You are on page 1of 107

AGENCY APPROVAL

PROJECT DIRECTORY:
OWNER: MECHANICAL/ELECTRICAL ENGINEER:

BENSON MULTIFAMILY
BENSON APARTMENT FUND 1, LLC MORRISSEY ENGINEERING, INC.
6457 FRANCES STREET 4940 N. 118T STREET
OMAHA, NE 68106 OMAHA, NE 68164
402.952.4351 402.491.4144

DEVELOPER: LANDSCAPE ARCHITECT:


SAGE CAPITAL REAL ESTATE INVESTMENTS LAMP RYNEARSON & ASSOCIATES
5818 S. 75TH STREET 14710 W. DODGE ROAD, STE 100
OMAHA, NE 68114 OMAHA, NE 68154
402.952.4351 402.496.2498

ARCHITECT: STRUCTURAL ENGINEER:


HOLLAND BASHAM ARCHITECTS NIELSEN-BAUMERT ENGINEERING, INC.
119 S. 49TH AVENUE 10855 W. DODGE ROAD, STE 180
OMAHA, NE 68132 OMAHA, NE 68154
402.551.0800 402.496.4750

CIVIL ENGINEER: CONTRACTOR:


LAMP RYNEARSON & ASSOCIATES OVERLAND CONSTRUCTORS, INC.
14710 W. DODGE ROAD, STE 100 5036 S. 135TH STREET
OMAHA, NE 68154 OMAHA, NE 68137
402.496.2498 402.895.5510

6152 MILITARY AVENUE


INDEX OF DRAWINGS:
OMAHA, NE 68104
G1.01 COVER SHEET ARCHITECTURAL A5.19 2 BED "C" UNIT PLANS & INTERIOR ELEVATIONS STRUCTURAL MECHANICAL ELECTRICAL
G1.02 SYMBOLS & ABBREVIATIONS A0.01 ORIENTATION PLAN A5.51 ENLARGED STAIR PLANS S0.01 STRUCTURAL GENERAL NOTES M0.0 MECHANICAL GENERAL INFORMATION E1.00 LOWER LEVEL PLAN - LIGHTING
A0.11 CODE REVIEW PLANS A5.52 ENLARGED STAIR SECTIONS S1.00 FOUNDATION PLAN M1.01 LOWER LEVEL PLAN - HVAC E1.01 FIRST FLOOR PLAN - LIGHTING
A0.12 CODE REVIEW PLANS A5.53 ENLARGED STAIR SECTIONS S1.01 FIRST FLOOR FRAMING PLAN M1.02 FIRST FLOOR PLAN - HVAC E1.02 SECOND FLOOR PLAN - LIGHTING
CIVIL
A0.21 CODE REVIEW UNIT PLANS A5.54 ENLARGED ELEVATOR PLANS & SECTIONS S1.02 SECOND FLOOR FRAMING PLAN M1.03 SECOND FLOOR PLAN - HVAC E1.03 THIRD FLOOR PLAN - LIGHTING
C1.1 CIVIL LEGEND SHEET
A0.31 CODE DETAILS A5.55 FINISH SCHEDULE S1.03 THIRD FLOOR FRAMING PLAN M1.04 THIRD FLOOR PLAN - HVAC E1.04 FOURTH FLOOR PLAN - LIGHTING
C1.2 ORIGINAL TOPOGRAPHIC SURVEY
A1.00 LOWER LEVEL FLOOR PLAN A8.01 INTERIOR ELEVATIONS S1.04 FOURTH FLOOR FRAMING PLAN M1.05 FOURTH FLOOR PLAN - HVAC E2.00 LOWER LEVEL PLAN - POWER
C1.3 ZONING COMPLIANCE PLAN
A1.01 FIRST FLOOR PLAN S1.05 ROOF FRAMING PLAN M1.06 ROOF PLAN - MECHANICAL E2.01 FIRST FLOOR PLAN - POWER
C1.4 REMOVAL PLAN
A1.02 SECOND FLOOR PLAN S3.01 FRAMING DETAILS M2.00 UNGROUND PLUMBING E2.02 SECOND FLOOR PLAN - POWER
C1.5 GRADNING PLAN
A1.03 THIRD FLOOR PLAN M2.01 LOWER LEVEL PLAN - PLUMBING E2.03 THIRD FLOOR PLAN - POWER
C1.6 PAVING PLAN
A1.04 FOURTH FLOOR PLAN M2.02 FIRST FLOOR PLAN - PLUMBING E2.04 FOURTH FLOOR PLAN - POWER
C1.7 UTILITY PLAN
A1.11 ROOF PLAN M2.03 SECOND FLOOR PLAN - PLUMBING E2.05 ROOF PLAN - POWER
C1.8 LANDSCAPE PLAN
A1.20 LOWER LEVEL REFLECTED CEILING PLAN M2.04 THIRD FLOOR PLAN - PLUMBING E3.01 ENLARGED ELECTRICAL PLANS
A1.22 SECOND FLOOR REFLECTED CEILING PLAN M2.05 FOURTH FLOOR PLAN - PLUMBING E3.02 ENLARGED ELECTRICAL PLANS
A1.23 THIRD FLOOR REFLECTED CEILING PLAN M3.01 ENLARGED PLANS - HVAC E4.01 ELECTRICAL RISER DIAGRAM

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


A1.24 FOURTH FLOOR REFLECTED CEILING PLAN M3.02 ENLARGED PLANS - HVAC E4.02 ELECTRICAL SCHEDULES No. Description Date
A1.30 LOWER LEVEL FLOOR FINISH PLAN M3.03 ENLARGED PLANS - PLUMBING E4.03 ELECTRICAL SCHEDULES
A1.31 FIRST FLOOR FINISH PLAN M3.04 ENLARGED PLANS - PLUMBING E5.01 ELECTRICAL DETAILS
A1.32
A1.33
SECOND FLOOR FINISH PLAN
THIRD FLOOR FINISH PLAN
M4.01
M5.01
WASTE AND VENT RISER DIAGRAMS
MECHANICAL DETAILS
E5.02 ELECTRICAL DETAILS
SAGE
A1.34
A2.01
FOURTH FLOOR FINISH PLAN
PARTITION TYPES
M5.02
M6.01
MECHANICAL DETAILS
MECHANICAL SCHEDULES
DEVELOPMENT
A2.11
A2.31
DOOR & FRAME TYPES & SCHEDULE
ROOM FINISH SCHEDULE
M6.02
M7.01
MECHANICAL SCHEDULES
PLUMBING FIXTURE SCHEDULE
GROUP
A3.01 BUILDING AXONOMETRICS / PERSPECTIVES
A3.11 BUILDING ELEVATIONS
A3.12
A3.13
BUILDING ELEVATIONS
BUILDING ELEVATIONS BENSON
A3.31
A4.01
BUILDING SECTIONS
WALL SECTIONS MULTIFAMILY
A4.02 WALL SECTIONS
A4.03 WALL SECTIONS
A5.01 ENLARGED PATIO PLAN
A5.02 ENLARGED PLANS
A5.11 STUDIO "A" UNIT PLANS & INTERIOR ELEVATIONS
A5.12 STUDIO "B" UNIT PLANS & INTERIOR ELEVATIONS
A5.13 JUNIOR UNIT PLANS & INTERIOR ELEVATIONS COVER SHEET
A5.14 1 BED "A" UNIT PLANS & INTERIOR ELEVATIONS
A5.15 1 BED "B" UNIT PLANS & INTERIOR ELEVATIONS
A5.16 1 BED "C" UNIT PLANS & INTERIOR ELEVATIONS
A5.17 2 BED "A" UNIT PLANS & INTERIOR ELEVATIONS
A5.18 2 BED "B" UNIT PLANS & INTERIOR ELEVATIONS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
ELIM NSTRU DATE: 8/26/19

8/27/2019 10:54:52 AM
R
P RC O
O
OTF
N C COPYRIGHT 2018

8/26/19
SHEET: G1.01
AGENCY APPROVAL

GENERAL NOTES
1. THE GENERAL CONTRACTOR SHALL VERIFY THE EXISTING
DIMENSIONS AND CONDITIONS SHOWN ON THE DRAWINGS PRIOR
TO COMMENCEMENT OF THE WORK. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO COORDINATE INSTALLATION
OF NEW WORK WITHIN THESE EXISTING CONDITIONS.
DEVIATIONS IN THE EXISTING CONDITIONS OR DIMENSIONS
INDICATED SHALL BE COORDINATED WITH THE ARCHITECT AND
OWNER IN ORDER TO MODIFY THE DRAWINGS ACCORDINGLY.

STANDARD ABBREVIATIONS MATERIAL SYMBOLS REFERENCE SYMBOLS


A/C AIR CONDITIONING CST CONCRETE - STAINED HD HEAVY DUTY OPNG OPENING SST SIMULATED STONE
EARTH WORKS (SECTION / DETAIL)
A/E ARCHITECT/ENGINEER CSWK CASEWORK HDBD HARDBOARD OPP OPPOSITE SSV SOLID SURFACE VENEER
AB ANCHOR BOLT CT CERAMIC TILE HDWD HARDWOOD OPT OPTIONAL ST STREET/STONE
AC INSUL ACOUSTIC INSULATION CTV CABLE TELEVISION HDWR HARDWARE ORIG ORIGINAL STAG STAGGERED NO
DETAIL REFERENCE
AC PLAS ACOUSTIC PLASTER DBL DOUBLE HIWC HIGH IMPACT WALL COVERING P PAINT STD STANDARD EARTH GRANULAR FILL SHT
ACC ACCESSIBLE DEMO DEMOLISH/DEMOLITION HLB HORIZONTAL LOUVER BLINDS PBO PARTICLEBOARD STL STEEL
ACMU ARCHITECTURAL CONRETE MASONRY DEPT DEPARTMENT HM HOLLOW METAL PC PRECAST CONCRETE STL PL STEEL PLATE
UNIT
CONCRETE (SECTION / DETAIL)
DET DETAIL HORIZ HORIZONTAL PERF PERFORATED STRUCT STRUCTURAL
ACOUS ACOUSTICAL DF DRINKING FOUNTAIN HPC HIGH-PERFOMANCE COATINGS PERIM PERIMETER STRUCT STRUCTURAL STEEL NO
SECTION REFERENCE
AD AREA DRAIN DIM DIMENSION HR HAND RAIL PERP PERPENDICULAR STL SHT
ADDL ADDITIONAL DIST DISTANCE HT HEIGHT PH PHASE SUPPL SUPPLEMENT
CONCRETE CONCRETE - SAND / MORTAR/
ADDM ADDENDUM DIV DIVIDER HVAC HEATING, VENTILATION, PL PLATE/PROPERTY LINE SURF SURFACE PRECAST PLASTER
ADJ ADJUSTABLE DN DOWN ID INSIDE DIAMETER PLAM PLASTIC LAMINATE SUSP SUSPENDED
ADJC ADJACENT DO DITTO IE INVERT ELEVATION PLYWD PLYWOOD SUSP CLG SUSPENDED CEILING
MASONRY (SECTION / DETAIL)
AF ACCESS FLOOR DPFG DAMPPROOFING IN INCH PNL PANEL SV SHEET VINYL
AFF ABOVE FINISHED FLOOR DR DOOR INSUL INSULATION POL POLISHED SY SQUARE YARD
AHU AIR HANDLING UNIT DS DOWNSPOUT INT INTERIOR POLY POLYSTYRENE SYM SYMBOL NO NO CROSS SECTION
CONCRETE - COMMON / FACE BRICK
AL ALUMINUM DW DISHWASHER JAN JANITOR POLYISO POLYISOCYANURATE SYMM SYMMETERICAL MASONRY UNIT SHT SHT REFERENCE

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


ALT ALTERNATE DWG DRAWING JST JOIST PR PAIR T TREAD
ANOD ANODIZED E EAST JT JOINT PREFAB PREFABRICATED T&B TOP AND BOTTOM
STONE (SECTION / DETAIL) No. Description Date
AP ACCESS PANEL EA EACH KO KNOCKOUT PRELIM PRELIMINARY T&G TONGUE AND GROOVE NO
APC ACOUSTIC PANEL CEILING EF EACH FACE LAV LAVATORY PROJ PROJECT TBA TOILET & BATH ACCESSORY ELEVATION REFERENCE
SHT
ARCH
AST
AV
ARCHITECT (URAL)
ARTIFICIAL STONE TILE
AUDIO VISUAL
EIFS
EJ
EL
EXT INSUL & FINISH SYSTEM
EXPANSION JOINT
ELEVATION
LB
LF
LH
POUND
LINEAR FOOT
LEFT HAND
PT
PTN
PVG
PORCELAIN TILE
PARTITION
PAVING
TBD
TC
TECH
TO BE DETERMINED
TOP OF CURB
TECHNICAL
STONE
- EXTERIOR
SAGE
METAL (SECTION / DETAIL)
AVE
AWP
B&B
AVENUE
ACOUSTIC WALL PANEL
BALLED AND BURLAPPED
ELEC
ELEV
ELECTRICAL
ELEVATOR
LHR
LIN
LEFT HAND REVERSE
LINEAR
PVMT
PWR
PAVEMENT
POWER
TEMP
TER
THK
TEMPORARY
TERRAZZO
THICK SHT
NO ELEVATION REFERENCE
- INTERIOR
DEVELOPMENT
EMER EMERGENCY LLH LONG LEG HORIZONTAL QT QUARRY TILE
BD
BLDG
BOARD
BUILDING
ENCL
ENGR
ENCLOSURE
ENGINEER
LLV
LN
LONG LEG VERTICAL
LINEOLEUM
QTY
QUAL
QUANTITY
QUALITY
THRU
TK BD
THROUGH
TACKBOARD
METAL ALUMINUM GROUP
BLK BLOCK EPS EXPANDED POLYSTYRENE LVL LEVEL R RISER/RADIUS TO TOP OF ROOM
BLKG BLOCKING EQ EQUAL LVR LOUVER RB RESILIENT BASE TOJ TOP OF JOIST WOOD (SECTION / DETAIL) NAME ROOM INDICATOR
BLKHD BULKHEAD EQ SP EQUALLY SPACED LVT LUXURY VINYL TILE RC RESIDENTIAL CONCRETE TOS TOP OF STEEL NO
BO BOTTOM OF EQUIP EQUIPMENT LW LIGHTWEIGHT RCP REFLECTED CEILING PLAN TOT TOTAL XX SF
BOT BOTTOM EQUIV EQUIVALENT MAINT MAINTENANCE RD ROOF DRAIN TOW TOP OF WALL
BOW
BR
BOTTOM OF WALL
BUMPER RAIL
EST
EW
ESTIMATE
EACH WAY
MAS
MATL
MASONRY
MATERIAL
RECD
RECT
RECEIVED
RECTANGULAR
TP
TRS
TOILET PARTITION
TRANSITION STRIP
FINISH ROUGH SHIM
NO
DOOR INDICATOR BENSON
BRG BEARING TS TUBE STEEL
BRG PL
BSMT
BEARING PLATE
BASEMENT
EWC
EXG
EXP
ELECTRIC WATER COOLER
EXISTING
EXPOSED
MAX
MDF
MDO
MAXIMUM
MEDIUM DENSITY FIREBOARD
MEDIUM DENSITY OVERLAY
REF
REINF
REM
REFERENCE
REINFORCEMENT
REMOVABLE
TV
TWC
TELEVISION
TEXTILE WALL COVERING PLYWOOD
MULTIFAMILY
BUR BUILT-UP ROOF EXPN EXPANSION MECH MECHANICAL REQ REQUIRED TYP TYPICAL
C&G CURB AND GUTTER EXT EXTERIOR MED MEDIUM REV REVERSE UNEX UNEXCAVATED INSULATION (SECTION / DETAIL) NO WINDOW TYPE INDICATOR
C/C CENTER TO CENTER EXTN EXTENSION MEMB MEMBRANE RF RUBBER FLOORING UNFIN UNFINISHED
CC CUBICLE CURTAIN F/F FACE TO FACE MET METAL RH RIGHT HAND UNO UNLESS NOTED OTHERWISE
CEM CEMENT FB FACE BRICK MEZZ MEZZANINE RHR RIGHT HAND REVERSE UTIL UTILITY
GRID LINE
CEM PLAS
CER
CEMENT PLASTER
CERAMIC
FD
FDN
FLOOR DRAIN
FOUNDATION
MFG
MFR
MANUFACTURING
MANUFACTURER
RM
RND
ROOM
ROUND
VAV
VCT
VARIABLE AIR VOLUME
VINYL COMPOSITION TILE
BATT / LOOSE FILL RIGID INSULATION GRID
SYMBOLS &
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
FE
FEC
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
MICRO
MIN
MICROWAVE
MINIMUM
RO
RS
ROUGH OPENING
ROLLER SHADES
VERT
VEST
VERTICAL
VESTIBULE
FINISHES (SECTION / DETAIL)
FIN. FLOOR
ELEVATION REFERNCE
ABBREVIATIONS
CFM CUBIC FEET PER MINUTE FF & E FIXT FURN & EQUIP MIR MIRROR RSA RESILIENT STAIR ACCESSORIES VLB VERTICAL LOUVER BLINDS EL. 100'-0"
CG CORNER GUARD FFE FINISH FLOOR ELEVATION MISC MISCELLANEOUS RT RUBBER TILE VOL VOLUME
CI CAST IRON FIN FINISH MO MASONRY OPENING RV ROOF VENT VWC VINYL WALL COVERING GYPSUM WALLBOARD
CIP CAST IN PLACE PARTITION/WALL
FIXT FIXTURE MPFG MOISTUREPROOFING RVS REVERSE/REVISION W WEST NO
TYPE INDICATOR
CJ CONTROL JOINT
CL CENTER LINE
FL FLOOR MT METAL TILE S SOUTH/STAIN W/ WITH ELEVATIONS
FPFG FIREPROOFING N NORTH SC SOLID CORE/SPECIAL COATING W/O WITHOUT
CLG CEILING FRM FRAME NA NOT APPLICABLE SCHED SCHEDULE W/W WALL TO WALL
CLG HT CEILING HEIGHT WD WOOD (INCLUDES HARDWOOD AND 1 REVISION INDICATOR
FRP FIBERGLASS REINFOCED PLASTIC NIC NOT IN CONTRACT SCT STATIC CONTROL TILE
CLOS CLOSET FT FEET NO NUMBER SD STORM DRAIN WOOD VENEER) BRICK CONCRETE CONCRETE -
CLR CLEAR FTG FOOTING NOM NOMINAL SEAL SEALANT/ SEALER WDW WINDOW MASONRY UNITS
CMT CERAMIC MOSAIC TILE G GROUT NST NATURAL STONE TILE SECT SECTION WMT WALK-OFF MAT
CMU CONCRETE MASONRY UNIT GALV GALVANIZED NTS NOT TO SCALE SF SQUARE FOOT WPFG WATERPROOFING
CO CLEANOUT GB GRAB BAR O/O OUT TO OUT SIM SIMILAR WT WEIGHT
COL COLUMN GC GENERAL CONTRACTOR OA OVERALL SLV SLEEV E WWM WELDED WIRE MESH CONCRETE - PRECASTEIFS SHINGLES 119 SOUTH 49TH AVENUE
CONC CONCRETE GCMU GLAZED CMU OC ON CENTER SM SHEET METAL OMAHA, NEBRASKA 68132
CONF CONFERENCE GEN GENERAL/GENERATOR OD OUTSIDE DIAMETER SOFF SOFFIT (402)551-0800
CONT CONTINUOUS GFI GROUND FAULT INTERRUPTER OFCI OWNER FURNISHED CONTRACTOR SPEC SPECIFICATION
COORD COORDINATE GL GLASS/GLAZING INSTALLED SPKLR SPRINKLER
CP CONCRETE - POLISHED GMT GLASS MOSAIC TILE OFOI OWNER FURNISHED OWNER SQ SQUARE
ARY N PROJECT: 17073
CPT CARPET GT GLASS TILE INSTALLED SS STAINLESS STEEL I N CTIO
CS CONCRETE - SEALED OH OVERHEAD
LIM NSTRU DATE: 8/26/19

8/27/2019 10:54:55 AM
GWB GYPSUM WALL BOARD SSM SOLID SURFACE MATERIAL
CSMT CASEMENT OP OPERABLE PARTITION E
PR R CO
GYP GYPSUM SSNK SERVICE SINK
GYP PLAS GYPSUM PLASTER
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: G1.02
AGENCY APPROVAL

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

CIVIL LEGEND SHEET

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.1
AGENCY APPROVAL

14710 W. DODGE RD, STE. 100


OMAHA, NE 68154
402.496.2498
LampRynearson.com

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

ORIGINAL TOPOGRAPHIC
SURVEY - FOR
INFORMATION ONLY

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.2
AGENCY APPROVAL

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

ZONING COMPLIANCE
PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.2
AGENCY APPROVAL

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

REMOVAL PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.4
AGENCY APPROVAL

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

GRADING PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.5
AGENCY APPROVAL

·
·
·
·

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

PAVING PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.6
AGENCY APPROVAL

POST CONSTRUCTION STORMWATER MANAGEMENT PLAN PROJECT INFORMATION

OMA-20190619-5045-P N/A N/A NOVEMBER 2019 NOVEMBER 2021


Project Number Assigned By PWD Grading Permit Project Number Assigned By PWD S&ID Number Estimated Start Date Estimated Completion Date

THE MILL N/A


Project Name Subdivision Name

6152 MILITARY AVENUE OMAHA NE 68104


Address City State Zip Code

N/A N/A N/A


City Council Resolution Number Granting Project Approval City Council Ordinance Number Granting Project Approval City Council Resolution/Ordinance Approval Date

GENERAL NOTES
1. Approval must be obtained from the City Of Omaha Public Works 8. All construction shall be as shown on these plans, any revisions
Department prior to the commencement of construction. The shall have the prior written approval of the DESIGNER and City
CONTRACTOR shall check with the INSPECTOR for City Of Of Omaha Public Works Department.
Omaha Public Works Department approval of the project before 9. Construction may require the disturbance of existing, drainage
starting work. and erosion control measures. The CONTRACTOR shall make
2. The CONTRACTOR and INSPECTOR must insure all impacted
government agencies (City of Omaha, Douglas County, State of
himself aware of the existing drainage and erosion control
measures prior to bidding this work. The function of these items
No. Description Date
Nebraska, Corps of Engineers, Papio – Missouri River Natural must be maintained throughout construction with emphasis
Resource District, United States Federal Government, etc.) have placed on restoring their integrity prior to any rainfall event.
granted all applicable permission to proceed with construction Erosion control improvements have been constructed on this site,
prior to mobilization. Furthermore, 48 hours prior to the
commencement of construction, The INSPECTOR must notify all
concerned parties that work will be preceding within each
including terraces, silt fencing, and temporary sediment basins.
The Contract or shall be responsible for prompt reconstruction of
any erosion control improvements disturbed by his operations.
SAGE
3.
impacted government agency jurisdictional boundary.
The CONTRACTOR must notify the INSPECTOR 48 hours prior
to all preconstruction meetings and 48 hours prior to the start of
any construction. 10.
All disturbed erosion control improvements shall be fully
reconstructed at the end of each working day prior to leaving the
site.
CONTRACTOR shall adjust all new and existing inlets, valve
DEVELOPMENT
4.

5.
Construction found to be unacceptable to the City Of Omaha
Public Works Department shall be removed and replaced.
The CONTRACTOR shall notify all impacted utility companies, 11.
boxes, manhole rims, and sewer clean outs, etc. to finish grade
as applicable whether or not they are shown on the plans.
The CONTRACTORS must adhere to good housekeeping best
GROUP
via One Call (402 -344-3565), 48 hours before work is started to management practices at all tim es. Good housekeeping best
verify utility locations. management practices focus on keeping the work site clean and
6. The existence and location of any overhead or underground orderly while handling materials and waste in a manner that
utility lines, pipes, or structures shown on these plans are eliminates the potential for pollutant runoff.
obtained by a research of the available records. Existing utilities
are approximate and for record purposes. Existing utilities are
located on plans only for the convenience of the CONTRACTOR.
Existing utility service laterals may not be shown on the plans.
12. The construction documents (e.g., Contract, Bond, Insurance,
Specifications, and Plans) are essential and a requirement in one
part is as binding as though occurring in all. Thus, the
construction documents are complementary in nature. The
BENSON
The CONTRACTOR shall locate all underground and overhead
interference’s which may affect his operation during construction
and shall take all necessary precautions to avoid damage to
documents describe and provide the complete construction
project. The CONTRACTOR may not take advantage of any
apparent construction project errors or omissions. The
MULTIFAMILY
same. CONTRACTOR shall notify the INSPECTOR promptly of any
7. The CONTRACTOR shall take all precautionary measures omissions or errors. In the case of a discrepancy between parts
necessary to protect existing utility lines, structures and street of the construction documents, the most stringent construction
improvements which are to remain in place, from damage, and all methodology shall rule.
such improvements or structures damaged by the 13. The APPLICANT, INSPECTOR, and CONTRACTOR must insure
CONTRACTOR’S operations shall be repaired or replaced an acceptable As Built Certification Form with all applicable
satisfactory to the INSPECTOR and owning utility company. paperwork has been submitted to the CITY OF OMAHA PUBLIC
WORKS DEPARTMENT within (30) thirty days after completion
of construction.

PROJECT DESCRIPTION
THIS PROJECT CONSISTS OF CONSTRUCTING A
POST CONSTRUCTION STORMWATER MANAGEMENT PLAN
BASED UPON THESE MEASURES THIS PLAN IS IN
UTILITY PLAN
APARTMENT BUILDING. POST CONSTRUCTION WILL COMPLIANCE WITH THE REQUIREMENTS OF
BE HANDLED BY SAFL BAFFLES, FIRST DEFENSE, ARTICLE V OF CHAPTER 32, POST CONSTRUCTION
HYDRODYNAMIC SEPARATOR, AND CONDITIONED STORMWATER MANAGEMENT PLANS (PCSMP),
SOILS. WITHIN THE OMAHA MUNICIPAL CODE.

THIS PROJECT WILL MEET THE NO NET INCREASE IN


THE 2 YEAR, 10 YEAR, AND 100 YEAR STORM
EVENTS FROM POST TO PRE-CONSTRUCTION
APPLICANT DESIGNER
CONDITIONS ALONG WITH TREATING THE FIRST 21"
SAGE CAPITAL REAL ESTATE LAMP RYNEARSON OF RAINFALL FOR WATER QUALITY UTILIZING
PM : AARON MOSER PE: RANDY KUSZAK
14710 West Dodge Road CONDITIONED SOILS AND A FIRST DEFENSE
5818 S 75TH STREET HYDRODYNAMIC SEPARATOR.
Omaha, NE 68154
OMAHA, NE 68114 P: 402 - 496 - 2498
P: 402-952-4.51 F: 402 - 496 - 2730
AMOSER@SAGECAPITALINVESTMENTS.COM RANDY.KUSZAK@LAMPRYNEARSON.COM

INSPECTOR CONTRACTOR
LAMP RYNEARSON OVERLAND CONSTRUCTORS INC 119 SOUTH 49TH AVENUE
PE: RANDY KUSZAK PE: TIM HUBER
14710 West Dodge Road
Omaha, NE 68154
5036 S 135TH ST
Omaha, NE 68137
OMAHA, NEBRASKA 68132
P: 402 - 496 - 2498
F: 402 - 496 - 2730
P: 402 - 895 - 5510
TIM@OCI-INC.COM
(402)551-0800
RANDY.KUSZAK@LAMPRYNEARSON.COM

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.7
AGENCY APPROVAL

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

LANDSCAPE PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

PROJECT: 17073
DATE: 8/26/2019
14710 W. DODGE RD, STE. 100
OMAHA, NE 68154
402.496.2498
C COPYRIGHT 2017
LampRynearson.com

SHEET: C1.8
AGENCY APPROVAL

NW RADIAL HIGHWAY GENERAL ORIENTATION


PLAN NOTES
1. ORIENTATION PLAN IS FOR REFERENCE ONLY. SEE CIVIL
DRAWINGS FOR ADDITIONAL INFORMATION.

2. SEE CIVIL FOR FINISH FLOOR ELEVATIONS AND ACTUAL BUILDING


LOCATIONS

DN

UP

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

SAGE
OLD

DEVELOPMENT
GROUP
MIL
ITAR
Y

BENSON
AVE

MULTIFAMILY
.

19'-0 3/4" 19'-0 3/4" 9'-6 3/4"

ORIENTATION PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:49:46 AM
E
1 FIRST FLOOR ORIENTATION PLAN PR R CO
A0.01 T FO
NO C COPYRIGHT 2018

0' 5' 10' 15' 20'

8/26/19
SHEET: A0.01
AGENCY APPROVAL
IBC TRAVEL DISTANCES BUILDING 1 STATISTICS BUILDING 2.1 STATISTICS BUILDING 2.2 STATISTICS ENERGY CODE KEYED CODE PLAN NOTES
TAG USED FOR THIS SCHEDULE
PATH OF COMMON PATH OF TRAVEL TOTAL TRAVEL CLASSIFICATION OF OCCUPANCY: CLASSIFICATION OF OCCUPANCY: CLASSIFICATION OF OCCUPANCY:
ENERGY CODE (2009)
TRAVEL ID DISTANCE DISTANCE 2012 IBC SECTION 310.1 S-2, PARKING GARAGES 2012 IBC SECTION 310.1 R-2, APARTMENT HOUSES 2012 IBC SECTION 310.1 R-2, APARTMENT HOUSES 1 IBC 420.2 SEPARATION WALLS: WALLS SEPARATING DWELLING UNITS IN THE SAME
CLIMATE ZONE 5 BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN COMPLIANCE
0A 0' - 0" 167' - 0" WITH SECTION 708.
TYPE OF CONSTRUCTION: TYPE OF CONSTRUCTION: TYPE OF CONSTRUCTION:
0B 0' - 0" 130' - 0" 2012 IBC TABLE 601, TYPE IA 2012 IBC TABLE 601, TYPE VA 2012 IBC TABLE 601, TYPE VA BUILDING ENVELOPE REQUIRED PROVIDED 2 IBC 706 FIRE WALLS: EACH PORTION OF A BUILDING SEPARATED BY ONE OR MORE
1A 38' - 0" 110' - 6" FIRE WALLS THAT COMPLY WITH THE PROVISIONS OF THIS SECTION SHALL
VERTICAL FENESTRATION 40% MAX <INSERT>
1B 35' - 6" 120' - 0" BE CONSIDERED A SEPARATE BUILDING
FIRE RESISTANCE RATINGS - IA FIRE RESISTANCE RATINGS - VA FIRE RESISTANCE RATINGS - VA FRAMING MATERIALS OTHER THAN
1C 40' - 0" 93' - 0" METAL OR WITHOUT REINFOCEMENT U-0.35 U-0.35 3 IBC 706.4 FIRE WALLS: FIRE RESISTANCE RATING: FIRE WALLS SHALL HAVE A FIRE
REQ'D REQ'D REQ'D RESISTANCE RATING OF NOT LESS THAN THAT REQUIRED BY TABLE 706.4.
1D 71' - 6" 95' - 6" RATING RATING RATING OR CLADDING
COMPONENTS UL NO. IBC TABLE COMPONENTS UL NO. IBC TABLE COMPONENTS UL NO. IBC TABLE TABLE 706.4 REQUIRES 2-HOUR RATING FOR GROUP R-2 (TYPE V
1E 0' - 0" 71' - 0" CURTAIN WALL / STOREFRONT U-0.45 U-0.43
EXTERIOR BEARING WALLS 3 HR U904 601 EXTERIOR BEARING WALLS 1 HR U356 601 EXTERIOR BEARING WALLS 1 HR U356 601 CONSTRUCTION)
1F 0' - 0" 45' - 6"
INTERIOR BEARING WALLS 3 HR U904 601 INTERIOR BEARING WALLS 1 HR U904 601 INTERIOR BEARING WALLS 1 HR U904 601 ENTRANCE DOOR U-0.80 U-0.65 4 IBC 706.5, HORIZONTAL CONTINUITY: FIRE WALLS SHALL BE PERMITTED TO
2A 38' - 0" 110' - 6"
EXTERIOR NON-BEARING WALLS 2 HR 0 HR > 30' 602 EXTERIOR NON-BEARING WALLS 1 HR 0 HR > 30' 602 EXTERIOR NON-BEARING WALLS 1 HR 0 HR > 30' 602 ALL OTHER U-0.55 U-0.50 EXCEPTION TERMINATE AT THE INTERIOR SURFACE OF COMBUSTIBLE EXTERIOR
2B 35' - 6" 120' - 0" 1 SHEATHING OR SIDING PROVIDED THE EXTERIOR WALL HAS A FIRE
2C 42' - 6" 80' - 6" STRUCTURAL FRAME 3 HR SEE PLANS 601 STRUCTURAL FRAME 1 HR SEE PLANS 601 STRUCTURAL FRAME 1 HR SEE PLANS 601 SHGC - ALL FRAME TYPES 0.40 0.35 RESISTANCE RATING OF NOT LESS THAN 1 HOUR FOR A HORIZONTAL
2D 54' - 0" 127' - 0" PERMANENT PARTITIONS 0 HR - 601 PERMANENT PARTITIONS 0 HR - 601 PERMANENT PARTITIONS 0 HR - 601 SKYLIGHTS U-0.60 N/A DISTANCE OF NOT LESS THAN 4 FEET ON BOTH SIDES OF THE FIRE WALL.
3A 38' - 0" 110' - 6" ROOF INSULATION OPENINGS WITHIN SUCH EXTERIOR WALL SHALL BE PROTECTED BY
SHAFT 2 HR SEE PLANS 707.4 SHAFT 2 HR SEE PLANS 707.4 SHAFT 2 HR SEE PLANS 707.4
OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
3B 35' - 6" 120' - 0" FLOOR/CEILING ASSEMBLY 2 HR D923 601 FLOOR/CEILING ASSEMBLY 1 HR D923 601 FLOOR/CEILING ASSEMBLY 1 HR D923 601 INSULATION ENTIRELY ABOVE DECK R-20ci R-20ci THAN 3/4 HOUR.
3C 42' - 6" 80' - 6" ROOF/CEILING ASSEMBLY 2 HR D923 601 ROOF/CEILING ASSEMBLY 1 HR D923 601 ROOF/CEILING ASSEMBLY 1 HR D923 601 ATTIC AND OTHER R-38 R-38 5 IBC 708.3 FIRE PARTITIONS: FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE
3D 54' - 0" 127' - 0" WALLS, ABOVE GRADE RATING OF NOT LESS THAN 1-HOUR. TABLE 601, TYPE VA REQUIRES
STAIRWAYS 2 HR SEE PLANS 707.4 STAIRWAYS 2 HR SEE PLANS 707.4 STAIRWAYS 2 HR SEE PLANS 707.4
4A 38' - 0" 110' - 6" MASS R-11.4ci R-12 INTERIOR BEARING WALLS TO BE CONSTRUCTED TO MEET 1 HR RATED
CORRIDORS 0 HR SEE PLANS 1017.1 CORRIDORS 1/2 HR SEE PLANS 1017.1 CORRIDORS 1/2 HR SEE PLANS 1017.1
4B 35' - 6" 120' - 0" CONSTRUCTION.
SEE SHEET A2.01 FOR PARTITION TYPES DWELLING UNIT SEPERATION 1/2 HR SEE PLANS 708.3 DWELLING UNIT SEPERATION 1/2 HR SEE PLANS 708.3 METAL FRAMED R-13 + R-5.6ci R-19
4C 42' - 6" 80' - 6" 6 IBC 713.4 SHAFT ENCLOSURES: SHAFT ENCLOSURES SHALL HAVE A
4D 54' - 0" 127' - 0" SEE SHEET A2.01 FOR PARTITION TYPES SEE SHEET A2.01 FOR PARTITION TYPES WALLS, BELOW GRADE
OPAQUE DOORS
R-7.5ci <INSERT> FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR WHERE
CONNECTING LESS THAN 4 STORIES.
GENERAL CODE NOTES
ALLOWABLE AREA & HEIGHT - IA (BUILDING 1) 7 IBC 718.4.2 DRAFTSTOPPING: GROUP R-2 DRAFTSTOPPING SHALL BE PROVIDED IN
SWINGING U-0.70 U-0.65
FEET STORIES ALLOWABLE AREA & HEIGHT - VA (BUILDING 2.1) ALLOWABLE AREA & HEIGHT - VA (BUILDING 2.2) ATTIC SPACES OF GROUP R-2 BUILDINGS WITH THREE OR MORE DWELLING THIS SECTION SUMMARIZES THE APPLICABLE PROVISIONS OF THE
ROLL-UP OR SLIDING U-0.50 U-0.45
UNITS. DRAFTSTOPPING SHALL BE INSTALLED ABOVE, AND IN LINE WITH,
CODE REVIEW KEY BUILDING HEIGHT:
ALLOWABLE HEIGHT:
16'
UL
1
UL BUILDING HEIGHT:
FEET
44'
STORIES
4 BUILDING HEIGHT:
FEET
44'
STORIES
4
VESTIBULE YES/NO YES SLEEPING UNIT AND DWELLING UNIT SEPARATION WALLS THAT DO NOT
EXTEND TO THE UNDERSIDE OF THE ROOF SHEATHING ABOVE. EXCEPTION
CODES REGULATING DESIGN AND CONSTRUCTION OF THE PROPOSED
PROJECT.

SPRINKLER INCREASE: NO NO ALLOWABLE HEIGHT: 50' 3 ALLOWABLE HEIGHT: 50' 3 3 - IN OCCUPANCIES IN GROUP R-2 THAT DO NOT EXCEED 4 STORIES ABOVE 1. FOR ADDITIONAL INTERIOR PARTITION TYPES
MODIFIED ALLOWABLE HEIGHT: UL UL SPRINKLER INCREASE: YES YES SPRINKLER INCREASE: YES YES GRADE PLANE, THE ATTIC SPACE SHALL BE SUBDIVIDED BY DRAFTSTOPS AND INFORMATION, SEE A2.01.
EGRESS PATH OF TRAVEL:

EXIT ACCESS PATH OF TRAVEL


MODIFIED ALLOWABLE HEIGHT: 60' 4 MODIFIED ALLOWABLE HEIGHT: 60' 4 STORM SHELTER INTO AREAS NOT EXCEEDING 3,000 SQUARE FEET OR ABOVE EVERY TWO
DWELLING UNITS, WHICHEVER IS SMALLER. 2. SPRINKLER SYSTEM REQUIRED PER 2012 IBC SECTION 903.2.10.
ID

EGRESS PATH ID
BUILDING AREA:
LOWER LEVEL FLOOR AREA: 23,779 SF BUILDING AREA: BUILDING AREA: CALCULATIONS 8 IBC 1020.2 CORRIDOR WIDTH: THE MINIMUM CORRIDOR WIDTH SHALL BE NOT LESS
THAN 44", AND NOT LESS THAN 36" WITHIN A DWELLING UNIT.
NFPA 13 THROUGHOUT GARAGE AND RETAIL, NFPA 13R IN RESIDENTIAL.

GROSS BUILDING AREA: 23,779 SF FIRST FLOOR AREA: 8,898 SF FIRST FLOOR AREA: 10,661 SF 9 IBC 1023.1 INTERIOR EXIT STAIRWAYS: INTERIOR EXIT STAIRS SERVING AS AN EXIT 3. MAXIMUM DEAD END CORRIDOR LENGTH (IBC SECTION 1018.4) = 20'
ID COMMON PATH OF TRAVEL COMPONENT IN A MEANS OF EGRESS SYSTEM SHALL LEAD DIRECTLY TO
SECOND FLOOR AREA: 9,505 SF SECOND FLOOR AREA: 10,661 SF STORM SHELTER CALCULATIONS: 4. MAX TRAVEL W/ SPRINKLER (IBC TABLE <insert>) = <insert>
THE EXTERIOR OF THE BUILDING.
ALLOWABLE AREA: THIRD FLOOR AREA: 9,505 SF THIRD FLOOR AREA: 10,661 SF (PER OMAHA ZONING SECTION 55-787)
10 IBC 1030.1 EMERGENCY ESCAPE: TABLE 1006.2(1) APPLIES ONLY TO GROUP R-2
FIRE-RATED PARTITIONS/WALLS: TYPE IA: UL FOURTH FLOOR AREA: 9,505 SF FOURTH FLOOR AREA: 10,661 SF BUILDINGS WITH ONE EXIT. THE TABLE IS NOT APPLIED BECAUSE THERE 5. MAX COMMON PATH OF TRAVEL (IBC <INSERT>) = <insert>
(SEE PARTITION TYPES ON SHEET A2.01 FOR UL ASSEMBLY) (87) STUDIO & 1-BEDROOM UNITS x 5.5 S.F. = 478.5 S.F. REQ'D
FRONTAGE INCREASE: N/A GROSS BUILDING AREA: 37,413 SF GROSS BUILDING AREA: 42,644 SF ARE TWO OR MORE EXITS FROM EACH STORY

1HR: 1 1 1 1 SPRINKLER INCREASE: N/A (9) 2-BEDROOM UNITS x 11.0 S.F. = 99 S.F. REQ'D 11 IBC 1107.6.2 GROUP R-2: ACCESSIBLE UNITS AND TYPE B UNITS SHALL BE PROVIDED IN
GROUP R-2 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1107.6.2.1,
BUILDING STATISTICS
MODIFICATION ALLOWABLE AREA: UL ALLOWABLE AREA: ALLOWABLE AREA: TOTAL AREA REQUIRED = 577.5 S.F. 1107.6.2.2 AND 1107.7.4.
2HR: 2 2 2 2 APPLICABLE CODES:
GROUP R-2: 12,000 SF GROUP R-2: 12,000 SF 12 IBC 1006.1 FULL ACCESSIBLE UNITS: IN GROUP R-2 OCCUPANCIES, PROVIDE
TOTAL AREA PROVIDED = 585 S.F. 2012 INTERNATIONAL BUILDING CODE
3 HR: 3 3 3 3 FRONTAGE INCREASE: x 13% 13,560 SF FRONTAGE INCREASE: x 22% 14,640 SF ACCESSIBLE COMMUNICATION FEATURES AS NOTED IN SECTION 1006 AND
OCCUPANCY AND MEANS OF EGRESS AS SHOWN ON ELECTRICAL DRAWINGS. 2012 INTERNATIONAL FIRE CODE & 2000 NFPA LIFE SAFETY CODE
SPRINKLER INCREASE: x2 NOT USED SPRINKLER INCREASE: x2 NOT USED 2015 OMAHA PLUMBING CODE, CH 49 OMAHA MUNICIPAL CODE
SMOKE: S S S S OCCUPANT LOAD 13 IBC TYPE B UNITS: WHERE THERE ARE FOUR OR MORE DWELLING UNITS

BUILDING EXITS:
LOWER LEVEL 110
ADDITIONAL STORY INCREASE: x4 54,240 SF ADDITIONAL STORY INCREASE: x4 58,560 SF
PLUMBING FIXTURE 1107.6.2.2.2. INTENDED TO BE OCCUPIED AS A RESIDENCE IN A SINGLE STRUCTURE,
EVERY DWELLING UNIT INTENDED TO BE OCCUPIED AS A RESIDENCE SHALL
2012 INTERNATIONAL MECHANICAL CODE
2017 NATIONAL ELECTRICAL CODE
2009 INTERNATIONAL ENERGY CONSERVATION CODE
TOTAL OCCUPANCY 110

101
EXIT / STAIR NUMBER OCCUPANCY AND MEANS OF EGRESS OCCUPANCY AND MEANS OF EGRESS CALCULATIONS 14 IBC 1207.2
BE A TYPE B UNIT
AIR-BORNE SOUND: WALL, PARTITIONS AND FLOOR/CEILING ASSEMBLIES APPLICABLE HANDICAPPED CODES:
33" EXIT / STAIR WIDTH OCCUPANT LOAD OCCUPANT LOAD SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR 2012 IBC (INCLUDING ACC/ANSI A117.1-2003)
MEANS OF EGRESS SERVICE AREA SHALL HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT
0.2 LOAD FACTOR (IBC 1005.1) FIRST FLOOR: 142 FIRST FLOOR: 48 FAIR HOUSING ACT
REQUIRED PROVIDED PLUMBING FIXTURE CALCULATIONS LESS THAN 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
165 EXIT CAPACITY (NUMBER OF OCCUPANTS) SECOND FLOOR: 41 SECOND FLOOR: 48 ACCORDANCE WITH ASTM E 90.
EXITS 2 2 (PER OMAHA PLUMBING CODE) CLASSIFICATION OF OCCUPANCY:
THIRD FLOOR: 41 THIRD FLOOR: 48 CALCULATED BUILDING OCCUPANCY: 106 15 IBC 1207.3 STRUCTURE-BORNE SOUND: FLOOR/CEILING ASSEMBLIES BETWEEN 2012 IBC SECTION 310.4 R-2; APARTMENT HOUSES
EXIT WIDTH 44" 72"
FOURTH FLOOR: 41 FOURTH FLOOR: 48 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR 2012 IBC SECTION 311.3 S-2; PARKING GARAGES
FIRE RESISTANCE RATED FLOORS AND/OR ROOFS CORRIDOR WIDTH 44" 60" SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
TOTAL OCCUPANCY 265 TOTAL OCCUPANCY 192 OCCUPANTS WC UR LAV DF
STAIR WIDTH 44" 50" INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD TESTED) CLASSIFICATION OF USE:
1-HR RATED STRUCTURE. SEE TYPICAL FLOOR MALE 1 1 1 2 WHEN TESTED IN ACCORDANCE WITH ASTM E 492. 2012 IBC SECTION 508.3.3 NON SEPERATED; ENCLOSED PARKING
AND ROOF ASSEMBLIES, SHEET <INSERT>.
SEE 16 IBC 3005.4 MACHINE ROOMS: ELEVATOR MACHINE ROOMS SHALL BE ENCLOSED WITH GARAGE, COMMUNITY HALL, RESIDENTIAL
MEANS OF EGRESS MEANS OF EGRESS FEMALE 3 - 2
ABOVE A FIRE-RESISTANCE RATING NOT LESS THAN THE REQUIRED RATING OF
REQUIRED PROVIDED REQUIRED PROVIDED THE HOISTWAY ENCLOSURE SERVED BY THE MACHINERY. OPENING SHALL TYPE OF CONSTRUCTION:
EXITS 2 2 EXITS 2 2 BE PROTECTED WITH ASSEMBLIES HAVING A FIRE-PROTECTION RATING 2012 IBC TABLE 601, TYPES IA & VA
NOT LESS THAN THAT REQUIRED FOR THE HOISTWAY ENCLOSURE DOORS.
EXIT WIDTH 44" 72" EXIT WIDTH 44" 72" HAZARD OF CONTENTS:
17 IBC 3006.2 ELEVATOR LOBBIES AND HOISTWAY OPENING PROTECTION: HOISTWAY
CORRIDOR WIDTH 44" 60" CORRIDOR WIDTH 44" 60" OPENING PROTECTION IS NOT REQUIRED WHERE AN ELEVATOR HOISTWAY ORDINARY
STAIR WIDTH 44" 50" STAIR WIDTH 44" 50" CONNECTS FEWER THAN 4 STORIES AND IS PROTECTED BY AN AUTOMATIC
SPRINKLER SYSTEM IN ACCORDANCE WITH 903.3.1.2 ROOFING CLASSIFICATION:
2012 IBC TABLE 1505.1 = B
18 CODE ENTER TEXT
19 NFPA 101 ELEVATOR LOBBIES AND HOISTWAY OPENING PROTECTION: HOISTWAY PARAPET:
30.2.6.3.2 OPENING PROTECTION IS NOT REQUIRED WHERE AN ELEVATOR HOISTWAY NOT REQUIRED; 2012 IBC SECTION 705.11 EXCEPTIONS 5 & 6
CONNECTS FEWER THAN 4 STORIES AND IS PROTECTED BY AN AUTOMATIC
SPRINKLER SYSTEM IN ACCORDANCE WITH 903.3.1.2
DRAFT STOPS:
2012 IBC SECTION 1203.2

FIRE PROTECTION SYSTEMS:


FULLY SPRINKLERED
NFPA 13 - GARAGE & COMMUNITY HALL
NFPA 13R - RESIDENTIAL AREAS
DETECTORS
FIRE ALARM
UNPROTECTED EXTERIOR WALL OPENING AREA
ALLOWABLE PROVIDED
UNLIMITED UNPROTECTED OPENINGS NORTH UNLIMITED N/A
SOUTH 45% 41%
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 EAST 15% 5%
DN

1
1

1
1 1 1 1 1 1 1 1 1 WEST UNLIMITED N/A
1 1

1
1A

1
2

1
SEE PLANS FOR WALL OPENINGS AT COURTYARD AREA

1
1 1 1

1
2

1
1

1
1

1
2

1
DN

1
2
1

1
2

1
1

2
2

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

1
2
2

1
2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2

1
1

1
1
1

1 1
1 1

1
1

1
1
1

1 1B
1

1
1

1
1

1
1 1 Revision 1 Date 1

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


1 1

1
1
1

1
1

1
No. Description Date

1
1
1

1 1

1
1
1

1
1
1 1

1
1 1

1
1

1
1

1
1 1 1 1 1 1 1 1 1 1 1 1 1 1
SAGE
1
1
1

1
1
2
STORM SHELTER AREA = 585 SF

1 DEVELOPMENT
2
1

1
1
2
1
2
2

1
1

2
GROUP
1
2
UNLIMITED UNPROTECTED OPENINGS

1
1

2
UNL

2 1F

1
0A 2
IMIT

2
1

1
ED

1E

1
0B
UNP

BENSON
RO

1
1
TEC

1
MULTIFAMILY
TED

2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

1
12
2

1
2

2 1C
2 2 4 BUILDING 2.2 (R-2) BUILDING 2.1 (R-2)
OP

2
1

2 2 2

1
1
ENI

1
3
2

2
2

1
NG

2 2 2 2

1
2

1
1
2
2
S

1
1
1
2
2

2 2 LL BUILDING 1 (S-2)

1
1
1
1

CODE REVIEW PLANS

1
1
1
1

2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2
1
2

1
1
1

1 1 1 1 1 1 1 1 1 1 1 1
2

2
1

1
UP
1
2

1
BUILDING 2.2 (R-2)
1

1
1
2

1
1

1
1

1
2

1
2
1

1
1
2

1
1

2
1

1 1 1 1 1 1
1D 1 1 1 1 1 1
1
1

1
1 1 1 1 1 1 1 1 1 1 1

UNLIMITED UNPROTECTED OPENINGS


119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
BUILDING 2.1 (R-2) (402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:01 AM
E
LOWER LEVEL CODE REVIEW PLAN - BLDG 1 FIRST FLOOR CODE REVIEW PLAN CODE KEY PLAN & SECTION DIAGRAM PR R CO
1 2
T FO
A0.11 A0.11 NOT TO SCALE NO C COPYRIGHT 2018

0' 4' 8' 16' 32' 0' 4' 8' 16' 32'
8/26/19
SHEET: A0.11
AGENCY APPROVAL
UNLIMITED UNPROTECTED OPENINGS
IBC TRAVEL DISTANCES
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1
1

1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 PATH OF COMMON PATH OF TRAVEL TOTAL TRAVEL
1 1 1 1 TRAVEL ID DISTANCE DISTANCE

1
1
2A 3A

2
1

1
1

1
0A 0' - 0" 167' - 0"

1
1
1 1 1 1 1 1 0B 0' - 0" 130' - 0"

2
1

1
1

1
15% UNPROTECTED OPENINGS PERMITTED
1

1
1A 38' - 0" 110' - 6"

5% UNPROTECTED OPENINGS PROVIDED


1

1
1
1

1
1B 35' - 6" 120' - 0"

2
1

1
1

1
1C 40' - 0" 93' - 0"

1
1

1
1

1
2

2
1

1
1D 71' - 6" 95' - 6"

1
1E 0' - 0" 71' - 0"

1
1

1
2

2
1F 0' - 0" 45' - 6"
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1
2A 38' - 0" 110' - 6"

1
1

1
2

2
1

1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2B 35' - 6" 120' - 0"
1 1 1 1

1
1 1 2C 42' - 6" 80' - 6"

1
1

1
1

1
1 1

1
1 1 1 1
1 1 2D 54' - 0" 127' - 0"

1
1

1
1 1

1
1

1
3A 38' - 0" 110' - 6"

1
1

1
1 2B 1 3B
3B 35' - 6" 120' - 0"

25% PERMITTED
1 1

1
1

1
1

1
1

1
1

1
13% PROVIDED
1

1
1 1 3C 42' - 6" 80' - 6"
1 1 1 1

1
3D 54' - 0" 127' - 0"

1
1

1
1 1

1
UNL

1 1

1
1

1
1 1 4A 38' - 0" 110' - 6"
1

1
1 1 1 1

1
1 1
IMIT

1
1

1
4B 35' - 6" 120' - 0"

1
1

1
1 1 1 1

1
1 1 1 1 4C 42' - 6" 80' - 6"
ED

1
1

1
1

1
1 1

1
1

1
1

1
4D 54' - 0" 127' - 0"
UNP

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

1
1

1
1 1

25% PROV
1

1
1

1
RO

25%
45% UNPROTECTED OPENINGS PERMITTED
1

1
2 2

1
TEC

40% UNPROTECTED OPENINGS PROVIDED

21'-1 7/8"
2 2

1
PER IDE
1

1
1

1
2 2

1
2 2
TED

MIT D
1

1
2 2

1
1

1
2 2

TED
OP

1
2 2

1
1

1
2 2
ENI

1
2 2

1
2 2
NG

1
1

1
2 2
S

2 1 2 1
1

1
1

1
1

1
2 1 2 1

45% PROV
1

1
1 1

46%

21'-1 7/8"
1

1
1

1
1 1

1
1 1

PER IDE
1

1
1 1
1

1
45% UNPROTECTED OPENINGS PERMITTED

MIT D
1

1
1

1
1

1
39% UNPROTECTED OPENINGS PROVIDED
1

1
TED
1

1
1 1

1
1

1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

1
1 1
1

1
2 2

1
12

12
1 1

1
2 2
1

1
1 2 2 1 2 2
1

1
1

1
2

2
1 2 2 1 2 2

1
1

1
1 1

1
1
1

1
2

2
1

1
15% UNPROTECTED OPENINGS PERMITTED
2

2
1 1
1

1
5% UNPROTECTED OPENINGS PROVIDED
2 2
UNL

1
1

1
2

2
1

1
1
2 2
1

1
1

1
IMIT

1
1

1
1

1
1

1
1

1
1 1
ED

1 1

1
1

1
1

1
1

1
1

1
UNP

1 1
1 1 1 1
1

1
1 1

1
1 1

1
RO

1
1

1
2C 1 2 2 3C 1 2 2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

1
1 1
TEC

2
1

1
1

1
1

1
TED

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1
2

2
1

1
1

1
OP

1
1

1
ENI

2
1

1
1

1
1

1
1

1
NG

1
2

1
1

1
S

1
1

1
1

1
1

1
2

2
1

1
1

1
1

1
1 1 1 1
1

1
2D 3D

1
1

1
1

2
1

1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

1
1

1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

45% UNPROTECTED OPENINGS PERMITTED


41% UNPROTECTED OPENINGS PROVIDED

1 SECOND FLOOR CODE REVIEW PLAN 2 THIRD FLOOR CODE REVIEW PLAN
A0.12 A0.12

0' 4' 8' 16' 32' 0' 4' 8' 16' 32'

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

1 1 1 1 1 1 1 1 1 1 1 1
1 1
1

1
1

4A
2

1
1

7 7 7 7
1

1
1

1 1 1
2

1
1
1

1
1
1

1
1
1

1
1

1
2
1
1

1
1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

7 7
2
1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2
1

1
1

1
1

1
1

1 1
1
1

1
1

1
1
1

1 4B
1
1

1
1

1
1

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


1 1
1

1
1

1
1

1 7
No. Description Date
1

1
1

1 1
1

1
1

7
1
1

1 1
1

1 1
1
1

1
1
1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 7
SAGE
1

1
1

1
1

2
1

2 7
DEVELOPMENT
1
1
1

2
1

2
1

2
1
1

2
GROUP
1

2
1
1

2
1

2
1

2
1
1

2
2 1
1
1

2 1
1

1
1
1

1
1

1
1

1
1

BENSON
1
1
1

7
1
1

1
1
1

1 1 1 1 1 1 1 1 1 1 1 1 1 1
MULTIFAMILY
1

1
1

2
1

1
12

1
1

2
1

1 2 2
1
1

BUILDING 2.2 (R-2) BUILDING 2.1 (R-2)


2

1 2 2 4
1

1
1
1
1

2
1

7 7
2

1 3
1

2 7
1

1
2

1
1

2 2
1

1
1

1
1
1

1
1

1 LL
1 BUILDING 1 (S-2)
1

1
1
1

1
1

1
1 1
CODE REVIEW PLANS
1

1 7
1

1
1
1
1

4C
1

1 1 1 1 1 1 1 1 1 1 1 1 1 2 2
1

1
2

1
1

1
1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1

2
1

1
1

2
1

1
1

BUILDING 2.2 (R-2)


1

1
1

1
1

1
2
1

7 7 7
1

1
1

1 1
1

4D
1
1

2
1

1 1 1 1 1 1 1 1 1 1 1 1 1
1
1

1 1 1 1 1 1 1 1 1 1 1 1

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
BUILDING 2.1 (R-2)

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:13 AM
E
FOURTH FLOOR CODE REVIEW PLAN 11 - ROOF DECK CODE REVIEW PLAN CODE KEY PLAN & SECTION DIAGRAM PR R CO
3 4
T FO
A0.12 A0.12 NOT TO SCALE NO C COPYRIGHT 2018

0' 4' 8' 16' 32' 0' 4' 8' 16' 32'
8/26/19
SHEET: A0.12
AGENCY APPROVAL
1'-0" MIN *

1'-0" MIN *
5'-0" MIN

5'-0" MIN

4'-6" MIN

4'-0" MIN *
4'-0" MIN

3'-6" MIN **

3'-6" MIN *
1'-6" MIN 3'-0" MIN 3'-6" MIN 1'-10" MIN 2'-0" MIN 2'-0" MIN

FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE HINGE APPROACH, PULL SIDE HINGE APPROACH, PULL SIDE HINGE APPROACH, PUSH SIDE LATCH APPROACH, PULL SIDE LATCH APPROACH, PUSH SIDE

* IF BOTH CLOSER AND LATCH ARE PROVIDED * IF BOTH CLOSER AND LATCH ARE PROVIDED * 4'-6" MIN IF CLOSER IS PROVIDED * 4'-0" MIN IF CLOSER IS PROVIDED GENERAL CODE DETAIL NOTES
** 4'-0" MIN IF BOTH CLOSER AND LATCH ARE
TYPICAL MANEUVERING CLEARANCE AT MANUAL SWINGING PROVIDED
1. DETAILS USED ON THIS SHEET ARE FOR REFERENCE ONLY.
1 DOORS
2. DETAILS ARE FROM 2010 ADA STANDS FOR ACCESSIBLE
A0.31
DESIGN AND ICC/ANSI A117.1-2003.
0' 6" 1' 2' 4' 12"

12"

34" - 38"

34" - 38"
5'-0" MIN

4'-0" MIN

4'-0" MIN
Y Y
1'-6" MIN 1'-0" MIN *
X> 8"

X> 8"

X> 8"
A IS THE TOP OF GRIPPING SURFACE DIMENSION FOR
HANDRAILS ABOVE THE FINISH NOSING.
PULL SIDE PUSH SIDE PUSH SIDE
X IS THE 1'-0" MINIMUM HANDRAIL EXTENSION AT THE
TOP OF THE STAIR FLIGHT.

Y IS THE MINIMUM HANDRAIL EXTENTION OF THE


WIDTH OF ONE TREAD THAT IS REQUIRED AT EACH
BOTTOM RISER.
* IF BOTH CLOSER AND LATCH ARE PROVIDED
TYPICAL MANEUVERING CLEARANCE AT RECESSED DOORS
2 AND GATES 3 HANDRAIL EXTENSION
A0.31 A0.31

0' 6" 1' 2' 4' 0' 6" 1' 2' 4'

36" MIN 39"-41"


16"-18"

1 1/4" TO 1 1/2" 1 1/2"


VERTICAL
GRAB BAR
60" MIN.

TOE
CLEARANCE 6"
33" TO 36"
MIN.
9"

GRAB BAR

56" MIN. WALL HUNG W.C.

59" MIN. FLOOR MOUNTED W.C.


STALL BACK WALL ELEVATION GRAB BAR SECTION

STALL AT END OF ROW

ALTERNATE
4" MAX. 32" MIN. DOOR LOCATION
18" MIN.

TOILET PAPER
4" MAX.

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


LOCATION
32" MIN.

No. Description Date


24" MIN.

60" MIN.

SAGE
36" MIN.

7"-9"
39"-41"
48" MAX.

33" - 36"

DEVELOPMENT
16"-18"

17"-19"

15" MIN.

42" MIN. 3'-0" MIN. 3'-0" MIN.


GROUP
16"-18" 1'-6" 1'-6" MIN 1'-6" MIN 1'-6"
12" MIN.

LATCH APPROACH 39"-41"


ONLY. OTHER
APPROACHES 48" MIN

42" MIN.

56" MIN.
12" MAX.

WALL HUNG W.C.


STALL SIDE WALL ELEVATION
BENSON
MULTIFAMILY
4'-8" MIN.

4'-8" MIN.
59" MIN. FLOOR MOUNTED W.C.
5'-6" MIN.

STANDARD STALL

60" MIN.

42" MIN.
4'-0" MIN. CODE DETAILS
12" MAX. 5'-0" MIN.

4'-0" MIN.

1 1/4" TO 1 1/2" 1 1/2"


3'-0" MIN.
32" MIN.

4'-6" MIN.
35" - 37"
17"-19"

3'-0" MIN.
1'-0" 3'-6" MIN. TOILET PAPER
1'-0" MIN. 1'-0" MIN.

119 SOUTH 49TH AVENUE


AMBULATORY STALL
OMAHA, NEBRASKA 68132
3'-2 3/4"

(402)551-0800
1'-7" MIN.

42" MIN.
2'-9" - 3'-0"

2'-9" - 3'-0"
1'-5"-1'-7"

GRAB BAR
LATCH APPROACH
ONLY, OTHER
ARY N PROJECT: 17073
APPROACHES 48" MIN.
I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:16 AM
E
4 MULTIUSER TOILET 5 SINGLE USER TOILET PR R CO
A0.31 A0.31 T FO
NO C COPYRIGHT 2018

0' 6" 1' 2' 4' 0' 6" 1' 2' 4'

8/26/19
SHEET: A0.31
AGENCY APPROVAL
A3.11

140'-8 1/4"
26'-8 11/16" 11'-11 3/16" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 23'-3 5/16" 13'-8 15/16"

3'-5 7/8"

4'-5 3/8"
DN

040A
A3.11
3

10'-6"
2'-0" 18'-0"

29'-4 3/16"

001
1
A5.51 GENERAL PLAN NOTES
1. SEE SHEET A1.01 FOR GENERAL PLAN NOTES.

R26'-0" 2'-8 1/2"

KEYED PLAN NOTES

62'-6"
STAIR
GARAGE A3.12
040 2
001 040
1. SEE SHEET A1.01 FOR KEYED PLAN NOTES.
21'-
7 7/
8"

006A
25'-
5 3/
4"

STORM
SHELTER
006

170'-11 3/8"
162'-6"
24'-
6 5/
16"

4"
4 1/
19'-
144

006
'-1 1

1
/8"

A3.11 TRASH
004

0" 62'-2"
44'-
ELEVATOR
003

004
3
VESTIBULE
A5.54
002
002

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

STAIR
041
SAGE
3
A3.12 DEVELOPMENT
UP GROUP
44'-0"

6
A5.51
005

041 BENSON
MECHANICAL
MULTIFAMILY
005

4'-0"
LOWER LEVEL FLOOR
3'-10"

PLAN
22'-9 1/4" 13'-6 1/2" 10'-2 3/4"
112'-8"

A3.12

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:19 AM
E
1 LOWER LEVEL FLOOR PLAN PR R CO
A1.00 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.00
AGENCY APPROVAL
A3.11

2
14'-0" 25'-0 1/8" 13'-7 3/4" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 13'-7 7/8" 13'-7 1/4" 9'-10"
7'-0" 6'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 1'-8"

4'-4 1/2"
10'-6 1/2"
11'-4 1/2"
A3.11 STAIR
3
V5 140

10"
UNIT J V3 UNIT J V3 UNIT J UNIT J V3 UNIT J V3 UNIT J
V3 V3
159 158 156 154 152 150

25'-3 5/8"
UNIT 2-C
DN
160
GENERAL PLAN NOTES
1. ALL BOLD OR FULL-TONE LINES INDICATE NEW CONSTRUCTION,
FIXTURES OR EQUIPMENT. ALL LIGHT OR HALF-TONE LINES
2
INDICATE EXISTING CONSTRUCTION, FIXTURES OR EQUIPMENT.
A5.51
UP 2. ALL DIMENSIONS ARE TAKEN TO THE FACE OF EXISTING
CONSTRUCTION OR THE FINISH FACE OF NEW CONSTRUCTION,

64'-6 1/2"
5'-6 3/4"
1 CORRIDOR A3.12 UNLESS OTHERWISE NOTED ON THE PLANS. LIGHT OR HALF TONE
A5.02 U2.1 130 U2.1 V2.1 2 DIMENSIONS ARE SHOWN FOR INFORMATION ONLY.

