265650 BE 265642 E2HA-24 265662 RACEWAY #10B, REFER TO ONE-LINE DIAGRAM, DRAWING E-601.
HH-E13 265723 265643 FURNISH WITH PULLSTRING AND MARKER TAPE. COORDINATE
BE
BFO

SD 320 BE
265636 265644 EXACT ROUTING WITH UTILITY.
E2HA-24 E2PB-39 BF
BE 265692 O 265666 FURNISH AND INSTALL CONDUIT SLEEVE 5'-0" BEYOND THE
ENTRY/EXIT #8
GATE #1 BE DETENTION HANDHOLE FOR FUTURE USE (I.E. FUTURE LIGHTING FOR FUTURE
SA
BE

E2HA-22 265710 VISITOR BASIN EXTENSION/ADDITION TO NEW YARD/YARD FENCING TO BE


#10 #8
PARKING LOT 319 INSTALLED). CAP CONDUIT END AND FLAG; RECORD LOCATION ON
BE #10 ELECTRICAL RECORD DRAWINGS. FURNISH WITH PULLSTRING IN
3 SC E2PB-37
CONDUIT SLEEVE.

09/12/19
09/26/19
265638

DATE
265691 265692 E2HA-24
#10 BE 265667 WALL MOUNT PHOTOCELL 12'-0" AFG (FIELD COORDINATE EXACT
PROTECTIVE
BE

265645 MOUNTING HEIGHT TO MATCH HEIGHT OF ADJACENT LIGHTING

BE
CONCRETE #10 280540
SD

O
BE
BE 280542 FIXTURES AS INDICATED ON ARCHITECTURAL

BF
BOLLARD (TYP) E2HA-24 ELEVATIONS/ELECTRICAL LIGHTING PLANS). FOR PHOTOCELL
#10 265642 BF EXISTING UTILITY
O #8 WIRING DETAILS, REFER TO EXTERIIOR LIGHTING WIRING
265644 POLE 'UP-3' DIAGRAMS ON SHEET E-807.
S BE #10 265692
3 HH-E7 280541 265668 REFER TO LIGHTING PLANS FOR DETAILED LOCATIONS OF
265710 BC BC BC
265636

REVISION
#10 TIMECLOCK, LIGHTING CONTACTORS, AND GENERATOR TRANSFER
SB 265660 265660 DEVICE; LOCATE THESE ELECTRICAL ITEMS ADJACENT TO ONE
#10
BE

BE
265692 E2HA-22 ANOTHER IN LOCATIONS AS INDICATED ON LIGHTING PLANS. FOR

1 Addendum #01
3 Addendum #03
#10 265710 #10
265641
BE

265638 EXTERIOR LIGHTING CONTROL WIRING DETAILS, REFER TO


#8 BE
SG (TYP.6 FLAG SPOTS) 265691 EXTERIOR LIGHTING WIRING DIAGRAMS ON SHEET E-807.
#10 E2HA-24
BE 265690 SD 265669 2 #10, #10G., 1"C (TYPICAL FOR ENTIRE CIRCUIT; I.E - ALL CIRCUIT

BF O BC
#8 SEGMENTS).
E2HA-24 265702
SG 280540 265670 2 #8, #10G., 1"C (TYPICAL FOR ENTIRE CIRCUIT; I.E - ALL CIRCUIT
DETENTION 265645

O
SJ

BF
265640 E2HA-24
BE

BE
BASIN 265692 265638 SEGMENTS).

BE

NO.
265692 E2HA-20
BE

SJ 265637 280542 265672 1#18 TWPR, 3/4"C.


SE
E2HA-20 25'H FLAGPOLE 318 265685 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
BFO

E1HA-10
SG 265640 265692 E1PB-66 PHOTOCELL. REFER TO DETAIL #3 ON SHEET E-807. CONTROL VIA
BE

SJ #10 317 CONTACTOR #LC3B.


E2HA-24
25'H FLAGPOLE SJ E2HA-20 265690 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
BFO

CHK'D: MLH
265637 E2HA-20 PHOTOCELL. REFER TO DETAIL #2 ON SHEET E-807. CONTROL VIA
BE
BE

SEPTEMBER 5, 2019
265691 265692
265709 #8 BE CONTACTOR #LC2B.

1663-1190-90
265638 265640

BC
SJ

BE
30'H FLAGPOLE #10 #8
SA SG 265691 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND

BF E
HH-C4 BFO 265637 E2HA-20 SJ

B
265670 E2HA-22 #10 E2HA-24 PHOTOCELL. REFER TO DETAIL #2 ON SHEET E-807. CONTROL VIA
BE

O
E2HA-24

265650 #10 E2HA-20 280541

O
SB SB CONTACTOR #LC2C.

PROJECT NUMBER
BF
E3H-7 SH #10
BE

3 #10 E1HA-12 265692 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND


BE

MLH
DESIGNED: TKF
E2HA-24 HH-E4
SG

BFO BE
BE

BFO 280541

BFO

DRAWN: RDW
265635 BE 265692 PHOTOCELL. REFER TO DETAIL #2 ON SHEET E-807. CONTROL VIA
265638 BE BE #10 265636 #10 265638 CONTACTOR #LC2D.
265692 265669 BE
265640

BE
265685 SB #10 SA #10 265710 #10 EMPLOYEE 265703

APPRV'D:
265638 265638 265640 #10 265709 265695 6#10, #10G., 1"C.
E3H-7 E3H-7 265647 265667 265650 BFO PARKING LOT
265685 265685 (TYP.) 265696 2#10, 2#8, #10G., 1"C.

DATE:
BC BC BC 265656
BF

265669 PC2 PC PC PC1 HH-C7 3 265692 265702 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
O

BE
G G G 265640 PHOTOCELL. REFER TO DETAIL #1 ON SHEET E-807. CONTROL VIA
BE

(TYP.) 265656
CONTACTOR #LC1B.
BE

265672 HH-C1 SG
BE

BC G 265656

BFO
265669 265709 G 265696 E2HA-24 265702 265703 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
#10 265650
BE

HH-E6 265669 G G 265638 PHOTOCELL. REFER TO DETAIL #1 ON SHEET E-807. CONTROL VIA

BE
TC2 TC1
265656 265636 (TYP.) G 280540 CONTACTOR #LC1C.
HH-C6

VIGO COUNTY SECURITY CENTER


BE

265650 G 280542 265704 RACEWAY #100, REFER TO ONE-LINE DIAGRAM, DRAWING E-601.
316
BFO G FURNISH WITH PULLSTRING AND MARKER TAPE.
265669 265660 HH-C3 SE E1PB-64
265709 265705 RACEWAY #105 AND #315, REFER TO ONE-LINE DIAGRAM, DRAWING
265656 265695 E1HA-10
(TYP.) G G 315 E-601. FURNISH WITH PULLSTRING AND MARKER TAPE.
BC

G 265706 FURNISH AND INSTALL (1)-1"C. FROM MECHANICAL #C1053 TO

ELECTRICAL SITE PLAN (NORTH)


265667 G 3 SMOKER'S HUT FOR FUTURE POWER/LIGHTING. FURNISH WITH
#10 EXISTING UTILITY
G #8 PULLSTRING AND MARKER TAPE. STUB AND CAP BELOW
BFO

BE

PC3 265656 3 POLE 'UP-1' SMOKER'S HUT. STUB UP AND CAP BELOW PANEL 'E1PA' IN
265656
BE

PC G 3 #10 265709 MECHANICAL ROOM.


G G G 3

BE
3 265709 3#10, #10G., 3/4"C. FOR SECURITY CAMERA CIRCUITRY.

BE
265672 E2PB E2HA 265709 265709 265710 2#10, #10G., 3/4"C. FOR SECURITY CAMERA CIRCUITRY.
BE BE G 265702

TERRE HAUTE, INDIANA


265696 265704 265706 265669 265661 265723 2#8, #10G., 3/4"C. (CIRCUIT E3PA-33) FOR GATE CONTROLLER.
G
BE

TC3 265668 265640 265702


265709
BFO

265636 SG 265640 265724 ROUTE CONDUIT UP TO NEMA 4X SECURITY ELECTRONICS


265668 E1HA G
HH-E5 E1HA-10 #10 #10 ENCLOSURE. REFER TO SE RISER DIAGRAM REFER TO SECURITY
L1H SG
DETENTION 265656 BE BE BE ELECTRONICS (SE) RISER ON SHEET ES-300 FOR DETAILED
E1HA-10
BC

BASIN BE BE REQUIREMENTS. FIELD COORDINATE EXACT LOCATION FOR

A NEW
DM BE BE SMOKER'S HUT SE/GATE EQUIPMENT WITHIN THIS AREA WITH SE/GATE VENDORS
BFO

#8 E3H BE
DP-L E1PB BE 265630 PRIOR TO CONSTRUCTION.
265670
#8 265668 265705 265725 2#8, #10G., 3/4"C. (CIRCUIT E2PB-41) FOR GATE CONTROLLER.
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

265657

BE
E3PA BE BE BE 270503 FURNISH AND INSTALL (1)-2"C. FROM BELOW COUNTER AREA OVER
MAIN DATA
CH-1

ROUTE TO SQE#1 CH-2


G FRAME #8 HOT AIR DISCHARGE 265661 265662 TO CHASE AND STUBBED OUT AT +12" A.F.F. FOR FUTURE
DM 265653 #8 HH-E12 COMMUNICATIONS CABLING. FURNISH WITH PULLSTRING.
BE

BE

B1060 BE
BE BE 265636 280540 CCTV EQUIPMENT ENCLOSURE AT BASE OF POLE. FURNISH AND
BFO BFO BFO BFO SC SC 265703 SC #8 INSTALL 120VAC POWER TO ENCLOSURE. CONNECT TO CIRCUIT
270503 265638
E1HA-12 265638 E1HA-12 265638 E1HA-12 #8 SHOWN USING 2#12+G. IN 3/4"C. REFER TO SECURITY DRAWINGS
265703 GROUND MOUNTED FOR ENCLOSURE INFORMATION.
265658

BE
G G G G LOAD BANK
265656 #8 280541 FURNISH AND INSTALL (1) 6-FIBER, 50 MICRON, MULTI-MODE,
HH-E3 BE BE 265723 SB
265656 UTILITY OUTDOOR DIRECT BURIAL FIBER CABLE LIKE WEST PENN
265636 SB #8 #8 #8 #8 265670 G #8 E1HA-12
G G 265658 TRANSFORMER 265662 #WP9C240T DAISY CHAINED TO EACH CAMERA FROM SECURITY

BE
E3H-7 (TYP.) G ELECTRONICS ROOM #C1079. REFER TO SECURITY DRAWINGS FOR
'UT-1' 265638
265638 MORE INFORMATION.

BE
SA 265703
265685 SC 265703
E3H-7 280542 SECURITY CAMERA(S) TO BE MOUNTED ON POLE WITH BOTTOM AT
265635 265638 E1HA-12 265638 265635 +15' AFG. REFER TO SECURITY DRAWINGS FOR MORE
265685 GEN-1 GEN-2 GEN-3 FUTURE BE INFORMATION.
GEN-4 SC

BE
E1HA-12 #8 265659
G
265638 BE
9/25/2019 5:19:09 PM

265656 G 265656
270503
G

FOR CONTINUATION, FOR

DRAWING NUMBER
FOR OC OC
FOR CONTINUATION, FOR CONTINUATION, SEE E-102 CONTINUATION,

E-101
CONTINUATION,

ELECTRICAL
SEE E-102 SEE E-102 SEE E-102 SEE E-102

1 ELECTRICAL SITE PLAN (NORTH)


E-101 SCALE: 1" = 30'-0"
NORTH
GENERAL NOTES SITE KEYNOTES 2656##

A. FOR LIGHTING FIXTURE SCHEDULE, SEE DRAWING E-606. L. BURY COMMUNICATIONS CONDUITS A MINIMUM OF 3'-0" BFG (I.E. 265634 (BASE BID) (IF SOUTH LOOP IS AN UNPAVED ROADWAY) -
BELOW FROSTLINE) U.O.N. PROVIDE CONDUIT SLEEVE (WITH PULLSTRING) FROM LIGHTING
B. (TYPICAL) CONDUIT DEPTH SHALL BE A MINIMUM 3'-6" BFG (I.E. POLE TO 5'-0" FROM LIGHTING POLE AND CAP CONDUIT; FLAG
BELOW FROSTLINE) U.O.N., COORDINATE DEPTH WITH PAVING M. PRIOR TO CONSTRUCTION, COORDINATE WITH CIVIL CONTRACTOR AND RECOED ON ELECTRICAL DRAWINGS. (ALTERNATE BID)
DETAILS. WHERE NECESSARY TO PROVIDE FINAL GRADING COVER AT POLE

DLZ INDIANA, LLC


LIGHTING POLE/FIXTURE. ALTERNATE BID (IF SOUTH LOOP IS
BASE FOUNDATIONS, BURIED CONDUITS, ETC. FOR SUFFICIENT PAVED ROADWAY) - FURNISH AND INSTALL CABLE CONDUIT TO
C. ELECTRIC UTILITY COMPANY IS DUKE ENERGRY, CONTACT: TYLER GROUND COVER WHERE TOPOGRAPHY DROPS OFF STEEPLY AT ALTERNATE LIGHTING POLES/FIXTURES LOCATED ALONG THE
ANGLE - PHONE: 812-231-8721 - EMAIL: Tyler.Angle@duke-energy.com. EDGES OF ROADWAYS FOR DETENTION BASINS, ETC. SOUTH LOOP (SEE SHEET E-102). REFER TO DIVISION 0 FRONT
END SPECIFICATIONS FOR DETAILED REQUIREMENTS FOR
D. REFER TO SITE-CIVIL DRAWINGS FOR TELEPHONE AND N. FOR DIRECT BURIED CONDUIT DETAIL, REFER TO SHEET E-XXX, ALTERNATES.
COMMUNICATIONS COMPANY CONTACT INFORMATION DETAIL X.
265635 FURNISH AND INSTALL CONDUIT SLEEVE 5'-0" BEYOND THE
LIGHTING POLE FOUNDATION FOR FUTURE USE (I.E. FUTURE
E. USE RIGID GALVANIZED SLEEVES UNDER VEHICLE TRAFFIC AREAS. O. ORIENT LIGHTING POLES HANDHOLES ON THE OPPOSITE SIDE (NON-
LIGHTING/POLES). CAP CONDUIT END AND FLAG; RECORD
EXTEND SLEEVES 5'-0" BEYOND THE PAVED VEHICLE TRAFFIC TRAFFIC SIDE) OF PAVED ROADWAYS/PARKING AREAS U.O.N.
LOCATION ON ELECTRICAL RECORD DRAWINGS. FURNISH WITH
AREAS.
PULLSTRING IN CONDUIT SLEEVE.
P. FOR BUILDING EXTERIOR, PERIMETER/COURTYARD/CANOPY
F. CONTRACTOR SHALL FIELD COORDINATE (ON-SITE) PRIOR TO LIGHTING, REFER TO SHEET E-301-A THROUGH E-301-E. ALSO REFER 265636 FURNISH AND INSTALL ELECTRICAL HANDHOLE. HANDHOLE
CONSTRUCTION WITH ELECTRIC UTILITY, TELEPHONE UTILITY AND TO ARCHITECTURAL FACADE ELEVATION PLANS. COVER SHALL BE LABELED "ELECTRICAL". FOR ELECTRICAL
CABLE TV UTILITY TO FIELD COORDINATE EXACT UTILITY HANDHOLE DETAIL, REFER TO SHEET E-802, DETAIL 2. MINIMIZE
REQUIREMENTS. Q. REFER TO SECURITY ELECTRONICS DRAWINGS FOR DETAILED SPLICES WITHIN HANDHOLE UNLESS OTHERWISE APPROVED BY
SECURITY ELECTRONICS (SE) CABLING REQUIREMENTS FOR SE ENGINEER.
G. REFERENCE DRAWING SD-401 FOR LOCATIONS OF INCOMING CONDUIT ROUTINGS INDICATED THIS SHEET (I.E. FIBER OPTIC 265638 TOP OF CONCRETE BASE FOR LIGHT POLE SHALL BE 2'-6" AFG.
UTILITIES. CABLING FOR CAMERAS, CARD READERS, INTERCOMS, ETC). REFER LIGHT POLE SHALL BE 30'-0"H. FOR LIGHTING POLE FOUNDATION
TO SHEET ES-300 AND ES-301 FOR SE RISER DIAGRAMS AND SHEET DETAIL, REFER TO SHEET E-802, DETAIL #5. PROVIDE 3'-0"
H. ROUTINGS ARE DIAGRAMMATIC. FIELD COORDINATE EXACT ES-400 FOR SE CABLE SCHEDULE. SPACING BETWEEN EDGE OF PAVED ROADWAY/PARKING LOT
ROUTINGS WITH SITE CIVIL CONTRACTOR, PRIOR TO AND EDGE OF CONCRETE POLE FOUNDATION.
CONSTRUCTION, TO AVOID UNDERGROUND UTILITIES, OBSTACLES, R. CONTRACTOR SHALL USE LONG RADIUS BENDS FOR ALL 265656 #1/0 CU GROUND LOOP IN FOOTING TRENCH FOR BUILDING
ETC. AS REQUIRED. COMMUNICATION/SECURITY ELECTRONICS (I.E. FIBER OPTIC GROUND. LOCATE 2'-6" BELOW FINISHED GRADE. BOND TO R
EE
CABLING) CONDUITS. MINIMIZE BENDS BETWEEN PULL POINTS TO BUILDING REBAR. CK IN
CO

SS D I A N G
I. REFER TO SITE CIVIL PLANS FOR UNDERGROUND UTILITIES, PIPING, NO MORE THAN THREE (3) 90 DEGREE BENDS;

I ON A L E N
PE60018676
D

H
265658 #1/0 CU GROUNDING ELECTRODE CABLE FROM GENERATOR TO

A
STATE OF
L . H I TC

E
STRUCTURES, RIGHT OF WAYS, PROPERTY LINES, ETC. COORDINATE/COMPLY WITH CABLING MANUFACTURERS PULLING

I ST ER
MAIN BUILDING GROUND BUS BAR #1 IN MECHANICAL #C1056.
TENSION REQUIREMENTS PRIOR TO INSTALLATION.

No.
LOCATE 2'-6" BELOW FINISH GRADE.
J. CONTRACTOR SHALL PATCH AND REPAIR ALL SURFACES
265659 POST INDICATOR VALVE (P.I.V.) REFER TO DRAWING SD-401-D

EG
DISTURBED TO MATCH NEW, ADJACENT SURFACES UNLESS S. FOR SITE ELECTRICAL DEMOLITION WORK, REFER TO SHEETS

IN
IN
FOR EXACT LOCATION. FURNISH AND INSTALL 3/4"C. BETWEEN R
OTHERWISE NOTED. FIELD COORDINATE UNDERGROUND ROUTINGS SD-102 AND SD-103 FOR DETAILED REQUIREMENTS. RV
P.I.V. AND ELECTRICAL #C1054 FOR FIRE ALARM CONNECTION
WITH STIE CIVIL CONTRACTOR, PRIOR TO CONSTRUCTION, TO
BETWEEN P.I.V. AND FIRE ALARM CONTROL PANEL (FACP-1),
MA FE
MINIMIZE PATCH AND REPAIR WORK. T. AT BASE OF EACH LIGHTING POLE HANDHOLE, CONTRACTOR SHALL P RO
PROVIDE CABLES AS REQUIRED.
PROVIDE BAYONET BUSE(S), INSULATING LINK, AND INSULATED
K. BURY GROUNDING ELECTRODE CABLE A MINIMUM OF 30" B.F.G. PER COMPRESSION FITTING ASSEMBLY. REFER TO DETAILS #3, #7, #11 265662 RACEWAY #10B, REFER TO ONE-LINE DIAGRAM, DRAWING E-601.
NEC. AND #12 ON DRAWING E-806. FURNISH WITH PULLSTRING AND MARKER TAPE. COORDINATE
EXACT ROUTING WITH UTILITY.
265663 TOP OF CONCRETE BASE FOR LIGHT POLE SHALL BE 0'-6" AFG.
LIGHT POLE SHALL BE 30'-0"H. FOR LIGHTING POLE FOUNDATION
DETAIL, REFER TO SHEET E-802, DETAIL #3. LOCATE EDGE OF
POLE FOUNDATION 5'-0" FROM THE EDGE OF THE FENCE.
265664 EXTERIOR TYPE 'SF' LIGHTING FIXTURES SHALL BE MANUALLY
FOR FOR SWITCHED FROM LOCAL TOGGLE LIGHT SWITCH; FIXTURES
FOR
CONTINUATION, CONTINUATION, SHALL ALSO BE CONTROLLED VIA LIGHTING CONTACTOR FOR
CONTINUATION,
SEE E-101 (TYP.3) SEE E-101 DUSK-TO-DAWN CONTROL. PROVIDE LABEL ON TOGGLE SWITCH
SEE E-101
FOR G 265658 FACEPLATE IDENTIFYING EXTERIOR LIGHTING ALSO
G FOR
CONTINUATION, G INTERLOCKED/CONTROLLED VIA LIGHTING CONTACTOR. YARD IS

BE
SA G CONTINUATION,
SEE E-101 E3H-7 265703 NOT NORMALLY OCCUPIED BY INMATES EXCEPT FOR AN
265638 SEE E-101 EMERGENCY EVACUATION.
265638 G SC
265685 265703 BE 265665 AVOID ROUTING UNDERGROUND ELECTRICAL WITHIN 20'-0" OF
GEN-1 GEN-2 GEN-3 FUTURE THE FUTURE POD BUILDINGS.
GEN-4 265638

BE
#8 265659 265666 FURNISH AND INSTALL CONDUIT SLEEVE 5'-0" BEYOND THE
SC
HANDHOLE FOR FUTURE USE (I.E. FUTURE LIGHTING FOR
BE FUTURE EXTENSION/ADDITION TO NEW YARD/YARD FENCING TO
265656 265656 BE INSTALLED). CAP CONDUIT END AND FLAG; RECORD
LOCATION ON ELECTRICAL RECORD DRAWINGS. FURNISH WITH
PULLSTRING IN CONDUIT SLEEVE.
G 265662
G 265667 WALL MOUNT PHOTOCELL 12'-0" AFG (FIELD COORDINATE EXACT
OC OC MOUNTING HEIGHT TO MATCH HEIGHT OF ADJACENT LIGHTING
FIXTURES AS INDICATED ON ARCHITECTURAL
ELEVATIONS/ELECTRICAL LIGHTING PLANS). FOR PHOTOCELL
WIRING DETAILS, REFER TO EXTERIIOR LIGHTING WIRING
DIAGRAMS ON SHEET E-807.
265668 REFER TO LIGHTING PLANS FOR DETAILED LOCATIONS OF

BE
TIMECLOCK, LIGHTING CONTACTORS, AND GENERATOR
TRANSFER DEVICE; LOCATE THESE ELECTRICAL ITEMS
ADJACENT TO ONE ANOTHER IN LOCATIONS AS INDICATED ON
LIGHTING PLANS. FOR EXTERIOR LIGHTING CONTROL WIRING
EXISTING UTILITY DETAILS, REFER TO EXTERIOR LIGHTING WIRING DIAGRAMS ON
G POLE 'UP-2' SHEET E-807.
G
265669 2 #10, #10G., 1"C (TYPICAL FOR ENTIRE CIRCUIT; I.E - ALL CIRCUIT
FUTURE POD FUTURE POD SEGMENTS).
UNPAVED ROAD UNPAVED ROAD
BUILDING ADDITION BUILDING ADDITION 265670 2 #8, #10G., 1"C (TYPICAL FOR ENTIRE CIRCUIT; I.E - ALL CIRCUIT
(BASE BID) (BASE BID)
265665 265665 SEGMENTS).
265671 4#10, 2#8, #10G., 1"C.
265672 1#18 TWPR, 3/4"C.
PAVED ROAD PAVED ROAD 265674 FIXTURE SHALL BE MANUALLY SWITCHED FROM LOCAL TOGGLE
(ALTERANTE BID) (ALTERANTE BID) LIGHT SWITCH, SWITCH LEG 'ZZ', IN STORAGE #E1016B; FIXTURE
SHALL ALSO BE CONTROLLED VIA LIGHTING CONTACTOR #LC4B
265656 265656 FOR DUSK-TO-DAWN CONTROL. CONNECT TO CIRCUIT SHOWN
E4H USING 2#10+G. IN 3/4"C.
265635 265668 E4PA 265675 FIXTURE SHALL BE MANUALLY SWITCHED FROM LOCAL TOGGLE
265635
SB YY LIGHT SWITCH, SWITCH LEG 'YY', IN STORAGE #E1016B; FIXTURE
265664 SB SHALL ALSO BE CONTROLLED VIA LIGHTING CONTACTOR #LC4C
E4H-39

BE
ZZ E4H-39
G G FOR DUSK-TO-DAWN CONTROL. CONNECT TO CIRCUIT SHOWN

09/12/19
09/26/19
265634 TO TC4 265634 USING 2#10+G. IN 3/4"C.

DATE
265676 265676
265672 265676 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
BE

PHOTOCELL. REFER TO DETAIL #6 ON SHEET E-807. CONTROL VIA


G G G G G

BE
CONTACTOR #LC4D.
265656 PC 265656
PC4 265685 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND

BE
265667 265671 PHOTOCELL. REFER TO DETAIL #3 ON SHEET E-807. CONTROL VIA
CONTACTOR #LC3B.
#10 265636 265703 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND

REVISION
HH-E8 PHOTOCELL. REFER TO DETAIL #1 ON SHEET E-807. CONTROL VIA
#8 BE CONTACTOR #LC1C.
SF SF SF
SF

1 Addendum #01
3 Addendum #03
ZZ ZZ YY 265711 MUFFIN MONSTER MANHOLE WITH CONTROL PANEL, 5HP, 480V,
FUTURE YARD FOR WEST YARD YY EAST YARD FUTURE YARD FOR
E4H-35 E4H-35 E4H-37 3-PHASE. REFER TO SPECIFICATIONS AND CIVIL PLANS FOR
FUTURE POD E4H-37 FUTURE POD
265663 265663 265663 #8 DETAILED REQUIREMENTS. CONNECT CONTROL PANEL TO
265663

BE
265674 265674 #10 265675 CIRCUIT E4H(32,34,36) USING 3#10+G. IN 3/4"C. PROVIDE
265675 CONNECTION BETWEEN CONTROL AND MUFFIN MONSTER PER
#10
BE

#10

BE
3 MANUFACTURER'S RECOMMENDATION. COORDINATE EXACT
265676 3 LOCATION OF MUFFIN MONSTER AND CONTROL PANEL BEFORE

NO.
BE

BE

BE

BE
265634 ROUGH-IN.
SA #10 SF SF 265712 MUFFIN MONSTER DISCONNECT, HEAVY DUTY 600VAC, 30A,
SF SF

BE
265674 ZZ 265674 ZZ (TYP.) 265675 YY 265675 YY 265636 265676 3-POLE NON-FUSED DISCONENCT SWITCH IN NEMA 3R
E4H-39
265663 E4H-35 265663 E4H-35 265669 265663 E4H-37 #10 265663 E4H-37 HH-E9 265634 C IF

ENCLOSURE. DISCONNECT TO BE LOCATED ADJACENT TO


#8 MUFFIN MONSTER CONTROL PANEL, PROVIDE UNI-STRUT

CHK'D: MLH
265666 265713 SA
BE BE BE BE BE BE 265666

SEPTEMBER 5, 2019
BE E4H-39 SUPPORTS AS NEEDED. MOUNT INDEPENENT OF COONTROL
HH-E10 #10

1663-1190-90
#10 #10 265669 PANEL WITH TOP AT +6'-0" AFG. VERIFY EXACT LOCATION OF
265636 BE BE BE CONTROL PANEL BEFORE ROUGH-IN. CONNECT TO CIRCUIT AS
(TYP.) #10 #10 SHOWN USING 3#10+G. IN 3/4"C.
265713 E4PA-44

PROJECT NUMBER
BE
265713 5#10, 2#10G., 1"C. FOR GRINDER AND RECEPTACLE CIRCUITRY.
BE

W.P. 265717

MLH
DESIGNED: TKF
265670 GFCI BE 265717 FURNISH AND INSTALL (1) 20A, DUPLEX GFCI RECEPTACLE IN
265676 SB

DRAWN: RDW
SB 265676 SB 265676 265676 SB WEATHERPROOF ENLCOSURE. RECEPTACLE TO BE MOUNTED
#8 265634 265634 (TYP.) 265634 E4H-39 265634 E4H-39
E4H-39 E4H-39 BELOW DISCONNECT, PROVIDE UNI-STRUT SUPPORTS AS

APPRV'D:
BE BE BE BE BE BE BE BE NEEDED. CONNECT TO CIRCUIT SHOWN USING 2#10+#10G. IN
HH-E11 #8 1"C., REFER TO KEYNOTE #265713 THIS SHEET.

DATE:
#8 265670 #8 #8 265670 #8 265712
265636 MUFFIN MONSTER CONTROL
(TYP.) (TYP.) E4H(32,34,36) PANEL NEW MANHOLE, SEE
SITE-CIVIL PLANS
265711

VIGO COUNTY SECURITY CENTER


C
1 ELECTRICAL SITE PLAN (SOUTH)
E-102 SCALE: 1" = 30'-0"
NORTH

ELECTRICAL SITE PLAN (SOUTH)


TERRE HAUTE, INDIANA
A NEW
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt
9/25/2019 5:20:14 PM

DRAWING NUMBER

E-102

ELECTRICAL
GENERAL NOTES
A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702, E-703,
E-704, E-705, E-706 AND E-707.

B. SEE MECHANICAL EQUIPMENT - ELECTRICAL CONNECTIONS


SCHEDULE ON DRAWINGS E-604 & E-605 FOR EQUIPMENT

DLZ INDIANA, LLC


CIRCUITING AND ADDITIONAL ELECTRICAL EQUIPMENT
REQUIREMENTS FOR MECHANICAL EQUIPMENT (I.E. DISCONNECT,
STARTER, ETC) AND EQUIPMENT NAMEPLATE ELECTRICAL LOAD
INFORMATION (I.E. VOLTS, PHASE, FLA, MOCP, ETC.).
2 3 4 1 2 3 4
C. CONTRACTOR SHALL FIELD COORDINATE, PRIOR TO
CONSTRUCTION, EXACT MOUNTING HEIGHTS AND LOCATIONS FOR
WIRING DEVICES WITH THE CASEWORK SHOP DRAWINGS AND
ARCHITECTURAL ELEVATIONS AND DETAILS.

E3PA-20 D. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND


E3PA-20 CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
AND OFFSET BACK TO BACK BOXES.

E. REFER TO SECURITY DRAWINGS, #SE SERIES, FOR ADDITIONAL


EQUIPMENT AND WIRING REQUIREMENTS. PROVIDE BOXES,
RACEWAYS, CABLING, SUPPORTS, ETC. AS REQUIRED FOR
SECURITY EQUIPMENT. REFER TO SPECIFICATION SECTIONS 078123
EVIDENCE "INTUMESCENT FIREPROOFING" AND 078443 "JOINT FIRESTOPPING"
A2001 FOR DETAIL FIRESTOP REQUIREMENTS.
EVIDENCE 3
3 F. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO R
A2001 SPECIFICATION 079200 "JOINT SEALANTS" FOR DETAILED EE
CK IN
REQUIREMENTS FOR SEALANT(S). CO

SS D I A N G
I ON A L E N
PE60018676
D

H
260550 260550

A
STATE OF
L . H I TC

E
I ST ER
SQE#5 SQE#5 G. WATER MANAGEMENT SYSTEM TO BE PROVIDED BY OTHERS.

No.
U2R-27 U2R-27 CONNECT ALL VALVE CONTROLLERS AS FOLLOWS:
IN AREA B TO CIRCUIT E2PA-36, E2PB-31, E2PC-31 OR E2PE-21.

EG

IN
IN AREA C TO CIRCUIT K1L-7.

IN
E3PA-20 R
E3PA-20 IN AREA D TO CIRCUIT E4PA-37, E5PA-45 OR E5PB-41. RV
MA FE
IN AREA E TO CIRCUIT E4PA-39, E4PB-41 OR E5PA-47. P RO
EACH CIRCUIT TO BE 2#12+G. IN 3/4"C. REFER TO CELL VALVE
E3PA-20 E3PA-20 CONTROLLER (CVC) CONNECTION DETAIL #5 ON SHEET E-804.
COORDINATE CONTROLLER LOCATIONS BEFORE ROUGH-IN.

OPEN
STORAGE
VEHICLE
SALLYPORT
OPEN
STORAGE POWER KEYNOTES 2605##
A2000 A1000 A2000
E3PA(27,29)
3 260501 FURNISH AND INSTALL POWER (20A, 120V) AND CONTROL WIRING
EUH-1
E3PA-27,29 K K FOR OVERHEAD DOOR CONTROLLERS. DOOR SAFETIES/LIMIT
SWITCHES AND KEYED OPEN-STOP-CLOSE PUSHBUTTON
EUH-1 E3PA-20 E3PA-20 CONTROLLER STATIONS (WHERE INDICATED) FURNISHED BY
OVERHEAD DOOR EQUIPMENT VENDOR. REFER TO
SPECIFICATION 083613 "SECTIONAL DOORS" FOR DETAILED
REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT SWITCHES,
DOOR STARTER/CONTROLLER, AND PUSHBUTTON CONTROL
STATION PER MANUFACTURERS RECOMMENDATION. FURNISH
AND INSTALL ALL CABLING/CONDUIT REQUIRED FOR COMPLETE
SYSTEM. FIELD-COORDINATE THE EQUIPMENT INSTALLATION AND
CABLING/CONDUIT REQUIREMENTS WITH THE DOOR EQUIPMENT
VENDOR PRIOR TO CONSTRUCTION.
260502 OVERHEAD DOOR SAFETY INTERLOCK DEVICES FURNISHED BY
OVERHEAD DOOR VENDOR, INSTALLED BY CONTRACTOR.
260503 OVERHEAD DOORS TO BE CONTROLLED FROM REMOTE
CONTROL PANEL IN MASTER CONTROL #B1016. FURNISH AND
INSTALL CONTROL WIRING AS NEEDED BETWEEN DOOR AND
CONTROL PANEL IN 3/4"C. PER MANUFACTURER'S
RECOMMENDATION. VERIFY EXACT LOCATION OF CONTROL
PANEL BEFORE ROUGH-IN.
M M 260504 FURNISH AND INSTALL CONDUIT (3/4"C.) FROM EACH DOOR
STARTER/CONTROLLER TO SECURITY CONTROL PANEL FOR
ACCESS CONTROL WIRING. WIRING AND TERMINATIONS BY
OTHERS. REFER TO SECURITY SERIES SHEETS FOR DETAILED
WIRING REQUIREMENTS.
260505 FURNISH AND INSTALL POWER (1/8HP, 120V) FOR SLIDING DOOR
CONTROLLERS, DOOR SAFETIES/LIMIT SWITCHES AND KEYED
OPEN-CLOSE PUSHBUTTON CONTROL STATIONS FURNISHED BY
DOOR EQUIPMENT VENDOR. CONTROL WIRING BY OTHERS.
REFER TO SPECIFICATION 087100 "DOOR HARDWARE" FOR
DETAILED REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT
SWITCHES AND CONTROL SWITCH(S) PER MANUFACTURERS
RECOMMENDATION. FURNISH AND INSTALL CONDUIT/POWER
WIRING REQUIRED FOR A COMPLETE SYSTEM.
FIELD-COORDINATE THE EQUIPMENT INSTALLATION AND
3 CONDUIT REQUIREMENTS WITH THE DOOR EQUIPMENT VENDOR
3 PRIOR TO CONSTRUCTION.
260510 EQUIPMENT TO BE MOUNTED ON CONCRETE PAD, REFER TO
STRUCTURAL DRAWING S-530, DETAILS #8 AND/OR #9 FOR
4 MEZZANINE FLOOR POWER - AREA 'A' ALTERNATE 2 MEZZANINE POWER PLAN - AREA 'A' BASE BID CONCRETE PAD INSTALLATION DETAIL.
E-201-A SCALE: 1/8" = 1'-0" E-201-A SCALE: 1/8" = 1'-0" 260518 KEYED OVERHEAD DOOR OPEN-CLOSE-STOP PUSHBUTTON
CONTROL STATIONS FURNISHED BY OVERHEAD DOOR VENDOR.
NORTH NORTH MOUNT TOP OF CONTROL STATION AT +48" AFF. COORDINATE
EXACT LOCATIONS WITH OWNER PRIOR TO CONSTRUCTION.
WIRE PER MANUFACTURER'S RECOMMENDATION.

09/26/19
DATE
260532 FURNISH AND INSTALL POWER (20A, 120V) AND CONTROL WIRING
FOR OVERHEAD COILING DOOR CONTROLLERS. DOOR
SAFETIES/LIMIT SWITCHES FURNISHED BY OVERHEAD DOOR
EQUIPMENT VENDOR. REFER TO SPECIFICATION 083323
"OVERHEAD COILING DOORS" FOR DETAILED REQUIREMENTS.
INSTALL DOOR SAFETIES/LIMIT SWITCHES AND DOOR
STARTER/CONTROLLER PER MANUFACTURERS
RECOMMENDATION. FURNISH AND INSTALL ALL

REVISION
2 E3PA-16 3 4 E3PA-14 1 E3PA-16 2 E3PA-16 3 4 E3PA-14 CABLING/CONDUIT REQUIRED FOR COMPLETE SYSTEM.
W.P. W.P. W.P. W.P. W.P. FIELD-COORDINATE THE EQUIPMENT INSTALLATION AND

3 Addendum #03
GFCI 260502 260502 GFCI E2PB-25 GFCI GFCI 260502 260502 GFCI E2PB-25 CABLING/CONDUIT REQUIREMENTS WITH THE DOOR EQUIPMENT
VENDOR PRIOR TO CONSTRUCTION.
E2PB-27 E2PB-27
E3PA-14 E3PA-14 E3PA-16 E3PA-14 E3PA-14 260545 CORD REEL WITH LED HEAD, 120V, 13A, LIKE REEL CRAFT
E3PA-16 E3PA-16
E3PA-16 *,GFCI+48" *,GFCI+48" *,GFCI+48" 260502 260502 *,GFCI+48" *,GFCI+48" #L-4035-163-10 OR APPROVED EQUAL. FURNISH WITH 35' TYPE
*,GFCI+48" *,GFCI+48"
*,GFCI+48" 260518 E3PA-14 E2PB-27 260518 E3PA-14 E2PB-27 SJTOW CORD AND #600626 UNIVERSAL SWING WALL MOUNTING
*,GFCI+48" USB+42" *,GFCI+48" USB+42" BRACKET. MOUNT ON WALL WITH BOTTOM AT +7'0" AFF.
E3PA-18 3 COORDINATE EXACT LOCATION WITH OWNER BEFORE ROUGH-IN.

NO.
E3PA-18
GFCI+48"
260550 WALL MOUNTED SECURITY RACK, REFER TO SE DRAWINGS FOR
260505 260504 INTERLOCK 260505 260504 INTERLOCK MORE INFORMATION. CONNECT TO CIRCUIT SHOWN USING
2#10+#10G. IN 3/4"C.
M

M
B1063 B1063
E3PA-25 E3PA-25

CHK'D: MLH
260501 260501 E2PB-29 260501 260501 260501 260501 E2PB-29

SEPTEMBER 5, 2019
STORAGE
260503 E3PA-18 260503 260503 260503 260503

1663-1190-90
E3PA-18 260503 EWH-2 A1001 EWH-2
260504 260504 *,GFCI+48" 260504 260504 260504 260504
*,GFCI+48"
E3PA-19 E3PA-23 E2PB-21 E3PA-11 E3PA-15 E3PA-19 E2PB-21
STORAGE

PROJECT NUMBER
3 SUR 3 E3PA-23 SUR

DESIGNED: RDW
A1001 GFCI+48" GFCI+48"

MLH
M M M M M M

DRAWN: RDW
IR-2 E3PA-14 IR-4 IR-2 E3PA-14

APPRV'D:
*,GFCI+48" *,GFCI+48"

DATE:
E3PA-24 E3PA-18 E3PA-22 E3PA-24
E3PA-18 GFCI+48"

E3PA-18 E3PA-18
E3PA-18 E3PA-18

FIRST FLOOR AND MEZZANINE POWER PLANS -


GFCI+48"
W.P. W.P.

VIGO COUNTY SECURITY CENTER


GFCI EVIDENCE GFCI
STORAGE EVIDENCE VEHICLE
A1002 STORAGE SALLYPORT
VEHICLE A1002 A1000
SALLYPORT E3H(25,27,29)
E3H-25,27,29 A1000 IWH-1
E3PA-14 K E3H E3PA-14 K
IWH-1 260510 E3H E3PA-8
*,GFCI+48" *,GFCI+48"
E3PA-8 GFCI+48" E3PA
TR-3
SPD-E3PA
E3PA
E3PA-8
GFCI+40"

E3PA-8
GFCI+40"

E3PA-8
GFCI+48"

E2PB-28 E2PB-28
E3PA-8
GFCI+48"

SPD-E3PA TR-3
* ABOVE *

TERRE HAUTE, INDIANA


E3PA-8 E3PA-28 E3PA-8
E3PA-36 +40" E3PA-36 +40"

AREA A
260505 260504 +84" E3PA-26 E3PA-28 260505 260504
+84" 260545
M

A NEW
260545 CORD REEL IR-1 CORD REEL IR-3 IR-1 E2HA(25,27,29)
E3PA-30 VEHICLE E3PA-8 E3PA-30 CRAC-4
EVIDENCE
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

*,GFCI+48"
M M STORAGE M M M M E3PA-12
E3PA-8 U2R-23 *,GFCI+48"
*,GFCI+48" E3PA-12 A1003
VEHICLE E3PA-17 E3PA-21 *,GFCI+48" +7' E3PA-9 E3PA-13 E3PA-17 E3PA-21 U2R-23 KEY PLAN
EVIDENCE E2HA(25,27,29) +7'
E2PB-30

260501 260501 260501 260501 260501 260501


STORAGE 260503 260503 CRAC-4
E3PA-34 260503 MAIN DATA E3PA-34 260503 260503 260503 E2PB-30
A1003 260504 260504 260504 260504 260504 260504
+84" FRAME M +84" M
CORD REEL MAIN DATA
CORD REEL B1060 FRAME
E2PB-30 E2PB-30
260545
260545 B1060
E3PA-12 E3PA-32 E3PA-12
E3PA-32 AIR COMPRESSOR
E3PA-12 SUR E3PA-12 SUR
AIR COMPRESSOR E3PA-10
E3PA-10 *,GFCI+48" GFCI+48" *,GFCI+48" GFCI+48"
GFCI+48"
M GFCI+48" E3PA-7 M
260532 E3PA-10 260518 260532 E3PA-10 E3PA-10
*,GFCI+48" E3PA-12 E3PA-12 *,GFCI+48" 260502 E3PA-10 *,GFCI+48" E3PA-12 E3PA-12
E3PA-7 *,GFCI+48" *,GFCI+48" *,GFCI+48" *,GFCI+48"
GFCI+48" A B C

260502 260502 E3PA-12 260502 260502 E3PA-10 260502 E3PA-12


260502 260502
E3PA-10 E3PA-10 W.P. E3PA-10 W.P. W.P.
9/25/2019 5:21:18 PM

W.P. W.P. GFCI W.P. GFCI GFCI


GFCI GFCI GFCI
3 3

DRAWING NUMBER

E-201-A

ELECTRICAL
3 FIRST FLOOR POWER - AREA 'A' ALTERNATE 1 FIRST FLOOR POWER - AREA 'A' BASE BID
E-201-A SCALE: 1/8" = 1'-0" E-201-A SCALE: 1/8" = 1'-0"
D E
NORTH NORTH
14
12
GENERAL NOTES
A A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702, E-703,
E-704, E-705, E-706 AND E-707.

B. SEE MECHANICAL EQUIPMENT - ELECTRICAL CONNECTIONS


260543 SCHEDULE ON DRAWINGS E-604 & E-605 FOR EQUIPMENT
J CIRCUITING AND ADDITIONAL ELECTRICAL EQUIPMENT

DLZ INDIANA, LLC


REQUIREMENTS FOR MECHANICAL EQUIPMENT (I.E. DISCONNECT,
260544 STARTER, ETC) AND EQUIPMENT NAMEPLATE ELECTRICAL LOAD
B INFORMATION (I.E. VOLTS, PHASE, FLA, MOCP, ETC.).
E1PC-12 J E1PC-16
KIOSK 260543 C. CONTRACTOR SHALL FIELD COORDINATE, PRIOR TO
E1PC-10 CONSTRUCTION, EXACT MOUNTING HEIGHTS AND LOCATIONS FOR
VESTIBULE KIOSK WIRING DEVICES WITH THE CASEWORK SHOP DRAWINGS AND
FCU-15
B1000 ARCHITECTURAL ELEVATIONS AND DETAILS.
E1PD-54
E1PC-8 E1PD-26 D. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND
VIDEO 8 9 10 11 E1PC-16 E1PC-14 KIOSK REFRIG CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
260543
VISITATION W.P. KIOSK RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
B1003 GFCI 260544 AND OFFSET BACK TO BACK BOXES.
J

E1PC-22

E1PC-20

E1PC-20

E1PC-20

E1PC-18

E1PC-18

E1PC-18
C E. REFER TO SECURITY DRAWINGS, #SE SERIES, FOR ADDITIONAL
J EQUIPMENT AND WIRING REQUIREMENTS. PROVIDE BOXES,
E1PC-16 E1PC-16 E1PD-10 RACEWAYS, CABLING, SUPPORTS, ETC. AS REQUIRED FOR

VV

VV

VV

VV

VV

VV

VV
E1PC-22
260542 E1PC-41 SECURITY EQUIPMENT. REFER TO SPECIFICATION SECTIONS 078123
260543 "INTUMESCENT FIREPROOFING" AND 078443 "JOINT FIRESTOPPING"
(TYP.)
FOR DETAIL FIRESTOP REQUIREMENTS.
E1PC-22 D

E1PC-20

E1PC-20

E1PC-20

E1PC-18

E1PC-18

E1PC-18
VV

VV

VV

VV

VV

VV
PRETRIAL PRETRIAL PRETRIAL PRETRIAL
SERVICES SERVICES SERVICES SERVICES VV E1PC-28 LOBBY E1PD-8 F. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO
WAITING
5 6 7 E2PA-8 VENDING B1001 SPECIFICATION 079200 "JOINT SEALANTS" FOR DETAILED
OFFICE OFFICE OFFICE OFFICE B1002
W.P. E1PC-22 REQUIREMENTS FOR SEALANT(S).
R
EE
B1070 B1071 B1072 B1073 GFCI E1PC-24 CK IN
GROUP GROUP GROUP CO

SS D I A N G
I ON A L E N
G. WATER MANAGEMENT SYSTEM TO BE PROVIDED BY OTHERS.

PE60018676
D

H
VIDEO VIDEO VIDEO

A
STATE OF
E1PC-24

L . H I TC

E
I ST ER
JAIL B1004 B1005 B1006 CONNECT ALL VALVE CONTROLLERS AS FOLLOWS:

E1PC-30
VENDING
E2PA-28 E2PA-26 E2PA-24 E2PA-22

No.
E2PA-24 STORAGE IN AREA B TO CIRCUIT E2PA-36, E2PB-31, E2PC-31 OR E2PE-21.
E2PA-28 E1PC-22 E1PC-22 E1PC-24
USB+40" E2PA-22 E2PA-8 IN AREA C TO CIRCUIT K1L-7.
USB+40" E2PA-26

EG
B1085 VV VV VV

IN
IN AREA D TO CIRCUIT E4PA-37, E5PA-45 OR E5PB-41.

IN
USB+40"

E1PC-24
USB+40" * E1PD-8
R
IN AREA E TO CIRCUIT E4PA-39, E4PB-41 OR E5PA-47. RV
E2PA-28 E2PA-26 E2PA-24 E2PA-22 E2PA-8 260524 E1PC-25 EACH CIRCUIT TO BE 2#12+G. IN 3/4"C. REFER TO CELL VALVE
MA FE
E2PA-28 E2PA-26 E2PA-24 E2PA-22
* JANITOR
F P RO
E1PC-31 E1PC-24 260505 M CONTROLLER (CVC) CONNECTION DETAIL #5 ON SHEET E-804.
B1007 GFCI+48" E1PC-25 260504 COORDINATE CONTROLLER LOCATIONS BEFORE ROUGH-IN.
E2PA-28 E2PA-26 E2PA-24 E2PA-22 E1PC-29 E1PC-25 TV+84" E2PA-29 U2R-8 U2R-8
COURTYARD GFCI U2R-7 E1PD-8
U2R-11
B1135
E2PA-30 CORRIDOR
STORAGE
B1084 E2PA-8
*
E1PC-29
GFCI E1PC-29
EWC-1
E1PC-26 E1PC-29 PUBLIC
PUBLIC
VISITATION
PUBLIC
PUBLIC
VISITATION - E2PA-33 260505
TV+96" U2R-9
MASTER
U2R-8
E1HB-7
FPV-1-02
POWER KEYNOTES 2605##

TRANSPORTATION CELL ADA CONTROL E1PC-23


OFFICE
E2PB-25 CLOSET B1068 GFCI+48" GFCI GFCI+48" VISITATION B1011 VISITATION *
E2PA-33 260504
GFCI E2PA-8 B1086 B1013 B1016 U2R-8 260506 260504 FURNISH AND INSTALL CONDUIT (3/4"C.) FROM EACH DOOR
B1069 E2PA-10 B1010 B1012 * E2PA-27
B1064 W.P. E2PA-30 E2PA-30 * 260506 260506 ATTORNEY TOILET E1PC-21 STARTER/CONTROLLER TO SECURITY CONTROL PANEL FOR
SUR

M
U2R-10 ACCESS CONTROL WIRING. WIRING AND TERMINATIONS BY
GFCI+48" J E1PC-35 J J E1PC-37 J E1PC-27 E1PC-27 E1PC-27 E1PC-25 CONFERENCE
U2R-12 12.7
B1017
13 OTHERS. REFER TO SECURITY SERIES SHEETS FOR DETAILED
E2PA-30 E2PA-20 E2PA-14 260522 260522 B1018 U2R-8 SEX WIRING REQUIREMENTS.
REFRIG E2PA-31 J

E2PA-18
INTERLOCK

COPIER
E2PB-25 PRETRIAL J E1PC-33 J J E1PC-39 J ATTORNEY *
INTERLOCK OFFENDER E1PC-19

GFCI+48"
260505 FURNISH AND INSTALL POWER (1/8HP, 120V) FOR SLIDING DOOR

E1PC-21
E2PB-27
B1067 SERVICES CELL 260506 260506 INMATE INMATE CONFERENCE B1015 E1PC-21 REGISTRY CONTROLLERS, DOOR SAFETIES/LIMIT SWITCHES AND KEYED

M
260522 J VISITATION VISITATION

MICRO+48"
E2PB-25 WORKROOM B1083 CELL J 260522 260524 C1002 E1PC-13
B1019 OPEN-CLOSE PUSHBUTTON CONTROL STATIONS FURNISHED BY

U2R-11

U2R-11
TV+96"

TV+96"
GFCI+48"
260522

U2R-11
E2PA-20 WOMENS

TV+96"
TOILET MENS TR-U2 B1023

E1PC-29

E2PB-35

E2PB-33
E2PA-10 B1087 B1021

REFRIG
B1074 E2PA-20 E2PA-31 E2PA-25 DOOR EQUIPMENT VENDOR. CONTROL WIRING BY OTHERS. REFER
E2PB-27 E2PA-30 GFCI+40" SUR B1008 INMATE TO SPECIFICATION 087100 "DOOR HARDWARE" FOR DETAILED
TRANSPORTATION B1066 GFCI+40" B1009 ABOVE INMATE * 260504 E1PC-19

SUR
E2PA-20
USB+42" E2PB-27 * GFCI+48" E1PC-31 VISITATION - J REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT SWITCHES AND
WAITING TOILET TR-2A VISITATION E2PA-31 260505 E1PC-21
E2PB-32 260522 J J 260522 ADA 3 CONTROL SWITCH(S) PER MANUFACTURERS RECOMMENDATION.
B1062 E2PA-16 260510 BELOW B1022 * SUR E1PC-19
J B1076 E2PA-10 B1020 FURNISH AND INSTALL CONDUIT/POWER WIRING REQUIRED FOR A
260506 MICRO+40" CELL GFCI+48"
260504 INTERLOCK E2PB-23 TOILET SUR COMPLETE SYSTEM. FIELD-COORDINATE THE EQUIPMENT
STORAGE

GFCI+48"
GFCI+48"
CELL U2R-25

E2PA-12
E2PA-7

E2PA-12
U2R-17

SPD-E2PB

SPD-E2PA
E2PB

E2PA
B1075 GFCI+48" B1088 E2HA E2PA-23 U2R-13 INSTALLATION AND CONDUIT REQUIREMENTS WITH THE DOOR

DIS-UPS2
B1063 E1PC-21 SQE#4
M

E2PA-12 B1082 UPS2 GFCI RADIO C1083 EQUIPMENT VENDOR PRIOR TO CONSTRUCTION.
260522 260522 260504 RADIO
E2PB-21

260504 SUR UPS WALL MOUNTED BYPASS, 260510 CHARGING CHARGING 260551
E2PB-29 E2PB-21 260505 260506 NEW ELECTRIC HAND DRYER, REFER TO SPECIFICATIONS.
GFCI+48" SEE SPECIFICATIONS M U2R-15

SPD-U2R
260505

E1PC-17
*,TV E2PB-34 E2PA-7 E1PC-21 COORDINATE EXACT HEIGHT AND LOCATION BEFORE ROUGH-IN.
EWH-2 E2PB-21 J J J J PA-1 SQE#6b RADIO
+84" ELECTRICAL * E1PC-17
*

* 260506 J U2R L1H U2R-30 E2PA-7 CHARGING 260508 FURNISH AND INSTALL RECEPTACLE IN CUSTOM FLUSH MOUNTED,
E2PA-12 SECURITY LOCKABLE WALL CABINET. FOR CABINET DETAIL, SEE SHEET
E2PB-21 TOILET B1024 * 3
SUR C1046 E-803, DETAIL #7.
SUR B1065 GFCI+48" CELL CELL E1PC-17
E2PA-7 SQE#6a CELL WOMENS 260510 EQUIPMENT TO BE MOUNTED ON CONCRETE PAD, REFER TO
GFCI+48" E2PA-12 B1081 E2PA-10 B1089 260530
GFCI U2R-28 DS-A B1040 B1026 CRAC-2 STRUCTURAL DRAWING S-530, DETAILS #8 AND/OR #9 FOR
SUR L1P-17 INTERLOCK
CONCRETE PAD INSTALLATION DETAIL.
GFCI+48" 260551 CELL E2PA-11 260522 E2PA-11 E2HA-13 C1044
CELL E1PD-48 260511 RECEPTACLE INDIVIDUALLY CONTROLLED BY SECURITY
B1041 GFCI+48" ELECTRONIC CABINET RELAY. REFER TO SECURITY EQUIPMENT
E2PB-19 CELL CELL CELL E2PA-10 B1091 CELL E2PA-15 J PLANS AND DIVISION 28 SPECIFICATIONS FOR DETAILED WIRING
* B1077 B1078 B1079 CELL SUR 3 SUR
E2PB-17 B1092 E2PA-11 REQUIREMENTS.
MALE GFCI+48" CELL GFCI+48"
B1080 SUR SUR
DETOX B1090 GFCI+48" 260512 PROVIDE POWER CONNECTION FOR "GUARDIAN SYSTEM"
E2HA-10 GFCI+48" EQUIPMENT. CONNECT TO CIRCUIT SHOWN USING 2#10+G. IN
B1061 E2PA-15 J E1PD-42
FPV-2-02 3/4"C. COORDINATE EXACT LOCATION WITH OWNER BEFORE
CELL SUR E2PA-11 ROUGH-IN.

E1PD-42
E1PD-44
E2PB-19 E2PB-19
B1042 GFCI+48" CELL ADAE2PA-11 260522 GFCI+48" CID WORK
SUR SUR 260514 FURNISH AND INSTALL (1)-1"C. FROM BELOW COUNTER RAISED
GFCI+48" B1039 MENS E1PD-42 GROUP
GFCI+48" FLOOR OVER TO CHASE AND STUBBED OUT AT +12" A.F.F. FOR
E2PB-26 FPV-2-03 * C1040 FUTURE POWER WIRING. FURNISH WITH PULLSTRING.
E2PB-26 E2PB-17 3 B1027 260521 260521
*,USB E2HA-9 260521 FURNISH AND INSTALL 4-GANG FLOOR BOX, LIKE
*,+40" 260514 * E2PA-9
+40"

E2PB-11
E2PA-19 260521 260521 LEGRAND/WIREMOLD #RFB4 OR APPROVED EQUAL. MOUNT FLUSH

E2PB-7
E2PA-15 260511 260508 SUR

E1PD-42
E1PD-44
E2PB-26 E2PB-24 E2PB-17 E2PB-17 *,BODY 260522 IN FLOOR. FURNISH WITH TWO (2)-20A DUPLEX RECEPTACLES,
*,VV E2PA-17 E2PA-17 GFCI+48"
*,+40" * * * SCANNER ONE (1) #RFB-B BLANK DEVICE PLATE AND ONE (1)
E2PA-21 *,TV +46" J
DAYROOM K COMMUNICATIONS OUTLET, REFERENCE KEYNOTE #270502 ON
E2PB-26 E2PB-24 BODY * C-I E2PA-9

U2R-14
E-401 SERIES SHEETS. VERIFY EXACT LOCATION WITH ARCHITECT

U2R-16
TESTING * E2PB-15 B1037 +96"
* E2PB-19 E2PB-9 SCANNER GFCI+48" E1PD-42

E2PB-11

E2PB-7
USB

USB
E2PB-24 E2PB-24 E2PA-9 BEFORE ROUGH-IN. ROUTE (1)-3/4"C. ROUTE ONE (1)-3/4"C. FROM
B1056 * E2PB-15 BOX OVER AND UP NEAREST CHASE/WALL FOR POWER.
* * MEDICAL B1035 STAFF
USB
E2PB-28 PRE-SCREENING E2PA-21 TOILET 260522 AUTOMATIC FLUSH VALVE. REFER TO AUTOMATIC ELECTRIC
* U2R-18
E2PB-24 B1057 E2PB-13 * B1031 FLUSH VALVE DETAIL #2 ON SHEET E-801.

09/12/19
09/26/19
E2PB-9 260505

DATE
* E2PB-13 E2PA-21 E2PD-9 260524 FURNISH AND INSTALL 8-GANG FLOOR BOX, LIKE
3 260521 260504
USB *,USB LEGRAND/WIREMOLD #EFB8S OR APPROVED EQUAL WITH TWO (2)

E2PD-7
USB+48"
260505 BOOKING #EFB-8M 4-GANG MOUNTING BRACKETS, ONE (1) #EFB610BTXX

M
INTERLOCK U2R-20 +18" E2HA-7 E2PD-7
260504 COUNTER PASSAGE FLUSH STYLE COVER LID WITH FINISH PER ARCHITECT. BOX TO
FPV-2-04 E2PA-13
E2HA(25,27,29) B1055 E2PB-14 B1029 HAVE SIX (6) DEVICE PLATES WITH SIX (6) 20A DUPLEX
M

B1053A E2PD-7
E2PB-8 RECEPTACLES, ONE (1) #EFB-B BLANK DEVICE PLATE AND ONE (1)
CRAC-4 E2PB-22 E2PB-14 TV MATRON E2PD-9
E2PB-28 E2PB-20 E2PA-9 E2PA-9 COMMUNICATIONS OUTLETS, REFERENCE KEYNOTE #270511 ON
USB +84" C1080
* * * * E-401 SERIES SHEETS. VERIFY EXACT LOCATION WITH ARCHITECT
MEDICAL U2R-22 E2PB-9
BEFORE ROUGH-IN. ROUTE (2)-3/4"C. FROM BOX OVER AND UP

REVISION
TOILET PRE-SCREENING E2PB-16 E2PC-8 NEAREST WALL FOR POWER. PROVIDE A MAXIMUM OF (3)
E2PD-9

E2PB-12

E2PB-10
TCP
U2R-23 E2PB-28 SHOWER SEARCH SEARCH E2PC-10 RECEPTACLES PER CIRCUIT.
B1058 E2PB-16 L1P-12

1 Addendum #01
3 Addendum #03
+7' TOILET E2PC-10

USB

USB
U2R-21

U2R-19
B1059 USB TOILET E2PD-34 E2PD-34
E2PB-20 SHOWER JANITOR +48" 260529 COMMUNICATIONS/DATA RACKS, REFER TO SPECIFICATIONS.
U2R-24 SHOWER
* CRAC-1 EACH RACK TO RECEIVE TWO 20A, 120V CIRCUITS, AS INDICATED,

GFCI+48"
E2PB-30 E2PB-20 B1033 B1030

E2PC-12
E2PB-19 E2PB-9 B1034 SECURITY IN 3/4"C. FROM PANEL 'U2R'. PROVIDE 2#12+G PER CIRCUIT.
SQE#13 * E2PC-10 E2HB(14,16,18) M

E2PB-12

E2PB-10
U1R-26 E2PB-20 * E2PC-10 +48" C1079 260530 PREACTION DRY-POWER SYSTEM, 120V. CONNECT TO CIRCUIT
E2PB-18 E2PB-18 E2PB-18
E2PB-30 * GFCI+48" SQE#1 SHOWN USING 2#12+G. IN 3/4"C. COORDINATE EXACT LOCATION.
* * *
E2PC-10 SECURE E2PD-34 260531 CONNECT TO CIRCUIT SHOWN WITH 2#10+G. IN 3/4"C.

NO.
E3PA-12 260529 E2PB-20 INTAKE +48" CORRIDOR 260542 ROUTE POWER CONDUCTORS UP TO VIDEO VISITATION STATION
SUR 260510 CENTER J E2PC-18 E2PC-8
SUR THROUGH CABINET SUPPORT LEGS. COORDINATE WITH
GFCI+48" FPV-2-07 M E2PE-17 E2PC-12 +42" E2PC-8 B1025 E2PD-34 E2PD-34
U2R-32 GFCI+48" E2HA-8 260504 B1053 260514 E2PB-18 E2PB-18 EQUIPMENT SUPPLIER.
260512 +42" GUARDIAN
U2R-34 260505 SUR SUR 260543 AUTOMATIC DOOR OPENER. PUSHBUTTONS BY MANUFACTURER,
GFCI+48" GFCI+48" E2PC-14,16 E2PC-8 E2PD-11
U2R-36

CHK'D: MLH
WIRE PER MANUFACTURER'S RECOMMENDATION, 120V.

E2PD-11
FEMALE USB+48"

SEPTEMBER 5, 2019
U2R-38 E2PC-12 * E2PD-11 COORDINATE EXACT LOCATION BEFORE ROUGH-IN.
DETOX

1663-1190-90
U2R-40 SECURE
U2R-42 B1054 CELL ADA E2PD-11 E2PD-17 260544 ELECTRIC DOOR. VERIFY WITH MANUFACTURER ALL FINAL
TOILET / PADDED TOILET / PADDED CORRIDOR TV CONNECTIONS.
CELL CELL B1044 ASSISTANT
SHOWER SHOWER B1025 +84" 260548 COMMUNICATIONS DATA CABINET, REFER TO SPECIFICATIONS.

PROJECT NUMBER
PADDED PADDED INMATE
B1051 B1050 B1048 B1047 JAIL CONNECT TO CIRCUIT INDICATED USING 2#12+G. IN 3/4"C.

DESIGNED: RDW
CELL PROPERTY

MLH
CELL INMATE COMMANDER 260551 WALL MOUNTED SECURITY CABINET/RACK, REFER TO SE

DRAWN: RDW
B1052 B1049 CELL CELL ADA E2PC-12 STORAGE
CLOTHING E2PD-17 C1078 DRAWINGS FOR MORE INFORMATION. CONNECT TO CIRCUIT
E2PE-11 E2PE-16 E2PE-16 B1046 B1045 E2PC-26 B1032
B1043 SHOWN USING 2#12+G. IN 3/4"C.

APPRV'D:
3 SUR SUR SUR GFCI+48"
GFCI+48" WASHER E2PD-17
GFCI+48"

DATE:
GFCI+48"
SQE#7b E2PE-11
JANITOR E2HB-9 E2PC-8
U1R-18 PADDED * STORAGE E2HA-11 JAIL E2PD-13
B1108 FPV-2-09 E2PC-24 COMMANDER
260551 CELL B1094 FEMALE FEMALE FEMALE FEMALE FPV-2-08
INTERLOCK C1077
B1109 PADDED CELL ADA CELL CELL CELL
260551 B1093 FEMALE E2PC-28,30
CELL B1114 B1115 B1116 B1117 E2PD-17

E2PD-13
SQE#7a TOILET / CELL DRYER+48"

VIGO COUNTY SECURITY CENTER


E2PE-13 E2PE-11 E2PC-12 TV
U1R-16 TR-2E SHOWER B1111 260508 260508 260508 260508 260508 B1118 260531
GFCI+48" +84"
B1110 E2PE-18 E2PE-18 E2PE-18 E2PE-18 E2PE-18 E2PD-13
E2PE C-I C-I C-I 3
C-I C-I USB+48"

FIRST FLOOR POWER PLAN - AREA B


SPD-E2PE GFCI GFCI GFCI GFCI MEDICAL
GFCI
RECORDS E2PC-20 COUNCILOR PA-2
E2PC-17
E2PE-11 U1R-17 E2PE-16 E2PE-16 E2PE-16 B1127 B1128 * 260530
* 260504 SUR FEMALE SUR SUR E2PC-20 L1P-15
E2PE-7 E2PC-17
260505 GFCI+48" DAYROOM GFCI+48" GFCI+48" E2PC-24 E2PC-8 E2PD-15
E2PE-13 M USB E2PC-24 * TR-2C TR-2D 3 E2PD-15
E2PE-14 E2PC-20 E2PC-17 ELECTRICAL JANITOR GFCI+48"
E2PE-15

SPD-E2PD
* E2PE-7 E2PE-7 B1112 BELOW ABOVE

*,GFCI+48"
*,VV E2PC-24 USB+48" * B1028 C1076

E2PC-17

E2PC-17
E2PE-9 260510 SPD-E2PC E2PC-8
E2PE-9 FEMALE
260508 *,TV DENTAL GFCI

TERRE HAUTE, INDIANA


TOILET E2PC-24
E2PE-9 B1129 3 E2PD-15
E2PE-14 C-I SHOWER E2PC-24 * E2HB
E2PC E2PD E2PD-19 E2PD-21
USB DS-B

*
+48" +88" PHARMACY * * *

DIS-UPS1
B1113 SQE#11 260510 M

SPD-U1R
U1R-17 260511 260504 E2PD-19 E2PD-19
B1126 MEDICAL U1R-15 NAC-1 E2PD-25 E2PD-21
RECREATION WAITING 260511 E2PC-15 UPS1 260505 * * *
260511 L2P-18 U1R

A NEW
E2PE-11 STAFF TR-U1 INMATE/ INMATE/
B1107 B1122 *
* E2PE-14 E2PE-14 *,TV E2PE-14 260522 *,TV ATTORNEY ATTORNEY
MALE WORK E2PE-14 J TOILET E2PC-15 260551 E2PC-15
*,VV +48" C-I *,VV E2PC-22 C-I E2PC-11 260510 CONFERENCE CONFERENCE
MEDICAL STATION * TOILET E2PC-22 B1125 * EXAM GFCI
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

260508 +88"

E2PC-7
DAYROOM +88" E2PC-7 E2PC-7 C1074
B1096 SHOWER SUR E2PC-22 B1130 C1075
E2PC-22 E2PC-15 USB+48"
B1095 B1120 GFCI+48" * *,GFCI+48" E2PC-7
GFCI+48" E2PC-15 UPS WALL MOUNTED E2PD-19 E2PD-21 KEY PLAN
USB+48" E2PC-11 * *
260504 * BYPASS, SEE
SPECIFICATIONS *
E2PC-22 260505 E2PD-19
E2PE-13 E2PC-9 E2PC-11
GFCI+48"

* E2PC-36 INMATE JAIL VIDEO N


E2PC-13

* E2PE-8 E2PE-8 E2PE-8 E2PE-8 E2PE-8 260504 INTERLOCK E2PC-15 *


SUR SUR SUR SUR SUR E2PC-34 TOILET E2PC-9 SUPERVISORS ARRAIGNMENT
260505 B1121 * USB+48"
SUR

GFCI+48" GFCI+48" GFCI+48" GFCI+48" GFCI+48" M M B1131 B1133 WAITING


C1073
260508 260508 260508 260508 260508 260508 260508 260508 260508 260508 E2PC-29 E2PC-11
E2PC-21 E2PC-25
E2PE-10 E2PE-10 E2PE-10 E2PE-10 E2PE-10 E2PE-12 E2PE-12 E2PE-12 E2PE-12 E2PE-12 *,GFCI REFRIG E2PC-9
E2PC-27
C-I C-I C-I C-I C-I C-I C-I C-I C-I C-I REFRIG EXAM
*,+42" E2PC-23 E2PC-9
E2PC-13

E2PC-13
*,GFCI+48"
*

GFCI GFCI GFCI GFCI GFCI GFCI GFCI GFCI GFCI GFCI GFCI REFRIG E2PC-25 B1132 USB+48"
E2PC-25
E2PC-27 E2PC-27 * E2PC-11
CELL CELL CELL CELL CELL CELL CELL CELL CELL CELL ADA * NURSE E2PC-13
E2HB-7 GFCI+42" E2PC-11
B1106 B1105 B1104 B1103 B1102 B1101 B1100 B1099 B1098 B1097
E2PC-27
E2PC-19
B1124 * A B C
FPV-2-12 * E2PD-23
MICRO+56" *
E2PC-25 E2PC-13
*
9/25/2019 5:21:45 PM

EWH-1 260504 260505 E2PE-8 LACTATION E2PC-13


E5PB-18 * 260504 ROOM *
E5PB-33 E2PC-32
* 3 260505
M

SECURE M B1123
INTERLOCK

DRAWING NUMBER

E-201-B
E5PB-26 CORRIDOR
M M
D1013 260504 D1012 IT U1R-40 260504

ELECTRICAL
E5PB-28 E5PB-31
E5PB-18 260505 SUR E5PB-31 D1010 IDF 260548 260505 E5PA-33 260505
D1005D 260508 E5PA-26
GFCI+48" * CABINET #1 *
* D E
STORAGE
D1005B E5PB-31 E5PB-31
1 FIRST FLOOR POWER - AREA 'B'
E-201-B SCALE: 1/8" = 1'-0"
NORTH
E1PD-30 E1PA-42
14 14.2 W.P. 15 15.3 16 17 18 19 W.P. 20 20.2 20.6 20.7 21
12.7 GFCI GFCI POWER KEYNOTES 2605##

E1PD-30 E1PD-38 E1PD-45 E1PD-43 E1PD-39 E1PA-39 E1PA-39 E1PA-41 E1PA-42 E1PA-42 A
13 E1PD-39 E1PD-39 260504 FURNISH AND INSTALL CONDUIT (3/4"C.) FROM EACH DOOR
E1PD-30 E1PD-30 E1PD-36 E1PD-36 E1PD-36 E1PD-38 E1PD-37 E1PA-41 E1PA-44 TV E1PA-42
E1PD-45 I.T. OFFICE TV+84" E1PA-39 STARTER/CONTROLLER TO SECURITY CONTROL PANEL FOR
E1PD-28 TV+84" E1PD-39 +96"
U2R-43 C1020 E1PD-37 USB+36" ACCESS CONTROL WIRING. WIRING AND TERMINATIONS BY
E1PD-36 E1PD-38 E1PD-40 E1PD-47 E1PD-43
E1PD-32 TV+84" E1PD-39 AGENCY USB+42" E1PA-39 E1PA-40 E1PA-42 OTHERS. REFER TO SECURITY SERIES SHEETS FOR DETAILED
E1PD-30 SHERIFF'S E1PD-47 TV+84" E1PD-41
USB+42" CHIEF USB+42" E1PA-40 WIRING REQUIREMENTS.
OFFICE USB+42" CHIEF C1021 E1PA-44

DLZ INDIANA, LLC


DEPUTY'S E1PD-40 E1PD-37 E1PA-37 SQUAD 260528 260528 260505 FURNISH AND INSTALL POWER (1/8HP, 120V) FOR SLIDING DOOR
E1PD-32 C1016 DEPUTY'S E1PD-43

E1PD-38
260544 OFFICE USB+42" E1PD-47 E1PD-41 E1PD-41 USB+36" ROOM E1PA-41 CONTROLLERS, DOOR SAFETIES/LIMIT SWITCHES AND KEYED
CONFERENCE OFFICE

E1PD-35

E1PD-35
E1PD-34 USB+42" TV B OPEN-CLOSE PUSHBUTTON CONTROL STATIONS FURNISHED BY
ROOM C1018 C1019 E1PA-37 C1027

E1PD-37
USB+42"
E1PD-41 +96"

USB+42"

USB+42"
E1PD-35

E1PD-35
E1PC-16 E1PD-28 E1PD-34 E1PA-42 DOOR EQUIPMENT VENDOR. CONTROL WIRING BY OTHERS. REFER
TV+84" C1015 TV+84" E1PD-45 E1PD-43 USB+42" E1PA-37 TV TO SPECIFICATION 087100 "DOOR HARDWARE" FOR DETAILED
E1PC-10 E1PD-32 E1PD-43 260528 260528
USB+36" +96" REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT SWITCHES AND
E1PD-38 E1PD-47 E1PD-43

USB+36"

USB+36"
E1PD-32 E1PD-34

E1PA-35

E1PA-33
VESTIBULE KIOSK E1PD-28 E1PA-37 E1PA-40 CONTROL SWITCH(S) PER MANUFACTURERS RECOMMENDATION.
E1PD-30 E1PA-41
FURNISH AND INSTALL CONDUIT/POWER WIRING REQUIRED FOR A

E1PA-35

E1PA-35

E1PA-33
B1000 TOILET E1PD-38 E1PD-40 E1PD-47 E1PD-33 E1PA-40 E1PA-38
E1PA-35 E1PA-44

GFCI+40"

GFCI+40"

GFCI+40"

GFCI+40"
COMPLETE SYSTEM. FIELD-COORDINATE THE EQUIPMENT

E1PD-28

E1PD-28

E1PD-28

E1PD-28

E1PD-40

E1PD-40
USB
C1017 E1PD-34 ADMIN E1PD-33 E1PD-31 USB+36" FITNESS
E1PC-8 260522 INSTALLATION AND CONDUIT REQUIREMENTS WITH THE DOOR
E1PD-26 SUPPORT E1PA-41
KIOSK E1PD-34 E1PD-31 C1028 EQUIPMENT VENDOR PRIOR TO CONSTRUCTION.
REFRIG E1PD-33
GFCI+48" C1010 CIVIL USB+42"
E1PA-33 E1PA-33 260506 NEW ELECTRIC HAND DRYER, REFER TO SPECIFICATIONS.
260544 J C1022 E1PD-31 USB+36" COORDINATE EXACT HEIGHT AND LOCATION BEFORE ROUGH-IN.
E1PD-31 260528 260528

E1PD-33
TRAINING E1PA-31 260509 SECURITY EQUIPMENT RACKS (5 TOTAL), REFER TO SECURITY
E1PD-10 CORRIDOR USB+42" E1PA-31 E1PA-44 E1PA-40 E1PA-38 C
OFFICE DRAWINGS. PROVIDE TEN (10) 20A, 120V CIRCUITS FROM PANEL
E1PD-10 TV+88" E1PA-44 E1PA-40

USB+42"

USB+42"

USB+42"
E1PD-27

E1PD-27

E1PD-29
E1PD-34 C1009 'U1R' TO RACKS, CIRCUITS #19-#27,29 AND FOUR (4) 20A, 120V
E1PD-10 E1PD-33 C1029

E1PD-27

E1PD-27

E1PD-29
E1PD-29 CIRCUITS FROM PANEL 'E2PD' TO RACKS, CIRCUITS #26, 28, 30, 32.
E1PA-38 E1PA-38 E1PA-38 E1PA-38 COORDINATE WITH SECURITY CONTRACTOR ON EXACT LOCATION
E1PD-25
E1PD-22 E1PD-29 E1PA-31 +12" +12" TV +12" C.7 OF CIRCUITS. PROVIDE 2#12+G IN 3/4"C. FOR EACH CIRCUIT.
E1PD-16 +42" E1PD-22 USB+42" E1PA-31 +96" E1PA-36
E1PD-8 D 260510 EQUIPMENT TO BE MOUNTED ON CONCRETE PAD, REFER TO
GFCI
LOBBY E1PD-10 E1PD-16 E1PD-22 E1PD-17 STORAGE E1PA-36 E1PA-36 STRUCTURAL DRAWING S-530, DETAILS #8 AND/OR #9 FOR
E1PD-8 260522 J 260522 J J 260522 TOILET / W.P.
E1PD-16 +40" E1PD-18 +42" E1PA-36 E1PA-36 BREAK CONCRETE PAD INSTALLATION DETAIL.
B1001 C1011 SHOWER C R
+40" +40" E1PD-17 E1PD-25 E1PD-25 E1PD-25 TV ROOM 260515 PROVIDE AND INSTALL AS REQUIRED TOGGLE SWITCH FOR EE
E1PD-12 E1PD-20 +44" SUR
C1026 CORRIDOR +84" GARBAGE DISPOSAL CONTROL WITH RACEWAY AND CK IN
CO

GFCI+42"

GFCI+42"

GFCI+42"

SS D I A N G
E1PD-24 C1030

E1PA-23

E1PA-32

E1PA-32
E1PD-16 +42" E1PD-25

I ON A L E N
TOILET /

PE60018676
USB CONDUCTORS FROM SWITCH TO GARBAGE DISPOSAL UNIT, 3/4HP, D

GFCI+48"

H
E1PD-18 GFCI+48"

A
C1023C

STATE OF
E1PD-25

L . H I TC
COPIER

E
E1PA-27
SUR E1PA-34 E1PA-34

REFRIG
+40" 3

E1PA-34

E1PA-34

E1PA-34

I ST ER
E1PD-12 E1PD-17 SHOWER A 120V. MOUNT SWITCH ABOVE COUNTERTOP. CIRCUIT AS SHOWN.
E1PD-18 GFCI+48" GFCI GFCI

No.
SHARED E1PD-20 FILE +44" C1024 E1PD-23 E1PD-25 260516 MAIN GROUND BUS BAR #1. FURNISH AND INSTALL 2'-0"W GROUND
WAITING USB +42" STORAGE GFCI+48" GFCI+48" W.P. W.P.
ADMINISTRATION BUS BAR. MOUNT AT +8'-0" AFF. REFER TO BUILDING GROUND BUS

EG
E1PD-18

IN
E1PD-16 WORK E1PD-22 M DETAIL #2, SHEET E-803.

