Professional Documents
Culture Documents
General Notes
000 TCCC COVER PAGE - TENDER E6 ELECTRICAL POWER - PANEL SCHEDULE - PHASE 1
A002 OBC MATRIX AND GENERAL INFO E7 ELECTRICAL DETAILS
A101 SITE PLAN E8 ELECTRICAL DETAILS
A200 EXISTING - FLOOR PLAN E9 ELECTRICAL SPECIFICATION
A201.0 DEMOLITION - FLOOR PLANS E10 ELECTRICAL SPECIFICATION
A201.1 PH1 - BASE BUILD (BB) PLAN M1 MECHANICAL HVAC - ROOF PLAN
A201.2 PH2 - INTERNAL FIT OUT (IFO) PLANS M2 MECHANICAL HVAC - PLANS
A202.1A PH1 - BB - REFLECTED CEILING PLAN (LOW ROOF) M3 MECHANICAL HVAC - SEPERATE PRICE
A202.1B PH1 - BB - REFLECTED CEILING PLAN (HIGH ROOF) M4 MECHANICAL HVAC - SCHEDULES
A204 EXISTING - ROOF PLAN M5 MECHANICAL HVAC - SCHEDULES
A204.0 DEMOLITION - ROOF PLAN M6 MECHANICAL SPECIFICATIONS
A204.1 PH1 - BB - ROOF PLAN M7 MECHANICAL SPECIFICATIONS
A300 EXISTING - EXTERNAL ELEVATIONS P1 MECHANICAL PLUMBING PLANS
A301.0 DEMOLITION - EXTERNAL ELEVATIONS P2 MECHANICAL PLUMBING-SCHEDULE DETAILS
A301.1 PH1 - BB - EXTERNAL ELEVATIONS P3 MECHANICAL PLUMBING-SCHEDULE DETAILS
A401.1 PH1 - BB - MAIN SECTIONS S101 GENERAL NOTES
A501 CONSTRUCTION DETAIL TYP. WALL S102 GENERAL NOTES
A502 CONSTRUCTION DETAILS Sht 1 S103 TYP. DETAILS
A503 CONSTRUCTION DETAILS - Sht 2 S104 TYP. DETAILS
A504 CONSTRUCTION DETAILS - ROOF S105 TYP. DETAILS
A505 CONSTRUCTION DETAILS - EXTERNAL STAIRS S106 TYP. DETAILS
A506 CONSTRUCTION DETAILS - FOLDING PARTITION 1 S107 TYP. DETAILS
A507 CONSTRUCTION DETAILS - PLINTH S201 PART FOUNDATION PLAN
A508 CONSTRUCTION DETAILS - PH2 - FOLDING PARTITION 2 S202 PART FOUNDATION PLAN
A509 CONSTRUCTION DETAIL - VIP AREA S203 NO DRAWING Rev. Date Description
A600.1 PH1- BB - DOOR SCHD S204 PART ROOF WATERPONDING LOADING DIAGRAM
A600.2 PH2 - IFO - DOOR SCHD S301 COLUMN SCHEDULE
A601.1 PH1 - BB - WINDOW SCHD S302 PIER DETAIL, PILE CAP DETAIL AND BASE SCHEDULE Coolearth Architecture Inc.
A601.2 PH2 - IFO - WINDOW SCHD S401 SECTIONS AND DETAILS 386 Pacific Avenue,
A602.1 PH1 - BB - CONST TYP.DETAILS S402 SECTIONS AND DETAILS
A602.2 PH2 - IFO - CONST TYP. DETAILS S410 SECTIONS AND DETAILS Toronto, ON M6P 2R1
E1 ELECTRICAL POWER & LIFE SAFETY PLAN S411 SECTIONS AND DETAILS www.coolearth.ca
E2 ELECTRICAL LIGHTING PLAN - PHASE 1 S412 SECTIONS, ELEVATIONS, AND DETAILS
E3 ELECTRICAL POWER (SEPERATE PRICE) S501 ELEVATIONS t: 416-868-9774
E4 ELECTRICAL SINGLE LINE DIAGRAM - PHASE 1 S502 ELEVATIONS
E5 ELECTRICAL FIRM ALARM DIAGRAM - PHASE 1
Engineering Link Incorporated Professional Seal
170501
16011
Scale
CW
TIBETAN CANADIAN
t: 416-599-5465 CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Enersync Ltd. Project
Drawing title
000
t: 289-652-5996
Sheet no.
20 Others - Describe N/A
Item Ontario's 2006 Building Code - Data Matrix Parts 3 & 9 OBC Reference
TRUE PROJECT
Item Ontario Building Code Data Matrix - Division B, Part 11 - Renovation of Existing Building OBC Reference NORTH NORTH
1 Project Description: New X Part 11 X Part 3 Part 9
Addition 11.1 Existing Building Describe Existing Use: Group A, Division 2 CULTURAL CENTRE 11.2.1
11.1 to 11.4 1.1.2[A] 1.1.2 [A] & DRAWING SHOULD NOT BE SCALED
Change of Use classification: Construction Index: - T 11.2.1.1A
X Alteration Contractor must check and verify all dimensions on the
9.10.1.3 - job and report any discrepencies to the architect before
Hazard Index: T 11.2.1.1B to N proceeding with the work. This drawing shall not be
2 Major Occupancy(s) Group A, Division 2 CULTURAL CENTRE 3.1.2.1.(1) 9.10.2 used for construction purposed until signed by the
x Not Applicable (no change of major occupancy) consultant responsible. This drawing, is an instrument
3 Building Area (m ²) Existing 4578.5 New Total 4578.5 1.4.1.2 [A] 1.4.1.2 [A] of service, is provided by and is the property of Coolearth
4 Gross Area Existing 4760.90 New Total 4760.90 1.4.1.2 [A] 1.4.1.2 [A] 11.2 Alteration to Basic Renovation 11.3.3.1 Architecture Inc.
5 Number of Storeys Above grade 2 Below grade: 0 1.1.4.2. [A] &3.2.1.1. 1.4.1.1. [A] & 9.10.4 Existing Building is: Extensive Renovation x 11.3.3.2
General Notes
6 Number of Streets/Fire Fighter Access 1 3.2.2.10 & 3.2.5. 9.10.20 11.3 Reduction in
7 Building Classification 3.2.2.24. Group A, Division 2, up to 6 Storeys 3.2.2.20-.83 9.10.2 Performance Level: 11.4.2
8 Sprinkler System Proposed EXISTING X Entire Building 3.2.2.20-.83 9.10.8.2 Structural: NO X Yes 11.4.2.1
Selected Compartments 3.2.1.5 By Increase in occupant load: X NO Yes 11.4.2.2
Selected Floor Areas 3.2.2.17 By change of major occupancy: X NO Yes 11.4.2.3
Basement INDEX INDEX Plumbing: NO X Yes 11.4.2.4
in lieu of roof rating INDEX INDEX Sewage-system: X NO Yes 11.4.2.5
not required 11.4 Compensating
X Yes No Construction: 1.4.3 N RD
9 Standpipe required 3.2.9 N/A TITA
Structural: NO X Yes (explain)
10 Fire Alarm required X Yes No 3.2.4 9.10.8
RENOVATION/REINFORCEMENT OF EXISTING STRUCTURE AND 11.4.3.2
11 Water Service/Supply is Adequate X Yes No 3.2.5.7 N/A
REPLACEMENT WHERE REQUIRED TO SUIT REQUIRED LOADS
12 High Building Yes X No 3.2.6 N/A
13 Permitted Construction Combustible X Non-combustible Both 3.2.2.20-.83 9.10.6
Increase in occupant load: X NO Yes 11.4.3.3
Actual Construction (NEW) Combustible X Non-combustible Both
-
14 Mezzanine(s) Area m² N/A 3.2.1.1.(3)-(8) 9.10.4.1
15 Occupant load based on m²/person X design of building 3.1.17 9.9.1.3
Ground Floor Occupancy: AS POSTED Load: 832 persons
ISLIN
Change of major occupancy: X NO Yes 11.4.3.4
KIPL
Second Floor Occupancy: 0 Load: 0 persons
GTO
-
ING
16 Barrier-free Design X Yes NO (Explain) 3.8 9.5.2
N AV
AVE
17 Hazardous Substances Yes X NO 3.3.1.2. & 3.3.1.19 9.10.1.3(4)
E.
CONTEXT MAP - GOOGLE IMAGE (NTS)
.
18 Required Horizontal Assemblies Listed Design No. 3.2.2.20-.83 & 3.2.1.4 9.10.8
Plumbing: NO X Yes 11.4.3.5
Fire FRR (Hours) or Description (SG-2) 9.10.9
ROUGH IN OF SERVICES BELOW SLAB FINISH FOR
Resistance Floors 1 Hours
FUTURE INSTALLATION
Rating Roof N/A Hours
(FRR)
Mezzanine 1 Hours Sewage System: X NO Yes 11.4.3.6
East 1100 m2 5.64 m # 52% 9.1% 45 min # Combustible or Non-Combustible Combustible or Non-Combustible OUTSIDE CURRENT AREA OF SCOPE (N.I.C)
FUTURE PHASE 4 EXTERIOR LANDSCAPING
West 967.95 m2 5.48 m # 52% 10.5% 45 min # Combustible or Non-Combustible Combustible or Non-Combustible
3
A401.1
219
3048
0
6
07
70
/2 "
/2"
863
15
23
23
81
31
120"
"
90
93
12192
480"
17
234
1703
41
"
99
67"
924
11
5
6
1"
2
/2"
A401.1
UP UP
HATCHED AREA DENOTES AREA OUTSIDE SCOPE
Professional Seal
LIFE SAFETY PLAN - GRND FLR
2 TENDER ISSUE
170501 As indicated
Drawing date Scale
16011 AM
Project no. Drawn by
TIBETAN CANADIAN
SCOPE OF WORK - KEY PLAN CULTURAL CENTER
1
1" = 40'-0" 40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
Drawing title
A002
Sheet no.
ZONING AND LOT INFORMATION
NET LOT AREA 8806.91SQM
PROPERTY LINE
NOTE: NO OCCUPANCY INCREASE FROM EXISTING
#44 LEGALIZED CAR PARKING SPACES
31.7
EXIS
TING
3.
99
CHA
N 89
11
IN L
11 3. 11
INK
3. 69 3.
36 3
FEN
11 1
°
11 3. 11
CE
3. 84 4.
3
70 11 49
4
4.
40
' 20"
11
4.
95 REDUCED WIDTH OF DRIVEWAY AS
PER MINOR VARIANCE/PERMISSION
E
11
5. 11
5.
FILE NUMBER A268/10EYK
14 19 148269 12149
11
3. 5837 1/2" 478 1/2"
72
98017
11 11
3. 4. 11 11 11 3859"
21 87 5. 11
0 4. 4. 3.
6 63 5 91
1 25 26 27
EXISTING CONCRETE BLOCK
11 11 RETAINING WALL
11 11 11
3.
63
11 11
3.
94
11
11
4. PROPERTY LINE 11
11
4. 11 N 16° 58' 20" W 11
4.
EXISTING CHAIN LINK FENCE
11
4.
20
4.
17
11
4.
13
4.
03
4.
1 1
3. 11 11 0 6 4. 05 4. 0
3. 74 46 47 48 4. 4. 05 06 8
07 3.
209 1/2"
61 9 02
5326
2
220 1/2"
11 11
5600
3. 11 11 3. 11 11
69 3. 11 96 11 3.
6 3. 11 3. 4. 4. 9
8 8 99 02 2
SETBACK SETBACK 4 SETBACK 3.
89
16 SETBACK SETBACK SETBACK
EXISTING CONCRETE SIDEWALK
11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 4. 28
11 04
3. CB
SETBACK
11 2600 83
11 3.
3. 88
93 102 1/2" 11
FALL
4. 29
19
261 1/2"
6000
236"
11
6636
11
MH 11
3.
3.
69 11
3.
EXISTING EXTERIOR PARKING LAYOUT 3.
89
70 82 11 11
3. 3.
8 84 11
4 30 3.
11 15405 87
3.
8 8 11 606 1/2"
4.
24
11 09
11 3.
3. 97 31
9
16
SETBACK
23
EXISTING
O/H 11
HP 11
#
3. EXISTING 5600 6020 5600 5600 7688 4.
45 11 11 02
3. HP
O/H 11 32
78 EXISTING 11 3. 3.
220 1/2" 237" 220 1/2" 220 1/2" 302 1/2" 89 92
17
11
22
TRANSFORMER 3.
3. 8 9 11
58
110.95
3.
49 50 51 9 1
#
33
53.34
18
11
21
#
11 11 FALL FALL
11 4. 11
0 4. 34 3.
0
3. 11 11 0 1 8
.5
77 4. 1 8
19
4.
m
20
1
11 0
∅
07
1
5
3
4.
.8
07 11 11
0
11 4. 11 3.
1
14 4. 0 4. 6
GAS METER 0 4 6
.1 8 11
3 35
11 11 11
3.
SETBACK
2085 1/2"
17 41 5
7
52969
N 72° 51' 30" E
11 40 TITAN ROAD 11
4.
28 36
3. 11
05 3. EXISTING ONE STOREY INDUSTRIAL
PARKING LAYOUT
70
11
11
3.
11
4.
05
F.F.E.119.74 3.
32
4 4 37
LINE OF PARAPET TO SECOND FLOOR
0
.5
m
1
CENTERLINE OF ROAD
∅
4
.0
FALL
5
38
11
3.
11
68
4.
3000
118"
09
39
4512 3957 11
3.
16
177 1/2" 156" 40
11
11 3. 11
4. 11 3.
13
0
6
.5
41 9
m
1
1
∅
3
.9
5
11
2.
9 9 11 EXTENT OF PHASE 1 WORKS
3. 42
40
FALL
SETBACK
11
SETBACK
PROPERTY LINE
3. 4512
31 43
NEW EXTERIOR STEPS TO MATCH EXISTING NEW EXTERIOR STEPS TO MATCH EXISTING
N 73° 01' 40" E
177 1/2"
11
3.
45
11 SETBACK 44
11 11 SETBACK 11
11 3. SETBACK 11 SETBACK SETBACK 11
3.
SETBACK
3. 3.
3.
51 3 9 26 3.
30
16 3.
0 UP 2 2
FIRE 7
HYDRANT 28257
11 11
1112 1/2" 3. 3. 11 45
04 00 3.
07
11
2.
PROPERTY LINE N 17° 05' 30" W 88
CB 11
11 CB 11 11 160.56 3.
11 3. 11 18
5314
209"
134 1/2"
3. 3. 0 3. 2.
14 2
3420
9
615 1/2"
28 00 7 CB
15633
11
3.
EXISTING EXTERIOR PARKING LAYOUT Rev. Date Description
09 11
3. 11
30 3.
6 7
11 9913 5823
3.
0 9 390 1/2" 229 1/2"
11
3. 11 11 11 11
4 2 3. 3. 3. 160560 6103
46 42 18 3.
11 15
3. 6321" 240 1/2"
30
11
3. 11 11 11
2 7 3. 3. 3.
32 04 69
11
3.
19 REDUCED WIDTH OF DRIVEWAY AS
PER MINOR VARIANCE/PERMISSION
FILE NUMBER A268/10EYK
Professional Seal
TENDER ISSUE
Issued for
0 1 5
SITE PLAN
13/10/2017 10:28:26 AM
Drawing title
A101
Sheet no.
TRUE PROJECT
NORTH NORTH
General Notes
DEMOLITION
NEW
EXISTING
WALL LEGEND
1" = 10'-0"
EXISTING ADJACENT SINGLE STOREY BUILDING
S R Q P O N M L K J 132510 I H G F E2 E1 D C B2 B A
5217"
118673
4672"
6955 6882 7315 7315 7315 7315 14634 7315 7315 7315 7315 7316 3652 3663 8026 7620 7620 7620
13837
274" 271" 288" 288" 288" 288" 576" EXISTING CHAIN LINK FENCE 288" 288" 288" 288" 288" 144" 144" 316" 300" 300" 300"
545" 762
30"
404
16"
1 1
Room D5 3805
D29
19 m²
45 1/2"
1150
150"
30467
1199 1/2"
EXISTING ASPHALT & PARKING LAYOUT D18 D8
3762
148"
9754
9754
9754
384"
384"
384"
13030
513"
D4
7442
D3
293"
2 2
71" 96 1/2"
71"x107"
BASE 1
2718
107"
TEMPORARY WALL
9754
9754
9754
384"
384"
384"
EXT. PRAYER WHEEL LOCATION OF STATUE 3
TITAN ROAD
2408
95"
D2
LOCATION OF STATUE 2
71"x107"
BASE 2
2718
107"
3 3
20474
806"
40894
1610"
D26
EXISTING ASSEMBLY HALL
D25
174"
Room 2103 m²
2411
95"
Room 42 m²
D75 Room
38 m² UNFINISHED
D27 94 m² LOCATION OF STATUE 1
3b CONCRETE SLAB
71"x107"
BASE 3
2718
107"
10509
10509
10509
THROUGHOUT
414"
414"
414"
116 1/2"
2953
Room
D24 D28 74 m²
3c VOID AREA -
OPEN
11
Room D23
123 1/2"
3.
68
3137
D19
137 m² (NO ROOF)
CORRIDOR
4 41 m² Room 4
41 m² Room 7315
140 1/2"
Room
3564
38 m²
48 m² 288"
UP
4b
D22
9A
10877
10877
D11
428"
428"
D1 D21 D20
D12
7313
288"
224 1/2"
Room
208 1/2"
5704
5298
220 m²
405
16"
UP
L1
Rev. Date Description
170501 As indicated
Drawing date Scale
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
Drawing title
A200
Sheet no.
READ IN CONJUNCTION WITH
STRUCTURAL ENGINEERS DRAWINGS
TRUE PROJECT
REFER TO STRUCTURAL ENGINEERS NORTH NORTH
G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
DEMOLITION
EXISTING CHAIN LINK FENCE
NEW
557
22"
D29
REMOVE FOUNDATION WALL TO ALLOW FOR NEW STRUCTURE.
REFER TO STRUCTURAL ENGINEERS DRAWINGS
98 1/2"
3824 EXISTING
2500
3637
45 1/2"
143"
1150
150 1/2"
286 1/2"
7273
HATCH INDICATES AREA D8 1A
WHERE TOP 3 5/8" OF
4068
FINISHED CONCRETE TO BE
9754
384"
1199 1/2"
13030
513"
6
2438 2078
3535
139"
3555
140"
96" 82"
278 1/2"
7070
6A
1803 2451
2035
80"
SITE VERIFY EXTENT OF EX. CONCRETE
71" 96 1/2" FOUNDATION WALL, TO REMOVE. REFER TO
STRUCTURAL DRAWINGS AND CONFIRM ON
SITE W/ STRUCTURAL ENGINEER
2718
107"
7
9754
384"
A401.1
31187
1228"
PROTECT STATUE 3
3536
139"
2408
95"
278 1/2"
7070
7A
2718
107"
3
1610"
PROTECT STATUE 2
8
TEMPORARY WALL TO BE REMOVED.
2411
95"
REMOVE ALL CROSS BRACING.
REFER TO STRUCTURAL ENGINEERS DRAWINGS
4902
193"
PROPERTY LINE
SPECIFICATIONS AND FOOTING
2718
SCHEDULE FOR DETAILS
107"
10509
414"
PROTECT STATUE 1
9698
382"
8A
24"
43"
9
59 1/2"
1509
4756
187"
UP A401.1
Rev. Date Description
9783
385"
126 2564 3341 1465
D12
5" REMOVE SLAB TO ALLOW FOR NEW STRUCTURE. 101" 131 1/2" 57 1/2"
2502
98 1/2" REFER TO STRUCTURAL ENGINEERS DRAWINGS
NEW OPENING
5 D13
5
D14
Professional Seal
TENDER ISSUE
UP REMOVE FOUNDATION WALL TO ALLOW FOR NEW STRUCTURE. 8234 Issued for
REFER TO STRUCTURAL ENGINEERS DRAWINGS
324"
170501 1" = 10'-0"
REMOVE EXISTING DOORS Drawing date Scale
2500 614
1 98 1/2" 16011 Author
NEW OPENING 24" Project no. Drawn by
DEMOLITION - FLOOR
RED LINE DENOTES AREA OF SCOPE OF WORK PLANS
13/10/2017 10:28:30 AM
Drawing title
General Notes
7315 7316 3652 3663 8026 7620 7620 7620
25 26 27
EXISTING CHAIN LINK FENCE
11
NEW
1 1270
4.
W1 A506 A501 W1.1
09
11
50"
A600.1
4.
EXISTING
16
12 1/2"
D30 D32
557 318
1 1
11
22"
4.
62 1/2"
04
68 1/2"
1588
1738
71
3" D33 28 WALL LEGEND
3637
143"
2207 150 2596
286 1/2"
NEW OPENING
7273
1A
98 1/2"
2500
101
D0 DOOR TAG
1 1.1
1i WALL TYPE TAG
A507 30 1i
W1 WINDOW TAG
2387
1i
R1 ROOF TAG
1516 2345
94"
3 1/2"
6
91
59 1/2" 92 1/2" 1i
F1 FLOOR TAG
NEW BASE
3535
139"
3555
140"
SYMBOLS LEGEND
71"x107"
BASE 4
2 3048 NEW LOCATION STATUE 3
120"
PREPARE EXISTING SLAB FOR NEW 1" = 10'-0"
278 1/2"
BASE PLINTH TO MATCH EXISTING
32 6A
7070
ALIGN
64 1/2"
1635
33
12192
480"
7
71"x107"
BASE 1
MULTI- SPORTS HALL
PURPOSE NEW LOCATION OF STATUE 2
34
3536
139"
HALL
F1
278 1/2"
7070
7A
NEW LOCATION OF STATUE 1
EXISTING STATUES TO BE MOVED 35
ALONG AS SHOWN, AND NEW STATUE
3 TO BE INSTALLED EXISTING PLINTH
71"x107"
BASE 2
AMENDED TO NEW LOWER HEIGHT NEW AREA OF INFILL AND SLAB
(FINAL DIMENSION TO BE CONFIRMED
40894
1610"
REFER TO STRUCTURAL DRAWINGS
ON SITE W/ CLIENT) TOTAL NEW SLAB AREA TO BE
CONFIRMED ON SITE FOLLOW
NB: MULTIPURPOSE DEMOLITION WORKS. 36 8
HALL TO REMAIN IN
OPERATION DURING
11
3.
WORKS
32
37
4902
W1.1
193"
71"x107"
BASE 3
9698
382"
38 8A
88
788 150 2596 356 3188 150 3 1/2" PREPARE EXISTING PLINTH TO SUIT
NEW TEMPORARY WALL TO BE 31" 6" 102" 14" 125 1/2" 6" NEW LOWER HEIGHT (HEIGHT TO
INSTALLED DURING BE REDUCED - REFER TO DETAILS
459 W3
CONSTRUCTION
18"
150
6"
2675
105 1/2"
150
6"
1592
62 1/2"
150
6"
4016
158"
150
6"
2006
79"
39
150
150
6"
6"
D40 D89 DOWNPIPE FOR RAINWATER
4 D94 REFER TO PLUMBING DRAWINGS
1703
W2 W2 W2 W2 W2
67"
67"
W2
2596
9
150
150
102"
6"
6"
D36
40
59 1/2"
1509
W2
W2 194
W2
6
4756
187"
CL
7 1/2"
CL
3069
121"
3198
126"
CL CL A501
D87 D45 W2
ALIGN
41
ALIGN WITH ENTRANCE DOOR
6"
9A 1
A509
9783
385"
126 2564 3343 1465
NEW AREA OF INFILL AND SLAB Rev. Date Description
5" 101" 131 1/2" 57 1/2"
W2 REFER TO STRUCTURAL DRAWINGS
W2 W4 TOTAL NEW SLAB AREA TO BE 42
2899
114"
CONFIRMED ON SITE FOLLOW
230 1/2"
DEMOLITION WORKS.
EXISTING -REVIEW AND CONFIRM EXTENT ON SITE. cl 1 351
W2
14"
ADDITIONAL PROTECTIVE HOARDING MAY BE 4 A600.2 D42
3
150
6"
REQUIRED IF AREA EXTENDS OUTSIDE MAIN SCOPE 2502
A501 cl
cl
W2 A502 43
98 1/2"
OF WORK AREA 2 2461 150
1874
74"
NEW OPENING
D44 97" 6"
A502 W2
CL
12 1/2"
5 5
318
D35 D34
44
11
W1 W1.1
3.
8234
22
UP
324"
EXT.STAIR 1 EXT.STAIR 2
5
45 Professional Seal
11
2 2500
3.
98 1/2" 614
07
TENDER ISSUE
A505 NEW OPENING A505 Issued for
24"
16011 AM
11
Drawing title
A201.1
Sheet no.
TRUE PROJECT
NORTH NORTH
- -
DRAWING SHOULD NOT BE SCALED
--- --- Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A used for construction purposed until signed by the
7315 consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
288" Architecture Inc.
7315 7316 3652 3663 8026 7620 7620 7620
288" 288" 144" 144" 316" 300" 300" 300" General Notes
50"
DEMOLITION
2617
103"
NEW
950 1219 448
3637
143"
AV SPECIALIST - ALSO REFER TO
286 1/2"
7273
FOLDING PARTITION SPECIALIST TO PROVIDE 1A
DETAILED SHOP DRAWINGS FOR CUPBOARD 101
D0 DOOR TAG
1i
W1 WINDOW TAG
SYMBOLS LEGEND
3535
139"
2 1" = 10'-0"
278 1/2"
7070
6A
-
7
---
F1
3536
139"
278 1/2"
7070
7A
3
250
40894
1610"
F1 10"
4902
193"
FOLDING PARTITION SPECIALIST TO PROVIDE FOLDING PARTITION SPECIALIST TO
DETAILED SHOP DRAWINGS FOR CUPBOARD PROVIDE DETAIL SHOP DRAWINGS FOR
9698
382"
WITH DOOR SETTING OUT AND DETAILS CUPBOARD WITH DOOR SETTING OUT AND 8A
DETAILS
W3
W5
CL
D39
D38 D85
750 240
4 W2 W5 W5
ALIGN WITH ENTRANCE DOOR
1097
1304
W2
43" 316 1/2" 103" 62"
9
D88
EQ
-
126 1/2"
C C ---
3210
L L
EQ
ALIGN
W6 W2
150
6" D49 D48 D47
9A
150 175
W6 6" 7"
1723
68"
W2 W2
9783
3212 1652
385"
1500 1647
W6 W6 W6 W6 Rev. Date Description
126 1/2" 65" 59" 65" 150 4416
169 1/2"
4310
400 1067 1802 1778 1067 406
6" 174"
15 1/2" 42" 71" 70" 42" 16"
6247
246"
6043
W2
238"
W4
W4
275
11"
231
9"
275
11"
63 1/2"
63 1/2"
1611
1611
275 3002 125 3269 125 1442 1809 125 2997 275 2414
11" 118" 5" 128 1/2" 5" 57" 71" 5" 118" 11" 95"
UP
Professional Seal
TENDER ISSUE
Issued for
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
Drawing title
2
1" = 10'-0" A201.2
Sheet no.
REFER TO STRUCTURAL ENGINEERS
DRAWINGS AND SPECIFICATIONS FOR FULL
DETAILS FOR STEEL SIZES AND SETTING TRUE PROJECT
OUT. NORTH NORTH
KEY PLAN
4 4013 3810 762 3810 3810
A301.1
158" 150" 30" 150" 150"
A401.1
1 2
1270
3
A506 50"
A401.1
19072
751"
3637
EXISTING REINFORCED 18" OWSJ
143"
286 1/2"
7273
EXISTING 18" OWSJ
NEW W460x97
NEW W460x97
EXISTING OWSJ
(REINFORCED)
DO
6
3535
139"
EX W310x39 EX W310x39 EX W410x54
2
278 1/2"
7070
6A
EXISTING REINFORCED 18" OWSJ
RO OO
NEW W460x97
NEW W460x97
7 A401.1
RJ1
RJ1
BLUE AREA DENOTES DRYWALL BULKHEAD
H R
31111
1225"
DO
DO
3536
139"
HI IGH
TRACK AND STEEL SUPPORTS ABOVE.
REQUIREMENTS FOR MAINTENANCE ACCESS
HATCHES TO TRACK TO BE CONFIRMED W/
SPECIALIST.
W H
278 1/2"
7070
1829
72"
E
N TO
7A
3
EX W310x39 EX W310x39 EX W410x54
ER
EF
R 8
EXISTING REINFORCED
EXISTING REINFORCED
EXISTING REINFORCED
REINFORCED
OWSJ
(REINFORCED)
NEW W460x97
NEW W460x97
EXISTING 18" OWSJ
4902
193"
EXISTING
18" OWSJ
18" OWSJ
EXISTING
18" OWSJ
18" OWSJ
DO
DO
DO
VXB
9698
382"
EX RTU
WT: 3,000
8A
lbs GRAY AREA INDICATES DRYWALL BULK HEAD TO
SEPARATE SPACE AND ALLOW FOR FUTURE FINISHED
CEILINGS TO BE INSTALLED
- REFER TO SECTIONS/DETAILS
GRAY AREA INDICATES DRYWALL BULK HEAD TO
SEPARATE SPACE AND ALLOW FOR FUTURE
FINISHED CEILINGS TO BE INSTALLED
- REFER TO SECTIONS/DETAILS
EX W310x52 EX W310x39
4 FULL HEIGHT TO SUIT
PARTITION HEIGHT -
REFER TO DETAILS 16'-6" OFF FFL TO UNDERSIDE OF NEW 38mm STEEL DECK
941
37"
NEW HSS305x203x9.5
2
3661
144"
1829
A401.1
72"
W138
83 1/2"
W200X27 TO BRACE TOP OF STEEL COLUMN
2121
CONNECTION - REFER TO STRUCTURAL DRAWINGS
9A
2546
100"
NEW 1'-8" OWSJ
9783
NEW 1'-8" OWSJ
385"
CL
EXISTING REINFORCED
EXISTING REINFORCED
EXISTING REINFORCED
16 1/2"
425
EXISTING 18" OWSJ
117 1/2"
NEW W460x68
NEW W460x97
NEW W460x97
2985
W137
18" OWSJ
18" OWSJ
238
9 1/2"
DO
DO
DO
DO
1927 1905 1905 1905 1905 1905 1905 1905 1905 1905 1905 1905 1905 1905 1905 1905 1905
76" CL 75" 75" 75" 75" 75" 75" 75" 75" 75" 75" 75" 75" 75" 75" 75" 75"
58 1/2"
1482
17'-2" OFF FFL TO UNDERSIDE OF NEW 38mm STEEL DECK
EXISTING BEAM EXISTING BEAM NEW W410x39 NEW W410x39 EXIST W410x54
5 (REINFORCED)
5
W66 W136 W67 W139 W68 W140 W69 W70 W71 W72
1385 918 1829 1702 914 584 1829 2700 914 597 1829 4288 914 580 1829 2719 1829 2692 1829 698 1829
54 1/2" 36" 72" 67" 36" 23" 72" 106 1/2" 36" 23 1/2" 72" 169" 36" 23" 72" 107" 72" 106" 72" 27 1/2" 72"
916 786 EQ EQ 953 1739 1525
EQ EQ
1 37 1/2" 68 1/2" 60"
Professional Seal
36" 31"
TENDER ISSUE
VXB Issued for
UNDERSIDE OF DECK AND ALL STEELS AND DUCT WORK TO BE PAINTED A301.1 REFER TO STRUCTURAL DRAWINGS
BLACK THROUGHOUT REVIEW ON SITE TO ENSURE NO CLASH W/ WINDOWS 170501 1" = 10'-0"
Drawing date Scale
16011 Author
REFER TO MEP CONSULTANTS ELECTRICAL DRAWINGS FOR Project no. Drawn by
Drawing title
A202.1A
Sheet no.
TRUE PROJECT
NORTH NORTH
7315 7315 7316 3652 3663 8026 7620 7620 7620 General Notes
288" 288" 288" 144" 144" 316" 300" 300" 300"
1596 1829 475 3543 470 3543 470 1829 1829 546 914 675 1829 541 914 678 1829 1525
63" 72" 18 1/2" 139 1/2" 18 1/2" 139 1/2" 18 1/2" 72" 72" 21 1/2" 36" 26 1/2" 72" 21 1/2" 36" 26 1/2" 72" 60"
1 1
19072
VXB - NEW LATERAL CROSS
751"
2433
BRACING (HIGH AND LOW)
96"
1956 1006 GYALSTEN STATUE ABOVE
3637
143"
77" 39 1/2" REFER TO STRUCTURAL
NEW 5'-4" OWSJ @ ± 8'-0" C/C NEW 3'-0" OWSJ @ ± 8'-0" C/C SPECIFICATIONS FOR
ADDITIONAL FRAMING REQ'D
GYALSTEN STATUE ABOVE 30'-5 1/2" FROM FFL TO UNDERSIDE OF METAL DECK
REFER TO STRUCTURAL 250
286 1/2"
284 1/2"
95 1/2"
7273
2421
7223
SPECIFICATIONS FOR 10" 1A
ADDITIONAL FRAMING REQ'D
NEW W540x74
2419
95"
711
FUTURE RETRACTABLE
934
37"
BASKETBALL HOOP TO BE 28"
INSTALLED 6
REFER TO STRUCTURAL
SPECIFICATIONS FOR
91 1/2"
2326
2358
ADDITIONAL FRAMING/
93"
SUPPORT.
3535
139"
30'- 8 1/2" FROM FFL TO UNDERSIDE OF METAL DECK
2
NEW W840x176
278 1/2"
7070
2356
NEW 5'-4" OWSJ NEW 3'-0" OWSJ
93"
6A
556 1/2"
14139
2356
93"
1
31111
1225"
2356
93"
NEW OWSJ INSTALLED TO 1.15 DEGREE FALL NEW OWSJ INSTALLED TO 1.15 DEGREE FALL
3536
139"
278 1/2"
2356
7070
93"
NEW 3" x 0.036"STEEL DECK NEW 76mm STEEL DECK 7A
ADDITIONAL LATERAL SUPPORT
FOR ACCESS LADDER REFER TO
STRUCTURAL DRAWINGS
3 711
28"
2357
93"
2132
DUCTS TO BE INSTALLED AS HIGH
84"
AS POSSIBLE WITHIN ROOF
STRUCTURE WITH DIFFUSERS TO
BE INSTALLED 330" OFF FFL 8
DUCTS AND DIFFUSERS TO ALIGN
1116
44"
WITH LIGHTING AS SHOWN
95 1/2"
ALSO REFER TO MEP CONSULTANT
2430
DRAWINGS
4902
193"
NEW W610x125
97 1/2"
UNDERSIDE OF DECK AND ALL STEELS
2472
AND DUCT WORK TO BE PAINTED BLACK
THROUGHOUT
9698
382"
8A
93 1/2"
2375
GYALSTEN STATUE ABOVE 30'-4 1/2" FROM FFL TO UNDERSIDE OF METAL DECK
REFER TO STRUCTURAL 510 1174 1956 1006 1174 561
SPECIFICATIONS FOR
20" 46" 77" 39 1/2" 46" 22"
ADDITIONAL FRAMING REQ'D
GYALSTEN STATUE ABOVE
REFER TO STRUCTURAL
1148
SPECIFICATIONS FOR
4 45" ADDITIONAL FRAMING REQ'D
9
W15 W150 W17 W18 W20 W134 W21 W135 W22
1596 1829 475 3543 470 3543 470 1829 1829 546 914 675 1829 541 914 678 1829 1525
63" 72" 18 1/2" 139 1/2" 18 1/2" 139 1/2" 18 1/2" 72" 72" 21 1/2" 36" 26 1/2" 72" 21 1/2" 36" 26 1/2" 72" 60"
9783
385"
AND DETAILS RELATING TO STRUCTURE.
Rev. Date Description
5 5
Professional Seal
A301.1
TENDER ISSUE
Issued for
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
RED LINE DENOTES AREA OF SCOPE OF WORK 40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
PH1 - BB - REFLECTED
PH1 - BB - GRND FLR RCP - HIGH LEVEL CEILING PLAN (HIGH ROOF)
1
13/10/2017 10:28:35 AM
A202.1B
Sheet no.
TRUE PROJECT
NORTH NORTH
General Notes
AREA OPEN TO
THE ELEMENTS
EXISTING RWO
Professional Seal
TENDER ISSUE
Issued for
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
Drawing title
A204
Sheet no.
TRUE PROJECT
NORTH NORTH
1504"
7315 7315 7315 7316 3652 3663 8026 7620 7620 7620
288" 288" 288" 288" 144" 144" 316" 300" 300" 300"
KEY PLAN
1 1
286 1/2"
7273
9754
384"
278 1/2"
7070
EXISTING ROOF RWP, AND MECHANICAL EQUIPMENT TO REMAIN. 7
9754
384"
31111
1225"
278 1/2"
7070
3
40894
1610"
8
414"
9698
382"
4
428"
9783
385"
5 5
Professional Seal
TENDER ISSUE
Issued for
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION
40 TITAN ROAD,
EXISTING ROOFING STRUCTURE TO BE REINFORCED
RED LINE DENOTES AREA OF SCOPE OF WORK REMOVE EXISTING BUILD-UP TO FACILITATE WORK AS REQ'D, SEE
ETOBICOKE, ON, M8Z 2J8
STRUCTURAL ENGINEERS DRAWINGS & SPECIFICATION Project
Drawing title
1
1" = 10'-0" A204.0
Sheet no.
4 3
A401.1 A401.1 TRUE PROJECT
NORTH NORTH
12"
1 1
SCUPPER
A STATUE STATUE
NEW STRUCTURE TO
3637
143"
1.15 DEGREE FALLS
19074
751"
286 1/2"
284 1/2"
7273
7223
1A
EXT. RWO
EXT. RELOCATED
RWO
2210 714
87" 28"
1041
MECHANICAL UNIT
41"
NEW MECHANICAL
MECHANICAL UNIT
EXT.
RWO 6
CRICKETS
EXISTING
RWO
2132
EXISTING
84"
UNIT
3535
139"
(U.S.METAL DECK 29' 9")
(U.S.METAL DECK 31' 0 1/2")
2
NEW STRUCTURE TO REFER TO NEW STRUCTURE TO
1.15 DEGREE FALLS STRUCTURAL FOR 1.15 DEGREE FALLS
278 1/2"
21362
841"
STEEL FRAMEWORK
7070
DETAILS AND SPEC 6A
31111
1225"
+/- 31' - 5 1/2"
A
3536
139"
EXISTING ROOF 1
EXT. TO FALLS NEW STRUCTURE TO 4
RWO A502 NEW STRUCTURE TO
278 1/2"
1.15 DEGREE FALLS
7070
EXT. RWO 1.15 DEGREE FALLS
RELOCATED NEW ACCESS A502 7A
EXT. LADDER
RWO
2210
87"
NEW MECHANICAL
87 1/2"
2221
R1
710
CRICKETS 28"
8
UNIT
RWO
1041
41"
+ 119.74M
2216
87"
REFER TO
STRUCTURAL FOR
STEEL FRAMEWORK
305
4902
12"
193"
DETAILS AND SPEC
SCUPPER
NEW STRUCTURE TO
374 1/2"
1.15 DEGREE FALLS
9514
9698
382"
8A
MECHANICAL UNIT
STATUE
EXISTING
EXISTING
4 A504
305
12" SCUPPER
EXT.
RWO
9
1097 +/- 17' - 4"
EXT. A A A
(U.S.METAL DECK 16' 6")
RWO 43" 2
305
12"
SCUPPER
A401.1
RWO RWO
5
A504
9A
EXT. RWO
RELOCATED
384 1/2"
384 1/2"
9772
9772
9783
385"
4
A504
Rev. Date Description
VENT VENT
NEW STRUCTURE TO
NEW STRUCTURE TO
VENT
1.15 DEGREE FALLS
UP
14630 38202
576" 1504"
Professional Seal
TENDER ISSUE
Issued for
F E D C B A
PH1 - BB - ROOF PLAN
PROPOSED ROOF PLAN
1
13/10/2017 10:28:39 AM
1" = 10'-0" TOTAL: 10.5" 9.5" 8.5" 7.5" 6.5" 5.5" 4.5"
Drawing title
A204.1
TAPERED INSULATION
Sheet no.
1/4" = 1'-0"
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
Architecture Inc.
General Notes
R Q P O N M L2 L1 K J I H G F E2 E1 D C B A
PROPERTY LINE
PROPERTY LINE
SETBACK
SETBACK
8.61 T/O STRUCTURE
PROPERTY LINE
SETBACK
C D H I N O
A B E1 E2 F G J K L2 M P R
SETBACK
Q
5 4 3 2 1 1 2 3 3b 4 5
PROPERTY LINE
PROPERTY LINE
PROPERTY LINE
SETBACK
SETBACK
SETBACK
PROPERTY LINE
SETBACK
Rev. Date Description
EXISTING TRANSFORMER
+114.04
+114.05
+113.26
Professional Seal
TENDER ISSUE
Issued for
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
EXISTING - EXTERNAL
ELEVATIONS
13/10/2017 10:28:40 AM
Drawing title
A300
Sheet no.