1'-10"
140
3. FIELD VERIFY ALL DIMENSIONS SHOWN ON THE PLANS WITH

123
THE ACTUAL EXISTING CONDITIONS.
V3 U2.1 4. FINISH FLOOR ELEVATION = 100'-0" (<insert> CIVIL ELEVATION),
V3 UNLESS OTHERWISE NOTED ON PLAN.
6'-0

UNIT 1-C
"

5. ALL NEW PARTITIONS SHOWN WITHIN THE LIMITS OF


U2.1 157
CONSTRUCTION ARE TYPE #.# UNLESS NOTED OTHERWISE.

STORAGE V3 6. SEE SHEET A/#.## FOR PARTITION TYPES.


123
21'-

29'-3 5/8"
3/4" 7. PROVIDE CONTINUOUS BLOCKING OR STRAPPING WITHIN NEW
5'-6
7 7/

V3
WALLS AS REQUIRED FOR ALL WALL MOUNTED CASEWORK,
8"

"
7'-0 FIXTURES, ACCESSORIES AND EQUIPMENT. ANCHOR BLOCKING
W2 BETWEEN THE STUDS, AT THE FACE OF THE STUDS, FOR THE

17'-9 15/16"
U2.1 ENTIRE WIDTH OF THE ITEM TO BE MOUNTED ON THE WALL.
ANCHOR <22 GA> SHEET METAL STRAPPING TO THE FACE OF THE
6'-4

U2.1 UNIT S-B UNIT S-B UNIT 1-A

3'-6
STUDS, FOR THE ENTIRE WIDTH OF THE ITEM TO BE MOUNTED ON
UNIT 1-B
"

155 153 151 THE WALL. VERIFY VERTICAL LOCATION OF BLOCKING WITH THE

"
161 MOUNTING HEIGHT REQUIRED AND THE REQUIREMENTS OF THE

15'-
V3 V3 ITEM TO BE MOUNTED ON THE WALL.
/2"
6'-2

11 1
28'-

7 1/
UNIT S-B 8. OWNER FURNISHED EQUIPMENT SHOWN DASHED ON PLAN,
1/4"

V3

16"
163 UNLESS OTHERWISE NOTED.

5'-8" 3'-10" 3'-10" 5'-8" 6'-4" 5'-8" 9. PROVIDE SELF-LEVELING CONCRETE FLOOR UNDERLAYMENT

4'-8
"
5'-0 AS REQUIRED TO ACHIEVE A SMOOTH AND LEVEL SUBSTRATE FOR

3/4"
7 1/2" 19'-0 3/4" 7 1/4" 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2" FLOOR FINISHES.
25'-

UNIT 1-B CORRIDOR


10. ALL FURNITURE IS NOT-IN-CONTRACT AND SHOWN FOR
131
5 3/

162 2" 3 INFORMATION AND COORDINATION ONLY.


'-11 1/
4"

28
A3.13 11. FOR DESIGNATED WALL RATING REFER TO BUILDING CODE

5'-0
6" REVIEW PLANS, SHEET A/#.##
4

"
6" 12. WHEN PARTITIONS OF DIFFERENT RATINGS ARE LOCATED
6'-2

5'-0 OUTDOOR KITCHEN W/ BRICK VENEER


ACE ALONG THE SAME WALL, ALIGN FINISH FACE OF WALL AS
EPL & CONCRETE COUNTERTOPS
1/4"

REQUIRED.
"
IR
SF
R GA 1
EA 9 13. FOR ALL INTERIOR FINISHES REFER TO ROOM FINISH
131 LIN

171'-4 3/4"
01 SCHEDULE, SHEET A/#.##

24'-5 1/2"

42'-3 3/4"
A8. A3.13
6'-4

X1 10 (2) BUILT-IN
GAME OUTDOOR GRILLS
"
12'-

ROOM 2
3 7/

103
8"

103 44'-8"
6 HALL
01 108 1
A8.
7 A5.01
8
PARTY PEDESTRIAN CANTILEVERED
ROOM BRIDGE W/ GUARDRAILS TO
12'-

102 107 WOMEN'S MATCH BUILDING STANDARD


3 7/

HALL RR
6'-4
8"

107 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
106 104
"

102 01
A8.
01 A8. 5'-6" 3'-10" 5'-6" 6'-4" 6'-4" 5'-6"
5/8" 12
1 3'-4 11MEN'S RR
106 105 JANITOR
A3.11 105

TRASH
UNIT S-B UNIT 1-A UNIT 1-A
121
01 171 173 175
A8.
8.01 2 MECH
BUSINESS A

29'-3 5/8"
CENTER 4 122
01

121
109 A8.
37'-

1 3
8 1/

LOBBY 8.01
122

A
2"

101 4
A5.54
ELEVATOR
VESTIBULE LOBBY

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


100
101
120 BUILDING UNIT SCHEDULE No. Description Date
100
QTY UNIT TYPE

1'-10"
12 UNIT 1-A ONE BEDROOM
SAGE

64'-6 1/2"
5'-6 3/4"
141
111

CORRIDOR 14 UNIT 1-B ONE BEDROOM


V2.1
133 4 UNIT 1-C ONE BEDROOM
120

A3.12
3
2
UNIT 2-A
UNIT 2-B
TWO BEDROOM
TWO BEDROOM DEVELOPMENT
113

OFFICE 113A
111 3 4 UNIT 2-C TWO BEDROOM
7

5
A5.51 28
7
UNIT J
UNIT S-A
JUNIOR
STUDIO
GROUP
22 UNIT S-B STUDIO
01 A8.01
A8. 13 TOTAL UNITS: 96
112

MAIL

25'-3 5/8"
110 STORAGE
112
FIRST FLOOR UNIT COUNT BENSON
34'-
0 7/

FITNESS
MULTIFAMILY
16"

UNIT S-A UNIT J UNIT J QTY UNIT TYPE


CENTER
170 172 174 3 UNIT 1-A ONE BEDROOM
113 V3 V5
V3 STAIR 2 UNIT 1-B ONE BEDROOM
V3 V3
141 1 UNIT 1-C ONE BEDROOM
1 UNIT 2-C TWO BEDROOM
8 UNIT J JUNIOR

141A

4'-4 1/2"
110

1 UNIT S-A STUDIO


3'-4 1/2"

4 UNIT S-B STUDIO


TOTAL UNITS: 20

5'-0" 5'-0" 3'-3"


FIRST FLOOR PLAN
3'-3" 5'-0" 5'-0" 5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 5'-0"
13'-6 5/8" 13'-6 1/2" 13'-8" 25'-8 1/8" 13'-7 3/4" 13'-7 1/4" 9'-10"

A3.12

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:26 AM
E
1 FIRST FLOOR PLAN PR R CO
A1.01 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.01
AGENCY APPROVAL
A3.11

2
14'-0" 25'-0 1/8" 13'-7 3/4" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 13'-7 7/8" 13'-7 1/4" 9'-10"
6'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 1'-8"

W4 W1 W4 W4 W1 W1 W4 W4 W1 W1 W4 W4 W1

4'-4 1/2"
W12

10 1/4" 10'-6 1/2"


11'-4 3/4"
A3.11 STAIR
3 240
V5
UNIT J V3 UNIT J V3 UNIT J UNIT J V3 UNIT J V3 UNIT J
V3 V3
259 258 256 254 252 250
DN

25'-3 5/8"
UNIT 2-C
3
W3.2
260 A5.51 GENERAL PLAN NOTES
W3.2
1. SEE SHEET A1.01 FOR GENERAL PLAN NOTES.
W3.2

64'-6 1/2"
KEYED PLAN NOTES

5'-6 3/4"
2 CORRIDOR A3.12
A5.02 U2.1 230 U2.1 V2.1 2
W3.2

1'-10"
240
1. SEE SHEET A1.01 FOR KEYED PLAN NOTES.

223
V3 U2.1
V3
6'-0

UNIT 1-C
"

W4
U2.1 STORAGE 257
223
V3

224

29'-3 5/8"
21'-

U2.1

A
V3
7 7/

W4
W4 3/4" W2
5'-6
8"

W2 W4
ELECTRICAL "
U2.1 7'-0

3'-6
224
6'-4

U2.1 UNIT S-B UNIT S-B UNIT 1-A

5/16
224

13'-10"
UNIT 1-B
"

255 253 251


W4

"
261
V3 V3
/2"
6'-2

11 1
28'-
UNIT S-B
1/4"

V3
263

3'-4

1'-4
" W4 W4 W4

"
5'-0

3/4"
X1 5'-8" 3'-3" 3'-3" 5'-8" 6'-2" 5'-8"
CORRIDOR

3'-4
UNIT 1-B 231 7 1/2" 19'-0 3/4" 7 1/4" 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
25'-

"
262 2" 3
1 1/
5 3/

-1 W4
2 8'
U2.1
4"

A3.13

19'-
5'-0
6"
4

0 3/
"
6"

4"
6'-2

5 '-0
1/4"

"

5'-0
UNIT S-B W4 1

6'-0
"
231 265

171'-4 3/4"
3/4"

42'-3 3/4"
A3.13
5'-0

7 1/
6'-4

"
X1 5'-0
"

4"
"

W4 6" V3 2
6"

6'-0
3/4"
6

19'-
01 W4
A8.
24'-

0 3/
7
7 3/

4"
4"

W4
U2.1 UNIT S-B 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
"
3'-0 267 3'-3" 5'-8" 6'-2" 6'-2" 5'-8"
6'-4

3'-4
UNIT 1-B
"

"
01
264 A8. W4 W4
12 V3 W4
1
6'-2

U2.1
1/4"

A3.11 V3 5'-8"

13'-10"
CORRIDOR TRASH UNIT S-B UNIT 1-A UNIT 1-A
221 V3 V3 V3
UNIT 1-B 232 271 273 275
25'-

266
5 3/

TELECOM

29'-3 5/8"
W2
4"

222

221
1
01
222

A8.
6'-2

5
1/4"

A5.54
ELEVATOR
EQ

LOBBY

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


6'-1

220 BUILDING UNIT SCHEDULE No. Description Date


1/2"

V3
W4
EQ
11'-

QTY UNIT TYPE


7 1/

1'-10"
5'-6

12 UNIT 1-A ONE BEDROOM


SAGE

64'-6 1/2"
2"

5'-6 3/4"
241
EQ

W3.2
"

CORRIDOR V2.1 14 UNIT 1-B ONE BEDROOM


U2.1 U2.1
4 UNIT 1-C ONE BEDROOM
EQ

233
3 UNIT 2-A TWO BEDROOM
DEVELOPMENT
7 1/

5'-6

A3.12 2 UNIT 2-B TWO BEDROOM


4"

EQ

3
"

W4 4 UNIT 2-C TWO BEDROOM

GROUP
EQ

28 UNIT J JUNIOR
38'-

7 UNIT S-A STUDIO


22 UNIT S-B STUDIO
4 13

A8.01
12'-

13 TOTAL UNITS: 96
/16"

8
11 1

UNIT 2-A A5.51

25'-3 5/8"
/4"

268

W5
SECOND FLOOR UNIT COUNT BENSON
UNIT S-A
269
UNIT S-A
270
UNIT J
272
V3
UNIT J
274
V5 STAIR
QTY UNIT
3 UNIT 1-A
TYPE
ONE BEDROOM MULTIFAMILY
V3 V3 V3 4 UNIT 1-B ONE BEDROOM
3'-11 3/8"

241 1 UNIT 1-C ONE BEDROOM


1 UNIT 2-A TWO BEDROOM
1 UNIT 2-C TWO BEDROOM

4'-4 1/2"
8 UNIT J JUNIOR
W12
2 UNIT S-A STUDIO
6 UNIT S-B STUDIO

W1 W4 W4 W1 W1 W4 W4 W1
TOTAL UNITS: 26 SECOND FLOOR PLAN
5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 5'-0" 5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 5'-0" 1'-8"
13'-7 11/16" 13'-6 1/2" 13'-8" 25'-8 1/8" 13'-7 3/4" 13'-7 1/4" 9'-10"

A3.12

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:33 AM
E
1 SECOND FLOOR PLAN PR R CO
A1.02 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.02
AGENCY APPROVAL
A3.11

2
14'-0" 25'-0 1/8" 13'-7 3/4" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 13'-7 7/8" 13'-7 1/4" 9'-10"
6'-4" 5'-2 1/4" 5'-1 3/4" 3'-3" 3'-3" 5'-1 3/4" 5'-2 1/4" 5'-2 1/4" 5'-1 3/4" 3'-3" 3'-3" 5'-1 3/4" 5'-2 1/4" 5'-2 1/4" 5'-1 3/4" 3'-3" 3'-3" 5'-1 3/4" 5'-2 1/4" 1'-8"

W4 W1 W4 W4 W1 W1 W4 W4 W1 W1 W4 W4 W1

4'-4 1/2"
W12

10 1/4" 10'-6 1/2"


11'-4 3/4"
A3.11 STAIR
3
V5 340
EWA-2UNIT 2-B V3 UNIT J UNIT J V3 UNIT J V3 UNIT J
V3 V3
358 356 354 352 350

25'-3 5/8"
6
A5.19 4
A5.13
UNIT 2-C 4
W3.2
360
6 A5.18
8 A5.51 GENERAL PLAN NOTES
W3.2
A5.18
19 7 A5.18 1. SEE SHEET A1.01 FOR GENERAL PLAN NOTES.
A5. 5
W3.2
4 4

64'-6 1/2"
19
KEYED PLAN NOTES

5'-6 3/4"
A5. 3 CORRIDOR A3.12
A5.02 U2.1 U2.1 V2.1 2
330 W3.2

1'-10"
340
1. SEE SHEET A1.01 FOR KEYED PLAN NOTES.

323
V3 U2.1
V3
6'-0

UNIT 1-C
"

W4
U2.1 357
16
A5.
STORAGE 16
V3 A5. 4
323

324
5

29'-3 5/8"
21'-

U2.1

A
V3
7 7/

W4
W4 3/4" W2
5'-6
8"

V3 W4 "
U2.1 ELECTRICAL 7'-0
6'-4

U2.1 324 UNIT S-B UNIT S-B UNIT 1-A


324

13'-10"
UNIT 1-B
"

355 353 351


361 W4
4" V3 V3
1 3/
6'-2

28'-
UNIT S-B
1/4"

V3
363

3'-4

1'-4
3/4" W4 W4

"
5'-9 W4

3/4"
X1 5'-8" 3'-4" 3'-4" 5'-8" 6'-2" 5'-8"
CORRIDOR

3'-4
UNIT 1-B 331 7 1/2" 19'-0 3/4" 7 1/4" 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
25'-

"
362 2" 3
1 1/
5 3/

-1 W4
2 8'
U2.1
4"

A3.13

19'-
5'-0
4

0 3/
"
4"
6 3/

4"
6'-2

5 '-0
1/4"

"

5'-0
UNIT S-B W4 1

6'-0
"
331 365

171'-4 3/4"
3/4"

42'-3 3/4"
A3.13
5'-0

7 1/
6'-4

"
X1 5'-0
"

4"
"

W4 6" V3 2
6"

6'-0
3/4"

19'-
W4
24'-

0 3/
7 3/

4"
4"

W4
U2.1 UNIT S-B 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
"
3'-0 367 3'-4" 5'-8" 6'-2" 6'-2" 5'-8"
6'-4

3'-4
UNIT 1-B
"

"
364 W4 W4 W4
V3
1
6'-2

U2.1
5'-8"
1/4"

A3.11
4 5
15
A5.

13'-10"
6
TRASH UNIT S-B UNIT 1-A UNIT 1-A
CORRIDOR V3 V3 V3
UNIT 1-B 321 371 373 375
332
25'-

366
5 3/

TELECOM

29'-3 5/8"
4"

322

321
322
6'-2

6
1/4"

15 6
A5. A5.54
5
ELEVATOR
EQ

7 A5.14
LOBBY

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


6'-1

5 320
A5.14
BUILDING UNIT SCHEDULE No. Description Date
1/2"

V3
W6 17
A5.
EQ
11'-

4
QTY UNIT TYPE
7 1/

1'-10"
5'-6

12 UNIT 1-A ONE BEDROOM


SAGE

64'-6 1/2"
2"

5'-6 3/4"
341 W3.2
CORRIDOR
"

V2.1 14 UNIT 1-B ONE BEDROOM


U2.1 U2.1
333 4 UNIT 1-C ONE BEDROOM
EQ

3 UNIT 2-A TWO BEDROOM


DEVELOPMENT
7 1/

5'-6

A3.12 2 UNIT 2-B TWO BEDROOM


4"

3
"

W6 4 UNIT 2-C TWO BEDROOM

GROUP
EQ

28 UNIT J JUNIOR
38'-

7 UNIT S-A STUDIO


4 22 UNIT S-B STUDIO
4 13

A5.11
17 A5.17
12'-

A5. 5 TOTAL UNITS: 96


/16"

6
11 1

4 9
UNIT 2-A A5.11

25'-3 5/8"
A5.51
/4"

368

W7
THIRD FLOOR UNIT COUNT BENSON
UNIT S-A
369
UNIT S-A
370
UNIT J
372
V3
UNIT J
374
V5
QTY UNIT
3 UNIT 1-A
TYPE
ONE BEDROOM MULTIFAMILY
V3 STAIR 4 UNIT 1-B ONE BEDROOM
3'-11 3/8"

V3 V3
341 1 UNIT 1-C ONE BEDROOM
1 UNIT 2-A TWO BEDROOM
1 UNIT 2-B TWO BEDROOM

4'-4 1/2"
1 UNIT 2-C TWO BEDROOM
W4 W12
6 UNIT J JUNIOR
2 UNIT S-A STUDIO
10'-
0"
W1 W4 W4 W1 W1 W4 W4 W1
6 UNIT S-B STUDIO THIRD FLOOR PLAN
TOTAL UNITS: 25
5'-10" 5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 5'-0" 5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 5'-0" 1'-8"
13'-7 11/16" 13'-6 1/2" 13'-8" 25'-8 1/8" 13'-7 3/4" 13'-7 1/4" 9'-10"

A3.12

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:40 AM
E
1 THIRD FLOOR PLAN PR R CO
A1.03 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.03
AGENCY APPROVAL
A3.11

2
14'-4 1/8" 24'-8" 13'-7 3/4" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 13'-7 7/8" 13'-7 1/4" 9'-10"
6'-0" 6'-8" 3'-3" 3'-3" 6'-8" 6'-8" 3'-3" 3'-3" 6'-8" 6'-8" 3'-3" 3'-3" 6'-8" 1'-8"

W8 W10 W10 W10 W10 W10 W10

4'-4 1/2"
W12

11'-0 1/4"
10 1/4" 10'-2"
A3.11 STAIR
3
V5
EWA-2UNIT 2-B V3 UNIT J UNIT J V3 UNIT J V3 UNIT J 440
V3 V3
458 456 454 452 450

25'-3 5/8"
UNIT 2-C
W3.3
460
A5.18
8 GENERAL PLAN NOTES
W3.3
1. SEE SHEET A1.01 FOR GENERAL PLAN NOTES.
W3.3
5
A5.51

64'-6 1/2"
KEYED PLAN NOTES

5'-6 3/4"
4 CORRIDOR A3.12
A5.02 U2.1 U2.1 430 V2.1 2
W3.2

1'-10"
440
1. SEE SHEET A1.01 FOR KEYED PLAN NOTES.

423
V3 U2.1
V3
6'-0

UNIT 1-C
W8
"

U2.1 U2.1 457

STORAGE ROOF V3
423 ACCESS

29'-3 5/8"
21'-

425 V3
7 7/

W4
W8 425 3/4" W2
5'-6
8"

ELEC W4 "
U2.1 424 7'-0
6'-4

UNIT S-B UNIT S-B UNIT 1-A


424

13'-10"
UNIT 1-B
"

455 453 451


461 W4
4" V3 V3
1 3/
6'-2

28'-
UNIT S-B
1/4"

V3
463

3'-4

1'-4
3/4" W4 W4 W4

"
5'-9

3/4"
CORRIDOR X1 5'-8" 3'-4" 3'-4" 5'-8" 6'-2" 5'-8"

3'-4
UNIT 1-B 431 7 1/2" 19'-0 3/4" 7 1/4" 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
25'-

"
462 2" 3
1 1/
5 3/

-1 W4
2 8'
U2.1
4"

A3.13

19'-
5'-0
4

0 3/
"

4"
6'-2

5' -0
1/4"

"

5'-0
UNIT S-B W4 1

6'-0
"
431 465

171'-4 3/4"
3/4"

42'-3 3/4"
A3.13
5'-0

7 1/
6'-4

"
X1 5'-0
"

4"
"

W8 6" V3 2
6"

6'-0
3/4"

19'-
W4
24'-

0 3/
7 3/

4"
4"

W8
U2.1 UNIT S-B 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
"
3'-0 467 3'-4" 5'-8" 6'-2" 6'-2" 5'-8"
6'-4

3'-4
UNIT 1-B
"

"
464 W4 W4 W4
V3
1
6'-2

U2.1
1/4"

A3.11 5'-8"

13'-10"
CORRIDOR TRASH UNIT S-B UNIT 1-A UNIT 1-A
V3 V3 V3
UNIT 1-B 432 421 471 473 475
25'-

466
5 3/

TELECOM

29'-3 5/8"
W2
4"

422

421
422
6'-2

7
1/4"

A5.54 6
ELEVATOR
EQ

A5.14
LOBBY

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


6'-1

420
A5.14
BUILDING UNIT SCHEDULE No. Description Date
1/2"

V3
W9
EQ
11'-

4
QTY UNIT TYPE
7 1/

1'-10"
5'-6

12 UNIT 1-A ONE BEDROOM


SAGE

64'-6 1/2"
2"

5'-6 3/4"
CORRIDOR 441 W3.2
"

V2.1 14 UNIT 1-B ONE BEDROOM


U2.1 U2.1
433 4 UNIT 1-C ONE BEDROOM
EQ

3 UNIT 2-A TWO BEDROOM


DEVELOPMENT
7 1/

5'-6

A3.12 2 UNIT 2-B TWO BEDROOM


4"

10 3
"

W9 4 UNIT 2-C TWO BEDROOM


A5.51
GROUP
EQ

28 UNIT J JUNIOR
38'-

7 UNIT S-A STUDIO


22 UNIT S-B STUDIO
4 13

12'-

TOTAL UNITS: 96
/16"

11 1

UNIT 2-A

25'-3 5/8"
/4"

468

W11
FOURTH FLOOR UNIT COUNT BENSON
UNIT S-A
469
UNIT S-A
470
UNIT J
472
V3
UNIT J
474
V5
QTY UNIT
3 UNIT 1-A
TYPE
ONE BEDROOM MULTIFAMILY
V3 STAIR 4 UNIT 1-B ONE BEDROOM
3'-11 3/8"

V3 V3
441 1 UNIT 1-C ONE BEDROOM
1 UNIT 2-A TWO BEDROOM
1 UNIT 2-B TWO BEDROOM

4'-4 1/2"
1 UNIT 2-C TWO BEDROOM
W8 W12
6 UNIT J JUNIOR
2 UNIT S-A STUDIO
10'-
0"
W10 W10 W10 W10 6 UNIT S-B STUDIO FOURTH FLOOR PLAN
TOTAL UNITS: 25
6'-1 3/16" 6'-8" 3'-3" 3'-3" 6'-8" 6'-8" 3'-3" 3'-3" 6'-8" 1'-8"
13'-11 13/16" 13'-2 3/8" 13'-8" 25'-8 1/8" 13'-7 3/4" 13'-7 1/4" 9'-10"

A3.12

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:46 AM
E
1 FOURTH FLOOR PLAN PR R CO
A1.04 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.04
AGENCY APPROVAL
*HBA_CD_KEYED ROOF...
_ 1
A3.31
TAG USED IN THIS SCHEDULE
1 KEYNOTE 1
2 KEYNOTE 2
_ 4 _ 1 _ 3 1
_ 3 KEYNOTE 3
A4.02 A4.02 A4.02 A5.52 4 KEYNOTE 4
5 KEYNOTE 5
CORRUGATED METAL CANOPY 6 KEYNOTE 6
7 KEYNOTE 7
8 KEYNOTE 8
HSS20x4 STEEL TUBE AT CORNER _ 5 9 KEYNOTE 9
A4.02 10 KEYNOTE 10
11 KEYNOTE 11
12 KEYNOTE 12
13 KEYNOTE 13
14 KEYNOTE 14
15 KEYNOTE 15
16 KEYNOTE 16
17 KEYNOTE 17
18 KEYNOTE 18
19 KEYNOTE 19
20 KEYNOTE 20

GENERAL ROOF NOTES


1. LEVEL ROOF STRUCTURE. ROOF SLOPE SHALL BE
ACCOMPLISHED WITH TAPERED INSULATION AS SHOWN (1/4" PER
12" MINIMUM).

FD 2. SLOPED ROOF STRUCTURE. SEE STRUCTURAL FRAMING


T PLANS FOR SLOPE.

_ 2 3. PROVIDE TAPERED INSULATION CRICKETS TO ROOF DRAINS


F F A5.52 AS SHOWN.
F 4. SINGLE PLY ROOF ASSEMBLY SHALL BE FULLY ADHERED
EPDM MEMBRANE <OVER COVER BOARD,> OVER INSULATION
(TAPERED AND CONSTANT THICKNESS), <OVER GYPSUM DECK
SHEATHING>.

5. PROVIDE CONSTANT THICKNESS POLYISO- CYANURATE


INSULATION TO ACHIEVE <A TOTAL THICKNESS OF <insert>"> or
T
<AN "R" VALUE OF <insert> (MINIMUM)>. PROVIDE TAPERED
INSULATION OVER THE CONSTANT THICKNESS INSULATION (1/4"
ROOF ACCESS HATCH PER FOOT MIN SLOPE) TO ACHIEVE ELEVATIONS SHOWN ON THE
30"x54" ROOF PLAN.

6. TAPERED INSULATION SPOT ELEVATIONS, INDICATED THUS (+


4 3/4") ON THE ROOF PLAN DENOTE THE THICKNESS OF THE
TAPERED INSULATION ABOVE THE TOP OF THE CONSTANT
THICKNESS POLYISO INSULATION (0). SEE ROOF DRAIN DETAIL
A#.##

FD
7. SEE MECHANICAL AND PLUMBING SHEETS FOR ADDITIONAL
ROOFTOP EQUIPMENT, VENTS AND OTHER ITEMS REQUIRING
PENETRATIONS THRU THE ROOF, NOT SHOWN ON THIS PLAN.

2 8. SEE ELECTRICAL SHEETS FOR LIGHTNING PROTECTION NOT


_
F SHOWN ON THIS PLAN.
A3.31
9. ATTIC VENTILATION: PROVIDE A COMBINATION OF SOFFIT
VENTS AND ROOF VENTS. PROVIDE VENTS AS REQUIRED TO
ACHIEVE A VENT AREA TO ROOF AREA RATIO OF 1/300 (MINIMUM).
HALF OF THE VENT AREA SHALL BE IN THE SOFFIT W/ REMAINING
HALF IN THE ROOF, NEAR THE RIDGE. FINISH VENTS TO MATCH
ADJACENT SURFACE.

_ 2
A4.02

_ 1
A4.03

_ 3
_ 4
A4.03
A4.03
FD

_ 1
A4.01
SEE SECTIONS FOR RAISED
FSD ROOF AT ELEVATOR
_ 1
T A5.54
_ 2
A3.31

_ 2
A5.54
F

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


T
No. Description Date
FD

_ 2 FD
A4.01 F F T
_ 2
A5.53
SAGE
DEVELOPMENT
_ 3 GROUP
A4.01

BENSON
MULTIFAMILY

HSS20x4 STEEL TUBE AT CORNER ROOF PLAN


CORRUGATED METAL CANOPY 1
_
A5.53
_ 4 _ 1
A4.01 A3.31

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:51 AM
E
1 ROOF PLAN PR R CO
A1.11 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.11
AGENCY APPROVAL

GENERAL RCP NOTES


1. SEE SHEET A1.21 FOR GENERAL RCP NOTES.

RATED PARTITION NOTES


1. SEE SHEET A1.21 FOR GENERAL RATED PARTITION NOTES.

KEYED RCP NOTES


1. SEE SHEET A1.21 FOR KEYED RCP NOTES.

LEGEND OF SYMBOLS
1. SEE SHEET A1.21 FOR RCP LEGEND OF SYMBOLS

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

LOWER LEVEL
REFLECTED CEILING
PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:50:52 AM
E
1 LOWER LEVEL REFLECTED CEILING PLAN PR R CO
A1.20 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.20
LEGEND OF SYMBOLS AGENCY APPROVAL
GWB CEILING / SOFFIT

2 X 2 APC

EXP TO STRUCTURE ABOVE

RECESSED DOWN LIGHT


HANGING PENDANT
1 X 1 LIGHT FIXTURE

2 X 2 LIGHT FIXTURE

2 X 4 LIGHT FIXTURE

1 X 4 LIGHT FIXTURE
1 X 4 SURFACE MOUNTED
LIGHT FIXTURE
SURFACE MOUNTED LIGHT FIXTURE

MECHANICAL SUPPLY DIFFUSER


GENERAL RCP NOTES
1. SEE ROOM FINISH SCHEDULE FOR CEILING FINISHES UNLESS
MECHANICAL RETURN GRILLE NOTED OTHERWISE ON THE REFLECTED CEILING PLAN.

S SMOKE DETECTOR 2. ALL GYPSUM BOARD SOFFITS SHALL BE AT <insert> ABOVE


FINISH FLOOR UNLESS NOTED OTHERWISE.
FD
H HEAT DETECTOR
3. ALL CEILINGS TO BE AT <insert> ABOVE FINISH FLOOR UNLESS
EXIT LIGHT NOTED OTHERWISE.

4. CEILING HEIGHT AS NOTED FOR ACOUSTIC PANEL CEILINGS


DECORATIVE PENDANT LIGHT SHALL BE MEASURED TO THE FINISH FACE OF THE GRID.

CUBICLE CURTAIN TRACK 5. PAINT ALL HORIZONTAL AND VERTICAL SURFACES OF SOFFITS
TO MATCH ADJACENT WALL COLOR AND FINISH UNLESS NOTED
OTHERWISE.

RATED PARTITION NOTES


1. VERIFY THAT ALL EXISTING WALLS SHOWN AS FIRE RATED,
MEET ALL APPLICABLE CODE REQUIREMENTS. PATCH AND REPAIR
AS REQUIRED, WITH APPROVED FIRESTOPPING MATERIALS, ANY
EXISTING WALLS FOUND TO BE NONCOMPLIANT.

2. SPRINKLER HEAD LOCATIONS ARE NOT SHOWN ON THE


REFLECTED CEILING PLAN. THE FIRE SPRINKLER CONTRACTOR
SHALL SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR THE

FD
SYSTEM.

*HBA_CD_KEYED RCP...
TAG USED FOR THIS SCHEDULE
1 KEYNOTE 1
2 KEYNOTE 2
3 KEYNOTE 3
4 KEYNOTE 4
5 KEYNOTE 5
6 KEYNOTE 6
7 KEYNOTE 7
8 KEYNOTE 8
9 KEYNOTE 9
10 KEYNOTE 10
11 KEYNOTE 11
12 KEYNOTE 12
13 KEYNOTE 13
14 KEYNOTE 14
15 KEYNOTE 15
16 KEYNOTE 16
17 KEYNOTE 17
18 KEYNOTE 18
19 KEYNOTE 19
20 KEYNOTE 20

FSD

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
FD

SAGE
FD
DEVELOPMENT
GROUP

BENSON
FD

MULTIFAMILY
FD
FD

FIRST FLOOR REFLECTED


CEILING PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:00 AM
E
1 FIRST FLOOR REFLECTED CEILING PLAN PR R CO
A1.21 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.21
AGENCY APPROVAL

GENERAL RCP NOTES


1. SEE SHEET A1.21 FOR GENERAL RCP NOTES.

FD

RATED PARTITION NOTES


1. SEE SHEET A1.21 FOR GENERAL RATED PARTITION NOTES.

KEYED RCP NOTES


1. SEE SHEET A1.21 FOR KEYED RCP NOTES.

LEGEND OF SYMBOLS
1. SEE SHEET A1.21 FOR RCP LEGEND OF SYMBOLS

FD

FD

FSD

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
FD

FD

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

SECOND FLOOR
REFLECTED CEILING
PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:07 AM
E
1 SECOND FLOOR REFLECTED CEILING PLAN PR R CO
A1.22 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.22
AGENCY APPROVAL

GENERAL RCP NOTES


1. SEE SHEET A1.21 FOR GENERAL RCP NOTES.

FD

RATED PARTITION NOTES


1. SEE SHEET A1.21 FOR GENERAL RATED PARTITION NOTES.

KEYED RCP NOTES


1. SEE SHEET A1.21 FOR KEYED RCP NOTES.

LEGEND OF SYMBOLS
1. SEE SHEET A1.21 FOR RCP LEGEND OF SYMBOLS

FD

FD

FSD

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
FD

FD

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

THIRD FLOOR
REFLECTED CEILING
PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:11 AM
E
1 THIRD FLOOR REFLECTED CEILING PLAN PR R CO
A1.23 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.23
AGENCY APPROVAL

GENERAL RCP NOTES


1. SEE SHEET A1.21 FOR GENERAL RCP NOTES.

FD

RATED PARTITION NOTES


1. SEE SHEET A1.21 FOR GENERAL RATED PARTITION NOTES.

KEYED RCP NOTES


1. SEE SHEET A1.21 FOR KEYED RCP NOTES.

LEGEND OF SYMBOLS
1. SEE SHEET A1.21 FOR RCP LEGEND OF SYMBOLS

FD

FD

FSD

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
FD

FD

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

FOURTH FLOOR
REFLECTED CEILING
PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:17 AM
E
1 FOURTH FLOOR REFLECTED CEILING PLAN PR R CO
A1.24 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.24
AGENCY APPROVAL

DN

N CO GENERAL FINISH NOTES


1. SEE SHEET A1.31 FOR GENERAL FINISH NOTES.

KEYED FINISH NOTES

CO
N
1. SEE SHEET A1.31 FOR KEYED FINISH NOTES.

MATERIAL KEY
1. SEE SHEET A1.31 FOR THE MATERIAL KEY LEGEND.

CO N
N C
O

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

SAGE
DEVELOPMENT
UP
GROUP
N CO

BENSON
MULTIFAMILY

LOWER LEVEL FLOOR


FINISH PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:18 AM
E
1 LOWER LEVEL FLOOR FINISH PLAN PR R CO
A1.30 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.30
MATERIAL KEY AGENCY APPROVAL

EXTENTS OF CPT-1 / CPT-2

EXTENTS OF CPT-1

EXTENTS OF CPT-3

EXTENTS OF CPT-4

DN
GENERAL FINISH NOTES

T
EXTENTS OF CPT-5 / CPT-6 1. PROVIDE SELF-LEVELING CONCRETE FLOOR UNDERLAYMENT
AS REQUIRED TO ACHIEVE A SMOOTH AND LEVEL SUBSTRATE
FOR FLOOR FINISHES.
UP
2. WHERE FLOOR FINISHES DIFFER IN COLOR AND/OR MATERIAL
BETWEEN ROOMS, LOCATE THE JOINT BELOW THE CENTERLINE
EXTENTS OF CPT-7 OF THE (CLOSED) DOOR. PROVIDE TRANSITION STRIPS BETWEEN
FLOORS OF DIFFERENT MATERIALS. SEE COLOR SCHEDULE,
T SECTION 09 0600, FOR TRANSITION STRIP (TRS) TYPES AND
LOCATIONS.

3. ALL FREE-STANDING COLUMNS WITHIN A ROOM SHALL BE


FINISHED WITH THE SAME MATERIAL SCHEDULED FOR THE
EXTENTS OF PC-1 WALLS, UNLESS NOTED OTHERWISE.

4. PAINT ALL ELECTRICAL PANELS AND ACCESS DOORS


THROUGHOUT EXTENTS OF CONSTRUCTION TO MATCH
ADJACENT WALL OR CEILING COLOR, UNLESS NOTED
OTHERWISE.
EXTENTS OF CT-1 5. OWNER FURNISHED EQUIPMENT SHOWN DASHED ON PLAN,
UNLESS NOTED OTHERWISE.

EXTENTS OF CT-2

EXTENTS OF LVT-1

*HBA_CD_KEYED FINISH...
TAG USED FOR THIS SCHEDULE
1 KEYNOTE 1
2 KEYNOTE 2
T

T
3 KEYNOTE 3
4 KEYNOTE 4
5 KEYNOTE 5
6 KEYNOTE 6
T
7 KEYNOTE 7
8 KEYNOTE 8
9 KEYNOTE 9
10 KEYNOTE 10
11 KEYNOTE 11
T
12 KEYNOTE 12
13 KEYNOTE 13
14 KEYNOTE 14
15 KEYNOTE 15
16 KEYNOTE 16
GRAPHIC VWC 17 KEYNOTE 17
BY OTHERS
T 18 KEYNOTE 18
19 KEYNOTE 19
20 KEYNOTE 20

T
T
F

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


T

No. Description Date

T
T
SAGE
DEVELOPMENT
GROUP
T

T
BENSON

T
T
MULTIFAMILY

FIRST FLOOR FINISH


GRAPHIC VWC
BY OTHERS
PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:26 AM
E
1 FIRST FLOOR FINISH PLAN PR R CO
A1.31 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.31
AGENCY APPROVAL

DN

GENERAL FINISH NOTES


1. SEE SHEET A1.31 FOR GENERAL FINISH NOTES.

T
KEYED FINISH NOTES
1. SEE SHEET A1.31 FOR KEYED FINISH NOTES.

MATERIAL KEY
T

1. SEE SHEET A1.31 FOR THE MATERIAL KEY LEGEND.

J J J J

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


T
No. Description Date

T
SAGE
T
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

SECOND FLOOR FINISH


PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:30 AM
E
1 SECOND FLOOR FINISH PLAN PR R CO
A1.32 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.32
AGENCY APPROVAL

T
GENERAL FINISH NOTES

T
1. SEE SHEET A1.31 FOR GENERAL FINISH NOTES.

KEYED FINISH NOTES


1. SEE SHEET A1.31 FOR KEYED FINISH NOTES.

T
MATERIAL KEY
1. SEE SHEET A1.31 FOR THE MATERIAL KEY LEGEND.

T
T

T
T

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


T
No. Description Date

T
T
SAGE
DEVELOPMENT
GROUP
T

BENSON
MULTIFAMILY

THIRD FLOOR FINISH


PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:35 AM
E
1 THIRD FLOOR FINISH PLAN PR R CO
A1.33 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.33
AGENCY APPROVAL

GENERAL FINISH NOTES


1. SEE SHEET A1.31 FOR GENERAL FINISH NOTES.

KEYED FINISH NOTES


1. SEE SHEET A1.31 FOR KEYED FINISH NOTES.

T
MATERIAL KEY
1. SEE SHEET A1.31 FOR THE MATERIAL KEY LEGEND.

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


T
No. Description Date

T
SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

FOURTH FLOOR FINISH


PLAN

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:38 AM
E
1 FOURTH FLOOR FINISH PLAN PR R CO
A1.34 T FO
NO C COPYRIGHT 2018

0' 2' 4' 8' 16'

8/26/19
SHEET: A1.34
WALL TYPE U2.2 = 7 3/8"
2 1/2" @ W3
AGENCY APPROVAL
WALL TYPE U2 = 6 3/4"
6 1/8" @ W2 8" @ V2 7 1/4" B.O. SUBFLOORING/ROOF 6 3/4"
WALL TYPE U1 = 4 3/4" 4 1/8" @ W1 STRUCTURE B.O. SUBFLOORING/ROOF
6" @ V1
B.O. STRUCTURE STRUCTURE
BOTTOM OF CEILING AS SCHEDULED BOTTOM OF CEILING AS SCHEDULED
SEE SEE
SOUND ATTENUATION BLANKET - WHERE INDICATED SOUND ATTENUATION BLANKET - WHERE INDICATED STRUCT. STRUCT.
TWO THICKNESSES OF 2-1/2" TWO THICKNESSES OF 2-1/2"
3 1/2" ACOUSTIC INSULATION FOR HEAD FOR HEAD
FIBERGLASS INSULATION FIBERGLASS INSULATION
5/8" GYPSUM WALL BOARD DETAIL DETAIL
ADDITIONAL 5/8" GYPSUM WALL BOARD @ U2.2
5/8" GYPSUM WALL BOARD 5/8" GYPSUM WALL BOARD
5/8" GYPSUM WALL BOARD 2x4 WOOD STUDS AT 16" O.C. @ W1 (2) LAYERS 5/8" GWB - EACH SIDE
2X4 WOOD STUDS
2X4 WOOD STUDS AT 16 INCHES 2x4 WOOD STUDS TURNED FLAT AT 16" O.C. @ W3 2X4 WOOD STUDS
(STAGGERED) AT 16" O.C.
ON CENTER (WALL TYPE U1) (STAGGERED) AT 16" O.C.
2X4 WOOD STUDS AT 16" O.C. 7/16" PLYWD, ONE SIDE ONLY
2x6 WOOD STUDS AT 16" O.C. @ W2
2X6 WOOD STUDS AT 16 INCHES (WALL TYPE V1)
2X6 WOOD STUDS AT 16" O.C. BASE AS SCHEDULED BASE AS SCHEDULED
ON CENTER (WALL TYPE U2)
BASE AS SCHEDULED (WALL TYPE V2)
BASE AS SCHEDULED PERIMETER SEALANT BOTH SIDES, PERIMETER SEALANT BOTH SIDES,
BASE AS SCHEDULED (DASHED) SEE SPEC SEE SPEC
PERIMETER SEALANT BOTH SIDES PERIMETER SEALANT BOTH SIDES
FLOOR LINE FLOOR LINE
PERIMETER SEALANT - BOTH SIDES
FLOOR LINE FLOOR LINE - SEE PARTITION TYPE NOTES
2X6 SILL PLATE 2X6 SILL PLATE

U1 U2
WOOD STUD W/ GWB W1 W2 W3
WOOD STUD W/ GWB FLOOR LINE
V3
WOOD STUD - SHEAR V4
WOOD STUD - SOUND WALL
1 HR - UL: U314/GA: WP 3510 (WHERE RATED) (NON-RATED) WOOD STUD W/ GWB 1 HR - UL: U340 (WHERE RATED) 1 HR - UL: U340 (WHERE RATED)

U1.1 U2.1
STC - 35
W1.1
V1 V2
2 HR - UL: U411/GA: WP 1522 (WHERE RATED)
STC - 51
NAIMA SOUND CONTROL FOR COMMERCIAL AND RESIDENTIAL BUILDINGS,
STC - 51
NAIMA SOUND CONTROL FOR COMMERCIAL AND RESIDENTIAL BUILDINGS, PARTITION TYPE NOTES
.1 INDICATES SOUND WALL .2 INDICATES SOUND WALL W/ ADDITIONAL GWB .1 INDICATES SOUND WALL STC: 55-59 STAGGERED WOOD STUD WALLS FIGURE 7, VARATION 7D. STAGGERED WOOD STUD WALLS FIGURE 7, VARATION 7D.
1. EXTEND WALL FRAMING AND GYPSUM BOARD AT ALL
PARTITIONS FULL HEIGHT UNLESS OTHERWISE SHOWN OR
1 PARTITION TYPE - U.1 & U.2 2 PARTITION TYPE - W1 & W2 3 PARTITION TYPE - V1 & V2 4 PARTITION TYPE - V3 5 PARTITION TYPE - V4 NOTED. EXTEND WALL FURRING AND GYPSUM BOARD A MINIMUM
A2.01 A2.01 A2.01 A2.01 A2.01 OF 4 INCHES ABOVE THE FINISH CEILING. IF NO CEILING OCCURS,
NOT TO SCALE NOT TO SCALE NOT TO SCALE NOT TO SCALE NOT TO SCALE EXTEND FURRING AND GYPSUM BOARD FULL HEIGHT. <IF ROOM
IS INDICATED ON PLAN TO RECEIVE A VAPOR RETARDER, EXTEND
FURRING AND GYPSUM BOARD FULL HEIGHT.>
8"
2. USE ACOUSTICAL SEALANT, TYPICAL AT THE PERIMETERS OF
1'-4 3/4" PARTITION WALLS AS SHOWN ON THE PARTITION TYPES AND
B.O. SUBFLOORING/ROOF SPECIFIED IN SECTION 07 9005 - JOINT SEALERS. USE FIRE
COMPRESSIBLE FILLER, IF
STRUCTURE SEALANT AT RATED PARTITIONS (PERIMETER AND
PERIMETER RELIEF IS REQUIRED
PENETRATIONS AS SPECIFIED IN SECTION 07 8400 -
SOUND ATTENUATION BLANKET
IF PERIMETER RELIEF IS REQUIRED - FIRESTOPPING). SEALANT NOT REQUIRED AT NON RATED WALLS
(2) LAYERS 1" GWB LINER PANELS 10 GA. BENT PLATE PL'S x 16" LONG OR NON SOUND WALLS.
W/ (3) - 5/8" DIA. EXPN. ANCHORS (3"
ALUMINUM CLIPS EMBED) @ 6" O.C. TO STRUCT. 3. CONSTRUCT PERIMETER RELIEF AND CONTROL JOINTS IN
ABOVE - LOCATE @ GROUTED B.O. STRUCTURE ACCORDANCE WITH 'GA-600-2000 FIRE RESISTANCE DESIGN
B.O. STRUCTURE
5/8" GYPSUM WALL BOARD CORES @ 6'-0" O.C. MANUAL - 16th EDITION', FIGURES 9 AND 10.

2X6 WOOD STUDS AT 16" O.C. 4. SEE SPECIFICATIONS FOR LOCATION OF PAPER - FACED
1/2" (MAX) CAULK JOINT - GWB CEILING GYPSUM WALLBOARD, GLASS-MAT-FACED GYPSUM WALLBOARD
7/16" PLYWD 8" CONC, SEE STRUCT. TYP. BOTH SIDES AND CEMENT-BASED WALLBOARD.
FOR REINF. AND 1/2" (MAX) CAULK JOINT - RUNNER - ATTACH TO
3/4" AIR SPACE LOCATION OF HEAD TYP. BOTH SIDES STRUCTURE METAL EDGE
BASE AS SCHEDULED RELIEF DETAILS TRIM
METAL EDGE
PERIMETER SEALANT BOTH SIDES TRIM METAL STUDS CUT 1/2" GWB - DO NOT ATTACH WD STUDS CUT 1/2"
GWB - DO NOT ATTACH SHORT OF RUNNER - DO TO TOP RUNNER SHORT OF TOP
FLOOR LINE
FLOOR LINE TO TOP RUNNER NOT ATTACH TO TOP RUNNER - DO NOT
RUNNER ATTACH TO TOP RUNNER

WOOD STUD - FIRE WALL


X1
2 HR - UL: U347 CONFIGURATION B
S1
CONCRETE
STC - 62

6 PARTITION TYPE - X1 7 PARTITION TYPE - S1 8 PERIMETER RELIEF DETAIL 9 ACOUSTIC JOINT DETAIL
A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE
VARIES SEE SECTION
ADDITIONAL LAYER 5/8" GWB @ EWA-1B. 5/8" GWB. SEE SPEC SECTION 09 2116

5/8" GWB. SEE SPEC SECTION 09 2116 5/8" GWB. SEE SPEC SECTION 09 2116 7/16" WALL SHEATHING @ EWA-3A. SEE STRUCTURAL. 5/8" GWB. SEE SPEC SECTION 09 2116 5/8" GWB. SEE SPEC SECTION 09 2116

7/16" WALL SHEATHING @ EWA-1A & EWA-1B. SEE STRUCTURAL. VAPOR RETARDER. SEE SPEC SECTION 07 2100 VAPOR RETARDER. SEE SPEC SECTION 07 2100 VAPOR RETARDER. SEE SPEC SECTION 07 2100 VAPOR RETARDER. SEE SPEC SECTION 07 2100

VAPOR RETARDER. SEE SPEC SECTION 07 2500 2x6 WOOD STUD FRAMING @ 16" O.C. SEE STRUCTURAL 2x6 WOOD STUD FRAMING @ 16" O.C. SEE STRUCTURAL 2x6 WOOD STUD FRAMING @ 16" O.C. SEE STRUCTURAL 2x6 WOOD STUD FRAMING @ 16" O.C. SEE STRUCTURAL

2x6 WOOD STUD FRAMING @ 16" O.C. SEE STRUCTURAL FILL CAVITY W/ BATT INSULATION. MIN R-19. FILL CAVITY W/ BATT INSULATION. MIN R-19. FILL CAVITY W/ BATT INSULATION. MIN R-19. FILL CAVITY W/ BATT INSULATION. MIN R-19.
SEE SPEC SECTION 07 2100 SEE SPEC SECTION 07 2100 SEE SPEC SECTION 07 2100 SEE SPEC SECTION 07 2100
FILL CAVITY W/ BATT INSULATION. MIN R-19.
SEE SPEC SECTION 07 2100 7/16" WALL SHEATHING W/ FACTORY LAMINATED 7/16" WALL SHEATHING W/ FACTORY LAMINATED 7/16" WALL SHEATHING W/ FACTORY LAMINATED 7/16" WALL SHEATHING W/ FACTORY LAMINATED
WATER-RESISTIVE AND AIR BARRIER LAYER. SEE WATER-RESISTIVE AND AIR BARRIER LAYER. SEE WATER-RESISTIVE AND AIR BARRIER LAYER. SEE WATER-RESISTIVE AND AIR BARRIER LAYER. SEE
7/16" WALL SHEATHING W/ FACTORY LAMINATED SPEC SECTION 06 1000 SPEC SECTION 06 1000 SPEC SECTION 06 1000 SPEC SECTION 06 1000
WATER-RESISTIVE AND AIR BARRIER LAYER. SEE
SPEC SECTION 06 1000

1 3/4" AIR SPACE

BRICK TIE. SEE SPEC SECTION 04 2000

FACING BRICK. SEE SPEC SECTION 04 2000 FIBER CEMENT LAP SIDING. SEE SPEC SECTION 07 4646 METAL PANEL. SEE SPEC SECTION 07 4619 METAL COMPOSITE MATERIAL. SEE SPEC SECTION 07 4213 WOOD SIDING. SEE SPEC SECTION

2012 IECC: ASSEMBLY U-FACTOR REQUIRED: 0.060 MAX. 2012 IECC: ASSEMBLY U-FACTOR REQUIRED: 0.060 MAX. 2012 IECC: ASSEMBLY U-FACTOR REQUIRED: 0.060 MAX. 2012 IECC: ASSEMBLY U-FACTOR REQUIRED: 0.060 MAX. 2012 IECC: ASSEMBLY U-FACTOR REQUIRED: 0.060 MAX.

NFPA 285: N/A NFPA 285: N/A NFPA 285: N/A NFPA 285: N/A NFPA 285: N/A

FIRE RATING: 1HR (UL-U356) FIRE RATING: 1HR (UL-U356) FIRE RATING: 1HR (UL-U356) FIRE RATING: 1HR (UL-U356) FIRE RATING: 1HR (UL-U356)

10 TYP EXTERIOR WALL ASSEMBLY #1 (EWA-1) 11 TYP EXTERIOR WALL ASSEMBLY #2 (EWA-2) 12 TYP EXTERIOR WALL ASSEMBLY #3 (EWA-3) 13 TYP EXTERIOR WALL ASSEMBLY #4 (EWA-4) 14 TYP EXTERIOR WALL ASSEMBLY #5 (EWA-5)
A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE

MECHANICALY FASTENED. TPO ROOF MEMBRANE.


SEE SPEC SECTION 07 5423
WOOD SIDING. SEE SPEC SECTION
1" GYPSUM BASED UNDERLAYMENT. 1-1/4" GYPSUM BASED UNDERLAYMENT. MECHANICALY FASTENED. TPO ROOF MEMBRANE. MECHANICALY FASTENED. TAPERED INSULATION.
SEE SPEC SECTION 03 5400. SEE SPEC SECTION 03 5400. SEE SPEC SECTION 07 5423 SEE ROOF MEMBRANE SPEC SECTION 07 5423
7/16" WALL SHEATHING W/ FACTORY LAMINATED
MECHANICALY FASTENED. TAPERED INSULATION

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


WATER-RESISTIVE AND AIR BARRIER LAYER. MECHANICALY FASTENED CONT INSULATION.
SEE SPEC SECTION 06 1000 AT ROOF CRICKETS ONLY. SEE ROOF SEE ROOF MEMBRANE SPEC SECTION 07 5423
1/4" ACOUSTICAL MAT.
SEE SPEC SECTION 03 5400
MEMBRANE SPEC SECTION 07 5423 No. Description Date
7/16" WALL SHEATHING. SEE STRUCTURAL.
VAPOR RETARDER. SEE SPEC SECTION 07 5423
2x6 WOOD STUD FRAMING @ 16" O.C. SEE STRUCTURAL

7/16" WALL SHEATHING W/ FACTORY LAMINATED


3/4" SHEATHING. SEE SPEC SECTION 06 1000

WOOD JOIST. SEE STRUCTURAL AND SPEC


3/4" SHEATHING. SEE SPEC SECTION 06 1000

2x10 MIN WOOD JOIST. SEE STRUCTURAL AND


SAGE
WATER-RESISTIVE AND AIR BARRIER LAYER.
SEE SPEC SECTION 06 1000
SECTION 06 1753

3 1/2" BATT INSULATION. SEE SPEC


SPEC SECTION 06 1753

3 1/2" BATT INSULATION. SEE SPEC


3/4" SHEATHING. SEE SPEC SECTION 06 1000

WOOD JOIST. SEE STRUCTURAL AND SPEC


3/4" SHEATHING. SEE SPEC SECTION 06 1000 DEVELOPMENT
SECTION 06 1753 WOOD JOIST. SEE STRUCTURAL AND SPEC
WOOD SIDING. SEE SPEC SECTION SECTION 09 2166

1/2" RESELIENT CHANNEL. SEE SPEC SECTION 09 2116


SECTION 09 2166

1/2" RESELIENT CHANNEL. SEE SPEC SECTION 09 2116


BATT INSULATION. SEE SPEC
SECTION 07 2100
SECTION 06 1753
GROUP
5/8" TYPE 'X' GWB. SEE SPEC SECTION 09 2116 5/8" TYPE 'X' GWB. SEE SPEC SECTION 09 2116 VAPOR RETARDER. SEE SPEC SECTION 07 2100
1/2" RESELIENT CHANNEL. SEE SPEC SECTION 09 2116
2012 IECC: N/A FIRE RATING: 1HR (UL L521) FIRE RATING: 1HR (UL L502)
5/8" TYPE 'X' GWB. SEE SPEC SECTION 09 2116 2012 IECC: MIN R-36* CONTINUOUS INSULATION (PROVIDED)
NFPA 285: N/A

FIRE RATING: N/A UNIT FLOOR/CEILING ASSEMBLY CORRIDOR FLOOR/CEILING ASSEMBLY


2012 IECC: MIN R-49 ATTIC INSULATION (REQUIRED)

FIRE RATING: 1HR (UL L528 SYSTEM NO. 1)


*R-36 REQUIRED PER COMCHECK

FIRE RATING: NON-RATED


BENSON
MULTIFAMILY
15 TYP EXTERIOR WALL ASSEMBLY #6 (EWA-6) 16 TYP FLOOR/CEILING ASSEMBLY #1 (FCA-1) 17 TYP FLOOR/CEILING ASSEMBLY #2 (FCA-2) 18 TYP ROOF/CEILING ASSEMBLY #1 (RCA-1) 19 TYP ROOF/CEILING ASSEMBLY #2 (RCA-2)
A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE A2.01 NOT TO SCALE

PARTITION TYPES

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:41 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A2.01
VERIFY SPEC SECTIONS ARE USED BELOW

AGENCY APPROVAL
REMEMBER TO ADD REMARKS
IN DOOR SCHEDULE FOR:
DOOR SCHEDULE
DOOR DOOR FRAME
• CARD READERS
NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
• DELAYED EGRESS 001 18' - 0" 9' - 0"
• ACCESS CONTROL 002 --- 3' - 0" 7' - 0" D2 HM --- --- HM --- 0' - 5 3/4" --- ---
• SPECIALTY DOORS 004 PR. 4' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 5 3/4" --- ---
• SPECIAL GLASS TYPES 005 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 5 3/4" --- ---
SEE SEE 006 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 5 3/4" --- ---
SEE SEE 006A --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 5 3/4" --- ---
SCHED SCHED
040 --- 3' - 0" 7' - 0" D3 HM --- --- HM --- 0' - 5 3/4" --- ---
SCHED SCHED 6" 4" 040A --- 3' - 0" 7' - 6" D2 AL ANOD --- AL ANOD 0' - 4 1/2" --- ---
041 --- 3' - 0" 7' - 0" D3 HM --- --- HM --- 0' - 5 3/4" --- ---
100 PR. 6' - 0" 7' - 6" D2 AL ANOD --- AL ANOD 0' - 4 1/2" --- ---
GLAZING 101 PR. 6' - 0" 7' - 6" D2 AL ANOD --- AL ANOD 0' - 4 1/2" --- ---
GLAZING

SEE SCHED
2'-6"
102 12' - 4" 7' - 8" D34
SEE SCHED

SEE SCHED

SEE SCHED
103 PR. 6' - 0" 7' - 6" D2 AL ANOD --- AL ANOD 0' - 4 1/2" --- ---
105 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 5 3/4" --- ---
106 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---

3'-7" MAX
10" MIN

SEE SPEC 107 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 5 3/4" --- ---
FOR STILE 110 --- 3' - 0" 7' - 6" D2 AL ANOD --- AL ANOD 0' - 4 1/2" --- ---
AND RAIL 111 --- 3' - 0" 7' - 4 1/2" D2 AL ANOD --- AL ANOD 0' - 4 1/2" --- ---
WIDTHS
112 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 5 3/4" --- ---
113 --- 3' - 0" 7' - 4 1/2" D2 AL ANOD --- AL ANOD 0' - 4 1/2" --- ---
MEDIUM STILE SECTIONAL 113A
120
---
---
3' - 0"
3' - 6"
7' - 0"
7' - 0"
D1
D3
WD
WD
---
---
---
---
WD
HM
---
---
0' - 4 3/4"
0' - 8 1/4"
---
---
---
---
GENERAL NOTES
GLAZED 121 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
D1 D2 D3 D7 122 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- --- 1. DOOR THICKNESS AS SPECIFIED UNLESS OTHERWISE NOTED.
123 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- ---
2. ALL WINDOWS SHALL BE GLAZED WITH GLASS TYPE <insert>
131 --- 3' - 6" 7' - 0" D3 WD --- --- HM --- 1' - 5 3/4" --- ---
AT EXTERIOR AND <insert> AT INTERIOR UNLESS OTHERWISE
140 --- 3' - 0" 7' - 0" D3 WD --- --- HM --- 0' - 9 1/2" --- ---
DOOR TYPES 141
141A
---
---
3' - 0"
3' - 0"
7' - 0"
8' - 0"
D3
D2
WD
AL
---
ANOD
---
---
HM
AL
---
ANOD
0' - 9 1/2"
0' - 4 1/2"
---
---
---
---
NOTED. SEE SPEC SECTION 08 8000 GLAZING.

3. ALL DOORS AND FRAMES SHALL BE GLAZED WITH GLASS


221 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- --- TYPE <insert> AT EXTERIOR AND <insert> AT INTERIOR UNLESS
222 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- --- OTHERWISE NOTED. SEE SPEC SECTION 08 8000 GLAZING.
223 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- --- 4. CONTRACTOR TO VERIFY LOCATIONS OF REQUIRED SAFETY
224 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- --- GLAZING WITH LOCAL CODE AND PROVIDE AS NECESSARY.
224A --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- ---
231 PR. 2' - 10" 7' - 0" D1 WD --- --- HM --- 1' - 5 3/4" --- --- 5. SILICONE SEALANT AT ALL INTERIOR BUTT GLAZED JOINTS,
240 --- 3' - 0" 7' - 0" D3 WD --- --- HM --- 0' - 9 1/2" --- --- UNO. SEE SPEC SECTION 08 8000 GLAZING.
241 --- 3' - 0" 7' - 0" D3 WD --- --- HM --- 0' - 9 1/2" --- --- 6. ALUMINUM FRAME (ALF) SEE SPEC SECTION 08 1116.
321 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
5'-11" 8'-10 1/2" 11'-9" SEE SCHEDULE 322 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- --- 7. ALUMINUM STOREFRONT (ALSF) SEE SPEC SECTION 08 4313.
323 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- ---
324 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- --- <PICK ONE>
8. HOLLOW METAL DOOR AND FRAME (HM) SEE SPEC
324A --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- ---
SECTION 08 1113. TYPICAL FRAME WIDTH 2 INCHES UNO.
331 PR. 2' - 10" 7' - 0" D1 WD --- --- HM --- 1' - 5 3/4" --- --- 8. HOLLOW METAL FRAME (HM) SEE SPEC SECTION 08 1213.
340 --- 3' - 0" 7' - 0" D3 WD --- --- HM --- 0' - 9 1/2" --- --- TYPICAL FRAME WIDTH 2 INCHES UNO.
341 --- 3' - 0" 7' - 0" D3 WD --- --- HM --- 0' - 9 1/2" --- ---
7'-11 1/2"

7'-11 1/2"

7'-11 1/2"

421 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- --- 9. FLUSH WOOD DOOR (WD) SEE SPEC SECTION 08 1416.
422 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
423 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- ---
424 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- ---
425 --- 3' - 0" 7' - 0" D1 HM --- --- HM --- 0' - 7 3/4" --- --- GENERAL DOOR SCHEDULE
431 PR. 2' - 10" 7' - 0" D1 WD --- --- HM --- 1' - 5 3/4" --- ---
440
441
---
---
3' - 0"
3' - 0"
7' - 0"
7' - 0"
D3
D3
WD
WD
---
---
---
---
HM
HM
---
---
0' - 9 1/2"
0' - 9 1/2"
---
---
---
---
NOTES (DSN)
D22 D23 D24 D34 1. <insert notes keyed to the door schedule remarks column>.

NANA WALL WD65 FOLDFLAT

DOOR TYPES (CONT.)