IN
C1000 C1014 C1012 E1PD-23
R
E1PD-8 +40" E1PD-20 ROOM E1PD-17 TOILET / E RV
E1PD-12 E1PA-25 E1PA-29 E1PA-30 E1PA-28 260517 FURNISH AND INSTALL 2-GANG FLOOR BOX, LIKE MA FE
E1PC-25 +42" +44" SHOWER B GFCI+42" LEGRAND/WIREMOLD #RFB2 OR APPROVED EQUAL. MOUNT FLUSH P RO
C1013 CORRIDOR 260515 E1PA-30 E1PA-30 E1PA-28 F
E1PD-22 C1025 MICRO E1PA-28 IN FLOOR. FURNISH WITH ONE (1)-20A DUPLEX RECEPTACLE AND
E1PD-12 E1PD-17 C1023B CLOSET

E1PD-20

E1PD-20
E1PA-17 ONE (1) COMMUNICATIONS OUTLET, REFERENCE KEYNOTE #S-- ON
USB E1PD-14 +44" LACTATION E1PA-7 260527 260527 260527 260527 260527
U2R-8 260506 C1035 E-401 SERIES SHEETS. VERIFY EXACT LOCATION WITH ARCHITECT
E1PD-14 +40" GFCI+48" E1PA-8 E1PA-12 E1PA-16 E1PA-20 E1PA-24

+42"

+42"
E1PD-8 E1PD-14 C1008A E1PA-23 BEFORE ROUGH-IN. ROUTE ONE (1)-3/4"C. FROM BOX OVER AND UP
U2R-7 E1PD-10 +40" +40" E1PD-17
U2R-8 E1PA-23 NEAREST CHASE/WALL FOR POWER.
U2R-9 E1PD-8 J J J
E1HB-7 E1PD-14 J J E1PA-15 260521 FURNISH AND INSTALL 4-GANG FLOOR BOX, LIKE
MASTER E1PD-21

E1PA-13
FPV-1-02 3 CORRIDOR STORAGE E1PA-23 TRAINING LEGRAND/WIREMOLD #RFB4 OR APPROVED EQUAL. MOUNT FLUSH
CONTROL E1PC-23 REFRIG+18"
ELECTRICAL C1008 260522 ROOM IN FLOOR. FURNISH WITH TWO (2)-20A DUPLEX RECEPTACLES,
260506 260551 C1003 E1PD-23 E1PA-7 E1PA-30 E1PA-28
B1016 U2R-8 C1004 JANITOR (TYP.3) ONE (1) #RFB-B BLANK DEVICE PLATE AND ONE (1)
TOILET E1PC-21 E1PC-7 U2R-29 E1PD-23 GFCI C1034 COMMUNICATIONS OUTLET, REFERENCE KEYNOTE #270502 ON
WOMENS
U2R-10 B1017 E1PC-11 GFCI SQE#2 TR-1C C1005 E1PD-13 E1PD-19 E-401 SERIES SHEETS. VERIFY EXACT LOCATION WITH ARCHITECT

260522

260522

260522
U2R-12 C1033
260527 260527 260527 260527 260527 BEFORE ROUGH-IN. ROUTE (1)-3/4"C. ROUTE ONE (1)-3/4"C. FROM
U2R-8 SEX E1PD-23
J E1HB TCP E1PD-15 BOX OVER AND UP NEAREST CHASE/WALL FOR POWER.
OFFENDER E1PC-19 E1PC-11 DS-C E1PD-11 E1PD-13 E1PD-19
GFCI+42"
E1PA-8 E1PA-12 E1PA-16 E1PA-20 E1PA-24
GFCI+48"

L1P-10
E1PC-21

REGISTRY E1PC * * GFCI+48" EWC-1 260522 AUTOMATIC FLUSH VALVE. REFER TO AUTOMATIC ELECTRIC
E1PC-21 E1PC-7 E1PC-7 E1PA-7 J J J
E1PC-11 E1PD-19 E1PA-30 FLUSH VALVE DETAIL #2 ON SHEET E-801.
MICRO+48"

260524 C1002 E1PC-13 GFCI SPD-E1PC E1PA-19


GFCI+48" SUR E1PA-21
U2R-11
TV+96"

260522 E1PC-13 GFCI


U2R-11
TV+96"

260523 FURNISH AND INSTALL 240V, 30A NEMA L6-30 RECEPTACLE FOR
E2PB-35

E2PB-33

E1PD GFCI
REFRIG

USB+40" E1PC-11 INTERVIEW GFCI+48" CORRIDOR 260541 E1PA-26


USB+40" SPD-E1PD INTERVIEW DEF TAC J J J OWNER PROVIDED PORTABLE PLUGIN WELDER. VERIFY EXACT
J E1PC-19 C1007 C1031 E1PA-18 LOCATION WITH OWNER BEFORE ROUGH-IN.
E1PC-13 STORAGE

260522

260522

260522
E1PC-21 E1PC-7 C1006 E1PD-19 E1PA-17
3 260510 E1PD-7 260524 FURNISH AND INSTALL 8-GANG FLOOR BOX, LIKE
SUR E1PC-19 GFCI C1039 E1PD-19
E1PD-9 E1PD-11 E1PD-13 E1PD-15 ARMORY LEGRAND/WIREMOLD #EFB8S OR APPROVED EQUAL WITH TWO (2)
GFCI+48" E1PC-9 IDF RACK GFCI+48" MENS
STORAGE * * * * E1PA-10 #EFB-8M 4-GANG MOUNTING BRACKETS, ONE (1) #EFB610BTXX
U2R-17 U2R-25 USB+40" #1 260529 E1PD-9 C1038 260527 260527 260527 260527
E1PD-7 C1032 E1PA-7 FPV-1-15 FLUSH STYLE COVER LID WITH FINISH PER ARCHITECT. BOX TO
RADIO E1PC-21 SQE#4 C1083 E1PC-15 U2R-45 E1PA-10 E1PA-14 E1PA-18 E1PA-22 E1PA-26 HAVE SIX (6) DEVICE PLATES WITH SIX (6) 20A DUPLEX
GFCI

E1PA-9
E1PC-9 U2R-47 E1PD-19 E1HA-7

E1PA-18
CHARGING 260551 USB+40" E1PD-7 260522 260527 RECEPTACLES, ONE (1) #EFB-B BLANK DEVICE PLATE AND ONE (1)
E1PA-22
USB+42" (TYP.3) E1PA-14 E1PA-18 TV E1PA-26 COMMUNICATIONS OUTLETS, REFERENCE KEYNOTE #270511 ON
E1PA-7 E1PA-11
E1PC-17

E1PC-21 E1PC-15 E1PC-9 E1PD-9


E1PD-11 E1PD-13 E1PA-21 TV E1PA-14 +96" E1PA-22 E-401 SERIES SHEETS. VERIFY EXACT LOCATION WITH ARCHITECT
E1PC-17 * E1PD-15 GFCI+48" J J J J J
* +96" BEFORE ROUGH-IN. ROUTE (2)-3/4"C. FROM BOX OVER AND UP
SECURITY E1PA-10 H
H.2 NEAREST WALL FOR POWER. PROVIDE A MAXIMUM OF (3)
C1046 SEX E1PC-9 RECEPTACLES PER CIRCUIT.
E1PC-17 OFFENDER E1PD-11 E1PA-17 3 E1PA-21
CID 3 CORRIDOR E1PA-21
AND 260506 E1PA-7 260525 FURNISH AND INSTALL 2-GANG FLOOR BOX, LIKE
SUPERVISOR CORRIDOR C1082 VESTIBULE W.P.+24"
CRAC-2 INTERLOCK 3 LEGRAND/WIREMOLD #RFB2 OR APPROVED EQUAL. MOUNT FLUSH

E1PA-21
EVICTION OFFICE GFCI
C1085 E1PB-22 E1PB-32 TR-L1P 260510 260510 C1036 IN FLOOR. FURNISH WITH TWO (2)-20A DUPLEX RECEPTACLE.
E2HA-13 C1044

SPD-MDP
OFFICE E1PB-10 E1PB-10
E1PD-48 C1043 ABOVE ATS-LEGAL TR-1A 260516 TR-G2 COORDINATE EXACT LOCATION WITH OWNER PROVIDED
C1001 +48" +48"
ABOVE CASEWORK BEFORE ROUGH-IN. ROUTE (1)-3/4"C.FROM BOX OVER
E1PB-22 H.7 AND UP NEAREST CHASE/WALL FOR POWER.
E1PD-48
EVIDENCE E1PD-52 +40" E1PB-22 L1P-13 E1PB-32 E1HA J
SPD-ODPA 260527 FLUSH, 4-GANG COMBO FLOOR BOX LIKE LEGRAND/WIREMOLD
E1PD-48 E1PD-48 TV
OFFICE E1PD-52 EVIDENCE +40" 260530 GFCI+48" ODPA E1PB-47 TR-G1 TR-G3 E1PB-47
E1PB-10 ABOVE ABOVE #RFB4 OR APPROVED EQUAL. MOUNT FLUSH IN FLOOR. FURNISH
+88" C1048 USB+48" E1PB-10 E1PB-22 PREP. E1PB-22 ELECTRICAL E1PA
DP-L 260531 WITH THREE (3)-20A DUPLEX RECEPTACLES AND ONE (1)-CAT6
E1PD-42
E1PD-48 DARK ROOM E1PB-8 C1045 C1054 SPD-E1PA 260510 COMMUNICATIONS OUTLET, REFERENCE KEYNOTE #270502 ON
E1PB-60,62
E1PD-42
E1PD-44

E1PD-52
E1PD-46
E1PD-46

LAB E1PB-24 SPD-DPL E1PB DRAWING #E-401-A. PROVIDE FLANGED CUTOUT COVER LIKE
CID WORK E1PD-52 E1PB-10 E1PB-12 E1PB-22 E1PB-32 MDPB STATION BATTERY
C1047C L1P SPD-E1PB MDPA #FPCTC##. VERIFY EXACT LOCATION WITH ARCHITECT BEFORE
E1PD-42 GROUP E1PB-20 E1PB-24 CHARGER
E1PD-52 260510 ROUGH-IN AND COORDINATE WITH G.C. DURING CONSTRUCTION.
* C1040 REFRIG GFCI+48" SPD-L1P
E1PB-12 260510 E1PB-47 COVER ASSEMBLY FINISH BY ARCHITECT. PROVIDE ALL
260521 260521 260521 260521

E1PB-8
260525 260525 E1PB-48 3 COMPONENTS FOR A COMPLETE INSTALLATION. ROUTE (1)-3/4"C.
E1PB-8 E1PB-24 RECEIVING FACP-1 E1PB-48
E1PD-48 E1PB-32 E1PB-32 W.P.+48" FROM BOX AS SHOWN FOR POWER. CONNECT TO CIRCUIT SHOWN
260521 260521 260521 260521

E1PB-12
GFCI+48" L1P-7
E1PD-42
E1PD-44

C1052A GFCI USING 2#12+G.


E1PD-44
E1PD-46

E1PB-12 GFCI+48" GFCI+48" TP-2


FCU-13
USB E1PB-28 E1PB-28 E1PB-24 E1PB-38 260528 FURNISH AND INSTALL 1-GANG FULLY ADJUSTABLE SHALLOW
DRUGS EVIDENCE E1PB-45 3 E1PB-44 E1PB-48 K
E1PD-50 GFCI+48" E1PB(61,63,65) E1HA(32,34,36) REV-1 CAST IRON FLOOR BOX, LIKE WALKER #880CM1-1 WITH ONE (1)

E1PB-8
GFCI+48" E1PB-45 GFCI+48"

E1PB-12
E1PD-50 C1051 PROCESSING

E1PB-14

E1PB-16

E1PB-18
#817B ONE-GANG BRASS FLANGE AND ONE (1) #828R BRASS

E1PB-30

E1PB-30
B-1 GFCI+48" HWP-1

REFRIG

REFRIG

REFRIG
E1PD-42 CID E1PD-50 C1047 E1PB-30 DUPLEX COVER PLATE. BOX TO HAVE ONE (1) 20A DUPLEX
STORAGE CWP-2 ODPA-10
GFCI+48"

+48"

+48"
RECEPTACLE. VERIFY EXACT LOCATION WITH OWNER AND
E1PD-50 E1PD-50 C1041 E1PB-8 E1HA(37,39,41) DWBP-1 ARCHITECT BEFORE ROUGH-IN. ROUTE (1)-3/4"C. FROM BOX OVER
E1PB-45
J TP-1 E1PB-40 MDPA-4 MDPA-5 AND UP/DN NEAREST WALL FOR POWER.

09/12/19
09/26/19
B-2 HWP-2 CWP-1

DATE
E1PB-30 REV-2 MECHANICAL E1PB-48 CHILLER CHILLER 260529 COMMUNICATIONS/DATA RACKS, REFER TO SPECIFICATIONS.
E2PD-9 E1PB(67,69,71) E1HA(38,40,42) L
E1PB-19 E1PB-19 E1PB-19 E1PB-19 E1PB-26 E1HA(31,33,35) C1053 GFCI+48" EACH RACK TO RECEIVE TWO 20A, 120V CIRCUITS, AS INDICATED,
E2PD-7

USB+48" E1PB-45
FUME HOOD B-FTR IN 3/4"C. FROM PANEL 'U2R'. PROVIDE 2#12+G PER CIRCUIT.
E2PD-7 GFCI+48"
E1PB-19 260530 PREACTION DRY-POWER SYSTEM, 120V. CONNECT TO CIRCUIT
TCP HWP-FTR CWP-FTR
E2PD-7 E1PB-21 CH-1 CH-2 SHOWN USING 2#12+G. IN 3/4"C. COORDINATE EXACT LOCATION.
L1P-8
TV MATRON E2PD-9 REFRIG E1PB-23 260531 CONNECT TO CIRCUIT SHOWN WITH 2#10+G. IN 3/4"C.
+84" E1PB-39 260541 DEVICE TO BE FLUSH MOUNTED IN CEILING FOR CEILING
C1080 E1HA(14,16,18) REV-FTR
ARMORY WH-3 E1PB-46 PROJECTOR. COORDINATE EXACT LOCATION WITH OWNER AND

REVISION
E1HA(20,22,24) HWRP-1 E1PB-37 3 E1PB-34 E1PB-36
C1050 FCU-14 RECEPTS RECEPTS ARCHITECT BEFORE ROUGH-IN.
E2PD-9 E1PB-23 HWRP-1 WH-FTR WH-2
260544 ELECTRIC DOOR. VERIFY WITH MANUFACTURER ALL FINAL

1 Addendum #01
3 Addendum #03
+48" 260531 E1PB-35 E1PB-33 CONNECTIONS.
E2PD-34 E2PD-34 E1PB-23 E1PB-23 E1PB(54,56) W.P.+48"
WH-1 E1PB-33 260546 FURNISH AND INSTALL 240VAC, 3-POLE, 30A HEAVY DUTY

GFCI+48"

GFCI+48"
CRAC-1 RO-1 WS-1

E1PB-33

E1PB-33
260509 EVIDENCE +48" GFCI NON-FUSED SAFETY DISCONNECT SWITCH IN NEMA 4X STAINLESS
SECURITY GFCI+48"
E2HB(14,16,18) 260510 STORAGE M STELL ENCLOSURE WITH KEY INTERLOCK SYSTEM. CONNECT TO
C1079 E1PB-58 CIRCUIT SHOWN USING 3#10+G. IN 3/4"C. PROVIDE CONNECTION
SQE#1 C1049 FA-GAP TMV-1 E1PB-43
E1PB-25 RO+48" AS NEEDED BETWEEN DISCONNECT AND WASHER.
L1P-9 GFCI+48"
E2PD-34 E1PB-23 GFCI

NO.
SECURE 260547 FURNISH AND INSTALL 125VAC, 20A, 1-POLE MANUAL MOTOR
CORRIDOR E1PB-25 E1PB-43 E1PB-43 STARTER WITH TOGGLE DISCONNECT IN NEMA 1 ENCLOSURE.
B1025 FACILITY USB GFCI+48" E1PB-29 GFCI+36" E1PB-29 FURNISH WITH RED (RUN) LED PILOT LIGHT, MOTOR RATED.
E2PD-34 E2PD-34

E2PD-11
E1PB-17
E1PB-25
OFFICE
C1055
HUH-2
E1PB-27
HUH-1 GENERAL NOTES CONNECT TO CIRCUIT SHOWN USING 2#12+G. IN 3/4"C. PROVIDE
CONNECTION AS NEEDED BETWEEN SWITCH AND DRYER.
E1PB-31

CHK'D: MLH
E1PB-25
E2PD-11

RECEIVING

SEPTEMBER 5, 2019
USB+48" A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702, E-703, 260548 COMMUNICATIONS DATA CABINET, REFER TO SPECIFICATIONS.
E2PD-11 E1HA(19,21,23)

1663-1190-90
E1PB-17 C1052 E-704, E-705, E-706 AND E-707. CONNECT TO CIRCUIT INDICATED USING 2#12+G. IN 3/4"C.
SECURE E2PD-11 E2PD-17 DAC-1 260551 WALL MOUNTED SECURITY CABINET/RACK, REFER TO SE
CORRIDOR E1PB-17 3
TV E1PB-25 B. SEE MECHANICAL EQUIPMENT - ELECTRICAL CONNECTIONS DRAWINGS FOR MORE INFORMATION. CONNECT TO CIRCUIT
ASSISTANT

PROJECT NUMBER
B1025 +84" SCHEDULE ON DRAWINGS E-604 & E-605 FOR EQUIPMENT 3 SHOWN USING 2#12+G. IN 3/4"C.
JAIL

DESIGNED: RDW
CIRCUITING AND ADDITIONAL ELECTRICAL EQUIPMENT

MLH
E1PB-17 E1PB-29
COMMANDER

DRAWN: RDW
W.P.+48" REQUIREMENTS FOR MECHANICAL EQUIPMENT (I.E. DISCONNECT,
E2PD-17 C1078 PASSAGE GFCI STARTER, ETC) AND EQUIPMENT NAMEPLATE ELECTRICAL LOAD

APPRV'D:
C1052B INFORMATION (I.E. VOLTS, PHASE, FLA, MOCP, ETC.).
E2PD-17 E1PB-29 E1PB-29

DATE:
E1PB-29 C. CONTRACTOR SHALL FIELD COORDINATE, PRIOR TO
CONSTRUCTION, EXACT MOUNTING HEIGHTS AND LOCATIONS FOR
E1PB-17 WIRING DEVICES WITH THE CASEWORK SHOP DRAWINGS AND
JAIL E2PD-13
COMMANDER E1PB-13 E1PB-13 FREEZER ARCHITECTURAL ELEVATIONS AND DETAILS.
E1PB-13 GFCI+48" GFCI+48" E1PB-13
C1077 C1064B D. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND
E2PD-17 STORAGE INTERLOCK CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
E2PD-13

VIGO COUNTY SECURITY CENTER


TV C1057 K1L C1063 FREEZER DIS-1EPP RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
+84" FACILITY K2L AND OFFSET BACK TO BACK BOXES.
E2PD-13 E1PB-15 K1H C1064B DIS-2EPP
AIR COMPRESSOR WORKSHOP

FIRST FLOOR POWER PLAN - AREA C


3 USB+48" E. REFER TO SECURITY DRAWINGS, #SE SERIES, FOR ADDITIONAL
C1056 E1PB-13 DIS-3EPP
EQUIPMENT AND WIRING REQUIREMENTS. PROVIDE BOXES,
PA-2 WELDING RACEWAYS, CABLING, SUPPORTS, ETC. AS REQUIRED FOR
260530 3
E1PB-11

B1056B SECURITY EQUIPMENT. REFER TO SPECIFICATION SECTIONS 078123


L1P-15 "INTUMESCENT FIREPROOFING" AND 078443 "JOINT FIRESTOPPING"
E2PD-15 E2PD-15 E1HA(13,15,17) 260531 E1PB-11 FOR DETAIL FIRESTOP REQUIREMENTS.
E1PB-11

JANITOR GFCI+48" 260523


EF-8 TR-K1 TR-K2
C1076 E1PB-7,9 E1PB-11 F. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO
ABOVE OFFICE
E1PB-11 3 COOLER SPECIFICATION 079200 "JOINT SEALANTS" FOR DETAILED
E1PB-11 C1062

TERRE HAUTE, INDIANA


C1064A REQUIREMENTS FOR SEALANT(S).
E2PD-15 E2PD-19 E2PD-21 E2PD-22 VIDEO E2PD-20 E2PD-18 E2PD-18
* 260510 G. WATER MANAGEMENT SYSTEM TO BE PROVIDED BY OTHERS.
* * * ARRAIGNMENT * E2PD-18 USB+48"
M CONNECT ALL VALVE CONTROLLERS AS FOLLOWS:
260504 E2PD-19 E2PD-19 E2PD-21 E2PD-21 C1070 E2PD-16 JUDGE
* IN AREA B TO CIRCUIT E2PA-36, E2PB-31, E2PC-31 OR E2PE-21.
260505 * * * E2PD-20 E2PD-16

A NEW
260521 C1069 DRY 1 IN AREA C TO CIRCUIT K1L-7.
INMATE/ INMATE/ * KITCHEN
E2PD-24 TV E2PD-18 STORAGE E-201-K IN AREA D TO CIRCUIT E4PA-37, E5PA-45 OR E5PB-41.
ATTORNEY ATTORNEY E2PD-22 C1059 K3L-7
+84" C1064 IN AREA E TO CIRCUIT E4PA-39, E4PB-41 OR E5PA-47.
CONFERENCE CONFERENCE E2PD-20 GFCI+48" 260547
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

* E2PD-16 EACH CIRCUIT TO BE 2#12+G. IN 3/4"C. REFER TO CELL VALVE


C1074 E2PD-24 *,TV WASHER
C1075 CONTROLLER (CVC) CONNECTION DETAIL #5 ON SHEET E-804.
260517 +88"
E2PD-12 E2PD-14 DRYER COORDINATE CONTROLLER LOCATIONS BEFORE ROUGH-IN. KEY PLAN
E2PD-19 E2PD-21 STAFF M M M
E2PD-12 USB+48" TOILET CHASE
* *

K3L-14

K3L-16
K3L-18
ATTORNEY K3L-10 K3L
E2PD-22 E2PD-20 C1061 C1065B
K3L-10

K3L-10
*
E2PD-19 E2PD-12 C1068 *
* * TV *,TV
* VIDEO PASSAGE E2PD-14 N
+84" INMATE +84"
ARRAIGNMENT E2PD-23 E2PD-8 C1067 FPV-1-24 K3L-9,11
WAITING * * E2PD-14 TOILET DRYER+48"
VIDEO K1H-8
C1073 ARRAIGNMENT C1060 260531

E2PD-23 VIDEO C1071 E2PD-8


* ARRAIGNMENT 260521 E2PD-8
WAITING K3L-10 LAUNDRY
* TRASH
C1072 *,+40" C1065

K3L-8
E2PD-10
K3L(13,15,17)

K3L(19,21,23)
E2PD-8 C1066

K3L(25,27,29)
* E2PD-10 *,TV A B C
K3L-8

*
260546

260546
+88"

260546
FPV-1-25 K3L-8 K3L-8
E2PD-23
E2PD-23 E2PD-10 K1H-10 K3L-10 *,+40" K3L-8 W.P.
* K3L-8 *
* * *,+40" * GFCI+48"
9/25/2019 5:22:09 PM

*
E2PD-23 E4PB-18 EWH-3
260504 E4PB-26
E4PB-18
*

* E2PD-8 *
* 260505 260504 E4PB-33
SECURE
U1R-42 K1L-30 M 260505

E-201-C
M

DRAWING NUMBER
CORRIDOR
M 260548 E1012 M

ELECTRICAL
260504 IT E4PB-28 260504 INTERLOCK
IDF E4PB-31
E5PA-33 260505 E1004 E4PB-31 260505 E1013
E5PA-32 CABINET #2 SUR
* GFCI+48" * D E
E4PB-31 E1009D E4PB-31
1 FIRST FLOOR POWER - AREA 'C'
E-201-C SCALE: 1/8" = 1'-0"
NORTH
GENERAL NOTES
A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702, E-703,
E-704, E-705, E-706 AND E-707.

B. SEE MECHANICAL EQUIPMENT - ELECTRICAL CONNECTIONS


SCHEDULE ON DRAWINGS E-604 & E-605 FOR EQUIPMENT
CIRCUITING AND ADDITIONAL ELECTRICAL EQUIPMENT

DLZ INDIANA, LLC


REQUIREMENTS FOR MECHANICAL EQUIPMENT (I.E. DISCONNECT,
STARTER, ETC) AND EQUIPMENT NAMEPLATE ELECTRICAL LOAD
INFORMATION (I.E. VOLTS, PHASE, FLA, MOCP, ETC.).

C. CONTRACTOR SHALL FIELD COORDINATE, PRIOR TO


CONSTRUCTION, EXACT MOUNTING HEIGHTS AND LOCATIONS FOR
WIRING DEVICES WITH THE CASEWORK SHOP DRAWINGS AND
ARCHITECTURAL ELEVATIONS AND DETAILS.

D. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND


CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
5 6 7 8 9 AND OFFSET BACK TO BACK BOXES.

E. REFER TO SECURITY DRAWINGS, #SE SERIES, FOR ADDITIONAL


E2PC-19 EQUIPMENT AND WIRING REQUIREMENTS. PROVIDE BOXES,
MICRO+56" RACEWAYS, CABLING, SUPPORTS, ETC. AS REQUIRED FOR
E2PC-25 E2PC-13
* SECURITY EQUIPMENT. REFER TO SPECIFICATION SECTIONS 078123
"INTUMESCENT FIREPROOFING" AND 078443 "JOINT FIRESTOPPING"
EWH-1 260504 260505 E2PE-8 LACTATION E2PC-13 FOR DETAIL FIRESTOP REQUIREMENTS.
E5PB-18 * 260504 ROOM *
E5PB-33 E2PC-32
* 3 260505 F. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO

M
SECURE M B1123
INTERLOCK E5PB-26 CORRIDOR SPECIFICATION 079200 "JOINT SEALANTS" FOR DETAILED R
EE
M U1R-40 M REQUIREMENTS FOR SEALANT(S). CK IN
D1013 260504 D1012 IT 260504 CO

SS D I A N G
E5PB-28 E5PB-31

I ON A L E N
PE60018676
IDF 260548 D

H
260505 260502 260505

A
E5PB-31 D1010

STATE OF
E5PB-18 SUR

L . H I TC
G. WATER MANAGEMENT SYSTEM TO BE PROVIDED BY OTHERS.

E
D1005D 260508 E5PA-26

I ST ER
* GFCI+48" * CABINET #1 CONNECT ALL VALVE CONTROLLERS AS FOLLOWS:

No.
STORAGE IN AREA B TO CIRCUIT E2PA-36, E2PB-31, E2PC-31 OR E2PE-21.
E5PB-31 E5PB-31 E5PA-25 E5PA-25 E5PA-30

EG
D1005B IN AREA C TO CIRCUIT K1L-7.

IN
3 TOILET / TOILET / INMATE

IN
260508 * *,VV E5PA-33 IN AREA D TO CIRCUIT E4PA-37, E5PA-45 OR E5PB-41.
R
E5PB-18 E5PB-35 TOILET RV
SHOWER SHOWER E5PA-25 *
E5PB-18 *,GFCI M
IN AREA E TO CIRCUIT E4PA-39, E4PB-41 OR E5PA-47. MA FE
*,GFCI+48" JANITOR D1007 D1008 * D1014 EACH CIRCUIT TO BE 2#12+G. IN 3/4"C. REFER TO CELL VALVE P RO
E5PB-16 260501 E5PA-30 DS-D STORAGE
E5PA-25 CONTROLLER (CVC) CONNECTION DETAIL #5 ON SHEET E-804.
GFCI+48" D1004 3 260504 D1012A COORDINATE CONTROLLER LOCATIONS BEFORE ROUGH-IN.
*
260519 CONFERENCE
260508 260511 E4PA-31 E5PA-33
ROOM
E5PB-31 E5PB-29 * GFCI+48"
CELL 260508 1 D1009

CHASE
D1126 E5PB-9
C-G
E5PB-23
*
INDOOR/OUTDOOR
RECREATION
E5PA-27
*
E5PA-27
*
*,TV
C-I
E5PA-25
260508
E4PA-7
POWER KEYNOTES 2605##

+88"
D1015A +46" D1005 * C-G
260508 CELL 260501 FURNISH AND INSTALL POWER (20A, 120V) AND CONTROL WIRING
E5PA-25 +46"
D1021 FOR OVERHEAD DOOR CONTROLLERS. DOOR SAFETIES/LIMIT
E5PB-27 E5PB-29 *
CELL E5PA-27 SWITCHES AND KEYED OPEN-STOP-CLOSE PUSHBUTTON
*,TV E5PA-27 1 * CONTROLLER STATIONS (WHERE INDICATED) FURNISHED BY
D1125 260511
C-I * CLASSROOM INTERLOCK OVERHEAD DOOR EQUIPMENT VENDOR. REFER TO
INTERLOCK +96" SPECIFICATION 083613 "SECTIONAL DOORS" FOR DETAILED
D1003 D1006 D1011 CHASE
E5PB-29 REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT SWITCHES, DOOR
E5PB-16 *,TV E1016 STARTER/CONTROLLER, AND PUSHBUTTON CONTROL STATION
GFCI+48"
CELL C-I 260511 E5PA-27 PER MANUFACTURERS RECOMMENDATION. FURNISH AND
+96" * CELL E4PA-19 INSTALL ALL CABLING/CONDUIT REQUIRED FOR COMPLETE
D1124 GFCI+48" SYSTEM. FIELD-COORDINATE THE EQUIPMENT INSTALLATION AND
VESDA
D1022
L2P-18 260508 CABLING/CONDUIT REQUIREMENTS WITH THE DOOR EQUIPMENT
260508 VENDOR PRIOR TO CONSTRUCTION.
CP-1 E5PB-27 E5PB-27

VESDA

VESDA
L2P-12 260502 OVERHEAD DOOR SAFETY INTERLOCK DEVICES FURNISHED BY
E5PA-27 CP-6 OVERHEAD DOOR VENDOR, INSTALLED BY CONTRACTOR.
CELL E5PB-23 E5PA-27 E4PA-31
* E4PA-31 L2P-13 260504 FURNISH AND INSTALL CONDUIT (3/4"C.) FROM EACH DOOR
D1123 *,VV E5PB-27 * * CP-7
FCU-1 *,VV STARTER/CONTROLLER TO SECURITY CONTROL PANEL FOR
E5PB-23 *,VV
E5PB-23 ACCESS CONTROL WIRING. WIRING AND TERMINATIONS BY
E5PB-20 * E4PA-31 CELL
1-K OTHERS. REFER TO SECURITY SERIES SHEETS FOR DETAILED
*,VV *,VV D1023 WIRING REQUIREMENTS.
D1120
CELL E5PB-23 INTERLOCK 260505 FURNISH AND INSTALL POWER (1/8HP, 120V) FOR SLIDING DOOR
E4PA-31 1-A
*,VV E5PB-30 D1001A E5PA-28 CONTROLLERS, DOOR SAFETIES/LIMIT SWITCHES AND KEYED
D1122 *,VV D1020 OPEN-CLOSE PUSHBUTTON CONTROL STATIONS FURNISHED BY

M
E5PB-23 DOOR EQUIPMENT VENDOR. CONTROL WIRING BY OTHERS.
3 260504 260504 260505 E4PA-31
*,VV REFER TO SPECIFICATION 087100 "DOOR HARDWARE" FOR
260505 *,VV
STAFF DETAILED REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT
3 TOILET E5PB-25 260508 SWITCHES AND CONTROL SWITCH(S) PER MANUFACTURERS
SP-2 E5PB-32 260511 E5PB-25 * 260511 CELL ADA
260550 260508 E4PA-21 260508 RECOMMENDATION. FURNISH AND INSTALL CONDUIT/POWER
D0001 CELL ADA E5PB-7 260508 3 * E4PA-10 260508
U1R-31 E5PB-39 D1024 C-I WIRING REQUIRED FOR A COMPLETE SYSTEM.
E5PB-8 D1121 *,TV E5PB-9 1 CONTROL *,TV E4PA-7 FIELD-COORDINATE THE EQUIPMENT INSTALLATION AND CONDUIT
J 260522 SQE#14 C-I REFRIG GFCI E4PA-19
E5PB-42 C-I C-G INTERLOCK C-I C-G REQUIREMENTS WITH THE DOOR EQUIPMENT VENDOR PRIOR TO
E5PB-36 GFCI D1000 GFCI+48"
+96" +46" U1R-13 D1002A +96" +46" CONSTRUCTION.
EWH-4
GFCI E5PB-32 U1R-11 GFCI+42" E5PB-37
E5PB-16 260508 FURNISH AND INSTALL RECEPTACLE IN CUSTOM FLUSH
E5PB-32 GFCI+48" MICRO+42"
GFCI+48" MOUNTED, LOCKABLE WALL CABINET. FOR CABINET DETAIL, SEE
GFCI+48" 3 SHEET E-803, DETAIL #7.

U1R-11
CELL E5PB-7 E5PB-11 U1R-7 E4PA-10 E4PA-9 CELL
*,TV C-G U1R-9 260524 BELOW 260511 RECEPTACLE INDIVIDUALLY CONTROLLED BY SECURITY
E5PB-32 SPD-E5PB D1112 2 *,TV C-G D1031
INTERLOCK ELECTRONIC CABINET RELAY. REFER TO SECURITY EQUIPMENT
GFCI
E5PB-34

C-I +46" U1R-11 C-I +46"


E5PB 1-J E5PB-21 E-201-D 1-B PLANS AND DIVISION 28 SPECIFICATIONS FOR DETAILED WIRING
+96" 260508 D1001B E4PA-33 +96" 260508
SP-1 D1110 E5PB-21 *,VV E4PA-33 D1030 REQUIREMENTS.
TR-5B 260511 E5PB-25 *,VV 260511
*,VV *,VV
* U1R-11 260519 CONTROL SWITCH(S) TO BE LOCATED IN CONTROL #D1000,
MECHANICAL SQE#8 260508 3 COORDINATE EXACT LOCATION PRIOR TO ROUGH-IN.
D0002 U1R-38 CELL ADA E4PA-25 260508
CELL ADA E5PB-21 E4PA-33 260508 260522 AUTOMATIC FLUSH VALVE. REFER TO AUTOMATIC ELECTRIC
260550 E5PB-8 C-I
D1111 E5PB-21 *,VV E5PB-25 *,VV E4PA-33 E4PA-9 D1032 FLUSH VALVE DETAIL #2 ON SHEET E-801.
C-I E5PB-11 E5PB-21 * *,VV GFCI
260508 *,VV E4PA-33 C-G 260524 FURNISH AND INSTALL 8-GANG FLOOR BOX, LIKE
GFCI C-G 260508 *,VV INTERLOCK *,VV +46" LEGRAND/WIREMOLD #EFB8S OR APPROVED EQUAL WITH TWO (2)

09/12/19
09/26/19
DATE
+46" D1002B #EFB-8M 4-GANG MOUNTING BRACKETS, ONE (1) #EFB610BTXX
FLUSH STYLE COVER LID WITH FINISH PER ARCHITECT. BOX TO
E5PB-13 HAVE SIX (6) DEVICE PLATES WITH SIX (6) 20A DUPLEX
2 LOWER LEVEL POWER - AREA 'D' 1-C
C-G 260508 E5PB-19 E4PA-35 E4PA-11 RECEPTACLES, ONE (1) #EFB-B BLANK DEVICE PLATE AND ONE (1)
E5PB-16 260508 +46" D1040 E4PA-19
E-201-D SCALE: 1/8" = 1'-0" 1-H *,VV *,VV C-G COMMUNICATIONS OUTLETS, REFERENCE KEYNOTE #270511 ON
GFCI+48" GFCI+48"
D1090 +46" E-401 SERIES SHEETS. VERIFY EXACT LOCATION WITH ARCHITECT
NORTH E5PB-8 CELL ADA E5PB-19 E4PA-35 CELL ADA E4PA-23
260508 BEFORE ROUGH-IN. ROUTE (2)-3/4"C. FROM BOX OVER AND UP
VESDA

C-I D1093 *,VV *,VV D1041 C-I 260508 NEAREST WALL FOR POWER. PROVIDE A MAXIMUM OF (3)
L2P-18 GFCI E5PB-19 GFCI

REVISION
CP-2 E4PA-35 260508 RECEPTACLES PER CIRCUIT.
E5PB-19 *,VV *,VV E4PA-35

VESDA

VESDA
*,VV *,VV L2P-12 260548 COMMUNICATIONS DATA CABINET, REFER TO SPECIFICATIONS.

1 Addendum #01
3 Addendum #03
CP-5 CONNECT TO CIRCUIT INDICATED USING 2#12+G. IN 3/4"C.
E5PB-19 E4PA-35 L2P-13 260549 COMMUNICATIONS DATA CABINET, REFER TO SPECIFICATIONS.
260511 E5PB-19 260511 CP-8
*,VV E4PA-35 *,VV CONNECT TO CIRCUIT INDICATED USING 2#10+#10G. IN 3/4"C.
E5PB-13 *,VV E4PA-11 260508
E5PB-19 *,VV E4PA-35 260550 WALL MOUNTED SECURITY RACK, REFER TO SE DRAWINGS FOR
C-G C-G
CELL *,VV E4PA-10 CELL MORE INFORMATION. CONNECT TO CIRCUIT SHOWN USING
E5PB-7 +46" *,VV 1-D +46"
*,TV D1042 2#10+#10G. IN 3/4"C.
D1092 *,TV 1-E
260508 C-I D1050 C-I

NO.
260511 +96"
D1060
+96" 1-F E4PA-10
260511
1-G E5PB-17 D1070 *,TV
D1080 C-G C-I
260511 +46" +96" 260511

CHK'D: MLH
E4PA-10

SEPTEMBER 5, 2019
E5PB-15 E5PB-7 E4PA-12
*,TV

1663-1190-90
C-G *,TV C-G CELL E4PA-19
CELL +46" +46" C-I
C-I GFCI+48"
D1091 +96" D1043
E5PB-7 +96" 260508

PROJECT NUMBER
*,TV 260508 E4PA-8

DESIGNED: RDW
C-I

MLH
E5PB-16 C-G
+96"

DRAWN: RDW
GFCI+48" +46"
260508 260508
E5PB-15 E4PA-8

APPRV'D:
260508 C-G 260508 C-G 260508
E5PB-22

DATE:
+46" E5PB-17 260508 +46"
FCU-2 IDF C-G E4PA-12
CABINET #3 +46" C-G
260549 +46"
U1R-46

FIRST FLOOR AND LOWER LEVEL POWER PLANS -


VIGO COUNTY SECURITY CENTER
E5PB-14 FCU-5
CELL CELL CELL CELL ADA CELL ADA CELL CELL CELL ADA CELL ADA CELL CELL CELL
GFCI+48" E4PA-14
D1084 D1083 D1082 D1081 D1072 D1071 D1062 D1061 D1054 D1053 D1052 D1051
E4PA-17 STORAGE
* E1016B
TCP
L2P-16
INTERLOCK
D1016
E5PB-12 E5PB-12 E4PA-27 E4PA-27
C-I C-I C-I C-I
CHASE GFCI GFCI GFCI GFCI E4PA-17

TERRE HAUTE, INDIANA


E5PB-14 EWH-6
GFCI+48" D1015B GFCI+48"
E4PA-40
260508 260508 260508 260508
E5PB-24 L2P-14 L2P-14 E4PA-16 E4PA-17

AREA D
E5PB-14 FCU-3 E5PB-14 CP-3 E5PB-14 E4PA-13 CP-4 FCU-4 E4PA-13 E4PA-13 GFCI+48"

A NEW
GFCI+48" GFCI+48" VESDA GFCI+48" GFCI+48" VESDA GFCI+48" GFCI+48"

E4PA-13
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

W.P.
GFCI
KEY PLAN

1 FIRST FLOOR POWER - AREA 'D'


E-201-D SCALE: 1/8" = 1'-0"
NORTH

A B C
9/25/2019 5:22:47 PM

E-201-D
DRAWING NUMBER

ELECTRICAL
D E
GENERAL NOTES
A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702, E-703,
E-704, E-705, E-706 AND E-707.

B. SEE MECHANICAL EQUIPMENT - ELECTRICAL CONNECTIONS


SCHEDULE ON DRAWINGS E-604 & E-605 FOR EQUIPMENT

DLZ INDIANA, LLC


CIRCUITING AND ADDITIONAL ELECTRICAL EQUIPMENT
REQUIREMENTS FOR MECHANICAL EQUIPMENT (I.E. DISCONNECT,
STARTER, ETC) AND EQUIPMENT NAMEPLATE ELECTRICAL LOAD
INFORMATION (I.E. VOLTS, PHASE, FLA, MOCP, ETC.).

C. CONTRACTOR SHALL FIELD COORDINATE, PRIOR TO


CONSTRUCTION, EXACT MOUNTING HEIGHTS AND LOCATIONS FOR
WIRING DEVICES WITH THE CASEWORK SHOP DRAWINGS AND
ARCHITECTURAL ELEVATIONS AND DETAILS.

18 19 D. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND


CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS

K3L-8
260546

260546

260546
FPV-1-25 K3L-8 K3L-8 AND OFFSET BACK TO BACK BOXES.
E2PD-23
E2PD-23 E2PD-10 K1H-10 K3L-10 *,+40" K3L-8 W.P.

*
* K3L-8
* * *,+40" * GFCI+48" E. REFER TO SECURITY DRAWINGS, #SE SERIES, FOR ADDITIONAL
*
EQUIPMENT AND WIRING REQUIREMENTS. PROVIDE BOXES,
E2PD-23 E4PB-18 EWH-3 RACEWAYS, CABLING, SUPPORTS, ETC. AS REQUIRED FOR
260504 E4PB-26

E4PB-18
*
* E2PD-8 * SECURITY EQUIPMENT. REFER TO SPECIFICATION SECTIONS 078123
* 260505 260504 "INTUMESCENT FIREPROOFING" AND 078443 "JOINT FIRESTOPPING"
SECURE
U1R-42 K1L-30 M 260505 M FOR DETAIL FIRESTOP REQUIREMENTS.
CORRIDOR
M 260548 E1012 M
260504 IT E4PB-28 260504 INTERLOCK F. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO
IDF E4PB-31
E5PA-33 260505 E1004 260502 E4PB-31 260505 E1013 SPECIFICATION 079200 "JOINT SEALANTS" FOR DETAILED R
E5PA-32 CABINET #2 SUR EE
* GFCI+48" * REQUIREMENTS FOR SEALANT(S). CK IN
CO

SS D I A N G
I ON A L E N
PE60018676
D

A
STORAGE

STATE OF
L . H I TC
E5PA-34

E
E5PA-31 E5PA-31 E4PB-31 E1009D E4PB-31 G. WATER MANAGEMENT SYSTEM TO BE PROVIDED BY OTHERS.

I ST ER
* *,VV TOILET / TOILET / 260508 E1009B 3 CONNECT ALL VALVE CONTROLLERS AS FOLLOWS:

No.
E4PB-35 260508 E4PB-18
SHOWER SHOWER *,GFCI IN AREA B TO CIRCUIT E2PA-36, E2PB-31, E2PC-31 OR E2PE-21.
DS-E M

EG
IN AREA C TO CIRCUIT K1L-7.

IN
E1006 E1007 E4PB-18

IN
E5PA-31 260501 JANITOR IN AREA D TO CIRCUIT E4PA-37, E5PA-45 OR E5PB-41.
R
E5PA-34 E5PA-31 *,GFCI+48" E4PB-16 RV
E4PA-32 *
* 260504 E1011 GFCI+48" IN AREA E TO CIRCUIT E4PA-39, E4PB-41 OR E5PA-47. MA FE
260520 EACH CIRCUIT TO BE 2#12+G. IN 3/4"C. REFER TO CELL VALVE P RO
E5PA-33 FCU-6 * CONFERENCE 260511
E5PA-35 260508 E4PB-23 CONTROLLER (CVC) CONNECTION DETAIL #5 ON SHEET E-804.
GFCI+48" ROOM E4PB-29
260508 E5PA-29 E5PA-29 E4PB-31 2 * CELL COORDINATE CONTROLLER LOCATIONS BEFORE ROUGH-IN.
E1005 *,TV 260508
E4PA-20 C-I * * INDOOR/OUTDOOR E1021
E5PA-31 E4PB-9
C-G RECREATION

CELL
+46" * +88"
E1009
260508
C-G
+46"
CHASE
POWER KEYNOTES 2605##

E1124 E5PA-31 E5PA-29 E4PB-27 E1014A


E5PA-29 E4PB-29 260501 FURNISH AND INSTALL POWER (20A, 120V) AND CONTROL WIRING
* * CELL
2 * *,TV FOR OVERHEAD DOOR CONTROLLERS. DOOR SAFETIES/LIMIT
CLASSROOM C-I 260511 E1022
SWITCHES AND KEYED OPEN-STOP-CLOSE PUSHBUTTON
E1008 E4PB-29 +96" CONTROLLER STATIONS (WHERE INDICATED) FURNISHED BY
CHASE INTERLOCK
INTERLOCK *,TV OVERHEAD DOOR EQUIPMENT VENDOR. REFER TO SPECIFICATION
E1016 260511 C-I E1010 083613 "SECTIONAL DOORS" FOR DETAILED REQUIREMENTS.
E1003 E5PA-29 INSTALL DOOR SAFETIES/LIMIT SWITCHES, DOOR
+96" CELL
E4PA-19 * STARTER/CONTROLLER, AND PUSHBUTTON CONTROL STATION
GFCI+48" CELL
E1023 PER MANUFACTURERS RECOMMENDATION. FURNISH AND INSTALL

VESDA
E1123 E5PA-29 ALL CABLING/CONDUIT REQUIRED FOR COMPLETE SYSTEM.
L2P-19
* 260508
CP-12 FIELD-COORDINATE THE EQUIPMENT INSTALLATION AND
VESDA E4PB-27 E4PB-27 CABLING/CONDUIT REQUIREMENTS WITH THE DOOR EQUIPMENT

VESDA
L2P-12 E4PA-32
* 260508 VENDOR PRIOR TO CONSTRUCTION.
CP-6 E4PA-32 CELL E4PB-16
L2P-13 E5PA-29 E4PB-27 E4PB-23 260502 OVERHEAD DOOR SAFETY INTERLOCK DEVICES FURNISHED BY
*,VV E4PB-23 E1024 GFCI+48"
CP-7 * *,VV *,VV OVERHEAD DOOR VENDOR, INSTALLED BY CONTRACTOR.
E4PA-32 *
FCU-10 260504 FURNISH AND INSTALL CONDUIT (3/4"C.) FROM EACH DOOR
CELL *,VV E4PB-23
E4PB-20 STARTER/CONTROLLER TO SECURITY CONTROL PANEL FOR
2-A *,VV
E1122 ACCESS CONTROL WIRING. WIRING AND TERMINATIONS BY
E1120 E4PA-32 2-K OTHERS. REFER TO SECURITY SERIES SHEETS FOR DETAILED
INTERLOCK E4PB-23 CELL
*,VV INTERLOCK E1020 WIRING REQUIREMENTS.
E5PA-36 E1001A E4PB-30 *,VV E1025
E1002A 260505 FURNISH AND INSTALL POWER (1/8HP, 120V) FOR SLIDING DOOR

M
STAFF U1R-33 CONTROLLERS, DOOR SAFETIES/LIMIT SWITCHES AND KEYED
TOILET 260504 260504 SQE#15 OPEN-CLOSE PUSHBUTTON CONTROL STATIONS FURNISHED BY
E4PB-25 DOOR EQUIPMENT VENDOR. CONTROL WIRING BY OTHERS. REFER
E0001 260505 260505
3 260508 * SPD-E4PB
SP-2 260511 260511 TO SPECIFICATION 087100 "DOOR HARDWARE" FOR DETAILED
E4PB-32 260508 E4PA-21 ADA CELL E4PB-25 260508 E4PB REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT SWITCHES AND
E4PA-30 260508 E4PB-7 260508 CELL ADA
C-I E4PB-39 1 CONTROL * 3 CONTROL SWITCH(S) PER MANUFACTURERS RECOMMENDATION.
E1121 *,TV E4PA-20 *,TV E4PB-9 E1026 E4PB-8 TR-4B
GFCI REFRIG E1000 FURNISH AND INSTALL CONDUIT/POWER WIRING REQUIRED FOR A
E4PB-42 260522 J E4PA-19 C-I C-G C-I C-G C-I SQE#10 COMPLETE SYSTEM. FIELD-COORDINATE THE EQUIPMENT
E4PB-36 GFCI+48" +96" +46" +96" +46" GFCI
EWH-5 U1R-14 U1R-41 INSTALLATION AND CONDUIT REQUIREMENTS WITH THE DOOR
E4PB-32 GFCI U1R-12
E4PB-37 GFCI+42" EQUIPMENT VENDOR PRIOR TO CONSTRUCTION.
GFCI+48" E4PB-32 MICRO+42" E4PB-16
260508 FURNISH AND INSTALL RECEPTACLE IN CUSTOM FLUSH MOUNTED,
GFCI+48" GFCI+48" LOCKABLE WALL CABINET. FOR CABINET DETAIL, SEE SHEET
CELL U1R-8 BELOW E4PB-7 E4PB-11
E4PA-30 E4PA-22 260524 2 CELL 3
E4PB-32 U1R-12 *,TV C-G E-803, DETAIL #7.
E1112 *,TV C-G E1031
U1R-12 E-201-E C-I +46" 260511 RECEPTACLE INDIVIDUALLY CONTROLLED BY SECURITY
GFCI
E4PB-34

C-I +46" E4PA-34 E4PB-21


2-B 2-J +96" 260508 ELECTRONIC CABINET RELAY. REFER TO SECURITY EQUIPMENT
+96" 260508 E4PA-34 *,VV *,VV E4PB-21
SP-1 E1110 U1R-12 E1030 260511 PLANS AND DIVISION 28 SPECIFICATIONS FOR DETAILED WIRING
260511 *,VV E4PB-25 *,VV
U1R-12 REQUIREMENTS.
260508 *
260520 CONTROL SWITCH(S) TO BE LOCATED IN CONTROL #E1000,
260508 E4PA-25 CELL ADA INTERLOCK 260508 3
E4PA-34 E4PB-21 CELL ADA COORDINATE EXACT LOCATION PRIOR TO ROUGH-IN.
MECHANICAL C-I E4PB-25 E1001B E4PB-8
E1111 E4PA-34 *,VV *,VV E4PB-21 E1032 260522 AUTOMATIC FLUSH VALVE. REFER TO AUTOMATIC ELECTRIC
E0002 GFCI E4PA-22 * E4PB-11 C-I
E4PA-34 *,VV *,VV E4PB-21 FLUSH VALVE DETAIL #2 ON SHEET E-801.
C-G 260508 *,VV INTERLOCK *,VV 260508 C-G GFCI
260524 FURNISH AND INSTALL 8-GANG FLOOR BOX, LIKE
+46" E1002B +46" LEGRAND/WIREMOLD #EFB8S OR APPROVED EQUAL WITH TWO (2)
2-H #EFB-8M 4-GANG MOUNTING BRACKETS, ONE (1) #EFB610BTXX

09/12/19
09/26/19
2 LOWER LEVEL POWER - AREA 'E' E4PA-24 E4PB-13 FLUSH STYLE COVER LID WITH FINISH PER ARCHITECT. BOX TO

DATE
C-G 260508 E4PB-19 E1040 E4PB-16
E4PA-36 260508 C-G HAVE SIX (6) DEVICE PLATES WITH SIX (6) 20A DUPLEX
E-201-E SCALE: 1/8" = 1'-0" E4PA-19 +46" *,VV GFCI+48"
*,VV +46" 260508 RECEPTACLES, ONE (1) #EFB-B BLANK DEVICE PLATE AND ONE (1)
GFCI+48" E4PA-23 2-C
NORTH CELL ADA E4PB-19 CELL ADA COMMUNICATIONS OUTLETS, REFERENCE KEYNOTE #270511 ON
C-I E1090 E4PA-36 E4PB-8 E-401 SERIES SHEETS. VERIFY EXACT LOCATION WITH ARCHITECT

VESDA
E1093 *,VV E1041
260508 GFCI *,VV C-I L2P-19 BEFORE ROUGH-IN. ROUTE (2)-3/4"C. FROM BOX OVER AND UP
260508 E4PA-36 E4PB-19
E4PB-19 GFCI CP-10 NEAREST WALL FOR POWER. PROVIDE A MAXIMUM OF (3)
E4PA-36 *,VV *,VV
RECEPTACLES PER CIRCUIT.
VESDA

VESDA

L2P-12 *,VV *,VV

REVISION
CP-5 260546 FURNISH AND INSTALL 240VAC, 3-POLE, 30A HEAVY DUTY
L2P-13 E4PB-19 260511
260508 E4PA-36 NON-FUSED SAFETY DISCONNECT SWITCH IN NEMA 4X STAINLESS
CP-8 *,VV E4PA-36 E4PB-19 *,VV E4PB-7
STELL ENCLOSURE WITH KEY INTERLOCK SYSTEM. CONNECT TO

1 Addendum #01
3 Addendum #03
E4PA-24 *,VV *,VV *,TV
C-G 2-D E4PB-19 CIRCUIT SHOWN USING 3#10+G. IN 3/4"C. PROVIDE CONNECTION
E4PA-36 *,VV C-I CELL
CELL E4PA-30 +46" AS NEEDED BETWEEN DISCONNECT AND WASHER.
E1080 *,VV +96"
*,TV E4PB-13 E1042 260548 COMMUNICATIONS DATA CABINET, REFER TO SPECIFICATIONS.
E1092 260511 C-I 2-E
C-G 260508 CONNECT TO CIRCUIT INDICATED USING 2#12+G. IN 3/4"C.
+96" E1070 2-F +46"
260508 260508 260549 COMMUNICATIONS DATA CABINET, REFER TO SPECIFICATIONS.
E1060 CONNECT TO CIRCUIT INDICATED USING 2#10+#10G. IN 3/4"C.
E4PA-28 E4PB-17

NO.
C-G C-G
+46" +46" 260511
E4PA-30 E4PB-7
260508 E4PB-7 2-G
*,TV *,TV
E4PA-19 CELL E4PA-26 *,TV C-I E1050 CELL
C-I 260511

CHK'D: MLH
GFCI+48" C-G 260511 C-I +96" E1043

SEPTEMBER 5, 2019
E1091 +96"
+46" +96"

1663-1190-90
E4PB-15
E4PA-30 C-G
*,TV +46" E4PB-16

PROJECT NUMBER
SQE#9b 260511 C-I 260508 260508 GFCI+48"

DESIGNED: RDW
E4PA-26 +96"

MLH
U1R-39 E4PB-15

DRAWN: RDW
E4H 260508 C-G C-G
+46" 260508 260508 E4PB-22
+46"
TR-4A

APPRV'D:
E4PA-28 E4PB-17 IDF FCU-9
ABOVE C-G C-G 2-G CABINET #4

DATE:
E4PA +46" +46" 260549
E1050
SPD-E4PA U1R-44
SQE#9a
U1R-37

FIRST FLOOR AND LOWER LEVEL POWER PLANS -


CHASE
E4PA-17 E4PB-14
GFCI+48" GFCI+48" E1014B
CELL CELL CELL CELL ADA CELL ADA CELL CELL CELL ADA CELL ADA CELL CELL CELL

VIGO COUNTY SECURITY CENTER


STORAGE E4PA-17 E1084 E1083 E1082 E1081 E1072 E1071 E1062 E1061 E1054 E1053 E1052 E1051
E1016B *
TCP
L2P-17
INTERLOCK
E1017
E4PA-29 E4PA-29 E4PB-12 E4PB-12
C-I C-I C-I C-I
GFCI GFCI GFCI CHASE
GFCI
EWH-7 E1014B
E4PB-14
E4PA-38 GFCI+48"
260508 260508 260508 260508

TERRE HAUTE, INDIANA


E4PA-17 L2P-15 E4PA-18 L2P-15 E4PB-24
GFCI+48" E4PA-15 CP-9 E4PA-15 E4PA-15 E4PB-14 CP-10 E4PB-14 FCU-8 E4PB-14
GFCI+48" GFCI+48" FCU-7 GFCI+48" GFCI+48" GFCI+48" GFCI+48"
VESDA VESDA

AREA E
A NEW
E4PA-15
W.P.
GFCI
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

KEY PLAN
1 FIRST FLOOR POWER - AREA 'E'
E-201-E SCALE: 1/8" = 1'-0"
NORTH

A B C
9/25/2019 5:23:24 PM

DRAWING NUMBER

E-201-E

ELECTRICAL
D E
GENERAL NOTES KITCHEN KEYNOTES 2606##

A. REFER TO FOOD SERVICE DRAWINGS FOR ADDITIONAL KITCHEN


ELECTRICAL DETAILS AND INTERCONNECTION WIRING 260504 FURNISH AND INSTALL CONDUIT (3/4"C.) FROM EACH DOOR
STARTER/CONTROLLER TO SECURITY CONTROL PANEL FOR
REQUIREMENTS.
ACCESS CONTROL WIRING. WIRING AND TERMINATIONS BY
OTHERS. REFER TO SECURITY SERIES SHEETS FOR DETAILED
B. FIELD COORDINATE EXACT RECEPTACLE NEMA CONFIGURATIONS
WIRING REQUIREMENTS.
REQUIRED FOR KITCHEN EQUIPMENT PLUGS PRIOR TO

DLZ INDIANA, LLC


CONSTRUCTION. PROVIDE CORD AND PLUG SETS WHERE 260505 FURNISH AND INSTALL POWER (1/8HP, 120V) FOR SLIDING DOOR
REQUIRED FOR FINAL CONNECTION OF EQUIPMENT. CONTROLLERS, DOOR SAFETIES/LIMIT SWITCHES AND KEYED
OPEN-CLOSE PUSHBUTTON CONTROL STATIONS FURNISHED BY
C. FIELD COORDINATE EXACT RECEPTACLE AND/OR EQUIPMENT DOOR EQUIPMENT VENDOR. CONTROL WIRING BY OTHERS.
CONNECTION LOCATIONS WITH FOOD SERVICE EQUIPMENT REFER TO SPECIFICATION 087100 "DOOR HARDWARE" FOR
CONTRACTOR PRIOR TO CONSTRUCTION. DETAILED REQUIREMENTS. INSTALL DOOR SAFETIES/LIMIT
SWITCHES AND CONTROL SWITCH(S) PER MANUFACTURERS
D. MINIMIZE CONDUIT PENETRATIONS. REFER TO ARCHITECTURAL RECOMMENDATION. FURNISH AND INSTALL CONDUIT/POWER
SPECIFICATIONS AND PLANS FOR SEALANT REQUIREMENTS. WIRING REQUIRED FOR A COMPLETE SYSTEM.
3 FIELD-COORDINATE THE EQUIPMENT INSTALLATION AND CONDUIT
REQUIREMENTS WITH THE DOOR EQUIPMENT VENDOR PRIOR TO
E. ALL CIRCUITS THIS DRAWING FED FROM PANELBOARD 'K1H', 'K1L'
CONSTRUCTION.
'K2L' OR 'K3L' U.O.N.
260510 EQUIPMENT TO BE MOUNTED ON CONCRETE PAD, REFER TO
F. ALL 20A, 120V DUPLEX RECEPTACLES IN KITCHEN ROOM #C1059 STRUCTURAL DRAWING S-530, DETAILS #8 AND/OR #9 FOR
SHALL BE NON-FEED-THRU GFCI TYPE, U.O.N. WITH VANDALPROOF CONCRETE PAD INSTALLATION DETAIL.
STYLE RECEPTACLE FACEPLATE 260522 AUTOMATIC FLUSH VALVE. REFER TO AUTOMATIC ELECTRIC
FLUSH VALVE DETAIL #2 ON SHEET E-801.
G. PROVIDE FINAL CONNECTIONS TO ALL KITCHEN EQUIPMENT. ALL 260531 CONNECT TO CIRCUIT SHOWN WITH 2#10+G. IN 3/4"C.
FINAL DIRECT CONNECTIONS OF EQUIPMENT SHALL BE RUN IN
FLEXIBLE "LIQUID-TIGHT" CONDUIT WITH NEOPRENE JACKET. 260546 FURNISH AND INSTALL 240VAC, 3-POLE, 30A HEAVY DUTY
NON-FUSED SAFETY DISCONNECT SWITCH IN NEMA 4X STAINLESS
STELL ENCLOSURE WITH KEY INTERLOCK SYSTEM. CONNECT TO
H. PROVIDE SHUNT-TRIP CIRCUIT BREAKERS TO SHUT OFF FUEL
CIRCUIT SHOWN USING 3#10+G. IN 3/4"C. PROVIDE CONNECTION
VALVE(S), ELECTRICAL POWER AND CONTROL SOURCE TO ALL R
EE
AS NEEDED BETWEEN DISCONNECT AND WASHER.
COOKING APPLIANCES LOCATED UNDER THE EXHUAST HOOD(S). CK IN
CO

SS D I A N G
SHUNT-TRIP BREAKERS SHALL BE INTERLOCKED WITH THE MICRO 260547 FURNISH AND INSTALL 125VAC, 20A, 1-POLE MANUAL MOTOR

I ON A L E N
PE60018676
D

A
STATE OF
STARTER WITH TOGGLE DISCONNECT IN NEMA 1 ENCLOSURE.

L . H I TC

E
SWITCH OF THE FIRE PROTECTIONS SYSTEM. THE SHUNT-TRIP

I ST ER
BREAKERS SHALL OPEN ON ACTUATION OF THE FIRE PROTECTION FURNISH WITH RED (RUN) LED PILOT LIGHT, MOTOR RATED.

No.
SYSTEM AND CAUSE ALL POWER TO THE COOKING EQUIPMENT TO CONNECT TO CIRCUIT SHOWN USING 2#12+G. IN 3/4"C. PROVIDE
CONNECTION AS NEEDED BETWEEN SWITCH AND DRYER.

EG
BE SHUT OFF. REFER TO DETAILS #3 AND #4 ON DRAWING E-801.

IN
IN
R
260601 CONNECT TO CIRCUIT SHOWN WITH 2#12+G. IN 3/4"C. RV
I. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO 260602 CONNECT TO CIRCUIT SHOWN WITH 3#12+G. IN 3/4"C. MA FE
SPECIFICATION 079200 FOR TYPE. P RO
260603 CONNECT TO CIRCUIT SHOWN WITH 3#6+#6G. IN 1"C.
ALL DEVICES IN KITCHEN SHALL BE VANDAL RESISTANT STYLE. 260604 CONNECT TO CIRCUIT SHOWN WITH 3#8+#8G. IN 3/4"C.
J.
260605 CONNECT TO CIRCUIT SHOWN WITH 2#10+#10G. IN 3/4"C.
K. REFER TO DRAWING E-203 OR KITCHEN ROOFTOP EQUIPMENT. 260606 FLOOR MOUNTED JUNCTION BOX, REFER TO DETAIL #1 ON FS101.
PROVIDE FLEX CONNECTION PER SPECIFICAITON FROM FLOOR
3 MOUNTED JUNCTION BOX TO ITEM #E22 AND #ECO1 DEVICES.
260607 DEVICE POWERED FROM UTILITY DISTRIBUTION SYSTEM (UDS)
(ITEM #E43), CONNECT TO UDS USING 2#12+G. IN 3/4"C. REFER TO
DRAWING FS110 FOR ADDITIONAL INFORMATION.
260608 ITEM #E43 - UTILITY DISTRIBUTION SYSTEM (UDS) BY FOOD
SERVICE EQUIPMENT SUPPLIER,
18 19 260609 PROVIDE CONDENSATE SEAL-OFF FITTING AT ALL TRANSITIONS
BETWEEN DIFFERENT AMBIENT TEMPERATURES.
260610 FEED POWER TO EQUIPMENT FROM ABOVE.
260611 PROVIDE INTER CONNECTION AS REQUIRED TO DOOR LIGHT,
HEATER AND ADDITIONAL LIGHT FITURES.
260612 COMPRESSOR LOCATED ON ROOF ABOVE FREEZER/COOLER
UNITS. COORDINATE WITH EQUIPMENT SUPPLIER FOR EXACT
LOCATION. REFER TO DRAWING E-203 FOR ADDITIONAL
PASSAGE K2L-27 M 260615 260618 REQUIREMENTS.
RECEIVING 260504 260614
C1052B K2L-15 260610 260613 MANUAL MOTOR STARTER WITH 20A, 240VAC, 1P TOGGLE SWITCH
C1052 260505 260610 K2L-10,12 ITEM #E9.3 DISCONNECT, RED (ON) LED PILOT LIGHT, IN NEMA 4X STAINLESS
E1PB-29 E1PB-29 ITEM #E9.3
E1PB-29
260602 260601 HEAT TAPE STEEL ENCLOSURE. CONNECT TO CIRCUIT AS SHOWN USING
+132" AFF +132" AFF 2#12+G, IN 3/4"C.
M M
260614 MANUAL MOTOR STARTER WITH 20A, 240VAC, 2P TOGGLE SWITCH
J J J J DISCONNECT, RED (ON) LED PILOT LIGHT, IN NEMA 4X STAINLESS
K1L(8,10) K1L-20 K1L-22 K1L(12,14) K1L-24 K1L-24 K1H(13,15,17) K1L(16,18) K2L-8 260617 STEEL ENCLOSURE. CONNECT TO CIRCUIT AS SHOWN USING
ITEM #E37 ITEM #E36 ITEM #E36 ITEM #E35 +48" +48" ITEM #E28 ITEM #E25 ITEM #E9.1 260617 UP 260618 2#12+G. IN 3/4"C.
UP
+48" NEMA 5-20R NEMA 5-20R +48" +12" +70" +132" AFF 260610 260615 LOCATE MANUAL MOTOR STARTER ADJACENT TO FREEZER COIL

M
+48" +48" 260603 260610 K2L-17 (INSIDE WALK-IN COOLER). MOUNT INDEPENDENT OF COIL TO
260613 260609 FREEZER ITEM #E4.3 COOLER ENCLOSURE PER MANUFACTURER DIRECTIONS.
INTERLOCK K2L-9
260616 J ITEM #9 C1064B HEAT TAPE PROVIDE WEATHERPROOF ENCLOSURE.
3 C1063 FREEZER
260612 +132" AFF

M M
+111" 260616 LOCATE MANUAL MOTOR STARTER ADJACENT TO COOLER COIL
E1PB-13 K2L-29 C1064B 260609 (INSIDE WALK-IN COOLER). MOUNT INDEPENDENT OF COIL TO
* J 260609 COOLER ENCLOSURE PER MANUFACTURER DIRECTIONS.
K1L
K2L-7 K2L-14,16 PROVIDE WEATHERPROOF ENCLOSURE.
ITEM #E9 260611 260612 ITEM #E4.3
K1L-24 260617 3/4"C. BETWEEN COMPRESSOR AND COIL FOR CONTROL CABLING.
K2L +111" 260610 +132" AFF CONTROL CABLING AS REQUIRED BY EQUIPMENT
K2L-11 260610
ITEM #E4 J
260610 MANUFACTURER.
K1H UP 260614
+111" 260611 260618 PROVIDE CONNECTION TO DRAIN LINE HEAT TAPE AS NEEDED
260617 260615
BETWEEN SWITCH AND TAPE.
260504 260619 CONNECT TO CIRCUIT SHOWN WITH 3#3+#6G. IN 1-1/4"C.
260505
260620 FURNISH AND INSTALL OCTAGONAL BOX FOR FIRE PULL STATION
K2L-25 M AT +48" AFF WITH 1/2"C. FROM TOP OF BOX TO HOOD FIRE
E1PB-13
260634 260605 SUPPRESSION CABINET. COORDINATE EXACT LOCATIONS
KITCHEN
FACILITY 260632 260633 K2L-24,26 BEFORE ROUGH-IN. PULL STATION SHALL BE LOCATED NO LESS
C1059 THAN 10'-0" AND NO GREATER THAN 20'-0" FROM ANSUL/HOOD
WORKSHOP 260636 260635 260630 260631 ITEM #E22
NEMA L6-30R AND LOCATED ALONG PATH OF EGRESS.
C1056 260626 260625 J K1L-36 K2L-18 K2L-13
260621 HOOD FIRE SUPPRESSION SYSTEM, CIRCUIT AS SHOWN USING
ITEM #E47 ITEM #ECO1 ITEM #E4 J 260610
260628 260627 J 260611 2#12+G. IN 3/4"C. VERIFY EXACT LOCATION BEFORE ROUGH-IN.
NEMA 5-20R +111"
NEMA 5-15R

NEMA 5-15R

NEMA 5-15R

NEMA 5-15R

NEMA 5-15R

260622 PROVIDE 3/4"C. FROM FIRE SYSTEM MICROSWITCH ABOVE HOOD


260607

260607

260607
ITEM #E45

ITEM #E45

ITEM #E45

ITEM #E42

ITEM #E42

260629
260607

260607

260620

09/12/19
09/26/19
260619 K1L-26 K2L-20 TO UTILITY DISTRIBUTION SYSTEM (UDS) FOR SHUNT TRIP

DATE
260610 J * 260606 ITEM #E4.1 BREAKER CONTROL WIRING. WIRING AS REQUIRED BY
260637

M
E1PB-11 260608 +132" AFF EQUIPMENT MANUFACTURER.
TR-K1 3
260612 260610 260623 PROVIDE 3/4"C. FROM FIRE SYSTEM MICROSWITCH ABOVE HOOD
TR-K2 K1L-34 K1L(37,39,41) 260613
J J ITEM #E43 TO FACP, IN ELECTRICAL #C1054, FOR FIRE SUPPRESSION
ABOVE ITEM #E47 260616
K2L-28 K2L-22 260617 MONITORING WIRING. WIRING AS REQUIRED BY EQUIPMENT
ITEM #E50

ITEM #E50
NEMA 5-15R

NEMA 5-15R

260621
ITEM #E48

ITEM #E48

ITEM #E48

ITEM #E49
NEMA 5-20R

NEMA 5-20R

NEMA 5-20R

NEMA 5-15R

ITEM #E18 ITEM #E18 MANUFACTURER.