HATCH INDICATES THE AREAS TO BE REMOVED
NB: EXISTING WALL TO BE REMOVED TO ALLOW STRUCTURAL WORKS
AS REQUIRED - SEE STRUCTURAL ENGINEER DRAWINGS
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
Architecture Inc.
General Notes
R Q P O N M L2 L1 K J I H G F E2 E1 D C B A
PROPERTY LINE
PROPERTY LINE
34138
SETBACK
SETBACK
1344"
3658 7620 7620 7620 7620
5104
PROPERTY LINE
SETBACK
C D H I N O
A B E1 E2 F G J K L2 M P R
SETBACK
Q
1200"
REMOVE TO ALLOW FOR REMOVE FOR NEW FOUNDATION STRIP EXISTING INTERNAL COLUMNS TO BE REINFORCED
DEMOLITION WEST ELEVATION REINFORCEMENT OF AND NEW COLUMNS - REFER TO REFER TO STRUCTURAL ENGINEERS DRAWINGS
2 FOUNDATIONS STRUCTURAL ENGINEERS DRAWINGS - MINIMAL DISRUPTION TO EXTERNAL ENVELOPE REQUIRED
1" = 20'-0" REFER TO STRUCTURAL
ENGINEERS DRAWINGS
5 4 3 2 1 1 2 3 3b 4 5
PROPERTY LINE
PROPERTY LINE
PROPERTY LINE
SETBACK
40893
SETBACK
SETBACK
PROPERTY LINE
1610"
SETBACK
10693 10693 9753 9753
TENDER ISSUE
Issued for
TIBETAN CANADIAN
EXISTING WALL TO BE OUTSIDE AREA OF SCOPE CULTURAL CENTER
REMOVED TO ALLOW NEW
FOUNDATIONS FOR NEW 40 TITAN ROAD,
DEMOLITION NORTH ELEVATION
STEEL STRUCTURE
DEMOLITION SOUTH ELEVATION ETOBICOKE, ON, M8Z 2J8
3 4 Project
Drawing title
A301.0
Sheet no.
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
S R Q P O N M L L1 K J I H G F E2 E1 D1 D C1 C B1 B A1 A2 A Architecture Inc.
B2
34549 General Notes
1360"
6955 6882 7315 7315 7315 7315 7315 7319 7315 7315 7315 7315 7316 3652 3663 8026 7620 7620 7620
274" 271" 288" 288" 288" 288" 288" 288" 288" 288" 288" 288" 288" 144" 144" 316" 300" 300" 300"
1173 4 3
46"
A401.1 A401.1
387 1/2"
9847
W66 W136 W67 W139 W68 W140 W69 W70 W71 W72
+/- 113.26
D35
W1.1
D34
+/- 113.22
PH3 - FF- GROUND FLOOR
0' - 0"
A A2 A1 B B1 C C1 D D1 E1 E2 F G H I J K L M N O P Q R S
B2 34549 97961
300" 300" 300" 316" 144" 144" 288" 288" 288" 288" 288" 288" 288" 288" 288" 288" 288" 271" 274"
3810 3810 3810 4013
3
150" 150" 150" 158" 4
762
1270 A401.1
30" A401.1
50"
EXPANSION JOINTS TO BE
INSTALLED AS PER
MANUFACTURERS DETAILS IN EFIS
RENDER FINISH.
DETAILED SHOP DRAWINGS
SHOWING LOCATIONS TO BE
APPROVED BY ARCHITECT
17' - 11"
+/- 114.04
5460
215"
5 9 8A 8 7A 7 6A 6 1A 1 1 1A 6 6A 7 7A 8 8A 9 5
40894
31111
1610"
9783 9698 7070 7070 7273
1225"
385" 382" 278 1/2" 278 1/2" 286 1/2" 7273 7070 7070 9698 9783
4902 3536 3535 3637 286 1/2" 278 1/2" 278 1/2" 382" 385"
3637 3535 3536 4902
Rev. Date Description
193" 139" 139" 143"
143" 139" 139" 193"
- -
-
--- ---
---
172 1/2"
W1.1
4387
4387
W1.1
318 +/- 114.04 Professional Seal
12 1/2" T.O. EXISTING ROOF T.O. EXISTING ROOF
TENDER ISSUE
17' - 11" 17' - 11"
W137 W138 Issued for
5460
215"
215"
Drawing title
S R Q P O N M L K J I H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
34549
DRAWING SHOULD NOT BE SCALED
1360" Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
7319 7315 7315 7315 7315 7316 7315 8026 7620 7620 7620 proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
288" 288" 288" 288" 288" 288" 288" 316" 300" 300" 300" consultant responsible. This drawing, is an instrument
3652 3663
4013 3810 762 3810 3810 of service, is provided by and is the property of Coolearth
144" 144" Architecture Inc.
RED LINE INDICATES SCOPE OF WORK (AT REAR OF PROPERTY) 158" 150" 30" 150" 150"
6955 6882 7315 7315 7315 7315 7315
General Notes
274" 271" 288" 288" 288" 288" 288"
1200
914
36"
47"
172 1/2"
W1.1 W14 W13 W12 W11 W8 W133 W7 W132 W6
3
4387
R1
90 1/2" 52 1/2"
25' - 5"
1333
A506
T.O. EXISTING ROOF
3629
143"
387 1/2"
9847
2296
17' - 11"
+/- 113.26
5460
215"
4800
189"
W1.1 W1.1
3583
141"
D30 F3 D32 2387 2300 +/- 113.22
94" 90 1/2" PH3 - FF- GROUND FLOOR
0"
0
0' - 0"
1956
77"
REFER TO DETAIL FOR COORDINATED DETAIL AROUND UNDERSIDE OF STEEL HEIGHT
STEELS AND NEW FOLDING PARTITION. COORDINATED W/ FOLDING SPACE TO BEHIND PLINTH TO ALLOW FOR FUTURE DECORATION INSTALLATION
COORDINATED SHOP DRAWINGS TO BE SUBMITTED TO PARTITION REQUIREMENTS PLINTH TO BE AMENDED TO SUIT NEW STATUES AS PER DETAILS
PH1 - BB SECTION 01 (NRTH-STH) - ASSEMBLY HALL STRUCTURAL ENGINEER AND ARCHITECT FOR
APPROVAL. REFER TO PHASE 2 DETAILS
1 COLUMN AND FOOTING AS PER STRUCTRAL DETAILS - DECORATIVE
CLADDING AND FINISHES TO BE APPLIED AT LATER STAGE (CLIENTS).
1" = 20'-0"
REFER TO STRUCTURAL ENGINEERS DETAILS FOR COLUMN AND NEW
FOOTING DETAILS.
3 4
A401.1 A401.1
A B C D E1 E2 F G H I J K L1 L M N O P Q R S
34549 18283
1360" 720"
3663 3652
144" 144"
7620 7620 7620 8026 7315 7316 7315 7315 7315 7315 7319 7315 7315 7315 7315 7315 6882 6955
ROOF KERB BETWEEN NEW 300" 300" 300" 316" 288" 288" 288" 288" 288" 288" 288" 288" 288" 288" 288" 288" 271" 274"
1173
AND EXISTING ROOF - REFER
TO ROOF PLANS AND 46"
DETAILS RED LINE INDICATES SCOPE OF WORK (AT REAR OF PROPERTY)
W1.1
+/- 114.04 D43 D41 D34 D35 F1
PH3 - FF- GROUND FLOOR
0' - 0"
FOOTINGS AS PER
STRUCTURAL ENGINEERS
DRAWINGS
1 1A 6 6A 7 7A 8 8A 9 5
40894
1610"
5 9 8 7 6 1
2
1
A401.1
A401.1 2
Rev. Date Description
1
A401.1
RED LINE INDICATES SCOPE OF WORK A401.1
(AT REAR OF PROPERTY)
31111
1225" 40894
1610"
7273 7070 7070 9698 9783
286 1/2" 278 1/2" 278 1/2" 382" 385" 9783 9698 7070 7070 7273
3637 3535 3536 4902 INDICATIVE OF HOLES IN BEAM WEB FOR DUCTS 385" 382" 278 1/2" 278 1/2" 286 1/2"
DUCTS TO BE LOCATED PASS THROUGH PRE-CUT
HOLES IN STEEL WEB TO ALLOW FOR FUTURE 143" 139" 139" 193" FUTURE CEILING LEVEL
FOLDING PARTITION TRACK. ALSO REFER TO
DETAIL A508 RED LINE INDICATES SCOPE OF WORK (AT REAR OF PROPERTY)
RETURN DRYWALL PARTITION UP TO MEET HIGH
WALL ABOVE (ANGLED TO ALLOW CLEANING). REFER TO ROOF PLAN FOR
REFER TO ROOF AND
ENSURE HEIGHT SUFFICENT TO ALLOW FOR FUTURE FALLS, DRAINAGE, SETTING OUT
CEILING LEVELS TO BE INSTALLED
CONSTRUCTION DETAILS FOR 9A OF SUPPERS AND ACCESS STAIR
PARAPET DETAILS
T.O. NEW ROOF (PARAPET)
32' - 3 1/2" R2
W1.1 17' - 6 1/2" NEW COLUMN REFER TO
STRUCTRAL ENGINEERS PLANS
3661
T.O. NEW ROOF (PARAPET)
172 1/2"
AND SPECIFICATIONS
4387
172 1/2"
SPECIFICATION AND DETAILS FOR Professional Seal
T.O. EXISTING ROOF 9' 4" FUTURE WASHROOM CEILING LEVEL. ENSURE
4387
INSTALLATION OF ANY SERVICES ETC TO ALLOW FOR WINDOWS
W1.1
17' - 11" FUTURE CEILING (INDICATED BY DOTTED LINE) R5 TENDER ISSUE
W138 W137 W71 NEW EXTERNAL W1.1
ENTRY STAIR - Issued for
FALL
T.O. EXISTING ROOF
REFER TO DETAILS
5460
215"
W1.1
+/- 114.04 D33 W1.1 16011
5460
Author
215"
PH3 - FF- GROUND FLOOR +/- 113.22 W3 Project no. Drawn by
0' - 0" F1 F3 W2
+/- 113.07 +/- 114.17
TRENCH FOR SERVICES - SIZE TO BE CONFIRMED
PH3 - FF- GROUND FLOOR TIBETAN CANADIAN
BY MEP CONSULTANT
REFER TO STRCUTRAL ENGINEERS DETAILS FOR
0' - 0" CULTURAL CENTER
BACKFILL TO SLAB ETC
40 TITAN ROAD,
STAGE & DISPLAY AREA TO BE
INSTALLED - CLIENTS REVIEW
AND ADVISE ON LOCATIONS OF
FOOTINGS AS PER STRUCTRAL
ENGINEERS DRAWINGS
ETOBICOKE, ON, M8Z 2J8
STEP ACCESS ON SITE Project
NEW PLINTH TO MATCH EXISTING
FOOTINGS AS PER STRUCTRAL
EXISTING PLINTH HEIGHT TO BE
ALTERED TO SUIT NEW HIEGHT.
ENGINEERS DRAWINGS
PH1 - BB - MAIN SECTIONS
AREAS WITH NEW PILES/ FOOTINGS FOR COLUMNS
REFER TO STRUCTRAL ENGINEERS SPECIFICATIONS
STATUES TO BE PROTECTED WHILE WORKS CONTINUE ON SITE.
PLINTHS TO BE ALTERED TO HEIGHT AS SHOWN (ARCHITECT TO
REVIEW THE PLINTH ON SITE W/SPECIALIST AND ADVISE ON STEEL FRAME TO BE CLOSED IN WITH DRYWALL
13/10/2017 10:28:50 AM
APPROACH TO ALTERATION WORKS) READY FOR INSTALLATION OF FOLDING PARTITION Drawing title
PH1 - BB - SECTION 03 (WST-EST) - ASSEMBLY HALL PH1 - BB - SECTION 04 (WST-EST)- GYM WALL.
3 4 A401.1
1" = 20'-0" 1" = 20'-0"
Sheet no.
A
5 1
EXTERNAL INTERNAL
REFER TO STRUCTURAL ENGINEERS DRAWING SHOULD NOT BE SCALED
WALL TYP. W1.1 DETAILS FOR BOLT FASTENINGS TO
NEW CONCRETE KERB Contractor must check and verify all dimensions on the
4" THICK DuROCK PUCCS INSULATION WITH 10MM job and report any discrepencies to the architect before
GEOMETRICALLY DEFINES DRAINAGE CAVITY (GDDC) 203
NEOPRENE GASKET TO TOP OF proceeding with the work. This drawing shall not be
8" CONCRETE KERB used for construction purposed until signed by the
INSTALL RENDER IN ACCORDANCE consultant responsible. This drawing, is an instrument
WITH DuROCK MANUFACTURERS 129 75 14 14
NEW CONCRETE KERB TO FOUNDATION WALL, of service, is provided by and is the property of Coolearth
RECOMMENDATIONS SUITABLE FOR STUD-WALL INSTALLATION 1/2" 1/2"
5" 3"
EXTERNAL INTERNAL EXTERNAL INTERNAL Architecture Inc.
UNI-TRACK DRAINAGE TRACK LIP 135 203 202
SAW CUT CAPILLARY BREAK INTO EXISTING SLAB
149 4" THICK DuROCK PUCCS INSULATION WITH 10MM 5 1/2" 8"
5" THICK DuROCK PUCCS INSULATION WITH 10MM
8" General Notes
6" FALL BOND BREAK GEOMETRICALLY DEFINES DRAINAGE CAVITY (GDDC)
GEOMETRICALLY DEFINES DRAINAGE CAVITY (GDDC)
51
TO MATCH EXISTING FINISHED INTERNAL LEVEL
2"
INSTALL RENDER IN ACCORDANCE
INSTALL RENDER IN ACCORDANCE REFER TO STRUCTURAL ENGINEERS DETAILS FOR BOLT WITH DuROCK MANUFACTURERS
PH3 - FF- GROUND FLOOR WITH DuROCK MANUFACTURERS FASTENINGS TO NEW CONCRETE KERB RECOMMENDATIONS
126 76 REFER TO STRUCTURAL ENGINEERS DETAILS FOR BOLT
5 1/2"
RECOMMENDATIONS
140
3 1/2"
0' - 0" NEW CONCRETE KERB TO FOUNDATION WALL, FASTENINGS TO NEW CONCRETE KERB
92
UNI-TRACK DRAINAGE TRACK LIP 127 76 SUITABLE FOR STUD-WALL INSTALLATION DuROCK UNI-TRACK DRAINAGE TRACK LIP. 5" 3"
PROPRIETARY METAL DRIP FLASHING MINIMUM 200MM (8") CLEARANCE REQUIRED NEW CONCRETE KERB TO FOUNDATION WALL,
202 5" 3" ABOVE GRADE LEVEL SUITABLE FOR STUD-WALL INSTALLATION
NEOPRENE GASKET TO TOP OF
SEALANT 0 381 8" CONCRETE KERB
NEW 6MIL POLYETHYLENE VAPOR BARRIER TO PROPRIETARY METAL DRIP FLASHING PROPRIETARY METAL DRIP FLASHING
0" 15" NEW SLAB TO LAP UP NEW CONCRETE KERB NEOPRENE GASKET TO TOP OF
SAW CUT CAPILLARY BREAK INTO EXISTING SLAB CONCRETE KERB
4" THICK POLYISO INSULATION
51
51
2"
2"
102 305 SAW CUT CAPILLARY BREAK INTO EXISTING
PH3 - FF- GROUND FLOOR PH3 - FF- GROUND FLOOR SLAB
5 1/2"
5 1/2"
4" 12"
279
11"
140
140
3 1/2"
0' - 0" 0' - 0"
200
92
8"
SEALANT
5 1/2"
140
4" THICK POLYISO INSULATION
CEMENT BOARD
354
14"
GRAY INDICATES AREAS OF EXISTING
4" THICK POLYISO INSULATION
EXTERIOR GRADE
CEMENT BOARD
GEO FABRIC
127
5"
117 255 202
TREMCO DIMPLE BOARD WITH FABRIC 4 1/2" 10" 8"
COMPOSITE SOIL SHEET DRAIN SYSTEM
GEO FABRIC
FOUNDATION WALL JUNCTION DETAIL TYP.1 FOUNDATION WALL JUNCTION DETAIL TYP.2 FOUNDATION WALL JUNCTION DETAIL TYP. 3
1 2 3
1" = 1'-0" 1" = 1'-0" 1" = 1'-0"
D
INTERNAL EXTERNAL
Rev. Date Description
76
INTERNAL 3"
405
16"
EXTERNAL
1/2"
13
77
3"
LEDGE BELOW
203
5
8"
405 404
203
150
8"
6"
203
9
127
16" 16"
5"
8"
1/2"
13
126
5"
126
5"
1/2"
13
404
16"
131
5"
404 405
150
208
6"
8"
203
16" 16" 1
8"
LEDGE BELOW
LEDGE BELOW
76
3"
1/2"
13
203 Professional Seal
EXTERNAL
8" TENDER ISSUE
13 203 143 3 202
Issued for
1/2" 8" 5 1/2" 0" 8" INTERNAL
170501 1" = 1'-0"
Drawing date Scale
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
CONSTRUCTION DETAIL
TYP. EAST WALL TYP. NORTH WALL TYP. WEST WALL TYP. WALL
4 6 5
1" = 1'-0" 1" = 1'-0" 1" = 1'-0"
13/10/2017 10:28:52 AM
Drawing title
A501
Sheet no.
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
8 used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
AIR CONDITIONER UNIT REFER TO MEP CONSULTANT SPECIFICATION & DRAWINGS of service, is provided by and is the property of Coolearth
Architecture Inc.
EXTERIOR.
General Notes
REFER TO TYP. WALL TYPES
DUROCK EFIS BUILD UP.
DuROCK FIRE MESH EMBEDDED IN
MOISTURE BEAR
BACKWRAPPED STARTER MESH
CANT STRIP.
LAP AND SEAL ALL EDGES MIN 6"/150MM.
156
6"
UPSTAND DETAIL
3226 1 1/2" = 1'-0"
127"
A
HVAC UNIT - SECTION 1
4 355
1" = 1'-0" 14"
13 201 13 127
1/2"
13
W/ MANUFACTURERS DETAILS
5
FIBER MESH 20MM (8") OVERLAP
TO BOTH SIDES OF CORNERS
200
8"
LEDGE BELOW W/ FLASHING
150
6"
200
8"
EXTERNAL
E2
CAPPING TO BE LAPPED AND SEALED IN
ACCORDANCE W/ MANUFACTURERS
PROPRIETARY FASTENING W/ WATER PROOF SEALANT TO EDGES RECOMMENDATIONS
1
257
METAL PARAPET CAPPING TO BE POWDERCOATED IN GRAY FINISH METAL SUPPER AND DOWN PIPE
PAINTED TO MATCH RENDER WALL
10" EXTERIOR GRADE TIMBER BLOCKING TO CREATE FALL ON PARAPET AS SHOWN
FALL PARAPET CAPPING - COLOR TBC
MIN 150MM/4" UPSTAND
REFER TO ROOFING TYPES FOR ROOF BUILD-UP DETAILS SECONDARY FLASHING, LAPPED AND SEALED
INTERNAL TAPE SKIM JOINTS IN DRYWALL
FALL
PROPRIETARY WEATHER TRANSITION BACKER ROD W/ SEALANT Rev. Date Description
1/2"/17MM (MIN) EXTERIOR GRADE OSB BOARD TO BE VAPOR AND AIR CONTROL LAYER, LAP STRIP, ENSURE LAPPED AND SEALED
AND SEAL AROUND EDGES, AND UP UPSTAND. EDGES 150MM FROM EDGE
96
4"
TIMBER FRAME UPSTAND FASTENED BACK TO METAL DECK, LINE WITH OSB TO PROVIDE ALL EDGES SEALED W/ WATERPROOF
82
3"
RIGIDITY, REFER TO STRUCTURAL ENGINEERS DETAILS ALSO MASTIC AS PER MANUFACTURERS
RECOMMENDATIONS 5
4 1/2"
116
LAP AND SEAL ALL EDGES TO CREATE VAPOR AND AIR CONTROL LAYER,
122
METAL TRIM INSIDE OF OPENING BACKER ROD W/ SEALANT
5"
AND TO LAP DOWNPIPE, SEALED W/
PACK UPSTAND W/ INSULATION TO ENSURE NO WATERPROOF MASTIC
COLD BRIDGING ENSURE PARAPET FILLED
BENT CLOSURE PLATE UNDER STUD TRACK. TO BE ATTACHED TO DECK BY SELF ADHERING TRANSITION MEMBRANE AT JOINT,
CONTRACTOR. ADDITIONAL TIMBER STUD SUPPORT AS REQ'D TO LAP AND SEAL BETWEEN EXISTING AND NEW
WALLS, C/W BACKER ROD AND SEALANT.
ADDITIONAL CONNECTION FOR SUPPORT TO WATERPROOF MASTIC TO UNDERSIDE OF METAL TRIM
FOR ALL EDGES AND FASTENINGS
ALLOW FOR BUILDING DEFLECTION. REFER TO BACKER ROD W/ SEALANT
STRUCTURAL ENGINEERS DETAILS
EXTERNAL
BENT CLOSURE PLATE UNDER STUD TRACK. TO BE ATTACHED TO DECK BY
CONTRACTOR. ADDITIONAL TIMBER STUD SUPPORT AS REQ'D
METAL TRIM BELOW
204 METAL STUD CONNECTION TO ALLOW FOR METAL STUD SUPPORTING ANGLE WITH CONNECTION TO ALLOW FOR RETURN AND LAP ALL FINISHES AT LOW LEVEL,
BUILDING DEFLECTION. INSTALLATION AS BUILDING DEFLECTION.
8" USE ADDITIONAL METAL FLASHING LAPPED AND
RECOMMENDED BY MANUFACTURER. SEALED AS REQ'D.
128 78
REFER TO STRUCTURAL ENGINEERS DETAILS
5" 3"
REFER TO WALL TYPES FOR DETAILS EXISTING NEW Professional Seal
NB: SECONDARY EMERGENCY ROOF SCUPPERS AT HIGH POINTS ON ROOF
REFER TO ROOF PLAN FOR LOCATIONS
TENDER ISSUE
Issued for
123 77
170501 As indicated
5" 3"
Drawing date Scale
16011 Author
Project no. Drawn by
NEW- OLD WALL TRANSITION
2
1" = 1'-0" TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
TYP. PARAPET SCUPPER DETAIL Project
1
1" = 1'-0" 1" = 1'-0" CONSTRUCTION DETAILS
Sht 1
13/10/2017 10:28:54 AM
Drawing title
A502
Sheet no.
SCREW FASTENING INTO CONCRETE SLAB
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
5" THRESHOLD COVER PLATE (MAX HEIGHT 7MM)
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
ALLOW 2" GAP BETWEEN SLAB AND MAPLE FLOOR
used for construction purposed until signed by the
AS PER MANUFACTURERS RECOMMENDATIONS consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
Architecture Inc.
General Notes
ROBBINS SPORTS WOOD ULTRA STAR SPORTS
FLOOR - LOW PROFILE 1 3/4" (44MM)
1 1/2"
44
6 MIL VAPOR RETARDER ALLOW 2" GAP BETWEEN SLAB AND MAPLE FLOOR AS
PER MANUFACTURERS RECOMMENDATIONS
49
49
2"
2"
PH2 - NEW FLOOR TRANSITION DETAIL
2
1 1/2" = 1'-0"
Professional Seal
TENDER ISSUE
Issued for
170501 1 1/2" =
Drawing date 1'-0"
Scale
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
CONSTRUCTION DETAILS -
Sht 2
13/10/2017 10:28:55 AM
Drawing title
A503
Sheet no.
E2
2) CANT STRIPS ARE NOT REQUIRED WHEN CAP SHEET FLASHING OR ALL PLIES ARE THERMOFUSED. General Notes
ACCESS LADDER
3) PRIMING IS REQUIRED W/ ALL THERMO FUSED/SELF ADHERED MEMBRANES.
ACCESS LADDER TO HAVE SHOP DRAWINGS TO BE STAMPED BY AN
ENGINEER QUALIFIED IN THE PROVINCE OF ONTARIO
1200
47"
CAGES 680 mm (27") MIN WIDTH & EXTEND BETWEEN 680 mm (27") - 760
mm (30") FROM THE CENTERLINE OF THE RUNG (MEASURE ON THE
E2
• 2 PLY MODIFIED BITUMEN THERMOFUSIBLE ROOFING SYSTEM
CLIMBER SIDE OF THE LADDER, HORIZONTAL & PERPENDICULAR TO THE • OVERLAY SUITABLE FOR TORCH APPLIED MEMBRANES
RUNG). • 1.4" PROTECTION BOARD
150MM MIN
• 2" POLYISO TAPERED INSULATION
• 4" POLYISO INSULATION
• 6MIL VAPOR BARRIER
• 1" (25MM) EXTERIOR GRADE OSB (VAPOR AND AIR CONTROL LAYER)
• STEEL DECK
1.15 DEGREE FALL
• OWS JOISTS
FALLS TO EXISTING RWO AND JUNCTION BETWEEN NEW AND EXISTING ROOFING BUILD UP.
NB: LAP AND SEAL NEW ROOF FINISH OVER EXISTING MIN 150MM
ENSURE ALL RELOCATED RWO CLEANED AND
REFER TO STRUCTURAL ENGINEERS DETAILS EXISTING STRUCTURE
STATUE: GYALTSEN - 8FT HIGH AND WEIGH 180LBS. • 2 PLY MODIFIED BITUMEN THERMOFUSIBLE ROOFING SYSTEM
• OVERLAY (SUITABLE FOR TORCH APPLIED MEMBRANES)
E2 • 1.4" PROTECTION BOARD
• 2" POLYISO TAPERED INSULATION
1524 • 4" POLYISO INSULATION
• 6MIL VAPOR BARRIER
60"
• 1" (25MM) EXTERIOR GRADE OSB (VAPOR AND AIR CONTROL LAYER)
• STEEL DECK
127 1270 127
• OWS JOISTS
5" 50" 5"
150(6")
25(1") 25(1")
min.
150
6"
184
7"
NOTES:
AN ADDITIONAL AIR/VAPOR TRANSITION MEMBRANE SUCH AS BLUESKIN IS TO
BE INSTALLED PRIOR TO THE WOOD PARAPET. THIS TIES THE ROOFING
SYSTEM INTO THE WALL AIR/VAPOR BARRIER TO MAINTAIN CONTINUITY.
ENSURE OVERLAY IS SUITABLE TO RECEIVE TORCH APPLIED MEMBRANES
WHEN THE BASE SHEET IS THERMOFUSED. THE GAP BETWEEN THE VENT STACK AND VENT FLASHING
SHALL BE INSULATED TO PREVENT
CANT STRIPS ARE NOT REQUIRED WHEN THE CAP SHEET FLASHING OR CONDENSATION. SEAL THE TOP WITH MASTIC AND FASTEN
PLIES ARE THERMOFUSED. CAP.
PRIMING IS REQUIRED FOR ALL THERMOFUSED APPLICATIONS, A VAPOR RETARDER MAY BE USED TO WRAP THE
EXCEPT TO RE-COVER BOARD OR "TORCH SAFE" INSULATION INSULATION LAYER AT THE VENT.
PRODUCTS.
MECHANICAL FASTENERS SHOULD BE SPACED AT 200MM (8") VENT STACK THE VENT FLASHING IS SET IN POLYBITUME 570-05
SEALANT (OR SIMILAR) AND THE TOP SURFACE PRIMED
O.C. ON THE OUTSIDE AND 450MM (18") O.C ON THE INSIDE OF 5
CL THE PARAPET.
1" = 1'-0"
PRIOR TO INSTALLATION OF MEMBRANE
124 79
5" 3"
REFER TO STRUCTURAL ENGINEERS DETAILS FOR ADDITIONAL
STRUCTURAL SUPPORT FOR FASTENINGS SPECIFICATIONS
E2
121
5"
60"
5" 5"
COMPRESSION RING
TAPERED INSULATION
OSB SUBSTRATE
TENDER ISSUE
Issued for
89 89
A VAPOR RETARDER MAY BE USED TO TIBETAN CANADIAN
WRAP THE INSULATION LAYER AT THE
CULTURAL CENTER
133
5"
3
1" = 1'-0" A504
Sheet no.
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
5 Architecture Inc.
General Notes
SHOP DRAWINGS TO BE SUBMITTED TO
METAL EXTERIOR GRADE GALVANIZED STEEL ARCHITECT AND ENGINEER FOR APPROVAL.
E1 E2 HANDRAILS TO FASTEN BACK TO STRUCTURE OF STEPS
STAIRCASE, LANDING, AND HANDRAIL TO BE SUPPLIED
BY METAL SUB-CONTRACTOR. E2 E1 ALL DIMENSIONS AND LEVELS TO BE
SHOP DRAWINGS TO BE PROVIDED FOR REVIEW AND OVERALL DIMENSION W1.1 CONFIRMED ON VIA SITE MEASURE PRIOR
5326 TO FABRICATION
APPROVAL BY ARCHITECT AND STRUCTURAL ENGINEER. 1
209 1/2"
A505
581 2500 581
D35
CIRCULAR METAL HANDRAIL 2"/50MM DIAMETER 23" 98 1/2" 23"
3 VERTICAL BALUSTRADES TO EXTEND TO
THE GROUND LEVEL AS SHOWN. HANDRAIL TO BE FASTENED TO STAIR FRAMEWORK -
HANDRAIL BALUSTERS TO BE MAX 4"/100MM O/C A505 TO MINIMIZE PENETRATIONS TO WALLS
W1.1 3
STAIRCASE LANDING TO BE OPEN GRATE TO
STAIR STRUCTURAL FRAMEWORK TO HAVE MINIMAL
STEPS TO DRAIN TOWARD BACK OF TREADS ALLOW FOR DRAINAGE & ANTI SLIP (SHOP A505
935
FASTENINGS/PENETRATIONS INTO EFIS WALL.
DRAWINGS TO BE PROVIDE FOR APPROVAL STEPS TO RUN DOWN SIDE OF FOUNDATION WALL, AS
STEPS EXTERIOR NOSING FASTENINGS TO BE AT FOUNDATION WALL LEVEL.
728 37" SHOWN.
TO BE VISUALLY DIFFERENT FROM REST OF STAIR 5
28 1/2" ALL DIMENSIONS AND LEVEL TO BE SHOP DRAWINGS TO BE SUBMITTED AND APPROVED BY
CONFIRMED BY SITE MEASURE ARCHITECT AND STRUCTURAL ENGINEER
149
6"
575 871
HANDRAIL TO EXTEND 12"/300MM
BEYOND BOTTOM TREAD 22 1/2" 34 1/2" 365 300
PH3 - FF- GROUND FLOOR
+114.08
0' - 0" 14 1/2" 12"
STEPS TO DRAIN TOWARD BACK OF OPEN TREADS 0' - 0"
D35
W1
2499 1305
STEPS EXTERIOR NOSING
PH3 - FF- GROUND FLOOR
6 98 1/2" 51 1/2" TO BE VISUALLY DIFFERENT FROM REST OF STAIR
0' - 0" 947 3663 724
5
2485 2624 -3' - 7"
+113.07 37 1/2" 144" 28 1/2"
4 REFER TO STRUCTURAL ENGINEERS DRAWINGS AND
1092
43"
3 98" 103 1/2" SPECIFICATIONS FOR FOOTINGS/SLAB DETAILS
1
RISE: 180MM(7") 2
TREAD: 275MM(11") 1 A505
300
6 5 4 3 2 1
12"
914
36"
36"
PH3 - FF- GROUND FLOOR 4037 PH3 - FF- GROUND FLOOR
5
159" STEPS EXTERIOR NOSING
4 0' - 0" TO BE VISUALLY DIFFERENT 0' - 0"
2788
110"
3 +
-2' -113.18
11 1/2" FROM REST OF STAIR
35 1/2"
35 1/2"
UP
900
900
2508 2512
2
RISE: 180MM(7") 98 1/2" 99"
1 STEPS TO DRAIN TOWARD BACK OF
TREAD: 275MM(11") 1281 2519 1568 OPEN TREADS
300 50 1/2" 99" 61 1/2"
4 REFER TO STRUCTURAL ENGINEERS
12" DRAWINGS AND SPECIFICATIONS FOR
A505 5317
300 FOOTINGS/SLAB DETAILS
209 1/2" 5 4 3 2 1 12"
Professional Seal
TENDER ISSUE
Issued for
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
CONSTRUCTION DETAILS -
EXTERNAL STAIRS
13/10/2017 10:29:00 AM
Drawing title
A505
Sheet no.
F E2
3652
144"
General Notes
1779
70"
1516
OPENING
59 1/2"
286 1/2"
3101
7273
122"
3890
153"
F E2
E2
3652
19507
144"
768"
2
278 1/2"
7070
3 1/2"
92
378
15"
MIN DEPTH
62 1/2"
1588
7
W2
W2
6"
1779
70"
OPENING
W2
278 1/2"
7070
28 1/2"
1516
59 1/2"
3101
12 1/2"223
9"
1516
321
59 1/2"
LINE INDICATE LOCATION OF TRACK
150 2596 356
10509
888 1782 76
8604
150
6"
6"
22 1/2"
568
67"
APPROVED BY ARCHITECT AND LEVEL TO BE CONFIRMED VIA SITE MEASURE AND SUBMISSION OF SHOP
ENGINEER DRAWINGS FOR APPROVAL
OVERALL CUPBOARD SIZE TO BE
CONFIRMED W/ SPECIALIST
SUPPLIERS
W2
CUPBOARD OPENING TO ACCOMMODATE PARTITION DOORS Professional Seal
4
W2 TENDER ISSUE
CENTER LINE OF FOLDING PARTITION
3 1/2"
92
9
1094
Issued for
516MM (4'-11 1/2") FROM GRIDLINE-F
43"
6"
Drawing title
A506
Sheet no.
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
406
16"
proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
NEW PLINTH: REFER TO STRUCTURAL SPECIFICATIONS AND DETAILS: consultant responsible. This drawing, is an instrument
FOOTING: 13'-0" x 9'-3" x 8" THICK FOOTING R/W 15M @ 12" c/c T&B, EACH WAY of service, is provided by and is the property of Coolearth
Architecture Inc.
WALLS:6" CONCRETE FOUNDATION WALL R/W 15M @ 12" c/c V&H MIDDLE, PROVIDE
MATCHING DOWELS TO FOOTING & SLAB TO MATCH VERTICAL REINFORCEMENT.
1600 406
General Notes
PLINTH CAP: 8" THICK CONCRETE SLAB REINFORCED w/ 15M @ 12" c/c T&B, EACH WAY
63" 16" SIZE AND ARRANGEMENT TO MATCH EXISTING ADJACENT PLINTH.
152
6"
CONCRETE PLINTH TO BE CAST SQUARE
DETAILING AND FINISH FINISHES TO BE
COMPLETED BY CLIENT IN WOOD
2743
CONFIRM ALL DIMENSIONS VIA DETAILED SITE MEASURE OF
108"
EXISTING PLINTHS ON SITE. PROVIDE DETAILS FOR APPROVAL
BEFORE FABRICATION.
NEW PLINTH TO MATCH EXISTING.
ELEVATION 2
158
6"
380
15"
ELEVATION 1
PLINTH DETAIL CL CL
1
1/2" = 1'-0"
1 1/2"
41
203
203
8"
8"
102 102
4" 4"
152
6"
EQ EQ EQ EQ
139 1/2"
139 1/2"
3542
3542
406 2742 406 1600 406
152
6"
Professional Seal
TENDER ISSUE
Issued for
170501 As indicated
Drawing date Scale
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
1600
63"
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
ELEVATION 1 ELEVATION 2
CONSTRUCTION DETAILS -
PLINTH
13/10/2017 10:29:01 AM
Drawing title
PLINTH DETAILS
A507
1" = 1'-0"
Sheet no.
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
Architecture Inc.
C B2
General Notes
762 1928 1
W1.1
2464
97"
W5 W5 C B2
52 1/2"
1327
762
1219
48"
ROOF DRAIN BEYOND, LOCATIONS TO BE
CONFIRMED ON SITE.
151
1994
29' - 9"
6"
2917
115"
251
ALL PENETRATIONS (INC.
10" SERVICES/STRUCTURAL/ETC) IN BULK HEAD TO BE
FULLY TAPED AND SEALED WITH ACOUSTIC
CAULKING.
20"W x 12"H OPENING THROUGH BEAM WEB FOR HVAC DUCTS
REFER TO MECHANICAL AND STRUCTURAL DETAILS
300
12"
WALL TYP. W5
250
NB: NO PENETRATION TO METAL ROOF DECK - 10"
SUPPORT TO BE PROVIDE HORIZONTALLY BETWEEN
STEEL OWSJ's
31111
1225"
ACOUSTIC PARTITION TO WRAP UP AROUND STEEL
SUPPORT BEAM TO ENSURE FULL SEPARATION OF
SPACES AROUND FOLDING PARTITION
3 1/2" 69 1/2"
BULK HEAD TO ACCOMMODATE TRACK FOR
FOLDING PARTITION
511 213 44
20" 72 87 ALL CORNERS AND EDGES TO BE TAPED AND SEALED
8 1/2" 1 1/2"
WITH ACOUSTIC SEALANT/CAULK THROUGHOUT
3"3 1/2" W3 D85
HOLES IN BOTTOM FLANGE OF
691 258 291 227 512 SECTION TO BE COORDINATED W/
27" 10" 11 1/2" 9" 20"
HANGING PARTITION SUPPLIER
W5
56 1/2"
1436
1703
67"
W5
PANEL SIZE: EACH 1219MM WIDTH BY
77 1219 4714MM HEIGHT
FULL DIMENSIONS AND LENGTH ETC TO
3" 48"
BE CONFIRMED BY SITE MEASURE AND
SHOP DRAWINGS TO BE APPROVED BY
LOCATION FOR ARCHITECT AND ENGINEER
SERVICES
(DOWNPIPES ETC
REFER TO MEP
DRAWINGS)
9
Professional Seal
TENDER ISSUE
Issued for
170501 As indicated
Drawing date Scale
16011 Author
1 3
1/2" = 1'-0" 1" = 1'-0" TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
CONSTRUCTION DETAILS -
PH2 - FOLDING PARTITION
2
13/10/2017 10:29:05 AM
Drawing title
A508
Sheet no.
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
Architecture Inc.
General Notes
E2 E1 D C B2 B A KEY PLAN
30"
GRAY AREA INDICATE ARE OF DRY WALL GRAY AREA INDICATE ARE OF DRY WALL
CEILING TO BE INSTALLED CEILING TO BE INSTALLED
731 88
W3
29" 3 1/2" W2
19994
D89
787"
150
150
6"
6"
4269
150
6"
LINE INDICATES WHERE WALL ABOVE 168"
D40 237 227
STEPS UP TO HIGHER ROOF AREA
494 484
D94
9 1/2" 9"
W2
65 1/2"
1662
19 1/2" 19" W2
1703
67"
1853
73"
662
14" 125 1/2" 6" 88
3 1/2" 26"
W2 W2
D36
9
7 1/2"
7 1/2"
190
190
150
W2
6"
AREA OF SEPARATE COST INTERIOR WALLS BETWEEN GRID LINE E2 AND A 6" 105 1/2" 6" 62 1/2" 6" 158" 85"
W2
AREA OF WALL TO SEPARATE THE PRAYER HALL , AND TO CREATE THE VIP RECEPTION AND SUIT.
INCLUDE COST FOR INSTALLATION OF NEW WASHROOM, AND BATHROOM SUITE.
ALL DOORS AND ASSOCIATED DETAILS TO BE ALLOWED FOR IN SEPARATE COST.
3069
121"
D45
W2
ALIGN
722
D41 28 1/2"
150
6"
9A D43
25 1/2"
EQ
650
43 1/2"
1100
17 1/2"
EQ
450
150
6"
915
36"
915
36"
W2 W2
169 1/2"
4299
3 1/2"
84
555
22"
2899
114"
W4
17 1/2"
445
17 1/2"
450
17 1/2"
450
D42
W2
1209
47 1/2"
1874
74"
2648
104 1/2"
D44
Professional Seal
TENDER ISSUE
Issued for
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
CONSTRUCTION DETAIL -
VIP AREA
13/10/2017 10:29:06 AM
Drawing title
A509
Sheet no.
DOOR SCHEDULE - PH1 - DEMOLITION DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
Mark Phase Created Phase Demolished Height Width proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
D6 Existing Phase 1 - Shell_Core 6' - 10 1/2" 5' - 11" Architecture Inc.