EXTERIOR BRICK
4" HEAD AT
TYP UNO

SEE TYP UNO SEE TYP UNO

SCHED SCHED
SEE SCHED

SEE SCHED

F1 F2

FRAME TYPES

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
34'-0 1/2"
EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ
SAGE
WINDOW SCHEDULE DEVELOPMENT
QTY TYPE WIDTH HEIGHT MFR MODEL
GROUP
5'-0"

30 W1 2' - 0" 5' - 0"


8 W2 2' - 4" 5' - 0"
7'-8"

3 W3.1 3' - 0" 5' - 0"


14 W3.2 3' - 0" 5' - 0"
3 W3.3 3' - 0" 5' - 6"
2'-8"

94 W4 5' - 11 1/2" 4' - 11 3/4"


1
2
1
W5
W6
W7
9' - 0"
6' - 0"
9' - 0"
5' - 0"
5' - 0"
5' - 0"
BENSON
S1 S2 S3 6
3
10
W8
W9
W10
6' - 0"
6' - 0"
9' - 0"
5' - 6"
5' - 6"
5' - 6"
MULTIFAMILY
1 W11 9' - 0" 5' - 6"
7 W12 3' - 4" 5' - 0"

FRAME TYPES
UNITS W3.1-W3.3 TO BE MULLED
TOGETHER IN FIELD AT CORNER CURVE.
DOOR & FRAME TYPES &
5'-11 1/2" 9'-0" 6'-0" 9'-0"

3'-0"
EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ 6'-0" 6'-0" 9'-0" 9'-0"
SCHEDULE
2'-0" 2'-4" 3'-0"
3'-0" EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ
CHECK RAIL

CHECK RAIL

CHECK RAIL

CHECK RAIL

CHECK RAIL
1'-6"

1'-6"

1'-6"

1'-6"

1'-6"
4'-11 3/4"
5'-6"

5'-6"

5'-6"

5'-6"

5'-6"
5'-0"

5'-0"

5'-0"

5'-0"

5'-0"

5'-0"

5'-0"
8'-0"

8'-0"

8'-0"
7'-6"

7'-6"

7'-6"

F F F F F F F F F F F F F F F
3'-0 1/2"
2'-6"

2'-6"

2'-6"

2'-6"

2'-6"

2'-6"
3'-0"

3'-0"

3'-0"

3'-0"

3'-0"

3'-0"

F F F F F F F F F F F F 119 SOUTH 49TH AVENUE


6"

6"

6"

6"

6"

6"
OMAHA, NEBRASKA 68132
(402)551-0800

W1 W2 W3.1 W3.2 W3.3 W4 W5 W6 W7 W8 W9 W10 W11 RY N PROJECT: 17073


I A
N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:48 AM
E
PR R CO
FO
WINDOW TYPES NO
T C COPYRIGHT 2018

8/26/19
SHEET: A2.11
AGENCY APPROVAL

*HBA_CD_ROOM FINISH SCHEDULE


Number Name Floor Finish Base Finish Wall Finish Ceiling Finish Comments
LOWER LEVEL PLAN
001 GARAGE
002 VESTIBULE
003 ELEVATOR
004 TRASH
005 MECHANICAL
006 STORM SHELTER
040 STAIR
041 STAIR
FIRST FLOOR PLAN
100 VESTIBULE CPT-3 RB-1 P-1 P-1
101 LOBBY CPT-3 / CPT-4 / PC-1 RB-1 P-1 P-1 / WD-4
102 PARTY ROOM P1 / PT-4
103 GAME ROOM CPT-1 / CPT-4 RB-1 P2 / WD-2 P1
104 HALL
105 JANITOR PC-1 RB-1 P-1 P-1
106 MEN'S RR PT-1 PT-2 PT-2 / P-3 P-1
107 WOMEN'S RR PT-1 PT-2 PT-2 / P-3 P-1
108
109
HALL
BUSINESS CENTER
PC-1
PC-1
RB-1
RB-1
P-1
P-1
WD-4
P-1
ROOM FINISH SCHED NOTES
110 MAIL PC-1 RB-1 P-1 / WD-2 / PT-3 P-1
111 OFFICE CPT-1 RB-1 P-1 P-1 1. SEE FLOOR FINISH PLAN, <sheet>, FOR ACCENT FLOOR FINISH
112 STORAGE CPT-1 RB-1 P-1 P-1 LOCATIONS.
113 FITNESS CENTER CPT-5 / CPT-6 RB-1 P-3 / WD-2 P-3 / ACT-1 2. ALL WALLS TO BE PAINTED <P-X> UNLESS NOTED
120 ELEVATOR LOBBY PC-1 RB-1 P-1 P-1 OTHERWISE. SEE FLOOR FINISH PLAN <sheet> FOR ACCENT WALL
121 TRASH PC-1 RB-1 P-1 P-1 FINISH LOCATIONS. (alternate wording: ALL WALLS TO BE FIRST
122 MECH PC-1 RB-1 P-1 FINISH LISTED, UNLESS NOTED OTHERWISE. SEE FLOOR FINISH
123 STORAGE PLAN <sheet> FOR ACCENT WALL LOCATIONS.)
130 CORRIDOR
3. SEE REFLECTED CEILING PLAN, <sheet>, FOR ACCENT CEILING
131 CORRIDOR CPT-1 / CPT-2 RB-1 P-1 / P-3 P-3 / ACT-2 FINISH LOCATIONS.
133 CORRIDOR CPT-1 / CPT-2 RB-1 P-1 / P-3 P-3 / ACT-2
140 STAIR 4. SEE INTERIOR ELEVATIONS, A8 SERIES, FOR TILE PATTERN.
141 STAIR
5. SEE INTERIOR ELEVATIONS, A8 SERIES, FOR ACCENT FINISH
SECOND FLOOR PLAN
LOCATIONS.
220 ELEVATOR LOBBY
221 TRASH 6. FIBERGLASS REINFORCED PLASTIC (FRP) UP TO 4’-0” A.F.F.
222 TELECOM WITH PAINT AS SCHEDULED ABOVE AND AT ALL OTHER WALLS.
223 STORAGE SEE FLOOR FINISH PLAN <sheet> FOR EXTENTS.
224 ELECTRICAL
230 CORRIDOR
231 CORRIDOR
232 CORRIDOR
233 CORRIDOR
240 STAIR
241 STAIR
THIRD FLOOR PLAN
320 ELEVATOR LOBBY
321 TRASH
322 TELECOM
323 STORAGE
324 ELECTRICAL
330 CORRIDOR
331 CORRIDOR
332 CORRIDOR
333 CORRIDOR
340 STAIR
341 STAIR
FOURTH FLOOR PLAN
420 ELEVATOR LOBBY
421 TRASH
422 TELECOM
423 STORAGE
424 ELEC
425 ROOF ACCESS
430 CORRIDOR
431 CORRIDOR
432 CORRIDOR
433 CORRIDOR
440 STAIR
441 STAIR

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

ROOM FINISH SCHEDULE

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:51:52 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A2.31
AGENCY APPROVAL

GENERAL AXONOMETRIC /
PERSPECTIVE NOTES
1. ALL AXONMETRIC AND PERSPECTIVE DRAWINGS ARE SHOWN
NOT TO SCALE AND ARE FOR REFERENCE ONLY.

1 NORTHWEST PERSPECTIVE 3 SOUTHEAST PERSPECTIVE


A3.01 NOT TO SCALE A3.01 NOT TO SCALE

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

SAGE
DEVELOPMENT
GROUP
2 NORTHEAST PERSPECTIVE 4 SOUTHWEST PERSPECTIVE
A3.01 NOT TO SCALE A3.01 NOT TO SCALE
BENSON
MULTIFAMILY

BUILDING
AXONOMETRICS /
PERSPECTIVES

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:52:42 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A3.01
AGENCY APPROVAL
MATERIAL KEY
_ 2
_ 2 _ 1 _ 2 _ 3
A3.31
A4.02 A4.01 A4.01 A4.01
MET-2 MT-1 MET-3 MET-3 EXTENTS OF MT-1
MT-1 MET-3
WD-1 MET-3
FCB-1

T.O. ROOF DECK


144' - 0" EXTENTS OF MET-2

EXTENTS OF WD-1
FOURTH FLOOR PLAN
133' - 0"

EXTENTS OF FCB-1

GENERAL ELEVATION NOTES


THIRD FLOOR PLAN 1. SEE SHEET A0.01 - ORIENTATION PLAN - FOR EXTERIOR BUILDING
122' - 0" ELEVATION LOCATIONS
EXTENTS OF CONC-1

SECOND FLOOR PLAN EXTENTS OF FB-1


111' - 0"

FIRST FLOOR PLAN


100' - 0"
SF-1
WD-1
PC-1 FB-1
FB-1
FB-1

CONC-1
KEYED ELEVATION NOTES
TAG USED FOR THIS SCHEDULE
1 KEYNOTE 1
2 KEYNOTE 2
LOWER LEVEL PLAN 3 KEYNOTE 3
84' - 0"
4 KEYNOTE 4
5 KEYNOTE 5
6 KEYNOTE 6
7 KEYNOTE 7
1 WEST ELEVATION 8 KEYNOTE 8
A3.11 9 KEYNOTE 9
10 KEYNOTE 10
0' 2' 4' 8' 16' 11 KEYNOTE 11
12 KEYNOTE 12
13 KEYNOTE 13
14 KEYNOTE 14
15 KEYNOTE 15
4 16 KEYNOTE 16
_ 1 1 3 _ 1 _
_ _ 17 KEYNOTE 17
A5.52 A4.02 A4.02
A3.31 A4.02 PC-1 MT-1 MET-3 WD-1 FCB-1 MET-3 MT-1 FCB-1 MT-1 18 KEYNOTE 18
19 KEYNOTE 19
FCB-1 20 KEYNOTE 20

T.O. ROOF DECK T.O. ROOF DECK


144' - 0" 144' - 0"

FOURTH FLOOR PLAN FOURTH FLOOR PLAN


133' - 0" 133' - 0"
MET-2

THIRD FLOOR PLAN THIRD FLOOR PLAN


122' - 0" 122' - 0"

SECOND FLOOR PLAN 5 SECOND FLOOR PLAN


111' - 0" A3.11 111' - 0"

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
FIRST FLOOR PLAN FIRST FLOOR PLAN
100' - 0" 100' - 0"

CONC-1
SAGE
SF-1
DEVELOPMENT
PC-1 FB-1 CONC-1
FB-1 CONC-1
GROUP
LOWER LEVEL PLAN LOWER LEVEL PLAN
84' - 0" 84' - 0"
FB-1 CONC-1

_ 1
BENSON
NORTH ELEVATION
A3.31

NORTHWEST ELEVATION
MULTIFAMILY
2 3
A3.11 A3.11

0' 2' 4' 8' 16' 0' 2' 4' 8' 16'

1 1/2" 2'-11" 1 1/2" 2'-11" 1 1/2"


BUILDING ELEVATIONS
WD-1
2" 2"

3/4"
3/4"x2-1/2" FLAT STEEL; GALVANIZED

3"
1-1/2" SQ. TUBE; GALVANIZED

2'-11 1/4"
PERFORATE METAL; GALVANIZED

COMPOSITE DECKING FASICA

3"
SECOND FLOOR PLAN
111' - 0" 8 1/4"
119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800

HSS16x4 AT BALCONIES; TYP.

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:52:58 AM
E
5 ENLARGED BALCONY RAILING PR R CO
A3.11 T FO
NO C COPYRIGHT 2018

0' 6" 1' 2' 4'

8/26/19
SHEET: A3.11
AGENCY APPROVAL

_ 2
_ 2
A5.52
A5.53

T.O. ROOF DECK T.O. ROOF DECK


144' - 0" 144' - 0"

FOURTH FLOOR PLAN FOURTH FLOOR PLAN


133' - 0" 133' - 0"

THIRD FLOOR PLAN THIRD FLOOR PLAN


GENERAL ELEVATION NOTES
122' - 0" 122' - 0"
1. SEE SHEET A3.11 FOR GENERAL ELEVATION NOTES.

SECOND FLOOR PLAN SECOND FLOOR PLAN


KEYED ELEVATION NOTES
111' - 0" 111' - 0"
1. SEE SHEET A3.11 FOR KEYED ELEVATION NOTES.

FIRST FLOOR PLAN FIRST FLOOR PLAN


MATERIAL LEGEND
100' - 0" 100' - 0"
1. SEE SHEET A3.11 FOR THE MATERIAL LEGEND.

LOWER LEVEL PLAN LOWER LEVEL PLAN


84' - 0" 84' - 0"

3 EAST ELEVATION - SOUTH 2 EAST ELEVATION - NORTH


A3.12 A3.12

0' 2' 4' 8' 16' 0' 2' 4' 8' 16'

_ 1
A5.53
_ 4 1
_
A4.01 A3.31

T.O. ROOF DECK


144' - 0"

FOURTH FLOOR PLAN


133' - 0"

THIRD FLOOR PLAN


122' - 0"

SECOND FLOOR PLAN


111' - 0"

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
FIRST FLOOR PLAN
100' - 0"

SAGE
DEVELOPMENT
GROUP
LOWER LEVEL PLAN
84' - 0"

_ 1
BENSON
A3.31
MULTIFAMILY
1 SOUTH ELEVATION
A3.12

0' 2' 4' 8' 16'

BUILDING ELEVATIONS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:03 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A3.12
AGENCY APPROVAL

_ 1
A3.31

T.O. ROOF DECK T.O. ROOF DECK


144' - 0" 144' - 0"

FOURTH FLOOR PLAN FOURTH FLOOR PLAN


133' - 0" 133' - 0"

THIRD FLOOR PLAN THIRD FLOOR PLAN


122' - 0" 122' - 0"

SECOND FLOOR PLAN SECOND FLOOR PLAN


111' - 0" 111' - 0"

FIRST FLOOR PLAN FIRST FLOOR PLAN


100' - 0" 100' - 0"

_ 1
A3.31

3 COURTYARD NORTHWEST 1 COURTYARD NORTH


A3.13 A3.13

0' 2' 4' 8' 16' 0' 2' 4' 8' 16'

_ 2
A3.31

3 _ 4
_ 1 _ 1
_ A4.03
A4.03 A4.03
A3.31

T.O. ROOF DECK T.O. ROOF DECK


144' - 0" 144' - 0"

FOURTH FLOOR PLAN FOURTH FLOOR PLAN


133' - 0" 133' - 0"

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


THIRD FLOOR PLAN THIRD FLOOR PLAN
122' - 0" 122' - 0" No. Description Date

SAGE
SECOND FLOOR PLAN
111' - 0"
SECOND FLOOR PLAN
111' - 0"
DEVELOPMENT
GROUP
FIRST FLOOR PLAN FIRST FLOOR PLAN
100' - 0" 100' - 0"
BENSON
MULTIFAMILY
4 COURTYARD WEST 2 COURTYARD SOUTH
A3.13 A3.13
_ 1
0' 2' 4' 8' 16' 0' 2' 4' 8' 16'
A3.31

BUILDING ELEVATIONS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:10 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A3.13
AGENCY APPROVAL

_ 5
A4.02

T.O.
T.O.ROOF DECK
ROOF DECK T.O. ROOF DECK
144'- -0"
144' 0" 144' - 0"

FOURTH FLOOR
FOURTH FLOOR LEVEL PLAN
FOURTH FLOOR PLAN
133' - 0" 133'- -0"
133' 0"

THIRD FLOOR
THIRD FLOOR LEVEL PLAN
THIRD FLOOR PLAN
122' - 0" 122'- -0"
122' 0"

SECOND FLOOR
SECOND FLOOR LEVEL PLAN
SECOND FLOOR PLAN
111' - 0" 111' - -0"0"
111'

FIRST FLOOR
FIRST FLOOR LEVEL PLAN
FIRST FLOOR PLAN
100' - 0" 100'- -0"
100' 0"

LOWER LEVEL
LOWER LEVELPLAN
PLAN LOWER LEVEL
84'84'- -0"
0" 84' - 0"

1 NORTH-SOUTH SECTION
A3.31

0' 2' 4' 8' 16'

_ 2
A5.54

T.O.ROOF
T.O. ROOF DECK
DECK T.O. ROOF DECK
144' - 0"
144' - 0" 144' - 0"

FOURTH FLOOR
FOURTH FLOOR LEVEL PLAN
FOURTH FLOOR PLAN
133' - 0" 133' - -0"0"
133'

THIRD FLOOR
THIRD FLOOR LEVEL PLAN
THIRD FLOOR PLAN
122' - 0" 122'- -0"
122' 0"

SECOND FLOOR

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


SECOND FLOOR LEVEL PLAN
SECOND FLOOR PLAN
111' - 0" 111'- -0"
111' 0" No. Description Date

SAGE
FIRST FLOOR
FIRST FLOOR LEVEL
100' - 0"
PLAN
FIRST FLOOR PLAN
100'- -0"
100' 0"
DEVELOPMENT
GROUP

LOWER LEVEL BENSON


PLAN
LOWER LEVEL PLAN LOWER LEVEL
84' - 0"
84' - 0" 84' - 0"
MULTIFAMILY

2 EAST-WEST SECTION ANGLED


A3.31

0' 2' 4' 8' 16'


BUILDING SECTIONS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:23 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A3.31
AGENCY APPROVAL

T.O. ROOF DECK


144' - 0"

GENERAL SECTION NOTES


1. SEE SECTION 1 ON THIS SHEET FOR ALL TYPICAL NOTES AND
DETAILS REFERENCES. SEE THE INDIVIDUAL WALL SECTION FOR
NOTES AND DETAIL REFERENCES DESCRIBING UNIQUE
CONDITIONS.

2. SEE BUILDING STATISTICS ON SHEET A0.11 FOR FIRE


PROTECTION REQUIREMENTS OF BUILDING COMPONENTS.

3. SEE CIVIL PLANS FOR FINISH GRADES.

4. SEE STRUCTURAL DRAWINGS FOR ALL <edit the following:>


CAST-IN-PLACE CONCRETE PIER CAP, DRILLED PIERS AND
FOURTH FLOOR PLAN GRADE BEAM SIZES.
133' - 0"
5. CONSTRUCT CAST-IN-PLACE CONCRETE SLABS-ON-GRADE
OVER VAPOR BARRIER AND GRANULAR FILL. SEE STRUCTURAL
DRAWINGS FOR SLAB THICKNESS, REINFORCING AND
GRANULAR FILL THICKNESS.

6. TYPICAL FLOOR/CEILING ASSEMBLY SHALL BE


<edit the following:> COMPOSITE METAL DECK WITH CONCRETE
FILL OVER STEEL BEAMS, WITH SUSPENDED CEILINGS AS
SCHEDULED. SEE STRUCTURAL FRAMING PLANS.

7. PROVIDE PERIMETER INSULATION, 2" MINIMUM THICKNESS


AND AS SHOWN ON THE DRAWINGS. EXTEND INSULATION TO A
MINIMUM OF 24" BELOW FINISHED GRADE, AND AS SHOWN ON
THE DRAWINGS.

8. EXTEND BRICK VENEER TO 8" MINIMUM BELOW GRADE. STEP


VENEER TO FOLLOW GRADES AS SHOWN ON BUILDING
ELEVATIONS. COORDINATE WITH CIVIL GRADING PLAN.

9. TYPICAL EXTERIOR WALL ASSEMBLY SHALL BE <edit the


following:> 6" METAL STUD FRAMING AT 16" 0.C. WITH 1/2"
EXTERIOR SHEATHING, BUILDING WRAP, CAVITY AS SHOWN ON
THE DRAWINGS AND STONE OR BRICK VENEER. PROVIDE BATT
INSULATION IN STUD CAVITY WITH VAPOR RETARDER AND 5/8"
GYPSUM BOARD ON INTERIOR FACE OF STUDS.
THIRD FLOOR PLAN 10. METAL ROOF ASSEMBLY SHALL BE <edit the following:> PRE
122' - 0"
FINISHED METAL ROOF PANELS, FLASHING AND ACCESSORIES
OVER 1-1/2" ROOF DECK. ALL HIPS, VALLEYS, RIDGES AND
EAVES SHALL RECEIVE 20 GAUGE GALVANIZED SHEET METAL
OVER THE DECK TO RECEIVE SELF-ADHERING POLYMER-
MODIFIED BITUMINOUS SHEET UNDERLAYMENT.

11. SINGLE PLY ROOF ASSEMBLY SHALL BE <edit the following:>


FULLY ADHERED EPDM MEMBRANE OVER TAPERED INSULATION.

13. BACK SIDE OF PARAPET SHALL BE CONSTRUCTED WITH 7/16"


PLYWOOD SHEATHING AND 5/8" FIRE RESISTIVE EXTERIOR
SHEATHING WITH ROOF MEMBRANE TO EXTEND UP AND OVER
THE TOP OF PARAPET.

14. SEE ROOM FINISH SCHEDULE ON SHEET A2.31 FOR FLOOR,


WALL AND CEILING FINISHES. SEE ROOM FINISH SCHEDULE FOR
CEILING HEIGHTS.

SECOND FLOOR PLAN

8 1/4"
111' - 0"

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

FIRST FLOOR PLAN


100' - 0"
SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

WALL SECTIONS

LOWER LEVEL PLAN


84' - 0"

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

WALL SECTION ARY N PROJECT: 17073


3
I N CTIO
WALL SECTION WALL SECTION WALL SECTION LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:27 AM
A4.01
1 2 4
E
A4.01 A4.01 0' 1' 2' 4' A4.01 PR R CO
T FO
NO
0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' C COPYRIGHT 2018

8/26/19
SHEET: A4.01
AGENCY APPROVAL

T.O. ROOF DECK


144' - 0"

GENERAL SECTION NOTES


1. SEE SHEET A4.01 FOR GENERAL WALL SECTION NOTES

2. SEE SECTION 1 ON THIS SHEET FOR ALL TYPICAL NOTES,


DIMENSIONS, AND DETAIL REFERENCES. SEE THE INDIVIDUAL
WALL SECTION FOR NOTES, DIMENSIONS AND DETAIL
REFERENCES DESCRIBING UNIQUE CONDITIONS.

FOURTH FLOOR PLAN


133' - 0"

THIRD FLOOR PLAN


122' - 0"

SECOND FLOOR PLAN


111' - 0"

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

FIRST FLOOR PLAN


100' - 0"
SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

WALL SECTIONS

LOWER LEVEL PLAN


84' - 0"

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
WALL SECTION WALL SECTION WALL SECTION WALL SECTION BALCONY CROSS-SECTION LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:31 AM
1 2 3 4 5
E
A4.02 A4.02 A4.02 A4.02 A4.02 PR R CO
T FO
NO
0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' C COPYRIGHT 2018

8/26/19
SHEET: A4.02
AGENCY APPROVAL

T.O. ROOF DECK


144' - 0"

GENERAL SECTION NOTES


1. SEE SHEET A4.01 FOR GENERAL WALL SECTION NOTES

2. SEE SECTION 1 ON THIS SHEET FOR ALL TYPICAL NOTES,


DIMENSIONS, AND DETAIL REFERENCES. SEE THE INDIVIDUAL
WALL SECTION FOR NOTES, DIMENSIONS AND DETAIL
REFERENCES DESCRIBING UNIQUE CONDITIONS.

FOURTH FLOOR PLAN


133' - 0"

THIRD FLOOR PLAN


122' - 0"

SECOND FLOOR PLAN


111' - 0"

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

FIRST FLOOR PLAN


100' - 0"
SAGE
DEVELOPMENT
GROUP

1 WALL SECTION 3 WALL SECTION 4 WALL SECTION


A4.03 A4.03 A4.03
BENSON
0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4'

MULTIFAMILY

WALL SECTIONS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:34 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A4.03
AGENCY APPROVAL

GENERAL ENLARGED FLOOR


PLAN NOTES
1. SEE SHEET A1.01 FOR GENERAL PLAN NOTES.

2. ADD ANY ADDITIONAL NOTES REQUIRED HERE FOR


ENLARGED FLOOR PLANS.

5'-1
1/4"
EL
D PAN
ATE
RFOR
W / PE
ING
RAIL
IO
PAT DEPRESS STRUCTURAL SLAB AT TURF LOCATIONS

PROVIDE OUTDOOR 1-1/2”SLITFILM FIBER SYNTHETIC


TURF SYSTEM WITH THATCH LAYER ON A ½” THICK
DRAINABLE SHOCK PAD AND 1-1/4” ULTRABASE
PROFESSIONAL PANEL SYSTEM. THE UNDERLYING
SLAB AREAS TO RECEIVE THE ARTIFICIAL TURF
SYSTEM SHALL BE SLOPED TO A CENTRAL DRAIN
LOCATION AND BE WATERPROOFED
2x12 STEEL SUPPORTS ABOVE (12'-0" AFF) TO PROVIDE
_ 1
SUPPORT FOR DECORATIVE STRING LIGHTS
A3.31
5x5 STEEL POSTS IN PLANTERS (2 EA)
18"H. PRECAST CONCRETE PLANTERS

TO SHEATHING
_ 2
A3.31
3/8"

5'-0"
5'-0 PATIO RAILING W/ PERFORATED PANEL PATIO RAILING W/ PERFORATED PANEL

CONCRETE TRAFFIC TOPPING


W/ WATERPROOF SEALANT;
TYP. AT EXPOSED CONC. SLAB

4'-0"
3 5x5 STEEL COLUMN (16'L.)
FASTENED TO FOUNDATION
A3.13
WALL TO SUPPORT WOOD
4 SLAT WALL.

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


2x12 WOOD SLAT WALL
(12'-0"H.). STAIN TO MATCH
No. Description Date
EXTERIOR WD-1
11 BRICK VENEER OUTDOOR KITCHEN
A2.

11'-6"
DEPRESS STRUCTURAL SLAB AT TURF LOCATIONS
7
+42" +30"
W/ CONCRETE COUNTERTOP
SAGE
9 1
DEVELOPMENT
A8.
01
A3.13 GROUP

24'-5 1/2"
10
BUILT-IN GAS GRILLS
_ 1 2
A4.03
PROVIDE OUTDOOR 1-1/2”SLITFILM FIBER SYNTHETIC
TURF SYSTEM WITH THATCH LAYER ON A ½” THICK
DRAINABLE SHOCK PAD AND 1-1/4” ULTRABASE
PROFESSIONAL PANEL SYSTEM. THE UNDERLYING
SLAB AREAS TO RECEIVE THE ARTIFICIAL TURF
BENSON
SYSTEM SHALL BE SLOPED TO A CENTRAL DRAIN
MULTIFAMILY

11'-6"
LOCATION AND BE WATERPROOFED

CONCRETE TRAFFIC TOPPING


W/ WATERPROOF SEALANT;
TYP. AT EXPOSED CONC. SLAB
18'-0" 8'-8" 18'-0" 10'-0"

_ 2
A3.31
ENLARGED PATIO PLAN

4'-0"
SEE A1.01 FOR EXTENTS OF
CANTILEVERED PEDESTRIAN
BRIDGE AND GUARD RAILS

TO SHEATHING
PATIO RAILING W/ PERFORATED PANEL

5'-0"
01
A8. _ 4 _ 3
12 A4.03 A4.03

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
_ 1
A3.31

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:36 AM
E
1 ENLARGED PATIO PLAN PR R CO
A5.01 T FO
NO C COPYRIGHT 2018

0' 1' 2' 4' 8'

8/26/19
SHEET: A5.01
AGENCY APPROVAL

4'-9"

4'-9"

4'-9"
ROOF DRAIN & ROOF DRAIN & ROOF DRAIN & ROOF DRAIN &
GENERAL ENLARGED FLOOR
OVERFLOW OVERFLOW OVERFLOW OVERFLOW
PLAN NOTES
6'-10 1/2"

6'-10 1/2"
T T T

7'-4 1/2"
3'-0"

3'-0"
3'-6"
1. SEE SHEET A5.01 FOR GENERAL ENLARGED FLOOR PLAN
NOTES.
ROOF LADDER

3'-0"

3'-0"
KEYED ENLARGED FLOOR
3'-6"
3'-0"

3'-0"

3'-0"

3'-0"
PLAN NOTES

4'-0"

4'-0"
3'-0"

3'-0"

3'-0"
3'-6"

1. SEE SHEET A5.01 FOR KEYED ENLARGED FLOOR PLAN NOTES.

3'-0"
LOW VOLTAGE LOW VOLTAGE PANEL
LOW VOLTAGE PANEL SWITCHGEAR FOR

3'-0"
CONDUIT ROOFTOP GENERATOR

5'-11 1/2"
5'-5"

4'-11 1/2"
6'-0"

ELECTRICAL METERS
ELECTRICAL

3'-0"
& SERVICE GEAR ELECTRICAL METERS
CONDUITS
& SERVICE GEAR

5'-4" 5'-1"
5'-4" 5'-3" 5'-4" 15'-11"
5'-4" 5'-3" 5'-4"

1 STORAGE 01 ENLARGED 2 STORAGE 02 ENLARGED 3 STORAGE 03 ENLARGED 4 STORAGE 04 ENLARGED


A5.02 A5.02 A5.02 A5.02

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

ENLARGED PLANS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:53:39 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.02
AGENCY APPROVAL

11'-10 7/8" 7'-1 7/8"

3'-0"

LIVING ROOM

BEDROOM
28'-4 3/4"
22'-0"

7'-9"

3'-10 3/4"
A5.11 CLOSET
4
KITCHEN
06
1'-4"

4'-11 3/4"
A5.11

04
BATHROOM
3'-4 3/4"

3'-11"
CLOSET

3'-6"
COAT

02 MECH
03

01
2'-4 3/4" 3'-4 3/4" 3'-0" 5'-4 3/4"
5'-5 1/4" 13'-6 1/2"
18'-11 3/4"

1 STUDIO "A" UNIT FLOOR PLAN 2 STUDIO "A" UNIT FLOOR FINISH PLAN 3 STUDIO "A" UNIT REFLECTED CEILING PLAN
A5.11 A5.11 A5.11

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

3'-0 3/4" 2'-0" 2'-6" 1'-6" 2'-6" 1'-6"

VANITY FIXTURE
3'-0"

MIRROR

WD-4
4'-0"
7'-3"
1'-2"

SST-1 SST-3
4"

WD-4

WD-4
3'-0"

2'-7"

No. Description Date


1" 2'-0" 2'-6" 1'-6" 2'-6" 1'-6" 3'-1"

4 STUDIO KITCHEN 5 STUDIO BATHROOM SAGE


A5.11

0' 1' 2' 4'


A5.11

0' 1' 2' 4'


DEVELOPMENT
GROUP

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


BENSON
MULTIFAMILY

STUDIO "A" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:20 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.11
AGENCY APPROVAL

15'-7 1/4"
LIVING ROOM BEDROOM
25'-0"
28'-4 3/4"

7'-9"

3'-10 3/4"
A5.11 CLOSET
4
KITCHEN
06
1'-4"

4'-11 3/4"
A5.11

04
BATHROOM
3'-4 3/4"

3'-11"
CLOSET

3'-6"
COAT

03 02 MECH

01
2'-4 3/4" 3'-4 3/4" 3'-0" 5'-4 3/4"
5'-5 1/4" 13'-7 1/2"
19'-0 3/4"

1 STUDIO "B" UNIT FLOOR PLAN 2 STUDIO "B" UNIT FLOOR FINISH PLAN 3 STUDIO "B" UNIT REFLECTED CEILING PLAN
A5.12 A5.12 A5.12

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

No. Description Date

SAGE
DEVELOPMENT
GROUP

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


BENSON
MULTIFAMILY

STUDIO "B" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:24 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.12
AGENCY APPROVAL

7'-1 3/4" 11'-11"

3'-0"
SLIDING DOOR SLIDING DOOR SLIDING DOOR
PANELS W/ TRACKS PANELS W/ TRACKS PANELS W/ TRACKS

LIVING ROOM
12'-7 1/4"

BEDROOM

22'-0"
SLIDING DOOR SLIDING DOOR SLIDING DOOR
7'-9" PANELS W/ TRACKS PANELS W/ TRACKS PANELS W/ TRACKS
25'-4 3/4"

4
3'-10 3/4"

A5.13
CLOSET

KITCHEN
06
1'-4"
4'-11 3/4"

A5.11
5

BATHROOM 04

3'-4 3/4"
3'-11"

CLOSET
3'-6"

COAT

MECH 02
03

01
5'-4 3/4" 3'-0" 3'-4 3/4" 2'-4 3/4"
13'-7 1/2" 5'-5 1/4"
19'-0 3/4"

1 JUNIOR UNIT FLOOR PLAN 2 JUNIOR UNIT FINISH PLAN 3 JUNIOR UNIT REFLECTED CEILING PLAN
A5.13 A5.13 A5.13

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

1'-6" 2'-6" 1'-6" 2'-6" 2'-0" 3'-0 3/4"


3'-0"

WD-4
1'-2"

PAINT
SST-1 AS SCHEDULED

WD-4 No. Description Date


3'-0"

SAGE
1'-6" 2'-6" 1'-6" 2'-6" 2'-0" 1" 2'-11 3/4"
DEVELOPMENT
4 STUDIO MIRRORED KITCHEN GROUP
A5.13

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


0' 1' 2' 4'

BENSON
MULTIFAMILY

JUNIOR UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:28 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.13
AGENCY APPROVAL

24'-0 3/4"
11'-4 3/4" 12'-8"

15'-0 1/2"

BEDROOM LIVING ROOM

3'-2" 3'-4 3/4"

26'-0"
28'-4 3/4"
05
3'-10 3/4"

MECH 02

CLOSET
3'-0 3/4"

6
5
A5.14
06
KITCHEN
5'-4 3/4"

04
BATHROOMA5.14

4 03

2'-4 3/4"
COAT
1'-0"

CLOSET
01
2'-6" 8'-10 3/4" 3'-4 3/4"
16'-7 1/2" 7'-5 1/4"

1 1 BED "A" UNIT FLOOR PLAN 2 1 BED "A" UNIT FLOOR FINISH PLAN 3 1 BED "A" UNIT REFLECTED CEILING PLAN
A5.14 A5.14 A5.14

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

2'-0" 1'-6" 2'-6" 1'-6" 3'-4"

VANITY FIXTURE

MIRROR

3'-5"

3'-9"
WD-4

PAINT
No. Description Date

7'-3"
SST-1 AS SCHEDULED SST-1
SST-3

4"
WD-4
SAGE
3'-8 1/2"

WD-4

WD-4

2'-10"
3'-0"

DEVELOPMENT
1'-1 1/2" 2'-0" 1'-6" 2'-6" 1'-6" 3'-4" 1" 2'-0" 2'-6" 1'-6" 2'-0" 1'-9" 3'-6" GROUP

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


5 1 BEDROOM "A" UNIT KITCHEN 6 1 BEDROOM "A" UNIT KITCHEN 4 1 BEDROOM "A" UNIT BATHROOM
A5.14 A5.14 A5.14

0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4'
BENSON
MULTIFAMILY

1 BED "A" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:32 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.14
AGENCY APPROVAL

24'-0 3/4"
11'-0" 13'-0 3/4"

3'-0"
9'-9 3/4"

7'-4 3/4" 7 1/4" 3'-0"


28'-4 3/4"

05
5'-4 3/4"

25'-4 3/4"
13

06
2'-4 3/4"

A5.15

03
7

A5.15
4
4'-4 3/4"

6
10'-2 1/4"

5 50% OF UNITS
04
RECEIVE AN
ISLAND
02
3'-4 3/4"

01

5'-4 3/4" 3'-6" 5'-6" 9'-1 3/4"


11'-9 3/4" 12'-3"

1 1 BED "B" UNIT FLOOR PLAN 2 1 BED "B" UNIT FINISH FLOOR PLAN 3 1 BED "B" UNIT REFLECTED CEILING PLAN
A5.15 A5.15 A5.15

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

1'-6" 2'-6" 2'-0" 2'-6" 1'-11" 1'-1" 1'-1" 1'-11" 3'-0" 3'-1 3/4"
VANITY FIXTURE

MIRROR

3'-9 1/4"
WD-4
3'-0"

3'-0"

7'-3 1/4"
WD-4
1'-2"

SST-1

4"
PAINT
PAINT AS SCHEDULED
1'-2"

SST-1 SST-1
AS SCHEDULED WD-4
SST-1

2'-10"
WD-4 WD-4

WD-4
No. Description Date
2'-10"
3'-0"

3'-0"

4'-0"

SAGE
2'-8" 2'-8"
1'-6" 2'-6" 2'-0" 2'-6" 1'-0" 2'-0"
DEVELOPMENT
1 BEDROOM "B' UNIT KITCHEN - A 1 BEDROOM "B' UNIT KITCHN - B 1 BEDROOM "B' UNIT KITCHN ISLAND 1 BEDROOM "B' UNIT BATHROOM
A5.15
4
A5.15
5 6
A5.15
7
A5.15
GROUP

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4'

BENSON
MULTIFAMILY

1 BED "B" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:37 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.15
AGENCY APPROVAL

43'-8 1/4"
16'-5 1/2" 27'-2 3/4"
11'-2 1/2" 3'-4 3/4"
3'-0 1/2" 2'-0" 2'-6" 1'-6" 2'-6" 1'-6"
01

VANITY FIXTURE

02

10'-6 3/16"
MIRROR

3'-5"
07 05 04 WD-4

3'-8
3'-0

"
03
3/4"

PAINT
AS SCHEDULED SST-1
SST-1

2'-4
16
A5.

4"
3/4"
" 4 WD-4
2'-4
20'-

WD-4
16
A5.

3'-9"
3/4"
3 5/

1'-0

2'-10"
5
8"

5'-1
0 1/
11'-

2"
11 1

1" 2'-0" 2'-6" 1'-6" 2'-6" 1'-6"


8"
/4"

8 1/
18'-

8" 1 BED "C" UNIT KITCHEN 1 BED "C" UNIT BATHROOM

4'-1
8 7/ 4 5
24'-

0 3/
A5.16 A5.16

16"
3/4" 0' 1' 2' 4' 0' 1' 2' 4'
5'-4
8"

1 1 BED "C" UNIT FLOOR PLAN


A5.16

0' 1' 2' 4' 8'

2 1 BED "C" FLOOR FINISH PLAN


A5.16

0' 1' 2' 4' 8'


No. Description Date

SAGE
DEVELOPMENT
GROUP

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


BENSON
MULTIFAMILY

1 BED "C" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
3 1 BED "C" UNIT REFLECTED CEILING PLAN 2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
A5.16 2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---

0' 1' 2' 4' 8'


20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:42 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.16
AGENCY APPROVAL

15 '-6"
A5. '-2 1/4" /4 " 2

1'-1
10 10 3
7 3/4"

0 1/
3'-4

2"
4 3/
4" 3/4"
28'- 3/4" 3'-4
5'-4

3'-1
0 3/

9'-8
4"

"
5
4"
9 3/

1'-6
12'- 17
A5.

" 2
10

'-4 3
4" /
7'-4 03

4'-0

4'-10"
3/4"

"
01
18

09 04

5'-6 3/4"
4'-0
"

6'-4 3/4"
17 A5.17
A5. 6

24'-11 1/2"
06 14

5'-6 3/4" 5'-10"


14'-
4 1/
16"

13'-0"
05

14'-4 7/16"

1 2 BED "A" UNIT FLOOR PLAN 2 2 BED "A" UNIT FLOOR FINISH PLAN 3 2 BED "A" UNIT REFLECTED CEILING PLAN
A5.17 A5.17 A5.17

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

3'-0 3/4" 2'-0" 2'-6" 1'-6" 2'-6" 1'-6"

VANITY FIXTURE VANITY FIXTURE

MIRROR
3'-0"

MIRROR
3'-5"

3'-5"
4'-0"

4'-0"

WD-4

No. Description Date


1'-2"

7'-6 5/16"

7'-6 1/8"

PAINT
SST-1
AS SCHEDULED SST-1
SST-1

SAGE
4"

4"

WD-4
WD-4
WD-4
2'-11 1/2"

3'-9"

3'-9"

DEVELOPMENT
2'-10"

2'-10"

3'-6 1/2" 1'-9" 2'-0"


GROUP
2'-11 3/4" 1" 2'-0" 2'-6" 1'-6" 2'-6" 1'-7 3/4" 2'-0" 4'-0"

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


4 2 BED "A" UNIT KITCHEN 5 2 BED "A" UNIT BATH 1 6 2 BED "A" UNIT BATH 2
A5.17 A5.17 A5.17

0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4'
BENSON
MULTIFAMILY

2 BED "A" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:47 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.17
AGENCY APPROVAL

12'-9 3/4"
14'-5 3/4"

BEDROOM BEDROOM

LIVING ROOM

8'-5 3/4" 3'-5 1/4" 3'-0" 5 1/4" 8'-5 3/4"

05

09 CLOSET

5'-4 3/4"
CLOSET
5'-4 3/4"

2'-8"
13
PANTRY
3'-0"

12 06

2'-4 3/4"
COAT
10 CLOSET
8
03 A5.18
5'-4 3/4"

4'-4 3/4"
A5.18 6
7
A5.18 04
BATHROOM 1 KITCHEN5 BATHROOM 2
4
02

3'-4 3/4"
11 LINEN MECH
01

7'-2" 2'-8 3/4" 13'-1 1/4" 5'-6" 3'-6" 5'-4 3/4" 1'-4"

38'-8 3/4"

50% OF UNITS
RECEIVE AN
ISLAND
1 2 BED "B" UNIT FLOOR PLAN 2 2 BED "B" UNIT FLOOR FINISH PLAN 3 2 BED "B" UNIT REFLECTED CEILING PLAN
A5.18 A5.18 A5.18

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

1'-11" 2'-6" 2'-7 1/2"


3'-1 1/4" 2'-0" 3'-0" 2'-0" 1'-11" 1'-1"

VANITY FIXTURE VANITY FIXTURE


PAINT
AS SCHEDULED PAINT
AS SCHEDULED

MIRROR MIRROR
3'-0"

WD-4
2'-4"

PAINT PAINT
AS SCHEDULED AS SCHEDULED
4" 10"

SST-3 SST-3
SST-1
SST-1

4"

4"
WD-4
WD-4
WD-4 WD-4
3'-0"

2'-10"

2'-10"
3'-0"

4'-0"
3'-0 1/4" 1" 2'-0" 3'-0" 2'-0" 10 1/2" 2'-1 1/2"
2'-0" 1'-0" 2'-6" 2'-7 1/2"
2'-6" 2'-6" 1'-6" 1'-6" 1'-6" 1'-6" 3'-7 1/2"
No. Description Date

2 BED "B" UNIT KITCHEN - A 2 BED "B" UNIT KITCHEN - B 2 BED "B" UNIT KITCHEN ISLAND 2 BED "B" UNIT BATH 1 2 BED "B" UNIT BATH 2
A5.18
4 5
A5.18
6
A5.18
7
A5.18
8
A5.18
SAGE
0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4'
DEVELOPMENT
GROUP

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


BENSON
MULTIFAMILY

2 BED "B" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:52 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.18
AGENCY APPROVAL

12'-0"
BEDROOM

7" 5'-11"

2'-4 3/4"
CLOSET

05
LIVING ROOM
6
A5.19
04

6'-6 3/4"
BATHROOM 1

"
3'-9

3'-0"
KITCHEN A5.18
7
2'-5

2"
197 1/
A154. '-
5/8"

2'-4 3/4"
DINING 4
COAT
CLOSET
03

3" 1'-0" 3'-0"


6'-7

10'-
"

09
5
19
A5.
MASTER
BATHROOM
CLOSET
2'-8

13 01
"

10

1/2"
BEDROOM 2'-3
MECH
" 1/2"
7'-9 1'-5

2"
'-10 1/
6

4"
4 3/
28'-

/2"
10 1
12'-

1 2 BED "C" UNIT FLOOR PLAN 2 2 BED "C" UNIT FLOOR FINISH PLAN 3 2 BED "C" UNIT REFLECTED CEILING PLAN
A5.19 A5.19 A5.19

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

2'-0" 2'-6" 2'-0" 3'-0" 2'-0" 3'-0 3/4"

VANITY FIXTURE VANITY FIXTURE No. Description Date


WD-4

SAGE
3'-0"

MIRROR MIRROR
3'-5"

DEVELOPMENT
SST-3
PAINT
GROUP
1'-2"

AS SCHEDULED SST-3 SST-3

C:\Users\bbeatty\Documents\Revit\17073_Sage Benson Housing_CENTRAL_Arch_R19_Single RR_bbeatty.rvt


WD-4
3'-9"

WD-4 WD-4
2'-10"
3'-0"

BENSON
2'-0" 2'-6" 2'-0" 3'-0" 2'-0" 1" 2'-11 3/4"

4 2 BED "C" UNIT KITCHEN 5


1'-6" 4'-4 11/16"

2 BED "C" UNIT MASTER BATHROOM 6 2 BED "C" UNIT BATHROOM 1 MULTIFAMILY
A5.19
A5.19 A5.19
0' 1' 2' 4'
0' 1' 2' 4' 0' 1' 2' 4'

2 BED "C" UNIT PLANS &


INTERIOR ELEVATIONS

HBA_CD_DOOR SCHEDULE_UNIT
DOOR DOOR FRAME
QTY NO. PR. WIDTH HEIGHT TYPE MAT'L FIN. TYPE MAT'L FIN. DEPTH HEAD DETAIL JAMB DETAIL SILL DETAIL LABEL HDWR. REMARKS
96 01 --- 3' - 0" 7' - 0" D1 WD --- --- HM --- 0' - 7 3/4" --- ---
96 02 --- 3' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 03 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
96 04 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
43 05 --- 7' - 0" WD --- --- WD --- 0' - 4 3/4" --- ---
88 06 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
8 07 * 3' - 8" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- --- 119 SOUTH 49TH AVENUE
9 09 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- OMAHA, NEBRASKA 68132
9 10 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- --- (402)551-0800
2 11 --- 2' - 0" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
2 12 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
20 13 * 3' - 2" 7' - 2" D1 WD --- --- --- --- 0' - 0" --- ---
ARY N PROJECT: 17073
3 14 --- 2' - 10" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
I N CTIO
3 18 --- 2' - 6" 7' - 0" D1 WD --- --- WD --- 0' - 4 3/4" --- ---
LIM NSTRU DATE: 8/26/19

8/27/2019 2:55:57 PM
62 D22 5' - 11" 7' - 11 1/2" E
26 D23 8' - 10 1/2" 7' - 11 1/2" PR R CO
4 D24 11' - 9" 7' - 11 1/2"
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.19
AGENCY APPROVAL

_ 1 _ 1 _ 1 _ 1 _ 1
A5.52 A5.52 A5.52 A5.52 A5.52

RE: FIRST FLOOR

5'-6"

5'-6"

5'-6"

5'-6"
EQ EQ EQ EQ EQ EQ EQ EQ
U1
18'-10 7/8"

18'-10 7/8"

18'-10 7/8"

18'-10 7/8"

18'-10 7/8"
U1
S1 V5 V5 V5 V5

U1 U1 U1 U1 U1

RE: 1ST FLOOR RE: 1ST FLOOR


5'-6"

5'-6"

5'-6"

5'-6"

5'-6"
_ 2 _ 2 _ 2 _ 2 _ 2
A5.52 A5.52 A5.52 A5.52 A5.52

S1 V2.1 V2.1 V2.1 V2.1

1 NORTH STAIR ENLARGED LOWER LEVEL 2 NORTH STAIR ENLARGED FIRST FLOOR PLAN 3 NORTH STAIR ENLARGED SECOND FLOOR PLAN 4 NORTH STAIR ENLARGED THIRD FLOOR PLAN 5 NORTH STAIR ENLARGED FOURTH FLOOR PLAN
A5.51 A5.51 A5.51 A5.51 A5.51

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

S1 V2.1 V2.1 V2.1 V2.1


RE: FIRST FLOOR

_ 2 _ 2 _ 2 _ 2 _ 2
5'-6"

5'-6"

5'-6"

5'-6"
A5.53 A5.53 A5.53 A5.53 A5.53

U1

UP

S1 V5 V5 V5 V5
18'-10 7/8"

18'-10 7/8"

18'-10 7/8"

18'-10 7/8"

18'-10 7/8"
U1 U1 U1 U1 U1

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
U1

SAGE
RE: FIRST FLOOR

RE: 1ST FLOOR RE: 1ST FLOOR EQ EQ EQ EQ EQ EQ EQ EQ


DEVELOPMENT
5'-6"

5'-6"

5'-6"

5'-6"
GROUP

_ 1 _ 1 _ 1 _ 1
_ 1
A5.53
A5.53 A5.53 A5.53 A5.53
BENSON
MULTIFAMILY
6 SOUTH STAIR ENLARGED LOWER LEVEL 7 SOUTH STAIR ENLARGED FIRST FLOOR PLAN 8 SOUTH STAIR ENLARGED SECOND FLOOR PLAN 9 SOUTH STAIR ENLARGED THIRD FLOOR PLAN 10 SOUTH STAIR ENLARGED FOURTH FLOOR PLAN
A5.51 A5.51 A5.51 A5.51 A5.51

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

ENLARGED STAIR PLANS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:54:24 AM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/26/19
SHEET: A5.51
AGENCY APPROVAL
_ 2 1
_
A5.52 A5.52

T.O. ROOF DECK


144' - 0"

3'-6"
FOURTH FLOOR PLAN
133' - 0"

(19) EQ RISERS
11'-0"
WOOD STAIR

THIRD FLOOR PLAN


122' - 0"

(19) EQ RISERS
11'-0"
WOOD STAIR

SECOND FLOOR PLAN


111' - 0"

(19) EQ RISERS
11'-0"
WOOD STAIR

GWB REVEAL AT

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


FLOOR TRANSITION
No. Description Date
3'-6"

FIRST FLOOR PLAN


100' - 0"
SAGE
DEVELOPMENT

(9) EQ RISERS
GROUP

5'-0"
COMPOSITE STAIR (BEYOND)

BENSON
MULTIFAMILY

(19) EQ RISERS
COMPOSITE DECK
AT LANDING

10'-8"
ENLARGED STAIR
COMPOSITE STAIR
SECTIONS
FLOOR SLOPE
4"

LOWER LEVEL PLAN


84' - 0"

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:54:27 AM
E
1 NORTH STAIR SECTION 2 NORTH STAIR CROSS-SECTION PR R CO
A5.52 A5.52 T FO
NO C COPYRIGHT 2018

0' 1' 2' 4' 0' 1' 2' 4'

8/26/19
SHEET: A5.52
AGENCY APPROVAL
2 _ 1
_
A5.53 A5.53

T.O. ROOF DECK


144' - 0"

FOURTH FLOOR PLAN


133' - 0"

(19) EQ RISERS
11'-0"
WOOD STAIR

THIRD FLOOR PLAN


122' - 0"

(19) EQ RISERS
11'-0"
WOOD STAIR

SECOND FLOOR PLAN


111' - 0"

(19) EQ RSERS
11'-0"
WOOD STAIR

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

FIRST FLOOR PLAN


100' - 0"
SAGE
DEVELOPMENT
GROUP

(19) EQ RISERS
BENSON

11'-0"
COMPOSITE STAIR
MULTIFAMILY

ENLARGED STAIR

(3) EQ RISERS
CONC. STEPS BEYOND

SECTIONS
1'-6 3/4"

LOWER LEVEL PLAN


84' - 0"

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:54:29 AM
E
1 SOUTH STAIR SECTION 2 SOUTH STAIR CROSS SECTION PR R CO
A5.53 A5.53 T FO
NO C COPYRIGHT 2018

0' 1' 2' 4' 0' 1' 2' 4'

8/26/19
SHEET: A5.53
AGENCY APPROVAL
_ 2 _ 1
A5.54 A5.54
TPO ROOF MEMBRANE
12
1/4"
R-38 BATT INSULATION

EXTEND TPO MEMBRANE


UP WALLS AT ELEVATOR

T.O. ROOF DECK


144' - 0"

FOURTH FLOOR PLAN


133' - 0"

S1

8'-8" 10'-0 1/4"

CLEAR WIDTH

006

S1

_ 1

CLEAR DEPTH
A5.54
THIRD FLOOR PLAN

6'-11"
122' - 0"

S1
S1

6"
11'-
2 S1

6'-7 13/16"
_
A5.54

S1

004
002

8'-7
11/1
6"

"
8'-0
SECOND FLOOR PLAN
111' - 0" 11'-
4"

3 ELEVATOR ENLARGED LOWER LEVEL


A5.54

0' 1' 2' 4' 8'

8'-8" 8'-8"

CLEAR WIDTH

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
_ 1 _ 1

3'-4"

3'-4"
FIRST FLOOR PLAN
A5.54 A5.54
SAGE

6'-11"
CLEAR DEPTH
100' - 0"

DEVELOPMENT

9'-5 3/4"
GROUP

2'-6 3/4"
_ 2 _ 2
A5.54 A5.54

BENSON
MULTIFAMILY
4 ELEVATOR ENLARGED FIRST FLOOR PLAN 5 ELEVATOR ENLARGED SECOND FLOOR PLAN
A5.54 A5.54

0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

8'-8" 8'-8" ENLARGED ELEVATOR


PLANS & SECTIONS

_ 1 _ 1

3'-4"

3'-4"
A5.54 A5.54
6'-11"

6'-11"
5'-0"

5'-0"

LOWER LEVEL PLAN


84' - 0"
2'-6 3/4"

2'-6 3/4"
119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
_ 2 _ 2
(402)551-0800
A5.54 A5.54

ARY N PROJECT: 17073


I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:54:33 AM
E
1 ELEVATOR SECTION EAST-WEST 2 ELEVATOR SECTION NORTH-SOUTH 6 ELEVATOR ENLARGED THIRD FLOOR PLAN 7 ELEVATOR ENLARGED FOURTH FLOOR PLAN PR R CO
A5.54 A5.54 A5.54 A5.54 T FO
NO C COPYRIGHT 2018

0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

8/26/19
SHEET: A5.54
*HBA_CD_ROOM FINISH SCHEDULE
Number Name Floor Finish Base Finish Wall Finish Ceiling Finish Comments
LOWER LEVEL PLAN
001 GARAGE
002 VESTIBULE
003 ELEVATOR
004 TRASH
005 MECHANICAL
006 STORM SHELTER
040 STAIR
041 STAIR
FIRST FLOOR PLAN
100 VESTIBULE CPT-3 RB-1 P-1 P-1
101 LOBBY CPT-3 / CPT-4 / PC-1 RB-1 P-1 P-1 / WD-4
102 PARTY ROOM P1 / PT-4
103 GAME ROOM CPT-1 / CPT-4 RB-1 P2 / WD-2 P1
104 HALL
105 JANITOR PC-1 RB-1 P-1 P-1
106 MEN'S RR PT-1 PT-2 PT-2 / P-3 P-1
107 WOMEN'S RR PT-1 PT-2 PT-2 / P-3 P-1
108 HALL PC-1 RB-1 P-1 WD-4
109 BUSINESS CENTER PC-1 RB-1 P-1 P-1
110 MAIL PC-1 RB-1 P-1 / WD-2 / PT-3 P-1
111 OFFICE CPT-1 RB-1 P-1 P-1
112 STORAGE CPT-1 RB-1 P-1 P-1
113 FITNESS CENTER CPT-5 / CPT-6 RB-1 P-3 / WD-2 P-3 / ACT-1
120 ELEVATOR LOBBY PC-1 RB-1 P-1 P-1
121 TRASH PC-1 RB-1 P-1 P-1
122 MECH PC-1 RB-1 P-1
123 STORAGE
130 CORRIDOR
131 CORRIDOR CPT-1 / CPT-2 RB-1 P-1 / P-3 P-3 / ACT-2
133 CORRIDOR CPT-1 / CPT-2 RB-1 P-1 / P-3 P-3 / ACT-2
140 STAIR
141 STAIR
SECOND FLOOR PLAN
220 ELEVATOR LOBBY
221 TRASH
222 TELECOM
223 STORAGE
224 ELECTRICAL
230 CORRIDOR
231 CORRIDOR
232 CORRIDOR
233 CORRIDOR
240 STAIR
241 STAIR
THIRD FLOOR PLAN
320 ELEVATOR LOBBY
321 TRASH
322 TELECOM
323 STORAGE
324 ELECTRICAL
330 CORRIDOR
331 CORRIDOR
332 CORRIDOR
333 CORRIDOR
340 STAIR
341 STAIR
FOURTH FLOOR PLAN
420 ELEVATOR LOBBY
421 TRASH
422 TELECOM
423 STORAGE
424 ELEC
425 ROOF ACCESS
430 CORRIDOR
431 CORRIDOR
432 CORRIDOR
433 CORRIDOR
440 STAIR
441 STAIR

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

FINISH SCHEDULE

HOLLAND BASHAM ARCHITECTS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT:17073
I N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:54:35 AM
E
PR R CO
T FO
NO C COPYRIGHT

A5.55
2013

SHEET:
AGENCY APPROVAL

PAINT AS SCHEDULED

BACKLIT GRAPHIC WALLCOVERING


BY OTHERS PAINT AS SCHEDULED WD-2

PL-1

1 3/16"
OPEN BELOW COUNTER

1 1/2"
SST-1
P-2 PL-1
SST-1
PL-1
2'-9 11/16"

2'-9 11/16"

3'-0 1/4"
PL-1 SST-1

2'-8 1/2"

2'-4 1/2"
OPEN BELOW COUNTER
WD-1
RB-1 PL-2 GEN INTERIOR ELEV NOTES
5'-2 7/8" 2'-2 3/16" 1. PROVIDE CONTINUOUS BLOCKING OR STRAPPING WITHIN
1 3/16" 1'-6" 2'-10" 1'-6" 1 3/16" 1" 2'-6" 3'-2 1/2" 1'-6" 1" 4" 4" 1'-10 3/8" 6"
NEW WALLS AS REQUIRED FOR ALL WALL MOUNTED CASEWORK,
6'-0 3/8" 1'-0" 18'-9 3/4" 1'-0" FIXTURES, ACCESSORIES AND EQUIPMENT. ANCHOR BLOCKING
BETWEEN THE STUDS, AT THE FACE OF THE STUDS, FOR THE
ENTIRE WIDTH OF THE ITEM TO BE MOUNTED TO THE WALL.
1 LOBBY, 101 2 LOBBY, 101 3 LOBBY, 101 4 BUSINESS CENTER, 109 5 MAIL, 110 ANCHOR 22 GA SHEET METAL STRAPPING TO THE FACE OF THE
STUDS FOR THE ENTIRE WIDTH OF THE ITEM TO BE MOUNTED TO
A8.01 A8.01 A8.01 A8.01 A8.01 THE WALL. VERIFY VERTICAL LOCATION OF BLOCKING WITH THE
MOUNTING HEIGHT REQUIRED AND THE REQUIREMENTS OF THE
0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' ITEM TO BE MOUNTED TO THE WALL.

2. PROVIDE MINIMUM 1” FILLER PANEL BETWEEN ALL


CASEWORK DOORS/DRAWERS AND ADJACENT WALLS, UNLESS
NOTED OTHERWISE.

3. PROVIDE FINISHED END PANELS AT ALL EXPOSED CASEWORK


SIDES.

4. ALL PLASTIC LAMINATE HORIZONTAL FINISHES SHALL BE


<insert> AND VERTICAL SURFACES SHALL BE <insert>, UNLESS
NOTED OTHERWISE.

5. ARROWS ON CABINETS INDICATE THE LAMINATE PATTERN


DIRECTION.

*HBA_CD_KEYED INTERI...

