ISSUED FOR:
ISSUE DATE:
PROJECT NUMBER:
BUILDING PERMIT
07DEC 2020
ARCHITECTURAL
A0.01
A001
COVER SHEET
PROPOSED SITE PLAN
DEVELOPMENT - BUILDING 1 OWNER
2354538 ONTARIO INC.
A0.02 OBC DATA MATRIX AND CODE COMPLIANCE PLAN C/O 3245HARVESTER RD., UNIT 14
A0.03 WALL TYPES
UPPER CENTENNIAL PKWY & MUD ST W
BURLINGTON, ON L7N 3T7
A1.01
A1.02
GROUND FLOOR PLAN
ROOF PLAN
HAMILTON, ON
A2.01 ELEVATIONS
A4.01 WALL SECTIONS ARCHITECT
A4.02 WALL SECTIONS SAPLYS ARCHITECTS INC.
A6.01 DOOR SCHEDULE
A6.02 WINDOW SCHEDULE
610 FORD DRIVE, SUITE 338
OAKVILLE, ON L6J 7W4
STRUCTURAL
S-000 COVER SHEET DEVELOPMENT CONSULTANT
DEVELOPMENT - BUILDING 1
S-103 TYPICAL DETAILS OAKVILLE, ON L6J 7W5
S-104 TYPICAL DETAILS
S-105 TYPICAL DETAILS 07DEC 2020 TEL: 905-337-7249
S-106 TYPICAL DETAILS URL: APIDEVELOPMENTCONSULTANTS.COM
S-107 TYPICAL DETAILS
S-108 LOADING PLANS
S-200 FOUNDATION PLAN STRUCTURALENGINEER
S-201 ROOF FRAMING PLAN
S-300 ELEVATIONS
EXP SERVICES INC.
S-301 ELEVATIONS 499 KING ST E, SUITE 200
S-400 SCHEDULES HAMILTON, ON L8N 1C9
MECHANICAL& PLUMBING
M1.0 MECHANICAL LEGEND & DRAWING LIST
MECHANICALENGINEER
M1.1 MECHANICAL SPECIFICATIONS I MILLENNIUM® ENGINEERING INC.
M2.1 UNDERGROUND DRAINAGE LAYOUT 5045MAINWAY, #211
M2.2 GROUND FLOOR PLUMBING LAYOUT
M3.1 GROUND FLOOR HVAC LAYOUT BURLINGTON, ONTARIO L7L 5H9
M3.2 MECHANICAL ROOF PLAN
M4.1 MECHANICAL DETAILS I
M4.2 MECHANICAL DETAILS II
M5.1 MECHANICAL SCHEDULES I
ELECTRICAL
E01 ELECTRICAL SITE PLAN
E02 GROUND FLOOR POWER AND LIGHTING PLAN
E03 ELECTRICAL ROOF PLAN
E04 ELECTRICAL SPECIFICATION, LEGEND AND NOTES
UPPER CENTENNIAL
PKWY & MUD ST W
HAMILTON, ON
PROJECT ADDRESS:
BUILDING ENVELOPE INSULATION VALUES
ROOF
INSULATION ENTIRELY
R-35 ci
ABOVE DECK
WALLS
WALL ABOVE GRADE,
SPATIAL SEPARATION
R-13 + R-12 ci
STEEL FRAMED
VERTICAL LIMITING UNPROTECTED
ELEVATION EBF (m 2 )
FLOORS FENESTRATION (%) DISTANCE (m) OPENING ALLOWED
TD: 51'-7"
DATE
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-110 OBC, WT & FIRE SEPARATION B1 | PLOT DATE: November 8, 2021
ISSUE BY DESCRIPTION [DD-MMM-YYYY]
GENERAL NOTES
TD: 42'-11"
TD: 42'-11"
TD: 42'-11"
TD: 52'-4"
DEVELOPMENT CONSULTANT
2"
5'-
:4
TD
TD: 42'-2"
PROJECT NAME
TD: 42'-2"
TD: 38'-0"
TD: 41'-2"
MECH.
ROOM UPPER CENTENNIAL
10.6m2 COMMERCIAL DEVELOPMENT
OCC. 0 PER. BUILDING 1
BY DESIGN PROJECT ADDRESS
UPPER CENTENNIAL PKWY & MUD ST W
HAMILTON, ON
DRAWING TITLE
A0.02
S20-031
SCALE: 3/32"=1'-0" A0.02 SCALE: 1"=1'-0" A0.02 SCALE
1
AS NOTED
WALL & PARTITION TYPE NOTES
GENERAL
1. CONFIRM & COORDINATE ALL STUD WALL VERTICAL
SPAN / HEIGHT LIMITATIONS WITH MANUFACTURER.