D29 Existing Phase 1 - Shell_Core 6' - 6 1/2" 2' - 11 1/2" EXTERNAL CAULK AND SEAL ALL EDGES AROUND DOOR OPENINGS
Grand total: 8 BACKER ROD AND SEALANT
EXTERNAL DOORS:
128
128
5"
5"
SELF ADHERING TRANSITION MEMBRANE
1 WRAPPED INTO ROUGH OPENING
74
74
3"
3"
DOOR SCHEDULE - BB NEW EXTERNAL DOORS
Constructio Fire
DOUBLE UP METAL STUDS TO OPENING
n Type Function Mark Phase Created Phase Demolished Height Width Rating INTERNAL
PROVIDE TIMBER PACKING AROUND OPENING TO ALLOW FASTENING OF
FRAME AND ADHERENCE OF TRANSITION MEMBRANE
BACKING ROD AND SEALANT TO EDGES
Type 4 Exterior D30 Phase 1 - Shell_Core None 6' - 10 1/2" 7' - 10 1/2"
METAL THRESHOLD NO LARGER THAN 5/8" (15MM)
Type 4 Exterior D32 Phase 1 - Shell_Core None 6' - 10 1/2" 7' - 10 1/2"
Type 4 Exterior D33 Phase 1 - Shell_Core None 6' - 10 1/2" 7' - 10 1/2" DOOR
- IN LINE W/ INSIDE LINE OF INSULATION AS SHOWN, TO
Type 2 Exterior D34 Phase 1 - Shell_Core None 6' - 10 1/2" 7' - 10 1/2" AVOID THERMAL BRIDGING ETC
Type 2 Exterior D35 Phase 1 - Shell_Core None 6' - 10 1/2" 7' - 10 1/2"
Grand total: 5
TYP. EXTERNAL DOOR JAMB
1
1 1/2" = 1'-0"
DOOR TYPE PLAN EXTERIOR INTERIOR HARDWARE INSTALL METAL STUD ABOVE IN ACCORDANCE W/
1X2 WOOD TRIM AROUND 121 77 MANUFACTURERS DETAILS
FRAME / OPENING 5" 3"
400
41 1/2" 41 1/2"
DOOR HARDWARE TO BE LOCATED BETWEEN 700MM- 1100MM SCREW FIX THRESHOLD IN ACCORDANCE WITH
FROM FINISHED FLOOR DOOR/FRAME TO HAVE MANUFACTURERS DETAILS
43 1/2"
1100
INTERNAL
700
3 1/2"
92
REFER TO DOOR DETAILS DRAWING FOR ADDITIONAL INFORMATION
ALL DOOR ENTRANCE HARDWARE TO BE MOUNTED BETWEEN 700-1100mm FROM THE FINISHED FLOOR
• UNIVERSAL WASHROOM DOOR TO BE OPERABLE FROM OUTSIDE IN CASE OF EMERGENCY 170501 As indicated
• UNLESS NOTED - LEVER HANDLES TO BE USED THROUGHOUT Drawing date Scale
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
DOOR TYPES - EXTERNAL TYP. EXTERNAL DOOR HEAD & THRESHOLD DETAIL 40 TITAN ROAD,
2
1/4" = 1'-0" 1 1/2" = 1'-0" ETOBICOKE, ON, M8Z 2J8
Project
Drawing title
A600.1
Sheet no.
DOOR TYPE PLAN FRONT BACK HARDWARE
INTERNAL DOORS:
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
DOOR SCHEDULE - PH1 NEW INTERNAL DOORS TYPE 1 proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
INTERNAL DOORS HOLLOW METAL DOOR & FRAME SITE PAINTED - COLOR TO BE CONFIRMED consultant responsible. This drawing, is an instrument
LEVERS HANDLES & KICK PLATES. of service, is provided by and is the property of Coolearth
Constructio KEY LOCKS AND SELF CLOSER. Architecture Inc.
n Type Function Mark Phase Created Height Width Comments
General Notes
15 1/2"
400
Type 7 Interior D38 Phase 2 - Internal Fit Out 2 6' - 10 1/2" 3' - 5 1/2"
43 1/2"
1100
Type 5 Interior D39 Phase 2 - Internal Fit Out 2 6' - 10 1/2" 7' - 10 1/2"
27 1/2"
700
Type 8 Interior D40 Phase 1 - Shell_Core 6' - 10 1/2" 3' - 5 1/2"
Type 7 Interior D41 Phase 1 - Shell_Core 6' - 10 1/2" 3' - 5 1/2"
Type 7 Interior D42 Phase 1 - Shell_Core 6' - 10 1/2" 3' - 5 1/2"
Type 7 Interior D43 Phase 1 - Shell_Core 6' - 10 1/2" 3' - 5 1/2"
TYPE 6 HOLLOW METAL DOOR & FRAME SITE PAINTED - COLOR TO BE CONFIRMED
Type 9 Interior D44 Phase 1 - Shell_Core 6' - 10 1/2" 3' - 5 1/2" STORAGE LEVERS HANDLES AND ONE SIDED KEY LOCK
Type 6 Interior D45 Phase 1 - Shell_Core 6' - 10 1/2" 6' - 10 1/2" DOORS
Type 10 Interior D46 Phase 2 - Internal Fit Out 2 6' - 10 1/2" 3' - 5 1/2"
Type 10 Interior D47 Phase 2 - Internal Fit Out 2 6' - 10 1/2" 3' - 5 1/2"
15 1/2"
400
Type 7 Interior D48 Phase 2 - Internal Fit Out 2 6' - 10 1/2" 3' - 5 1/2"
43 1/2"
1100
Type 7 Interior D49 Phase 2 - Internal Fit Out 2 6' - 10 1/2" 3' - 5 1/2"
27 1/2"
700
Type 1 Interior D59 Phase 2 - Internal Fit Out 2 6' - 8" 3' - 0"
Type 1 Interior D60 Phase 2 - Internal Fit Out 2 6' - 8" 3' - 0"
Type 7 Interior D85 Phase 2 - Internal Fit Out 2 6' - 10 1/2" 3' - 5 1/2"
Type 1 Interior D86 Phase 1 - Shell_Core 6' - 8" 3' - 0"
Type 8 Interior D87 Phase 1 - Shell_Core 6' - 10 1/2" 3' - 5 1/2"
TYPE 8 HOLLOW METAL DOOR & FRAME SITE PAINTED - COLOR TO BE CONFIRMED
Type 1 Interior D88 Phase 2 - Internal Fit Out 2 6' - 8" 3' - 0" LEVERS HANDLES
SMALL CUPB'D
Type 8 Interior D89 Phase 1 - Shell_Core 6' - 10 1/2" 3' - 5 1/2" DOORS
Type 1 Interior D94 Phase 1 - Shell_Core 6' - 8" 3' - 0"
15 1/2"
400
43 1/2"
1100
27 1/2"
700
TYPE 7 HOLLOW METAL DOOR & FRAME SITE PAINTED - COLOR TO BE CONFIRMED
LEVERS HANDLES & KICK PLATES.
MAIN VIP DOORS KEY LOCKS AND SELF CLOSER.
DETAILING TO BE SUPPLIED AND INSTALLED BY CLIENT/SPECIALIST
15 1/2"
400
43 1/2"
1100
27 1/2"
700
150
15 1/2"
PAINTED
400
43 1/2"
1100
REFER TO DOOR SCHEDULE
27 1/2"
FOR DOOR SIZES
700
192 TYPE 10 SAFETY GLASS TO LOWER PANELS
7 1/2" KITCHEN HOLLOW METAL DOOR & FRAME SITE PAINTED - COLOR TO BE CONFIRMED
STAINLESS STEEL D SHAPED PULL HANDLES, PUSH PLATE & KICK
44 86 62 CLASSROOM PLATES.
1 1/2" 3 1/2" 2 1/2" DOORS KEY LOCKS, AND SELF CLOSER.
15 1/2"
400
43 1/2"
1100
27 1/2"
700
Rev. Date Description
TYP. INTERNAL DOOR JAMB TYPE 12 HOLLOW METAL DOOR & FRAME SITE PAINTED - COLOR TO BE CONFIRMED
1 LEVERS HANDLES W/ ONE SIDED KEY LOCK
1 1/2" = 1'-0" CUPBOARD
DOORS TBC
Professional Seal
ALL DOOR ENTRANCE HARDWARE TO BE MOUNTED BETWEEN 700-1100mm FROM THE FINISHED FLOOR
TENDER ISSUE
Issued for
GENERAL NOTES:
• PROVIDE DOOR STOPS AS REQ'D TO AVOID DAMAGE OF WALLS (O.B.C REQ'D FOR DOORS WITHIN F.R.R WALL - MECHANICAL/ELECTRICAL/JANITORIAL DOORS TO BE F.R. W/ 170501 As indicated
Drawing date Scale
SELF CLOSER AND POSITIVE LATCHING)
• MAIN ENTRANCE DOOR, INTERNAL MULTI-USE DOOR, AND UNIVERSAL WASHROOM DOORS TO BE POWERED OPENING WITH PUSH BUTTONS. 16011 Author
Project no. Drawn by
• UNIVERSAL WASHROOM DOOR TO BE OPERABLE FROM OUTSIDE IN CASE OF EMERGENCY
• UNLESS NOTED - LEVER HANDLES TO BE USED THROUGHOUT
TIBETAN CANADIAN
CULTURAL CENTER
SPECIALIST DOORS: LARGE FOLDING PARTITIONS (OR SIMILAR APPROVED)
CORFLEX Series 5500 54STC 102'x15' 6" (along gridline E2) - 5500 series - Track 40 (11,9 lbs/sqft) 102' x 15.5' = 1,581 sqft x 11.9lbs = 18,900 lbs 40 TITAN ROAD,
CORFLEX Series 5600 54STC 102'X25' 5" (along grid line C) - 5600 series - Track 11 (11,9 lbs/sqft) 102' x 26' = 2,652 sqft x 11.9lbs = 31,600 lbs ETOBICOKE, ON, M8Z 2J8
Project
Drawing title
A600.2
Sheet no.
EXTERNAL WINDOWS:
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
EXTERIOR WINDOW SCHEDULE BASE BUILD PHASE 1 EXTERIOR BACK proceeding with the work. This drawing shall not be
used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
Ref# Window Type Construction Phase Height Width Head Height Sill Height Description of service, is provided by and is the property of Coolearth
Architecture Inc.
TYPE 1
General Notes
W6 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane HIGH LEVEL IN PRAYER ROOM & MUTI-USE HALL
41 1/2"
1054
LAMINATED TOUGHENED GLASS
W7 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane FIXED, DOUBLE GLAZED, FIBRE GLASS INSULATED
1703
67"
W8 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane FRAMES
FRAME COLOR - BLACK
W11 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane 1829
W12 Type 2 Phase 1 - Shell_Core 3' - 5 1/2" 11' - 7 1/2" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane 72"
W13 Type 2 Phase 1 - Shell_Core 3' - 5 1/2" 11' - 7 1/2" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
W14 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane TYPE 2
HIGH LEVEL PRAYER ROOM AND MULTI-USE
W15 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane HALL
41 1/2"
1054
W17 Type 2 Phase 1 - Shell_Core 3' - 5 1/2" 11' - 7 1/2" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane LAMINATED TOUGHENED GLASS 1696 1696
1696 1696
FIXED, DOUBLE GLAZED, FIBRE GLASS 67" 67"
W18 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane INSULATED FRAMES 67" 67"
W20 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane FRAME COLOR - BLACK 3543
W21 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane 139 1/2"
W22 Type 1 Phase 1 - Shell_Core 3' - 5 1/2" 6' - 0" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
W66 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane TYPE 3
W67 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane CLASSROOMS AND WASHROOMS
FIXED, DOUBLE GLAZED, FIBRE GLASS
34 1/2"
876
W68 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane INSULATED FRAMES
FRAME COLOR - BLACK
W69 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
W70 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane 1829
72"
W71 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
W72 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
TYPE 4
W132 TYPE 9 Phase 1 - Shell_Core 3' - 5 1/2" 3' - 0" 28' - 10 1/2" 25' - 5"
MULTI-USE HALL
W133 TYPE 9 Phase 1 - Shell_Core 3' - 5 1/2" 3' - 0" 28' - 10 1/2" 25' - 5" FIXED, DOUBLE GLAZED, FIBRE GLASS
34 1/2"
44
876
1407 1 1/2" 1407
W134 TYPE 9 Phase 1 - Shell_Core 3' - 5 1/2" 3' - 0" 28' - 10 1/2" 25' - 5" INSULATED FRAMES
55 1/2" 55 1/2"
FRAME COLOR - BLACK
W135 TYPE 9 Phase 1 - Shell_Core 3' - 5 1/2" 3' - 0" 28' - 10 1/2" 25' - 5"
2985
W136 TYPE 10 Phase 1 - Shell_Core 2' - 10" 3' - 0" 15' - 8" 12' - 10" 117 1/2"
W137 Type 4 Phase 1 - Shell_Core 2' - 10 1/2" 9' - 9 1/2" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
W138 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
TYPE 6
W139 TYPE 10 Phase 1 - Shell_Core 2' - 10" 3' - 0" 15' - 8" 12' - 10"
HIGH LEVEL IN PRAYER ROOM & MUTI-USE HALL
W140 TYPE 10 Phase 1 - Shell_Core 2' - 10" 3' - 0" 15' - 8" 12' - 10"
41 1/2"
1054
LAMINATED TOUGHENED GLASS 788
W150 Type 2 Phase 1 - Shell_Core 3' - 5 1/2" 11' - 7 1/2" 28' - 10 1/2" 25' - 5" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane FIXED, DOUBLE GLAZED, FIBRE GLASS INSULATED
31"
FRAMES
W151 Type 4 Phase 1 - Shell_Core 2' - 10 1/2" 9' - 9 1/2" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane FRAME COLOR - BLACK
914
W152 Type 3 Phase 1 - Shell_Core 2' - 10 1/2" 6' - 0" 15' - 8 1/2" 12' - 10" U-VALUE: U-0.250 MIN. Wood/PVC/Fiberglass Frame w/ Fixed pane
36"
TYPE 7
CLASSROOMS AND WASHROOMS
864
34"
FIXED, DOUBLE GLAZED, FIBRE GLASS
INSULATED FRAMES
FRAME COLOR - BLACK
914
36"
METAL FLASHING
WINDOW
- TO BE IN LINE W/ INSIDE LINE OF INSULATION AS SHOWN, TO DOUBLE UP METAL STUD FRAMING AROUND OPENING IN
AVOID THERMAL BRIDGING ETC ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS
ALL EDGES TO BE CAULKED AND SEALED DuROCK MOISTURE BARRIER ADHESIVE W/ PUCCS INSULATION W/ 10MM
EXTERIOR
GEOMETRICALLY DEFINED DRAINAGE CAVITY (GDDC)
CAULK AND SEAL ALL EDGES TO WINDOWS
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
A601.1
Sheet no.
INTERNAL WINDOWS: DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
job and report any discrepencies to the architect before
proceeding with the work. This drawing shall not be
INTERNAL WINDOW SCHEDULE used for construction purposed until signed by the
consultant responsible. This drawing, is an instrument
of service, is provided by and is the property of Coolearth
Ref# Window Type Construction Phase Height Width Head Height Sill Height Description Architecture Inc.
General Notes
W76 Type 7 Phase 2 - Internal Fit Out 2 3' - 1" 6' - 0 1/2" 15' - 7" 12' - 6" Fixed Internal Glazing
W77 Type 7 Phase 2 - Internal Fit Out 2 3' - 1" 6' - 0 1/2" 15' - 7" 12' - 6" Fixed Internal Glazing
W78 Type 7 Phase 2 - Internal Fit Out 2 3' - 1" 6' - 0 1/2" 15' - 7" 12' - 6" Fixed Internal Glazing
W79 Type 7 Phase 2 - Internal Fit Out 2 3' - 1" 6' - 0 1/2" 15' - 7" 12' - 6" Fixed Internal Glazing
W80 Type 7 Phase 2 - Internal Fit Out 2 3' - 1" 6' - 0 1/2" 15' - 7" 12' - 6" Fixed Internal Glazing
W81 Type 7 Phase 2 - Internal Fit Out 2 3' - 1" 6' - 0 1/2" 15' - 7" 12' - 6" Fixed Internal Glazing
Grand total: 6
TYPE 7
940
37"
FIXED
72 1/2"
Professional Seal
TENDER ISSUE
Issued for
16011 Author
Project no. Drawn by
TIBETAN CANADIAN
CULTURAL CENTER
40 TITAN ROAD,
ETOBICOKE, ON, M8Z 2J8
Project
Drawing title
A601.2
Sheet no.
EXTERNAL WALLS
R1 ASSUMED:
EXISTING • 2 PLY THERMOFUSIBLE ROOFING SYSTEM
1/2"
13
DRAWING SHOULD NOT BE SCALED
INTERNAL (ASSUMED BUILD-UP) • OVERLAY SUITABLE FOR TORCH APPLIED MEMBRANES
Contractor must check and verify all dimensions on the
WALL TYP. W1 ASSUMED: • 1.4" PROTECTION BOARD job and report any discrepencies to the architect before
EXISTING BRICK EXTERNAL WALL - 1/2" GYPSUM BOARD - R0.9/" • 6" INSULATION proceeding with the work. This drawing shall not be
152
6"
used for construction purposed until signed by the
- METAL FRAME • 6MIL VAPOR BARRIER consultant responsible. This drawing, is an instrument
• 1" (25MM) EXTERIOR GRADE OSB
14 1/2"
- 2" BATT INSULATION - R3/" of service, is provided by and is the property of Coolearth
368
- 2" AIR GAP - R0/" • 1 1/2" (38MM) STEEL DECK Architecture Inc.
203
8"
• PAINT FINISH General Notes
EXTERNAL
• 2 PLY MODIFIED BITUMEN THERMOFUSIBLE ROOFING SYSTEM
• OVERLAY SUITABLE FOR TORCH APPLIED MEMBRANES
24
1"
R2
• 1.4" PROTECTION BOARD
102
4"
NEW HIGH FLAT ROOF
• 4" POLYISO INSULATION R24.9 (OR SIMILAR APPROVED)
227
9"
76 25
1"
• 6MIL VAPOR BARRIER
3"
• 1" (25MM) EXTERIOR GRADE OSB R0.6 (VAPOR AND AIR CONTROL LAYER)
• 3" (76MM) STEEL DECK
• 63" (1600MM) OWS JOISTS
• PAINT FINISH
WALL TYPE W1.1
NEW RENDERED EXTERNAL WALL
- PAINT FINISH R-VALUE VARIES MIN R25.5
- 1/2" GYPSUM BOARD - R0.9/"
INTERNAL - 8" (203x35MM) GALVANIZED STEEL STUD FRAME (800S137-68) AT 16"O.C
1/2"
13
- 1/2"/17MM (MIN) EXTERIOR GRADE OSB SHEATHING BOARD - R1.5/" (VAPOR AND AIR CONTROL LAYER)
- DuROCK ROLLER /POLAR BEAR MOISTURE BARRIER
- DuROCK POLAR BEAR MOISTURE BARRIER/ADHESIVE
203
8"
- 5" DuROCK PUCCS INSULATION (EPS) W/10MM GDDC - R3.75/"
359
14"
NEW LOW FLAT ROOF • OVERLAY SUITABLE FOR TORCH APPLIED MEMBRANES
FR - 45MIN (NON-COMBUSTIBLE CONSTRUCTION) (REINFORCED) • 1.4" PROTECTION BOARD
• 2" POLYISO TAPERED INSULATION (REFER TO PLANS) FIRESTONE ISO95+ R11.4 (OR SIMILAR APPROVED)
EXTERNAL
• 4" POLYISO INSULATION R24.9 (OR SIMILAR APPROVED)
R-VALUE R19 • 6MIL VAPOR BARRIER
• 1" (25MM) EXTERIOR GRADE OSB R0.6 (VAPOR AND AIR CONTROL LAYER)
• 1 1/2" (38MM) STEEL DECK
• 18" (450MM) OWS JOISTS
• PAINT FINISH
406 406
1/2"
13
100
5"
4"
1/2"
13
CORRIDOR SIDE
62
12"
4"
SERVICES - 1/2" (13MM) PLY BOARD or OSB BOARD (ADDITIONAL SUPPORT FOR FIXTURES)
- 1/2" (13MM) DRYWALL
3 1/2"
- PAINT FINISH
AS EXISTING - ASSUMED
F1 - 3 5/8" CONCRETE SLAB W/ POLISHED FINISH
92
1/2"
1/2"
13
13
WASHROOMS SIDE EXISTING CONCRETE FINISHED SLAB - 5" (125-130MM) STRUCTURAL CONCRETE SLAB
(ASSUMED BUILD-UP) - 6MIL POLYETHYLENE VAPOR BARRIER
127
5"
- INSULATION? TBC
- 5" (125-130MM) COMPACTED STRUCTURAL IN-FILL (HARD-
CORE/GRANULAR BASE)
127
5"
- 27 1/2" (700MM) EARTH - FILL SAND/GRAVEL
SPORTS HALL SIDE
406 406
16" 16"
WALL TYPE W5 - PAINT FINISH
INTERIOR PARTITION (150MM)
151
1/2" 4"
1 1/2"
44
F2
1HR FR & 50 STC
49
2"
NEW CONCRETE UNFINISHED SLAB
NB: NON LOAD BEARING CONSTRUCTION
25
1"
NB: MUST ACHIEVE 44MM DIFFERENCE FROM ADJACENT EXISTING
WALL TYPES
127
5"
LEVEL FOR FUTURE FINISHES TO BE APPLIED (AND FINISH FLUSH)
EXISTING
1" = 1'-0" - 2" CONCRETE SLAB
127
5"
- 6MIL POLYETHYLENE VAPOR BARRIER
- 25MM MILLED OFF EXISTING SLAB AND REINSTATED TO SAME
THICKNESS TO SAME EXISTING LEVEL (AS PER GEOTECHNICAL
RECOMMENDATIONS)
- AS EXISTING Rev. Date Description
F3
3 1/2"
92
NEW STRUCTURAL SLAB FINISHED - 3 5/8" CONCRETE SLAB W/ POLISHED FINISH
- 6" (150MM) STRUCTURAL CONCRETE SLAB
- 6MIL POLYETHYLENE VAPOR BARRIER
152
6"
- 1" SAND BLINDING (TO LEVEL)
- 5 1/2" (125-130MM) COMPACTED STRUCTURAL IN-FILL (HARD-
25
1"
CORE/GRANULAR BASE)
5 1/2"
137
-EARTH - FILL SAND/GRAVEL (AS REQUIRED TO ENSURE LEVELS Professional Seal
16011 Author
Project no. Drawn by
PH1 - BB - CONST
TYP.DETAILS
13/10/2017 10:29:14 AM
Drawing title
A602.1
Sheet no.
DRAWING SHOULD NOT BE SCALED
Contractor must check and verify all dimensions on the
SPORTS WOOD ADHESIVE W/ SUBFLOOR PANELS
406 406 job and report any discrepencies to the architect before
1/2"
13
7/16" (11MM) MFMA MAPLE FLOORING proceeding with the work. This drawing shall not be
16" 16" - PAINT FINISH used for construction purposed until signed by the
6 MIL VAPOR RETARDER
WALL TYPE W2 - 1/2" (13MM) DRYWALL consultant responsible. This drawing, is an instrument
TO MATCH EXISTING FINISHED of service, is provided by and is the property of Coolearth
CONCRETE FLOOR INSTALLED AT EARLIER PHASE
INTERIOR PARTITION - 4"/100MM METAL STUD @16" (400MM) O.C
1 1/2"
125
100
INTERNAL LEVEL114.09
5"
4"
Architecture Inc.
44
7/16" RESILIENT PADS (125MM) - 1/2" (13MM) DRYWALL
- PAINT FINISH General Notes
1/2"
13
F4
NEW SPORTS HALL SPRUNG FLOOR - 1 3/4" (44MM) ROBBINS SPORTS WOOD ULTRA STAR SPORTS FLOOR
49
2"
- 2" (49MM) CONCRETE SLAB (ALREADY INSTALLED IN PHASE 1)
- 6MIL POLYETHYLENE VAPOR BARRIER (ALREADY INSTALLED IN PHASE 1)
SPORTS HALL SIDE
- AS EXISTING
1/2"
1/2"
406 406
13
13
EXISTING
16" 16"
25
1"
WALL TYPE W3 - PAINT FINISH
5 1/2"
INTERIOR PARTITION (140MM) - 1/2" (13MM) DRYWALL
138
100
4"
(IMPACT RESISTANT) - 1/2" (13MM) PLY/OSB
SPORTS HALL - 12"/300MM METAL STUD @16" (400MM) O.C
1/2"
- 1/2" (13MM) DRYWALL
13
- PAINT FINISH
CUPBOARD SIDE
INSTALL ADDITIONAL STUD CROSS BRACING AND DRY WALL CORNER PROTECTION
1/2"
13
CORRIDOR SIDE
19
1"
F5
44
100
- 1/2" (13MM) DRYWALL W/ SKIM FINISH
4"
NEW TIMBER FLOOR - 3/4" (19MM) THICK, REAL WOOD TNG PLANKS. (FINISH ETC TO BE CONFIRMED) REAR WASHROOM WALL - 4" (100MM) CMU BLOCKWORK
2 1/2"
- 1" (25MM) SUB-FLOOR - 1x 25MM PLY BOARD or 2x 12MM PLY BOARDS
25
1"
300
62
12"
- 2 1/2" SERVICES VOID - TO BE CONFIRMED ON SITE FOLLOWING REVIEW OF SERVICES
SPACE FOR WASHROOM - 4" (100MM) METAL STUD
100
4"
NB: OVERALL BUILD UP TO EQUAL 1 1/2" BUILD UP TO CREATE A FLUSH FINISH SERVICES - 1/2" (13MM) PLY BOARD or OSB BOARD (ADDITIONAL SUPPORT FOR FIXTURES)
- 1/2" (13MM) DRYWALL
EXISTING
1/2"
1/2"
13
13
WASHROOMS SIDE
CONFIRM DEPTH OF BUILD UP VIA SITE MEASURE
406 406
16" 16"
151
- 1/2" (13MM) DRYWALL
6"
13 100
1/2" 4"
1" = 1'-0" (ACOUSTIC) - RESILIENT METAL CHANNELS
SPORTS & PRAYER HALL - 1/2" (13MM) OSB BOARD
CUPBOARD SIDE
- 4" (100MM) METAL STUD @16" (400MM) O.C
- 2 143/256" (65MM) ROCKWOOL BATT INSULATION
- 1/2" (13MM) DRYWALL
- PAINT FINISH
1/2"
13
WALL TYPE W6 - PAINT FINISH
INTERIOR PARTITION (125MM)
125
100
- 1/2" (13MM) DRYWALL W/ SKIM FINISH
5"
4"
WASHROOM/CHANGING RM WALL - 4" (100MM) CMU BLOCKWORK
- 1/2" (13MM) DRYWALL W/ SKIM FINISH
1/2"
13
- PAINT FINISH
B1 - NEW
DRY WALL CEILING NB: WHERE POSSIBLE USE HANG WIRE, WHEN DRYWALL CEILING IS IN
CUPBOARDS WITHIN THE MULTI-PURPOSE HALL CREATE TO DRYWALL BULK
HEAD VIA METAL STUD DETAIL
406
TENDER ISSUE
Issued for
TIBETAN CANADIAN
FOR FINISHED CEILING LEVELS REFER TO RCP CULTURAL CENTER
PLANS THROUGHOUT
40 TITAN ROAD,
CEILING TYPES
ETOBICOKE, ON, M8Z 2J8
Project
1" = 1'-0"
PH2 - IFO - CONST TYP.
DETAILS
13/10/2017 10:29:15 AM
Drawing title
A602.2
Sheet no.
TRUE PROJECT
NORTH NORTH
TABLE 1
170613 NTS
16011 DB
General Notes
10/05/2017 4:56:41 PM
S101
TRUE PROJECT
NORTH NORTH
170613 NTS
16011 DB
S102
TRUE PROJECT
NORTH NORTH
2 5
7
10
1 1
1 1
5
4 5
2 3
1
1
170613 NTS
16011 DB
Typical Details
10/05/2017 4:56:41 PM
S103
TRUE PROJECT
NORTH NORTH
L
O
O
O
C
C
100 (4") 10@500 (10@20") 10@400 (10@16")
120 (5") 10@425 (10@17") 10@325 (10@13")
140 (5-1/2") 10@350 (10@14") 10@275 (10@11")
150 (6") 10@325 (10@13") 10@250 (10@10")
160 (6-1/2") 10@300 (10@12") 15@500 (15@20")
180 (7") 10@275 (10@11") 15@450 (15@18")
200 (8") 15@500 (15@20") 15@400 (15@16")
220 (9") 15@450 (15@18") 15@350 (15@14")
L
L
L
O
O
O
240 (9-1/2") 15@400 (15@16") 20@500 (20@20") C
C
C
260 (10") 15@375 (15@15") 20@450 (20@18")
280 (11") 15@350 (15@14") 20@425 (20@17")
300 (12") 20@500 (20@20") 20@400 (20@16")
L
O
O
C
C
6 2017-10-10 ISSUED FOR TENDER
MECHANICAL PAD
170613 NTS
16011 DB
Typical Details
10/05/2017 4:56:41 PM
S104
TRUE PROJECT
NORTH NORTH
170613 NTS
16011 DB
Typical Details
10/05/2017 4:56:41 PM
S105
TRUE PROJECT
NORTH NORTH
CL
170613 NTS
16011 DB
S106
TRUE PROJECT
NORTH NORTH
170613 NTS
16011 DB
Typical Details
10/05/2017 4:56:41 PM
S107
TRUE PROJECT
NORTH NORTH
16011 DB
S201
TRUE PROJECT
NORTH NORTH
16011 DB
S202
TRUE PROJECT
NORTH NORTH
16011 DB
S204
FOOTING AND COLUMN SCHEDULE TRUE PROJECT
NORTH NORTH
PIER (CAP)
FOOTING/ PILE CAP
PIER (CAP)
2 2017-09-08 ISSUED FOR REVIEW
16011 DB
COLUMN SCHEDULE
10/05/2017 4:56:41 PM
S301
TRUE PROJECT
NORTH NORTH
PIER DETAIL TYPE - P1A 4 PIER DETAIL TYPE - P2A 5 PIER DETAIL TYPE - P3A 6
3/4"=1'-0" S302 3/4"=1'-0" S302 3/4"=1'-0" S302
16011 DB
PIER DETAIL TYPE - P1C 12 PIER DETAIL TYPE - P2C 13 PILE CAP DETAIL TYPE - PC2 14 PILE CAP DETAIL TYPE - PC2A 15 PILE CAP DETAIL TYPE - PC2B 16 S302
3/4"=1'-0" S302 3/4"=1'-0" S302 3/4"=1'-0" S302 3/4"=1'-0" S302 3/4"=1'-0" S302
TRUE PROJECT
NORTH NORTH
16011 DB
S401
TRUE PROJECT
NORTH NORTH
PLAN DETAIL 3A
1/2"=1'-0" S402
SECTION 1 SECTION 3
1/2"=1'-0" S402 1/2"=1'-0" S402
SECTION 2
1/2"=1'-0" S402
16011 DB
SECTION 4 SECTION 5
Tibetan Canadian Cultural
1/2"=1'-0" S402 1/2"=1'-0" S402
Centre
40 Titan Road,
Etobicoke, ON, M8Z 2J8
S402
TRUE PROJECT
NORTH NORTH
16011 DB
S410
TRUE PROJECT
NORTH NORTH
SECTION 4
3/4"=1'-0" S411
16011 DB
S411
TRUE PROJECT
NORTH NORTH
12" AT ENDS
16011 DB
SECTIONS, ELEVATIONS
AND DETIALS
10/05/2017 4:56:41 PM
S412
TRUE PROJECT
NORTH NORTH
16011 DB
S501
TRUE PROJECT
NORTH NORTH
16011 DB
ELEVATIONS
10/05/2017 4:56:41 PM
S502
3. 9 3. Existing One Storey Building
36 11 3 1 - DO NOT SCALE DRAWINGS.
11 3. 11
3. 84 4
70 .4
11
4.
9 - CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
40 AGAINST SPECIFICATIONS AND REPORT ANY
11 DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
4.
95
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
11
SCOPE OF WORK.
5. 11
14 5.
19 - USE ONLY THE LATEST DRAWINGS.
11
3.
72 J I H G F E2 E1 D1
D1 D C1 C B2
B2 B1 B A1 A2 A
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
11 11
PRODUCED.
3.
21
4.
87
11
5.
0
11
4.
11
4. PROPERTY LINE
[11833]
38'-10"
6 63 51 148.23
25 26 27
11 11 EXISTING CHAIN LINK FENCE
3. 3. 11 11 11
63 11 94 4 11 4. 11
11 11 .0 4. 0 4. 4.0
3. 3. 4 EXISTING CONCRETE 11 11 6 05 5 06 8
61 74 .0 BLOCK 3. 4.
18'-4 1/2"
7 RETAINING WALL 92 02
[5607]
NO. ISSUE DATE
11 11
3. 11 3.
69 3.
68
11
3.
8 11
SET BACK
11
3.
99
96 11
4.
0
1. ISSUED FOR REVIEW 08AUG.17
4 3 .8 2
18 SETBACK 9 2. ISSUED FOR REVIEW 14SEPT.17
28
3. ISSUED FOR REVIEW 29SEPT.17
11 VERIFY THE EXISTING GAS SUPPLY
11 3.
4. ISSUED FOR REVIEW 4 OCT.17
NEW STRUCTURE TO
3. 88
[21306]
3.
69'-11"
11
MH 3.
70
69 3. 11 11
9 RD AND LABOR TO COMPLY
82
(APPROX. TOTAL 3. 3 .8 EXT.
EXT. RWO
RELOCATED RD
84 4 RWO
EX. EX. RTU2 GAS SUPPLIER STANDARD 30
LOAD: 2500MBH
11 N.4''
NEW MECHANICAL
3.
88 RD
FCRD
MECHANICAL UNIT
11
72'-5 1/2" AT 5PSI) 4. EX. RTU1 CRICKETS
MECHANICAL UNIT
13 11 4 Courtyard 09 EXT.
RWO 6 6
11 3.
27.5 GPM
UNIT
[22081]
EXISTING
RWO
3. 97 31
96
EXISTING
REFER TO STRUCTURAL FOR
EXISTING
HP
O/H 11 2 2
UP TO NEW ROOF. STEEL FRAMEWORK DETAILS
AND SPEC
3.
45 11
3. EXISTING O/H 11 11 CTE INSTALL PER NEW STRUCTURE TO
1.15 DEGREE FALLS N. RTU5 NEW STRUCTURE TO
1.15 DEGREE FALLS
6A
11
78 HP 11 3.
89
3.
92 G G G G G G
B.149.15 32 6A
6A
3.
3. 89
5 8
G
EX. FIRE MAIN FROM STREET N.4'' 33
53.34
EXISTING G G G G G G G G G
SOD 11
(TO
4.
04 BE VERIFIED) Existing Prayer Wheel
FCRD
RWO
7 7
TITAN ROAD
11
11 4.
00
11
4. EX. A UP TO NEW ROOF.
27.5 GPM
3.
77
11
4.
Updated 11 11 EX. RD
34
Transformer 4.
EX.
1
11 05 07 INSTALL PER
G
1
REL.
3
4.
RD
.8
EXISTING ROOF
07 11
0
EXT. TO FALLS
11
NFHB 4. 11 RWO B.149.15 NEW STRUCTURE TO
NEW STRUCTURE TO
1
RD
1.15 DEGREE FALLS
4. 04 4. EXT. RWO 1.15 DEGREE FALLS
GAS 1 7A
NEW ACCESS
4
METER
.1 08 11 EXT.
RWO
RELOCATED
LADDER 7A 7A
3 35
11 11
3. 3. 3 3
17 41
EX. EX. N.4''
G
G G G G
11 EX. 1/2'' GAS VENT VENT
R1
FCRD 36
NEW MECHANICAL
3.
G
11 8 8
0 5 3.
70
FOR WATER HEATING CRICKETS
RWO
EX.
+ 119.74M
27.5 GPM
11 (TO BE VERIFIED) GENERAL NOTE:
N.RTU6
UNIT
11 4.
G
3.
44
05 EX.INCOMING WATER PRV 37
FOR EXACT LOCATION OF ALL
FROM STREET
CENTERLINE OF ROAD
SCUPPER
ROOF OPENINGS REFER TO
G
EX. 2'' GAS LINE ARCHITECTURAL AND
1
(TO BE VERIFIED)
1
4
STRUCTURAL DRAWINGS.
.0
NEW STRUCTURE TO
1.15 DEGREE FALLS
G G G G G G G G G G G G
5
PRINCIPAL UP TO ROOF 8A 38 8A
ENTRANCE
FOR FIRE EX. CTE REFER TO STRUCTURAL FOR
STEEL FRAMEWORK DETAILS
AND SPEC
11
FIGHTING
3.
PRV
11
3
68
4.
09
MECHANICAL UNIT
MECHANICAL UNIT
A504
EX. RTU3
G
STATUE 39
EXISTING
EXISTING
4 4
XSAN XSAN XSAN SCUPPER
EXT. EX. RTU4 N.4''
9 9
RWO
A A N.4'' A 40
EX. EXT.
EX.
RWO
FCRD
11 FCRD
4. RD RD
RWO
20.3 GPM
RWO
41
FUTURE PHASE 3
1
11
2. (TO BE VERIFIED)
(N.I.C)
EXT. RWO
RELOCATED REL. INSTALLATION (TYP.)
99 11
3. RD 3''VENT
SETBACK
40 42
VENT VENT
3''VENT
NEW STRUCTURE TO
NEW STRUCTURE TO
VENT
UP
45
SCUPPER
11 11 11
11
11
3. SETBACK 11 XS
44
3. 3. 3. 16
PROPERTY LINE
51 39 26 3. 3 3 .0 T UP
30 7 M
EX.FIRE DEPARTMENT 11
3.
11
3
EX.BLDG STORM
04 .0 EXITING 45
SIAMESE CONNECTION 0
(TO BE VERIFIED)
11 11 CB
11
3.
28
3.
14
CB
3.
02 PROPERTY LINE 11
3.
00
11
2.
9 7
[15624]
51'-3"
11
3 RED LINE INDICATES AREA OF SCOPE OF WORK
11
3.
09
1 ROOF PLAN
M1 SCALE: 1''=20'-0''
2. THERE SHALL BE A SUPPORT AT EVERY FITTING AND BEND. ALL SUPPORT LOCATIONS TO COMPLY SUPPLY AIR DUCT
THE LATEST GAS CODE. DUCT COLLAR
3. STYROFOAM ROOFMATE INSULATION TO BE SECURELY ADHERED TO ROOF.
1" ACOUSTIC LINED
4. ALL PIPING ON ROOF TO BE PAINTED YELLOW BY GENERAL CONTRACTORS. VENT STACK DUCTWORK
5. ALL VERTICAL PIPING UP SIDE OF WALLS OR ROOF ELEVATION CHANGES TO BE PAINTED TO MATCH WALL
NOTE:
FINISHING BY GENERAL CONTRACTOR AND BANDED BY MECHANICAL CONTRACTOR (LABEL GAS PIPE)
RETURN AIR DUCT
THIS DETAIL IS DIAGRAMMATIC ONLY.
EXACT UNIT CONFIGURATION(S) MAY VARY.
DWG. NO.
M1
NEW STEEL TO SUPPORT FUTURE - DO NOT SCALE DRAWINGS.
LARGE FOLDING PARTITION -
24''x36''
FROM RA TRANSFER
FFL TO UNDERSIDE WALL
OF STEEL - CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
M L K J I H G OPENING C/W GRILLE FOR
FUTURE PARTITION CLOSET.
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
H G W1 F E2 E1 D1 D C1 C B2 INSTALL
B1 AS HIGH ASBPOSSIBLE A1 A2 A
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
W1.1 SCOPE OF WORK.
AND BELOW FUTURE FINISH CEILING LEVEL.
11
4.
(TYP FOR
W8 4) - USE ONLY THE LATEST DRAWINGS.
16
W14 W13 W12 W11 W133 W7 W132 W6
D30 D32 - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
1 1 1 WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
VXB - NEW LATERAL CROSS PRODUCED.
D33
BRACING (HIGH AND LOW)
RTU5 GYALSTEN STATUE ABOVE
REFER TO STRUCTRAL
SPCIFICATIONS FOR
NEW TEMPORARY WALL TO BE ADDITIONAL FRAMING REQ'D
INSTALLED DURING CONSTUCTION GYALSTEN STATUE ABOVE NO. ISSUE DATE
REFER TO STRUCTRAL
SPCIFICATIONS FOR "A'' 18''x10'' 1A 1. ISSUED FOR REVIEW 08AUG.17
EX.
ADDITIONAL FRAMING REQ'D 800 CFM
RD 2. ISSUED FOR REVIEW 14SEPT.17
C/W DD,BD B.D.
3. ISSUED FOR REVIEW 29SEPT.17
45 deg DN.
TYP. FOR 10 4. ISSUED FOR REVIEW 4 OCT.17
EX. RTU1 EX. EX. RTU3 EX. 18''x10'' 5. ISSUED FOR REVIEW 10 OCT.17
RD RD 6. ISSUED FOR TENDER 11 OCT.17
FUTURE RETRACTABLE
BASKETBALL HOOP TO BE
INSTALLED NEW ROOF TOP 6
REFER TO STRUCTURAL
SPECIFICATIONS FOR RTU5 ABOVE
ADDITIONAL FRAMING/
SUPPORT.