260622 OFFICE
260607

260607

260607

260607

260607

260607

260510 NEMA 5-15R K2L-23 NEMA 5-15R K2L-21 K2L-19 260609 260624 PROVIDE 3/4"C. FROM FIRE SYSTEM MICROSWITCH ABOVE HOOD
260623 C1062 UP

REVISION
+48" +48" +48" +48" +48" TO HOOD MAKE-UP AIR FAN TO SHUT DOWN RETURN AIR FAN AS
260624 K1L-28 NEEDED. WIRING AS REQUIRED BY EQUIPMENT MANUFACTURER.
K1L-26 K1L-26 * UP

1 Addendum #01
3 Addendum #03
260625 PROVIDE 4 SQ. JUNCTION BOX ABOVE HOOD FOR CONNECTION
* * 260638 J OF HOOD LIGHTS.
JUDGE K1L-26 260617 260626 ITEM #40A - PROVIDE 3/4"C. BETWEEN HOOD CONTROL PANEL AND
C1069 *,USB JUNCTION BOX ABOVE HOOD FOR HOOD LIGHT WIRING,
REFERENCE NOTE #K13. PROVIDE FINAL CONNECTION AS
3 NEEDED TO HOOD LIGHTS.
ITEM #E54 260627 ITEM #40D - PROVIDE 3/4"C. BETWEEN HOOD CONTROL PANEL

NO.
E2PD-18 K1L(13,15) K1L(17,19) K1L-28
K1L(13,15) ITEM #E54 ITEM #E54 * DRY AND HOOD FIRE SUPPRESSION SYSTEM PANEL FOR CONTROL
K1L(17,19) +5-3/4" +5-3/4" STORAGE COOLER WIRING, CONTROL CABLING AS REQUIRED BY EQUIPMENT
C1064 C1064A MANUFACTURER.
J J J
260601 K1L(21,23) 260628 ITEM #40E - PROVIDE 3/4"C. BETWEEN HOOD CONTROL PANEL AND
260522 K1L-28

CHK'D: MLH
J ITEM #E35 DUCT SENSORS AT TOP OF EACH HOOD SECTION FOR CONTROL
SUR

SEPTEMBER 5, 2019
J WIRING, CONTROL CABLING AS REQUIRED BY EQUIOPMENT
+48" GFCI+48"

1663-1190-90
MANUFACTURER. VERIFY EXACT SENSOR LOCATION.
K1L-28
260629 ITEM #40F - PROVIDE 3/4"C. BETWEEN HOOD CONTROL PANEL AND
STAFF KITCHEN TEMPERATURE SENSOR FOR CONTROL WIRING,

PROJECT NUMBER
ATTORNEY TOILET CONTROL CABLING AS REQUIRED BY EQUIPMENT

DESIGNED: RDW
MLH
M M M MANUFACTURER. VERIFY EXACT SENSOR LOCATION.
C1068 C1061

DRAWN: RDW
K1L-28 K3L 260630 HOOD MAKE-UP AIR UNIT AND EXHAUST FAN LOCATED ON ROOF
K1L-29 K3L-7 K3L-14 K3L-16 K3L-18
GFCI+48" K3L-10 K3L-10 K3L-10 ABOVE, REFER TO SHEET E2.3 FOR MORE INFORMATION.

APPRV'D:
ITEM #E36 GFCI+48" 260547 260547 260547
KITCHEN WASHER *,TV * * 260631 PROVIDE WIRING AS NEEDED BETWEEN HOOD CONTROL PANEL
NEMA 5-20R

DATE:
C1059 +84" AND HOOD MAKE-UP AIR UNIT VFD DRIVE. VFD QUICK
+48"
E2PD-14 K3L-9,11 DRYER CONNECTOR TO BE INCLUDED IN CONTROL PANEL, COORDINATE
N DRYER+48" WITH EQUIPMENT MANUFACTURER. WIRE PER MANUFACTURER'S
CHASE
260531 RECOMMENDATION.
C1065B
INMATE 260632 PROVIDE WIRING AS NEEDED BETWEEN HOOD CONTROL PANEL
K1L-25
TOILET AND HOOD EXHAUST FAN VFD DRIVE. VFD QUICK CONNECTOR TO
ITEM #E56 3
C1060 BE INCLUDED IN CONTROL PANEL, COORDINATE WITH EQUIPMENT

VIGO COUNTY SECURITY CENTER


NEMA 5-15R MANUFACTURER. WIRE PER MANUFACTURER'S
+48"

ENLARGED KITCHEN PLAN - ELECTRICAL


RECOMMENDATION.
K1L-28 260633 FURNISH AND INSTALL SEPARATE 120VAC INPUT TO HOOD
K1L-27 SUPPLY FAN. CONNECT TO CIRCUIT K1L-31 USING 2#12+G. IN
ITEM #E57 *
3/4"C.
NEMA 5-15R
TRASH +48" 260634 PROVIDE 3/4"C. BETWEEN EXHAUST FAN AND HOOD FOR
CONTROL WIRING, CONTROL CABLING AS REQUIRED BY
C1066 EQUIPMENT MANUFACTURER.
K3L-10
*,+40" 260635 FURNISH AND INSTALL (1) CAT.6 CABLE TO CASELINK MONITOR
AND CONTROL SYSTEM UNDER HOOD.
260636 FURNISH AND INSTALL POWER (120VAC) TO MOTORZIED
DAMPERS. CONNECT TO CIRCUIT K1L-32 USING 2#12+G. IN 3/4"C.

TERRE HAUTE, INDIANA


VERIFY EXACT LOCATION OF DAMPERS BEFORE ROUGH-IN.
LAUNDRY
K3L-8 260637 GAS SHUTOFF SOLENOID VALVE SHALL BE DE-ENERGIZED (VIA
C1065 SHUNT TRIP BRANCH CIRCUIT BREAKER) UPON HOOD ANSUL
*
K3L-8 ACTIVATION. FIELD COORDINATE/VERIFY SOLENOID VOLTAGE

A NEW
W.P. PRIOR TO CONSTRUCTION. REFER TO DETAIL #3 ON SHEET E-801.
K3L-10 GFCI+48" 260638 INSTALL REMOTE GAS VALVE SHUT-OFF CONTROL STATION
K1H(14,16,18) K1H(20,22,24) *,+40"
ITEM #E61 ITEM #E61 K3L-8 260546 FURNISHED BY KITCHEN EQUIPMENT VENDOR. WALL MOUNT 48"
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

260546 260546 AFF AND PROVIDE EMERGENCY INSTRUCTION SIGNAGE


TANK HEAT+72" BOOSTER+72" *,+40" K3L-8 K3L-8 K3L-8 K3L(25,27,29)
K3L(13,15,17) K3L(19,21,23) ADJACENT TO CONTROL STATION. INTERLOCK SO THAT GAS
J J * * *
VALVE OPENS UPON CONTROL STATION ACTIVATION AND/OR
HOOD ANSUL ACTIVATION. REFER TO DETAIL #3 ON SHEET E-801.
260603 260604 E4PB-18 EWH-3
SECURE E4PB-18 *
260504 260504 E4PB-33
CORRIDOR *
260505 260505
E1012 E4PB-26 M
K1L-30 M INTERLOCK
E1013

1 ENLARGED KITCHEN PLAN - ELECTRICAL


E-201-K SCALE: 1/4" = 1'-0"
NORTH
9/25/2019 5:23:31 PM

DRAWING NUMBER

E-201-K

ELECTRICAL
GENERAL NOTES
A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702, E-703,
E-704, E-705, E-706 AND E-707.

B. SEE MECHANICAL EQUIPMENT - ELECTRICAL CONNECTION


SCHEDULE ON DRAWINGS E-604 & E-605 FOR EQUIPMENT

DLZ INDIANA, LLC


CIRCUITING AND ADDITIONAL ELECTRICAL REQUIREMENTS FOR
MECHANICAL EQUIPMENT (I.E. DISCONNECT, STARTER, ETC) AND
LOAD INFORMATION.

C. FOR LIGHTING FIXTURE SCHEDULE, SEE SHEET E-606. REFER TO


REMARKS COLUMN ON LIGHTING FIXTURE SCHEDULE FOR FIXTURE
MOUNTING HEIGHTS AND REQUIREMENTS U.O.N. ON THIS
DRAWING.

D. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND


CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
AND OFFSET BACK TO BACK BOXES.

E. REFER TO SECURITY DRAWINGS, #SE SERIES, FOR ADDITIONAL


REQUIREMENTS. PROVIDE BOXES AND RACEWAYS AS NEEDED FOR
SECURITY EQUIPMENT.

F. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO


SPECIFICATION 079200 FOR TYPE.

G. REFER TO DRAWING E-803, DETAIL #10 FOR FIRE ALARM DEVICES


MOUNTING REQUIREMENTS PER NFPA.
R
EE
H. ALL FIRE ALARM CONDUITS SHALL BE FACTORY PAINTED "RED". ALL CK IN
CO

SS D I A N G
I ON A L E N
PULL/JUNCTION BOX COVERS SHALL BE FACTORY PAINTED RED.

PE60018676
D

A
STATE OF
L . H I TC

E
I ST ER
No.
I. ALL FIXTURES TO BE HUNG AT 11' -0" AFF IN MECHANICAL B2000.

EG

IN
IN
R
RV
MA FE
P RO

2605##
2705##

PENTHOUSE KEYNOTES 2805##

260507 SECURITY EQUIPMENT RACKS (3 TOTAL), REFER TO SECURITY


DRAWINGS. PROVIDE FOUR (5) 20A, 120V CIRCUITS FROM PANEL
'U1R' TO RACKS, CIRCUITS #28, 30, 32, 34, 36 AND THREE (3) 20A,
120V CIRCUITS FROM PANEL 'E5PA' TO RACKS, CIRCUITS #49, 51,
53. COORDINATE WITH SECURITY CONTRACTOR ON EXACT
LOCATION OF CIRCUITS. PROVIDE 2#12+G IN 3/4"C. FOR EACH
CIRCUIT.
260510 EQUIPMENT TO BE MOUNTED ON CONCRETE PAD, REFER TO
STRUCTURAL DRAWING S-530, DETAILS #8 AND/OR #9 FOR
CONCRETE PAD INSTALLATION DETAIL.
260530 PREACTION DRY-POWER SYSTEM, 120V. CONNECT TO CIRCUIT
SHOWN USING 2#12+G. IN 3/4"C. COORDINATE EXACT LOCATION.
265716 FURNISH AND INSTALL CENTRAL UNINTERRUPTIBLE EMERGENCY
LIGHTING INVERTER, SINGLE PHASE, 277V INPUT/OUTPUT WITH 4
OUTPUT BREAKERS, 90-MINUTE RATED BATTERY BACKUP
AA1 AA1 3 CAPACITY AT RATED LOAD, UL 924 LISTED, 3KW MINIUM FOR L1E,
ss ss 10KW MINIMUM FOR L2E, CONTROLLED POWER MODEL ELU OR
9 +14' +14' 3 APPROVED EQUAL BY MYERS, DUAL-LITE, EATON.
3 E5PA-23
3 ABOVE 14 14.2 ABOVE E5PA-23 15 15.3
W.P. W.P. 265719 LIGHTING CONTACTOR, LC5A, REFER TO EXTERIOR LIGHTING
ROOF ROOF
GFCI WP GFCI WIRING DIAGRAM, SHEET E-807, DETAIL #7.
260507 270575 270509 E5H-16 F E5H-16
265720 NEW TIME CLOCK #TC5 FOR CONTROL OF EXTERIOR LIGHTING,
260510
E5PA-21 F6 F6 F6 E5PA-23
F REFER TO EXTERIOR LIGHTING WIRING DIAGRAM, SHEET E-807,
F4 E5PA-23 265721 E5PA-23

E5PA-21 E5PA-21
3 265721 DETAIL #7. CONNECT TO CIRCUIT E5PA-40 USING 2#12+G. IN 3/4"C.
+10'-0" a a a GFCI+48" GFCI+48" GFCI+48"
F6 265721 LIGHTING FIXTURE SHALL BE MANUALLY SWITCHED FROM LOCAL
AFF SECURITY
265722 SQE#3 a ODPB-9 E5PA-8 TOGGLE SWITCH 'ss'. FIXTURES SHALL ALSO BE CONTROLLED
B2001 F6 F6 VIA LIGHTING CONTACTOR FOR DUSK-TO-DAWN CONTROL.
E5PA-10 F6 SUPPLY FAN AHU RECEPTS
PC AHU-1 a a PROVIDE LABEL ON TOGGLE SWITCH FACEPLATE INDENTIFYING
ODPB-5 AHU RECEPTS E5H(31,33,35) F6 a
260530 SUPPLY FAN ENERGY WHEEL a EXTERIOR LIGHTING ALSO INTERLOCKED/CONTROLLED VIA
TO TC5 F4 280507 ODPB-10 3 LIGHTING CONTACTOR.
AHU-2

GFCI+48"
E5PA-19 +10'-0" AHU RETURN FAN 265722 WALL MOUNT PHOTOCELL 14'-0" ABOVE ROOF (FIELD

E5PA-21
265721 ODPB-6 S
AFF ZAM S LIGHTS D COORDINATE EXACT MOUNTING HEIGHT TO MATCH HEIGHT OF
AA1 3 RETURN FAN D 265721
E5PA-9 ADJACENT LIGHTING FIXTURES AS INDICATED ON
AA1

E5PA-21
ss ODPB-13 IAM ARCHITECTURAL ELEVATIONS/ELECTRICAL LIGHTING PLANS).
+14' L2P-7 IAM ss
CRAC-3 F6 E5PA-18 +14' FOR PHOTOCELL WIRING DETAILS, REFER TO EXTERIIOR
ABOVE 260530 280506
E5PA-19

F6 280506 F6 F6 N.L. F6 LIGHTING WIRING DIAGRAMS ON SHEET E-807.


ROOF F4 GFCI+48" ABOVE
PA-4 F6 a a a L2H-11 a 270509 #1/0 AWG GREEN INSULATED GROUND CABLE. BOND TO MAIN
F
E5H-16 +10'-0" ROOF
a 280519 E5H-16 GROUND BUS #1 (IN MECHANICAL #C1053). REFER TO DETAIL #4,
AFF F6 F6
WP E5PA-19
F DRAWING E-803.
OS a a
F

F
270575 GROUND BUS BAR NO.4. MOUNT AT +8'-0" AFF. REFER TO
F4 TR-L2P E5H-13 WP
L2H ODPB TELE-DATA EQUIPMENT GROUND BUS DETAIL #3, SHEET E-803.
+10'-0"AFF 260510 (ALL FIXTURES HUNG AT BOND TO MAIN GROUND BUS BAR NO.1 (IN location) USE #1/0AWG
F 135° L2P 3 FACE MECHANICAL
E5H-13 11'-0" AFF IN THIS AREA) COPPER GREEN INSULATED CABLE.
E5PA-17 F6 B2000
E5PA-19 N
E5H-13

a 280506 ADDRESSABLE DUCT DETECTOR FURNISHED AND INSTALLED BY

F
GFCI+48"
GFCI+48" HVAC EQUIPMENT SUPPLIER. FURNISH AND INSTALL ONE (1) IAM
SPD-L2P
F6 F6 F6 MODULE AS NEEDED FOR INTERLOCKING/SHUTDOWN CONTROL

09/19/19
09/26/19
ELECTRICAL N.L. N.L. N.L. OF AIR HANDLING UNIT UPON DUCT SMOKE DETECTION. LOCATE

DATE
F6 F6 F6 F6 F6 F6
B2002 L2H-11 a L2H-11 a a a a L2H-11 a REMOTE TEST STATION FOR EACH AIR HANDLING UNIT IN
FCU-11 MASTER CONTROL ROOM #B1026, REFER TO DRAWING E-401-B.
E5PA-17
ss E5PA-15 280506 280506 FIELD COORDINATE PRIOR TO CONSTRUCTION EXACT QUANTITY
W.P. a E5H-16 OF DUCT DETECTORS; ONE (1) DUCT DETECTOR SHALL BE
GFCI 3
E5H-13 IAM IAM REQUIRED AT EACH RETURN DUCT TO THE AIR HANDLING UNIT.
AHU E5PA-18 REFER TO HVAC PLANS FOR DUCTWORK LAYOUT/RETURN
S ODPB-11 S E5H(32,34,36) FCU-12 GFCI+48" LOCATIONS. ALSO REFER TO DETAIL 7 ON DRAWING E-801
3 ODPB-7 D LIGHTS D
SUPPLY FAN ENERGY WHEEL WIRING/INTERLOCKING/CONTROL REQUIREMENTS FOR
E5PA-11 E5PA-16

REVISION
SUPPLY FAN AHU-3 AHU-4 AHU ASSOCIATED SMOKE DAMPER(S) UPON DUCT DETECTOR SMOKE
E5PA-18
ODPB-8 E5H(37,39,41) LIGHTS DETECTION AT AHU.
ODPB-12 W.P.

2 Addendum #02
3 Addendum #03
RETURN FAN ENERGY WHEEL F6 E5PA-13 GFCI
E5PA-12 RETURN FAN E5PA-14 F6 280507 ROOM CONTAINS SELF-CONTAINED DRY-POWDER FIRE
F6 N.L. F6
AHU RECEPTS AHU RECEPTS a SUPPRESSION SYSTEM. PROVIDE ZAM FOR ALARM MONITORING
a L2H-11 a OF FIRE SUPPRESSION SYSTEM CONTROL PANEL BY FIRE ALARM
F6 F6 F6 F6 F6 F6 CONTROL PANEL (FACP-1) LOCATED IN ELECTRICAL ROOM
a a a a a a #C1054 AS RECOMMENDED BY SYSTEM MANUFACTURER.

SPD-E5PA
265716 a
E5PA-18 FURNISH CABLING AS REQUIRED IN 3/4"C. COORDINATE WITH
L2E TR-5A 3 E5PA-18 E5PA-18
TCP

E5PA
E5PA-17 E5PA-17 MECHANICAL CONTRACTOR AND INSTALL/WIRE ALL ASSOCIATED

NO.
GFCI+48"

E5H
E5H-13 TP-3 GFCI+48"
GFCI+48" GFCI+48" L2P-20 ELECTRICAL APPURTENANCES AND DEVICES (I.E. SMOKE
F F
X2 DETECTOR, PULL STATION, TELEPHONE OUTLET) TO FIRE
SQE#12 SUPPRESSION PANEL AS NECESSARY AND AS REQUIRED BY FIRE
R1 R1
E5PA-38 265720 260510 U1R-35 E5PA-38 SUPPRESSION SYSTEM MANUFACTURER.
W.P. +8'-0" +8'-0" W.P.
265719

CHK'D: MLH
GFCI AFF AFF GFCI 280519 ROOF ACCESS HATCH. AVOID ROUTING PIPING, CONDUITS, ETC.

SEPTEMBER 5, 2019
3 E5H-13 E5H-13 IN CLEAR OPENING SPACE.

1663-1190-90
3

PROJECT NUMBER
DESIGNED: RDW
MLH
1 OVERALL PENTHOUSE PLAN - ELECTRICAL

DRAWN: RDW
E-202-BC SCALE: 1/8" = 1'-0"

APPRV'D:
NORTH

DATE:
VIGO COUNTY SECURITY CENTER

PENTHOUSE PLAN - ELECTRICAL


TERRE HAUTE, INDIANA
A NEW
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

KEY PLAN

A B C
9/25/2019 5:23:54 PM

BC

E-202-BC
DRAWING NUMBER

ELECTRICAL
D E
GENERAL NOTES
A. FOR PANELBOARD SCHEDULES, SEE SHEETS E-701, E-702,
E-703, E-704, E-705, E-706 AND E-707.

B. SEE MECHANICAL EQUIPMENT - ELECTRICAL


CONNECTIONS SCHEDULE ON DRAWINGS E-604 & E-605

DLZ INDIANA, LLC


FOR EQUIPMENT CIRCUITING AND ADDITIONAL ELECTRICAL
EQUIPMENT REQUIREMENTS FOR MECHANICAL
EQUIPMENT (I.E. DISCONNECT, STARTER, ETC) AND
EQUIPMENT NAMEPLATE ELECTRICAL LOAD INFORMATION
(I.E. VOLTS, PHASE, FLA, MOCP, ETC.).

C. REFER TO SECURITY DRAWINGS, #SE SERIES, FOR


ADDITIONAL REQUIREMENTS. PROVIDE BOXES AND
RACEWAYS AS NEEDED FOR SECURITY EQUIPMENT.

D. SUPPORT ALL EXPOSED CONDUITS ON ROOF. REFER TO


ROOF CONDUIT SUPPORT DETAIL #6 ON DRAWING E-806.

ROOF KEYNOTES 2605##

E1PA-46 260526 RECEPTACLE TO BE STANCHION MOUNTED WITH BOTTOM AT


EF-1 +12" ABOVE ROOF. PROVIDE GALVANIZED UNISTRUT SUPPORTS
E1PA-46 AS NEEDED.
W.P. 260535 (ALTERNATE BID) RECEPTACLE TO BE STANCHION MOUNTED R
EE
GFCI WITH BOTTOM AT +12" ABOVE ROOF. PROVIDE GALVZANIZED CK IN
260526 CO

SS D I A N G
UNISTRUT SUPPORTS AS NEEDED.

I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC

E
260536 WALK-IN COOLER COMPRESSOR DISCONNECT, HEAVY DUTY

I ST ER
No.
600VAC, 30A, 3-POLE NON-FUSED DISCONENCT SWITCH IN NEMA
4X STAINLESS STEEL ENCLOSURE. DISCONNECT TO BE LOCATED

EG
ADJACENT TO COMPRESSOR, PROVIDE UNI-STRUT SUPPORTS AS

IN
IN
R
EF-5 NEEDED. MOUNT INDEPENENT OF COMPRESSOR. VERIFY EXACT RV
E1PC-36 LOCATION OF COMPRESSOR BEFORE ROUGH-IN. CONNECT TO MA FE
CIRCUIT AS SHOWN USING 3#12+G. IN 3/4"C. P RO
260537 WALK-IN FREEZER COMPRESSOR DISCONNECT, HEAVY DUTY
E1PC(32,34) 600VAC, 30A, 3-POLE NON-FUSED DISCONENCT SWITCH IN NEMA
ACC-C 4X STAINLESS STEEL ENCLOSURE. DISCONNECT TO BE LOCATED
E2PA-7 E1PB-53 ADJACENT TO COMPRESSOR, PROVIDE UNI-STRUT SUPPORTS AS
W.P. 260526 W.P. NEEDED. MOUNT INDEPENENT OF COMPRESSOR. VERIFY EXACT
GFCI ACC-A E2HA-12 GFCI LOCATION OF COMPRESSOR BEFORE ROUGH-IN. CONNECT TO
SEF-6B E2PA(32,34) ACC-2 260526 CIRCUIT AS SHOWN USING 3#12+G. IN 3/4"C.
L2H(44,46,48)
260538 WALK-IN COOLER COMPRESSOR DISCONNECT, HEAVY DUTY
600VAC, 30A, 2-POLE NON-FUSED DISCONENCT SWITCH IN NEMA
4X STAINLESS STEEL ENCLOSURE. DISCONNECT TO BE LOCATED
E3H(19,21,23) EF-2 E1PB-50 ADJACENT TO COMPRESSOR, PROVIDE UNI-STRUT SUPPORTS AS
E1PB-53 EF-9
EF-6A NEEDED. MOUNT INDEPENENT OF COMPRESSOR. VERIFY EXACT
DP-L(8,10,12) LOCATION OF COMPRESSOR BEFORE ROUGH-IN. CONNECT TO
CIRCUIT AS SHOWN USING 2#12+G. IN 3/4"C.
EF-10 DOAS-1
260539 KITCHEN HOOD MAKE-UP AIR UNIT DISCONNECT, HEAVY DUTY
260526 260526 SEF-5 E1PB-52 260526 600VAC, 30A, 3-POLE NON-FUSED DISCONENCT SWITCH IN NEMA
E3PA-20 L2P-10 E1PB-51 4X STAINLESS STEEL ENCLOSURE. DISCONNECT TO BE LOCATED
E2PB-17
W.P. W.P. W.P. ADJACENT TO UNIT, PROVIDE UNI-STRUT SUPPORTS AS NEEDED.
GFCI GFCI GFCI MOUNT INDEPENENT OF UNIT. VERIFY EXACT LOCATION OF UNIT
BEFORE ROUGH-IN. CONNECT TO CIRCUIT AS SHOWN USING
3#10+#10G. IN 3/4"C.
EF-6B L2H(50,52,54) 260540 KITCHEN HOOD EXHUAST FAN DISCONNECT, HEAVY DUTY
EF-7
E3H(20,22,24) EF-4 600VAC, 30A, 3-POLE NON-FUSED DISCONENCT SWITCH IN NEMA
SEF-6A SEF-6C E1PB-51 4X STAINLESS STEEL ENCLOSURE. DISCONNECT TO BE LOCATED
E1PB-49
E2HA(19,21,23) L2H(38,40,42) ADJACENT TO FAN, PROVIDE UNI-STRUT SUPPORTS AS NEEDED.
E2HB(8,10,12) E1PB-49
E2PB-19 MOUNT INDEPENENT OF FAN. VERIFY EXACT LOCATION OF FAN
ACC-1 W.P.
W.P. BEFORE ROUGH-IN. CONNECT TO CIRCUIT AS SHOWN USING
ACC-4 260526 GFCI
GFCI 260526 3#12+G. IN 3/4"C.

RTU-1
E3H(13,15,17)

E2PD(27,29)
ACC-B 260537
K2L(31,33,35)
E5PA-23 E5PA-23 ITEM #E9.4 K2L(38,40,42)
W.P. W.P. ITEM #E4.2
GFCI GFCI 260539 260540 260536
K2L(30,32)
K1H-19,21,23 K1H-25,27,29 ITEM #E9.2
HOOD MAU HOOD EF 260538
E2PE-19 E5H(38,40,42) 260537
W.P. K2L-29
ACC-3 W.P. 260526 K2L-37,39,41
GFCI
GFCI ITEM #E4.4
SEF-3 SEF-4
E5PA-23 K2L-29
L2H(43,45,47) 260526 L2P-8 260526 W.P. W.P.
GFCI GFCI
260526 MAU-1
DOAS-2 K1H(31,33,35)

09/26/19
DATE
EF-ALT-A L2H-49,51,53
E3H-19,21,23
E5PA-17
260535 W.P.
E3PA-20 3 GFCI
W.P. E5PA-18
GFCI W.P.
E3H-20,22,24 GFCI

REVISION
EF-ALT-B

3 Addendum #03
3
E5PA-38 E5PA-38
W.P. W.P.
GFCI GFCI
ACC-E E5PA-22
E3H(13,15,17) ACC-D
EF-3
E5PA(37,39) E5PA(41,43)

NO.
RTU-1

L2H(13,15,17) L2H(26,28,30)

CHK'D: MLH

SEPTEMBER 5, 2019
SEF-1-6 SEF-2-6

1663-1190-90
E5PA-24
OVERALL ROOF PLAN - ELECTRICAL AREA 'A' E5PA-20 260526
W.P.

PROJECT NUMBER
2 ALTERNATE W.P.
GFCI

DESIGNED: RDW
GFCI

MLH
E-203 SCALE: 1/16" = 1'-0" 260526

DRAWN: RDW
L2H(8,10,12) L2H(25,27,29)
E5PA-24
NORTH 260526 SEF-2-1 L2H(32,34,36)
SEF-1-1 W.P.

APPRV'D:
SEF-1-5 GFCI SEF-2-5

DATE:
ACC-F ACC-G
L2H(19,21,23) E5PA-20
E4PB(38,40)
W.P. 260526
E5PB(38,40) GFCI

E5PA-24
260526 W.P.
260526
GFCI

VIGO COUNTY SECURITY CENTER


E5PA-20
W.P.
GFCI
L2H(20,22,24) L2H(37,39,41)
L2H(14,16,18) L2H(31,33,35)
SEF-1-4 SEF-2-4
L2P-9 SEF-1-2 SEF-2-2 L2P-11
SEF-1-3 SEF-2-3

ROOF PLAN - ELECTRICAL


TERRE HAUTE, INDIANA
A NEW
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

KEY PLAN

1 OVERALL ROOF PLAN - ELECTRICAL A B C


E-203 SCALE: 1/16" = 1'-0"
9/25/2019 5:24:34 PM

NORTH

DRAWING NUMBER

E-203

ELECTRICAL
D E
GENERAL NOTES
A. FOR LIGHTING FIXTURE SCHEDULE, SEE SHEET E-606. REFER TO
REMARKS COLUMN ON LIGHTING FIXTURE SCHEDULE FOR
FIXTURE MOUNTING HEIGHTS AND REQUIREMENTS U.O.N ON THIS
DRAWING.

B. FOR OCCUPANCY SENSOR WIRING DETAIL, SEE DETAIL #6/E-802.

DLZ INDIANA, LLC


C. CONDUITS SHALL NOT BE ROUTED ALONG BUILDING EXTERIOR.
CONCEAL BY ROUTING ON INTERIOR AND PENETRATE THROUGH
WALL AT EACH EXTERIOR FIXTURE LOCATION.

2 3 4 1 2 3 4 D. FIELD COORDINATE, PRIOR TO CONSTRUCTION, EXACT MOUNTING


HEIGHT OF ALL FIXTURES TO AVOID DUCTWORK AND EQUIPMENT.
3 3
E. FOR EXTERIOR LIGHTING WIRING DIAGRAM, SEE DRAWING E-807.

F. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND


CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
F3 F3 F3 F3 RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
AND OFFSET BACK TO BACK BOXES.

G. CEILING MOUNTED OCCUPANCY SENSORS SHALL BE MOUNTED IN


EVIDENCE CENTER OF CEILING TILE U.O.N. COORDINATE EXACT LOCATIONS
A2001 BEFORE ROUGH-IN.

H. OCCUPANCY SENSORS ARE SHOWN FOR PURPOSES OF


F3 F3 F3 F3 IDENTIFYING ROOMS/AREAS WHERE REQUIRED. COORDINATE
EVIDENCE WITH MANUFACTURER ON QUANTITY AND LOCATIONS REQUIRED
A2001 FOR COMPLETE COVERAGE. R
EE
265618 CK IN
CO

SS D I A N G
I. PROVIDE POWER PACKS AS REQUIRED FOR OCCUPANCY

I ON A L E N
PE60018676
D

A
E3H-10 OC

STATE OF
L . H I TC

E
SENSORS. POWER PACKS ARE NOT SHOWN. FIELD COORDINATE

I ST ER
E3H-10 OC LOCATIONS AND RECORD ON ELECTRICAL RECORD DRAWINGS.

No.
EG
F3 F3 J. CROSS HATCHED/SHADED FIXTURES = FIXTURES POWERED VIA

IN
F3 F3

IN
R
EMERGENCY BACKUP GENERATOR FOR EMERGENCY EGRESS. RV
MA FE
K. EM = EMERGENCY EGRESS FIXTURE. N.L. = NIGHT LIGHT P RO

L. WHERE SWITCH CIRCUIT IS NOT INDICATED, ALL FIXTURES IN


OPEN ROOM OR AREA SHALL BE ON SAME SWITCH CIRCUIT
STORAGE CONTROLLED BY LIGHTING CONTROL DEVICE INDICATED IN SPACE.
A2000
VEHICLE M. SEAL ALL PENETRATIONS THROUGH PRECAST, REFER TO
SALLYPORT 265618 SPECIFICATION 079200 FOR TYPE.
F3 F3 A1000 F3 E3H-10 OC F3
E3H-10 OC N. REFER TO DRAWING E-302-E FOR LIGHTING CONTROL NOTES.
OPEN
STORAGE
K K
A2000 3
REFER TO FIRST FLOOR LIGHTING PLAN FOR
REFER TO FIRST FLOOR LIGHTING PLAN FOR ADDITIONAL LIGHTING IN THIS AREA
ADDITIONAL LIGHTING IN THIS AREA

LIGHTING KEYNOTES 2656##

265602 PIR HIGH BAY OCCUPANCY SENSOR. PROVIDE POWER PACK(S) AS


RECOMMENDED. DEVICE TO BE FIXTURE MOUNTED OR PENDANT
M M MOUNTED AT SAME HEIGHT AS FIXTURES IN ROOM.
265618 ALIGN FIXTURES IN ROOM WITH BOTTOM OF CIELING JOIST.
265681 CONNECT TO CIRCUIT SHOWN USING 2#10+#10G. IN 3/4"C.
265682 LIGHTING CONTACTORS, LC3A AND LC3B, REFER TO EXTERIOR
LIGHTING WIRING DIAGRAM, SHEET E-807, DETAIL #3.
265683 NEW TIME CLOCK #TC3 FOR CONTROL OF EXTERIOR LIGHTING,
REFER TO EXTERIOR LIGHTING WIRING DIAGRAM, SHEET E-807,
DETAIL #3. CONNECT TO CIRCUIT E3PA-31 USING 2#12+G. IN 3/4"C.
265684 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
MODULE #GTD3, LIKE LVS INC #EPC-1 OR APPROVED EQUAL IN
WALL FOR CONTROL OF EXTERIOR EMERGENCY LIGHT.
NON-EMERGENCY CIRCUIT SHALL BE CIRCUIT E4H-33. REFERENCE
DETAIL #7 ON SHEET E-802. MODULE TO BE FLUSH MOUNTED AS
INDICATED. RECORD EXACT LOCATION ON RECORD DRAWINGS.
265687 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
PHOTOCELL. REFER TO DETAIL #3 ON SHEET E-807. CONTROL VIA
3 CONTACTOR #LC3A.
265688 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER CONTROL
MODULE LOCATED IN VEHICLE SALLYPORT #A1000.
4 MEZZANINE LIGHTING - AREA 'A' ALTERNATE 2 MEZZANINE LIGHTING PLAN - AREA 'A' BASE BID
E-301-A SCALE: 1/8" = 1'-0" E-301-A SCALE: 1/8" = 1'-0"

09/12/19
09/26/19
DATE
NORTH NORTH

265687 265687 265687


265688 AA1 265681 265681 265681 265688 AA1
2 3 4 1 AA1 2 3 AA1 4 265687 EM
265687 AA1 265687 EM AA1
265681 E3H-9 265681 L1H-12 E3H-9 E3H-9 E3H-9 265681 L1H-12

REVISION
X1 X1
L1E-2 L1E-2
P1 P1 P1 F5 F5 P1 P1 P1 P1 P1

1 Addendum #01
3 Addendum #03
F5 F5 N.L. a N.L. N.L. a N.L. a N.L.
L1E-2 E3H-8 L1E-2 L1E-2 L1E-2 L1E-2

X1
3 L1E-2 3

NO.
L1
N.L.
P1 P1 P1 F5 F5 P1 P1 P1 P1 P1
E3H-10 OC L1E-2 E3H-10 OC
F5 F5 a a a 3 b a a a a
E3H-8 E3H-8 E3H-8
STORAGE

CHK'D: MLH

SEPTEMBER 5, 2019
265602 AA1 A1001
AA1 b a a a a

1663-1190-90
OC a 265602 OC a 265602 OC a E3H-9 OC 265602 OC 265602 OC OC 265602 OC
E3H-9 STORAGE E3H-8 E3H-8 E3H-8 E3H-8 E3H-8
E3H-8 E3H-8 E3H-8 265681 265602 265602
A1001

DESIGNED: MHK,RDW
265681
265687

DRAWN: MHK,RDW

PROJECT NUMBER
265687 P1 P1 P1 F5 F5 P1 P1 P1 P1 P1
F5 F5 a N.L. a b N.L. a N.L. a

MLH
E3H-8 L1E-2 E3H-8 L1E-2 L1E-2

APPRV'D:
DATE:
EVIDENCE F3 F3
STORAGE
F3 F3 P1 P1 P1 P1 P1 P1 P1 P1
3 A1002 a a a 3 b a a a a
3 VEHICLE
E3H-8 E3H-8 E3H-8

FIRST FLOOR AND MEZZANINE LIGHTING PLANS -


SALLYPORT 3
E3H-10 OC W E3H-10 W
OC VEHICLE
J 265684 A1000 J 265684

VIGO COUNTY SECURITY CENTER


SALLYPORT
F3 EVIDENCE F3 265682 A1000
265682
F3 F3 265683 K STORAGE E3H 265683 K
E3H
P1 P1 P1 A1002 P1 P1 P1 P1 P1
E3PA
N.L. a a N.L. a N.L. a a
E3PA E3H-8 E3H-8 E3H-8 E3H-8

F4 F4
F4 F4
VEHICLE
EVIDENCE
STORAGE P1 P1 P1 P1 P1 P1 P1 P1

TERRE HAUTE, INDIANA


A1003 a N.L. a X1 b N.L. a N.L. a
3 E3H-8 L1E-2 E3H-8 L1E-2 3 L1E-2 L1E-2
F4 F4

AREA A
F4 E3H-10 OC F4 265602 AA1 E3H-10 OC
AA1 b a a a a

A NEW
OC a 265602 OC a 265602 OC a E3H-9 OC 265602 OC 265602 OC OC 265602 OC
E3H-9 265602 265602 E3H-8 E3H-8 E3H-8 E3H-8 E3H-8
3 E3H-8 E3H-8 E3H-8 265681 265602 265602
265681
265687
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

265687 E3H-10 P1 P1 P1 P1 P1 P1 P1 P1
F4 F4
a a a b a a a a
E3H-8 E2HA-17 E3H-10
F4 F4 E3H-8 E3H-8
M M KEY PLAN
VEHICLE 3
EVIDENCE
STORAGE
A1003
3 P1 P1 P1 F4 F4 P1 P1 P1 P1 P1
F4 F4 a a
N.L. a N.L. N.L. N.L. N.L.
X1 L1E-2 E3H-8 L1E-2 X1 X1 L1E-2 L1E-2 L1E-2 X1
L1E-2 L1E-2 L1E-2 L1E-2

265681 AA1 265681 AA1 3 265681 AA1 AA1 265681 AA1 AA1 AA1 265681 AA1
265687 E3H-9 265687 EM 265687 EM E3H-9 265687 EM E3H-9 E3H-9 265687 EM A B C
265688 L1H-12 265688 L1H-12 265681 265688 L1H-12 265681 265681 265688 L1H-12
265687 265687 265687
9/25/2019 5:25:36 PM

3 FIRST FLOOR LIGHTING - AREA 'A' ALTERNATE 1 FIRST FLOOR LIGHTING - AREA 'A' BASE BID
E-301-A SCALE: 1/8" = 1'-0" E-301-A SCALE: 1/8" = 1'-0"

DRAWING NUMBER

E-301-A
NORTH NORTH

ELECTRICAL
D E
12 12.7
14
GENERAL NOTES
A. FOR LIGHTING FIXTURE SCHEDULE, SEE SHEET E-606. REFER TO
265690 265690 A REMARKS COLUMN ON LIGHTING FIXTURE SCHEDULE FOR
265629 GG1 GG1 265629 13
E2HA-20 E2HA-20 FIXTURE MOUNTING HEIGHTS AND REQUIREMENTS U.O.N ON THIS
DRAWING.
D2 D2
265714
EM EM B. FOR OCCUPANCY SENSOR WIRING DETAIL, SEE DETAIL #6/E-802.
265689

DLZ INDIANA, LLC


E2HA-18 E2HA-18
C. CONDUITS SHALL NOT BE ROUTED ALONG BUILDING EXTERIOR.
CONCEAL BY ROUTING ON INTERIOR AND PENETRATE THROUGH
265627 VESTIBULE B WALL AT EACH EXTERIOR FIXTURE LOCATION.
B1000
D. FIELD COORDINATE, PRIOR TO CONSTRUCTION, EXACT MOUNTING
Y1 Y1 Y1
HEIGHT OF ALL FIXTURES TO AVOID DUCTWORK AND EQUIPMENT.
pp pp pp pp

Y1 OC E2HA-16 E. FOR EXTERIOR LIGHTING WIRING DIAGRAM, SEE DRAWING E-807.


Y1 265602 Y1
N.L.
pp pp F. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND
8 9 10 11 265689 L1H-9
CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
FF1 FF1 FF1 FF1 FF1 RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
265689 265689 E2HA-18 265689 265689 265614
E2HA-18 E2HA-18 E2HA-18 E2HA-18 AND OFFSET BACK TO BACK BOXES.

X3A p C G. CEILING MOUNTED OCCUPANCY SENSORS SHALL BE MOUNTED IN


L1H-9 E2HA-16
OC Z1 CENTER OF CEILING TILE U.O.N. COORDINATE EXACT LOCATIONS
G2 G2 Y1 265602
G2 G2 G2 G2 G2 v BEFORE ROUGH-IN.
VIDEO N.L. N.L. p Y1
m m m m Y1 265714 N.L. Z1
m VISITATION L1H-9 L1H-9 EM p
OC p L1H-9 v H. OCCUPANCY SENSORS ARE SHOWN FOR PURPOSES OF
E2HA-16 L1H-9 Z1A
265689 B1003 IDENTIFYING ROOMS/AREAS WHERE REQUIRED. COORDINATE
3 C J Y1 Y1 Y1 v 4'-0" D WITH MANUFACTURER ON QUANTITY AND LOCATIONS REQUIRED
AA1 G2 GROUP GROUP
AA1 G2 G2 265608 p LOBBY p p E1PC-40 OC FOR COMPLETE COVERAGE.
+12'-0" X3A N.L. VIDEO VIDEO
5 6 +12'-0" 7 m m WAITING R
EE
AFG L1E-1 L1H-9 B1001
AFG B1005 B1006 B1002 Z1 I. PROVIDE POWER PACKS AS REQUIRED FOR OCCUPANCY CK IN
E2HA-18 Y1 265627 Y1 Y1 G2 CO

SS D I A N G
265689 v

I ON A L E N
E2HA-18

PE60018676
SENSORS. POWER PACKS ARE NOT SHOWN. FIELD COORDINATE D

H
G2 G2 G2

A
p p p n

STATE OF
L . H I TC

E
OS OS OS Z1

I ST ER
GROUP m m m LOCATIONS AND RECORD ON ELECTRICAL RECORD DRAWINGS.
E2HA-16 E2HA-16 E2HA-16 Y1 v

No.
265689 A2 A2 A2 A2 VIDEO Y1 Y1
JAIL p Z1 J. CROSS HATCHED/SHADED FIXTURES = FIXTURES POWERED VIA
B1004 G2 m 265714

EG
AA1 p p

IN
STORAGE OC EM n Z1Av EMERGENCY BACKUP GENERATOR FOR EMERGENCY EGRESS.

IN
+12'-0" B1 B1 B1 m 3 E2HA-16 p OC
R
PRETRIAL PRETRIAL PRETRIAL PRETRIAL L1 L1 B1085 L1 m L1H-9 E2HA-16 8'-0" RV
AFG
SERVICES SERVICES SERVICES SERVICES
OC OC E2HA-16 K. EM = EMERGENCY EGRESS FIXTURE. N.L. = NIGHT LIGHT
MA FE
E2HA-18 WG OC C1 X3A
E2HA-16
265602 P RO
OFFICE A2 OFFICE OFFICE A2 OFFICE F
A2 A2 E2HA-17 L1H-9 G1 G2 Z1
B1071 G1 G2 L. WHERE SWITCH CIRCUIT IS NOT INDICATED, ALL FIXTURES IN
B1070 B1072 B1073 N.L. G2 X3A G2 G2 n
JANITOR OS m N.L. v ROOM OR AREA SHALL BE ON SAME SWITCH CIRCUIT
COURTYARD OS L1H-9 m L1H-9 m m
OS OS OS B1007 E2HA-16 m L1H-9 B1 B1 Z1 CONTROLLED BY LIGHTING CONTROL DEVICE INDICATED IN SPACE.
265686 B1135 E2HA-17 OC
265689 E2HA-17 E2HA-17 E2HA-17 E2HA-16 X1 a a LOBBY v
vv 265689 OS ATTORNEY
CC1 265681 CC1 A1 OS OS OS L1E-1 G2 Z1A M. SEAL ALL PENETRATIONS THROUGH PRECAST, REFER TO
WP E2HA-17 WOMENS MENS OS CONFERENCE G3 B1001
vv vv A1 A1 A1 M1N-SC E2HA-16 E2HA-16 E2HA-16 n 4'-0" SPECIFICATION 079200 FOR TYPE.
D OC E2HA-17 OC E2HA-17 L2 D1 D1 E2HA-16 B1018 N.L.
E2HA-18 CC1 E2HA-18 C1 EM WG E2HA-15 B1008 B1009 L1
E2HA-18 OC
m m B1 B1 B1 L1H-9 SEX
vv C J L1E-2 CORRIDOR E2HA-17 B2 B1 L1 N.L. B1 B1 N. REFER TO DRAWING E-302-E FOR LIGHTING CONTROL NOTES.
CLOSET STORAGE ZONE-5 CELL C1 C1 OFFENDER
E2HA-18 B1068 L1E-1 a a
265689 B1069 265608 X1 3 B1084 265601 PUBLIC MASTER REGISTRY
B1086 PUBLIC PUBLIC
B2 VISITATION PUBLIC
M1N
INTERLOCK
L1E-2
C2 C2 ZONE-5
F1
E2HA-14
VISITATION
B1011
VISITATION VISITATION -
*
INTERLOCK B1 CONTROL C1002
LIGHTING KEYNOTES 265###

E2HA-16
B1067 M1N OS,D EM OC E2HA-16 F1 E2HA-16 OC ADA B1015 a B1016
B1010 B1012E2HA-16 q G1 G1
A2 N.L. E2HA-17 M1N-SC L1E-2 M1N-SC E2HA-16 EM B1
OC WG B1 B1 B1013
* WG OC
L1E-2 E2HA-15 E2HA-15 WG WG WG WG L1E-1 a B1 265601 (TYPICAL) ALL CELLS, TOILETS & SHOWERS WILL HAVE LIGHTING

OS
TRANSPORTATION E2HA-17 PRETRIAL E2HA-16 r
B1 B1 E2HA-16 E2HA-16 E2HA-16 E2HA-16 E2HA-16 C J FIXTURE(S) SUPPLIED BY CELL MANUFACTURER AND BE
X1 OFFICE SERVICES a E2HA-16
a a OC M1 OC M1 OC M1 OC L1
M1 s OC
CONNECTED BY DIV. 26. FIXTURE SHALL BE 277V AND BE
L1E-2 WORKROOM CELL 265601 CELL D 265608
P1 B1064 265601 F1 E2HA-16 TOILET E1HB-13 CONTROLLED THROUGH THE UTILITY CONTROL PANELS.
OS TRANSPORTATION B1074 C2 B1083 B1 B1 L1 G1 G1
N.L. A2 TOILET C2 PASSAGE B1087 E2HA-16 B1 B1
E2HA-17 WAITING B1 F1 F1 ATTORNEY q B1017 265602 PIR HIGH BAY OCCUPANCY SENSOR. PROVIDE POWER PACK(S) AS
L1E-2 a B1066 B1053E INMATE INMATE a a
B1 WG E2HA-14 E2HA-14 CONFERENCE F1 RECOMMENDED. DEVICE TO BE FIXTURE MOUNTED OR PENDANT
B1062 M1N-SC 265694 265693 INMATE VISITATION INMATE VISITATION - 265718
a M1
OC M1N-SC B1019 E2HA-16 MOUNTED AT SAME HEIGHT AS FIXTURES IN ROOM.
F1 E2HA-15 265611 E2HA-15 VISITATION VISITATION ADA
INTERLOCK X1 a N.L. a E2HA-17 B1022 STORAGE 265604 LIGHTING IN ROOM/AREA TO BE CONTROLLED BY UTILITY
X1 OC OC E2HA-17 OS OS B1023 B1021 B1020 SECURITY
E2HA-17 L1E-2 E2HA-17 E2PB E2PA E2HA X1 3 CONTROL PANEL, REFER TO LIGHTING CONTROLS NOTE ON
L1E-2 B1063 L1E-2
E2HA-17 B1 E2HA-17 B1 CELL CELL
UPS2 DIS-UPS2 C1083
L1 TOILET W J L1E-1 C1046 E-302-E AND SPECIFICATIONS FOR MORE INFORMATION.
F3 B1 B1 B1 A2
N.L. B1 B1065 OC TOILET TOILET B1082 265601 265601 B1088 265716 ELECTRICAL 265606 (TYPICAL) PROVIDE WALLBOX DIMMER(S) FOR 277V LED DRIVERS,
P1 B1 WG 265609 q q N.L. B1 B1 F2 F2
L1E-2 a B1024 F3 E2HA-16 SLIDER WITH POSITIVE OFF. DIMMER SHALL BE PROVIDED PER
a a B1076 B1075 L1E F3 L1E-1 q q OS 3
M1N-SC SQE#6b SQE#6a X1 LIGHT FIXTURE MANUFACTURERS RECOMMENDATION FOR
M1 F1 M1N-SC OS E1HB-13
F1 E2HA-15 B2 U2R L1H U2R-30 U2R-28 265715 PROPER DIMMING OF LED FIXTURE(S).
E2HA-17 E2HA-15 L1E-1
F1 E2HA-17 E2HA-17 ZONE-5 INTERLOCK
WOMENS 265608 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
a E2HA-17 L1 C1044 MODULE LIKE LVS, INC #EPC-1 OR APPROVED EQUAL IN
265602 OC E3H-8 CELL CELL CELL CELL CELL CELL CELL CELL B1026
CELL 265601 265601 ZONE-1 3 L1 A1 OC ROOM/AREA FOR CONTROL OF EMERGENCY LIGHT(S).
M1A M1N M1N B1089 M1A-SC B1041 M1A-SC B1040
B2 B1077 B1078 B1079 B1081 B1091M1N-SC B1092 M1N-SC EM OS X1 N.L. k NON-EMERGENCY CIRCUIT SHALL BE SAME CIRCUIT AS REST OF
E2HA-17 E2HA-17 E2HA-17 F1 F1 E2HA-15 E2HA-15
N.L. E2HA-15 E2HA-15 L1E-2 L1E-1 E1HB-13 EM J ROOM LIGHTING. REFERENCE DETAIL #7 ON SHEET E-802. MODULE
P1 L1E-2 M1N-SC M1N-SC M1N-SC E2HA-14 B2 E2HA-14 C
ZONE-5 M1N-SC 265601 265601 B1 DP-L-9 TO BE FLUSH MOUNTED AS INDICATED. RECORD EXACT LOCATION
a E2HA-15 E2HA-15 E2HA-15 M1N-SC
EM E2HA-15 E2HA-14 ON RECORD DRAWINGS. MODULE TO CONTROL FIXTURES IN AREA
E2HA-15
MALE F1 W2 U.O.N. WITH DOTTED LINE.
L1E-2

E2HA-14

E2HA-14
3 F1 F1 B1
DETOX CELL E2HA-14 E2HA-14 B1 265609 MOUNT FIXTURES IN ROOM/AREA WITH BOTTOM AT +10'-0" AFF.
265601 265601 265601 C J 265601 265601 E2HA-14 E2HA-14 N.L.
B1061 CELL q A1 A1 CONTROL AND CIRCUIT AS SHOWN.
F1 265601 265601 B1090 M1A-SC M1A-SC L1E-1
F1

F1
265604 X1 B1080 265608 MENS b b
E2HA-14 E2HA-15 E2HA-15 265610 (TYPICAL) OCCUPANCY SENSOR. PROVIDE POWER PACK(S) AS
M1N M1N M1N L1E-2 X1 265628 B1027 RECOMMENDED. DEVICE TO BE FIXTURE MOUNTED OR PENDANT
E2HA-17 E2HA-17 E2HA-17 L1E-2 DM MOUNTED AT SAME HEIGHT AS ROOM/AREA FIXTURES.
L1
P1
B2 B2 CELL 265601 265601
a X1 ZONE-1 CELL ADA B1 OS
SECURE
a,b 265611 FIXTURES IN ROOM/AREA TO BE CONTROLLED BY LIGHTING
B2 ZONE-1 B3 B2 B2 ZONE-1 B1042 E2HA-14 E2HA-14 E1HB-13 CONTROL SWITCH (DIMMER) IN BOOKING COUNTER #B1053A.
X1 L1E-2 B1039 CORRIDOR
ZONE-1 EM ZONE-1 ZONE-1 ZONE-1 EM A1 OC A1 265614 STEM/PENDANT MOUNT FIXTURE WITH BOTTOM AT +8'-0" AFF.
265604 3
B2 L1E-2 INTAKE L1E-2 B1025 b b
ZONE-1 DAYROOM F1 265619 ROOM LIGHTING CONTROLLER AND INDICATOR LIGHTS (ONE PER
MEDICAL CENTER 265619 BODY
TESTING E2HA-14 ZONE). REFER TO ASSOCIATED ROOM DETAIL ON SHEET E-805
E2HA-14 SCANNER B1037
PRE-SCREENING A2 B1053 B1 B1 FOR LIGHTING CONTROL SCHEMATIC.
B1056 L1 B1035 L1 L1 L1
B1057 B2 ZONE-1 A2 q q K 265620 FLUSH MOUNT EPC IN WALL FOR CONTROL OF MALE MEDICAL
L1B L1B ZONE-2 ZONE-2
P1 ZONE-1 A2 A2 ZONE-3 A2 B2 L1 E2HA-14 ZONE-1 ZONE-1 DAYROOM B1095 EMERGENCY FIXTURES.

J
a EM ZONE-1 ZONE-3 EM 3 ZONE-3 ZONE-1 OC
ZONE-2 EM
L1B WG L1E-2 B1 A1 A1 265621 FLUSH MOUNT EPC IN WALL FOR CONTROL OF FEMALE DAYROOM
L1E-2 L1E-2 E2HA-14 STAFF
E2HA-17 E2HA-14 E2HA-14 b b B1112 EMERGENCY FIXTURES.
DM 265628 TOILET
OS 5 OS 265623 INSTALL EPC ABOVE CEILING FOR CONTROL OF MEDICAL WAITING

09/12/19
09/26/19
WG OC B1031 B1122 AND INTERLOCK B1121 EMERGENCY FIXTURES.

DATE
_____________________
W1 W1 W2 W1 W1 W2 3
E2HA-17 ZONE-2 ZONE-2 ZONE-4 ZONE-4
E-807 ZONE-4
INTERLOCK ZONE-4 265627 PROVIDE DAYLIGHT SENSOR (QTY AND LOCATION PER
B2 A2 A2 X1 PASSAGE X1 3
B1055 B2 MATRON MANUFACTURER) FOR AUTOMATIC CONTROL OF ROOM LIGHTING
WG ZONE-1 ZONE-1 ZONE-3 L1E-2 B2 L1E-2
L1B L1B L1B W1 W1 W2 W1 W1 W2 ZONE-6 B2 B1029 C1080 LEVELS, REFER TO ASSOCIATED ROOM DETAIL ON E-806 FOR
P1 OC B2 ZONE-6
a X1
E2HA-17 ZONE-2 ZONE-2 ZONE-4 BOOKING ZONE-4 ZONE-4 ZONE-4 ZONE-1 N.L. ZONE-6 EM B2 B1 A1 OC A1
LIGHTING CONTROL SCHEMATIC.
COUNTER 265611 B1
L1E-2 L1E-2 L1E-2 ZONE-6 ZONE-1 WG 265628 PROVIDE DAYLIGHT SENSOR (QTY AND LOCATION PER
X1 B1053A q
W1 W1 W2 W1 W1 W2 N.L. E1HB-15 MANUFACTURER) FOR AUTOMATIC CONTROL OF ROOM LIGHTING
L1E-2 ZONE-1 LEVELS, REFER TO ASSOCIATED ROOM DETAIL ON E-805 FOR
ZONE-2 ZONE-2 ZONE-4 ZONE-4 ZONE-4 ZONE-4 L1E-1 DM
E1HB-15

REVISION
a SEARCH SEARCH LIGHTING CONTROL SCHEMATIC, WALL MOUNT AT +12'-0" AFF.
265602 OC E3H-8 OS TOILET TOILET 265627
WG TOILET JANITOR
TCP 265629 FIXTURE TO BE MOUNTED ON TOP OF CANOPY FOR ILLUMINATION
E2HA-17 A2 265610

1 Addendum #01
3 Addendum #03
L1 OC
SHOWER DM 265628 SHOWER SHOWER OF SIGN ABOVE. FIELD COORDINATE EXACT LOCATION PRIOR TO
E2HA-17 B2 ZONE-1 L1P-12
B1030
MAIN DATA L1B A2 B1034 B1033 B1 B1 ROUGH-IN.
P1 B1059 ZONE-1 A2 A2 A2 B2 OC WG
FRAME ZONE-3 M1 M1 265673 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
a EM ZONE-1 ZONE-3 ZONE-3 ZONE-1 OC OC X1 OC E1HB-15
E2HA-17 M1A J EM E2HA-14 E2HA-14 B1 PHOTOCELL. REFER TO DETAIL #6 ON SHEET E-807. CONTROL VIA
B1060 F1 L1E-2 265619 WG WG M1 L1E-1
MEDICAL F1 E2HA-14 M CONTACTOR #LC4A.
L1 E2HA-17 E2HA-14
PRE-SCREENING 265608 INTAKE E2HA-14 SECURITY 265680 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER CONTROL
B1
B2 CENTER (TYP. 5/E-807) B1 B1

NO.
B1058 J C C1079 MODULE LOCATED IN STORAGE #E1016B.
F1 ZONE-1 X1 B2 B2 q q
B1053 X1 ZONE-1 ZONE-1 265681 CONNECT TO CIRCUIT SHOWN USING 2#10+#10G. IN 3/4"C.
E2HA-17 L1E-2 B2 ZONE-1 B2 B2 B2 ZONE-1
L1E-2 265686 EXTERIOR TYPE 'CC1' LIGHTING FIXTURES SHALL BE MANUALLY
ZONE-1 EM ZONE-1 ZONE-1 ZONE-1 EM B1 B1
P1 E2HB-15 OC B1 SWITCHED FROM LOCAL EXTERIOR DIMMER SWITCH. DIMMER
M1N L1E-2 L1E-2
N.L. M1A M1N SWITCH SHALL BE COMPATIBLE WITH LED FIXTURE DRIVER.
E2HA-17 INMATE

CHK'D: MLH
L1E-2 E2HA-17 E2HA-17 FIXTURES SHALL ALSO BE CONTROLLED VIA LIGHTING
X1

SEPTEMBER 5, 2019
B1 B1 PROPERTY SECURE
L1E-2 CONTACTOR FOR DUSK-TO-DAWN CONTROL. PROVIDE LABEL ON

1663-1190-90
STORAGE CORRIDOR A1 A1
FEMALE OC E2HB-15 TOGGLE SWITCH FACEPLATE INDENTIFYING EXTERIOR LIGHTING
F1
E2HA-14

F1
E2HA-14
X1 PADDED TOILET / PADDED PADDED TOILET / PADDED B1032 B1025 ASSISTANT ALSO INTERLOCKED/CONTROLLED VIA LIGHTING CONTACTOR.
DETOX INMATE

DESIGNED: MHK,RDW
OC SHOWER CELL OC SHOWER CELL 265601 265601 OC
L1E-1 CELL WG CELL CLOTHING JAIL
WG B1 B1 B1 265687 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND

DRAWN: MHK,RDW

PROJECT NUMBER
B1054 B1052 B1051 B1050 B1049 B1048 B1047 265601 E1HB-15 E1HB-15 COMMANDER
M1N-SC M1N-SC B1043 B1 B1 B1 PHOTOCELL. REFER TO DETAIL #3 ON SHEET E-807. CONTROL VIA

MLH
265604 L1 M1N M1A M1N M1N M1N M1N-SC OC E2HB-15 B1 ZONE-1 C1078 CONTACTOR #LC3A.
M1N E2HA-15 E2HA-15 E2HA-15 M1A E2HA-15 E2HA-15 E2HA-15 E2HA-15 q A1 A1
M1N M1N E2HA-15 B1 B1 N.L. 265689 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
E2HA-17 E2HA-17 E2HA-17 E2HA-15 ZONE-1 L1E-1
E2HA-14
E2HA-14

PHOTOCELL. REFER TO DETAIL #2 ON SHEET E-807. CONTROL VIA

APPRV'D:
B1 B1 B1
WG CELL CELL ADA CELL ADA CONTACTOR #LC2A.
OC 265604 265604 265604 265604

DATE:
E2HB-11 OC E2HB-15
L1 B1046 B1045 B1044 B1 B1 265690 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
F1
F1

N.L. B1 B1 A1 A1 PHOTOCELL. REFER TO DETAIL #2 ON SHEET E-807. CONTROL VIA


L1E-1 B1 B1 OC E2HB-15 CONTACTOR #LC2B.
PADDED
F1
E2HB-11

SQE#7b JANITOR PADDED FEMALE FEMALE FEMALE FEMALE FEMALE


CELL INTERLOCK WG B1 B1 B1 B1 E1HB-15 265693 LIGHTING CONTACTORS, LC2A, LC2B, LC2C AND LC2D, REFER TO
U1R-18 B1108 CELL CELL ADA CELL CELL CELL CELL
B1093 OC E2HB-11 JAIL EXTERIOR LIGHTING WIRING DIAGRAM, SHEET E-807, DETAIL #2.
B1109 B1111 B1114 B1115 B1116 B1117 B1118 B1 B1 OC
SQE#7a M1N B1 OC E2HB-15 COMMANDER 265694 NEW TIME CLOCK #TC2 FOR CONTROL OF EXTERIOR LIGHTING,
M1 M1N M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC
U1R-16 M1A B1 B1 E1HB-15 C1077

VIGO COUNTY SECURITY CENTER


265686 E2HB-13 OC E2HB-15
B1 B1 B1 REFER TO EXTERIOR LIGHTING WIRING DIAGRAM, SHEET E-807,
E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 MEDICAL B1 3
ww TR-2E L1 q DETAIL #2. CONNECT TO CIRCUIT E2PA-35 USING 2#12+G. IN 3/4"C.
3 RECORDS B1 B1 q A1 A1
E2HB-11

WP
E2HB-11

E2HB-11

E2HB-15 ZONE-1 265714 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER CONTROL

FIRST FLOOR LIGHTING PLAN - AREA B


L1 B1 OC ZONE-1
D 265604 WG OC
TOILET / 265604 STORAGE B1 B1127 E2HB-15 MODULE LOCATED IN ELECTRICAL #B1024.
* SHOWER OC B1 B1
E3H-9 E2HB-11 B1094 265601 265601 265601 265601 265601 265715 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
F1
F1

F1

E2HB-11 B1110
B1 B1 MODULE #GTD2, LIKE LVS INC #EPC-1 OR APPROVED EQUAL IN
COUNCILOR JANITOR WALL FOR CONTROL OF EXTERIOR EMERGENCY LIGHT.
CC1 L2 B1
CC1 X1 L2 B1128 B1 B1 C1076 NON-EMERGENCY CIRCUIT SHALL BE CIRCUIT E2HA-18.
L1 L2 L2 L2 h,k L1
ww ww L1B L1B L1E-1 j L2 L2 3 REFERENCE DETAIL #7/E-802. FLUSH MOUNT AS INDICATED.
h h,k h,k h,k EM OC E2HB-15 OC E2HB-15 B1 L1 L1
E3H-9 E3H-9 h h WORK 265608 3 B1 WG OC RECORD EXACT LOCATION ON RECORD DRAWINGS.
EM L1E-1 L2 B1 DENTAL
265687 STATION 265620 265621 FEMALE E1HB-15
265687 L1E-1 h,k C J *,OS B1 B1 265716 FURNISH AND INSTALL CENTRAL UNINTERRUPTIBLE EMERGENCY
DAYROOM B1129
DM

B1096 h,k 265608 265628 E2HB-11 B1 LIGHTING INVERTER, SINGLE PHASE, 277V INPUT/OUTPUT WITH 4
J FEMALE
3 B1112 B1

TERRE HAUTE, INDIANA


265619 *,D 3 L2 265608 L1 N.L. OUTPUT BREAKERS, 90-MINUTE RATED BATTERY BACKUP
3 J WG TOILET PHARMACY q INMATE/
COURTYARD E2HB-11 L2 h,k 265623 L1E-1 CAPACITY AT RATED LOAD, UL 924 LISTED, 3KW MINIUM FOR L1E,
L2 OC E2HB-11 SHOWER
B1126 ELECTRICAL ATTORNEY
L2 h,k L2 E2HB E2PC E2PD 10KW MINIMUM FOR L2E, CONTROLLED POWER MODEL ELU OR
B1134 L2B L2B j hh B1113 OS * CONFERENCE
CC1 hh hh L1B j h,k EM h,k F1 L1 L1
E2HB-11
SQE#11 F3 F3 B1028 APPROVED EQUAL BY MYERS, DUAL-LITE, EATON.
265681 *,D L1E-1 M1N E2HB-11 A1 E2HB-11 U1R-15 L1B C1075 L1B
ww L1B h *,D X1 265718 FURNISH AND INSTALL MULLION MOUNT SWITCH, ROUTE WIRING
E2HB-11 E2HB-15

A NEW
h TOILET NAC-1 L1E-1 THROUGH MULLION.
E3H-9 EM E2HB-11 U1R
SHOWER STAFF L2P-18
265687 L1E-1 L1 L1 L1
TOILET OC WG OC
L2B L2B L1 L1 L2 B1120 MEDICAL DIS-UPS1
h
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

MALE M1A M1N E1HB-15


hh hh h h EM h F1 B1125 WAITING
MEDICAL 3 *
DAYROOM L1E-1 WGOC E2HB-11 B1122 WG OC EXAM
265687 E2HB-11 B1 B1 KEY PLAN
E2HB-11 E2HB-11 A1 A1 A1
B1095 B1130 s N.L.
DM

265687 CC1 265628 OS L2 WG L2


L1E-1 OC
ww E2HB-11 L1 JAIL E1HB-15
CC1 L1 L1 WG L1
E3H-9 SUPERVISORS VIDEO
ww h L1B L1B h L1 L1 L2 E2HB-11 OC L1 EM M1N SECURE SECURE
L1E-1 INMATE ARRAIGNMENT N
E3H-9 EM h h EM h h h INTERLOCK E2HB-11 F1 E2HB-15 OC B1133 CORRIDOR CORRIDOR
L1 TOILET WAITING
L1E-1 L1E-1 B1121 3 E2HB-11 D1012 E1012
EM C1073
B1131 A1 A1
L1 L1E-1 WG OC
265601 C2 C2 L2
F1
E2HB-11

F1
E2HB-11
F1
E2HB-11

F1
E2HB-11

F1
E2HB-11

LACTATION s s EM
265601 265601 265601 265601 265601 265601 265601 265601 265601 265601 ROOM WG OC
EXAM C E1HB-15
B1123 NURSE

J
L1 L1 L1 B1132
B1124
L1 * L1 L1 265608
M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC
E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 E2HB-13 L1 OC
* E2HB-11 A1 A B C
WG C2 C2 C2 L2
CELL CELL CELL CELL CELL CELL CELL CELL CELL ADA 265606 E2HB-11
CELL E2HB-11 X1 N.L. s N.L.
B1105 B1104 B1103 B1102 B1101 B1100 B1099 B1098 B1097 *,D,OS L1E-1 E2HB-15 X1
B1106 X1 L1E-1 L2E-3
9/25/2019 5:26:00 PM

E2HB-11 L2E-2
AA1 L1E-1
EM X1 X1 X1
+12'-0" B1 L2E-1 B1 B1 B1 L1E-1 L2E-2
X1
AFG L1 N.L. B1 B1 N.L. B1 B1 N.L. SECURE B1 B1 N.L. B1 C2 C2 C2 C2
L1E-1

DRAWING NUMBER

E-301-B
L1H-11 N.L. L1E-1 s s L1E-1 s s L1E-1 CORRIDOR s s L1E-1 s s SECURE s s SECURE s
L1E-1 CORRIDOR CORRIDOR

ELECTRICAL
265673 X1 D1012
265680 L1E-1 D1012 E1012
D E
1 FIRST FLOOR LIGHTING - AREA 'B'
E-301-B SCALE: 1/8" = 1'-0"
NORTH
14 14.2 AA1 15 15.3 AA1 16 17 AA1 18 AA1 19 AA1 20 20.2 20.6 20.7 21

12.7
+12'-0" 265699
AFG E1HA-8
+12'-0" 265699
AFG E1HA-8
265699 +12'-0"
E1HA-8 AFG
265699 +12'-0"
E1HA-8 AFG
265699 +12'-0"
E1HA-8 AFG
GENERAL NOTES
A. FOR LIGHTING FIXTURE SCHEDULE, SEE SHEET E-606. REFER TO
265690 A
GG1 13 REMARKS COLUMN ON LIGHTING FIXTURE SCHEDULE FOR
265629 A2 A2 FIXTURE MOUNTING HEIGHTS AND REQUIREMENTS U.O.N ON THIS
E2HA-20 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1
j j DRAWING.
D2 A2 A2 A2 A2 B1 B1 B1
265714 CONFERENCE SHERIFF'S CHIEF CHIEF
EM B. FOR OCCUPANCY SENSOR WIRING DETAIL, SEE DETAIL #6/E-802.
265689

DLZ INDIANA, LLC


E2HA-18 ROOM OFFICE DEPUTY'S DEPUTY'S I.T. OFFICE AGENCY
C1016 OFFICE OFFICE OC
C1015 C1020 C1021 C. CONDUITS SHALL NOT BE ROUTED ALONG BUILDING EXTERIOR.
C1018 C1019 SQUAD E1HB-13 CONCEAL BY ROUTING ON INTERIOR AND PENETRATE THROUGH
265627 VESTIBULE A2 A2 A1 A1 A1 A1 E1HB-9 OC FITNESS B
A1 A1 A1 A1 A1 A1 A1 ROOM WALL AT EACH EXTERIOR FIXTURE LOCATION.
j j
B1000 C1027 C1028
OC
E1HB-9 OC 265699 D. FIELD COORDINATE, PRIOR TO CONSTRUCTION, EXACT MOUNTING
Y1 Y1 j OS OS OS OS A2 A2 A2 A2 B1 B1 B1 AA1 HEIGHT OF ALL FIXTURES TO AVOID DUCTWORK AND EQUIPMENT.
pp pp E1HB-9 E1HB-9 E1HB-9 E1HB-9
pp h +12'-0"
OC E2HA-16 C1F G1 E1HB-9 AFG E. FOR EXTERIOR LIGHTING WIRING DIAGRAM, SEE DRAWING E-807.
Y1
265602 Y1 A2 A2 OS A1 A2 A1 A1 OS E1HA-8
N.L. OC
pp j j E1HB-9 E1HB-9 g h h g g E1HB-9 E1HB-9 F. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND
L1H-9
265606 TOILET E1HB-9 ADMIN A2 A2 CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
j D2 E1HB-9 TRAINING
C1017 RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
D SUPPORT CORRIDOR OFFICE
3 CIVIL AND OFFSET BACK TO BACK BOXES.
C1010 C1009 C1029 B1 OC B1 B1
CORRIDOR X3A (TYP. ALL EXITS C1022
X3A p 265608 A2 A2 A2 E1HB-13 C G. CEILING MOUNTED OCCUPANCY SENSORS SHALL BE MOUNTED IN
OC E2HA-16 Z1 C1009 A1 g g DP-L-9 THIS SHEET)
L1H-9 A1 OC C J A1 OC CENTER OF CEILING TILE U.O.N. COORDINATE EXACT LOCATIONS
Y1 265602 G2 v A2 OC g g E1HB-9 E1HB-9 A1
g A1 A1 E1HB-9 g A1 BEFORE ROUGH-IN.
p Y1 N.L. Z1 a E1HB-9 EM A2 A2 OS g
EM
265714 p g g EM g g OC
L1H-9 v X3A E1HB-9 C.7 H. OCCUPANCY SENSORS ARE SHOWN FOR PURPOSES OF
DP-L-9 F1 E1HB-9
L1H-9 Z1A OC a DP-L-9 IDENTIFYING ROOMS/AREAS WHERE REQUIRED. COORDINATE
E1HB-9 E1HB-9 F1 D
Y1 Y1 v 4'-0" SHARED F1 WITH MANUFACTURER ON QUANTITY AND LOCATIONS REQUIRED
c TOILET / TOILET / F1 TOILET / E1HB-9
p p E1PC-40 OC ADMINISTRATION STORAGE E1HB-9 CORRIDOR
CC2 OUTDOOR FOR COMPLETE COVERAGE.
D2 SHOWER A D2 SHOWER B E1HB-9
SHOWER C D2 OC E1HB-13 X3A CC2 265699 EM CC2
R
EE
D1 C1014 C1011 DP-L-9 STAFF CK IN
Z1 A1 A2 A1 C1024 C1025 C1026 C1023C dd 265700 DP-L-11 dd CO

SS D I A N G
Y1 Y1 G2 c A2 A2 g E1HB-9 B1 B1 B1 DINING I. PROVIDE POWER PACKS AS REQUIRED FOR OCCUPANCY

I ON A L E N
e f E1HB-9 CC2 265699 CC2 CC2

PE60018676
D

H
v B1 B1

A
C1F C1F C1F BREAK

STATE OF
OC

L . H I TC
A2 dd SENSORS. POWER PACKS ARE NOT SHOWN. FIELD COORDINATE

E
p p n d d EM C1030A

I ST ER
Z1 A1 E1HB-9 F1 E1HB-9 265608 ROOM dd 265700 EM dd
a DP-L-9 E1HA-8 LOCATIONS AND RECORD ON ELECTRICAL RECORD DRAWINGS.