8"
TAG USED FOR THIS SCHEDULE

2'-8"
TILE AS
SCHEDULED PAINT AS SCHEDULED 1 KEYNOTE 1
2 KEYNOTE 2
3 KEYNOTE 3
PT-3 WD-2 4 KEYNOTE 4
TILE AS SCHEDULED 5 KEYNOTE 5

2'-0"
6 KEYNOTE 6
7 KEYNOTE 7

8'-0"
8 KEYNOTE 8
9 KEYNOTE 9
SST-2

2'-0"
SST-2
10 KEYNOTE 10
FIREBOX
SST-2
11 KEYNOTE 11
12 KEYNOTE 12
2'-10"

2'-10"

3'-0"
13 KEYNOTE 13

2'-0"
PL-2 PL-2 14 KEYNOTE 14
15 KEYNOTE 15
16 KEYNOTE 16
2'-2" 1'-6" 3'-3" 3'-11 3/4" 3'-0" 1'-6" 1" 8'-0" 1" 17 KEYNOTE 17
1" 1'-6" 1'-6" 2'-10 1/2" 2'-10 1/2" 2'-2" 1"
1'-5" 10 3/8" 7'-0" 10 3/8" 1'-5" 14'-4 9/16" 6" 18 KEYNOTE 18
19 KEYNOTE 19
20 KEYNOTE 20
6 PARTY ROOM, 102 7 PARTY ROOM, 102 8 PARTY ROOM ISLAND, 102
A8.01 A8.01 A8.01 9 GAME ROOM FIREPLACE, 103
A8.01
0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4'
0' 1' 2' 4'

PAINT AS SCHEDULED

PAINT AS PAINT AS
2'-0"

SCHEDULED SCHEDULED
PAINT AS SCHEDULED

\\10.12.0.25\projects\2017\17073 Sage Benson Housing 6152 Military\Consultants\architectural\17073_Sage Benson Housing_CENTRAL_Arch_R19.rvt


No. Description Date
5'-0"

GRAPHIC VWC
BY OTHERS
PT-2 PT-2
WD-2

PL-1 PL-1
SAGE
DEVELOPMENT
3'-0"

3'-0"
1'-8"

TILE AS TILE AS

6" 9'-9 13/16" 6 3/4" 4'-0" 1'-1 13/16" 10'-4" 1'-1"


SCHEDULED

5'-0"
SCHEDULED

8'-11 13/16"
GROUP
10 GAME ROOM BENCH, 103 11 MEN'S RR, 106 12 WOMEN'S RR, 107
A8.01 A8.01 A8.01

0' 1' 2' 4' 0' 1' 2' 4' 0' 1' 2' 4' BENSON
MULTIFAMILY

WD-3 WD-3 INTERIOR ELEVATIONS


3"

PAINT AS
SCHEDULED

MIRROR
8'-1"

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

RY N PROJECT: 17073
4'-0" PL-4 PL-3

3" 17'-6" 3" 6'-6" 3'-10 3/4"


I A
N CTIO
LIM NSTRU DATE: 8/26/19

8/27/2019 10:54:44 AM
E
13 FITNESS CENTER, 113 PR R CO
T FO
NO
A8.01 C COPYRIGHT 2018

0' 1' 2' 4'


8/26/19
SHEET: A8.01
STRUCTURAL GENERAL NOTES
FOUNDATIONS
F1. Subsoil investigation for this project was made by Terracon of Omaha, Nebraska dated 26 C19. Deformed bar anchors shall conform to ASTM A 496. S9. Connections not specifically detailed shall be designed by the fabricator to support a minimum L27. Framing plans show primary framing members, sizes and supports. Framer shall provide and G7. WIND LOAD
February 2015. A copy of their investigation is available from the Architect. The accuracy of of one-half the total uniform load capacity calculated from the tables for Allowable Uniform install all framing required (whether specifically shown or not) for headers, nailers, corners, Design Criteria Section 6 of ASCE 7-05, per
C20. Portland cement shall conform to ASTM C150, type I.
the investigation is not guaranteed and it is not to be construed as part of the plans Loads for Beams in the AISC "Manual of Steel Construction (Ninth Edition) for the given shape, partition supports, roof crickets, ceiling joists, stairs, bridging, etc. to make a complete and Section 1609.1 of IBC.
governing construction of the project. C21. Air-entraining admixtures shall conform to ASTM C260. Other admixtures, if used, span and steel specification of the beam in question, unless otherwise noted. Shop drawings sound installation in accordance with all applicable codes. Base Wind Speed (3-second gust) = 90 MPH
F2. The Geotechnical Engineer shall be retained for testing and observation during all earthwork and shall conform to ASTM C494. shall be prepared by a registered professional engineer in the State of Nebraska, and shall be L28. Contractor shall take special care at floor tile areas to install framing in a manner that will Risk Category = 'II'
foundation construction phases to verify that the recommendations of the subsoil investigation C22. Any horizontal construction joints in concrete pours not shown on the drawings submitted for review by the Project Engineer. minimize any floor movement that would damage the tile. Such measures may include, but Wind Exposure = 'B'
are being implemented. The Geotechnical Engineer shall inspect all footing excavations and shall be submitted to the Structural Engineer for review. not be limited to lapping and nailing joists together at bearing lines, providing full sheets of
S10. All steel shall be prime painted with fabricators standard shop primer. Galvanize exterior lintel G8. EARTHQUAKE LOAD
slab subgrade immediately prior to placement of any concrete, and shall test all fill for proper floor sheathing approximately centered over bearing lines or transitions in framing direction,
members in contact with masonry Site Class = D
compaction. and providing full depth blocking between joists near the ends of plywood sheets to prevent
CONCRETE MASONRY S11. The thickness of curved angles and tubes indicated on these drawings is a minimum and shall Spectral Response Coefficient SD S = 0.133
F3. Remove all topsoil, rubble, and tree roots in excess of 2-inch diameter. Soils below footing rotation of the sheathing. Concrete topping under floor tile shall be properly cured, and
M1. Concrete masonry units shall be normal aggregate, hollow units and shall comply with "Quality be increased as required by the fabrication method utilized to prevent buckling. Spectral Response Coefficient SD 1 = 0.065
level disturbed by grubbing shall be recompacted to depths and extents as directed by the reinforced with wire mesh if necessary to control cracking of the topping.
Concrete Block Specifications for the State of Nebraska." Seismic Design Category = A
Geotechnical Engineer. Keep excavations free of standing water during construction.
M2. Masonry units shall conform to ASTM C 90. Minimum compressive strength of individual units S12. Anchor rods, nuts, and washer plates in contact with preservative treated lumber shall be G90 Section 6 of ASCE 7-05, per Section 1609.1 of IBC.
F4. Structural fill materials shall consist of suitable on-site or borrow materials approved by the shall be 1900 PSI on the net area of the block. Design compressive strength of masonry, f'm hot-dip galvanized.
Geotechnical Engineer and placed in 8-inch maximum lifts and compacted as directed by the = 1,500 PSI. PREFABRICATED WOOD TRUSSES COORDINATION AND VERIFICATION
Geotechnical Engineer. M3. Mortar shall conform to ASTM C 270 type S. STRUCTURAL LUMBER AND CARPENTRY WT1. Prefabricated wood trusses and connections thereof shall be designed, fabricated and installed
V1. Structural drawings shall be coordinated with Architectural, Mechanical, and Electrical drawings
F5. Fill below slabs-on-grade shall consist of clean granular material compacted as directed by M4. Furnish equipment and materials and perform all labor necessary to build concrete L1. All stress grades and stress criteria shall be based on the National Design Specifications for in accordance with the National Design Specification and Truss Plate Institute publications TPI1,
for additional openings, sleeves, under-floor ducts, floor depressions, etc. not shown on the
the Geotechnical Engineer. masonry, complete, as shown on the drawings and/or in accordance with "Quality Wood Construction, 2001. TPI DSB-89, and TPI HIB-91.
structural drawings. Coordinate location, size, and reinforcement of all openings with respective
Concrete Block Specifications for the State of Nebraska."
L2. Lumber for 2x8's and larger shall be No. 2 and better Hem-Fir, Spruce-Pine-Fir, or Doug Fir- WT2. Design trusses for the following loads: trades before fabrication.
F6. Backfill behind basement walls shall consist of free-draining granular material within 2'-0" of
M5. Grout for bond beams and for filling vertically reinforced masonry cells shall comply with Larch. Unless noted otherwise.
the wall down to the perimeter drain, and suitable on-site soils for the remaining materials. V2. The Contractor shall verify all dimensions before starting work or fabricating any structural
cast-in-place concrete specifications and shall be well consolidated by rodding or vibrating. Roof Trusses Top Chord DL = 15 psf (5 psf additional at Valley Sets)
Place in 8-inch maximum lifts and compact as directed by the Geotechnical Engineer. L3. Lumber for 2x4's, 2x6's, 4x4's and 6x6's shall be Stud grade (or better) Hem-Fir or Spruce- materials. The Architect shall be notified of any discrepancies found.
Grout by low-lift method with a maximum grout height of 4'-8". Top Chord LL = 25 psf
Pine-Fir. Unless noted otherwise.
M6. Reinforce all masonry horizontally with galvanized 9 gage Durowal at 16 inches on center. Bottom Chord DL = 10 psf
F7. Bear footings on natural soils or suitable compacted fill materials. No footings shall be placed L4. Where rectangular wood beams are specifically noted to be Structural Composite Lumber (SCL),
Reinforce walls vertically as shown on the drawings. Lap splice vertical reinforcing as shown on
they shall be laminated veneer lumber or parallel strand lumber, meeting the following criteria: Floor Trusses Top Chord DL = 25 psf SPECIAL INSPECTIONS
on frozen soils. All footings have been designed for an allowable net bearing pressure of the drawings.
1,500 psf at columns and 2,000 psf at continuous walls. Top Chord LL = 40 psf SP1. The Contractor shall insure conformance with the 2006 IBC as amended by the City of
M7. Masonry may not be laid during freezing weather unless suitably protected. Conform to
Bottom Chord DL = 10 psf Omaha Building Code.
F8. Basement walls retaining unbalanced earth fill have been designed using an equivalent fluid "Recommended Practice for Cold Weather Masonry Construction" by the International Masonry . Minimum allowable stresses .
SP2. Special inspections as defined and required by the above code shall be performed
pressure of 40 pounds per cubic foot. Brace walls laterally until all permanent support is in Industry All-Weather Council. Extreme fiber in bending Fb = 2,800 psi WT3. Design floor trusses for the following maximum overall truss deflections: by an independent inspection agency approved by the Building Official to perform
place. Soils at foundation perimeter shall be treated for termites in accordance with accepted Horizontal Shear Fv = 285 psi
M8. The contractor shall provide all temporary shoring necessary to laterally support all masonry Total Load L/360 such work. The designated Special Inspector shall also be approved by the Architect
local practice. Modulus of elasticity E = 2,000,000 psi
walls. and Engineer of Record and shall be paid for by the testing allowance.
F9. The Contractor shall provide all temporary shoring necessary to laterally support all walls below Live Load L/480 SP3. The Special Inspector shall observe the work here in after assigned for conformance
M9. All openings required in masonry walls greater than 8 inches wide shall be placed at the L5. All framing lumber shall be stamped with grade and trademark for each piece.
grade. WT4. Design roof trusses for the following maximum overall truss deflections: with approved design drawings and specifications and shall bring all discrepancies
time of wall construction. The Contractor shall contact the Structural Engineer if openings
F10. The Contractor shall locate and protect any existing utilities from damage or interruption during L6. All lumber shall have a maximum moisture content of 19% and shall be smooth on 4 sides. Total Load L/240 to the immediate attention of the Contractor for correction. Uncorrected
greater than 8 inches wide are required after the walls have been constructed. Do not
construction. discrepancies shall be reported to the Building Official and Architect/Engineer of
place any duct openings directly below beam bearing locations unless specifically shown on Live Load L/360
L7. Pressure treat sill plates, blocking, furring, and similar items in direct contact with masonry or Record.
the drawings.
WT5. Design roof trusses for the following maximum localized deflection between panel points: SP4. The Special Inspector shall furnish inspection reports to the Building Official and the
concrete or use redwood.
CONCRETE AND REINFORCEMENT M10. Shore steel lintels if required during construction to prevent rotation due to eccentric loads.
Top Chord Total Load L/180
Architect/Engineer of Record at monthly intervals and shall submit a final signed report
L8. Floor sheathing shall be APA Rated Sturd-I-Floor, plywood or OSB, Exposure 1, 23/32 at the project completion stating whether the work inspected was, to the best of his
C1. Concrete work shall conform to all requirements of ACI 301, "Specifications for Structural
Performance Category, 24oc Span Rating, with tongue and groove edges, glued to supports in Top Chord Live Load L/240 knowledge, in accordance with approved design drawings and specifications.
Concrete for Buildings", except as modified by the Supplemental Requirements below. M11. Lintel bearing length specified on the Drawings is the length on the structural CMU wall,
addition to nailing specified under “Installation”. Bottom Chord Total Load L/240 SP5. Special inspection requirements for specific classifications of work are as follows
exclusive of any 4-inch brick or CMU veneer returns which may be shown on the Architectural
C2. Submit a concrete mix design for each class of concrete for approval by the Project Engineer. L9. Roof sheathing shall be APA Rated Sheathing, plywood or OSB, Exposure 1, 19/32 Performance Bottom Chord Live Load L/360 (by IBC Section Reference):
Plans and jamb details.
The mix design shall include the proportions and test results or certifications for all 1704.2 Inspection of Fabricators. Items fabricated in fabricator's shop shall be
Category, with 40/20 Span Rating. Use ply clips at all unsupported edges. WT6. Valley sets (or "over-framing") shall consist of prefabricated wood trusses or on site stick
components of the mix in accordance with the latest ACI 301. Submit documented results of M12. Additional vertical control joints or vertical joints between dissimilar block types not shown or inspected per all applicable portions of Section 1704.2, except when fabricator
L10. Wall sheathing at exterior walls and indicated interior shear walls shall be APA Rated Sheathing, framing. If stick framing is used, provide posts at 4 feet maximum centers in order to
“field test data” or “trial mixtures” in accordance with ACI 301 for each class of concrete to be prescribed on the drawings must be approved by the structural engineer, particularly when such is approved in accordance with Section 1704.2.2.
plywood or OSB, Exposure 1. Use 7/16 performance category with 24/16 Span Rating or transfer loads evenly to main framing below.
used. The mix designs shall meet the following guidelines except as approved by the Project joints occur near beam or joist bearing conditions. 1704.3 Steel Construction. Steel elements shall be inspected per all applicable portions
15/32 Performance Category with 32/16 Span Rating. WT7. The truss manufacturer, subject to approval by the Architect, may alter truss layouts and of Section 1704.3 and Table 1704.3.
Engineer.
Installation geometry shown. Submit any proposed changes on the shop drawings.
PRECAST CONCRETE 1704.4 Concrete Construction. Concrete foundations, structural members, reinforcing and
C3. Use f'c = 4,000 PSI (L6.5) limestone concrete for all exterior stoops, walls and parking garage WT8. Truss manufacturer shall submit as shop drawings a complete erection drawing and engineering all applicable portions of Table 1704.4. Exception numbers (1) and (2) listed
P1. Use f'c = 5000 PSI for all precast concrete. Minimum strength at strand release L11. Standards: except as otherwise noted, comply with "Manual of House Framing" by
slabs-on-grade. Use f'c = 3,000 PSI (SG6.0) sand-gravel concrete or f'c = 3,000 PSI (L5.5) calculations for all trusses. A registered engineer in the State of Nebraska shall stamp the in Section 1704.4 will not be allowed.
f'c = 3500 PSI. National Forest Products Association, including nailing, fire stopping, anchorage, framing
limestone concrete for all other structural concrete. Use f'c = 3,000 PSI (SG7.0) sand-gravel calculations. The calculations shall be presented in a logical and orderly manner and shall be 1704.5 Masonry Construction. Masonry elements shall be inspected per all applicable
and bracing.
concrete for all masonry grouting and bond beam lintels. Design concrete mixes to the P2. Prestressing strands shall conform to ASTM A 416, grade 270. keyed to the erection plans. The truss calculations shall include inner panel deflections or a portions of Section 1704.5 and Table 1704.5.1 (level 1 special inspection).
L12. Unless specifically noted otherwise, nail plywood or OSB roof sheathing at 6 inches on-center
following specifications: letter stating the inner panel deflections meet the requirements of note WT5. The erection Exception numbers (1) and (2) listed in Section 1704.5 will not be allowed.
P3. Precast connections shown are suggested only and may be schematic. They do not cover at edges of panels and 12 inches on-center at intermediate supports with 8d nails (0.131"
plans shall include a complete layout plan of all trusses, with the trusses labeled using the 1704.7 Soils. Soil excavation, fill placement and existing site soil conditions shall be
Cement per Water/ Air all conditions. The Precaster shall design all connections (including all bearing details and diameter x 2" min. length) with a minimum of 1 3/8-inch penetration. Leave 1/8 inch
same designations as the calculations. The truss layout plans shall dimension truss spacing, inspected per Section 1704.7.1 through 1704.7.3. and as specified elsewhere in
cu. yd. Cement Content Slump tie-back details), for gravity loads and lateral loads, volume change forces, and rotational spacing at all ends and edges. Apply with the plywood perpendicular to the joists. Nails of
and shall show the location of any concentrated loads. Any required hangers for concentrated these Contract Documents.
Mix (min. sacks) (max. ratio) (%) (inches) forces due to load eccentricities. The Precaster shall also review such fabricated steel different type, diameter, or length shall be submitted to the structural engineer for approval.
loads shall be called for on the erection plans. Truss manufacturer shall design/detail all
L6.5 6 ½ .42 5-7 2-4 details as provided for precast support and inform the Architect of any revisions necessary
truss to truss connections. Required roof and floor truss bridging and erection bracing shall
L5.5 5 ½ .47 5-7 2-4 to make the connections work. Design, detailing, and erection of precast members shall L13. Unless specifically noted otherwise, nail plywood or OSB floor sheathing at 6 inches on-center be designated on the erection drawings.
SG6.0 6 .47 5-7 2-4 be in accordance with ACI 318-08, PCI MNL-116-99, and PCI MNL-120-10. Loads and at edges of panels and 12 inches on-center at intermediate supports with 8d nails (0.131”
SG7.0 7 -- -- 8-10 load combinations shall be as specified in these notes and in the referenced building code. WT9. Roof trusses shall be anchored to the top plate with one Simpson type 'H1' hurricane tie at
diameter x 2 1/8” min. length) with a minimum of 1 3/8-inch penetration. Leave 1/8 inch
Connection design for all precast members shall utilize an additional load factor of 1.3 as each end of each truss unless noted otherwise on the Drawings.
spacing at all ends and edges. Apply with the plywood perpendicular to the joists. Nails of
C4. The addition of water to the mix on site will not be allowed, unless specifically approved. recommended in PCI MNL-120-10, Section 6.3. Submit letter of certification stamped and different type, diameter, or length shall be submitted to the structural engineer for approval. WT10. Floor trusses shall have continuous 2x6 strong-back bracing in addition to the standard lateral
Concrete may not be placed during freezing weather unless suitably protected, per ACI 306.1. signed by a registered professional engineer in the State of Nebraska stating conformance
bracing required by the Truss Plate Institute. The strong-backs shall have long dimension
Conform to ACI 305.1 for hot weather concreting. with specifications and requirements stated herein.
L14. Unless specifically noted otherwise, nail plywood or OSB wall sheathing at 6 inches on- vertical, and shall be nailed to verticals in the truss with 2-16d nails (0.162"x3½").
C5. Cure concrete flatwork by moist cure or membrane forming curing compound for 72 hours. center at edges of panels and 12 inches on-center at intermediate supports with 8d nails
P4. All precast planks shall have joints grouted. (0.131" diameter x 1 7/8" min. length) with a minimum of 1 3/8-inch penetration. All
C6. All reinforcing steel shall be ASTM A 615 grade 60. The number of rows of strong-backs shall be as follows:
P5. Plumbing penetrations shall be coordinated by the General Contractor with the Precast Engineer panel edges shall be blocked with 2 inch nominal or wider material. Leave 1/8 inch
C7. Provide lap splices as indicated below unless noted otherwise in details and schedules. Top spacing at all ends and edges. Nails of different type, diameter, or length shall be 0 - 12' span none required
for acceptance.
bars are horizontal bars with more than 12-inches of fresh concrete cast below the bars in submitted to the structural engineer for approval. 12 - 20' span 1 row at center of span
question. P6. A precoordination meeting is required between the Contractor, Plumbing Contractor and Precaster
L15. All metal hangers and connectors shall be manufactured by Simpson or approved equivalent 20 - 28' span 2 rows at one-third span points No. Description Date
before installation can begin.
Splice Length and be size and type recommended for the application by the manufacturer.
28 - 36' span 3 rows at one-quarter span points
Bar Size Top Bars All Other Bars P7. Holes in precast planks shall be field cut in cores, and shall not interrupt prestressing L16. All metal hangers, connectors, and fasteners in contact with preservative treated wood shall
#3 1'-4" 1'-1" strands. Conform to manufacturer's recommendations for field cut holes. Precaster be stainless steel or G185 hot-dip galvanized. Fasteners shall be compatible with hangers WT11. Each truss shall be legibly branded, marked or otherwise have affixed within two feet of the SAGE
#4 1'-10" 1'-5" to coordinate all plumbing penetrations. and connectors. Do not mix stainless steel with galvanized steel. center span on the face of the bottom chord with:
#5 2'-3" 1'-9" P8. Concrete topping shall be reinforced with 6x6-W2.9xW2.9 WWF. L17. 5/8-inch drywall sheathing used on designated shear walls shall be attached with 6d cooler or a. Identity of the truss manufacturer. DEVELOPMENT
#6 2'-8" 2'-1" b. Design loads
#7 3'-11" 3'-0" P9. Pour concrete on planks to indicated elevation. Due to camber in the planks, the
topping thickness at mid-span will be less than the nominal thickness specified at the
wallboard nails (minimum 3/8-inch head, 1 3/4-inch long), or #6-1 1/4-inch Type S or W
screws. c. Truss spacing GROUP
#8 4'-6" 3'-6"
ends. Engineer shall be notified prior to placement of topping if anticipated to be less L18. Bed all sills and plates resting on masonry or concrete on a sill sealer strip.
#9 5'-1" 3'-11"
than two inches.
L19. Solid joists or I-joists having spans in excess of 8 feet shall be rigidly braced with continuous GENERAL DESIGN CRITERIA
C8. Concrete cover of reinforcement shall conform to ACI 318-02 unless detailed otherwise.
STRUCTURAL STEEL
rows of bridging at intervals not exceeding 8 feet.
G1. Building Code - 2006 International Building Code (IBC) as adopted and amended by the City of
BENSON
C9. Submit reinforcing steel shop drawings indicating placement, spacing and lap lengths for review L20. Use double joists under all stud partitions running parallel to the floor joists.
by the Project Engineer. S1. All W-shape and WT-shape sections shall conform to ASTM A 992 (Fy = 50 ksi).
L21. Use triple 2x studs at all exterior wall corners unless shown otherwise.
Omaha Building Code.
G2. Dead Load (in addition to weight of structural members and non-load bearing walls/partitions):
MULTIFAMILY
C10. Welded wire fabric shall be flat sheets and shall conform to ASTM A 1064. S2. All S-shapes, M-shapes, channels, angles, bars and plates shall conform to ASTM A 36
L22. All headers and built-up beams shall be glued with PL400 and nailed at 8" o.c. staggered
C11. Macro-synthetic fibers in concrete slabs-on-grade shall be Euclid Tuf-Strand SF or equivalent (Fy = 36 ksi). Mech/Elect/Ceiling/Fireproofing/misc. = 15 PSF
both side's w/16d nails (0.162” x 3 ½”).
and shall be mixed uniformly into the concrete with a minimum dose of 3 lb per cubic yard. S3. Tube sections shall conform to ASTM A 500 Grade B (Fy = 46 ksi). Raised Access Floor (where applicable) = 10 PSF
L23. Under built-up wood beams provide built-up columns with at least the same number of 2x's
Substitutes shall have a minimum performance rating of Re3 = 10%. Extra Concrete for floor leveling = 5 PSF
S4. Pipe sections shall conform to ASTM A 53 Grade B (Fy = 35 ksi) or ASTM A500 Grade B as contained in the built up beam. Built-up wood columns shall be glued with PL400 and
Roofing System = 15 PSF
C12. Slabs-on-grade shall be 4-inches thick with welded wire fabric or macro-synthetic fibers and
(Fy = 42 ksi). nailed at 8 inches on-center. STRUCTURAL GENERAL
shall be placed over a vapor barrier and 4-inches minimum of granular fill. L24. Bolt all nailers to steel beams with 1/2" round bolts @ 2'-0" (staggered) G3. The following roof live and snow loads are the minimums required by the building code. The
S5. Bolts for structural connections shall be 3/4-inch diameter A325 in bearing-type center-to-center unless detailed otherwise. minimum load used in design was 25 psf, or applicable snow drift (whichever was greater). NOTES
C13. Slabs-on-grade shall not be air entrained.
connections, tightened to snug tight, unless noted otherwise. Snug tight is the tightness G4. Roof Live Load (non-concurrent with Roof Snow Loads) = 25 psf

19-030_NBE_Benson Multifamily_R19_detached.rvt
L25. In exterior walls where windows or other openings interrupt wall studs, use the following
C14. Vapor barrier shall be 15 mil polyethylene sheets unless otherwise specified, with all laps that exists when all plies in a joint are in firm contact, and may be achieved by a few G5. ROOF SNOW LOAD
number of studs at each opening jamb, unless shown otherwise:
sealed and edges turned up 1/2 inches below finish floor slabs. impacts of an impact wrench or the full effort of a man using an ordinary spud wrench. Ground Snow Load (Pg) = 25 PSF
Wall Opening Number Of Full Number Of Flat Roof Snow Load (Pf) = 17.5 PSF
C15. Non-shrink grout shall be factory premixed as manufactured by L & M Chemicals, or S6. Anchor rods shall conform to ASTM A 36 or ASTM F 1554, Grade 36 unless indicated otherwise.
Width Height Studs Bearing Studs Rain-on-Snow = 0 PSF
equivalent. Anchor rods designated as “high strength” shall conform to ASTM A 193, Grade B7 or ASTM F
1554, Grade 105. All nuts used with anchor rods shall be heavy hex head conforming to ASTM Snow Exposure Factor (Ce) = 1.0
Up to 3'-0" 1 1
C16. Expansion anchors shall be Hilti Kwik-Bolt 3, Red Head Trubolt or approved equivalent, with Snow Load Importance Factor (Is) = 1.0
A 563. 3'-0" to 5'-0" 2 1
size as noted on the drawings. Install per manufacturer's instructions. Thermal Factor (Ct) = 1.0
S7. Headed studs shall conform to ASTM A 108 complying with AWS Code. 5'-0" to 7'-0" 3 1
C17. Screw anchors shall be Hilti HUS-H, Red Head Large Diameter Tapcon, Simpson TitenHD or G6. FLOOR LIVE LOAD
Over 7'-0" 4 2 119 SOUTH 49TH AVENUE
approved equivalent, with size as noted on the drawings. Install per manufacturer's instructions. S8. Welding shall be performed by certified welders using low hydrogen E70 electrodes. Comply
Typical (reduced for girders, columns OMAHA, NEBRASKA 68132
with AWS for electrodes and procedures. L26. Unless detailed or shown otherwise, provide the following minimum header sizes: (402)551-0800
& footings; not reduced for beams) = 40 PSF
C18. Adhesive anchors shall utilize Red Head “A7 Acrylic Adhesive” Anchor System. Simpson
Wall Opening Mechanical Room = 60 PSF
Strong-Tie “Acrylic-Tie” and “Epoxy-Tie” anchor systems or Hilti “HIT HY-70” system are also
Width Header Size Assembly Areas, Lobbies, 1st Floor
ARY N PROJECT: 17073
acceptable provided their shear and tension allowable load capacities are equivalent to or N UCTIO
Corridors = 100 PSF I DATE: 8/__/19
greater than Red Head A7 Acrylic Adhesive. Threaded rods shall be ASTM A193 Grade B7 unless Up to 4'-6" (2) - 2 X 8's LIM NSTR

8/26/2019 7:11:35 PM
Corridors above 1st Floor = 80 PSF E
noted otherwise. Installation of anchors shall be in strict accordance with manufacturer’s 4'-6" to 5'-6" (2) - 2 X 10's Stairways & exit facilities = 100 PSF
PR R CO
recommendations including finish, minimum embedment, adhesive types, recommended T FO
5'-6" to 6'-6" (2) - 2 X 12's
accessories for base conditions (such as screens at hollow base conditions) and cure times for Decks = 60 PSF NO C COPYRIGHT 2019

weather conditions.
8/__/19
SHEET: S0.01
AGENCY APPROVAL

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

FOUNDATION PLAN

19-030_NBE_Benson Multifamily_R19_detached.rvt
119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


1 FOUNDATION PLAN I N UCTIO
LIM NSTR DATE: 8/__/19

8/26/2019 7:11:36 PM
E
PR R CO
S1.00 1/8" = 1'-0"

T FO
NO C COPYRIGHT 2018

8/__/19
SHEET: S1.00
AGENCY APPROVAL
FRAMING PLAN NOTES

8"
1. DENOTES SPAN DIRECTION AND DEPTH IN INCHES FOR HOLLOW
CORE PLANKS. DEPTH OF PLANKS MAY BE INCREASED AS REQUIRED TO MEET
STRENGTH REQUIREMENTS. PLANKS UNDER THE BUILDING SHALL HAVE 4” NORMAL
WEIGHT CONCRETE TOPPING. PRECASTER SHALL DESIGN PLANKS FOR AS MANY AS
(2) STRANDS PER PLANK TO BE FIELD CUT FOR PLUMBING INSTALLATION.

2. PRECAST BEAMS AND COLUMNS SHALL BE SIZED BY THE PRECASTER. THE


PREFERRED MAXIMUM COLUMN SIZE IS 18”X18”. A MINIMUM CLEARANCE OF 8’-0”
IS REQUIRED FROM THE GARAGE SLAB TO THE BOTTOM OF THE STRUCTURE. THE
GARAGE SLAB WILL SLOPE IN ORDER TO MINIMIZE THE RETAINED SOIL HEIGHT
AROUND THE BUILDING. (GARAGE FLOOR TO FIRST FLOOR HEIGHT IS ANTICIPATED
TO BE 16 FEET AT THE NORTHEAST CORNER, 14 FEET AT THE NORTHWEST
CORNER, AND 12 FEET ALL ALONG THE SOUTH WALL).

NOTE 10. SEE NOTE 5 FOR TYP. UNIFORM AREA 3. ABBREVIATIONS:


LOADS APPLIED DIRECTLY TO PODIUM ITB = PRECAST INVERTED ‘T’ BEAM
LB = PRECAST ‘L’ SHAPED BEAM
RB = PRECAST RECTANGULAR BEAM

4. BEAMS BEARING AT CONCRETE WALLS WILL GENERALLY BEAR ON C.I.P.


PILASTERS INTEGRAL WITH THE WALL. ALL OTHER COLUMNS WILL BE PRECAST.

5. SUPERIMPOSED UNIFORM LOADS ON PODIUM UNDER THE BUILDING


4” TOPPING: 50 PSF
MISCELLANEOUS DEAD LOAD: 15 PSF

8"
LB
LIVE LOAD AT LIVING UNITS: 40 PSF, REDUCIBLE TO 30 PSF FOR STRUCTURAL
ELEMENTS SUPPORTING MULTIPLE STORIES.
LIVE LOAD AT ALL OTHER FIRST FLOOR AREAS: 100 PSF, NON-REDUCIBLE.

6. SUPERIMPOSED LINE LOADS FROM WALLS AND POINT LOADS ON THE PODIUM
UNDER THE BUILDING FROM STEEL COLUMNS OR WOOD POSTS: SEE FRAMING
8" PLAN. ‘D’ = SERVICE DEAD LOAD, ‘L’ = REDUCED SERVICE LIVE LOAD + NON-
ITB ITB ITB ITB ITB REDUCED ROOF LIVE LOAD, BOTH IN KIPS OR KIPS/FT. (NOTE THAT FOR THIS
PRELIM LAYOUT, ONLY THE MAJOR LOADS HAVE BEEN SHOWN, FINAL DRAWINGS
WILL BE MORE COMPLETE, INCLUDING HOLD-DOWN FORCES AT THE ENDS OF
PLYWOOD SHEAR WALLS. ALSO NOTE THAT THE LIVE LOAD USED FOR ALL AREAS
8" OF LEVELS 2, 3, AND 4 WAS 40 PSF, REDUCED TO 30 PSF FOR THE PODIUM

ITB
DESIGN.

LB
7. SUPERIMPOSED UNIFORM LOADS ON PODIUM OVER COURTYARD

12"
DEAD LOAD: TO BE DETERMINED. MINIMUM TOPPING THICKNESS TO BE 4”, BUT

ITB
NOTE 9.
THE STRUCTURE IN THIS AREA MAY BE DEPRESSED AND THE TOPPING MAY BE
THICKENED TO ACHIEVE SLOPE TO DRAINS. A WATERPROOF TRAFFIC TOPPING WILL
BE APPLIED OVER THE CONCRETE TOPPING.

LIVE LOAD: 100 PSF TYPICAL, 150 PSF OVER SHELTER, BOTH NON-REDUCIBLE.
ADDITIONAL LOADS SUCH AS CONTINOUS PLANTERS WILL BE SHOWN ON THE FINAL
LB DRAWINGS.

ITB
POSSIBLE RB UNDER
ITB LB LB LB CORRIDOR WALL 8. 12" PLANKS REFERENCED TO THIS NOTE MUST BE DESIGNED AS NON-
COMPOSITE DUE TO THERMAL BREAK REQUIRED IN TOPPING ALONG THE EXTERIOR
LOAD-BEARING WALL WALL.
ABOVE w/ TRAPEZOIDAL BEAM UNDER EXTERIOR 8" 9. TYPICAL CORRIDOR LINE LOADS:
LINE LOAD. AT WEST END NOTE 9. COURTYARD WALL

LB
D=2.5K/FT L=2.0K/FT. D=2.5K/FT, L=2.0K/FT (NOTE THAT WHERE THE CORRIDOR WALLS ABOVE SECOND

NOTE 8.
AT EAST END D=1.9 8" 12" FLOOR ARE NOT SHOWN ON THIS PLAN, THEY BEAR ON STEEL BEAMS AT SECOND

12"

LB

ITB

ITB
K/FT, L=1.4 K/FT FLOOR).
8"

ITB
10. TYPICAL RECESSED EXTERIOR WALL LOADS: D=2.2K/FT, L=1.7K/FT.
NOTE 10.

12" RB RB RB
ITB

8" DASHED LINE = OUTSIDE FACE


OF EXTERIOR WALL ABOVE
PRECAST BEAM LINES UNDER
EXTERIOR COURTYARD WALLS

ITB
SHADED AREA = EXTERIOR (D=2.3K/FT, L=1.7K/FT)
COURTYARD (NOTE 7.)

RB

STEEL COL. ABOVE,


8" 8" 12" 8"

ITB

ITB
(D=31.4K, L=26.2K)

STEEL COL. ABOVE,


(D=37.7K, L=27.8K)
ITB

RB

ITB
STEEL COL. ABOVE, C.I.P. PILASTER BELOW
(D=87.7K, L=67.5K) (TYP. @ PRECAST BEAM
BEARING ON C.I.P. WALLS)
LB LB RB
ITB

ITB
RB

RB

8"
8"

8"

8"
RB

LB
12" No. Description Date
8"

SAGE
8"
8"

STEEL COL. ABOVE,


(D=83.5K, L=66.8K)
ITB ITB ITB
DEVELOPMENT
ITB

RB

P.C. COL. BELOW


GROUP
12" (TYP. UNLESS NOTED OTHERWISE)
12"

12"
RB

LB
ITB

NOTE 9.
BENSON
ITB

STEEL COL. ABOVE,


(D=68.3K, L=57.5K)
STEEL COL. ABOVE,
(D=32.6K, L=30.4K)
8" POSSIBLE RB UNDER CORRIDOR WALL
MULTIFAMILY

ITB ITB ITB

FIRST FLOOR FRAMING


PLAN

19-030_NBE_Benson Multifamily_R19_detached.rvt
8"

8"

NOTE 10.

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


1 FIRST FLOOR FRAMING PLAN I N UCTIO
LIM NSTR DATE: 8/__/19

8/26/2019 7:11:41 PM
E
PR R CO
S1.01 1/8" = 1'-0"

T FO
NO C COPYRIGHT 2018

8/__/19
SHEET: S1.01
AGENCY APPROVAL
SECOND FLOOR FRAMING PLAN NOTES:

X = GENERAL PLAN NOTE

X = NOTE REFERENCED ON PLAN

14'-0" 25'-0 1/8" 13'-7 3/4" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 13'-7 7/8" 13'-7 1/4" 9'-10"
1. SEE SHEET S0.01 FOR STRUCTURAL GENERAL NOTES.
7'-0" 6'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 1'-8"
1 2. SECOND FLOOR ELEVATION (TOP OF UNDERLAYMENT OVER WOOD DECK) = 111'-0".
S3.01
3. ALL EXTERIOR WOOD STUD WALLS (SHOWN HALF-TONE) SHALL HAVE 2x6 STUDS @
16"o.c., WITH 7/16" PLYWOOD OR O.S.B. SHEATHING ON OUTSIDE FACE, ATTACHED PER

4'-4 1/2"
STRUCTURAL GENERAL NOTES. INTERIOR STRUCTURAL WOOD STUD WALLS ARE
INDICATED ON FOUNDATION AND FRAMING PLANS AS FOLLOWS:

10'-6 1/2"
11'-4 1/2"
2x6 @ 16"o.c. INTERIOR STUD WALLS.
2 1
S3.01 2x6 @ 16"o.c. INTERIOR STUD SHEARWALLS WITH TIEDOWN AT
V5

10"
V3 V3 V3
V3 V3 V3 BOTH ENDS, PER SHEARWALL SCHEDULE ON SHEET ____.
(SHEAR WALL MARK IS SHOWN ON PLANS THUS: SW-1 ETC.)
DN
SEE ARCHITECTURAL DRAWINGS FOR FULL EXTENT OF PLYWOOD
SHEATHING BEYOND THE SPECIFIC SHEARWALL ZONE SHOWN ON
7

25'-3 5/8"
1 FRAMING PLAN.
S3.01
4. L-1, H-1, B-1 ETC = LINTEL IN CMU WALL, WOOD HEADER, OR WOOD BEAM IN
WALL BELOW. SEE SCHEDULES ON SHEET _____ . (NOTE THAT STEEL ANGLE
LINTELS IN BRICK VENEER WALLS ARE SHOWN ON DETAIL _____ .)

5. STRUCTURAL ELEMENT TYPE/SPAN DIRECTION.


3 1
24" DEEP LOW-JOIST WOOD FLOOR TRUSSES AT 19.2"o.c.
1 S3.01
6 2
24" DEEP WOOD ROOF TRUSSES AT 24"o.c.

64'-6 1/2"
3

5'-6 3/4"
2x8 @ 16"o.c.
6 U2.1 U2.1 6 V2.1

1'-10"
140 4 2x8 @ 24"o.c.
5

123
5 2x10 @ 16"o.c.
V3 U2.1 3
S3.01 6 2x10 @ 19.2"o.c.
V3
6'-0
"

6 U2.1 2 6. FLOOR TRUSS DESIGN LOAD IN HATCHED AREAS IS AS FOLLOWS:


5

1
S3.01 S3.01
V3 TOP CHORD DEAD LOAD = 25 PSF
TOP CHORD LIVE LOAD = 100 PSF
21'-

29'-3 5/8"
3/4" 7 BOTTOM CHORD DEAD LOAD = 10 PSF
5'-6
7 7/

V3 1
S3.01
8"

"
7'-0 7. FOR SNOW DRIFT LOADING, SEE
6 W2 1

17'-9 15/16"
U2.1 S3.01
S3.01
6'-4

1 U2.1 1

3'-6
"

S3.01 2

"
8. MISCELLANEOUS SYMBOLS:
S3.01
V3

15'-
/2" V3
STEEL BEAM SHEAR SPLICE - SEE DETAIL _____ .
6'-2

-11 1
3 '

7 1/
2 8
1/4"

V3

16"
S3.01 STEEL BEAM TO FACE OF CMU WALL.

3 5'-8" 3'-10" 3'-10" 5'-8" 6'-4" 5'-8" STEEL BEAM TO COLUMN MOMENT CONNECTION.

4'-8
7 5'-0
"
1

3/4"
S3.01 S3.01 7 1/2" 19'-0 3/4" 7 1/4" 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
SW-X PLYWOOD SHEAR WALL MARK - SEE SCHEDULE ON
S3.01
25'-

SHEET _____
5 3/

/2" 9. SEE SHEET _____ FOR TYPICAL STEEL FRAMING CONNECTIONS. USE TYPICAL
'-11 1
4"

2 8 CONNECTIONS UNLESS SHOWN OTHERWISE.

5'-0
"
6'-2

OUTDOOR KITCHEN W/ BRICK VENEER

5'-0
E
PLAC & CONCRETE COUNTERTOPS
8 E
1/4"

"
FIR
AS
S3.01 EARG

131
LIN

171'-4 3/4"
24'-5 1/2"

42'-3 3/4"
6'-4

X1 (2) BUILT-IN
OUTDOOR GRILLS
"
12'-

1
3 7/
8"

8 103 44'-8"
S3.01

6
1 PEDESTRIAN CANTILEVERED
BRIDGE W/ GUARDRAILS TO
12'-

S3.01
107 MATCH BUILDING STANDARD
3 7/

1
6'-4

1
8"

19'-0 3/4"
S3.01 7 1/4" 24'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
106
"

102 5'-6" 3'-10" 5'-6" 6'-4" 6'-4" 5'-6"


5/8"
3'-4

105
2
5 S3.01

STEEL BEAMS (TYP. @ BOLD LINES) 5

29'-3 5/8"
TO SUPPORT LOAD-BEARING STUD 7

121
WALLS THAT DO NOT CONTINUE 1
S3.01
37'-

DOWN TO FIRST FLOOR.


8 1/

122
2"

5 No. Description Date


1
3
101
S3.01

100 6 SAGE

1'-10"
DEVELOPMENT

64'-6 1/2"
5'-6 3/4"
141
111

6 V2.1
120

GROUP
113

113A
3
S3.01

BENSON
112

25'-3 5/8"
MULTIFAMILY
34'-

1 1
7
0 7/
16"

S3.01

V3 V3 V5
V3 V3

SECOND FLOOR FRAMING

141A

4'-4 1/2"
110

3'-4 1/2"

PLAN

19-030_NBE_Benson Multifamily_R19_detached.rvt
5'-0" 5'-0" 3'-3"
3'-3" 5'-0" 5'-0" 5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 15'-0"
13'-6 1/2" 13'-8" 25'-8 1/8" 13'-7 3/4" S3.011/4"
13'-7 9'-10"

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
1 SECOND FLOOR FRAMING PLAN
S1.02 1/8" = 1'-0"
ARY N PROJECT: 17073
I N UCTIO
LIM NSTR DATE: 8/__/19

8/26/2019 7:11:48 PM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/__/19
SHEET: S1.02
AGENCY APPROVAL
THIRD FLOOR FRAMING PLAN NOTES:

X = GENERAL PLAN NOTE

X = NOTE REFERENCED ON PLAN

14'-0" 25'-0 1/8" 13'-7 3/4" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 13'-7 7/8" 13'-7 1/4" 9'-10"
1. SEE SHEET S0.01 FOR STRUCTURAL GENERAL NOTES.
6'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 5'-4" 5'-0" 3'-3" 3'-3" 5'-0" 5'-4" 1'-8"
1 2. THIRD FLOOR ELEVATION (TOP OF UNDERLAYMENT OVER WOOD DECK) = 122'-0".
S3.01
W4 W1 W4 W4 W1 W1 W4 W4 W1 W1 W4 W4 W1 3. ALL EXTERIOR WOOD STUD WALLS (SHOWN HALF-TONE) SHALL HAVE 2x6 STUDS @
16"o.c., WITH 7/16" PLYWOOD OR O.S.B. SHEATHING ON OUTSIDE FACE, ATTACHED PER

4'-4 1/2"
STRUCTURAL GENERAL NOTES. INTERIOR STRUCTURAL WOOD STUD WALLS ARE
W12 INDICATED ON FOUNDATION AND FRAMING PLANS AS FOLLOWS:

10 1/4" 10'-6 1/2"


11'-4 3/4"
2x6 @ 16"o.c. INTERIOR STUD WALLS.
2 1
S3.01 2x6 @ 16"o.c. INTERIOR STUD SHEARWALLS WITH TIEDOWN AT
V5
V3 V3 V3 V3 BOTH ENDS, PER SHEARWALL SCHEDULE ON SHEET ____.
V3 V3
(SHEAR WALL MARK IS SHOWN ON PLANS THUS: SW-1 ETC.)
SEE ARCHITECTURAL DRAWINGS FOR FULL EXTENT OF PLYWOOD
SHEATHING BEYOND THE SPECIFIC SHEARWALL ZONE SHOWN ON
7
FRAMING PLAN.

25'-3 5/8"
1
S3.01
4. L-1, H-1, B-1 ETC = LINTEL IN CMU WALL, WOOD HEADER, OR WOOD BEAM IN
WALL BELOW. SEE SCHEDULES ON SHEET _____ . (NOTE THAT STEEL ANGLE
W3.2 LINTELS IN BRICK VENEER WALLS ARE SHOWN ON DETAIL _____ .)

W3.2 5. STRUCTURAL ELEMENT TYPE/SPAN DIRECTION.


3 1
24" DEEP LOW-JOIST WOOD FLOOR TRUSSES AT 19.2"o.c.
W3.2 1 S3.01
6 2
24" DEEP WOOD ROOF TRUSSES AT 24"o.c.

64'-6 1/2"
3

5'-6 3/4"
2x8 @ 16"o.c.
6 U2.1 U2.1 6 V2.1
W3.2

1'-10"
240 4 2x8 @ 24"o.c.
5

223
5 2x10 @ 16"o.c.
V3 U2.1 3
S3.01 6 2x10 @ 19.2"o.c.
V3
6'-0
"

W4
6 U2.1 2 6. FLOOR TRUSS DESIGN LOAD IN HATCHED AREAS IS AS FOLLOWS:
5

1
S3.01 S3.01
V3 TOP CHORD DEAD LOAD = 25 PSF

224
TOP CHORD LIVE LOAD = 100 PSF

29'-3 5/8"
7
21'-

U2.1 BOTTOM CHORD DEAD LOAD = 10 PSF

A
V3 1
7 7/

W4 S3.01
W4 3/4" W2
5'-6
8"

7. FOR SNOW DRIFT LOADING, SEE


6 W2 W4 1
0"
7'-S3.01
U2.1

3'-6
S3.01
6'-4

1 U2.1 1
224

5/16

13'-10"
"

W4S3.01
2 8. MISCELLANEOUS SYMBOLS:

"
S3.01
V3 V3
/2" STEEL BEAM SHEAR SPLICE - SEE DETAIL _____ .
6'-2

11 1
3 28'-
1/4"

V3
S3.01 STEEL BEAM TO FACE OF CMU WALL.

3'-4

1'-4
3 STEEL BEAM TO COLUMN MOMENT CONNECTION.
7 " W4 W4 W4

"
5'-0 1

3/4"
S3.01 S3.01 5'-8" 3'-3" 3'-3" 5'-8" 6'-2" 5'-8" PLYWOOD SHEAR WALL MARK - SEE SCHEDULE ON
X1 SW-X
S3.01

3'-4
7 1/2" 19'-0 3/4" 7 1/4" 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2" SHEET _____
25'-

"
/2" 9. SEE SHEET _____ FOR TYPICAL STEEL FRAMING CONNECTIONS. USE TYPICAL
5 3/

8'-11 1 W4
2 U2.1 CONNECTIONS UNLESS SHOWN OTHERWISE.
4"

19'-
5'-0
6"

0 3/
"

4"
6'-2

5 '-0
8
1/4"

"

5'-0
W4

6'-0
S3.01

"
231

171'-4 3/4"
3/4"

42'-3 3/4"
5'-0

7 1/
6'-4

"
X1
" 5'-0

4"
"

W4 6" V3
6" 1

6'-0
3/4"
8

19'-
S3.01 W4
24'-

0 3/
7 3/

4"
6
1
4"

W4
S3.01 U2.1 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
"
3'-0
1 3'-3" 5'-8" 6'-2" 6'-2" 5'-8"
6'-4

3'-4
S3.01
"

"
W4 W4
V3 W4
6'-2

U2.1
1/4"

V3 5'-8"

13'-10"
2
5 V3 V3 V3 S3.01
25'-

5
5 3/

29'-3 5/8"
7 W2
4"

221
1
S3.01
222
6'-2
1/4"

5 No. Description Date


EQ

1
6'-1

3
1/2"

V3 S3.01
W4
SAGE
EQ
11'-

6
7 1/

1'-10"
5'-6

DEVELOPMENT

64'-6 1/2"
2"

5'-6 3/4"
241
EQ

W3.2
"

U2.1 6 U2.1 V2.1


EQ

GROUP
7 1/

5'-6
4"

EQ

"

W4 3
EQ

S3.01
38'-
4 13

12'-
/16"

BENSON
11 1

25'-3 5/8"
/4"

W5 1 1
7
MULTIFAMILY
S3.01

V3 V3 V5
V3 V3
3'-11 3/8"

THIRD FLOOR FRAMING

4'-4 1/2"
W12
PLAN

19-030_NBE_Benson Multifamily_R19_detached.rvt
W1 W4 W4 W1 W1 W4 W4 W1
5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 5'-0" 5'-0" 5'-0" 3'-3" 3'-3" 5'-0" 15'-0" 1'-8"
13'-7 11/16" 13'-6 1/2" 13'-8" 25'-8 1/8" 13'-7 3/4" S3.011/4"
13'-7 9'-10"

1 THIRD FLOOR FRAMING PLAN


S1.03 1/8" = 1'-0" 119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N UCTIO
LIM NSTR DATE: 8/__/19

8/26/2019 7:11:54 PM
E
PR R CO
T FO
NO C COPYRIGHT 2018

1'-7 1/4" 8/__/19


SHEET: S1.03
EQ EQ EQ EQ EQ
AGENCY APPROVAL
FOURTH FLOOR FRAMING PLAN NOTES:

X = GENERAL PLAN NOTE

X = NOTE REFERENCED ON PLAN

1. SEE SHEET S0.01 FOR STRUCTURAL GENERAL NOTES.

1 2. FOURTH FLOOR ELEVATION (TOP OF UNDERLAYMENT OVER WOOD DECK) = 133'-0".


S3.01
3. ALL EXTERIOR WOOD STUD WALLS (SHOWN HALF-TONE) SHALL HAVE 2x6 STUDS @
16"o.c., WITH 7/16" PLYWOOD OR O.S.B. SHEATHING ON OUTSIDE FACE, ATTACHED PER
STRUCTURAL GENERAL NOTES. INTERIOR STRUCTURAL WOOD STUD WALLS ARE
INDICATED ON FOUNDATION AND FRAMING PLANS AS FOLLOWS:

2x6 @ 16"o.c. INTERIOR STUD WALLS.


2 1
S3.01 STAIR
2x6 @ 16"o.c. INTERIOR STUD SHEARWALLS WITH TIEDOWN AT
UNIT 2-B UNIT J UNIT J UNIT J UNIT J 440
BOTH ENDS, PER SHEARWALL SCHEDULE ON SHEET ____.
458 456 454 452 450
(SHEAR WALL MARK IS SHOWN ON PLANS THUS: SW-1 ETC.)
SEE ARCHITECTURAL DRAWINGS FOR FULL EXTENT OF PLYWOOD
7 SHEATHING BEYOND THE SPECIFIC SHEARWALL ZONE SHOWN ON
1 FRAMING PLAN.
S3.01
4. L-1, H-1, B-1 ETC = LINTEL IN CMU WALL, WOOD HEADER, OR WOOD BEAM IN
UNIT 2-C WALL BELOW. SEE SCHEDULES ON SHEET _____ . (NOTE THAT STEEL ANGLE
460 LINTELS IN BRICK VENEER WALLS ARE SHOWN ON DETAIL _____ .)

5. STRUCTURAL ELEMENT TYPE/SPAN DIRECTION.


3 1
24" DEEP LOW-JOIST WOOD FLOOR TRUSSES AT 19.2"o.c.
1 S3.01
6 2
24" DEEP WOOD ROOF TRUSSES AT 24"o.c.

3
CORRIDOR 2x8 @ 16"o.c.
6 6
430
4 2x8 @ 24"o.c.
5
5 2x10 @ 16"o.c.
3
S3.01 6 2x10 @ 19.2"o.c.
UNIT 1-C
6 457 2 6. FLOOR TRUSS DESIGN LOAD IN HATCHED AREAS IS AS FOLLOWS:
5

1
S3.01 S3.01
STORAGE TOP CHORD DEAD LOAD = 25 PSF
ROOF
423 ACCESS TOP CHORD LIVE LOAD = 100 PSF
7 BOTTOM CHORD DEAD LOAD = 10 PSF
425 1
S3.01
1 7. FOR SNOW DRIFT LOADING, SEE
6 ELEC
424 S3.01
S3.01
1 1 UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B
S3.01 2 455 453 451
8. MISCELLANEOUS SYMBOLS:
461
S3.01
STEEL BEAM SHEAR SPLICE - SEE DETAIL _____ .
3
UNIT S-B
S3.01 463 STEEL BEAM TO FACE OF CMU WALL.

7 3 STEEL BEAM TO COLUMN MOMENT CONNECTION.


S3.01
1
S3.01 CORRIDOR PLYWOOD SHEAR WALL MARK - SEE SCHEDULE ON
S3.01 SW-X
UNIT 1-B 431 SHEET _____
462
9. SEE SHEET _____ FOR TYPICAL STEEL FRAMING CONNECTIONS. USE TYPICAL
CONNECTIONS UNLESS SHOWN OTHERWISE.

8
UNIT S-B
S3.01 465

8
S3.01

6
1
S3.01 UNIT S-B
467
1
1
UNIT 1-B S3.01
464

2
CORRIDOR 5
TRASH UNIT S-B UNIT 1-A UNIT 1-A
S3.01
UNIT 1-B 432 421 471 473 475
466 5
TELECOM
422 7
1
S3.01

5 ELEVATOR No. Description Date


1LOBBY
3
420
S3.01

6 SAGE
6
CORRIDOR
433
DEVELOPMENT
GROUP
3
S3.01

UNIT 2-A
468
BENSON
1 1
7
MULTIFAMILY
UNIT S-A UNIT S-A UNIT J S3.01 UNIT J
469 470 472 474
STAIR
441

FOURTH FLOOR FRAMING


PLAN

19-030_NBE_Benson Multifamily_R19_detached.rvt
1
S3.01

1 FOURTH FLOOR FRAMING PLAN


S1.04 1/8" = 1'-0" 119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N UCTIO
LIM NSTR DATE: 8/__/19

8/26/2019 7:11:58 PM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/__/19
SHEET: S1.04
AGENCY APPROVAL
ROOF FRAMING PLAN NOTES:

X = GENERAL PLAN NOTE

X = NOTE REFERENCED ON PLAN

14'-4 1/8" 24'-8" 13'-7 3/4" 25'-8 1/4" 13'-7 3/4" 25'-8 1/8" 13'-7 7/8" 13'-7 1/4" 9'-10"
1. SEE SHEET S0.01 FOR STRUCTURAL GENERAL NOTES.
6'-0" 6'-8" 3'-3" 3'-3" 6'-8" 6'-8" 3'-3" 3'-3" 6'-8" 6'-8" 3'-3" 3'-3" 6'-8" 1'-8"
2. ROOF ELEVATION (TOP OF 5/8" ROOF SHEATHING) = 144'-0".

W8 W10 W10 W10 W10 W10 W10 3. ALL EXTERIOR WOOD STUD WALLS (SHOWN HALF-TONE) SHALL HAVE 2x6 STUDS @
16"o.c., WITH 7/16" PLYWOOD OR O.S.B. SHEATHING ON OUTSIDE FACE, ATTACHED PER

4'-4 1/2"
STRUCTURAL GENERAL NOTES. INTERIOR STRUCTURAL WOOD STUD WALLS ARE
W12 INDICATED ON FOUNDATION AND FRAMING PLANS AS FOLLOWS:

11'-0 1/4"
10 1/4" 10'-2"
2x6 @ 16"o.c. INTERIOR STUD WALLS.

STAIR
V5 2x6 @ 16"o.c. INTERIOR STUD SHEARWALLS WITH TIEDOWN AT
EWA-2UNIT 2-B V3 UNIT J UNIT J V3 UNIT J V3 UNIT J 440
V3 V3 BOTH ENDS, PER SHEARWALL SCHEDULE ON SHEET ____.
458 456 454 452 450
(SHEAR WALL MARK IS SHOWN ON PLANS THUS: SW-1 ETC.)
SEE ARCHITECTURAL DRAWINGS FOR FULL EXTENT OF PLYWOOD
SHEATHING BEYOND THE SPECIFIC SHEARWALL ZONE SHOWN ON

25'-3 5/8"
FRAMING PLAN.

4. L-1, H-1, B-1 ETC = LINTEL IN CMU WALL, WOOD HEADER, OR WOOD BEAM IN
UNIT 2-C WALL BELOW. SEE SCHEDULES ON SHEET _____ . (NOTE THAT STEEL ANGLE
W3.3
460 LINTELS IN BRICK VENEER WALLS ARE SHOWN ON DETAIL _____ .)

W3.3
5. STRUCTURAL ELEMENT TYPE/SPAN DIRECTION.
1
W3.3 24" DEEP LOW-JOIST WOOD FLOOR TRUSSES AT 19.2"o.c.

2
24" DEEP WOOD ROOF TRUSSES AT 24"o.c.

64'-6 1/2"
3

5'-6 3/4"
CORRIDOR 2x8 @ 16"o.c.
U2.1 U2.1 430 V2.1
W3.2

1'-10"
440 4 2x8 @ 24"o.c.

423
5 2x10 @ 16"o.c.
V3 U2.1
6 2x10 @ 19.2"o.c.
V3
6'-0

UNIT 1-C
W8
"

U2.1 U2.1 457 6. FLOOR TRUSS DESIGN LOAD IN HATCHED AREAS IS AS FOLLOWS:

STORAGE V3 TOP CHORD DEAD LOAD = 25 PSF


ROOF
423 ACCESS TOP CHORD LIVE LOAD = 100 PSF

29'-3 5/8"
21'-

425 V3 BOTTOM CHORD DEAD LOAD = 10 PSF


7 7/

W4
W8 425 3/4" W2
5'-6
8"

7. FOR SNOW DRIFT LOADING, SEE


ELEC W4 "
U2.1 424 7'-0
6'-4

UNIT S-B UNIT S-B UNIT 1-A


424

13'-10"
UNIT 1-B
"

455 453 451


461 W4 8. MISCELLANEOUS SYMBOLS:

4" V3 V3
1 3/ STEEL BEAM SHEAR SPLICE - SEE DETAIL _____ .
6'-2

28'-
UNIT S-B
1/4"

V3
463 STEEL BEAM TO FACE OF CMU WALL.

3'-4

1'-4
3/4" W4 W4 W4 STEEL BEAM TO COLUMN MOMENT CONNECTION.

"
5'-9

3/4"
CORRIDOR X1 5'-8" 3'-4" 3'-4" 5'-8" 6'-2" 5'-8" PLYWOOD SHEAR WALL MARK - SEE SCHEDULE ON
SW-X

3'-4
UNIT 1-B 431 7 1/2" 19'-0 3/4" 7 1/4" 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2" SHEET _____
25'-

"
462
/2" 9. SEE SHEET _____ FOR TYPICAL STEEL FRAMING CONNECTIONS. USE TYPICAL
5 3/

8'-11 1 W4
2 U2.1 CONNECTIONS UNLESS SHOWN OTHERWISE.
4"

19'-
5'-0

0 3/
"

4"
6'-2

5'-0 "
1/4"

5'-0
UNIT S-B W4

6'-0
"
465

431

171'-4 3/4"
3/4"

42'-3 3/4"
5'-0

7 1/
6'-4

"
X1 5'-0
"

4"
"

W8 6" V3
6"

6'-0
3/4"

19'-
W4
24'-

0 3/
7 3/

4"
4"

W8
U2.1 UNIT S-B 19'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/4" 24'-0 3/4" 7 1/2"
"
3'-0 467 3'-4" 5'-8" 6'-2" 6'-2" 5'-8"
6'-4

3'-4
UNIT 1-B
"

"
464 W4 W4 W4
V3
6'-2

U2.1
1/4"

5'-8"

13'-10"
CORRIDOR TRASH UNIT S-B UNIT 1-A UNIT 1-A
V3 V3 V3
UNIT 1-B 432 421 471 473 475
25'-

466
5 3/

TELECOM

29'-3 5/8"
W2
4"

422

421
422
6'-2
1/4"

ELEVATOR No. Description Date


EQ

LOBBY
6'-1

420
1/2"

V3
W9
SAGE
EQ
11'-
7 1/

1'-10"
5'-6

DEVELOPMENT

64'-6 1/2"
2"

5'-6 3/4"
CORRIDOR 441 W3.2
"

U2.1 U2.1 V2.1


433
EQ

GROUP
7 1/

5'-6
4"

"

W9
EQ
38'-
4 13

12'-
/16"

BENSON
11 1

UNIT 2-A

25'-3 5/8"
/4"

468

W11 MULTIFAMILY
UNIT S-A UNIT S-A UNIT J UNIT J
469 470 472 474
V3 V3 V5 STAIR
3'-11 3/8"

V3 V3
441

ROOF FRAMING PLAN

4'-4 1/2"
W8 W12

0"
10'-

19-030_NBE_Benson Multifamily_R19_detached.rvt
W10 W10 W10 W10
6'-1 3/16" 6'-8" 3'-3" 3'-3" 6'-8" 6'-8" 3'-3" 3'-3" 6'-8" 1'-8"
13'-2 3/8" 13'-8" 25'-8 1/8" 13'-7 3/4" 13'-7 1/4" 9'-10"

1 ROOF FRAMING PLAN


S1.05 1/8" = 1'-0" 119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800

ARY N PROJECT: 17073


I N UCTIO
LIM NSTR DATE: 8/__/19

8/26/2019 7:12:04 PM
E
PR R CO
T FO
NO C COPYRIGHT 2018

8/__/19
SHEET: S1.05
SIMPSON RSP4 STUD TIE
(4th FLOOR ONLY)
2x6 @ 16"c/c
(2) - 1/4"x4 1/2" WOOD
SCREWS @ EACH STUD INTO
(2) - 1/4"x4 1/2" WOOD (2) - 1/4"x4 1/2" SIMPSON RSP4 STUD PL.
CONTINUOUS RIM BOARD
2x6 @ 16"c/c SCREWS @ EACH STUD INTO WOOD SCREWS @ EACH TIE (4th FLOOR ONLY)
2x6 @ 16"c/c (4th FLOOR ONLY)
CONTINUOUS RIM JOIST (4th STUD INTO CONTINUOUS 2x6 @ 16"c/c
2x6 CONT. (NAIL TO RIM 1" UNDERLAYMENT + 2x6 @ 16"c/c 1" UNDERLAYMENT + FLOOR ONLY) SIMPSON RSP4 STUD PL. RIM BOARD (4th FLOOR 1" UNDERLAYMENT +
1" UNDERLAYMENT +
BOARD BELOW w/ 16d 1/4" ACOUSTICAL MAT 1/4" ACOUSTICAL MAT 1" UNDERLAYMENT + TIE (4th FLOOR ONLY) ONLY) 1/4" ACOUSTICAL MAT
1/4" ACOUSTICAL MAT 2x6 CONT.
NAIL @ 6"o.c.) 1/4" ACOUSTICAL MAT
3/4" PLYWOOD SUBFLOOR 2x6 CONT. 3/4" PLYWOOD SUBFLOOR 2x6 3/4" PLYWOOD SUBFLOOR
7/16" PLYWOOD SHEATHING 2x6 CONT. 3/4" PLYWOOD SUBFLOOR 1 1/2"x 24" LSL RIM BOARD
3/4" PLYWOOD SUBFLOOR
SEE ARCH ON ONE SIDE OF WALL. SEE ARCH. SEE ARCH. SEE ARCH.
SEE ARCH.
PROVIDE 2x BLOCKING @ ALL
FREE EDGES & NAIL W/ 10d
HORIZ. PLYWOOD JOINT NAILS [SEE SCHEDULE FOR
(NOTE 1) NAIL SPACING AT PANEL
EDGES] & 12"o.c. @ BEARING TRUSS
24" LOW-JOIST BRIDGING PER
1 1/2"x24" LSL RIM BOARD NOTE 2 INTERMEDIATE SUPPORTS. FLOOR TRUSSES TRUSS MFR.
@ 19.2"c/c 2x10 JOIST
BLOCKING @ FREE EDGES OF
7/16" WALL SHEATHING 1 1/2"x 24" LSL RIM BOARD
PLYWOOD SHALL BE ORIENTED JOIST HANGER
THUS:
1 1/2"x 24" LSL RIM BOARD
HORIZ. PLYWOOD JOINT
(2) - 2x6 CONT. BRIDGING PER BRIDGING PER
(NOTE 1) BRIDGING PER
STUD TRUSS MFR. BRIDGING PER TRUSS MFR.
TRUSS MFR.
7/16" SHEATHING CONT. 2x6 STRONGBACK (2) - 2x6 CONT. TRUSS MFR.
24" LOW-JOIST FLOOR 24" LOW-JOIST FLOOR 24" FLOOR TRUSS
(2) - 2x6 CONT @ TRUSS VERTS. TRUSSES @ 19.2"c/c TRUSSES @ 19.2"c/c
NOTE:
24" LOW-JOIST BLOCKING 2x6 @ 16"c/c 24" LOW-JOIST FLOOR
SEE DETAIL _____ FOR (2) - 2x6 CONT.
LEVEL TRUSSES @ 2x4 BLOCKING @ 24"c/c 2x6 @ 16"c/c TRUSSES @ 19.2"c/c
(2) - 2x6 CONT. CONDITION @ PLYWOOD SHEAR
19.2"c/c
WALL ALONG CORRIDOR WALL. 2x6 @ 16"c/c
2x6 @ 16"c/c
NOTES:
1) PLYWOOD JOINT LOCATIONS NOTED ARE BASED ON PREFAB WALL ASSEMBLIES.
2) USE (2) END BEARING VERTICALS.

1 FLOOR FRAMING DETAIL 2 FLOOR FRAMING DETAIL 3 FLOOR FRAMING DETAIL 4 FLOOR FRAMING DETAIL 5 FLOOR FRAMING DETAIL
S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0"

3/4"∅ THREADED ROD


2x6 @ 16"c/c ALIGN
2x6 @ 16"c/c TIES @ 16"o.c. w/PLATE
STUDS BELOW 2x6 @ 16"c/c ALIGN w/
PLYWOOD SHEATHING ON ONE ALIGN STUDS BELOW 3/16"x2"x2" T&B T.O. PARAPET
3/4"∅ THREADED ROD TRUSS/STUDS BELOW NAIL PLYWOOD TO BLOCKING w/ EL SEE PLAN
SIDE OF SHEAR WALLS SEE PLAN
TIES @ 16"o.c. w/PLATE PLYWOOD SHEATHING ON 8d NAILS @ 6"o.c. (TYP)
NAIL FLOOR SHEATHING 3/4"∅ THREADED ROD
3/16"x2"x2" T&B SHEATHING ON SHEAR WALLS ONE SIDE OF SHEAR WALLS 1" UNDERLAYMENT +
TIES @ 16"o.c. w/PLATE 2x4 @ 16"c/c NAIL BLOCKING TOGETHER
TO DBL TOP PLATE
2x BOT PLATE 1 1/4" UNDERLAYMENT @ 1" UNDERLAYMENT + 3/16"x2"x2" T&B 1/4" ACOUSTICAL MAT 1" UNDERLAYMENT + w/ 10d NAILS @ 4"o.c.
w/ 8d NAIL @ 6"o.c.
CORRIDOR 1/4" ACOUSTICAL MAT 1/4" ACOUSTICAL MAT
1" UNDERLAYMENT (TYP @ SHEARWALLS) 3/4" PLYWOOD SUBFLOOR 2x4 CONT.
2x6 CONT. 7/16" PLYWOOD
+ 1/4" ACOUSTICAL MAT 3/4" PLYWOOD SUBFLOOR 2x6 BOT PLATE 3/4" PLYWOOD SUBFLOOR 3/4" PLYWOOD SUBFLOOR
SEE ARCH SEE ARCH
5/8" PLYWOOD (3)-2x BLOCKING BTWN
SHEATHING TRUSSES (TYP)

CONTINUOUS 2x6 STUD @


END OF TRUSS TO BE PART
OF TRUSS. MANUFACTURER
(2) - 2x6 CONT.
SHALL DESIGN FOR ±40 PSF

VARIES
WIND LOAD (NOTE 1)
2x4 BLOCKING SEE ARCH DWGS FOR SIDING,
BTWN TRUSSES VENEER OR DECORATIVE WALL
NOT SHOWN ON THIS DETAIL
24" LOW-JOIST FLOOR 24" LOW-JOIST FLOOR TRUSS BEARING
24" LOW JOIST FLOOR TRUSSES @ 19.2"c/c 2x6 STUDS PER
TRUSSES @ 19.2"c/c TRUSSES @ 19.2"c/c 2x4 @ 16"c/c 24" LOW JOIST (SEE PLAN)
(NOTCH @ TRUSS HANGER) 2x6 @ 16"c/c 24" LOW-JOIST FLOOR STRUCTURAL
FLOOR. TRUSSES ROOF TRUSS @ 16"o.c.
TRUSSES @ 19.2"c/c WALL SCHEDULE 2x4 BLOCKING @ 24"c/c @ 19.2"c/c HORIZ. PLYWOOD JOINT LOCATION
2x6 @ 16"o.c. TRUSS HANGER (NOTE 1) ON SHEET _____ SIMPSON 'H10A' HURRICANE TIE @ EA TRUSS
(2) - 2x4 CONT. (ASSUMING PREFAB WALL
TOP ⅊ NAILING (2) - 16d NAILS @ 8"o.c. ASSEMBLIES)
NOTES: 2x4 @ 16"c/c
1) TRUSS HANGER SHALL BE SIMPSON 'THA426' HANGERS w/ "TOP FLANGE" INSTALLATION 2x6 STUDS @ 16"o.c. SEE OTHER DETAILS FOR
(FIELD BEND VERT. STRAPS OVER DOUBLE TOP PLATE). PROVIDE (4) 0.162"∅x3 1/2" PLACED DIRECTLY UNDER HEADERS/LINTELS, BLOCKING
NAILS INTO TOP OF TOP PLATE, (4) 0.162"∅x3 1/2" NAILS INTO SIDE OF TOP PLATE, ROOF TRUSS DIRECTLY BELOW WHERE
AND (6) 0.148"∅x3" NAILS STRAIGHT INTO SIDE OF TRUSS. NOTES: APPLICABLE
1. LIMIT PARAPET WALL DEFLECTION TO L/300.
2. WHERE NO WALL EXISTS UNDER PARAPET SEE DETAIL 16/ S3.01 .
_____

6 INTERIOR SHEARWALL SECTION @ FLOOR 7 INTERIOR SHEARWALL SECTION 8 INTERIOR SHEARWALL SECT. @ FLR. 9 TYP. NON-BEARING WALLS @ FLOOR TRUSSES 10 ROOF FRAMING DETAIL
S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0"

DBL TOP PLATE


T.O. PARAPET
7/16" PLYWOOD SHEATHING T.O. PARAPET SEE ARCH.
EL SEE ARCH
(2)-2x6 BLOCKING BTWN 2x6 @ 16"o.c.
STUDS (TYP).