EX.
NEW BASE
EX. 38''X26''
71"x107"
BASE 4
OED OED NEW LOCATION STATUE 3
2000 2 2 2000
SA & RA DUCTS C/W 1'' ACOUTIC LINING. PREPARE EXISTING SLAB FOR NEW
ALL INDICATED DUCTS SIZES ARE BASE PLINTH TO MATCH EXISTING
EX. EX. 6A
OED OED INSIDE DIMENSIONS, INCREASE SIZE
EX.38''X35''
3000 3000 EX.
ALIGN
EX.38''X35'' WHERE REQUIRED TO SUIT INTERNAL
OED
2000 EX.
INSULATION. (TYP)
EX. CFM
TAG
OED
1400
GENERAL NOTE:
C P
OED
F
O FR
2000
FOR EXACT LOCATION OF ALL ROOF
RO OO
AND STRUCTURE OPENINGS REFER TO 7
71"x107"
BASE 1
ALL SA & RA DUCTS MOUNT IN ARCHITECTURAL AND STRUCTURAL
DRAWINGS.
HIGH LEVEL BETWEEN AND H R
G NEW LOCATION OF STATUE 2
HI IGH
ABOVE OWJS.
MIN. 15 FT LONG RADUCT
EX. EX. EX.
RD RD F1
RD W H WITH 50''X24'' RA OPENING
NE TO
EX. C/W BIRDSCREEN (TYP FOR 2) 7A
EX. ADDITIONAL LATERAL SUPPORT
FOR ACCESS LADDER REFER TO OED
NEW LOCATION OF STATUE 1
OED 2000
PROVIDE TRANSITION FROM
4000
3 3
STRUCTRAL DRAWINGS
71"x107"
38''X26''
BASE 2
DUCTS TO BE INSTALLED AS HIGH F
RE
FOR SMOOTH AIR FLOW. (TYP)
AS POSSIBLE WITHIN ROOF
STRUCTURE WITH DIFUSSERS TO
BE INSTALLED 330" OFF FFL 8
DUCTS AND DIFFUSERS TO ALIGH
WITH LIGHTING AS SHOWN
ALSO REFER TO MEP CONSULTANT
11
DRAWINGS
3.
18''x10''
32
"A''
EX. EX. EX. EX. 800 CFM
W1.1
71"x107"
45 deg DN.
BASE 3
18''x10'' INDICATES
TYP. FOR 10 DRYWALL BULK
EX. RTU2 UNDERSIDE OF DECK AND
EX. RTU4 ALL STEELS AND DUCT
HEAD TO
SEPERATE SPACE 8A
WORK TO BE PAINTED BLACK AND ALLOW FOR
THROUGHOUT FUTURE FINISHED
THERMAL STAT AND CO2 SENSOR CEILINGS TO BE
GYALSTEN STATUE ABOVE C/W PROTECTIVE LOCKBOX. DUCTS THRU 20''X12'' BEAM OPENING
EX. REFER TO STRUCTRAL
INSTALLED
C/W- ACOUSTIC
REFER TO SLEEVES AND SUPPORTS
NEW TEMPORARY WALL TO BE OED SPCIFICATIONS FOR CONFIRM WITH OWNERGREY
OR ARCHITECT
AREA INDICATES
DRYWALL BULK HEAD TO SECTIONS/DETAILS
INSTALLED DURING CONSTUCTION
2600 ADDITIONAL FRAMING REQ'D FOR PROGRAMMER
W3 LOCATION. (TYP) LOCATION SEE STRUCTURAL DRAWINGS
SEPERATE SPACE AND ALLOW GYALSTEN STATUE ABOVE
FOR FUTURE (TYP FOR 4) REFER TO STRUCTRAL
EX. EX. D40 FINISHED CEILINGS TO BE
RTU6 D89 SPCIFICATIONS FOR
4 4 INSTALLED 16'-6" OFF FFL TO ADDITIONAL FRAMING REQ'D
RD RD FULL HEIGHT TO SUIT
W2 - REFER TO SECTIONS/DETAILS W2 UNDERSIDE OF NEW 38mm W2 W2
D94
W2 W2
PARTITION HEIGHT -
REFER TO DETAILS
STEEL DECK
REMOVE AND DISPOSAL 9
W15 W150 W17 W18 D36
ALL OBSOLETE DUCTWORKS W20 W134 W21
W2
W135 W22
"C''
W2
AND SUPPORTS. MAKE GOOD W2
100 CFM
FOR NEW CONNECTION
CL
DEM. 36''X12'' RA WALL OPENING (HI) C/W DD,BD W138
CTE W200X27 TO
C/W GRILLES ON BOTH SIDE 3/4'' UNDERCUT
BRACE TOP
OF STEEL W2
30 DEG DN.
D87 COLUMN D45
CONNECTION
- REFER TO
TYP. FOR 2
STRUCTURAL
DRAWINGS D41 D43
D44
17'-2" OFF FFL TO UNDERSIDE OF NEW 38mm STEEL DECK W2
5 5 5 D35 D34
5
1. CONFORM TO ALL APPLICABLE LAWS, CODES, STANDARDS, 9. CLEAN MECHANICAL SYSTEMS PRIOR TO COMMISSIONING 2.0 CEILING REMOVAL DRAWING NOTES
REGULATIONS AND BYLAWS. AND HANDING OVER TO OWNER.
2.0.1 EXISTING CEILINGS THAT ARE REQUIRED TO BE
10. THE DRAWINGS ACCOMPANYING THIS SPECIFICATION REMOVED AND/OR REINSTALLED AFTER CONSTRUCTION SUPPLY & INSTALL NEW RTU 'S ROOF-TOP UNITS AS PER
2. ARRANGE AND PAY FOR ALL PERMITS, FEES, APPROVALS
ARE TO BE CONSIDERED AS DIAGRAMMATIC ONLY AND DO COMPLETION, SHALL BE THE RESPONSIBILITY OF THE MANUFACTURER'S RECOMMENDATIONS, SPECIFICATION AND
AND INSPECTIONS, INCLUDING: COORDINATION WITH OTHER
NOT SHOW ALL THE STRUCTURAL AND CONSTRUCTION GENERAL TRADES CONTRACTOR. ALL TRADES SHALL SCHEDULE. SEE STRUCTURAL DRAWINGS FOR SUPPORT
TRADES. CARRY OUT WORK IN SAFE MANNER THAT
DETAILS. ANY INFORMATION INVOLVING MEASUREMENTS OF COORDINATE WITH THE GENERAL TRADES CONTRACTOR TO DETAIL. DIV. 16 TO WIRE. DIV. 15 TO WIRE 24V CONTROL (
CONFORMS TO ALL SAFETY REQUIREMENTS OF THE OWNER.
THE BUILDING SHALL BE TAKEN FROM THE STRUCTURAL PREARRANGE FOR ACCESS TO SERVICES ABOVE CEILING TYPICAL).
DRAWINGS, AND AT THE BUILDING SITE. MAKE WITHOUT SPACES. ALL CEILING HEIGHTS ARE TO REMAIN THE SAME
3. SUPPLY NEW EQUIPMENT AND INSTALLATION OF THE SAME REFER TO STRUCTURAL DRAWINGS FOR EXACT LOCATION
AS THEY CURRENTLY ARE, UNLESS OTHERWISE NOTED ON
INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
POINT FOR DURING CONSTRUCTION
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF
IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION OF UNITS ROOF CURBS, SIZES, AND CONFIGURATION.
S R Q P O N M L K J I H
H G
G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
ADDITIONS TO THE RUNS TO ACCOMMODATE STRUCTURAL THE DRAWINGS. INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
POINT FOR DURING CONSTRUCTION
AND OPERATING INSTRUCTIONS AND IN A MANNER THAT CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION EXISTING CHAIN LINK FENCE
25
11
PRACTICES.
4.1
6
D30 D32
1 1
D33
11. ALL GYPSUM BOARD BULKHEADS AND T-BAR CEILING 2.1.1 WHERE DUCTWORK IS TO BE REMOVED, AND NEW TEMPORARY WALL TO BE
INSTALLED DURING CONSTUCTION
1A
4. PROVIDE ADEQUATE CLEARANCES AROUND THE CEILING BY GENERAL TRADES CONTRACTOR. WHERE NEW PENETRATES EXISTING WALLS AND FLOORS, THE UNUSED SCOPE OF WORK
EQUIPMENT AS PER MANUFACTURERS' RECOMMENDATIONS. BULKHEADS ARE BEING INSTALLED IN AREAS THAT OPENINGS SHALL BE FILLED IN WITH THE SAME MATERIALS
6
RENOVATION
NEW BASE
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
USE TRAINED AND EXPERIENCED PERSONS TO DO THE CURRENTLY USE A T-BAR CEILING, ALLOW FOR T-BAR AS THE WALL CONSTRUCTION, BY THE GENERAL TRADES
6A
ALIGN
WORK. MODIFICATIONS TO SUIT NEW BULKHEAD. CONTRACTOR. MAINTAIN EXISTING FIRE SEPARATOR RATING 7
FOR EXISTING
71"x107"
BASE 1
NEW LOCATION OF STATUE 2
CULTURAL
NEW LOCATION OF STATUE 1
71"x107"
BASE 2
5. CONFORMANCE OF ELECTRICAL WORK TO THE PENETRATION. 8
STANDARDS AND REQUIREMENTS INDICATED ON THE 12. THE DRAWINGS INDICATE THE GENERAL LOCATION AND
CENTER
71"x107"
BASE 3
DRAWINGS AND SPECIFICATIONS. ROUTE TO BE FOLLOWED BY THE PIPES, DUCTS, CONDUITS, 2.2 EXISTING ROOF DRAINS.
8A
11
4.0
NEW TEMPORARY WALL TO BE
9
INSTALLED DURING CONSTUCTION
D40 D89
4 D94
AND OTHER FOREIGN MATERIALS. ETC., IS NOT SHOWN ON THE PLANS OR ONLY SHOWN WHERE NEW ROOFTOP EQUIPMENT IS SHOWN TO BE D41 D43
DIAGRAMMATIC ALLY, THESE SHALL BE INSTALLED AS TIGHT INSTALLED AND INTERFERENCE CANNOT BE AVOIDED, THE D42
HVAC-PLANS
MECHANICAL CONTRACTOR SHALL RELOCATE THE DRAIN,
D44
7. PROVIDE NECESSARY STRUCTURAL SUPPORT TO AS POSSIBLE TO STRUCTURAL MEMBERS, CONCRETE, 5 5 D35 D34
5
11
3.2
UP
2
EXT.STAIR 2
SUSPEND/SUPPORT DUCTING, EQUIPMENT, ETC. PROVIDE CEILINGS, AND WALLS TO INTERFERE AS LITTLE AS POSSIBLE AND EXTEND PIPING TO SUIT THIS NEW LOCATION. EXT.STAIR 1
11
J I H G
3.0
7
WITH THE FREE USE OF THE SPACE THROUGH WHICH THEY COORDINATE WITH ROOFING CONTRACTOR TO ALLOW FOR
RED LINE DENOTES AREA OF SCOPE OF WORK
11
REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
3.1
REQUIRED FOR ROUGH-IN OF SERVICES
8
DRAWN:GC
INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
POINT FOR DURING CONSTRUCTION REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
8. APPLY ONE COAT OF CORROSION RESISTANT PAINT TO 13. SHOULD ANY DISCREPANCY APPEAR BETWEEN THE J I H G
APPROVED:
ALL FERROUS SUPPORTS. CUT AND PATCH AS REQUIRED. SPECIFICATIONS AND THE DRAWINGS TO CAUSE DOUBT AS
TO THE TRUE MEANING AND INTENT OF THE DRAWINGS AND PROJECT NO:160603
REPAIR DAMAGE CAUSED AS A RESULT OF CONSTRUCTION
TO ANY EXISTING EQUIPMENT, PIPING, FINISHES, ETC. SPECIFICATIONS, A RULING SHALL BE OBTAINED FROM THE
CONSULTANT.
DWG. NO.
M2
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
E2 E1 D C B2 B A
GREY AREA INDICATE ARE OF DRY WALL GREY AREA INDICATE ARE OF DRY WALL
CEILING TO BE INSTALLED CEILING TO BE INSTALLED
NO. ISSUE DATE
W3
W2
D89
1. ISSUED FOR REVIEW 08AUG.17
LINE INDICATES WHERE WALL ABOVE
D40
STEPS UP TO HIGHER ROOF AREA
D94 2. ISSUED FOR REVIEW 14SEPT.17
W2
W2
W2 W2 3. ISSUED FOR REVIEW 29SEPT.17
W2 W2
D36
4. ISSUED FOR REVIEW 4 OCT.17
REMOVE AND DISPOSAL W2
9
5. ISSUED FOR REVIEW 10 OCT.17
ALL OBSOLETE DUCTWORKS W15 W150 W17 W18 W20 W134 W21 W135 W22 6. ISSUED FOR TENDER 11 OCT.17
AREA OF SEPERATE COST INTERIOR WALLS BETWEEN GRID LINE E2 AND A W2 W2
ALIGN
- REFER TO
STRUCTURAL D41
DRAWINGS
[0'-6"]
LOWER ROOF
150
D43
CL
D44
W66 W136 W67 W139 W68 W140 W69 W70 W71 W72
VXB
P O N M L K J I H G
H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
11
4.1
6
D30 D32
1 1
D33
1A
NEW BASE
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
6A
ALIGN
7
71"x107"
BASE 1
NEW LOCATION OF STATUE 2
3
7A
NEW LOCATION OF STATUE 1
RENOVATION
71"x107"
BASE 2
FOR EXISTING
8
3b
71"x107"
BASE 3
3c
8A
CULTURAL
11
3.6
11
4.0
8
D40 D89
CENTER
4 D94
9
D36
4b D87 D45
D41 D43
MECHANICAL
HVAC-SEPERATE PRICE
D42
D44
5 5 D35 D34
5
11
3.2
UP
2
EXT.STAIR 1
EXT.STAIR 2
11
J I H G
3
.0
7
DRAWN:GC
CHECKED:GC
M3 KEY PLAN APPROVED:
F1 SCALE: NTS PROJECT NO:160603
DWG. NO.
M3
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
SUPPLY FAN VANED SHORT-RADIUS ELBOW - CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
MAIN DUCT THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
R4
'D' R3 - USE ONLY THE LATEST DRAWINGS.
R2 R3 - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
STRAIGHT TRUNK DUCT R2 WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
ROOF D-3/4 D HEEL R 4D R2
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
3/4 D THROAT BRANCH DUCT
RADIUS 'D' 'D' 'D'
BALANCING DAMPER (BD.) "MULTI-LEAF DAMPERS" AT ALL MAIN
WHERE INDICATED ON DRAWING. 150 150 150
MINIMUM OF 1 DUCT DIA. BRANCH DUCTS FROM TRUNK DUCTS.
D R2 R2 R3 R2 R3 R4
MAY BE USED ANYWHERE FROM MAIN DUCT NO. ISSUE DATE
'R'=20 D"
300 262
STRUCTURAL 1. ISSUED FOR REVIEW 08AUG.17
350 275
STEEL WEB "SPLITTER DAMPERS" AT ALL BRANCH 'D' 2. ISSUED FOR REVIEW 14SEPT.17
400 287
JOIST OR DUCTS FROM MAIN BRANCH DUCTS 3. ISSUED FOR REVIEW 29SEPT.17
450 300
TRUSS 4. ISSUED FOR REVIEW 4 OCT.17
MAIN DUCT RATIO TO SUIT 500 312
AIR QUANTITIES 550 325
5. ISSUED FOR REVIEW 10 OCT.17
FULL RADIUS ELBOW 600 337
6. ISSUED FOR TENDER 11 OCT.17
L 650 262 481
W BRANCH DUCT 700 270 475
L=W/4 (4" MIN.) N.T.S. 750 275 495
BALANCING DAMPER (BD.)
WHERE INDICATED 800 281 512
MINIMUM OF 1 DUCT DIA. MAIN BRANCH DUCT 850 281 531
FROM MAIN DUCT BRANCH DIFFUSERS 900 287 550
USE ONLY AT LAST TAKEOFF BEFORE OUTLETS & TRUNK DUCT DUCT RIVETS SPACED NOT OVER 150 950 295 570
O.C. MIN. OF 3 RIVETS ON
THEN ONLY WHERE RECTANGULAR RUNOUTS ARE EACH END OF VALVE 1000 300 581
INDICATED ON DRAWINGS 1050 306 600
SPLITTER DAMPER 1100 306 612
1150 312 625
PROVIDE ALL
1200 312 637
TRANSITION MAIN DUCT
1250 312 662
FITTINGS TO OUTLET DUCT 1300 325 675
POSITION SUPPLY AIR DOUBLE HEM
L EDGE 1350 325 700
OUTLETS REGISTER/GRILLE
L=W/4 (4" MIN.) 1400 325 712
OVER OWJS. SEE SCHEDULE W BRANCH DUCT
1450 337 725
RECTANGULAR BALANCING DAMPER (BD.) 1500 337 750
OPPOSED HEAVY GRADE WHERE INDICATED 25x3mm (1"x1/8")
1550 275 500 925
SEALANT/CAULKING MINIMUM OF 1 DUCT DIA. GALVANIZED STEEL D
BLADE ROUND FROM MAIN DUCT RETURN AND EXHAUST SYSTEMS TO BE AS SUPPLY SYSTEM SHOWN EXCEPT ALL 1600 275 512 950
DAMPER AROUND THE OPENING SPLITTER DAMPERS TO BE REPLACED BY MULTI-LEAF VOLUME CONTROL DAMPERS
1650 281 512 962
IN BRANCH DUCTS
1700 281 525 975
150 THROAT 1750 287 537 1000
USE ONLY AT LAST TAKEOFF BEFORE OUTLETS & DEFINITIONS RADIUS
THEN ONLY WHERE ROUND RUNOUTS ARE
INDICATED ON DRAWINGS TRUNK DUCT:-SERVING TWO OR MORE MAIN BRANCH DUCTS
STAYS AT ENTERING & LEAVING
MAIN BRANCH DUCT:-SERVING TWO OR MORE BRANCH DUCTS EDGE OF VANES SPACED 600 MAX.
BRANCH DUCTS:-SERVING TWO OR MORE DIFFUSERS INSTALL STAYS WITH SLIGHT TENSION
OUTLET DUCTS:-SERVING ONE DIFFUSER
VANED SHORT RADIUS ELBOW
1 M4 3 TYP. BRANCH CONNECTION
M3 NTS M4 NTS 5 TYPICAL BALANCE DAMPER INSTALLATION 7 TYPICAL VANED ELBOW STANDARD
M4 NTS M4 NTS
LINER TO BE
ADHERED TO DUCT ACOUSTIC WALL
w 100% ADHESIVE - CROSS SECTION -
ALL AROUND
SEAL BETWEEN
9" SLEEVE AND WALL
DUCT SIZE AS INDICATED ON PLAN 3-1/4"
3-1/4"
12mm (1/2") THICK
SHEET METAL SLEEVE
AIR FLOW
VANES PRE-ASSEMBLED ON
RUNNER PLATES
DWG. NO.
M4
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
RENOVATION
FOR EXISTING
CULTURAL
CENTER
MECHANICAL
HVAC
SCHEDULES
SCALE: SEE NOTE
DRAWN:GC
CHECKED:GC
APPROVED:
PROJECT NO:160603
DWG. NO.
M5
M L K J I H G
- DO NOT SCALE DRAWINGS.
H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
11
AGAINST SPECIFICATIONS AND REPORT ANY
4.
16
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
D30 D32
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
1 1 THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
D33
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
NEW TEMPORARY WALL TO BE PRODUCED.
INSTALLED DURING CONSTUCTION
EX. REL. 1A
RD
NO. ISSUE DATE
EX. 1. ISSUED FOR REVIEW 08AUG.17
EX. 4'' RD
RWL
RD 2. ISSUED FOR REVIEW 14SEPT.17
RD ABV. 3. ISSUED FOR REVIEW 29SEPT.17
6 4. ISSUED FOR REVIEW 4 OCT.17
VERIFY EXISTING. 5. ISSUED FOR REVIEW 10 OCT.17
RWL
REPAIR OR PROVIDE NEW 6. ISSUED FOR TENDER 11 OCT.17
NEW BASE
TO COMPLY LOCAL CODE UNDER STRUCTURAL
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 CTE BEAM TO RWL PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
6A
ALIGN
CUT THE BRANCH 4'' OFF FROM MAIN,
GENERAL NOTE:
SEAL AND CAP. REMOVE AND DISPOSAL
OF ALL PIPING, ASSOCIATED FITTINGS,
RWL
FOR EXACT LOCATION OF ALL ROOF
RWL
ACCESSORIES AND SUPPORTS OPENINGS REFER TO ARCHITECTURAL
AND STRUCTURAL DRAWINGS. 4'' RD
THAT ARE NOT BEING REUSED. TYP. 7
71"x107"
ABV.
BASE 1
NEW LOCATION OF STATUE 2
3 UNDER STRUCTURAL
71"x107"
BASE 2
RWL
BEAM TO RWL
8
4'' RD
ABV.
71"x107"
BASE 3
EX. 2''ID DCW IN HIGH LEVEL
(TO BE VERIFIED) TIGHT TO COLUMN C/W 'T' BASE 8A
RWL
CLEANOUT
(TO BE VERIFIED) DOMESTIC WATER 6''RWL CONNECT
NEW TEMPORARY WALL TO BE
INSTALLED DURING CONSTUCTION SUPPLY IN HIGH LEVEL. TO 8'' RWL IN
XSAN XSAN XSAN XSAN XSAN XSAN XSAN XSAN XSAN BETWEEN OWJS
CTE HIGH LEVEL
EX. EX. D40 D89
4 EX. D94
RD RD
2''ID RD DN.
WITH BALL SHUT-OFF 9
DCW CTE D36
RWL RWL 4'' RD AND CAPPED IN
(52 FU) 4''RD RWL
RWL
RWL RWL RWL ABV. JOIST SPACE.
ABV.
(TYPICAL)
CTE D87 D45
XSAN
SAN
SAN
VERIFY INVERT BEFORE VERIFY EXACT
SAWCUT THE FLOOR RWL
LOCATION
REL. WHERE EX. STM
VERIFY EXISTING. 3''VENT 3''VENT ROOF PROVISION
ENSURE THE MIN.SLOPE LEAVE THE
EX. REPAIR OR PROVIDE NEW CAPPED AT 12"
TO BE DEVELOPED STM BLDG. PROVIDE
CO TO COMPLY LOCAL CODE XS
BELOW ROOF DECK.
D42
TM NEW CLEANOUT CO (TYP)
CO IF NOT EXISTING
(TO BE VERIFIED) D44
CO CTE
CO
5 5 D35 D34
5
11
J I H G
3.
07
1 FLOOR PLAN
P1 SCALE: 1''=10'-0''
TO UNDER FLOOR
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION
D45 S R Q P O N M L K J I H
H G
G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
(TYP FOR 2)
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF 25
ALIGN
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION
SAN SAN
EXISTING CHAIN LINK FENCE
P O N M L K J I H G
D41 H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
[0'-6"]
11
4.1
150
6
SCOPE OF WORK
D30 D32
1 1
D33
SAN
1A
2''DCW LAV 6
NEW BASE
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 PREPARE EXISTING SLAB FOR NEW
WC
BASE PLINTH TO MATCH EXISTING
6A
ALIGN
7
RENOVATION
71"x107"
3''VENT
BASE 1
NEW LOCATION OF STATUE 2
7A
NEW LOCATION OF STATUE 1
HWT 3
FOR EXISTING
71"x107"
BASE 2
CONFIRM WITH OWNER/ARCHIECT FOR ALL FINAL 3/4''DHW W2 W2
8
FIXTURES. SH
71"x107"
BASE 3
1-3/4''DCW 8A
CULTURAL
SAN
11
4.
09
NEW TEMPORARY WALL TO BE
INSTALLED DURING CONSTUCTION
D40 D89
4 D94
CENTER
D36
D87 D45
FD
D41 D43
3''VENT W4
D42
STACK
D44
5 5 D35 D34
5
MECHANICAL
11
3.2
UP
2
EXT.STAIR 2
EXT.STAIR 1
PLUMBING-PLANS
11
J I H G
3
.0
7
RED LINE DENOTES AREA OF SCOPE OF WORK
11
3.1 REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
8 REQUIRED FOR ROUGH-IN OF SERVICES
INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
POINT FOR DURING CONSTRUCTION REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF REQUIRED FOR ROUGH-IN OF SERVICES
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION
J I H G DRAWN:GC
W2
CHECKED:GC
APPROVED:
2 PLUMBING GENERAL NOTE 3 WASHROOM PLAN 4 KEY PLAN PROJECT NO:160603
P1 P1 SCALE:1: P1 SCALE:N.T.S. DWG. NO.
P1
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
NIBCO TYPE 604 COMMERCIAL GRADE - CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
ADAPTOR AND LAVATORY SUPPLY THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
CHROME PLATED KIT: HEAVY ANGLE STOP
REFER TO FLOOR PIPE SLEEVE OR BRASS ESCUTCHEON. VALVE W/ LOOSE KEY - USE ONLY THE LATEST DRAWINGS.
PLANS FOR PIPE TYPE "L" HANDLES AND HEAVY
SIZES SHEET METAL SLEEVE - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
COPPER PIPE CHROME PLATED COPPER
1/2" TO 5/8" SUMMER POSIFIX FIRE PROTECTION PLANS UNLESS THEY ARE NOT
OR EQUAL. SUPPLIES W/ INSULATED PRODUCED.
CONNECT TO ANNULAR SUPPORT BRACKETS
FILL OPENING WITH OR ENGINEER COVERS, (TYPICAL).
LOOP TO PREVENT 20 (3/4") SERVICES AS SPACE-PACK 1-1/2" VENT, (MIN.) GRID
GRAVITY GROUT OR SEALANT APPROVED EQUAL.
SHOWN ON PLANS SPACE WITH STRAINER
CIRCULATION DEPENDING UPON
FIBERGLASS NO. ISSUE DATE
BUILDING MATERIALS NOTE:
SET HEATER WITHIN MATERIAL ISSUED FOR REVIEW 08AUG.17
PENETRATED ALL EXPOSED PIPING, 1.
24''X24''X4'' DEEP 2. ISSUED FOR REVIEW 14SEPT.17
INDIRECT DRAIN FULL VALVES, EQUIPMENT,
SIZE OF RELIEF HOT GALVANIZED SHEET ECT. TO BE A.D.A. 3. ISSUED FOR REVIEW 29SEPT.17
CONNECTION WATER METAL DRAIN PAN COMPLIANT. A.D.A. LAVATORY 4. ISSUED FOR REVIEW 4 OCT.17
OFFSET, USE AS REQUIRED 5. ISSUED FOR REVIEW 10 OCT.17
ACCESS DOOR TANK 2" WASTE, (MIN.),
WALL PIPE OR ELECTRICAL CONDUIT TO ACHIEVE A.D.A. COMPLIANCE, 6. ISSUED FOR TENDER 11 OCT.17
CAVITY ACCESS FOR LOCATION AND REQUIRES ENGINEER APPROVAL.
3"(75) OPEN DOOR ROUTING OF WASTE, VENT
WASTE CEILING
1-1/2" & WATER PIPING REF.
(38) PLANS. LOCATE P-TRAP TO
SEAL ALL PROVIDE FOR MIN. KNEE
CEILING 2"x1-1/4" (FOR
1-1/4"(32) AROUND EDF'S) AND CLEARANCE
VENT WITH BUILDING WALL 2"x1-1/2" OF 8"(PER A.D.A.).
PAN TO OVERFLOW RESILIENT FOR SINKS AND
OR FLOOR LAVS); SANITARY HEAVY CHROME PLATED BRASS
NON-HARDENING P-TRAP W/ CLEANOUT PLUG
LAVATORY WALL SEALER-TYP
TAPPED TEE.
AND HEAVY CHROME PLATED BRASS
ELBOW, INSULATE ALL EXPOSED SINK
WASTE AND
NIBCO TYPE DWV WATER OUTLET PIPING AND
804 ADAPTOR. STOP VALVES, AS PER
SPECIFICATIONS AND A.D.A.
DRAIN PIPE
1-1/2"(38) 1/2'' ALL THREAD ROD
WALL NIBCO DWV TRAP ADAPTOR AND
ANCHOR TO STRUCTURE HEAVY CHROME PLATED BRASS
CONSTRUCTION
(TOTAL OF FOUR RODS) (REF. ARCH DWG'S). COVER TUBE. PROVIDE CHROME
ELEC. PLATED SOLID CAST BRASS
WATER ESCUTCHEON W/ SET SCREW,
HEATER (TYP. AT WASTE AND WATER
UNISTRUT WALL PENETRATIONS).
CHANNEL
PLUMBING GENERAL NOTES
2 PIPE/ELECTRICAL CONDUIT PENETRATION
1 ELECTRIC WATER HEATER DETAIL NUT AND 6 TYPICAL LAVATORY & SINK CONNECTION DETAIL
WASHER P2 THRU NOISE BARRIER
P2 NTS P2 N.T.S.
FLOW
UNISTRUT CHANNEL
PIPE ROLLER
FOR PIPE 3" SHIELD FOR PIPE
AND LARGER 3" AND LARGER
BRACING AT 90 DEGREE ELBOW IN CLEAR SHAFT
3 ELECTRIC WATER HEATER PLUMBING DETAIL 4 WATER PIPING HANGERS & SUPPORTS DETAIL
P2 NTS NTS
P2
PIPE SLEEVE 1 SIZE LARGER CLEVIS HANGER START PIPE AS HIGH AS POSSIBLE.
THAN OUTSIDE SURFACE E. MYATT & CO. SUSPEND PIPE DO NOT DROP BELOW THE BOTTOM
OF PIPE OR INSULATION, MOD. #151 CT ROOF DRAIN
FROM O.W.S.J.'S OF THE BEAM. ABOVE DOUBLE BOLT RISER
(TYPICAL). CLAMP (TYPICAL)
FINISHED
INSULATION TO ROOF FLOW CONTROL TIE ROD (TYPICAL)
ROOF DRAIN
BE CONTINUOUS
MIN. 4"DIA. BRACING AT 90 DEGREE ELBOW THROUGH SLAB
PIPE STORM
PIPING
DOUBLE BOLT RISER
ESCUTCHEON DECK CLAMP CLAMP
PLATES( BOTH RIGID FIBREGLASS (TYPICAL)
SIDES WHERE INSULATION
BEAM OR INSULATE ROOF DRAIN M.J. COUPLING
RENOVATION
EXPOSED ) TRUSS (TYPICAL)
FIRE RESISTANT
BODY & FINISH WITH 6 OZ
CANVAS TIE ROD
FOR EXISTING
FOAM SEALANT PROVIDE INSULATION
INSULATION
SHIELD E. MYATT SHIELDS AT PIPE SHORT RADIUS ELBOW
ROOF DRAIN
ABOVE
(TYPICAL)
CULTURAL
& CO. MOD. #251 - HANGERS UNTED AS HIGH AS
WRAP CANVAS POSS. TO ROOF DRAIN AT CENTER
OVER SHIELD INSULATE AS PER START OF RUN)
SECONDARY TIE ROD TO RISER
MECHANICAL
SPECIFICATION
WALL OR FLOOR CLAMP PLUMBING-SCHEDULE,
CONSTRUCTION
REF: ARCH. &
STRUCTURAL JOISTS DETAILS
STRUC.DRAWINGS. RWL ELBOW SCALE: SEE NOTE
HORIZONTAL STORM DRAIN DOWN TO MAIN
LEADER BRACING AT WYE FITTING DRAWN:GC
NOT TO RUN BELOW BEAM.
CHECKED:GC
5 PIPE SLEEVE DETAIL 7 STORM PIPING RUN AT HIGH LEVEL 8 MECHANICAL JOINT SPACING APPROVED:
NTS NTS NTS PROJECT NO:160603
P2 P2 P2
DWG. NO.
P2
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
RENOVATION
FOR EXISTING
CULTURAL
CENTER
MECHANICAL
PLUMBING-SCHEDULE,
DWG. NO.
P3
- DO NOT SCALE DRAWINGS.
GENERAL - CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
THE DRAWINGS INDICATE THE APPROXIMATE LOCATIONS OF SERVICES AS FAR AS THESE ARE AGAINST SPECIFICATIONS AND REPORT ANY
MECHANICAL DEMOLITION DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
PERFORM ALL MECHANICAL WORK DETAILED ON THESE DRAWINGS TO PROVIDE A COMPLETE AND MATERIALS AND ALTERNATIVES KNOWN. SHOULD ANY MECHANICAL OR ELECTRICAL SERVICE LINE BE BROKEN, OR DISRUPTED BY
FULLY FUNCTIONAL OPERATING SYSTEM TO THE SATISFACTION OF THE MECHANICAL CONSULTANT. OPERATIONS SPECIFIED UNDER THIS CONTRACT, REPAIR SERVICE LINES, AND MAKE GOOD ALL - CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
PROVIDE LABOUR, MATERIALS, PRODUCTS, EQUIPMENT AND SERVICES REQUIRED TO COMPLETE THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
USE ONLY NEW MATERIALS, CAPITALS AND CODE APPROVED IN ACCORDANCE WITH ALL LAWS, DAMAGE DUE TO THE DISRUPTION OR BREAK, AT NO EXPENSE TO THE OWNER. NOTIFY THE OWNER SCOPE OF WORK.
THE DEMOLITION WORK SPECIFIED HEREIN.
SPECIFIED WORK DESCRIBED OR INDICATED ON DRAWINGS DOES NOT DELEGATE FUNCTION TO REGULATIONS AND AUTHORITIES HAVING JURISDICTION. IMMEDIATELY WHENEVER ANY SERVICE LINE IS BROKEN OR DAMAGED. - USE ONLY THE LATEST DRAWINGS.
ANY SPECIFIED SUBCONTRACTOR OR IDENTIFY ABSOLUTE CONTRACTUAL LIMITS BETWEEN
REFER TO DRAWINGS FOR EXTENT OF DEMOLITION WORK. THE DRAWINGS INDICATE THE - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
MECHANICAL OR SUBCONTRACTORS. BEFORE PROCEEDING WITH ANY CHANGES, SUBMIT FOR APPROVAL BY THE ENGINEERS AND ACCEPT LIABILITY FOR COSTS INCURRED BY THE OWNER IN REPAIRING AND CLEANING EQUIPMENT, WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
APPROXIMATE LOCATIONS OF SERVICES AS FAR AS THESE ARE KNOWN. FIRE PROTECTION PLANS UNLESS THEY ARE NOT
OWNER. ETC., RESULTING FROM FAILURE TO COMPLY WITH THE ABOVE REQUIREMENTS. PRODUCED.
ENGINEERS FINAL INSPECTION IS IMPERATIVE. PRIOR TO INSTALLATION OF ALL CEILINGS, THIS
DISPOSE, OFF SITE, OF ALL DEBRIS IN ACCORDANCE WITH THE JURISDICTIONAL AUTHORITIES.
CONTRACTOR SHALL CONTACT GUNTHER LAMMERS (416-499 8000 EXT.203 OR EMAIL ALL MATERIAL AND EQUIPMENT (EXHAUST FANS, PIPE, INSULATION, METERS, ETC.) TO MEET OR USE ONLY THOSE EXISTING ENTRANCES AND STAIRS DESIGNATED BY THE OWNER FOR ACCESS TO
GLAMMERS@TMPTORONTO.COM) AND THE LANDLORD TO PERFORM A FINAL INSPECTION. WHEN EXCEED BASE BUILDING STANDARDS AND HAVE LANDLORD'S/TENANT'S APPROVAL BEFORE AND EGRESS FROM THE EXISTING BUILDINGS AND VARIOUS FLOORS WHERE WORK OF THIS
REMOVAL AND STORAGE OF SALVAGEABLE ITEMS AS DIRECTED BY THIS SPECIFICATION SECTION
CEILING TILES HAVE BEEN INSTALLED IT WILL BE NECESSARY FOR THE CONTRACTOR TO REMOVE ORDERING. CONTRACT IS TO BE CARRIED OUT. NO TRAFFIC THROUGH OTHER AREAS OF THE BUILDING WILL BE
PORTIONS FOR INSPECTION.
AND THE OWNER OF THEIR REPRESENTATIVE.
PERMITTED WITHOUT THE PRIOR CONSENT OF THE OWNER.
NO. ISSUE DATE
TENDER PRICE TO BE AS SPECIFIED, SHOW ALTERNATIVE EQUIPMENT AND ITEMIZED COST SAVINGS 1. ISSUED FOR REVIEW 08AUG.17
MEET THE REQUIREMENTS AND RECOMMENDATIONS OF ALL MUNICIPAL, PROVINCIAL AND FEDERAL
THE MOST RIGOROUS OF THIS SPECIFICATION AND BASE BUILDING STANDARDS SHALL FORM THE WITH TENDER DOCUMENTS. KEEP STAIRS AND CORRIDORS CLEAR AND OPEN AS REQUIRED BY FIRE MARSHALL FOR EXIT 2. ISSUED FOR REVIEW 14SEPT.17
BYLAWS AND ORDINANCES.
BASIS FOR THIS CONSTRUCTION. COMPLY WITH LANDLORD'S REQUIREMENTS FOR SYSTEM PURPOSES IN CASE OF FIRE, AND AS REQUIRED FOR USE BY THE OWNER'S PERSONNEL.
3. ISSUED FOR REVIEW 29SEPT.17
SHUTDOWN AND CONNECTION. IDENTIFICATION
EXECUTE THIS WORK IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING CODES AND
ARRANGE AND PAY FOR THE DISCONNECTION, CAPPING AND FOR PLUGGING OF GAS, WATER, 4. ISSUED FOR REVIEW 4 OCT.17
STANDARDS. 5. ISSUED FOR REVIEW 10 OCT.17
CODES AND BYLAWS SHALL BE STRICTLY ADHERED TO. OBTAIN NECESSARY PERMITS, APPROVALS PROVIDE NAME PLATES ON ALL MECHANICAL EQUIPMENT SHOWING VOLTAGE, DESIGNATION, CRU# SEWER, STORM AND OTHER SERVICES TO THE BUILDING TO BE DEMOLISHED. IN EACH CASE THE
CAN/CSA-S350-M1980 - CODE OF PRACTICE FOR SAFETY IN DEMOLITION OF STRUCTURES. 6. ISSUED FOR TENDER 11 OCT.17
AND INSPECTIONS FROM THE AUTHORITIES HAVING JURISDICTION. AND USE. NUMBERS AND LETTERS TO BE 3/8" (10MM) HIGH, WHITE LETTERING ON BLACK LAMINATED UTILITY COMPANY INVOLVED SHALL BE NOTIFIED IN ADVANCE AND ITS APPROVAL OBTAINED
ONTARIO BUILDING CODE.
PLASTIC. BEFORE COMMENCING THAT PORTION OF THE WORK. DISCONNECT AND CAP SERVICES AT THE
OCCUPATIONAL HEALTH AND SAFETY ACT.
PERMITS AND FEES REQUIRED BY THE AUTHORITIES HAVING JURISDICTION SHALL BE OBTAINED LOCATIONS INDICATED BY THE CONSULTANT.
REGULATIONS FOR CONSTRUCTION PROJECTS.
AND PAID FOR BY THIS CONTRACTOR. INCLUDE ALL APPLICABLE TAXES. ARRANGE FOR THE IDENTIFY ALL VALVES WITH TAGS. PROVIDE A FRAMED LIST OF VALVES, INDICATING THEIR
ONTARIO FIRE CODE.
INSPECTION OF WORK BY ALL INSPECTION AUTHORITIES HAVING JURISDICTION OVER THE WORK OF LOCATION AND USE, SUPPLY TO OWNER/TENANT. ARRANGE, SCHEDULE AND PERFORM WORK WITH MINIMUM DISTURBANCE TO EXISTING FACILITIES
REGULATIONS UNDER FIRE MARSHALS ACT.
THIS DIVISION. ALL CHANGES AND ALTERATIONS REQUIRED BY SUCH AUTHORITIES SHALL BE AND SERVICES.
CARRIED OUT PROMPTLY AND WITHOUT CHARGE. DUCTWORK
REMOVAL FROM SITE AND DISPOSAL OF DEBRIS SHALL BE CARRIED OUT IN ACCORDANCE WITH THE
SUBMIT A COMPLETE SCHEDULE OF SERVICE INTERRUPTIONS AND CHANGEOVERS WITH
REQUIREMENTS OF THE LOCAL JURISDICTIONAL AUTHORITIES.
EXISTING SITE CONDITIONS AFFECTING THE WORK OF THIS TRADE SHALL BE REVIEWED PRIOR TO FABRICATE DUCTWORK FROM GALVANIZED SHEET METAL WITH A MINIMUM COATING OF {1.83 APPROXIMATE DATES, REQUIRED DURATIONS AND TIMES OF DAY, FOR APPROVAL BEFORE
TENDER SUBMISSION. FAILURE TO DO SO SHALL NOT RELIEVE CONTRACTOR OF FULL CONTRACT PROCEEDING.