No.
Y1 v f MAIL E1HB-9 C J DP-L-11
Y1 F1 C1030 ZONE-1
p Z1 WAITING WORK OS OS OS A1 J. CROSS HATCHED/SHADED FIXTURES = FIXTURES POWERED VIA
C1023A OC g

EG
265714 d e FILE E1HB-9 (TYP. QUADRANT)

IN
p f E1HB-9 E1HB-9 E1HB-9

IN
EM n Z1Av ROOM g EMERGENCY BACKUP GENERATOR FOR EMERGENCY EGRESS.
C1000 E1HB-9 OC OC OC E1HB-9
R
E1HB-9 E1HB-9 STORAGE RV
L1H-9 p OC
g OC EM
E2HA-16 8'-0"
A2
C1013 C1012 A1 A1 E
MA FE
OC E2HA-16 X3A E1HB-9 DP-L-9 K. EM = EMERGENCY EGRESS FIXTURE. N.L. = NIGHT LIGHT P RO
265602 a A1 A2 g 265608 A1 g T1 T1 T1 T1
G2 A2 A2 DP-L-9 C1 F 3
Z1 EM e f A1 g X3A T1 T1 T1 T1 T1 T1
n
D1 d B1 OC B1 OC J C g OC E1HB-13 L. WHERE SWITCH CIRCUIT IS NOT INDICATED, ALL FIXTURES IN
DP-L-9 d A1 g g EM
v J C b E1HB-9 X3B E1HB-9 DP-L-9 ZONE-3 ROOM OR AREA SHALL BE ON SAME SWITCH CIRCUIT
f E1HB-9 CORRIDOR DP-L-9 OC
B1 Z1 265608 DP-L-9 (TYP. QUADRANT) CONTROLLED BY LIGHTING CONTROL DEVICE INDICATED IN SPACE.
v C1023B X3A CLOSET
a LOBBY b T1 T1 T1 T1 T1 T1
DP-L-9 T1 T1 T1 T1 ZONE-5
B1001 G2 Z1A B1 C1035 (TYP. QUADRANT)
M. SEAL ALL PENETRATIONS THROUGH PRECAST, REFER TO
G3 OC a X3A OS LACTATION
n 4'-0" CORRIDOR E1HB-13 WOMENS X3A
X3A SPECIFICATION 079200 FOR TYPE.
N.L. E1HB-9 DP-L-9 A1 X3A A1 DP-L-9 T1 TRAINING
A1 A1 A1 A1 C1008A C1033 E1HB-13 OC C1 T1 T1 T1 T1 T1
L1H-9 SEX A2 C J C1003 DP-L-9 DP-L-9 ROOM N. REFER TO DRAWING E-302-E FOR LIGHTING CONTROL NOTES.
B1 g g g g g g A1
a OFFENDER a 265608 EM B1
X3A g OC EM g OC g OC B1 aa C1034
REGISTRY DP-L-9 STORAGE B1
DP-L-9 E1HB-9 DP-L-9 E1HB-9 E1HB-9 T1 T1 T1 T1
C1002 3 X3A C1008 E1HB-13 T1 T1 T1 T1 T1 T1 265699
DP-L-9 OC bb
E2HA-16

OS

E1HB-13

E1HB-13
G1 G1 Z1A
B1 E1HB-13 E1HB E1HB-13 INTERVIEW INTERVIEW E1PC-38 265619
E1HB-13 B1 B1 D1 AA1

E1PD E1PC
a B1 F2 B1 Z1 E1HB-11
265608
OS

r F2 C1006 C1007 B2 B2 aa +12'-0"

F1

F1
E2HA-16 265609 A1 A1 A1 bb
OC A1 A1 A1 ALCOVE C J T1 T1 T1 AFG
s ELECTRICAL JANITOR k aa Z1 T1 T1 T1 T1 T1 T1 T1 T1 E1HA-8
E2HA-16 TOILET E1HB-13 SEX C1031A bb
G1 G1 C1004 C1005 A1 A1 DEF TAC EM ZONE-2 ZONE-6
B1 OFFENDER D1 DP-L-9 Z1 (TYP. QUADRANT) (TYP. QUADRANT)
B1017 STORAGE ARMORY B1 T1
a OC AND OC OC
aa CORRIDOR bb T1 T1
F1 E1HB-13 C1039 E1HB-13 k T1 T1 T1 T1 T1 T1 T1 T1
E1HB-13EVICTION E1HB-13 C1038 OC E1HB-13
E2HA-16 OC OC C1031
SECURITY
STORAGE
C1083
OFFICE
C1001
A2 A2 A2 A1 A1 A1 A1 B1 B1 MENS
aa
E1HB-11
265619 T1 T1 T1 LIGHTING KEYNOTES 2656##

E1HB-13
A1 B2 B2
C1046 A1 A1 OC B1 C1032 C1 OC E1HB-13
A2 CID k
E1HB-13 OC X3A 265602 PIR HIGH BAY OCCUPANCY SENSOR. PROVIDE POWER PACK(S) AS
B1 F2 F2 SUPERVISOR EM A1 T1 T1 T1 T1 T1 T1 T1 T1
DP-L-9 T1 T1 T1 RECOMMENDED. DEVICE TO BE FIXTURE MOUNTED OR PENDANT
q OS E1HB-13 OFFICE DP-L-9 aa H
X1 OS E1HB-13 3 MOUNTED AT SAME HEIGHT AS FIXTURES IN ROOM.
C1043
L1E-1 265606 (TYPICAL) PROVIDE WALLBOX DIMMER(S) FOR 277V LED DRIVERS,
INTERLOCK H.2 SLIDER WITH POSITIVE OFF. DIMMER SHALL BE PROVIDED PER
CORRIDOR A1
C1044 265608 X3A VESTIBULE A1 X3A CC2 3 LIGHT FIXTURE MANUFACTURERS RECOMMENDATION FOR
k k A1 k OC CORRIDOR A1 C1082 A1 X2 aa
3 L1 A1 OC C J A1 A1 X2 A1 A1 J C A1 DP-L-9 A1 DP-L-9 265699 EM PROPER DIMMING OF LED FIXTURE(S).
E1HB-13 A1 E1HB-13 OC k C1085 k OC OC
k OC
EM C1036 N.L. CC2 CC2 ZONE-4
X1 N.L. k k E1HB-13 k DP-L-9 k k X2 k k k k DP-L-9 j DP-L-9 265699 E1HA-8 265700 DP-L-11 265699 E1HA-8 (TYP. QUADRANT)
k EM 265608 EM X2 EM DP-L-9 265608 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
L1E-1 E1HB-13 EM J 265608 b DP-L-9
265699 CC2
OC
DP-L-9 DP-L-9 DP-L-9 DP-L-9 j 265699 CC2 265699 CC2 MODULE LIKE LVS, INC #EPC-1 OR APPROVED EQUAL IN
E1HB-13

DP-L-9 C E1HB-13 265697 X3A E1HA-8 265700 EM E1HA-8 ROOM/AREA FOR CONTROL OF EMERGENCY LIGHT(S).
DARK ROOM EVIDENCE 3
X2 DP-L-9 DP-L-11 NON-EMERGENCY CIRCUIT SHALL BE SAME CIRCUIT AS REST OF
LAB E1HB-13 E1HB-13 z H.7
ROOM LIGHTING. REFERENCE DETAIL #7 ON SHEET E-802. MODULE

E1HB-13
PREP.
E1HB-13
OS

B1 A2 DP-L-9 F5 J W
a

OC B1
E1HA
265701 3
N.L. C1047C C1045 E1HA-9 TO BE FLUSH MOUNTED AS INDICATED. RECORD EXACT LOCATION
A1 A1 A1 A1 A1 265698 E1HA-9 3 ON RECORD DRAWINGS. MODULE TO CONTROL FIXTURES IN AREA

E1PB E1PA
L1E-1 B1 F2
b b a a a EVIDENCE F4 F4 F4 AA1 U.O.N. WITH DOTTED LINE.
B1 OC y DP-L
OFFICE F4 z z z X2 EM
B2 B2 E1HB-13 F5 MDPB 265609 MOUNT FIXTURES IN ROOM/AREA WITH BOTTOM AT +10'-0" AFF.
ELECTRICAL z DP-L-9 +12'-0"
A2 C1048 B1 B1 B1 E1HA-9 CONTROL AND CIRCUIT AS SHOWN.
265602 C1054 E1HA-9 AFG
a,b a,b L1P z 265610 (TYPICAL) OCCUPANCY SENSOR. PROVIDE POWER PACK(S) AS
SECURE DP-L-11
E1HB-13 E1HB-13 DRUGS y OC 3 4 RECOMMENDED. DEVICE TO BE FIXTURE MOUNTED OR PENDANT
CORRIDOR EVIDENCE F5 MDPA 265699
A1 OC A1 A1 A1 OC A1 E1HB-13 OC E1HA-9 E1HA-9 MOUNTED AT SAME HEIGHT AS ROOM/AREA FIXTURES.
B1025 B1 C1051 PROCESSING
E1HA-9
N.L. 265700
b b a a a FACP-1 3 265613 MOUNT FIXTURES IN ROOM/AREA WITH BOTTOM AT +9'-0" AFF.
B1 B1 B1 C1047 F2 L1P-7 DP-L-9 F4 F4 F4 F4 CONTROL AND CIRCUIT AS SHOWN.
E1HA-9
N.L. z z z z
B1 DP-L-9 265617 IP65 RATED OCCUPANCY SENSOR LIKE HUBBELL
q B1 CID E1HB-13 N.L. MECHANICAL N.L. K #WSP-LWO-SM-UNV WITH #WSPLW0L260LM LENS OR APPROVED
E1HB-13 STORAGE DP-L-9 DP-L-9
ZONE-1 OC
E1HB-13 C1053 EQUAL. OUTDOOR SENSOR TO BE LOW/SURFACE MOUNTED WITH
OC C1041 F4 F4 360 DEGREE COVERAGE, UNIVERSAL VOLTAGE IN WHITE FINISH.
A1 A1 A1 A1 A1 B1 OC
B1 B1 B1 z z
b b a a a RECEIVING 265619 ROOM LIGHTING CONTROLLER AND INDICATOR LIGHTS (ONE PER
B1 ZONE). REFER TO ASSOCIATED ROOM DETAIL ON SHEET E-805
C1052A

09/12/19
09/26/19
F4 F4 F4 F4 FOR LIGHTING CONTROL SCHEMATIC.

DATE
3
z z z z 265627 PROVIDE DAYLIGHT SENSOR (QTY AND LOCATION PER
3 F2 L MANUFACTURER) FOR AUTOMATIC CONTROL OF ROOM LIGHTING
MATRON y TCP
OC
L1P-8 LEVELS, REFER TO ASSOCIATED ROOM DETAIL ON E-806 FOR
C1080 E1HA-9 LIGHTING CONTROL SCHEMATIC.
B1 B1 B1 B1 OC B1 F4 F4
B1 A1 OC A1 E1HA-9 265602 z z 265629 FIXTURE TO BE MOUNTED ON TOP OF CANOPY FOR ILLUMINATION
q WG B1 B1 3 OF SIGN ABOVE. FIELD COORDINATE EXACT LOCATION PRIOR TO
E1HB-15 ARMORY
OCy F4
DMZONE-1 OC F4 F4 F4 F4 ROUGH-IN.
z

REVISION
E1HB-15 E1HA-9 X2 z z z z
E1HA-9 C1050 N.L. F4 265673 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
B1 OC B1 OC B1 OC B1 OC B1 DP-L-9 N.L. N.L. PHOTOCELL. REFER TO DETAIL #6 ON SHEET E-807. CONTROL VIA
DP-L-9 z

1 Addendum #01
3 Addendum #03
E1HA-9

E1HA-9

E1HA-9

E1HA-9

265610 F2 DP-L-9 DP-L-9 CONTACTOR #LC4A.


B1
y z 3 265689 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
B1 B1 B1 B1 B1 B1 B1 3 PHOTOCELL. REFER TO DETAIL #2 ON SHEET E-807. CONTROL VIA
OC E1HB-15 EVIDENCE CONTACTOR #LC2A.
B1 E1HA-9
STORAGE F4
F4 F4 F4 M 265690 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
B1 B1 B1 B1 B1 C1049 F4 z z z z PHOTOCELL. REFER TO DETAIL #2 ON SHEET E-807. CONTROL VIA
SECURITY OC OC OC OC FACILITY z
B1 B1 CONTACTOR #LC2B.

NO.
E1HA-9

E1HA-9

E1HA-9

E1HA-9

C1079 A2 OFFICE A2
q 265697 LIGHTING CONTACTORS, LC1A, LC1B AND LC1C, REFER TO
ZONE-1 C1055
B1 B1 B1 B1 B1 B1 EXTERIOR LIGHTING WIRING DIAGRAM, SHEET E-807, DETAIL #1.
B1 E1HA-9 OC
265698 NEW TIME CLOCK #TC1 FOR CONTROL OF EXTERIOR LIGHTING,
OC F4 F4 265700 REFER TO EXTERIOR LIGHTING WIRING DIAGRAM, SHEET E-807,
F4 F4 F4 F4

CHK'D: MLH
E1HA-9 N.L. N.L. 265699 DETAIL #1. CONNECT TO CIRCUIT E1PA-48 USING 2#12+G. IN 3/4"C.
B1 B1 B1 B1 B1 y y y y

SEPTEMBER 5, 2019
OC OC OC OC
SECURE DP-L-9 DP-L-9 AA1 265699 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND

1663-1190-90
E1HA-9

E1HA-9

E1HA-9

E1HA-9

CORRIDOR A1 A1 A2 A2
EM 3 PHOTOCELL. REFER TO DETAIL #1 ON SHEET E-807. CONTROL VIA
ASSISTANT
265602 RECEIVING 265602 265602
B1025 +12'-0" CONTACTOR #LC1A.

DESIGNED: MHK,RDW
OC B1 B1 B1 B1 B1
JAIL y OC C1052 y OC y OC AFG

DRAWN: MHK,RDW

PROJECT NUMBER
E1HA-9 265700 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER CONTROL
E1HB-15 E1HB-15 COMMANDER B1 E1HA-9 E1HA-9 E1HA-9 DP-L-11 MODULE LOCATED IN MECHANICAL #C1053.
B1

MLH
ZONE-1 C1078 265701 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
A1 A1 F4
N.L. 265602 PASSAGE F4 3 F4 F4 F4 F4 F4 MODULE #GTD1, LIKE LVS INC #EPC-1 OR APPROVED EQUAL IN
E1HB-15 N.L.
y y y y y y

APPRV'D:
L1E-1 F4 F4 C1052B F4 WALL FOR CONTROL OF EXTERIOR EMERGENCY LIGHTS.
OC OC DP-L-9
y y y y X2 3 NON-EMERGENCY CIRCUIT SHALL BE CIRCUIT E1HA-8. REFERENCE

DATE:
X2
B1 E1HA-9 DP-L-9 DETAIL #7 ON SHEET E-802. MODULE TO BE FLUSH MOUNTED AS
DP-L-9
INDICATED. RECORD EXACT LOCATION ON RECORD DRAWINGS.
A1 A1 B1 B1 OC B1
b a 265714 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER CONTROL
E1HB-15 X1 MODULE LOCATED IN ELECTRICAL #B1024.
E1HB-15 E1HA-9 E1HA-9 L1B L1B L1B L1B L1B L1B L2E-2
JAIL M1
OC
COMMANDER STORAGE F4 265613 F4 N.L.
L2E-3

VIGO COUNTY SECURITY CENTER


E1HB-15 C1077 C1057 b a
B1 FACILITY K1L INTERLOCK LIGHTING IN THIS
q WORKSHOP WG WG AREA PROVIDED
A1 A1 OC L1B OC L1B C1063

FIRST FLOOR LIGHTING PLAN - AREA C


ZONE-1 K1H-7 K1H-7 K2L
F4 C1056 F4 K1H EM EM WITH
B1 B1 B1 b a L1B L1B
L1B L2E-3 L1B L1B L2E-3 COOLER/FREEZER
X2
WALK-IN UNITS
L2E-2 L1B L1B
(REFER TO FS
JANITOR DRAWINGS)
C1076 E1HB-15
3 OC
WG OC WG
L1 L1 L1B OC
K1H-7
WG OC F4 F4 K1H-7
EM
E1HB-15 b a L1B L2E-3 OS L1B L1B L1B
B1 B1 B1 K1H-7 EM

TERRE HAUTE, INDIANA


B1 B1 L2E-3
q INMATE/ INMATE/
ATTORNEY ATTORNEY JUDGE OFFICE
CONFERENCE CONFERENCE C1069
L1 L1 L1 L1 C1062
X1 L1B C1075 L1B C1074 b b a a A1 A2 A2 L1B L1B L1B L1B

A NEW
B1 B1 B1 B1
L1E-1 3 WG
OC
WG OC
VIDEO K1H-7
OC WG OC WG OC a,b a,b KITCHEN STAFF K1H-7
ARRAIGNMENT
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

E1HB-15 E1HB-15 WG WG b TOILET DRY


D,OS C1059
E1HB-15 C1070 E1HB-15 OC D L1B C1061 STORAGE
B1 L1 L1 L1 E1HB-15
E1HB-15 OS B1 F1 KEY PLAN
L1 EM C1064
N.L. b b a ATTORNEY L1B K1H-7 K1H-7
L2 WG L2 b a L2E-3 L1B L1B
L1E-1 OC 265606 A2 C1068 A2
E1HB-15 EM D b K3L F1 F1
VIDEO L2E-3 E1HB-15 M1 * E1HA-9 DRYER E1HA-9
M1 M1 3
SECURE ARRAIGNMENT L1 b CHASE
a a N
CORRIDOR WAITING D,OS WG WG
L1 L1 OC OC WG OC C1065B
E1012 c A1 E1HB-15 K1H-7 K1H-7 F1
C1073 d L1 K1H-7 3
D L1B L1B L1B L1B K1H-7
C2 L2 EM c OC a
s VIDEOL2E-3 PASSAGE INMATE a LAUNDRY
EM d E1HB-15 WG
WG OC WG ARRAIGNMENT c,d TOILET WG C1065
C D 265608 C1067 E1HA-9
E1HB-15 E1HB-15 OC WAITING OC WG M1A E1HA-9 M1
C1060 OC M1 OC
J C
J

C E1HB-15 E1HB-15 M1 M1 M1 a
J C1072 VIDEO L1B a
265608 TRASH a a a
ARRAIGNMENT EM L1B
265608
L1B L1B
A B C
C1071 A1 C1066 L1B L2E-3
C2 C2 L2
L1 L1 L1 EM
s 265617
N.L. 3 X1 d c L2E-3 X2 X1
9/25/2019 5:26:21 PM

L2E-3 L2E-2 OC
L2E-2
AA1
X1 X1 EM
L2E-2 B1 B1 B1 L2E-2 B1 X1 L1
+12'-0"
C2 C2 B1 N.L. B1 B1 N.L. B1 B1 N.L. B1 B1 N.L. L2E-3 N.L. X1

E-301-C
AFG

DRAWING NUMBER
s s s L2E-3 s s L2E-3 s s L2E-3 s s L2E-3 L2E-3 L2E-3 L1H-11

ELECTRICAL
265673
D E
1 FIRST FLOOR LIGHTING - AREA 'C'
E-301-C SCALE: 1/8" = 1'-0"
NORTH
GENERAL NOTES
A. FOR LIGHTING FIXTURE SCHEDULE, SEE SHEET E-606. REFER TO
REMARKS COLUMN ON LIGHTING FIXTURE SCHEDULE FOR
FIXTURE MOUNTING HEIGHTS AND REQUIREMENTS U.O.N ON THIS
DRAWING.

DLZ INDIANA, LLC


B. FOR OCCUPANCY SENSOR WIRING DETAIL, SEE DETAIL #6/E-802.

C. CONDUITS SHALL NOT BE ROUTED ALONG BUILDING EXTERIOR.


CONCEAL BY ROUTING ON INTERIOR AND PENETRATE THROUGH
WALL AT EACH EXTERIOR FIXTURE LOCATION.

D. FIELD COORDINATE, PRIOR TO CONSTRUCTION, EXACT MOUNTING


HEIGHT OF ALL FIXTURES TO AVOID DUCTWORK AND EQUIPMENT.

5 6 7 8 9 E. FOR EXTERIOR LIGHTING WIRING DIAGRAM, SEE DRAWING E-807.

F. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND


CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
AA1 RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
EM X1 X1
AND OFFSET BACK TO BACK BOXES.
+12'-0" B1 L2E-1 B1 B1 B1 L1E-1
X1
AFG L1 N.L. B1 B1 N.L. B1 B1 N.L. SECURE B1 B1 N.L. B1 C2 C2
L1E-1 G. CEILING MOUNTED OCCUPANCY SENSORS SHALL BE MOUNTED IN
L1H-11 N.L. L1E-1 s s L1E-1 s s L1E-1 CORRIDOR s s L1E-1 s s SECURE s CENTER OF CEILING TILE U.O.N. COORDINATE EXACT LOCATIONS
X1 L1E-1 CORRIDOR
265673 D1012 INMATE BEFORE ROUGH-IN.
265680 L1E-1 INTERLOCK 3 D1012 X1
TOILET
265681 L2E-1 H. OCCUPANCY SENSORS ARE SHOWN FOR PURPOSES OF
D1013 D1014 IDENTIFYING ROOMS/AREAS WHERE REQUIRED. COORDINATE
STORAGE
X2 L2 D1005B IT 3 WITH MANUFACTURER ON QUANTITY AND LOCATIONS REQUIRED
X1 WG WG X1 WG WG
R1 L2E-1 WG E5H-12 F1 R1 X2 FOR COMPLETE COVERAGE. R
EE
L2E-1 OC E5H-12 E5H-12 OC 265608 J D1010 L2E-1 E5H-12 E5H-12 CK IN
+8'-0" E5H-12 E5H-12 J1 +8'-0" L2E-2 CO

SS D I A N G
B1 M1N OC M1 OC
M1N

I ON A L E N
I. PROVIDE POWER PACKS AS REQUIRED FOR OCCUPANCY

PE60018676
D

H
265718

A
AFF AFF,

STATE OF
OC c OC L1

L . H I TC
B1

E
STORAGE SENSORS. POWER PACKS ARE NOT SHOWN. FIELD COORDINATE

I ST ER
E4H-17 JANITOR WG a OS d EM.
TOILET / L1 M1 LOCATIONS AND RECORD ON ELECTRICAL RECORD DRAWINGS.

No.
REFER TO DRAWING E-302-D FOR TOILET / E5H-12 D1012A L2E-1
M1 D1004 M1 SHOWER EM
c SHOWER a
N2N ADDITIONAL LIGHTING IN THIS ROOM AREA L2E-1

EG
WG OC J. CROSS HATCHED/SHADED FIXTURES = FIXTURES POWERED VIA

IN
D1007 D1008 Sim

IN
E5H-9 a OCCONFERENCE N2N
R
E5H-12 B1 d 4 EMERGENCY BACKUP GENERATOR FOR EMERGENCY EGRESS. RV
M1A-SC CELL M1N-SC B1 1 E5H-12 ROOM OC _____________________
E5H-9 MA FE
1 N.L. WG
E5H-7 D1126 E5H-7 N.L. INDOOR/OUTDOOR D1009
E-807
K. EM = EMERGENCY EGRESS FIXTURE. N.L. = NIGHT LIGHT P RO
CLASSROOM L2E-1 E5H-12
R1 265601 L2E-1 RECREATION a TYP. FOR ALL
L1 OC L1D1006 L1 M1N-SC CELL M1A-SC R1
+8'-0" D1005 *D FIXTURES BELOW L. WHERE SWITCH CIRCUIT IS NOT INDICATED, ALL FIXTURES IN
b b b b E5H-7 D1021 E5H-7 +8'-0"
AFF, L1 GRATING ROOM OR AREA SHALL BE ON SAME SWITCH CIRCUIT
EM E5H-12 AFF
B1 a CONTROLLED BY LIGHTING CONTROL DEVICE INDICATED IN SPACE.
L2E-1 M1A-SC M1N-SC 265606 265601 E4H-17
CELL c B1
E5H-7 E5H-7 3 3 M. SEAL ALL PENETRATIONS THROUGH PRECAST, REFER TO
D1125 INTERLOCK d
CHASE SPECIFICATION 079200 FOR TYPE.
265601 D1003 L1 L1
D1015A L1 INTERLOCK
b 265608 b N. REFER TO DRAWING E-302-E FOR LIGHTING CONTROL NOTES.
b D1011
B1 J c
EM M1N-SC CELL M1A-SC
R1 M1A-SC M1N-SC c B1
CELL 3 L2E-1 E5H-7 D1022 E5H-7 R1
+8'-0" E5H-7 E5H-7 d
D1124 +8'-0"
AFF AFF
265601
AA2 E4H-17 265601 L1 L1 E4H-17
OC
E4H-33 b b b B1
265673 B1 E5H-12 N.L.
265681 M1A-SC CELL M1N-SC N.L.
265655 c L2E-1
E5H-7 E5H-7 L2E-1
D1123 265604 WG OC d
265606 b OC
E5H-12 WG M1N-SC CELL M1A-SC
265601 *D
E5H-12 265655 E5H-7 D1023 E5H-7 R1
R1
+8'-0"
AFF M1A-SC CELL M1N-SC
B1
c INTERLOCK B1
d
265604
265601
+8'-0"
AFF,
LIGHTING KEYNOTES 265###

E4H-17 E5H-7 D1001A C2 C2


X1
EM.
E5H-7 X1 b b 1-A L2E-1
D1122 1-K L2E-1 265601 (TYPICAL) ALL CELLS, TOILETS & SHOWERS WILL HAVE LIGHTING
L2E-1 D1020 FIXTURE(S) SUPPLIED BY CELL MANUFACTURER AND BE
D1120 265615
C2 C2 CONNECTED BY DIV. 26. FIXTURE SHALL BE 277V AND BE
REFER TO DRAWING E-302-D FOR b b REFER TO DRAWING E-302-D FOR CONTROLLED THROUGH THE UTILITY CONTROL PANELS.
265726 265615 ADDITIONAL LIGHTING IN THIS ROOM AREA CELL ADA
ADDITIONAL LIGHTING IN THIS ROOM AREA EM EM M1N-SC M1A-SC 265604 LIGHTING IN ROOM/AREA TO BE CONTROLLED BY UTILITY
CELL ADA D1024 E5H-7
M1A-SC M1N-SC L2E-1 B1 B1 L2E-1 E5H-7 CONTROL PANEL, REFER TO LIGHTING CONTROLS NOTE ON
D1121 E5H-7 g a INTERLOCK
R1 R1 E5H-7 E5H-12 a R1 E-302-E AND SPECIFICATIONS FOR MORE INFORMATION.
+7'-0" +8'-0" E5H-12 EM D1002A
265606 ab 265601 +8'-0" 265606 (TYPICAL) PROVIDE WALLBOX DIMMER(S) FOR 277V LED
AFF AFF C2 L2E-1
265601 N2N (TYP.2) DD N2N AFF DRIVERS, SLIDER WITH POSITIVE OFF. DIMMER SHALL BE
E5H-12 E4H-17 b C2
C1 E5H-9 E5H-9 E4H-17 PROVIDED PER LIGHT FIXTURE MANUFACTURERS
B1 1 CONTROL B1 b
265608 RECOMMENDATION FOR PROPER DIMMING OF LED FIXTURE(S).
OS X2 X1 a a
D1000 X2 265608 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
E5H-12 L2E-1 L2E-1 J c
M1A-SC CELL M1N-SC N2N REFER TO DRAWING E-302-D FOR N2N CELL L2E-1 MODULE LIKE LVS, INC #EPC-1 OR APPROVED EQUAL IN
M1N-SC M1A-SC CHASE
R1 E4H-15 E4H-15 E4H-9 ADDITIONAL LIGHTING IN THIS ROOM AREA C2 E4H-7 ROOM/AREA FOR CONTROL OF EMERGENCY LIGHT(S).
D1112 E4H-15 D1031 E4H-15 E1016
+7'-0" V1 J1 1-J b B1 B1 1-B NON-EMERGENCY CIRCUIT SHALL BE SAME CIRCUIT AS REST OF
AFF g 3 265604 EM a 265601
+8'-0" 265601 D1110 265615 a D1030 ROOM LIGHTING. REFERENCE DETAIL #7 ON SHEET E-802.
E5H-12 265655 L2E-1 EM C2 R1 MODULE TO BE FLUSH MOUNTED AS INDICATED. RECORD EXACT
AFF,
INTERLOCK L2E-1 b REFER TO DRAWING E-302-D FOR +8'-0" LOCATION ON RECORD DRAWINGS. MODULE TO CONTROL
N.L.
265727 ADDITIONAL LIGHTING IN THIS ROOM AREA AFF FIXTURES IN AREA U.O.N. WITH DOTTED LINE.
L2E-1 D1001B C2 265655 CELL ADA
M1A-SCCELL ADA M1N-SC b 265615 M1N-SC M1A-SC E4H-17
265604 265615 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER CONTROL
E4H-15 D1111 E4H-15 C2 X1 E4H-15 D1032 E4H-15 CHASE
MODULE LOCATED IN CONTROL #D1000.
b L2E-1 E1016
C2 265655 FOR WALL MOUNT FIXTURES UNDER GRATED CATWALK, REFER
265601 N2N b EM N2N 265601 TO DETAIL 4 ON E-807 FOR MOUNTING DETAILS.
2 LOWER LEVEL LIGHTING - AREA 'D' E4H-9 L2E-1 E4H-7
INTERLOCK 265673 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
E-301-D SCALE: 1/8" = 1'-0" PHOTOCELL. REFER TO DETAIL #6 ON SHEET E-807. CONTROL
R1 D1002B R1
N2N N2N VIA CONTACTOR #LC4A.
NORTH +8'-0" +8'-0"
AFF E4H-9 E4H-7 AFF, 265680 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER CONTROL
M1A-SC CELL ADAM1N-SC MODULE LOCATED IN STORAGE #E1016B.
AA2 E4H-17 M1N-SCCELL ADA M1A-SC EM.
E4H-15 D1093 E4H-15 1-C

09/12/19
09/26/19
1-H E4H-15 D1041 E4H-15 L2E-1 265681 CONNECT TO CIRCUIT SHOWN USING 2#10+#10G. IN 3/4"C.

DATE
E4H-33 3
D1090 D1040
265673 265718 FURNISH AND INSTALL MULLION MOUNT SWITCH, ROUTE WIRING
265681 265601 REFER TO DRAWING E-302-D FOR 265601 THROUGH MULLION.
REFER TO DRAWING E-302-D FOR ADDITIONAL LIGHTING IN THIS ROOM AREA 265726 TOGGLE SWITCH FOR CONTROL OF LOWER LEVEL FIXTURE, SEE
ADDITIONAL LIGHTING IN THIS ROOM AREA DETAIL 2 THIS SHEET.
265604 265727 LIGHT FIXTURE CONTROLLED ON/OFF BY TOGGLE SWITCH AT
R1 265655 R1 TOP OF STAIRS, SEE DETAIL 1 THIS SHEET.
+8'-0" M1N-SC +8'-0"
M1A-SC CELL 265604

REVISION
AFF E4H-15 265655 M1N-SC CELL M1A-SC AFF
E4H-15 D1092
E4H-17 E4H-15 D1042 E4H-15 E4H-17

1 Addendum #01
3 Addendum #03
1-G 1-F 1-E 1-D 265601
265601
D1080 D1070 D1060 D1050
REFER TO DRAWING E-302-D FOR REFER TO DRAWING E-302-D REFER TO DRAWING E-302-D
REFER TO DRAWING E-302-D FOR
ADDITIONAL LIGHTING IN THIS ROOM AREA FOR ADDITIONAL LIGHTING IN FOR ADDITIONAL LIGHTING IN
ADDITIONAL LIGHTING IN THIS ROOM AREA
R1 THIS ROOM AREA THIS ROOM AREA R1
M1A-SC CELL M1N-SC

NO.
+8'-0" M1N-SC CELL M1A-SC +8'-0"
AFF E4H-15 D1091 E4H-15
E4H-15 D1043 E4H-15 AFF
E4H-17 E4H-17
265601 N2N N2N 265601
E4H-9 E4H-7

CHK'D: MLH

SEPTEMBER 5, 2019
N2N
N2N

1663-1190-90
E4H-7
E4H-9 R1
R1 +8'-0"

DESIGNED: MHK,RDW
+8'-0" N2N AFF,

DRAWN: MHK,RDW

PROJECT NUMBER
AFF, E4H-9 N2N EM.

MLH
EM N2N N2N N2N N2N N2N E4H-7 L2E-1
265604 265604 N2N
L2E-1 E4H-9 E4H-8 E4H-8 265604 E4H-8 E4H-7
265655 265655 E4H-8 265604
265655 STORAGE

APPRV'D:
265655 E1016B
N2

DATE:
R1
+8'-0"
AFF M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC
R1
E4H-17 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15
R1 WG +8'-0"

FIRST FLOOR AND LOWER LEVEL LIGHTING PLANS


+8'-0" E4H-7 AFF
AFF CELL OC E4H-17
CELL CELL CELL CELL ADA CELL ADA CELL CELL CELL ADA CELL ADA CELL CELL
AA2 E4H-17 CHASE D1051

VIGO COUNTY SECURITY CENTER


E4H-33 D1084 D1083 D1082 D1081 D1072 D1071 D1062 D1061 D1054 D1053 D1052 INTERLOCK
D1015B 265601 265601 265601 265601 265601 265601 265601 265601 265601 265601 265601 265601
265673 D1016
M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC M1A-SC
265681
E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15 E4H-15
N2 R1
R1 N.L. +8'-0"
+8'-0" L2E-1 AFF
AFF R1 R1 R1 R1 E4H-17
E4H-17 +8'-0" R1 R1 R1 +8'-0" R1 R1 R1 +8'-0" R1 R1 R1 +8'-0" R1
AFF, +8'-0" +8'-0" +8'-0" AFF, +8'-0" +8'-0" X2 +8'-0" AFF, +8'-0" +8'-0" +8'-0" AFF, X2 +8'-0"
X2 X1
X2 L2E-1EM AFF AFF AFF EM AFF AFF L2E-1 AFF EM AFF AFF AFF EM L2E-1 AFF
E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 L2E-1 E4H-17
L2E-1 L2E-1 L2E-1 L2E-1 L2E-1

TERRE HAUTE, INDIANA


265681 265673 265681 265673 265681 265673 265673
AA2 AA2 AA2 265680 AA2

- AREA D
E4H-33 E4H-33 E4H-33 265681 EM
L1H-11

A NEW
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

1 FIRST FLOOR LIGHTING - AREA 'D'


E-301-D SCALE: 1/8" = 1'-0"
KEY PLAN
NORTH

A B C
9/25/2019 5:26:49 PM

E-301-D
DRAWING NUMBER

ELECTRICAL
D E
GENERAL NOTES
A. FOR LIGHTING FIXTURE SCHEDULE, SEE SHEET E-606. REFER TO
REMARKS COLUMN ON LIGHTING FIXTURE SCHEDULE FOR
FIXTURE MOUNTING HEIGHTS AND REQUIREMENTS U.O.N ON THIS
DRAWING.

B. FOR OCCUPANCY SENSOR WIRING DETAIL, SEE DETAIL #6/E-802.

DLZ INDIANA, LLC


C. CONDUITS SHALL NOT BE ROUTED ALONG BUILDING EXTERIOR.
CONCEAL BY ROUTING ON INTERIOR AND PENETRATE THROUGH
WALL AT EACH EXTERIOR FIXTURE LOCATION.

D. FIELD COORDINATE, PRIOR TO CONSTRUCTION, EXACT MOUNTING


HEIGHT OF ALL FIXTURES TO AVOID DUCTWORK AND EQUIPMENT.

E. FOR EXTERIOR LIGHTING WIRING DIAGRAM, SEE DRAWING E-807.

F. REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND


18 19 CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
X1 AND OFFSET BACK TO BACK BOXES.
OC
L2E-2
AA1 G. CEILING MOUNTED OCCUPANCY SENSORS SHALL BE MOUNTED IN
X1 X1 EM CENTER OF CEILING TILE U.O.N. COORDINATE EXACT LOCATIONS
L2E-2 B1 B1 B1 L2E-2 B1 X1 L1 BEFORE ROUGH-IN.
+12'-0"
C2 C2 B1 N.L. B1 B1 N.L. B1 B1 N.L. B1 B1 N.L. L2E-3 N.L. X1 AFG
s SECURE s s L2E-3 s s L2E-3 s s L2E-3 s s L2E-3 L2E-3 L2E-3 L1H-11 H. OCCUPANCY SENSORS ARE SHOWN FOR PURPOSES OF
CORRIDOR IDENTIFYING ROOMS/AREAS WHERE REQUIRED. COORDINATE
SECURE 265673
E1012 WITH MANUFACTURER ON QUANTITY AND LOCATIONS REQUIRED
CORRIDOR INTERLOCK 265680 FOR COMPLETE COVERAGE. R
E1012 265681 EE
E1013 CK IN
3 CO

SS D I A N G
I. PROVIDE POWER PACKS AS REQUIRED FOR OCCUPANCY

I ON A L E N
PE60018676
D

A
STATE OF
3 SENSORS. POWER PACKS ARE NOT SHOWN. FIELD COORDINATE

L . H I TC

E
X1 IT WG WG L2 X1 X2

I ST ER
X2 F1
L2E-2 J 265608 OC E5H-11 E5H-11 OC STORAGE E5H-11 L2E-2 WG L2E-2 R1 LOCATIONS AND RECORD ON ELECTRICAL RECORD DRAWINGS.

No.
L2E-2 E1004 J1 E5H-11
B1 L1 L1 M1N E1009B B1 E5H-11 +8'-0"
265718 M1N J. CROSS HATCHED/SHADED FIXTURES = FIXTURES POWERED VIA

EG
OC d OC AFF

IN
c a a

IN
R1 OS TOILET / WG JANITORM1 E4H-17 EMERGENCY BACKUP GENERATOR FOR EMERGENCY EGRESS. R
TOILET / RV
+8'-0" E5H-11 SHOWER N2N M1 MA FE
SHOWER E1011
AFF E5H-10 K. EM = EMERGENCY EGRESS FIXTURE. N.L. = NIGHT LIGHT P RO
CONFERENCE E1006 E1007 2 B1
E4H-17 N2N Sim B1
4 N.L. ROOM OC a INDOOR/OUTDOOR N.L. L. WHERE SWITCH CIRCUIT IS NOT INDICATED, ALL FIXTURES IN
E5H-10 M1N-SC CELL M1N-SC
_____________________

L2E-2 E1005 E5H-11 RECREATION L2E-2 ROOM OR AREA SHALL BE ON SAME SWITCH CIRCUIT
E-807 E5H-8 E1021 E5H-8
E1009 CONTROLLED BY LIGHTING CONTROL DEVICE INDICATED IN SPACE.
TYP. FOR ALL c OC L1 L1 L1 L1 OC d R1
M1A-SC CELL M1N-SC WG 265606 a WG 265601
FIXTURES BELOW a b b b +8'-0" M. SEAL ALL PENETRATIONS THROUGH PRECAST, REFER TO
E5H-8 E1124 E5H-8 E5H-11 *D REFER TO DRAWING E5H-11
GRATING OC 3 AFF, SPECIFICATION 079200 FOR TYPE.
b E-302-E FOR ADDITIONAL 3 EM
B1 2 LIGHTING IN THIS B1
265601 E5H-11 L2E-2
c d M1N-SC CELL M1N-SC N. REFER TO DRAWING E-302-E FOR LIGHTING CONTROL NOTES.
CLASSROOM ROOM/AREA
E5H-8 E1022 E5H-8
3 INTERLOCK E1008 INTERLOCK
L1 L1 265601
E1003 b L1 J b E1010
b 265608 CHASE
M1A-SC CELL M1N-SC B1 EM B1
E1014A
E5H-8 L2E-2 d M1N-SC CELL M1N-SC R1
E1123 E5H-8 c
E5H-8 E1023 E5H-8 +8'-0"
AFF
265601 L1 L1 265601 E4H-17 AA2
B1 b
OC
b b B1 E4H-33
N.L. E5H-11 N.L.
265604 265673
L2E-2 L2E-2
265655 M1N-SC CELL M1N-SC 265681
c OC d E5H-8 E1024 E5H-8
WG OC 265606 WG
M1A-SC CELL M1N-SC

b
*D
E5H-11
E5H-8 E1122 E5H-8
2-A B1 B1
E5H-11 265601
R1
+8'-0"
LIGHTING KEYNOTES 265###
265604 d
265601 E1120 c C2 AFF
265655 C2 2-K M1N-SC CELL M1N-SC 265601 (TYPICAL) ALL CELLS, TOILETS & SHOWERS WILL HAVE
X1 b b E4H-17
REFER TO DRAWING E-302-E FOR ADDITIONAL 265616 X1 E1020 E5H-8 E1025 E5H-8 LIGHTING FIXTURE(S) SUPPLIED BY CELL MANUFACTURER AND
L2E-2 BE CONNECTED BY DIV. 26. FIXTURE SHALL BE 277V AND BE
LIGHTING IN THIS ROOM/AREA 265616 L2E-2 265601
C2 C2 REFER TO DRAWING E-302-E FOR ADDITIONAL CONTROLLED THROUGH THE UTILITY CONTROL PANELS.
ADA CELL b b LIGHTING IN THIS ROOM/AREA 265604 LIGHTING IN ROOM/AREA TO BE CONTROLLED BY UTILITY
N.L. 3 265726 N.L. J1
M1A-SC E1121 M1N-SC CONTROL PANEL, REFER TO LIGHTING CONTROLS NOTE ON
L2E-2 B1 B1 L2E-2 INTERLOCK CELL ADA +8'-0" E4PB E-302-E AND SPECIFICATIONS FOR MORE INFORMATION.
E5H-8 E5H-8 g M1N-SC E1026 M1N-SC
INTERLOCK a a E1001A AFF,
R1 EM E5H-11b E5H-11 E5H-8 E5H-8 265606 (TYPICAL) PROVIDE WALLBOX DIMMER(S) FOR 277V LED
E1002A N.L.
+7'-0" L2E-2 a 265606 DRIVERS, SLIDER WITH POSITIVE OFF. DIMMER SHALL BE
265601 DD C2 E4H-17
C1 AFF N2N (TYP.2) 265601 3 PROVIDED PER LIGHT FIXTURE MANUFACTURERS
C2 b N2N SQE#10
E5H-11 E5H-10 RECOMMENDATION FOR PROPER DIMMING OF LED FIXTURE(S).
b B1 B1 E5H-10 U1R-41
265608 X1 265608 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
OS a a
1 CONTROL C J L2E-2 X2 MODULE LIKE LVS, INC #EPC-1 OR APPROVED EQUAL IN
E5H-11 N2N N2N
R1 E1000 M1N-SC CELL M1N-SC L2E-2 ROOM/AREA FOR CONTROL OF EMERGENCY LIGHT(S).
CHASE M1A-SC CELL M1N-SC 265616 REFER TO DRAWING E-302-E FOR ADDITIONAL E4H-11
+7'-0" E4H-13 NON-EMERGENCY CIRCUIT SHALL BE SAME CIRCUIT AS REST
E1016 E4H-14 E1112 E4H-14 C2 LIGHTING IN THIS ROOM/AREA E4H-14 E4H-14
V1 AFF B1 B1 E1031 OF ROOM LIGHTING. REFERENCE DETAIL #7 ON SHEET E-802.
265601 265604 2-B b
g E5H-11 a a 265604 265601 R1 MODULE TO BE FLUSH MOUNTED AS INDICATED. RECORD
3 265655 C2 N.L. 2-J EXACT LOCATION ON RECORD DRAWINGS. MODULE TO
E1110 X1 EM 265655 +8'-0"
b L2E-2 CONTROL FIXTURES IN AREA U.O.N. WITH DOTTED LINE.
L2E-2 E1030 AFF,
265727 REFER TO DRAWING E-302-E FOR ADDITIONAL L2E-2 INTERLOCK
LIGHTING IN THIS ROOM/AREA C2 CELL ADA EM 265616 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER
M1A-SCCELL ADA M1N-SC C2 E1001B M1N-SC M1N-SC L2E-2 CONTROL MODULE LOCATED IN CONTROL #E1000.
265616 b E4H-14 E1032 E4H-14
E4H-14 E1111 E4H-14 b 265655 FOR WALL MOUNT FIXTURES UNDER GRATED CATWALK, REFER
N.L. TO DETAIL 4 ON E-807 FOR MOUNTING DETAILS.
265601 N2N L2E-2 C2
N2N 265601 265664 EXTERIOR TYPE 'SF' LIGHTING FIXTURES SHALL BE MANUALLY
2 LOWER LEVEL LIGHTING - AREA 'E' E4H-13 INTERLOCK b
E4H-11 SWITCHED FROM LOCAL TOGGLE LIGHT SWITCH; FIXTURES
E-301-E SCALE: 1/8" = 1'-0" E1002B SHALL ALSO BE CONTROLLED VIA LIGHTING CONTACTOR FOR
R1 DUSK-TO-DAWN CONTROL. PROVIDE LABEL ON TOGGLE

09/12/19
09/26/19
NORTH N2N

DATE
2-H N2N CELL ADA +8'-0" SWITCH FACEPLATE IDENTIFYING EXTERIOR LIGHTING ALSO
E4H-13 E4H-11
M1N-SC E1041 M1N-SC AFF INTERLOCKED/CONTROLLED VIA LIGHTING CONTACTOR. YARD
M1A-SCCELL ADA M1N-SC 2-C E1040
E4H-14 E4H-14 E4H-17 AA2 IS NOT NORMALLY OCCUPIED BY INMATES EXCEPT FOR AN
E4H-14 E1093 E4H-14 E1090 E4H-33 EMERGENCY EVACUATION.
REFER TO DRAWING E-302-E FOR ADDITIONAL
REFER TO DRAWING E-302-E FOR ADDITIONAL LIGHTING IN THIS ROOM/AREA 265673 265673 FIXTURE TO BE CONTROLLED ON/OFF VIA TIMECLOCK AND
265601 LIGHTING IN THIS ROOM/AREA 265601 265681 PHOTOCELL. REFER TO DETAIL #6 ON SHEET E-807. CONTROL
VIA CONTACTOR #LC4A.
265677 LIGHTING CONTACTORS, LC4A-LC4D, REFER TO EXTERIOR

REVISION
LIGHTING WIRING DIAGRAM, SHEET E-807, DETAIL #6.
R1
2-G +8'-0" 265678 NEW TIME CLOCK #TC4 FOR CONTROL OF EXTERIOR LIGHTING,

1 Addendum #01
3 Addendum #03
265604
M1A-SC CELL M1N-SC 2-D 2-E 2-F E1050 265604 M1N-SC CELL M1N-SC AFF REFER TO EXTERIOR LIGHTING WIRING DIAGRAM, SHEET E-807,
265655 DETAIL #6. CONNECT TO CIRCUIT E4PA-42 USING 2#12+G. IN
E4H-14 E1092 E4H-14 E1080 E1070 E1060 265655 E4H-14 E1042 E4H-14 E4H-17
REFER TO DRAWING 3/4"C.
265601 REFER TO DRAWING
REFER TO DRAWING REFER TO DRAWING E-302-E FOR ADDITIONAL 265679 FURNISH AND INSTALL (1) EMERGENCY POWER CONTROL (ECP)
E-302-E FOR ADDITIONAL 265601
E-302-E FOR ADDITIONAL E-302-E FOR ADDITIONAL LIGHTING IN THIS MODULE #GTD4, LIKE LVS INC #EPC-1 OR APPROVED EQUAL IN
LIGHTING IN THIS WALL FOR CONTROL OF EXTERIOR EMERGENCY LIGHT.
LIGHTING IN THIS LIGHTING IN THIS ROOM/AREA
ROOM/AREA

NO.
ROOM/AREA ROOM/AREA NON-EMERGENCY CIRCUIT SHALL BE CIRCUIT E4H-33.
REFERENCE DETAIL #7 ON SHEET E-802. MODULE TO BE FLUSH
R1 MOUNTED AS INDICATED. RECORD EXACT LOCATION ON
M1A-SC CELL M1N-SC M1N-SC CELL M1N-SC +8'-0" RECORD DRAWINGS.
E4H-14 E1091 E4H-14 E4H-14 E1043 E4H-14 AFF 265680 FIXTURE TO BE CONTROLLED BY EMERGENCY POWER

CHK'D: MLH
E4H-17 CONTROL MODULE LOCATED IN STORAGE #E1016B.

SEPTEMBER 5, 2019
265601 N2N N2N 265681 CONNECT TO CIRCUIT SHOWN USING 2#10+#10G. IN 3/4"C.

1663-1190-90
E4H-13 265601
E4H-11 265718 FURNISH AND INSTALL MULLION MOUNT SWITCH, ROUTE

DESIGNED: MHK,RDW
N2N N2N WIRING THROUGH MULLION.

DRAWN: MHK,RDW

PROJECT NUMBER
R1 E4H-13 E4H-11 265726 TOGGLE SWITCH FOR CONTROL OF LOWER LEVEL FIXTURE,
SQE#9b SEE DETAIL 2 THIS SHEET.

MLH
+8'-0"
U1R-39 R1
AFF E4H N2N 265604 265727 LIGHT FIXTURE CONTROLLED ON/OFF BY TOGGLE SWITCH AT
N2N +8'-0"
E4H-17 E4H-13 265655 TOP OF STAIRS, SEE DETAIL 1 THIS SHEET.
265604 E4H-11 AFF,

APPRV'D:
265604 265604
265655 N2N N2N 265655 N2N N2N 265655 N2N N2N EM

DATE:
E4PA E4H-13 E4H-12 E4H-12 E4H-12 E4H-12 E4H-11 L2E-2
SQE#9a
U1R-37 N2 R1
265664 YY +8'-0"

FIRST FLOOR AND LOWER LEVEL LIGHTING PLANS


ZZ M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC AFF
R1 265677 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-17
+8'-0" 265678 R1

VIGO COUNTY SECURITY CENTER


AFF +8'-0"
E4H-17 J OC CELL CELL CELL CELL ADA CELL ADA CELL CELL CELL ADA CELL ADA CELL CELL CELL
AFF
W WG E1084 E1083 E1082 E1081 E1072 E1071 E1062 E1061 E1054 E1053 E1052 E1051 E4H-17 AA2
265679 E4H-13 E4H-33
265601 265601 265601 265601 265601 265601 265601 265601 265601 265601 265601 265601
INTERLOCK M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC M1N-SC 265673
E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 E4H-14 265681
E1017
R1
R1
+8'-0" N2
CHASE +8'-0"
AFF, N.L.
E1014B AFF
EM. L2E-2
E4H-17
L2E-2 R1 R1 R1 R1
R1 +8'-0" R1 R1 R1 +8'-0" R1 R1 R1 +8'-0" R1 R1 R1 X2
+8'-0"

TERRE HAUTE, INDIANA


X2 +8'-0" +8'-0" +8'-0" +8'-0" X2 +8'-0" CHASE +8'-0" +8'-0" +8'-0" +8'-0"
+8'-0" AFF, AFF, AFF, AFF,
X1 L2E-2 EM AFF AFF AFF AFF L2E-2 AFF E1014C AFF AFF AFF AFF
AFF EM EM EM X2
L2E-2 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17 E4H-17
E4H-17 L2E-2 L2E-2 L2E-2 L2E-2 L2E-2

- AREA E
A NEW
265681 265673 265681 265673 265681 265673
AA2 AA2 AA2
E4H-33 E4H-33 E4H-33
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

1 FIRST FLOOR LIGHTING - AREA 'E' KEY PLAN


E-301-E SCALE: 1/8" = 1'-0"
NORTH

A B C
9/25/2019 5:27:13 PM

DRAWING NUMBER

E-301-E

ELECTRICAL
D E
14
12 12.7 2705##
GENERAL NOTES A
SYSTEMS KEYNOTES 2805##
13
A. REFER TO DRAWING E-803, DETAIL #10 FOR FIRE ALARM DEVICES G. PROPOSED WAP LOCATIONS AND QUANTITY SHOWN ARE SCHEMATIC H. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO SPECIFICATION 079200
MOUNTING REQUIREMENTS PER NFPA. ONLY. WAP VENDOR SHALL PROVIDE EXACT LOCATIONS AND QUANTITY OF FOR TYPE. 270502 NEW 4-GANG FLOOR BOX, REFER TO KEYNOTE #260521 OR
WIRELESS ACCESS POINTS. WP #260527 ON DRAWING #E-201-C. FURNISH AND INSTALL (1)
B. CONTRACTOR SHALL COORDINATE ALL DEVICE HEIGHTS AND EXACT I. SEE DRAWING E-607, DETAIL #1 FOR CATV DISTRIBUTION RISER. 280505 DATA/COMMUNICATIONS OUTLET WITH SIX (6) CAT.6
LOCATIONS WITH CASEWORK SHOP DRAWINGS AND 1. FURNISH AND INSTALL SPECIFICATION GRADE, POWER OVER ETHERNET, F JACKS/CABLES. ROUTE (1)-1-1/4"C. AS SHOWN FROM BOX OVER

DLZ INDIANA, LLC


ARCHITECTURAL ELEVATION DRAWINGS. WIRELESS ACCESS POINT (WAP) ROUTERS FOR COMPLETE COVERAGE OF J. DRY FIRE SUPPRESSION TO BE INSTALLED IN ELECTRICAL AND IT ROOMS AND UP WALL TO NEAREST CABLE TRAY FOR CABLING.
BUILDING; QUANTITY AND LOCATION TO BE DETERMINED BY WAP VENDOR (REFER TO FIRE SUPPRESSION SERIES DRAWINGS). DRY FIRE 270513 270503 FURNISH AND INSTALL (1)-2"C. FROM BELOW COUNTER AREA

F
C. ALL FIRE ALARM CONDUITS SHALL BE FACTORY PAINTED "RED". ALL USING PREDICTIVE ANALYSIS SOFTWARE. SUPPRESSION ALARM/DETECTION CABINET(S) SHALL BE CONNECTED TO HD B OVER TO CHASE AND STUBBED OUT AT +12" A.F.F. FOR FUTURE
PULL/JUNCTION BOX COVERS SHALL BE FACTORY PAINTED RED. THE FIRE ALARM CONTROL PANEL. CABINET(S) ARE NOT INDICATED ON FAAP-1 +84" COMMUNICATIONS CABLING. FURNISH WITH PULLSTRING.
2. ROUTER MANUFACTURERS SHALL BE BY NETGEAR, RUCKUS OR CISCO. THIS DRAWING (FIELD COORDINATE CABINET LOCATIONS PRIOR TO KIOSK 280504 TV 270506 TELEPHONE TERMINAL BOARD 'TTB-1'. FURNISH AND INSTALL 4' X
PROVIDE WITH NETWORK MANAGEMENT SOFTWARE. WAP VENDOR SHALL

F
D. FOR MUTOA BACKBOX AND IN-WALL SLEEVE DETAIL, SEE DETAIL #10 CONSTRUCTION) AND INCLUDE WITH SHOP DRAWING SUBMITTAL. PROVIDE KIOSK +84" 8' X 3/4" FIRE RETARDENT PLYWOOD FOR TELEPHONE/CATV
ON DRAWING E-801. PROVIDE A PREDICTIVE ANALYSIS OF WIRELESS PERFORMANCE AND 2 #12, #12G. FROM EACH DRY SUPPRESSION ALARM/DETECTION CABINET VESTIBULE DEMARK. PAINT (2) COATS MARINE GRADE FIRE RETARDENT
WIRELESS ROUTERS. BACK TO NEAREST AVAILABLE 20A/1P BREAKER (IN A LEGALLY REQUIRED PAINT TO MATCH WALL FINISH.
B1000
E. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS AND PANELBOARD). KIOSK 270507 FURNISH AND INSTALL A 10-POINT GROUND TERMINAL STRIP ON
CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE 3. PROVIDE INDICATING PREDICTIVE TRAFFIC/USAGE AND COVERAGE
PATTERNS AS PART OF SHOP DRAWING SUBMITTAL. 8 9 10 11 TELEPHONE TERMINAL BOARD. BOND ALL COMMUNICATIONS
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS K. ROUTE VESDA SAMPLING TUBING IN CONDUIT (SIZE AS REQUIRED BY FIRE EQUIPMENT ON TELEPHONE TERMINAL BOARD TO TERMINAL
AND OFFSET BACK TO BACK BOXES. ALARM VENDOR) ABOVE INACCESSIBLE DETENTION CEILINGS. KIOSK +40" STRIP WITH #10 AWG GREEN INSULATED GROUND CABLE. REFER
4. FURNISH AND INSTALL (2) CAT 6 DATA CABLE WITH 10' OF SLACK FOR
FINAL PLACEMENT OF ROUTER HARDWARE. TO DETAIL 2 ON SHEET E-803.
F. REFER TO SECURITY DRAWINGS, #SE SERIES, AND DIVISION 28 L. SMOKE DETECTORS IN MECHANICAL CHASES (LOCATED BEHIND CELLS)
VIDEO 270508 GROUND BUS BAR NO.2. MOUNT AT +8'-0" AFF. REFER TO
SPECIFICATIONS FOR ADDITIONAL SECURITY SYSTEM ARE NOT REQUIRED FOR SMOKE EVAC SYSTEM FOR CELLS/DAYROOMS.

F
5. UNITS TO BE SURFACE MOUNTED ON BOTTOM OF PRECAST, ACOUSTICAL VISITATION F C TELE-DATA EQUIPMENT GROUND BUS DETAIL #3, SHEET E-803.
REQUIREMENTS. PROVIDE BOXES AND RACEWAYS CABLING, AND REFER TO MECHANICAL PLANS FOR SMOKE EVAC SYSTEM SEQUENCE OF
CEILING OR STRUCTURE. PROVIDE MOUNTING ACCESSORIES AS B1003 BOND TO MAIN GROUND BUS BAR NO.1 (IN location) USE #1/0AWG
ASSOCIATED ITEMS AS NECESSARY FOR A COMPLETE AND CONTROL.
REQUIRED. VV VV VV VV VV VV VV COPPER GREEN INSULATED CABLE.
FUNCTIONAL SECURITY SYSTEM. 270527
270509 #1/0 AWG GREEN INSULATED GROUND CABLE. BOND TO MAIN
6. FURNISH AND INSTALL CUSTOM COVER OVER WIRELESS ACCESS POINT GROUND BUS #1 (IN MECHANICAL #C1053). REFER TO DETAIL #4,
(WAP) ROUTERS LOCATED IN INMATE AREAS LIKE TERRAWAVE VV VV VV VV VV VV VV D DRAWING E-803.
SOLUTIONS #V10102-C-1131 OR APPROVED EQUAL. COVER SHALL BE LOBBY 270510 GROUND BUS BAR NO.3. MOUNT AT +8'-0" AFF. REFER TO
SIZED TO MATCH ROUTER AND UTILIZE TORX-HEAD CENTER PIN SCREWS. 5 6 7 B1001 TELE-DATA EQUIPMENT GROUND BUS DETAIL #3, SHEET E-803.
WAITING R
BOND TO MAIN GROUND BUS BAR NO.1 (IN location) USE #1/0AWG EE
F F B1002 COPPER GREEN INSULATED CABLE. CK IN
CO

SS D I A N G
I ON A L E N
PE60018676
GROUP D

A
STATE OF
GROUP GROUP 270511 NEW 8-GANG FLOOR BOX, REFER TO KEYNOTE #260524 ON E-201

L . H I TC

E
I ST ER
VIDEO VIDEO VIDEO SERIES DRAWINGS. FURNISH AND INSTALL (1)

No.
B1004 B1005 B1006 DATA/COMMUNICATIONS OUTLET WITH SIX (6) CAT.6
JACKS/CABLES. ROUTE (2)-1"C. FROM BOX OVER AND UP WALL

EG
PRETRIAL PRETRIAL PRETRIAL VV VV VV

IN
PRETRIAL

IN
SERVICES SERVICES SERVICES JAIL TO NEAREST CABLE TRAY FOR CABLING. R
SERVICES RV
OFFICE
OFFICE OFFICE OFFICE STORAGE 270511 270513 FURNISH AND INSTALL SPECIALTY OUTLET WITH (1) HDMI PORT MA FE
B1085 ATTORNEY F FOR INTERFACING LAPTOP/COMPUTER WITH TV IN ROOM. P RO
B1071 B1072 B1073
B1070 CONFERENCE FURNISH AND INSTALL PRE-TERMINATED HDMI BETWEEN
JANITOR LAPTOP/COMPUTER INTERFACE MUTOA AND TV INTERFACE
HD TV B1018
B1007 +88" +88" MUTOA WITH 1"C. FURNISH MATCHING HDMI PORT AT TV

F
F F F LOCATION.
F F
270522 MASTER 270515 PROVIDE SIGNAL REFERENCE GROUNDING FOR RAISED FLOOR,
COURTYARD 280501 s s PUBLIC PUBLIC CONTROL REFER TO RAISED FLOOR GROUNDING DETAIL #10 ON SHEET
CLOSET VISITATION VISITATION - *
B1135 STORAGE * CELL B1016 E-802.
B1069 CORRIDOR P PUBLIC B1011 PUBLIC ADA
B1084 * B1086 270515 270519 ATS ANNUNCIATOR PANEL 'ATS-ANN1', RECESS MOUNTED.
B1068 VISITATION VISITATION B1013 * VERIFY EXACT LOCATION WITH OWNER BEFORE ROUGH-IN.
WP 280501 *
F B1010 B1012 270522 270520 ATS ANNUNCIATOR PANEL 'ATS-ANN2', RECESS MOUNTED.
F F s 270521
WOMENS * 270520 VERIFY EXACT LOCATION WITH OWNER BEFORE ROUGH-IN.

F
TRANSPORTATION P * MENS F
*

F
280501 280501 B1008 * 270519 270521 GENERATOR ANNUNCIATOR PANEL 'GEN-ANN', RECESS
WAITING B1009 F
INTERLOCK 280520 MOUNTED. VERIFY EXACT LOCATION WITH OWNER BEFORE
CELL CELL SEX
B1062 * P ROUGH-IN.
s
F F
PRETRIAL P * P * * * * * *
HD 270513 B1067
B1087 280501 270511 RTS FAAP-2 TOILET OFFENDER
B1083 INMATE INMATE 270522 FURNISH AND INSTALL (1)-2"C. FROM BELOW WORKSTATION

F
* SERVICES B1017 REGISTRY

s
VISITATION VISITATION INMATE RTS

s
TOILET WORKROOM * ROUTED TO NEAREST WALL AND STUBBED OUT ABOVE CEILING

F
* TRANSPORTATION 280501 +40" INTERLOCK 280509
B1023 INMATE B1021 VISITATION - RTS C1002 WITH BUSHING FOR DVI CABLE BETWEEN MONITOR(S) AND
B1066 B1074

SPD-E2PB

SPD-E2PA
OFFICE * B1015 NETWORK VIDEO CLIENTS PCS. FURNISH WITH PULLSTRING.
VISITATION ADA RTS
B1064 P * COORDINATE EXACT LOCATION OF WORKSTATION.

E2PB

E2PA
F
* * * B1022 B1020
280501

s
CELL CELL 270527 ROUTE COMMUNICATIONS CABLING UP TO VIDEO VISITATION
INTERLOCK F F STATION THROUGH CABINET SUPPORT LEGS. COORDINATE WITH
* P B1082 B1088 DIS-UPS2 E2HA 270509 280501 SECURITY
B1063 s s UPS2 ELECTRICAL ATTORNEY EQUIPMENT SUPPLIER.
TOILET P * P * 280501
270513 B1024 CONFERENCE C1046 270530 NEW 4-GANG FLOOR BOX, REFER TO KEYNOTE #260521 OR
280501 TOILET TOILET 280501 280501 TR-U2
* * *,HD *,TV B1065 * P * P B1019 #260527 ON DRAWING #E-201-C. FURNISH AND INSTALL (1)

F
135° F ABOVE 280501 * 280507
* +84" +84" B1076 B1075 P TR-2A 270510 DATA/COMMUNICATIONS OUTLET WITH TWO (2) CAT.6
P

F
F F * 280501 280501 BELOW +48" ZAM JACKS/CABLES. ROUTE (1)-1"C. FROM BOX OVER AND UP WALL

s
F * P TO NEAREST CABLE TRAY FOR CABLING.
CELL U2RSPD-U2R
CELL P * P * F
270532 FURNISH AND INSTALL SPECIALTY OUTLET WITH (1) USB PORT
280501

F
B1089 WOMENS
B1081 FOR INTERFACING OWNER PROVIDED CAMERA SYSTEM WITH
CELL CELL CELL CELL 280501 280501 CELL B1026 INTERLOCK
CELL P CELL COMPUTER IN BOOKING COUNTER #B1053A. FURNISH AND
* B1091 B1041 * B1040 C1044 INSTALL PRE-TERMINATED USB CABLE BETWEEN CAMERA

s
B1077 B1078 B1079 B1092

F
P * P * * INTERFACE AND COMPUTER INTERFACE WITH 1-1/4"C. FURNISH
* * WITH MATCHING USB PORT AT COMPUTER LOCATION. VERIFY
280501 280501 EXACT LOCATION OF OUTLETS WITH OWNER BEFORE ROUGH-IN,
* 280501 280501 280501 CELL CELL
MALE MODIFY LOCATION(S) AS NEEDED PER OWNER'S WRITTEN
DETOX P B1080 * * B1090 INSTRUCTION.
P * P * P * P P P * P *
280501 * * 270576 GROUND BUS BAR NO.5. MOUNT AT +8'-0" AFF. REFER TO
B1061 280501 280501 CELL
280501 TELE-DATA EQUIPMENT GROUND BUS DETAIL #3, SHEET E-803.
* B1042 * 280501 * CELL ADA BOND TO MAIN GROUND BUS BAR NO.1 (IN location) USE #1/0AWG

s
* * B1039 * COPPER GREEN INSULATED CABLE.

F
P P * * P P * P
280501 280525 * 280501 280501 MENS 280501 REFER TO SMOKE DETECTOR DETENTION COVER DETAIL #9,
270503 270503
270513 280501 DRAWING E-801.

F
* DAYROOM B1027 270530 270530
280501 280504 FIRE ALARM ANNUNCIATOR PANEL (F.A.A.P.). PANEL TO BE
CO

280501 B1037
280501 * P 270530 270530 RECESS MOUNTED WITH TOP AT +60" A.F.F. PROVIDE
280508 MEDICAL * HD *,HD *,TV CID WORK CONNECTION PER MANUFACTURER'S RECOMMENDATION TO
* * * * *,VV
* PRE-SCREENING P P P BODY +48" +96" +96" GROUP MAIL FIRE ALARM CONTROL PANEL (FACP-1) IN ELECTRICAL
B1057 SCANNER 270513 C1040 K ROOM #C1054.
* STAFF
* B1035 *,TCS
USB TOILET 280505 FIRE ALARM HORN/STROBE TO ACTIVATE WHEN WATER IS
F

F
TESTING * 270532 *,+48"
* USB 270532 B1031 FLOWING IN SPRINKLER SYSTEM. FIELD LOCATE EXTERIOR
B1056 3 P * 280525 HORN/STROBE SO THAT IT IS READILY VISIBLE TO THE
* s 280501 s APPROACHING FIRE DEPARTMENT FROM THE PUBLIC STREET,
F

* *
F F ROAD, OR HIGHWAY AND PUBLIC ENTRY WAY. REFER TO IBC

09/12/19
09/26/19
*,TCS

DATE
280525 903.4.2 FIELD VERIFY LOCATION IS ACCEPTABLE TO AHJ PRIOR
TO CONSTRUCTION.
280501 280525 280501 HD
BOOKING 270502 270513 280507 ROOM CONTAINS SELF-CONTAINED DRY-POWDER FIRE
3 PASSAGE HD SUPPRESSION SYSTEM. PROVIDE ZAM FOR ALARM MONITORING
INTERLOCK COUNTER * P * P
B1029 +78" 270513 OF FIRE SUPPRESSION SYSTEM CONTROL PANEL BY FIRE ALARM
270507 * B1055 B1053A * TV CONTROL PANEL (FACP-1) LOCATED IN ELECTRICAL ROOM
270506 270509 +78" #C1054 AS RECOMMENDED BY SYSTEM MANUFACTURER.
270515 280525 MATRON
F F FURNISH CABLING AS REQUIRED IN 3/4"C. COORDINATE WITH
*,TCS

REVISION
F F 280501 C1080 MECHANICAL CONTRACTOR AND INSTALL/WIRE ALL ASSOCIATED
MEDICAL
ELECTRICAL APPURTENANCES AND DEVICES (I.E. SMOKE
F

270576 * PRE-SCREENING +48"

F
s s
*,+48" * * DETECTOR, PULL STATION, TELEPHONE OUTLET) TO FIRE

1 Addendum #01
3 Addendum #03
s

* P

s
B1058 * SUPPRESSION PANEL AS NECESSARY AND AS REQUIRED BY FIRE
MAIN DATA

F
280504 * SUPPRESSION SYSTEM MANUFACTURER.
*

F
FRAME TOILET JANITOR
FAAP-3 SEARCH SEARCH +48" 280507
B1060 SHOWER B1030 280508 CO AND NO2 SENSORS (FURNISHED AND INSTALLED BY OTHERS)
TOILET TOILET M
B1059 SHOWER SECURE SHALL BE MONITORED BY THE BMS (BUILDING MANAGEMENT
* 280501 280501 280501 SHOWER SECURITY
CORRIDOR ZAM SYSTEM). ALARMING TO FIRE ALARM CONTROL PANEL FOR HIGH

F
* B1034 B1033 C1079 CO OR NO2 LEVELS SHALL BE ACTIVATED BY THE BMS PANEL

NO.
P INTAKE 270503 P P B1025 (VIA BACnet COMMUNICATION/MONITORING PATHWAY BETWEEN
* * *
CENTER 270503 BMS AND FACP-1).
280501 +42" +42"
B1053 280509 REMOTE TEST STATIONS FOR AIR HANDLING UNITS IN
PENTHOUSE (FOR INTERLOCKING SHUT-DOWN INDICATION AND

F
P * * * * * * 270513 TESTING OF AIR HANDLING UNIT UPON DUCT SMOKE

CHK'D: MLH
* +48" HD
*

SEPTEMBER 5, 2019
* FEMALE F P 280501 HD DETECTION). REFER TO PENTHOUSE ELECTRICAL PLAN ON
270513

1663-1190-90
F F DRAWING E-202-BC. MOUNT ON WALL NEAR FIRE ALARM

F
DETOX +78"
* * * * * * * * ASSISTANT ANNUNCIATOR PANEL 'FAAP-2'.
B1054 P TV
* JAIL

DESIGNED: RDW,TKF
P P P * P P P P P P +78" 280513 REFER TO FIRE ALARM/DETECTION RISER DIAGRAM ON DRAWING

PROJECT NUMBER
280501 280501 280501 280501 280501 280501 280501 280501 280501 COMMANDER E-804.
280501
C1078

MLH
280520 INTERACTIVE FIREFIGHTERS' TOUCHSCREEN DISPLAY PANEL TO
INMATE

DRAWN: RDW
TOILET / TOILET / BE RECESS MOUNTED WITH TOP AT +60" AFF. PROVIDE
P * 280501 CLOTHING
PADDED SHOWER PADDED PADDED SHOWER PADDED P CONNECTION PER MANUFACTURER'S RECOMMENDATION TO
CELL CELL ADA CELL ADA

APPRV'D:
CELL B1051 CELL CELL B1048 CELL B1043 FIRE ALARM CONTROL PANEL (FACP-1) IN ELECTRICAL ROOM
P B1046 B1045 B1044 #C1054.