2. COORDINATE W/ INTERIOR DESIGN DRAWINGS FOR
LOCATIONS OF WALL BLOCKING & SHEET METAL OR
PLYWOOD REINFORCING FOR WALL MOUNTED
EQUIPMENT.
3. COMBUSTIBLE MATERIALS SHALL COMPLY WITH OBC
2012 ARTICLE 3.1.5.12
4. EXTEND GYPSUM BOARD 8" ABOVE CEILING ON GROUND
FLOOR.
5. CONTRACTOR TO PROVIDE 3/4" FIRE RETARDANT
PLYWOOD BACKING FOR SIGNAGE SUPPORT (TO BE
APPROVED UNDER SEPARATE PERMIT), TO BE 12"
LARGER THAN SIGNAGE MIN. ON ALL SIDES.
INTERIOR
PERIMETER ACOUSTICAL SEALANT AT STC RATED
±2mm ±1/16" LAMINA FINISH: BASE COAT, REINFORCING MESH & FINISH PARTITIONS
COAT (REFER TO ELEVATIONS FOR COLOUR & TEXTURE)
75mm 3" EXPANDED POLYSTYRENE (EPS) RIGID INSULATION BD
(MIN R12 CI) ADHERED TO SUBSTRATE C/W DRAINAGE
CHANNELS
1 5 - DUAL WATER RESISTIVE BARRIER (WRB) & AIR BARRIER
3" 2" 8" 8"
13mm 1/2" EXTERIOR GLASS FIBER MAT GYPSUM BOARD SHEATHING
1'-01 8" 152mm 6" ENGINEERED STEEL STUD FRAMING C/W
- BATT INSULATION (MIN R13) TO FILL STUD CAVITY
- 6 MIL POLYETHYLENE VAPOUR RETARDER
16mm 5/8" GYPSUM WALL BOARD
WE1A SAME AS WE1 WITH ADDED 6" METAL STUD FURRING (IN ADDITION TO 8"
STUD).
SAME AS WE1 WITH ADDED 3 5/8" METAL STUD FURRING (IN ADDITION TO
WE1B
8" STUD)
89mm 3 1/2"
3 1/2 " MASONRY VENEER MECHANICALLY FASTENED 2 NZ ISSUED FOR CONSTRUCTION 01-NOV-2021
TO STEEL STUDS, C/W WEEP HOLES & VENTS AS PER
1 AF ISSUED FOR BUILDING PERMIT 07-DEC-2020
STONE MFG. SPEC. (REFER TO ELEVATION FOR TYPES)
DATE
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-110 OBC, WT & FIRE SEPARATION B1 | PLOT DATE: November 8, 2021
25mm 1" AIR SPACE ISSUE BY DESCRIPTION [DD-MMM-YYYY]
51mm 2" EXTRUDED POLYSTYRENE (XPS) RIGID INSULATION BD
GENERAL NOTES
(MIN R12ci)
- DUAL WATER RESISTIVE BARRIER (WRB) & AIR BARRIER DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS
16mm 5/8" SECUROCK GLASS-MAT SHEATHING OR EQUIV. PROVIDE M AR KED " ISSUED FOR C ON STR U C TION " . VERIFY
31 2" 1" 2" 5
8" 6" 5
8" REINFORCING & SEALANT AS REC. BY MANUFACTURER CONFIGURATIONS & DIMENSIONS ON SITE BEFORE
3 AT JOINTS & INTERSECTIONS FOR CONT. AIR BARRIER BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF
1'-3 4"
SUPPORT ANY ERRORS, OMISSIONS OR DISCREPANCIES.
152mm 6" ENGINEERED STEEL STUD FRAMING @ 16" O.C.
(SUPPLIER TO PROVIDE ENG. STAMPED SHOP DWGS.) CLIENT
WE2
C/W 2354538 ONTARIO INC.