ARRANGE AND PAY FOR ALL PERMITS, NOTICES AND INSPECTIONS NECESSARY FOR THE PROPER
RESPONSIBILITY. DUCT INSTALLATION SHALL CONFORM TO THE FOLLOWING:
EXECUTION AND COMPLETION OF THE DEMOLITION WORK.
NOTIFY OWNER IN WRITING AT LEAST 72 HOURS IN ADVANCE OF PLANNED INTERRUPTION TO
CUTTING, PATCHING AND CORE DRILLING REQUIRED BY THIS TRADE SHALL BE PAID FOR BY THIS DUCTWORK SHALL BE SMOOTH ON THE INSIDE AND FREE OF OBSTRUCTIONS, VIBRATION AND EXISTING SERVICES.
ALL MATERIALS WHICH HAVE NOT BEEN DESIGNATED FOR SALVAGE FROM THE DEMOLITION SHALL
CONTRACTOR. X-RAY CONCRETE STRUCTURE IN ACCORDANCE WITH OWNER/LANDLORD RATTLE.
BECOME THE PROPERTY OF THE CONTRACTOR. REMOVE ALL MATERIAL AND DEBRIS FROM THE
STRUCTURAL ENGINEER'S REQUIREMENTS. PROVIDE DETAILS OF NEW OPENINGS THROUGH FABRICATE DUCTWORK, EXCEPT AS DESCRIBED IN THE NEXT ITEM, ACCORDING TO THE FOLLOWING INTERRUPTION OF SERVICE MUST OCCUR AT THE TIMES AND FOR THE DURATION STIPULATED BY
SITE AS QUICKLY AS POSSIBLE AND DISPOSE OF LEGALLY. BURNING OF DEBRIS OR SELLING OF
STRUCTURAL COMPONENTS FOR ENGINEER'S APPROVAL. INCUR ALL RELATED COSTS FOR CLASSIFICATIONS: THE OWNER.
MATERIALS ON THE SITE WILL NOT BE PERMITTED.
STRUCTURAL APPROVAL.
NOTE : ALL DUCTWORK MUST BE SEALED AS PER SMACNA CLASS 'C' AS A MINIMUM. PROVIDE LABOUR, MATERIALS, PRODUCTS, EQUIPMENT AND SERVICES REQUIRED TO COMPLETE KEEP SERVICE INTERRUPTION DURATION TO AN ABSOLUTE MINIMUM. CARRY OUT ALL
FIRE STOP SHALL BE ULC LISTED FOR THE REQUIRED SEPARATION AND PROVIDED AT ALL PIPE THE DEMOLITION WORK SPECIFIED HEREIN. PREPARATORY WORK, MEASUREMENTS, ETC., WITHOUT INTERRUPTION OF EXISTING SERVICES.
PENETRATIONS THROUGH RATED ASSEMBLIES. REPAIR/PROVIDE ALL SPAY FIRE PROOFING
REQUIRED TO MAINTAIN ORIGINAL RATINGS. W.G.] OR LESS WITH MAXIMUM VELOCITIES OF {13 M/S} [2500 FPM] SHALL BE CONSTRUCTED IN IF SERVICE INTERRUPTIONS ARE REQUIRED BY THE OWNER DURING THE NIGHT OR ON WEEKENDS,
REFER TO DRAWINGS FOR EXTENT OF DEMOLITION WORK. THE DRAWINGS INDICATE THE ETC., PREMIUM TIME SHALL BE INCLUDED AT THE CONTRACT PRICE. NO EXTRA CHARGES WILL BE
APPROXIMATE LOCATIONS OF SERVICES AS FAR AS THESE ARE KNOWN. ALLOWED AT A LATER DATE FOR FAILURE TO INCLUDE SAME.
PREMIUM TIME COSTS SHALL BE INCLUDED FOR WORK OUTSIDE OF NORMAL WORKING HOURS.
CLASS 2: ALL DUCTING SUBJECT TO POSITIVE OR NEGATIVE STATIC PRESSURE OF MORE THAN {250
PA} [1 IN W.G.] UP TO {500 PA} [2 IN W.G.] WITH MAXIMUM VELOCITY OF {13 M/S} [2500 FPM] SHALL BE DISPOSE, OFF SITE, OF ALL DEBRIS IN ACCORDANCE WITH THE JURISDICTIONAL AUTHORITIES. HANGERS AND SUPPORTS
FLASHING AND COUNTER FLASHING FOR EXTERIOR PENETRATIONS OR WATER-PROOFED FLOORS
SHALL BE PROVIDED UNDER THIS CONTRACT. FLASH ALL MECHANICAL PARTS PASSING THROUGH, CONSTRUCTED IN ACCORDANCE WITH SMACNA CONSTRUCTION STANDARDS FOR {500 PA} [2 IN
W.G.] DUCT. REMOVAL AND STORAGE OF SALVAGEABLE ITEMS AS DIRECTED BY THIS SPECIFICATION SECTION PROVIDE ALL REQUIRED SUPPORTS ON OUTSIDE OF DUCTWORK, INSTALLATION SHALL BE TO THE
OR BUILT INTO A ROOF, OUTSIDE WALL OR WATERPROOF FLOOR. USE PREFABRICATED ALUMINUM
AND THE OWNER OF THEIR REPRESENTATIVE. REQUIREMENTS OF APPLICABLE CODES. ALL SUPPORT MUST BE FROM BUILDING STRUCTURE AND
OR PVC FLASHINGS FOR ROOF, AND MEMBRANE OR COPPER FOR WALLS AND FLOORS. ENSURE ALL
OPENINGS ARE WEATHER, WATER AND FIRE PROOF, USING AN APPROVED FLEXIBLE SEALANT. DUCTWORK AND HANGERS SHALL BE FABRICATED IN ACCORDANCE WITH THE LATEST SMACNA NOT FROM OTHER EQUIPMENT, PIPING OR DUCTWORK.
STANDARDS AS A MINIMUM. MEET THE REQUIREMENTS AND RECOMMENDATIONS OF ALL MUNICIPAL, PROVINCIAL AND FEDERAL
BYLAWS AND ORDINANCES. PIPING INSTALLATION
SHOP DRAWINGS SHALL BE COMPLETE WITH CONTRACTORS REVIEWED STAMP. SUBMIT 6 COPIES.
ALLOW ONE (1) WEEK FOR ENGINEERS REVIEW. FLEXIBLE DUCTWORK SHALL BE FLEXMASTER TRIPLE LOC OR EQUAL INSULATED, SPIRAL WOUND EXECUTE THIS WORK IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING CODES AND PROVIDE AND INSTALL ALL PIPING AS REQUIRED FOR A COMPLETE INSTALLATION WHETHER
ALUMINUM. SECURE TO RIGID DUCT USING GEAR CLAMPS. AT THE INLET OF EACH VAV TERMINAL STANDARDS. INDICATED OR NOT AND IN ACCORDANCE WITH RELEVANT CODES.
EQUIPMENT SUBSTITUTIONS AFTER AWARD OF CONTRACT WILL NOT BE CONSIDERED WITHOUT CONTROL UNIT, PROVIDE A MINIMUM OF 3 DIAMETERS OF STRAIGHT FLEX DUCT. MAXIMUM LENGTH CAN/CSA-S350-M1980 - CODE OF PRACTICE FOR SAFETY IN DEMOLITION OF STRUCTURES.
WRITTEN EXPLANATION AND CONSULTANT'S WRITTEN AUTHORIZATION. THE QUALITY AND 1200 MM [4 FT.-0 IN.]. FLEXIBLE DUCTS SERVING DIFFUSERS SHALL BE INSTALLED AS ONE ONTARIO BUILDING CODE. CONFORM TO MANUFACTURER'S RECOMMENDATIONS.
PERFORMANCE CHARACTERISTICS OF SUBSTITUTED PRODUCT SHALL BE EQUIVALENT TO THE CONTINUOUS PIECE AND SHALL NOT EXCEED 10'-0" LENGTHS. OCCUPATIONAL HEALTH AND SAFETY ACT.
SPECIFIED PRODUCT. ALL SUBSTITUTE PRODUCTS SHALL BE APPROVED BY CONSULTANTS. ANY REGULATIONS FOR CONSTRUCTION PROJECTS. PROVIDE AND INSTALL VENT PIPING AS PER LOCAL CODE REQUIREMENTS.
ADDITIONAL COSTS INCURRED BY ALL TRADES FOR SUBSTITUTED EQUIPMENT INSTALLATION MUST FIRE DAMPER SHALL BE OUT OF STREAM ULC LABELED. PROVIDE FIRE DAMPERS AS REQUIRED IN ONTARIO FIRE CODE.
BE INCURRED BY THIS CONTRACT. NEW AND EXISTING DUCTWORK C/W ACCESS DOORS. PROVIDE FIRE DAMPERS AND FIRE FLAPS REGULATIONS UNDER FIRE MARSHALS ACT. FOR UNDERGROUND INSTALLATIONS, PROVIDE SUITABLE BEDDING, COVERAGE AND SLOPE TO
WHERE REQUIRED BY LOCAL AUTHORITY AND CODES. RATE FIRE DAMPERS TO MATCH THE RATING EASE DRAINAGE.
CONTROL WIRING AND DEVICES SHALL BE PROVIDED UNDER THIS CONTRACT. CONTROL WORK OF THE SEPARATION CROSSED. PROVIDE ONLY ULC LABELED DAMPERS, INSTALL AS SPECIFIED IN REMOVAL FROM SITE AND DISPOSAL OF DEBRIS SHALL BE CARRIED OUT IN ACCORDANCE WITH THE
SHALL BE COMPLETED BY OWNER'S/LANDLORD'S APPROVED CONTRACTOR AND PAID FOR UNDER NFPA/CUA 90A. PROVIDE ACCESS DOORS AS REQUIRED. REQUIREMENTS OF THE LOCAL JURISDICTIONAL AUTHORITIES. INSTALL TEMPORARY CAPS OR CLOSURES ON THE END OF ALL PIPES, CONDUITS ETC.; TO PREVENT
THIS CONTRACT. DEBRIS ENTERING DURING CONSTRUCTION.
.1 PROVIDE CURTAIN OR PARALLEL BLADE TYPE DAMPERS TO MAINTAIN FIRE RATING INTEGRITY ARRANGE AND PAY FOR ALL PERMITS, NOTICES AND INSPECTIONS NECESSARY FOR THE PROPER
PROVIDE A COMPLETE AND FULLY FUNCTIONING SYSTEM OPERATING IN ACCORDANCE WITH THE OF MEMBRANE BEING PIERCED. MINIMUM RATING TO BE 1-1/2 HOURS WITH {100OC} [212OF] FUSIBLE EXECUTION AND COMPLETION OF THE DEMOLITION WORK. SEPARATE DISSIMILAR METALS BY MEANS OF GASKETS, DI-ELECTRIC UNIONS OR COUPLINGS THAT
SEQUENCE OF OPERATIONS. LINK. PROVIDE MULTIPLE DAMPERS WHERE SIZES EXCEED CODE LIMITATION. PREVENT ELECTROLYTIC ACTION. (E.G. BRASS BETWEEN COPPER AND STEEL).
ALL MATERIALS WHICH HAVE NOT BEEN DESIGNATED FOR SALVAGE FROM THE DEMOLITION SHALL
ALL LOAD SIDE WIRING AND ELECTRICAL DEVICES SHALL BE PROVIDED INCLUDING WIRING, .2 PROVIDE FIRE DAMPERS EQUIVALENT TO THE FOLLOWING RUSKIN MODELS AS FOLLOWS, TO BECOME THE PROPERTY OF THE CONTRACTOR. REMOVE ALL MATERIAL AND DEBRIS FROM THE SUSPEND ALL PIPES, IN THE CEILING SPACE, AS HIGH AS POSSIBLE. COORDINATE ALL WORK WITH
STARTERS, DISCONNECTS, VFD'S ETC. VERIFY AND COORDINATE VOLTAGE AND PHASE WITH THE SUIT APPLICATION: SITE AS QUICKLY AS POSSIBLE AND DISPOSE OF LEGALLY. BURNING OF DEBRIS OR SELLING OF OTHER SUB-TRADES SO AS NOT TO INTERFERE WITH DUCTWORK, ETC. SUPPORT ALL SUSPENDED
ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT. MATERIALS ON THE SITE WILL NOT BE PERMITTED. HUB DRAINS FROM BELOW.
MODEL NO. APPLICATION
ACCESS DOORS SHALL BE PROVIDED FOR ALL INACCESSIBLE MECHANICAL EQUIPMENT AND CONFORM TO REQUIREMENTS OF MUNICIPALITY'S WORKS DEPARTMENT REGARDING DISPOSAL OF SLOPE HOT WATER, COLD WATER & RECIRCULATION PIPING TO LOW POINTS FOR DRAINAGE OF THE
SERVICES REQUIRING INSPECTION OR SERVICE. FINISH SHALL SUIT ARCHITECT/DESIGNERS DIBD-2, STYLE B OR C NORMAL DUCT APPLICATION (2 HRS.) WASTE MATERIALS. SYSTEM C/W DRAIN VALVES.
REQUIREMENTS. ACCESS DOORS SHALL BE RECESSED AS REQUIRED TO SUIT WALL FINISH (EG.
TILE.). PROVIDE FIRE RATED ACCESS DOORS IN FIRE RATED PARTITIONS. DIBD-20 STYLE G BEHIND GRILLES (2 HRS.) MATERIALS PROHIBITED FROM MUNICIPALITY WASTE MANAGEMENT FACILITIES SHALL BE REMOVED PROVIDE ACCESSIBLE SHUT-OFF VALVES ON HOT AND COLD WATER SUPPLIES TO EACH PIECE OF
FROM SITE AND DISPOSED OF THROUGH RECYCLING COMPANIES SPECIALIZING IN RECYCLABLE EQUIPMENT, INCLUDING KITCHEN EQUIPMENT. (PROVIDE BACK FLOW PREVENTOR ON ALL
ARCHITECT/DESIGNER APPROVAL OF AIR TERMINAL, THERMOSTAT, AND ACCESS DOOR LOCATIONS IBDT IN DOORS (2 HRS.) MATERIALS. EQUIPMENT AS STATED ON EQUIPMENT SCHEDULE.)
MUST BE OBTAINED PRIOR TO INSTALLATION.
DIBD-23 IN FIRE WALLS (4 HRS.) AT THE END OF EACH WORK SHIFT, LEAVE WORK IN A SAFE CONDITION. INSERTS AND SLEEVES
ONE YEAR WRITTEN WARRANTY SHALL BE PROVIDED FOR THE COMPLETE MECHANICAL
INSTALLATION FROM DATE OF ACCEPTANCE. FSF BEHIND OUTLETS IN FIRE RATED FLOOR (ROOF) AND CEILING ASSEMBLIES PATCH FIRE RATED PARTITIONS AND FLOORS TO MAINTAIN RATING UPON REMOVAL OF PIPE SLEEVES PASSING THROUGH WALLS, FLOORS AND CEILINGS TO BE SCHEDULE 40, BLACK
MECHANICAL SERVICES ORIGINALLY SPANNING FIRE RATED ASSEMBLIES. STEEL, PACKED FOR WATER TIGHTNESS AND SOUND TRANSMISSION WITH FIREPROOF, SMOKE
CAD AS-BUILT DRAWINGS SHALL BE COMPLETED UTILIZING AUTOCAD. RECORD ACCURATELY DFD-35 COMBINATION FIRE AND BALANCING DAMPER (2 HRS.) PROOF, FLEXIBLE SEALANT. INSTALL POLISHED CHROME ESCUTCHEON PLATES ON ALL PIPES,
INSTALLED WORK ON WHITE PRINTS TRANSFERRING TO AUTOCAD. SUBMIT BOTH COPIES. KEEP ONE DEMOLISH WORK INTO SECTIONS OF PRACTICAL SIZE FOR REMOVAL WITHOUT ALTERATION OR WHICH ARE VISIBLE TO STAFF OR PUBLIC PERSONAL.
UP TO DATE SET ON SITE. .3 SELECT DAMPERS WITH AIR FLOW RESISTANCE NOT EXCEEDING {13 PA} [0.05 IN. W.G.] AT DAMAGE TO EXISTING BUILDING.
DESIGN FLOW RATES.
OPERATING AND MAINTENANCE MANUALS CONTAINING APPROVED SHOP DRAWINGS, AIR AND STORE MATERIALS ONLY IN AREAS DESIGNATED BY THE OWNER AND AS PERMITTED BY THE LOCAL
WATER BALANCING REPORTS, EQUIPMENT DATA SHEETS, WRITTEN WARRANTY, OPERATING FLEXIBLE DUCT CONNECTIONS SHALL BE DURODYNE NEOPRENE AND INSTALLED BETWEEN ALL AIR JURISDICTIONAL AUTHORITIES.
INSTRUCTIONS AND MAINTENANCE PROCEDURES SHALL BE SUBMITTED TO CONSULTANT FOR HANDLING EQUIPMENT AND SYSTEM DUCTWORK.
REVIEW. MANUALS SHALL BE SEPARATED WITH DIVIDERS IN APPROPRIATE SECTIONS. MAKE ALL MATERIALS AND DEBRIS SHALL NOT BE STACKED IN BUILDING TO THE EXTENT THAT OVERLOADING
CORRECTIONS REQUESTED BY CONSULTANT AND RESUBMIT FOR REVIEW. AIR TRANSFER OPENINGS INDICATED WITHOUT DUCT SHALL BE THIS CONTRACTOR'S OF ANY PART OF THE STRUCTURE WILL OCCUR.
RESPONSIBILITY TO ADVISE AND CONFIRM PROVISION BY GENERAL TRADES.
CHANGE NOTICE QUOTATIONS SHALL BE SUBMITTED COMPLETE WITH COST BREAKDOWN OF CONFER WITH THE OWNER CONCERNING SCHEDULE, DUST AND NOISE CONTROL PRIOR TO
LABOUR AND MATERIALS. FAILURE TO PROVIDE WILL RESULT IN REJECTION. ALL MECHANICAL BALANCING AND VOLUME CONTROL DAMPERS SHALL BE PROVIDED IN NEW OR EXISTING COMMENCING WORK IN OR ADJACENT TO EXISTING FACILITIES WHERE SUCH WORK MIGHT AFFECT
CHANGE NOTICES SHALL BE PRICED IN ACCORDANCE WITH "MECHANICAL CONTRACTORS DUCTWORK TO PROVIDE A COMPLETE AND BALANCED SYSTEM. BALANCING CONTRACTOR SHALL BE EITHER THOSE FACILITIES OR THEIR OCCUPANTS.
ASSOCIATION" (MCA). LABOUR UNITS NOT MARKED UP TO REFLECT SITE CONDITIONS STRICTLY FOR A MEMBER OF AABC OR NEBC. SUBMIT BALANCING REPORT IN TRIPLICATE TO THE CONSULTANT
LABOUR AND FOR MATERIAL COST USE "ALL PRICER" LESS DISCOUNT OF 20%. AND THE LANDLORD INDICATING TERMINAL DESIGN AND MEASURED FLOW RATES. WHEN REQUIRED, EXECUTE WORK WITH LEAST POSSIBLE INTERFERENCE OR DISTURBANCE TO OCCUPANTS, PUBLIC
BALANCING WORK SHALL BE COMPLETED BY OWNER'S/LANDLORD'S APPROVED CONTRACTOR AND AND NORMAL USE OF PREMISES.
TEMPORARY FILTERS 25MM (1 IN.) SHALL BE PROVIDED AT ALL BASE BUILDING RETURN AIR PAID FOR UNDER THIS CONTRACT. PROVIDE SIX (6) ADDITIONAL HOURS OF BALANCING WORK. THIS
OPENINGS WHICH REMAIN OPERATIONAL DURING CONSTRUCTION. FILTERS TO BE REPLACED WORK SHALL BE PERFORMED AFTER THE TENANT HAS MOVED IN, AS MAY BE REQUIRED FOR PROVIDE TEMPORARY MEANS TO MAINTAIN SECURITY WHEN SECURITY HAS BEEN REDUCED BY
WEEKLY. REMOVE UPON CONSTRUCTION COMPLETION. COMFORT BALANCING. DIVISION 15.
BASE BUILDING HVAC COMPONENTS REMOVED I.E. LIGHT TROFFERS, DIFFUSERS, VAV BOXES ETC. PROVIDE NEW SHEAVES, BELT AND ALL LABOUR REQUIRED TO BALANCE ALL AIR HANDLERS, ONLY ELEVATORS, DUMBWAITERS, CONVEYORS OR ESCALATORS ASSIGNED FOR CONTRACTOR'S
SHALL BE TURNED OVER TO THE LANDLORD/OWNER AT THEIR DIRECTIONS. ROOFTOP UNITS, FANS AS REQUIRED TO MEET SPECIFIED AIR FLOW. USE MAY BE USED FOR MOVING MEN AND MATERIAL WITHIN BUILDING. PROTECT WALLS OF
PASSENGER ELEVATORS, TO APPROVAL OF OWNER PRIOR TO USE. ACCEPT LIABILITY FOR
COMPLY WITH THE GENERAL CONTRACTORS CONSTRUCTION SCHEDULE. ALL KITCHEN RELATED EXHAUST DUCTWORK TO BE 16 GAUGE ALL WELDED BLACK CARBON STEEL, DAMAGE, SAFETY OF EQUIPMENT AND OVERLOADING OF EXISTING EQUIPMENT.
OR 18 GAUGE STAINLESS STEEL. TO CONFORM TO NFPA 96. (GALVANIZED NOT ACCEPTABLE).
CLEAN UP PROVIDE TEMPORARY DUST SCREENS, BARRIERS, WARNING SIGNS IN LOCATIONS WHERE
FIREPROOFING OF KITCHEN EXHAUST DUCTWORK WHERE REQUIRED SHALL BE BY DIVISION 15. RENOVATIONS AND ALTERNATION WORK IS ADJACENT TO AREAS WHICH WILL BE OPERATIVE
DURING THE PROCESS OF THE WORK EACH CONTRACTOR SHALL KEEP HIS WORK TIDY. THE VERIFY WITH LOCAL AUTHORITIES PRIOR TO STARTING ANY WORK. DURING WORK.
PREMISES SHALL AT ALL TIMES BE FREE FROM RUBBISH AND SURPLUS MATERIALS, CLEAN DAILY.
PROTECTING-TRADES
FAN SHEAVES, BELTS AND PULLEYS SHALL BE ADJUSTED OR REPLACED AS REQUIRED TO OBTAIN
DESIGN AIR QUANTITIES. COORDINATE THIS WORK WITH OWNER/LANDLORD.
PROTECT ALL MECHANICAL SYSTEMS, INDICATED TO REMAIN, FROM DAMAGE. RENOVATION
DIVISION 15 IS ENTIRELY FINANCIALLY RESPONSIBLE FOR ALL DAMAGE TO PROPERTY OR ADJACENT All new dampers must be Tamco series 9000 or equal.
PROVIDE AND MAINTAIN READY ACCESS TO FIRE FIGHTING EQUIPMENT AT ALL TIMES.
FOR EXISTING
PROPERTY, ARISING OF THE WORK OF THIS CONTRACTOR, WHETHER CAUSED BY HIMSELF OR ANY PROVIDE AND MAINTAIN PROPER AND SUITABLE FIRE EXTINGUISHERS THROUGHOUT THE DURATION
PERSONS ENGAGED ON HIS WORK. OF THE WORK. CULTURAL
DIVISION 15 CONTRACTORS ARE RESPONSIBLE TO ENSURE THAT THEIR EMPLOYEES AND
SUB-TRADES USE ONLY SAFE PRACTICES AND CONDITIONS, OBSERVE ALL SAFETY REGULATIONS, CENTER
SECURITY REGULATIONS AND FIRE SAFETY RULES.
MECHANICAL
SPECIFICATION
SCALE: SEE NOTE
DRAWN:GC
CHECKED:GC
APPROVED:
PROJECT NO:160603
DWG. NO.
M6
HANGERS AND SUPPORTS PROVIDE THE FOLLOWING DUCTWORK INSULATION TYPE AS INDICATED IN THE DUCTWORK 1. SUBMIT A CERTIFICATE TO PROVE THAT ALL EQUIPMENT ARE CLEANED, LUBRICATED AND - DO NOT SCALE DRAWINGS.
ENSURE BY OPERATION OF ISOLATING VALVES OR THE INSTALLATION OF CHECK VALVES, THAT THE INSULATION TABLE BELOW. TESTED. ALL GAUGES AND INSTRUMENTS MUST BE CALIBRATED PRIOR TO START-UP. - CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
SUPPORTS AND CLEVIS TYPE HANGERS SHALL BE ON OUTSIDE OF INSULATION, INSTALLATION DISINFECTING SOLUTION AGAINST SPECIFICATIONS AND REPORT ANY
DOES NOT FLOW BACK INTO STREET MAINS OR OTHER SECTIONS OF PIPING IN USE. DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
SHALL BE TO THE REQUIREMENTS OF APPLICABLE CODES. ALL SUPPORT MUST BE FROM BUILDING 'TYPE D1' OWENS CORNING RIGID VAPOUR SEAL DUCT INSULATION, JOHN MANSVILLE 814 2. ALL PIPING MUST BE PRESSURE TESTED TO 150% OF DESIGN CONDITIONS. PROVIDE A
STRUCTURE AND NOT FROM OTHER EQUIPMENT, PIPING OR DUCTWORK. - CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
SPIN-GLAS WITH FSK FACING, MANSON SPIN-GLAS RIGID INSULATING BOARD WITH REINFORCED CERTIFICATE TO THE ENGINEER. THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
ARRANGE AND PAY FOR WATER QUALITY TESTS TO BE PERFORMED BY A RECOGNIZED FOIL FACING, OR KNAUF RIGID INSULATION BOARD WITH FSK FACING. DENSITY SHALL BE NOT LESS SCOPE OF WORK.
EXISTING SANITARY DRAIN LOCATIONS AND INVERT ELEVATIONS SHALL BE VERIFIED ON SITE PRIOR INDEPENDENT TESTING LABORATORY. THAN 3LBS./CU.FT. IMPALE ON MECHANICALLY FASTENED PINS LOCATED AT NOT GREATER THAN 3. THE AIR BALANCING SUBCONTRACTOR MUST BE APPROVED BY THE ENGINEER PRIOR TO THE - USE ONLY THE LATEST DRAWINGS.
TO COMMENCEMENT OF WORK. OBTAIN CERTIFICATES CONFIRMING SAFETY OF POTABLE WATER SUPPLY. 12" CENTERS. SECURE WITH SPEED WASHERS. BUTT JOINTS TIGHTLY TOGETHER AND SEAL ACTUAL WORK BEING DONE. CORRECT ALL DEFICIENCIES NOTED BY THE BALANCING - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WASHERS, BREAKS AND JOINTS WITH SELF-ADHERING 4" WIDE PLAIN ALUMINUM TAPE, OR ADHERE CONTRACTOR. WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
PIPING MATERIALS: PLUMBING FIXTURES INCLUDING DOMESTIC HOT WATER HEATERS SHALL BE NEW, OF FIRST FIRE PROTECTION PLANS UNLESS THEY ARE NOT
FOIL WITH CHILDERS CP82 OR BAKELITE 230-39 ADHESIVE. PRODUCED.
QUALITY, IN PERFECT CONDITION AND INSTALLED IN BEST WORKMANLIKE MANNER. VERIFY 4. ALL NEW OR RE-USED, RE-INSTALLED EQUIPMENT MUST BE CLEANED, LUBRICATED, AND
TYPE PIPE SIZE {65MM} [2-1/2"] & SMALLER PIPE SIZE {75MM} [3"] & LARGER PLUMBING FIXTURE QUANTITIES AND LOCATIONS WITH ARCHITECT'S/DESIGNER'S DRAWINGS. 'TYPE D2' OWENS CORNING FLEXIBLE DUCT INSULATION, JOHNS MANVILLE MICROLITE TYPE 75 DUCT TESTED. THIS WORK IS TO BE DONE BY A QUALIFIED AND CERTIFIED TECHNICIAN. PROVIDE A
REUSE OF DOMESTIC WATER HEATER IS NOT PERMITTED. WRAP, MANSON MICROLITE INSULATION OR KRAFT DUCT WRAP, (3/4LB./CU.FT.) DENSITY WITH CERTIFICATE TO THE ENGINEER STATING COMPLETION OF THIS WORK.
SANITARY - DWV COPPER PIPE WITH DRAINAGE FITTINGS CSA CLASS 4000 CAST IRON SOIL FACTORY APPLIED REINFORCED FOIL FACING. ADHERE INSULATION TO DUCT SURFACE WITH
TRAP SEAL PRIMER MUST BE PROVIDED ON ALL NEW FLOOR DRAINS, FUNNEL FLOOR DRAINS AND NO. ISSUE DATE
PIPE AND CHILDERS CP82 OR BAKELITE 230-39 ADHESIVE, WHICH SHALL BE APPLIED IN STRIPS 6" WIDE AT NOT
ABOVE GROUND AND 95/5 TIN/ANTIMONY SOLDER JOINTS. FITTINGS, WITH MECHANICAL HUB DRAINS. 1. ISSUED FOR REVIEW 08AUG.17
GREATER THAN 12" CENTERS. BUTT EDGES OF INSULATION TIGHTLY TOGETHER, AND SEAL BREAKS
JOINTS. AND JOINTS OF FACING WITH SELF-ADHERING 4" WIDE ALUMINUM TAPE OR ADHERE FOIL WITH 2. ISSUED FOR REVIEW 14SEPT.17
EXPOSED PIPING AND FITTINGS WITHIN WASHROOMS SHALL BE CHROME PLATED. PROVIDE
CHILDER CP82 OR BAKELITE 230-39 ADHESIVE. 3. ISSUED FOR REVIEW 29SEPT.17
SANITARY - PROFILE PVC SEWER PIPE WITH SOLVENT CSA CLASS 4000 CAST IRON SOIL CHROME PLATED ESCUTCHEONS ON ALL PIPING PASSING THROUGH FINISHED SURFACES AND
MILLWORK. 4. ISSUED FOR REVIEW 4 OCT.17
PIPE AND BELOW GROUND WELDED FITTINGS DUTY INSULATION THICKNESS VAPOUR NOTES
FITTINGS, WITH MECHANICAL JOINTS OR IPEX RING-TITE 5. ISSUED FOR REVIEW 10 OCT.17
TYPE BARRIER 6. ISSUED FOR TENDER 11 OCT.17
SDR35, CSA CERTIFIED TO B182.2 PVC STAINLESS STEEL WATER HAMMER ARRESTORS EQUAL TO ZURN SHOKTROL SHALL BE PROVIDED
GASKETTED SEWER PIPE. ON ALL LINES SERVING GROUPS OF FIXTURES, QUICK CLOSING VALVES AND FLUSH VALVES. PANELS BEHIND UNUSED
PORTION OF LOUVERS D-1 2" YES
INSULATION
VENT PIPING - DWV COPPER PIPE WITH DRAINAGE FITTINGS, CSA CLASS 4000 CAST IRON SOIL FINAL 10' OF EXHAUST DUCT
PIPE AND ABOVE GROUND 95/5 TIN /ANTIMONY SOLDER JOINTS. PIPING INSULATION BEFORE EXITING BUILDING D-1 1" YES
FITTINGS WITH MECHANICAL JOINTS.
IPEX RING-TITE SDR35, CSA PROVIDE ALL LABOUR, MATERIALS, PRODUCTS, EQUIPMENT AND SERVICES TO SUPPLY AND INSTALL EXPOSED DUCTWORK D-1 1" YES IN THE CONDITIONED
CERTIFIED THERMAL INSULATION, VAPOUR BARRIERS AND FINISHES FOR MECHANICAL WORK AS INDICATED ON SPACE
TO B182.2 PVC GASKETTED THE DRAWINGS AND SPECIFIED IN THIS SECTION OF THESE SPECIFICATIONS. ONLY WHERE INDICATED
SEWER PIPE. ALUMINUM BANDS - SEAL
MAINTAIN AMBIENT TEMPERATURES AND CONDITIONS REQUIRED BY MANUFACTURERS OF WATERTIGHT.
DOMESTIC WATER: ADHESIVES, MASTICS AND INSULATING CEMENTS.
SUPPLY DUCTWORK D-2 2" YES
DOMESTIC HOT WATER AND RECIRCULATION - ALL SIZES: INSULATION MATERIALS MUST BE MANUFACTURED AT FACILITIES CERTIFIED AND REGISTERED WITH
.1 TYPE L HARD COPPER PIPE, WROUGHT COPPER FITTINGS WITH 95/5 TIN/ANTIMONY SOLDER AN APPROVED REGISTRAR TO CONFORM TO ISO 9000 QUALITY STANDARD.
JOINTS. PROTECT THE WORK OF THIS TRADE FROM BEING DEFACED BY OTHER TRADES. MAKE GOOD ANY
ALL INSULATION PERTAINING TO DIVISION 15 SHALL BE CARRIED OUT BY ONE FIRM SPECIALIZING IN DAMAGE AND LEAVE IN PERFECT CONDITION, READY FOR FINAL PAINTING.
DOMESTIC COLD WATER AND DOMESTIC CHILLED WATER ALL SIZES. INSULATION WORK. DO NOT MIX SIMILAR PRODUCTS OF MULTIPLE MANUFACTURERS.
.1 TYPE L HARD COPPER PIPE, WROUGHT COPPER FITTINGS WITH 95/5 TIN/ANTIMONY SOLDER APPLY INSULATION OVER CLEAN DRY SURFACES, firmly butting all sections together.
JOINTS. ACCEPTABLE INSULATION MANUFACTURERS ARE OWENS CORNING CANADA, JOHNS MANVILLE,
MANSON INSULATION INC. KNAUF FIBER GLASS AND CERTAINTEED. ACOUSTIC DUCT LINING
PROVIDE TYPE K SOFT COPPER PIPE WITHOUT JOINTS BELOW GROUND.
PROVIDE INSULATION AND COVERS IN STRICT ACCORDANCE WITH AUTHORITIES GOVERNING PROVIDE {25 MM} [1"] THICK ACOUSTIC DUCT LINER WHERE SHOWN ON DRAWINGS AND AS
VALVES COMBUSTIBILITY AND FIREPROOFING OF MATERIALS AND IN ACCORDANCE WITH MANUFACTURER'S FOLLOWS:
RECOMMENDATIONS.
PROVIDE ASTM DOMESTIC WATER VALVES TO THE FOLLOWING KITZ FIGURE NUMBERS: RECTANGULAR DUCT LINER: PERMACOTE LINACOUSTIC MEETING ASTM C 1071 WITH AIR SURFACE
PROVIDE NON-COMBUSTIBLE INSULATION, JACKETS AND FINISHES HAVING A FLAME SPREAD/SMOKE COATED WITH ACRYLIC
GATE VALVES: DEVELOPED RATING OF 25/50 OR LESS, MEETING CAN/ULC S-102 REQUIREMENTS. COATING TREATED WITH EPA REGISTERED ANTI-MICROBIAL AGENT PROVEN TO RESIST MICROBIAL
GROWTH AS DETERMINED BY
.1 {50 MM} [2"] AND SMALLER - SOLDERED {1400 KPA} [200 PSI] W.O.G. FIG. 44. ATTAIN A COMPLETE AND CONTINUOUS VAPOUR BARRIER OVER INSULATION APPLIED TO COLD AND ASTM G 21 AND G 22.
DUAL TEMPERATURE PIPING, SHEET METAL AND EQUIPMENT. USE EITHER FACTORY APPLIED
.2 {65 MM} [2-1/2"] AND LARGER - FLANGED {1400 KPA} [200 PSI] W.O.G. FIG. 75. VAPOUR BARRIER JACKET OF FIELD APPLIED REINFORCED FOIL FLAME RESISTANT KRAFT VAPOUR .1 NOISE REDUCTION COEFFICIENT : 70 OR HIGHER BASED ON "TYPE A MOUNTING" AND TESTED IN
BARRIER JACKET. APPLY TO PIPING,FITTINGS, VALVES AND INLINE COMPONENTS, SHEET METAL ACCORDANCE TO
GLOBE VALVES: AND FITTINGS AND EQUIPMENT. SEAL LONGITUDINAL AND CIRCUMFERENTIAL LAPS WITH CHILDERS ASTM C 423.
CP82 OR BAKOR 230-39 ADHESIVE. IF VAPOUR BARRIER JACKET IS NOT LAPPED, SEAL JOINTS WITH
.1 {50 MM} [2"] AND SMALLER - SOLDERED {2070 KPA} [300 PSI] W.O.G. FIG. 10 WITH SUITABLE SELF-ADHERING 4" WIDE PLAIN ALUMINUM FOIL TAPE, OR ADHERE 4" WIDE ALUMINUM FOIL TAPE .2 ADHESIVE: MEETING ASTM C 916.
COMPOSITION DISC. WITH CHILDERS CP82 OR BAKOR 230-39 ADHESIVE. JACKETING WITH SELF-ADHESIVE LAPS AND
SELF-ADHESIVE BARRIER TAPE WILL BE AN ACCEPTABLE ALTERNATIVE CLOSURE SYSTEM. .3 FASTENERS: DUCT LINER GALVANIZED STEEL PINS, WELDED OR MECHANICALLY FASTENED.
.2 {65 MM} [2-1/2"] AND LARGER - FLANGED {1400 KPA} [200 PSI] W.O.G. FIG. 76.
PROVIDE INSULATION MATERIALS WITH A MINIMUM THERMAL CONDUCTIVITY OF 0.24BTU.IN/(HR. ROUND DUCT LINER: PERMACOTE SPIRACOUSTIC, RIGID PREFORMED ROUND LINER, OR
STANDARD CHECK VALVES: SPIRACOUSTIC PLUS WITH AIR SURFACE COATED WITH ACRYLIC COATING TREATED WITH EPA
REGISTER ANTI-MICROBIAL AGENT PROVEN TO RESIST MICROBIAL GROWTH AS DETERMINED BY LEGEND - MECHANICAL
.1 {50 MM} [2"] AND SMALLER - SOLDERED {2070 KPA} [300 PSI] W.O.G. FIG. 23. ON HOT PIPING APPLICATIONS, HOLD INSULATION IN PLACE WITH FLARE TYPE STAPLES (OUTWARD ASTM G 21 AND G 22.
CLINCH).
.2 {65 MM} [2-1/2"] AND LARGER - FLANGED {1400 KPA} [200 PSI] W.O.G. FIG. 78. NOISE REDUCTION COEFFICIENT OF .70 AS PER ASTM C 423. (TYPE A MOUNTING)
ON COLD PIPING APPLICATIONS, APPLY VAPOUR BARRIER JACKET OVER INSULATION AND SEAL EXISTING SANITARY DRAIN
VERIFICATION OF INVERTS CONTROLS
LONGITUDINAL AND CIRCUMFERENTIAL LAPS WITH CHILDERS CP82 OR BAKELITE 230-39 ADHESIVE.
XSAN EXISTING BURIED SANITARY DRAIN
SEAL ALL PIPE TERMINATIONS, INCLUDING FITTINGS, WALL PENETRATIONS AND PIPE SUPPORTS
.1 VERIFY ALL FIELD SERVICE CONDITIONS (PIPE SIZE, DIRECTION OF FLOW) IMMEDIATELY AFTER NEW THERMOSTATS SHALL MATCH BASE BUILDING.
WITH VAPOUR BARRIER MASTIC. FOR CHILLED WATER SYSTEMS PROVIDE VAPOUR SEAL PIPE EXISTING ROOF DRAIN
AWARD OF CONTRACT TO TERMINATIONS EVERY FOUR PIPE SECTIONS.
ENSURE THAT DRAINAGE RUNS CAN MEET THE INVERTS OF THE SITE SERVICES. MOUNTING HEIGHT SHALL BE 1200 MM FROM FINISHED FLOOR. COORDINATE LOCATION WITH XSTM EXISTING BURIED STORM DRAIN
ARCHITECT/DESIGNER. DO NOT INSTALL IN VICINITY OF ELECTRICAL LIGHTING DIMMERS.
PROVIDE ON ALL BARRIER FREE LAVATORY APPLICATIONS, A SEAMLESS P-TRAP INSULATION KIT
.2 GIVE NOTIFICATION IMMEDIATELY OF ANY APPARENT DIFFICULTIES OR DISCREPANCIES. FURNISHED WITH SEAMLESS RISER TUBE COVERS, SUPPLY ANGLE STOP COVERS, SEAMLESS DRAIN EXISTING VENT PIPE
PROVIDE ALL NECESSARY EMT CONDUIT, FITTINGS AND WIRE TO PROVIDE A COMPLETE AND
TAILPIECE COVER AND ANGLE STOP WHEEL HANDLE COVERS. EXISTING DRAIN WITH CLEANOUT
.3 NO EXTRA WILL BE PAID AT A LATER DATE FOR REROUTING OF DRAINS BECAUSE SITE INVERTS OPERATING CONTROL SYSTEM. HARD WIRE ALL ELECTRICAL CONTROL DEVICES INTO THE
CANNOT BE MET. ASSOCIATED SYSTEM MAGNETIC STARTER. PROVIDE POWER TO CONTROL PANEL FROM THE
APPLY PIPE INSULATION OVER 1-1/2" THICKNESS IN TWO LAYERS WITH JOINTS STAGGERED. EXISTING DOMESTIC COLD WATER
NEAREST NORMAL POWER ELECTRICAL DISTRIBUTION PANEL.