DATE:
B1052 B1050 B1049 B1047
F

* INMATE 280525 SMOKE DAMPER. PROVIDE CONNECTION TO FIRE ALARM AS


PROPERTY NEEDED PER MANUFACTURER'S RECOMMENDATION. REFER TO
PADDED TOILET / PADDED FEMALE FEMALE FEMALE FEMALE FEMALE 270513 JAIL MECHANICAL DRAWINGS AND SPECIFICATION 233300 FOR
JANITOR INTERLOCK STORAGE
CELL SHOWER CELL CELL ADA CELL CELL CELL CELL HD COMMANDER DETAILED REQUIREMENTS.
STORAGE B1032
B1108 B1093 MEDICAL +78" C1077
B1109 B1110 B1111 B1094 B1114 B1115 B1116 B1117 B1118 P
RECORDS
TV

VIGO COUNTY SECURITY CENTER


280501 280501 280501 280501 280501 280501 280501 280501 B1127 +78"
TR-2E
270513

FIRST FLOOR SYSTEMS PLAN - AREA B


E2PE P * P * P * P * P * P * P * P * HD
280504 280501
F P P
F

FAAP-4 * * * *
WP 280501 * 280501 * * JANITOR
P
* * C1076
270515 FEMALE COUNCILOR
* P * P *,VV DENTAL 280525
DAYROOM 280501 +48" B1128

SPD-E2PD
SPD-E2PC
WORK * B1129
270509
STATION B1112 280501 270508

E2PC

E2PD
E2HB
* P 270513
P FEMALE
F TR-2C

TERRE HAUTE, INDIANA


B1096 BELOW
HD TOILET ELECTRICAL
270513 * *,HD *,TV INMATE/ INMATE/
HD SHOWER
*,+48" +88" +88" *,TCS PHARMACY * * B1028 ATTORNEY ATTORNEY

DIS-UPS1
F

280501 B1113 +48"


F B1126 135° F CONFERENCE CONFERENCE

F
COURTYARD MALE NAC-1 P *
UPS1 C1075 C1074

A NEW
* P *,TV U1R * * * *
B1134 MEDICAL 280525 * 270506 FA-NAC TR-U1
*,TCS *,VV *,+48" *,HD *,TV *,+48" *,VV +88"
DAYROOM 270507

SPD-U1R
+88" +88" STAFF 270513 *,HD s s
B1095 * *
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

* TOILET
F
270513 TOILET +88" * F F
s

s
B1125 280513
F

280501 280501 * s SHOWER EXAM


F
280501 KEY PLAN

F
B1120 *
P * P F B1130 * *
* F MEDICAL P
280501 *
WAITING JAIL
280501 SUPERVISORS N
F

* P B1122 * INMATE VIDEO


*
s

* * * * * TOILET B1133 ARRAIGNMENT


* P
INTERLOCK B1131 WAITING
B1121 270513 C1073
* * * * * * * * * *
*,+42" HD
P P P P P P P P P P
280501 280501 280501 280501 280501 280501 280501 280501 280501 280501 LACTATION *
ROOM NURSE
280501
B1123 +42" B1124 EXAM
F

*
A B C
s

CELL CELL CELL CELL CELL CELL CELL CELL CELL CELL ADA * P B1132
*
B1106 B1105 B1104 B1103 B1102 B1101 B1100 B1099 B1098 B1097 * s s *
F

F F F
9/25/2019 5:29:06 PM

F
F

* * 280501 280501 280501 280501 280501 280501


SECURE 280525
* * * CORRIDOR * * * P

DRAWING NUMBER

E-401-B
P P P P P
INTERLOCK D1012

ELECTRICAL
* * *
D1013 IDF
CABINET #1 *
F F F F D E
FF s F F
F
1 FIRST FLOOR SYSTEMS - AREA 'B'
E-401-B SCALE: 1/8" = 1'-0"
NORTH
GENERAL NOTES
A. REFER TO DRAWING E-803, DETAIL #10 FOR FIRE ALARM DEVICES
MOUNTING REQUIREMENTS PER NFPA.

B. CONTRACTOR SHALL COORDINATE ALL DEVICE HEIGHTS AND EXACT


LOCATIONS WITH CASEWORK SHOP DRAWINGS AND
ARCHITECTURAL ELEVATION DRAWINGS.

DLZ INDIANA, LLC


C. ALL FIRE ALARM CONDUITS SHALL BE FACTORY PAINTED "RED". ALL
PULL/JUNCTION BOX COVERS SHALL BE FACTORY PAINTED RED.

D. FOR MUTOA BACKBOX AND IN-WALL SLEEVE DETAIL, SEE DETAIL #10
ON DRAWING E-801.

E. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS AND


CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
AND OFFSET BACK TO BACK BOXES.

F. REFER TO SECURITY DRAWINGS, #SE SERIES, AND DIVISION 28


SPECIFICATIONS FOR ADDITIONAL SECURITY SYSTEM
REQUIREMENTS. PROVIDE BOXES AND RACEWAYS CABLING, AND
5 6 7 8 9 ASSOCIATED ITEMS AS NECESSARY FOR A COMPLETE AND
FUNCTIONAL SECURITY SYSTEM.
CELL CELL CELL CELL CELL CELL CELL CELL CELL CELL ADA * G. PROPOSED WAP LOCATIONS AND QUANTITY SHOWN ARE
B1106 B1105 B1104 B1103 B1102 B1101 B1100 B1099 B1098 B1097 * s s * SCHEMATIC ONLY. WAP VENDOR SHALL PROVIDE EXACT LOCATIONS

F
F F F AND QUANTITY OF WIRELESS ACCESS POINTS.
F

F
1. FURNISH AND INSTALL SPECIFICATION GRADE, POWER OVER ER E
* * 280501 280501 280501 280501 280501 280501 ETHERNET, WIRELESS ACCESS POINT (WAP) ROUTERS FOR CK IN
CO

SS D I A N G
SECURE 280525 COMPLETE COVERAGE OF BUILDING; QUANTITY AND LOCATION

I ON A L E N
PE60018676
D

A
*

STATE OF
* * P TO BE DETERMINED BY WAP VENDOR USING PREDICTIVE

L . H I TC
* CORRIDOR * *

E
P P P P P

I ST ER
INTERLOCK D1012 ANALYSIS SOFTWARE.

No.
* * *
D1013 IDF 2. ROUTER MANUFACTURERS SHALL BE BY NETGEAR, RUCKUS

EG
*

IN
CABINET #1

IN
F F F F OR CISCO. PROVIDE WITH NETWORK MANAGEMENT R
RV
FF F F SOFTWARE. WAP VENDOR SHALL PROVIDE A PREDICTIVE MA FE
P RO

s
ANALYSIS OF WIRELESS PERFORMANCE AND WIRELESS

F
STORAGE 270514 270514 TOILET / TOILET / * *,VV * ROUTERS.
270513 280501
D1005B SHOWER SHOWER IT P INMATE
*,HD 3. PROVIDE INDICATING PREDICTIVE TRAFFIC/USAGE AND
D1007 D1008 D1010 TOILET
* CONFERENCE * * P COVERAGE PATTERNS AS PART OF SHOP DRAWING

s
REFER TO DRAWING E-402-D FOR D1014 SUBMITTAL.

F
ROOM

F
* *
FIRE ALARM SMOKE DETECTION IN

s
*,TV D1009
THIS AREA 4. FURNISH AND INSTALL (2) CAT 6 DATA CABLE WITH 10' OF

s
270514 +96" *

F
1 * SLACK FOR FINAL PLACEMENT OF ROUTER HARDWARE.

F
*
*,HD 270513

F
INDOOR/OUTDOOR * *
+96"

SD
CELL RECREATION 5. UNITS TO BE SURFACE MOUNTED ON BOTTOM OF PRECAST,

SD

SD
D1126 *,+48" D1005 ACOUSTICAL CEILING OR STRUCTURE. PROVIDE MOUNTING
* ACCESSORIES AS REQUIRED.
CELL

SD

SD
* 280501

SD
270514 *,TV D1021 6. FURNISH AND INSTALL CUSTOM COVER OVER WIRELESS
1
+96" ACCESS POINT (WAP) ROUTERS LOCATED IN INMATE AREAS
CELL * CLASSROOM * P
*,HD LIKE TERRAWAVE SOLUTIONS #V10102-C-1131 OR APPROVED

SD

SD
CHASE D1006
D1125 +96" EQUAL. COVER SHALL BE SIZED TO MATCH ROUTER AND

SD
D1015A *,TV
280523 INTERLOCK 270513 +96" INTERLOCK UTILIZE TORX-HEAD CENTER PIN SCREWS.

SD

SD
PWR D1003 *,HD * D1011
280516 H. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO SPECIFICATION
+96"

SD
HLI 079200 FOR TYPE.
270513 CELL
*,+48" *,+48"

SD

SD
CELL
VESDA

270513 D1022 280502 280523 I. SEE DRAWING E-607, DETAIL #1 FOR CATV DISTRIBUTION RISER.
280502 SD SD D1124
SD SD *,+48" 270514 HD 270513 *,+48"
CP-6 CP-7 J. DRY FIRE SUPPRESSION TO BE INSTALLED IN ELECTRICAL AND IT

VESDA

VESDA
270514 *,HD
CP-1 ROOMS (REFER TO FIRE SUPPRESSION SERIES DRAWINGS). DRY
* PWR PWR
SD

*,VV *,VV *,VV FIRE SUPPRESSION ALARM/DETECTION CABINET(S) SHALL BE

F
* CONNECTED TO THE FIRE ALARM CONTROL PANEL. CABINET(S) ARE

F
CELL * 280501 HLI HLI
NOT INDICATED ON THIS DRAWING (FIELD COORDINATE CABINET
D1123 REFER TO DRAWING E-402-D FOR 280516
*,VV *,VV LOCATIONS PRIOR TO CONSTRUCTION) AND INCLUDE WITH SHOP

SD

SD
*
SD

FIRE ALARM SMOKE DETECTION IN * P CELL

F
* DRAWING SUBMITTAL. PROVIDE 2 #12, #12G. FROM EACH DRY

F
THIS AREA REFER TO DRAWING E-402-D FOR D1023
1-K SUPPRESSION ALARM/DETECTION CABINET BACK TO NEAREST
*,VV 2 FIRE ALARM SMOKE DETECTION IN AVAILABLE 20A/1P BREAKER (IN A LEGALLY REQUIRED
*,VV

SD

SD
D1120 INTERLOCK E-401-D THIS AREA
CELL PANELBOARD).
SD

D1002A 1-A
D1122
F

*,VV 280501 *,VV D1020 K. ROUTE VESDA SAMPLING TUBING IN CONDUIT (SIZE AS REQUIRED

SD

SD
BY FIRE ALARM VENDOR) ABOVE INACCESSIBLE DETENTION
SD

* P CEILINGS. ALSO REFER TO SPECIFICATION 284621.11 FOR DETAILED


REQUIREMENTS FOR VESDA EQUIPMENT/TUBING/DETECTORS,

SD

SD
3
CONTRACTOR QUALIFICATION REQUIREMENTS, AND

270513
F
270514 * 280501 270514 CELL ADA
CELL ADA

F
STAFF REQUIREMENTS FOR A WORKMANLIKE INSTALLATION OF ALL
SD

270513

F
270513 270513 D1024
D1121 ASSOCIATED APPURTENANCES.

*,TCS

*,TCS

*,TCS
*,TCS

*,TCS

*,TCS

SD

SD
TOILET

s
*,HD *,TV HD * P * *,HD *,TV HD
*
D0001 +96" +96" +48" 1 CONTROL +96" +96" +48"
L. SMOKE DETECTORS IN MECHANICAL CHASES (LOCATED BEHIND
s F F
MECHANICAL F D1000 FAAP-5 CELLS) ARE NOT REQUIRED FOR SMOKE EVAC SYSTEM FOR
F
D0002 F CELLS/DAYROOMS. REFER TO MECHANICAL PLANS FOR SMOKE
270515
F F

HD *,TV *,HD *,+48" *,+48" 280504 *,+48" *,+48" HD *,TV *,HD EVAC SYSTEM SEQUENCE OF CONTROL.
INTERLOCK 270511
+48" +96" +96" * +48" +96" +96"

SD

SD
SD

CELL D1001B * 1-B CELL


270513 270513
F

270513 270513
D1112 270514
1-J
D1110 *,VV *
*
*,VV
D1030 270514 D1031
SYSTEMS KEYNOTES 2805## 2705##

SD

SD
*,VV P
SD

*,VV
*,TCS 280501 * *,TCS

F
REFER TO DRAWING E-402-D FOR CHASE

F
270511 NEW 8-GANG FLOOR BOX, REFER TO KEYNOTE #260524 ON E-201
FIRE ALARM SMOKE DETECTION IN *,VV E1016 SERIES DRAWINGS. FURNISH AND INSTALL (1)
*,VV
F

09/12/19
09/26/19
SD

SD
THIS AREA *

DATE
CELL ADA *,VV CELL ADA DATA/COMMUNICATIONS OUTLET WITH SIX (6) CAT.6
SD

*,VV
*,VV *,VV D1032 JACKS/CABLES. ROUTE (2)-1"C. FROM BOX OVER AND UP WALL TO
D1111 * P
* NEAREST CABLE TRAY FOR CABLING.
280501

F
SD

SD
2 LOWER LEVEL SYSTEMS - AREA 'D' *,+48" F F *,+48" 270513 FURNISH AND INSTALL SPECIALTY OUTLET WITH (1) HDMI PORT
SD

REFER TO DRAWING E-402-D FOR FOR INTERFACING LAPTOP/COMPUTER WITH TV IN ROOM.


E-401-D SCALE: 1/8" = 1'-0" 280523 FURNISH AND INSTALL PRE-TERMINATED HDMI BETWEEN
FIRE ALARM SMOKE DETECTION IN

SD

SD
NORTH *,+48" *,VV *,VV *,+48" THIS AREA LAPTOP/COMPUTER INTERFACE MUTOA AND TV INTERFACE
280516 PWR MUTOA WITH 1"C. FURNISH MATCHING HDMI PORT AT TV
SD

1-C

REVISION
F
F
HLI 1-H * LOCATION.

F
*

F
CELL ADA *,TCS *,VV *,+48" *,VV *,TCS D1040 CELL ADA

SD

SD
D1090 270514 FURNISH AND INSTALL DEVICE IN CUSTOM FLUSH MOUNTED,
VESDA

280502 * *
*,+48" D1041
SD SD D1093 280502

1 Addendum #01
3 Addendum #03
*,TCS *,TCS LOCKABLE WALL CABINET. FOR CABINET DETAIL, SEE SHEET
SD SD *,+48" *,VV *,+48" 280523
REFER TO DRAWING E-402-D FOR *,VV *,VV E-803, DETAIL #7.
*,+48" *,VV
FIRE ALARM SMOKE DETECTION IN

VESDA

VESDA
CP-2 *,+48" CP-5 CP-8 270515 PROVIDE SIGNAL REFERENCE GROUNDING FOR RAISED FLOOR,
SD

THIS AREA REFER TO RAISED FLOOR GROUNDING DETAIL #10 ON SHEET


*,+48" *,+48" 270513 PWR PWR
*,VV *,VV E-802.
260513 *,TCS *,VV *,TCS 270514 HLI HLI
*,VV 280501 REFER TO SMOKE DETECTOR DETENTION COVER DETAIL #9,
SD

*,HD *,VV HD DRAWING E-801.

NO.
*,VV 1-F CELL 280516
1-E

SD

SD
*,TV +96" *,TCS *,TCS +48" *,TV
CELL 1-D 280502 ONE (1) VESDA SMOKE DETECTION SAMPLING POINT/HEAD SHALL
+96" D1070 D1060 +96" D1042
D1092 BE INSTALLED ON THE RETURN DUCTWORK FOR EACH CELL.
D1050
SD

260513 HD *,TCS *,TCS *,HD ROUTE VESDA TUBING BACK TO VESDA AIR SAMPLING SMOKE

SD
SD
260514 +48" +96" DETECTOR/ALARM CABINET. FIELD COORDINATE EXACT CABINET
270514 270513 QUANTITIES AND LOCATIONS WITH FIRE ALARM VENDOR PRIOR

CHK'D: MLH
1-G 270513

SEPTEMBER 5, 2019
SD

HD *,HD 270514 HD TO PROCUREMENT/CONSTRUCTION, PROVIDE SHOP DRAWING


270513

SD
SD

1663-1190-90
D1080 +96"
*,TV +48" 270513 +48" SUBMITTAL INDICATING EXACT LOCATIONS. VESDA CABINET(S)
+96" *,TV *,TV SHALL BE INSTALLED IN THE CHASE ADJACENT TO THE CELLS(S),
SD

WALL MOUNT TOP OF CABINET +6'-0" AFF. REFER TO M-SERIES

DESIGNED: RDW,TKF
HD +96" +96" 270513

SD
SD
*,HD *,HD

PROJECT NUMBER
CELL +48" *,HD CELL DRAWINGS FOR HVAC DUCTWORK FOR EACH CELL AND
270513 +96" +96" SPECIFICATION SECTION 284621.11 FOR DETAILED

MLH
D1091 270513 +96" D1043
270513 *,TV REQUIREMENTS. REFER TO FIRE ALARM/DETECTION RISER

DRAWN: RDW
SD

SD
SD
270514
*,TCS +96" DIAGRAM ON DRAWING E-804.
REFER TO DRAWING E-402-D FOR *,TCS

APPRV'D:
HD 280504 FIRE ALARM ANNUNCIATOR PANEL (F.A.A.P.). PANEL TO BE
FIRE ALARM SMOKE DETECTION IN REFER TO DRAWING E-402-D FOR
+48" RECESS MOUNTED WITH TOP AT +60" A.F.F. PROVIDE

DATE:
THIS AREA *,TCS
*,TCS 270513 FIRE ALARM SMOKE DETECTION IN CONNECTION PER MANUFACTURER'S RECOMMENDATION TO MAIL
REFER TO DRAWING E-402- THIS AREA FIRE ALARM CONTROL PANEL (FACP-1) IN ELECTRICAL ROOM
REFER TO DRAWING E-402- 270514
D FOR FIRE ALARM SMOKE #C1054.
DETECTION IN THIS AREA D FOR FIRE ALARM SMOKE
280516 PROVIDE HIGH-LEVEL-INTERFACE (HLI) AT EACH VESDA AIR

FIRST FLOOR AND LOWER LEVEL SYSTEMS PLANS


DETECTION IN THIS AREA
IDF SAMPLING SMOKE DETECTOR/ALARM CABINET FOR VESDA
CABINET #3 COMMUNICATION NETWORK. CONNECT TO ADJACENT VESDA

VIGO COUNTY SECURITY CENTER


CABINETS WITHIN A SMOKE CONTROL ZONE AND HOMERUN BACK
TO MAIN FIRE ALARM CONTROL PANEL (FACP-1) IN ELECTRICAL
ROOM #C1054. [ALTERNATIVELY, WHERE FACP-1 IS NOT
SUPPORTED BY THE VESDA COMMUNICATIONS NETWORK,
PROVIDE ONE(1) ZAM (FOR MONITORING SMOKE DETECTION
ALARM) FOR EACH SMOKE DETECTION SAMPLING POINT ALARM.
PROVIDE ONE (1) ZAM (FOR MONITORING GENERAL ALARMS SUCH
AS TROUBLE, CLEAN FILTER, ETC.) EACH VESDA AIR SAMPLING
SMOKE DETECTION/ALARM CABINET; REFER TO SPECIFICATION
CELL CELL ADA 284621.11 FOR DETAILED REQUIREMENTS. ROUTE ZAM(S) BACK
CELL CELL CELL ADA CELL CELL CELL TO MAIN FIRE ALARM PANEL (FACP-1) IN ELECTRICAL ROOM
CELL ADA CELL CELL CELL ADA
D1083 D1082 D1081 D1061 D1053 D1051 #C1054].
D1084 D1072 D1062 D1054 D1052
D1071

TERRE HAUTE, INDIANA


280523 PROVIDE VESDA POWER SUPPLY CABINET WITH BATTERY
CHARGER/BATTERIES (120VAC INPUT POWER, 24VDC OUTPUT
POWER). LOCATE ADJACENT TO EACH AIR SAMPLING SMOKE
CHASE
DETECTOR ALARM/MONITORING PANEL. REFER TO DRAWINGS

- AREA D
D1015B E-201-D AND E-201-E FOR CIRCUITING INFORMATION.
SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD

A NEW
280525 SMOKE DAMPER. PROVIDE CONNECTION TO FIRE ALARM AS
SD SD
SD SD

SD SD
SD SD
NEEDED PER MANUFACTURER'S RECOMMENDATION. REFER TO
F F

280523 PWR CP-4 PWR 280523 MECHANICAL DRAWINGS AND SPECIFICATION 233300 FOR
CP-3
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

DETAILED REQUIREMENTS.
HLI VESDA F VESDA HLI F F F
KEY PLAN
280516 280502 280502 280516

1 FIRST FLOOR SYSTEMS - AREA 'D'


E-401-D SCALE: 1/8" = 1'-0"
NORTH

A B C
9/25/2019 5:29:41 PM

E-401-D
DRAWING NUMBER

ELECTRICAL
D E
GENERAL NOTES
A. REFER TO DRAWING E-803, DETAIL #10 FOR FIRE ALARM DEVICES
MOUNTING REQUIREMENTS PER NFPA.

B. CONTRACTOR SHALL COORDINATE ALL DEVICE HEIGHTS AND EXACT


LOCATIONS WITH CASEWORK SHOP DRAWINGS AND
ARCHITECTURAL ELEVATION DRAWINGS.

DLZ INDIANA, LLC


C. ALL FIRE ALARM CONDUITS SHALL BE FACTORY PAINTED "RED". ALL
PULL/JUNCTION BOX COVERS SHALL BE FACTORY PAINTED RED.

D. FOR MUTOA BACKBOX AND IN-WALL SLEEVE DETAIL, SEE DETAIL #10
ON DRAWING E-801.

E. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS AND


CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE
RATED PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS
AND OFFSET BACK TO BACK BOXES.

F. REFER TO SECURITY DRAWINGS, #SE SERIES, AND DIVISION 28


SPECIFICATIONS FOR ADDITIONAL SECURITY SYSTEM
REQUIREMENTS. PROVIDE BOXES AND RACEWAYS CABLING, AND
ASSOCIATED ITEMS AS NECESSARY FOR A COMPLETE AND
FUNCTIONAL SECURITY SYSTEM.

G. PROPOSED WAP LOCATIONS AND QUANTITY SHOWN ARE


18 19 SCHEMATIC ONLY. WAP VENDOR SHALL PROVIDE EXACT LOCATIONS
AND QUANTITY OF WIRELESS ACCESS POINTS.
280521
280525 1. FURNISH AND INSTALL SPECIFICATION GRADE, POWER OVER
* *,WP *
ETHERNET, WIRELESS ACCESS POINT (WAP) ROUTERS FOR R
F F COMPLETE COVERAGE OF BUILDING; QUANTITY AND LOCATION EE
F CK IN
TO BE DETERMINED BY WAP VENDOR USING PREDICTIVE CO

SS D I A N G
I ON A L E N
PE60018676
D

A
280525 ANALYSIS SOFTWARE.

STATE OF
L . H I TC

E
280501 280501 280501 280501 280501 280501 *

I ST ER
SECURE

No.
* P 2. ROUTER MANUFACTURERS SHALL BE BY NETGEAR, RUCKUS
* P * P CORRIDOR * P * P * P INTERLOCK OR CISCO. PROVIDE WITH NETWORK MANAGEMENT

EG

IN
E1012 SOFTWARE. WAP VENDOR SHALL PROVIDE A PREDICTIVE

IN
*

F
E1013
R
* * RV
IDF * ANALYSIS OF WIRELESS PERFORMANCE AND WIRELESS
*
MA FE
F F CABINET #2 F F
ROUTERS. P RO
F F FF
*,VV 3. PROVIDE INDICATING PREDICTIVE TRAFFIC/USAGE AND

s
COVERAGE PATTERNS AS PART OF SHOP DRAWING

F
* * TOILET / TOILET / 270514 270514 STORAGE
270513 SUBMITTAL.
P SHOWER SHOWER 280501
280501 IT *,HD E1009B
E1004 * * E1006 E1007 4. FURNISH AND INSTALL (2) CAT 6 DATA CABLE WITH 10' OF
P * P SLACK FOR FINAL PLACEMENT OF ROUTER HARDWARE.
*

F
*

s
REFER TO DRAWING E-402-E FOR

s
*,TV

F
* * FIRE ALARM SMOKE DETECTION IN 5. UNITS TO BE SURFACE MOUNTED ON BOTTOM OF PRECAST,
+96" *

F
* THIS AREA ACOUSTICAL CEILING OR STRUCTURE. PROVIDE MOUNTING

F
270513 *,HD 270514 2

s
* * ACCESSORIES AS REQUIRED.
+96" INDOOR/OUTDOOR

SD
RECREATION CELL

SD

SD
CONFERENCE 6. FURNISH AND INSTALL CUSTOM COVER OVER WIRELESS
ROOM E1009 *,+48" E1021 ACCESS POINT (WAP) ROUTERS LOCATED IN INMATE AREAS
CELL
E1005 * * LIKE TERRAWAVE SOLUTIONS #V10102-C-1131 OR APPROVED

SD

SD
E1124

SD
2 270514 280501 EQUAL. COVER SHALL BE SIZED TO MATCH ROUTER AND
280501 *,TV
CLASSROOM UTILIZE TORX-HEAD CENTER PIN SCREWS.
+96"
* * P CELL
E1008 *,HD

SD

SD
* P *,TV H. SEAL ALL PENETRATIONS THRU PRECAST, REFER TO SPECIFICATION
+96" E1022

SD
+96" 079200 FOR TYPE.
270513 280523
INTERLOCK *,HD

SD

SD
E1003 +96" INTERLOCK PWR 280516 I. SEE DRAWING E-607, DETAIL #1 FOR CATV DISTRIBUTION RISER.
*
270513

SD
CELL E1010 HLI
*,+48" *,+48" CELL J. DRY FIRE SUPPRESSION TO BE INSTALLED IN ELECTRICAL AND IT
SD

SD

VESDA
E1123 280502 ROOMS (REFER TO FIRE SUPPRESSION SERIES DRAWINGS). DRY
280523 280502 E1023
270513 270514 SD SD FIRE SUPPRESSION ALARM/DETECTION CABINET(S) SHALL BE
*,+48" *,HD *,+48" SD SD CONNECTED TO THE FIRE ALARM CONTROL PANEL. CABINET(S) ARE
CP-6 CP-7 HD
VESDA

VESDA
270513 NOT INDICATED ON THIS DRAWING (FIELD COORDINATE CABINET
270514 CP-12
*,VV LOCATIONS PRIOR TO CONSTRUCTION) AND INCLUDE WITH SHOP

SD
PWR PWR *,VV * *,VV CELL DRAWING SUBMITTAL. PROVIDE 2 #12, #12G. FROM EACH DRY

F
* CHASE

F
HLI HLI REFER TO DRAWING E-402-E FOR *
FIRE ALARM SMOKE DETECTION IN 280501 E1024 SUPPRESSION ALARM/DETECTION CABINET BACK TO NEAREST
280516 280501 E1014A AVAILABLE 20A/1P BREAKER (IN A LEGALLY REQUIRED

SD
THIS AREA *,VV *,VV REFER TO DRAWING E-402-E FOR
SD

SD
* PANELBOARD).

F
CELL * FIRE ALARM SMOKE DETECTION IN

F
* P

F
* P
E1122 THIS AREA
K. ROUTE VESDA SAMPLING TUBING IN CONDUIT (SIZE AS REQUIRED

SD
*,VV * *,VV
SD

SD

2 2-K BY FIRE ALARM VENDOR) ABOVE INACCESSIBLE DETENTION


2-A E-401-E E1020 CELL CEILINGS. ALSO REFER TO SPECIFICATION 284621.11 FOR DETAILED
INTERLOCK

F
E1025 REQUIREMENTS FOR VESDA EQUIPMENT/TUBING/DETECTORS,

SD
E1120 E1002A *,VV
SD

SD

280501 CONTRACTOR QUALIFICATION REQUIREMENTS, AND


REQUIREMENTS FOR A WORKMANLIKE INSTALLATION OF ALL
ASSOCIATED APPURTENANCES.

SD
3 * P
SD

SD

ADA CELL 270514

F
* 270514 L. SMOKE DETECTORS IN MECHANICAL CHASES (LOCATED BEHIND

F
E1121 270513 CELL ADA

s
270513

F
270513 270513 CELLS) ARE NOT REQUIRED FOR SMOKE EVAC SYSTEM FOR

SD
STAFF

*,TCS

*,TCS

*,TCS
E1026
SD

SD

*,TCS

*,TCS

*,TCS
*,HD *,TV HD * * P *,HD *,TV HD CELLS/DAYROOMS. REFER TO MECHANICAL PLANS FOR SMOKE
TOILET
+96" +96" +48" * +96" +96" +48" EVAC SYSTEM SEQUENCE OF CONTROL.
E0001 280501
s F 270515 F
MECHANICAL FAAP-6
F
F 1 CONTROL F
E0002 INTERLOCK *,+48" SYSTEMS KEYNOTES 2805## 2705##
F F

HD *,TV *,HD *,+48" *,+48" 280504 E1000 *,+48" HD *,TV *,HD


270511 *
+48" +96" +96" E1001B +48" +96" +96"
SD

SD

SD
CELL * CELL
F

270513 270513 270513 270513


E1112 2-B 280501 E1031 270511 NEW 8-GANG FLOOR BOX, REFER TO KEYNOTE #260524 ON E-201
270514 2-J 270514
*,VV *,VV SERIES DRAWINGS. FURNISH AND INSTALL (1)
E1110 E1030
SD

SD

*,VV DATA/COMMUNICATIONS OUTLET WITH SIX (6) CAT.6

SD
*,VV * P *

09/12/19
09/26/19
*,TCS REFER TO DRAWING E-402-E JACKS/CABLES. ROUTE (2)-1"C. FROM BOX OVER AND UP WALL TO

F
*,TCS

DATE
CHASE
FOR FIRE ALARM SMOKE NEAREST CABLE TRAY FOR CABLING.
E1016 *,VV *,VV

F
DETECTION IN THIS AREA
SD

SD

CELL ADA *,VV 280501 *,VV 270513 FURNISH AND INSTALL SPECIALTY OUTLET WITH (1) HDMI PORT

SD
CELL ADA
E1111 *,VV *,VV FOR INTERFACING LAPTOP/COMPUTER WITH TV IN ROOM.
* P E1032 FURNISH AND INSTALL PRE-TERMINATED HDMI BETWEEN
* *
LAPTOP/COMPUTER INTERFACE MUTOA AND TV INTERFACE
F
SD

SD

* F
2 LOWER LEVEL SYSTEMS - AREA 'E' *,+48" F MUTOA WITH 1"C. FURNISH MATCHING HDMI PORT AT TV

SD
*,+48"
F LOCATION.
E-401-E SCALE: 1/8" = 1'-0" 280523

REVISION
270514 FURNISH AND INSTALL DEVICE IN CUSTOM FLUSH MOUNTED,
SD

SD

*,+48" *,VV *,VV *,+48"


NORTH PWR 280516 LOCKABLE WALL CABINET. FOR CABINET DETAIL, SEE SHEET

SD
REFER TO DRAWING E-402-E FOR

F
2-C * HLI E-803, DETAIL #7.

1 Addendum #01
3 Addendum #03
* *,TCS FIRE ALARM SMOKE DETECTION IN

F
CELL ADA *

F
*,TCS *,VV *,VV 270515 PROVIDE SIGNAL REFERENCE GROUNDING FOR RAISED FLOOR,
SD

SD

E1090 THIS AREA CELL ADA

VESDA
E1093 *,+48" * *,+48" *,TCS SD SD 280502 REFER TO RAISED FLOOR GROUNDING DETAIL #10 ON SHEET
280502 *,TCS *,+48" E1041
280523 *,VV SD SD E-802.
REFER TO DRAWING E-402-E FOR *,VV *,+48" *,VV 2-H
*,VV CP-11 280501 REFER TO SMOKE DETECTOR DETENTION COVER DETAIL #9,
VESDA

VESDA

CP-5 CP-8 FIRE ALARM SMOKE DETECTION IN *,+48" *,+48" E1040

SD
THIS AREA *,+48" *,+48" DRAWING E-801.
PWR PWR *,VV *,VV 280502 ONE (1) VESDA SMOKE DETECTION SAMPLING POINT/HEAD SHALL

NO.
*,TCS 270514
HLI HLI 270513 *,VV *,VV *,TCS BE INSTALLED ON THE RETURN DUCTWORK FOR EACH CELL.
270513

SD
HD *,VV *,VV ROUTE VESDA TUBING BACK TO VESDA AIR SAMPLING SMOKE
280516 2-E 2-F HD
*,TCS DETECTOR/ALARM CABINET. FIELD COORDINATE EXACT CABINET
SD

SD

CELL *,TV +96" *,TCS +96" *,TV


+96" E1070 E1060 CELL QUANTITIES AND LOCATIONS WITH FIRE ALARM VENDOR PRIOR TO
E1092 +96" PROCUREMENT/CONSTRUCTION, PROVIDE SHOP DRAWING

SD
270513 HD *,TCS E1042

CHK'D: MLH
*,TCS HD 270513 SUBMITTAL INDICATING EXACT LOCATIONS. VESDA CABINET(S)

SEPTEMBER 5, 2019
SD
SD

270514 +48" 2-D +48" SHALL BE INSTALLED IN THE CHASE ADJACENT TO THE CELLS(S),

1663-1190-90
270514 2-G
E1080 WALL MOUNT TOP OF CABINET +6'-0" AFF. REFER TO M-SERIES
270513 HD

SD
HD 270513 E1050 DRAWINGS FOR HVAC DUCTWORK FOR EACH CELL AND
SD
SD

+96"

DESIGNED: RDW,TKF
+48" SPECIFICATION SECTION 284621.11 FOR DETAILED

PROJECT NUMBER
*,TV REQUIREMENTS. REFER TO FIRE ALARM/DETECTION RISER
*,TV 270513
270513

MLH
+96"

SD
DIAGRAM ON DRAWING E-804.
SD

*,HD +96" HD
SD

HD

DRAWN: RDW
CELL *,HD +96"
+96" +48" CELL 280504 FIRE ALARM ANNUNCIATOR PANEL (F.A.A.P.). PANEL TO BE RECESS
E1091 +96" *,TV

APPRV'D:
*,TV 270513 270513 E1043 MOUNTED WITH TOP AT +60" A.F.F. PROVIDE CONNECTION PER

SD
SD
SD

+96" MANUFACTURER'S RECOMMENDATION TO MAIL FIRE ALARM


+96" 270514

DATE:
HD CONTROL PANEL (FACP-1) IN ELECTRICAL ROOM #C1054.
HD *,TCS *,TCS
270513 +48" +48"
280516 PROVIDE HIGH-LEVEL-INTERFACE (HLI) AT EACH VESDA AIR
REFER TO DRAWING E-402-E FOR
270514 REFER TO DRAWING E-402-E FOR
270513
*,TCS SAMPLING SMOKE DETECTOR/ALARM CABINET FOR VESDA
FIRE ALARM SMOKE DETECTION IN *,TCS FIRE ALARM SMOKE DETECTION IN
270514 COMMUNICATION NETWORK. CONNECT TO ADJACENT VESDA

FIRST FLOOR AND LOWER LEVEL SYSTEMS PLANS


THIS AREA THIS AREA CABINETS WITHIN A SMOKE CONTROL ZONE AND HOMERUN BACK
REFER TO DRAWING E-402- REFER TO DRAWING E-402-
E FOR FIRE ALARM SMOKE E FOR FIRE ALARM SMOKE TO MAIN FIRE ALARM CONTROL PANEL (FACP-1) IN ELECTRICAL
ROOM #C1054. [ALTERNATIVELY, WHERE FACP-1 IS NOT

VIGO COUNTY SECURITY CENTER


DETECTION IN THIS AREA DETECTION IN THIS AREA
IDF SUPPORTED BY THE VESDA COMMUNICATIONS NETWORK,
CABINET #4 PROVIDE ONE(1) ZAM (FOR MONITORING SMOKE DETECTION
ALARM) FOR EACH SMOKE DETECTION SAMPLING POINT ALARM.
PROVIDE ONE (1) ZAM (FOR MONITORING GENERAL ALARMS SUCH
AS TROUBLE, CLEAN FILTER, ETC.) EACH VESDA AIR SAMPLING
SMOKE DETECTION/ALARM CABINET; REFER TO SPECIFICATION
284621.11 FOR DETAILED REQUIREMENTS. ROUTE ZAM(S) BACK TO
MAIN FIRE ALARM PANEL (FACP-1) IN ELECTRICAL ROOM #C1054].
280521 DEVICES IN TRASH ROOM #c1066 SHALL BE EQUIPPED WITH
WATERTIGHT COVER SUITABLE FOR PROTECTION FROM WATER
CELL CELL ADA CELL ADA CELL CELL CELL HOSE SPRAY.
CELL CELL
E1084 CELL CELL ADA CELL ADA CELL 280523 PROVIDE VESDA POWER SUPPLY CABINET WITH BATTERY

TERRE HAUTE, INDIANA


E1071 E1061 E1054 E1053 E1052 E1051
E1083 CHARGER/BATTERIES (120VAC INPUT POWER, 24VDC OUTPUT
E1082 E1081 E1072 E1062
POWER). LOCATE ADJACENT TO EACH AIR SAMPLING SMOKE
DETECTOR ALARM/MONITORING PANEL. REFER TO DRAWINGS

- AREA E
CHASE E-201-D AND E-201-E FOR CIRCUITING INFORMATION.

A NEW
E1014B 280525 SMOKE DAMPER. PROVIDE CONNECTION TO FIRE ALARM AS
NEEDED PER MANUFACTURER'S RECOMMENDATION. REFER TO
SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD MECHANICAL DRAWINGS AND SPECIFICATION 233300 FOR
SD SD
SD SD

SD SD
SD SD
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

DETAILED REQUIREMENTS.

F F
280523 PWR CP-9 280523 PWR CP-10
HLI VESDA HLI VESDA
KEY PLAN
F F F F

280516 280502 280516 280502

1 FIRST FLOOR SYSTEMS - AREA 'E'


E-401-E SCALE: 1/8" = 1'-0"
NORTH
A B C
9/25/2019 5:30:01 PM

DRAWING NUMBER

E-401-E

ELECTRICAL
D E
GENERAL NOTES
8 (N) GROUND MOUNTED DIESEL GENERATOR GEN-1 8 (N) GROUND MOUNTED DIESEL GENERATOR GEN-2 8 (N) GROUND MOUNTED DIESEL GENERATOR GEN-3 A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702,
900KW/1175KVA, 480/277V, 3 PHASE, 4W, 0.8PF 900KW/1175KVA, 480/277V, 3 PHASE, 4W, 0.8PF 900KW/1175KVA, 480/277V, 3 PHASE, 4W, 0.8PF E-703, E-704, E-705, E-706 AND E-707.

DLZ INDIANA, LLC


B. FOR CONDUIT AND CABLE SCHEDULE, SEE DRAWING E-603.
FROM ELECTRIC UTILITY 4 18 4 18 4 18
(E) UTILITY (E) UTILITY C. FOR SERVICE GROUNDING ELECTRODE SCHEMATIC, SEE DETAIL #
POLE 'UP-1' POLE 'UP-2' G G 2000AF G G 2000AF G G 2000AF 19 1 ON DRAWING E-803.
10A 10B 1500AT 50A 1500AT 50B 1500AT 50C
(N) GROUND MOUNTED 1100KW D. REFERENCE MECHANICAL EQUIPMENT CONNECTION SCHEDULE,
LOAD BANK DRAWING E-604 AND E-605.
LSIG LSIG LSIG
100% SS 100% SS 100% SS E. FOR TRANSFORMER SCHEDULE, SEE SHEET E-607.
RATED RATED RATED
300 303 306 F. BREAKERS INDICATED ARE 80% RATED, THERMAL MAGNETIC,
2 (N) UTILITY GENSET GENSET GENSET
MOLDED CASE U.O.N.
METER M-1 Y HV
480/277V
FIELD VERIFY WITH
ELECTRIC UTILITY
BATTERY
CHARGER
BATTERY
CHARGER
BATTERY
CHARGER
3-PHASE
M 4-WIRE 11 11 11
(N) (N) (N)
1EPP-GEN GENSET 301 2EPP-GEN GENSET 304 3EPP-GEN GENSET 307

(N) PADMOUNT UTILITY


TRANSFORMER UT-1 1
240/120V
1P,3W
CONTROL
PANEL
240/120V
1P,3W
CONTROL
PANEL
240/120V
1P,3W
CONTROL
PANEL CODED NOTES #
10C 60A CP-GEN 60A CP-GEN 60A CP-GEN
100 MCB MCB MCB 1. UTILITY TRANSFORMER FURNISHED AND INSTALLED BY DUKE
ENERGEY. CONCRETE PAD FURNISHED AND INSTALLED BY
CONTRACTOR IN ACCORDANCE WITH THE ELECTRIC UTILITY'S R
STANDARDS. EE
CK IN
CO

SS D I A N G
GEN-1 DAY GEN-2 DAY GEN-3 DAY

I ON A L E N
2. METER CABINET FURNISHED AND INSTALLED BY CONTRACTOR.

PE60018676
D

A
STATE OF
192 192 192

L . H I TC

E
TANK TANK TANK

I ST ER
105 FIELD COORDINATE CABINET REQUIREMENTS WITH DUKE

No.
ENERGY. METER BASE FURNISHED AND INSTALL BY DUKE
302 305 308 315 ENERGY.

EG
TO DISCONNECT 'DIS-E1PP' TO DISCONNECT 'DIS-E2PP' TO DISCONNECT 'DIS-E3PP'

IN
IN
(IN MECHANICAL #C1053) (IN MECHANICAL #C1053) (IN MECHANICAL #C1053)
R
3. EQUIP SWITCGEAR 'MDPA' WITH REMOVABLE NEUTRAL LINK. RV
SEE SHEET E-602 SEE SHEET E-602 304 SEE SHEET E-602 MA FE
P RO
4. FOR SERVICE ENTRANCE GROUNDING ELECTRODE SYSTEM
307 DETAIL, SEE DRAWING E-803, DETAIL #1. ALSO, REFER TO DETAIL #
8 ON DRAWING E-803 FOR SERVICE ENTRANCE GROUNDING
306 SCHEME.
300
301 50B 5. SECTION SHALL BE SWITCHBOARD CONSTRUCTION. REFER TO
SPECIFICATION 262413 FOR DETAILED EQUIPMENT
50A 50C REQUIREMENTS.

305 308 TO FUTURE 6. ANNUNCIATOR LOCATED IN MASTER CONTROL ROOM #B1016.


100B 20
GENERATOR
302 7. REMOTE SURGE PROTECTIVE DEVICE (SPD). REFER TO
303 SPECIFICATION 264313 FOR DETAILED EQUIPMENT
(N) PARALLELING SWITCHGEAR 'MDPA' (N) PARALLELING SWITCHGEAR 'MDPB' REQUIREMENTS. PROVIDE A MAXIMUM LENGTH OF 6' OF
(IN MECHANICAL ROOM #C1053) 21 22 22 21 (IN MECHANICAL ROOM #C1054) CONDUCTORS TO SPD.
AUX. MASTER SECTION NO. 1 SECTION NO. 2 SECTION NO. 4 SECTION NO. 5 SECTION NO. 9 SECTION NO. 10 8. DIESEL ENGINE GENERATOR WITH NON-WALK-IN LEVEL 1 SOUND
CONTROL UTILITY MAIN LEGALLY DISTRIBUTION DISTRIBUTION DISTRIBUTION MASTER CONTROL ENCLOSURE AND 48 HOUR DOUBLE WALL FUEL TANK. REFER TO
18 REQUIRED 18 18 18 18 SPECIFICATION 263213.14 FOR DETAILED EQUIPMENT
CONTROLS CONTROLS
4000AF AUTO TRANSFER CONTROLS CLOSED 1600AF 1600AF 1600AF 1600AF REQUIREMENTS.
4000AT TRANSITION PARALLEL WITH UTILITY 1500AT 1500AT 1500AT 1500AT
9. AUTOMATIC TRANSFER SWITCH WITH SWITCHED NEUTRAL AND
LSIG SS M M LSIG SS LSIG SS LSIG SS LSIG SS
MAINTENANCE BYPASS. REFER TO SPECIFICATION 263600 FOR
SEGREGATED 100% 100% 100% 100% 100% SEGREGATED
4-POLE 4-POLE DETAILED EQUIPMENT REQUIREMENTS.
MASTER PLC RATED RATED RATED RATED RATED MASTER PLC
CONTROLLER CONTROLLER 10. FOR TRANSFORMER GROUNDING DETAIL, SEE DETAIL #6 ON
4000AF 4000AF SHEET E-803. (TYPICAL FOR ALL TRANFORMERS). REFER TO
4000AT 3 4000AT SPECIFICATIONS FOR DETAILED EQUIPMENT REQUIREMENTS.
23
LSIG LSIG
3 100% 100% 11. PANEL, 120/240V, 1-PHASE, 3-WIRE FOR GENSET CHARGERS,
RATED RATED 3
3 SS SS SS SS SS SS SS SS SS SS SS SS HEATERS, LIGHTS AND RECEPTACLES. PANEL PROVIDED AND PRE-
SS SS 4 N WIRED BY GENERATOR MANUFACTURER.
4 N
800AF 800AF 800AF 800AF 1600AF 1600AF 800AF 1600AF 1600AF G 800AF 800AF 800AF 800AF
G 200AT 600AT 100AT 600AT 1200AT 1600AT 600AT ---AT 1600AT 200AT 200AT 200AT 200AT 12. FURNISH AND INSTALL 240VAC, 2-POLE, 100A HEAVY DUTY FUSED
100% LSIG LSIG LSIG LSIG LSIG LSIG LSIG LSIG LSIG LSIG LSIG LSIG SAFETY DISCONNECT SWITCHES 'DIS-1EPP', 'DIS-2EPP' AND
RATED 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 'DIS-3EPP' IN NEMA 3R ENCLOSURES, FUSE AT 60A. REFER TO
SECTION NO. 3 RATED RATED RATED RATED RATED RATED RATED RATED SECTION NO. 6 SECTION NO. 7 SECTION NO. 8 RATED RATED RATED RATED DRAWING E-201-C FOR LOCATION.
TIE BREAKER TIE BREAKER GEN'S 1&2 CONTROLS/PLC'S GEN'S 1&2 CONTROLS/PLC'S
13. FURNISH AND INSTALL (3) EMPTY 1" CONDUITS STUBBED OUT
111A 135 FUTURE 140 130 111B ABOVE ACCESSIBLE CEILING FOR FUTURE USE. CAP THE END OF
100A
137 THE CONDUIT LOCATED IN CEILING.
136 320
BREAKER 105 SPARE SPARE SPARE 14. NEW UPS. REFER TO KEYNOTE #260533, ON DRAWING E-201-B AND
7 SPACE BREAKER BREAKER BREAKER SPECIFICATION 263353 FOR DETAILED EQUIPMENT
SPD REQUIREMENTS.

135 (N) SPD-MDP FUTURE 15. NEW UPS BATTERY CABINET WITH DISCONNECT. REFER TO
137 KEYNOTE #260534, ON DRAWING E-201-B AND SPECIFICATION
263353 FOR DETAILED EQUIPMENT REQUIREMENTS.
TO CHILLER #1
16. FURNISH AND INSTALL 240VAC, 3-POLE, 200A HEAVY DUTY FUSED
EXTERIOR 325 SAFETY DISCONNECT SWITCH 'DIS-UPS1' IN NEMA 1 ENCLOSURE,
TO CHILLER 'CH-1' TO FUTURE CHILLER TO SWITCHBOARD TO CHILLER 'CH-2' FUSE AT 250A. REFER TO DRAWING E-201-B FOR LOCATION.
(EXTERIOR) 'CH-FTR' 'ODPB' (EXTERIOR) TO CHILLER #2 PROVIDE NEUTRAL LUGS SUITABLE FOR TWO (2) NEUTRALS.
SEE SHEET E-602 SEE SHEET E-602 (MECHANICAL #B2000) SEE SHEET E-602 EXTERIOR BATTERY

09/12/19
09/26/19
DATE
SEE SHEET E-602 CHARGER 17. SWITCHBOARD SECTION TO BE PROVIDED WITH A MINIMUM OF 60"
321 MOUNTING SPACE.

18. BREAKER SHALL BE SERVICE ENTRANCE RATED.

111B 19. LOAD BANK, REFER TO SPECIFICATIONS FOR DETAILED


EQUIPMENT REQUIREMENTS.

REVISION
20. 4000A, 480V, 3-PHASE BUS DUCT, REFER TO SPECIFICATIONS FOR
9 310 DETAILED EQUIPMENT REQUIREMENTS.

1 Addendum #01
3 Addendum #03
(IN ELECTRICAL
RM #A178) N 21. PARALLELING SWITCHGEAR. REFER TO SPECIFICATIONS FOR
E
DETAILED EQUIPMENT REQUIREMENTS.
130
ATS-LEGAL (N)
42 200A, 22. SUBMIT DIMENSIONED PLAN SHOWING ELECTRICAL GEAR WITH
KAIC L 4POLE REQUIRED CLEARANCES AND SERVICE SPACE AROUND
EQUIPMENT IN MECHANICAL #C1053 AND ELECTRICAL #C1054 TO

NO.
330 ENGINEER FOR APPROVAL PRIOR TO SUBMITTING GEAR
(N) SWITCHBOARD ODPA (IN
SUBMITTALS.
MECHANICAL ROOM #C1053) ATS-ANN
6
SECTION NO. 1 SECTION NO. 2 23. FURNISH AND INSTALL (1)-CAT6 CABLE FROM SECTION 10 -
MASTER CONTROL CABINET AND NEAREST COMMUNICATIONS
5 17

CHK'D: MLH
5 17 OUTLET.

SEPTEMBER 5, 2019

1663-1190-90
1600AF
24. FURNISH AND INSTALL CENTRAL UNINTERRUPTIBLE EMERGENCY
1600AT 120 LIGHTING INVERTER, SINGLE PHASE, 277V INPUT/OUTPUT WITH 4
LSIG OUTPUT BREAKERS, 90-MINUTE RATED BATTERY BACKUP
SS

PROJECT NUMBER
100% (IN ELECTRICAL CAPACITY AT RATED LOAD, UL 924 LISTED, 3KW MINIMUM FOR L1E,
(N)

DESIGNED: RDW
RATED

MLH
480/277V, 3 PHASE, 4 W, 1600A, 42KAIC RM #C1054) 10KW MINIMUM FOR L2E, CONTROLLED POWER MODEL ELU OR
DP-L

DRAWN: RDW
120A APPROVED EQUAL BY MYERS, DUAL-LITE, EATON.
480/277V
7 3P,4W

APPRV'D:
200A

DATE:
3 MCB
SPD 42KAIC
2-POLE 2-POLE 2-POLE 2-POLE
(N) SPD-DPL 125
125AF 125AF 225AF 225AF 225AF 225AF 225AF 125AF 125AF 400AF 225AF 125AF 125AF 125AF 125AF 125AF
100AT
80AT 110AT 200AT 200AT 200AT 200AT 70AT 70AT 400AT ---AT ---AT 70AT 70AT 70AT 70AT
LSI

VIGO COUNTY SECURITY CENTER


80% 3 3 3 3 122
123
SS 2#6+8G. 2#12+G.
IN 1"C. IN 3/4"C.
(N) TR-L1P (N) (N)
130A 133 (IN ELECTRICAL L2H (N) L1H (N)
SPARE SPARE SPARE RM #C1054) 480/277V L2E 480/277V L1E
7 160 165 170 175 180 185 190 195 BREAKER BREAKER 210 215 220 BREAKER
SPD FOR FUTURE 3P,4W 24 3P,4W 24
GENERATOR 125A 125A
(N) SPD-ODPA 480V MLO (IN MECHANICAL MLO (IN ELECTRICAL
15KVA 42KAIC RM #B2000) 42KAIC RM #B1024)

ONE-LINE DIAGRAM
Y 208/120V
(IN ELECTRICAL (IN ELECTRICAL

TERRE HAUTE, INDIANA


RM #B2002) RM #B1024)

10 124
(N) TR-L2P

A NEW
122A (IN ELECTRICAL
RM #B2002)
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

(IN ELECTRICAL
RM #C1054)
480V
TO DOMESTIC TO PANELS 'E1PA' & TO PANEL 'E1HA' TO PANEL 'E1HB' TO PANEL 'E2HA' TO PANEL 'E3H' TO 'UPS-1' VIA TO 'UPS-2' VIA TO PANEL 'K1H' TO GEN PANEL 'E3PP' TO GEN PANEL 'E1PP' TO GEN PANEL 'E2PP' (N) 15KVA
BOOSTER PUMP 'E1PB' VIA (ELECTRICAL #C1053) (ELECTRICAL #C1004) (ELECTRICAL #B1024) (VEH. SALLYPORT #A1003) TRANSFORMER 'TR-U1' TRANSFORMER 'TR-U2' (KITCHEN #C1059) VIA TRANSFORMER VIA TRANSFORMER VIA TRANSFORMER L1P
208/120V
122B Y 208/120V
'DWBP-1' TRANSFORMER 'TR-1A' SEE SHEET E-602 SEE SHEET E-602 SEE SHEET E-602 SEE SHEET E-602 (ELECTRICAL #B1028) (ELECTRICAL #B1024) SEE SHEET E-602 'TR-G3' 'TR-G1' 'TR-G2'
SEE SHEET E-602 (ELEC #C1004) SEE SHEET E-602 SEE SHEET E-602 (IN GEN #3) (IN GEN #1) (IN GEN #2) 3P,4W 7
SEE SHEET E-602 SEE SHEET E-602 SEE SHEET E-602 SEE SHEET E-602 60A
MCB
10KAIC SPD 10
(N) SPD-L1P 124A

(IN ELECTRICAL
RM #B2002)

(N)
L2P 124B
208/120V
3P,4W 7
9/25/2019 5:31:38 PM

60A
MCB
10KAIC SPD

(N) SPD-L2P

DRAWING NUMBER

E-601

ELECTRICAL
TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'ODPA'
SECTION 2 SECTION 2 SECTION 2 SECTION 2 SECTION 2 SECTION 2
IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM #C1053 TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'ODPA'
SEE SHEET E-601 SEE SHEET E-601 SEE SHEET E-601 SEE SHEET E-601 SEE SHEET E-601 SEE SHEET E-601 SECTION 2 SECTION 2 SECTION 2
IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM #C1053
SEE SHEET E-601 SEE SHEET E-601 SEE SHEET E-601
165 170 195 175 185 190

DLZ INDIANA, LLC


13
(N) TR-U1 (N) TR-U2
(IN ELECTRICAL (IN ELECTRICAL
ROOM #B1028) ROOM #B1024)
(IN (IN (IN ELECTRICAL 210 215 220
(N) (N) (N) (N)
MECHANICAL ELECTRICAL ROOM #B1024) (N) TR-G3 (N) TR-G1 (N) TR-G2
E1HA E1HB K1H E2HA
ROOM #C1053) ROOM 480V 480V (IN MECHANICAL (IN MECHANICAL (IN MECHANICAL
480/277V 480/277V 480/277V 480/277V
TO SWITCHBOARD 'ODPA' #C1004) 10 45KVA 10 45KVA #C1053) #C1053) #C1053)
3P,4W 3P,4W 3P,4W 3P,4W
SECTION 2
IN MECHANICAL ROOM #C1053
250A 250A 400A 250A Y 208/120V
K13
Y 208/120V
K13
MLO MLO MLO MLO
SEE SHEET E-601 42KAIC 42KAIC 42KAIC 42KAIC 480V 480V 480V
25KVA 25KVA 25KVA
(IN KITCHEN
#C1059)
Y 240/120V
Y 240/120V
Y 240/120V

186 (N) 191 (N)


160 171 201 176
196 DISCONNECT DISCONNECT
'DIS-UPS1' 'DIS-UPS2' 10 10 10
(N) TR-1A (N) TR-1C (N) TR-K1 (N) TR-K2 (N) TR-2A
(N) (N) (N)
(IN MECHANICAL (IN ELECTRICAL (IN FACILITY (IN FACILITY (IN ELECTRICAL 211 216 221
(IN ELECTRICAL (IN DISCONNECT DISCONNECT DISCONNECT
ROOM #C1053) ROOM #C1004) WORKSHOP #C1056) WORKSHOP #C1056) ROOM #B1024) 200A 200A
16 ROOM #B1028) 16 ELECTRICAL 'DIS-3EPP' 'DIS-1EPP' 'DIS-2EPP'
12 12 12
175A 175A ROOM #B1024) R
EE
CK IN
CO

SS D I A N G
480V 480V 480V 480V 480V

I ON A L E N
PE60018676
100A 100A 100A D

A
STATE OF
L . H I TC

E
75KVA 45KVA 75KVA 30KVA 45KVA

I ST ER
Y 208/120V
Y 208/120V Y 208/120V
Y 208/120V
Y 208/120V 600V 600V

No.
100A 100A 100A
NEMA 1 NEMA 1

EG

IN
IN
R
187 192 3 RV
600V 600V 600V MA FE
10 10 10 10 10 UNINTERRUPTABLE POWER UNINTERRUPTABLE NEMA 1 NEMA 1 NEMA 1 P RO
161 172 197 202 177 40KVA SUPPLY 'UPS1' 40KVA POWER SUPPLY 'UPS2'
162 173 13 13 13 178 UPS (N+1) UPS (N+1) 212 217 222
(IN ELECTRICAL ROOM (IN ELECTRICAL ROOM
#B1028) #B1024)
(N) (N) (N) (N) (N) (N) 14 14
161A E1PA E1PB 162A 172A E1PC E1PD 173A 177A E2PA E2PB 178A 189 194
208/120V 208/120V 208/120V 208/120V 208/120V 208/120V TO PANEL 'E3PP' IN TO PANEL 'E1PP' IN TO PANEL 'E2PP' IN
7 3P,4W 3P,4W 7 7 3P,4W 3P,4W 7 (N) 198 (N) (N) 7 3P,4W 3P,4W 7 GENERATOR-3 (ON SITE) GENERATOR-1 (ON SITE) GENERATOR-2 (ON SITE)
250A 250A 175A 200A K1L K2L K3L 175A 200A UNINTERRUPT UNINTERRUPT SEE SHEET E-601 SEE SHEET E-601 SEE SHEET E-601
MCB MLO MCB MLO 208/120V 208/120V 208/120V MCB MLO 188 LIGHTING 193 LIGHTING
SPD SPD SPD SPD SPD SPD 189A 194A
10KAIC 10KAIC 10KAIC 10KAIC 3P,4W 3P,4W 3P,4W 10KAIC 10KAIC PANEL PANEL
250A 200A 110A 7 U1R 7 U2R
(N) SPD-E1PA (N) SPD- (N) SPD-E1PC (N) SPD- MCB MLO MCB (N) SPD-E2PA (N) SPD-
(IN (IN E1PB WITH FEED- (IN ELECTRICAL E1PD WITH FEED- (IN ELECTRICAL E2PB 175A 175A
MECHANICAL MECHANICAL THRU LUGS ROOM #C1004) 10KAIC 10KAIC 10KAIC THRU LUGS ROOM #B1024) 15 MCB 15 MCB
ROOM #C1053) ROOM #C1053) (IN ELECTRICAL (IN ELECTRICAL SPD 120/208V SPD 120/208V
ROOM #C1004) (IN KITCHEN (IN KITCHEN (IN LAUNDRY ROOM #B1024)
#C1059) #C1059) #C1065) (N) SPD-U1R (N) SPD-U2R
(IN ELECTRICAL (IN ELECTRICAL
ROOM #B1028) ROOM #B1024)
3 3 UNINTERRUPTABLE UNINTERRUPTABLE
POWER SUPPLY POWER SUPPLY
BATTERY CABINET (IN BATTERY CABINET (IN
ELECTRICAL ROOM ELECTRICAL ROOM
#B1028) #B1024)

GENERAL NOTES
TO SWITCHBOARD 'ODPA'
A. FOR PANELBOARD SCHEDULES, SEE DRAWINGS E-701, E-702,
SECTION 2
E-703, E-704, E-705, E-706 AND E-707.
IN MECHANICAL ROOM #C1053
SEE SHEET E-601
B. FOR CONDUIT AND CABLE SCHEDULE, SEE DRAWING E-603.

TO SWITCHBOARD 'MDPB' TO SWITCHBOARD 'MDPB' C. FOR SERVICE GROUNDING ELECTRODE SCHEMATIC, SEE DETAIL #
SECTION 10 SECTION 10 1 ON DRAWING E-803.
IN MECHANICAL ROOM IN MECHANICAL ROOM
#C1053 SEE SHEET E-601 #C1053 SEE SHEET E-601 D. REFERENCE MECHANICAL EQUIPMENT CONNECTION SCHEDULE,
180
DRAWING E-604 AND E-605.

TO SWITCHBOARD 'ODPA' TO SWITCHBOARD 'MDPA' TO SWITCHBOARD 'MDPB' TO SWITCHBOARD 'MDPA' E. FOR TRANSFORMER SCHEDULE, SEE SHEET E-607.
SECTION 2 SECTION 4 SECTION 5 SECTION 4
IN MECHANICAL ROOM #C1053 IN MECHANICAL ROOM IN MECHANICAL ROOM IN MECHANICAL ROOM #C1053 F. BREAKERS INDICATED ARE 80% RATED, THERMAL MAGNETIC,
SEE SHEET E-601 #C1053 SEE SHEET E-601 #C1053 SEE SHEET E-601 SEE SHEET E-601 MOLDED CASE U.O.N.
13
TO SWITCHBOARD 'MDPA'
SECTION 4
IN MECHANICAL ROOM #C1053 320
SEE SHEET E-601
133 135
321
136
137 (FUTURE)
(N)
(IN VEHICLE
SALLYPORT
CODED NOTES #
(N) (N) (N) FUTURE E3H
#A1000) 1. UTILITY TRANSFORMER FURNISHED AND INSTALLED BY DUKE
DISCONNECT DISCONNECT DISCONNECT DISCONNECT 480/277V
BY OTHERS BY OTHERS BY OTHERS BY OTHERS 3P,4W ENERGEY. CONCRETE PAD FURNISHED AND INSTALLED BY
250A CONTRACTOR IN ACCORDANCE WITH THE ELECTRIC UTILITY'S
140 MLO STANDARDS.
100A 600A 600A 600A 42KAIC

09/26/19
DATE
2. METER CABINET FURNISHED AND INSTALLED BY CONTRACTOR.
FIELD COORDINATE CABINET REQUIREMENTS WITH DUKE
600V 600V 600V 600V
(N) SWITCHBOARD ODPB (IN ENERGY. METER BASE FURNISHED AND INSTALL BY DUKE
NEMA 1 NEMA 3R NEMA 3R NEMA 3R
MECHANICAL #B2000, PENTHOUSE) ENERGY.
137A (FUTURE) 181
SECTION NO. 1 SECTION NO. 2 133A 135A 136A 3. EQUIP SWITCGEAR 'MDPA' WITH REMOVABLE NEUTRAL LINK.
5 17 5 17 (N) TR-3 4. FOR SERVICE ENTRANCE GROUNDING ELECTRODE SYSTEM

REVISION
1200AF (IN VEHICLE DETAIL, SEE DRAWING E-803, DETAIL #1. ALSO, REFER TO DETAIL #
SALLYPORT #A1000) 8 ON DRAWING E-803 FOR SERVICE ENTRANCE GROUNDING
1200AT SCHEME.

3 Addendum #03
LSIG SS (3) 15HP 495 MCA 495 MCA
100% 5. SECTION SHALL BE SWITCHBOARD CONSTRUCTION. REFER TO
RATED 480V
480/277V, 3 PHASE, 4 W, 1200A, 42KAIC (N) DOMESTIC BOOSTER (N) CHILLER 'CH-1' (N) CHILLER 'CH-2' (FUTURE) CHILLER 'CH-FTR' SPECIFICATION 262413 FOR DETAILED EQUIPMENT
30KVA
PUMP 'DWBP-1' (EXTERIOR) (EXTERIOR) (EXTERIOR) REQUIREMENTS.
(IN MECHANICAL #C1053) Y 208/120V
6. ANNUNCIATOR LOCATED IN MASTER CONTROL ROOM #B1016.

NO.
3 3 3 3 3
7. REMOTE SURGE PROTECTIVE DEVICE (SPD). REFER TO
10 SPECIFICATION 264313 FOR DETAILED EQUIPMENT
182 REQUIREMENTS. PROVIDE A MAXIMUM LENGTH OF 6' OF
125AF 225AF 225AF 225AF 400AF 225AF 125AF 125AF 125AF 125AF 125AF 125AF 125AF 225AF CONDUCTORS TO SPD.

CHK'D: MLH
100AT 200AT 200AT ---AT ---AT 125AT 70AT 100AT 30AT 70AT 35AT 70AT 35AT 200AT

SEPTEMBER 5, 2019
8. DIESEL ENGINE GENERATOR WITH NON-WALK-IN LEVEL 1 SOUND

1663-1190-90
80% 80% 80% 80% 80% 80% 80% 80% 80% 80% 80% 80% 80% ENCLOSURE AND 48 HOUR DOUBLE WALL FUEL TANK. REFER TO
RATED RATED RATED RATED RATED RATED RATED RATED RATED RATED RATED RATED RATED 13
SPECIFICATION 263213.14 FOR DETAILED EQUIPMENT
REQUIREMENTS.

PROJECT NUMBER
DESIGNED: RDW
MLH
140A 9. AUTOMATIC TRANSFER SWITCH WITH SWITCHED NEUTRAL AND

DRAWN: RDW
MAINTENANCE BYPASS. REFER TO SPECIFICATION 263600 FOR
(N)
DETAILED EQUIPMENT REQUIREMENTS.
7 142 147 150A 150C 151A 151C 152A 152C 153A 153C 155 E3PA

APPRV'D:
182A
SPD 208/120V
10. FOR TRANSFORMER GROUNDING DETAIL, SEE DETAIL #6 ON

DATE:
7 3P,4W
(N) SPD-ODPB SHEET E-803. (TYPICAL FOR ALL TRANFORMERS). REFER TO
110A
SPARE SPARE SPECIFICATIONS FOR DETAILED EQUIPMENT REQUIREMENTS.
MCB
BREAKER BREAKER SPD 10KAIC
11. PANEL, 120/240V, 1-PHASE, 3-WIRE FOR GENSET CHARGERS,
(N) SPD-E3PA HEATERS, LIGHTS AND RECEPTACLES. PANEL PROVIDED AND PRE-
(IN VEHICLE WIRED BY GENERATOR MANUFACTURER.
SALLYPORT

VIGO COUNTY SECURITY CENTER


#A1000) 12. FURNISH AND INSTALL 240VAC, 2-POLE, 100A HEAVY DUTY FUSED
SAFETY DISCONNECT SWITCHES 'DIS-1EPP', 'DIS-2EPP' AND
'DIS-3EPP' IN NEMA 3R ENCLOSURES, FUSE AT 60A. REFER TO
DRAWING E-201-C FOR LOCATION.

142 147 155 13. FURNISH AND INSTALL (3) EMPTY 1" CONDUITS STUBBED OUT
ABOVE ACCESSIBLE CEILING FOR FUTURE USE. CAP THE END OF
THE CONDUIT LOCATED IN CEILING.

14. NEW UPS. REFER TO KEYNOTE #260533, ON DRAWING E-201-B AND

ONE-LINE DIAGRAM
SPECIFICATION 263353 FOR DETAILED EQUIPMENT
REQUIREMENTS.

TERRE HAUTE, INDIANA


(IN STORAGE (IN MECHANICAL (IN ELECTRICAL
(N) (N) (N)
ROOM #E1016B) #B2000, PENTHOUSE) ROOM #B1028) 15. NEW UPS BATTERY CABINET WITH DISCONNECT. REFER TO
E4H E5H E2HB
480/277V 480/277V 480/277V KEYNOTE #260534, ON DRAWING E-201-B AND SPECIFICATION
3P,4W 3P,4W 3P,4W 263353 FOR DETAILED EQUIPMENT REQUIREMENTS.
200A 200A 250A

A NEW
MLO MLO MLO 16. FURNISH AND INSTALL 240VAC, 3-POLE, 200A HEAVY DUTY FUSED
42KAIC 42KAIC 42KAIC SAFETY DISCONNECT SWITCH 'DIS-UPS1' IN NEMA 1 ENCLOSURE,
FUSE AT 250A. REFER TO DRAWING E-201-B FOR LOCATION.
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

PROVIDE NEUTRAL LUGS SUITABLE FOR TWO (2) NEUTRALS.


158
150A 150C 151A 151C 152A 152C 153A 153C 17. SWITCHBOARD SECTION TO BE PROVIDED WITH A MINIMUM OF 60"
143 144 148 156 MOUNTING SPACE.
149
157 18. BREAKER SHALL BE SERVICE ENTRANCE RATED.
(N) TR-4A (N) TR-5A (N) TR-2C (N) TR-2D (N) TR-2E
(IN STORAGE (N) TR-4B (IN MECHANICAL (N) TR-5B (IN ELECTRICAL (IN ELECTRICAL (IN JANITOR 19. LOAD BANK, REFER TO SPECIFICATIONS FOR DETAILED
ROOM #E1016B) (IN CHASE #E1014) #B2000, PENTHOUSE) (IN CHASE #D1014) VFD VFD VFD VFD ROOM #B1028) ROOM #B1028) #B1108) EQUIPMENT REQUIREMENTS.
SEE SEE SEE SEE
SPECS SPECS SPECS SPECS 20. 4000A, 480V, 3-PHASE BUS DUCT, REFER TO SPECIFICATIONS FOR
VFD VFD VFD VFD
480V 480V 480V 480V 150B 150D SEE SPECS 151B 151D SEE SPECS 152B 152D SEE SPECS 153B 153D SEE SPECS 480V 480V 480V DETAILED EQUIPMENT REQUIREMENTS.
30KVA 30KVA 30KVA 30KVA 30KVA 30KVA 15KVA
21. PARALLELING SWITCHGEAR. REFER TO SPECIFICATIONS FOR
Y 208/120V
Y 208/120V
Y 208/120V
Y 208/120V
Y 208/120V
Y 208/120V
Y 208/120V
DETAILED EQUIPMENT REQUIREMENTS.