- BATT INSULATION (MIN R13) TO FILL STUD CAVITY C/O 3245 HARVESTER RD., UNIT 14
- - 6 MIL POLYETHYLENE VAPOUR RETARDER BURLINGTON, ON L7N 3T7
16mm 5/8" GYPSUM WALL BOARD DEVELOPMENT CONSULTANT
±2mm ±1/16" FULL ADHERED EPDM ROOFING MEMBRANE 16mm 5/8" TYPE X GYPSUM BOARD AS REC. BY MANUFACTURER AT JOINTS &
13mm 1/2" PROTECTION BOARD 92mm 8" STEEL STUDS @ 16"/ 406mm O/C INTERSECTIONS FOR CONT. AIR BARRIER SUPPORT UPPER CENTENNIAL
WE3
152mm 6" MIN TAPERED POLYISOCYANURATE RIGID INS. (MIN R35ci) 89mm 3 1/2" ROXUL AFB INSULATION WITHIN 152mm 6" ENGINEERED STEEL STUD FRAMING @ 16" O.C. COMMERCIAL DEVELOPMENT
· VAPOUR RETARDER (OVER HEATED SPACES) STUD CAVITY (SUPPLIER TO PROVIDE ENG. STAMPED SHOP DWGS.) BUILDING 1
STRUCTURAL STEEL DECK, REFER TO STRUCTURAL DWG'S 16mm 5/8" TYPE X GYPSUM BOARD C/W
R1 PROJECT ADDRESS
89mm 3-1/2" BATT INSULATION (MIN R13) TO FILL STUD CAVITY UPPER CENTENNIAL PKWY & MUD ST W
5
8" 8" 5
8"
P1A P1A SAME AS P1, WITH 3-5/8" INSTEAD OF - - 6 MIL POLYETHYLENE VAPOUR RETARDER
NOTE: SLOPE MEMBRANE TOWARDS DRAIN MIN 2% VIA TAPERED HAMILTON, ON
8" STEEL STUD. P.ENG TO CONFIRM 16mm 5/8" GYPSUM WALL BOARD
INSULATION OR STRUCTURE. 91 4" DRAWING TITLE
STEEL STUD SIZE
R-VALUE FRR TEST REF. STC & REF FRR TEST REF. STC TEST REF. NOTE: PROVIDE TWO-STAGED DRAINED CAULKING & BACKER ROD
P1 P1A BETWEEN PANELS ON ALL SIDES. PROVIDE IMPACT RESISTANT WALL TYPES
MIN. R40 - - - 1 HR ULC W453 40 RAL-TL11-125 REINFORCING MESH AT GROUND FLOOR LOCATIONS <6'-0" AFF.
BY CHECK ISSUED FOR
NZ - SEE TABLE ABOVE
A0.03
S20-031
SCALE: 1"=1'-0" A0.03 SCALE: 1"=1'-0" A0.03 SCALE
1
1"=1'-0"
GENERAL NOTES
1. INTERIOR BUILD-OUT TO BE APPLIED FOR UNDER A
SEPARATE PERMIT
2. WASHROOMS ARE RESPONSIBILITY OF TENANTS
(UNDER SEPARATE PERMIT)
3. ALL FLOOR FINISHES TO BE INSTALLED BY TENANT
4. TENANTS TO PROVIDE DRAWINGS FOR UNDER-SLAB
ROUGH-INS
5. POUR SLABS THOUGH EXTERIOR DOOR OPENINGS
6. PROVIDE 4" OF UNDER-SLAB RIGID INSULATION AT ALL
EXTERIOR DOORWAYS
5. MIN R-15 UNDER-SLAB INSULATION FOR 48" AT FULL
BUILDING PERIMETER.
6. DRAWING LINES IN GRAYSCALE REPRESENT 'TENANT
WORK' AND ARE NOT INCLUDED IN THE BASE BUILDING
DRAWINGS. TENANT WORK IS SHOWN AS REFERENCE
ONLY. SPECIFIC CODE REQUIREMENTS FOR TENANT
WORK ARE NOTED ON THE OBC MATRIX, AND WHERE
REQUIRED ON THE BASE BUILDING DRAWINGS.
2 SYMBOL LEGEND
A2.01 # DOOR TAG
1
# KEY NOTE
1 A4.01 2a 2 2b 3
20'-2" 5'-10" 10'-7" 15'-5" 111 4" # REVISION
73 8"
53'-65 8" # WINDOW TAG
WE1a 1'-6" 3'-4" 14'-4" 3'-4" 14'-4" 3'-4" 1'-6" 8'-65 8" 3'-4"
WT WALL TYPE
1'-11 8"
111 8"
2
3'-4"
R L
6'-61 8"
14'-4"
R 101
W2 GAS METER LOCATION
3
1° (C/W BOLLARDS AS PER GAS METER SPECS.)