TESTING INSULATE FITTINGS WITH FABRICATED MITERED OR PREFORMED SECTIONS OF SPECIFIED EXISTING DOMESTIC HOT WATER
THERMOSTAT CONTROL WIRING
INSULATION.
CARRY OUT NOT LESS THAN THE FOLLOWING TESTS: EXISTING GAS PIPE
ALL THERMOSTAT/CONTROL WIRING IS TO BE 18AWG SHIELDED PLENUM RATED FT6 MINIMUM.
INSULATE OVER FLANGES AND MECHANICAL COUPLINGS WITH SPECIFIED INSULATION AND PIPES & EQUIPMENT TO BE REMOVED
.1 BALL TEST DRAINS. THICKNESS, SIZED TO SUIT FLANGE DIAMETERS. FILL SPACES BETWEEN INSULATION AND
A. SUPPORT ALL WIRING IN CEILING PLENUM USING WIRE TIES / BRIDLE RINGS.
ADJOINING PIPE INSULATION WITH SIMILAR MATERIAL. EXISTING FLOOR DRAIN OR ROOF DRAIN
.2 PERFORM WATER TESTS ON ALL SOIL, WASTE, VENT AND RAINWATER SYSTEMS WHEN
ROUGH-IN OF THE SYSTEM, OR SECTION THEREOF INCLUDING FITTINGS, BRANCHES, CLEANOUTS B. MECHANICAL CONTRACTOR IS TO WIRE AND INSTALL THERMOSTATS AND CONTROL WIRING TO EXISTING GATE VALVE
INSULATE VALVES AND INLINE COMPONENTS WITH FLEXIBLE INSULATION DENSITY (3/4 LBS./CU.FT.)
AND TRAPS EXCEPT FIXTURE TRAPS IS COMPLETED. WHEN THE SYSTEM OR SECTION IS FILLED, EACH MECHANICAL UNIT SHOWN ON HVAC PLAN.
COMPRESSED NOT MORE THAN 50% OF ORIGINAL THICKNESS. BUILD UP TO SPECIFIED THICKNESS
SANITARY DRAIN
SHUT OFF THE WATER, AND ALLOW TO STAND FOR ONE HOUR. THERE SHALL BE NO LOSS BY WITH APPROVED ASBESTOS FREE FINISHING CEMENT.
LEAKAGE DURING THIS TIME. TESTING
SAN BURIED SANITARY DRAIN
DO NOT INSULATE TERMINAL UNIT AUTOMATIC CONTROL VALVES INSTALLED IN HOT PIPING. DO
.3 PRESSURE TEST DOMESTIC COLD WATER, DOMESTIC HOT WATER, AND RECIRCULATION ALL EQUIPMENT SHALL BE CHECKED, ADJUSTED AND STARTED TO THE MANUFACTURER'S
NOT INSULATE TERMINAL UNIT AUTOMATIC CONTROL VALVES WHICH ARE INSTALLED IN COLD V EXISTING VENT PIPE
LINES WITH WATER AT 150% OF MAXIMUM OPERATING PRESSURE, FOR 6 HOURS WITHOUT LOSS OF RECOMMENDATIONS, UNDER HIS SUPERVISION.
PIPING AND WHICH ARE LOCATED OVER CONDENSATE DRAIN PANS.
PRESSURE. DRAIN WITH CLEANOUT
CONDUCT EQUIPMENT TESTS TO DEMONSTRATE PERFORMANCE AS SOON AS CONDITIONS PERMIT.
UNDER ALL HANGERS USED ON CHILLED WATER AND DOMESTIC COLD WATER, PROVIDE AN INSERT
O
MAKE ADJUSTMENT TO SUIT. DRAIN WITH CLEANOUT UP TO FLOOR
C
CONDUCT ADDITIONAL TESTS REQUIRED BY THE AUTHORITIES HAVING JURISDICTION.
OPERATE EQUIPMENT FOR ONE WEEK MINIMUM PERIOD AND REPAIR ANY BREAKDOWNS. REPLACE DOMESTIC COLD WATER (DCW)
IF TESTS ARE REQUIRED BY AN AUTHORITY HAVING JURISDICTION, PERFORM TESTS IN THE PROVIDE THE FOLLOWING PIPE INSULATION TYPE AS INDICATED IN THE PIPE INSULATION TABLE
PRESENCE OF EACH GOVERNING AUTHORITY'S AUTHORIZED INSPECTOR, AND OBTAIN ALL FILTERS AND LUBRICATE EQUIPMENT AND ADJUST ALL MOVING PARTS TO MANUFACTURER'S
BELOW. DOMESTIC HOT WATER (DHW)
CERTIFICATION. RECOMMENDATIONS. CALIBRATE THERMOSTATS AND ADJUST AUTOMATIC CONTROLS AS DIRECTED.
ELIMINATE ALL VIBRATION AND REDUCE SOUND, WHETHER AIR BOURNE OR TRANSMITTED. DOMESTIC HOT WATER RETURN (DHR)
'TYPE P1' OWENS CORNING 850 PIPE INSULATION, JOHNS MANVILLE MICRO-LOK AP-T PLUS
CERTIFY TESTS NOT REQUIRED BY THE AUTHORITIES HAVING JURISDICTION. FIBERGLAS PIPE INSULATION, MANSON FIBERGLAS PIPE INSULATION OR KNAUF PIPE INSULATION NEW VENT PIPE
IT SHALL BE THE RESPONSIBILITY OF DIV. 15 TO TEST RUN AND COMMISSION ALL EQUIPMENT. DIV.
WITH FACTORY APPLIED ALL PURPOSE VAPOUR BARRIER JACKET WHERE SCHEDULED.
PERFORM TESTS BEFORE PIPING, DRAINS OR VENTS ARE COVERED OR CONCEALED. 15 SHALL HIRE AND PAY FOR THE EQUIPMENT MANUFACTURER'S REPRESENTATIVE TO START-UP
ALL EQUIPMENT AND CHECK OUT ALL ASSOCIATED CONTROLS AND SAFETY CUTOUTS, THIS
DUTY INSULATION THICKNESS VAPOUR
REMOVE ALL COMPONENTS WHICH WILL NOT WITHSTAND TEST PRESSURE, AND REPLACE AFTER INCLUDES THERMOSTATS, UNIT OUTSIDE AIR DAMPERS, FIRE STATS, EXHAUST FAN INTERLOCKS
TYPE BARRIER
TESTS. ETC. THIS WORK SHALL BE COMPLETE AND ANY DEFICIENCIES RECTIFIED PRIOR TO NOTIFYING THE LEGEND - MECHANICAL
BALANCING COMPANY THAT THE SYSTEMS ARE READY TO BE BALANCED.
DOMESTIC COLD WATER
ELIMINATE LEAKS, OR REMOVE AND REFIT DEFECTIVE PARTS. CAULKING OF THREADED OR 4" AND LESS P-1 1/2" YES
WELDED JOINTS WILL NOT BE PERMITTED. AIR BALANCING
1. ALL MODULATING DAMPER, VAV BOXES AND ZONE DAMPERS MUST BE SET TO PROVIDE
DOMESTIC HOT WATER DOUBLE LINE DUCT
REPEAT TESTS AS OFTEN AS NECESSARY TO OBTAIN CERTIFICATION. SPECIFIED MAXIMUM AIR FLOW. ALSO SET AT 25% FOR MINIMUM FLOW UNLESS OTHERWISE
CLEANING, FLUSHING AND DISINFECTING WATER PIPING 2" AND LESS P-1 1" NO
SET ALL FIXTURES AND FILL ALL TRAPS WITH WATER AFTER TESTS HAVE BEEN COMPLETED.
2-1/2" AND LARGER P-1 1-1/2" NO FD FIRE DAMPER
RENOVATION
BE RESPONSIBLE FOR CARE AND CLEANING OF THE PIPING SYSTEM DURING AND AFTER 2. THIS CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT THE EXISTING AREAS ARE NOT SD SPLIT DAMPER
CONSTRUCTION. PLUG ALL OPEN
ENDS DURING CONSTRUCTION TO PREVENT THE ENTRANCE OF FOREIGN MATERIALS.
HORIZONTAL STORM AND SANITARY DRAINAGE
ALL PIPE SIZES P-1 1" YES
AFFECTED BY NEW ADDITIONS.
MD MOTORIZED DAMPER
FOR EXISTING
FLUSH ALL SYSTEMS WITH CLEAN, POTABLE WATER TO REMOVE SCALE AND SEDIMENT HORIZONTAL CONDENSATE DRAINS
ALL PIPE SIZES P-1 1/2" YES
3. IF NECESSARY, PROVIDE A SECOND FOLLOW-UP BALANCING REPORT TO CORRECT ALL
DEFICIENCIES. MANUAL BALANCING DAMPER CULTURAL
IMMEDIATELY UPON FILLING. THERMOSTAT
11
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
4.
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
16
LED, INCANDESCENT, H.I.D. OR COMPACT FLUORESCENT LIGHT FIXTURE - WALL MOUNT FIRE PROTECTION PLANS UNLESS THEY ARE NOT
D30 D32 PRODUCED.
EXIT LIGHT FIXTURE - WALL / CEILING MOUNT - FILLED SIDE INDICATES FACE 1 1
SC-1
SC-1
H.2
BATTERY OPERATED REMOTE EMERGENCY LIGHT - WALL MOUNT - SINGLE / DOUBLE UNIT
120/208V
120/208V
347/600V
PP-H
PP-AV
PP-Y
SL
FA-1-13
FA-1-14
D33
ES SL
H.4
H.4
BATTERY OPERATED REMOTE EMERGENCY LIGHT - CEILING MOUNT - SINGLE / DOUBLE UNIT SL EM1 EM2 ES
110cd EM2 ES
BATTERY OPERATED EMERGENCY LIGHTING UNIT - WALL MOUNT / CEILING MOUNT 110cd H.1 EM2 110cd H.1 NO. ISSUE DATE
EM2
SC-1 ISSUED FOR REVIEW 08AUG.17
TRX.AV
FA LETTERS INDICATE LIGHT FIXTURE TYPE NEW TEMPORARY WALL TO BE 1.
INSTALLED DURING CONSTUCTION
SINGLE POLE SWITCH J H.17 2. ISSUED FOR REVIEW 14SEPT.17
FA-12 1A
3 4 D 3-WAY SWITCH, 4-WAY SWITCH, DIMMER SWITCH 3. ISSUED FOR REVIEW 29SEPT.17
PROJECTOR 4. ISSUED FOR REVIEW 4 OCT.17
MULTI GANG SWITCHES
BACKBOARD WINCH MOTOR
H.4 5. ISSUED FOR REVIEW 10 OCT.17
PANELBOARD - RECESSED / SURFACE CONFIRM EXACT POWER CONFIRM EXACT POWER 6. ISSUED FOR TENDER 11 OCT.17
REQUIREMENT AND SET UP REQUIREMENT AND R2
DUPLEX RECEPTACLE - WALL MOUNT / FLOOR MOUNT / CEILING MOUNT R2
WITH AV CONTRACTOR LOCATION PER
TELEPHONE OUTLET - WALL MOUNT / FLOOR MOUNT / CEILING MOUNT
ARCH DRAWING
EM2 EM2
DATA OUTLET - WALL MOUNT / FLOOR MOUNT / CEILING MOUNT 6
J J JUNCTION BOX - FLOOR MOUNT / CEILING MOUNT
ELECTRIC MOTOR R2
NEW BASE
SL EM2
71"x107"
WP
BASE 4
DISCONNECT SWITCH NEW LOCATION STATUE 3
2
R2 PREPARE EXISTING SLAB FOR NEW
DOOR PROXIMITY SWITCH EM1 110cd BOTTOM OF RTU-5 BASE PLINTH TO MATCH EXISTING
SC-2 UPPER WALL
6A
FIRE ALARM HEAT DETECTOR R2
EM1 SL
ALIGN
FIRE ALARM SMOKE DETECTOR
S
110cd FB H.6
CO FIRE ALARM CARBON MONOXIDE DETECTOR
SC-2 CONFIRM EXACT POWER
AV-XX
FIRE ALARM PULL STATION BOTTOM OF REQUIREMENT AND SET UP
PROVIDE JB FOR FUTURE UPPER WALL PROVIDE JB FOR FUTURE WITH AV CONTRACTOR
SL SL FIRE ALARM HORN/STROBE - WALL MOUNT / CEILING MOUNT DIVIDER CURTAIN. CONFIRM DIVIDER CURTAIN. CONFIRM
FM FIRE ALARM FAULT ISOLATION MODULE EXACT UNIT NUMBER, EXACT UNIT NUMBER, 7
71"x107"
POWER REQUIREMENT
BASE 1
RM FIRE ALARM RELAY MODULE POWER REQUIREMENT
AND LOCATION PER AND LOCATION PER
MM FIRE ALARM MONITOR MODULE ARCH DRAWING ARCH DRAWING NEW LOCATION OF STATUE 2
SC SEPARATE CIRCUIT
71"x107"
EM1 BACKBOARD
BASE 2
R2 R2
R2 EM3
WINCH MOTOR R2
CONFIRM EXACT EM3 EM3
EM1 BOTTOM OF POWER
UPPER WALL 8
REQUIREMENT
SL AND LOCATION
110cd PER ARCH DWG WP
SC-2 H.6
RTU-6
BOTTOM OF
UPPER WALL
J H.15
71"x107"
BASE 3
8A
EXIT
ES H-6
NEW TEMPORARY WALL TO BE
ES EM3
INSTALLED DURING CONSTUCTION
EXIT EM3 SL EXIT
SL R2 EM3 110cd SL
H.8
H.8
D40 D89
110cd EM1 110cd
SC-2
4 H.1 D94
SC-1
SC-2
9
D36
R2
85cd
K.6
EM4
K.6
ES K.4
SL
EM1
SC-1
D87 D45
D41 D43
K.4
FA-1-11
110cd
110cd
FA-1-10
D42
SL ES ES
SL
SL
EM4
K.6
K.6
R2 EM4
K.2
K.4
EM4
PP-K
110cd
SC-1
SC-2
EM1 K.1
SC-1 EXIT EXIT
D44
5 5 D35 D34
5
11
1 FLOOR PLAN UP
3.
2 2
EXT.STAIR 2
E1 SCALE: 1''=10'-0'' EXT.STAIR 1
E1 D1 D C1 C B2 B1 B A1 A2 A
RENOVATION
ADJACENT DEVICES ARE ON SEPARATE CIRCUITS. INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
FOR EXISTING
POINT FOR DURING CONSTRUCTION
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF 25 26 27
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION EXISTING CHAIN LINK FENCE
P O N M L K J I H G
H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
11
4.
16
D30 D32
1 1 1 1
CULTURAL
D33 28
MAIN BUILDING.
NEW TEMPORARY WALL TO BE
INSTALLED DURING CONSTUCTION 29
1A 1A
30
6 6
31
NEW BASE
CENTER
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 2 PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
ALIGN
33
7 7
71"x107"
REQUIREMENTS ON SITE PRIOR TO TENDER CLOSE.
BASE 1
NEW LOCATION OF STATUE 2
34
ELECTRICAL
7A
NEW LOCATION OF STATUE 1 7A
35
3 3
71"x107"
BASE 2
8 36 8
71"x107"
BASE 3
8A 38 8A
WITH CAN/ULC-S524-M 3c
11
3.
11
68
4.
09
NEW TEMPORARY WALL TO BE
INSTALLED DURING CONSTUCTION
39
PLAN - PHASE 1
D40 D89
4 4
2
9 9
D36
40
4b D87 D45
41
42
SCALE: SEE NOTE
E1 WITH CAN/ULC-S537-M TO ENSURE SATISFACTORY
D42
N.T.S.
43
D44
5 5 5 5 5
DRAWN:GC
D35 D34
44
11
3.
OPERATION.
22
UP
EXT.STAIR 2
EXT.STAIR 1
45
11
J I H G
3.
07
RED LINE DENOTES AREA OF SCOPE OF WORK
CHECKED:GC
11
REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
3.
REQUIRED FOR ROUGH-IN OF SERVICES
18
INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
POINT FOR DURING CONSTRUCTION REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF REQUIRED FOR ROUGH-IN OF SERVICES
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION
G W1 F E2 E1 D1 D C1 W1.1 C B2 B1 B A1 A2 A
'LE' 'LE'
H.22 H.22
FUTURE RETRACTABLE
BASKETBALL HOOP TO BE
INSTALLED 'LC' 'LC' 'LD' 6
REFER TO STRUCTURAL H.32 H.30 H.26
SPECIFICATIONS FOR
ADDITIONAL FRAMING/
SUPPORT. 'LC' 'LC' 'LD' 'LA'
NEW BASE
H.32 H.30 H.26 H.16
71"x107"
BASE 4
NEW LOCATION STATUE 3
PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
6A
ALIGN
'PA' 'LA'
'LD' H.18 H.16
CP H.26
F R 'LD'
H.26
O F
RO OO
'LA'
'LC' 'LC' 7
71"x107"
H.16
BASE 1
H.32 H.30
'LC' H R'LC'
G NEW LOCATION OF STATUE 2
HI IGH
H.32 H.30
'LD'
H.28
F1
E W H 'LA'
H.16
N TO
ADDITIONAL LATERAL SUPPORT
'LD' 7A
NEW LOCATION OF STATUE 1
H.28 'PA'
FOR ACCESS LADDER REFER TO H.20
STRUCTRAL DRAWINGS
E R
71"x107"
BASE 2
DUCTS TO BE INSTALLED AS HIGH
AS POSSIBLE WITHIN ROOF
STRUCTURE WITH DIFUSSERS TO
R EF 'LA'
11
DRAWINGS 'LC' 'LC' 'LD'
3 .3
H.34 H.36 H.28
2
W1.1
GREY AREA
71"x107"
BASE 3
INDICATES
DRYWALL BULK
UNDERSIDE OF DECK AND HEAD TO
ALL STEELS AND DUCT SEPERATE SPACE 8A
'LC' WORK TO BE'LC'
PAINTED BLACK AND ALLOW FOR
H.34 H.36 'LE' 'LE'
THROUGHOUT FUTURE FINISHED
H.24 H.24
CEILINGS TO BE
GYALSTEN STATUE ABOVE
'LC' 'LC' INSTALLED
REFER TO STRUCTRAL
NEW TEMPORARY WALL TO BE GREYH.34
AREA INDICATES H.36 - REFER TO
SPCIFICATIONS FOR
INSTALLED DURING CONSTUCTION DRYWALL BULK HEAD TO SECTIONS/DETAILS
ADDITIONAL FRAMING REQ'D W3 SEPERATE SPACE AND ALLOW GYALSTEN STATUE ABOVE
FOR FUTURE REFER TO STRUCTRAL
D40 FINISHED CEILINGS TO BE D89 SPCIFICATIONS FOR
INSTALLED 16'-6" OFF FFL TO D94 ADDITIONAL FRAMING REQ'D
FULL HEIGHT TO SUIT
PARTITION HEIGHT - W2 - REFER TO SECTIONS/DETAILSW2 UNDERSIDE OF NEW 38mm W2 W2 W2 W2
REFER TO DETAILS
STEEL DECK
9
W15 W150 W17 W18 W20 W134 W21 W135 W22 D36
W2
W2 'LF' 'LF' 'LF' 'LF' 'LF' 'LF' 'LF' W2
K.12 K.12 K.12 K.12 K.12 K.12 K.12
CL 'LF' 'LF'
K.16.1 K.16.1 W138
W200X27 TO
'LF'
BRACE TOP 'LF' 'LF' 'LF' 'LF' 'LF' 'LF'
D87
OF STEEL
K.12
COLUMN K.12 K.12 K.12 K.12 K.12 K.12 D45 W2
CONNECTION
- REFER TO
STRUCTURAL
DRAWINGS D41 D43
CL
W137
'LF' 'LF' 'LF' 'LF' 'LF' 'LF' 'LF' W2 'LF'
K.14 K.14 K.14 K.14 K.14 K.14 K.14 K.16.2
D42
'LF'
W2
CL K.16.2
D44
17'-2" OFF FFL TO UNDERSIDE OF NEW 38mm STEEL DECK W2
5 D35 D34
5
W66 W136 W67 W139 W68 W140 W69 W70 W71 W72
11
3.
W1 W1.1
22
UP
EXT.STAIR 2
EXT.STAIR 1
1
11
VXB
G 3.
07
UNDERSIDE OF DECK AND ALL STEELS AND DUCT WORK TO BE PAINTED
BLACK THROUGHOUT
A301.1 REFER TO STRUCTURAL DRAWINGS
REVIEW ON SITE TO ENSURE NO CLASH W/ WINDOWS
RED LINE DENOTES AREA OF SCOPE OF WORK
1 FLOOR PLAN
SCOPE OF WORK
E2 SCALE: 1''=10'-0''
S R Q P O N M L K J I H
H G
G F E2
INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
POINT FOR DURING CONSTRUCTION
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION
E1 D1 D C1 C B2 B1 B A1 A2 A
RENOVATION
INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
FOR EXISTING
POINT FOR DURING CONSTRUCTION
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF 25 26 27
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION EXISTING CHAIN LINK FENCE
P O N M L K J I H G
H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
11
4.
16
D30 D32
1 1 1 1
CULTURAL
D33 28
30
6 6
31
NEW BASE
CENTER
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 2 PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
6A 32 6A
ALIGN
33
7 7
71"x107"
BASE 1
NEW LOCATION OF STATUE 2
34
ELECTRICAL
7A
NEW LOCATION OF STATUE 1 7A
35
3 3
71"x107"
BASE 2
8 36 8
71"x107"
BASE 3
8A 38 8A
3c
11
3.
11
68
4.
09
NEW TEMPORARY WALL TO BE
INSTALLED DURING CONSTUCTION
39
D40 D89
4 4 D94
9 9
D36
40
4b D87 D45
D41 D43
41
D42
42
43
SCALE: SEE NOTE
D44
5 5 5 5 5
DRAWN:GC
D35 D34
44
11
3.
22
UP
EXT.STAIR 2
EXT.STAIR 1
45
11
J I H G
3.
07
RED LINE DENOTES AREA OF SCOPE OF WORK
CHECKED:GC
11
REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
3.
REQUIRED FOR ROUGH-IN OF SERVICES
18
INSTALL SECURITY FENCE/HOARDING W/ SECURITY ACCESS/SIGN IN
POINT FOR DURING CONSTRUCTION REFER TO PLUMBING DRAWINGS FOR TRENCHES TO SLAB
CONTRACTOR TO CONFIRM FINAL LOCATION AND METHOD OF REQUIRED FOR ROUGH-IN OF SERVICES
ACCESS/SIGN IN FOR SITE SAFETY DURING CONSTRUCTION
E2 E1 D C B2 B A
NO. ISSUE DATE
1. ISSUED FOR REVIEW 08AUG.17
GREY AREA INDICATE ARE OF DRY WALL
CEILING TO BE INSTALLED
GREY AREA INDICATE ARE OF DRY WALL
CEILING TO BE INSTALLED 2. ISSUED FOR REVIEW 14SEPT.17
W3
D89
W2
3. ISSUED FOR REVIEW 29SEPT.17
D40
LINE INDICATES WHERE WALL ABOVE 4. ISSUED FOR REVIEW 4 OCT.17
STEPS UP TO HIGHER ROOF AREA
W2
D94
W2 5. ISSUED FOR REVIEW 10 OCT.17
W2 W2
6. ISSUED FOR TENDER 11 OCT.17
W2 W2
D36
9
W2
AREA OF WALL TO SEPERATE THE PRAYER HALL , AND TO CREATE THE VIP RECEPTION AND SUIT.
INCLUDE COST FOR INSTALLATION OF NEW WASHROOM, AND BATHROOM SUITE.
ALL DOORS AND ASSOCIATED DETAILS TO BE ALLOWED FOR IN SEPERATE COST.
R1
K.8.2
D45 EM4 W2
ALIGN
D41
[0'-6"]
150
D43
EF1
K.8.1 'G'
W2
K.8.3W2
'G'
36''MIN.
K.8.6 W4
K.8.4
D42
W2
EF1
D44
K.8.5
5
P O N M L K J I H G
H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
11
4.1
6
D30 D32
1 1
D33
1A
NEW BASE
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
6A
ALIGN
7
71"x107"
BASE 1
NEW LOCATION OF STATUE 2
3
7A
NEW LOCATION OF STATUE 1
RENOVATION
71"x107"
BASE 2
FOR EXISTING
8
3b
71"x107"
BASE 3
3c
8A
CULTURAL
11
3.6
11
4.0
8
D40 D89
CENTER
4 D94
9
D36
4b D87 D45
D41 D43
ELECTRICAL
POWER-SEPERATE PRICE
D42
D44
5 5 D35 D34
5
11
3.2
2
UP
EXT.STAIR 1
EXT.STAIR 2
11
J I H G
3.0
7
DRAWN:GC
CHECKED:GC
2 KEY PLAN APPROVED:
E3 SCALE: NTS PROJECT NO:160603
DWG. NO.
E3
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
SCOPE OF WORK
NOTE:
RENOVATION
FOR EXISTING
CULTURAL
SCOPE OF WORK
SCOPE OF WORK CENTER
ELECTRICAL
SINGLE LINE DIAGRAM
- PHASE 1
SCALE: SEE NOTE
DRAWN:GC
CHECKED:GC
APPROVED:
PROJECT NO:160603
DWG. NO.
E4
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
EX. EX. EX. EX. EX. EX. PRODUCED.
EX.
SPARE NO. ISSUE DATE
EXISTING 1. ISSUED FOR REVIEW 08AUG.17
EXISTING FIRE ALARM 2. ISSUED FOR REVIEW 14SEPT.17
FIRE ALARM ISSUED FOR REVIEW 29SEPT.17
ANNUNCIATOR CONTROL 3.
PANEL 4. ISSUED FOR REVIEW 4 OCT.17
5. ISSUED FOR REVIEW 10 OCT.17
6. ISSUED FOR TENDER 11 OCT.17
EX.
EX.
3 FA ANNUUNCIATOR
E5
2 FA ANNUUNCIATOR
E5
P O N M L K J I H G
H G F E2 E1 D1 D C1 C B2 B1 B A1 A2 A
11
4
.1
6
D30 D32
1 1
D33
1A
NEW BASE
71"x107"
BASE 4
NEW LOCATION STATUE 3
2 PREPARE EXISTING SLAB FOR NEW
BASE PLINTH TO MATCH EXISTING
6A
ALIGN
7
RENOVATION
71"x107"
BASE 1
3
7A
NEW LOCATION OF STATUE 1
FOR EXISTING
71"x107"
BASE 2
CULTURAL
CENTER
71"x107"
BASE 3
8A
ELECTRICAL
11
4.0
D40 D89
4
9
D36
D87 D45
D41 D43
- PHASE 1
SCALE: SEE NOTE
D42
DRAWN:GC
5 5 D35 D34
D44
E5
3.
2
APPROVED:
UP
2
EXT.STAIR 1
EXT.STAIR 2
N.T.S.
PROJECT NO:160603
11
J I H G
3.
70
DWG. NO. E5
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
RENOVATION
FOR EXISTING
CULTURAL
CENTER
ELECTRICAL
POWER- PANEL SCHEDULE
PHASE 1
SCALE: SEE NOTE
DRAWN:GC
CHECKED:GC
APPROVED:
PROJECT NO:160603
DWG. NO. E6
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
9/16" ROD HANGERS. THREAD LOWER END TO ACCEPT NUT AND WASHER
- USE ONLY THE LATEST DRAWINGS.
SECURING CHANNEL IRON SUPPORT. PROVIDE LENGTH AS REQUIRED.
(TYPICAL) - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
TRANSFORMER TO BE HUNG FROM OPEN WEB STEEL JOIST TOP CHORD OR
FROM CONCRETE SLAB ABOVE. IF THE TRANSFORMER IS SUSPENDED FROM ALLOW LENGTH OF STEM
OPEN WEB STEEL JOISTS. SHE TRANSFORMER TO BE CENTRED BETWEEN THE FROM BUILDING STRUCTURE
OPEN WEB STEEL JOISTS AND BE SUPPORTED BY 2-C75x6 CHANNELS TO WHERE LIGHTING
SPANNING BETWEEN AND CONNECTED TO THE TOP CHORD OF THE JOIST AT NO. ISSUE DATE
FIXTURE IS 24'' BELOW HVAC
A PANEL JOINT DUCTWORK 1. ISSUED FOR REVIEW 08AUG.17
2. ISSUED FOR REVIEW 14SEPT.17
HEX BOLT 3. ISSUED FOR REVIEW 29SEPT.17
SPRING ISOLATION (TYPICAL)
4. ISSUED FOR REVIEW 4 OCT.17
GFCI 5. ISSUED FOR REVIEW 10 OCT.17
TRANSFORMER MOUNTING BRACKET C/W ALL 6. ISSUED FOR TENDER 11 OCT.17
RECEPTACLE
REQUIRED ACCESSORIES BY
VIBRATION MOUNTING PAD (TYPICAL) LIGHTING SUPPLIER
MIN 750mm
CHANNEL C/W NUT
HIGH BAY LINEAR AND SPRING PER
2"x4" CHANNEL IRONS WELDED TOGETHER TO MAKE PLATFORM LIGHTING FIXTURE MANUFACTURER'S
NOTES:
1.SPACE CHANNEL IRONS SO THAT
TRANSFORMER IS PROPERLY NOTES:
SUPPORTED.
1. PROVIDE AT LEAST ONE (1) GFCI RECEPTACLE 5-20R C/W
2.ALLOW ADEQUATE ACCESS SPACE IN-USE WEATHERPROOF COVER.
CHANNEL/STEM CABLE
BETWEEN RODS AND TRANSFORMER WIRING LIGHTING SUPPORT
FOR REMOVAL OF FRONT COVER. SYSTEM (UNISTRUT OR 2. RECEPACLE SHALL NOT BE INSTALLED LESS THAN 750mm
KINDORF) BY ELECTRICAL ABOVE GRADE AND LOCATED WITHIN 7.5m OF THE ROOFTOP
CONTRACTOR HVAC EQUIPMENT.
3.CO-ORDINATE TRANSFORMER
LOCATION AND MOUNTING WITH BASE
3. RECEPTACLE SHALL BE SUPPLIED BY A SEPARATE BRANCH
BUILDING STRUCTURE ENGINEER STRAIN RELIEF CIRCUIT THAT DOES NOT SUPPLY ANY OTHER OUTLETS OR
PRIOR TO START OF WORK. EQUIPMENT.
4.PROVIDE FLEXIBLE CONDUIT FOR 4. REFER TO ELECTRICAL DRAWINGS FOR NUMBER OF OUTLET(S)
PRIMARY AND SECONDARY AND LOCATION(S).
EMT CONDUIT CONNECTIONS TO THE TRANSFORMER.
SECURITY BOX
1 TYPICAL TRANSFORMER SUSPENSION DETAIL SINGLE OR DOUBLE DUPLEX (BY OTHERS)
E7 NTS (OR QUADPLEX) RECEPTACLE
AS PER DRAWINGS EXIT SIGN
JB
PERMANENT LABEL CONDUIT(TYPICAL)
INDICATING POWER
NOTES: OR COMMUNICATION PULL STATION
CABLE TRAY SHALL BE /DATA CIRCUIT
OWJS/TRUSS MEMBER INSTALLED 1'-0" MINIMUM KEY PAD
KEY PAD BY OTHER)
FROM CENTERLINE OF (BY OTHER)
SPRINKLER SPRINKLER AS
MEASURED
HORIZONTALLY FROM
CABLE TRAY CENTERLINE OF
SPRINKLER TO
NEAREST EDGE OF CABLE
TRAY.
2'-0"
2'-0"
1'-0" min. min.
MIN RENOVATION
1. NON-GALVANIZED, SUITABLE FOR PAINTING, STEEL FOR EXISTING
2. SOLID BOTTOM, OPEN TOP, 6" WIDTH x 3-3/8" H. COMMUNICATION CULTURAL
/DATA OUTLET C/W
3. STRAIGHT LENGTHS = 144" MAX SINGLE GANG PLASTER CENTER
RING. COVER PLATES JACKS ELECTRICAL
4. HORIZONTAL BENDS (ELBOWS) 12" AND WIRING BY COMMUNICATION
DETAILS
CONTRACTOR.
RADIUS TO INSIDE SIDERAIL.
NOTES:
SCALE: SEE NOTE
5. HORIZONTAL TEES, WIDTH TO MATCH TRAY, ALWAYS MAINTAIN A 24" CLEARANCE FROM THE DOOR.
DRAWN:GC
12" RADIUS TO INSIDE SIDERAIL. 5 OUTLET LABELLING DETAIL
NTS CHECKED:GC
E7 APPROVED:
4 ELECTRICAL CABLE TRAY DETAIL 6 TYPICAL DOOR ELEVATION DETAIL PROJECT NO:160603
E7 NTS E7 NTS
DWG. NO. E7
- DO NOT SCALE DRAWINGS.
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
- CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
- USE ONLY THE LATEST DRAWINGS.
- THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
FIRE PROTECTION PLANS UNLESS THEY ARE NOT
PRODUCED.
CONDUIT
NOTES:
1. METAL CHANNEL STRUT SUPPORT
FIRE ALARM LONGER THAN 36'' SHALL BE INSTALLED
NOTES:
CABLING WITH A CENTER SUPPORT ROD.
1. ALL OPEN FIRE ALARM CABLING SHALL BE CONCEALED FROM
PUBLIC VIEW.
2. FASTEN THREADED ROD TO STRUCTURE
2. FIRE ALARM CABLE SHALL NOT BE PAINTED. BY APPROVED METHOD
BY MANUFACTURER. SIRE VERIFY EXACT
CONDITIONS.
1 CEILING MOUNT JUNCTION BOX DETAIL 2 OPEN FIRE ALARM CABLING DETAIL 3 TYPICAL DOOR ELEVATION DETAIL
E8 NTS E8 NTS E8 NTS
110 #2 #6
125 #1 #6
150 1/0 #6
175 2/0 #6
200 3/0 #6
225 4/0 #4
SCHEDULE NOTES:
1. FEEDER SIZES INDICATED ON PLAN AS 50 REFER TO A 50A FEEDER WITHOUT
NEUTRAL. 50N REFERS TO A 50A FEEDER WITH A NEUTRAL
2. SOME FEEDER SIZES DO NOT MATCH BREAKER/FUSE SIZES DUE TO UP-SIZING
OF THE FEEDER FOR VOLTAGE DROP.
RENOVATION
3. CONDUIT SIZES ARE SIZED AS PER C.E.C. AND MAY BE UP-SIZED FOR EASE OF FOR EXISTING
PULLING OR DOWNSIZED AS ALLOWED BY C.E.C. FOR CONDUIT/INSULATION
TYPES BEING INSTALLED. CULTURAL
CENTER
ACTUAL RATING OF LUGS AS PER C.E.C.
ELECTRICAL
DETAILS
DWG. NO. E8
- DO NOT SCALE DRAWINGS.
Electrical Specifications 31. ELECTRICAL CONNECTIONS FOR MECHANICAL, OWNER'S ETC., EQUIPMENT
- CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
AGAINST SPECIFICATIONS AND REPORT ANY
DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
1. SCOPE OF WORK 12.2 IN FIRE RATED CONSTRUCTION PACK AND SEAL VOID BETWEEN OPENING AND 17.2 WHERE CONDUIT AND/OR CONDUCTORS ARE EXPOSED, ARRANGE SAME TO 22. FASTENING AND SECURING HARDWARE - CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
CONDUIT FOR LENGTH OF OPENING WITH ASBESTOS-FREE ELASTOMERIC ULC AVOID INTERFERENCE WITH OTHER WORK AND PARALLEL TO BUILDING LINES. 31.1 PROVIDE REQUIRED ELECTRICAL CONNECTIONS TO APPARATUS SUPPLIED BY THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
1.1 SUPPLY LABOUR, TOOLS, SERVICES, EQUIPMENT AND PROVIDE MATERIALS LISTED AND LABELLED MATERIALS. INSTALL FIRE-STOP AND SMOKE SEAL WHERE HORIZONTAL CONDUITS AND/OR CONDUCTORS ARE EXPOSED, INSTALL AS 22.1 PROVIDE PROPER FASTENERS AND SIMILAR HARDWARE REQUIRED FOR DIVISION 15, OWNER AND AS PART OF OTHER DIVISIONS. DO REQUIRED
REQUIRED TO COMPLETE WORK IN ACCORDANCE WITH THIS SPECIFICATION AND MATERIALS IN ACCORDANCE TO ULC CERTIFICATION AND MANUFACTURER'S CONDUIT CONDUCTORS AND FOR EQUIPMENT HANGER AND/OR SUPPORT ELECTRICAL WORK FOR EQUIPMENT SCHEDULED ON DRAWINGS. DIVISION 15 WILL - USE ONLY THE LATEST DRAWINGS.
HIGH AS POSSIBLE DO NOT INSTALL CONDUIT AND/OR CONDUCTORS WITHIN 6"
DRAWINGS. COMPLY WITH LAWS, REGULATIONS AND CODES OF AUTHORITIES REQUIREMENTS TO PROVIDE FIRE-STOP RATINGS OF OPENINGS IN ACCORDANCE (150MM) OF 'HOT' PIPES OR EQUIPMENT UNLESS CONDUIT AND/OR CONDUCTORS MATERIAL UNLESS OTHERWISE NOTED. EXPLOSIVE POWER ACTUATED FASTENERS SUPPLY STARTERS FOR MOTORIZED APPARATUS SUPPLIED BY THEM AND WILL - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
HAVING JURISDICTION. CONFORM TO REQUIREMENTS OF BIDDING DOCUMENTS WITH GOVERNING BUILDING CODE REQUIREMENTS. WILL NOT BE PERMITTED UNLESS SPECIFIC WRITTEN APPROVAL FOR USE AND TYPE PROVIDE LAMACOID IDENTIFICATION THROUGHOUT. WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
ARE ASSOCIATED WITH EQUIPMENT. INDEPENDENTLY RUN CONDUIT AND FIRE PROTECTION PLANS UNLESS THEY ARE NOT
AND DIVISION 1. CONDUCTORS MUST BE SUPPORTED FROM THE CEILING OR WALL STRUCTURE, NOT HAS BEEN OBTAINED FROM CONSULTANT. UNDER NO CIRCUMSTANCES USE PRODUCED.
12.3 DO NO CUT OR DRILL EXISTING WORK WITHOUT PRIOR OWNER'S APPROVAL. IN FROM CEILING HANGERS, DUCTWORK, PIPING, CABLE TRAYS ETC.. CEILING SUSPENSION HANGERS OR GRIDS FOR SUSPENSION OF CONDUIT AND 31.2 BE RESPONSIBLE FOR:
2. EXAMINATION OF SITE AND DOCUMENTS CONSULTATION WITH OWNER AND BY USE OF X-RAY WITH OWNER'S APPROVAL, CONDUCTORS. 31.2.1 COMPLETE INSTALLATION AND CONNECTION OF STARTERS AND PROVIDE
DETERMINE PRESENCE OF EXISTING SERVICES AND REINFORCING RODS 17.3 IDENTIFY CONDUIT RUNS (IE. TAG BOTH ENDS OF CONDUIT RUNS). 'LINE' AND 'LOAD'
2.1 PROVIDE TO SUBMITTING BID, CAREFULLY EXAMINE CONDITIONS AT SITE WHICH CONCEALED BEHIND SURFACE TO BE CUT. NOTE: ELECTRICAL CONTRACTOR WILL 23. IDENTIFICATION NAMEPLATES POWER CONNECTIONS AND INTERLOCKING AS REQUIRED. NO. ISSUE DATE
WILL OR MAY AFFECT WORK, DRAWINGS AND SPECIFICATIONS AND BECOME BE HELD RESPONSIBLE FOR DAMAGE DONE TO EXISTING BUILDING AND SERVICES 18. CONDUITS 31.2.2 PROVIDE MOTOR STARTER PANELS CONSISTING OF NO. 14 GAUGE STEEL
FAMILIAR WITH BUILDING CONSTRUCTION, FINISHES AND OTHER WORK CAUSED BY CUTTING OR DRILLING. 23.1 FOR EACH PIECE OF ELECTRICAL DISTRIBUTION EQUIPMENT FROM ELECTRICAL BOLTED 1. ISSUED FOR REVIEW 08AUG.17
ASSOCIATED WITH WORK IN ORDER THAT BID INCLUDES FOR EVERYTHING 18.1 PROVIDE CONDUIT FOR CONDUCTORS. CONDUIT TO BE EMT (THIN WALL) SOURCE OF SUPPLY UP TO AND INCLUDING PANELBOARDS, PROVIDE ENGRAVED PANELS SIZED TO ACCOMMODATE STARTERS AS REQUIRED AND SUITABLE 2. ISSUED FOR REVIEW 14SEPT.17
NECESSARY FOR COMPLETION OF WORK. 13. DISCONNECTION, REMOVAL AND RELOCATION GALVANIZED, ELECTRICAL METALLIC TUBING TO CSA C222 NO. 83, COMPLETE WITH LAMACOID IDENTIFICATION NAMEPLATES SECURED TO APPARATUS WITH SPLITTER. ISSUED FOR REVIEW 29SEPT.17
3.
