Professional Documents
Culture Documents
SWITCHBOARD
NOTE: MOUNTING HEIGHTS FOR DEVICES UNLESS NOTED OTHERWISE
D I
4" 4"
BACKSPLASH HOUSEKEEPING PAD (TYPICAL, REQUIRED BUT NOT SHOWN ON PLANS) NOTES:
INCOMING OR 'MAIN' SECTION 1. The design on this drawing is copyright and remains
48" the property of Century Property Developments.
DISTRIBUTION SECTION 2. All work to be carried out in strict accordance
with local authority requirements, National Building
18" 18" Regulations, and the S.A.B.S standards.
FLOOR MOTOR CONTROL CENTER 3. This drawing may not be scaled. Only figured
I D D D F dimensions and levels may be used.
RECEPTACLE COMMUNICATION ABOVE ABOVE WALL SWITCH, LOW VOLTAGE 4. All relevant details, levels, dimensions must be
& TV COUNTER COUNTER SWITCH, WALL SWITCH checked on site before commencement of work. Any
discrepenies to be reported to the Architects office
RECEPTACLE COMMUNICATIONS OCCUPANCY SENSOR, TIMER FUTURE SECTION
immediately.
& WALLBOX DIMMER DISTRIBUTION SECTION
REV DATE DESCRIPTION
CEILING INCOMING SECTION
12" MAX TO TOP
X HOUSEKEEPING PAD (TYPICAL, REQUIRED BUT NOT SHOWN ON PLANS)
PANELBOARD
FLOOR
PANELBOARD/SWITCHBOARD NAMING
WALL PHONE CARD READER, SHUNT TRIP TIMECLOCK WALL MOUNTED WALL BLDG-E1MDPHA1
KEYPAD, RTE, PUSHBUTTON (LIGHTING CAMERA, & PTZ MOUNTED
PUSHPLATE, DOORBELL, (EMERGENCY CONTROL) CAMERA SPEAKER A,B,C... DESIGNATOR DISTINGUISHES ROOM OR ROOM PANEL SERVED FROM
& BIOMETRIC READER POWER OFF) 1,2,3... DESIGNATOR DISTINGUISHES INDIVIDUAL PANEL/SWITCHBOARD
H - 480Y/277V
L - 208Y/120V
CL NOTHING INDICATES LIGHTING/RECEPTACLE PANEL BRANCH PANEL
M AV - AUDIO VISUAL PANEL
EXIT
DP - DIMMING PANEL
6" GDP - GENERATOR DISTRIBUTION PANEL
GSB - GENERATOR SWITCHBOARD
INV - INVERTER
K - KITCHEN PANEL
90" (AUDIBLE
LC - LOAD CENTER
8" BELOW CEILING, DEVICES SHALL DOOR LCP - LIGHTING CONTROL PANEL
MAXIMUM 12'-0" AFF. NOT BE CLOSER 6"
F MC - METER CENTER
THAN 6" TO TOP
MCC - MOTOR CONTROL CENTER
OF DEVICE TO
4" MDP - MAIN DISTRIBUTION PANEL (SERVICE ENTRANCE)
CEILING IN LOW
MSB - MAIN SWITCHBOARD (SERVICE ENTRANCE)
48" CEILING AREAS)
PDU - POWER DISTRIBUTION UNIT
EXIT EXIT
SB - SWITCHBOARD
10"-12" 10"-12" ST - SHUNT TRIP PANEL
FLOOR T - TENANT PANEL
TC - TELECOMMUNICATIONS PANEL
WALL WALL MOUNTED FIRE ALARM FIRE ALARM WALL
SC - SHOW CONTROL PANEL
MOUNTED EMERGENCY PULL VISUAL, AUDIO &
R - RIDE POWER PANEL
OCCUPANCY LIGHT STATION AUDIO/VISUAL
SENSOR NOTIFICATION INDICATES WHICH FLOOR PANEL IS LOCATED ON (IF REQUIRED)
NOTHING INDICATES NORMAL
E - EMERGENCY
SINGLE LINE SYMBOLS INDICATES WHICH BUILDING/AREA PANEL IS LOCATED IN (IF REQUIRED)
TRANSFORMER
CKT BREAKER, '###' INDICATES NAME
###/# TRIP SETTING, '#' INDICATES M UTILITY METER
NUMBER OF POLES FLOOR MOUNTED TRANSFORMER, NUMBER INDICATES KVA RATING
X
SS - SOLID STATE
GFP - GROUND FAULT PROTECTION HOUSEKEEPING PAD (TYPICAL, REQUIRED BUT NOT SHOWN ON PLANS)
ERMS - ENERGY-REDUCING MINI POWER
MAINTENANCE SWITCH ZONE PANEL
PANEL INDICATES TRANSFORMER IS SUSPENDED
EO - ELECTRICALLY OPERATED
NAME
ENCLOSED NON-FUSED TRANSFORMER DESIGNATION
BLDG-TE1DPHA1
DISCONNECT SWITCH
INDICATES PANEL SERVED
INDICATES TRANSFORMER
PANEL INDICATES WHICH BUILDING/AREA TRANSFORMER IS LOCATED IN (IF
ENCLOSED FUSED PANELBOARD
NAME REQUIRED)
DISCONNECT SWITCH
L GENERATOR
ENCLOSED CIRCUIT CONNECTION exp U.S. Services Inc.
BREAKER S2 PANEL WITH AUTOMATIC TRANSFER SWITCH DESIGNATION
S1 BLDG-ATSE1HA1 t: +1.414.221.0088 f: +1.414.221.0537
MANUAL 241 North Broadway, Suite 203
TRANSFER Milwaukee, WI 53202
FUSED SWITCH, '###' INDICATES SWITCH USA
INDICATES PANEL SERVED
###/# TRIP SETTING, '#' INDICATES www.exp.com
INDICATES AUTOMATIC TRANSFER SWITCH
NUMBER OF POLES L Project #: 21008941-00
AUTOMATIC INDICATES WHICH BUILDING/AREA AUTOMATIC TRANSFER SWITCH IS Cert of Auth: 29701
TRANSFER LOCATED IN (IF REQUIRED)
E N SWITCH
KIRK KEY
K INTERLOCK
PROJECT NAME
PHASE
11/12/2021 12:19:30 PM
0000 E002