NAIL PLYWOOD TO 2x4


2x6 BLOCKING
BLOCKING w/ 8d NAILS (2) 2x6 CONT
@ 4"o.c. 1'-0" 1'-0"
5/8" PLYWOOD SHEATHING 2x8 CONT LEDGER 5/8" PLYWOOD SHEATHING 8d NAILS @
5/8" PLYWOOD NAIL PLYWOOD TO BLOCKING 5/8" PLYWOOD SHEATHING - NAIL LSTA15 STRAPS w/ PLYWOOD ROOF
4"o.c. EXCEPT @
SHEATHING w/ 8d NAILS @ 6"o.c. TO DBL TOP ⅊ w/ 8d NAIL @ 6"o.c. (12)-12d NAILS (1/2 EA SHEATHING
LSTA15 STRAPS
BLOCKING)

NAIL NAILER TO BLOCKING 2x4 x 0'-8" H6 TIE H6 TIE 2x4 x 0'-8"


ROOF TRUSS @
w/ 10d x 3" NAIL @ 6"o.c. BLOCKING BLOCKING

2'-0"
VARIES
24"o.c. BTWN 2x4
SIMPSON 'H8' TIE @ EA STUD
SHEAR WALLS 2x4 BLOCKING
@ TOP OR BOT OF BLOCKING 2x8 - SEE PLAN
ROOF BLOCKING
TRUSS BRG TRUSS BRG ROOF TRUSS
TRUSSES
2x6 STUDS @ 16"o.c., SEE PLAN JOIST HANGER SEE PLAN ROOF TRUSS B.O. TRUSS
BRIDGING PER
CONTINUOUS TO TOP OF PARAPET BRIDGING PER SEE PLAN
TRUSS MFR. (2) - 2x6 CONT.
TRUSS MFR.
PLYWOOD EA SIDE w/ 8d No. Description Date
ROOF TRUSSES SIMPSON H10A HURRICANE (4) #14 x 3" WOOD NAILS @ 4"o.c. ALL SIDES
3'-0" MIN. LST16 TWIST STRAP @
TIE @ EA. STUD ROOF TRUSSES @ BRIDGING PER TRUSS MFR SCREWS TOP & BOTTOM
@ 24"c/c EA TRUSS w/ (6)-10d LSTA15 STRAPS w/
24"c/c

NOTES
SIMPSON H10A
HURRICANE TIE @ 2x6 @ 16"c/c ALIGN w/
NAILS INTO TRUSS
&(6)-10d NAILS INTO
STUD
2x6 STUDS @ 16"o.c., 2x4 CONT. (12)-10d NAILS (1/2 EA
BLOCKING) SAGE
1. WHERE NO WALL EXISTS UNDER EA. TRUSS ROOF TRUSSES
15/ S3.01
PARAPET SEE DETAIL 16/S4.01
HORIZ PLYWD JT w/
SOLID BLOCKING BACK-UP (2) - 2x6 CONT.
2x6 @ 16"c/c ALIGN w/
FLOOR TRUSSES
PLYWOOD SHEATHING ON ONE SIDE
PER STRUCTURAL WALL SCHEDULE
DEVELOPMENT
ON SHEET _____ .
GROUP
11 ROOF FRAMING DETAIL 12 ROOF FRAMING DETAIL 13 ROOF FRAMING DETAIL 14 INTERIOR SHEARWALL @ ROOF 15 ROOF PARAPET DETAIL
S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0" S3.01 3/4" = 1'-0"

T.O. PARAPET
SEE ARCH.
DBL TOP ⅊ BENSON
2x6 @ 16"o.c. @
MULTIFAMILY
EA ROOF TRUSS

19-030_NBE_Benson Multifamily_R19_detached.rvt
±180#/TRUSS 2x6 BLOCKING

PLYWOOD ROOF SHEATHING


FRAMING DETAILS

±900#/TRUSS

HOLLAND BASHAM ARCHITECTS


2'-0"

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
±600#/TRUSS (402)551-0800
B.O. TRUSS
SEE PLAN

ROOF TRUSS
TRUSS DESIGNER SHALL
DESIGN TRUSS FOR
PROJECT:17073
ADDITIONAL LOADS NOTED (4)-12d NAILS NEAR SIDE &
(4)-12d NAILS FAR SIDE DATE: 8/__/19

8/26/2019 7:12:06 PM
(8 TOTAL BOT & 8 TOTAL
TOP)

16 ROOF PARAPET DETAIL C COPYRIGHT

S3.01
2014

S3.01 3/4" = 1'-0" SHEET:


AGENCY APPROVAL
GENERAL MECHANICAL NOTES ENLARGED PLAN GENERAL NOTES
MECHANICAL SYMBOLS 1. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS. MAINTAIN ALL CODE 1. DO NOT ROUTE DUCTWORK ABOVE ELECTRICAL PANELS. MAINTAIN ALL CODE REQUIRED
REQUIRED CLEARANCES. CLEARANCES.
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
TYPICAL PIPING 2. ALL NOTES MAY NOT BE APPLICALBE TO EACH FLOOR PLAN. 2. ENLARGED UNIT PLANS ARE "TYPICAL". SOME UNITS MAY HAVE A MIRRORED OR ROTATED
PIPE TEE / PIPE ELBOW UNION CONFIGURATION. COORDINAE WITH OVERALL FLOOR PLANS. ADJUST MECHANICAL LAYOUT
ELBOW DN / ELBOW UP STRAINER
ISOLATION VALVE (BALL OR BUTTERFLY) CHECK VALVE (ARROW INDICATES FLOW) 3. PLANS ARE SCHEMATIC IN NATURE. COORDINATE EXACT EQUIPMENT LOCATIONS, DUCTWORK AS REQUIRED.
BALANCING VALVE AUTOMATIC CONTROL VALVE TWO-WAY/THREE-WAY ROUTING, AND PIPE WITH STRUCTURE AND ALL OTHER TRADES.
GATE VALVE PRESSURE REGULATING VALVE (PRV) 3. ALL NOTES MAY NOT BE APPLICABLE TO EVERY UNIT.
GLOBE VALVE PRESSURE GAUGE 4. COORDINATE ALL ROOF, FLOOR, AND WALL PENETRATIONS, ETC. WITH GENERAL
P.T.T PRESSURE/TEMPERATURE TEST PORT THERMOMETER
CONTRACTOR. SEAL ALL BUILDING ENVELOPE PENETRATIONS WATER TIGHT. 4. PLANS ARE SCHEMATIC IN NATURE. COORDINATE EXACT ROUTING AND EQUIPMENT
PLUMBING LOCATIONS WITH ALL OTHER TRADES. PROVIDE OFFSETS AS REQUIRED.
DOMESTIC COLD WATER (CW) W SITE WATER PIPING
5. SPACE ABOVE CEILINGS IS LIMITED. CONTRACTOR SHALL COORDINATE ALL DUCTWORK AND
DOMESTIC HOT WATER (HW) (NUMBER INDICATES TEMPERATURE) GAS COCK
DOMESTIC HOT WATER CIRCULATION (HWC) (NUMBER INDICATES TEMPERATURE) 2" D-1 FLOOR DRAIN - SIZE TYPE
PIPING ROUTING WITH ARCHITECTURAL DRAWINGS AND ALL OTHER TRADES. OFFSET, 5. COORDINATE ALL ROOF, FLOOR, AND WALL PENETRATIONS, ETC. WITH GENERAL
SANITARY WASTE (BELOW GRADE) 2" RD-1 ROOF DRAIN - SIZE TYPE EXTEND, TRANSITION, AND/OR CHANGE DUCTWORK SIZE AS REQUIRED TO AVOID CONFLICTS. CONTRACTOR. SEAL PENETRATIONS WATER TIGHT.
SANITARY WASTE (ABOVE GRADE) 2" OD-1 OVERFLOW DRAIN - SIZE TYPE
VENT PIPING HB HOSE BIBB 6. ROUTE ALL PIPING ABOVE CEILINGS, IN PLUMBING CHASES, OR IN WALLS. ANY PIPING SHOWN 6. SPACE ABOVE CEILINGS IS LIMITED. CONTRACTORS SHALL COORDINATE ALL DUCTWORK AND
ST STORM PIPING (BELOW GRADE) WH WALL HYDRANT (NON-FREEZE) PIPE ROUTING WITH ARCHITECTURAL DRAWINGS AND ALL OTHER TRADES. PROVIDE ALL
IN PLANS OUTSIDE OF WALL IS FOR CLAIRITY. UNLESS INDICATED OTHER WISE, ROUTE ALL
ST STORM PIPING (ABOVE GRADE) VTR VENT THROUGH ROOF
OF OVERFLOW STORM PIPING (BELOW GRADE) I.E. INVERT ELEVATION PIPING AS HIGH AS POSSIBLE. MOST PIPING AND DUCTWORK SHALL BE ROUTED WITHIN ADDITIONAL OFFSETS AND TRANSITIONS AS REQUIED TO AVOID CONFLICTS AND COMPLETE
OF OVERFLOW STORM PIPING (ABOVE GRADE) F.L. FLOW LINE JOIST/TRUSS SPACE, BUT CONTRACTOR SHALL VERIFY CEILING HEIGHTS WITH INSTALLATION.
GW GREASE WASTE (BELOW GRADE) WC WATER CLOSET (SEE SPECIFICATIONS FOR TYPE) ARCHITECTURAL PLANS.
GW GREASE WASTE (ABOVE GRADE) UR URINAL (SEE SPECIFICATIONS FOR TYPE) 7. CONTRACTORS ARE RESPONSIBLE FOR INSTALLING FIRESTOPPING AT ALL PENETRATIONS OF
GV GREASE VENT PIPING L LAVATORY (SEE SPECIFICATIONS FOR TYPE)
7. ROUTE DUCTWORK BETWEEN JOISTS AND TRUESSES. PER 2009 I.E.C.C. , DUCTWORK FIRE RESISTANT CONSTRUCTION CREATED BY THAT CONTRACTOR. ALL DUCTWORK
AW ACID WASTE PIPING (BELOW GRADE) S SINK (SEE SPECIFICATIONS FOR TYPE)
AW ACID WASTE PIPING (ABOVE GRADE) EWC ELECTRIC WATER COOLER (SEE SPECIFICATIONS FOR TYPE) INSULATION SHALL NOT BE REQURIED SINCE ALL DUCTWORK IS ROUTED WITHIN THE BUILDING PENETRATIONS OF RATED ASSEMBLIES SHALL BE PROVIDED WITH PROPER FIRE, SMOKE OR
AV ACID VENT PIPING MS MOP SINK (SEE SPECIFICATIONS FOR TYPE) ENVELOPE. COMBINATION DAMPERS. DAMPERS SHALL BE INSTALLED TO ALLOW ACCESS FOR TESTING
A COMPRESSED AIR PIPING DI DUCTILE IRON AND MAINTENANCE. REFER TO ARCHITECTURAL DRAWNGS TO CONFIRM WALL
G NATURAL GAS PIPING CI CAST IRON 8. FLOOR/CEILING ASSEMBLY IS FIRE RATED. PROVIDE RADIATION DAMPER WITH EACH CONSTRUCTION.
SAN SITE SANITARY PIPING PVC POLY VINYL CHLORIDE
ST SITE STORM PIPING
DIFFUSER, REGISTER, AND/OR GRILLE LOCATED IN GYP. BOARD CEILING AT BOTTOM OF
TRUSSES. THE GYP. BOARD IS APART OF THE RATING. COORDINATE FIRE RATINGS WITH 8. ALL DUCTWORK AND PIPING SHALL BE CONCEALED, ROUTED WITH IN JOIST OR TRUSS SPACE,
HVAC ABOVE LOWERED CEILINGS, OR IN SOFFITS. COORDINATE DUCTWORK AND PIPING ROUTED
ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
6x6 R-1 NECKSIZE (IN), TAG S SENSOR
100 SIDEWALL SUPPLY REGISTER OR GRILLE AIRFLOW (CFM) T THERMOSTAT
WITH IN TRUSSES WITH STRUCTURE AND ALL OTHER TRADES. ROUTE DUCTWORK OR PIPING
6x6 R-1 NECKSIZE (IN), TAG H HUMIDISTAT 9. FIRE CAULK ALL DUCTWORK AND PIPING PENETRATIONS THROUGH FIRE RATED WALLS AND BETWEEN TRUSSES. DUCTWORK INSULATION SHALL NOT BE REQUIRED PER 2009 I.E.C.C.
SIDEWALL RETURN OR EXHAUST REGISTER OR GRILLE
100 AIRFLOW (CFM) M
MOTORIZED CONTROL DAMPER WITH ACTUATOR ASSEMBLIES. CAULK AROUND ALL DUCWORK AND PIPING PENETRATIONS THROUGH FULL
6 Ø D-1
SUPPLY AIR REGISTER
NECKSIZE (IN), TAG B.D.D. BACKDRAFT DAMPER HEIGHT SOUND WALLS. REFER TO ARCHITECTURAL DRAWINGS FOR WALL CONSTRUCITON. 9. COORDINATE ALL DUCTWORK, DIFFUSER, AND REGISTER LOCATIONS WITH ARCHITECTURAL
100 AIRFLOW (CFM) V.D. VOLUME DAMPER DRAWINGS AND SECTIONS. ALL REGISTERS AND GRILLES SHALL BE CENTERED WITH
FD FIRE DAMPER WITH SLEEVE AND ACCESS DOOR
SUPPLY AIR , OUTSIDE AIR OR MIXED AIR DUCT END OR RISER UP/RISER DN SD SMOKE DAMPER WITH SLEEVE AND ACCESS DOOR 10. LOCATE FIRE DAMPERS, FIRE/SMOKE DAMPERS, VOLUME DAMPERS, ETC. IN ACCESSIBLE ARCHITECTURAL ELEMENTS.
FSD FIRE/SMOKE DAMPER WITH SLEEVE AND ACCESS DOOR LOCATIONS. PROVIDE CEILING ACCESS PANELS AS REQUIRED IN GYP. BOARD CEILINGS TO
RETURN AIR, EXHAUST AIR OR RELIEF AIR DUCT END OR RISER UP/RISER DN
S.A. SUPPLY AIR SERVE DAMPERS. LOCATE DAMPERS ABOVE ACCESSIBLE LAY-IN TILE CEILINGS WHERE 10. PROVIDE RADIATION DAMPERS WITH EACH DIFFUSER, REGISTER, AND GRILLE LOCATED IN
12/8 RECTANGULAR DUCTWORK (WIDTH/DEPTH)(IN) (FIRST NUMBER IS SIDE SHOWN)
R.A. RETURN AIR POSSIBLE. COORDINATE ALL LOCATIONS WITH REFLECTED CEILING PLANS, GENERAL GYP. BOARD CEILINGS AT BOTTOM OF JOISTS OR TRUSSES.
E.A. EXHAUST AIR
RLF.A. RELIEF AIR
CONTRACTOR, AND ARCHITECT. MAINTAIN ACCESSIBILITY TO ALL DAMPERS.
12"Ø ROUND DUCTWORK (DIAMETER)(IN) (SPIRAL DUCT IN EXPOSED AREAS)
O.A. OUTSIDE AIR 11. MAINTAIN MANUFACTURER'S REQURIED CLEARANCES AROUND ALL EQUIPMENT TO ALLOW
M.A. MIXED AIR 11. ALL DIFFUSERS, REGISTERS, AND GRILLES SHALL BE CENTERED WITH ARCHITETURAL FOR PROPER PERFORMANCE, SAFETY, AND MAINTENANCE ACCESS.
TURNING VANES
ELEMENTS WHEN POSSIBLE.
FIRE PROTECTION
F FIRE SPRINKLER PIPING FH FIRE HYDRANT 12. CONTRACTOR TO PROVIDE ALL LOW VOLTAGE AND LINE VOLTAGE CONTROL WIRING GENERAL PLUMBING NOTES
P.I.V.
SP STANDPIPE PIPING POST INDICATOR VALVE REQUIRRED FOR COMPLETE OPERATION OF ALL MECHANICAL EQUIPMENT.
SPRINKLER BRANCH AND HEADS ALARM CHECK VALVE
FHC FIRE HOSE CABINET O,S & Y VALVE
1. DO NOT ROUTE PIPING ABOVE ELECTRICAL PANELS. MAINTAIN ALL CODE REQUIRED
FVC FIRE VALVE CABINET FS FLOW SWITCH 13. MAINTIAN MANUFACTURER'S REQUIRED CLEARANCES AROUND ALL EQUIPMENT TO ALLOW CLEARANCES.
FOR PROPER PERFORMANCE, SAFETY, AND MAINTENANCE ACCESS.
2. SPACE ABOVE CEILINGS IS LIMITED. COORDINATE PIPE ROUTING WITH ALL OTHER TRADES.
PROVIDE ALL ADDITIONAL OFFSETS AND TRANSITIONS AS REQUIRED TO COMPLETE
AIR BALANCE NOTES INSTALLATION.
1. CORRIDORS AND COMMON AREAS:
3. PLANS ARE SCHEMATIC IN NATURE. COORDINATE EXACT ROUTING AND EQUIPMENT
1.1 CORRIDOR AND COMMON AREA VRF SYSTEM: LOCATIONS WITH ALL OTHER TRADES. PROVIDE ALL ADDITIONAL OFFSETS AS REQUIRED TO
COMPLETE INSTALLATION.
CONTRACTOR SHALL START UP AND COMFORT BALANCING OF ALL VRF
EQUIPMENT. VERIFY AIRFLOW AND HEATING / COOLING OPERATION FOR 4. INSTALL ALL ISOLATION VALVES AND BALANCING VALVES IN ACCESSIBLE LOCATIONS.
EACH UNIT. VERIFY PROPER OPERATION OF VRF TEMPERATURE
CONTROLS. EXACT BALANCING OF SUPPLY AIRFLOW NOT REQUIRED. 5. ALL PIPING SHOWN FOR CLARITY. ROUTE WASTE, VENT, WATER, AND GAS PIPING CONCEALED
BALANCE OUTSIDE AIR TO EACH UNIT TO CFM INDICATED ON THE IN CHASES, IN WALLS, OR ABOVE CEILINGS AS REQUIRED.
VENTILATION SCHEDULE ON SHEET M6.02.
6. DO NOT ROUTE WATER PIPING IN EXTERIOR WALLS UNLESS OTHERWISE NOTED. PIPING
1.2 EXHAUST FANS ROUTED IN EXTERIOR WALLS SHALL BE LOCATED ON THE INTERIOR SIDE OF INSULATION.

VERIFY AIRFLOW AT EACH CEILING MOUNTED EXHAUST FAN. 7. NOT ALL CLEANOUTS ARE SHOWN. PROVIDE CLEANOUTS PER OMAHA PLUMBING CODE.
EXTEND CLEANOUTS TO WALLS WHERE APPLICABLE. COORDINATE CLEANOUT LOCATIONS
2. APARTMENTS: (RESIDENTIAL FAN COIL - HEAT PUMP SPLIT SYSTEMS): WITH GENERAL CONTRACTOR.

2.1 FAN COILS: 8. COORDINATE ALL BELOW GRADE PIPING WITH STRUCTURAL FOOTINGS. SLEEVE PIPING AS
REQUIRED. SEE STRUCTURAL DRAWINGS. COORDINATE WITH GENERAL CONTRACTOR.
CONTRACTOR SHALL STARTUP EACH FAN COIL AND HEAT PUMP UNIT,
PROVIDE CLEAN FILTERS, AND PROVIDE COMFORT BALANCING OF 9. PER OMAHA PLUMBING CODE, CAT IRON WASTE PIPING AND VENT PIPING TO BE USED IN
HVAC EQUIPMENT. VERIFY AIRFLOW AT EACH TERMINAL REGISTER GARAGE SPACE ONLY. PVC WASTE AND VENT PIPING TO BE USED ON FLOORS FIRST
AND GRILLE. EXACT BALANCING OF SUPPLY AND RETURN THROUGH FOURTH ONLY.
AIRFLOW NOT REQUIRED.
10. SEE WASTE AND VENT RISER DIAGRAMS ON SHEET M4.1 FOR WASTE AND VENT PIPE SIZES.
2.2 EXHAUST FANS:
11. SEE PLUMBING FIXTURE SCHEDULE SHEET M7.01-M7.02 FOR PLUMBING FIXTURE CONNECTION
VERIFY AIRFLOW AT EACH CEILING MOUNTED EXHAUST FAN. REQUIREMENTS.

2.3 DRYER VENTS: 12. ALL PENETRATIONS OF FIRE RESISTANT CONSTRUCTION SHALL BE SEALED WITH A LISTED
FIRESTOPPING ASSEMBLY BY THE CONTRACTOR RESPONSIBLE FOR THE PENETRATION.
VERIFY AIRFLOW AT EACH DRYER DISCHARGE VENT CAP.

FIRE SPRINKLER GENERAL NOTES


1. THE PROJECT SHALL BE PROVIDED WITH A MANUAL WET-TYPE, CLASS 1 STANDPIPE SYSTEM IN
GENERAL MECHANICAL ROOF NOTES EACH STAIRWAY.
1. SEAL ALL ROOF PENETRATIONS WATER TIGHT. COORDINATE ALL PENETRATIONS WITH 2. PROVIDE FIRE SERVICE ENTRANCE WITH DOUBLE CHECK BACKFLOW PREVENTER, ISOLATION
GENERAL CONTRACTOR AND ROOFING CONTRACTOR. VALVES, CHECK VALVES, FLOW SWITCH, ETC. AS REQURIED BY NFPA 13R AND AUTHORITY
HAVING JURISDICTION.
2. ALL OUTDOOR AIR INTAKES SHALL BE LOCATED AT LEAST 10 FEET FROM EXHAUST OUTLETS,
COMBUSTION AIR STACKS, FIREPLACE FLUES AND PLUMBING VENTS. 3. ROUTING AND SIZING OF FIRE SPRINKLER PIPING SHALL BE BY FIRE SPRINKLER CONTRACTOR.
3. MAINTAIN ALL CODE AND MANUFACTURER'S RECOMMENDED CLEARANCES AROUND ALL ROOF 4. CONTRACTOR SHALL VERIFY AVAILABLE PRESSURE AND FLOW.
EQUIPMENT.
5. THE PROJECT SHALL BE PROTECTED THROUGHOUT BY A WET PIPE FIRE SPRINKLER SYSTEM.
4. PLANS ARE SCHEMATIC IN NATURE. COORDINATE EXACT ROUTING AND EQUIPMENT ALL AREAS OF THE BUILDING, GARAGE, AND RESIDENTIAL APARTMENT AREAS, SHALL BE
LOCATIONS WITH ALL OTHER TRADES. PROVIDE ALL ADDITIONAL OFFSETS AS REQURIED TO PROTECTED BY A SYSTEM IN ACCORDANCE WITH NFPA 13R.
COMPLETE INSTALLATION.
6. NO DRY PIPE SPRINKLER SYSTEM REQUIRED IN THIS BUILDING. AREAS SUBJECT TO FREEZING
5. ALL PENETRATIONS OF FIRE RESISTANT CONSTRUCTION SHALL BE SEALED WITH A LISTED SHAL BE PROTECTED BY DRY SIDEWALL HEADS WITH WATER SUPPLIED FROM HEATED AREAS.
FIRESTOPPING ASSEMBLY BY THE CONTRACTOR RESPONSIBLE FOR THE PENETRATION.
7. AREA BETWEEN FLOORS AND ABOVE THE UPPER FLOOR CEILING WILL REQUIRE FIRE
6. SEE WASTE AND VENT RISER DIAGRAMS ON SHEET M4.4 FOR WASTE AND VENT PIPE SIZES. SPRINKLER PROTECTION PER NFPA 13R.

8. ALL EXTERIOR PATIOS AND BALCONIES SHALL BE PROTECTED BY THE FIRE SPRINKLER PER
NFPA 13R.
TEMPERATURE CONTROL NOTES
9. SPRINKLER HEADS AS FOLLOWS:
1. CORRIDORS AND COMMON AREAS: A. IN APARTMENT: SEMI-RECESSED OR SIDEWALL HEADS.
B. LOBBY AND COMMON CORRIDOR: DROP DOWN CONCEALED HEADS. COVERPLATE COLOR
1.1 CORRIDOR FAN COIL UNITS: TO MATCH CEILING. COLOR SELECTED BY ARCHITECT.
C. AREA SUBJECT TO FREEZING: DRY SIDEWALL HEADS.
PROVIDE STAND ALONE PROGRAMMABLE HEAT PUMP THERMOSTAT
AT EACH CORRIDOR UNIT AS SHOWN ON FLOOR PLANS. THERMOSTAT 10. SEE SPECIFICATION SECTION 211000 - WATER BASED FIRE SUPRESSION SYSTEMS FOR
SHALL BE MOUNTED AT ADA HEIGHT, 48" A.F.F. MECHANICAL
CONTRACTOR SHALL PROVIDE ALL 24 VOLT CONTROL WIRING AND
ADDITIONAL INFORMATION.
No. Description Date
ACCESSORIES REQUIRED FOR FULLY OPERATING SYSTEM.

2. APARTMENT UNITS: (RESIDENTIAL FAN COIL - HEAT PUMP SPLIT SYSTEMS):

2.1 APARTMENT FAN COIL UNITS: SAGE


PROVIDE STAND ALONE PROGRAMMABLE HEAT PUMP THERMOSTAT IN
EACH APARTMENT AS SHOWN ON THE ENLARGED PLANS.
THERMOSTAT SHALL BE MOUNTED AT ADA HEIGHT, 48" A.F.F.
DEVELOPMENT
MECHANICAL CONTRACTOR SHALL PROVIDE ALL 24 VOLT CONTROL
WIRING AND ACCESSORIES REQUIRED FOR FULLY OPERATING
SYSTEM.
GROUP

GARAGE VENTILATION SYSTEM AND CONTROL NOTES


1. MECHANICAL CONTRACTOR SHALL PROVIDE COMPLETE HONEYWELL OR
EQUIVALENT VENTILATION CONTROL SYSTEM WITH CARBON MONOXIDE
BENSON
AND NITROGEN DIOXIDE DETECTORS SHOWN ON PLANS. SUBMIT
ALTERNATE MANUFACTURER'S FOR ENGINEER'S APPROVAL PRIOR TO
BIDDING.
MULTIFAMILY
2. SYSTEM SHALL CONSIST OF THE FOLLOWING:

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


(1) HONEYWELL CONTROL PANEL.
(6) CARBON MONOXIDE (CO) ELECTROCHEMICAL
TRANSMITTER/ANALYZERS.
(6) NITROGEN DIOXIDE (NO2) ELECTROCHEMICAL
TRANSMITTER/ANALYZERS.
-SEE PLANS FOR SENSOR LOCATIONS. MECHANICAL GENERAL
3. AT EACH SENSOR LOCATION SHOWN ON THE PLANS, INSTALL CO
TRANSMITTER/ANALYZER AT 48" A.F.F. AND NO2 TRANSMITTER/ANALYZER
INFORMATION
36" BELOW THE STRUCTURE ABOVE.

4. THE SYSTEM SHALL ACTIVATE THE EXHAUST FANS GEF-XA (PARKING


LEVEL) AND OPEN THE MOTORIZED DAMPER ON THE INTAKE LOUVERS AS
REQUIRED TO MAINTAIN THE FOLLOWING CONCENTRATIONS:
4.1. AVERAGE CO CONCENTRATION OF 25 PPM DURING ANY 8 HOUR
PERIOD.
4.2. NO2 CONCENTRATION OF 5 PPM AT ANY TIME.
4.3. THE SYSTEM SHOULD ONLY OPERATE THE FAN SERVING THE
PARKING LEVEL WHEN HIGH CO OR NO2 CONCENTRATION IS DETECTED.

5. ALL LOW VOLTAGE CONTROL WIRING FOR GAS DETECTION SYSTEM SHALL
BE PROVIDED BY THE MECHANICAL CONTRACTOR. COORDINATE
INSTALLATION OF THE CONTROL WIRING WITH THE ELECTRICAL
CONTRACTOR.
119 SOUTH 49TH AVENUE
6. ELECTRICAL CONTRACTOR SHALL PROVIDE THE MOTOR STARTERS AND OMAHA, NEBRASKA 68132
POWER FOR THE FANS AND LOUVERS AND ANY LINE VOLTAGE WIRING
REQUIRED. COORDINATE WITH ELECTRICAL CONTRACTOR TO PROVIDE A (402)551-0800
HAND/OFF/AUTO SWITCH TO ALLOW MANUAL ACTIVATION OF FANS.
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:19 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M0.0
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
GENERAL NOTES
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

N CO

GUH-2

GUH-1

CO
N

CO N
N

12x8 DUCT UP
CO

12"x6" R-3
300

No. Description Date

SAGE
DEVELOPMENT
GROUP
N CO

BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


EF-2 GUH-3

LOWER LEVEL PLAN -


HVAC

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 LOWER LEVEL - HVAC MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M1.01
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:20 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M1.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

4 4 4 4 4 4 KEYNOTES
M3.01 M3.01 M3.01 M3.01 M3.01 M3.01

M112 M105 EXHAUST FAN IN CEILING. COORDINATE EXACT LOCATION WITH STRUCTURE,
LIGHTS, AND ARCHITECTURAL PLANS. ROUTE 6" DIA. EXHAUST DUCT FROM
M110 M110 M110 M110 M110 M110 M110 FAN TO EXTERIOR WALL CAP. SEE PLANS FOR ROUTING. SEE EXHAUST FAN
MOUNTING DETIAL X/MX.XX.
M108 6" DIA OUTSIDE AIR DUCTWORK UP TO PLENUM SPACE. ROUTE 6" DIA
M111 M111 M111 M111 M111 M111
OUTSIDE AIR DUCTWORK FROM FAN COIL TO EXTERIOR WALL CAP. PROVIDE
3 FIRE DAMPER AT ALL GYP. BOARD PENETRATIONS. BALANCE TO CFM
M3.01 INDICATED ON VENTILATION SCHEDULE ON SHEET MX.XX.
6"Ø 6"Ø 6"Ø 6"Ø 6"Ø M109 PROVIDE RECESSED METAL DRYER BOX (DRYERBOX BY IN-O-VATE
M111 TECHNOLOGIES OR EQUIVALENT) FOR CONNECTION OF DRYER TO RIGID
UNIT J UNIT J UNIT J UNIT J UNIT J UNIT J EXHAUST DUCTWORK IN WALL. FOR WALLS LESS THEN 6", USE OVAL SKINNY
6"Ø 6"Ø DRYER DUCTWORK. COORDINATE EXACT LOCATION OF DUCTWORK WITH
139 138 136 134 132 130 STRUCTURE AND GENERAL CONTRACTOR FOR BEST CONNECTION TO DRYER
6"Ø 6"Ø 6"Ø 6"Ø 6"Ø 6"Ø
4"Ø 6"Ø SPECIFIED. CONTINUE RIGID EXHAUST AIR DUCTWORK UP TO PLENUM SPACE
TO DISCHARGE VENT IN EXTERIOR WALL CAP. COORDINATE WITH GENERAL
CONTRACTOR THE PLACEMENT OF A PERMANENT LABLE INDICATING DUCT
M108 M108 M108 M108 M108 M108 LENGTH AND NUMBER OF BENDS IN DUCWORK RUN. SEE DRYER
CONNECTION DETAIL X/MX.XX.
M105
M110 UNIT 2-C M110 PROVIDE 6" METAL WALL CAP WITH BACKDRAFT DAMPER FOR BATH EXHAUST.
COORDINATE WALL PENITRATION WITH ARCHITECT AND GENERAL
140 CONTRACTOR. COORDINATE WALL CAP COLOR WITH ARCHITECT.
6"Ø M111 PROVIDE 6" METAL WALL CAP FOR OUTSIDE AIR INTAKE. COORDINATE WALL
M112 4"Ø EF-1 M108 M105 M105 M108 M108 M105 M105 M108 M108 M105 M105 M108 PENITRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
FC-1.5 FC-1.5 FC-1.5 FC-1.5 FC-1.5 FC-1.5
EF-1 EF-1 EF-1 EF-1 EF-1 EF-1 WALL CAP COLOR WITH ARCHITECT. PROVIDE FIRE DAMPER AT WALL
PENETRATION BETWEEN APARTMENTS (TYP).
M112 PROVIDE 4" DIA METAL WALL CAP FOR DRYER EXHUAST. COORDINATE WALL
PENETRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
DF-1 FD WALL CAP COLOR WITH ARHCITECT.
DF-1 M109
M109 TU-08C
EF-1
M105 M109 M109
M111 M108 FC-1.5 DF-1 FC-1.5 FC-1.5 DF-1 T TU-0.8C

M108 M108

6"Ø M109 EF-1


EF-1 EF-1
M108 M108 M105 M110
DF-1
M105 EF-1 FC-2.0 UNIT 1-C M105 M105
M109
6"Ø 4"Ø 137 4"Ø 6"Ø
FC-1.5 M112
6"Ø
M110 4"Ø M108
M108
M108
DF-1
M112 6"Ø FC-1.5
M109 4"Ø M108 M108 4"Ø
M112 6"Ø M111
M110
M111 6"Ø 6"Ø
UNIT S-B UNIT S-B UNIT 1-A M108
UNIT 1-B TU-05C 5
135 133 131
141 M108 2 M3.02
4 M111

FD
M108 6"Ø M3.02 6"Ø 6"Ø
M3.02
6"Ø
6"Ø UNIT S-B M110
M111 M108 M108
M112 143
FC-1.5
M109 M112 M112 M110 M110 M112
6"Ø
6"Ø
M108
M108 DF-1 4"Ø
UNIT 1-B
M112 142 FC-1.5 EF-1 2 2 4
M108 M105 M3.02 M3.02 M3.02
TU-05C T

T
TU-12C
EF-1
M109 M108 M111
M105 6"Ø TU-18C
M108 T 6"Ø
4 DF-1 6"Ø
6"Ø
M3.02 TU-12C M111
4"Ø 6"Ø
TU-12C
T

M112
TU-12C GAME
ROOM
M108
RENTAL 014 M108
M110 TU-12C ROOM
TU-12C 6"Ø
015 T M111
6"Ø
M108 4
TU-12C 2 4
M3.02
M3.02 M3.02
WOMEN'S
RR
TU-05C
012

M110 M111 M110 M112 M111 M111


MEN'S RR
TU-05C
013 EF-6 M111
TU-12C EF-5
M112
TU-12C
T EF-4
12"x6" R-3
FSD 50
UNIT S-B UNIT 1-A 6"Ø UNIT 1-A
4"Ø
151 6"Ø 153 6"Ø 155 M108
6"Ø 6"Ø M108 6"Ø
4"Ø DF-1
HVAC M108
STORAGE 6"Ø
010 M108
011

T TU-05C
T FC-1.5 M108
TU-05C
M109 FC-1.5 M112
4"Ø
TU-05C
TU-05C TU-08C M105 M109 M110
TU-08C T
M108
EF-1
M105 No. Description Date
EF-1
M105 6"Ø
6"Ø

DF-1 FC-1.5 M109 EF-1


FD
T TU-08C SAGE
TU-18C M109
DEVELOPMENT
T
TU-05C FC-1.5 FC-1.5 TU-08C FC-1.5
TU-18C M109 M109
OFFICE FD
008
TU-05C
FC-2.5
DF-1 DF-1 DF-1 GROUP
T

EF-1 EF-1 EF-1


M108 M108 M108
M105 M105 M105
MAIL
PACKAGE 6"Ø
019
ROOM
FITNESS 6"Ø
022 CENTER
TU-18C 007 BENSON
FD

4"Ø 4"Ø 4"Ø

BUSINESS
T TU-18C
6"Ø
M108
6"Ø
UNIT S-A
150
UNIT J
152
M108
6"Ø
M108
6"Ø
UNIT J
154
MULTIFAMILY
6"Ø 6"Ø 6"Ø
FD

CENTER

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


018 6"Ø

TU-12C
6"Ø
FD

M111
M112 M112
M111 M111
M112
FIRST FLOOR PLAN -
M110 M110 M110
HVAC

6 1 4
M3.02 M3.01 4
M3.02
M3.01

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 FIRST FLOOR PLAN - HVAC MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M1.02
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:26 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M1.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
GENERAL NOTES
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

4 4 4 4 4 4
KEYNOTES
M3.01 M3.01 M3.01 M3.01 M3.01 M3.01
M105 EXHAUST FAN IN CEILING. COORDINATE EXACT LOCATION WITH STRUCTURE,
LIGHTS, AND ARCHITECTURAL PLANS. ROUTE 6" DIA. EXHAUST DUCT FROM
FAN TO EXTERIOR WALL CAP. SEE PLANS FOR ROUTING. SEE EXHAUST FAN
M110 M110 M110 M110 M110 M110 M110 MOUNTING DETIAL X/MX.XX.
M108 6" DIA OUTSIDE AIR DUCTWORK UP TO PLENUM SPACE. ROUTE 6" DIA
M111 M111 M111 M111 M111 M111 OUTSIDE AIR DUCTWORK FROM FAN COIL TO EXTERIOR WALL CAP. PROVIDE
3 FIRE DAMPER AT ALL GYP. BOARD PENETRATIONS. BALANCE TO CFM
M3.01 INDICATED ON VENTILATION SCHEDULE ON SHEET MX.XX.
6"Ø 6"Ø 6"Ø 6"Ø 6"Ø M109 PROVIDE RECESSED METAL DRYER BOX (DRYERBOX BY IN-O-VATE
TECHNOLOGIES OR EQUIVALENT) FOR CONNECTION OF DRYER TO RIGID
M111
EXHAUST DUCTWORK IN WALL. FOR WALLS LESS THEN 6", USE OVAL SKINNY
UNIT J UNIT J UNIT J UNIT J UNIT J UNIT J DRYER DUCTWORK. COORDINATE EXACT LOCATION OF DUCTWORK WITH
6"Ø 239 238 236 6"Ø 234 232 230 STRUCTURE AND GENERAL CONTRACTOR FOR BEST CONNECTION TO DRYER
6"Ø 6"Ø 6"Ø 6"Ø 6"Ø 6"Ø SPECIFIED. CONTINUE RIGID EXHAUST AIR DUCTWORK UP TO PLENUM SPACE
6"Ø TO DISCHARGE VENT IN EXTERIOR WALL CAP. COORDINATE WITH GENERAL
?
? CONTRACTOR THE PLACEMENT OF A PERMANENT LABLE INDICATING DUCT
M108 M108 M108 M108 M108 M108 LENGTH AND NUMBER OF BENDS IN DUCWORK RUN. SEE DRYER
CONNECTION DETAIL X/MX.XX.
M105
M110 M110 PROVIDE 6" METAL WALL CAP WITH BACKDRAFT DAMPER FOR BATH EXHAUST.
UNIT 2-C
COORDINATE WALL PENITRATION WITH ARCHITECT AND GENERAL
240 CONTRACTOR. COORDINATE WALL CAP COLOR WITH ARCHITECT.
6"Ø M111 PROVIDE 6" METAL WALL CAP FOR OUTSIDE AIR INTAKE. COORDINATE WALL
M112 4"Ø EF-1 M108 M105 M105 M108 M108 M105 M105 M108 M108 M105 M105 M108 PENITRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
FC-1.5 FC-1.5 FC-1.5 FC-1.5 FC-1.5 FC-1.5 WALL CAP COLOR WITH ARCHITECT. PROVIDE FIRE DAMPER AT WALL
EF-1 EF-1 EF-1 EF-1 EF-1 EF-1 PENETRATION BETWEEN APARTMENTS (TYP).
M112 PROVIDE 4" DIA METAL WALL CAP FOR DRYER EXHUAST. COORDINATE WALL
PENETRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
DF-1 FD WALL CAP COLOR WITH ARHCITECT.
T TU-08C
M109 TU-08C
EF-1
M105 M109 M109
M111 FC-1.5 DF-1 FC-1.5 FC-1.5 DF-1

M108 M108
M108 EF-1
6"Ø EF-1 EF-1
M108 M108 M105 M110
M105 6"Ø
EF-1 FC-2.0 UNIT 1-C M105 M105
M109 M109
237 M108 4"Ø 6"Ø
FC-1.5 M112
6"Ø T
M110 4"Ø TU-05C DF-1 M108
M108 M105
DF-1
M112 4"Ø EF-1 M111 FC-1.5
M109 4"Ø M108 M108 4"Ø
6"Ø M111
6"Ø
M112
6"Ø 6"Ø
M110
M112 UNIT S-B UNIT S-B UNIT 1-A M108
UNIT 1-B 5
TU-05C 2 235 233 231
M110 M3.02
4 241 M3.02

FD
M3.02 M108 6"Ø 6"Ø
6"Ø
6"Ø UNIT S-B
M108 M108
M112 M111 243

M108 4"Ø M112 M110 M110 M112


6"Ø FC-1.5
6"Ø M111
6"Ø
UNIT 1-B DF-1 M108
M108 FC-1.5
M112 242 2 3
M108 M105 2
EF-1 M3.02 M3.02
M109 M3.02
M110 2
6"Ø M3.02
EF-1
M109 4"Ø
M105 M112
M105
UNIT S-B
4 EF-1
DF-1 245
M3.02
4"Ø 6"Ø
M109
DF-1 M111
FC-1.5
M112
M105 EF-1 M108 6"Ø
M108
FC-1.5 M111
6"Ø DF-1
M110 4"Ø
M110 6"Ø 2
M108
M108 M3.02
M109
M112
UNIT S-B 2 3 3
M3.02 M3.02 M3.02
247
TU-05C
UNIT 1-B
M110
244 M111 M111
4 M112 M110 M111 M110 M112
M108 FD 4"Ø
M3.02
6"Ø
6"Ø 6"Ø M111
M108 M105
M111 M112
M112 FC-1.5
EF-1
M109
6"Ø
DF-1 12"x6" R-3
M108 FSD UNIT S-B UNIT 1-A6"Ø UNIT 1-A
50 4"Ø 6"Ø M108
UNIT 1-B FC-1.5 251 6"Ø 253 255
6"Ø 6"Ø M108 6"Ø
M112 246 TU-05C T
M108 4"Ø DF-1

T
M108
M108

EF-1 FC-1.5 M108


M109
M105 M109 FC-1.5 M112
4"Ø
4
DF-1 TU-08C
M3.02 M105 M109 M110
4"Ø 6"Ø
FC-2.0
TU-08C T M108
EF-1
M105 No. Description Date
EF-1
DF-1 M105 6"Ø
M112
FD

6"Ø
4"Ø M109 EF-1 DF-1 FC-1.5 M109 EF-1
FD
T TU-08C SAGE
M110
M110 M112 M105 FC-1.5 M109 M109 FC-1.5 FC-1.5
M109
TU-08C M109 FC-1.5
DEVELOPMENT
M105
EF-1
DF-1
EF-1 EF-1
DF-1 DF-1
EF-1 EF-1
DF-1 GROUP
M108 M108 M108 M108
M105 M105 M105 M105

UNIT 2-A

1
248
6"Ø 6"Ø
6"Ø 4"Ø 4"Ø 4"Ø 4"Ø
BENSON
M3.01
M108
UNIT S-A
249
M108
6"Ø
M108
6"Ø
UNIT S-A
250
UNIT J
252
M108
6"Ø
M108
6"Ø
UNIT J
254
MULTIFAMILY
6"Ø 6"Ø 6"Ø 6"Ø

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


M110
M111

M111
M111 M111
M112 M112
M111 M111
M112
SECOND FLOOR PLAN -
M112
M110 M110 M110 M110
HVAC
1 1 4 4
M3.02 M3.02 M3.01 M3.01

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 SECOND FLOOR PLAN - HVAC MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M1.03
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:31 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M1.03
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

2 4 4 4 4
M3.01 M3.01 M3.01 M3.01 M3.01 KEYNOTES

M105 EXHAUST FAN IN CEILING. COORDINATE EXACT LOCATION WITH STRUCTURE,


LIGHTS, AND ARCHITECTURAL PLANS. ROUTE 6" DIA. EXHAUST DUCT FROM
FAN TO EXTERIOR WALL CAP. SEE PLANS FOR ROUTING. SEE EXHAUST FAN
M110 M110 M112 M110 M110 M110 M110 MOUNTING DETIAL X/MX.XX.
M108 6" DIA OUTSIDE AIR DUCTWORK UP TO PLENUM SPACE. ROUTE 6" DIA
M110 M111 M111 M111 M111 OUTSIDE AIR DUCTWORK FROM FAN COIL TO EXTERIOR WALL CAP. PROVIDE
FIRE DAMPER AT ALL GYP. BOARD PENETRATIONS. BALANCE TO CFM
INDICATED ON VENTILATION SCHEDULE ON SHEET MX.XX.
M109 PROVIDE RECESSED METAL DRYER BOX (DRYERBOX BY IN-O-VATE
6"Ø 6"Ø 6"Ø TECHNOLOGIES OR EQUIVALENT) FOR CONNECTION OF DRYER TO RIGID
M111 EXHAUST DUCTWORK IN WALL. FOR WALLS LESS THEN 6", USE OVAL SKINNY
4"Ø UNIT J UNIT J UNIT J UNIT J DRYER DUCTWORK. COORDINATE EXACT LOCATION OF DUCTWORK WITH
6"Ø 6"Ø 6"Ø 336 6"Ø 334 332 330 STRUCTURE AND GENERAL CONTRACTOR FOR BEST CONNECTION TO DRYER
UNIT 2-B 6"Ø 6"Ø 6"Ø 6"Ø SPECIFIED. CONTINUE RIGID EXHAUST AIR DUCTWORK UP TO PLENUM SPACE
338 DF-1 6"Ø TO DISCHARGE VENT IN EXTERIOR WALL CAP. COORDINATE WITH GENERAL
6"Ø CONTRACTOR THE PLACEMENT OF A PERMANENT LABLE INDICATING DUCT
M109 LENGTH AND NUMBER OF BENDS IN DUCWORK RUN. SEE DRYER
M108 M108 M108 M108 M108
CONNECTION DETAIL X/MX.XX.
M105 M110 PROVIDE 6" METAL WALL CAP WITH BACKDRAFT DAMPER FOR BATH EXHAUST.
M110 UNIT 2-C COORDINATE WALL PENITRATION WITH ARCHITECT AND GENERAL
340 CONTRACTOR. COORDINATE WALL CAP COLOR WITH ARCHITECT.
3 6"Ø M111 PROVIDE 6" METAL WALL CAP FOR OUTSIDE AIR INTAKE. COORDINATE WALL
M105 PENITRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
M3.01 M112 4"Ø EF-1 M108 M105 M105 M108 M108 M105 M105 M108
FC-1.5 FC-1.5 FC-1.5 FC-1.5 WALL CAP COLOR WITH ARCHITECT. PROVIDE FIRE DAMPER AT WALL
M105 EF-1 EF-1 EF-1 EF-1 EF-1 PENETRATION BETWEEN APARTMENTS (TYP).
M112 PROVIDE 4" DIA METAL WALL CAP FOR DRYER EXHUAST. COORDINATE WALL
EF-1 PENETRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
FD WALL CAP COLOR WITH ARHCITECT.
DF-1 M108 T
FC-2.0 TU-08C
M109 TU-08C
EF-1
M105 M109 M109
M111 FC-1.5 DF-1 FC-1.5 FC-1.5 DF-1

M108 M108
M108 EF-1
6"Ø EF-1 EF-1
T M108 M108 M105 M110
M105 6"Ø
EF-1 FC-2.0 UNIT 1-C M105 M105
M109 M109
337 M108 4"Ø 6"Ø
FC-1.5 M112
6"Ø T
M110 4"Ø TU-05C DF-1 M108
M108 M105
DF-1
M112 4"Ø EF-1 M111 FC-1.5
M109 4"Ø M108 M108 4"Ø
6"Ø M111
6"Ø
M112
6"Ø 6"Ø
M110 5
M112 UNIT S-B UNIT S-B UNIT 1-A M108
TU-05C M3.02
UNIT 1-B 335 333 331
M110
4 341

FD
M3.02 M108 6"Ø 6"Ø
2
6"Ø M3.02
6"Ø UNIT S-B
M108 M108
M112 M111 343
FC-1.5 4"Ø
M112 M110 M110 M112
6"Ø
M108 6"Ø M111
DF-1 6"Ø
UNIT 1-B FC-1.5 M108
M112 342
M108 M105 2
M109 2 3
EF-1 M3.02
M3.02 M3.02
M110
2
6"Ø M3.02
EF-1
M109 4"Ø
M105 M112
M105
4 UNIT S-B
EF-1
M3.02 DF-1 345
4"Ø 6"Ø
M109
DF-1 M111
FC-1.5
M105 EF-1 M108 6"Ø
M112 M108
DF-1 FC-1.5 M111
M110 6"Ø
M110 4"Ø
6"Ø 2
M108
M109 M3.02
M112 M108
3
2 3
UNIT S-B M3.02
M3.02 M3.02
347
TU-05C
UNIT 1-B
M110
344 M111 M111
4 M112 M110 M111 M110 M112
FD
M3.02 M108 4"Ø
6"Ø M111
6"Ø 6"Ø
M108 M105 M112
M112 M111 FC-1.5
EF-1
M109
6"Ø
DF-1 12"x6" R-3
M108 FSD 50 UNIT S-B UNIT 1-A6"Ø UNIT 1-A
6"Ø 4"Ø 6"Ø M108
UNIT 1-B 351 353 355
6"Ø 6"Ø M108 6"Ø
M112 346 M108 TU-05C T
4"Ø DF-1
M108
FC-1.5 M108

EF-1 FC-1.5 M108


M109
M105 M109 FC-1.5 M112
DF-1 4"Ø
4 TU-08C
M3.02 M105 M109 M110
4"Ø 6"Ø FC-2.0 TU-08C T M108
EF-1
M105 No. Description Date
EF-1
M105 6"Ø
FD

M112

M110
6"Ø
4"Ø M109 EF-1 DF-1 FC-1.5 M109 EF-1
FD
T TU-08C SAGE
M110
M112 M105 FC-1.5 M109 M109 FC-1.5 FC-1.5
M109
TU-08C M109 FC-1.5
DEVELOPMENT
M105
EF-1
DF-1
EF-1 EF-1
DF-1 DF-1
EF-1 EF-1
DF-1 GROUP
M108 M108 M108 M108
M105 M105 M105 M105

UNIT 2-A

1
348
6"Ø 6"Ø
6"Ø 4"Ø 4"Ø 4"Ø 4"Ø
BENSON
M3.01
M108
UNIT S-A
349
M108
6"Ø
M108
6"Ø
UNIT S-A
350
UNIT J
352
M108
6"Ø
M108
6"Ø
UNIT J
354
MULTIFAMILY
6"Ø 6"Ø 6"Ø 6"Ø

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


M110
M111

M111
M111 M111
M112 M112
M111 M111
M112
THIRD FLOOR PLAN -
M112
M110 M110 M110 M110
HVAC

1 4 4
1
M3.02 M3.01 M3.01
M3.02

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 THIRD FLOOR PLAN - HVAC MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M1.04
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:36 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M1.04
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
GENERAL NOTES
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

4 4 4
KEYNOTES
4 4
M3.01 M3.01 M3.01 M3.01 M3.01
M105 EXHAUST FAN IN CEILING. COORDINATE EXACT LOCATION WITH STRUCTURE,
LIGHTS, AND ARCHITECTURAL PLANS. ROUTE 6" DIA. EXHAUST DUCT FROM
FAN TO EXTERIOR WALL CAP. SEE PLANS FOR ROUTING. SEE EXHAUST FAN
M110 M110 M112 M110 M110 M110 M110 MOUNTING DETIAL X/MX.XX.
M108 6" DIA OUTSIDE AIR DUCTWORK UP TO PLENUM SPACE. ROUTE 6" DIA
M111 M111 M111 M111 OUTSIDE AIR DUCTWORK FROM FAN COIL TO EXTERIOR WALL CAP. PROVIDE
M110 FIRE DAMPER AT ALL GYP. BOARD PENETRATIONS. BALANCE TO CFM
INDICATED ON VENTILATION SCHEDULE ON SHEET MX.XX.
M109 PROVIDE RECESSED METAL DRYER BOX (DRYERBOX BY IN-O-VATE
6"Ø 6"Ø 6"Ø TECHNOLOGIES OR EQUIVALENT) FOR CONNECTION OF DRYER TO RIGID
M111 EXHAUST DUCTWORK IN WALL. FOR WALLS LESS THEN 6", USE OVAL SKINNY
4"Ø UNIT J UNIT J UNIT J UNIT J DRYER DUCTWORK. COORDINATE EXACT LOCATION OF DUCTWORK WITH
6"Ø 6"Ø 6"Ø 436 6"Ø 434 432 430 STRUCTURE AND GENERAL CONTRACTOR FOR BEST CONNECTION TO DRYER
UNIT 2-B 6"Ø 6"Ø 6"Ø 6"Ø SPECIFIED. CONTINUE RIGID EXHAUST AIR DUCTWORK UP TO PLENUM SPACE
438 DF-1 6"Ø TO DISCHARGE VENT IN EXTERIOR WALL CAP. COORDINATE WITH GENERAL
6"Ø CONTRACTOR THE PLACEMENT OF A PERMANENT LABLE INDICATING DUCT
M109 LENGTH AND NUMBER OF BENDS IN DUCWORK RUN. SEE DRYER
M108 M108 M108 M108 M108 CONNECTION DETAIL X/MX.XX.
3
M3.01 M105 M110 PROVIDE 6" METAL WALL CAP WITH BACKDRAFT DAMPER FOR BATH EXHAUST.
M110 UNIT 2-C COORDINATE WALL PENITRATION WITH ARCHITECT AND GENERAL
440 CONTRACTOR. COORDINATE WALL CAP COLOR WITH ARCHITECT.
M111 PROVIDE 6" METAL WALL CAP FOR OUTSIDE AIR INTAKE. COORDINATE WALL
6"Ø
M105 PENITRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
M112 4"Ø EF-1 M108 M105 M105 M108 M108 M105 M105 M108
WALL CAP COLOR WITH ARCHITECT. PROVIDE FIRE DAMPER AT WALL
FC-1.5 FC-1.5 FC-1.5 FC-1.5
M105 EF-1 EF-1 EF-1 EF-1 EF-1 PENETRATION BETWEEN APARTMENTS (TYP).
M112 PROVIDE 4" DIA METAL WALL CAP FOR DRYER EXHUAST. COORDINATE WALL
EF-1 PENETRATION WITH ARCHITECT AND GENERAL CONTRACTOR. COORDINATE
WALL CAP COLOR WITH ARHCITECT.
DF-1 FD
M108 FC-2.0 T
TU-08C
M109 TU-08C
EF-1
M105 M109 M109
M111 FC-1.5 DF-1 FC-1.5 FC-1.5 DF-1

M108 M108
M108 EF-1
6"Ø EF-1 EF-1
M108 M108 M105 M110
M105 6"Ø
EF-1 FC-2.0 M109 UNIT 1-C M105 M105
M109
437 M108 4"Ø 6"Ø
FC-1.5 M112
6"Ø T
M110 4"Ø TU-05C M108
M108 M105
DF-1 DF-1
M112 4"Ø EF-1 M111 FC-1.5
M109 4"Ø M108 M108 4"Ø
6"Ø M111
6"Ø
M112
6"Ø 6"Ø
M110
M112 5 UNIT S-B UNIT S-B UNIT 1-A M108
UNIT 1-B TU-05C M3.02 435 433 431
M110
4 441

FD
M3.02 M108 2 6"Ø 6"Ø
6"Ø M3.02
6"Ø UNIT S-B
M111 M108 M108
M111 443
M108 4"Ø
FC-1.5 M112 M110 M110 M112
6"Ø
M108 6"Ø M111
6"Ø
UNIT 1-B FC-1.5 M108
M112 442 2 2 3
M108 DF-1 M105 M3.02 M3.02 M3.02
EF-1
M110 2
M3.02
6"Ø
EF-1
M109 4"Ø
M105 M112
M105
UNIT S-B
EF-1
4 DF-1 445
M3.02
4"Ø 6"Ø
M109
DF-1 M111
FC-1.5
M105 EF-1
M112 M108 6"Ø
M108
DF-1 FC-1.5 M111
M110 6"Ø
M110 4"Ø
6"Ø 2
M109 M108 M3.02
M112 M108

3 3
UNIT S-B 2
M3.02 M3.02
M3.02
447
TU-05C
UNIT 1-B
M110
444 M111 M111
4 M112 M110 M111 M110 M112
FD
M3.02 M108 4"Ø
6"Ø
6"Ø 6"Ø M111
M108 M105 M112
M112 M111 FC-1.5
EF-1
M109
6"Ø
DF-1 12"x6" R-3
M108 FSD UNIT S-B UNIT 1-A6"Ø UNIT 1-A
FC-1.5 50 6"Ø 4"Ø 6"Ø M108
UNIT 1-B AC-1 451 453 455
6"Ø 6"Ø M108 6"Ø
M112 446 TU-05C T
M108 4"Ø DF-1
M108
M108

EF-1 FC-1.5 M108


M109
M105 M109 FC-1.5 M112
4"Ø
4 DF-1 TU-08C
M105 M109 M110
M3.02
4"Ø 6"Ø
FC-2.0
TU-08C T
M108
EF-1
M105 No. Description Date
EF-1
M105 6"Ø
FD

M112

M110
6"Ø
4"Ø M109 EF-1 DF-1 FC-1.5 M109 EF-1

M109
FD
T TU-08C SAGE
M110
M112 M105 FC-1.5 M109 M109 FC-1.5 FC-1.5 TU-08C M109 FC-1.5
DEVELOPMENT
M105
EF-1
DF-1
EF-1 EF-1
DF-1 DF-1
EF-1 EF-1
DF-1 GROUP
M108 M108 M108 M108
M105 M105 M105 M105

UNIT 2-A

1
448
6"Ø
6"Ø
6"Ø 4"Ø 4"Ø 4"Ø 4"Ø
BENSON
M3.01
M108
UNIT S-A
449
M108
6"Ø
M108
6"Ø
UNIT S-A
450
UNIT J
452
M108
6"Ø
M108
6"Ø
UNIT J
454
MULTIFAMILY
6"Ø 6"Ø 6"Ø 6"Ø

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


M110
M111

M111
M111 M111
M112 M112
M111 M111
M112
FOURTH FLOOR PLAN -
M112
M110 M110 M110 M110
HVAC

1 1 4
M3.02 4
M3.02 M3.01 M3.01

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 FOURTH FLOOR PLAN - HVAC MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M1.05
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:41 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M1.05
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

10'-0" MINIMUM CLEARANCE TO ROOF EDGE FOR


ALL EQUIPMENT REQUIRING MAINTENANCE (TYP).

JUNIOR JUNIOR JUNIOR JUNIOR JUNIOR JUNIOR

HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5

HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5
2 BED C

HP-2.0 HP-2.0
RH-1 4" RD-1
VRF-HP-1 4" OFD-1
HP-2.0 HP-2.0 3 TON VRF HP
1 BED B
HP-1.5 HP-1.5

HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5


HP-1.5 HP-1.5
4" RD-1
HP-1.5
4" OFD-1 HP-1.5 HP-1.5 HP-1.5 HP-1.5
HP-1.5 HP-1.5
STUDIO
HP-1.5 HP-1.5
JUNIOR C
STUDIO

HP-1.5 HP-1.5

1 BED B

VRF-HP-2
4 TON VRF HP

STUDIO
HP-1.5 HP-1.5
1 BED B

HP-1.5 HP-1.5
HP-1.5

HP-1.5

HP-1.5

HP-1.5 HP-1.5
STUDIO
1 BED B
HP-1.5
HP-1.5

HP-1.5
HP-1.5

VRF-HP-3
3 TON VRF HP HP-1.5
STUDIO

HP-1.5

HP-1.5

EF-3
RH-1

VRF-HP-4 AC-1
3 TON VRF HP
4" RD-1
4" OFD-1 HP-1.5 HP-1.5 HP-1.5 HP-1.5

1 BED B HP-1.5 HP-1.5


STUDIO HP-1.5 HP-1.5
HP-1.5 HP-1.5

HP-1.5 HP-1.5 1 BED B 1 BED B


HP-1.5 VRF-HP-5
3 TON VRF HP
HP-1.5 HP-1.5
No. Description Date

2 BED B
HP-2.0 HP-2.0
RH-1 4" RD-1
4" OFD-1
VRF-HP-6
SAGE
3 TON VRF HP

HP-2.0 DEVELOPMENT
RH-2 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5
GROUP
VRF-HP-7
4 TON VRF HP HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5

STUDIO
STUDIO JUNIOR
JUNIOR
BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


ROOF PLAN -
MECHANICAL

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 ROOF PLAN - MECHANICAL MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M1.06
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:43 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M1.06
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
GENERAL NOTES
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

4" W UP
TO DRAIN 4" W UP 4" W UP 4" W UP 4" W UP
TO DRAIN TO DRAIN TO DRAIN TO DRAIN

4" V UP
4" W

4" W UP
4" V TO DRAIN

4" W UP
TO DRAIN

TYPE I OIL
INTERCEPTOR

4" W UP
TO DRAIN

4" W UP
TO DRAIN

4" W

4" W
60" I.E.E

D.G.C.O.

4" W UP
TO DRAIN

SP-1

4" W UP
TO DRAIN

4" W UP
TO DRAIN

No. Description Date


W

SAGE
DEVELOPMENT
4" W UP
TO DRAIN
4" W
4" W UP
TO DRAIN
4" W UP
TO DRAIN GROUP

F UP TO PIV
BENSON
6" F

4" W UP
MULTIFAMILY
TO DRAIN

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


W

4" CW
W UP TO DRAIN
UNGROUND PLUMBING

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 UNDERGROUND - PLUMBING MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M2.00
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:44 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M2.00
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

N CO
GUH-2

2" G

4" V GD-1 GD-1 GD-1 GD-1 GD-1


GUH-1

CO
N
2" G
GAS METER

GD-1

GD-1
TYPE I OIL
INTERCEPTOR

GD-1

CO N
GD-1

2" G
GD-1

GD-1

2" W
N
CO

SP-1 MS-1

GD-1

GD-1

No. Description Date

SAGE
DEVELOPMENT
GROUP
GD-1 GD-1 GD-1

N CO

F UP TO PIV
AND DN TO
BENSON
MAIN
MULTIFAMILY
4" D-2

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


GUH-3

LOWER LEVEL PLAN -


2" AD-1 PLUMBING

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

2 LOWER LEVEL - PLUMBING MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M2.01
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:46 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M2.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

5 5 5 5 5 5
KEYNOTES
M3.03 M3.03 M3.03 M3.03 M3.03 M3.03

UNIT J
136
UNIT J UNIT J UNIT J UNIT J UNIT J
139 138 134 132 130

UNIT 2-C
140

4
M3.03

EWH-1 EWH-1 EWH-1 EWH-1 EWH-1 EWH-1

EWH-1 EWH-1 EWH-1 WH-1

UNIT 1-C
EWH-1
EWH-1 137

EWH-1

4" D-2
UNIT 1-B UNIT S-B UNIT S-B UNIT 1-A
141 5 135 133 131
M3.04
4
M3.04

UNIT S-B
143
WH-1

1
UNIT 1-B EWH-1 4
1 M3.04
142 M3.04 M3.04

4
M3.04
4" D-2 4" D-2 4" D-2

GAME
ROOM
014
IWH-1

WH-1
S-2 RENTAL 6
M3.04 1
ROOM WOMEN'S 4 4
M3.04
015 RR M3.04 M3.04
012

WH-1
MEN'S RR
013

EWH-2

UNIT 1-A
153
UNIT 1-A
155
STORAGE HVAC
011 010 EWH-1 EWH-1

No. Description Date

EWH-1 SAGE
OFFICE
EWH-1 EWH-1 EWH-1
DEVELOPMENT
2" D-1
008
GROUP
EWC-1

MAIL
019 FITNESS
CENTER
BENSON
PACKAGE
ROOM 007
022

UNIT S-A
150
MULTIFAMILY
BUSINESS UNIT J UNIT J
CENTER 152 154

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


018
FDC-1

FIRST FLOOR PLAN -


AREA WELL WH-1 PLUMBING

1 5 5
M3.04 M3.03 M3.03

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 FIRST FLOOR PLAN - PLUMBING MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M2.02
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:49 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M2.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
GENERAL NOTES
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

5 5 5 5 5 5 KEYNOTES
M3.03 M3.03 M3.03 M3.03 M3.03 M3.03

4
M3.03

UNIT J UNIT J UNIT J UNIT J UNIT J


238 236 234 232 230
UNIT J
239

UNIT 2-C
240

EWH-1 EWH-1 EWH-1 EWH-1 EWH-1 EWH-1

EWH-1 EWH-1 EWH-1

EWH-1 UNIT 1-C


EWH-1 237

EWH-1

UNIT S-B UNIT S-B UNIT 1-A


5
UNIT 1-B 1 235 233 231
M3.04
4 241 M3.04
M3.04

UNIT S-B
243

EWH-1
UNIT 1-B
242 EWH-1 1 1 3
M3.04 M3.04 M3.04
1
M3.04

4 UNIT S-B
M3.04 245

EWH-1
EWH-1

1
M3.04

1 3
UNIT S-B M3.04 M3.04
247
UNIT 1-B
244
4
M3.04 EWH-1

UNIT S-B
251 UNIT 1-A UNIT 1-A
UNIT 1-B 253 255
246

EWH-1
EWH-1 EWH-1

4
M3.04
No. Description Date
EWH-1
EWH-1 SAGE
EWH-1 EWH-1 EWH-1 EWH-1
DEVELOPMENT
GROUP

UNIT 2-A
248
BENSON
UNIT S-A
249
UNIT S-A UNIT J UNIT J
MULTIFAMILY
250 252 254

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


SECOND FLOOR PLAN -
PLUMBING
1 1 5 5
M3.04 M3.04 M3.03 M3.03

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 SECOND FLOOR PLAN - PLUMBING MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M2.03
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:51 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M2.03
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
GENERAL NOTES
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

5 5
1 5
M3.03 M3.03 5 M3.03 KEYNOTES
M3.03 M3.03

UNIT J UNIT J UNIT J


336 334 330
UNIT 2-B UNIT J
338 332

UNIT 2-C
340
4
M3.03

EWH-1 EWH-1 EWH-1

EWH-1 UNIT 1-C


EWH-1 337

EWH-1

UNIT 1-B UNIT S-B UNIT S-B UNIT 1-A


341 5 335 333 331
M3.04
4 1
M3.04 M3.04
UNIT S-B
343

EWH-1
UNIT 1-B
1
342 EWH-1 2 3
M3.04
M3.04 M3.04

1
M3.04

UNIT S-B
4
345
M3.04

EWH-1
EWH-1

1
M3.04

1 3 3
UNIT S-B M3.04 M3.04 M3.04
347
UNIT 1-B
344
4
M3.04 EWH-1

UNIT 1-B UNIT S-B UNIT 1-A


346 351 353
UNIT 1-A
355
EWH-1
EWH-1 EWH-1

4
M3.04
No. Description Date

EWH-1 SAGE
EWH-1 EWH-1 EWH-1 EWH-1
DEVELOPMENT
GROUP

UNIT 2-A

3
348
BENSON
M3.03
UNIT S-A
349
UNIT S-A
350
MULTIFAMILY
UNIT J UNIT J
352 354

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


THIRD FLOOR PLAN -
PLUMBING

1
1 M3.04 5 5
M3.04 M3.03 M3.03

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 THIRD FLOOR PLAN - PLUMBING MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M2.04
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:54 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M2.04
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

1 5 5 5 KEYNOTES
5
M3.03 M3.03 M3.03 M3.03 M3.03

UNIT J
434
UNIT 2-B UNIT J UNIT J UNIT J
438 436 432 430

4 EWH-1
M3.03
UNIT 2-C
440

EWH-1 EWH-1 EWH-1

UNIT 1-C
437
EWH-1
EWH-1

EWH-1

UNIT S-B
4 435
UNIT 1-B M3.04 UNIT S-B UNIT 1-A
441 433 431
4
M3.04 1
M3.04
UNIT S-B
443

EWH-1
UNIT 1-B 1 1 3
442 EWH-1 M3.04 M3.04 M3.04

1
M3.04

UNIT S-B
4 445
M3.04

EWH-1
EWH-1

1
M3.04

UNIT S-B
3 3
447 1
M3.04 M3.04
M3.04

UNIT 1-B
444
4
M3.04 EWH-1

UNIT 1-B UNIT S-B UNIT 1-A


446 451 455
T UNIT 1-A
453
EWH-1
EWH-1 EWH-1

4
M3.04 T
No. Description Date
EWH-1
EWH-1 T SAGE
EWH-1 EWH-1 EWH-1 EWH-1
DEVELOPMENT
GROUP
UNIT 2-A
448

3
BENSON
M3.03
UNIT S-A
449
UNIT S-A
450
UNIT J
452
MULTIFAMILY
UNIT J

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


454

FOURTH FLOOR PLAN -


PLUMBING
1 1 5
M3.04 5
M3.04 M3.03 M3.03

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 FOURTH FLOOR PLAN - PLUMBING MEI PROJECT NO: 19164

ARY N PROJECT: 17073


M2.05
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:56 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M2.05
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

M102 LIVING UNIT PLAN MAY APPEAR IN BUILDING FLOOR PLANS AS A MIRROR OR
ROTATED IMAGE OF THOSE SHOWN HERE. ADAPT THESE MECHANICAL
DESIGNS ACCORDINGLY.
M103 RETURN AIR THROUGH DOOR UNDERCUT. CUNDERCUT MUST BE MINIMUM 1"
ABOVE TOP OF FLOOR COVER.
M104 LOCATE WALL-MOUNTED RETURN AIR GRILLES AS HIGH AS POSSIBLE AND
CENTERED WITH ARCHITECTURAL ELEMENTS. LOCATE CEILING MOUNTED
R.A. GRILLES IN COORDINATION WITH STRUCTURE AND LIGHTING LAYOUT.
COORDINATE EXACT LOCATIONS WITH GENERAL CONTRACTOR AND
ARCHITECTURAL ELEMENTS.
M106 LOCATE ALL REGISTERS SYMMETRICALLY WITH ARCHITECTURAL ELEMENTS.
COORDINATE EXACT LOCATION WITH STRUCTURE AND OTHER TRADES AS
WELL. ALL REGISTERS LOCATED IN GYP. CEILING ON STRUCTURE SHALL BE
PROVIDED WITH RADIATION DAMPERS. SEE DIFFUSER/REGISTER
CONNECTION DETAILS X/MX.XX.
M107 ROUTE SUPPLY AIR DUCT MAIN BETWEEN BEAMS. COORDINATE EXACT
FC-2.0
ROUTING WITH STRUCTURE, GENERAL CONTRACTOR, AND OTHER TRADES.
12"x6" R-1 EF-1
50

M103
18"x12" G-1
800
T FC-2.0 M104

M103
14/10 M103
(TYP.) M107
12"x6" R-1 12"x6" R-1
8"Ø 6"Ø 100 100
12"x6" R-1
100 8"Ø
8"Ø
12"x6" R-1 12"x6" R-1
100 100
12"x6" R-1
100 8"Ø 8"Ø M107 (TYP.)