FACTORY MADE BENDS WHERE SITE BENDING IS NOT POSSIBLE AND JOINTS AND STAINLESS STEEL SCREWS. WORDING TO INDICATE SOURCE OF ELECTRICAL 31.2.3 UNLESS OTHERWISE NOTED OR SHOWN ON DRAWINGS, MOUNT 1-PHASE
SUPPLY AND SIZED TO SUIT EQUIPMENT FOR WHICH IT IS PROVIDED. CONFIRM STARTERS 4. ISSUED FOR REVIEW 4 OCT.17
3. PERMITS, CERTIFICATES AND FEES 13.1 WHERE INDICATED ON DRAWINGS AND DETERMINED BY SITE VISIT, TERMINATIONS MADE WITH SET SCREW TYPE CONNECTORS, FOR SHORT BRANCH
DISCONNECT AND REMOVE ITEMS OF EXISTING OBSOLETE ELECTRICAL WORK AND CIRCUIT CONNECTORS TO MOTORIZED EQUIPMENT AND TRANSFORMERS (MINIMUM EXACT NAMEPLATE WORDING, DESIGNATIONS AND SIZES WITH OWNER PRIOR TO ADJACENT TO EQUIPMENT THEY SERVE AND CONNECT COMPLETE. 5. ISSUED FOR REVIEW 10 OCT.17
3.1 PAY FOR AND OBTAIN PERMITS TO COMPLETE WORK. WHEN WORK IS RELOCATE DEVICES, WHERE FIXTURES, SWITCHES, RECEPTACLES AND OTHER LENGTH 18" (450MM), MAXIMUM LENGTH 24" (600MM) WITH 180 DEGREE LOOP WERE MANUFACTURE. 31.2.4 CO-ORDINATE FEEDER ENTRIES TO STARTERS AND STARTER ASSEMBLIES 6. ISSUED FOR TENDER 11 OCT.17
COMPLETE, SUPPLY AND TURN OVER INSPECTION CERTIFICATES FROM GOVERNING DEVICES AND/OR EQUIPMENT IS REMOVED. DISCONNECT AT POINT OF ELECTRICAL POSSIBLE).- GALVANIZED STEEL FLEXIBLE FLUID-TIGHT METALLIC CONDUIT TO CSA WITH
AUTHORITIES TO CONSULTANT. PAY FEES AND CHARGES LEVIED BY MUNICIPALITY SUPPLY, REMOVE OBSOLETE WRING AND MAKE SYSTEM SAFE. WHERE EXISTING C222 NOT. 56, COMPLETE WITH IDEAL 'STEEL TOUGH' LIQUID TIGHT FLEXIBLE 24. FUSES DIVISION 15.
AND OTHER GOVERNING AUTHORITIES FOR PERMITS, INSPECTIONS AND OBSOLETE CONDUIT AND SIMILAR RACEWAY MATERIAL CANNOT BE REMOVED, CUT CONDUIT CONNECTORS AT TERMINATIONS. FOR CONDUIT GREATER THAN 2" 31.2.5 PROVIDE ADDITIONAL DISCONNECT SWITCHES (COMPLETE WITH
CERTIFICATES. KEEP COPY OF SUCH PERMITS AND CERTIFICATES, ETC. ON JOB BACK AND CAP OBSOLETE CONDUITS OR RACEWAYS. REVISE PANELBOARD (50MM) DIAMETER AND FOR SURFACE MOUNTED CONDUIT AT HEIGHT LESS THAN 4' 24.1 PROVIDE COMPLETE SET OF FUSES FOR EACH FUSIBLE DISCONNECT OR IDENTIFICATION DETAILED
SITE. DIRECTORIES ACCORDINGLY, IF AFFECTED BY WORK. (1200MM), PROVIDE RIGID GALVANIZED STEEL TO CSA C222 NO. 45 COMPLETE WITH SIMILAR FUSIBLE EQUIPMENT. FUSES TO BE FORM 1, CLASS 'J' HRC FUSES FOR ON DRAWINGS, REQUIRED BY CODE, OR FOR APPARATUS WHICH CANNOT BE
FITTINGS, CONNECTORS AND RIGID COUPLINGS. CONSTANT RUNNING EQUIPMENT AND FOR 11 CLASS 'C' FUSES FOR MOTOR SEEN FROM ITS
4. CO-ORDINATION AND CO-OPERATION 13.2 UNLESS OTHERWISE NOTED, OBSOLETE MATERIALS WHICH ARE EQUIPMENT THAT CYCLES 'ON' AND 'OFF'. ACCEPTABLE MANUFACTURERS ARE STARTER OR IS IN EXCESS OF 30' (9M) FROM ITS STARTER).
DISCONNECTED AND ARE NOT TO BE RELOCATED OR REUSED WILL BECOME THE 18.2 SUPPORT AND SECURE CONDUIT AT SPACING IN ACCORDANCE WITH CODE ENGLISH ELECTRIC, BUSSMAN AND GOULD. 31.2.6 DO INTERLOCK WIRING INDICATED ON DRAWINGS AND/OR SCHEDULES.
4.1 ELECTRICAL CONTRACTOR TO CO-ORDINATE HIS WORK WITH WORK OF ALL PROPERTY OF THE ELECTRICAL CONTRACTOR. REMOVE FROM SITE AND DISPOSE. REQUIREMENTS BY MEANS OF GALVANIZED PIPE STRAPS, CONDUIT CLIPS, RING 31.2.7 CONNECT REQUIRED CIRCUITS TO MOTOR STARTER PANEL SO AS TO
TRADES TO ENSURE A PROPER AND COMPLETE INSTALLATION. NOTIFY ALL TRADES OBTAIN FROM OWNER, LIST OF EXISTING ITEMS TO BE CAREFULLY REMOVED AND BOLT TYPE HANGERS OR BY OTHER PROPER MANUFACTURED DEVICES. PROVIDE 25. DISCONNECT SWITCHES BALANCE ACTUAL
CONCERNED OF REQUIREMENT FOR OPENINGS, SLEEVES, INSERTS AND OTHER TURNED OVER TO OWNER. SAID ITEMS WILL REMAIN PROPERTY OF OWNER. CONDUIT FITTINGS CONSTRUCTED OF SAME MATERIALS AS CONDUIT AND SUITABLE LOADS (WATTAGE).
HARDWARE NECESSARY IN THEIR WORK FOR INSTALLATION OF HIS WORK AND FOR APPLICATION. SQUARE AND PROPERLY REAM ENDS OF SITE CUT CONDUIT. 25.1 PROVIDE DISCONNECT SWITCHES, CUTLER-HAMMER CANADA, HEAVY DUTY,
WHERE HIS WORK IS TO BE INTEGRATED WITH WORK OF OTHER TRADES OR IS TO 13.3 PROVIDE JUNCTION BOXES, OUTLET BOXES, WIRING, PLATES, ETC., AS GENERALLY CONDUIT IS SIZED ON DRAWINGS. SIZE CONDUIT NOT SIZED ON CSA APPROVED FRONT OPERATED TYPE. FUSIBLE UNITS TO BE COMPLETE WITH 32. GENERAL ELECTRICAL WORK TESTING
BE INSTALLED IN CLOSE PROXIMITY WITH WORK OF OTHER TRADES. CAREFULLY NECESSARY FOR COMPLETE RELOCATION OF DEVICES. CLEAN AND RE-LAMP DRAWINGS IN ACCORDANCE WITH CODE. BEND CONDUIT AT FULL CONDUIT FUSE CLIPS SUITABLE FOR HRC FUSES, UNLESS OTHERWISE NOTED. ENCLOSURES
CO-ORDINATE WORK PRIOR TO AND DURING INSTALLATION. RELOCATED LUMINAIRES. REPLACE FAULTY BALLASTS. WHEN RELOCATION WORK DIAMETER WITH NO KINKS AND NO FLAKING OR CRACKING OF FINISHES. TO BE SPRINKLER-PROOF. AMP RATING, NUMBER OF POLES AND FUSE 32.1 IN ADDITION TO TESTS REQUIRED BY GOVERNING AUTHORITIES AND
IS COMPLETE, CONFIRM RELOCATED DEVICES ARE IN PROPER ORDER. REQUIREMENTS ARE AS INDICATED ON DRAWINGS. ACCEPTABLE MANUFACTURERS REGULATIONS, TEST WORK TO ENSURE THERE ARE NO LEAKS, GROUNDS OR
4.2 EXACT LOCATIONS AND ROUTING OF SERVICES MUST BE PROPERLY PLANNED, 19. CONDUCTORS INCLUDE SIEMENS ELECTRIC, FEDERAL PIONEER AND SQUARE 'D' CANADA. CROSSES. ENSURE DEVICES ARE COMMISSIONED AND OPERABLE. CONNECT
CO-ORDINATED AND ESTABLISHED WITH ALL AFFECTED TRADES PRIOR TO 13.4 WHERE EXISTING SERVICES PASS THROUGH OR ARE IN AN AREA TO SERVE CIRCUITS TO PANELBOARDS SO AS TO BALANCE ACTUAL LOADS (WATTAGE) WITHIN
INSTALLATION SUCH THAT THEY WILL CLEAR EACH OTHER AS WELL AS ANY ITEMS WHICH ARE TO REMAIN, MAINTAIN SERVICES. INCLUDE FOR RE-ROUTING 19.1 PROVIDE CONDUCTORS. REFER TO DRAWINGS FOR SIZING OF CONDUCTORS. 26. SPLITTER TROUGH 5%. IF REQUIRED TRANSPOSE CIRCUITS WHEN WORK IS COMPLETE TO MEET THIS
OBSTRUCTIONS. GENERALLY, PIPING REQUIRING UNIFORM PITCH SHALL BE GIVEN EXISTING SERVICES CONCEALED BEHIND FINISHES AND WHICH BECOME EXPOSED GENERALLY, BRANCH CIRCUIT CONDUCTOR SIZES ARE INDICATED ON REQUIREMENT.
RIGHT OF WAY WITH OTHER SERVICES LOCATED AND ARRANGED TO SUIT. DURING RENOVATION WORK, SO AS TO BE CONCEALED BEHIND FINISHES. CONSULTANT'S DRAWINGS. SUCH SIZES ARE MINIMUM REQUIREMENTS AND MUST 26.1 PROVIDE CSA APPROVED SPLITTER TROUGH AS SHOWN ON DRAWINGS
BE INCREASED TO SUIT LENGTH OF RUN AND VOLTAGE DROP IN ACCORDANCE COMPLETE WITH FORMED PRIMED AND PAINTED STEEL BOX WITH KNOCKOUTS. 33. EXISTING FIRE ALARM SYSTEM WORK
4.3 REVIEW ALL MECHANICAL AND PLUMBING DRAWINGS FOR ITEMS WHICH 13.5 IN AREAS WHICH ARE NOT BEING ARCHITECTURALLY RENOVATED AND WHICH WITH SCHEDULE OBTAINED FROM CONSULTANT. CONDUCTORS NOT SIZED ON TERMINAL BLOCKS COMPLETE WITH PRESSURE TYPE LUGS, HINGED FORMED
REQUIRE ELECTRICAL POWER THAT MAY NOT BE SHOWN ON ELECTRICAL DIVISION 16 MUST RUN SERVICES THROUGH, BE RESPONSIBLE FOR REMOVAL AND DRAWINGS SHALL BE SIZED IN ACCORDANCE WITH CODE. PROVIDE CABLE COVERPLATE, SUITABLE MOUNTING PROVISIONS AND ALUMINIUM I.D. NAMEPLATE. 33.1 WHERE SHOWN ON DRAWINGS, DISCONNECT, RELOCATE AND RECONNECT
DRAWINGS. PROVIDE POWER TO THESE ITEMS, INCLUDING OVER-CURRENT DEVICE REINSTALLATION OF ARCHITECTURAL CEILINGS, MECHANICAL EQUIPMENT, SUPPORT SYSTEM ACCESSORIES WHICH ARE NOT SPECIFIED HEREIN OR SHOWN SECURE SPLITTER IN PLACE ON BACKBOARD INDEPENDENT OF CONNECTING REQUIRED DEVICES. NEW WORK TO BE AN EXTENSION OF EXISTING SYSTEM.
(BREAKER OR SWITCH & FUSE), CABLE, CONDUIT, ETC. SPRINKLERS, ETC., AS REQUIRED FOR INSTALLATION OF ELECTRICAL ON DRAWINGS BUT ARE REQUIRED FOR PROPER INSTALLATION. CONDUIT. CONNECT COMPLETE ACCEPTABLE MANUFACTURERS INCLUDE BELL, PROVIDE ADDITIONAL DEVICES WHERE SHOWN, CONDUCTORS IN CONDUIT AND
CONTRACTOR'S WORK. PATCH AND MAKE GOOD (INCLUDING PAINTING) SURFACES STELPRO AND PURSLEY. END-OF-LINE RESISTORS. PROVIDE ULC LISTED DEVICES TO MATCH EXISTING
5. NOISE CONTROL TO MATCH EXISTING. 19.2 CONDUCTORS TO BE 'T90 NYLON' SINGLE CONDUCTOR TO CSA C222 NO. 75, DEVICES AND BE COMPLETELY COMPATIBLE WITH EXISTING SYSTEM. PERFORM
COLOUR CODED 194 DEGREES F. (90 DEGREES C) RATED, PVC INSULATED AND 27. CIRCUIT BREAKERS FOR EXISTING PANELBOARDS WORK IN ACCORDANCE WITH LATEST ADDITION OF CAN/ULC-S524. SEQUENCE OF
5.1 WORK WHICH MAY CAUSE NOISE DISTURBANCES MUST BE SCHEDULED AT 14. HAZARDOUS MATERIALS NYLON COVERED. OPERATION OF NEW WORK TO FUNCTION AS EXISTING SYSTEM. UNLESS
TIMES APPROVED BY CONSULTANT. CO-ORDINATE WORK WITH TRADES TO 27.1 PROVIDE BREAKERS IN EXISTING PANELBOARDS OF TYPE TO MATCH EXISTING OTHERWISE NOTED, CONNECT ADDITIONAL DEVICES TO EXISTING ZONES SERVING
MINIMIZE NOISE DISTURBANCES. 14.1 AT ANY TIME DURING COURSE OF WORK ASBESTOS MATERIALS ARE 19.3 BRANCH CIRCUIT CONDUCTORS IN ACCESSIBLE SUSPENDED CEILING SPACES, DEVICES. QUALITY AND STANDARDS OF BREAKERS SHALL MATCH EXISTING. AREA AND PROVIDE WIRING OF MINIMUM NO. 16 AWG IN CONDUIT AND AS PER
ENCOUNTERED OR SUSPECTED, CEASE WORK IN AREA IN QUESTION AND IN STUB WALL CONSTRUCTION TO SUSPENDED CEILING SPACES (MAXIMUM 20' (6M) CONFIRM REQUIREMENTS ON SITE PRIOR TO ORDERING. PROVIDE FOR ALL ELECTRICAL SAFETY AUTHORITY CODE REQUIREMENTS. ALARM RECEIVING
6. CLEAN UP IMMEDIATELY REPORT IN ACCORDANCE WITH ONTARIO REGULATION 654/85 RUN PERMITTED MAY BE 'BX' TYPE AC-90 FLEXIBLE ARMOURED CABLE WITH 'RW-90' MODIFICATIONS TO PANELBOARDS FOR BREAKERS AND FEEDER INSTALLATIONS. CIRCUITS SHALL BE RUN IN SEPARATE CONDUITS FROM ALARM SIGNALLING
(SECTION 7) TO CONSULTANT. DO NOT RESUME WORK IN AFFECTED AREA CONDUCTORS AND BARE COPPER GROUND CONDUCTORS TO CSA C22 NO. 51 PROVIDE REPLACEMENT BRANCH CIRCUIT DIRECTORY CARDS NEATLY CIRCUITS.
6.1 DURING CONSTRUCTION, KEEP SITE REASONABLY CLEAR OF RUBBISH AND WITHOUT APPROVAL FROM CONSULTANT. (BULLETIN NO. 994). PROVIDE PROPER SQUEEZED TYPE CONNECTORS AND TYPEWRITTEN TO INCORPORATE ADDITIONAL AND EXISTING CONNECTED LOADS TO
WASTE MATERIAL RESULTING FROM WORK ON DAILY BASIS. AFTER COMPLETION PLASTIC ANTI-SHORT BUSHINGS AT TERMINATIONS. SUPPORT 'BX' IN CEILING CONSULTANTS DIRECTIONS. DIRECTORIES SHALL USE OWNERS ACTUAL ROOM 33.2 DURING WORK TO THE EXISTING FIRE ALARM SYSTEM THE TIME AND DURATION
OF WORK, REMOVE RUBBISH AND DEBRIS, ARRANGE AND PAY FOR REPAIR OF 15. RECORD DRAWINGS (AS-BUILTS) SPACES AND IN STUD WALL CONSTRUCTION WITH STEEL 2 HOLE CABLE STRAPS TO NAMES & NUMBERS AND NOT CONTRACT DRAWINGS NAMES & NUMBERS. PROVIDE OF INTERRUPTION SHALL BE APPROVED BY THE OWNER AND ONLY 1 ZONE SHALL
DAMAGES CAUSED AND LEAVE PREMISES AND WORK IN GOOD ORDER. 'CODE' REQUIREMENTS. ENGRAVED LAMACOID I.D. NAMEPLATES FOR DISTRIBUTION PANELBOARDS TO BE INTERRUPTED AT ANY 1 TIME. IN ALL AREAS WHERE THE RENOVATION WORK
15.1 DRAWINGS FOR THIS PROJECT HAVE BEEN PREPARED ON A CAD SYSTEM. THE CONSULTANTS DIRECTION REQUIRES SHUTDOWN OF ANY PART OF THE FIRE ALARM PROTECTION SYSTEM,
7. PROTECTION OF EQUIPMENT SOFTWARE USED IS AUTOCAD RELEASED LT 2011. 19.4 BRANCH CIRCUIT CONDUCTORS UP TO AND INCLUDING NO. 10 AWG SHALL BE PROVIDE MANUAL FIRE ALARM PROTECTION (FIRE WARDEN BY MEANS OF
SOLID CONDUCTORS IN SIZES LARGER THAN NO. 10 SHALL BE STRANDED. PROVIDE 28. PANELBOARDS SUPERVISING THE AREA AS APPROVED BY GOVERNING AUTHORITIES. AT NO TIME
7.1 PROPERLY PROTECT AND STORE ALL EQUIPMENT AND MATERIALS ON SITE 15.2 WHEN WORK BEGINS AT SITE, CLEARLY AND ACCURATELY MARK ON A BOUND CONDUCTORS CONSTRUCTED OF 98% CONDUCTIVE COPPER AND APPROVED FOR SHALL THE FIRE ALARM SYSTEM OR ANY 1 ZONE BE LEFT INOPERATIVE OVERNIGHT
FROM DAMAGE. CONTRACTOR SHALL BE RESPONSIBLE FOR SAFE STORAGE OF ALL SET OF WHITE PRINTS OF CONTRACT DRAWINGS ON A DAILY BASES ALL CHANGES 600V. DO NOT USE CONDUCTORS SMALLER THAT NO. 12 AWG UNLESS OTHERWISE 28.1 PROVIDE CUTLER-HAMMER CANADA TYPE 'POW-R-LINE 1' FACTORY PROVIDE ALL REQUIRED BYPASS WIRING AND TEMPORARY WIRING AS MAY BE
EQUIPMENT AND GOODS TO BE RELOCATED AND SHALL REPAIR OR REPLACE AND DEVIATIONS FROM ROUTING OF AND LOCATIONS OF EQUIPMENT SHOWN ON NOTED. ASSEMBLED DEAD FRONT PANELBOARDS, 120/208V 3 PHASE 4 WIRE REQUIRED TO MAINTAIN ALL PARTS OF THE FIRE ALARM SYSTEM OPERATIVE
DAMAGED EQUIPMENT AND GOODS AT DISCRETION OF OWNER. CONTRACT DRAWINGS CHANGES AND DEVIATIONS INCLUDING THOSE MADE BY MANUFACTURED TO CSA STANDARD C222 NO 29 AND ELECTRICAL SAFETY DURING CONSTRUCTION AND ALTERATIONS.
ADDENDA, CHANGE ORDERS AND SITE INSTRUCTIONS, AND CHANGES AND 19.5 PROVIDE IDI ELECTRIC 'IDEAL' NO. 451, NO. 452 AND NO. 453 'WING-NUT' CSA AUTHORITY CODE AND DESIGNATED FOR AN INTERRUPTING CAPACITY OF 10KA
8. INSPECTION OF WORK DEVIATIONS INDICATED ON SUPPLEMENTAL DRAWINGS ISSUED WITH ADDENDA, CERTIFIED 600V RATED PRESSURE TYPE CONNECTORS. SYMMETRICAL AT 208V. 33.3 COVER EXISTING DETECTORS TO PROTECT FROM DEMOLITION &
CHANGE ORDERS AND SITE INSTRUCTIONS. MAINTAIN "AS-BUILT" WHITE PRINTS AT CONSTRUCTION DUST. REMOVE COVERS WHEN ALTERNATIVE FIRE ALARM
8.1 CONSULTANT SHALL AT ALL TIMES HAVE ACCESS TO WORK AND SHALL BE SITE FOR PERIODIC INSPECTION BY CONSULTANT THROUGHOUT DURATION OF 19.6 COLOUR CODE CONDUCTORS IN ACCORDANCE WITH CODE, THROUGHOUT TO 28.2 INSTALL PANELBOARDS WHERE SHOWN COMPLETE WITH: PROTECTION IN AREA IS NOT AVAILABLE OVERNIGHT.
NOTIFIED AT AGREED UPON TIMES OF STAGES OF WORK. WORK. PAY PARTICULAR ATTENTION TO ACCURATELY DIMENSIONING LOCATION OF IDENTIFY PHASES, NEUTRALS AND GROUND BY MEANS OF SELF-LAMINATING 28.2.1 EEMAC 2 SPRINKLER-PROOF ENCLOSURE CONSTRUCTED OF CODE GAUGE
ALL CONCEALED SERVICES TERMINATED FOR FUTURE EXTENSION, ALL BURIED COLOURED TAPE, COLOURED CONDUCTOR INSULATION OR PROPERLY SECURED GALVANIZED STEEL WITH REMOVABLE BOX ENDS, WIRING GUTTER SPACE ON 33.4 WHEN FIRE ALARM SYSTEM WORK IS COMPLETE AND READY FOR ACCEPTANCE
8.2 CONTRACTOR SHALL GIVE CONSULTANT TIMELY NOTICE OF DATE (WITHIN 48 WORK AND SERVICES AND WORK CONCEALED WITHIN BUILDING IN INACCESSIBLE COLOURED PLASTIC DISCS. SIDES AND A ASA-61 GREY BAKED ACRYLIC ENAMEL FINISH. PROVIDE AND ARRANGE FOR INDEPENDENT TESTING COMPANY SUCH AS BROSZ
HOURS AFTER PERFORMANCE) WHEN FOLLOW STAGES OF WORK HAVE BEEN LOCATIONS. 28.2.2 TRIM FOR RECESSED OR SURFACE WALL MOUNTING AS SHOWN AND ASSOCIATES, LEBER/RUES, RANDALL BROWN AND ASSOCIATES OR DETRON
PERFORMED: 19.7 WHEN PULLING WIRES INTO CONDUIT, USE IDI ELECTRIC 'IDEAL YELLOW 77' CONSTRUCTED CODE GAUGE STEEL, BONDERIZED, FINISHED WITH ASA-61 GREY SAFETY CONSULTANTS OR IF APPROVED BY OWNER - EXISTING FIRE ALARM
8.2.1 WHEN 33% OF WORK HAS BEEN COMPLETED; 15.3 WHEN WORK ENDS AT SITE, UPDATE A COPY OF CONTRACT DOCUMENT LUBRICANT. ENSURE WIRES ARE KEPT STRAIGHT AND ARE NOT TWISTED OR BAKED ACRYLIC ENAMEL AND COMPLETE WITH CONCEALED FASTENERS, MAINTENANCE CONTRACTOR TO INSPECT, TEST AND CERTIFY EQUIPMENT,
8.2.2 WHEN 66% OF WORK HAS BEEN COMPLETED; DRAWING DISK SET SO THAT IT REFLECTS ALL DEVIATIONS FROM ORIGINAL ABRAISED. CONCEALED HINGE, CHROME PLATED DOOR LATCH AND KEYED ALIKE LOCK WITH INCLUDING INITIATING DEVICES, SIGNALLING DEVICES, CONTROL DEVICES AND
8.2.3 WHEN 95% OF WORK HAS BEEN COMPLETED; CONTRACT DOCUMENT DRAWINGS, THUS FORMING A TRUE "AS-BUILT" DRAWING KEY, STEEL FRAME HOLDER AND CIRCUIT DIRECTORY BACK OF DOOR AND MYLAR WIRING. PROVIDE CERTIFICATE OF LIABILITY INSURANCE REGISTERED FOR THIS
20. OUTLET BOXES, PULL BOXES AND JUNCTION BOXES
8.2.4 UPON SUBSTANTIAL PERFORMANCE OF WORK. DISK SET. PROVIDE A SET OF REPRODUCIBLE MYLAR PRINTS OF CONTRACT CIRCUIT BREAKER IDENTIFICATION STRIPS. PROJECT TO SHOW SATISFACTORY PROOF OF MANUFACTURER'S AND TESTING
DRAWINGS PRODUCED FROM TRUE "AS-BUILT" DRAWING DISK SET. SUBMIT 28.2.3 DRIP SHIELD FOR SURFACE MOUNTED PANELBOARDS. COMPANY'S LIABILITY COVERAGE FOR BOTH HIS PRODUCT AND PERSONNEL.
20.1 PROVIDE CSA APPROVED STAMPED GALVANIZED STEEL OUTLET BOX FOR EACH
8.3 WHERE STANDARDS OF WORK ARE SPECIFIED OR IMPLIED AND WORK DOES "AS-BUILT" PRINTS AND CAD PRODUCED "AS-BUILT" MYLAR PRINTS TO CONSULTANT. 28.2.4 HARD DRAWN ELECTRICAL GRADE COPPER BUS AND GROUND BUS. CONDUCT WORK IN ACCORDANCE WITH LATEST EDITIONS OF CAN/ULC-S536 AND
LUMINAIRE, FIRE ALARM DEVICE, ETC. REFER TO DRAWINGS FOR LOCATIONS OF
NOT COMPLY WITH PERFORMANCE SPECIFIED OR IMPLIED, SUCH DEFICIENCY ALL SUBMITTED DRAWINGS SHALL BE OF THE SAME QUALITY AS ORIGINAL 28.2.5 HIGH STRENGTH SET SCREW TYPE ANTI-TURNING WIRE CONNECTORS. S537. TESTS TO BE CONDUCTED IN PRESENCE OF OWNER AND/OR CONSULTANT
OUTLETS. CONFIRM EXACT LOCATIONS PRIOR TO ROUGH-IN.
SHALL BE CORRECTED AS DIRECTED BY CONSULTANT. ANY SUBSEQUENT TESTING CONTRACT DOCUMENT DRAWINGS. 28.2.6 BOLT ON MOULDED CASE CIRCUIT BREAKERS.
TO VERIFY PERFORMANCE SHALL BE DONE AT CONTRACTOR'S EXPENSE. ANY 28.2.7 MAIN BREAKER AND GREEN POWER 'ON' INDICATOR LIGHT, WHERE 34. PROVISION FOR TELEPHONE SYSTEM COMPONENTS
20.2 PROVIDE PULL BOXES AND JUNCTION BOXES WHEREVER NECESSARY TO
CHARGES FOR OWNER'S STAFF, CONSULTANT OR OTHER PERSONNEL RELATED TO 15.4 UPDATE OWNER'S DISTRIBUTION RISER DIAGRAMS POSTED IN ELECTRICAL SCHEDULED.
FACILITATE CONDUCTOR & CONDUIT INSTALLATIONS. GENERALLY, PROVIDE
SUCH RE-TESTING SHALL ALSO BE AT EXPENSE OF CONTRACTOR. ROOM. 28.2.8 200% CAPACITY NEUTRALS FOR PANELBOARDS AS SCHEDULED. 34.1 PROVIDE COMPLETE SYSTEM OF EMPTY CONDUITS, OUTLET BOXES, JUNCTION
CONDUIT RUNS EXCEEDING 100' (30M) IN LENGTH OR WITH MORE THAN 3, 90
BOXES, FACE PLATES AND SLEEVES OF REQUIRED AND FIRE RETARDENT PLYWOOD
DEGREE BENDS WITH PULL BOX INSTALLED AT CONVENIENT AND SUITABLE
9. PRODUCTS 16. SHOP DRAWINGS AND OPERATING & MAINTENANCE INSTRUCTION MANUALS 28.3 PROVIDE DOUBLE LUGGING TO EXISTING PANELBOARDS AS SHOWN. BACKBOARDS TO ACCOMMODATE FUTURE EXTENSION OF EXISTING TELEPHONE
INTERMEDIATE ACCESSIBLE LOCATION. PROVIDE JUNCTION BOXES AND PULL
SYSTEM BY SYSTEM INSTALLER WHO WILL PROVIDE EQUIPMENT AND WIRING.
BOXES SIZED IN ACCORDANCE WITH CODE TO SUIT NUMBER AND SIZE OF
9.1 PRODUCTS LISTED AND /OR SPECIFIED ON CONTRACT DOCUMENTS ARE 16.1 SUBMIT SHOP DRAWINGS AND OPERATION & MAINTENANCE INSTRUCTION 28.4 SUPPORT CABINET INDEPENDENT OF CONNECTING CONDUIT. TURN OVER TO PROVIDE BLANK TYPE FACE PLATES.
CONDUITS AND CONDUCTORS. BOXES TO BE GALVANIZED OR PRIME COATED
SELECTED TO ESTABLISH DESIGN STANDARDS. IN MOST CASES, ACCEPTABLE MANUALS FOR THE FOLLOWING: CONSULTANT PRIOR TO APPLICATION FOR SUBSTANTIAL PERFORMANCE OF WORK
PLATE STEEL COMPLETE WITH SCREW-ON OR HINGED COVERS AND KNOCKOUTS.
MANUFACTURERS ARE LISTED. BASE YOUR BID PRICE ON BASE SPECIFIED 16.1.1 SPECIAL RECEPTACLES AND SWITCHES; QUANTITY OF 2 PANELBOARD CABINET KEYS FOR PANELBOARD. IDENTIFY 34.2 PROVIDE CONDUIT WITH MINIMUM DIAMETER AS SHOWN. PROVIDE PULL
BOXES MUST BE ACCESSIBLE AFTER WORK IS COMPLETE.
PRODUCTS OR PRODUCTS SUPPLIED FROM ACCEPTABLE MANUFACTURERS. 16.1.2 LUMINAIRES; PANELBOARD BREAKERS IN PERMANENT MANNER AND COMPLETE TYPED CIRCUIT BOXES
ENSURE PRODUCTS SUPPLIED FROM MANUFACTURERS OTHER THAN BASE 16.1.3 TRANSFORMERS; DIRECTORY TO OWNER'S APPROVAL. IN CONDUIT RUNS LARGER THAN 100' (30M) OR HAVING MORE THAN 2- 90 DEGREE
20.3 SIZE, ARRANGEMENT AND TYPE OF BOXES MUST BE SUITABLE FOR
SPECIFIED MANUFACTURERS ARE EQUIVALENT TO SPECIFIED PRODUCTS. 16.1.4 PANELBOARDS; BENDS. PULL BOX SIZES SHALL NOT BE LESS THAN 6 TIMES ENTERING CONDUIT IN
APPLICATION. PROVIDE BLANK COVER PLATES ON EXISTING OBSOLETE BOXES
PROPOSED SUBSTITUTIONS OF MANUFACTURERS OF PRODUCTS MAY BE 16.1.5 DIMMERS; 28.5 ACCEPTABLE MANUFACTURERS INCLUDE SIEMENS ELECTRIC, FEDERAL LENGTH. LEAVE CONDUITS FREE AND CLEAR OF OBSTRUCTIONS AND TERMINATE
WHICH ARE TO REMAIN. CLEARLY IDENTIFY MAIN PULL OR JUNCTION BOXES BY
PROPOSED TO CONSULTANT FOR ACCEPTANCE, LISTING IN EACH CASE 16.1.6 EMERGENCY LIGHTING BATTERY UNITS; PIONEER AND SQUARE 'D' CANADA. AS SHOWN. EQUIPMENT TERMINATIONS WITH BUSHINGS AND CLEARLY IDENTIFY
SPRAY PAINTING COVERS IN ACCORDANCE WITH FOLLOWING COLOUR SCHEDULE:
CORRESPONDING CREDIT. CONSULTANT HAS SOLE DISCRETION IN ACCEPTING 16.1.7 FIRE ALARM SYSTEM COMPONENTS; EACH RUN. PROVIDE FISH WIRES IN EMPTY CONDUIT.
20.3.1 LIGHTING - YELLOW
ANY PROPOSED SUBSTITUTION. INCLUDE IN BID PRICE ANY ADDITIONAL COSTS 16.1.8 PIPE TRACING AND ACCESSORIES; 29. DISTRIBUTION TRANSFORMERS
20.3.2 NORMAL POWER - BLUE
FOR CHANGES TO ASSOCIATED OR ADJACENT WORK RESULTING FROM PROVISION 16.1.9 SURFACE METAL RACEWAY; 34.3 CONFIRM EXACT REQUIREMENTS AND LOCATIONS OF EQUIPMENT WITH
20.3.3 ESSENTIAL POWER - ORANGE
OF PRODUCTS SUPPLY BY MANUFACTURER OTHER THAN BASE SPECIFIED 16.1.10 ELECTRIC HEATING UNITS; 29.1 PROVIDE HAMMOND MANUFACTURING TYPE 'DI', 3 PHASE DRY TYPE OWNER AND SYSTEM INSTALLER PRIOR TO ROUGH-IN.
20.3.4 FIRE ALARM - RED
MANUFACTURER. 16.1.11 LOW VOLTAGE LIGHTING CONTROL COMPONENTS; TRANSFORMERS AS SIZED ON DRAWINGS AND IN ACCORDANCE WITH CSA
16.1.12 OUTSIDE LIGHTING CONTROL COMPONENTS; STANDARD C9-M1981 REQUIREMENTS AND COMPLETE WITH SPRINKLER-PROOF 35. LUMINAIRES
20.4 WHERE REQUIRED, SUPPLY ACCESS DOORS OF MINIMUM NO. 12 GAUGE. PRIME
10. WARRANTY 16.1.13 ELECTRIC HEATING CABLE FOR PIPE TRACING; VENTILATED STEEL ENCLOSURE WITH REMOVABLE FRONT AND REAR PLATES AND
COATED STEEL COMPLETE WITH HINGES AND FRAMES TO GIVE ACCESS TO BOXES
16.1.14 FLOOR FITTINGS; CLASS 'H' COIL INSULATION. 35.1 PROVIDE LUMINAIRES AS SCHEDULED COMPLETE WITH ENERGY SAVING
AND CONDUCTOR JOINTS AND OTHER SIMILAR ELECTRICAL WORK WHICH MAY
10.1 WARRANT WORK TO BE IN STRICT ACCORDANCE WITH CONTRACT DOCUMENTS 16.1.15 SNOW & ICE MELTING SYSTEM COMPONENTS; BALLAST. CONFIRM FINISHES WITH CONSULTANT PRIOR TO ORDERING. PROVIDE
NEED MAINTENANCE OR REPAIR, BUT WHICH IS CONCEALED IN INACCESSIBLE
AND FREE FROM DEFECTS FOR 1 YEAR PERIOD FROM DATE OF WRITTEN 16.1.16 SERVICE POLES; 29.2 PROVIDE EACH TRANSFORMER COMPLETE WITH COPPER WINDINGS STACKED STANDARD LIFE LAMPS AS MANUFACTURED BY GE LIGHTING CANADA, PHILIPS
CONSTRUCTION. CONFIRM FINISHES WITH OWNER.
ACCEPTANCE BY CONSULTANT. REFER AND/OR REPLACE ANY SUCH DEFECTS 16.1.17 VOICE & DATA COMMUNICATION SYSTEM; LAMINATIONS OF SILICONE STEEL CORE SUITABLE LUGS OR PRESSURE TYPE LIGHTING OR GTE SYLVANIA. INCLUDE LAMP LISTING IN LUMINAIRE MANUALS.
WHICH APPEAR IN WORK WITHIN WARRANTY PERIOD, ORDINARY WEAR AND TEAR 16.1.18 SECURITY SYSTEM; TERMINALS 1 ABOVE AND 2 BELOW NORMAL - 2-1/2% FULL CAPACITY TAPS, AN
21. RECEPTACLES, SWITCHES AND FACE PLATES
AND WILFUL DAMAGE BY, OR CARELESSNESS OF OWNER'S STAFF OR AGENTS 16.1.19 NETWORK CABLING SYSTEM. INTEGRAL VIBRATION DAMPENING SYSTEM, ASA-61 ENAMEL FINISH AND ALUMINIUM 35.2 PROVIDE LUMINAIRES AS NOTED COMPLETE WITH ELECTRONIC BALLASTS.
EXCEPTED, WITHOUT ADDITIONAL COSTS INCURRED IN MAKING DEFECTIVE WORK I.D. NAMEPLATE. CONFIRM FINISHES WITH CONSULTANT PRIOR TO ORDERING. PROVIDE T8 (2950
21.1 PROVIDE HUBBELL CANADA CSA APPROVED SPECIFICATION GRADE AC QUIET
GOOD, INCLUDES REPAIR OR REPLACEMENT OF BUILDING FINISHES, OTHER 16.2 PROPERLY IDENTIFY SHOP DRAWING FOR REVIEW AND SHOW IN DETAIL LUMENS INITIAL, 3500K, MINIMUM CRI 85) LAMPS AS MANUFACTURED BY GE
ACTION TOGGLE TYPE, 20A, 120V-277V SWITCHES AND SPECIFICATION GRADE
MATERIALS OR DAMAGE TO OTHER EQUIPMENT CAUSED BY SUCH DEFECTS, OR BY EQUIPMENT AND MATERIALS. ENDORSE EACH DRAWING, INCLUDE COMPANY NAME 29.3 SECURE TRANSFORMERS IN PLACE AS SHOWN AND CONNECT COMPLETE ON LIGHTING CANADA, PHILIPS LIGHTING OR OSRAM SYLVANIA. INCLUDE LAMP LISTING
PREMIUM QUALITY DUPLEX NYLON CONSTRUCTION U-GROUND 15A-125V, 3W
AN ANGLE WALL MOUNTING BRACKET SUPPORT ASSEMBLY LOCATED IN LUMINAIRE MANUALS. ACCEPTABLE BALLAST MANUFACTURES ARE ADVANCE,
SUBSEQUENT REPLACEMENT OR REPAIRS. AND SUBMITTAL DATE. PROVIDE MANUALS AS INDEXED, IDENTIFIED HARD COVER
3-RING BINDERS COMPLETE WITH:
RECEPTACLES. DEVICES SHALL BE BACK AND SIDE WIRED. PROVIDE GRADE 18-8
TYPE 302/304 0.041" (1MM) THICK STAINLESS STEEL FACE PLATES WITH MATCHING
APPROXIMATELY 12" (300MM) BELOW CEILING. PROVIDE EACH SUPPORT ASSEMBLY
AND ADEQUATELY SECURE TO WALL AND/OR CEILING. PROVIDE VIBRATION
VALMONT, EBT AND MAGNETEK. ELECTRONIC BALLASTS SHALL BE ADVANCE
TRANSFORMER CO. (PHILIPS), ELECTRONIC ENERGY SAVING BALLAST AS FOLLOWS:
RENOVATION
11. INTERRUPTIONS TO AND SHUTDOWNS OF EXISTING SERVICES AND SYSTEMS 16.2.1 A COPY OF EACH 'REVIEWED' SHOP DRAWING; SCREWS. CONFIRM TYPE AND FINISH OF DEVICES WITH OWNER PRIOR TO
11.1 CO-ORDINATE AND PERFORM SHUTDOWNS AND INTERRUPTIONS TO EXISTING
16.2.2 EXPLANATIONS OF OPERATING PRINCIPLES AND SEQUENCES;
16.2.3 PART LISTS WITH NUMBERS;
ORDERING.