14'-4"
28'-1 2"
45.0
27'-71 2"
UNIT 1-1 R
142.0 m²
(1,529.2 sf)
3X W1 4 SIAMESE CONNECTION
10'-51 2"
B1
ROOF ACCESS LADDER, AS PER MMAH
WE2 SUPPLEMENTARY STANDARD
7'-51 2"
WE1 7
SB-8, “DESIGN, CONSTRUCTION AND INSTALLATION
2 1
OF ANCHORAGE SYSTEM FOR FIXED ACCESS
1'-
11
14'-11"
5
8 LADDERS”
"
B B 8
21'-25 8"
FROST SLAB (REFER TO STRUCT. DWGS)
6'-8"
2 P1
11
E2
'-0
A4.01
"
102
W
1'-
B2
E2
11
"
5
1
W6
"
'-3
4 6 A4.02 8
8'-10"
62
W4
11
21'-31 8" 40'-0" 40'-11 2" 111 8"
'-0
"
103 80'-8"
2'-53 8"
1'-
UNIT 1-2 5 3'-105 8"
32'-21 4"
11
3'-3"
"
WE1 211.8 m²
W6
111 8"
(2,280.2 sf) WE2 WE2 WE2 WE2 4
1'-
6"
W
C
E2
3'-4"
R L R L
1X 5 104 W1 W1 105 5 5 106 W1 W1 107 5
W3 2 NZ ISSUED FOR CONSTRUCTION 01-NOV-2021
W
WE2
E1
a
14'-4"
DATE
ISSUE BY DESCRIPTION [DD-MMM-YYYY]
W3
GENERAL NOTES
14'-4"
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS
4 3 M AR KED " ISSUED FOR C ON STR U C TION " . VERIFY
25'-101 2"
A2.01 A2.01 CONFIGURATIONS & DIMENSIONS ON SITE BEFORE
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-200 PLANS B1 | PLOT DATE: November 8, 2021
P1
BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF
6'-4"
W
E1
E2
WE1
CLIENT
D2 2354538 ONTARIO INC.
3'-13 8" C/O 3245 HARVESTER RD., UNIT 14
R UNIT 1-3 UNIT 1-4 UNIT 1-5 UNIT 1-6 UNIT 1-7
W2 216.7 m² 97.7 m² 97.8 m² 99.6 m² 90.8 m² BURLINGTON, ON L7N 3T7
(2,332.5 sf) (1,052.0 sf) (1,053.0 sf) (1,072.2 sf) (977.8 sf) DEVELOPMENT CONSULTANT
53'-71 4"
2'-
26'-11 4"
W
14
E2
112
24'-101 2"
2"
TRUE
2"
3 7 WE2
2
A4.02
Y
15'-0"
A4.02
MECH.
6 ROOM
2
14
14 m²
'-4
9'-10"
R L
23
E
'-1
1'-0"
W2 109 108 W8 115
WE2 WE2 WE2 COMMERCIAL DEVELOPMENT
F BUILDING 1
6'-
111 8"
PROJECT ADDRESS
3"
2
5 8"
6'-91 4" 14'-4" 7'-3" 5'-7" 6'-5" 2'-05 8" 14'-4" 5'-8" 14'-4" 2'-03 4" 3'-8" 14'-4" 5'-8" 8'-111 2" 9'-31 8"
HAMILTON, ON
X 154'-111 4" DRAWING TITLE
111 8"
21'-3" 18'-3"
GROUND FLOOR PLAN
3a 3 4a 4
1 BY CHECK ISSUED FOR
A4.01
A2.01 NZ - SEE TABLE ABOVE
PROJECT No. SHEET No. SHEET REVISION
A1.01
S20-031
SCALE
1/8"=1'-0" 1
EXTEND ROOFING MEMBRANE UP MECHANICAL EQUIPMENT GENERAL ROOF NOTES
AND OVER CURB BY ROOFING CONT. REFER TO MECHANICAL DWGS
FLASHING CLAMP DEVICE 1. ROOF COVERING SHALL COMPLY WITH CAN/ULC-S107-M
GALV METAL FLASHING UP AND DOME SCREEN AND GRAVEL STOP
OVER CURB BY ROOFING CONT. 2. PROVIDE 2% SLOPE OF ROOF COVERING TOWARD ROOF DRAINS
PREFABRICATED OR FIELD INSTALLED VIA ROOF STRUCTURE (SEE STRUCTURAL DWG'S) AND/OR
FLOOD BASIN LEVEL 6" INSULATED METAL CURB C/W PROVIDE SUNKEN AREA SEAL VAPOR BARRIER TAPERED INSULATION.