12"x6" R-1
8"Ø 50

14/10
8"Ø 8"Ø
8"Ø 12"x6" R-1 12"x6" R-1
12"x6" R-1 M103
100 (TYP.) M106

T
100 100
FC-2.0 8"Ø
(TYP.) M106 M103
8"Ø 12"x6" R-1 12"x6" R-1
SEE UNIT TYPE 2 BED A ON 100 M103 100
SHEETS M1.02-M1.06 FOR
OURSIDE AIR, BATH AND
DRYER EXHAUST DUCTWORK
SIZE, ROUTING, AND 8"Ø
KEYNOTES. SEE UNIT TYPE 2 BED B ON
12"x6" R-1 SHEETS M1.02-M1.06 FOR M103
100 M102 OURSIDE AIR, BATH AND
DRYER EXHAUST DUCTWORK M102
M103 SIZE, ROUTING, AND
KEYNOTES.
M103 6"Ø 6"Ø
12"x6" R-1
50
12"x6" R-1
12"x6" R-1
100 8"Ø
50 18"x12" G-1
12"x6" R-1
12"x6" R-1 800
100 EF-1
100
M104

EF-1
FC-2.0

1 ENLARGED PLAN - 2 BED "A" - HVAC 2 ENLARGED PLAN - 2 BED "B" - HVAC
M3.01 M3.01

0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

12"x6" R-1
100

12"x6" R-1
100

8"Ø
8"Ø

No. Description Date


12"x6" R-1
100
12"x6" R-1 M103
100
8"Ø
SAGE
12"x6" R-1
50
12"x6" R-1
100 12"x6" R-1
100
DEVELOPMENT
8"Ø
M103
12"x6" R-1 8"Ø
GROUP
100
6"x12" R-1 EF-1 8"Ø
100
FC-2.0 8"Ø
T

8"Ø

8"Ø

12"x6" R-1 M106 (TYP.)


(TYP.) M107
12/10
SEE UNIT TYPE JUNIOR ON
SHEETS M1.02-M1.06 FOR
OURSIDE AIR, BATH AND
BENSON
MULTIFAMILY
DRYER EXHAUST DUCTWORK
100 SIZE, ROUTING, AND
KEYNOTES.

M102 M107 (TYP.)

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


12/10

M103 M106 (TYP.)


12"x6" R-1
EF-1 18"x12" G-1 100
8"Ø 800 FC-1.5
ENLARGED PLANS - HVAC
T

M103
6"Ø 12"x6" R-1
50
12"x6" R-1
50
SEE UNIT TYPE 2 BED C ON M104 6"Ø
SHEETS M1.02-M1.06 FOR M103
OURSIDE AIR, BATH AND FC-2.0
12"x6" R-1 DRYER EXHAUST DUCTWORK
100 SIZE, ROUTING, AND 12"x6" R-1
KEYNOTES.
150
EF-1
M102 8"Ø M104
18"x10" G-1
FC-1.5 600

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


3 ENLARGED PLAN - 2 BED "C" - HVAC 4 ENLARGED PLAN - JUNIOR - HVAC morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:09:59 PM
M3.01 M3.01 unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M3.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

M102 LIVING UNIT PLAN MAY APPEAR IN BUILDING FLOOR PLANS AS A MIRROR OR
ROTATED IMAGE OF THOSE SHOWN HERE. ADAPT THESE MECHANICAL
FC-2.5 DESIGNS ACCORDINGLY.
M103 RETURN AIR THROUGH DOOR UNDERCUT. CUNDERCUT MUST BE MINIMUM 1"
FC-1.5
ABOVE TOP OF FLOOR COVER.
30"x12" G-1 M104 LOCATE WALL-MOUNTED RETURN AIR GRILLES AS HIGH AS POSSIBLE AND
CENTERED WITH ARCHITECTURAL ELEMENTS. LOCATE CEILING MOUNTED
EF-1 1000 R.A. GRILLES IN COORDINATION WITH STRUCTURE AND LIGHTING LAYOUT.
18"x10" G-1
EF-1 18"x10" G-1 COORDINATE EXACT LOCATIONS WITH GENERAL CONTRACTOR AND
600
600 ARCHITECTURAL ELEMENTS.
M103 M104
M104 12"x6" R-1 M106 LOCATE ALL REGISTERS SYMMETRICALLY WITH ARCHITECTURAL ELEMENTS.
12"x6" R-1 6"Ø COORDINATE EXACT LOCATION WITH STRUCTURE AND OTHER TRADES AS
200
50 8"Ø WELL. ALL REGISTERS LOCATED IN GYP. CEILING ON STRUCTURE SHALL BE
6"Ø PROVIDED WITH RADIATION DAMPERS. SEE DIFFUSER/REGISTER
M103 12"x6" R-1 CONNECTION DETAILS X/MX.XX.
150 M107 ROUTE SUPPLY AIR DUCT MAIN BETWEEN BEAMS. COORDINATE EXACT
8"Ø ROUTING WITH STRUCTURE, GENERAL CONTRACTOR, AND OTHER TRADES.
6"Ø
12"x6" R-1 12"x6" R-1
12"x6" R-1 50 8"Ø 200
100
FC-1.5 FC-1.5

14/12
SEE UNIT TYPE STUDIO B ON

12/10
SHEETS M1.02-M1.06 FOR
12"x6" R-1
OURSIDE AIR, BATH AND
100 T FC-2.5
SEE UNIT TYPE STUDIO A ON DRYER EXHAUST DUCTWORK
12"x6" R-1 8"Ø SIZE, ROUTING, AND
SHEETS M1.02-M1.06 FOR

12/10
150 OURSIDE AIR, BATH AND KEYNOTES.
(TYP.) M106 8"Ø DRYER EXHAUST DUCTWORK
SIZE, ROUTING, AND M102
KEYNOTES.
(TYP.) M107 (TYP.) M107 8"Ø
M102 (TYP.) M106
12"x6" R-1
8"Ø
200
8"Ø

12"x6" R-1
8"Ø 8"Ø
100
8"Ø
8"Ø 12"x6" R-1
200
12"x6" R-1
100
12"x6" R-1
8"Ø 8"Ø 200
12"x6" R-1 12"x6" R-1
12"x6" R-1 100 100
100

12"x6" R-1
100

1 ENLARGED PLAN - STUDIO "A" - HVAC 2 ENLARGED PLAN - STUDIO "B" - HVAC 6 ENLARGED PLAN - FITNESS - HVAC
M3.02 M3.02 M3.02

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

M102

12"x6" R-1
12"x6" R-1
150 SEE UNIT TYPE 1 BED B ON
12"x6" R-1 100
SHEETS M1.02-M1.06 FOR
100 OUTSIDE AIR, BATH AND DRYER
EXHAUS DUCTOWRK SIZE,
ROUTING AND KEYNOTES. No. Description Date
12"x6" R-1 18"x10" G-1
12"x6" R-1

8"Ø
8"Ø 100 100
12"x6" R-1
100
600
M104 12"x6" R-1
100
SEE UNIT TYPE 1 BED C ON
SHEETS M1.02-M1.06 FOR
SAGE
M104
12"x6" R-1
100
(TYP.) M107
M102 SEE UNIT TYPE 1 BED A ON
12"x6" R-1
8"Ø

8"Ø
FC-1.5
18"x10" G-1
OURSIDE AIR, BATH AND
DRYER EXHAUST DUCTWORK
SIZE, ROUTING, AND
DEVELOPMENT
SHEETS M1.02-M1.06 FOR M103 8"Ø
GROUP
8"Ø 600 KEYNOTES.
OURSIDE AIR, BATH AND 8"Ø 100
T FC-1.5 M103
DRYER EXHAUST DUCTWORK
12/10

FC-1.5 (TYP.) M106 8"Ø


SIZE, ROUTING, AND
KEYNOTES. M103 12"x6" R-1
.5 T 50
FC-1
8"Ø FC-1.5 12/10
M103

M104
6"Ø
M103
6"Ø 12"x6" R-1
150
BENSON
M107 (TYP.)
12/10 12"x6" R-1
50
(TYP.) M107
(TYP.) M106 MULTIFAMILY
18"x10" G-1
8"Ø 8"Ø 12"x6" R-1

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


600 M103
8"Ø 8"Ø 150
EF-1

12"x6" R-1
M103 12"x6" R-1
12"x6" R-1
50
100
12"x6" R-1
150
150 ENLARGED PLANS - HVAC
EF-1 (TYP.) M106

M103

3 ENLARGED PLAN - 1 BED "A" - HVAC 4 ENLARGED PLAN - 1 BED "B" - HVAC 5 ENLARGED PLAN - 1 BED "C" - HVAC
M3.02 M3.02 M3.02

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:03 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M3.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

M303 PROVIDE PLUMBING CONNECTION TO DISHWASHER. SEE DETIAL X/MX.XX.

L-1

BT-1 2" D-1


EWH-1

WC-1

WMB-1

BT-1

WC-1

S-1 L-1
OB-1 M303

WMB-1

L-1

L-1
BT-1

WC-1

WC-1 M303 BT-1


OB-1
S-1

EWH-1 2" D-1

3 ENLARGED PLAN - 2 BED "A" - PLUMBING 1 ENLARGED PLAN - 2 BED "B" - PLUMBING
M3.03 M3.03

0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

No. Description Date

SAGE
L-1
DEVELOPMENT
GROUP
WC-1
3/4" CW

3/4" HW
3/4" CW
SH-1
BENSON
OB-1
M303
S-1
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


WC-1 BT-1 1" HW

3/4" HW
3/4" CW 1" HW
1" CW
ENLARGED PLANS -
1 1/4" CW

WMB-1
PLUMBING
3/4" CW S-1

L-1
M303
EWH-1

3/4" CW
2" D-1 3/4" HW 3/4" CW
L-1

3/4" HW 1/2" HW OB-1

3/4"WC-1
CW
WMB-1 2" D-1
BT-1 119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800
EWH-1
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


4 ENLARGED PLAN - 2 BED "C" - PLUMBING 5 ENLARGED PLAN - JUNIOR - PLUMBING morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:06 PM
M3.03 M3.03 unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M3.03
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. SEE SHEET M0.0 - MECHANICAL GENERAL INFORMATION FOR ALL APPLICABLE NOTES
AND SYMBOLS.

KEYNOTES

M303 PROVIDE PLUMBING CONNECTION TO DISHWASHER. SEE DETIAL X/MX.XX.

2" D-1 EWH-1


2" D-1 EWH-1

BT-1 WMB-1
BT-1

3/4" CW
3/4" CW WMB-1
3/4" HW
3/4" HW WC-1 3/4" CW 3/4" CW OB-1
3/4" CW
WC-1 OB-1 L-1
L-1 3/4" HW
3/4" CW 1/2" HW
3/4" HW
3/4" HW WC-3
M303
M303
2" D-1

S-1
S-1
L-2
EWC-1
WC-4

L-2
2" D-1 WC-4

L-2

EWH-2
UR-1

2" D-1

WC-3

1 ENLARGED PLAN - STUDIO "A" - PLUMBING 2 ENLARGED PLAN - STUDIO "B" - PLUMBING 6 ENLARGED PLAN - COMMONS RESTROM - PLUMBING
M3.04 M3.04 M3.04

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

S-1

M303

OB-1

No. Description Date

EWH-1
2" D-1
EWH-1
SAGE
WMB-1
DEVELOPMENT
2" D-1
GROUP
WMB-1
BT-1
2" D-1

EWH-1
S-1 BENSON
S-1 WC-1 M303
MULTIFAMILY
L-1 L-1 WC-1

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


WMB-1 M303 OB-1

BT-1
BT-1
ENLARGED PLANS -
PLUMBING
WC-1 L-1 OB-1

3 ENLARGED PLAN - 1 BED "A" - PLUMBING 4 ENLARGED PLAN - 1 BED "B" - PLUMBING 5 ENLARGED PLAN - 1 BED "C" - PLUMBING
M3.04 M3.04 M3.04

0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8'

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:09 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M3.04
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL

Page Intentionally Left Blank

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


WASTE AND VENT RISER
DIAGRAMS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:10 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M4.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
LABEL CLEANOUT PLUG AS EITHER 'STORM' OR 'SANITARY' REFRIGERANT PIPING RACKED ON
WALL, (RATED FOR USE IN PLENUM)
CLEANOUT PLUG
EXTERIOR WALL CLEANOUT COVER
D=WIDTH
4" CONCRETE SLAB OF DUCT SPECIFIC UNITS ONLY - OUTDOOR AIR WITH
SUPPLY AIR DUCT MOTORIZED DAMPER. BALANCE TO
GRADE D
AIRFLOW SHOWN ON PLANS.
WEATHERPROOF FUSED DISCONNECT (SEE ELECTRICAL)
FLEX CONNECTION
AT SUPPLY AIR
R=1/2 D R=1/2 D M
FAN COIL WITH LINED PLENUM OPEN ON TOP
WATER HEATER
R=1XD
BELOW DOMESTIC CW RISER
(UNLESS SHOWN POWER WIRING
4" OTHERWISE) WATER
HEATER NOTE: INTERIOR OF MECHANICAL CLOSET & AC
FROM CU
DISCONNECT DOOR PAINTED WITH INTUMESCENT PAINT -1
BUILDING TO SEWER
UNIT RETURN AIR GRILLE TO ALLOW OPEN RETURN FROM SIDEWALL CONDENSING UNIT LOCATED ON ROOF
GRILLE TO FAN COIL UNIT IN CLOSET
10" W 12" W "Y" BRANCH FITTING 90° ELBOW MAINTAIN MANUFACTURER'S
CEILING RADIATION DAMPER. REFERENCE ARCHITECTURAL DRAWINGS PLAN VIEW RECOMMENDED CLEARANCE
FOR UL CEILING ASSEMBLY TYPE. FIRE RADIATION DAMPER SHALL BE AROUND ALL SIDES OF UNIT
LISTED FOR UL CEILING ASSEMBLY. PROVIDE WITH ACCESS DOOR.
CONTROL WIRING

45° ENTRY BRANCH


30° MAX. 30° MAX. SUPPLY AIR DUCT
CONVERGING TEE
CE
1 DOUBLE GRADE CLEANOUT DETAIL SIDEWALL RETURN GRILLE WITH FR.D.
ILIN
G
FILTER DRYER
SCALE: NONE LINED ELBOW DOWN, OPEN BELOW OPEN RETURN SPECIFIC UNITS ONLY - OUTDOOR AIR WITH MOISTURE INDICATOR SIGHT GLASS
M5.01
TO FAN COIL MOTORIZED DAMPER. BALANCE TO
AIRFLOW SHOWN ON PLANS. LIQUID LINE
NOTE: AP
BLOWER ACCESS PANEL PR SUCTION LINE
WHERE FITTING OX
DOMESTIC CW RISER . 4"
NOT POSSIBLE,
USE EXTRACTOR. COIL ACCESS PANEL WALL-HUNG FAN COIL
UNION
M
PROVIDE FLOOR LEVEL STEEL
GRATED LID (150 PSF) 24 VOLT DAMPER INTERLOCKED WITH SUPPLY FAN IN FAN AC
2" PUMP DISCHARGE -1

CORD SET FOR PLUG CONNECTION


SINGLE BRANCH TAKE-OFF DOUBLE BRANCH TAKE-OFF CONDENSATE ROUTED TO DRAIN. PROVIDE
COIL UNIT. DAMPER SHALL OPEN WHEN FAN OPERATES.
DAMPER SHALL CLOSE WHEN FAN IS NOT OPERATING.
INTO A SINGLE NON-GFCI OUTLET RECTOSEAL SAFE-T-SWITCH MODEL SS2 (OR
ELEVATOR PIT FLOOR EQUAL) CONDENSATE DRAIN PAN OVERFLOW REFRIGERANT PIPING TO HEAT PUMP ON ROOF.
CONTROL WIRE TO CONTROL PANEL KIT INTERLOCKED TO SHUT DOWN UNIT IN PIPING SHALL BE RATED FOR USE IN PLENUM.
THE EVENT OF CONDENSATE OVERFLOW. SIZE PER MANUFACTURER'S RECOMMENDATIONS. WALL MOUNTED AIR CONDITIONING UNIT
PUMPED CONDENSATE TO FLOOR DRAIN (SEE FLOOR PLANS)
ISOLATION VALVE (TYP.)
30° MAX. SEE ENLARGED UNIT PLANS FOR PIPE SIZES INDOOR UNIT POWER
UNION (TYP.)
DUCTWORK MAIN WATER HEATER DISCONNECT SIZE REFRIGERANT PIPING PER
CHECK VALVE 45° ENTRY BRANCH
MANUFACTURER'S RECOMMENDATIONS
R NOTE: WATER HEATER CONNECTIONS MUST BE NOTES:
LOCATED AT THE FRONT OF THE MECHANICAL
ROUTE RELIEF TO FLOOR DRAIN CLOSET TO ALLOW ACCESS TO THE WATER PIPING
SUMP PUMP SP-1 1) WIRING AND PIPING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ONLY AND
HI-EFFICIENCY TAKEOFF CONNECTIONS TO THE WATER HEATER
ARE NOT INTENDED FOR A SPECIFIC INSTALLATION. REFER TO FLOOR PLANS FOR
WITH VOLUME DAMPER 50 GALLON ELECTRIC LOW EQUIPMENT ORIENTATION. ALSO REFER TO MANUFACTURER'S INSTALLATION MANUALS
VOLUME DAMPER
BOY WATER HEATER
SUMP PIT (VERIFY SIZE AND ROUND DUCT TO DIFFUSER FOR SPECIFIC INSTALLATION REQUIREMENTS.
COORDINATE LOCATION WITH HUB DRAIN.
MICRO SWITCH CONVERGING TEE
STRUCTURAL) 2) CONDENSATE PIPING ROUTED IN CEILING PLENUMS SHALL BE COPPER AND SHALL BE
(ROUND) INSULATED. SEE SPECIFICATIONS.
FLOOR
DIFFUSER TAKE-OFF 45° ROUND TAKE-OFF REFRIGERANT PIPING 3) INSULATE SUCTION LINES.
FLOOR SINK IN METAL ENCLOSURE (1ST FLOOR AND NON RACKED ON WALL
STACKED MECHANICAL CLOSETS). SEE PLUMBING WASTE & 2" DEEP DRAIN PAN 4" LARGER
SUCTION STRAINER VENT RISER DIAGRAMS, SHEET M4.4. THAN WATER HEATER DIAMETER
DRAIN VALVE WITH HOSE END CONNECTION

SECTION VIEW
2 ELEVATOR SUMP PUMP DETAIL 3 DUCT FITTINGS DETAIL 4 RESIDENTIAL MECHANICAL CLOSET DETAIL 5 WALL MOUNTED DUCTLESS A/C UNIT DETAIL
M5.01 SCALE: NONE M5.01 SCALE: NONE M5.01 SCALE: NONE M5.01 SCALE: NONE

OVERLAP CAP AND SEAL WATERTIGHT

EXTERIOR CROSS BEAD AND SLOPE TO DRAIN


WALL
CONCENTRIC ADAPTER 1/4" NEOPRENE SHEET
RH-1 INSTALL UNIT HEATER AND
FACTORY MOUNTED VENT CAP ASSOCIATED E.A. / C.A.
WEATHERPROOF DISCONNECT SWITCH PER MANUFACTURER'S
THREADED HOSE OUTLET EXHAUST FAN RECOMMENDATIONS AND
W/ INTEGRATED VACUUM BREAKER SIZE HOLES 1/8" SMALLER THAN PIPE DIAMETER
PER NFPA 54 REQUIREMENTS
MECHANICAL SEAL
EPDM BOOT TO PROTECT REFRIGERANT PIPING
INLET AIR
MECHANICAL SEAL 1" OVERHANG POLYPROPYLENE HEAT PUMP PAD WITH
HYDRANT SUPPORT MOUNT
INTEGRAL NEOPRENE PAD VIBRATION
ROOF INSULATION SUPPORT FROM CANT STRIP WITH FLASHING ISOLATION. MODEL HP3636-8 BY
CLAMP TO ROOF DECKING DIVERSITECH OR EQUAL.
ROOF DECKING SECURE FAN TO ROOF CURB STRUCTURE
ALTERNATE: PROVIDE TREATED WOOD
PREFABRICATED ROOF CURB COMBUSTION AIR SLEEPERS WITH HEAT PUMP STAND OFF
ADJUSTABLE COORDINATE WITH
LOUVER SIZE PIPING PER MANUFACTURER'S SUPPORTS AND NEOPRENE PAD
24-V MOTORIZED BACK-DRAFT DAMPER EXHAUST ROOFING CONTRACTOR ISOLATION AT EACH HEAT PUMP.
COORDINATE ROOF-CURB RECOMMENDATIONS. ROUTE PIPING
WITH ROOF CONSTRUCTION ROOF FLASHING FROM ACCU / HEAT PUMP UNIT TO
GAS COOLING COIL.
3/4" DRAIN LINE. ROUTE DRAIN TO FLOOR M
DRAIN IN NEAREST UNIT MECHANICAL CLOSET. GAS COCK 7" (MINIMUM)
ROOF

G
1" CW LBS TO OZ GAS PRESSURE REGULATOR
SIZE HOOD AS REQUIRED TO
SECURE DAMPER TO ROOF CONSTRUCTION ACCOMMODATE REFRIGERANT PIPING,
NOTE: INSTALL PER ROOF CONSTRUCTION UNION
POWER CONDUIT, AND CONTROL CONDUIT
MANUFACTURER'S SECURE DUCTWORK TO DAMPER DIRT LEG
RECOMMENDATIONS

6 ROOF HYDRANT DETAIL 7 EXHAUST FAN MOUNTING DETAIL 8 GAS UNIT HEATER DETAIL 9 REFRIGERANT PIPING HOOD DETAIL 10 HEAT PUMP SUPPORT DETAIL
M5.01 SCALE: NONE M5.01 SCALE: NONE M5.01 SCALE: NONE M5.01 SCALE: NONE M5.01 SCALE: NONE

GRATE (SEE STRUCTURAL) 60" MIN GRADE


FIRST FLOOR WALL CAVITY

4"Ø RIGID DRYER EXHAUST


No. Description Date
DRYER-BOX (CONFIRM
WALL CONSTRUCTION)
RIGID PIPE NOT TO EXCEED 2" THROUGH
DRYERBOX
SAGE
MOTORIZED
4" WATER SERVICE
MOUNT DRYERBOX AS LOW AS POSSIBLE,
DEVELOPMENT
DISCHARGE
DAMPER
SUPPORT FAN FROM STRUCTURE
FLEXIBLE CONNECTION TO
OWNER FURNISHED DRYER
UNLESS DRYER IS ON A PEDESTAL OR A
STACKABLE UNIT GROUP
FAN SIDE GUARD

AREA WELL FAN MOTOR


13 DRYER CONNECTION DETAIL
COORDINATE
17,600 CFM
M5.01 SCALE: NONE BENSON
OPENING WITH
GENERAL
CONTRACTOR
EXHAUST FAN
LABEL CLEANOUT PLUG AS EITHER 'STORM' OR 'SANITARY' MULTIFAMILY
4" TO BUILDING CLEANOUT COVER CLEANOUT PLUG
LOUVER M PRESSURE GAUGE WITH PEAK INDICATOR

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


24 VOLT DAMPER INTERLOCKED WITH EXHAUST FLOOR
BIRD SCREEN FAN. DAMPER AND OPERATOR SHALL FIT WITHIN FAN WALL COLLAR 1" TEST TEE FACING UP WITH RIGID NIPPLE & THREADED CAP
THE CONCRETE GARAGE WALL. DAMPER SHALL LOCKABLE BYPASS VALVE
OPEN WHEN FAN OPERATES. DAMPER SHALL
CLOSE WHEN FAN IS NOT OPERATING. AREA DRAIN CLOSURE ANGLES PRESSURE REDUCING VALVE (PRV)
COORDINATE CONTROL WITH GARAGE

COORDINATE LOUVER LOCATION AND


VENTILATION SYSTEM CONTROL SYSTEM. AD-1 UNION
MECHANICAL DETAILS
SEE ARCHITECTURAL
HEIGHT ABOVE GRADE WITH OPEN AND STRUCTURAL PLANS METER
ARCHITECTURAL PLANS. WHEN
MULTIPLE LOUVERS ARE INSTALLED WATER METER (COORDINATE METER SIZE
ON A COMMON EXTERIOR WALL, WITH METROPOLITAN UTILITIES DISTRICT)
LOUVERS SHALL BE AT THE SAME FLOOR TO SEWER FROM BUILDING
ELEVATION. 4"
SEE PLANS FOR MAIN SIZE

CONNECT TO SANITARY
PIPING IN GARAGE. SEE
COORDINATE SANITARY PIPING WITH BUILDING FOOTING SHEET M2.00
14 CLEANOUT DETAIL
GARAGE INTAKE GARAGE EXHAUST M5.01 SCALE: NONE
119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800
11 GARAGE VENTILATION SYSTEM SECTIONS 12 WATER SERVICE ENTRANCE DETAIL MEI PROJECT NO: 19164
M5.01 SCALE: NONE M5.01 SCALE: NONE
ARY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:10 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M5.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL

S LO
PE
PIPE
PUMPED CONDENSATE PAINT STEEL PLATE P-20
BENT STEEL PLATE 1/2" DIA STUD TYPE
EXPANSION ANCHOR 2 1/4"
CEILING PLENUM ROUND DUCT
EMBEDMENT (3 EACH SIDE) 36" MAXIMUM LENGTH
45º MAXIMUM BEND
3" 1" MIN. CLEAR ROUND DUCT SHEET
METAL 90°
ROUND DUCT ELBOW
SHEET
CONNECT TO TOP OF GRAVITY DRAIN LINE 9"
METAL 90°
SHEET METAL ELBOW
90° ELBOW DUCT TO BE SAME SIZE
SEE FLOOR PLANS FOR SIZE FIRE DAMPER AS DIFFUSER/GRILLE NECK

36"
GRAVITY CONDENSATE MAIN 9" DUCT TO BE SAME SIZE
1/4" BENT STEEL PLATE AS DIFFUSER/GRILLE NECK GYP. CEILING AT BOTTOM OF JOISTS
PROVIDE WYE FITTING TO DIRECT PUMPED
DUCT TO BE SAME SIZE
CONDENSATE IN DIRECTION OF GRAVITY FLOW CONCRETE COLUMN 36" MAXIMUM
AS DIFFUSER NECK
3" LENGTH 45°
MAXIMUM BEND FLEXIBLE DUCT FIRE DAMPER
FLEXIBLE DUCT ACCESS DOOR
CONCRETE COLUMN 36" MAXIMUM
SLOPE TOWARDS DRAIN LOCATION EXPANSION ANCHOR CEILING LENGTH 45°
CEILING MAXIMUM BEND FLEXIBLE DUCT
FLOOR
DIFFUSER DIFFUSER/GRILLE

RADIATION DAMPER LAY-IN TILE CEILING

DIFFUSER/GRILLE
1 CONDENSATE CONNECTION DETAIL 2 PIPE GUARD DETAIL 3 DIFFUSER/REGISTER CONNECTION DETAILS
M5.02 SCALE: NONE M5.02 SCALE: NONE M5.02 SCALE: NONE

FAUCET FAUCET FAUCET


DOUBLE BOWL SINK DOUBLE BOWL SINK DOUBLE BOWL SINK FULL HEIGHT WALL
1/2" CW 1/2" CW 1/2" CW
1/2" HW CONNECT DISHWASHER WASTE TO GARBAGE DISPOSAL 1/2" HW FULL HEIGHT WALL CONNECT DISHWASHER WASTE TO GARBAGE DISPOSAL 1/2" HW
CONNECT DISHWASHER WASTE TO GARBAGE DISPOSAL VENT PER OMAHA
2" VENT
ROUTE WASTE AS HIGH AS POSSIBLE ROUTE WASTE AS HIGH AS POSSIBLE PLUMBING CODE
ROUTE WASTE AS HIGH AS POSSIBLE

VENT PER OMAHA


PLUMBING CODE

DISHWASHER DISHWASHER DISHWASHER


2" VENT
GARBAGE GARBAGE GARBAGE
DISPOSAL DISPOSAL DISPOSAL
2" VENT
5/8" WASTE 1-1/2" WASTE 5/8" WASTE 1-1/2" WASTE 5/8" WASTE 1-1/2" WASTE

2" WASTE 2" WASTE

3/8" HW 3/8" HW 3/8" HW

2" DRAIN LEG


STANDARD CONFIGURATION PENINSULA COUNTER CONFIGURATION ISLAND COUNTER CONFIGURATION
WASTE

NOTE: ACTUAL DISHWASHER, GARBAGE DISPOSAL AND SINK CONFIGURATIONS MAY VARY. SEE ARCHITECTURAL PLANS
FOR EXACT CONFIGURATION FOR EACH APARTMENT UNIT. VENT SINKS AS REQUIRED BY OMAHA PLUMBING CODE.
4 DISHWASHER/GARBAGE DISPOSAL DETAILS
M5.02 SCALE: NONE

SUPPORT FROM STRUCTURE (TYP)

HOOD
THREADED ROD (TYP) 4" INTERCEPTOR VENT

PROVIDE VENT FLUSH


VIBRATION ISOLATOR (TYP) WITH WALL (PROVIDE
WITH INSECT SCREEN)

SECURE HOOD TO ROOF CURB


PREFABRICATED ROOF CURB
COORDINATE ROOF-CURB
WITH ROOF CONSTRUCTION ROOF FLASHING
PUMPED CONDENSATE. DO NOT ROOF CONSTRUCTION (VERIFY)
24 VOLT MOTORIZED
TRAP. ROUTE TO NEAREST
DAMPER M
FLOOR DRAIN OR MOP SINK. SEE FLOOR PLANS FOR CONTINUATION
INTERLOCKED WITH
VRF TU UNIT FAN
SECURE DAMPER TO 26"Ø BOLTED AIR TIGHT COVER
VOLUME DAMPER ROOF CONSTRUCTION 120V MOTORIZED DAMPER 4" SANITARY VENT
M CLEANOUT NEENAH R-1916-F (OR APPROVED EQUAL) MANHOLE COVER AND FRAME
FOR ELEVATOR SMOKE
SECURE RELIEF. SEE ELECTRICAL
OA DUCTWORK TO FOR CONTROL.
OUTSIDE AIR DAMPER
ELEVATOR SHAFT
SEE DRAWINGS FOR
SIZE AND CFM
6 SMOKE RELIEF HOOD DETAIL
24"Ø CONCRETE PIPE

M5.02 SCALE: NONE


TRANSITION FROM 30" TO 24" CONCRETE PIPE
FACE PLATE. ADJUST HANGER
ROD TO ENSURE FLUSH FIT WITH CONTROL PANEL
CEILING. COORDINATE WITH ALL
TRADES AND CEILING LAYOUT.

REFRIGERANT PIPING TO/FROM CONDENSING UNIT. SIZE


AND INSTALL PER MANUFACTURER'S RECOMMENDATIONS 4"
THREADED STEEL HANGER ROD 4" No. Description Date
MAINTAIN MANUFACTURER'S
RECOMMENDED SERVICE CLEARANCES
4" MIN.

NOTE:
1) INSTALL VRF CEILING CASSETTE UNIT PER MANUFACTURER'S RECOMMENDATIONS.
EXHAUST AIR DUCTWORK. SEE
PLAN FOR LOCATION AND SIZE SUPPORT UNIT FROM STRUCTURE WITH
SEE FLOOR PLAN FOR
CONTINUATION
8" MIN.
SEE FLOOR PLANS
FOR PIPE ROUTING SAGE
HANGING SPRING ISOLATORS OR NEOPRENE PADS
MOUNTING FLANGE
FROM GARAGE DRAINS
DEVELOPMENT

36" MIN
FAN HOUSING WITH FAN
5 VRF TU INDOOR UNIT (CASSETTE) DETAIL 4" SANITARY
GROUP
M5.02 SCALE: NONE PROVIDE RADIATION DAMPER 36"∅ CONCRETE PIPE 6" SANITARY
COORDINATE FAN LOCATION WITH
STRUCTURE AND ARCHITECTURAL DEPTH OF PIPE IS AS REQUIRED FOR MINIMUM DIMENSIONS
PROVIDE HEAT TRAPS ON INLET AND ELEMENTS INSTALL INTERCEPTOR PER PLUMBING CODE REQUIREMENTS
INDICATED BY PLUMBING CODE
OUTLET PER ENERGY CODE (REQUIRED CEILING, VERIFY CEILING TYPE
FACE GRILLE EMBED CONCRETE PIPE IN CONCRETE SLAB
FOR NON-CIRCULATING SYSTEMS)

CHECK VALVE
INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.
BENSON
BALL VALVE (TYP.)
3/4" HW MULTIFAMILY
3/4" CW THERMOMETER (TYP.) 7 EXHAUST FAN MOUNTING DETAIL 8 TYPE 1 INTERCEPTOR DETAIL

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


M5.02 SCALE: NONE M5.02 SCALE: NONE

UNION (TYP.)

TEMPERATURE AND PRESSURE RELIEF VALVE

EWH-3 R
MECHANICAL DETAILS
ROUTE RELIEF TO ABOVE DRAIN PAN
DRAIN VALVE WITH HOSE END CONNECTION
PROVIDE WALL REINFORCEMENT AS REQUIRED
2" DEEP GALVANIZED DRAIN PAN 4" LARGER
THAN WATER HEATER DIAMETER
MOUNT WATER HEATER ON WALL
WITH ANGLE IRON SUPPORTS UNLESS
NOTED OTHERWISE MOUNT WATER HEATER AS
HIGH AS POSSIBLE ON WALL
ROUTE RELIEF TO MOP SINK
FLOOR

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
9 ELECTRIC WATER HEATER DETAIL MEI PROJECT NO: 19164
M5.02 SCALE: NONE
ARY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:10 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M5.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
AIR CONDITIONING UNIT SCHEDULE VRF AIR-TO-AIR HEAT PUMP UNIT SCHEDULE HEAT PUMP SCHEDULE FAN COIL UNIT SCHEDULE - ELECTRIC FURNACE
PLAN TAG AC-1 PLAN TAG VRF-HP-1 VRF-HP-2 VRF-HP-3 VRF-HP-4 VRF-HP-5 VRF-HP-6 VRF-HP-7 PLAN TAG HP-1.5 HP-2.0 HP-2.5 PLAN TAG FC-1.5 FC-2.0 FC-2.5
MANUFACTURER SAMSUNG (9) MANUFACTURER SAMSUNG SAMSUNG SAMSUNG SAMSUNG SAMSUNG SAMSUNG SAMSUNG MANUFACTURER CARRIER CARRIER CARRIER MANUFACTURER CARRIER CARRIER CARRIER
MODEL NUMBER AR24NSWSPWK MODEL NUMBER AM036FXMDCH/AA (5) AM048FXMDCH/AA (5) AM036FXMDCH/AA (5) AM036FXMDCH/AA (5) AM036FXMDCH/AA (5) AM036FXMDCH/AA (5) AM036FXMDCH/AA (5) MODEL NUMBER CH14NB-018 CH14NB-024 CH14NB-030 MODEL NUMBER FFMA 019 FFMA 025 FFMA 031

SERVES ELEV EQUIP RM SERVES SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS SERVES FC-1.5 FC-2.0 FC-2.5 SERVES SEE PLANS SEE PLANS SEE PLANS
GENERAL GENERAL GENERAL GENERAL
CONFIGURATION (1) CONFIGURATION - - - - - - - CONFIGURATION - - - CONFIGURATION (1) (1) (1)

MAXIMUM SIZE (LxWxH)(IN) 42"x12"x12" MAXIMUM SIZE (LxWxH)(IN) 37"x13"x47 5/8" 37"x13"x47 5/8" 37"x13"x47 5/8" 37"x13"x47 5/8" 37"x13"x47 5/8" 37"x13"x47 5/8" 37"x13"x47 5/8" MAXIMUM SIZE (LxW)(IN) 24"x24"x36" 26"x26"x36" 32"x32"32" MAXIMUM SIZE (H x W x D)(IN) 37x21x15 37x21x15 40x22x19
REMARKS (2) (4) (6) MAXIMUM WEIGHT (LBS.) 220 220 220 220 220 220 220 MAXIMUM WEIGHT (LBS.) 175 175 200 MAXIMUM WEIGHT 100 100 120
AIRFLOW (CFM) 660 REMARKS (3) (4) (3) (4) (3) (4) (3) (4) (3) (4) (3) (4) (3) (4) REMARKS (1) (1) (1) OUTSIDE AIRFLOW (CFM) (7) (7) (7)

FAN EXTERNAL STATIC PRESSURE (IN. W.C.) - VOLTS 208 208 208 208 208 208 208 VOLTS 208 208 208 REMARKS (1) (1) (1)
MOTOR HP - PHASE 1 1 1 1 1 1 1 PHASE 1 1 1 AIRFLOW (CFM) (9) 600 800 1,000
MAXIMUM CURRENT AMPS 30 MAXIMUM UNIT KW - - - - - - - MAXIMUM UNIT KW - - - FAN EXTERNAL STATIC PRESSURE (IN. W.C.) 0.30 0.30 0.40
MAXIMUM FUSE SIZE 20 ELECTRICAL MOCP 40 50 40 40 40 40 40 ELECTRICAL MAXIMUM FUSE SIZE (AMPS) 20 25 30 MAXIMUM FAN BHP - - -
ELECTRICAL
VOLTS 208 MINIMUM CIRCUIT AMPACITY (MCA) 23 29 23 23 23 23 23 MINIMUM CIRCUIT AMPACITY (MCA) 11.8 14.2 18.3 RPM - - -
DATA
PHASE 1 REMARKS - - - - - - - REMARKS - - - HP 1/3 (ECM) 1/3 (ECM) 1/2 (ECM)
REMARKS (8) AMBIENT AIR TEMPERATURE (F) 95.0 95.0 95.0 95.0 95.0 95.0 95.0 AMBIENT AIR TEMPERATURE (F) 95 95 95 VOLTS 208 208 208

ENTERING DB (ºF) 80 MINIMUN NET EER (ARI) - - - - - - - SEER 14 14 14 MOTOR PHASE 1 1 1


COOLING COOLING
ENTERING WB (ºF) 67 NOMINAL CAPACITY (TONS) 3.0 4.0 3.0 3.0 3.0 3.0 3.0 NOMINAL CAPACITY (TONS) 1.5 2.0 2.5 TYPE - - -
COOLING & LEAVING DB (ºF) - TOTAL COOLING (MBH) (1) (1) (1) (1) (1) (1) (1) TOTAL COOLING (MBH) 17.9 21.3 28.7 CONTROL DEVICE - - -
HEATING
LEAVING WB (ºF) - SENSIBLE COOLING (MBH) - - - - - - - SENSIBLE COOLING (MBH) 12.9 15.7 21.6 REMARKS (11) (11) (11)
TOTAL COOLING CAPACITY (MBH) 24.0 TYPE R-410A R-410A R-410A R-410A R-410A R-410A R-410A TYPE R-410A R-410A R-410A ENTERING AIR TEMP (ºF) 70 70 70
TOTAL HEATING CAPACITY (MBH) - REFRIGERANT MIN. NUMBER OF CIRCUITS 1 1 1 1 1 1 1 REFRIGERANT MIN. NUMBER OF CIRCUITS 1 1 1 LEAVING AIR TEMP (ºF) - - -
HEATING
REMARKS (HEAT PUMP) CAPACITY (MBH)
(3) (5) (7) (8) REMARKS - - - - - - - REMARKS (2) (2) (2) 18.1 22.0 28.7

(1) HIGH WALL MOUNT AIR-COOLED SPLIT SYSTEM WITH OUTDOOR REMOTE TYPE - - - - - - - TYPE SCROLL SCROLL SCROLL REMARKS (2) (2) (2)
CONDENSING UNIT WITH R-410A REFRIGERANT. COMPRES- COMPRES-
REMARKS QUANITY/SIZE 1 1 1 1 1 1 1 QUANTITY / SIZE 1 @ 1.5 TON 1 @ 2 TON 1 @ 2.5 TON ENTERING DB (ºF) 80.0 80.0 80.0
(2) PROVIDE WITH CONDENSATE PUMP CAPABLE OF MINIMUM 6 FOOT OF HEAD. SORS SORS
PUMP RESERVE SHALL HAVE HIGH LEVEL ALARM. HP - - - - - - - HP - - - ENTERING WB (ºF) 67.0 67.0 67.0
(3) CONDENSING UNIT ( ACCU-1), LOCATED ON PARKING GARAGE WALL. REMARKS (2) (2) (2) (2) (2) (2) (2) REMARKS (1) (1) (1) LEAVING DB (ºF) - - -
PROVIDE ALL ADDITIONAL REFRIGERANT PIPING ACCESSORIES AS COOLING
REQUIRED TO ACCOMMODATE REFRIGERANT LINE LENGTHS AND TYPE - - - - - - - TYPE PROP PROP PROP LEAVING WB (ºF) - - -
CONDENSING UNIT ELEVATION (SEE PLANS). CONDENSING UNIT MITSUBISHI CONDENSER QUANITY/SIZE 2 2 2 2 2 2 2 CONDENSER QUANTITY / SIZE 1 1 1 TOTAL CAPACITY (MBH) 17.9 21.3 28.7
MODEL PUY-A24NHA7. FANS FANS
(4) PROVIDE MANUFACTURER'S REMOTE WALL MOUNTED WIRED THERMOSTAT. HP - - - - - - - HP 1/12 1/10 1/4 SENSIBLE CAPACITY (MBH) 12.9 15.7 21.6
(5) PROVIDE COMPRESSOR WITH 5-YEAR WARRANTY. REMARKS - - - - - - - REMARKS - - - REMARKS - - -
(6) PROVIDE MANUFACTURER'S WASHABLE FILTERS. (1) PROVIDE WITH 5-YEAR COMPRESSOR WARRANTY. VOLTAGE/PHASE 208/1 208/1 208/1
(7) PROVIDE LOW AMBIENT KIT TO ALLOW COOLING DOWN TO -20°F. (1) COOLING PERFORMANCE SHALL MATCH SCHEDULED AC UNIT CAPACITIES.
REMARKS REMARKS (2) RESIDENTIAL HEAT PUMPS REQUIRED LONG LINE SETS UP TO 200 TOTAL LINEAL FEET SIZE (KW) 7.5 7.5 10.0
(8) PROVIDE MANUFACTURER'S OUTDOOR CONDENSING UNIT MODEL
(2) PROVIDE WITH DC INVERTER-DRIVEN TWIN ROTARY WITH 7 YEAR COMPRESSOR WARRANTY. ELECTRIC
PUY-A24NHA6 WITH INVERTER COMPRESSOR. POWER FOR INDOOR UNIT WITH 90 FOOT RISE. COORDINATE LONG LINE SET REQUIREMENTS WITH MANUFACTURER. NUMBER OF STAGES 1 1 1
PROVIDE ALL ACCESSORIES REQUIRED FOR PROPER LONG LINE SET OPERATION. HEAT
WIRED FROM OUTDOOR UNIT.
(3) UNIT SHALL CONSIST OF COMPRESSOR, AIR COOLED COIL, PROPELLER TYPE CONDENSER CAPACITY (MBH) AT 208 VOLTS 22.2 22.2 24.6
(9) ACCEPTABLE MANUFACTURERS: CARRIER, DAIKIN, MITSUBISHI, TRANE, FAN, ACCUMULATOR, HOLDING REFRIGERANT CHARGE, LOW AMBIENT CONTROL (WIND
FUJITSU, TOSHIBA, SAMSUNG BAFFLE KIT) WITH TWO OUTLET GUIDES, AND CONTROL BOX. REMARKS (3) (8) (3) (8) (3) (8)
REFRIGERANT TYPE R-410A R-410A R-410A
(4) UNIT SHALL BE RATED FOR HEATING OPERATION DOWN TO -13 DEGREES F. DIRECT
EXPANSION SATURATED SUCTION TEMP (ºF) - - -
(5) OUTDOOR UNIT WITH VARIABLE REFRIGERANT FLOW ZONING TECHNOLOGY.
REMARKS (4) (4) (4)
FILTERS (5) (5) (5)
HUMIDIFIER - - -

THERMOSTAT (6) (6) (6)


DIFFUSER REGISTER AND GRILLE SCHEDULE VRF HEAT PUMP - INDOOR UNIT SCHEDULE REMARKS (7) (7) (7)

PLAN TAG R-1 R-2 G-1 PLAN TAG TU-05C TU-08C TU-12C TU-18C (1) BASE SERIES FAN COIL, UP FLOW , WALL HUNG INSTALLATION, ECM MOTOR.
(2) HEAT PUMP HEATING CAPACITY AT 47°F.
MANUFACTURER US AIRE (5) KRUEGER (7) METALAIRE (5) MANUFACTURER SAMSUNG SAMSUNG SAMSUNG SAMSUNG REMARKS
(3) FACTORY INSTALLED ELECTRIC HEAT WITH SINGLE POINT CONNECTION.
MODEL NUMBER 102M S80H RH-1 MODEL NUMBER AM005NNNDCH/AA AM009NNNDCH/AA AM012NNNDCH/AA AM018NNNDCH/AA
(4) CASED DX COOLING COIL TO MATCH FAN COIL AND UNIT HEAT PUMP.
FUNCTION SUPPLY EXHAUST RETURN SERVES SEE PLANS SEE PLANS SEE PLANS SEE PLANS (5) 1" PLEATED DISPOSABLE FILTER.
GENERAL
DESCRIPTION REGISTER GRILLE GRILLE CONFIGURATION (1) (1) (1) (1) (6) 7-DAY PROGRAMMABLE SETBACK HEAT PUMP THERMOSTAT WITH HEAT/COOL/AUTO, FAN ON/OFF/AUTO CONTROL.

DEFLECTION DOUBLE SINGLE FIXED - 40° MAXIMUM SIZE (LxWxH)(IN) (4) (4) (4) (4) (7) SEE OUTDOOR AIR VENTILATION SCHEDULE ON SHEET M5.2.
(8) SIZE (KW) INDICATED IS NOMINAL FOR 240V. ACTUAL CAPACITY (MBH) IS DERATED FROM 240V TO ACTUAL 208V OPERATION.
MAXIMUM STATIC PRESSURE (IN W.G.) 0.10" 0.10 0.10 REMARKS (2) (2) (2) (2)
(9) BASE SERIES FAN COIL, UP FLOW , FLOOR SET INSTALLATION, ECM MOTOR.
CONSTRUCTION MATERIAL STEEL STEEL STEEL AIRFLOW (CFM) 300 (5) (6) 353 371 \459
(10) FACTORY INSTALLED ELECTRIC HEAT WITH TWO ELECTRICAL CONNECTIONS.
FINISH WHITE WHITE WHITE FAN EXTERNAL STATIC PRESSURE (IN. W.C.) - - - - (11) ELECTRICAL DISCONNECT BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS.
NECK SIZE (IN) SEE PLANS SEE PLANS SEE PLANS MOTOR HP - - - -
FACE SIZE (IN) NECK + 1-3/4" NECK + 1-3/4" NECK + 3" (6) MCA 0.24 0.24 0.26 0.38
ACCESSORIES (3 (4) - - MOCP 15 15 15 15
REMARKS (1) (2) (1) (2) (1) (2)
ELECTRICAL
DATA
VOLTS 208 208 208 208 FAN SCHEDULE GAS FIRED UNIT HEATER SCHEDULE
REMARKS (1) VERIFY CEILING/WALL CONSTRUCTION PRIOR TO FURNISHING MATERIAL. PHASE 1 1 1 1
PLAN TAG EF-1 (1) EF-2 EF-3 EF-4 EF-5 EF-6 DF-1 PLAN TAG UH-1, 2, 3
(2) NOISE CRITERIA (NC) SHALL BE LESS THAN 25 ON DIFFUSERS, REGISTERS AND GRILLES IN LOCATED REMARKS - - - -
OCCUPIED SPACES. MANUFACTURER BROAN GREENHECK GREENHECK GREENHECK GREENHECK GREENHECK FANTECH MANUFACTURER REZNOR
(3) O.B. DAMPER. ENTERING DB (ºF) 80.0 80.0 80.0 80.0
(4) RADIATION DAMPER (REQUIRED AT PENETRATION OF ALL GYP. CEILINGS AT MODEL NUMBER QTXE110 SBE-3L36-30 G-090-VG CSP-A290 CSP-A250 CSP-A200 DBF 4XL MODEL NUMBER UDAS-400
BOTTOM OF JOISTS). ENTERING WB (ºF) 67.0 67.0 67.0 67.0
(5) ACCEPTABLE MANUFACTURERS: US AIRE, HART AND COOLEY. GENERAL SERVES (1) PARKING GARAGE TRASH COMMONS COMMONS COMMONS DRYER EA SERVES PARKING GARAGE
LEAVING DB (ºF) - - - - GENERAL
(6) RETURN GRILLE TO BE SIZED AT MAXIMUM 500 FPM. TYPE CEILING SIDEWALL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL IN-LINE CONFIGURATION (2)
COOLING &
(7) ACCEPTABLE MANUFACTURERS: KREUGER, PRICE, TITUS. LEAVING WB (ºF) - - - -
HEATING
MAXIMUM WEIGHT (LBS) 15 463 49 23 23 23 8 MAXIMUM SIZE (LxWxH)(IN) 41x42x35
TOTAL COOLING CAPACITY (MBH) 5.0 9.5 12.0 18.0
ROOF/WALL/CEILING OPENING SIZE - 44.75"x44.75" (6) 12.5"x12.5" (6) 14"x12"(6) 14"x12" (6) 14"x12" (6) - MAXIMUM WEIGHT (LBS.) 307
TOTAL HEATING CAPACITY (MBH) 6.0 10.0 13.5 20.0
ACCESSORIES (2) (4) (8) (8) (8) (8) (10) MINIMUM OUTSIDE AIRFLOW (CFM) -
REMARKS (3) (3) (3) (3)
AIRFLOW (CFM) 86 17,600 500 225 150 75. 160 REMARKS (3)
(1) CEILING MOUNTED, DUCTLESS, AIR COOLED, VRF UNIT.
TOTAL SP (IN. W.C.) 0.50 0.25 0.625 0.5 0.5 0.5 - AIRFLOW (CFM) 5,123
LOUVER SCHEDULE REMARKS (2) PROVIDE UNIT WITH HANGING BRACKETS, INTEGRAL FACE GRILLE, HIGH EFFICIENCY AIR FILTER, WIRED WALL CLASS - - - - - - - FAN EXTERNAL STATIC PRESSURE (IN. W.C.) 0
MOUNTED CONTROLLER, AND BUILT-IN CONDENSATE PUMP.
PLAN TAG L-1 WHEEL TYPE - PROP BI BI BI BI - MAXIMUM FAN BHP -
FAN
(3) SEE AIR VRF AIR-TO-AIR HEAT PUMP SCHEDULE. MINIMUM WHEEL DIA. - - - - - - - RPM 1,050
MANUFACTURER RUSKIN
MODEL NUMBER ELF375DX (4) 22 5/8x22 5/8x10 (LxWxH). MAXIMUM SONES 1 24 8.8 3 3 2 - HP 1/2

FUNCTION GARAGE MAXIMUM FAN RPM - 745 1.718 1,050 1,000 900 - VOLTS 115
(5) INTERLOCK OA MOTORIZED DAMPER WITH CEILING CASSETTE FAN. MOTORIZED DAMPER TO BE CLOSED WHEN FAN
DESCRIPTION STATIONARY IS OFF. MAXIMUM FAN BHP - -- -- -- -- -- - MOTOR PHASE 1 No. Description Date
DEFLECTION HORIZ. (6) SET FAN TO RUN IN AUTOMATIC MODE. RPM - 1,725 1,725 1,050 1,000 900 2800 TYPE ENCLOSED
HP CONTROL DEVICE WALL STAT
SAGE
MAX. STATIC PRESSURE (IN W.G.) 0.30 - 3 1/10 0.05 0.03 0.02 83 WATTS

CONSTRUCTION MATERIAL ALUMINUM VOLTS 120 208 115 115 115 115 120 REMARKS -

DEVELOPMENT
FINISH (3) MOTOR PHASE 1 3 1 1 1 1 1 ENTERING AIR TEMP (ºF) 40

NECK SIZE (IN) SEE PLANS DOMESTIC WATER HEATER SCHEDULE TYPE - ODP ODP ODP ODP ODP - HEATING LEAVING AIR TEMP (ºF) 100

FACE SIZE (IN)


ACCESSORIES
SEE PLANS
(2)
PLAN TAG
MANUFACTURER
EWH-1
A.O. SMITH
EWH-2
A.O. SMITH
IWH-1
EEMAX
CONTROL DEVICE
REMARKS
(3)
-
(5)
-
(7)
-
(7)
-
(7)
-
(7)
-
(9)
(11)
TOTAL CAPACITY (MBH)
REMARKS
400
- GROUP
REMARKS (1) (1) BATHROOMS FUEL NAT. GAS
GENERAL MODEL NUMBER DEL-50 DEL-40 SP4208 (2) PLASTIC INTAKE GRILLE, DISCHARGE DUCT COLLAR, GRAVITY BACKDRAFT DAMPER, INTEGRAL DISCONNECT, UL-LISTED, RADIATION
DAMPER MODEL #RDFQF, AND 3-YEAR WARRANTY. INPUT 400
REMARKS (1) VERIFY WALL CONSTRUCTION PRIOR TO FURNISHING REMARKS
SERVES (1) (1) (6) (3) WALL SWITCH WITH HUMIDITY SENSOR. BROAN 82W WALL SWITCH / HUMIDITY SENSOR.
MATERIAL. GAS OUTPUT 332
24 24 24 (4) PROVIDE WITH 208V/1PH MOTORIZED DAMPER, GALVANIZED WEATHERHOOD WITH BIRD SCREEN, NEMA-1 DISCONNECT SWITCH,
RECOVERY (GPH@ 90ºF RISE) FIRED

BENSON
(2) PROVIDE FLANGE FRAME COMPATIBLE WITH WALL WALL HOUSING WITH OSHA GUARD, MOTOR WITH THERMAL OVERLOAD PROTECTION. EFFICIENCY 83%
CONSTRUCTION, EXPANDED FLATTENED ALUMINUM TYPE (2) (2) (8) (5) PARKING GARAGE CO/NO2 SYSTEM.
(6) COORDINATE SIZE OF OPENING WITH STRUCTURE AND GENERAL CONTRACTOR. VENT CONNECTION (1)
STORAGE CAPACITY (GAL.) 50 40 - (7) CONTINUOUS OPERATION.
BIRDSCREEN IN REMOVABLE FRAME.

(3) COLOR TO BE SELECTED BY ARCHITECT.


TANK
DIMENSIONS (LxWxH)(IN.)
REMARKS
24"Ø x 32-1/4"
(3) (4)
24"Ø x 32-1/4"
(3) (4)
9.6"x5.33"
-
(8) PROVIDE WITH EC MOTOR, 12" CURB, BIRDSCREEN, UNIT MOUNT FAN SPEED DIAL (FOR BALANCING), AND 1-YEAR WARRANTY.
ELECTRICAL DISCONNECT BY ELECTRICAL. FAN TO RUN CONTINUOUS.
(9) PRESSURE SENSING WITH SELF-CLEANING SENSING TUBE DESIGN. AUTOMATICALLY ACTIVATES FAN BASED ON OPERATION OF
REMARKS
REMARKS -
(1) PROVIDE SEALED COMBUSTION UNIT COMPLETE WITH 6" VENT AND 6"
INTAKE CONCENTRIC FITTING PROVIDED BY UNIT MANUFACTURER.
MULTIFAMILY
DRYER.
VOLTAGE/PHASE 208 / 1 208 / 1 208 / 1

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


(10) SECONDARY LINT TRAP, FANTECH MODEL DBLT4 (OR APPROVED EQUAL), INTEGRAL PRESSURE SENSING SWITCH, AND (2) GAS FIRED, SEPARATED COMBUSTION, LOW STATIC, AXIAL FAN UNIT
CONTROLS.
CAPACITY (KW) 6.0 6.0 4.1 HEATER.
(11) FAN TO BE HARDWIRED.
ELECTRIC
NUMBER OF STAGES (9) (9) 1 (3) PROVIDE WITH DISCHARGE LOUVERS, FAN GUARDS, AND FACTORY
KW PER STAGE
REMARKS
-
-
-
-
-
-
MOUNTED DISCONNECT SWITCH.
MECHANICAL
(1) APARTMENTS. SCHEDULES
REMARKS (2) RESIDENTIAL, LOWBOY ELECTRIC WATER HEATER.
(3) INTEGRAL GLASS LINED STORAGE TANK.
(4) TEMPERATURE PRESSURE RELIEF VALVE.
(6) PUBLIC RESTROOM LAVATORIES
(7) 59° F @ 0.5 GPM
(8) INSTANTANEOUS TANKLESS WATER HEATER
(9) DUAL NON-SIMULTANEOUS ELEMENTS.

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:11 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M6.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL

HOOD SCHEDULE PUMP SCHEDULE OUTDOOR AIR VENTILATION SCHEDULE


PLAN TAG RH-1 PLAN TAG SP-1 LOCATION AREA OCCUPANCY ASHRAE 62.1 DESIGN
(# OF PEOPLE) AIRFLOW (CFM) AIRFLOW (CFM)
MANUFACTURER GREENHECK MANUFACTURER LIBERTY PUMP
MODEL NUMBER FGR MODEL NUMBER 290 APARTMENTS VARIES N/A (1) 10% OF
GENERAL SUPPLY
60 CFM PER 1.5 TON UNIT
SERVES ELEVATOR SHAFT SERVES ELEVATOR PIT 80 CFM PER 2.0 TON UNIT AIRFLOW OF
CONFIGURATION RELIEF TYPE SUBMERSIBLE 100 CFM PER 2.5 TON UNIT FURNACE
115 CFM PER 3.0 TON UNIT
MAX. WEIGHT (LBS) 75 ACCESSORIES (1) 160 CFM PER 4.0 TON UNIT
200 CFM, PER 5.0 TON UNIT
AIRFLOW (CFM) - FLOW (GPM) 50
STATIC PRES. DROP - TOTAL HEAD (FEET) 26 LOWER LEVEL: 724 SQ FT N/A 5 CFM / PERSON 50 CFM
001 ENTRY & 004 LOBBY + 0.06 CFM / SQ FT
ROOF OPENING SIZE 20 x 30 SHUT-OFF HEAD (FEET) 48 = 44 CFM
NECK SIZE (LxW) (IN.) 20 x 30 NPSH AVAILABLE (FEET) -
FIRST LEVEL: 157 SQ FT N/A 0 CFM / PERSON 50 CFM
HOOD SIZE (LxW) (IN.) 34 x 51 MIN. EFFICIENCY - 100B.1 EXIT HALL + 0.06 CFM / SQ FT
PUMP = 10 CFM
OPENING TO NECK RATIO - FLUID WATER
ACCESSORIES FIRST LEVEL: 460 SQ FT N/A 0 CFM / PERSON 50 CFM
(1) (2) RPM 3450
100B CORRIDOR + 0.06 CFM / SQ FT
(1) PROVIDE WITH FACTORY 14" HIGH ROOF CURB. SUCTION SIZE (IN) OPEN = 28 CFM
REMARKS DISCHARGE SIZE (IN) 1-1/2" FIRST LEVEL: 1,564 SQ FT N/A 0 CFM / PERSON 100 CFM
(2) MOTORIZED DAMPER, 120V, FAIL OPEN.
100C CORRIDOR + 0.06 CFM / SQ FT
SOLIDS HANDLING SIZE (IN) 3/4" = 94 CFM
RPM 3450
FIRST LEVEL: 120 SQ FT N/A 0 CFM / PERSON 50 CFM
HP 3/4 100C HALL + 0.06 CFM / SQ FT
= 7 CFM
VOLTS 115
SECOND LEVEL: 460 SQ FT N/A 0 CFM / PERSON 50 CFM
MOTOR PHASE 1 + 0.06 CFM / SQ FT
200B CORRIDOR
TYPE HERM. SEALED = 28 CFM

CONTROL DEVICE (2) SECOND LEVEL: 1,564 SQ FT N/A 0 CFM / PERSON 100 CFM
200C CORRIDOR + 0.06 CFM / SQ FT
REMARKS - = 94 CFM

(1) PROVIDE ELEVATOR SUMP PUMP WITH FLOAT LEVEL CONTROL AND THIRD LEVEL: 460 SQ FT N/A 0 CFM / PERSON 50 CFM
CORD AND PLUG POWER. PUMP SHALL HAVE STAINLESS STEEL BOTTOM 300B CORRIDOR + 0.06 CFM / SQ FT
REMARKS SCREEN, STAINLESS STEEL ROTOR SHAFT, AND EPOXY POWER COAT = 28 CFM
FINISH. SUMP PUMP SHALL BE ASME 17.1 COMPLIANT. THIRD LEVEL: 1,564 SQ FT N/A 0 CFM / PERSON 100 CFM
300C CORRIDOR + 0.06 CFM / SQ FT
(2) PUMP SHALL BE CONTROLLED BY PUMP FLOAT CONTROLS WITH HIGH = 94 CFM
WATER ALARM.
FOURTH LEVEL: 723 SQ FT N/A 0 CFM / PERSON 50 CFM
401A CORRIDOR, 400A CORRIDOR + 0.06 CFM / SQ FT
400B CORRIDOR = 43 CFM

FOURTH LEVEL: 1,518 SQ FT N/A 0 CFM / PERSON 100 CFM


400C CORRIDOR + 0.06 CFM / SQ FT
400D CORRIDOR = 91 CFM

NOTES:
(1) APARTMENTS. OUTDOOR AIR PROVIDED 10% OF TOTAL SUPPLY AIRFLOW OF FAN COIL TO
PROVIDE MINIMUM 5 CFM / PERSON + 0.06 CFM / SQ FT.