3 22. SUBMIT DIMENSIONED PLAN SHOWING ELECTRICAL GEAR WITH


3 3 3 REQUIRED CLEARANCES AND SERVICE SPACE AROUND
SUPPLY RETURN SUPPLY RETURN SUPPLY RETURN SUPPLY RETURN EQUIPMENT IN MECHANICAL #C1053 AND ELECTRICAL #C1054 TO
10 10 10 10 66.3FLA 34FLA 74FLA 23.2FLA 54.5FLA 26.8FLA 54.5FLA 26.8FLA 10 10 10
143A 144A 148A 149A 156A 157A 158A
9/25/2019 5:31:44 PM

ENGINEER FOR APPROVAL PRIOR TO SUBMITTING GEAR


SUBMITTALS.
(N) AHU-1 (IN MECHANICAL (N) AHU-2 (IN MECHANICAL (N) AHU-3 (IN MECHANICAL (N) AHU-4 (IN MECHANICAL
(N) (N) (N) (N) #B2000, #B2000, #B2000, #B2000, (N) (N) (N) 23. FURNISH AND INSTALL (1)-CAT6 CABLE FROM SECTION 10 -
E4PA E4PB 144B E5PA E5PB 149B PENTHOUSE) PENTHOUSE) PENTHOUSE) PENTHOUSE) E2PC E2PD E2PE MASTER CONTROL CABINET AND NEAREST COMMUNICATIONS
143B 148B 156B 157B 158B

DRAWING NUMBER
208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V OUTLET.
7 7 7 7 7

E-602

ELECTRICAL
3P,4W 3P,4W 7 3P,4W 3P,4W 7 3P,4W 3P,4W 3P,4W
110A 110A 110A 110A 110A 110A 60A 24. FURNISH AND INSTALL CENTRAL UNINTERRUPTIBLE EMERGENCY
MCB MCB MCB MCB MCB MCB MCB LIGHTING INVERTER, SINGLE PHASE, 277V INPUT/OUTPUT WITH 4
SPD 10KAIC 10KAIC SPD SPD 10KAIC 10KAIC SPD SPD 10KAIC SPD 10KAIC SPD 10KAIC OUTPUT BREAKERS, 90-MINUTE RATED BATTERY BACKUP
CAPACITY AT RATED LOAD, UL 924 LISTED, 3KW MINIMUM FOR L1E,
(N) SPD-E4PA (N) SPD-E4PB (N) SPD-E5PA (N) SPD-E5PB (N) SPD-E2PC (N) SPD-E2PD (N) SPD- 10KW MINIMUM FOR L2E, CONTROLLED POWER MODEL ELU OR
(IN STORAGE (IN CHASE (IN MECHANICAL (IN CHASE (IN ELECTRICAL (IN ELECTRICAL E2PE (IN JANITOR
ROOM #E1016B) #E104) #B2000, PENTHOUSE) #D1014) ROOM #B1028) ROOM #B1028) #B1108) APPROVED EQUAL BY MYERS, DUAL-LITE, EATON.
CONDUIT AND CABLE SCHEDULE (POWER) CONDUIT AND CABLE SCHEDULE (POWER) CONDUIT AND CABLE SCHEDULE (POWER)
CONDUIT CONDUIT CONDUIT
OCPD OCPD OCPD
RACEWAY SOURCE DESTINATION VOLTAGE O Wire POWER CONDUCTORS QUANTITY AND COMMENTS RACEWAY SOURCE DESTINATION VOLTAGE O Wire POWER CONDUCTORS QUANTITY AND COMMENTS RACEWAY SOURCE DESTINATION VOLTAGE O Wire POWER CONDUCTORS QUANTITY AND COMMENTS
AMPS AMPS AMPS
SIZE SIZE SIZE
HIGH VOLTAGE CABLING BY UTILITY.
VFD - AIR HANDLER 'AHU-3' SPECIAL VFD CABLE, REFER TO
ELECTRIC UTILITY FROM NEW ELECTRIC UTILITY PAD RACEWAY, TRENCHING AND/OR 152D AHU-3 RETURN FAN 480 3 3 35A 3#10, #12G. 3/4"C. 216 TRANSFORMER 'TR-G1' DISCONNECT 'DIS-1EPP' 120/240 1 3 100A 3#3, #6G. 1-1/4"C.
10A HV 3 3 BY UTILITY 4"C. (RETURN FAN) SPECIFICATIONS
EXISTING POLE 'UP-1' MOUNT TRANSFORMER 'UT-1' DIRECTIONAL BORING FURNISHED BY
ELECTRICAL CONTRACTOR.
VFD - AIR HANDLER 'AHU-4' LIGHTING PANEL 'E1PP'

DLZ INDIANA, LLC


HIGH VOLTAGE CABLING BY UTILITY. 153A SWITCHBOARD 'ODPB' 480 3 3 70A 3 3#4, #8G. 1"C. 217 DISCONNECT 'DIS-1EPP' 120/240 1 3 100A 3#3, #6G. 1-1/4"C.
(SUPPLY FAN) SUPPLIED WITH GENSET #1
ELECTRIC UTILITY FROM NEW ELECTRIC UTILITY PAD RACEWAY, TRENCHING AND/OR
10B HV 3 3 BY UTILITY 4"C.
EXISTING POLE 'UP-2' MOUNT TRANSFORMER 'UT-1' DIRECTIONAL BORING FURNISHED BY
ELECTRICAL CONTRACTOR. VFD - AIR HANDLER 'AHU-4' SPECIAL VFD CABLE, REFER TO
153B AHU-4 SUPPLY FAN 480 3 3 70A 3 3#4, #8G. 1"C. 220 SWITCHBOARD 'ODPA' TRANSFORMER 'TR-G2' 480 1 3 70A 2#4, #6G. 1"C.
(SUPPLY FAN) SPECIFICATIONS
CABLING AND METER BY UTILITY, METER
NEW ELECTRIC UTILITY PAD
10C NEW UTILITY METER 'M-1' 480 3 3 BY UTILITY 2"C. BASE AND RACEWAY BY E.C.
MOUNT TRANSFORMER 'UT-1' VFD - AIR HANDLER 'AHU-4'
COORDINATE REQUIREMENTS WITH UTILITY. 153C SWITCHBOARD 'ODPB' 480 3 3 35A 3#10, #12G. 3/4"C. 221 TRANSFORMER 'TR-G2' DISCONNECT 'DIS-2EPP' 120/240 1 3 100A 3#3, #6G. 1-1/4"C.
(RETURN FAN)
SWITCHGEAR 'MDPB' 5 SETS; EACH W/ 4#350
50A GENSET 'GEN-1' 480/277 3 4 1500A (5) 3"C
SECTION 7 KCMIL, 1#1/0 G. VFD - AIR HANDLER 'AHU-4' SPECIAL VFD CABLE, REFER TO LIGHTING PANEL 'E2PP'
153D AHU-4 RETURN FAN 480 3 3 35A 3#10, #12G. 3/4"C. 222 DISCONNECT 'DIS-2EPP' 120/240 1 3 100A 3#3, #6G. 1-1/4"C.
(RETURN FAN) SPECIFICATIONS SUPPLIED WITH GENSET #2
SWITCHGEAR 'MDPB' 5 SETS; EACH W/ 4#350
50B GENSET 'GEN-2' 480/277 3 4 1500A (5) 3"C
SECTION 7 KCMIL, 1#1/0 G.
155 SWITCHBOARD 'ODPB' LIGHTING PANEL 'E2HB' 480/277 3 4 200A 4#3/0, #6G. 2"C.
SWITCHGEAR 'MDPB' 5 SETS; EACH W/ 4#350
50C GENSET 'GEN-3' 480/277 3 4 1500A (5) 3"C
SECTION 8 KCMIL, 1#1/0 G.
156 LIGHTING PANEL 'E2HB' TRANSFORMER 'TR-2C' 480 3 3 50A 3#6, #8G. 1"C.
NEW ELECTRIC UTILITY PAD 4000A 10 SETS; EACH W/ 4#500
100 SWITCHGEAR 'MDPA' 480/277 3 4 (10) 4"C
MOUNT TRANSFORMER 'UT-2' (100% RATED) KCMIL, 1#250 KCMIL G.
156A TRANSFORMER 'TR-2C' LIGHTING PANEL 'E2PC' 120/208 3 4 110A 4#2, #6G. 1-1/4"C.
USE SCHEDULE 40 PVC WITH LONG RADIUS
SURGE PROTECTIVE
100A SWITCHGEAR 'MDPA' / SECTION 4 480/277 3 4 100A 4#2, #2G. 1-1/4"C. ELBOWS, CABLING LENGTH SHALL NOT USE SCHEDULE 40 PVC WITH LONG RADIUS
DEVICE 'SPD-MDP' SURGE PROTECTIVE
EXCEED 6'-0". 156B LIGHTING PANEL 'E2PC' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E2PC'
EXCEED 6'-0".
SWITCHGEAR 'MDPB' R
100B SWITCHGEAR 'MDPA' / SECTION 3 480/277 3 4 4000A 4000A, BUS DUCT BUS DUCT EE
SECTION 6 CK IN
157 LIGHTING PANEL 'E2HB' TRANSFORMER 'TR-2D' 480 3 3 50A 3#6, #8G. 1"C. CO

SS D I A N G
I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC
5 SETS; EACH W/ 4#400

E
I ST ER
105 SWITCHGEAR 'MDPB' / SECTION 5 LOAD BANK 480/277 3 4 1600A (5) 3-1/2"C
KCMIL, 1#1/0 KCMIL G.

No.
157A TRANSFORMER 'TR-2D' LIGHTING PANEL 'E2PD' 120/208 3 4 110A 4#2, #6G. 1-1/4"C.
AUTOMATIC TRANSFER SWITCH

EG

IN
111A SWITCHGEAR 'MDPA' / SECTION 2 480/277 3 4 200A 4#3/0, #6G. 2"C.

IN
'ATS-LEGAL' USE SCHEDULE 40 PVC WITH LONG RADIUS R
SURGE PROTECTIVE RV
157B LIGHTING PANEL 'E2PD' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E2PD'
EXCEED 6'-0".
MA FE
AUTOMATIC TRANSFER SWITCH P RO
111B SWITCHGEAR 'MDPB' / SECTION 9 480/277 3 4 200A 4#3/0, #6G. 2"C.
'ATS-LEGAL'
158 LIGHTING PANEL 'E2HB' TRANSFORMER 'TR-2E' 480 3 3 30A 3#10, #12G. 3/4"C.
AUTOMATIC TRANSFER SWITCH
120 DISTRIBUTION PANEL 'DP-L' 480/277 3 4 200A 4#3/0, #6G. 2"C.
'ATS-LEGAL'
158A TRANSFORMER 'TR-2E' LIGHTING PANEL 'E2PE' 120/208 3 4 60A 4#6, #6G. 1"C.
USE SCHEDULE 40 PVC WITH LONG RADIUS
CONDUIT AND CABLE SCHEDULE (CONTROLS)
SURGE PROTECTIVE CONDUIT
120A DISTRIBUTION PANEL 'DP-L' 480/277 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT USE SCHEDULE 40 PVC WITH LONG RADIUS
DEVICE 'SPD-DPL' SURGE PROTECTIVE SOURCE
EXCEED 6'-0". 158B LIGHTING PANEL 'E2PE' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT RACEWAY DESTINATION QUANTITY AND COMMENTS
DEVICE 'SPD-E2PE' SIZE
EXCEED 6'-0".
122 DISTRIBUTION PANEL 'DP-L' TRANSFORMER 'TR-L1P' 480 3 3 30A 3#10, #12G. 3/4"C. (2) #8 AWG - SWGR. CONTROL POWER
SWITCHGEAR 'MDPB' / SECTION 7
300 GENSET 'GEN-1' CONTROL PANEL (1)-3/4"C. & (1)-1"C. (2) BELDEN #8760 - SPEED BIAS & VOLTAGE BIAS
160 SWITCHBOARD 'ODPA' TRANSFORMER 'TR-1A' 480 3 3 110A 4#2, #6G. 1-1/4"C GEN 1 - CONTROLS/PLC
(16) #14 AWG - PRE-ALARM & SHUT-DOWN SIGNAL CONTROLS
122A TRANSFORMER 'TR-L1P' LIGHTING PANEL 'L1P' 120/208 3 4 60A 4#6, #8G. 1"C. (2) #14 AWG - ENGINE START CONTACTS
(2) #14 AWG - E-STOP CONTROL CONTACTS
161 TRANSFORMER 'TR-2C' LIGHTING PANEL 'E1PA' 120/208 3 4 250A 4#250 KCMIL, #4G. 2-1/2"C (4) #14 AWG - SPARE CONDUCTORS
USE SCHEDULE 40 PVC WITH LONG RADIUS
SURGE PROTECTIVE
122B LIGHTING PANEL 'L1P' 120/208 3 4 60A 4#6, #8G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT USE SCHEDULE 40 PVC WITH LONG RADIUS SWITCHGEAR 'MDPB' / SECTION 7
DEVICE 'SPD-L1P' SURGE PROTECTIVE 301 GENSET 'GEN-1' BATTERY CHARG. 3/4"C. (4) #14 AWG - BATTERY CHARGER FAILURE & SPARE
EXCEED 6'-0". 161A LIGHTING PANEL 'E1PA' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT GEN 1 - CONTROLS/PLC
DEVICE 'SPD-E1PA'
EXCEED 6'-0".
123 DISTRIBUTION PANEL 'DP-L' LIGHTING PANEL 'L2H' 3 480/277 3 4 100A 4#3, #6G. 3 1-1/4"C. SWITCHGEAR 'MDPB' / SECTION 7
302 GENSET 'GEN-1' DAY TANK 3/4"C. (8) #14 AWG - HIGH FUEL, LOW FUEL, RUPTURE & SPARE
162 LIGHTING PANEL 'E1PA' LIGHTING PANEL 'E1PB' 120/208 3 4 250A 4#250 KCMIL, #4G. 2-1/2"C GEN 1 - CONTROLS/PLC
(2) #8 AWG - SWGR. CONTROL POWER
124 LIGHTING PANEL 'L2H' TRANSFORMER 'TR-L2P' 480 3 3 30A 3#10, #12G. 3/4"C. SWITCHGEAR 'MDPB' / SECTION 7
USE SCHEDULE 40 PVC WITH LONG RADIUS 303 GENSET 'GEN-2' CONTROL PANEL (1)-3/4"C. & (1)-1"C. (2) BELDEN #8760 - SPEED BIAS & VOLTAGE BIAS
SURGE PROTECTIVE GEN 2 - CONTROLS/PLC
162A LIGHTING PANEL 'E1PB' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT (16) #14 AWG - PRE-ALARM & SHUT-DOWN SIGNAL CONTROLS
DEVICE 'SPD-E1PB'
EXCEED 6'-0". (2) #14 AWG - ENGINE START CONTACTS
124A TRANSFORMER 'TR-L2P' LIGHTING PANEL 'L2P' 120/208 3 4 60A 4#6, #8G. 1"C. (2) #14 AWG - E-STOP CONTROL CONTACTS
165 SWITCHBOARD 'ODPB' LIGHTING PANEL 'E1HA' 480/277 3 4 200A 4#3/0, #6G. 2"C. (4) #14 AWG - SPARE CONDUCTORS
USE SCHEDULE 40 PVC WITH LONG RADIUS
SURGE PROTECTIVE SWITCHGEAR 'MDPB' / SECTION 7
124B LIGHTING PANEL 'L2P' 120/208 3 4 60A 4#6, #8G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT 304 GENSET 'GEN-2' BATTERY CHARG. 3/4"C. (4) #14 AWG - BATTERY CHARGER FAILURE & SPARE
DEVICE 'SPD-L2P' GEN 2 - CONTROLS/PLC
EXCEED 6'-0". 170 SWITCHBOARD 'ODPB' LIGHTING PANEL 'E1HB' 480/277 3 4 200A 4#3/0, #6G. 2"C.
SWITCHGEAR 'MDPB' / SECTION 7
125 DISTRIBUTION PANEL 'DP-L' LIGHTING PANEL 'L1H' 3 480/277 3 4 100A 4#3, #6G. 3 1-1/4"C. 305 GENSET 'GEN-2' DAY TANK 3/4"C. (8) #14 AWG - HIGH FUEL, LOW FUEL, RUPTURE & SPARE
GEN 2 - CONTROLS/PLC
171 LIGHTING PANEL 'E1HB' TRANSFORMER 'TR-1C' 480 3 3 70A 3#4, #8G. 1"C
(2) #8 AWG - SWGR. CONTROL POWER
5 SETS; EACH W/ 4#400 SWITCHGEAR 'MDPB' / SECTION 8
130 SWITCHGEAR 'MDPB' / SECTION 5 SWITCHBOARD 'ODPA' 480/277 3 4 1600A (5) 3-1/2"C 306 GENSET 'GEN-3' CONTROL PANEL (1)-3/4"C. & (1)-1"C. (2) BELDEN #8760 - SPEED BIAS & VOLTAGE BIAS
KCMIL, 1#1/0 KCMIL G. GEN 3 - CONTROLS/PLC
172 TRANSFORMER 'TR-1C' LIGHTING PANEL 'E1PC' 120/208 3 4 175A 4#2/0, #6G. 2"C (16) #14 AWG - PRE-ALARM & SHUT-DOWN SIGNAL CONTROLS
USE SCHEDULE 40 PVC WITH LONG RADIUS (2) #14 AWG - ENGINE START CONTACTS
SURGE PROTECTIVE (2) #14 AWG - E-STOP CONTROL CONTACTS
130A SWITCHBOARD 'ODPA' 480/277 3 4 100A 4#2, #2G. 1-1/4"C. ELBOWS, CABLING LENGTH SHALL NOT USE SCHEDULE 40 PVC WITH LONG RADIUS
DEVICE 'SPD-ODPA' SURGE PROTECTIVE (4) #14 AWG - SPARE CONDUCTORS
EXCEED 6'-0". 172A LIGHTING PANEL 'E1PC' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E1PC'
EXCEED 6'-0". SWITCHGEAR 'MDPB' / SECTION 8
DOMESTIC BOOSTER PUMP 307 GENSET 'GEN-3' BATTERY CHARG. 3/4"C. (4) #14 AWG - BATTERY CHARGER FAILURE & SPARE
133 SWITCHBOARD 'ODPA' 480 3 3 80A 3#3, #6G. 1-1/4"C. GEN 3 - CONTROLS/PLC
'DWBP-1' DISCONNECT
173 LIGHTING PANEL 'E1PC' LIGHTING PANEL 'E1PD' 120/208 3 4 175A 4#2/0, #6G. 2"C
SWITCHGEAR 'MDPB' / SECTION 8
DOMESTIC BOOSTER PUMP DOMESTIC BOOSTER PUMP 308 GENSET 'GEN-3' DAY TANK 3/4"C. (8) #14 AWG - HIGH FUEL, LOW FUEL, RUPTURE & SPARE
133A 480 3 3 80A 3#3, #6G. 1-1/4"C. 3 USE SCHEDULE 40 PVC WITH LONG RADIUS GEN 3 - CONTROLS/PLC
'DWBP-1' DISCONNECT 'DWBP-1' SURGE PROTECTIVE
173A LIGHTING PANEL 'E1PD' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT (4) #14 AWG - EMERGENCY START & LOAD SHED
DEVICE 'SPD-E1PD' AUTOMATIC TRANSFER SWITCH
EXCEED 6'-0". 310 SWITCHGEAR 'MDPB' / SECTION 10 (1)-1"C. (2) #14 AWG - SPARE
CHILLER 'CH-1' DISCONNECT 2 SETS; EACH W/ 3#250 'ATS-LEGAL'
135 SWITCHGEAR 'MDPA' / SECTION 4 480/277 3 3 600A (2) 2-1/2"C. (2) #14 AWG - SPARE
(EXTERIOR) KCMIL, 1#1 G.
175 SWITCHBOARD 'ODPB' LIGHTING PANEL 'E2HA' 480/277 3 4 200A 4#3/0, #6G. 2"C. (1) CAT6 MULTI-STRAND COMM CABLE WITH RJ-45 CONNECTORS
CHILLER 'CH-1' DISCONNECT CHILLER 'CH-1' 2 SETS; EACH W/ 3#250 3
135A 480/277 3 3 600A (2) 2-1/2"C. GROUND MOUNTED LOAD
(EXTERIOR) (EXTERIOR) KCMIL, 1#1 G. 315 SWITCHGEAR 'MDPB' / SECTION 10 1"C. (6) #12 AWG - LOAD DUMP CIRCUIT & STRIP HEATER
176 LIGHTING PANEL 'E2HA' TRANSFORMER 'TR-2A' 480 3 3 70A 3#4, #8G. 1"C BANK
CHILLER 'CH-2' DISCONNECT 2 SETS; EACH W/ 3#250
136 SWITCHGEAR 'MDPB' / SECTION 5 480/277 3 3 600A (2) 2-1/2"C.
(EXTERIOR) KCMIL, 1#1 G. 320 SWITCHGEAR 'MDPB' / SECTION 10 CHILLER #1 (EXTERIOR) 3/4"C. (4) #12 AWG - CHILLER SHUTDOWN / RESTART PERMISSIVE
177 TRANSFORMER 'TR-2A' LIGHTING PANEL 'E2PA' 120/208 3 4 175A 4#2/0, #6G. 2"C
CHILLER 'CH-2' DISCONNECT CHILLER 'CH-2' 2 SETS; EACH W/ 3#250 3
136A 480/277 3 3 600A (2) 2-1/2"C.

09/26/19
(EXTERIOR) (EXTERIOR) KCMIL, 1#1 G. USE SCHEDULE 40 PVC WITH LONG RADIUS 321 SWITCHGEAR 'MDPB' / SECTION 10 CHILLER #2 (EXTERIOR) 3/4"C. (4) #12 AWG - CHILLER SHUTDOWN / RESTART PERMISSIVE

DATE
SURGE PROTECTIVE
177A LIGHTING PANEL 'E2PA' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E2PA'
EXCEED 6'-0".
137 FUTURE CHILLER 'CH-3' (2) #8 AWG - 24VDC CONTROL POWER
SWITCHGEAR 'MDPA' / SECTION 4 480/277 3 3 600A "FUTURE" "FUTURE" 325 SWITCHGEAR 'MDPB' / SECTION 10 24VDC BATTERY CHARGER 1"C.
(FUTURE) (EXTERIOR) (2) #14 AWG - BATTERY CHARGER ALARM
178 LIGHTING PANEL 'E2PA' LIGHTING PANEL 'E2PB' 120/208 3 4 175A 4#2/0, #6G. 2"C
4 SETS; EACH W/ 4#350 AUTOMATIC TRANSFER SWITCH REMOTE ANNUNCIATOR CONTROL WIRING, FIELD COORDINATE WITH GENERATOR SUPPLIER TO
140 SWITCHGEAR 'MDPA' / SECTION 4 SWITCHBOARD 'ODPB' 480/277 3 4 1200A (4) 3"C USE SCHEDULE 40 PVC WITH LONG RADIUS 330 1"C.
KCMIL, 1#1/0 G. SURGE PROTECTIVE 'ATS-LEGAL' 'ATS-ANN' DETERMINE CABLE TYPE/SIZE/QUANTITY REQUIRED
178A LIGHTING PANEL 'E2PB' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E2PB'
USE SCHEDULE 40 PVC WITH LONG RADIUS EXCEED 6'-0".

REVISION
SURGE PROTECTIVE
140A SWITCHBOARD 'ODPB' 480/277 3 4 100A 4#2, #2G. 1-1/4"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-ODPB'
EXCEED 6'-0". 180 SWITCHBOARD 'ODPB' LIGHTING PANEL 'E3H' 480/277 3 4 200A 4#3/0, #6G. 2"C. SCHEDULE CONTROLS NOTES:

3 Addendum #03
1. COORDINATE CONTROL WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIERS
142 SWITCHBOARD 'ODPB' LIGHTING PANEL 'E4H' 480/277 3 4 200A 4#3/0, #6G. 2"C.
181 LIGHTING PANEL 'E3H' TRANSFORMER 'TR-3' 480 3 3 50A 3#6, #8G. 1"C.

143 LIGHTING PANEL 'E4H' TRANSFORMER 'TR-4A' 480 3 3 50A 3#6, #8G. 1"C.
182 TRANSFORMER 'TR-3' LIGHTING PANEL 'E3PA' 120/208 3 4 110A 4#2, #6G. 1-1/4"C.

NO.
143A TRANSFORMER 'TR-4A' LIGHTING PANEL 'E4PA' 120/208 3 4 110A 4#2, #6G. 1-1/4"C. USE SCHEDULE 40 PVC WITH LONG RADIUS
SURGE PROTECTIVE
182A LIGHTING PANEL 'E3PA' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E3PA'
USE SCHEDULE 40 PVC WITH LONG RADIUS EXCEED 6'-0".
SURGE PROTECTIVE
143B LIGHTING PANEL 'E4PA' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E4PA'
EXCEED 6'-0". 185 SWITCHBOARD 'ODPA' TRANSFORMER 'TR-U1' 480 3 3 70A 3#4, #8G. 1"C.

CHK'D: MLH

SEPTEMBER 5, 2019
144 LIGHTING PANEL 'E4H' TRANSFORMER 'TR-4B' 480 3 3 50A 3#6, #8G. 1"C.

1663-1190-90
3#2/0, 1#500 KCMIL N,
186 TRANSFORMER 'TR-U1' DISCONNECT 'DIS-UPS1' 120/208 3 4 175A 3"C.
#6G.
144A TRANSFORMER 'TR-4B' LIGHTING PANEL 'E4PB' 120/208 3 4 110A 4#2, #6G. 1-1/4"C.

PROJECT NUMBER
UNINTERRUPTIBLE POWER 3#2/0, 1#500 KCMIL N,
187 DISCONNECT 'DIS-UPS1' 120/208 3 4 175A 3"C.

DESIGNED: RDW
#6G.

MLH
SUPPLY 'UPS-1'
USE SCHEDULE 40 PVC WITH LONG RADIUS

DRAWN: RDW
SURGE PROTECTIVE
144B LIGHTING PANEL 'E4PB' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E4PB' UNINTERRUPTIBLE POWER UNINTERRUPTIBLE POWER WIRING PER MANUFACTURERS
EXCEED 6'-0". 188 DC - - - - -

APPRV'D:
SUPPLY 'UPS-1' SUPPLY BATTERY CABINET RECOMMENDATION

DATE:
147 SWITCHBOARD 'ODPB' LIGHTING PANEL 'E5H' 480/277 3 4 200A 4#3/0, #6G. 2"C.
UNINTERRUPTIBLE POWER 3#2/0, 1#500 KCMIL N,
189 LIGHTING PANEL 'U1R' 120/208 3 4 175A 3"C.
SUPPLY 'UPS-1' #6G.
148 LIGHTING PANEL 'E5H' TRANSFORMER 'TR-5A' 480 3 3 50A 3#6, #8G. 1"C. USE SCHEDULE 40 PVC WITH LONG RADIUS
SURGE PROTECTIVE
189A LIGHTING PANEL 'U1R' 120/208 3 4 60A 4#6, #8G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-U1R'
EXCEED 6'-0".
148A TRANSFORMER 'TR-5A' LIGHTING PANEL 'E5PA' 120/208 3 4 110A 4#2, #6G. 1-1/4"C.

VIGO COUNTY SECURITY CENTER


190 SWITCHBOARD 'ODPA' TRANSFORMER 'TR-U2' 480 3 3 70A 3#4, #8G. 1"C.
USE SCHEDULE 40 PVC WITH LONG RADIUS
SURGE PROTECTIVE
148B LIGHTING PANEL 'E5PA' 120/208 3 4 60A 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E5PA' 3#2/0, 1#500 KCMIL N,
EXCEED 6'-0". 191 TRANSFORMER 'TR-U2' DISCONNECT 'DIS-UPS2' 120/208 3 4 175A 3"C.
#6G.

CONDUIT AND CABLE SCHEDULE


149 LIGHTING PANEL 'E5H' TRANSFORMER 'TR-5B' 480 3 3 50A 3#6, #8G. 1"C.
UNINTERRUPTIBLE POWER 3#2/0, 1#500 KCMIL N,
192 DISCONNECT 'DIS-UPS2' 120/208 3 4 175A 3"C.
SUPPLY 'UPS-2' #6G.
149A TRANSFORMER 'TR-5B' LIGHTING PANEL 'E5PB' 120/208 3 4 110A 4#2, #6G. 1-1/4"C.
UNINTERRUPTIBLE POWER UNINTERRUPTIBLE POWER WIRING PER MANUFACTURERS
193 DC - - - - -
SUPPLY 'UPS-2' SUPPLY BATTERY CABINET RECOMMENDATION
USE SCHEDULE 40 PVC WITH LONG RADIUS
SURGE PROTECTIVE
149B LIGHTING PANEL 'E5PB' 120/208 3 4 60A 3 4#6, #6G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-E5PB' UNINTERRUPTIBLE POWER 3#2/0, 1#500 KCMIL N,
EXCEED 6'-0". 194 LIGHTING PANEL 'U2R' 120/208 3 4 175A 3"C.

TERRE HAUTE, INDIANA


SUPPLY 'UPS-2' #6G.
VFD - AIR HANDLER 'AHU-1'
150A SWITCHBOARD 'ODPB' 480 3 3 125A 3#1, #6G. 1-1/4"C. USE SCHEDULE 40 PVC WITH LONG RADIUS
(SUPPLY FAN) SURGE PROTECTIVE
194A LIGHTING PANEL 'U2R' 120/208 3 4 60A 4#6, #8G. 1"C. ELBOWS, CABLING LENGTH SHALL NOT
DEVICE 'SPD-U2R'
EXCEED 6'-0".
VFD - AIR HANDLER 'AHU-1' SPECIAL VFD CABLE, REFER TO
150B AHU-1 SUPPLY FAN 480 3 3 125A 3#1, #6G. 1-1/4"C.

A NEW
(SUPPLY FAN) SPECIFICATIONS
195 SWITCHBOARD 'ODPA' LIGHTING PANEL 'K1H' 480/277 3 4 400A 4#500 KCMIL, #1/0G. 3-1/2"C.
VFD - AIR HANDLER 'AHU-1'
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

150C SWITCHBOARD 'ODPB' 480 3 3 70A 3#4, #8G. 1-1/4"C.


(RETURN FAN)
196 LIGHTING PANEL 'K1H' TRANSFORMER 'TR-K1' 480 3 3 110A 3#2, #6G. 1-1/4"C.
VFD - AIR HANDLER 'AHU-1' SPECIAL VFD CABLE, REFER TO
150D AHU-1 RETURN FAN 480 3 3 70A 3#4, #8G. 1-1/4"C.
(RETURN FAN) 3 SPECIFICATIONS
197 TRANSFORMER 'TR-K1' LIGHTING PANEL 'K1L' 120/208 3 4 250A 4#250 KCMIL, #4G. 2-1/2"C.
VFD - AIR HANDLER 'AHU-2'
151A SWITCHBOARD 'ODPB' 480 3 3 100A 3#3, #6G. 1"C.
(SUPPLY FAN)
198 LIGHTING PANEL 'K1L' LIGHTING PANEL 'K2L' 120/208 3 4 200A 4#3/0, #6G. 2"C.
VFD - AIR HANDLER 'AHU-2' SPECIAL VFD CABLE, REFER TO
151B AHU-2 SUPPLY FAN 480 3 3 100A 3#3, #6G. 1"C.
(SUPPLY FAN) SPECIFICATIONS
201 LIGHTING PANEL 'K1H' TRANSFORMER 'TR-K2' 480 3 3 50A 3#6, #8G. 1"C.
VFD - AIR HANDLER 'AHU-2'
151C SWITCHBOARD 'ODPB' 480 3 3 30A 3#10, #12G. 3/4"C.
(RETURN FAN)
202 TRANSFORMER 'TR-K2' LIGHTING PANEL 'K3L' 120/208 3 4 110A 4#2, #6G. 1-1/4"C.
VFD - AIR HANDLER 'AHU-2' SPECIAL VFD CABLE, REFER TO
151D AHU-2 RETURN FAN 480 3 3 30A 3#10, #12G. 3/4"C.
(RETURN FAN) SPECIFICATIONS
210 SWITCHBOARD 'ODPA' TRANSFORMER 'TR-G3' 480 1 3 70A 2#4, #6G. 1"C.
VFD - AIR HANDLER 'AHU-3'
152A SWITCHBOARD 'ODPB' 480 3 3 70A 3#4, #8G. 1"C.
(SUPPLY FAN)
211 TRANSFORMER 'TR-G3' DISCONNECT 'DIS-3EPP' 120/240 1 3 100A 3#3, #6G. 1-1/4"C.
9/25/2019 5:37:09 PM

VFD - AIR HANDLER 'AHU-3' SPECIAL VFD CABLE, REFER TO


152B AHU-3 SUPPLY FAN 480 3 3 70A 3#4, #8G. 3 1"C.
(SUPPLY FAN) SPECIFICATIONS LIGHTING PANEL 'E3PP'
212 DISCONNECT 'DIS-3EPP' 120/240 1 3 100A 3#3, #6G. 1-1/4"C.
SUPPLIED WITH GENSET #3
VFD - AIR HANDLER 'AHU-3'
152C SWITCHBOARD 'ODPB' 480 3 3 35A 3#10, #12G. 3/4"C.

DRAWING NUMBER
(RETURN FAN)
215 SWITCHBOARD 'ODPA' TRANSFORMER 'TR-G1' 480 1 3 70A 2#4, #6G. 1"C.

E-603

ELECTRICAL
SCHEDULE NOTES:

1. ELECTRIC UTILITY = DUKE ENERGY


MECHANICAL EQUIPMENT - ELECTRICAL CONNECTION SCHEDULE
GENERAL NOTES DESCRIPTION
VOLTS
ELECTRICAL DATA
o KW FLA HP
CIRCUIT (*)
DESIGNATION AMPS
O.C.P.
POLE
CONDUCTORS CONDUIT
DISCONNECT
BY
STARTER
BY
DRAWING
LOCATION
REMARK / DISC
OR STARTER TYPE E.C. - CONTRACTOR SHALL FURNISH AND INSTALL, SIZE AS SHOWN. SEE REMARKS FOR SIZE
A. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHERS M.C. - STARTER/DISCONNECT TO BE PROVIDED BY EQUIPMENT SUPPLIER, REFER TO MECHANICAL/PLUMBING SCHEDULES.
2 3 7
DIVISIONS/TRADES AS NECESSARY TO FIELD VERIFY ELECTRICAL AIR HANDLER 'AHU-1' (CKT1 - SUPPLY) 480 3 --- 66.3 --- ODPB-9 125 3 3#1, 1#6 GND. 1-1/4"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * * MFGR - INDICATES DISCONNECT INTEGRAL TO UNIT BY MANUFACTURER

DLZ INDIANA, LLC


REQUIREMENTS FOR MECHANICAL EQUIPMENT (OR OTHER 2 3 6
DIVISIONS/TRADES EQUIPMENT) SUBMITTED FOR ENGINEER AIR HANDLER 'AHU-1' (CKT2 - RETURN) 480 3 --- 34 --- ODPB-10 70 3 3#4, 1#8 GND. 1-1/4"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * *
1
REVIEW/APPROVAL. 1 (* ) - FURNISH AND INSTALL 125VAC, 20A, 1-POLE MANUAL MOTOR
AIR HANDLER 'AHU-1' (CKT3 - RECEPT) 120 1 --- 8.0 --- E5PA-8 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #B2000, DRAWING E-204 *
STARTER WITH TOGGLE DISCONNECT IN NEMA 1 ENCLOSURE.
B. EQUIPMENT SUBMITTALS OR SUBSTITUES WITH DIFFERENT FURNISH WITH RED (RUN) PILOT LIGHT.
ELECTRICAL CONNECTION REQUIREMENTS SHALL BE THE
RESPONSIBILITY OF ALL CONTRACTORS (ELECTRICAL AND/OR 1 2
AIR HANDLER 'AHU-2' (CKT1 - LIGHTS) 120 1 --- 5.22 --- E5PA-9 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #B2000, DRAWING E-204 * (* ) - UNIT PROVIDED WITH STARTER/DISCONNECT.
MECHANICAL AND/OR OTHER DIVISIONS/TRADES) TO FIELD
STARTER/DISCONNECT TO BE MOUNTED/WIRED BY CONTRACTOR.
COORDINATE PRIOR TO SUBMITTING FOR ENGINEER 2 3 5
AIR HANDLER 'AHU-2' (CKT2 - SUPPLY) 480 3 --- 74 --- ODPB-5 100 3 3#3, 1#6 GND. 1"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * *
REVIEW/APPROVAL; PROVIDE ALL NECESSARY MODIFICATIONS 3
2 3 4 (* ) - UNIT PROVIDED WITH STARTER/DISCONNECT (VFD).
NECESSARY FOR ELECTRICAL CONNECTIONS (I.E. BREAKERS, AIR HANDLER 'AHU-2' (CKT3 - RETURN) 480 3 --- 23.2 --- ODPB-6 30 3 3#10, 1#12 GND. 3/4"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * *
CABLE, CONDUIT, ETC.) AS NECESSARY FOR A COMPLETE SYSTEM STARTER/DISCONNECT TO BE MOUNTED/WIRED BY CONTRACTOR.
AT NO ADDITIONAL COST TO THE OWNER. 2 3 4 FURNISH AND INSTALL SPECIAL VFD CABLE BETWEEN VFD AND
AIR HANDLER 'AHU-2' (CKT 4 - EN. WH.) 480 3 --- 1.52 --- E5H(31,33,35) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * *
UNIT PER SPECIFICATIONS. FURNISH AND INSTALL 3/4"C. BETWEEN
C. ENGINEER SHALL NOT BE REPSONISBLE FOR RE-ENGINEERING FOR 1 VFD DRIVE AND DISCONNECT FOR INTERLOCK WIRING, PROVIDE
AIR HANDLER 'AHU-2' (CKT5 - RECEPT) 120 1 --- 8.0 --- E5PA-10 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #B2000, DRAWING E-204 *
THESE AFOREMENTIONED ELECTRICAL MODIFICATIONS; WHERE WIRING PER MANUFACTURER'S RECOMMENDATION.
REQUIRED, CONTRACTOR SHALL REIMBURSE ENGINEER FOR ANY 4
AND ALL ENGINEERING MODIFICATIONS NECESSARY PRIOR TO (* ) - 600V NON-FUSED, 30A, 3-POLE, HEAVY DUTY DISCONNECT IN NEMA
REVIEW/APPROVAL OF SUBMITTALS BY ENGINEER. 1 1 ENCLOSURE.
AIR HANDLER 'AHU-3' (CKT1 - LIGHTS) 120 1 --- 5.22 --- E5PA-11 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #B2000, DRAWING E-204 *
2 3 5 5
D. ELECTRICAL CONTRACTOR SHALL SUBMIT AIR HANDLER 'AHU-3' (CKT2 - SUPPLY) 480 3 --- 54.5 --- ODPB-7 70 3 3#4, 1#8 GND. 1"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * * (* ) - 600V NON-FUSED, 60A, 3-POLE, HEAVY DUTY DISCONNECT IN NEMA
PANELBOARD/SWITCHBOARD SHOP DRAWINGS FOR ENGINEER 1 ENCLOSURE.
2 3 4
REVIEW/APPROVAL ONLY AFTER EQUIPMENT FOR ALL AIR HANDLER 'AHU-3' (CKT3 - RETURN) 480 3 --- 26.8 --- ODPB-8 35 3 3#8, 1#10 GND. 3/4"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * *
6 R
EE
DIVISIONS/TRADES HAVE BEEN REVIEWED/APPROVED. SHOP (* ) - 600V NON-FUSED, 100A, 3-POLE, HEAVY DUTY DISCONNECT IN NEMA
2 3 4 CK IN
DRAWING SUBMITTALS SHALL REFLECT ALL NECESSARY AIR HANDLER 'AHU-3' (CK4 - EN. WH.) 480 3 --- 1.71 --- E5H(37,39,41) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * * CO

SS D I A N G
1 ENCLOSURE.

I ON A L E N
PE60018676
D

A
MODIFICATIONS (I.E. BREAKERS) AS AFOREMENTIONED.

STATE OF
L . H I TC

E
1 7

I ST ER
AIR HANDLER 'AHU-3' (CK5 - RECEPT) 120 1 --- 8.0 --- E5PA-12 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #B2000, DRAWING E-204 * (* ) - 600V NON-FUSED, 200A, 3-POLE, HEAVY DUTY DISCONNECT IN NEMA

No.
1 ENCLOSURE.
3

EG

IN
8

IN
1 (* ) - UNIT IS CORD AND PLUG. FURNISH AND INSTALL 20A, 120V DUPLEX
R
AIR HANDLER 'AHU-4' (CKT1 - LIGHTS) 120 1 --- 5.22 --- E5PA-13 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #B2000, DRAWING E-204 * RV
RECEPTACLE NEAR UNIT (I.E. 12" AWAY AND 12" ABOVE FROM THE MA FE
AIR HANDLER 'AHU-4' (CKT2 - SUPPLY) 480 3 --- 54.5 --- ODPB-11 70 3 3#4, 1#8 GND. 1"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204
2 3 5
* * * UNITS HEATER SHEILD). P RO

2 3 4 9
AIR HANDLER 'AHU-4' (CKT3 - RETURN) 480 3 --- 26.8 --- ODPB-12 35 3 3#8, 1#10 GND. 3/4"C. E.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * * (* ) - 600V, 20A, 2-POLE MANUAL STARTING SWITCH WITH THERMAL
2 3 4 OVERLOAD, RED (RUN) LED PILOT LIGHT AND (1) NO/NC CONTACT,
AIR HANDLER 'AHU-4' (CKT4 - EN. WH.) 480 3 --- 1.71 --- E5H(32,34,36) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. MECHANICAL #B2000, DRAWING E-204 * * * MOTOR RATED.
1 10
AIR HANDLER 'AHU-4' (CKT5 - RECEPT) 120 1 --- 8.0 --- E5PA-14 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #B2000, DRAWING E-204 * (* ) - REFER TO TYPICAL VAV BOX WIRING SCHEMATIC, DETAIL #9 ON
3 DRAWING E-803.
11
2 19 (* ) - PROVIDE 3/4"C. BETWEEN UNIT AND ASSOCIATED AC UNIT FOR
CHILLER 'CH-1' 480 3 --- 495MCA --- MDPA-4 600 3 2 SETS 3#250MCM, 1#1 GND. (2)-2-1/2"C. M.C. M.C. EXTERIOR, DRAWING E-201-C * *
INTERLOCK WIRING. PROVIDE WITH PULLSTRING. WIRING BY
1 TEMPERATURE CONTROLS CONTRACTOR. VERIFY EXACT
CHILLER 'CH-1' (RECEPT) 120 1 --- 8.0 --- E1PB-34 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- EXTERIOR, DRAWING E-201-C *
LOCATIONS OF EQUIPMENT BEFORE ROUGH-IN.
2 19
CHILLER 'CH-2' 480 3 --- 495MCA --- MDPA-5 3 600 3 2 SETS 3#250MCM, 1#1 GND. (2)-2-1/2"C. M.C. M.C. EXTERIOR, DRAWING E-201-C * * 12
(* ) - 600V NON-FUSED, 30A, 3-POLE, HEAVY DUTY DISCONNECT IN NEMA
1
CHILLER 'CH-2' (RECEPT) 120 1 --- 8.0 --- E1PB-36 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- EXTERIOR, DRAWING E-201-C * 3R ENCLOSURE.
19 13
REMOTE EVAPORATOR 'REV-1' 120 1 --- --- --- E1PB-38 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- MECHANICAL #C1053, DRAWING E-201-C * (* ) - 600V NON-FUSED, 30A, 2-POLE, HEAVY DUTY DISCONNECT IN NEMA
19 3R ENCLOSURE.
REMOTE EVAPORATOR 'REV-2' 120 1 --- --- --- E1PB-40 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- MECHANICAL #C1053, DRAWING E-201-C *
14
(* ) - INDOOR UNIT (DS) IS POWERED BY OUTDOOR UNIT (ACC). TOTAL
SYSTEM POWER RATING AS SHOWN. PROVIDE CONNECTION TO
ELEC. WALL HEATER 'EWH-1' 120 1 1.5 12.5 --- E5PB-33 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- INTERLOCK #D1013, DRAWING E-201-D INDOOR UNIT PER MANUFACTURER REQUIREMENTS.
15
ELEC. WALL HEATER 'EWH-2' 120 1 1.5 12.5 --- E2PB-29 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- INTERLOCK #B1063, DRAWING E-201-B (* ) - UNIT IS CORD AND PLUG, REFER TO PLAN FOR LOCATION.
16
ELEC. WALL HEATER 'EWH-3' 120 1 1.5 12.5 --- E4PB-33 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- INTERLOCK #E1013, DRAWING E-201-E (* ) - PUMPS ARE PRE-WIRED TO CONTROL PANEL.
17
ELEC. WALL HEATER 'EWH-4' 120 1 1.5 12.5 --- E5PB-42 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- STAFF TOILET #D0001, DRAWING E-201-E (* ) - MAKE FINAL CONNECTION TO TRAP PRIMER FROM CIRCUIT SHOWN
ON PLANS.
ELEC. WALL HEATER 'EWH-5' 120 1 1.5 12.5 --- E4PB-42 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- STAFF TOILET #E0001, DRAWING E-201-E
18
(* ) - SAFETY DISCONNECT SWITCH FOR SMOKE CONTROL EXHAUST FAN
ELEC. WALL HEATER 'EWH-6' 120 1 1.5 12.5 --- E4PA-40 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- INTERLOCK #D1016, DRAWING E-201-D SHALL BE EQUIPPED WITH ONE (1) NO/NC AUXILIARY CONTACT KIT.
WIRE NC (FAIL SAFE) CONTACT BACK TO SMOKE CONTROL (VIA FAN
ELEC. WALL HEATER 'EWH-7' 120 1 1.5 12.5 --- E4PA-38 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- INTERLOCK #E1017, DRAWING E-201-E
STARTER); CONTACT SHALL BE MONITORED BY SMOKE CONTROL TO
VERIFY SAFETY DISCONNECT IS IN THE CLOSED POSITION AS PART
OF SMOKE CONTROL ANNUNICIATION AT MASTER CONTROL ROOM
2 3 4 #B1016 FOR FIREFIGHTERS. REFER TO IBC SECTION 900 AND NFPA 92
CHILLED WATER PUMP 'CWP-1' 480 3 --- --- 15 E1HA(31,33,35) 30 3 3#10, 1#12 GND. 3/4"C. E.C. M.C. MECHANICAL #C1053, DRAWING E-201-C * * *
FOR DETAILED SMOKE CONTROL REQUIREMENTS.
2 3 4
CHILLED WATER PUMP 'CWP-2' 480 3 --- --- 15 E1HA(37,39,41) 30 3 3#10, 1#12 GND. 3/4"C. E.C. M.C. MECHANICAL #C1053, DRAWING E-201-C * * * 19
(* ) - PROVIDE 3/4"C. BETWEEN CHILLER AND REMOTE EVAPORATOR FOR
2 3 4
HOT WATER PUMP 'HWP-1' 480 3 --- --- 5 E1HA(32,34,36) 20 3 3#10, 1#12 GND. 3/4"C. E.C. M.C. MECHANICAL #C1053, DRAWING E-201-C * * * COMMUNICATIONS CABLING. FURNISH AND INSTALL CABLING AS
2 3 4 RECOMMENDED BY MANUFACTURER.
HOT WATER PUMP 'HWP-2' 480 3 --- --- 5 E1HA(38,40,42) 20 3 3#10, 1#12 GND. 3/4"C. E.C. M.C. MECHANICAL #C1053, DRAWING E-201-C * * *
20
(* ) - CIRCUITS E1HA(14,16,18) AND E1HA(20,22,24).
HOT WATER RECIRC PUMP 'HWRP-1' 480 3 --- --- 1.0 VARIES *20 30 3 3#10, 1#12 GND. 3/4"C. E.C. MFGR MECHANICAL #C1053, DRAWING E-201-C
21
16 (* ) - UNIT TO BE DELETED IN ALTERNATE BID. REFER TO DRAWING E-201-A
DOMESTIC BOOSTER PUMP 'DWBP-1' 480 3 --- 64 (3)-15 ODPA-10 3 80 3 3#3, 1#6 GND. 1-1/4"C. MFGR MFGR MECHANICAL #C1053, DRAWING E-201-C *
FOR MORE INFORMATION.
15
SEWAGE PUMP 'SP-1' 120 1 --- --- 4/10 E5PB-34, E4PB-34 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECH. #D0002& #E0002, DRAWING E-201-D&E *
15
SEWAGE PUMP 'SP-2' 120 1 --- --- 1/2 E5PB-36, E4PB-36 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECH. #D0002& #E0002, DRAWING E-201-D&E *

09/26/19
DATE
8
INFRARED HEATER 'IR-1' 120 1 --- 1.8 --- E3PA-28 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- VEH. SALLYPORT #A1000, DRAWING E-201-A *
8
INFRARED HEATER 'IR-2' 120 1 --- 1.8 --- E3PA-24 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- VEH. SALLYPORT #A1000, DRAWING E-201-A *
21 8
INFRARED HEATER 'IR-3' * 120 1 --- 1.8 --- E3PA-26 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- VEH. SALLYPORT #A1000, DRAWING E-201-A *
21 8
INFRARED HEATER 'IR-4' * 120 1 --- 1.8 --- E3PA-22 3 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- VEH. SALLYPORT #A1000, DRAWING E-201-A *

REVISION
ELEC. UNIT HEATER 'EUH-1' 208 1 3 14.5 --- E3PA(27,29) 20 2 2#12, 1#12 GND. 3/4"C. MFGR --- OPEN STORAGE #A2000, DRAWING E-201-A

3 Addendum #03
DOOR AIR CURTAIN 'DAC-1' 480 3 --- 9.6 --- E1HA(19,21,23) 20 3 3#12, 1#12 GND. 3/4"C. MFGR --- EVIDENCE STOR. #A1002, DRAWING E-201-A

2 18
SMOKE EXHAUST FAN 'SEF 1-1' 480 3 --- 2.1 1 L2H(8,10,12) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 1-2' 480 3 --- 1.6 3/4 L2H(14,16,18) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *

NO.
2 18
SMOKE EXHAUST FAN 'SEF 1-3' 120 1 --- 9.8 1/2 L2P-9 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 1-4' 480 3 --- 1.6 3/4 L2H(20,22,24) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18

CHK'D: MLH
SMOKE EXHAUST FAN 'SEF 1-5' 480 3 --- 2.1 1 L2H(19,21,23) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *

SEPTEMBER 5, 2019

1663-1190-90
2 18
SMOKE EXHAUST FAN 'SEF 1-6' 480 3 --- 1.6 3/4 L2H(13,15,17) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 2-1' 480 3 --- 2.1 1 L2H(25,27,29) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *

PROJECT NUMBER
2 18

DESIGNED: RDW
SMOKE EXHAUST FAN 'SEF 2-2' 480 3 --- 1.6 3/4 L2H(31,33,35) 20 3 3#12, 1#12 GND. M.C. M.C. ROOF, DRAWING E-203 * *

MLH
3/4"C.

DRAWN: RDW
2 18
SMOKE EXHAUST FAN 'SEF 2-3' 120 1 --- 9.8 1/2 L2P-11 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *

APPRV'D:
2 18
SMOKE EXHAUST FAN 'SEF 2-4' 480 3 --- 1.6 3/4 L2H(37,39,41) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *

DATE:
2 18
SMOKE EXHAUST FAN 'SEF 2-5' 480 3 --- 2.1 1 L2H(32,34,36) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 2-6' 480 3 --- 1.6 3/4 L2H(26,28,30) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 3' 480 3 --- 1.6 3/4 L2H(43,45,47) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18

VIGO COUNTY SECURITY CENTER


SMOKE EXHAUST FAN 'SEF 4' 120 1 --- 5.8 1/4 L2P-8 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 5' 120 1 --- 5.8 1/4 L2P-10 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *

MECHANICAL EQUIPMENTELECTRICAL
2 18
SMOKE EXHAUST FAN 'SEF 6A' 480 3 --- 1.6 3/4 L2H(50,52,54) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 6B' 480 3 --- 1.6 3/4 L2H(44,46,48) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *
2 18
SMOKE EXHAUST FAN 'SEF 6C' 480 3 --- 1.6 3/4 L2H(38,40,42) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 * *

CONNECTION SCHEDULE
2
EXHAUST FAN 'EF-1' 120 1 --- 5.8 1/4 E1PA-46 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *

TERRE HAUTE, INDIANA


2
EXHAUST FAN 'EF-2' 120 1 --- 2.6 1/10 E1PB-53 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-3' 120 1 --- 2.6 1/10 E5PA-22 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2

A NEW
EXHAUST FAN 'EF-4' 120 1 --- 2.6 1/10 E1PB-49 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-5' 120 1 --- 2.6 1/10 E1PC-36 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

2
EXHAUST FAN 'EF-6A' 480 3 --- 3.4 2 E3H(19,21,23) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-6B' 480 3 --- 3.4 2 E3H(20,22,24) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-7' 120 1 --- 9.8 1/2 E1PB-51 20 3 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-8' 480 3 --- 2.35 -- E1HA(13,15,17) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. WELDING #C1056B, DRAWING E-201-C *
2
EXHAUST FAN 'EF-9' 120 1 --- 2.85 1/4 E1PB-50 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-10' 120 1 --- 2.85 1/4 E1PB-52 20 1 2#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-ALT-A' 480 3 --- 1.6 3/4 E3H(19,21,23) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *
2
EXHAUST FAN 'EF-ALT-B' 480 3 --- 9.8 3/4 E3H(20,22,24) 20 3 3#12, 1#12 GND. 3/4"C. M.C. M.C. ROOF, DRAWING E-203 *

15
WATER SOFTNER 'WS-1' 120 1 --- --- --- E1PB-33 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #C1053, DRAWING E-201-C *
9/25/2019 5:37:11 PM

15
REVERSE OSMOSIS 'RO-1' - TANK/HEAD 120 1 --- 3 --- E1PB-58 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #C1053, DRAWING E-201-C *
-
REVERSE OSMOSIS 'RO-1' - GUARD 208 1 --- --- --- E1PB(54,56) 30 2 2#10, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #C1053, DRAWING E-201-C *
15

DRAWING NUMBER
DIGITAL THERMO. MIXING VALVE 'TMV-1' 120 1 --- --- --- E1PB-43 20 1 2#12, 1#12 GND. 3/4"C. E.C. --- MECHANICAL #C1053, DRAWING E-201-C *

E-604

ELECTRICAL
17
TRAP PRIMER 'TP-1' 120 1 .006 --- --- E1PB-45 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- MECHANICAL #C1053, DRAWING E-201-C *
17
TRAP PRIMER 'TP-2' 120 1 .006 --- --- E1PB-48 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- MECHANICAL #C1053, DRAWING E-201-C *
17
TRAP PRIMER 'TP-3' 120 1 .006 --- --- E5PA-18 20 1 2#12, 1#12 GND. 3/4"C. MFGR --- MECHANICAL #B2000, DRAWING E-203 *
Lighting Fixture Schedule
TYPE Count LAMP WATTAGE VOLTAGE DESCRIPTION BASIS OF DESIGN EQUAL MANUFACTURER AS APPROVED BY ENGINEER EQUAL MANUFACTURER AS APPROVED BY ENGINEER TYPE COMMENTS

A1 117 LED 30 W 277 V 2' X 4' LED GRID LAY IN BASKET STYLE TROFFER, 3000 LUMENS, 4000K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE, METAL DIFFUSER WITH .075' DIA. ROUND HOLES, LITHONIA 2AVL4G-30L-MDR-MVOLT-EZ1-LP840 EATON METALUX 24RDI-30-UNV-L840-CD1-U HUBBELL COLUMBIA LSTE-24-40-VW-G-MPO-ED1-U LAY IN
ACRYLIC DIFFUSER BACKING

DLZ INDIANA, LLC


A2 68 LED 41 W 277 V 2' X 4' LED GRID LAY IN BASKET STYLE TROFFER, 4000 LUMENS, 4000K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE, METAL DIFFUSER WITH .075' DIA. ROUND HOLES, LITHONIA 2AVL4G-40L-MDR-MVOLT-EZ1-LP840 EATON METALUX 24RDI-40-UNV-L840-CD1-U HUBBELL COLUMBIA LSTE-24-40-LW-G-MPO-ED1-U LAY IN
ACRYLIC DIFFUSER BACKING
AA1 29 LED 34 W 277 V WALL MOUNTED ARCHITECTURAL AREA LIGHT, 34W, 3730 LUMENS, 600mA DRIVER, 1 LIGHT SQUARES, TYPE IV FORWARD THROW DISTRIBUTION, FINISH PER EATON McGRAW EDISON GWC-AF(600Ma)-01-LED-E1-T4FT-XX-8030-F277-600 MOUNT ON WALL WITH BOTTOM AT +17'-4" AFG UNLESS OTHERWISE NOTED.
ARCHITECT, 80CRI, 3000K COLOR, 277V, 1P66 RATED.
AA2 13 LED 34 W 277 V WALL MOUNTED ARCHITECTURAL AREA LIGHT, 34W, 3638 LUMENS, 600mA DRIVER, 1 LIGHT SQUARES, TYPE II DISTRIBUTION, FINISH PER ARCHITECT, 80CRI, EATON McGRAW EDISON GWC-AF(600Ma)-01-LED-E1-T2-XX-8030-F277-600 LITHONIA DSXW SERIES AS AN APPROVED EQUAL. HUBBELL LIGHTING WDS SERIES AS AN APPROVED EQUAL. MOUNT ON WALL WITH BOTTOM AT +12'-0" AFG UNLESS OTHERWISE NOTED.
3000K COLOR, 277V, 1P66 RATED.
B1 264 LED 23 W 277 V 2' X 4', LAY-IN GRID TROFFER WITH FLAT 0.156 ACRYLIC LENS, 3000 LUMENS, 4000K, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER LITHONIA 2GTL-4-30L-FW-A19-MVOLT-EZ1-LP840-PAF LAY IN
COAT FINISH. PAINTED AFTER FABRICATION
B2 40 LED 30 W 277 V 2' X 4', LAY-IN GRID TROFFER WITH FLAT 0.156 ACRYLIC LENS, 4000 LUMENS, 4000K, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER LITHONIA 2GTL-4-40L-FW-A19-MVOLT-EZ1-LP840-PAF EATON METALUX 24GR-FA-LD5-42-A19/156-UNV-L840-CD1-PAF-U HUBBELL COLUMBIA LJT-24-40-MW-G-FA-A19-ED1-U-PAF LAY IN
COAT FINISH. PAINTED AFTER FABRICATION
B3 1 LED 36 W 277 V 2' X 4', LAY-IN GRID TROFFER WITH FLAT 0.156 ACRYLIC LENS, 4800 LUMENS, 4000K, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER LITHONIA 2GTL-4-48L-FW-A19-MVOLT-EZ1-LP840-PAF EATON METALUX 24GR-FA-LD5-48-A19/156-UNV-L840-CD1-PAF-U HUBBELL COLUMBIA LJT-24-40-ML-G-FA-A19-ED1-U-PAF LAY IN
COAT FINISH. PAINTED AFTER FABRICATION
C1 9 LED 18 W 277 V 2' X 2', LAY-IN GRID TROFFER WITH FLAT 0.156 ACRYLIC LENS, 2000 LUMENS, 4000K, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER LITHONIA 2GTL-2-20L-FW-A19-MVOLT-EZ1-LP840-PAF EATON METALUX 22GR-FA-LD5-20-A19/156-UNV-L840-CD1-PAF-U HUBBELL COLUMBIA LJT-22-40-MW-G-FA-A19-ED1-U-PAF LAY IN
COAT FINISH. PAINTED AFTER FABRICATION
C1F 4 LED 18 W 277 V 2' X 2', LAY-IN GRID TROFFER WITH FLAT 0.156 ACRYLIC LENS, 2000 LUMENS, 4000K, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER LITHONIA 2GTLF-2-20L-FW-A19-MVOLT-EZ1-LP840-PAF EATON METALUX 22GR-FA-LD5-20-A19/156-UNV-L840-CD1-PAF-U, DF-22-W HUBBELL COLUMBIA LJT-22-40-MW-SM-FA-A19-ED1-U-PAF LAY IN
COAT FINISH. PAINTED AFTER FABRICATION, FLANGE-MOUNTED
C2 35 LED 29 W 277 V 2' X 2', LAY-IN GRID TROFFER WITH FLAT 0.156 ACRYLIC LENS, 3300 LUMENS, 4000K, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER LITHONIA 2GTL-2-33L-FW-A19-MVOLT-EZ1-LP840-PAF EATON METALUX 22GR-FA-LD5-32-A19/156-UNV.L840-CD1-PAF-U HUBBELL COLUMBIA LJT-22-40-ML-G-FA-A19-ED1-U-PAF LAY IN
COAT FINISH. PAINTED AFTER FABRICATION
CC1 8 LED 19 W 277 V 2' LONG LINEAR WALL MOUNT WITH DIRECT (DOWN) WALL GRAZE LIGHTING, 19W, 1732 LUMENS, 3000K COLOR, 80CRI, UNIVERSAL VOLTAGE, DIFFUSE LENS, 3" ARCHITECTURAL AREA LIGHTING RN-D-X-2-7-3K8-WG-DL-UNV-F3-EMF1-XX CALIFORNIA ACCENT LIGHTING ALS600T-ASM-XX-3.0K-8W-10V-BF-WET-UNV-2FT BARTCO BSW214-2-30-ID-H-ASYM / DISTRIBUTION ARM MOUNT / SN FINISH MOUNT ON WALL WITH BOTTOM AT +12'-0" AFG UNLESS OTHERWISE NOTED.
FIXED MOUNTING BRACKET AND FINISH AS SELECTED BY ARCHITECT. / ALS600T-AA-XX-3"
CC2 12 LED 19 W 277 V 2' LONG LINEAR WALL MOUNT WITH DIRECT (DOWN) PENDANT MOUNTED SYMMETRICAL DISTRIBUTION LIGHT, 19W, 1732 LUMENS, 3000K COLOR, 80CRI, ARCHITECTURAL AREA LIGHTING RN-D-X-2-7-3K8-SM-DL-UNV-PSW12-EMF1-XX CALIFORNIA ACCENT LIGHTING ALS800T-F-XX-3.0K-8W-10V-BF-WET-277V-2FT / BARTCO BSW214-2-30-ID-H / STEM MOUNT / SN FINISH SURFACE MOUNTED
UNIVERSAL VOLTAGE, DIFFUSE LENS, 12" PENDANT MOUNTING BRACKET AND FINISH AS SELECTED BY ARCHITECT. PENDANT MOUNT R
EE
D1 6 LED 19 W 277 V 6" DIAMETER LED FIXTURE, RECESSED DOWNLIGHT, 16GA STEEL, 1500 LUMENS, 4000K, SEMI-SPECULAR REFLECTOR, WHITE DIE CAST TRIM RING, MEDIUM GOTHAM LIGHTING EVO-6AR-40/15-MD-LSS-MVOLT-EZ1-TRW EATON PORTFOLIO LD6B-15-D010-EU6B-1020-80-40-6LB-M-1-H-HB26 HUBBELL PRESCOLITE LTR-6RD-H-SL-15L-DM1 / LTR-6RD-T-SL-40K-8-MD-SS-WT-B24 FLUSH MOUNTED IN CEILING CK IN
CO

SS D I A N G
DISTRIBUTION.

I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC

E
I ST ER
D2 6 LED 19 W 277 V 6" DIAMETER LED FIXTURE, RECESSED DOWNLIGHT, 1000 LUMENS, 4000K, SPECULAR REFLECTOR, WHITE DIE CAST TRIM RING, RECESSED LENS, SUITABLE FOR GOTHAM LIGHTING EVO-40/10-6DFR-MVOLT EATON HALO PD610ED010 / PDM6A840 / 61VW HUBBELL PRESCOLITE LB6LEDA10L-40K-WH-DBXQL FLUSH MOUNTED IN CEILING

No.
WET LOCATION (SHOWER RATED)
EE1 3 LED 277 V 48"L. x 3-3/8"H. x 2-3/4"W., LINEAR LED LIGHT, EXTRUDED ALUMINUM HOUSING WITH ALUMINUM END CAPS, CUSTOM COLOR POWDER-COAT FINISH (FINISH INSIGHT LIGHTING MVWII-15-40K-ASYU-SMSCW-48"-INT1-NO-CC-CRF CALIFORNIA ACCENT LIGHTING ALS450T-F-XX-3.0K-9W-BF-WET-277V-4FT / OR APPROVED PERFORMANCE EQUAL. CUSTOM FINISH SHALL MATCH SIGN. SUBMIT COLOR CHART WITH ALL AVAILABLE COLORS

EG

IN
COLOR SHALL MATCH THE FINISH COLOR OF THE SIGN TO BE ILLUMINATED), CORROSION RESISTANT FINISH OPTICS, 15WATTS PER FOOT LIGHT SOURCE, 4000K ALS450T-MC-2 FOR IFNAL SELECTION BY ARCHITECT. FIELD COORDINATE MINIMUM LENGTH OF AC JUMPER

IN
R
COLOR, 82+CRI, 3686 LUMENS, 120V, NON-DIMMABLE, TEMPERED GLASS LENS, SUITABLE FOR -20 DEGREES C TO 50 DEGREES C AMBIENT TEMPERATURE, CABLES REQUIRED PRIOR TO PROCUREMENT FOR FEED THROUGH WIRING TO MULTIPLE RV
5-YEAR WARRANTY, SURFACE MOUNT, CONCEALED WIRE MOUNTING OPTION. FIXTURES AND FOR LEADER CABLE. FIXTURE REQUIRES A WET RATED JUNCTION BOX FOR
MA FE
P RO
CONCEALED WIRE CONNECTION.
F1 58 LED 10 W 277 V 2' LED SURFACE STRIPLIGHT WITH FLAT DIFFUSE LENS, 1500 LUMENS, 80CRI, 4000K COLOR, GENERAL DISTRIBUTION, DIMMING DRIVER, PIR INTEGRAL LITHONIA CLX-L24-1500LM-HEF-FDL-MVOLT-EZ1-40K-80CRI-MSD7-XX OR APPROVED PERFORMANCE EQUAL OR APPROVED PERFORMANCE EQUAL. WALL MOUNT, COORDINATE WITH MECHANICAL AND PLUMBING EQUIPMENT IN CHASE
OCCUPANCY SENSOR AND FINISH BY ARCHITECT.
F2 8 LED 19 W 277 V 4' LED SURFACE STRIPLIGHT WITH FLAT DIFFUSE LENS, 3000 LUMENS, 80CRI, 4000K COLOR, GENERAL DISTRIBUTION, PREMIUM EFFICIENCY WITH WHITE FINISH LITHONIA EATON METALUX 4ILED-LD5-5-W-FL/UPL-UNV-L840-CD1-U AYC-CHAIN/SET-U HUBBELL COLUMBIA EQUAL MOUNT WITH BOTTOM AT +12'-0" AFF UNLESS OTHERWISE NOTED.
AND WIDE DECORATIVE 48" REFLECTOR WITH UPLIGHT. CLX-L48-3000LM-HEF-FDL-MVOLT-EZ1-40K-80CRI-WH-CLXRWU48WH-ZACVH
F3 17 LED 19 W 277 V 4' LED SURFACE STRIPLIGHT WITH FLAT DIFFUSE LENS, 3000 LUMENS, 80CRI, 4000K COLOR, GENERAL DISTRIBUTION, PREMIUM EFFICIENCY WITH WHITE FINISH LITHONIA EATON METALUX 4ILED-LD5-5-W-FL-UNV-L840-CD1-U AYC-CHAIN/SET-U HUBBELL COLUMBIA EQUAL FIXTURE TO BE SURFACE MOUNTED ON BOTTOM OF FLOOR, PRECAST, STRUCTURE, ETC.
AND WIDE DECORATIVE 48" REFLECTOR. CLX-L48-3000LM-HEF-FDL-MVOLT-EZ1-40K-80CRI-WH-CLXRW48WH-ZACVH
F4 61 LED 32 W 277 V 4' LED SURFACE STRIPLIGHT WITH FLAT DIFFUSE LENS, 5000 LUMENS, 80CRI, 4000K COLOR, GENERAL DISTRIBUTION, PREMIUM EFFICEINCY WITH WHITE FINISH LITHONIA EATON METALUX 4ILED-LD5-5-W-FL/UPL-UNV-L840-CD1-U AYC-CHAIN/SET-U HUBBELL COLUMBIA EQUAL MOUNT WITH BOTTOM AT +12'-0" AFF UNLESS OTHERWISE NOTED.
AND WIDE DECORATIVE 48" REFLECTOR WITH UPLIGHT. CLX-L48-5000LM-HEF-FDL-MVOLT-EZ1-40K-80CRI-WH-CLXRWU48WH-ZACVH
F5 9 LED 32 W 277 V 4' LED SURFACE STRIPLIGHT WITH FLAT DIFFUSE LENS, 5000 LUMENS, 80CRI, 4000K COLOR, GENERAL DISTRIBUTION, PREMIUM EFFICEINCY WITH WHITE FINISH LITHONIA EATON METALUX 4ILED-LD5-5-W-FL-UNV-L840-CD1-U AYC-CHAIN/SET-U HUBBELL COLUMBIA EQUAL FIXTURE TO BE SURFACE MOUNTED ON BOTTOM OF FLOOR, PRECAST, STRUCTURE, ETC.
AND WIDE DECORATIVE 48" REFLECTOR. CLX-L48-5000LM-HEF-FDL-MVOLT-EZ1-40K-80CRI-WH-CLXRW48WH-ZACVH
F6 36 LED 32 W 277 V 4' LED SURFACE STRIPLIGHT WITH FLAT DIFFUSE LENS, 7000 LUMENS, 80CRI, 4000K COLOR, GENERAL DISTRIBUTION, PREMIUM EFFICEINCY WITH WHITE FINISH LITHONIA EATON METALUX 4ILED-LD5-7-W-FL/UPL-UNV-L840-CD1-U AYC-CHAIN/SET-U HUBBELL COLUMBIA EQUAL MOUNT WITH BOTTOM AT +11'-0" AFF UNLESS OTHERWISE NOTED.
AND WIDE DECORATIVE 48" REFLECTOR WITH UPLIGHT. CLX-L48-7000LM-HEF-FDL-MVOLT-EZ1-40K-80CRI-WH-CLXRWU48WH-ZACVH
FF1 5 LED 21 W 277 V DECORATIVE ADA COMPLIANT UP/DOWN LIGHT, 21W, 1078 LUMENS, 80CRI, 3000K COLOR, VERY NARROW 9 DEGREE OPTICS, 277V WITH FUSE AND FINISH AS LUMINIS LIGHTING SY302-L2L15NR-R9-277V-XX-FS-2K3 LIGMAN LIGHTING UMV-30031-2X10W-N-W30-XX-12/277 / FUSE G LIGHTING GL-6540-C-R2-R2 MOUNT ON WALL WALL WITH BOTTOM AT +6'-9" AFG UNLESS OTHERWISE NOTED.
SELECTED BY ARCHITECT.
G1 7 LED 20 W 277 V 2' X 2' LED LAY IN GRID BASKET STYLE TROFFER, 2000 LUMENS, 4000K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE, METAL DIFFUSER WITH .075' DIA. ROUND HOLES, LITHONIA 2AVL2G-20L-MDR-MVOLT-EZ1-LP840 EATON METALUX 22RDI-20-UNV-L840-CD1-U HUBBELL COLUMBIA LSTE-22-40-MW-G-MPO-ED1-U LAY IN
ACRYLIC DIFFUSER BACKING
G2 21 LED 31 W 277 V 2' X 2' LED LAY IN GRID BASKET STYLE TROFFER, 3000 LUMENS, 4000K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE, METAL DIFFUSER WITH .075' DIA. ROUND HOLES, LITHONIA 2AVL2G-30L-MDR-MVOLT-EZ1-LP840 EATON METALUX 22RDI-30-UNV-L840-CD1-U HUBBELL COLUMBIA LSTE-22-40-ML-G-MPO-ED1-U LAY IN
ACRYLIC DIFFUSER BACKING
G3 1 LED 41 W 277 V 2' X 2' LED LAY IN GRID BASKET STYLE TROFFER, 4000 LUMENS, 4000K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE, METAL DIFFUSER WITH .075' DIA. ROUND HOLES, LITHONIA 2AVL2G-40L-MDR-MVOLT-EZ1-LP840 EATON METALUX 22RDI-40-UNV-L840-CD1-U HUBBELL COLUMBIA LSTE-22-40-VL-G-MPO-ED1-U LAY IN
ACRYLIC DIFFUSER BACKING
GG1 2 LED 21 W 277 V 4' LONG EXTERIOR LINEAR SURFACE MOUNTED LIGHT, 7W / FT, 2950 LUMENS, 82 CRI, 3000K COLOR, 100 DEGREE X 100 DEGREE DISTRIBUTION, 277V, NO INSIGHT LIGHTING MVWII-7-30K-100 DEGREE-SMS-48-277-NO-XX CALIFORNIA ACCENT LIGHTING ALS450T-F-XX-3.0K-9W-BF-WET-277V-4FT / LUMENPULSE LOG SERIES AS AN APPROVED EQUAL FIXTURE TO BE SURFACE MOUNTED ON TOP OF VESTIBULE AND AIMED AT CENTER OF
DIMINNG WITH FINISH AS SELECTED BY ARCHITECT. ALS450T-MC-1 LOGO.
J1 4 LED 33 W 277 V 8" x 54", ROUGH SERVICE FIXTURE, SURFACE MOUNT, 4000 LUMENS, 3500K COLOR, CLEAR POLYCARBONATE LENS, MEDIUM DISTRIBUTION, UL LISTED FOR WET LITHONIA VAP-4000LM-PCL-MD-MVOLT-GZ10-35K-80CRI-STSL FIXTURE TO BE SURFACE MOUNTED U.O.N.
LOCATION, STAINLESS STEEL TAMPER RESISTANT LATCHES, IP65/66 RATED.
L1 89 LED 50 W 277 V 2' X 4', GRID LAYIN IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR POLYCARBONATE KENALL RMCD4-TG-0/0-45L40K-DCC-1-DV-2/J-1 EATON FAIL-SAFE FSR-TG-X-24-4-LD4-3LO-40-UNV-81/88-EDD1 / VRSD NEWSTAR LIGHTING 57-R-24-B/B-L2(MOD 4300LMS)-40-1C-4/B-UN INSTALL IN SECURITY GRID
OUTER LENS, CONTINUOUS CONCEALED PIANO HINGE, 14 GUAGE COLD ROLLED STEEL HOUSING WITH WHITE POWDER COAT FINISH. TAMPER RESISTANT TORX
SCREWS WITH SCREWDRIVER ACCESSORY.
L1B 52 LED 74 W 277 V 2' X 4', GRID LAYIN IMPACT AND VANDAL RESISTANT FIXTURE, 67 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR POLYCARBONATE KENALL RMCD4-TG-0/0-67L40K-DCC-1-DV-2/J-1 EATON FAIL-SAFE FSR-TG-X-24-4-LD4-3STD-40-UNV-81/88-EDD1 / VRSD NEWSTAR LIGHTING 57-R-24-B/B-L-40-1C-4/B-UN INSTALL IN SECURITY GRID
OUTER LENS, CONTINUOUS CONCEALED PIANO HINGE, 14 GUAGE COLD ROLLED STEEL HOUSING WITH WHITE POWDER COAT FINISH. TAMPER RESISTANT TORX
SCREWS WITH SCREWDRIVER ACCESSORY.
L2 22 LED 51 W 277 V 2' X 2', GRID LAYIN IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR POLYCARBONATE KENALL RMCD2-TG-0/0-45L40K-DCC-1-DV-2/J-1 EATON FAIL-SAFE FSR-TG-X-24-2-LD4-3STD-40-UNV-81/88-EDD1 / VRSD NEWSTAR LIGHTING 57-R-22-B/B-L2(MOD 3700LMS)-40-1C-4/B-UN INSTALL IN SECURITY GRID
OUTER LENS, CONTINUOUS CONCEALED PIANO HINGE, 14 GUAGE COLD ROLLED STEEL HOUSING WITH WHITE POWDER COAT FINISH. TAMPER RESISTANT TORX
SCREWS WITH SCREWDRIVER ACCESSORY.
L2B 42 LED 74 W 277 V 2' X 2', GRID LAYIN IMPACT AND VANDAL RESISTANT FIXTURE, 67 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR POLYCARBONATE KENALL RMCD2-TG-0/0-67L40K-DCC-1-DV-2/J-1 EATON FAIL-SAFE FSR-TG-X-24-2-LD4-4STD-40-UNV-81/88-EDD1 / VRSD NEWSTAR LIGHTING 57-R-22-B/B-L2(MOD 5300LMS)-40-1C-4/B-UN INSTALL IN SECURITY GRID
OUTER LENS, CONTINUOUS CONCEALED PIANO HINGE, 14 GUAGE COLD ROLLED STEEL HOUSING WITH WHITE POWDER COAT FINISH. TAMPER RESISTANT TORX
SCREWS WITH SCREWDRIVER ACCESSORY.
M1 25 LED 50 W 277 V 12" X 48", SURFACE CEILING MOUNT, IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR KENALL SDSA-4-0/0-45L40K-DDC-DV-2/J-1 ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE SHALL BE FILLED
POLYCARBONATE OUTER LENS, CONTINUOUS HINGED LENS FRAME WITH WHITE POWDER COAT FINISH, 14 GUAGE COLD ROLLED STEEL HOUSING WITH WHITE COMPLETELY. FIXTURE TO BE SURFACE MOUNTED ON BOTTOM OF PRECAST WHERE
POWDER COATE FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY. REMOVABLE GEAR TRAY. UL LISTED FOR DAMP LOCATION. INDICATED ON PLANS.
M1A 8 LED 50 W 277 V 12" X 48", SURFACE CEILING MOUNT, IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR KENALL SDSA-4-3/3-45L40K-DDC-DV-2/J-1-WL EATON FAIL-SAFE FUSL-X-12-4-LD4-2STD-40-UNV-81/88-EDD1-WL-SSP NEWSTAR LIGHTING WARN4-H-L2(MOD 4000LMS)-40-1-4/B-UN-TH-WL ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE SHALL BE FILLED
POLYCARBONATE OUTER LENS, CONTINUOUS HINGED LENS FRAME WITH WHITE POWDER COAT FINISH, 14 GUAGE STAINLESS STEEL HOUSING WITH WHITE COMPLETELY. FIXTURE TO BE SURFACE MOUNTED ON BOTTOM OF PRECAST WHERE
POWDER COATE FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY. REMOVABLE GEAR TRAY. UL LISTED FOR WET LOCATION INDICATED ON PLANS.
M1N 25 LED 50 W 277 V 12" X 48", SURFACE CEILING MOUNT, IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR KENALL SDSA-4-0/0-45L40K-DDC-DV-2/J-1-DLN EATON FAIL-SAFE FUSL-X-12-4-LD4-2STD-40-UNV-81/88-EDD1-LLNDL NEWSTAR LIGHTING WARN4-B-L2(MOD 4000LMS)-40-1-4/B-UN-TH-DLN ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE SHALL BE FILLED
POLYCARBONATE OUTER LENS, CONTINUOUS HINGED LENS FRAME WITH WHITE POWDER COAT FINISH, 14 GUAGE COLD ROLLED STEEL HOUSING WITH WHITE COMPLETELY. FIXTURE TO BE SURFACE MOUNTED ON BOTTOM OF PRECAST WHERE
POWDER COATE FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY. REMOVABLE GEAR TRAY. UL LISTED FOR DAMP LOCATION, LED INDICATED ON PLANS.
NIGHT LIGHT.
N1N 1 LED 50 W 277 V 8" X 48", SURFACE CORNER WALL MOUNT, IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" KENALL CD4-0/0-45L40K-DCC-DV-2/J-1-RGT-DLN EATON FAIL-SAFE FCC-X-4-LD4-2LO-40-UNV-81/88-EDD1-LLNL NEWSTAR LIGHTING 554-B-L2(MOD 3700LMS)-40-1-4/B-UN-TH-DLN-RGT ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE SHALL BE FILLED
CLEAR POLYCARBONATE OUTER LENS, CONTINUOUS HINGED LENS FRAME WITH WHITE POWDER COATE FINISH, 14 GUAGE COLD ROLLED STEEL HOUSING WITH COMPLETELY. FIXTURE TO BE SURFACE MOUNTED BELOW PRECAST IN CORNER WHERE
WHITE POWDER COAT FINISH. LED NIGHT LIGHT, TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY. REMOVABLE GEAR TRAY. UL LISTED INDICATED ON PLANS.
FOR DAMP LOCATION.