1'-0" MIN.
ABOVE ROOF DRAIN 2x4 BLOCKING TO BE ANCHORED BY TAPERED INSULATION AT EDGE
3. PARAPETS TO SLOPE MIN. 2% TOWARDS ROOF TYP.
TO STRUCTURE SLOPE SLOPE CONTINUOUS SEALANT 4. SEE A-111 FOR ROOF TYPES DESCRIPTION
R1
50mm RIGID INSULATION TYPICAL PARAPET CONSTRUCTION 5. LOCATIONS OF ALL ROOF TOP EQUIPMENT, PLUMBING, VENTS,
ADHESIVE W/ 9" QUICKSEAM FLASHING. CONDENSING UNITS, EXHAUST FANS, ROOF EXHAUSTS, BOILER
CANT STRIP AND BLOCKING FLUES, ROOF DRAINS ETC. ARE APPROXIMATE (SEE
PROVIDE CLEAN SURFACE BEFORE
WOLMANIZED WOOD PLATE. MECHANICAL DRAWINGS FOR EXACT SIZES AND LOCATIONS)
APPLYING ADHESIVE.
CUT TO SUIT
EXTEND FLEXIBLE VAPOR BARRIER UP 6. ALL ROOF TOP EQUIPMENT, PLUMBING, VENTS, CONDENSING
METAL CURBING FULL HEIGHT UNITS, EXHAUST FANS, BOILER FLUES, ETC. ARE TO BE
8" (W) x 4" (H) OPENING FOR SCUPPER CONCEALED FROM VIEW BEHIND PARAPET WALLS OR
R1 PROVIDE CONTINUOUS BEAD OF MECHANICAL EQUIPMENT SCREENS. MECHANICAL EQUIPMENT
CAST IRON CLASP CAULKING SCREEN TO BE TALL ENOUGH TO FULLY HIDE EQUIPMENT.
TO U/S OF THE 9" FORMFLASH CENTERED OVER SLOPE
CLAMP DEVICE PROVIDE CLEARANCE AND ACCESS AS REQUIRED BY
STEEL DECK 5" FLASHING AT BASE OF SCUPPER EQUIPMENT MANUFACTURER AND/OR LOCAL CODE PROVISIONS
PREFINISHED FLASHING, COLOUR
TO MATCH ADJACENT FINISH 7. ENSURE ALL ROOF TOP PENETRATIONS ARE AIR AND WATER
5" FLASHING CENTERED OVER SEALED AS PER NRCA REQUIREMENTS (TYP.)
EDGE OF SCUPPER FLANGE
8. ROOF ANCHORS ARE REQUIRED AS PER OBC. ROOF ANCHOR
MECHANICAL CURB DETAIL 4 ROOF DRAIN DETAIL 3
WOLMANIZED WOOD PLATE.
CUT TO SUIT
SUPPLIER TO PROVIDE B.C.I.N NUMBER STAMPED SHOP
DRAWINGS CONFORMING TO ALL JURISDICTIONAL AND CODE
SCALE: 1"=1'-0" A1.02 SCALE: 1"=1'-0" A1.02 REQUIREMENTS. LOCATION OF ANCHORING NOT SHOWN ON
WOOD NAILER THIS ROOF PLAN. REFER TO SHOP DRAWINGS FOR AMOUNT,
LOCATION AND SIZE.
9. MIN. R-35ci ROOF INSULATION TO BE PROVIDED
1 R1
1 A4.01 2a 2 2b 3
ROOF KEY NOTES
20'-2" 5'-10" 10'-7" 15'-5"
1 ROOF DRAIN (REFER TO DETAIL)
HIGH PARAPET LOW PARAPET ROOF TOP UNIT - REFER TO MECHANICAL DWGS.