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


MECHANICAL
SCHEDULES

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164

ARY N PROJECT: 17073


morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:11 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M6.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL

PLUMBING FIXTURE SCHEDULE PLUMBING FIXTURE SCHEDULE


TAG FIXTURE (2) FAUCET/ FLUSHVALVE/ ACCESSORY (2) DESCRIPTION CONNECTIONS TAG FIXTURE (2) FAUCET/ FLUSHVALVE/ ACCESSORY (2) DESCRIPTION CONNECTIONS

DESCRIPTION: ELONGATED, SIPHON JET BOWL, FLOOR MOUNTED, FLOOR OUTLET, TANK TYPE WATER CW HW WASTE VENT DESCRIPTION: BARRIER FREE WALL MOUNTED WATER COOLER WITH BOTTLE FILL STATION. CW HW WASTE VENT
CLOSET. ADA COMPLIANT: YES.
ADA COMPLIANT: NOT REQUIRED 1/2" - 3" 1-1/2" 1/2" - 1-1/4" 1-1/4"
NUMBER OF BUBBLERS: ONE.
COLOR: WHITE REMARKS: FIXTURE UNIT CAPACITY: 8 GPH. REMARKS:
TANK: CLOSED COUPLED. 1.6 GALLONS PER FLUSH 600 GRAMS PER FLUSH MINIMUM FIXTURE CABINET MATERIAL: VINYL COVERED STEEL.
SEAT: WHITE, ELONGATED, CLOSED FRONT WITH COVER REMOVAL RATE PER CWWA THERMOSTAT: ADJUSTABLE SET AT 50°F.
RIM HEIGHT: 14"-15.5" MAXIMUM PERFORMANCE TESTING
WC-1 EWC-2 ELECTRICAL: 120V, 3 WIRE CORD AND PLUG.
OF POPULAR TOILET MODELS DATA

ALTERNATES ARE ACCEPTABLE

MODEL: KOHLER K-3978 "WELLWORTH" MODEL: ELKAY EZS8WSSK

DESCRIPTION: ELONGATED, SIPHON JET BOWL, FLOOR MOUNTED, FLOOR OUTLET, TANK TYPE WATER CW HW WASTE VENT DESCRIPTION / MODEL #: AQUARIUS G3698BF EB (ADA/ANSI) SHOWER ENCLOSURE WITH KOHLER K-304-KS CW HW WASTE VENT
CLOSET. VALVE, AND KOHLER K-R45783-4E LINWOOD VALVE TRIM LESS TUB FILLER. SHOWER MUST MEET THE
ADA COMPLIANT: YES 1/2" - 3" 1-1/2" 1/2" 1/2" 1-1/2" 1-1/2"
REQUIREMENTS OF ADA.
COLOR: WHITE REMARKS: ADA COMPLIANT: YES REMARKS:
TANK: CLOSED COUPLED. 1.6 GALLONS PER FLUSH 600 GRAMS PER FLUSH MINIMUM COLOR: WHITE PROVIDE BACKING FOR
SEAT: WHITE, ELONGATED, CLOSED FRONT WITH COVER REMOVAL RATE PER CWWA FIXTURE ENCLOSURE: 39” X 39.5” X 77” GELCOAT FIBERGLASS, SMOOTH WALLS WITH SLIP RESISTANT, INSTALLATION OF GRAB BARS.
WC-2 RIM HEIGHT: 17.5"-18" MAXIMUM PERFORMANCE TESTING SH-1 TEXTURED BOTTOM. COORDINATE EXACT LOCATIONS
OF POPULAR TOILET MODELS DATA FIXTURE ENCLOSURE INSTALLATION: FLUSH MOUNTED TO THE FLOOR WITH ADA COMPLIANT THRESHOLD. WITH ARCHITECTURAL PLANS.
GRAB BARS AND SEAT: UNIT MUST BE REINFORCED FOR INSTALLATION OF GRAB BARS AND SEAT. VERIFY TRIM FINISH WITH
FIXTURE ENCLOSURE DRAIN: INTEGRAL CORROSION-RESISTANT METAL WITH REMOVABLE STRAINER. ARCHITECT.
ALTERNATES ARE ACCEPTABLE
SHOWER CURTAIN ROD: FACTORY INSTALLED.
SHOWER VALVE: PRESSURE BALANCED VALVE WITH SCREWDRIVER STOPS.
SHOWER HANDLE: SINGLE-LEVER.
MODEL: KOHLER K-3979 "HIGHLINE" MODEL: SEE DESCRIPTION MODEL: SEE DESCRIPTION

DESCRIPTION: ELONGATED, SIPHON JET BOWL, FLOOR MOUNTED, FLOOR OUTLET, TANK TYPE WATER CW HW WASTE VENT DESCRIPTION: GELCOAT FIBERGLASS TUB/SHOWER ENCLOSURE CW HW WASTE VENT
CLOSET. ADA COMPLIANT: NOT REQUIRED
1/2" - 3" 1-1/2" COLOR: WHITE 1/2" 1/2" 1-1/2" 1-1/2"
ADA COMPLIANT: YES
COLOR: WHITE FIXTURE DIMENSIONS: 60” X 32.75” X 73.5” GELCOAT FIBERGLASS, SMOOTH WALLS WITH SLIP RESISTANT REMARKS:
REMARKS: TEXTURED BOTTOM
TANK: CLOSED COUPLED. 1.6 GALLONS PER FLUSH 600 GRAMS PER FLUSH MINIMUM PROVIDE BACKING FOR FUTURE
FIXTURE ENCLOSURE DRAIN: INTEGRAL CORROSION-RESISTANT METAL WITH REMOVABLE STRAINER.
SEAT: WHITE, ELONGATED, OPEN FRONT WITHOUT COVER, SEAT WITH CHECK HINGE. REMOVAL RATE PER CWWA CURTAIN ROD: FACTORY INSTALLED.
INSTALLATION OF GRAB BARS.
RIM HEIGHT: 17.5"-18" BT-1 FAUCET CONSTRUCTION: PRESSURE BALANCED VALVE WITH SCREWDRIVER STOPS. COORDINATE EXACT LOCATIONS
WC-3 MAXIMUM PERFORMANCE TESTING
FAUCET COMPONENTS: SINGLE LEVER CHROME PLATED HANDLE, TUB FILLER SPOUT, SHOWER DIVERTER WITH ARCHITECTURAL PLANS.
OF POPULAR TOILET MODELS DATA
VALVE.
SHOWER HEAD: ARM AND FLANGE, POLISHED CHROME, 2.5 GALLONS PER MINUTE MAXIMUM
ALTERNATES ARE ACCEPTABLE
DRAIN: LEVER OPERATED POP-UP DRAIN.
TRIM FINISH: VERIFY WITH ARCHITECT.
MODEL: KOHLER K-R45783-4E
MODEL: KOHLER K-3979 "HIGHLINE" MODEL: AQUARIUS G6004 TS "LINWOOD"
DESCRIPTION: ELONGATED BOWL, FLOOR MOUNTED, FLOOR OUTLET, TANK TYPE WATER CLOSET, CW HW WASTE VENT DESCRIPTION: COUNTER MOUNTED 18 GA STAINLESS STEEL SINK WITH SWING SPOUT. CW HW WASTE VENT
CLASS FIVE FLUSHING SYSTEM. ADA COMPLIANT: NOT REQUIRED
1/2" - 4"
3" 1-1/2"
2" FIXTURE DIMENSIONS: SINGLE BOWL 22" X 19" X 7-5/8" 1/2" 1/2" 1-1/2" 1-1/2"
ADA COMPLIANT: NOT REQUIRED
COLOR: WHITE REMARKS: CONSTRUCTION: FAUCET INLET SPACING TO MATCH SINK OPENINGS. REMARKS:
TANK: CLOSED COUPLED. 1.6 GALLONS PER FLUSH HANDLE: SINGLE LEVER TOGGLE ADA COMPLIANT. VERIFY FAUCET FINISH WITH
SEAT: WHITE, ELONGATED, OPEN FRONT WITHOUT COVER, SEAT WITH CHECK HINGE. SPOUT: SWING WITH 1-1/2 GPM FLOW AERATOR. ARCHITECT
RIM HEIGHT: 14"-15.5" DRAIN: 1-1/2" GRID STRAINER WITH 3-1/2" REMOVABLE STAINLESS STEEL CRUMB CUP.
WC-4 S-1
FOOD WASTE DISPOSER: IN-SINK ERATOR, BADGER 5XP, 115VAC, 3/4 [1/2] HP DISPOSER. INCLUDE
MOTOR WITH OVERLOAD PROTECTION AND RESET BUTTON, WALL SWITCH, CORROSION RESISTANT
CHAMBER WITH JAM RESISTANT STAINLESS STEEL GRINDER, SPLASH GUARD, AND COMBINATION
COVER/STOPPER.

MODEL: KOHLER K-3978 "WELLWORTH" MODEL: ELKAY LR-2219 MODEL: MOEN MODEL 87090
CW HW WASTE VENT DESCRIPTION: COUNTER MOUNTED 18 GA STAINLESS STEEL SINK WITH SWING SPOUT. CW HW WASTE VENT
DESCRIPTION: WASHDOWN, WALL HANGING, WALL OUTLET URINAL WITH FLUSHOMETER.
ADA COMPLIANT: YES.
ADA COMPLIANT: YES
3/4" - 2" 1-1/2" FIXTURE DIMENSIONS: SINGLE BOWL 22" X 19" X 6-1/2" 1/2" 1/2" 1-1/2" 1-1/2"
COLOR: WHITE
FLUSHOMETER: TOP SPUD. 0.5 GALLONS PER FLUSH. CONSTRUCTION: FAUCET INLET SPACING TO MATCH SINK OPENINGS.
REMARKS: REMARKS:
FLUSHOMETER FINISH: POLISHED CHROME. HANDLE: SINGLE LEVER TOGGLE ADA COMPLIANT. VERIFY FAUCET FINISH WITH
FLUSHOMETER OPERATION: MANUAL. SPOUT: SWING WITH 1-1/2 GPM FLOW AERATOR. ARCHITECT
RIM HEIGHT: 17", ADA HEIGHT DRAIN: 1-1/2" GRID STRAINER WITH 3-1/2" REMOVABLE STAINLESS STEEL CRUMB CUP.
UR-1 S-2
ADA INSULATION KIT: PROVIDE SUPPLY AND DRAIN SOFT MOLDED INSULATION KITS FROM FIXTURE TO
WALL. COVERINGS TO BE CUSHIONED JACKET PLASTIC COVERING WITH SELF STICKING FASTENING
SYSTEM.
FOOD WASTE DISPOSER: IN-SINK ERATOR, BADGER 5XP, 115VAC, 3/4 [1/2] HP DISPOSER. INCLUDE
MOTOR WITH OVERLOAD PROTECTION AND RESET BUTTON, WALL SWITCH, CORROSION RESISTANT
MODEL: KOHLER K-4991-ET "BARDON" MODEL: ELKAY LR-2219 CHAMBER WITH JAM RESISTANT STAINLESS STEEL GRINDER, SPLASH GUARD, AND COMBINATION
MODEL: SLOAN REGAL 186-.05-XL MODEL: MOEN MODEL 87090 COVER/STOPPER.
DESCRIPTION: UNDERCOUNTER LAVATORY WITH MANUAL FAUCET. CW HW WASTE VENT DESCRIPTION: RECESSED WALL OUTLET BOX WITH ISOLATION VALVE. CW HW WASTE VENT
ADA COMPLIANT: NO.
1/2" 1/2" 1-1/4" 1-1/4" 1/4" - - -
COLOR: WHITE.
FIXTURE DIMENSIONS: 19” X 15” REMARKS: REMARKS:
CONSTRUCTION: FAUCET INLET SPACING TO MATCH LAVATORY OPENINGS. VERIFY FAUCET FINISH WITH
FAUCET VALVE OPERATION: MANUAL. ARCHITECT
L-1 HANDLE: DUAL-LEVER HANDLES. OB-1
SPOUT: INTEGRAL WITH BODY, VANDAL RESISTANT AERATOR. 1/2-GPM FLOW.
DRAIN: POP UP DRAIN

MODEL: KOHLER K-2211 "CAXTON" MODEL: KOHLER K-R45780 "LINWOOD" MODEL: OATEY #12K

DESCRIPTION: UNDERCOUNTER LAVATORY WITH MANUAL FAUCET. CW HW WASTE VENT DESCRIPTION: ROOF DRAIN WITH CAST IRON BODY, COMBINATION FLASHING COLLAR AND GRAVEL STOP, CW HW WASTE VENT
ADA COMPLIANT: YES. WITH THE FOLLOWING FEATURES:
1/2" 1/2" 1-1/4" 1-1/4" - - - -
COLOR: WHITE.
FIXTURE DIMENSIONS: 21"x14.5" REMARKS: 1. UNDERDECK CLAMP REMARKS:
CONSTRUCTION: FAUCET INLET SPACING TO MATCH LAVATORY OPENINGS. VERIFY FAUCET FINISH WITH 2. ADJUSTABLE INSULATION EXTENSION SEE FLOOR PLANS FOR STORM
FAUCET VALVE OPERATION: MANUAL. ARCHITECT 3. SUMP RECEIVER PIPING SIZE REQUIREMENTS.
L-2 HANDLE: DUAL-LEVER HANDLES. RD-1 4. CAST IRON VANDAL PROOF DOME
SPOUT: INTEGRAL WITH BODY, VANDAL RESISTANT AERATOR. 1/2-GPM FLOW. 5. REQUIRED GASKETS
DRAIN: GRID STRAINER
ADA INSULATION KIT: PROVIDE SUPPLY AND DRAIN SOFT MOLDED INSULATION KITS FROM FIXTURE TO
WALL. COVERINGS TO BE CUSHIONED JACKET PLASTIC COVERING WITH SELF STICKING FASTENING
SYSTEM.
MODEL: KOHLER K-2214 "LADENA" MODEL: KOHLER K-R45780 "LINWOOD" MODEL: J.R. SMITH #1010

DESCRIPTION: METAL WASHING MACHINE BOX. CW HW WASTE VENT DESCRIPTION: OVERFLOW ROOF DRAIN WITH CAST IRON BODY, COMBINATION FLASHING COLLAR AND CW HW WASTE VENT
CONSTRUCTION: RECESSED BOX AND FACEPLATE, TWO 3/4" HOSE CONNECTIONS WITH SHUT-OFF GRAVEL STOP, WITH THE FOLLOWING FEATURES:
VALVES, 2" STANDPIPE AND DRAIN. 3/4" 3/4" 2" 2" - - - -
REMARKS: PROVIDE FIRE RATED 1. UNDERDECK CLAMP REMARKS:
OUTLET BOX WHEN INSTALLED IN 2. ADJUSTABLE INSULATION EXTENSION SEE FLOOR PLANS FOR STORM
WMB-1 FIRE RATED WALL. 3. SUMP RECEIVER PIPING SIZE REQUIREMENTS.
OD-1 4. CAST IRON VANDAL PROOF DOME
5. REQUIRED GASKETS
6. 2" OVERFLOW STANDPIPE
MODEL: GUY GRAY B200 OR EQUAL
METAL WASHING MACHINE BOX
MODEL: J.R. SMITH #1010 No. Description Date
DESCRIPTION: FLOOR DRAIN WITH CAST IRON BODY, FLASHING COLLAR, 5" - 6" ROUND, ADJUSTABLE CW HW WASTE VENT DESCRIPTION: DOWNSPOUT NOZZLE WITH CAST-BRONZE BODY WITH THREADED INLET FOR PIPE SIZE CW HW WASTE VENT
NICKEL BRONZE GRATE. INDICATED ONPLANS, AND CAST-BRONZE WALL FLANGE WITH MOUNTING HOLES. FLANGE SHALL
- - 2" 1-1/2" - - - -

D-1
- - 3" 1-1/2
SERVE AS ANCHOR.

1. FINISH: NICKEL BRONZE FINISH


REMARKS:
SEE FLOOR PLANS FOR STORM
SAGE
- - 4" 2"
REMARKS:
SEE FLOOR PLANS FOR WASTE
DN-1
2. PROVIDE BIRD SCREEN PIPING SIZE REQUIREMENTS.
DEVELOPMENT
MODEL: J.R. SMITH #2010
AND VENT SIZE REQUIREMENTS.
GROUP
MODEL: J.R. SMITH #1770
DESCRIPTION: FLOOR DRAIN WITH CAST IRON BODY, FLASHING COLLAR, 8" ROUND MEDIUM DUTY GRATE. CW HW WASTE VENT DESCRIPTION: WALL HYDRANT WITH THE FOLLOWING FEATURES: NONFREEZE, AUTOMATIC DRAINING, CW HW WASTE VENT
[AND TRAP PRIMER CONNECTION] ANTIBACKFLOW TYPE, KEY OPERATION, 3/4" NPS THREADED OR SOLDER JOINT INLET, AND GARDEN
- - 2" 1-1/2" 3/4" - - -
-
-
-
-
3"
4"
1-1/2
2"
HOSE THREADS ON OUTLET. INCLUDE OPERATING KEY FOR EACH HYDRANT.

1. TYPE: SURFACE MOUNT


REMARKS: BENSON
2. FINISH: ROUGH BRASS
D-2 REMARKS:
SEE FLOOR PLANS FOR WASTE
WH-1 3. OPERATION: KEY-OPERATED
MULTIFAMILY
AND VENT SIZE REQUIREMENTS.

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_BRegier.rvt


MODEL: J.R. SMITH #2110 MODEL: WOODFORD MODEL #65

CW HW WASTE VENT CW HW WASTE VENT


DESCRIPTION: GARAGE DRAIN WITH CAST IRON BODY, SEDIMENT BUCKET, FLASHING COLLAR, 12"
ROUND REMOVABLE MEDIUM DUTY CAST IRON GRATE.
- - - -
DESCRIPTION: ROOF HYDRANT WITH THE FOLLOWING FEATURES: NONFREEZE, CAST IRON, AUTOMATIC
DRAINING, VACUUM BREAKER BACKFLOW PREVENTER, 3/4" NPS THREADED OR SOLDER JOINT INLET, 1" - -
PLUMBING FIXTURE
AND GARDEN HOSE THREADS ON OUTLET.
REMARKS:
SEE FLOOR PLANS FOR WASTE 1. TYPE: SURFACE MOUNT
REMARKS:
PROVIDE 3/4" DRAIN TO NEAREST
SCHEDULE
AND VENT SIZE REQUIREMENTS. RH-1 MOP SINK
2. OPERATION: MANUFACTURER'S STANDARD
GD-1 3. LENGTH AS REQUIRED FOR INSTALLING VALVE MINIMUM 30" ABOVE ROOF DECK.

MODEL: J.R. SMITH #2230 MODEL: WOODFORD MODEL RHY2-MS

DESCRIPTION: AREA DRAIN WITH CAST IRON BODY, FLASHING COLLAR AND SEEPAGE OPENINGS, 11" CW HW WASTE VENT DESCRIPTION: FLOOR MOUNTED MOP SINK WITH WALL MOUNTED FAUCET. CW HW WASTE VENT
SQUARE GRATE WITH THE FOLLOWING FEATURES: ADA COMPLIANT: NOT REQUIRED
- - 2" - 3/4" 3/4" 3" 1-1/2"
FIXTURE DIMENSIONS: 24" x 24" X 12" HIGH
1. UNDERDECK CLAMP - - 3" - FIXTURE CONSTRUCTION: TERRAZZO . RIM GUARD: STAINLESS STEEL. REMARKS:
2. ADJUSTABLE INSULATION EXTENSION FAUCET: ROUGH CHROME, WIDESPREAD CAST BRASS WITH SUPPLIES 8" ON CENTER.
- - 4" -
3. SUMP RECEIVER FAUCET MOUNTING: WALL CENTERED ON FIXTURE. FAUCET HANDLE: DUAL LEVER. 119 SOUTH 49TH AVENUE
AD-1 4. VANDAL PROOF GRATE REMARKS: MS-1 FAUCET SPOUT: INTEGRAL VACUUM BREAKER, PAIL HOOK, AND HOSE THREAD OUTLET.
5. SECONDARY FLASHING CLAMP SEE FLOOR PLANS FOR WASTE WALL BRACE: ASSEMBLY WITH WALL BRACKET AND SUPPORT TO FAUCET SPOUT. OMAHA, NEBRASKA 68132
6. NICKEL BRONZE GRATE AND VENT SIZE REQUIREMENTS. (402)551-0800
MEI PROJECT NO: 19164
MODEL: WILLIAMS SB-900
ARY N PROJECT: 17073
MODEL: J.R. SMITH #1470 [VERIFY ACCESSORIES AND GRATE FINISH WITH ARCHITECT AND PLANS] "SERVICECEPTOR" MODEL: KOHLER K-8907 "KINLOCK"
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
REMARKS: solely for the limited purpose of construction of this project or archiving.

8/26/2019 3:10:11 PM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
(1) SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS INCLUDING STOPS, FITTINGS AND ALL OTHER SPECIALTIES.
(2) PICTURES OF FIXTURES DO NOT INDICATE ACTUAL FIXTURE SPECIFIED. PICTURES ARE GRAPHICAL IN NATURE. SEE DESCRIPTION FOR ACTUAL FIXTURE AND MODEL. note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

M7.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. MINIMUM SIZE FOR BRANCH CIRCUIT CONDUITS SHALL BE 1/2." MINIMUM
DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS WHERE
LARGER CONDUITS ARE REQUIRED.

2. AT CONTRACTOR'S OPTION, THE USE OF MULTI-WIRE BRANCH CIRCUITS IS ALLOWED. PROVIDE


MEANS TO SIMULTANEOUSLY DISCONNECT ALL CIRCUIT BREAKERS SHARING A COMMON
NEUTRAL.

3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL LIGHTING AND POWER BRANCH CIRCUITS.

4. COORDINATE ROUTING OF EXPOSED CONDUIT WITH OWNER AND GENERAL CONTRACTOR


PRIOR TO ROUGH IN. MOUNT EXPOSED CONDUIT TIGHT AND PARALLEL TO STRUCTURE.

F F 9
22

KEYNOTES
13 10

22

10

F
8 8

8 8
N. STAIR
GARAGE
7 7 020
7E 7E 001 7E
nE 14 nE 10
13

nE 8 8

nE

7 7

17

11 11
14

nE
F

11 STORM 11
SHELTER
006
F

7E 7E
F
11 11

F 14

nE
11

17

F
TRASH
nE 004
7
12
7 E5.01 7
12 11 11
12
ELEVATOR F
12
003

11
nS F
VESTIBULE
F
002

No. Description Date

nE nE
10 SAGE
DEVELOPMENT
S. STAIR
7E 7 7E 021
14
F

GROUP
10

BENSON
MULTIFAMILY
MECHANICAL 13
005
17

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


F

11 11 11

'MSBR'
'CT' 'DPH' 'HG'
F F LOWER LEVEL PLAN -
LIGHTING

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 LOWER LEVEL - LIGHTING MEI PROJECT NO: 19164


RY N PROJECT: 17073
E1.00
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:20 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E1.00
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. MINIMUM SIZE FOR BRANCH CIRCUIT CONDUITS SHALL BE 1/2." MINIMUM
DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS WHERE
LARGER CONDUITS ARE REQUIRED.

2. AT CONTRACTOR'S OPTION, THE USE OF MULTI-WIRE BRANCH CIRCUITS IS ALLOWED. PROVIDE


MEANS TO SIMULTANEOUSLY DISCONNECT ALL CIRCUIT BREAKERS SHARING A COMMON
NEUTRAL.
1 1 1 1 1 1 3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL LIGHTING AND POWER BRANCH CIRCUITS.
E3.01 E3.01 E3.01 E3.01 E3.01 E3.01
4. COORDINATE ROUTING OF EXPOSED CONDUIT WITH OWNER AND GENERAL CONTRACTOR
PRIOR TO ROUGH IN. MOUNT EXPOSED CONDUIT TIGHT AND PARALLEL TO STRUCTURE.

10 KEYNOTES

UNIT J UNIT J UNIT J UNIT J UNIT J UNIT J


139 138 136 134 132 130

3
E3.02 10
UNIT 2-C
140

25 17 25 25 25 17 25 25 17 25 25 17 25
26 nS 26 26 nS
nS 26 26 26
25 25 25 25 25 25 13 10
13 F F

F 25

25 UNIT 1-C
11
25 137

PAD MOUNTED nS
SWITCH 25
17
11

5
E3.01 26 6
E3.01
UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 135 133 131
141 26 3
E3.01
25

TRANSFORMER UNIT S-B


143

25
3 3 4
nS F E3.01 E3.01 E3.01
UNIT 1-B
SINGLE PHASE 142 25
TRANSFORMER
17

25 13 23

5 23
E3.01 17 F
23
23
nS
23 24
23
24 GAME
24 13
23 ROOM 23
014 17 9
23 23 23 20

24 RENTAL F
23 20
24 ROOM
1P WOMEN'S
015 4PD
23 RR
012 3 4 4
20 23 E3.01 E3.01
F 1P nS E3.01
23 nS 23 18
MEN'S RR
23
013
19 11
23 nS

2PD
23
23 11 UNIT S-B UNIT 1-A UNIT 1-A
23 HVAC 151 153 155
23 010
23 'H1' 11
11 23 23 7
STORAGE 4PD 23 E5.01
011
23 23
F
F F
23 17
nS
23
23
13 23
23 nS No. Description Date
23
23
13
23

23 17
23 23 F 25 25
26 26
25
F
25 10 SAGE
21 21
OFFICE
F
13
25 17 nS 25 25 nS 17 25 13
DEVELOPMENT
F

23 008 2PD 17

16 GROUP
21
23 21
10
24 MAIL PACKAGE
019 ROOM 16 FITNESS
24 23 022 CENTER

nS
11
007
BENSON
nS
23
16 UNIT S-A
150
UNIT J
152
UNIT J
154
MULTIFAMILY
BUSINESS

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


CENTER
23 23
018 13
16 10

9
FIRST FLOOR PLAN -
LIGHTING
2 1 1
E3.01 E3.01 E3.01

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 FIRST FLOOR PLAN - LIGHTING MEI PROJECT NO: 19164


RY N PROJECT: 17073
E1.01
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:22 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E1.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. MINIMUM SIZE FOR BRANCH CIRCUIT CONDUITS SHALL BE 1/2." MINIMUM
DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS WHERE
LARGER CONDUITS ARE REQUIRED.

2. AT CONTRACTOR'S OPTION, THE USE OF MULTI-WIRE BRANCH CIRCUITS IS ALLOWED. PROVIDE


MEANS TO SIMULTANEOUSLY DISCONNECT ALL CIRCUIT BREAKERS SHARING A COMMON
NEUTRAL.
1 1 1 1 1 1
E3.01 E3.01 E3.01 E3.01 E3.01 E3.01 3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL LIGHTING AND POWER BRANCH CIRCUITS.

4. COORDINATE ROUTING OF EXPOSED CONDUIT WITH OWNER AND GENERAL CONTRACTOR


PRIOR TO ROUGH IN. MOUNT EXPOSED CONDUIT TIGHT AND PARALLEL TO STRUCTURE.

10 KEYNOTES

UNIT J UNIT J UNIT J UNIT J UNIT J UNIT J


239 238 236 234 232 230

10
3 UNIT 2-C
E3.02 240

17 25 25 26 26 25 17 25 26 26 25 17 25 26 26 25 17 25
25
nS nS nS 13
13 25 F 25 25 25 25 F 25 10
F
25

25 11
UNIT 1-C
237
25
nS
25
11
17

11
26 'RMC2'
11 6
E3.01 UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 26
235 233 231
5 241 3
E3.01 E3.01
25

UNIT S-B
243

F
25
3 3 4
nS E3.01 E3.01 E3.01
UNIT 1-B
242 25

17 30 30
FESTOON LIGHTING ACROSS
COURTYARD (TYP)
3
13 E3.01
25
5 UNIT S-B
E3.01 13 245
25

17 F

25
nS

25 3
E3.01

UNIT S-B
247
25 3 4 4
UNIT 1-B 26 E3.01 E3.01 E3.01
5 244
E3.01
26

25

UNIT S-B UNIT 1-A UNIT 1-A


UNIT 1-B 251 253 255
25
246

17
25 23 17
7
E5.01 23
nS F

5
25 23
E3.01
13
25
13 nS
No. Description Date

23 23 F 25 25 25 26 26 25 F
nS
25 10 SAGE
13 25 17 nS
25 25 25
17
13
DEVELOPMENT
GROUP
10

UNIT 2-A
248
BENSON
UNIT S-A
249
UNIT S-A
250
UNIT J
252
UNIT J
254
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


10

SECOND FLOOR PLAN -


LIGHTING
1 2 2 1 1
E3.02 E3.01 E3.01 E3.01 E3.01

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 SECOND FLOOR PLAN - LIGHTING MEI PROJECT NO: 19164


RY N PROJECT: 17073
E1.02
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:23 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E1.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. MINIMUM SIZE FOR BRANCH CIRCUIT CONDUITS SHALL BE 1/2." MINIMUM
DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS WHERE
LARGER CONDUITS ARE REQUIRED.

2. AT CONTRACTOR'S OPTION, THE USE OF MULTI-WIRE BRANCH CIRCUITS IS ALLOWED. PROVIDE


MEANS TO SIMULTANEOUSLY DISCONNECT ALL CIRCUIT BREAKERS SHARING A COMMON
NEUTRAL.
2 1 1 1 1
E3.02 E3.01 E3.01 E3.01 E3.01 3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL LIGHTING AND POWER BRANCH CIRCUITS.

4. COORDINATE ROUTING OF EXPOSED CONDUIT WITH OWNER AND GENERAL CONTRACTOR


PRIOR TO ROUGH IN. MOUNT EXPOSED CONDUIT TIGHT AND PARALLEL TO STRUCTURE.

10 KEYNOTES

UNIT J UNIT J UNIT J UNIT J


336 334 332 330
UNIT 2-B
338

10
UNIT 2-C
340

17 25 25 26 26 25 17 25 26 26 25 17 25 26 26 25
nS 17 25
25
nS nS 13
13 25 F 25 25 25 25 F 25 10
F
3 25
E3.02
25 11
UNIT 1-C
nS 337
25

25
11
17

11
26 'RMC3'
'H3'
11 6
E3.01 UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 26
335 333 331
5 341 3
E3.01 E3.01
25

UNIT S-B
343

F
25
3 3 4
nS E3.01 E3.01 E3.01
UNIT 1-B
342 25

17

3
E3.01
25 13

5 UNIT S-B
E3.01 13 345
25

17
F
25
nS

25 3
E3.01
UNIT S-B
347
25 3 4 4
UNIT 1-B 26 E3.01 E3.01 E3.01
5 344
E3.01
26

25

UNIT S-B UNIT 1-A UNIT 1-A


UNIT 1-B 351 353 355
25
346

17
25 23 17
7
E5.01
23
nS
F
5
25 23
E3.01

13
25
13 No. Description Date

23 23 F 25
nS
25 25 26 26 25 F
nS
25 10 SAGE
13 25 17 25 25 25 17 13
DEVELOPMENT
GROUP
10

UNIT 2-A
348
BENSON
UNIT S-A
349
UNIT S-A
350
UNIT J
352
UNIT J
354
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


10

THIRD FLOOR PLAN -


LIGHTING
1 2 2 1 1
E3.02 E3.01 E3.01 E3.01 E3.01

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 THIRD FLOOR PLAN - LIGHTING MEI PROJECT NO: 19164


RY N PROJECT: 17073
E1.03
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:26 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E1.03
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. MINIMUM SIZE FOR BRANCH CIRCUIT CONDUITS SHALL BE 1/2." MINIMUM
DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS WHERE
LARGER CONDUITS ARE REQUIRED.

2. AT CONTRACTOR'S OPTION, THE USE OF MULTI-WIRE BRANCH CIRCUITS IS ALLOWED. PROVIDE


MEANS TO SIMULTANEOUSLY DISCONNECT ALL CIRCUIT BREAKERS SHARING A COMMON
NEUTRAL.
2 1 1 1 1 3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL LIGHTING AND POWER BRANCH CIRCUITS.
E3.02 E3.01 E3.01 E3.01 E3.01
28 28 28 29 4. COORDINATE ROUTING OF EXPOSED CONDUIT WITH OWNER AND GENERAL CONTRACTOR
PRIOR TO ROUGH IN. MOUNT EXPOSED CONDUIT TIGHT AND PARALLEL TO STRUCTURE.

10 KEYNOTES

UNIT J UNIT J UNIT J UNIT J


436 434 432 430
UNIT 2-B
438
3
E3.02
10
UNIT 2-C
440

17 25 25 26 26 25 17 25 26 26 25 17 25 26 26 25 17 25
25 nS
nS nS 13
13 25 F 25 25 25 25 F 25 10
F
25

25
11 UNIT 1-C
437
25
nS 11
27 25
17
17
11 'ATS-ELEV'

26 6
11
E3.01
UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 26
435 433 431
3
5 441
E3.01
E3.01 25

UNIT S-B
443

F
25
3 3 4
nS E3.01 E3.01 E3.01
UNIT 1-B
442 25

17

3
E3.01
25 13

5 UNIT S-B
E3.01 13 445
25

17
nS
25 F
28

25 3
E3.01

UNIT S-B
447
25 3 4 4
UNIT 1-B 26 E3.01 E3.01 E3.01
444
5
E3.01
26

25

UNIT S-B UNIT 1-A UNIT 1-A


UNIT 1-B 451 453 455
25
446

17
25 23 17
7
E5.01 23
nS F

5 25 23
E3.01
13
25
13 nS No. Description Date

23 23 F 25
nS
25 25 26 26 25 F
nS 25 10 SAGE
13 25 17 25 25 25 17 13
DEVELOPMENT
GROUP
10

UNIT 2-A
448
BENSON
UNIT S-A
449
UNIT S-A
450
UNIT J
452
UNIT J
454
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


10

FOURTH FLOOR PLAN -


29 28 29 LIGHTING
1 2 2 1 1
E3.02 E3.01 E3.01 E3.01 E3.01

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800

1 FOURTH FLOOR PLAN - LIGHTING MEI PROJECT NO: 19164


RY N PROJECT: 17073
E1.04
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:29 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E1.04
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. MINIMUM DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS
WHERE LARGER CONDUITS ARE REQUIRED.

2. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.

3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL RECEPTACLE AND EQUIPMENT BRANCH
CIRCUITS.

G,48" G,48" G,WP,24"

KEYNOTES

N CO

N. STAIR
GARAGE

CO
020
001

N
G,48"

G,48"

G,48"

CO N
STORM
SHELTER
G,48" 006
G,48"
G,48"

G,48"

G,48"
N C

TRASH
O

004
7
E5.01 SP-1

G
ELEVATOR
003
G,48"
VESTIBULE
002

No. Description Date


S. STAIR
021

G,48" SAGE
DEVELOPMENT
N CO GROUP

MECHANICAL
G,48"
BENSON
'MSBR' 005
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


'CT' 'DPH' 'HG' G,48" G,48"
EF-2

LOWER LEVEL PLAN -


POWER

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
1 LOWER LEVEL - POWER MEI PROJECT NO: 19164
E2.00 RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:30 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E2.00
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. MINIMUM DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS
WHERE LARGER CONDUITS ARE REQUIRED.
1 1 1 1 1 1
2. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.
E3.01 E3.01 E3.01 E3.01 E3.01 E3.01
3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL RECEPTACLE AND EQUIPMENT BRANCH
CIRCUITS.

UNIT J UNIT J UNIT J UNIT J UNIT J UNIT J


139 138 136 134 132 130 KEYNOTES

3
E3.02

UNIT 2-C
140

T
TU-08C T

UNIT 1-C
137

PAD MOUNTED
SWITCH

5
E3.01 6
E3.01 UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 135 133 131
3
141
E3.01
TU-05C

UNIT S-B
TRANSFORMER
143

3 3 4
E3.01 E3.01 E3.01
UNIT 1-B
SINGLE PHASE 142
TRANSFORMER
T

T
G,WP,24" G,WP,24"

T
5
E3.01
TU-18C
TU-12C
T

44" 4
GAME (TYP.)
G,44" ROOM E5.01
G,44" 60"
014
60" 60" TV G,WP,24"
60" TV
TU-12C T G,WP,24" G,WP,24"
RENTAL
ROOM
G,44"
015 TU-05C
TU-12C
WOMEN'S
RR 3 4 4
012 E3.01 E3.01 E3.01
G,44"
EF-5
TU-05C
EF-6
G,44"
MEN'S RR
013 EWH-2
TU-12C V 60" EF-4
T
60" T

FSD UNIT S-B UNIT 1-A UNIT 1-A


151 153 155

G,WP,24" HVAC
STORAGE
4 'H1' 010
011 (TYP.)
E5.01 7
E5.01
T
T
4
(TYP.)
TU-05C E5.02

T
TU-08C
TU-05C

T
No. Description Date
G,WP,24" T
TU-05COFFICE TU-08C
008
FC-2.5
SAGE
TU-18C
DEVELOPMENT
T

MAIL PACKAGE
GROUP
019 ROOM
022 FITNESS
CENTER
007

TU-18C

BUSINESS
T
44"
UNIT S-A
150
UNIT J
152
UNIT J
154 BENSON
CENTER
018
44"
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


G,WP,24"

G,WP,24"

2
E3.01
1
E3.01
1
E3.01 FIRST FLOOR PLAN -
POWER

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
1 FIRST FLOOR PLAN - POWER MEI PROJECT NO: 19164
E2.01 RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:34 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E2.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. MINIMUM DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS
WHERE LARGER CONDUITS ARE REQUIRED.
1 1 1 1 1 1 2. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.
E3.01 E3.01 E3.01 E3.01 E3.01 E3.01
3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL RECEPTACLE AND EQUIPMENT BRANCH
CIRCUITS.

UNIT J UNIT J UNIT J UNIT J UNIT J UNIT J


239 238 236 234 232 230 KEYNOTES
3
E3.02

UNIT 2-C
240

UNIT 1-C
237
T

'RMC2' 6
E3.01 UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 235 233 231
241 3
E3.01

UNIT S-B
5 243
E3.01

3 3 4
E3.01 E3.01 E3.01
UNIT 1-B
242

3
E3.01

UNIT S-B
5
E3.01 245

3
E3.01

UNIT S-B
247
3 4 4
UNIT 1-B E3.01 E3.01 E3.01
244 4
5 (TYP.)
E3.01 E5.02

FSD UNIT S-B UNIT 1-A UNIT 1-A


UNIT 1-B 251 253 255
246 T

T
7
E5.01

5
E3.01
T

T
No. Description Date

T
SAGE
DEVELOPMENT
UNIT 2-A
GROUP
248

UNIT S-A
249
UNIT S-A
250
UNIT J
252
UNIT J
254 BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


1
E3.02
2
E3.01
2
E3.01
1
E3.01
1
E3.01
SECOND FLOOR PLAN -
POWER

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
1 SECOND FLOOR PLAN - POWER MEI PROJECT NO: 19164
E2.02 RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:36 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E2.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. MINIMUM DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS
WHERE LARGER CONDUITS ARE REQUIRED.

2 1 1 1 1 2. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.


E3.02 E3.01 E3.01 E3.01 E3.01
3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL RECEPTACLE AND EQUIPMENT BRANCH
CIRCUITS.

UNIT J UNIT J UNIT J UNIT J


336 334 332 330 KEYNOTES
UNIT 2-B
338

T
3

T
E3.02
UNIT 2-C
340

T
T

UNIT 1-C
337
T

T
'H3'
'RMC3' 6
E3.01 UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 335 333 331
5 3
341
E3.01 E3.01

UNIT S-B
343

3 3 4
UNIT 1-B E3.01 E3.01 E3.01
342

3
E3.01

5 UNIT S-B
E3.01
345

3
E3.01

UNIT S-B
347
3 4 4
UNIT 1-B E3.01 E3.01 E3.01
5 344 4
(TYP.)
E3.01 E5.02

FSD UNIT S-B UNIT 1-A UNIT 1-A


UNIT 1-B 351 353 355
346 T

T
7
T E5.01

5
E3.01
T

T
No. Description Date
T

SAGE
DEVELOPMENT
UNIT 2-A
GROUP
T

348

UNIT S-A
349
UNIT S-A
350
UNIT J
352
UNIT J
354 BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


1
E3.02
2
E3.01
2
E3.01
1
E3.01
1
E3.01
THIRD FLOOR PLAN -
POWER

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
1 THIRD FLOOR PLAN - POWER MEI PROJECT NO: 19164
E2.03 RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:39 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E2.03
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
GENERAL NOTES
1. MINIMUM DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS
WHERE LARGER CONDUITS ARE REQUIRED.
2 1 1 1 1
E3.02 E3.01 E3.01 E3.01 E3.01 2. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.

3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL RECEPTACLE AND EQUIPMENT BRANCH
CIRCUITS.

UNIT J UNIT J UNIT J UNIT J


436 434 432 430 KEYNOTES
UNIT 2-B
3 438
E3.02

UNIT 2-C
440

UNIT 1-C
437
T

'ATS-ELEV' 6
E3.01 UNIT S-B UNIT S-B UNIT 1-A
UNIT 1-B 435 433 431
441 3
5
E3.01
E3.01

UNIT S-B
443

3 3 4
UNIT 1-B E3.01 E3.01 E3.01
442

3
E3.01

5 UNIT S-B
E3.01 445

3
E3.01

UNIT S-B
447
3 4 4
UNIT 1-B E3.01 E3.01 E3.01
444 4
5 (TYP.)
E3.01 E5.02

FSD UNIT S-B UNIT 1-A UNIT 1-A


UNIT 1-B 451 453 455
T
AC-1
446

7
E5.01

5
E3.01
T

T
No. Description Date

SAGE
DEVELOPMENT
UNIT 2-A
GROUP
448

UNIT S-A
449
UNIT S-A
450
UNIT J
452
UNIT J
454 BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


1
E3.02
2
E3.01
2
E3.01
1
E3.01
1
E3.01
FOURTH FLOOR PLAN -
POWER

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
1 FOURTH FLOOR PLAN - POWER MEI PROJECT NO: 19164
E2.04 RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:42 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E2.04
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. MINIMUM DATA/COMMUNICATIONS CONDUIT SIZE SHALL BE 1." SEE DRAWINGS FOR AREAS
WHERE LARGER CONDUITS ARE REQUIRED.

2. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.

3. PROVIDE A GREEN INSULATED GROUND WIRE IN ALL RECEPTACLE AND EQUIPMENT BRANCH
CIRCUITS.

KEYNOTES

HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5

HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5

HP-2.0 HP-2.0 G,WP G,WP G,WP G,WP G,WP

VRF-HP-1
HP-2.0 HP-2.0

1 HP-1.5 HP-1.5
E5.02
HP-1.5 HP-1.5 HP-1.5 HP-1.5
HP-1.5 HP-1.5
HP-1.5 HP-1.5

EMERGENCY
GENERATOR
HP-1.5 HP-1.5 HP-1.5 HP-1.5
HP-1.5 HP-1.5

HP-1.5 HP-1.5
G,WP G,WP
HP-1.5 HP-1.5

G,WP

VRF-HP-2

HP-1.5 HP-1.5

HP-1.5 HP-1.5 HP-1.5


G,WP

HP-1.5 HP-1.5

HP-1.5 HP-1.5
HP-1.5 HP-1.5

HP-1.5
HP-1.5
G,WP

VRF-HP-3

HP-1.5 HP-1.5

HP-1.5
G,WP

EF-3

VRF-HP-4
AC-1
HP-1.5 HP-1.5 HP-1.5 HP-1.5

HP-1.5 HP-1.5 HP-1.5 HP-1.5


HP-1.5 HP-1.5

HP-1.5 HP-1.5
G,WP
HP-1.5 VRF-HP-5
HP-1.5 HP-1.5
G,WP

G,WP
HP-2.0 HP-2.0
VRF-HP-6 No. Description Date
HEAT PUMP (TYP.) (TYP)
HP-2.0 2
E2.05

EQUIP TAG DISCONNECT SIZE FEEDER SIZE


HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5
SAGE
HP-1.5 30/2 DISC. SW. 2#12, #12G. - 1/2"C.
HP-2.0 30/2 DISC. SW. 2#10, #10G. - 1/2"C.
VRF-HP-7
HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5 HP-1.5
DEVELOPMENT
NEMA 3R N.F.
DISCONNECT G,WP G,WP
GROUP
(TYP.)

BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


DUPLEX GFI RECEPTACLE RACK CONDUITS WITH
SEALTITE FLEXIBLE
WITH WEATHERPROOF REFRIGERANT LINES
CONDUIT TO DISCONNECT
COVER
NEMA 3R JUNCTION BOX
INSTALLED ON SIDE OF
ROOF PLAN - POWER
ROOF HOOD.

6 #10 AND #10G IN 1-1/4"C. TO APARTMENT LOAD CENTERS


VIA MECH. CHASE. TRANSITION TO 1/2"C. FOR EACH APT.
LOAD CENTER HOMERUN. (3 UNITS)

2 HEAT PUMP CONNECTION DETAIL


E2.05 NOT TO SCALE

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
1 ROOF PLAN - POWER MEI PROJECT NO: 19164
E2.05 RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
0' 2' 4' 8' 16' solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:44 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E2.05
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES AGENCY APPROVAL
1. CONNECT RECEPTACLE SERVING DWELLING UNIT REFRIGERATOR TO ONE OF THE SMALL-
APPLIANCE CIRCUITS, PROTECTED BY UPSTREAM GFI DEVICE. DO NOT PROVIDE GFI
RECEPTACLE FOR REFRIGERATOR.
6 6
G,WP,24" G,WP,24" 2. MINIMUM SIZE FOR BRANCH CIRCUIT CONDUITS SHALL BE 1/2".
G,WP,24" G,WP,24"
3. UNITS INDICATED ARE TYPICAL. COORDINATE RECEPTACLE LOCATIONS WITH ACTUAL FIELD
3 3
MEASUREMENTS TO COMPLY WITH NEC SPACING REQUIREMENTS. VERIFY KITCHEN
6 6 APPLIANCE LOCATIONS WITH OWNER AND ADJUST ACCORDINGLY.
1 1
4. PROVIDE 'AFCI' TYPE CIRCUIT BREAKER OR DEVICE (WHERE NEUTRALS ARE SHARED) FOR ALL
3 3 120 VOLT, SINGLE PHASE 15- AND 20-AMPERE BRANCH CIRCUITS AS REQUIRED BY NEC.

1 1 5. PROVIDE 'GFCI' TYPE RECEPTACLES FOR ALL 120 VOLT, SINGLE PHASE, 15- AND 20-AMPERE
1 1 RECEPTACLES PER NEC 210.8. PROVIDE 'GFCI' TYPE RECEPTACLES FOR ALL RECEPTACLES
INSTALLED WITHIN 6'-0" OF WATER, PER NEC 210.8.A.9.
(TYP.) E509
(TYP.) E508 1 1 1 1 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12.
3
(TYP.) E508 7. MINIMUM SIZE FOR BRANCH CIRCUIT WIRING SHALL BE #12 AWG FOR 20 AMP CIRCUITS AND #14
E508 (TYP.) FOR 15 AMP CIRCUITS.

1 1 8. COORDINATE FINAL DEVICE AND FIXTURE ROUGH-IN LOCATIONS WITH OWNER. ANY
INSTALLATION DEVIATION BETWEEN DRAWINGS AND ACTUAL LOCATIONS SHALL BE
E501

T
COORDINATED WITH OWNER/ARCHITECT PRIOR TO ROUGH-IN.
1 1 1 1

4
(TYP.) E508 G,44"
1 1 9. ALL KITCHEN RECEPTACLES SHALL BE GFI TYPE PER NEC 210.8.
(TYP.) E509 G,44" G,44"
10. VERIFY RECEPTACLE MOUNTING HEIGHTS WITH FINAL CASEWORK AND UNIT FINISH
DF-1 '1A' 60" 5 E509 (TYP.)
60" 5 60" DRAWINGS.
E505 3 3 E505 5 3 3 (TYP.) E509 E505
3 3
3

11. VERIFY FINAL LOCATION OF WASHER/DRYER PRIOR TO ROUGH-IN. COORDINATE WITH


E501 GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR.

T
G,44" G,44"
EWH-1 5
FC-1.5

E501 5

T
E506 E510 G,44" 5 12. GANG ADJACENT DEVICES WHERE POSSIBLE.
E503 E501 G,44"

T
E502 F 3 3 3
F 13. SEE "APARTMENT UNIT ELECTRICAL SYMBOLS" ON SHEET E6.01 FOR ADDITIONAL
3 F
E510 5 E510 E510 INFORMATION.
5
44" G,44" E506 E506 5 E506
3

5 14. DO NOT MOUNT DEVICES BACK-TO-BACK.


G,42" E504 G,42" G,42"
3 4 4 4 15. SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 36" OF AN HVAC DIFFUSER OR RETURN
44" F 5 60" G,44" G,44" G,44"
5 5 AIR GRILLE PER NFPA 72.
E505 5

E504 'SB' 'SA' 'J' E504


1 5 G,44" 44" 44"
EF-1 EF-1 EF-1 44"
2
E502 96" EWH-1

FC-1.5
96" E502 E502

FC-1.5

FC-1.5
96" 96" 1 E503 1 E503 1 96" 96"
EF-1 96" 5 E504 44" 44" E507 E503 E507
E507 2 EWH-1 44" 44" 2 2 44" 44"
4 44" EWH-1
G,42" 3 3 DF-1 DF-1 3
96" 3 KEYNOTES

E507
E501 PROVIDE A 4" SQUARE BOX WITH SINGLE-GANG PLASTER RING AND 1/2"
CONDUIT WITH PULLSTRING TO HEAT PUMP. COORDINATE INSTALLATION
4 ENLARGED ELECTRICAL PLAN - 1 BED "A" 3 ENLARGED ELECTRICAL PLAN - STUDIO "B" 2 ENLARGED ELECTRICAL PLAN - STUDIO "A" 1 ENLARGED ELECTRICAL PLAN - JUNIOR HEIGHT WITH MECHANICAL CONTRACTOR.
E502 FAN COIL PROVIDED WITH FACTORY DISCONNECT/CIRCUIT BREAKER.
E3.01 E3.01 E3.01 E3.01 PROVIDE ELECTRICAL CONNECTION TO MECHANICAL UNITS. PROVIDE
2#8,#10G-3/4"C. FOR ALL FC-1.5. PROVIDE 2#X,#XG-1"C. FOR ALL FC-2.0.
0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8' 0' 1' 2' 4' 8' PROVIDE 2#X,#XG-1"C. FOR ALL FC-2.5. SEE PANEL SCHEDULES FOR
REQUIRED CIRCUIT BREAKER SIZES.
E503 PROVIDE 2-#X, #XG-3/4"C FOR EHW-1. PROVIDE ELECTRICAL CONNECTION
FROM CIRCUIT BREAKER TO WATER HEATER. PROVIDE CIRCUIT BREAKER
PADLOCK/LOCKOUT ACCESSORY. SEE PANEL SCHEDULE FOR REQUIRED
CIRCUIT BREAKER SIZE.
E504 RECEPTACLE SHALL BE CONNECTED AS FEED-THRU FROM ADJACENT GFCI.
E505 RECEPTACLE FOR MICROWAVE OR OTR HOOD. VERIFY EXACT MOUNTING
HEIGHT WITH CABINETS AND APPLIANCES.
G,WP,24"
E506 RECEPTACLE FOR DISHWASHER. SEE DETAIL 6/E5.01.
E507 PROVIDE DEDICATED SPACE FOR FUTURE TELECOMMUNICATION BOX
6 MOUNTED IN 16" O.C. STUD SPACE. COORDINATE REQUIREMENTS WITH
OWNER.
E508 PROVIDE SINGLE STATION SMOKE DETECTORS WITHIN APARTMENT UNIT
3 WITH AUXILLARY CONTACTS (SEE SPECIFICATIONS). INTERLOCK DETECTORS
WITHIN UNIT PER NFPA REQUIREMENTS. CONNECT FAN COIL UNIT AND
E502 RESTROOM EXHAUST FAN TO AUXILLARY CONTACTS TO SHUT DOWN IN THE
E509 (TYP.) EVENT OF ALARM CONDITION IN RESPECTIVE UNIT.
FC-1.5 F 1 1 E509 PROVIDE SINGLE GANG CADDY RING FOR DATA ROUGH-IN.
3
E510 RECEPTACLE FOR GARBAGE DISPOSAL. SEE DETAIL 6/E5.01.

E503 1
3 EWH-1 1 1
E501
E501

T
T
G,44" (TYP.) E509
1

4
44" 5
'1C' (TYP.) E508 F
60"

3
E505
44"
(TYP.) E508 96"
5
96" G,44" 1 1 '1B' 1 1
DF-1
E507 3 APARTMENT ELECTRICAL SYMBOLS
5
DF-1 E510 44" SYMBOL DESCRIPTION
3 E506 G,44" GENERAL
4 44" TELEPHONE OUTLET - PROVIDE 3/4" ENT TO TERMINAL BOX
G,44" 5
5 96"
TV TELEVISION/VIDEO OUTLET - PROVIDE 3/4" ENT TO TERMINAL BOX
DUPLEX RECEPTACLE
G,42" 60" G
E507 "G" DENOTES GFCI TYPE, FEED-THRU WIRING METHOD IS ALLOWED
G,42" E505 SINGLE SHADING DENOTES SPLIT WIRED DEVICE
EF-1 4 96" FLOOR MOUNTED DUPLEX RECEPTACLE - SEE SPECIFICATIONS
44" E504 5 SINGLE RECEPTACLE
G,44" DRYER RECEPTACLE NEMA 14-30 (125/250V 30A) 3#10,#10G- 3/4"C.
RANGE RECEPTACLE NEMA 14-50 (125/250V 50A) 3#8,#10G-1"C.
NON-FUSED DISCONNECT SWITCH - SIZE PER DRAWINGS
2 E506
1 1 T THERMOSTAT BY MECHANICAL - PROVIDE 1-GANG BOX AND 1/2"C. CONCEALED TO FAN COIL
5 THERMOSTAT FOR ELECTRIC BASEBOARD HEAT - SEE "ELECTRIC HEAT SCHEDULE"-
T
PROVIDE 1-GANG BOX AND 1/2"C. CONCEALED TO BASEBOARD HEATER.
EF-1 F FIRE ALARM SPEAKER/STROBE COMBINATION - CONNECT TO HOUSE FIRE ALARM SYSTEM

E503 5 STAND ALONE SINGLE STATION FIRE ALARM SMOKE DETECTOR - SEE SPECIFICATIONS.
CO INTERLOCK PER INTERNATIONAL FIRE CODE. CONNECT UNSWITCHED TO LIGHTING CIRCUIT.
EWH-1 SR CO = PROVIDE COMBINATION SMOKE/CARBON MONOXIDE DETECTOR
3 3 SR = SLEEPING ROOM SINGLE STATION TYPE

2 G,44" PUSH BUTTON


44" G,44" G,44" F J-BOX WITH BLANK COVER FOR FUTURE FAN SPEED CONTROL
FC-1.5 F ADA ADA FIRE ALARM STROBE - ACTIVATED FROM SINGLE STATION DETECTOR WITHIN UNIT
ADA STAND ALONE SINGLE STATION SMOKE DETECTOR/ADA STROBE LIGHT COMBINATION 1 Revision 1 Date 1
LIGHTING PANEL
TELEPHONE/CATV TERMINAL CABINET
BRANCH CIRCUIT CONCEALED IN CEILING OR WALL No. Description Date
BRANCH CIRCUIT CONCEALED IN FLOOR
6 ENLARGED ELECTRICAL PLAN - 1 BED "C" 5 ENLARGED ELECTRICAL PLAN - 1 BED "B" HOMERUN TO PANEL (QUANTITY OF ARROWS INDICATES QUANTITY OF CIRCUITS)
SPECIAL PURPOSE HOMERUN AS INDICATED
E3.01

0' 1' 2' 4' 8'


E3.01

0' 1' 2' 4' 8'


#
LUMINAIRE: NUMBER DENOTES FIXTURE TYPE, SEE CORRESPONDING
NUMBER IN FIXTURE SCHEDULE
INDUSTRIAL FIXTURE

WALL BRACKET FIXTURE


SAGE
CEILING FIXTURE
WALL FIXTURE
TRACK FIXTURE
DEVELOPMENT
S
S2
S3
S4
SINGLE POLE SWITCH
DOUBLE POLE SWITCH
3 - WAY SWITCH
4 - WAY SWITCH
GROUP
WALL BOX DIMMER, SEE SPECIFICATIONS.

BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


ENLARGED ELECTRICAL
PLANS

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164
RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:48 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E3.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
GENERAL NOTES
AGENCY APPROVAL
1. CONNECT RECEPTACLE SERVING DWELLING UNIT REFRIGERATOR TO ONE OF THE SMALL-
APPLIANCE CIRCUITS, PROTECTED BY UPSTREAM GFI DEVICE. DO NOT PROVIDE GFI
RECEPTACLE FOR REFRIGERATOR.

2. MINIMUM SIZE FOR BRANCH CIRCUIT CONDUITS SHALL BE 1/2".

3. UNITS INDICATED ARE TYPICAL. COORDINATE RECEPTACLE LOCATIONS WITH ACTUAL FIELD
4 MEASUREMENTS TO COMPLY WITH NEC SPACING REQUIREMENTS. VERIFY KITCHEN
APPLIANCE LOCATIONS WITH OWNER AND ADJUST ACCORDINGLY.
2 E502
G,42" 4. PROVIDE 'AFCI' TYPE CIRCUIT BREAKER OR DEVICE (WHERE NEUTRALS ARE SHARED) FOR ALL
120 VOLT, SINGLE PHASE 15- AND 20-AMPERE BRANCH CIRCUITS AS REQUIRED BY NEC.
DF-1
EWH-1 E503
FC-2.0 5. PROVIDE 'GFCI' TYPE RECEPTACLES FOR ALL 120 VOLT, SINGLE PHASE, 15- AND 20-AMPERE
3 96" RECEPTACLES PER NEC 210.8. PROVIDE 'GFCI' TYPE RECEPTACLES FOR ALL RECEPTACLES
E507 INSTALLED WITHIN 6'-0" OF WATER, PER NEC 210.8.A.9.
44" EF-1

3
44" 96" 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12.

1 7. MINIMUM SIZE FOR BRANCH CIRCUIT WIRING SHALL BE #12 AWG FOR 20 AMP CIRCUITS AND #14
T
G,WP,24" FOR 15 AMP CIRCUITS.
E501
1 8. COORDINATE FINAL DEVICE AND FIXTURE ROUGH-IN LOCATIONS WITH OWNER. ANY
6 6 3 INSTALLATION DEVIATION BETWEEN DRAWINGS AND ACTUAL LOCATIONS SHALL BE
COORDINATED WITH OWNER/ARCHITECT PRIOR TO ROUGH-IN.

3 3
3 3
9. ALL KITCHEN RECEPTACLES SHALL BE GFI TYPE PER NEC 210.8.
'2A' 1 3

3
2 10. VERIFY RECEPTACLE MOUNTING HEIGHTS WITH FINAL CASEWORK AND UNIT FINISH
G,44" DRAWINGS.
E510 EF-1

3
1 1
3 E506 G,44" F 11. VERIFY FINAL LOCATION OF WASHER/DRYER PRIOR TO ROUGH-IN. COORDINATE WITH
60"
3 E509 (TYP.) G,42" GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR.
E504
12. GANG ADJACENT DEVICES WHERE POSSIBLE.
G,44" 5
44" 5 4 13. SEE "APARTMENT UNIT ELECTRICAL SYMBOLS" ON SHEET E6.01 FOR ADDITIONAL
5 INFORMATION.
3
5 14. DO NOT MOUNT DEVICES BACK-TO-BACK.
E501

T
1 1

4
15. SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 36" OF AN HVAC DIFFUSER OR RETURN
F 3
AIR GRILLE PER NFPA 72.

3
1 1
(TYP.) E508
DF-1
'2B' 3
44"
(TYP.) E509
3
1 1 44"
E507
KEYNOTES
96" 96" G,42" E508 (TYP.)
1 1
3
4 E501 PROVIDE A 4" SQUARE BOX WITH SINGLE-GANG PLASTER RING AND 1/2"
G,42" G,44" CONDUIT WITH PULLSTRING TO HEAT PUMP. COORDINATE INSTALLATION
3 HEIGHT WITH MECHANICAL CONTRACTOR.
4 E502 FAN COIL PROVIDED WITH FACTORY DISCONNECT/CIRCUIT BREAKER.
2
1 PROVIDE ELECTRICAL CONNECTION TO MECHANICAL UNITS. PROVIDE
60" E505 2#8,#10G-3/4"C. FOR ALL FC-1.5. PROVIDE 2#X,#XG-1"C. FOR ALL FC-2.0.
EF-1 PROVIDE 2#X,#XG-1"C. FOR ALL FC-2.5. SEE PANEL SCHEDULES FOR
5 5 5 5 6
REQUIRED CIRCUIT BREAKER SIZES.
EWH-1 E503 PROVIDE 2-#X, #XG-3/4"C FOR EHW-1. PROVIDE ELECTRICAL CONNECTION
G,44" E510 G,WP,24" FROM CIRCUIT BREAKER TO WATER HEATER. PROVIDE CIRCUIT BREAKER
3
PADLOCK/LOCKOUT ACCESSORY. SEE PANEL SCHEDULE FOR REQUIRED
EF-1 G,44" G,44" G,44" 2
44" CIRCUIT BREAKER SIZE.
FC-2.0 E504 RECEPTACLE SHALL BE CONNECTED AS FEED-THRU FROM ADJACENT GFCI.
E505 RECEPTACLE FOR MICROWAVE OR OTR HOOD. VERIFY EXACT MOUNTING
E506 E504 E502 HEIGHT WITH CABINETS AND APPLIANCES.
E506 RECEPTACLE FOR DISHWASHER. SEE DETAIL 6/E5.01.
E507 PROVIDE DEDICATED SPACE FOR FUTURE TELECOMMUNICATION BOX
MOUNTED IN 16" O.C. STUD SPACE. COORDINATE REQUIREMENTS WITH
OWNER.
2 ENLARGED ELECTRICAL PLAN - 2 BED "B" 1 ENLARGED ELECTRICAL PLAN - 2 BED "A" E508 PROVIDE SINGLE STATION SMOKE DETECTORS WITHIN APARTMENT UNIT
WITH AUXILLARY CONTACTS (SEE SPECIFICATIONS). INTERLOCK DETECTORS
E3.02 E3.02 WITHIN UNIT PER NFPA REQUIREMENTS. CONNECT FAN COIL UNIT AND
RESTROOM EXHAUST FAN TO AUXILLARY CONTACTS TO SHUT DOWN IN THE
0' 1' 2' 4' 8' 0' 1' 2' 4' 8' EVENT OF ALARM CONDITION IN RESPECTIVE UNIT.
E509 PROVIDE SINGLE GANG CADDY RING FOR DATA ROUGH-IN.
E510 RECEPTACLE FOR GARBAGE DISPOSAL. SEE DETAIL 6/E5.01.