09/12/19
09/26/19
DATE
N2 4 LED 74 W 277 V 8" X 48", IMPACT AND VANDAL RESISTANT FIXTURE, 67 WATT, 5000K, SURFACE CORNER WALL MOUNT, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" KENALL CD4-0/0-1-67L50K-DCC-1-DV-2/J-1-RGT EATON FAIL-SAFE FCC-X-4-LD4-2STD-40-UNV-81/88-EDD1 NEWSTAR LIGHTING 554-B-L2-40-1-4/B-UN-TH-RGT ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE SHALL BE FILLED
CLEAR POLYCARBONATE OUTER LENS, CONTINUOUS HINGED LENS FRAME WITH WHITE POWDER COATE FINISH, 14 GUAGE COLD ROLLED STEEL HOUSING WITH COMPLETELY. FIXTURE TO BE SURFACE MOUNTED BELOW PRECAST IN CORNER WHERE
WHITE POWDER COAT FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY. REMOVABLE GEAR TRAY. UL LISTED FOR DAMP LOCATION. INDICATED ON PLANS.
N2N 120 LED 74 W 277 V 8" X 48", SURFACE CORNER WALL MOUNT, IMPACT AND VANDAL RESISTANT FIXTURE, 67 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" KENALL CD4-0/0-67L40K-DCC-DV-2/J-1-RGT-DLN EATON FAIL-SAFE FCC-X-4-LD4-2STD-40-UNV-81/88-EDD1-LLNL NEWSTAR LIGHTING 554-B-L2-40-1-4/B-UN-TH-DLN-RGT ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE SHALL BE FILLED
CLEAR POLYCARBONATE OUTER LENS, CONTINUOUS HINGED LENS FRAME WITH WHITE POWDER COATE FINISH, 14 GUAGE COLD ROLLED STEEL HOUSING WITH COMPLETELY. FIXTURE TO BE SURFACE MOUNTED BELOW PRECAST IN CORNER WHERE
WHITE POWDER COAT FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY. LED NIGHT LIGHT. REMOVABLE GEAR TRAY. UL LISTED INDICATED ON PLANS.
FOR DAMP LOCATION.
N3N 180 LED 99 W 277 V 8" X 48", SURFACE CORNER WALL MOUNT, IMPACT AND VANDAL RESISTANT FIXTURE, 90 WATT, 4000K, 0.125" PRISMATIC POLYCARBONATE INNER LENS, 0.500" KENALL CD4-0/0-90L40K-DCC-DV-2/J-1-RGT-DLN EATON FAIL-SAFE FCC-X-4-LD4-2HI-40-UNV-81/88-EDD1-LLNL NEWSTAR LIGHTING 554-B-L3(MOD 6800 LMS)-40-1-4/B-UN-TH-DLN-RGT ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE SHALL BE FILLED

REVISION
CLEAR POLYCARBONATE OUTER LENS, CONTINUOUS HINGED LENS FRAME WITH WHITE POWDER COATE FINISH, 14 GUAGE COLD ROLLED STEEL HOUSING WITH COMPLETELY. FIXTURE TO BE SURFACE MOUNTED BELOW PRECAST IN CORNER WHERE
WHITE POWDER COAT FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY. LED NIGHT LIGHT. REMOVABLE GEAR TRAY. UL LISTED INDICATED ON PLANS.

1 Addendum #01
3 Addendum #03
FOR DAMP LOCATION.
P1 40 LED 31 W 277 V 4' INDUSTRIAL LED LINEAR BAY, 31 WATT, 4000K COLOR, 4000 LUMENS, WIDE DISTRIBUTION, HEAVY DUTY WIREGUARD, UNIVSERSAL VOLTAGE, ONE 0-10V EATON METALUX 4-ILED-LD5-5-W-WG-UNV-L840-CD1 LITHONIA LIGHTING UFIT-L48-4000LM-SEF-MVOLT-GZ10-40K-80CRI-WH-WGMS8Z HUBBELL COLUMBIA RLW-4-40-ML-FA-W-ED-U-RLWWG4 FIXTURE TO BE CHAIN MOUNTED WITH BOTTOM AT +14'-0" AFF.
DIMMING DRIVER, COLD ROLLED STEEL FULL BODY HOUSING.
R1 76 LED 44 W 277 V 8" X 48", SURFACE MOUNT, VANDAL RESISTANT FIXTURE, 4489 LUMENS, 4000K COLOR, OPAL POLYCARBONATE LENS, ELECTRONIC NON-DIMMABLE DRIVER, EATON FAIL-SAFE HVSL8-4-LD4-1-HI-40-UNV-O-EDC-1-XX-VRSD-OS1(277V) KENALL MLHA8-48-F-MW-PP-45L40K-DCC-DV-MS NEWSTAR LIGHTING VIC-4-N-L2-40-1C-RW-UN-XX-OC-TH FIXTURE TO BE SURFACE MOUNTED ON WALL AT +8'-0" AFF.
TAMPER RESISTANT TORX SCREWS AND INTEGRATED MOTION/OCCUPANCY SENSOR. FINISH TO BY ARCHITECT.
SA 7 LED 59 W 277 V SINGLE ARCHITECTURAL AREA LIGHT ON 30' POLE, 59W, 5414 LUMENS, 80CRI, 3000K COLOR, 277V, 01 LIGHT SQUARES, TYPE II DISTRIBUTION, FINISH PER EATON McGRAW EDISON GLEON-AF(1A)-01-LED-E1-T2-XX-8030-F277 LITHONIA DSX SERIES AS AN APPROVED EQUAL. HUBBELL BEACON VPS SERIES AS AN APPROVED EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.

NO.
ARCHITECT, ARM MOUNT AND IP66 RATED. POLE: EATON McGRAW EDISON SSA6X30W-XX
POLE: 30' SQUARE STRAIGHT ALUMINUM POLE, 6" SHAFT SIZE, 0.250" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.
SB 20 LED 113 W 277 V SINGLE ARCHITECTURAL AREA LIGHT ON 30' POLE, 113W, 10579 LUMENS, 80CRI, 3000K COLOR, 277V, 02 LIGHT SQUARES, TYPE II DISTRIBUTION, FINISH PER EATON McGRAW EDISON GLEON-AF(1A)-02-LED-E1-T2-XX-8030-F277 LITHONIA DSX SERIES AS AN APPROVED EQUAL. HUBBELL BEACON VPS SERIES AS AN APPROVED EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.
ARCHITECT, ARM MOUNT AND IP66 RATED. POLE: EATON McGRAW EDISON SSA6X30W-XX
POLE: 20' SQUARE STRAIGHT ALUMINUM POLE, 6" SHAFT SIZE, 0.250" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.

CHK'D: MLH

SEPTEMBER 5, 2019
SC 9 LED 59 W 277 V SINGLE ARCHITECTURAL AREA LIGHT ON 30' POLE, 59W, 5550 LUMENS, 80CRI, 3000K COLOR, 277V, 01 LIGHT SQUARES, TYPE IV FORWARD THROW DISTRIBUTION, EATON McGRAW EDISON GLEON-AF(1A)-01-LED-E1-T4FT-XX-8030-F277 LITHONIA DSX SERIES AS AN APPROVED EQUAL. HUBBELL BEACON VPS SERIES AS AN APPROVED EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.

1663-1190-90
FINISH PER ARCHITECT, ARM MOUNT AND IP66 RATED. POLE: EATON McGRAW EDISON SSA6X30W-XX
POLE: 30' SQUARE STRAIGHT ALUMINUM POLE, 6" SHAFT SIZE, 0.250" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.

DESIGNED: MHK,RDW
SD 3 LED 118 W 277 V TWIN ARCHITECTURAL AREA LIGHT ON 30' POLE, 59W, 5550 LUMENS, 80CRI, 3000K COLOR PER HEAD, 277V, 01 LIGHT SQUARES, TYPE IV FORWARD THROW EATON McGRAW EDISON GLEON-AF(1A)-01-LED-E1-T4FT-XX-8030-F277 LITHONIA DSX SERIES AS AN APPROVED EQUAL. HUBBELL BEACON VPS SERIES AS AN APPROVED EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.

DRAWN: MHK,RDW

PROJECT NUMBER
DISTRIBUTION, FINISH PER ARCHITECT, ARM MOUNT AND IP66 RATED. POLE: EATON McGRAW EDISON SSA9X30W-XX
POLE: 30' SQUARE STRAIGHT ALUMINUM POLE, 6-3/4" SHAFT SIZE, 0.250" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.

MLH
SE 2 LED 225 W 277 V SINGLE ARCHITECTURAL AREA LIGHT ON 30' POLE, 225W, 21383 LUMENS, 80CRI, 3000K COLOR, 277V, 04 LIGHT SQUARES, TYPE V WIDE SQUARE DISTRIBUTION, EATON McGRAW EDISON GLEON-AF(1A)-04-LED-E1-5WQ-XX-8030-F277 LITHONIA DSX SERIES AS AN APPROVED EQUAL. HUBBELL BEACON VPS SERIES AS AN APPROVED EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.
FINISH PER ARCHITECT, ARM MOUNT AND IP66 RATED. POLE: EATON McGRAW EDISON SSA4M20W-XX

APPRV'D:
POLE: 30' SQUARE STRAIGHT ALUMINUM POLE, 6" SHAFT SIZE, 0.250" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.

DATE:
SF 8 LED 113 W 277 V SINGLE ARCHITECTURAL AREA LIGHT ON 35' POLE, 113W, 10845 LUMENS, 80CRI, 3000K COLOR, 277V, 02 LIGHT SQUARES, TYPE IV FORWARD THROW EATON McGRAW EDISON GLEON-AF(1A)-02-LED-E1-T4FT-XX-8030-F277 LITHONIA DSX SERIES AS AN APPROVED EQUAL. HUBBELL BEACON VPS SERIES AS AN APPROVED EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.
DISTRIBUTION, FINISH PER ARCHITECT, ARM MOUNT AND IP66 RATED. POLE: EATON McGRAW EDISON SSA9X35W-XX
POLE: 35' SQUARE STRAIGHT ALUMINUM POLE, 6-3/4" SHAFT SIZE, 0.250" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.
SG 8 LED 75 W 277 V SINGLE ROUND ARCHITECTURAL AREA LIGHT ON 15' POLE, 75W, 7336 LUMENS, 80CRI, 3000K COLOR, 277V, 03 LIGHT SQUARES, TYPE II DISTRIBUTION WITH SPILL EATON INVUE MSA-E03-LED-E1-SL2-XX-8030 HUBBELL KIM LIGHTING (FIXTURE), HAPCO (POLE) APPROVED EQUAL OR APPROVED PERFORMANCE EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.
CONTROL, FINISH PER ARCHITECT AND IP66 RATED. POLE: EATON INVUE ARX-4-T-15-N-XX 3
POLE: 15' ROUND STRAIGHT ALUMINUM POLE, 4" SHAFT SIZE, 0.125" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.
SH 1 LED 75 W 277 V SINGLE ROUND ARCHITECTURAL AREA LIGHT ON 15' POLE, 75W, 7128 LUMENS, 80CRI, 3000K COLOR, 277V, 03 LIGHT SQUARES, TYPE IV DISTRIBUTION WITH SPILL EATON INVUE MSA-EO3-LED-E1-SL4-XX-8030 HUBBELL KIM LIGHTING (FIXTURE), HAPCO (POLE) APPROVED EQUAL OR APPROVED PERFORMANCE EQUAL. REFER TO LIGHT POLE FOUNDATION DETAIL #5 ON SHEET E-802 FOR POLE BASE DETAIL.

VIGO COUNTY SECURITY CENTER


CONTROL, FINISH PER ARCHITECT AND IP66 RATED. POLE: EATON INVUE ARX-4-T-15-N-XX
POLE: 15' ROUND STRAIGHT ALUMINUM POLE, 4" SHAFT SIZE, 0.125" THICK WITH FINISH PER ARCHITECT TO MATCH FIXTURE.
SJ 6 LED 25 W 277 V ARCHITECTURAL FLOOD LIGHT, DIE-CAST ALUMINUM HOUSING, 4000K COLOR, 70CRI, 2511 LUMENS, 25 WATTS, ELECTRONIC BALLAST, 4X4 DISTRIBUTION, HUBBELL OUTDOOR LIGHTING FSL-10L-25-4K-7-M-4-K-DB-F; FSL-SPC; LITHONIA DSXF SERIES AS AN APPROVED EQUAL. EATON INVUE LIGHTING VFS SERIES AS AN APPROVED EQUAL. FIXTURE TO MOUNTED ON CONCRETE BASE, REFER TO DETAIL #3 ON SHEET E-802.
VANDAL RESISTANT POLYCARBONATE LENS, TOP/BOTTOM VISOR, 5 YEAR WARRANTY WITH DARK BRONZE FINISH. FSL-VISOR-XX
T1 72 LED 12 W 277 V 4" X 48" DIRECT RECESSED LINEAR FIXTURE, 350 LUMENS / FT, 4000K COLOR, 80 CRI, UNIVERSAL VOLTAGE, 0-10V DIMMING DRIVER, EXTRUDED ALUMINUM FOCAL POINT FSM4L-FL-375LF-40K-1C-UNC-LD1-G1-WH-12 LITHONIA SL4L-LOP-4FT-FLP-XX-80CRI-40-400LMF-MIN1-277V-ZT HUBBELL LITECONTROL 4L-LG-D-4-4-SOF-C1-40K-040-D01-1C-UNV-W1 FLUSH MOUNT IN CEILING
HOUSING IN MATTE WHITE FINISH WITH SATIN FLUSH DIFFUSER.

LIGHT FIXTURE SCHEDULES


V1 2 LED 18 W 277 V 2' X 2', SURFACE MOUNT TROFFER WITH FLAT 0.156 ACRYLIC LENS, 2000 LUMENS, 4000K, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE LITHONIA 2TLX2-20L-FW-A12-MVOLT-EZ1-LP840 EATON METALUX 22GR SERIES AS AN APPROVED EQUAL. HUBBELL COLUMBIA LJT SERIES AS AN APPROVED EQUAL. SURFACE MOUNTED
POWDER COAT FINISH. PAINTED AFTER FABRICATION
W1 12 LED 277 V 4.5" X 48" STRAIGHT AND NARROW DIRECT/INDIRECT LED WALL MOUNT FIXTURE, EXTRUDED ALUMINUM HOUSING, 566.5 LUMENS / 7 WATTS PER FOOT UP AND EATON NEORAY S23-DI-W-1L40-SR-4-DD-U-SI-S93-XX PRUDENTIAL P46-LED4-LO-LO-4'-XX-SAL-D1-SYM-SC-UNV-WM-XX-DM10 HUBBELL LITECONTROL 4L-W-ID-LPA-4-04-SOF-XX-40K-1055-D055-D01-1C-UNV-W1 WALL MOUNT WITH BOTTOM AT +12'-0" AFF.
DOWN, 85+ CRI, 4000K COLOR, SINGLE CIRCUIT, UNIVERSAL VOLTAGE, 0-10V DIMMING DRIVER AND SATIN LAY-IN LENS. FINISH TO BE SELECTED BY ARCHITECT.
W2 7 LED 277 V 4.5" X 48" STRAIGHT AND NARROW DIRECT/INDIRECT LED WALL MOUNT FIXTURE, EXTRUDED ALUMINUM HOUSING, 616 LUMENS / 9 WATTS PER FOOT UP AND EATON NEORAY S23-DI-W-2L40-SR-4-DD-U-SI-S93-XX PRUDENTIAL P46-LED4-MO-MO-4'-XX-SAL-D1-SYM-SC-UNV-WM-XX-DM10 HUBBELL LITECONTROL WALL MOUNT WITH BOTTOM AT +12'-0" AFF.

TERRE HAUTE, INDIANA


DOWN, 85+ CRI, 4000K COLOR, SINGLE CIRCUIT, UNIVERSAL VOLTAGE, 0-10V DIMMING DRIVER AND SATIN LAY-IN LENS. FINISH TO BE SELECTED BY
X1 52 LED 1W VANDAL RESISTANT SINGLE FACE LED EXIT FIXTURE, RED LETTERS, POLYCARBONATE HOUSING, MATTE WHITE FINISH, UNIVERSAL MOUNTING ACCESSORIES. KENALL #METSU-MW-R-DT-XAC-9500-WIREGUARD (WHITE) CEILING, END OR WALL MOUNT AS REQUIRED. PROVIDE ARROWS AS SHOWN ON PLANS. FOR
TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY, UL LISTED FOR WET LOCATION. WHITE WIREGUARD. WALL MOUNTED EXITS, MOUNT 8'-0" AFF U.O.N.
X2 26 LED 1W ARCHITECTURAL LED EXIT FIXTURE, RED LETTERS, DIE-CAST ALUMINUM HOUSING, WHITE FINISH, UNIVERSAL MOUNTING ACCESSORIES. UL LISTED FOR DAMP LITHONIA #LES-W-X-R-120/277 CEILING, END OR WALL MOUNT AS REQUIRED. PROVIDE ARROWS AS SHOWN ON PLANS. FOR
LOCATION. CEILING, END OR WALL MOUNT AS REQUIRED. PROVIDE ARROWS AS SHOWN ON PLANS. WALL MOUNTED EXITS, MOUNT 8'-0" AFF U.O.N.

A NEW
X3A 20 LED 1W RECESSED ARCHITECTURAL EDGE LIT LED EXIT FIXTURE, RED LETTERS, CLEAR BACKGROUND, EXTRUDED ALUMINUM HOUSING WITH WHITE FINISH, SINGLE LITHONIA #EDGR-W-1-R AS SHOWN ON PLANS
FACE. PROVIDE ARROWS AS SHOWN ON PLAN.
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

X3B 1 LED 1W 277 V RECESSED ARCHITECTURAL EDGE LIT LED EXIT FIXTURE, RED LETTERS, CLEAR BACKGROUND, EXTRUDED ALUMINUM HOUSING WITH WHITE FINISH, SINGLE LITHONIA #EDGR-W-1-R EATON SURE-LITES EU-R-6-O-R HUBBELL DUAL-LITE LE-C-D-R-X-W-A AS SHOWN ON PLANS
FACE. PROVIDE ARROWS AS SHOWN ON PLAN.
Y1 18 LED 19 W 277 V 4" X 48" DIRECT/INDIRECT LINEAR PENDANT FIXTURE, 275 LUMENS / FT UP, 275 LUMENS / FT DOWN, 4000K COLOR, 80 CRI, UNIVERSAL VOLTAGE, 0-10V DIMMING FOCAL POINT FSM4BS-FLFL-275DN-275UP-4000K-1C-UNV-LD1-CXXWH-WH-XX MARK ARCHITECTURAL LIGHTING SLOT 4 LED S4LID SERIES AS APPROVED HUBBELL LITECONTROL 4L-P-ID-STD-4-4-SOF-C1-40K-1030-D030-1C-UNV-FAX-W1 PENDANT MOUNT WITH BOTTOM AT +12'-0" AFF.
DRIVER, EXTRUDED ALUMINUM HOUSING IN MATTE WHITE FINISH WITH FLUSH DIFFUSER UP AND DOWN. EQUAL
Z1 10 LED 15 W 120 V ADJUSTABLE BEAM LED TRACK FIXTURE, 15W ADJUSTABLE BEAM, 3500K COLOR, DIMMING DRIVER WITH WHITE FINISH. CONTECT LIGHTING CTL-844-35-D-P LF ILLUMINATION TRA19B-J-13C-8035-M-D11-WW BRUCK 250430-21LM-35K-90-120-ELV-WH-ECOWH TRACK MOUNT
Z1A 4 --- SINGLE CIRCUIT LINE VOLTAGE TRACK, 120V, WHITE FINISH, LEGTH AS SHOWN ON PLANS. CONTECT LT-X-S JUNO LIGHTING R SERIES TRACK BRUCK ECO TRACK, WHITE SURFACE MOUNT

Steel Cell Lighting Fixture Schedule LIGHT FIXTURE SCHEDULE NOTES:


TYPE Count LAMP WATTAGE VOLTAGE DESCRIPTION BASIS OF DESIGN EQUAL MANUFACTURER AS APPROVED BY ENGINEER EQUAL MANUFACTURER AS APPROVED BY ENGINEER TYPE COMMENTS
A. ALL LAY-IN FIXTURES TO HAVE EARTHQUAKE CLIPS AND BE SUPPORTED WITH SAFETY
M1A-SC 77 LED 50 W 12" X 48", IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 5000K, SURFACE CEILING MOUNT, 0.125" KENALL SDSA-4-3/3-1-45L50K-DDC-1-DV-2/J-1-WL-DLN EATON FAIL-SAFE AS AN APPROVED EQUAL. NEWSTAR LIGHTING AS AN APPROVED EQUAL. ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE CHAIN, SEE SPECIFICATIONS.
PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR POLYCARBONATE OUTER LENS, CONTINUOUS SHALL BE FILLED COMPLETELY. FIXTURE TO BE SURFACE MOUNTED ON
9/25/2019 5:31:54 PM

HINGED LENS FRAME WITH WHITE POWDER COAT FINISH, 14 GUAGE STAINLESS STEEL HOUSING WITH BOTTOM OF PRECAST WHERE INDICATED ON PLANS. B. ALL FIXTURES SHALL BE U.L. LISTED.
WHITE POWDER COATE FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER ACCESSORY.
REMOVABLE GEAR TRAY. UL LISTED FOR WET LOCATION WITH LED NIGHT LIGHT. C. VERIFY WITH UTILITY AND APPLY FOR ANY REBATES AVAILABLE FOR THE USE OF LED
M1N-SC 215 LED 50 W 12" X 48", IMPACT AND VANDAL RESISTANT FIXTURE, 45 WATT, 4000K, SURFACE CEILING MOUNT, 0.125" KENALL SDSA-4-0/0-1-45L40K-DDC-1-DV-2/J-1-DLN EATON FAIL-SAFE AS AN APPROVED EQUAL. NEWSTAR LIGHTING AS AN APPROVED EQUAL. ALL JOINTS IN FIXTURE AND BETWEEN FIXTURE AND MOUNTING SURFACE LIGHTING ON PROJECT. REBATES TO BE GIVEN TO OWNER.
PRISMATIC POLYCARBONATE INNER LENS, 0.500" CLEAR POLYCARBONATE OUTER LENS, CONTINUOUS SHALL BE FILLED COMPLETELY. FIXTURE TO BE SURFACE MOUNTED ON

DRAWING NUMBER
HINGED LENS FRAME WITH WHITE POWDER COAT FINISH, 14 GUAGE COLD ROLLED STEEL HOUSING BOTTOM OF PRECAST WHERE INDICATED ON PLANS.

E-606

ELECTRICAL
WITH WHITE POWDER COATE FINISH. TAMPER RESISTANT TORX SCREWS WITH SCREWDRIVER
ACCESSORY. REMOVABLE GEAR TRAY. UL LISTED FOR DAMP LOCATION, LED NIGHT LIGHT.
3
2-F DAYROOM #E1060 TV 75 OHM COAX 75 OHM COAX SPARE SPARE 75 OHM COAX 75 OHM COAX SPARE 75 OHM COAX SPARE
CABLE (TYPICAL) CABLE (TYPICAL) CABLE (TYPICAL) CABLE (TYPICAL) CABLE (TYPICAL)

2-E DAYROOM #E1070 TV SPARE ATTORNEY #C1068 TV SPARE TV CID WORK GROUP #C1040

DLZ INDIANA, LLC


3 3
2-D DAYROOM #E1080 TV SPARE JUDGE #C1069 TV SPARE TV CHIEF DEPUTY'S OFFICE #C1019

2-C DAYROOM #E1090 TV TV CONF. ROOM #E1005 VIDEO ARRAIGNMENT #C1071 TV TV DAYROOM #B1037 TV CHIEF DEPUTY'S OFFICE #C1018

2-B DAYROOM #E1110 TV TV 2-K DAYROOM #E1020 VIDEO ARRAIGNMENT #C1070 TV TV LAUNDRY #C1065 TV SHERIFF'S OFFICE #C1016

2-A DAYROOM #E1120 TV TV 2-J DAYROOM #E1030 MEDICAL WAITING #B1122 TV TV JAIL COMMANDER #C1077 TV CONFERENCE ROOM #C1015

2 INDOOR/OUTDOOR REC #E1009 TV TV 2-H DAYROOM #E1040 MALE MEDICAL WAITING #B1095 TV TV ASSISTANT JAIL COMMANDER #C1078 TV WAITING #C1000

2 CLASSROOM #E1008 TV TV 2-G DAYROOM #E1050 FEMALE DAYROOM #B1112 TV TV MATRON #C1080 TV WAITING #B1002

R
8-WAY INPUT INPUT 8-WAY 8-WAY INPUT INPUT 8-WAY INPUT 8-WAY EE
SPLITTER SPLITTER SPLITTER SPLITTER SPLITTER CK IN
CO

SS D I A N G
I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC

E
I ST ER
No.
IT ROOM #E1004 IT ROOM #E1004 ELECTRICAL #B1028 ELECTRICAL #B1028 ELECTRICAL #C1004

EG

IN
IN
R
RV
MA FE
P RO

IT ROOM #D1010 IT ROOM #D1010 MAIN DATA FRAME #B1060 CLOSET #C1035

8-WAY INPUT INPUT 8-WAY INPUT 6-WAY INPUT 6-WAY


SPLITTER SPLITTER SPLITTER SPLITTER

1 CLASSROOM #D1006 TV TV 1-G DAYROOM #D1080 INPUT 8-WAY TV AGENCY #C1021


(TYPICAL) SPLITTER

1 INDOOR/OUTDOOR REC #D1005 TV TV 1-H DAYROOM #D1090 TV SQUAD ROOM #C1027


CATV
1-A DAYROOM #D1020 TV TV 1-J DAYROOM #D1110 AMPLIFIER TV FITNESS #C1028

3
1-B DAYROOM #D1030 TV TV 1-K DAYROOM #D1120 TV TRANSPORTATION WAITING #B1062 TV FITNESS #C1028
3
1-C DAYROOM #D1040 TV TV CONF. ROOM #D1009 MAIN DATA FRAME #B1060 SPARE 3 TV FITNESS #C1028

1-D DAYROOM #D1050 TV SPARE SPARE TV BREAKROOM #C1030


NOTE: PROVIDE AMPLIFIERS
AS NEEDED DUE TO DISTANCES
1-E DAYROOM #D1060 TV SPARE SPARE TV TRAINING #C1034
75 OHM COAX
CABLE (TYPICAL) 75 OHM COAX INCOMING CABLE TV 75 OHM COAX 75 OHM COAX
1-F DAYROOM #D1070 TV CABLE (TYPICAL) SPARE CABLE (TYPICAL) SPARE CABLE (TYPICAL) TV TRAINING #C1034
BY UTILITY CABLE CO. (COMCAST)

1 CATV RISER DIAGRAM


E-607 SCALE: 1/4" = 1'-0"
NORTH

09/26/19
DATE REVISION
3 Addendum #03
TRANSFORMER SCHEDULE

NO.
NO. SIZE RATING LOCATION MOUNTING COMMENTS

CHK'D: MLH

SEPTEMBER 5, 2019
480V, 3-PHASE, 3-WIRE PRIMARY ON CONCRETE EQUIPMENT /
TR-1A 75KVA MECHANICAL #C0153, UNIT C 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY HOUSEKEEPING PAD

1663-1190-90
480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH
TR-1C 45KVA ELECTRICAL #C1004, UNIT C 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +6'-10"

PROJECT NUMBER
480V, 3-PHASE, 3-WIRE PRIMARY ON CONCRETE EQUIPMENT /

DESIGNED: RDW
MLH
TR-2A 45KVA ELECTRICAL #B1024, UNIT B 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY HOUSEKEEPING PAD

DRAWN: RDW
480V, 3-PHASE, 3-WIRE PRIMARY ON CONCRETE EQUIPMENT /
TR-2C 30KVA ELECTRICAL #B1028, UNIT B 115 DEGREE RISE

APPRV'D:
208V/120V, 3-PHASE, 4-WIRE SECONDARY HOUSEKEEPING PAD

DATE:
480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH
TR-2D 30KVA ELECTRICAL #B1028, UNIT B 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-2E 15KVA JANITOR #B1108, UNIT B 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-3 30KVA VEHICLE SALLYPORT #A1000, UNIT A 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +9'-6"

VIGO COUNTY SECURITY CENTER

CATV RISER DIAGRAM AND TRANSFORMER


480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH
TR-4A 30KVA STORAGE #E1016B, UNITS D & E 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-4B 30KVA CHASE #E1014, UNIT E 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

480V, 3-PHASE, 3-WIRE PRIMARY ON CONCRETE EQUIPMENT /


TR-5A 30KVA MECH. #B2000, PENTHOUSE 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY HOUSEKEEPING PAD

480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-5B 30KVA CHASE #D1014, UNIT D 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

480V, 1-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-G1 25KVA MECHANICAL #C1053, UNIT C 115 DEGREE RISE
240V/120V, 1-PHASE, 3-WIRE SECONDARY BOTTOM AT +8'-0"

TERRE HAUTE, INDIANA


480V, 1-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH
TR-G2 25KVA MECHANICAL #C1053, UNIT C 115 DEGREE RISE
240V/120V, 1-PHASE, 3-WIRE SECONDARY BOTTOM AT +8'-0"

SCHEDULE
480V, 1-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH
TR-G3 25KVA MECHANICAL #C1053, UNIT C 115 DEGREE RISE
240V/120V, 1-PHASE, 3-WIRE SECONDARY BOTTOM AT +8'-0"

A NEW
480V, 3-PHASE, 3-WIRE PRIMARY ON CONCRETE EQUIPMENT /
TR-K1 75KVA FACILITY WORKSHOP #C1056, UNIT C 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY HOUSEKEEPING PAD
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-K2 30KVA FACILITY WORKSHOP
--- #C1056, UNIT C 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-L1P 15KVA ELECTRICAL #C1054, UNIT C 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

480V, 3-PHASE, 3-WIRE PRIMARY ON CONCRETE EQUIPMENT /


TR-L2P 15KVA ELECTRICAL #B2002, PENTHOUSE 115 DEGREE RISE
208V/120V, 3-PHASE, 4-WIRE SECONDARY HOUSEKEEPING PAD

480V, 3-PHASE, 3-WIRE PRIMARY ON CONCRETE EQUIPMENT /


TR-U1 45KVA ELECTRICAL #B1028, UNIT B 115 DEGREE RISE, K13 FACTOR
208V/120V, 3-PHASE, 4-WIRE SECONDARY HOUSEKEEPING PAD

480V, 3-PHASE, 3-WIRE PRIMARY STRUCTURE/WALL, MOUNT WITH


TR-U2 45KVA ELECTRICAL #B1024, UNIT B 115 DEGREE RISE, K13 FACTOR
208V/120V, 3-PHASE, 4-WIRE SECONDARY BOTTOM AT +8'-0"

NOTE: GROUND ALL TRANSFORMER TO BUILDING STEEL PER NEC ARTICLE 250, REFER TO DETAIL 6, SHEET E-803.
NOTE: PROVIDE UNISTRUT SUPPORT OR MANUFACTURER PROVIDED MOUNTING BRACKET FOR STRUCTURE/WALL MOUNTED TRANSFORMERS
NOTE: TRANSFORMERS 'TR-U1' AND 'TR-U2' TO HAVE DOUBLE LUGS ON NEUTRAL.
NOTE: ALL TRANSFORMERS TO BE DRY TYPE, NON-VENTILATED. MAINTAIN 4' OF CLEARANCE BEHIND TRANSFORMER FOR VENTILATION
PER MANUFACTURER'S REQUIREMENTS.
NOTE: REFER TO SPECIFICATION 262213 FOR DETAILED EQUIPMENT REQUIREMENTS.
9/25/2019 5:37:13 PM

DRAWING NUMBER

E-607

ELECTRICAL
DLZ INDIANA, LLC
Switchboard: ODPA Switchboard: ODPB
Location: MECHANICAL C1053 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: MECHANICAL B2000 Volts: 480/277 Wye A.I.C. Rating: 42k AIC
Supply From: MDPA Phases: 3 Mains Type: MCB Supply From: MDPA Phases: 3 Mains Type: MCB
Mounting: Floor Wires: 4 Mains Rating: 1600 A Mounting: Floor Wires: 4 Mains Rating: 1200 A
Enclosure: 1 MCB Rating: 1600 A Enclosure: 1 MCB Rating: 1200 A

Notes: Notes:

3
R
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks EE
CK IN
1 Panel 'E1PA' & 'E1PB' via Transformer 'TR-1A' 3 400 A 250 A 90992 VA 1 Panel 'E5H' - Mechanical B2000 (Penthouse) 3 225 A 200 A 103866 VA CO

SS D I A N G
I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC
2 Panel 'K1H' - Rm C1059 3 400 A 400 A 201772 VA 2 Panel 'E2HB' - Electrical B1028 (First Floor) 3 225 A 200 A 102763 VA

E
I ST ER
3 Panel 'E2HA' - Rm B1024 3 225 A 200 A 92000 VA 3 Panel 'E4H' - Storage E1016B (First Floor) 3 225 A 200 A 106113 VA

No.
4 Panel 'E3H' - Rm A1003 3 225 A 200 A 81965 VA 4 Spare 3 225 A 0A 0 VA

EG

IN
IN
5 Panel 'E1HA' - Rm C1053 3 225 A 200 A 64746 VA 5 AHU-2 Supply Fan - Mechanical B2000 (Penthouse) 3 125 A 100 A 61494 VA R
RV
6 Panel 'E1HB' - Rm C1004 3 225 A 200 A 91789 VA 6 AHU-2 Return Fan - Mechanical B2000 (Penthouse) 3 125 A 30 A 19279 VA MA FE
7 Uniterruptible Power Supply 'UPS-1' via Tranformer 'TR-U1' - Rm B1024 3 125 A 70 A 36540 VA 7 AHU-3 Supply Fan - Mechanical B2000 (Penthouse) 3 125 A 70 A 45290 VA P RO
8 Uniterruptible Power Supply 'UPS-2' via Tranformer 'TR-U2' - Rm B1024 3 125 A 70 A 28710 VA 8 AHU-3 Return Fan - Mechanical B2000 (Penthouse) 3 125 A 35 A 22271 VA
9 Surge Protective Device 'SPD-DPOA' - Rm C1053 3 125 A 100 A 0 VA 9 AHU-1 Supply Fan - Mechanical B2000 (Penthouse) 3 225 A 125 A 55095 VA
3 10 Domestic Booster Pump 'DWBP-1' - Rm C1053 3 125 A 80 A 53184 VA 10 AHU-1 Return Fan - Mechanical B2000 (Penthouse) 3 125 A 70 A 28254 VA
3
11 Panel '1EPP' in Generator Enclosure via Transformer 'TR-G1' 2 125 A 70 A 0 VA 11 AHU-4 Supply Fan - Mechanical B2000 (Penthouse) 3 125 A 70 A 45290 VA
12 Panel '2EPP' in Generator Enclosure via Transformer 'TR-G2' 2 125 A 70 A 0 VA 12 AHU-4 Return Fan - Mechanical B2000 (Penthouse) 3 125 A 35 A 22271 VA
13 Panel '3EPP' in Generator Enclosure via Transformer 'TR-G3' 2 125 A 70 A 0 VA 13 Computer Room Unit 'CRAC-3' - Security B2001 (Penthouse) 3 125 A 30 A 16869 VA
14 14 Spare 3 125 A 0A 0 VA
15 15 Future Housing Pod Panel 'E6H' 3 200 A 0A 0 VA
16 16 Future Housing Pod Panel 'E7H' 3 200 A 0A 0 VA
17 17
18 18
19 19
20 20
Total Conn. Load: 722674 VA Total Conn. Load: 628845 VA
Total Amps: 869 A Total Amps: 756 A
Legend: Legend:

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
HVAC 79425 VA 100.00% 79425 VA HVAC 48671 VA 100.00% 48671 VA
Lighting 30952 VA 100.00% 30952 VA Total Conn. Load: 722674 VA Lighting 50724 VA 100.00% 50724 VA Total Conn. Load: 628845 VA
Motor 176988 VA 107.51% 190284 VA Total Est. Demand: 593716 VA Motor 315687 VA 104.87% 331061 VA Total Est. Demand: 591839 VA
Other 4160 VA 100.00% 4160 VA Total Conn. Current: 869 A Receptacle 107360 VA 54.66% 58680 VA Total Conn. Current: 756 A
Receptacle 167640 VA 52.98% 88820 VA Total Est. Demand Current: 714 A Cooling 67070 VA 100.00% 67070 VA Total Est. Demand Current: 712 A
Cooling 37122 VA 100.00% 37122 VA Electric Clothes Dryer 4800 VA 100.00% 4800 VA
Electric Clothes Dryer 9840 VA 100.00% 9840 VA Heating 9000 VA 100.00% 9000 VA
Heating 5892 VA 100.00% 5892 VA Equipment 10500 VA 100.00% 10500 VA
Equipment 49000 VA 100.00% 49000 VA Misc. 11444 VA 100.00% 11444 VA
Kitchen Equipment - Non-Dwelling Unit 117844 VA 65.00% 76599 VA Misc. Non-Continuous 3700 VA 0.01% 0 VA
Misc. 22620 VA 100.00% 22620 VA
Misc. Non-Continuous 22200 VA 0.01% 2 VA Notes:
Notes:

09/12/19
09/26/19
DATE
Branch Panel: DP-L Branch Panel: L1H Branch Panel: L2H
Location: ELECTRICAL C1054 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: ELECTRICAL B1024 Volts: 480/277 Wye A.I.C. Rating: 10kA Location: ELECTRICAL B2002 Volts: 480/277 Wye A.I.C. Rating: 10kA

REVISION
Supply From: MDPA Phases: 3 Mains Type: MCB Supply From: DP-L Phases: 3 Mains Type: MLO Supply From: DP-L Phases: 3 Mains Type: MLO
Mounting: Surface Wires: 4 Mains Rating: 200 A Mounting: Surface Wires: 4 Mains Rating: 125 A Mounting: Surface Wires: 4 Mains Rating: 125 A

1 Addendum #01
3 Addendum #03
Enclosure: 1 MCB Rating: 200 A Enclosure: 1 Enclosure: 1

Notes: Notes: Notes:


NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL.

NO.
CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2

CHK'D: MLH
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4

SEPTEMBER 5, 2019
5 SPARE 20 A 1 0 0 1 20 A SPARE 6

1663-1190-90
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6
7 Linghting Inverter 'L2E' - Rm B2000 50 A 1 0 582 3 20 A Smoke Exhaust Fan 'SEF-1-1' - Roof 8
7 SPARE 20 A 1 0 3546 3 20 A Dedicated Outdoor Air System 'DOAS-1' - on Roof 8 7 Linghting Inverter 'L1E' - Rm B1024 20 A 1 1981 0 1 20 A SPARE 8
9 SPARE 20 A 1 0 582 -- -- -- 10
9 EM Lighting - Admin Area 20 A 1 1045 3546 -- -- -- 10 9 EM Lighting - Lobby 20 A 1 261 0 1 20 A SPARE 10 11 Lighting MECHANICAL B2000 20 A 1 160 582 -- -- -- 12

PROJECT NUMBER
11 EM Lighting - Exterior Facade (Area C) [via GTD1] 20 A 1 68 3546 -- -- -- 12 11 EM Lighting - Exterior Facade (Pods) [via GTD4] 20 A 1 97 102 1 20 A EM Lighting - Exterior Facade (Sallyport) [via... 12 13 Smoke Exhaust Fan 'SEF-1-6' - Roof 20 A 3 443 443 3 20 A Smoke Exhaust Fan 'SEF-1-2' - Roof 14

DESIGNED: RDW
MLH
13 SPARE 20 A 1 0 0 1 20 A SPARE 14 13 SPARE 20 A 1 0 0 1 20 A SPARE 14 15 -- -- -- 443 443 -- -- -- 16

DRAWN: RDW
15 SPARE 20 A 1 0 0 1 20 A SPARE 16 17 -- -- -- 443 443 -- -- -- 18
15 SPARE 20 A 1 0 0 1 20 A SPARE 16
19 Smoke Exhaust Fan 'SEF-1-5' - Roof 20 A 3 582 443 3 20 A Smoke Exhaust Fan 'SEF-1-4' - Roof 20

APPRV'D:
17 SPARE 20 A 1 0 0 1 20 A SPARE 18 17 SPARE 20 A 1 0 0 1 20 A SPARE 18
21 -- -- -- 582 443 -- -- -- 22

DATE:
19 Panel 'L1P' via Transformer 'TR-L1P' 30 A 3 1000 1981 3 100 A Panel 'L1H' - Electrical B1024 20 19 SPACE -- -- 0 0 -- -- SPACE 20 23 -- -- -- 582 443 -- -- -- 24
21 -- -- -- 1000 261 -- -- -- 22 21 SPACE -- -- 0 0 -- -- SPACE 22 25 Smoke Exhaust Fan 'SEF-2-1' - Roof 20 A 3 582 443 3 20 A Smoke Exhaust Fan 'SEF-2-6' - Roof 26
23 -- -- -- 750 199 -- -- -- 24 23 SPACE -- -- 0 0 -- -- SPACE 24 27 -- -- -- 582 443 -- -- -- 28
25 SPACE -- -- 0 0 -- -- SPACE 26 29 -- -- -- 582 443 -- -- -- 30
25 Panel 'L2H' - Electrical B2002 (Penthouse) 100 A 3 13768 0 3 60 A Surge Protective Device 'SPD-DPL' 26
31 Smoke Exhaust Fan 'SEF-2-2' - Roof 20 A 3 443 582 3 20 A Smoke Exhaust Fan 'SEF-2-5' - Roof 32
27 -- -- -- 13350 0 -- -- -- 28 27 SPACE -- -- 0 0 -- -- SPACE 28
33 -- -- -- 443 582 -- -- -- 34
29 -- -- -- 13236 0 -- -- -- 30 29 SPACE -- -- 0 0 -- -- SPACE 30 35 -- -- -- 443 582 -- -- -- 36

VIGO COUNTY SECURITY CENTER


Total Load: 20244 VA 19179 VA 17772 VA Total Load: 1981 VA 261 VA 199 VA 37 Smoke Exhaust Fan 'SEF-2-4' - Roof 20 A 3 443 443 3 20 A Smoke Exhaust Fan 'SEF-6C' - Roof 38
Total Amps: 74 A 70 A 64 A Total Amps: 7A 1A 1A 39 -- -- -- 443 443 -- -- -- 40
Legend: 41 -- -- -- 443 443 -- -- -- 42
Legend:
43 Smoke Exhaust Fan 'SEF-3' - Roof 20 A 3 443 443 3 20 A Smoke Exhaust Fan 'SEF-6B' - Roof 44
45 -- -- -- 443 443 -- -- -- 46
47 -- -- -- 443 443 -- -- -- 48
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 49 Dedicated Outdoor Air System 'DOAS-2' - on Roof 20 A 3 3546 443 3 20 A Smoke Exhaust Fan 'SEF-6A' - Roof 50

PANELBOARD SCHEDULES
HVAC 21274 VA 100.00% 21274 VA Lighting 2437 VA 100.00% 2437 VA 51 -- -- -- 3546 443 -- -- -- 52
Total Conn. Load: 2437 VA 53 -- -- -- 3546 443 -- -- -- 54
Lighting 3702 VA 100.00% 3702 VA Total Conn. Load: 54944 VA
55 SPARE 20 A 1 0 0 1 20 A SPARE 56
Motor 24024 VA 101.82% 24460 VA Total Est. Demand: 55380 VA Total Est. Demand: 2437 VA
57 SPARE 20 A 1 0 0 1 20 A SPARE 58
Power 4032 VA 100.00% 4032 VA Total Conn. Current: 66 A Total Conn. Current: 3A 59 SPARE 20 A 1 0 0 1 20 A SPARE 60

TERRE HAUTE, INDIANA


Equipment 1500 VA 100.00% 1500 VA Total Est. Demand Current: 67 A Total Est. Demand Current: 3A 61 SPACE -- -- 0 0 -- -- SPACE 62
Misc 500 VA 100.00% 500 VA 63 SPACE -- -- 0 0 -- -- SPACE 64
65 SPACE -- -- 0 0 -- -- SPACE 66
67 Panel 'L2P' via Transformer 'TR-L2P' 30 A 3 3462 0 -- -- SPACE 68
Notes: Notes:
69 -- -- -- 3044 0 -- -- SPACE 70

A NEW
71 -- -- -- 2770 0 -- -- SPACE 72
Total Load: 13768 VA 13350 VA 13236 VA
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

Total Amps: 50 A 48 A 48 A
Legend:

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
HVAC 10637 VA 100.00% 10637 VA
Lighting 160 VA 100.00% 160 VA Total Conn. Load: 39353 VA
Motor 24024 VA 101.82% 24460 VA Total Est. Demand: 39789 VA
Power 4032 VA 100.00% 4032 VA Total Conn. Current: 47 A
Misc 500 VA 100.00% 500 VA Total Est. Demand Current: 48 A

Notes:
9/25/2019 5:31:58 PM

DRAWING NUMBER

E-701

ELECTRICAL
DLZ INDIANA, LLC
Branch Panel: E1HA Branch Panel: E1PA Branch Panel: E1PB
Location: MECHANICAL C1053 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: MECHANICAL C1053 Volts: 120/208 Wye A.I.C. Rating: 10k AIC Location: MECHANICAL C1053 Volts: 120/208 Wye A.I.C. Rating: 10k AIC
Supply From: ODPA Phases: 3 Mains Type: MLO Supply From: TR-1A Phases: 3 Mains Type: MCB Supply From: E1PA Phases: 3 Mains Type: MLO
Mounting: Surface Wires: 4 Mains Rating: 250 A Mounting: Surface Wires: 4 Mains Rating: 400 A Mounting: Surface Wires: 4 Mains Rating: 250 A
Enclosure: 1 Enclosure: 1 MCB Rating: 250 A Enclosure: 1

Notes: Notes: Notes:


NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL.

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4
R
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6 EE
CK IN
CO

SS D I A N G
7 Fan Powered VAV Box 'FPV-1-15' - Rm C1031 20 A 1 2715 238 1 20 A Exterior Wall Mounted Lighting - Area C 8 7 Recepts - Rms C1032 & C1033 20 A 1 1080 1080 1 20 A Floor Box Recepts- Rm C1034 8 7 Portable Welder - Rm C1056B 30 A 2 0 900 1 20 A Recepts - Rms C1047, C1051 8

I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC
9 Lighting - Mech C1053, Receiving 20 A 1 2957 568 1 20 A Exterior Area/Drive Lighting - Employee Parking 10 9 Hand Dryer - Rm C1032 20 A 1 1500 900 1 20 A Floor Box & Recepts- Rm C1034 10 9 -- -- -- 0 1260 1 20 A Recepts - Rm C1047C 10

E
I ST ER
11 SPARE 20 A 1 0 634 1 20 A Exterior Area/Drive Lighting - East Drive 12 11 Hand Dryer - Rm C1032 20 A 1 1500 1080 1 20 A Floor Box Recepts- Rm C1034 12 11 Recepts - Rms C1056, C1056B & C1057 20 A 1 1080 1080 1 20 A Recepts - Rm C1047 12

No.
13 Exhaust Fan 'EF-8' - Rm C1056B 20 A 3 651 498 3 20 A Hot Water Recirc Pump 'HWRP-1' - Rm C1053 14 13 Hand Dryer - Rm C1033 20 A 1 1500 900 1 20 A Floor Box & Recepts- Rm C1034 14 13 Recepts - Rm C1056 20 A 1 900 1000 1 20 A Refrig - Rm C1047 14

EG

IN
IN
15 -- -- -- 651 498 -- -- -- 16 15 Hand Dryer - Rm C1033 20 A 1 1500 1080 1 20 A Floor Box Recepts- Rm C1034 16 15 Air Compressor Recept - Rm C1056 20 A 1 1000 1000 1 20 A Refrig - Rm C1047 16 R
RV
17 -- -- -- 651 498 -- -- -- 18 17 Auto. Flush Valves - Rms C1032 & C1033 20 A 1 1200 1080 1 20 A Floor Box & Recepts- Rm C1034 18 17 Recepts - Rms C1049 & C1057 20 A 1 900 1000 1 20 A Refrig - Rm C1047 18 MA FE
19 Door Air Curtain 'DAC-1' - Rm C1052 20 A 3 1773 498 3 20 A Hot Water Recirc Pump 'HWRP-2' - Rm C1053 20 19 Elec. Water Cooler 'EWC-1' - Rm C1031 20 A 1 700 1080 1 20 A Floor Box Recepts- Rm C1034 20 19 Recepts - Rm C1049 20 A 1 900 1000 1 20 A Refrig - Rm C1047 20 P RO
21 -- -- -- 1773 498 -- -- -- 22 21 Recepts - Rms C1031, C1036 & Exterior 20 A 1 900 900 1 20 A Floor Box & Recepts- Rm C1034 22 21 Refrig - Rm C1049 20 A 1 1000 1080 1 20 A Recepts - Rms C1045, C1047 & C1085 22
23 -- -- -- 1773 498 -- -- -- 24 23 Recepts - Rms C1023C, C1030, C1031 & C1035 20 A 1 720 1080 1 20 A Floor Box Recepts- Rm C1034 24 23 Recepts - Rms C1049, C1050 & C1052A 20 A 1 900 720 1 20 A Recepts - Rms C1047 & C1052A 24
25 Future Cold Water Pump 'CWP-FTR' - Rm C1053 30 A 3 0 0 3 20 A Future Hot Water Pump 'HWP-FTR' - Rm C1053 26 25 Garbage Disposal 'WD-1' - Rm C1030 20 A 1 1656 900 1 20 A Floor Box & Recepts- Rm C1034 26 25 Recepts - Rm C1055 20 A 1 1260 840 1 20 A Fume Hood - Rm C1047 26
27 -- -- -- 0 0 -- -- -- 28 27 Refrig - Rm C1030 20 A 1 1000 720 1 20 A Receptacle TRAINING ROOM C1034 28 27 Hot Water Unit Heater 'HUH-2' - Rm C1052 20 A 1 264 1080 1 20 A Floor Boxes - Rm C1047 28
29 -- -- -- 0 0 -- -- -- 30 29 Micro - Rm C1030 20 A 1 1200 900 1 20 A Receptacle TRAINING ROOM C1034 30 29 Recepts - Rm C1052 & Exterior 20 A 1 1080 720 1 20 A Recepts - Rms C1047 & C1052A 30
31 Cold Water Pump 'CWP-1' - Rm C1053 30 A 3 5817 2105 3 20 A Hot Water Pump 'HWP-1' - Rm C1053 32 31 Recepts - Rm C1029 20 A 1 900 360 1 20 A Recepts - Rm C1030 32 31 Hot Water Unit Heater 'HUH-1' - Rm C1052 20 A 1 264 900 1 20 A Recepts - Rms C1052A, C1054 & C1082 32
33 -- -- -- 5817 2105 -- -- -- 34 33 Recepts - Rms C1027 & C1029 20 A 1 1080 900 1 20 A Recepts - Rm C1030 & Exterior 34 33 Water Softener 'WS-1' and Recepts - Rm C1053 20 A 1 900 960 1 20 A Chiller 'CH-1 Receptacles - Exterior 34
35 -- -- -- 5817 2105 -- -- -- 36 35 Recepts - Rms C1027 20 A 1 1080 900 1 20 A Recepts - Rm C1030 & Exterior 36 35 Gas Water Heater 'WH-1' - Rm C1053 20 A 1 1080 960 1 20 A Chiller 'CH-2' Receptacles - Exterior 36
37 Cold Water Pump 'CWP-2' - Rm C1053 30 A 3 5817 2105 3 20 A Hot Water Pump 'HWP-2' - Rm C1053 38 37 Recepts - Rms C1027 20 A 1 1080 1080 1 20 A Recepts - Rm C1028 38 37 Gas Water Heater 'WH-2' - Rm C1053 20 A 1 1080 0 1 20 A Remote Evaporator 'REV-1' - Rm C1053 38
39 -- -- -- 5817 2105 -- -- -- 40 39 Recepts - Rms C1027 20 A 1 900 1080 1 20 A Recepts - Rm C1028 40 39 Gas Water Heater 'WH-3' - Rm C1053 20 A 1 1080 0 1 20 A Remote Evaporator 'REV-2' - Rm C1053 40
41 -- -- -- 5817 2105 -- -- -- 42 41 Recepts - Rms C1027 20 A 1 900 1080 1 20 A Recepts - Rm C1028 & Exterior 42 41 Future Gas Water Hater 'WH-FTR' - Rm C1053 20 A 1 0 0 1 20 A Future Remote Evaporator 'REV-FTR' - Rm C1053 42
Total Load: 22194 VA 22718 VA 19837 VA 43 SPARE 20 A 1 0 900 1 20 A Recepts - Rm C1023C & C1028 44 43 Mixing Valve and Recepts - Rm C1053 20 A 1 900 372 1 20 A Fan Coil Unit 'FCU-14' - Rm C1053 44
Total Amps: 81 A 83 A 72 A 45 SPARE 20 A 1 0 876 1 20 A Exhaust Fan 'EF-1' - on Roof 46 45 Recept & Trap Primer 'TP-1' - Rm C1053 20 A 1 548 372 1 20 A Fan Coil Unit 'FCU-13' - Rm C1053 46
Legend: 47 SPARE 20 A 1 0 0 1 20 A Time Clock 'TC1' - Rm C1053 48 47 Recepts - Rm C1053 20 A 1 540 548 1 20 A Recepts & Trap Primer 'TP-2' - Rm C1053 48
49 Panel 'E1PB' 200 A 3 18064 0 3 60 A Surge Protective Deivce 'SPD-E1PA' 50 49 Exhaust Fan 'EF-4' - on Roof 20 A 1 492 696 1 20 A Exhaust Fan 'EF-9' - on Roof 50
51 -- -- -- 15996 0 -- -- -- 52 51 Exhaust Fan 'EF-7' - on Roof 20 A 1 1356 696 1 20 A Exhaust Fan 'EF-10' - on Roof 52
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 53 -- -- -- 17660 0 -- -- -- 54 53 Exhaust Fan 'EF-2' - on Roof 20 A 1 492 2080 2 30 A Reverse Osmosis Smart Guard 'RO-1' - Rm C1053 54
HVAC 8033 VA 100.00% 8033 VA Total Load: 31280 VA 29332 VA 30380 VA 55 Future Boiler 'B-FTR' - Rm C1053 20 A 3 0 2080 -- -- -- 56
Lighting 4346 VA 100.00% 4346 VA Total Conn. Load: 64746 VA Total Amps: 262 A 244 A 255 A 57 -- -- -- 0 1000 1 20 A RO Backwashing Tank/Head - Rm C1053 58
Motor 52475 VA 108.31% 56838 VA Total Est. Demand: 69108 VA Legend: 59 -- -- -- 0 2080 2 30 A Station Battery Charger - Rm C1053 60
Other 0 VA 0.00% 0 VA Total Conn. Current: 78 A 61 Boiler 'B-1' - Rm C1053 20 A 3 1200 2080 -- -- -- 62
Total Est. Demand Current: 83 A 63 -- -- -- 1200 0 1 20 A CCTV Enclosure - Employee Parking Lot 64
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 65 -- -- -- 1200 0 1 20 A CCTV Enclosure - Employee Parking Lot 66
HVAC 11200 VA 100.00% 11200 VA 67 Boiler 'B-2' - Rm C1053 20 A 3 1200 0 3 60 A Surge Protective Device 'SPD-E1PB' 68
Motor 9704 VA 110.72% 10744 VA Total Conn. Load: 90992 VA 69 -- -- -- 1200 0 -- -- -- 70
Notes: Other 4160 VA 100.00% 4160 VA Total Est. Demand: 65643 VA 71 -- -- -- 1200 0 -- -- -- 72
Receptacle 48380 VA 60.33% 29190 VA Total Conn. Current: 253 A Total Load: 18064 VA 15996 VA 17660 VA
Heating 528 VA 100.00% 528 VA Total Est. Demand Current: 182 A Total Amps: 153 A 133 A 149 A
Misc. 9820 VA 100.00% 9820 VA Legend:
Misc. Non-Continuous 7200 VA 0.01% 1 VA

Notes: Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
HVAC 11200 VA 100.00% 11200 VA
Motor 7352 VA 114.15% 8392 VA Total Conn. Load: 51720 VA
Other 4160 VA 100.00% 4160 VA Total Est. Demand: 46980 VA
Receptacle 21560 VA 73.19% 15780 VA Total Conn. Current: 144 A
Heating 528 VA 100.00% 528 VA Total Est. Demand Current: 130 A
Misc. 6920 VA 100.00% 6920 VA

Notes:

09/12/19
09/26/19
DATE
Branch Panel: E1HB Branch Panel: E1PC Branch Panel: E1PD
Location: ELECTRICAL C1004 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: ELECTRICAL C1004 Volts: 120/208 Wye A.I.C. Rating: 10k AIC Location: ELECTRICAL C1004 Volts: 120/208 Wye A.I.C. Rating: 10k AIC

REVISION
Supply From: ODPA Phases: 3 Mains Type: MLO Supply From: TR-1C Phases: 3 Mains Type: MCB Supply From: E1PC Phases: 3 Mains Type: MLO
Mounting: Surface Wires: 4 Mains Rating: 250 A Mounting: Surface Wires: 4 Mains Rating: 175 A Mounting: Surface Wires: 4 Mains Rating: 250 A

1 Addendum #01
3 Addendum #03
Enclosure: 1 Enclosure: 1 3 MCB Rating: 175 A Enclosure: 1

Notes: Notes: Notes:


NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL WITH FEED-THRU LUGS. NEW SURFACE MOUNTED PANEL.

NO.
CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4

CHK'D: MLH

SEPTEMBER 5, 2019
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6

1663-1190-90
7 Recepts - Rm C1043 20 A 1 900 900 1 20 A Recepts - Rm B1001 & C1000 8
7 Fan Powered VAV Box 'FPV-1-02' - Rm B1001 20 A 1 2715 0 -- -- SPACE 8 7 Recepts - Rms C1004 & C1005 20 A 1 900 1000 1 20 A Kiosk - Rm B1000 8
9 Recepts - Rm C1006, C1037 & C1043 20 A 1 720 900 1 20 A Recepts - Rm B1001 & C1000 10
9 Lighting - Area C North Offices 20 A 1 3158 0 -- -- SPACE 10 9 Recepts - Rm C1001 20 A 1 900 1000 1 20 A Kiosk - Rm B1000 10
11 Recepts - C1006 & C1037 20 A 1 900 1080 1 20 A Recepts - Rm C1014 12

PROJECT NUMBER
11 Lighting - Training Room C1034 20 A 1 4032 0 -- -- SPACE 12 11 Recepts - Rms C1000 & C1001 20 A 1 900 1000 1 20 A Kiosk - Rm B1000 12 13 Recepts - C1003 & C1007 20 A 1 900 720 1 20 A Recepts - Rms C1003 & C1014 14

DESIGNED: RDW
13 Lighting - Fitness C1028, Area C Central 20 A 1 3053 0 -- -- SPACE 14 13 Recepts - Rms C1001 & C1002 20 A 1 900 1000 1 20 A Kiosk - Rm B1000 14

MLH
15 Recepts - Rms C1003, C1007 & C1039 20 A 1 720 900 1 20 A Recepts - Rms C1009 & C1014 16

DRAWN: RDW
15 Lighting - Area C West 20 A 1 1905 0 -- -- SPACE 16 15 Receptacle SEX OFFENDER AND EVICTION... 20 A 1 540 720 1 20 A Recepts - Rms B1000, B1001 & Exterior 16 17 Recepts - Rms C1009 & C1012 20 A 1 1080 900 1 20 A Recepts - Rm C1014 18
17 SPARE 20 A 1 0 0 -- -- SPACE 18 17 Recepts - Rms C1044 & C1045 20 A 1 540 1080 1 20 A Recepts - Rms B1003 18 19 Recepts - C1008 & C1038 20 A 1 1080 900 1 20 A Receptacle WORK ROOM C1013 20

APPRV'D:
19 SPACE -- -- 0 0 -- -- SPACE 20 19 Recepts - Rm C1002 20 A 1 900 1080 1 20 A Recepts - Rms B1003 20 21 Refrig - Rm C1008A 20 A 1 1000 900 1 20 A Receptacle WORK ROOM C1013 22

DATE:
21 SPACE -- -- 0 0 -- -- SPACE 22 21 Recepts - Rm B1001 & B1017 20 A 1 1000 1080 1 20 A Recepts - Rms B1003, B1004 & B1005 22 23 Recepts - Rms C1008A, C1023B, C1024 & C1033 20 A 1 900 1000 1 20 A Copier - Rm C1013 24
25 Recepts - Rms C1025 & C1026 20 A 1 1020 1000 1 20 A Refrig - Rm C1015 26
23 SPACE -- -- 0 0 -- -- SPACE 24 23 Hand Dryer - Rm B1017 20 A 1 1500 900 1 20 A Recepts - Rm B1002 & B1006 24
27 Recepts - Rm C1022 20 A 1 1080 1260 1 20 A Recepts - Rm C1015 28
25 SPACE -- -- 0 25756 3 70 A Panels 'E1PC' & 'E1PD' via Transformer 'TR-1B' 26 25 Recepts - Rms B1001 & B1013 20 A 1 900 700 1 20 A Elec. Water Cooler 'EWC-1' - Rm B1002 26
29 Recepts - Rm C1022 20 A 1 1080 1080 1 20 A Recepts - Rm C1015 30
27 SPACE -- -- 0 26020 -- -- -- 28 27 Recepts - Rms B1010, B1011 & B1012 20 A 1 1080 1000 1 20 A *,Vending Machine - Rm B1002 28 31 Recepts - Rm C1022 20 A 1 1080 900 1 20 A Recepts - Rms C1016 32
29 SPACE -- -- 0 25507 -- -- -- 30 29 Recepts - Rms B1008 & B1009 20 A 1 900 1000 1 20 A *,Vending Machine - Rm B1002 30 33 Recepts - C1009 & C1022 20 A 1 900 1000 1 20 A Recepts - Rms C1016 & C1017 34
Total Load: 31393 VA 30893 VA 29539 VA 31 Recept - Rm B1007 and Flush Valves 20 A 1 1160 915 2 30 A Air Cooled Cond. Unit 'ACC-C' - on Roof 32

VIGO COUNTY SECURITY CENTER


35 Recepts - Rm C1021 20 A 1 1080 900 1 20 A Recepts - Rms C1016 36
Total Amps: 114 A 112 A 107 A 33 Hand Dryer - Rm B1008 20 A 1 1500 915 -- -- -- 34 37 Recepts - Rm C1021 20 A 1 1080 1260 1 20 A Recepts - Rms C1010 & C1018 38
Legend: 35 Hand Dryer - Rm B1008 20 A 1 1500 312 1 20 A Exhaust Fan 'EF-5' - on Roof 36 39 Recepts - Rm C1021 20 A 1 1080 1260 1 20 A Recepts - Rms C1018 & C1010 40
37 Hand Dryer - Rm B1009 20 A 1 1500 225 1 20 A Track Lighting Corridor C1031 38 41 Recepts - Rms C1020 & C1021 20 A 1 1080 1260 1 20 A Floor Box & Recepts - Rm C1040 42
43 Recepts - Rm C1020 20 A 1 1080 1080 1 20 A Floor Box Recepts - Rm C1040 44
39 Hand Dryer - Rm B1009 20 A 1 1500 525 1 20 A Lighting 40
45 Recepts - Rm C1019 20 A 1 720 1080 1 20 A Floor Box Recepts - Rm C1040 46
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 41 Auto Doors - Doors 'B100B' & 'B1000D' 20 A 1 792 0 1 20 A SPARE 42 47 Recepts - Rms C1009 & C1019 20 A 1 1080 1080 1 20 A Recepts - Rms C1040 & C1054 48
HVAC 3298 VA 100.00% 3298 VA

PANELBOARD SCHEDULES
43 SPARE 20 A 1 0 0 1 20 A SPARE 44 49 Surge Protective Device 'SPD-E1PD' 60 A 3 0 900 1 20 A Recepts - Rms C1040 & C1041 50
Lighting 12095 VA 100.00% 12095 VA Total Conn. Load: 91789 VA 45 SPARE 20 A 1 0 0 1 20 A SPARE 46 51 -- -- -- 0 1260 1 20 A Recepts - Rm C1048 52
Motor 1104 VA 117.93% 1302 VA Total Est. Demand: 60788 VA 47 SPARE 20 A 1 0 0 1 20 A SPARE 48 53 -- -- -- 0 583 1 20 A Fan Coil Unit 'FCU-15' - Rm B1000 54
Other 0 VA 0.00% 0 VA Total Conn. Current: 110 A 49 Panel 'E1PD' 200 A 3 14800 0 3 60 A Surge Protective Deivce 'SPD-E1PC' 50 Total Load: 14800 VA 14780 VA 15083 VA
Receptacle 55260 VA 59.05% 32630 VA Total Est. Demand Current: 73 A Total Amps: 123 A 123 A 126 A

TERRE HAUTE, INDIANA


51 -- -- -- 14780 0 -- -- -- 52
Cooling 1830 VA 100.00% 1830 VA 53 -- -- -- 15083 0 -- -- -- 54 Legend:
Misc. 10000 VA 100.00% 10000 VA Total Load: 25756 VA 26020 VA 25507 VA
Misc. Non-Continuous 8600 VA 0.01% 1 VA Total Amps: 215 A 217 A 213 A
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

A NEW
Legend:
Notes: HVAC 583 VA 100.00% 583 VA
Receptacle 40680 VA 62.29% 25340 VA Total Conn. Load: 44663 VA
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Misc. 2400 VA 100.00% 2400 VA Total Est. Demand: 28323 VA
HVAC 583 VA 100.00% 583 VA Misc. Non-Continuous 1000 VA 0.01% 0 VA Total Conn. Current: 124 A
Lighting 750 VA 100.00% 750 VA Total Conn. Load: 77281 VA Total Est. Demand Current: 79 A
Motor 1104 VA 117.93% 1302 VA Total Est. Demand: 46352 VA
Other 0 VA 0.00% 0 VA Total Conn. Current: 215 A
Receptacle 55260 VA 59.05% 32630 VA Total Est. Demand Current: 129 A Notes:
Cooling 1830 VA 100.00% 1830 VA
Misc. 10000 VA 100.00% 10000 VA
Misc. Non-Continuous 8500 VA 0.01% 1 VA
3
Notes:
* - PROVIDE GROUND FAULT CURRENT INTERRUPTING (GFCI) BREAKER
200A/3P BREAKER (49,51,53) FOR PANEL 'E1PD' IS SHOWN FOR LOADING PURPOSES ONLY. PANEL TO BE CONNECTED VIA FEED-THRU LUGS.
9/25/2019 5:32:02 PM

DRAWING NUMBER

E-702

ELECTRICAL
DLZ INDIANA, LLC
Branch Panel: E2HA Branch Panel: E2PA Branch Panel: E2PB
Location: ELECTRICAL B1024 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: ELECTRICAL B1024 Volts: 120/208 Wye A.I.C. Rating: 10k AIC Location: ELECTRICAL B1024 Volts: 120/208 Wye A.I.C. Rating: 10k AIC
Supply From: ODPA Phases: 3 Mains Type: MLO Supply From: TR-2A... Phases: 3 Mains Type: MCB Supply From: E2PA Phases: 3 Mains Type: MLO
Mounting: Surface Wires: 4 Mains Rating: 250 A Mounting: Surface Wires: 4 Mains Rating: 250 A Mounting: Surface Wires: 4 Mains Rating: 200 A
Enclosure: 1 Enclosure: 1 MCB Rating: 175 A Enclosure: 1
3
Notes: Notes: Notes:
NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL WITH FEED-THRU LUGS. NEW SURFACE MOUNTED PANEL.