2 (FOR CURB DETAIL REFER TO DETAIL)
LOW PARAPET
CONTINUOUS CANT STRIP - TYPICAL AROUND
1° 7
45.0 PARAPET PERIMETERS AND ALL CURBS
SL
27'-71 2"
OP
3X
E
B1
7'-51 2"
2
4'-0"
A2.01
B B
1
21'-25 8"
6'-8"
2 7
A4.01
31
B2
'-
4"
HI
GH
SL
O
1
PA
PE SLOPE
"
RA
'-3
4 6 A4.02 8
62
PE
T
HIGH PARAPET
2
21'-31 8" 40'-0" 40'-11 2"
SLOPE
32'-21 4"
5 LOW PARAPET
3
1X 5 ISSUE BY DESCRIPTION
DATE
[DD-MMM-YYYY]
7 GENERAL NOTES
PE
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-200 PLANS B1 | PLOT DATE: November 8, 2021
BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF
SLOPE
4 3 ANY ERRORS, OMISSIONS OR DISCREPANCIES.
25'-101 2"
A2.01 A2.01
CLIENT
SL 2 2 2 E 2
OP OP
E SL 2354538 ONTARIO INC.
C/O 3245 HARVESTER RD., UNIT 14
D2 7 BURLINGTON, ON L7N 3T7
LOW PARAPET
DEVELOPMENT CONSULTANT
7 API DEVELOPMENT CONSULTANTS INC.
1464 UNIT #7 CORNWALL ROAD
OAKVILLE, ON L6J 7W5
SLOPE
ARCHITECT
4'-0"
W
PA
SLOPE SLOPE 6
PE
SLOPE
1 3 1
5
TH
NOR
TRUE
24'-101 2"
3 PE 4
SLO SLO 2
A4.02 PE
Y A4.02 PROJECT NAME
SLOPE
4
HI
UPPER CENTENNIAL
G H
PA
COMMERCIAL DEVELOPMENT
RA
PE
23
7 E BUILDING 1
'-1
5
0"
1'-0"
PROJECT ADDRESS
UPPER CENTENNIAL PKWY & MUD ST W
F HAMILTON, ON
DRAWING TITLE
3"
2'-
A1.02
S20-031
SCALE
SCALE: 1/8"=1'-0" A1.02 1/8"=1'-0" 1
GENERAL NOTES
A B1 B B2 D2 E F
2 1. CONTRACTOR TO PROVIDE 3/4" FIRE RETARDANT
A4.01 ROOF PLYWOOD BACKING FOR SIGNAGE SUPPORT (TO BE
SCUPPER APPROVED UNDER SEPARATE PERMIT), TO BE 12"
C 3 D 1 A 2 D 1 A 1
D 1 B 1 23'-5"
LARGER THAN SIGNAGE MIN. ON ALL SIDES.
C 3
2'-11"
T/O HIGH PARAPET 2. ILLUMINATED SIGNS UNDER SEPARATE PERMITS.
20'-6"
CONTRACTOR TO PROVIDE ELECTRICAL OUTLETS.
T/O LOW PARAPET
4'-1"
16'-5" SYMBOL LEGEND
U/S OF DECK
X # FINISH TAG
SIGNAGE SIGNAGE SIGNAGE
23'-5"
EXTERIOR WALL SCONCE
A 1
16'-5"
FINISH LEGEND
EIFS - TERRANEO
A 1 COLOUR : DARK GRAY
A 2
EIFS - SMOOTH
0'-0" A 2
T/O GR. FLOOR COLOUR : MEDIUM GRAY
STONE VENEER,
SOUTH ELEVATION 4
B 1
LIGHT GREY
SCALE: 1/8" = 1'-0" A2.01 STONE VENEER,
B 2
DARK GREY
2'-11"
T/O HIGH PARAPET
FOR AMOUNT OF GAS METERS REFER
TO MECHANICAL DRAWINGS. A 2
20'-6"
T/O LOW PARAPET D 1 ILLUMINATED SIGN,
(UNDER SEPARATE PERMIT)
4'-1"
A 2
SIGN SIGN SIGNAGE 16'-5"
U/S OF DECK
C 1 C 1
23'-5"
16'-5"
B 2 B 2
0'-0"
T/O GR. FLOOR
B 2 B 2 B 2
NORTH ELEVATION 3
SCALE: 1/8" = 1'-0" A2.01
1
1
8 6 4 3 2b 2 2a A4.01 1
A4.02
C 3 D 1 C 2 C 1 A 1 C 3 A 2 B 2 D 1 B 2 A 1 C 3
C 3 D 1 D 1 D 1 D 1 ROOF
23'-5"
SCUPPER
ROOF
2'-11"
T/O HIGH PARAPET
SCUPPER
C 1 20'-6"
T/O LOW PARAPET
4'-1"
A 2
SIGNAGE SIGNAGE SIGNAGE SIGNAGE SIGN SIGN SIGN A 2
16'-5"
U/S OF DECK
2
1
NZ
AF
ISSUED FOR CONSTRUCTION
07-DEC-2020
C 1 C 1
23'-5"
DATE
ISSUE BY DESCRIPTION [DD-MMM-YYYY]
GENERAL NOTES
16'-5"
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-300 ELEVATIONS B1 | PLOT DATE: November 8, 2021
M AR KED " ISSUED FOR C ON STR U C TION " . VERIFY
CONFIGURATIONS & DIMENSIONS ON SITE BEFORE
B 2 B 1 BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF
ANY ERRORS, OMISSIONS OR DISCREPANCIES.