G,WP,24"

3
6
APARTMENT ELECTRICAL SYMBOLS
SYMBOL DESCRIPTION
GENERAL
TELEPHONE OUTLET - PROVIDE 3/4" ENT TO TERMINAL BOX
TV TELEVISION/VIDEO OUTLET - PROVIDE 3/4" ENT TO TERMINAL BOX
DUPLEX RECEPTACLE
G
"G" DENOTES GFCI TYPE, FEED-THRU WIRING METHOD IS ALLOWED
3 SINGLE SHADING DENOTES SPLIT WIRED DEVICE
FLOOR MOUNTED DUPLEX RECEPTACLE - SEE SPECIFICATIONS
SINGLE RECEPTACLE
DRYER RECEPTACLE NEMA 14-30 (125/250V 30A) 3#10,#10G- 3/4"C.
1 1 1 RANGE RECEPTACLE NEMA 14-50 (125/250V 50A) 3#8,#10G-1"C.
NON-FUSED DISCONNECT SWITCH - SIZE PER DRAWINGS
E509 (TYP.) T THERMOSTAT BY MECHANICAL - PROVIDE 1-GANG BOX AND 1/2"C. CONCEALED TO FAN COIL
T
THERMOSTAT FOR ELECTRIC BASEBOARD HEAT - SEE "ELECTRIC HEAT SCHEDULE"-
G,42" PROVIDE 1-GANG BOX AND 1/2"C. CONCEALED TO BASEBOARD HEATER.
4 F FIRE ALARM SPEAKER/STROBE COMBINATION - CONNECT TO HOUSE FIRE ALARM SYSTEM
STAND ALONE SINGLE STATION FIRE ALARM SMOKE DETECTOR - SEE SPECIFICATIONS.
CO
SR
INTERLOCK PER INTERNATIONAL FIRE CODE. CONNECT UNSWITCHED TO LIGHTING CIRCUIT.
CO = PROVIDE COMBINATION SMOKE/CARBON MONOXIDE DETECTOR No. Description Date
SR = SLEEPING ROOM SINGLE STATION TYPE
PUSH BUTTON
EF-1 F J-BOX WITH BLANK COVER FOR FUTURE FAN SPEED CONTROL

SAGE
1 1 1 1 3 F ADA ADA FIRE ALARM STROBE - ACTIVATED FROM SINGLE STATION DETECTOR WITHIN UNIT
ADA STAND ALONE SINGLE STATION SMOKE DETECTOR/ADA STROBE LIGHT COMBINATION
F LIGHTING PANEL
3 TELEPHONE/CATV TERMINAL CABINET
BRANCH CIRCUIT CONCEALED IN CEILING OR WALL

DEVELOPMENT

T
BRANCH CIRCUIT CONCEALED IN FLOOR
E501 2 HOMERUN TO PANEL (QUANTITY OF ARROWS INDICATES QUANTITY OF CIRCUITS)
5
SPECIAL PURPOSE HOMERUN AS INDICATED
E505

5
5
60" G,44"
96"
#
LUMINAIRE: NUMBER DENOTES FIXTURE TYPE, SEE CORRESPONDING
NUMBER IN FIXTURE SCHEDULE
INDUSTRIAL FIXTURE
GROUP
1 1 5 DF-1 E507 WALL BRACKET FIXTURE
E508 (TYP.) 96" CEILING FIXTURE
G,44" 4 WALL FIXTURE
1 TRACK FIXTURE
E504 G,44" S SINGLE POLE SWITCH
4 E510 S2 DOUBLE POLE SWITCH

'2C'
44" E506
G,42"

EF-1
2
S3
S4
3 - WAY SWITCH
4 - WAY SWITCH
WALL BOX DIMMER, SEE SPECIFICATIONS.
BENSON
MULTIFAMILY

3
1

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


44"
3
44"
E503
3 EWH-1
ENLARGED ELECTRICAL
FC-2.0 PLANS
E502

3 ENLARGED ELECTRICAL PLAN - 2 BED "C"


E3.02
119 SOUTH 49TH AVENUE
0' 1' 2' 4' 8' OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164
RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:51 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E3.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL

NATURAL GAS GENERATOR


208Y/120V, 3 PH., 4W, 60KW
INSTALLED IN WEATHERPROOF ENCLOSURE

EXTERIOR
INTERIOR

200/3
SWITCHBOARD SCHEDULE
CIRCUIT NAMEPLATE
DESIGNATION ACTIVE SPARE FUSE SPACE REMARKS
NUMBER DESIGNATION
ROOF
"MSBR" 1 "RMC2" 1600/3 SERVICE MAIN
208Y/120V, 3∅, 4W
WITH GROUND BAR
2 "RMC3" 1600/3 SERVICE MAIN
2500A MAIN LUG ONLY
BREAKER DISTRIBUTION
_K A.I.C.
PROVIDE MAINT. SWITCH FOR (3 TOTAL) (7 TOTAL) (7 TOTAL) (8 TOTAL)
ALL C.B. 1200A AND HIGHER
SERVICE ENTRANCE RATED PANEL PANEL PANEL PANEL AUTOMATIC TRANSFER
"2-BED" "1-BED" "JUNIOR "STUDIO" SWITCH "ATS-ELEV"
NOTES: 1-BED" N E 200A, 208/120V, 3-PHASE,
1. THE CURRENT LIMITING PLUG IN THE CIRCUIT BREAKER OR THE BREAKER ITSELF MUST BE THE NEXT LOGICAL 3-POLE, WITH
SIZE ABOVE THE SERVICE CONDUCTOR SIZE. IMPENDING TRANSFER
2. A PERMANENT "RED" ENGRAVED PHENOLIC PLATE MUST BE INSTALLED ON OR ABOVE THE MAIN CIRCUIT FEATURE FOR
BREAKER WITH THE FOLLOWING INFORMATION: ELEVATORS
1. SERVICE SIZE - PER NEC.
2. ALL PROGRAMMED BREAKER SETTINGS 150-3 125-3 125-3 125-3
3. "CAUTION - ANY CHANGES TO THESE SETTINGS COULD BE A POTENTIAL RISK TO LIFE AND
PROPERTY".

LEVEL 4
TO 'RMC3'

DISTRIBUTION PANEL SCHEDULE 150-3 125-3 125-3 125-3


NEW RESIDENTIAL METER
CENTER "RMC3" , SEE PLAN
FOR LOCATION.
CIRCUIT NAMEPLATE
DESIGNATION ACTIVE SPARE FUSE SPACE REMARKS
NUMBER DESIGNATION
1 6 11 16 21 26 31 36 41 46
"DPH" 1 PANEL "HG"
208Y/120V, 3∅, 4W
WITH GROUND BAR PANEL 2 7 12 17 22 27 32 37 42 47
PANEL PANEL PANEL PANEL
2 PANEL "H1" "H3"
600A MAIN BREAKER "2-BED" "1-BED" "JUNIOR "STUDIO"
BREAKER DISTRIBUTION 1-BED"
3 PANEL "H3" 3 8 13 18 23 28 33 38 43 48
_ K A.I.C.
SERVICE ENTRANCE RATED (3 TOTAL) (7 TOTAL) (7 TOTAL) (8 TOTAL)
4 PANEL "EL" 4 9 14 19 24 29 34 39 44 49
200-4
5 "ATS-ELEV"
5 10 15 20 25 30 35 40 45 50

LEVEL 3

TO 'RMC2'
1600-4
NEW RESIDENTIAL METER
150-3 125-3 125-3 125-3 CENTER "RMC2" , SEE PLAN
FOR LOCATION.

1 6 11 16 21 26 31 36 41

FEEDER SCHEDULE PANEL PANEL PANEL PANEL


2 7 12 17 22 27 32 37 42
"2-BED" "1-BED" "JUNIOR "STUDIO"
1-BED"
MARK WIRE AND CONDUIT 3 8 13 18 23 28 33 38 43

100-4 4-#2, #8 G - 1-1/2"C. (2 TOTAL) (7 TOTAL) (9 TOTAL) (8 TOTAL)


4 9 14 19 24 29 34 39 44
0'-170': 3-#1, #6 G - 1-1/2"C.
125-3 170'-220': 3-#1/0, #6 G - 1-1/2"C.
220'-260': 3-#2/0, #6 G - 2"C. 5 10 15 20 25 30 35 40 45

200-4 4-#3/0, #6 G - 2-1/2"C. LEVEL 2

600-4S 4-400 KCMIL IN EACH OF (2) 3"C. TO 'RMC2' 1600-4

2500-4S 4-600 KCMIL IN EACH OF (7) 3-1/2"C.


150-3 125-3 125-3 125-3
3200-4 4-750 KCMIL IN EACH OF (8) 4"C.

NOTE:
AT CONTRACTOR'S OPTION, COMPACT ELECTRICAL GRADE
ALUMINUM CONDUCTORS MAY BE USED FOR FEEDERS 100 AMPS
AND LARGER. IF ALUMINUM IS USED, CONTRACTOR TO SIZE PANEL PANEL
PANEL PANEL PANEL PANEL
ALUMINUM EQUAL TO FEEDER SCHEDULE (COPPER) AS INDICATED "H1" "H1"
"2-BED" "1-BED" "JUNIOR "STUDIO"
ON CONTRACT DOCUMENTS AND SHALL BE SUBMITTED TO
1-BED"
ENGINEER FOR REVIEW.

(1 TOTAL) (5 TOTAL) (9 TOTAL) (4 TOTAL)

FLAG NOTES 200-4


1 PROVIDE #3/0 COPPER IN 1" PVC CONDUIT TO BUILDING MAIN
GROUND BAR. FROM THE MAIN GROUND BAR PROVIDE #3/0 IN 1"
PVC CONDUIT TO STREET SIDE OF WATER METER. PROVIDE LEVEL 1
BONDING JUMPER ACROSS WATER METER. PROVIDE #3/0 COPPER
IN 1" PVC CONDUIT TO FIRE SERVICE. PROVDE #4 COPPER IN 1/2"C.
TO GROUND ROD. SEE DETAIL
2
E7.01 OPPD METERING
CT CABINET
PER OPPD
SPECIFICATIONS MAIN SWITCHBOARD
'MSBR'

200/3 FUSED DISCONNECT


175-3M 48KAIC No. Description Date
SWITCH. FUSES PER AVAIL.
ELEVATOR REQUIREMENTS 100-4 200-4
1000KVA OPPD
PADMOUNT
TRANSFORMER WITH
SECONDARY SIDE CAR. MAIN
SPD
1 SAGE
PANEL
'EL' 1
3
5
2
4
6
PANEL
'HG' DEVELOPMENT
CONCRETE PAD PER
3200-4
175-3M
7
9 10
8
2
GROUP
30HP ELEVATOR HOUSE DISTRIBUTION
OPPD METER SPEC
PANEL "DPH"

M
LEVEL G

1 1 BENSON
600-4S

4" CONDUIT TO SOUTH


2500-4S
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


PROPERTY LINE FOR
OPPD PRIMARY.

1 ELECTRICAL RISER DIAGRAM ELECTRICAL RISER


E4.01 NOT TO SCALE
DIAGRAM

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164
RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:51 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E4.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
LUMINAIRE SCHEDULE ELECTRICAL SYMBOLS
LIGHT SOURCE ELECTRICAL ACCEPTABLE SYMBOL DESCRIPTION SYMBOL DESCRIPTION
MARK DESCRIPTION MANUFACTURER CATALOG NUMBER SPEC. CCT TYPE LOAD VOLTS FINISH MOUNTING MANUFACTURERS REMARKS LIGHTING
LUMINAIRE SINGLE POLE SWITCH
1 7" DOWNLIGHT JUNO IC1JB JSF 7IN 10LM 30K 90CRI MVOLT2T WH 1,000LM 3000K LED 13 W 120 V WHITE SURFACE/CEILING LITHONIA, HALO, PHILIPS LUMINAIRE 3 - WAY SWITCH
3
2 7" DOWNLIGHT JUNO IC1JB JSF 7IN 10LM 30K 90CRI MVOLT2T WH 1,000LM 3000K LED 13 W 120 V WHITE SURFACE/CEILING LITHONIA, HALO, PHILIPS LUMINAIRE CONNECTED TO EMERGENCY CIRCUIT OR BATTERY 4 4 - WAY SWITCH
STRIP LUMINAIRE WALL BOX DIMMER SWITCH
3 APARTMENT BEDROOM SURFACE TBD $75 ALLOWANCE LED 30 W 120 V SURFACE/CEILING
CEILING MOUNTED MOTION SENSOR/SWITCH
4 APARTMENT VANITY TBD $150 ALLOWANCE LED 40 W 120 V SURFACE/WALL WALL MOUNTED LUMINAIRE
NUMBER OR LETTER WALL MOUNTED MOTION SENSOR/SWITCH
WALL MOUNTED LUMINAIRE DENOTES TYPE, SEE WALL MOUNTED MOTION SENSOR/SWITCH WITH 0-10V DIMMING
5 APARTMENT TRACK TBD $125 ALLOWANCE LED 25 W 120 V SURFACE/CEILING CORRESPONDING
D
TRACK LUMINAIRE LOW VOLTAGE LIGHTING CONTROL SWITCH
6 APARTMENT EXTERIOR SCONCE TBD $175 ALLOWANCE LED 20 W 120 V SURFACE/WALL EMERGENCY BATTERY PACK
MARK
P WALL MOUNTED PHOTOCELL
IN LUMINAIRE


7 PARKING GARAGE LIGHT GARDCO SVPG 140L 1675 NW SM 5 UNV MGY 8,000LM 4000K LED 76 W 120 V GRAY SURFACE/CEILING CEILING MOUNTED EXIT LIGHT WITH DIRECTIONAL ARROW SCHEDULE P CEILING MOUNTED PHOTOCELL
WALL OR END MOUNTED EXIT LIGHT WITH DIRECTIONAL ARROW
7E PARKING GARAGE LIGHT GARDCO SVPG 140L 1675 NW SM 5 EPB UNV MGY 8,000LM 4000K LED 76 W 120 V GRAY SURFACE/CEILING ▼

POLE MOUNTED LUMINAIRE


8 4' VAPORTIGHT LITHONIA VAP 12000LM FST MD MVOLT GZ10 35K 80CRI 12,000LM 3500K LED 99 W 120 V WHITE SURFACE/CEILING BOLLARD LUMINAIRE

9 EXTERIOR SCONCE LITHONIA WST LED P2 40K VF MVOLT DNAXD 3,000LM 4000K LED 25 W 120 V ALUMINUM SURFACE/WALL FIRE ALARM
FIRE ALARM SMOKE DETECTOR F FIRE ALARM HORN & STROBE COMBINATION
10 6' STAIRWELL NULITE RW2 4B 09 L35 UNV D 1C STF WH 6' 886LM/FT 3500K LED 91 W 120 V ALUMINUM SURFACE/WALL
FIRE ALARM HEAT DETECTOR F FIRE ALARM MINI-HORN & STROBE COMBINATION
11 4' STRIP LIGHT LITHONIA ZL1D L48 5000LM FST MVOLT 35K 80CRI WH 5,000LM 3500K LED 41 W 120 V WHITE SURFACE/CEILING DUCT MOUNTED SMOKE DETECTOR F CEILING FIRE ALARM STROBE
12 4' VAPORTIGHT LITHONIA VAP 6000LM FST MD MVOLT GZ10 35K 80CRI 6,000LM 3500K LED 49 W 120 V WHITE SURFACE/WALL F FIRE ALARM MANUAL PULL STATION F WALL FIRE ALARM STROBE
F FIRE SPRINKLER VALVE TAMPER SWITCH F CEILING FIRE ALARM HORN & STROBE COMBINATION
13 SIGNLE FACE EXIT SIGN LITHONIA EQC 1 R FURN W/FIXT -- LED 2W 120 V ALUMINUM NOTE 3 NOTE 1 F FIRE SPRINKLER FLOW SWITCH F CEILING FIRE ALARM SPEAKER & STROBE COMBINATION
14 DOUBLE FACE EXIT SIGN LITHONIA EQC 2 R FURN W/FIXT -- LED 2W 120 V ALUMINUM NOTE 3 NOTE 1 FACP FIRE ALARM CONTROL PANEL F WALL FIRE ALARM SPEAKER & STROBE COMBINATION
FAA FIRE ALARM ANNUNCIATOR PANEL S F CEILING FIRE ALARM SPEAKER
15 4' STRIP LIGHT LITHONIA ZL1D L48 5000LM FST MVOLT 35K 80CRI WH 5,000LM 3500K LED 41 W 120 V WHITE SURFACE/CEILING FIRE ALARM MAGNETIC DOOR HOLDER S F WALL FIRE ALARM SPEAKER
16 12' RECESSED LINEAR MARK ARCHITECTURAL SL4L LOP 12FT FLP TG 90CRI 35K 800LMF 120 ZT 800LM/FT 3500K LED 96 W 120 V FLUSH CEILING
LIGHTING POWER
17 EMERGENCY BATTERY LIGHT LITHONIA ELM2L FURN W/FIXT -- LED 7W 120 V WHITE SURFACE/WALL DUPLEX RECEPTACLE FLOOR BOX - COMBINATION POWER & DATA
G "G" DENOTES GFCI TYPE POKE-THRU FLOOR BOX
18 4' RECESSED LINEAR MARK ARCHITECTURAL SL2L LOP 4FT FLP GB 90CRI 35K 600LMF 120 ZT 600LM/FT 3500K LED 24 W 120 V FLUSH/CEILING " " DENOTES ISOLATED GROUND TYPE MULTI-OUTLET ASSEMBLY - LENGTH AS INDICATED
LIGHTING H "H" DENOTES HOSPITAL GRADE TYPE M # MOTOR ("#" DENOTES HORSEPOWER RATING)
19 8' RECESSED LINEAR MARK ARCHITECTURAL SL2L LOP 8FT FLP GB 90CRI 35K 600LMF 120 ZT 600LM/FT 3500K LED 48 W 120 V FLUSH/CEILING TR "TR" DENOTES TAMPER RESISTANT TYPE DISCONNECT SWITCH
U "U" DENOTES UNIVERSAL SERIAL BUS (USB) TYPE THERMAL ELEMENT SWITCH
LIGHTING TE
DOUBLE SHADING DENOTES RED DEVICE SWITCH & FUSE
20 13' RECESSED LINEAR MARK ARCHITECTURAL SL2L LOP 13FT FLP GB 90CRI 35K 600LMF 120 ZT 600LM/FT 3500K LED 78 W 120 V FLUSH/CEILING SINGLE SHADING DENOTES SPLIT WIRED DEVICE SWITCH & FUSTAT
LIGHTING HORIZONTAL MOUNTED DUPLEX RECEPTACLE MAGNETIC MOTOR STARTER
CEILING MOUNTED DUPLEX RECEPTACLE COMBINATION MAGNETIC STARTER/DISCONNECT
21 1x4 VOLUMETRIC LITHONIA BLT4 30L ADP MVOLT GZ1 LP835 3,000LM 3500K LED 23 W 120 V FLUSH/CEILING DOUBLE DUPLEX RECEPTACLE MOTOR CONTROL PUSHBUTTON STATION
22 18' RECESSED LINEAR MARK ARCHITECTURAL SL2L LOP 18FT FLP GB 90CRI 35K 600LMF 120 ZT 800LM/FT 3500K LED 108 W 120 V FLUSH/CEILING SINGLE RECEPTACLE R RELAY
LIGHTING DRYER RECEPTACLE NEMA 14-30 (125/250V 30A)
RANGE RECEPTACLE NEMA 14-50 (125/250V 50A)
23 6" DOWNLIGHT LITHONIA LND6 35/20 LO6 AR LSS MVOLT GZ10 2,000LM 3500K LED 23 W 120 V FLUSH/CEILING W "W" DENOTES WELDER RECEPTACLE NEMA 6-50 (250V 50A)
24 DECORATIVE PENDANT TBD TBD 0W 120 V SURFACE/CEILING SPECIAL PURPOSE RECEPTACLE (NEMA CONFIG. AS NOTED)

25 2' RECESSED LINEAR MARK ARCHITECTURAL SL4L LOP 2FT FLP TG 90CRI 35K 800LMF 120 ZT 800LM/FT 3500K LED 16 W 120 V FLUSH/CEILING COMMUNICATION
LIGHTING WALL PHONE OUTLET S INTERCOM CEILING SPEAKER
WALL COMMUNICATIONS DATA OUTLET S INTERCOM WALL SPEAKER
26 5' RECESSED LINEAR MARK ARCHITECTURAL SL2L LOP 5FT FLP GB 90CRI 35K 800LMF 120 ZT 800LM/FT 3500K LED 40 W 120 V FLUSH/CEILING CEILING COMMUNICATIONS DATA OUTLET S SOUND REINFORCEMENT WALL SPEAKER
LIGHTING WAP CEILING WIRELESS ACCESS POINT OUTLET S SOUND REINFORCEMENT CEILING SPEAKER
27 EXTERIOR WALL GRAZE 4000K LED 0W 120 V ALUMINUM SURFACE/WALL TV TELEVISION/VIDEO OUTLET M WALL MICROPHONE OUTLET
WALL CLOCK M CEILING MICROPHONE OUTLET
28 EXTERIOR WALL GRAZE 4000K LED 0W 120 V ALUMINUM SURFACE/WALL V VOLUME CONTROL C CALL-IN DEVICE
29 EXTERIOR WALL GRAZE 4000K LED 0W 120 V ALUMINUM SURFACE/WALL SECURITY
30 FESTOON LIGHTING CALI LIGHTING ML2000-CACA-2.7KGSFL-DM-WET-NOTE 4 256LM 2700K LED 3W 120 V BLACK SURFACE CEILING MOUNTED SECURITY MOTION DETECTOR # VIDEO SURVEILLANCE CAMERA (# INDICATES TYPE)
WALL MOUNTED SECURITY MOTION DETECTOR CR SECURITY CARD READER
RTE WALL MOUNTED REQUEST TO EXIT MOTION SENSOR ES ELECTRIC STRIKE
DOOR POSITION SWITCH ELECTRONIC LATCH RETRACTION
GENERAL REQUIREMENTS: MAGNETIC LOCK
EL

KP INTRUSION KEYPAD
IC INTERCOM STATION WG WANDER GUARD
A. CONTRACTOR SHALL VERIFY CATALOG NUMBERS AND INSTALLATION REQUIREMENTS PRIOR TO ORDERING. NOTIFY ENGINEER OF ANY CONFLICTS WITH PROPOSED INSTALLATION.
GENERAL
B. LIGHT SOURCE TYPES: LED = LIGHT EMITTING DIODE. LIGHTING PANEL J WALL MOUNTED JUNCTION BOX
DISTRIBUTION PANEL SWITCHBOARD OR MOTOR CONTROL CENTER J JUNCTION BOX
CABINET, ENCLOSURE, OR CONTROL PANEL, TYPE INDICATED ON PLANS CONDUIT SEAL
C. UNLESS NOTED OTHERWISE, REFER TO PLANS FOR SUSPENSION LENGTHS REQUIRED FOR ALL SUSPENDED LUMINAIRES. BRANCH CIRCUIT - EXPOSED CIRCUIT DOWN
BRANCH CIRCUIT CONCEALED IN CEILING OR WALL CIRCUIT UP
BRANCH CIRCUIT CONCEALED IN FLOOR CONDUIT STUB-OUT
LUMINAIRE SCHEDULE NOTES: BRANCH CIRCUIT - CLASS TWO WIRING CIRCUIT BREAK
HOMERUN TO PANEL (QUANTITY OF ARROWS INDICATES QUANTITY OF CIRCUITS) BELL
1. LUMINAIRE SHALL BE CONSIDERED EQUAL AS MANUFACTURED BY: ACUITY BRANDS, HUBBELL, COOPER, OR PHILIPS LIGHTING. SPECIAL PURPOSE HOMERUN AS INDICATED PUSH BUTTON
CONDUIT / CONDUIT SLEEVE (SIZE INDICATED ON PLANS) B BUZZER
SUBSCRIPT "WP" APPLIED TO ANY SYMBOL INDICATES WEATHERPROOF T THERMOSTAT
2. LUMINAIRE SHALL BE CONSIDERED EQUAL AS MANUFACTURED BY: GOTHAM, PATHWAY, PRESCOLITE, OR COOPER PORTFOLIO. WP
NEMA TYPE 3R OR EQUIVALENT
SUBSCRIPT "RT" APPLIED TO ANY SYMBOL INDICATES RAINTIGHT E SUBSCRIPT "E" ADDED TO ANY SYMBOL INDICATES EXISTING
RT
3. REFER TO PLANS FOR MOUNTING REQUIREMENTS SUCH AS WALL MOUNT, END MOUNT, CEILING MOUNT AND PROVIDE LUMINAIRES ACCORDINGLY. PROVIDE DIRECTIONAL CHEVRON ARROWS AS INDICATED ON PLANS. NEMA 3 OR EQUIVALENT R SUBSCRIPT "R" ADDED TO ANY SYMBOL INDICATES RELOCATED
SUBSCRIPT "PD" ADDED TO ANY FLOOR OUTLET INDICATES (TYP) WHERE (TYP) IS USED ON PLANS INDICATES A TYPICAL NOTE OR CONDITION
PD
PEDESTAL MOUNTED DL SUBSCRIPT "DL" ADDED TO ANY SYMBOL INDICATES DAMP LOCATION
4. REFER TO ARCHITECTURAL PLANS FOR RUN LENGTHS REQUIRED. LUMINAIRE SHALL BE CONTINUOUS FOR ENTIRE LENGTHS. PROVIDE ACCESSORY MOUNTING CABLE AND ALL REQUIRED HARDWARE FOR INSTALLATION PER MANUFACTURER'S INSTRUCTIONS.
SUBSCRIPT "EP" APPLIED TO ANY SYMBOL INDICATES EXPLOSION PROOF K SUBSCRIPT "K" ADDED TO ANY SYMBOL INDICATES KEY OPERATED
EP
CLASS, GROUP & DIVISION AS NOTED P SUBSCRIPT "P" ADDED TO ANY SYMBOL INDICATES PILOT LIGHT

LIGHTING PANEL SCHEDULE LIGHTING PANEL SCHEDULE LIGHTING PANEL SCHEDULE


Panel: H1 Voltage: 120/208 Wye Panel: H3 Voltage: 120/208 Wye Panel: HG Voltage: 120/208 Wye
Rating: 200 A Phase: 3 Rating: 200 A Phase: 3 Rating: 200 A Phase: 3
Mounting: SURFACE Wire: 4 Mounting: SURFACE Wire: 4 Mounting: SURFACE Wire: 4
Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating:
Remarks: Remarks: Remarks:

Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description
1 2 1 2 1 2
3 4 3 4 3 4
5 6 5 6 5 6
7 8 7 8 7 8
9 10 9 10 9 10
11 12 11 12 11 12
13 14 13 14 13 14
15 16 15 16 15 16
17 18 17 18 17 18
19 20 19 20 19 20
21 22 21 22 21 22
23 24 23 24 23 24
25 26 25 26 25 26
27 28 27 28 27 28
29 30 29 30 29 30
31 32 31 32 31 32
33 34 33 34 33 34
35 36 35 36 35 36
37 38 37 38 37 38
39 40 39 40 39 40
41 42 41 42 41 42
43 44 Options: Options:
45 46 G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. G – GFCI type circuit breaker. S – Shunt trip type circuit breaker.
47 48 L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker. L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker.
49 50
51 52 Notes: Notes:
53 54
55 56
57 58
59 60
61 62
63 64
65 66
67 68 No. Description Date
69 70
71 72
73 74 LIGHTING CONTROL DEVICE SCHEDULE
75
77
79
76
78
80
SYMBOL TAG MANUFACTURER CATALOG NUMBER DESCRIPTION SAGE
1P ACUITY CONTROLS NLIGHT nPODM LIGHTING CONTROL NETWORK ENTRY STATION WITH ON

Options:
81
83
82
84
2PD ACUITY CONTROLS NLIGHT nPODM 2P DX
AND OFF PUSH BUTTONS
LIGHTING CONTROL NETWORK ENTRY STATION WITH TWO
DEVELOPMENT
GROUP
SETS OF ON AND OFF PUSH BUTTONS AND RAISE/LOWER
G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. DIMMING CONTROL
L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker.
4PD ACUITY CONTROLS NLIGHT nPODM 4P DX LIGHTING CONTROL NETWORK ENTRY STATION WITH FOUR
Notes: SETS OF ON AND OFF PUSH BUTTONS AND RAISE/LOWER
DIMMING CONTROL
nS ACUITY CONTROLS NLIGHT nCM PDT 9 STANDARD RANGE LOW VOLTAGE CEILING SENSOR
CONNECTED TO LIGHTING CONTROL NETWORK
nE ACUITY CONTROLS NLIGHT nCM PDT 10 EXTENDED RANGE LOW VOLTAGE CEILING SENSOR
CONNECTED TO LIGHTING CONTROL NETWORK
BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


ELECTRICAL SCHEDULES

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164
RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:52 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E4.02
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL

LOAD CENTER SCHEDULE LOAD CENTER SCHEDULE LOAD CENTER SCHEDULE


Panel: 1C Voltage: 120/208 Single Panel: 1B Voltage: 120/208 Single Panel: 1A Voltage: 120/208 Single
Rating: 125 A Phase: 1 Rating: 125 A Phase: 1 Rating: 125 A Phase: 1
Mounting: RECESSED Wire: 3 Mounting: RECESSED Wire: 3 Mounting: RECESSED Wire: 3
Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating:
Remarks: Remarks: Remarks:

Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description
1 2 1 2 1 2
3 4 3 4 3 4
5 6 5 6 5 6
7 8 7 8 7 8
9 10 9 10 9 10
11 12 11 12 11 12
13 14 13 14 13 14
15 16 15 16 15 16
17 18 17 18 17 18
Options: Options: Options:
G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. G – GFCI type circuit breaker. S – Shunt trip type circuit breaker.
L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker. L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker. L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker.
Notes: Notes: Notes:

LOAD CENTER SCHEDULE LOAD CENTER SCHEDULE LOAD CENTER SCHEDULE


Panel: 2C Voltage: 120/208 Single Panel: 2B Voltage: 120/208 Single Panel: 2A Voltage: 120/208 Single
Rating: 125 A Phase: 1 Rating: 125 A Phase: 1 Rating: 125 A Phase: 1
Mounting: RECESSED Wire: 3 Mounting: RECESSED Wire: 3 Mounting: RECESSED Wire: 3
Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating:
Remarks: Remarks: Remarks:

Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description
1 2 1 2 1 2
3 4 3 4 3 4
5 6 5 6 5 6
7 8 7 8 7 8
9 10 9 10 9 10
11 12 11 12 11 12
13 14 13 14 13 14
15 16 15 16 15 16
17 18 17 18 17 18
Options: Options: Options:
G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. G – GFCI type circuit breaker. S – Shunt trip type circuit breaker.
L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker. L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker. L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker.
Notes: Notes: Notes:

LOAD CENTER SCHEDULE LOAD CENTER SCHEDULE LOAD CENTER SCHEDULE


Panel: J Voltage: 120/208 Single Panel: SB Voltage: 120/208 Single Panel: SA Voltage: 120/208 Single
Rating: 125 A Phase: 1 Rating: 125 A Phase: 1 Rating: 125 A Phase: 1
Mounting: RECESSED Wire: 3 Mounting: RECESSED Wire: 3 Mounting: RECESSED Wire: 3
Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating: Type: MLO W/GND. BAR A.I.C. Rating:
Remarks: Remarks: Remarks:

Circuit Description OPT R P CKT A B C CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B CKT P R OPT Circuit Description Circuit Description OPT R P CKT A B CKT P R OPT Circuit Description
1 2 1 2 1 2
3 4 3 4 3 4
5 6 5 6 5 6
7 8 7 8 7 8
9 10 9 10 9 10
11 12 11 12 11 12
13 14 13 14 13 14
15 16 15 16 15 16
17 18 17 18 17 18
Options: Options: Options:
G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. G – GFCI type circuit breaker. S – Shunt trip type circuit breaker. G – GFCI type circuit breaker. S – Shunt trip type circuit breaker.
L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker. L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker. L – Locking handle type circuit breaker. R – Reconnect to existing circuit breaker.
Notes: Notes: Notes:

No. Description Date

SAGE
DEVELOPMENT
GROUP

BENSON
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


ELECTRICAL SCHEDULES

119 SOUTH 49TH AVENUE


OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164
RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:52 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E4.03
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL
BOND AT BRASS FITTING, STEEL
MANIFOLD, OR RIGID STEEL PIPE
BUILDING
COMPONENT ONLY. COMPLY WITH LOCAL
EXTERIOR WALL
GAS COMPANY RULES AND REGULATIONS.

C
L

CL
6 EXIT CL CL METALLIC
MAIN SWITCHBOARD OR GAS PIPE
GAS PIPING

6"
APPLICABLE S.E. GROUNDING
NOTE 1 EQUIPMENT CLAMP
BUILDING STEEL
(WHERE AVAILABLE)
3 3 3

GAS
C NOTE 1 NOTE 1 METER
9" L (TYPICAL) (TYPICAL) WALL FIRE ACCESS
CL CL CL
7 OCCUPANCY WALL BOX ALARM CONTROL CARBON
6" 6" 6" 6" WALL SENSOR DIMMER ENTRY PULL CARD TV SHADE DIOXIDE TEMPERATURE GROUND TO PROVIDE
SWITCH SWITCH SWITCH STATION STATION READER CONTROL CONTROL SENSOR THERMOSTAT SENSOR BUILDING STEEL,

10"
NEUTRAL-GROUND BOND
PROVIDE LUG-TYPE
WATER PIPE GROUNDING
FIRE

82"

82"

82"
NOTE 1 CONNECTION;
BURNDY OR EQUAL CLAMP (TYP.)
(TYPICAL) 1 2 4 5 1 2 PROVIDE GROUNDING
JUMPER ACROSS WATER
6" 6" NOTE 2 METER
PROVIDE BURNDY

44" U.N.O.

44" U.N.O.

44" U.N.O.
CL CL COMPRESSION NEUTRAL BUS
FITTING TO BOND

NOTE 4
(UFER) GROUND TO GROUND BUS METER
F CR TC SC S T S BUILDING STEEL BURNDY
COMPRESSION-
WATER METER TYPE TEE FITTING
FLOOR FLOOR
STANDARD DOOR (A/V) EXIT DOOR STANDARD DOOR CONCRETE
FOUNDATION METALLIC
WALL UNDERGROUND
WATER SERVICE
DEVICES: NOTES:
1 WALL SWITCH, WALL OCCUPANCY SENSOR SWITCH, WALL BOX DIMMER SWITCH, OR ENTRY STATION 1. ALIGN DEVICES VERTICALLY AND HORIZONTALLY WHEREVER POSSIBLE. NOT ALL DEVICES OR CONFIGURATIONS ARE
DEPICTED ON THIS DETAIL. FOR ANY CONFIGURATIONS WITH FOUR OR MORE DEVICES, COORDINATE ARRANGEMENT 5/8" DIA. x 10'-0" 25LF BARE COPPER METALLIC CONCRETE
2 THERMOSTAT, TEMPERATURE SENSOR, OR CARBON DIOXIDE SENSOR ROUGH-IN WITH THE ENGINEER PRIOR TO ROUGH-IN. SEE FLOOR PLANS FOR INDIVIDUAL DOOR REQUIREMENTS. COPPER CLAD DRIVEN CONDUCTOR IN BOTTOM 2" UNDERGROUND FOOTING
GROUND ROD OF CONCRETE FOOTING FIRE SERVICE (TYP.)
3 FIRE ALARM AUDIO/VISUAL INDICATING DEVICE 2. WHERE MULTIPLE SWITCHES OR WALL BOX DIMMERS ARE GANGED TOGETHER, ALIGN FIRST GANG WITH DEVICES
ABOVE AND ADD DEVICES TO THE RIGHT AS REQUIRED.
4 FIRE ALARM PULL STATION
3. DIMENSIONS ARE TO BE MEASURED FROM OUTSIDE EDGE OF DOOR FRAME OR TRIM. WHERE SIDE LIGHT WINDOWS
5 ACCESS CONTROL CARD READER ARE PROVIDED, DIMENSIONS SHOULD BE MEASURED FROM OUTSIDE EDGE OF SIDE LIGHT WINDOW FRAME OR TRIM.
NOTES:
4. ALL DEVICES SHALL BE LOCATED TO MAINTAIN ALL A.D.A. MOUNTING HEIGHT REQUIREMENTS AND SUCH THAT 1. PHYSICAL LAYOUT SHOULD BE DETERMINED FROM FLOOR PLAN DRAWINGS AND FIELD DIMENSIONS.
6 EXIT SIGN
CENTER OF ADJACENT DEVICES ARE AT SAME ELEVATION (TYPICALLY 44" A.F.F. TO CENTER OF DEVICE). NOTIFY 2. ALL GROUNDING CONDUCTORS SIZED IN ACCORDANCE WITH NEC TABLE 250.66.
ENGINEER OF ANY CONFLICTS WITH THE PROPOSED INSTALLATION. 3. ALL CLAMPS AND FITTINGS SHALL BE UL LISTED FOR THE APPLICATION.
7 A/V TOUCHSCREEN

2 DEVICE ALIGNMENT DETAIL 1 MAIN SERVICE GROUNDING DETAIL


E5.01 NOT TO SCALE E5.01 NOT TO SCALE

ELEVATOR NOTES: OPPD TO INSPECT SITE PRIOR TO


1. ACTIVATION OF ANY OF THE SMOKE DETECTORS SHOWN SHALL INITIATE POURING CONCRETE. INSPECTION
ELEVATOR RECALL. WILL INCLUDE LOCATION AND DEPTH
OF HOLES FOR SUPPORT PIERS (IF
2. ACTIVATION OF SMOKE DETECTOR(S) ON A DESIGNATED LEVEL LABEL END REQUIRED), REBAR PLACEMENT,
SHALL CAUSE THE ELEVATOR TO RETURN TO AN ALTERNATE LEVEL. OF CONDUIT CONDUIT PLACEMENT, BACKFILL
DESIGNATED AND ALTERNATE LEVELS TO BE DETERMINED BY THE COMPACTION, AND OVERALL
RELAY OR ZONE ALARM SMOKE DETECTOR ELEVATOR INSPECTOR AND FIRE MARSHAL.
MODULE AS REQUIRED NOTES 1, 2 (TYP.) COMPACTION OF SLAB AREA.
SECONDARY DUCTS
BY F.A. VENDOR, NOTE 4 HEAT DETECTOR 3. HEAT DETECTORS USED FOR ELEVATOR POWER SHUT DOWN SHALL BE
MAXIMUM CONDUCTOR - 750 KCMIL
NOTE 3 (TYP.) LOCATED WITHIN 24" OF SPRINKLER HEADS IN THE SHAFT AND PROVIDE
120V POWER ELEVATOR MACHINE ROOM. ACTIVATION OF HEAT DETECTOR IN THE PULLSTRING
FOR DAMPER HOISTWAY OR ELEVATOR MACHINE ROOM SHALL SHUT DOWN POWER
S H TO ELEVATOR CONTROLLER. ROUTE MACHINE ROOM FIRE ALARM
ADDITIONAL FLOORS TO MANUAL CIRCUIT THROUGH FIRE ALARM RELAY AND TO SHUNT TRIP CONTROL
PER PLANS SWITCH COIL IN BREAKER SERVING ELEVATOR.

LIGHT FIXTURE, SEE PLANS. COORDINATE 4. DAMPER AT TOP OF SHAFT SHALL BE MANUALLY CONTROLLED FROM
ARLINGTON PRESS-ON
FIRE ALARM PANEL (OR OTHER LOCATION AS INDICATED).
LOCATION WITH ELEVATOR INSULATING BUSHING
MANUFACTURER. PROVIDE 19 5. PROVIDE COOPER BUSSMANN "POWER MODULE SWITCH" FUSIBLE
NOTE 6
FOOTCANDLES AT WORK AREA DEFINED ELEVATOR DISCONNECT WITH AUXILIARY CONTACTS, SHUNT TRIP
BY LOCAL ELEVATOR INSPECTOR. ELEVATOR CONTROL, FIRE ALARM MONITORING RELAY, CONTROL TRANSFORMER TURN CONDUIT OUT
POWER PER AND WIRING FOR SELF-LOWERING ELEVATORS (IF APPLICABLE), AND ABOVE ACCESSIBLE
PLANS MEANS FOR LOCKING IN "OPEN" POSITION. PROVIDE WITH CLASS "J"
DEDICATED CIRCUIT FOR
DUAL-ELEMENT, TIME-DELAY FUSES. SEE SPECIFICATIONS.
CEILING 7'
ELEVATOR CAB FROM
LOCKABLE SWITCH PER DEDICATED MACHINE ELEVATOR 6. WALL STUD
SHUNT TRIP CONTROL WIRES TO HEAT DETECTOR(S) OR FIRE 3'-4"
NEC 620 S ROOM CIRCUIT PER DISCONNECT, ALARM CONTROL PANEL. CONTROL WIRING FOR AUXILLIARY 1" CONDUIT STUBBED
NEC 620 NOTE 5 CONTACTS IN SERIES WITH DISCONNECT AUXILLIARY CONTACTS CONCEALED IN WALL NO SEC
GFI RECEPTACLE, PER PLANS
COORDINATE LOCATION WITH FOR SELF OWERING ELEVATORS (IF APPLICABLE) DUCT IN
TELEPHONE
ELEVATOR MANUFACTURER. 7. FIRE ALARM JUNCTION BOX WITH CONDUIT TO CONTROL PANEL OR THIS AREA
OUTLET AND 8"
RECALL DETECTORS AS REQUIRED. MOUNT DATA
CONDUIT PER
OUTLET ADJACENT
SWITCH, PER PLANS LOCATE SPECIFICATIONS 9. VERIFY ALL EQUIPMENT LOCATIONS WITH ELEVATOR MANUFACTURER'S TO RECEPTACLE
1'-4"
42" ABOVE HIGHEST FLOOR SHOP DRAWINGS PRIOR TO INSTALLATION OF EQUIPMENT. 1'-1"
TO ELEVATOR
LEVEL ADJACENT TO
ELEV. CONT. CAB.

CONTROL NOTE 3,7 10. CONNECT MAINTAINED CONTACT THREE POSITION SPDT SWITCH FOR MANUAL
ELEVATOR DOORS HATCH OPERATION TO BYPASS RELAY. PROVIDE PHENOLIC LABELS FOR EACH
CABINET
POSITION. SEE 'HATCH CONTROL WIRING SCHEMATIC' BELOW. 1'-6"
ELEVATOR 11. ELEVATOR PIT LIGHT, SWITCH AND RECEPTACLES SHALL BE NEMA 4 PER ASME 17.1-2007. 1'-8" 2' 1'-5" 7"
LOBBY
TO DAMPER AND RELAY
10'-11"
ELEVATOR MACHINE 4-11/16" SQUARE MO
BOX WITH SINGLE UN
LOCATED ON TOP OF SWITCH FOR MANUAL HATCH OPERATION, VA TIN
CAB OR TOP OF NOTE 10. VERIFY LOCATION. GANG PLASTER RING RIE G HE 1-4" NON-METALLIC 5/8" X 8' GROUND ROD
S-S IG
HOISTWAY EE HT CONDUIT WITH 90° FURNISHED AND
BLANK COVER PLATE PL A 36" RADIUS BEND INSTALLED BY OPPD
NS
S FOR PRIMARY CABLES

ELEVATOR CAB

4 DATA/COMM ROUGH - IN DETAIL 1. EACH LOCATION SHALL HAVE A SOIL TEST 4. ALL CUSTOMER INSTALLED PRIMARY CONDUITS TO BE RODDED AND

E5.01
PERFORMED AND A SLAB DESIGNED PER
THE RESULTS. BY CUSTOMER
PROVEN CLEAR, AND A JET LINE TO BE LEFT IN EACH CONDUIT
No. Description Date
DEDICATED PANEL FOR NOT TO SCALE
5. DUCTS ARE NOT TO BE INSTALLED IN CONCRETE WITHIN SLOT
BRANCH CIRCUITS SERVING
ELEVATOR ELEVATOR CAR, EQUIPMENT ROOM,
2. TRANSFORMER SLAB TO BE DESIGNED AND
PROVIDE LIGHTING PER PLANS,
TO MAINTAIN A MINIMUM OF 10
FOOTCANDLES AT THE
LOBBY HOISTWAY SHUNT TRIP POWER AND ELEVATOR
PIT. SEE PANEL SCHEDULES.
CONSTRUCTED BY CUSTOMER

3. LOCATION AND DIMENSIONS OF SLOT AND CONDUITS


6. OPPD ENGINEERING DEPT MUST REVIEW ALL DETAILS BEFORE CONSTRUCTION

7. NO WALLS TO BE BUILT AROUND OR CANOPIES ABOVE TRANSFORMERS


SAGE
120V DISHWASHER
DEVELOPMENT
ELEVATOR DOOR THRESHOLD. MUST BE MAINTAINED IN RELATION TO OVERALL
120V TO SHUNT TRIP
(TYPICAL AT EVERY FLOOR) CIRCUIT (SEE PLANS) SLAB DIMENSIONAL 8. ALL CONDUITS ENTERING SLAB TO BE VERTICAL AND AT A 90° WITH TOP OF SLAB
DEDICATED PIT BREAKER SERVING ELEVATOR POWER,
CIRCUIT PER MONITORED BY FIRE ALARM. SEE
120V DISPOSAL CIRCUIT

SWITCH,
NEC 620 SCHEMATIC BELOW.
(SEE PLANS)
BRANCH CIRCUITING 3 TRANSFORMER PAD WITH SIDE CAR GROUP
TO COUNTER TOP CONCEALED IN WALL (TYP)
PER PLANS GFI RECEPTACLE, SWITCH FOR RECEPTACLES E5.01
H MANUAL HATCH N SINGLE POLE NOT TO SCALE
PROVIDE LIGHTING PER PLANS PER PLANS (WHERE APPLICABLE)
OPERATION POWER TOGGLE SWITCH
(2 FIXTURE MIN.), TO MAINTAIN A H CLOSED
MINIMUM OF 10 FOOTCANDLES
48"

F.A. RELAY AUTO DAMPER


AT THE FLOOR. COORDINATE PIT DEDICATED
LOCATION WITH ELEVATOR
STRUCTURE/EQUIPMENT.
CIRCUIT
SIMPLEX RECEPTACLE,
PER PLANS
OPEN
CLOSED
COUNTER TOP
BENSON
120 VAC POWER
HATCH CONTROL WIRING SCHEMATIC DOUBLE DUPLEX RECEPTACLE
SEE PLANS (TYP)
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


H N 12"L x 2"W x 1/4" TIN PLATED
NOTE: ALL 120 VAC WIRING AND
GROUND BAR KIT STORM
ELEVATOR DISCONNECT TO BE PROVIDED
POWER PRODUCTS #
BY ELECTRICAL CONTRACTOR. DISHWASHER
B SCGBM-250212-T-KT
E.C. TO PROVIDE PROVIDE #6 COPPER IN 3/4"
CORD AND PLUG PVC CONDUIT TO GROUND
GARBAGE DISPOSAL
SHUNT TRIP
RELAY
ACTUATED MR-101C SHUNT TRIP POWER
SWITCHED RECEPTACLE
BAR IN ELECTRICAL ROOM

ALL WALLS, 8'H x 3/4"D AD


ELECTRICAL DETAILS
SUPERVISORY RELAY PLYWOOD PAINTED WITH 2 COATS
BY HEAT 0 24 115 230
DETECTORS OF GRAY FIRE RETARDANT PAINT
18"

WHITE
0V
BLACK FROM NEAREST
120V E.C. TO PROVIDE
RED INITIATING ZONE 1ST FLOOR
24V CORD AND PLUG
TO 24 VDC
THIS RELAY IS NORMALLY CONDUITS STUBBED
POWER
ENERGIZED, CONTACTS SHOWN OUT TO SITE FOR
IN DE-ENERGIZED STATE TELEPHONE SERVICE.
SHUNT TRIP MONITORING SCHEMATIC SEE SITE PLAN

7 ELEVATOR CONNECTION DETAIL (MACHINEROOMLESS SPRINKLED) 6 DISHWASHER/DISPOSAL CONNECTION (CORD) 5 COMMUNICATIONS BOARD DETAIL
E5.01 NOT TO SCALE E5.01 NOT TO SCALE E5.01 NOT TO SCALE
119 SOUTH 49TH AVENUE
OMAHA, NEBRASKA 68132
(402)551-0800
MEI PROJECT NO: 19164
RY N PROJECT: 17073
morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:54 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
note:
4940 North 118th Street do not scale drawings. verify all dimensions and clearances from T FO
Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E5.01
at site. lay out and coordinate all work prior to installation to
P: 402.491.4144

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19
AGENCY APPROVAL

WEATHERPROOF ENCLOSURE

120V SMOKE DAMPER BY


MECHANICAL. SEE PLANS. PH PH
FIRE ALARM CONTROL N N
GND GND
RELAY. PROVIDE ONE LOCATE NEAR
RELAY PER AIR HANDLING BATTERY RACK FOR
UNIT ZONE. SERVICE 3-POLE AUTOMATIC
BATTERY HEATER
ENTRANCE TRANSFER SWITCH
120V CKT. TO ADDITIONAL
PANEL EMERGENCY GENERATOR
DAMPERS IN AIR HANDLING UNIT
ZONE OUTPUT J-BOX FOR J J G
CIRCUIT ALTERNATOR GENERATOR
FIRE ALARM CONTROL CIRCUIT J
BREAKER DRYER
TO ADDITIONAL RELAY(S) NEW CENTRAL #4 GROUND
INVERTER 'INV-X' BOND TO
120V POWER OPEN, FAIL NEW CABINET GRADE
EVENLITE N BUS N BUS N BUS
CLOSED DAMPER ACTUATOR PANEL
'X'
XXX### (OR (TYP.) G GEN-22
EQUAL) 2#10, #10G-3/4"C.
GND BUS GND BUS GND BUS
J-BOX FOR CONV.
120V POWER PER PLANS 1 J-BOX FOR BATTERY BATTERY HEATER RECEPT
NEW LOCKABLE (20/1) INTERIOR EM LIGHTING SERVICE
GROUNDING CHARGER
CONTROL CIRCUIT TO FIRE CIRCUIT BREAKER IN 2
EXTERIOR EM LIGHTING 5/8" x 10'-0" COPPER CLAD
ALARM PANEL PANEL 'X' TO SERVE ELECTRODE BOND TO FRAME
3 RUN CONDUITS WITH DRIVEN GROUND ROD.
INVERTER LOAD EXIT LIGHTING
NOTES: GEN. OUTPUT CONDUITS
GROUNDING ELECTRODE
1. ANY FIRE ALARM SHALL CLOSE SMOKE DAMPERS AND (TYP. ALL ACCESSORIES) PANEL-X,X,X
PER NEC TABLE 250-66
SHUT DOWN ASSOCIATED MECHANICAL EQUIPMENT. TO LOAD 6#10,#10G - 1"C.
2. PROVIDE BREAKER LOCK AT PANEL FOR 120V CIRCUIT.
3. VERIFY AIR HANDLING UNIT ZONES WITH MECHANICAL.

4 FIRE/SMOKE DAMPER CONNECTION DETAIL 3 INVERTER WIRING DETAIL 2 GENERATOR GROUNDING WITH 3 - POLE A.T.S. DETAIL 1 GENERATOR CONNECTION DETAIL
E5.02 NOT TO SCALE E5.02 NOT TO SCALE E5.02 NOT TO SCALE E5.02 NOT TO SCALE

ACCESS CONTROL JUNCTION BOX, HOFFMAN CAT# A1412CHFL


(OR EQUAL), NEMA 4 RATED BOX, 12"X14"X6"D WITH HINGED
COVER. BOX TO HOUSE DOOR HARDWARE POWER SUPPLY.
LOCATE BOX AT ACCESSIBLE LOCATION ABOVE NEAREST FIRE ALARM CONNECTION
ACCESSIBLE CEILING ON SECURE SIDE OF DOOR (WHERE APPLICABLE)

LABEL CONDUIT END NOTE: WHERE ONE POWER SUPPLY CAN SERVE INCOMING 120V NORMAL
(TYPICAL) MULTIPLE DOORS, CONTRACTOR MAY CONSOLIDATE POWER CONNECTION
TO LIGHTING PANEL QUANTITY OF POWER SUPPLY JUNCTION BOXES
1/2" CONDUIT
ACCORDINGLY. COORDINATE REQUIREMENTS WITH
ARLINGTON PRESS-ON FOR ELECTRICAL ACCESSIBLE CEILING
ACCESS CONTROL MANUFACTURER PRIOR TO ROUGH-IN.
INSULATING BUSHING
LINE (120/277V)

1" CONDUITS TO
(TYPICAL)
ABOVE ACCESSIBLE
NEUTRAL

CEILING IN ROOM STUB 3/4" CONDUIT INTO TOP JAMB AT ANY STUB INTERCOM CONDUIT UP
PLENUM RATED LOW VOLTAGE CONDUCTORS, PROVIDE PULL STRING LOCATION WHERE DOOR POSITION SWITCH, TO ABOVE ACCESSIBLE
PROVIDE SENSOR MANUFACTURERS STANDARD (TYPICAL) 1-1/4" CONDUITS TO MAGNETIC LOCK, OR REQUEST-TO-EXIT CEILING
PRE-TERMINATED "QUICK CONNECT" TYPE. MOTION SENSOR ARE SHOWN (WIRING TO
ABOVE ACCESSIBLE
PROVIDE J-HOOK SUPPORT FROM STRUCTURE. CEILING IN ROOM DEVICES MAY SHARE SAME CONDUIT)
(NEUTRAL) ROUTE CABLING IN CONDUIT WHERE EXPOSED
STRUCTURE OCCURS, EXPOSED WIRING SHALL NOT
(POWER)
BE ALLOWED. NEATLY COIL EXCESS CABLING.
24V DC POWER (SENSOR POWER)
(SENSOR POWER)
PACK
(COMMON) 3/4" CONDUIT FLUSH
(SWITCHLEG) (MINIMUM 1 PACK
MOUNTED (TYP.)
PER ROOM OR (CONTROL)
CONTROLLED
SPACE)
PROVIDE ONE (1)
FLUSH MOUNTED JUNCTION BOX CR
DUPLEX RECEPTACLE
WITH BLANK COVER FOR CARD
STUB 3/4" CONDUIT IN SIDE READER OR PUSHBUTTON
TV PT STATION
JAMB TO CENTER HINGE FOR
ELECTRIC POWER TRANSFER
RECESSED 3-GANG STEEL
J BOX, HUBBELL #HBL263

WALL STUD (TYP)


STUB 3/4" CONDUIT IN SIDE FLUSH MOUNTED JUNCTION BOX
6" 12"
MO JAMB TO DOOR STRIKE FOR WITH BLANK COVER FOR
UN ELECTRIC STRIKE LOCK INTERCOM CALL STATION IC
TI

44"
VA
MOUNT SENSOR TO RIE NG H
S-S EIG
BACKBOX FLUSH EE H
WITH CEILING PL A T
NS

CEILING CEILING FINISH FLOOR

NOTES:
NOTES:
1. PROVIDE ARLINGTON PRESS-ON 1. ROUGH-IN REQUIREMENTS AND LOCATIONS SIMILAR FOR DOUBLE DOORS.
INSULATED BUSHING AT CONDUIT END.
2. NOT ALL DEVICES ROUGHED IN AT ALL DOORS, SEE PLANS FOR SPECIFIC DOOR ROUGH-IN REQUIREMENTS.
2. PROVIDE PULL-STRING AT ALL EMPTY CONDUITS.
3. SEE FLOORPLAN FOR MOUNTING HEIGHT OF DEVICES. 3. COORDINATE ACCESS CONTROL ROUGH-IN REQUIREMENTS WITH ARCHITECTURAL DOOR SCHEDULES.
4. PROVIDE DECORA STYLE PLATES FOR ALL DEVICES. 4. COORDINATE ACCESS CONTROL ROUGH-IN REQUIREMENTS WITH SECURITY EQUIPMENT SUPPLIER.

7 TYPICAL OCCUPANCY SENSOR CONNECTION DETAIL 6 TELEVISION ROUGH IN DETAIL 5 ACCESS CONTROL ROUGH - IN DETAIL
E5.02 NOT TO SCALE E5.02 NOT TO SCALE E5.02 NOT TO SCALE

No. Description Date


TO 3RD
TO OUTDOOR PARTY A/V
TO ADDITIONAL ZONES
PHOTOCELL SYSTEM

SAGE
4 5 7 8 9 10
120V DISHWASHER CIRCUIT (SEE
WIRE LEGEND 3
6 PLANS)

A
CAT 5
(LOW VOLTAGE)
A
A
1/2" CONDUIT TO PANEL DEVELOPMENT
A A A A A A A

B
CLASS 1
(LINE VOLTAGE)
A
A
GROUP
A B B TO COUNTER TOP CONDUIT CONCEALED IN WALL (TYP.)
B RECEPTACLES
CLASS 2 A HOT (WHERE APPLICABLE)
C A FROM CIRCUIT NEUTRAL
(LOW VOLTAGE)
B B B
SENSING CIRCUIT COUNTER TOP
ETHERNET LAN
D
(LOW VOLTAGE) TO EMERGENCY LOAD
FROM CIRCUIT
DIGITAL LIGHTING CONTROL SYSTEM - GENERAL NOTES DIGITAL LIGHTING CONTROL SYSTEM - KEYNOTES
1 NLIGHT GATEWAY DEVICE WITH POWER SUPPLIES AS REQUIRED TO ACCESS AND CONTROL CONNECTED SINGLE POLE
BENSON
A. REFER TO SPECIFICATIONS AND LIGHTING CONTROL DEVICE SCHEDULE FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
C
C
C
C
B. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE AND OPERABLE DIGITAL LIGHTING
CONTROL SYSTEM IN ACCORDANCE WITH ALL APPLICABLE LOCAL AND NATIONAL CODES. IT SHALL BE THE CONTRACTOR'S
SYSTEM DEVICES. CONNECT GATEWAY TO BUILDING LOCAL AREA NETWORK. PROVIDE DATA OUTLET
ON WALL ADJACENT TO GATEWAY. REFER TO PLANS FOR LOCATION OF DEVICES. CONNECT POWER
SUPPLIES TO NEARBY UNSWITCHED CIRCUIT.
TOGGLE SWITCH
MULTIFAMILY

C:\Revit Local Files\19164_Benson Multifamily Housing_MEI_R19_Jeff_Frank.rvt


2 RESPONSIBILITY TO MAKE ALL PROPER ADJUSTMENTS TO ENSURE OWNER SATISFACTION WITH THE LIGHTING CONTROL
SYSTEM. 2 PROVIDE NLIGHT BRIDGE DEVICES AS REQUIRED TO ROUTE COMMUNICATION AND DISTRIBUTE POWER DISHWASHER
TO 0-10V DIMMING DRIVER [GREY]
B HOT TO ALL CONNECTED SYSTEM DEVICES. BRIDGES SHALL BE CONNECTED WITH CAT-5 CABLING TO
TO 0-10 V DIMMING DRIVER [VIOLET] GATEWAY. QUANTITY OF BRIDGE DEVICES TO BE DETERMINED BY SYSTEM MANUFACTURER. LOCATE E.C. TO PROVIDE CORD
B NEUTRAL C. THE ELECTRICAL CONTRACTOR SHALL HOLD A PRE-CONSTRUCTION MEETING WITH THE LOCAL REPRESENTATIVE FROM THE
LIGHTING CONTROL SYSTEM MANUFACTURER PRIOR TO THE START OF CONSTRUCTION. BRIDGE DEVICE(S) ABOVE ACCESSIBLE CEILING NEAR AREAS BEING SERVED. CONNECT POWER AND PLUG
SUPPLIES TO NEARBY UNSWITCHED CIRCUITS. REFER TO SHOP DRAWINGS FOR QUANTITIES AND GARBAGE DISPOSAL
A APPROXIMATE LOCATIONS. SWITCHED RECEPTACLE
A D. AFTER CONSTRUCTION, THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE OWNER A RECORD DRAWING SET DETAILING THE
A TO ADDITIONAL LOCATIONS OF ALL CONTROL DEVICES LOCATED ABOVE CEILINGS AND THE LUMINAIRE OR GROUPS OF LUMINAIRES BEING
ELECTRICAL DETAILS

18" A.F.F.
TO ADDITIONAL A BRIDGES 3 NLIGHT LIGHTING CONTROL NETWORK LOAD CONTROLLER. CONNECT TO LUMINAIRES INDICATED ON
A CONTROLLED BY EACH DEVICE.
BRIDGES PLANS. REFER TO LIGHTING CONTROL DEVICE SCHEDULE FOR ADDITIONAL INFORMATION ABOUT TYPE.
2 1
A PROVIDE SENSING CONNECTION AS REQUIRED FOR OPERATION OF UL924 EMERGENCY DEVICES.
E. THE SYSTEM SHALL NOT REQUIRE ANY CENTRALLY HARDWIRED SWITCHING EQUIPMENT. PROVIDE POWER SUPPLIES, CABLING,
AND ALL OTHER EQUIPMENT REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM. PROVIDE 0-10V CONTROL WIRING TO ALL LUMINAIRES CONTROLLED BY 0-10V DIMMING DEVICES. REFER E.C. TO PROVIDE CORD
TO SHOP DRAWINGS FOR QUANTITIES AND APPROXIMATE LOCATIONS. AND PLUG
HUB F. PROVIDE NLIGHT POWER/SWITCH PACKS (REFER TO PLANS FOR TYPES AND QUANTITIES REQUIRED). LOCATE ALL LIGHTING
4 NLIGHT LIGHTING CONTROL NETWORK PUSH-BUTTON WALLPOD. REFER TO LIGHTING CONTROL DEVICE
D CONTROL RELAYS ABOVE ACCESSIBLE CEILINGS NEAR FIXTURES BEING CONTROLLED. IN AREAS WITHOUT ACCESSIBLE
A A CEILINGS, LOCATE RELAY IN JUNCTION BOX AND PAINT TO MATCH EXPOSED CEILING. SCHEDULE FOR ADDITIONAL INFORMATION ABOUT TYPE. REFER TO PLANS FOR LOCATIONS AND
C
C ETHERNET G. DAISY CHAIN ALL NLIGHT-ENABLED DEVICES TOGETHER USING CAT-5 CABLING ROUTED IN CONDUIT ABOVE DRYWALL CEILINGS
QUANTITIES.
8 DISHWASHER/DISPOSAL CONNECTION (ISLAND)
2 CONNECTION 5 NLIGHT GRAPHIC WALLPOD. REFER TO PLANS FOR LOCATIONS AND QUANTITIES. CONNECT POWER
AND WHERE CEILING IS EXPOSED. CONDUIT NOT REQUIRED ABOVE ACCESSIBLE CEILINGS. PROVIDE J-HOOKS TO SUPPORT E5.02 NOT TO SCALE
FROM STRUCTURE AT 48" MAX SPACING. SUPPLY TO NEARBY UNSWITCHED CIRCUIT.

3 H. PROVIDE CONNECTIONS TO BRIDGE DEVICES SUCH THAT EACH ROOM/SPACE IS A SEPARATE LIGHTING CONTROL ZONE THAT 6 NLIGHT LOW VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR. REFER TO LIGHTING CONTROL DEVICE
B HOT
APPEARS IN SENSORVIEW PROGRAMMING SOFTWARE. SUBMIT SHOP DRAWINGS INDICATING PROPOSED CONNECTIONS SCHEDULE FOR ADDITIONAL INFORMATION ABOUT TYPE. REFER TO PLANS FOR LOCATIONS AND
B NEUTRAL C BETWEEN DEVICES. QUANTITIES.
C 7 NLIGHT LOW VOLTAGE WALL OCCUPANCY SENSOR SWITCH. REFER TO LIGHTING CONTROL DEVICE
I. ALL LOW VOLTAGE CAT-5 CABLING SHALL BE PLENUM RATED AND CONSIST OF PRE-TERMINATED CABLES FOR LENGTHS
SHORTER THAN 150 FEET. FOR LENGTHS GREATER THAN 150 FEET, TERMINATIONS SHALL BE MADE BY A LOW VOLTAGE SCHEDULE FOR ADDITIONAL INFORMATION ABOUT TYPE. REFER TO PLANS FOR LOCATIONS AND 119 SOUTH 49TH AVENUE
LICENSED TECHNICIAN AND/OR QUALIFIED CONTRACTOR. POOR TERMINATIONS WILL RESULT IN A NON-OPERABLE SYSTEM. QUANTITIES. OMAHA, NEBRASKA 68132
B B
HOT J. INITIAL START-UP, COMMISSIONING, AND PROGRAMMING SHALL BE COMPLETED BY A QUALIFIED FACTORY REPRESENTATIVE. 8 NLIGHT ENABLED LUMINAIRE. REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION ABOUT (402)551-0800
PROVIDE TRAINING FOR THE OWNER. TRAINING SHALL BE VIDEO AND AUDIO RECORDED. COORDINATE TIME WITH ARCHITECT, TYPE. REFER TO PLANS FOR LOCATIONS AND QUANTITIES.
NEUTRAL MEI PROJECT NO: 19164
ELECTRICAL ENGINEER, AND OWNER.
9 NLIGHT NIO PC KIT WITH OUTDOOR PHOTOCELL. CONNECT POWER SUPPLY TO NEARBY UNSWITCHED RY N PROJECT: 17073
K. PROVIDE ENGRAVINGS FOR ALL WALLPOD DEVICES AND WALL SWITCH OCCUPANCY SENSORS. 120V CIRCUIT WITH ADEQUATE CAPACITY. REFER TO PLANS FOR LOCATIONS AND QUANTITIES - morrIssey c copyright
permission to reproduce all or part of this drawing is hereby granted
I A
N CTIO
COORDINATE EXACT LOCATION OF PHOTOCELL WITH ARCHITECT (FACING NORTH). engIneerIng Inc DATE: 8/26/19
LIM NSTRU
solely for the limited purpose of construction of this project or archiving.

8/27/2019 7:44:56 AM
unauthorized copying, disclosure or construction use without written
E
PR R CO
10 NIO X KIT FOR THIRD PARTY SYSTEM INTERFACE. REFER TO PLANS FOR LOCATIONS AND QUANTITIES. mechanical | electrical | lighting | technology | commissioning permission of morrissey engineering, inc. is prohibited by copyright law.
PROVIDE RS-232 CONNECTION TO 3RD PARTY A/V SYSTEM.
9 TYPICAL LIGHTING CONTROL DIAGRAM 4940 North 118th Street
note:
do not scale drawings. verify all dimensions and clearances from T FO
E5.02 Omaha, NE 68164 architectural, structural, shop and other appropriate drawings or
N O C COPYRIGHT 2018

E5.02
NOT TO SCALE P: 402.491.4144 at site. lay out and coordinate all work prior to installation to

www.morrisseyengineering.com
provide clearances required for operation, maintenance, and codes
and verify non-interference with other work. do not fabricate prior
to verification of clearance for all trades.
SHEET:
8/26/19