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 R
EE
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4 CK IN
CO

SS D I A N G
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6

I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC

E
7 Fan Powered Box 'FPV-2-04' - Rm B1029 20 A 1 886 637 1 20 A Fan Powered Box 'FPV-2-07' - Rm B1053 8 7 Recepts - Rms B1024 & B1025 20 A 1 900 900 1 20 A Recepts - Rms B1084, B1085 & Exterior 8 7 Recepts - Rm B1053A 20 A 1 540 540 1 20 A Recepts - Rm B1053A 8

I ST ER
No.
9 Fan Powered Box 'FPV-2-03' - Rm B1053 20 A 1 895 637 1 20 A Fan Powered Box 'FPV-2-02'- Rm B1061 10 9 Recepts - Rms B1029 & B1031 20 A 1 820 900 1 20 A Recepts - Rm B1053 (Chases) 10 9 Recepts - Rm B1053A 20 A 1 720 540 1 20 A Recepts - Rm B1053A 10
11 Fan Powered Box 'FPV-2-08' - Cell B1044 20 A 1 637 2909 1 20 A Air Cooled Condensing Unit 'ACC-2' - on Roof 12 11 Recepts - Rms B1026 & B1027 20 A 1 740 1120 1 20 A Recepts - Rms B1075 & B1076 12 11 Recepts - Rm B1053A 20 A 1 540 540 1 20 A Recepts - Rm B1053A 12

EG

IN
IN
R
13 Computer Room Unit 'CRAC-2' - Rm C1046 20 A 1 4543 1397 1 20 A Lighting - Intake Center, Dayroom B1037 14 13 Sliding Door 'B1029' 20 A 1 396 1000 1 20 A Refrig- Rm B1074 14 13 Recepts - Rm B1053A 20 A 1 540 540 1 20 A Recepts - Rm B1053A 14 RV
15 Lighting - Intake Center Cells 20 A 1 1350 2010 1 20 A Lighting - Lobby, Visit., Mast. Cntrl., Main Corridor 16 15 Recepts - Rms B1037 & B1038 20 A 1 540 1200 1 20 A Micro- Rm B1074 16 15 Recepts - Rm B1053A 20 A 1 540 540 1 20 A Recepts - Rm B1053A 16 MA FE
P RO
17 Lighting - Pretrial Offices, Transp, Detox, Testing 20 A 1 2358 282 1 20 A Exterior Wall Mounted - Area B 18 17 Recepts - Rm B1038 20 A 1 360 1000 1 20 A Copier - Rm B1074 18 17 Recepts - Rm B1053 20 A 1 900 900 1 20 A Recepts - Rm B1053 18
19 Air Cooled Condensing Unit 'ACC-4' - on Roof 20 A 3 2853 315 1 20 A Exterior Flagpole & Sign Lighting 20 19 Body Scanner - Rm B1035 20 A 1 1100 720 1 20 A Recepts - Rm B1074 20 19 Recepts - Rm B1053 20 A 1 1080 1080 1 20 A Recepts - Rms B1055 & B1058 20
21 -- -- -- 2853 909 1 20 A Exterior Area/Drive Lighting - North 22 21 Recepts - Rm B1035 20 A 1 720 1260 1 20 A Recepts - Rm B1073 22 21 Recepts - Rms B1062 & B1063 20 A 1 720 396 1 20 A Sliding Door 'B1055B' 22
23 -- -- -- 2853 1003 1 20 A Exterior Area/Drive Lighting - Visitor Parking 24 23 Sliding Door 'B1015B' 20 A 1 396 1260 1 20 A Recepts - Rm B1072 24 23 Sliding Door 'B1063B' 20 A 1 396 1080 1 20 A Recepts - Rms B1055 & B1057 24
25 Computer Room Unit 'CRAC-1' - Rm B1060 30 A 3 5817 0 -- -- SPACE 26 25 Sliding Door 'B1019' 20 A 1 396 1260 1 20 A Recepts - Rm B1071 26 25 Recepts - Rms B1135 & B1064 20 A 1 720 900 1 20 A Recepts - Rm B1056 26
27 -- -- -- 5817 0 -- -- SPACE 28 27 Sliding Door 'B1018' 20 A 1 396 1260 1 20 A Recepts - Rm B1070 28 27 Recepts - Rm B1064 20 A 1 720 720 1 20 A Recepts - Rms B1055 & B1060 28
29 -- -- -- 5817 0 -- -- SPACE 30 29 Sliding Door 'B1015A' 20 A 1 396 900 1 20 A Recepts - Rm B1062, B1067, B1068 & B1069 30 29 Elec. Wall Heater 'EWH-2' - Rm B1063 20 A 1 1500 720 1 20 A Recepts - Rm B1060 30
31 SPACE -- -- 0 0 -- -- SPACE 32 31 Recepts - Rm B1015 & B1019 20 A 1 720 915 2 30 A Air Cooled Cond. Unit 'ACC-A' - on Roof 32 31 Area B - Cell Valve Controllers 20 A 1 0 1500 1 20 A Hand Dryer - Rm B1066 32
33 SPACE -- -- 0 0 -- -- SPACE 34 33 Recepts - Rm B1018 20 A 1 540 915 -- -- -- 34 33 Micro - Rm B1016 20 A 1 1200 1500 1 20 A Hand Dryer - Rm B1065 34
35 SPACE -- -- 0 0 -- -- SPACE 36 35 Time Clock 'TC2' - Rm B1024 20 A 1 0 0 1 20 A Area B - Cell Valve Controllers 36 35 Refrig - Rm B1016 20 A 1 1000 0 1 20 A SPARE 36
37 SPACE -- -- 0 15747 3 70 A Panels 'E2PA' & 'E2PB' via Transformer 'TR-2A' 38 37 Panel 'E2PB' 200 A 3 7440 0 3 60 A Surge Protective Device 'SPD-E2PA' 38 37 CCTV Enclosure - Visitor Parking Lot 20 A 1 0 0 3 60 A Surge Protective Device 'SPD-E2PB' 38
39 SPACE -- -- 0 16147 -- -- -- 40 39 -- -- -- 7596 0 -- -- -- 40 3 39 CCTV Enclosure - Visitor Parking Lot 20 A 1 0 0 -- -- -- 40
41 SPACE -- -- 0 13748 -- -- -- 42 41 -- -- -- 7576 0 -- -- -- 42 41 Gate Controller (North Drive) 20 A 1 0 0 -- -- -- 42
Total Load: 32065 VA 30482 VA 29455 VA Total Load: 15747 VA 16147 VA 13748 VA Total Load: 7440 VA 7596 VA 7576 VA
Total Amps: 116 A 111 A 106 A Total Amps: 134 A 137 A 115 A Total Amps: 62 A 63 A 63 A
Legend: Legend: Legend:

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
HVAC 3692 VA 100.00% 3692 VA Motor 2772 VA 103.57% 2871 VA Motor 792 VA 112.50% 891 VA
Lighting 9526 VA 100.00% 9526 VA Total Conn. Load: 92000 VA Receptacle 30440 VA 66.43% 20220 VA Total Conn. Load: 45642 VA Receptacle 15120 VA 83.07% 12560 VA Total Conn. Load: 22612 VA
Motor 2772 VA 103.57% 2871 VA Total Est. Demand: 75487 VA Cooling 1830 VA 100.00% 1830 VA Total Est. Demand: 29122 VA Heating 1500 VA 100.00% 1500 VA Total Est. Demand: 15951 VA
Other 0 VA 0.00% 0 VA Total Conn. Current: 111 A Heating 1500 VA 100.00% 1500 VA Total Conn. Current: 127 A Misc. 1000 VA 100.00% 1000 VA Total Conn. Current: 63 A
Receptacle 30440 VA 66.43% 20220 VA Total Est. Demand Current: 91 A Misc. 2700 VA 100.00% 2700 VA Total Est. Demand Current: 81 A Misc. Non-Continuous 4200 VA 0.01% 0 VA Total Est. Demand Current: 44 A
Cooling 35292 VA 100.00% 35292 VA Misc. Non-Continuous 6400 VA 0.01% 1 VA
Heating 1500 VA 100.00% 1500 VA
Misc. 2700 VA 100.00% 2700 VA Notes: Notes:
Misc. Non-Continuous 6400 VA 0.01% 1 VA 200A/3P BREAKER (37,39,41) FOR PANEL 'E2PB' IS SHOWN FOR LOADING PURPOSES ONLY. PANEL TO BE CONNECTED VIA FEED-THRU LUGS.
Notes:

09/12/19
09/26/19
DATE
Branch Panel: E2HB Branch Panel: E2PC Branch Panel: E2PD
Location: ELECTRICAL B1028 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: ELECTRICAL B1028 Volts: 120/208 Wye A.I.C. Rating: 10k AIC Location: ELECTRICAL B1028 Volts: 120/208 Wye A.I.C. Rating: 10k AIC
Supply From: ODPB Phases: 3 Mains Type: MLO Supply From: TR-2C Phases: 3 Mains Type: MCB Supply From: TR-2D Phases: 3 Mains Type: MCB
Mounting: Surface Wires: 4 Mains Rating: 250 A Mounting: Surface Wires: 4 Mains Rating: 125 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Enclosure: 1 Enclosure: 1 MCB Rating: 110 A Enclosure: 1 MCB Rating: 110 A

REVISION
Notes: Notes: Notes:
NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL.

1 Addendum #01
3 Addendum #03
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2

NO.
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6
7 Fan Powered VAV Box 'FPV-2-12' - Rm B1121 20 A 1 609 5014 3 30 A Air Cooled Condensing Unit 'ACC-3' - on Roof 8 7 Recepts - Rm B1133 20 A 1 1080 1260 1 20 A Recepts - Rm B1032 8 7 Recepts - Rm C1080 20 A 1 720 900 1 20 A Recepts - Rms C1067 & C1071 8
9 Fan Powered VAV Box 'FPV-2-09' - Cell B1118 20 A 1 609 5014 -- -- -- 10 9 Recepts - Rm B1133 20 A 1 1080 1080 1 20 A Recepts - Rms B1025, B1030 & B1032 10 9 Recepts - Rm C1080 20 A 1 720 900 1 20 A Recepts - Rm C1071 10

CHK'D: MLH
11 Lighting - Medical Services, Medical Dayrooms 20 A 1 2347 5014 -- -- -- 12 11 Recepts - Rm B1133 20 A 1 1080 1080 1 20 A Recepts - Rm B1043 12 11 Recepts - Rm C1078 20 A 1 900 720 1 20 A Receptacle ATTORNEY C1068 12

SEPTEMBER 5, 2019
13 Lighting - Medical Center Cells 20 A 1 850 5817 3 30 A Computer Room Unit 'CRAC-1' - Rm C1079 14 13 Recepts - Rms B1131 & B1132 20 A 1 1080 1872 2 30 A Guardian - Rm B1043 14 13 Recepts - Rm C1077 20 A 1 900 720 1 20 A Receptacle ATTORNEY C1068 14

1663-1190-90
15 Lighting - Medical Records, Inmate Storage,... 20 A 1 1393 5817 -- -- -- 16 15 Recepts - Rms B1122 & B1130 20 A 1 1080 1872 -- -- -- 16 15 Recepts - Rms C1025 & C1076 20 A 1 720 720 1 20 A Recepts - Rm C1069 16
17 SPARE 20 A 1 0 5817 -- -- -- 18 17 Recepts - Rms B1129 20 A 1 900 1000 1 20 A Guardian - Rm B1043 18 17 Recepts - Rms C1077 & C1078 20 A 1 1080 900 1 20 A Recepts - Rm C1069 18

PROJECT NUMBER
19 SPACE -- -- 0 0 -- -- SPACE 20 19 Micro - Rm B1124 20 A 1 1200 900 1 20 A Recepts - Rm B1128 20 19 Recepts - Rms C1073 & C1075 20 A 1 900 720 1 20 A Recept - Rm C1070 20

DESIGNED: RDW
MLH
21 SPACE -- -- 0 0 -- -- SPACE 22 21 Refrig - Rm B1124 20 A 1 1000 820 1 20 A Recepts - Rms B1121, B1122 & B1125 22 21 Recepts - Rms C1073 & C1074 20 A 1 720 900 1 20 A Recept - Rm C1070 22

DRAWN: RDW
23 SPACE -- -- 0 0 -- -- SPACE 24 23 Refrig - Rm B1124 20 A 1 1000 1080 1 20 A Recepts - Rms B1126, B1127 & B1128 24 23 Recepts - Rms C1072 & C1073 20 A 1 900 1080 1 20 A Floor Boxes - Rm C1070 24

APPRV'D:
25 SPACE -- -- 0 0 -- -- SPACE 26 25 Recepts - Rms B1122 & B1124 20 A 1 900 1000 1 20 A Washer - Rm B1043 26 25 Sliding Door 'B1025' 20 A 1 396 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 26
27 SPACE -- -- 0 0 -- -- SPACE 28 27 Recepts - Rms B1123 & B1124 20 A 1 900 2400 2 30 A Electric Clothes Dryer - Rm B1043 28 27 Air Cooled Cond. Unit 'ACC-B' - on Roof 30 A 2 915 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 28

DATE:
29 SPACE -- -- 0 0 -- -- SPACE 30 29 Refrig - Rm B1123 20 A 1 1000 2400 -- -- -- 30 29 -- -- -- 915 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 30
31 SPACE -- -- 0 4140 3 30 A Panel 'E2PE' via Transformer 'TR-2E' 32 31 Area B - Cell Valve Controllers 20 A 1 0 396 1 20 A Sliding Door 'B1121A' 32 31 SPARE 20 A 1 0 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 32
33 SPACE -- -- 0 2916 -- -- -- 34 33 SPARE 20 A 1 0 396 1 20 A Sliding Door 'B1121C' 34 33 SPARE 20 A 1 0 900 1 20 A Recepts - Rm C1079 34
35 SPACE -- -- 0 3096 -- -- -- 36 35 SPARE 20 A 1 0 396 1 20 A Sliding Door 'B1121B' 36 35 SPARE 20 A 1 0 0 1 20 A SPARE 36
37 Panels 'E2PC' via Transformer 'TR-2C' 50 A 3 9688 8256 3 50 A Panels 'E2PD' via Transformer 'TR-2D' 38 37 SPACE -- -- 0 0 3 60 A Surge Protective Device 'SPD-E2PC' 38 37 SPACE -- -- 0 0 3 60 A Surge Protective Deivce 'SPD-E2PD' 38

VIGO COUNTY SECURITY CENTER


39 -- -- -- 10628 7995 -- -- -- 40 39 SPACE -- -- 0 0 -- -- -- 40 39 SPACE -- -- 0 0 -- -- -- 40
41 -- -- -- 9936 7995 -- -- -- 42 41 SPACE -- -- 0 0 -- -- -- 42 41 SPACE -- -- 0 0 -- -- -- 42
Total Load: 34374 VA 34311 VA 34083 VA Total Load: 9688 VA 10628 VA 9936 VA Total Load: 8256 VA 7995 VA 7995 VA
Total Amps: 124 A 124 A 123 A Total Amps: 81 A 89 A 83 A Total Amps: 69 A 67 A 67 A
Legend: Legend: Legend:

PANELBOARD SCHEDULES
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
HVAC 1218 VA 100.00% 1218 VA Motor 1188 VA 108.33% 1287 VA Motor 396 VA 125.00% 495 VA
Lighting 4553 VA 100.00% 4553 VA Total Conn. Load: 102763 VA Receptacle 16220 VA 80.83% 13110 VA Total Conn. Load: 30252 VA Receptacle 16020 VA 81.21% 13010 VA Total Conn. Load: 24246 VA

TERRE HAUTE, INDIANA


Motor 2376 VA 104.17% 2475 VA Total Est. Demand: 85863 VA Electric Clothes Dryer 4800 VA 100.00% 4800 VA Total Est. Demand: 26041 VA Cooling 1830 VA 100.00% 1830 VA Total Est. Demand: 21335 VA
Receptacle 41600 VA 62.02% 25800 VA Total Conn. Current: 124 A Misc. 6844 VA 100.00% 6844 VA Total Conn. Current: 84 A Equipment 6000 VA 100.00% 6000 VA Total Conn. Current: 67 A
Cooling 34322 VA 100.00% 34322 VA Total Est. Demand Current: 103 A Misc. Non-Continuous 1200 VA 0.01% 0 VA Total Est. Demand Current: 72 A Total Est. Demand Current: 59 A
Electric Clothes Dryer 4800 VA 100.00% 4800 VA

A NEW
Equipment 6000 VA 100.00% 6000 VA
Misc. 6844 VA 100.00% 6844 VA Notes: Notes:
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

Misc. Non-Continuous 1200 VA 0.01% 0 VA


Notes:
9/25/2019 5:32:05 PM

DRAWING NUMBER

E-703

ELECTRICAL
DLZ INDIANA, LLC
Branch Panel: E2PE Branch Panel: L1P
Location: JANITOR B1108 Volts: 120/208 Wye A.I.C. Rating: 10k AIC Location: ELECTRICAL C1054 Volts: 120/208 Wye A.I.C. Rating: 10k AIC
Supply From: TR-2E Phases: 3 Mains Type: MCB Supply From: TR-L1P Phases: 3 Mains Type: MCB
Mounting: Surface Wires: 4 Mains Rating: 125 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Enclosure: 1 MCB Rating: 60 A Enclosure: 1 MCB Rating: 60 A

Notes: Notes:
NEW SURFACE MOUNTED PANEL. NEW SURFACE MOUNTED PANEL.

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT R
EE
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 CK IN
CO

SS D I A N G
I ON A L E N
PE60018676
D

H
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4

A
STATE OF
L . H I TC

E
I ST ER
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6

No.
7 Recepts - Rm B1096 20 A 1 720 1080 1 20 A Recepts - Male Dayroom Chases 8 7 *, Fire Alarm Control Panel 'FACP-1' - Rm C1054 20 A 1 250 250 1 20 A Temperature Control Panel - Rm C1053 8

EG
9 Recepts - Rm B1096 20 A 1 720 900 1 20 A Recepts - Cells B1102-B1106 10 9 *, Fire Alarm Graphic Panel 'FA-GAP' - Rm C1055 20 A 1 250 250 1 20 A Temperature Control Panel - Rm C1005 10

IN
IN
R
11 Recepts - Rms B1094, B1095 & B1096 20 A 1 900 900 1 20 A Recepts - Cells B1096-B1101 12 11 SPARE 20 A 1 0 250 1 20 A Temperature Control Panel - Rm B1030 12 RV
3 MA FE
13 Recepts - Rms B105, B1108, B1134 & Exterior 20 A 1 1080 1080 1 20 A Recepts - Rms B1095 & B1112 14 13 Self Contained Dry Powder System - Rm C1052A 20 A 1 500 0 1 20 A SPARE 14 P RO
15 Sliding Door 'B1093B' 20 A 1 396 900 1 20 A Recepts - Female Dayroom Chases 16 15 Self Contained Dry Powder System - Rm C1076 20 A 1 500 0 1 20 A SPARE 16
17 Sliding Door 'B1093A' 20 A 1 396 900 1 20 A Recepts - Cells B1114-B1118 18 17 Self Contained Dry Powder System - Rm B1024 20 A 1 500 0 1 20 A SPARE 18
19 Recept on Roof 20 A 1 180 0 1 20 A SPARE 20 19 SPARE 20 A 1 0 0 1 20 A SPARE 20
21 Area B - Cell Valve Controllers 20 A 1 0 0 1 20 A SPARE 22 21 SPARE 20 A 1 0 0 1 20 A SPARE 22
23 SPARE 20 A 1 0 0 1 20 A SPARE 24 23 SPARE 20 A 1 0 0 1 20 A SPARE 24
25 SPACE -- -- 0 0 3 60 A Surge Protective Device 'SPD-E2PE' 26 25 SPACE -- -- 0 0 3 60 A Surge Protective Device 'SPD-L1P' 26
27 SPACE -- -- 0 0 -- -- -- 28 27 SPACE -- -- 0 0 -- -- -- 28
29 SPACE -- -- 0 0 -- -- -- 30 29 SPACE -- -- 0 0 -- -- -- 30
Total Load: 4140 VA 2916 VA 3096 VA Total Load: 1000 VA 1000 VA 750 VA
Total Amps: 35 A 24 A 26 A Total Amps: 9A 9A 6A
Legend: Legend:

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Motor 792 VA 112.50% 891 VA Equipment 1500 VA 100.00% 1500 VA
Receptacle 9360 VA 100.00% 9360 VA Total Conn. Load: 10152 VA Total Conn. Load: 1500 VA
Total Est. Demand: 10251 VA Total Est. Demand: 1500 VA
Total Conn. Current: 28 A Total Conn. Current: 4A
Total Est. Demand Current: 28 A Total Est. Demand Current: 4A

Notes: Notes:
* = PROVIDE RED BREAKER LOCK KIT FOR MAINTAINING BREAKER IN THE CLOSED POSITION.

09/12/19
09/26/19
DATE
Branch Panel: U1R Branch Panel: U2R Branch Panel: L2P
Location: ELECTRICAL B1028 Volts: 120/208 Wye A.I.C. Rating: 10k AIC Location: ELECTRICAL B1024 Volts: 120/208 Wye A.I.C. Rating: 10k AIC Location: ELECTRICAL B2002 Volts: 120/208 Wye A.I.C. Rating: 10kA
Supply From: TR-U1 Phases: 3 Mains Type: MCB Supply From: TR-U2... Phases: 3 Mains Type: MCB Supply From: TR-L2P Phases: 3 Mains Type: MCB
Mounting: Surface Wires: 4 Mains Rating: 250 A Mounting: Surface Wires: 4 Mains Rating: 250 A Mounting: Surface Wires: 4 Mains Rating: 125 A

REVISION
Enclosure: 1 MCB Rating: 175 A Enclosure: 1 MCB Rating: 175 A Enclosure: 1 MCB Rating: 60 A

1 Addendum #01
3 Addendum #03
Notes: Notes: Notes:
NEW SURFACE MOUNTED PANEL WITH 200% NEUTRAL. NEW SURFACE MOUNTED PANEL WITH 200% NEUTRAL. NEW SURFACE MOUNTED PANEL.

NO.
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4
5 SPARE 20 A 1 0 0 1 20 A SPARE 6
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6
7 Self-Contained Dry Powder System - Rm B2002 20 A 1 500 696 1 20 A Smoke Exhaust Fan 'SEF-2-4' - Roof 8

CHK'D: MLH
7 Floor Box - Rm D1000 20 A 1 540 540 1 20 A Floor Box - Rm E1000 8 7 Floor Box - Rm B1016 20 A 1 540 900 1 20 A Recepts - Rm B1016 8

SEPTEMBER 5, 2019
9 Smoke Exhaust Fan 'SEF-1-3' - Roof 20 A 1 1176 696 1 20 A Smoke Exhaust Fan 'SEF-2-5' - Roof 10

1663-1190-90
9 Floor Box - Rm D1000 20 A 1 540 540 1 20 A Floor Box - Rm E1000 10 9 Floor Box - Rm B1016 20 A 1 540 540 1 20 A Floor Box - Rm B1016 10 11 Smoke Exhaust Fan 'SEF-2-3' - Roof 20 A 1 1176 672 1 20 A *, Vesda Control Panel - Rm E1016 12
11 Recepts - Rm D1000 20 A 1 720 720 1 20 A Recepts - Rm E1000 12 11 TV Recepts - Rm B1016 20 A 1 720 540 1 20 A Floor Box - Rm B1016 12 13 *, Vesda Control Panel - Rm E1016 20 A 1 672 672 1 20 A *, Vesda Control Panel - Rm D1015 14
13 Recepts - Rm D1000 20 A 1 360 360 1 20 A Recepts - Rm E1000 14 13 Radio Charging Recept - Rm B1016 20 A 1 360 360 1 20 A Recepts - Rm B1053A 14 15 *, Vesda Control Panel - Rm E1015 20 A 1 672 250 1 20 A Temperature Control Panel - Rm D1015B 16

PROJECT NUMBER
17 Temperature Control Panel - Rm E1015 20 A 1 250 672 1 20 A *, Vesda Control Panel - Rm D1014 18
15 Security Relay Panel 'SQE#11' - Rm B1028 20 A 1 250 250 1 20 A Security Relay Panel 'SQE#7a' - Rm B1108 16 15 Radio Charging Recept - Rm B1016 20 A 1 360 360 1 20 A Recepts - Rm B1053A 16

DESIGNED: RDW
19 *, Vesda Control Panel - Rm E1014 20 A 1 672 250 1 20 A *, Fire Alarm Control Panel 'FACP-2' - Rm B1028 20

MLH
17 Recepts - Rm B1096 20 A 1 720 250 1 20 A Security Relay Panel 'SQE#7b' - Rm B1108 18 17 Radio Charging Recept - Rm B1016 20 A 1 360 360 1 20 A Recepts - Rm B1053A 18 3

DRAWN: RDW
21 Area 'D' Fire Smoke Dampers 20 A 1 0 250 1 20 A Temperature Control Panel - Rm B2000 22
19 Security Data Rack 'SQE#1' - Rm C1079 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 20 19 Recepts - Rm B1053A 20 A 1 360 360 1 20 A Recepts - Rm B1053A 20 23 Area 'E' Fire Smoke Dampers 20 A 1 0 0 1 20 A SPARE 24

APPRV'D:
21 Security Data Rack 'SQE#1' - Rm C1079 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 22 21 Recepts - Rm B1053A 20 A 1 360 360 1 20 A Recepts - Rm B1053A 22 25 Area 'B' Fire Smoke Dampers 20 A 1 0 0 3 60 A Surge Protective Device 'SPD-L2P' 26
27 SPARE 20 A 1 0 0 -- -- -- 28

DATE:
23 Security Data Rack 'SQE#1' - Rm C1079 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 24 23 Recept - Telephone Terminal Board - Rm B1060 20 A 1 360 360 1 20 A Recepts - Rm B1053A 24
29 SPARE 20 A 1 0 0 -- -- -- 30
25 Security Data Rack 'SQE#1' - Rm C1079 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#1' - Rm C1079 26 25 Security Wall Rack 'SQE#4' - Rm C1046 20 A 1 1500 250 1 20 A Security Relay Panel 'SQE#13' - Rm B1060 26
Total Load: 3462 VA 3044 VA 2770 VA
27 Security Data Rack 'SQE#1' - Rm C1079 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#3' - Rm B2001 28 27 Security Wall Rack 'SQE#5' - Rm B1137 20 A 1 1500 250 1 20 A Security Relay Panel 'SQE#6a' - Rm B1024 28
Total Amps: 29 A 26 A 23 A
29 Security Data Rack 'SQE#1' - Rm C1079 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#3' - Rm B2001 30 29 Security Wall Rack 'SQE#2' - Rm C1104 20 A 1 1500 250 1 20 A Security Relay Panel 'SQE#6b' - Rm B1024 30
Legend:
31 Security Wall Rack 'SQE#14' - Rm D1014 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#3' - Rm B2001 32 31 Emplyee Parking Lot Camera - Exterior 20 A 1 500 1500 1 20 A Communication/Data Rack - Rm B1060 32
33 Security Wall Rack 'SQE#15' - Rm E1014 20 A 1 1500 1500 1 20 A Security Data Rack 'SQE#3' - Rm B2001 34 33 Emplyee Parking Lot Camera - Exterior 20 A 1 500 1500 1 20 A Communication/Data Rack - Rm B1060 34

VIGO COUNTY SECURITY CENTER


35 Security Relay Panel 'SQE#12' - Rm B2000 20 A 1 250 1500 1 20 A Security Data Rack 'SQE#3' - Rm B2001 36 35 Emplyee Parking Lot Camera - Exterior 20 A 1 500 1500 1 20 A Communication/Data Rack - Rm B1060 36
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
37 Security Relay Panel 'SQE#9a' - Rm E1016B 20 A 1 250 250 1 20 A Security Relay Panel 'SQE#8' - Rm D1014 38 37 Visitor Parking Lot Camera - Exterior 20 A 1 500 1500 1 20 A Communication/Data Rack - Rm B1060 38
Motor 3744 VA 107.85% 4038 VA
39 Security Relay Panel 'SQE#9b' - Rm E1016B 20 A 1 250 1000 1 20 A IT Cabinet - Rm D1010 40 39 Visitor Parking Lot Camera - Exterior 20 A 1 500 1500 1 20 A Communication/Data Rack - Rm B1060 40
Power 4032 VA 100.00% 4032 VA Total Conn. Load: 8276 VA
41 Security Relay Panel 'SQE#10' - Rm E1014 20 A 1 250 1000 1 20 A IT Cabinet - Rm E1004 42 41 Visitor Parking Lot Camera - Exterior 20 A 1 500 1500 1 20 A Communication/Data Rack - Rm B1060 42
3 Misc 500 VA 100.00% 500 VA Total Est. Demand: 8570 VA
43 SPACE -- -- 0 1000 1 20 A IT Cabinet - Rm E1015 44 43 Recepts - Rm C1016 20 A 1 360 0 1 20 A SPARE 44
Total Conn. Current: 23 A
45 SPACE -- -- 0 1000 1 20 A IT Cabinet - Rm D1015 46 45 Communication/Data Rack - Rm C1004 20 A 1 1500 0 1 20 A SPARE 46
Total Est. Demand Current: 24 A

PANELBOARD SCHEDULES
47 SPACE -- -- 0 0 -- -- SPACE 48 47 Communication/Data Rack - Rm C1004 20 A 1 1500 0 1 20 A SPARE 48
49 SPACE -- -- 0 0 3 60 A Surge Protective Device 'SPD-U1R' 50 49 SPACE -- -- 0 0 3 60 A Surge Protective Device 'SPD-U2R' 50
51 SPACE -- -- 0 0 -- -- -- 52 51 SPACE -- -- 0 0 -- -- -- 52
Notes:
53 SPACE -- -- 0 0 -- -- -- 54 53 SPACE -- -- 0 0 -- -- -- 54
* = PROVIDE RED BREAKER LOCK KIT FOR MAINTAINING BREAKER IN THE CLOSED POSITION.

TERRE HAUTE, INDIANA


Total Load: 12300 VA 12830 VA 11410 VA Total Load: 8990 VA 9770 VA 9950 VA
Total Amps: 104 A 108 A 95 A Total Amps: 75 A 82 A 84 A
Legend: Legend:

A NEW
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

Receptacle 5040 VA 100.00% 5040 VA Receptacle 8460 VA 100.00% 8460 VA


Equipment 29500 VA 100.00% 29500 VA Total Conn. Load: 34540 VA Equipment 19500 VA 100.00% 19500 VA Total Conn. Load: 27960 VA
Total Est. Demand: 34540 VA Total Est. Demand: 27960 VA
Total Conn. Current: 96 A Total Conn. Current: 78 A
Total Est. Demand Current: 96 A Total Est. Demand Current: 78 A

Notes: Notes:
9/25/2019 5:32:08 PM

DRAWING NUMBER

E-704

ELECTRICAL
DLZ INDIANA, LLC
BASE BID SCHEDULE BASE BID SCHEDULE
Branch Panel: E3H Branch Panel: E3PA
Location: VEHICLE SALLYPORT A1000 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: VEHICLE SALLYPORT A1000 Volts: 120/208 Wye A.I.C. Rating: 10k AIC
Supply From: ODPA Phases: 3 Mains Type: MLO Supply From: TR-3 Phases: 3 Mains Type: MCB
Mounting: Flush Wires: 4 Mains Rating: 250 A Mounting: Flush Wires: 4 Mains Rating: 125 A
Enclosure: 1 Enclosure: 1 MCB Rating: 110 A

Notes: Notes:
NEW FLUSH MOUNTED PANEL - BASE BID LAYOUT. NEW FLUSH MOUNTED PANEL - BASE BID LAYOUT.
PROVIDE THREE (3) EMPTY 1"C. STUBBED OUT INTO VEHICLE SALLYPORT AT +17'-0" AFF FOR FUTURE USE. PROVIDE THREE (3) EMPTY 1"C. STUBBED OUT INTO VEHICLE SALLYPORT AT +17'-0" AFF FOR FUTURE USE.

CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT R
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2 EE
CK IN
CO

SS D I A N G
3 SPARE 20 A 1 0 0 1 20 A SPARE 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4

I ON A L E N
PE60018676
D

H
3

A
STATE OF
L . H I TC

E
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6

I ST ER
No.
7 Exterior Area/Drive Lighting - West 20 A 1 629 930 1 20 A Lighting - Vehicle Sallyport 8 7 Overhead Door 'A1003B' - Rm A1003 20 A 1 1656 1080 1 20 A Recepts - Rms A1000, A1002 & A1003 8
9 Exterior Wall Mounted - Sallyport 20 A 1 259 832 1 20 A Lighting - Evidence/Storage Rooms 10 9 Overhead Door 'A1000H' - Rm A1000 20 A 1 1656 1080 1 20 A Recepts - Rms A1000 & Exterior 10

EG

IN
IN
11 12 11 Overhead Door 'A1000E' - Rm A1000 20 A 1 1656 1080 1 20 A Recepts - Rms A1000 & Exterior 12
R
RV
13 Roof Top Unit 'RTU-1' - on Roof 20 A 3 2659 14 13 Overhead Door 'A1000'I - Rm A1000 20 A 1 1656 1080 1 20 A Recepts - Rms A1000 & Exterior 14 MA FE
15 -- -- -- 2659 16 P RO
15 Overhead Door 'A1000D' - Rm A1000 20 A 1 1656 900 1 20 A Recepts - Rms A1000 & Exterior 16
17 -- -- -- 2659 18 17 Overhead Door 'A1000J' - Rm A1000 20 A 1 1656 900 1 20 A Recepts - Rms A1001, A1002 & Exterior 18
19 Exhaust Fan 'EF-6A' - on Roof 20 A 3 942 942 3 20 A Exhaust Fan 'EF-6B' - on Roof 20 19 Overhead Door 'A1000C' - Rm A1000 20 A 1 1656 1080 1 20 A Recepts - Rm A2000 & A2001 20
21 -- -- -- 942 942 -- -- -- 22 21 Overhead Door 'A1000K' - Rm A1000 20 A 1 1656 216 1 20 A Infrared Heater 'IR-4' - Rm A1000 22
23 -- -- -- 942 942 -- -- -- 24 23 Overhead Door 'A1000B' - Rm A1000 20 A 1 1656 216 1 20 A Infrared Heater 'IR-2' - Rm A1000 24
25 Instantaneous Water Heater 'IWH-1' - Rm A1003 60 A 3 12000 9820 3 50 A Panel 'E3PA' via Transformer 'TR-3' 26 25 Sliding Door 'B1063A' 20 A 1 396 216 1 20 A Infrared Heater 'IR-3' - Rm A1000 26
27 -- -- -- 12000 9880 -- -- -- 28 27 Elec. Unit Heater 'EUH-1' - Rm A2000 20 A 2 1500 216 1 20 A Infrared Heater 'IR-1' - Rm A1000 28
29 -- -- -- 12000 10060 -- -- -- 30 29 -- -- -- 1500 396 1 20 A Sliding Door 'B1055A' 30
Total Load: 27860 VA 27503 VA 26603 VA 3 31 Time Clock 'TC3' - Rm A1000 20 A 1 0 1000 1 20 A Air Compressor Recept - Rm A1003 32
Total Amps: 101 A 100 A 96 A 33 Gate Controller (West Drive) 20 A 1 0 1000 1 20 A Recept Cord Reel - Rm A1003 34
Legend: 35 SPARE 20 A 1 0 1000 1 20 A Recept Cord Reel - Rm A1003 36
37 SPACE -- -- 0 0 3 60 A Surge Protective Deivce 'SPD-E3PA' 38
39 SPACE -- -- 0 0 -- -- -- 40
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 41 SPACE -- -- 0 0 -- -- -- 42
HVAC 43978 VA 100.00% 43978 VA Total Load: 9820 VA 9880 VA 10060 VA
Lighting 2600 VA 100.00% 2600 VA Total Conn. Load: 81965 VA Total Amps: 82 A 82 A 84 A
Motor 21346 VA 103.31% 22052 VA Total Est. Demand: 82571 VA Legend:
Other 0 VA 0.00% 0 VA Total Conn. Current: 99 A
Receptacle 10200 VA 99.02% 10100 VA Total Est. Demand Current: 99 A
Heating 3864 VA 100.00% 3864 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Motor 15696 VA 102.64% 16110 VA
Notes: Receptacle 10200 VA 99.02% 10100 VA Total Conn. Load: 29760 VA
Heating 3864 VA 100.00% 3864 VA Total Est. Demand: 30074 VA
Total Conn. Current: 83 A
Total Est. Demand Current: 83 A

Notes:

ALTERNATE BID SCHEDULE ALTERNATE BID SCHEDULE


Branch Panel: E3H Branch Panel: E3PA

09/12/19
09/26/19
DATE
Location: VEHICLE SALLYPORT A1000 Volts: 480/277 Wye A.I.C. Rating: 42k AIC Location: VEHICLE SALLYPORT A1000 Volts: 120/208 Wye A.I.C. Rating: 10k AIC
Supply From: Phases: 3 Mains Type: MLO Supply From: TR-3 Phases: 3 Mains Type: MCB
Mounting: Flush Wires: 4 Mains Rating: 250 A Mounting: Flush Wires: 4 Mains Rating: 125 A
Enclosure: 1 Enclosure: 1 MCB Rating: 110 A

Notes: Notes:
NEW FLUSH MOUNTED PANEL - ALTERNATE BID LAYOUT. NEW FLUSH MOUNTED PANEL - ALTERNATE BID LAYOUT

REVISION
PROVIDE THREE (3) EMPTY 1"C. STUBBED OUT INTO VEHICLE SALLYPORT AT +17'-0" AFF FOR FUTURE USE. PROVIDE THREE (3) EMPTY 1"C. STUBBED OUT INTO VEHICLE SALLYPORT AT +17'-0" AFF FOR FUTURE USE.

1 Addendum #01
3 Addendum #03
CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT
1 SPARE 20 A 1 0 0 1 20 A SPARE 2 1 SPARE 20 A 1 0 0 1 20 A SPARE 2
3 SPARE 20 A 1 0 0 1 20 A SPARE 3 4 3 SPARE 20 A 1 0 0 1 20 A SPARE 4
5 SPARE 20 A 1 0 0 1 20 A SPARE 6 5 SPARE 20 A 1 0 0 1 20 A SPARE 6

NO.
7 *, (BASE BID) Exterior Area/Drive Lighting - West 20 A 1 0 0 1 20 A *,(BASE BID) Lighting - Vehicle Sallyport 8 7 Overhead Door 'A1003B' - Rm A1003 20 A 1 1656 1080 1 20 A Recepts - Rms A1000, A1002 & A1003 8
9 *,(BASE BID) Exterior Wall Mounted - Sallyport 20 A 1 102 832 1 20 A *,(BASE BID) Lighting - Evidence/Storage Rooms 10 9 SPARE 20 A 1 0 720 1 20 A Recepts - Rms A1000 & Exterior 10
11 12 11 SPARE 20 A 1 0 0 1 20 A *,(BASE BID) Recepts - Rms A1000 & Exterior 12
13 *,(BASE BID) Roof Top Unit 'RTU-1' - on Roof 20 A 3 0 14 13 SPARE 20 A 1 0 0 1 20 A *,(BASE BID) Recepts - Rms A1000 & Exterior 14

CHK'D: MLH

SEPTEMBER 5, 2019
15 -- -- -- 0 16 15 SPARE 20 A 1 0 0 1 20 A *,(BASE BID) Recepts - Rms A1000 & Exterior 16

1663-1190-90
17 -- -- -- 0 18 17 *,(BASE BID) Overhead Door 'A1000J' - Rm A1000 20 A 1 0 900 1 20 A Recepts - Rms A1000, A1001 & A1002 18
19 Exhaust Fan 'EF-ALT-A' - on Roof 20 A 3 0 0 3 20 A Exhaust Fan 'EF-ALT-B' - on Roof 20 19 *,(BASE BID) Overhead Door 'A1000C' - Rm... 20 A 1 0 720 1 20 A Recepts - Rm A2000 & A2001 20
21 -- -- -- 0 0 -- -- -- 22 21 *,(BASE BID) Overhead Door 'A1000K' - Rm... 20 A 1 0 0 1 20 A SPARE 22

PROJECT NUMBER
23 -- -- -- 0 0 -- -- -- 24 23 *,(BASE BID) Overhead Door 'A1000B' - Rm... 20 A 1 0 0 1 20 A *,(BASE BID) Infrared Heater 'IR-1' - Rm A1000 24

DESIGNED: RDW
MLH
25 *,(BASE BID) Ins. Water Heater 'IWH-1' - Rm... 60 A 3 12000 4456 3 50 A *,(BASE BID) Panel 'E3PA' via Trans. 'TR-3' 26

DRAWN: RDW
25 *,(BASE BID) Sliding Door 'B1063A' 20 A 1 0 0 1 20 A SPARE 26
27 -- -- -- 12000 3220 -- -- -- 28 27 *,(BASE BID) Elec. Unit Heater 'EUH-1' - Rm... 20 A 2 1500 0 1 20 A *,(BASE BID) Infrared Heater 'IR-2' - Rm A1000 28

APPRV'D:
29 -- -- -- 12000 3400 -- -- -- 30 29 -- -- -- 1500 0 1 20 A *,(BASE BID) Sliding Door 'B1055A' 30
3

DATE:
Total Load: 16456 VA 16144 VA 15400 VA 31 Time Clock 'TC3' - Rm A1000 20 A 1 0 1000 1 20 A Air Compressor Recept - Rm A1003 32
Total Amps: 60 A 59 A 56 A 33 *,(BASE BID) Gate Controller (West Drive) 20 A 1 0 1000 1 20 A Recept Cord Reel - Rm A1003 34
Legend: 35 SPARE 20 A 1 0 1000 1 20 A Recept Cord Reel - Rm A1003 36
37 SPACE -- -- 0 0 3 60 A *,(BASE BID) Surge Protective Deivce 'SPD-E3PA' 38
39 SPACE -- -- 0 0 -- 3 -- -- 40
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 41 SPACE -- -- 0 0 -- -- -- 42

VIGO COUNTY SECURITY CENTER


HVAC 36000 VA 100.00% 36000 VA Total Load: 4456 VA 3220 VA 3400 VA
Lighting 925 VA 100.00% 925 VA Total Conn. Load: 48000 VA Total Amps: 37 A 27 A 29 A
Motor 1656 VA 125.00% 2070 VA Total Est. Demand: 48414 VA Legend:
Other 0 VA 0.00% 0 VA Total Conn. Current: 58 A
Receptacle 6420 VA 100.00% 6420 VA Total Est. Demand Current: 58 A
Heating 3000 VA 100.00% 3000 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

PANELBOARD SCHEDULES
Motor 1656 VA 125.00% 2070 VA
Notes: Receptacle 6420 VA 100.00% 6420 VA Total Conn. Load: 11076 VA
Heating 3000 VA 100.00% 3000 VA Total Est. Demand: 11490 VA
Total Conn. Current: 31 A

TERRE HAUTE, INDIANA


Total Est. Demand Current: 32 A

Notes:

A NEW
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt
9/25/2019 5:32:17 PM

DRAWING NUMBER

E-707

ELECTRICAL
FURNISH AND INSTALL 120V PROVIDE 120V CONDUIT/WIRE
CONDUIT AND WIRE TO CONNECTION TO TRANSFORMER
TRANSFORMER

LOCATE IN CHASE NEAR CVC


CONDUIT UP AND/OR DOWN PROVIDE J-BOX & COVER PLATE
AS REQUIRED INSTALL SENSOR, SENSOR AND LABEL

DLZ INDIANA, LLC


PROVIDED OTHERS
LOW VOLTAGE (120/24) XFMR
4"x4" BOX PROVIDE BY WATER MANAGEMENT
SYSTEM SUPPLIER. FURNISH AND
EXTENSION RING INSTALL 2-GANG BOX WITH COVER
FOR MOUNTING XFMR
LOW VOLTAGE CONNECTION
BETWEEN TRANSFORMER AND
FURNISH AND INSTALL 2-GANG
DEEP BOX WITH COVER, LOCATE PER CVC FURNISHED AND INSTALLED
MANUFACTURERS RECOMMENDATION BY WATER MANAGEMENT
10 GAUGE SYSTEM SUPPLIER.
BACKPLATE 120VAC (UTILITY DISTRIBUTION NOTES:
PANEL)
DUPLEX RECEPTACLE L N 1. SEE GENERAL NOTE G ON DRAWINGS E-201-A, E-201-B,
OR SWITCH AS PER CONTROL STATION AND E-201-C FOR CIRCUITING REQUIREMENTS.
SPECIFICATIONS. COLOR: GRAY FURNISH AND INSTALL 15 WATT LOW PB1
VOLTAGE TRANSFORMER. TRANSFORMER (FURNISHED BY OTHERS; INSTALLED 2. LOW VOLTAGE CONNECTION BETWEEN CVC AND NOTES:
PROVIDED BY OTHERS AND CONNECTED BY CONTRACTOR) SEE NOTE 3 EACH VAVLE SHALL BE FURNISHED AND INSTALLED 1. DETENTION COVER SHALL BE UL LISTED FOR USE WITH SMOKE DETECTOR.
BY WATER MANAGEMENT SYSTEM SUPPLIER. VERIFY WITH SMOKE DETECTOR MFR THAT COVER WILL ALLOW DETECTOR
MOMENTARY TO FUNCTION PROPERLY.
"OFF" 3. FURNISH AND INSTALL NETWORK CABLING (CAT.6) AS 2. COVER SHALL HAVE CONTINUOUS WELD.
MOMENTARY PB1
R
EE
REQUIRED BY SYSTEM MANUFACTURER BETWEEN 3. COVER SHALL BE 16 GUAGE STEEL WITH PERFORATED HOLES. PROVIDE 3/16"
RESET PB1 CK IN
CO

SS D I A N G
EACH CONTROLLER AND CENTRAL PC WORKSTATION. PERFORATED HOLES ON 1/2" CENTERS. SECURE COVER WITH TORX TYPE SCREWS.

I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC

E
4. COVER SHALL BE NATIONALLY RECOGNIZED TESTING LABORATORIES (NRTL) LISTED.

I ST ER
SEALANT AROUND INSTALL LOW VOLTAGE LEADS FROM

No.
RECEPTACLE PLATE TRANSFORMER TO SOLENOID CELL VALVE CONTROLLERS (CVC) CONNECTION
R1

EG
8 9

IN
DETAIL SMOKE DETECTOR DETENTION COVER DETAIL

IN
R
E-801 SCALE: N.T.S. E-801 SCALE: N.T.S. RV
MOMENTARY CONTACT
MA FE
14 GAUGE STEEL SECURITY P RO
PLATE WITH (4) SECURITY N.O. PUSHBUTTON
MOMENTARY CONTACT N.C.
FASTENERS HUBBEL SWP8 WITH SPRING RETURN FOR
PUSHBUTTON WITH SPRING
ENERGIZING (CLOSING)
OR EQUAL (SWP1 FOR SWITCH) RETURN FOR DE-ENERGIZING
GAS SHUT-OFF VALVE 120VAC CONTROL POWER TRANSFORMER (IN UTILITY DISTRIBUTION PANEL)
NOTES: (OPENING) GAS SHUT-OFF
*COORDINATE LOCATION OF ALL ITEMS VALVE (TYP)
1. SEALANT SHALL BE NONPERMANENT ADHESIVE WHICH WILL ALLOW REMOVAL OF WIRING DEVICE. WITH ALL TRADES AND MANUFACTURERS L N
R1
2. SECURITY FASTENERS SHALL BE CENTER PIN REJECTION TORX. RECOMMENDATION
ANSUL OR EMERGENCY
ANSUL SEE NOTE 2
PUSHBUTTON ACTIVATED
1 2 SHUNT TRIP
VANDALPROOF STYLE RECEPTACLE DETAIL AUTOMATIC ELECTRONIC FLUSH VALVE DETAIL
E-801 SCALE: N.T.S. E-801 SCALE: N.T.S. R2 R1
R1
ANSUL ACTIVATED

MANUAL RESET OF BREAKER


1 2 3 4 5 6 7 8 9 10 11 12 REQUIRED AFTER SHUNT TRIP
R1 (TYPICAL)
120VAC
BR1
24VAC TO UTILITY DISTRIBUTION BRANCH BREAKER 1
PANEL SHUNT TRIP CONTROL
12 PORT FIBER OPTIC PATCH PANEL 3 R2 CIRCUIT. SEE DETAIL 4,
DRAWING E-801.
BR2
BUILDING OUTLET LOCATIONS MAIN DATA FRAME #B1060 (1) 12-FIBER TYPE OM2 SINGLE-MODE
FIBER OPTIC CABLE TO MDF R3
IT #D1010; IT #E1004 BRANCH BREAKER 2
CHASE #D1015B; CHASE #E1014B FROM EACH IDF LOCATION R2
ELECTRICAL #C1004
24VAC GAS SHUTOFF SOLENOID VALVE [N.O.
WHEN DE-ENERGIZED] (VALVE FURNISHED BY
OTHERS) [WIRE FAIL SAFE SO THAT THE GAS
TERMINATE CAT6 CABLE ON VALVE FAILS OPEN WHEN DE-ENERGIZED]
SEE NOTE 1
CAT6 CABLE CAT 6 PATCH PANEL
QUANTITY OF PATCH PANELS
AS REQUIRED. PROVIDE 1 PORT BN
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
FOR EACH CAT.6 DATA CABLE NOTES: BRANCH BREAKER N
1. REFER TO MECHANICAL/PLUMBING FOR ADDITIONAL REQUIREMENTS.
MUTOA 2. REFER TO DRAWING E-201-K, NOTE 260638 FOR PB1 CONTROL STATION LOCATION. NOTES:
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
3. PROVIDE INSTRUCTION SIGN ABOVE PB1 CONTROL STATION FOR 1. QUANTITY 'N' BREAKERS AS INDICATED BY UTILITY DISTRIBUTION PANEL SCHEDULE.
CAT6 PATCH CORD -
OPERATION INSTRUCTIONS FOR A KITCHEN FIRE EVENT. 2. REFER TO DETAIL #3 ON DRAWING E-801.
PROVIDE PATCH
CORD FOR EACH ANSUL OR EMERGENCY PUSHBUTTON CONTROL
VOICE LOCATION
VOICE BLANK 48 PORT CAT 6 PATCH PANEL (DATA) 3 WIRING DIAGRAM 4 SHUNT-TRIP BREAKER WIRING DIAGRAM
(VOIP)
QUANTITY OF PATCH PANELS E-801 SCALE: N.T.S. E-801 SCALE: N.T.S.
AS REQUIRED. PROVIDE 1 PORT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
FOR EACH CAT.6 DATA CABLE
DATA BLANK
NOTES:
1. F/SD ACTUATORS, 120V, TO BE "POWER OPEN - FAIL
SYMBOL SYMBOL 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
CLOSED". POWER SUPPLY BY E.C.
CONNECT TO CIRCUIT L2P-19, L2P-21 OR L2P-23 USING
2#12+G. IN 3/4"C.
2. DUCT SMOKE DETECTOR(S) IN AHU(S):

09/12/19
09/26/19
F/SD (FIRE/SMOKE CORRIDOR A. CABLING PROVIDED BY CONTRACTOR. CABLING.

DATE
48 PORT CAT 6 PATCH PANEL (VOIP)
DAMPER) TERMINATIONS TO AHU BY T.C.C. INTERLOCK TO
3/4" CONDUIT UP AND/OR DOWN
AS REQUIRED OUTSIDE AIR
SHUT-DOWN AHU UPON SMOKE DETECTION.
B. CLOSE F/SD UPON SMOKE DETECTION AT AHU.
F/SD C. SHUT-DOWN AHU REFRIGERATION.
16" 4"x4" BOX
CAT6 CABLE VOICE-LAND LINE TERMINATE CAT 6 CABLE D. DUCT DETECTOR(S) AND REMOTE TEST STATION(S)
AT 110 BLOCK EXTENSION RING FOR EACH AHU PROVIDED BY EQUIPMENT SUPPLIER.
(USE 1 OF 4 PAIRS) 3. WIRING

REVISION
110 BLOCK FOR LAND
AHU A. ALL 120V POWER WIRING BY CONTRACTOR.
SYMBOL LINE/ EMERGENCY
COMMUNICATIONS RTU 4. SMOKE DAMPER
SD RAG

1 Addendum #01
3 Addendum #03
POTS ADAPTOR IF REQUIRED A. CONNECT TO LEGALLY REQUIRED 120VAC BRANCH CIRCUIT.
DAMPER SHALL OPEN UPON ENERGIZATION (OR FAIL CLOSED
TYPICAL DUPLEX RECEPTACLE, UPON DE-ENERGIZATION). POWER TO SMOKE DAMPER(S)
DATA OUTLET, OR SWITCH ASSOCIATED WITH AHU SHALL BE CONTROLLED BY THE FIRE
AND COVERPLATE AS PER F/SD F/SD
RETURN AIR DUCT. ALARM CONTROL PANEL - I.E. THE 120VAC CIRCUIT SHALL BE
SPECIFICATION
8" WIRED VIA THE DRY, FORM C ISOLATION CONTACT (IN THE

NO.
3/4" NIPPLE IAM). UPON DUCT DETECTOR SMOKE DETECTION AS AHU,
ASSOCIATED DAMPER(S) SHALL BLOSE (BE DE-ENERGIZED).
(N) UTILITY DEMARCATION AT TELEPHONE TERMINAL BOARD 'TTB-1' 24V WIRING TO STOP REFER TO DRAWINGS E-203 AND E-204 FOR LOCATIONS OF
SEALANT AROUND AHU FAN AND CLOSE AHU(S) REQUIRING DUCT SMOKE DETECTOR(S). REFER TO
F/SD
RECEPTACLE PLATE F/S DAMPERS BY EC F/SD HVAC PLANS FOR SMOKE DAMPER/DUCTWORK LOCATIONS.

CHK'D: MLH
(SEE SEALANT SD

SEPTEMBER 5, 2019
3
100 PAIR CAT6 FROM UTILITY

1663-1190-90
SPECIFICATION) AHU
LAND A MINIMUM OF 25 OF 100 6"OR 8"OR 12" RAG (RETURN
RIGID PREFORMED BLOCK INSULATION STARTER IAM @ F/S DAMPER
PAIR AT 'TTB-1' AIR GRILL)
NOTES: (ATTACH AS REQUIRED) (SEE NOTE 1) 120V BY E.C. RAG

PROJECT NUMBER
DUCTED RA (RETURN AIR)

DESIGNED: RDW
1. HEAD-END NETWORK EQUIPMENT (SERVER INFRASTRUCTURE, FIREWALL INFRASTRUCTURE, SWITCH INFRASTRUCTURE, WIRELESS INFRASTRUCTURE, MISCELLANEOUS HARDWARE AND FIRE/SMOKE DAMPERS

MLH
ACROSS CORRIDOR
DUCT SMOKE DETECTOR

DRAWN: RDW
INSTALLATION SHALL BE FURNISHED AND INSTALLED BY CONTRACTOR UTILIZING THE OWNER APPROVED IT VENDOR: EDGE INFORMATION TECHNOLOGIES. CONTACT: RYAN EDGELL;
BY EQUIPMENT SUPPLIER * THE CODE REQUIREMENT (IBC SECTION 1 HR RATED CORRIDOR
MOBILE PHONE: 812-514-8127; OFFICE PHONE: 317-436-0190 x810EMAIL: redgell@edgeit.com. OTHER IT VENDORS SHALL NOT BE ACCEPTABLE FOR THIS WORK UNLESS OTHERWISE NOTES:
909 AND NFPA 92) IS TO PROTECT THE AND WALLS

APPRV'D:
PRE-APPROVED BY THE OWNER.
MDF/IDF RACKS/CABINETS AND ALL RACK/CABINET ACCESSORIES (I.E. POWER STRIPS, SURGE PROTECTION, POWER CONDITIONERS, POE INJECTORS, SHELVES/ANCHORS, GROUND STRIPS, 1. ADJACENT BOXES FOR TWO ROOMS SHALL BE INSULATED COMPLETELY AROUND BOX AIR SPACE CORRIDOR FROM SMOKE TO INSURE A

DATE:
WIREWAYS, ETC.) SHALL BE FURNISHED AND INSTALLED AS PART OF THE HEAD-END NETWORK EQUIPMENT. AS INDICATED TO REDUCE SOUND TRANSMISSION THROUGH WALLS. CLEAR EXIT PATH OUT OF THE BUILDING.

REFER TO ELECTRICAL SYSTEMS DRAWINGS FOR MDF AND IDF LOCATIONS. HEAD-END NETWORK EQUIPMENT VENDOR SHALL FIELD COORDINATE MINIMUM RACK UNIT (RU) SPACES AND
LOCATIONS REQUIRED FOR PATCH PANELS WITH STRUCTURED CABLING IT VENDOR. CONTRACTOR/VENDOR SHALL COORDINATE WITH OWNER IN REGARDS TO EXACT REQUIREMENTS FOR 6 BACK TO BACK OUTLET SOUNDPROOFING DETAIL 7 TYPICAL FIRE-SMOKE DAMPER WIRING DETAIL
EQUIPMENT SELECTION, EQUIPMENT PERFORMANCE, MANUFACTURER PREFERENCES, SYSTEM PERFORMANCE, WARRANTIES, PROGRAMMING, TESTING, STARTUP, ETC. AS NECESSARY PRIOR TO
PROCUREMENT. ALL COMPONENTS, ACCESSORIES, SERVICES SHALL BE SUBMITTED AS A COMPLETE, INTEGRATED SYSTEM SHOP DRAWING SUBMITTAL AND SHALL INCLUDE ALL EQUIPMENT E-801 SCALE: N.T.S. E-801 SCALE: N.T.S.
PRODUCT DATA SELECTED AS WELL AS DETAILED AND ITEMIZED MATERIAL AND LABOR FOR EACH EQUIPMENT/LINE ITEM INDICATED IN THE ITEMIZED BILL OF MATERIAL. SUBMITTAL SHALL INCLUDE

VIGO COUNTY SECURITY CENTER


WIRELESS ACCESS POINT HEAT MAP STUDY AND LOCATIONS OF WIRELESS ACCESS POINTS FOR FULL COVERAGE THROUGHOUT THE BUILDING. SUBMITTAL SHALL INCLUDE NETWORK CONNECTION
DRAWINGS AND SYSTEM INTEGRATION DRAWINGS INDICATING EQUIPMENT INTERCONNECT REQUIREMENTS AND DETAILED LABELING OF EQUIPMENT AND COMPONENTS. EQUIPMENT AND
ASSOCIATED COSTING SHALL BE ITEMIZED FOR REVIEW/APPROVAL BY OWNER PRIOR TO PROCUREMENT

SHOP DRAWING SUBMITTAL SHALL INCLUDE ALL COMPONENTS, ACCESSORIES, OPTIONS, AND ITEMS AS NECESSARY FOR A COMPLETE AND FUNCTIONAL NETWORK SYSTEM INCLUDING SERVER
WORKSTATIONS, SOFTWARE, LICENSING, SERVICE, TESTING, STARTUP, AND COMMISSIONING SERVICES. CONTRACTOR/VENDOR SHALL INCLUDE ALL COSTING FOR A COMPLETE AND FUNCTIONAL
SYSTEM. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL COORDINATION, DOCUMENTATION, EQUIPMENT AND NECESSARY FOR A COMPLETE AND FUNCTIONAL SYSTEM; CONTRACTOR
SHALL NOT UTILIZE ENGINEER TO COORDINATE THESE REQUIREMENTS; SUBMITTALS AND PRICING SHALL ALSO BE SUBMITTED TO ENGINEER FOR REVIEW PRIOR TO EQUIPMENT PROCUREMENT. LABELING @ WORK STATION LOCATION LABELING @ PATCH PANEL
CAT 6 BLUE UTP TO
EQUIPMENT SHALL BE WARRANTIED (FULL PARTS AND LABOR) FOR THREE (3) YEARS UPON SUBSTANTIAL COMPLETION. DURING STARTUP AND TRAINING, VENDOR SHALL PROVIDE THE OWNER DESIGNATED PATCH PANEL MAIN DATA ROOM #B1060

ELECTRICAL DETAILS
TYPICAL ROOM ROOM NUMBER OF JACK LOCATION
SERVICE CONTRACT OPTIONS FOR ONGOING FULL SERVICE, PREVENTATIVE MAINTENANCE, AND REPAIRS OF THIS EQUIPMENT FOR ANNUAL/RENEWABLE PERIODS BEYOND THE WARRANTY PERIOD.
ELECTRICAL #C1004
IT #D1010; IT #E1004 CABLE NUMBER IN SEQUENCE OF
CONTRACTOR SHALL FURNISH AND INSTALL UPS BRANCH CIRCUITS, GROUNDING, HOUSEKEEPING, PADS, ANCHORING, AND OTHER EXTRANEOUS ITEMS NECESSARY TO ACCOMMODATE THIS

TERRE HAUTE, INDIANA


CHASE #D1015B; CHASE #E1014B ORDER AS TERMINATED AT PATCH
VENDOR FURNISHED AND INSTALLED EQUIPMENT. CONTRACTOR SHALL INCLUDE THIS ASSOCIATED WORK IN BID
PANEL
CAT 6 STATION CABLE
2. STRUCTURED CABLING AND ALL RELATED ACCESSORIES (I.E. MUTOA OUTLETS, CONDUIT, PATCH CORDS, HORIZONTAL STRUCTURED CABLING SYSTEMS, BACKBONE STRUCTURED CABLING 1-1/4" EMT STUBBED TO CEILING
SYSTEMS, PATCH PANELS, J-HOOKS, CABLE TRAY, TELEPHONE INFRASTRUCTURE, MATV INFRASTRUCTURE, ETC.) SHALL BE FURNISHED AND INSTALLED BY CONTRACTOR UTILIZING THE OWNER PLENUM. PROVIDE WITH
APPROVED IT VENDOR: INNOVATIVE COMMUNICATIONS SOLUTIONS, INC. (ICS). CONTACT:STEVE CLARK; MOBILE PHONE: 812-243-1548; OFFICE PHONE: 812-232-8600; EMAIL: sclark@ics-networking.com. INSULATED BUSHING AT END OF

A NEW
OTHER IT VENDORS SHALL NOT BE ACCEPTABLE FOR THIS WORK UNLESS OTHERWISE PRE-APPROVED BY THE OWNER. RACEWAY IN CEILING
A118-D001 A118-D00 2 A118-D003 A118-D004
STRUCTURED CABLING IT VENDOR SHALL SHALL FIELD COORDINATE MINIMUM RACK UNIT (RU) SPACES AND LOCATIONS REQUIRED FOR PATCH PANELS WITH THE HEAD-END NETWORK EQUIPMENT TRA-V001 TRA-V002
C:\users\rwilley\Documents\1663-VIGO-ELEC_rwilley-DLZ.rvt

FLUSH MOUNTED
VENDOR. DOUBLE GANG BOX
WITH SINGLE GANG TILE
STRUCTURED CABLING IT VENDOR SHALL PROVIDE A MINIMUM FIVE (5) YEAR WARRANTY, INCLUDING ALL PARTS AND LABOR, FOR THE END-TO-END PERMANENT LINK CABLING AND CABLING RING MOUNTED AT 18"
INFRASTRUCTURE. IN ADDITION, THE CABLING OEM (IN CONJUCTION WITH THE USE OF THE OEM'S ASSOCIATED EQUIPMENT PARTNERS) SHALL PROVIDE A MINIMUM TWENTY FIVE (25) YEAR AFF (U.O.N.) VOICE CABLES
WARRANTY. ON TOP 1 2 3 4
COMMUNICATIONS/CONTROL CABLING FOR OTHER SPECIALTY SYSTEMS (I.E. FIRE ALARM, ACCESS CONTROL, SECURITY CAMERAS, INTERCOM, ETC.) IS NOT PART OF THE IT VENDOR STRUCTURED A118-D001
CABLING WORK. CONTRACTOR SHALL INCLUDE THIS ASSOCIATED WORK IN BID; THIS ASSOCIATED WORK BY CONTRACTOR SHALL BE INCLUDED WITH BID AND SHALL NOT BE PART OF THE
AFOREMENTIONED AFOREMENTIONED IT VENDOR STRUCTURED CABLING WORK. TRA-D001 A118-D002
A118-D025 A118-D026 A118-D027 A118-D028
3. SINGLE GANG
MISCELLANEOUS SYSTEMS: CONTRACTOR SHALL FURNISH AND INSTALL CONDUIT, GROUNDING, CABLE TRAY, J-HOOKS, FIRESTOPPING, PENETRATIONS/BLOCKOUTS, PULLSTRINGS, WIRING
DEVICE BOXES, SLEEVES/ENDBELLS/BUSHINGS, SUPPORTS/HANGERS, PULLBOXES, HANDHOLES, PLYWOOD BACKBOARDS, AND OTHER EXTRANEOUS ITEMS NECESSARY TO ACCOMMODATE THIS FACE PLATE
VENDOR FURNISHED AND INSTALLED EQUIPMENT FOR A COMPLETE AND FUNCTIONAL SYSTEM. CONTRACTOR SHALL INCLUDE THIS ASSOCIATED WORK IN BID; THIS ASSOCIATED WORK BY DATA CABLES TRA-D002
CONTRACTOR SHALL BE INCLUDED WITH BID AND SHALL NOT PART OF THE STRUCTURED CABLING VENDOR OR NETWORK HEAD-END EQUIPMENT VENDOR WORK AFOREMENTIONED. ON BOTTOM

4. OWNER SHALL PROCURE THE FOLLOWING SYSTEMS AS PART OF THE FF&E (FINISHES, FURNITURE, AND EQUIPMENT) ALLOWANCE: 25 26 27 28
A. WORKSTATIONS AND ACCESSORIES (I.E. PATCH CORDS, UNINTERRUPTIBLE POWER SUPPLIES).
B. VOIP HEAD-END EQUIPMENT, VOIP HANDSETS, VOIP INTERCOM INTERFACE. TRA-D001 TRA-D002
POINT OF
C. TELEVISIONS AND TV MOUNTING ACCESSORIES. TERMINATION
D. AUDIO/VIDEO CONFERENCING EQUIPMENT. CATEGORY 6 DATA
9/25/2019 5:37:16 PM

(IT CLOSET NUMBER)


E. SPECIALTY COMMUNICATIONS SYSTEMS NOT OTHERWISE NOTED IN PLANS AND SPECIFICATIONS JACKS 48 PORT CAT 6 PATCH PANEL

5. SEE ELECTRICAL SYSTEMS PLANS FOR DETAILED LOCATIONS AND MUTOA OUTLETS REQUIRED.
CABLE NUMBER CABLE LABELED AT PATCH PANEL
NOTE: (IN SEQUENCE OF TO MATCH PATCH PANEL LABEL

DRAWING NUMBER
6. BICSII INSTALLER LEVEL 2 CERTIFICATION IS REQUIRED BY THE CONTRACTOR. TELECOMM DESIGNER SHALL HAVE RCDD CERTIFICATION. PROVIDE DOCUMENTATION OF ALL
TERMINATION)
3 CERTIFICATIONS FOR ENGINEER REVIEW/APPROVAL PRIOR TO PROCUREMENT/INSTALLATION. CONTRACTOR SHALL PROVIDE AND INSTALL

E-801

ELECTRICAL
ALL ACCESSORIES REQUIRED FOR A
COMPLETE AND FUNCTIONAL SYSTEM CABLE LABELED AT STATION LOCATION
TO MATCH JACK LABEL
5 TYPICAL HORIZONTAL WIRING DIAGRAM TYPICAL JACK CABLE AND PATCH PANEL LABELING
E-801 SCALE: N.T.S. 10 TYPICAL 2-PORT DATA DETAIL 11 DIAGRAM
E-801 SCALE: N.T.S. E-801 SCALE: N.T.S.
MECHANICAL OR EXOTHERMAL
BONDING POINT (TYPICALLY
ABOVE PEDESTAL LEVELER UNIT)
SIGNAL REFERENCE GRID
(METAL STRINGERS OF WIRE HANGER AT EACH
RAISED FLOOR SYSTEM) CORNER OF FIXTURE
INDEPENDENT OF RECESSED TROFFER
CEILING SUPPORT SYSTEM

#1 BLACK

DLZ INDIANA, LLC


EMERGENCY HOT #5 BLUE
BONDING STRAP REGULAR HOT
24" MAX. TYP. 20A EMERGENCY
POWER #2 ORANGE 20A
#6 YELLOW *
EMERGENCYLIGHT #3 RED
UTILITY
METALLIC BOND POWER
TO "SRG" #4 WHITE
EMERGENCY NEUTRAL #7 WHITE/BLUE

EMERGENCY REGULAR
NEAREST AVAILABLE POWER POWER
WATER PIPE OR * = RELAY PANEL, POWER PACK, SENSOR OR OTHER (OPTIONAL) FIXTURE CLAMP
BUILDING STEEL PROVIDE 2 PER SIDE
EMERGENCY POWER CONTROL MODULE WIRING
FLOOR PANEL
2'X2' (TYP.)
7 DIAGRAM
E-802 SCALE: N.T.S.
ALL HORIZONTAL AND VERTICAL
METALLIC OBJECTS TYPICALLY
BONDED TO PERIMETER
CONDUCTOR LAY-IN R
EE
CEILING GRID
CK IN
CO

SS D I A N G
HOT

I ON A L E N
PE60018676
D

A
STATE OF
L . H I TC

E
I ST ER
4 TYPICAL RECESSED FIXTURE MOUNTING DETAIL

No.
DATA CABLE E-802 SCALE: N.T.S.
CONDUIT (TYP.) NEUTRAL

EG

IN
IN
R
RV
MA FE
P RO

BLACK
#2/0 BARE COPPER SOLID
OR STRANDED AROUND
PERIMETER OF ROOM WHITE
W.P., GALV. C.I. J-BOX
RED (+20 - 24V)
W/NEOPRENE GASKET,
10 RAISED FLOOR GROUDING DETAIL RED LIGHTING CONCRETE BASE HOPE # H402 W/ # P70
BLUE (SIGNAL) 3 5 12" X 12" X 12"
E-802 SCALE: N.T.S. LOAD COVER. TOP OF BOX
RACK MOUNT, CAT 6 BLACK (COMMON) RED 1/2" ABOVE CONC.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
48 PORT PATCH PANEL
(BY CONTRACTOR)
(QTY AS REQUIRED) DRILLED & TAPPED
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 STUB OUT HOLES FOR CONDUIT
1 EMPTY 3/4"C. AS SIZED ON PLANS
WHERE SHOWN
2 2 2 ON PLANS

IT ROOM
BUILDING STATION
LOCATIONS
3 TYPICAL FLOOD LIGHT CONCRETE BASE DETAIL
E-802 SCALE: N.T.S.
6'-0" CAT 6
PATCH CORD (MAX 3 SENSORS
LEGEND: 4
[TYPICAL] PER ZONE)
VOIP - VOICE OVER INTERNET PROTOCOL
DATA
WAP - WIRELESS ACCESS POINT # CODED NOTES:
VOIP/DATA
CAT 6
WAP 1. FURNISH AND INSTALL MANUAL OFF OVERRIDE SWITCH(S) WHERE
INDICATED ON PLANS.
WORKSTATION LABEL "ELECTRICAL"
TYPICAL WIRELESS AS NEEDED
(BY OWNER) 2. FURNISH AND INSTALL CEILING MOUNT DUAL SENSOR (INFRARED, 3/8-16 UNC STAINLESS
SYMBOL ACCESS POINT SYMBOL
ULTRASOUND) OCCUPANCY SENSOR. SEE LIGHTING PLAN FOR STEEL HEX HEAD BOLT
LOCATIONS. FIELD ADJUST 0-30 MINUTE TIME DELAY ON SENSOR W/WASHER (2)
PER OWNER'S WRITTEN INSTRUCTION. 73
/8"
TELEPHONE HANDSET "
(BY OWNER) 3. POWER PACK WITH HEAVY DUTY CONTACT AND RELAY CONTROL. 9 3/8
"
NOTES: 4. ALL CONTROL WIRING SHALL BE NOT LESS THAN 2#14, #14G., 3 /4
1/2"C., U.O.N. GO
1. RECEPTACLES (TELEPHONE AND/OR DATA/TELEPHONE), CONDUIT, PATH CABLES, PATCH LO
PANELS, FLOOR STANDING CABINETS, ETC. A COMPLETE FUNCTIONING AND CERTIFIED . ..
.. .. .. .. .. ... . . 1/2" X 2"
. . .. . . .
DATA-COMMUNICATION SYSTEM SHALL BE PROVIDED AND INSTALLED AS REQUIRED. 5. TRANSFORMER, POWER PACK AND ALL ASSOCIATED COMPONENTS . .... .... .. .. .. .... .. PULL SLOT
SHALL BE INSTALLED IN A NEMA APPROVED BOX. COVER
.
GENERAL NOTES:
2. DOCUMENTS REFLECT BASIS-OF-DESIGN AND SYSTEM PERFORMANCE REQUIREMENTS. SKID RESISTANT
PROVIDE SYSTEM COMPONENTS COMPATIBLE WITH EACH OTHER AND OVERALL SYSTEM. SURFACE 1. COVER LOGO TO STATE "ELECTRICAL" OR "COMMUNICATIONS".
6 OCCUPANCY SENSOR WIRING DETAIL
3. PROPOSED SUBSTITUTIONS SHALL BE SUBMITTED AND REVIEWED IN ACCORDANCE WITH E-802 9" 2. TIER 22 BOX AND COVER TO BE MANUFACTURER BY
SCALE: N.T.S.
DIVISION 00 AND DIVISION 01 OF THE PROJECT MANUAL. " HUBBELL/QUAZITE (OR EXACT EQUAL APPROVED BY ENGINEER).
11
4. BICSI/RCDD CERTIFICATION IS REQUIRED FOR CABLING LAYOUT AND INSTALLATION. 71
/2" 3. POWER CABLE SPLICES (AS APPROVED BY ENGINEER) SHALL

09/12/19
09/26/19
CONTRACTOR SHALL PROVIDE DOCUMENTATION. "
1/2

DATE
BE WATER RESISTANT. USE GEL FILL WIRE NUTS (I.E. IDEAL
8 6 3/4"
5. PROVIDE TWO (2) DEDICATED POTS LINES FOR FIRE ALARM CONTROL PANEL. PROVIDE OR APPROVED EQUAL) WITH MASTIC TAPE WRAPPED AROUND
ADDITIONAL POTS LINES AS REQUIRED FOR BMS, SECURITY, ETC. FIELD COORDINATE WITH #10 PHASE CONDUCTORS UP SPLICES FOR WATERTIGHT SEAL (I.E. 3M OR APPROVED EQUAL).
COMMUNICATION UTILITY ON REQUIREMENTS PRIOR TO CONSTRUCTION. TO LUMINAIRE (1 OR 2 CONDUCTORS)
#10 GROUND AND NEUTRAL 4. PROVIDE SOLID BOTTOM FOR RODENT RESISTANCE. HANDHOLE
6. FOR DETAILED REQUIREMENTS FOR COMMUNICATIONS HORIZONTAL CABLING, REFER TO TYPICAL WATERTIGHT IN LINE FUSE HOLDER WITH FUSE BOX SHALL HAVE BITUMINOUS COATING ON THE EXTERIOR TO
SPECIFICATIONS. SIZED PER MANUFACTURER RECOMMENDATIONS FOR MINIMIZE WATER PENETRATION.
(TYPICAL) COIL EXCESS TO ALLOW
EACH PHASE CONDUCTOR
FUSES AND CONNECTORS TO BE

REVISION
REMOVED THRU HANDHOLE 5. REFER TO DRAWING E-101 FOR PULLBOX LOCATIONS.
STRUCTURED CABLING DETAIL - TYPICAL FOR EACH HANDHOLE WITH COVERPLATE

1 Addendum #01
3 Addendum #03
9 INTERMEDIATE DISTRIBUTION FRAME 2 X 2-1/2" X 4"
POLE GROUNDING LUG OPTIONAL MOUSEHOLES
E-802 SCALE: N.T.S. OPPOSITE OF HANDHOLE 1 EACH END
LEVELING NUTS WITH WASHERS. PROTECT NUTS
AND THREADS DURING CONCRETE POUR

4"
30" 1" ROUNDED CHAMFER. SLOPE

NO.
TOP FROM CENTER TO EDGE
"
36

4"
TELECOM EQUIPMENT SCHEDULE
BLANK ANCHOR BOLTS FURNISHED BY 2 ELECTRIC HANDHOLE DETAIL

(TYP.FOR FIXTURES 'SB', 'SC', 'SD' & 'SE')