CLIENT
0'-0"
T/O GR. FLOOR
2354538 ONTARIO INC.
max. 3'-0"
min. 1'-0"
D 1 C 3 A 1
D 1 C 3 C 3 D 1 C 1 B 2 D 1 A 2 B 1 D 1 D 1 C 3 23'-5"
C 3
2'-11"
ROOF T/O HIGH PARAPET
SCUPPER
20'-6"
T/O LOW PARAPET
4'-1"
A 2 SIGNAGE SIGNAGE SIGNAGE SIGNAGE A 2
16'-5"
U/S OF DECK PROJECT NAME
UPPER CENTENNIAL
SIGNAGE SIGNAGE
23'-5"
COMMERCIAL DEVELOPMENT
B 1
C 1 BUILDING 1
PROJECT ADDRESS
16'-5"
UPPER CENTENNIAL PKWY & MUD ST W
HAMILTON, ON
B 2 DRAWING TITLE
ELEVATIONS
0'-0"
T/O GR. FLOOR
BY CHECK ISSUED FOR
NZ - SEE TABLE ABOVE
EAST ELEVATION 1
PROJECT No. SHEET No. SHEET REVISION
A2.01
S20-031
SCALE: 1/8" = 1'-0" A2.01 SCALE
1
1/8"=1'-0"
F 1 A
SLOPE AIR/MOISTURE BARRIER LAPPED UP OVER SLOPE AIR/MOISTURE BARRIER LAPPED UP OVER SLOPE AIR/MOISTURE BARRIER LAPPED UP OVER
23'-5" 23'-5" 23'-5"
PARAPET & UNDER METAL FLASHING PARAPET & UNDER METAL FLASHING PARAPET & UNDER METAL FLASHING
T/O HIGH PARAPET T/O HIGH PARAPET T/O HIGH PARAPET
PREFINISHED METAL CAP PREFINISHED METAL CAP SEALANT PREFINISHED METAL CAP
1'-7"
SEALANT SEALANT 6"
FLASHING C/W STARTER STRIP FLASHING C/W STARTER STRIP FLASHING C/W STARTER STRIP
EIFS
PROVIDE LOUVER VENT AS NEEDED PROVIDE LOUVER VENT AS NEEDED PROVIDE LOUVER VENT AS NEEDED
SEALANT C/W WEEPS @ 2' O/C
1'-4"
PREFINISHED METAL SIDING (TYPE: CL-725-R PREFINISHED METAL SIDING (TYPE: CL-725-R PREFINISHED METAL SIDING (TYPE: CL-725-R
OR CL-622-RBY VICWEST OR APPROVED EQ, OR CL-622-RBY VICWEST OR APPROVED EQ, SIM TO WE3 OR CL-622-RBY VICWEST OR APPROVED EQ,
COLOR: STONE GREY) COLOR: STONE GREY) COLOR: STONE GREY)
- ON 78" FURRING CHANEL @ 24" O.C. MAX - ON 78" FURRING CHANEL @ 24" O.C. MAX - ON 78" FURRING CHANEL @ 24" O.C. MAX
PREFINISHED METAL FLASHING
(HORIZONT.) (HORIZONT.) (HORIZONT.)