ISOLATION HANGERS AND/OR PADS TO ISOLATE VIBRATIONS. TEST AND CHECK
VOLTAGES AND MAKE REQUIRED ADJUSTMENTS. TRANSFORMERS LARGER THAN
35.2.1 CSA APPROVED AND ULC LISTED AND LABELLED;
35.2.2 COMPLY WITH FCC RULES AND REGULATIONS AND ANSI SPECIFICATION
FOR EXISTING
SYSTEMS AND SERVICES AT TIMES ACCEPTABLE TO OWNER. OBTAIN WRITTEN 16.2.4 RECOMMEND MAINTENANCE PRACTICES AND PRECAUTIONS; 75KVA SHALL BE SECURED TO CONCRETE PADS ON VIBRATION ISOLATION TYPE C62.41-1980/C62.45-87;
APPROVAL IN ADVANCE OF SHUTDOWN OR INTERRUPTION. INCLUDE FOR COSTS
OF PREMIUM TIME TO PERFORM WORK DURING NIGHTS, WEEKENDS OR OTHER
16.2.5 COPIES OF INSPECTION CERTIFICATES ISSUED BY GOVERNING
AUTHORITIES;
21.2 WHERE SHOWN, PROVIDE HUBBELL NO. IG5262, 15A-125V, ULC LISTED, 2-POLE
3W, ORANGE COLOURED, SPECIFICATION GRADE ISOLATED GROUND DUPLEX
PADS. 35.2.3 RAPID START IN ACCORDANCE WITH ANSI SPECIFICATION C82.1;
35.2.4 CLASS A SOUND RATING;
CULTURAL
RECEPTACLE COMPLETE WITH STAINLESS STEEL COVER PLATE AND MATCHING
TIME OUTSIDE OF NORMAN WORKING HOURS, AS NECESSARY TO MAINTAIN
SERVICES IN OPERATION OR WITH MINIMUM INTERRUPTIONS AND TO COMPLY WITH
16.2.6 WIRING AND CONNECTION DIAGRAMS;
16.2.7 COPIES OF PANELBOARD DIRECTORIES.
SCREWS.
29.4 ACCEPTABLE MANUFACTURERS INCLUDE HAMMOND, FEDERAL PIONEER AND
POLYGON INDUSTRIES.
35.2.5 CAPABLE OF STARTING LAMPS DOWN TO 50 DEGREES F. (10 DEGREES C);
35.2.6 TOTAL HARMONIC DISTORTION SUMMARIZING SECOND TO THIRTY-NINTH CENTER
OWNER'S REQUIREMENTS. NOTE: WORK ASSOCIATED WITH SHUTDOWNS AND HARMONIC NOT GREATER THAN 20%;
21.3 WHERE SHOWN, PROVIDE HUBBELL NO. GF5252, 15A-125V ULC LISTED CLASS A ,
INTERRUPTIONS WILL BE CARRIED OUT AS CONTINUOUS OPERATIONS TO MINIMIZE 16.3 PROVIDE 2 SETS OF MANUALS. CONFIRM EXACT QUANTITY AND METHOD OF 30. GROUNDING 35.2.7 MINIMUM POWER FACTOR OF 0.95 AND BALLAST FACTOR OF AT LEAST 0.85;
SHUTDOWN TIME AND TO REINSTATE SYSTEMS AS SOON AS POSSIBLE AND PRIOR SUBMISSION WITH CONSULTANT.
GROUP ONE, 2-POLE, 3W IVORY COLOURED SPECIFICATION GRADE, GROUND FAULT
35.2.8 LAMP CURRENT CREST FACTOR NOT GREATER THAN 1.7; ELECTRICAL
INTERRUPTER DUPLEX RECEPTACLE, COMPLETE WITH STAINLESS STEEL COVER
TO SHUTDOWN, ENSURE MATERIALS AND LABOUR REQUIRED TO COMPLETE WORK 30.1 PROVIDE COMPLETE SYSTEM OF GROUNDING WHICH COMPLIES WITH 35.2.9 FREQUENCY OF OPERATION BETWEEN 20 KHZ MINIMUM TO 60 KHZ MAXIMUM
FOR WHICH SHUTDOWN IS REQUIRED ARE AVAILABLE AT SITE. 17. GENERAL CONDUIT AND CONDUCTOR INSTALLATION REQUIREMENTS
PLATE AND MATCHING SCREWS.
REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION FOR ELECTRICAL WORK. WITHOUT VISIBLE FLICKER.
SPECIFICATION
INCLUDE REQUIRED GROUNDING SECTIONS OF ELECTRICAL SAFETY AUTHORITY 35.2.10 5 YEAR FULL REPLACEMENT PARTS AND LABOUR INCLUDED WARRANTY.
21.4 PROVIDE PERMANENTLY LABELLED, SELF ADHESIVE IDENTIFICATION TAPE ON
12. CUTTING, PATCHING AND CORE DRILLING 17.1 INSTALL CONDUIT AND CONDUCTORS CONCEALED TO DEGREE MADE POSSIBLE INSIDE AND OUTSIDE OF EACH DEVICE OUTLET FACE PLATE IDENTIFYING LOCATION
CODE. CONNECT GROUNDING CONDUCTORS TO EXISTING BUILDING GROUND SCALE: SEE NOTE
BY FINISHES AND PROVED INSTALLATIONS IN ACCORDANCE WITH ELECTRICAL SYSTEM. PROVIDE SEPARATE INSULATED GROUND WIRE FOR EACH ISOLATED
12.1 DO CUTTING, PATCHING AND CORE DRILLING OF EXISTING BUILDING REQUIRED SAFETY CODE AND LOCAL GOVERNING AUTHORITIES. PLAN AND CO-ORDINATE
FROM WHERE EACH DEVICE IS FED.
GROUND CIRCUIT. DRAWN:GC
FOR INSTALL OF WORK. PERFORM CUTTING IN NEAT AND TRUE FASHION, WITH LOCATIONS AND ROUTING OF SERVICES WITH TRADES PRIOR TO INSTALLATION. IN CHECKED:GC
21.5 ACCEPTABLE MANUFACTURERS INCLUDE LEVITON, PASS AND SEYMOUR,
PROPER TOOLS AND EQUIPMENT TO OWNER'S APPROVAL. AREAS WHERE A MULTIPLICITY OF SERVICES OCCURS, PREPARE DETAIL DRAWINGS ARROW-HART AND BRYANT. APPROVED:
AND SUBMIT TO CONSULTANT FOR REVIEW PRIOR TO START OF AFFECTED WORK.
PROJECT NO:160603
DWG. NO.
E9
- DO NOT SCALE DRAWINGS.
41.3 WESTINGHOUSE CANADA, CSA APPROVED MAGNETIC, FULL VOLTAGE 46. CABLE TRAY - CONTRACTOR MUST CHECK AND VERIFY DRAWINGS
35.3 THOROUGHLY REVIEW CEILING TYPES, FINISHES, AND CONSTRUCTION DETAILS 49. VOICE & DATA AGAINST SPECIFICATIONS AND REPORT ANY
WITH OWNER BEFORE PLACING LUMINAIRE ORDERS AND ENSURE REQUIRED CONTACTORS, SUITABLE FOR APPLICATION COMPLETE WITH SPRINKLER-PROOF DISCREPANCIES TO THE ENGINEER BEFORE PROCEEDING.
MOUNTING ASSEMBLIES, RINGS AND SIMILAR FEATURES ARE INCLUDED. INCLUDE ENCLOSURE AND RATING AS SHOWN ON DRAWINGS. 46.1 PURSLEY INC. TOTALLY ENCLOSED 6" (150MM) WIDE X 6" (150MM) HIGH CABLE 49.1 THE VOICE & DATA SYSTEM COMPONENTS SHALL BE SUPPLIED AND INSTALLED - CONTRACTOR SHALL SITE VISIT AND BE FAMILIAR WITH
FOR ASSEMBLY, MOUNTING AND ADJUSTING OF LUMINAIRES COMPLETE WITH TRAY MANUFACTURED FROM MINIMUM NO. 16 GAUGE GALVANIZED STEEL AND BY A BELDEN/NORDX/CDT CERTIFIED SYSTEM VENDOR. THE PRODUCTS AND THE JOB SITE. VERIFY ALL SITE SERVICES RELATED TO THE
SCOPE OF WORK.
WIRING, CONNECTIONS, HANGERS ALIGNERS, BOX COVERS AND ACCESSORIES FOR 41.4 PROVIDE TIME SWITCH AND PHOTOCELL IN LOCATIONS AS SHOWN. CONFIRM SUPPLIED IN 10' (3M) LENGTHS, COMPLETE WITH TWO (2) 5' (1.5M) LENGTH HINGED INSTALLATION MUST COMPLY WITH BELDEN/NORDX/CDT'S REQUIREMENTS AND
COMPLETE SAFE, FULLY OPERATION ASSEMBLY. CAREFULLY CO-ORDINATE LOCATIONS PRIOR TO ROUGH-IN. CONNECT PHOTOCELL AND TIME SWITCH TO COVERS. EACH LENGTH OF TRAY SHALL BE COMPLETE WITH COUPLING TO 1 END THUS BE PROVIDED WITH BELDEN/NORDX/CT'S 15 YEAR APPLICATION ASSURANCE - USE ONLY THE LATEST DRAWINGS.
LUMINAIRE INSTALLATION WITH WORK OF OTHER TRADES TO ENSURE NECESSARY CONTACTOR AND TO PANELBOARD CONTROLLING OUTSIDE LIGHTING. WHEN PREPUNCHED TO ALIGN WITH HOLES PRE-PUNCHED IN OTHER END OF THE PRODUCT WARRANTY. THE SELECTED CONTRACTOR MUST TEST AND CERTIFY THE - THESE DRAWINGS ARE TO BE READ IN CONJUNCTION
WORK IS COMPLETE, TEST SYSTEM AND ADJUST. PHOTOCELL SHALL SWITCH ADJACENT SECTION OF THE TRAY. 2 SECTIONS SHALL BOLT TOGETHER TOP, WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
RECESSING DEPTHS AND MOUNTING SPACE ARE PROVIDED. INSTALL LUMINAIRES INSTALLATION AND HONOUR MANUFACTURER'S WARRANTY PROGRAMS. PROVIDE FIRE PROTECTION PLANS UNLESS THEY ARE NOT
IN ACCORDANCE WITH APPLICABLE ARCHITECTURAL REFLECTED CEILING PLANS DESIGNATED OUTSIDE LIGHTING ON AND TIME SWITCH SHALL SWITCH LIGHTING BOTTOM, AND SIDE OPPOSITE COVERS SHALL BE PROVIDED WITH TEN (10) 1/2" TO CONSULTANT, A DOCUMENTED LETTER ATTESTING THE BELDEN/NORDX/CDT'S PRODUCED.
AND/OR WALL ELEVATIONS. CONFIRM LUMINAIRE LOCATIONS PRIOR TO ROUGH-IN. OFF. (13MM) DIAMETER KNOCKOUTS, SPACED 1' (300MM) APART FOR A TOTAL 30 CERTIFICATION OF CONTRACTOR REGARDING CATEGORY 5/6 (OWNER'S
SUPPORT LUMINAIRES DIRECTLY TO CEILING SLAB STRUCTURE, NOT TO CEILING KNOCKOUTS PER LENGTH OF TRAY. REQUIREMENT) CABLING INSTALLATIONS.
HANGERS, DUCTWORK, PIPING, CABLE TRAYS ETC.. 41.5 ACCEPTABLE MANUFACTURERS INCLUDE YORK CANADA AND INTERMATIC.
46.2 INSTALL AND HANG TRAY AT MAXIMUM 5' (1.5M) CENTRES IN ACCORDANCE 49.2 PROVIDE PRODUCTS AS FOLLOWS: NO. ISSUE DATE
36. WALL BOX DIMMERS 42. EMERGENCY LIGHTING BATTERY UNITS WITH THE MANUFACTURER'S PUBLISHED LITERATURE EMPLOYING UNISTRUT 49.2.1 CATEGORY 5/6, FT6 PLENUM RATED, 4 PAIR, 24 AWG, ULC LISTED AND
HANGERS. TERMINATE CONDUITS AT OR IN TRAY WITH PROPER GROMMETTED AND VERIFIED 1. ISSUED FOR REVIEW 08AUG.17
36.1 PROVIDE LUTRON ELECTRONICS CO. 'NOVA' SERIES, VOLTAGE STABILIZED, 42.1 PROVIDE LONG LIFE SEALED LEAD BATTERY UNITS. UNITS SHALL BE BUSHED TERMINATIONS. THE CABLE TRAY ROUTING SHOWN ON FLOOR PLANS IS UNSHIELDED TWISTED PAIR, COPPER CONDUCTOR WIRING; 2. ISSUED FOR REVIEW 14SEPT.17
SOLID STATE, SQUARE LAW DIMMING PRINCIPLE SIZED TO SUIT LOADS, COMPLETE WITH SOLID STATE CHARGER, AC LINE CORD AND PLUG SET NO. 18 GENERAL ONLY AND SHALL BE CAREFULLY CO-ORDINATED WITH WORK OF OTHER 49.2.2 BELDEN/NORDX/CDT NO. QNE3FN8/8A/AC(10) CATEGORY 5/6 DUAL MODULAR 3. ISSUED FOR REVIEW 29SEPT.17
INCANDESCENT WALL BOX DIMMERS, EACH COMPLETE WITH CALIBRATED LINEAR GAUGE STEEL CABINET AND WHERE SHOWN. CONNECT REMOTE LIGHTING HEADS TRADES. ADJUST LOCATION OR ROUTING AS MAY BE REQUIRED AND INCLUDE FOR DATA & VOICE JACK COMPLETE WITH FLUSH WALL MOUNTING FACE PLATE AND
COMPLETE, BACK TO BATTERY UNIT. CHARGE TO RESTORE BATTERIES TO FULL ALL OFFSETS NECESSARY FOR CO-ORDINATION. PROPERLY SECURE ADEQUATELY 4. ISSUED FOR REVIEW 4 OCT.17
SLIDE CONTROL WITH SILVER CONTACTS AND SILENT POSITIVE ON/OFF, FACE NO. PO07029 SERIES IDENTIFICATION LABELS;
PLATE, EMI AND RFI FILTERING. CONFIRM FINISH WITH CONSULTANT PRIOR TO CHARGE WITHIN 12 HOURS. SYSTEM TO HAVE OBC REQUIRE DURATION OF OUTPUT SUPPORT AND NEATLY HARNESS CONDUCTORS IN TRAY. SEAL CABLE TRAY 49.2.3 BELDEN/NORDX/CDT NO. QMB1X31A CONNECTOR MOUNTS WITH COVERS
5. ISSUED FOR REVIEW 10 OCT.17
ORDERING. CAPACITY FOR LOAD OF SYSTEM (BUT MINIMUM OF 30 MINUTES). MOUNT UNIT IN PENETRATIONS OF BUILDING FIRE BARRIERS BY MEANS OF ULC LISTED AND AND 4 N0. QCBIX-36DA CONNECTORS. DISTRIBUTION RINGS, DESIGNATION STRIPS; 6. ISSUED FOR TENDER 11 OCT.17
AREA AS SHOWN ON DRAWINGS AND PLUG UNIT INTO ADJACENT RECEPTACLE. LABELLED PACKING MATERIAL. IDENTIFICATION LABELS AND ALL REQUIRED ANCILLARY DEVICES.
36.2 INSTALL FLUSH WALL BOX DIMMERS IN ACCORDANCE WITH MANUFACTURER'S PROVIDE REMOTE LAMP HEADS WHERE SHOWN AND PROVIDE WIRING IN CONDUIT
REQUIREMENTS, WHERE SHOWN AND CONNECT TO CONTROL LIGHTING AS TO BATTERY UNIT. CONFIRM EXACT LOCATION. CIRCUIT RUN WIRING SIZES SHALL 46.3 ACCEPTABLE MANUFACTURERS INCLUDE ELECTROTRAY, PILGRAM TECHNICAL 49.3 PROVIDE 2 RUNS OF CABLING TO EACH DUAL JACK OUTLET.
INDICATED. CONFIRM EXACT LOCATIONS PRIOR TO ROUGH-IN EQUIPMENT. EACH BE IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS FOR VOLTAGE DROP PRODUCTS LTD. AND CANSTRUT INC.
DIMMER WITH FACE PLATE, CONFIRM FACE PLATE COLOUR PRIOR TO ORDERING. PROTECTION. TEST, CHECK AND ADJUST AS REQUIRED. ACCEPTABLE 49.4 CABLING MUST BE RUN IN RACEWAYS OR CONDUIT AND ADEQUATELY
WHEN INSTALLATION IS COMPLETE, CHECK AND TEST OPERATION OF EACH DIMMER MANUFACTURERS INCLUDE EMERGI-LITE AND DUAL-LITE. 47. LADDER TYPE CABLE TRAY SUPPORTED WITH PROPER CLAMPS OR HARNESS. IN ACCESSIBLE SUSPENDED
AND ADJUST AS REQUIRED. ENSURE EACH DIMMERS IS PROPERLY SIZED TO SUIT CEILING SPACES, CABLING IS NOT REQUIRED TO BE RUN IN CONDUIT, BUT MUST BE
CONNECTED LOAD. ACCEPTABLE MANUFACTURERS INCLUDE HUBBELL CANADA. 43. FLOOR FITTINGS 47.1 PURSLEY INC. OPEN LADDER CABLE TRAY MANUFACTURED FOR MINIMUM NO. NEATLY BUNDLED AND PROPERLY SUPPORTED. TAG AND LABEL BOTH ENDS OF
16 GAUGE GALVANIZED STEEL. TRAY SHALL HAVE MINIMUM CSA CLASS C1 LOAD CABLES AND LABEL JACKS IN ACCORDANCE WITH OWNER'S WRITTEN
37. ELECTRIC HEATING CABLE FOR PIPE TRACING AND ACCESSORIES 43.1 HUBBELL CANADA FULLY ADJUSTABLE, POKE-THROUGH ASSEMBLY FLOOR RATING. RUNG SPACING SHALL BE MAXIMUM 6" (150MM). TRAY SHALL BE INSTRUCTIONS. PROVIDE GROUNDING AS REQUIRED. INSTALL MOUNTS ON OBC
FITTING. 2 HOUR FIRE RATED, 2 PIECE DESIGN, CONTOURED DIE-CAST ALUMINIUM, COMPLETE WITH MOUNTING ANGLE BRACKETS, SUPPORTS ETC. TO PROVIDE FLAME SPREAD RATING PLYWOOD BACKBOARD WHERE SHOWN.
37.1 PROVIDE RAYCHEM CANADA, SELF-REGULATING ELECTRICAL HEAT TRACING SATIN CHROME FINISHED COVER, SEPARATE ABOVE FLOOR FITTING, WITH CARPET SYSTEM AS DETAILED ON DRAWINGS.
CABLES COMPLETE WITH THE FOLLOW: FLANGE LIFT COVER ASSEMBLY, FIRE STOPS, COLD SMOKE BARRIERS, JUNCTION 49.5 WHEN PREPARING CABLE FOR TERMINATION, STRIP AS LITTLE OUTER JACKET
37.1.1 5XL (5W) AND 8XL (8W) (AS REQUIRED) - 1 STRIP SELF-REGULATING HEAT BOX AND AS REQUIRED KNOCKOUTS. 47.2 INSTALL AND SUPPORT TRAY IN ACCORDANCE WITH THE MANUFACTURER'S AS POSSIBLE AND DO NOT UNTWIST CABLE PAIRS MORE THAN 1/2\ (13MM) FROM
TRACING CABLE IN LENGTHS EQUAL TO PIPE LENGTHS PLUS 10%; PUBLISHED LITERATURE EMPLOYING UNISTRUT HANGERS. TERMINATE CONDUITS END. DO NOT SPLICE CABLES.
37.1.2 REQUIRED POWER CONNECTION KITS, END SEALS, TEE KITS AND SPLICE 43.2 PROVIDE SEPARATE FLOOR FITTING ASSEMBLIES WITH EACH OF THE AT OR IN TRAY WITH PROPER GROMMETTED AND BUSHED TERMINATIONS. THE
KITS; FOLLOWING: CABLE TRAY ROUTING SHOWN ON FLOOR PLANS IS GENERAL ONLY AND SHALL BE 49.6 UPON COMPLETION OF INSTALLATION, TEST ENTIRE STRUCTURAL CABLING
43.2.1 TWO SPECIFICATION GRADE DUPLEX 15A 125V RECEPTACLES; CAREFULLY CO-ORDINATED WITH WORK OF OTHER TRADES. ADJUST LOCATION OR SYSTEM AND PROVIDE DOCUMENTATION OF TEST RESULTS TO CONSULTANT.
43.2.2 TWO TELEPHONE & DATA COVER PLATES WITH GROMMETTED OPENINGS; ROUTING AS MAY BE REQUIRED AND INCLUDE FOR ALL OFFSETS NECESSARY FOR TESTING SHALL INCLUDE BUT NOT LIMITED TO THE FOLLOWING:
37.1.4 CONTRACTOR TO ENERGIZE HEATING CABLE CIRCUITS (UPON ACTIVATION 43.2.3 TWO SPECIFICATION GRADE ISOLATED GROUND DUPLEX 15A 125V CO-ORDINATION. PROPERLY SECURE, ADEQUATELY SUPPORT AND NEATLY 49.6.1 CABLE LENGTH;
OF THERMOSTAT). PROVIDE MANUAL OVERRIDE SWITCH FOR DE-ENERGIZATION RECEPTACLES. HARNESS CONDUCTORS IN TRAY. SEAL CABLE TRAY PENETRATIONS OF BUILDING 49.6.2 ATTENUATION;
DURING SUMMER MONTHS. FIRE BARRIERS BY MEANS OF ULC LISTED AND LABELLED PACKING MATERIAL. 49.6.3 END TO END CONTINUITY;
43.3 PROVIDE POKE-THROUGH ASSEMBLY IN LOCATIONS SHOWN ON DRAWINGS. 49.6.4 OPENS OR SHORTS;
37.2 APPLY HEATING CABLE LINEARLY (WITHOUT SPIRALLING) ON PIPE AFTER PIPE PROVIDE WIRING IN CONDUIT IN ACCORDANCE WITH MANUFACTURER'S 47.3 ACCEPTABLE MANUFACTURERS INCLUDE ELECTROTRAY, PILGARAM 49.6.5 PAIR POLARITY'
HAS BEEN SUCCESSFULLY PRESSURE TESTED. SECURE HEATING CABLE TO PIPE REQUIREMENTS. INSTALL AND MOUNT DEVICES THROUGH SLAB IN ACCORDANCE TECHNICAL PRODUCTS LTD., CANSTRUT AND NEPCO.
WITH CABLE TIES. AFTER INSTALLATION, TEST CABLE WITH 1000 VDC MEGGER. WITH MANUFACTURER'S INSTRUCTIONS. NOTE: INSTALL CONDUCTORS 49.7 INCLUDE COSTS FOR CONNECTION AND RE-TESTING OF DEFECTIVE WIRING
MINIMUM INSULATION RESISTANCE SHOULD BE 20 TO 1000 MEGAOHMS CONNECTED TO FLOOR FITTING IN CEILING SPACE OF FLOOR BELOW. 48. SECURITY SYSTEM COMPONENTS (IF APPLICABLE-BY OTHERS) AND/OR COMPONENTS FOUND.
REGARDLESS OF LENGTH. INSTALL CABLE IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS, TABLE NO. 1 (OBTAINED FROM THE 43.4 ACCEPTABLE MANUFACTURERS INCLUDE WIREMOLD CANADA AND THOMAS 48.1 INTERCON SECURITY LTD. (TEL. 416-229-6811) INTEGRATED ACCESS CONTROL 49.8 SYSTEM SHALL COMPLY WITH REQUIREMENTS OF APPLICABLE CODES
CONSULTANT) AND WITH MAXIMUM CIRCUIT LENGTH OF 150' (45M) FOR 15A 1P AND BETTS. SYSTEM BASED ON THE 'PASS PLUS' SYSTEM SERIES COMPONENTS. SYSTEM INCLUDING T1A/E1A T568A/B, TS836 AND T6840.
BREAKER (BASED ON START-UP TEMPERATURE OF 40 DEGREES F. (4.4 DEGREES C) SHALL BE FULLY COMPATIBLE AND CONNECTED TO EXISTING CENTRAL
WITH 120V SUPPLY. 44. SNOW & ICE MELTING SYSTEM COMPONENTS (NOT APPLICABLE) PROGRAMMING UNIT. 49.9 PROVIDE CONDUIT WITH MINIMUM DIAMETER AS SHOWN. PROVIDE PULL
BOXES IN CONDUIT RUNS LONGER THAN 100' (30M) OR HAVING MORE THAN 2 - 90
37.3 PROVIDE LABELS AT START AND END OF RUNS, EVERY 15' (4.5M) AT ALL BENDS, 44.1 PROVIDE PYROTENAX OF CANADA 'PYROTENAX', CSA CERTIFIED, FACTORY 48.2 SYSTEM OPERATION: DEGREE BENDS. PULL BOX SIZES SHALL NOT BE LESS THAN 6 TIMES ENTERING
BRANCHES, RISERS, BOTH SIDES OF WALL & FLOOR PENETRATIONS AND AT ASSEMBLED AND TESTED HEATING CABLE AS SCHEDULED ON DRAWINGS, 48.2.1 THE ACCESS CONTROL UNIT (ACU) SHALL CONTROL PERSONNEL ACCESS CONDUIT IN LENGTH. LEAVE CONDUITS FREE AND CLEAR OF OBSTRUCTIONS AND
ACCESS DOORS. CONSISTING OF HEATING CABLE SPLICED TO COLD SECTION AND EQUIPPED WITH THROUGH REQUIRED DOORS. ACCESS THROUGH DOORS SHALL BE THROUGH THE TERMINATE AS SHOWN EQUIPMENT TERMINATIONS WITH BUSHINGS AND CLEARLY
TAIL LENGTHS AS REQUIRED, CONTROL COMPONENTS AND REQUIRED USE OF WIEGAND TYPE CARDS; IDENTIFY EACH RUN.
37.4 ACCEPTABLE MANUFACTURERS INCLUDE PYROTENAX OF CANADA AND INSTALLATION AND CONNECTION ACCESSORIES. EXACT TYPE AND RATING OF 48.2.2 THE ACU SHALL BE CONNECTED TO CARD READERS AT EACH CONTROLLED
CHROMALOX. CABLE MUST BE SUITABLE FOR APPLICATION AND BE RECOMMENDED FOR THE DOOR. THE ACU SHALL PROCESS INFORMATION READ FROM CARDS AND UNLOCK 49.10 CONFIRM EXACT REQUIREMENTS, FINISHES AND LOCATIONS OF EQUIPMENT
APPLICATION BY THE MANUFACTURER. THE APPROPRIATE CONTROLLED DOOR, IF THE CARD IS VALID FOR ACCESS WITH OWNER AND SYSTEM INSTALLERS PRIOR TO ROUGH-IN.
38. ELECTRIC BASEBOARD HEATERS THROUGH THAT DOOR, IF CARD IS NOT VALID, THE DOOR SHALL REMAIN LOCKED;
44.2 PROVIDE THE FOLLOWING: 48.2.3 THE ACU SHALL BE CAPABLE OF MONITORING THE POSITION OF EACH DOOR
38.1 PROVIDE CHROMALOX, 'BN' SERIES, CSA CERTIFIED, ELECTRIC BASEBOARD 44.2.1 HEATING CABLE CONSISTING OF: COPPER OR RESISTANCE ALLOW AT ALL TIMES AND DEFINE THE TIME THE DOOR SHALL REMAIN OPEN. THE SYSTEM
HEATERS COMPLETE WITH PAINTED STEEL ENCLOSURE, ALUMINIUM FINNED CONDUCTORS EMBEDDED IN HIGH COMPRESSED MAGNESSIUM-OXIDE INSULATION SHALL ALLOW SUCCESSIVE CARDS TO BE READ WITHOUT REQUIRING DOOR
HEATING ELEMENTS, TERMINAL WIRING BOXES AT EACH END JOINED BY AN COVERED BY COPPER ALLOY SHEATH. COLD LEAD-IN SECTIONS CONSISTING OF CLOSURE BETWEEN READS. THE DOOR SHALL AUTOMATICALLY BE RE-LOCKED
INTERNAL RACEWAY. LINEAR HIGH LIMIT THERMAL CUT-OUT AND INTEGRAL NON-HEATING MINERAL INSULATED COPPER SHEATHED CONDUCTOR; TAIL WHEN THE USER DEFINED UNLOCK DURATION EXPIRES, IRRESPECTIVE OF THE
ADJUSTABLE THERMOSTAT WITH PILOT LIGHT. SIZED ON DRAWINGS OR LENGTHS COMPLETE WITH INSULATED CONDUCTOR PIGTAILS AND THREADED DOOR POSITION. DOOR POSITION MONITOR SHALL BE PROVIDED BY FLUSH OR
SCHEDULES. CONFIRM FINISH WITH CONSULTANT PRIOR TO ORDERING. CONNECTORS FOR CONNECTION TO JUNCTION BOXES; PROTECTIVE HIGH DENSITY SURFACE MOUNTED MAGNETIC DOOR CONTACTS AS SHOWN ON DRAWINGS.
POLYETHYLENE JACKET; ELECTRIC DOOR LOCKING DEVICES SHALL BE 12VDC ELECTRIC STRIKES OR POWER
38.2 ACCEPTABLE MANUFACTURERS INCLUDE STELPRO AND QUELLET CANADA. 44.2.2 CORROSION RESISTANT MESH OR STAINLESS STEEL PRE-PUNCHED MAGNETIC LOCKS AS REQUIRED FOR THE DOOR TYPES SHOWN ON DRAWINGS;
STRAPPING OR CLIPS TO HOLD SNOW MELTING CABLES IN PLACE AND TO MAINTAIN 48.2.4 AN 'ANTI-PASS BACK' FEATURE SHALL BE PROVIDED TO PREVENT MULTIPLE
39. SURFACE METAL RACEWAYS DESIRED SPACING FOR APPLICATION; USE OF A CARD AT THE SAME DOOR WITHIN A USER DEFINABLE PERIOD OF TIME;
44.2.3 CAST ALUMINIUM FLUSH AND SURFACE MOUNTING JUNCTION BOXES 48.2.5 IT SHALL BE POSSIBLE (FROM THE ACU) TO MANUALLY COMMAND A
39.1 WIREMOLD CANADA 'G-4000 SERIES' CSA APPROVED, SURFACE METAL COMPLETE WITH GASKETTED LID AND ENTRIES SUITABLE FOR ENTRIES REQUIRED CONTROLLED DOOR TO LOCK, UNLOCK, OR LOCK OUT ALL CARDS IF NECESSARY;
RACEWAYS SHALL CONSIST OF 2 PIECE STEEL RACEWAY WITH DIVIDER AND SNAP AT EACH LOCATION. DO NOT LOCATE JUNCTION BOXES IN HEATED SURFACE OR 48.2.6 THE ACU SHALL FEATURE A MEANS OF ACTUATING AN ALARM OUTPUT AT
ON COVER COMPLETE WITH PRE-WIRED RECEPTACLES, GROMMETTED TELEPHONE BELOW GRADE OR IN LOCATION WHERE MOISTURE WILL ENTER BOX; EACH DOOR, WHERE REQUIRED. AN ALARM OUTPUT SHALL BE ACTIVATED FOR ALL
& DATA OUTLETS. CLAMPS, FITTINGS, ELBOWS, ETC. TO MAKE A COMPLETE 44.2.4 SURFACE WALL MOUNTING REMOTE BULB TYPE THERMOSTAT, CATALOGUE OR ANY OF THE FOLLOWING:
SYSTEM AS SHOWN ON DRAWINGS. CONFIRM FINISH WITH CONSULTANT PRIOR TO 48.2.6.1 ACCESS DENIED AT DOOR;
ORDERING. 48.2.6.2 DETECTION OF ILLEGAL USED OF DOOR;
COPPER CAPILLARY, SPST CONTACTS, MANUAL ON/OFF KEY SWITCH, MOISTURE 48.2.6.3 DETECTION OF INTRUDING;
39.2 ACCEPTABLE MANUFACTURERS INCLUDE CANADIAN ELECTRICAL RACEWAYS. AND DUST RESISTANT ENCLOSURE AND STAINLESS STEEL IDENTIFICATION LABEL. 48.2.6.4 DETECTION OF TAMPERING OF ACU CABINET;
48.2.7 THE ACU SHALL ALLOW CARD NUMBERS TO BE PROGRAMMED BY THE
40. LOW VOLTAGE LIGHTING CONTROL COMPONENTS 44.3 INSTALL ELECTRIC HEATING CABLES IN STRICT ACCORDANCE WITH LATEST SYSTEM USER. ALL CARD AND SYSTEM INFORMATION WHICH IS ENTERED INTO
EDITION OF PYROTENAX INSTALLATION RECOMMENDATIONS NO. 526 AND ENSURE THE ACU SHALL BE STORED IN A SOLID STATE POWER INDEPENDENT
40.1 PROVIDE GE LIGHTING CANADA 'TLC' SERIES CSA APPROVED, FACTORY CABLE TESTING RECOMMENDATIONS IS PERFORMED; (NON-VIOLATED) MEMORY IN ORDER TO ELIMINATE THE NEED TO RE-ENTER
PRE-WIRED, ASSEMBLED AND TESTED PANELS FOR CONTROL OF LOW VOLTAGE INFORMATION AFTER A POWER FAILURE OR SERVICING THE UNIT. THE
LIGHTING AS FOLLOWS: 44.4 INSTALL THERMOSTATS IN STRICT ACCORDANCE WITH LATEST EDITION OF PROGRAMMING FUNCTIONS SHALL REQUIRE ENTRY OF A PASSKEY CODE.
40.1.1 ENAMEL PAINTED STEEL TUB, INTERIOR MOUNTING PANEL WITH HINGED PYROTENAX INSTALLATION RECOMMENDATIONS NO. 535 . ENSURE EACH 48.4 INSTALLATION OF COMPONENTS:
KEY LOCKABLE SURFACE OR FLUSH MOUNTING COVER AND IDENTIFICATION CARD; THERMOSTAT IS CLEARLY IDENTIFIED; 48.4.1 CONNECT CARD READERS, DOOR ALARM CONTACTS, MAGNETIC LOCKS AND
40.1.2 SIZED SUITABLE FOR UP TO 48 RELAYS; EGRESS
40.1.3 CATALOGUE NO. RR9P, SPECIFICATION GRADE, HEAVY DUTY, 24V, 20A 44.5 PROVIDE LABELS AT START AND END OF RUNS. EVERY 15' (4.5M) AT ALL PUSH BUTTONS AS SHOWN ON THE DETAIL ON THE DRAWINGS. EXTEND WIRING
RATED RELAYS; BENDS, BRANCHES, RISERS, BOTH SIDES OF WALL & FLOOR PENETRATIONS AND AT IN CONDUIT TO
40.1.4 POWER SUPPLY AND RECTIFIERS AS REQUIRED; ACCESS DOORS. THE TELEPHONE CLOSET FOR CONNECTION TO THE BASE BUILDING SYSTEM;
40.1.5 CATALOGUE NO. RS2-22, 3A RATED, 24V, MOMENTARY CONTACT IVORY 48.4.2 CONNECT NEW FIRE ALARM PULL STATIONS TO BASE BUILDING FIRE ALARM
PUSH-BUTTON TYPE SWITCHES COMPLETE WITH PILOT LIGHTS; 45. SERVICE POLES SYSTEM.
40.1.6 SERIES RP2 TYPE 302 STAINLESS STEEL WALL PLATES, NUMBER OF GANG ALL ELECTRIC MAGNETIC LOCKS SHALL RELEASE OPEN ON FIRE ALARM SYSTEM
AS REQUIRED SUITABLE FOR SWITCHES, SPECIFIED AND COMPLETE WITH 45.1 PROVIDE WIREMOLD CANADA 'NP660' SERIES, CSA APPROVED, ULC LISTED ACTIVATION;
MOUNTING BRACKETS AND MATCHING SCREWS. CONFIRM FINISHES WITH SERVICE POLES IN LOCATIONS AS SHOWN COMPLETE WITH THE FOLLOW:
CONSULTANT; 45.1.1 2 COMPARTMENT (POWER AND COMMUNICATIONS) EXTRUDED ALUMINIUM 48.5 ENGAGE INTERCON SECURITY (TEL. 416-229-6811) TO PERFORM THE
40.17 WIRING IN CONDUIT. COLUMN BARRIERED INTERNALLY TO SEPARATE POWER WIRING FROM FOLLOWING SERVICES:
COMMUNICATIONS WIRING; 48.5.1 PERFORM FINAL CONNECTIONS FROM THE CARD READER TO THE ACU IN
40.2 FLUSH WALL MOUNT LOW VOLTAGE SWITCHES WHERE SHOWN COMPLETE 45.1.2 15 125V SINGLE RECEPTACLES FACTORY WIRED TO 10' (3M) U-GROUND THE
WITH MOUNTING BRACKETS AND STAINLESS STEEL FACE PLATES. INSTALL PANELS PLUG AND CORD SET; OR HARDWIRED TO CEILING CONNECTION BOX; TELEPHONE CLOSET;
ADJACENT TO LIGHTING LOAD PANELBOARD. PROVIDE DRIP SHIELDS FOR SURFACE 45.1.3 PROVISION FOR TELEPHONE CONDUCTORS; 48.5.2 PERFORM FINAL CONNECTIONS FROM THE FIRE ALARM AUXILIARY RELAY
MOUNTED PANELS. IDENTIFY CIRCUITS. CHECK COMPONENTS CONNECTIONS. 45.1.4 PROVISION FOR DATA COMMUNICATION CONDUCTORS; TO THE ACU IN
TEST OPERATION AND ADJUST OR REPAIR AS REQUIRED. 45.1.5 SNAP OPEN COVER ON COMMUNICATIONS SIDE OF POLE; THE TELEPHONE CLOSET;
45.1.6 BASE PLATE FOR SECURING POLE ASSEMBLY TO FLOOR AND PROVISIONS 48.5.3 VERIFY THE SEQUENCE OF OPERATION WITH CONSULTANT AND PROVIDE
40.3 ACCEPTABLE MANUFACTURERS INCLUDE DOUGLAS POWER EQUIPMENT. AT TOP FOR CLAMPING TO T-BAR CEILING SYSTEM AND TRIM PLATE TO COVER WRITTEN
CEILING OPENING. CONFIRMATION THAT THE SYSTEM IS FUNCTIONING PROPERLY.
41. OUTSIDE LIGHTING CONTROL COMPONENTS 45.1.7 PAINTED OR ANODIZED ALUMINIUM FINISH.
48.3 SYSTEM COMPONENTS:
41.1 PARAGON ELECTRIC, 4200-SZ SERIES 'ASTRO DIAL', CSA APPROVED, 120V 45.2 ACCEPTABLE MANUFACTURERS INCLUDE ELECTROTRAY, PUSLEY, NEPCO 48.3.1 ACU - INTERCON SECURITY LIMITED "PASS 100 PLUS" CARD READER
ADJUSTABLE SURFACE MOUNTED, TIME SWITCH COMPLETE WITH 40A CONTACTS, CANADA AND PILGRIM TECHNICAL PRODUCTS. CONTROLLER;
MANUAL ON/OFF LEVER, HEAVY DUTY SYNCHRONOUS TIMING MOTOR AND
LOCKABLE WEATHERPROOF ENCLOSURE. SWITCH TO AUTOMATICALLY ADJUST
48.3.2 CARD READERS - INTERCON SECURITY LIMITED FLUSH MOUNTED "PASS 176"
READ HEAD. READERS SHALL BE WIEGAND TYPE; RENOVATION
FOR SEASON CHANGES IN SUNRISE AND SUNSET AND COMPLETE WITH 'SKIP-A-DAY 48.3.3 DOOR ALARM CONTACTS - NORMALLY OPEN CONCEALED TYPE COMPLETE
FEATURE' AND SPRING WOUND CARRYOVER TO MAINTAIN OPERATION DURING
POWER FAILURE.
WITH S.P.D.T. SWITCH;
48.3.4 CEILING MOUNTED INFRARED MOTION DETECTORS TO ALL OW FREE
FOR EXISTING
41.2 PARAGON, CW200 SERIES, CSA APPROVED, 120V WEATHERPROOF,
HERMETICALLY SEALED, CADMIUM SULPHIDE, PHOTOCELL COMPLETE WITH
EGRESS;
48.3.5 CONDUIT AND WIRING AS DETAILED ON DRAWINGS; CULTURAL
48.3.6 SENTROL INC. SERIES 1079 OR EQUIVALENT, ELECTRIC MAGNETIC DOOR
COLOUR CODED LEADS AND THREADED PIPE NIPPLE. SYSTEM PROVIDED SUCH
THAT LOAD REMAINS ON IF CELL FAILS AND COMPLETE WITH THERMAL INERTIA
LOCKS;
48.3.7 FIR ALARM PULL STATIONS COMPLETE WITH AUXILIARY CONTACTS TO
CENTER
MINIMUM 15 SECOND TIME DELAY. MATCH EXISTING FOR CONNECTION TO BASE BUILDING FIRE ALARM SYSTEM TO