C/W DRIP EDGE,
- ON PEEL AND STICK MEMBRANE - ON PEEL AND STICK MEMBRANE - ON PEEL AND STICK MEMBRANE
COLOUR TO MATCH ADJACENT FINISH
- ON 1/2" EXTERIOR SHEATHING - ON 1/2" EXTERIOR SHEATHING - ON 1/2" EXTERIOR SHEATHING
9'-1"
9'-1"
CONT. METAL FLASHING UPSTAND MIN. 8" CONT. METAL FLASHING UPSTAND MIN. 8" SEALANT C/W WEEPS @ 2' O/C CONT. METAL FLASHING UPSTAND MIN. 8"
CONU. SEAL UNDER MEMBRANE CONU. SEAL UNDER MEMBRANE CONU. SEAL UNDER MEMBRANE
6'-2"
FILL CAVITY WITH MEDIUM FILL CAVITY WITH MEDIUM FILL CAVITY WITH MEDIUM
DENSITY SPRAY FOAM INSULATION CONT. FIBRE CANT STRIP R1 DENSITY SPRAY FOAM INSULATION CONT. FIBRE CANT STRIP R1 DENSITY SPRAY FOAM INSULATION CONT. FIBRE CANT STRIP R1
TO LEVEL THAT MATCHES TO LEVEL THAT MATCHES TO LEVEL THAT MATCHES
ROOF R INSULATION VALUE ROOF R INSULATION VALUE ROOF R INSULATION VALUE
1'-4"
C/W DRIP EDGE, WE3
1'-4"
COLOUR TO MATCH ADJACENT FINISH
2'-111 2"
STEEL ANGLE
DRIP EDGE REFER TO STRUCTURAL
10'-0 1/2" 10'-0 1/2"
U/S HSS HEADER U/S HSS HEADER
PREFINISHED METAL FLASHING RETURN GYPSUM BOARD RETURN GYPSUM BOARD
PREFINISHED METAL FLASHING
C/W DRIP EDGE
SEALANT C/W DRIP EDGE SEALANT
6" 6"
BACKER ROD & SEALANT
C/W WEEPS @ 600 O/C BACKER ROD & SEALANT
C/W WEEPS @ 600 O/C
12'-4"
AL WINDOW AL WINDOW 2 NZ ISSUED FOR CONSTRUCTION 01-NOV-2021
DATE
ISSUE BY DESCRIPTION [DD-MMM-YYYY]
LOW EXPANSION SPRAY FOAM
9'-41 2"
9'-41 2"
LOW EXPANSION SPRAY FOAM GENERAL NOTES
ALL AROUND WINDOW FRAME
ALL AROUND WINDOW FRAME
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-400 WALL SECTIONS B1 | PLOT DATE: November 8, 2021
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS
SEALANT M AR KED " ISSUED FOR C ON STR U C TION " . VERIFY
SEALANT
CONFIGURATIONS & DIMENSIONS ON SITE BEFORE
RETURN GYPSUM BOARD BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF
RETURN GYPSUM BOARD
ANY ERRORS, OMISSIONS OR DISCREPANCIES.
6 MIL POLY VAPOUR BARRIER
6 MIL POLY VAPOUR BARRIER
BACKER ROD & SEALANT BACKER ROD & SEALANT SILL PLATE GASKET BETWEEN BACKER ROD & SEALANT CLIENT
C/W WEEPS @ 2' O/C C/W WEEPS @ 2' O/C FOUNDATION & STEEL STUDS C/W WEEPS @ 2' O/C METAL CORNER 2354538 ONTARIO INC.
METAL CORNER
C/O 3245 HARVESTER RD., UNIT 14
PREFINISHED METAL SILL THROUGH WALL FLASHING PREFINISHED METAL SILL SILL PLATE GASKET BETWEEN
BURLINGTON, ON L7N 3T7
C/W WATER DRIP EDGE. 3 5 8 " LGS STUD C/W BATT INSULATION MEMBRANE. TO EXTEND UP WALL 3 5 8 " METAL STUD C/W BATT INSULATION C/W WATER DRIP EDGE. FOUNDATION & STEEL STUD
DEVELOPMENT CONSULTANT
COLOUR TO MATCH WINDOW FRAME MIN 2" BEHIND AIR BARRIER COLOUR TO MATCH WINDOW FRAME 3-5/8" LGS STUD C/W BATT INSULATION
API DEVELOPMENT CONSULTANTS INC.
SEAL VAPOUR BARRIER INTO FLOOR SLAB SEAL VAPOUR BARRIER INTO FLOOR SLAB
SEAL VAPOUR BARRIER INTO FLOOR SLAB 1464 UNIT #7 CORNWALL ROAD
w/ CONT. ACOUSTIC CAULKING (TYP.) w/ CONT. ACOUSTIC CAULKING (TYP.)
EXPOSED CONCRETE TO BE EXPOSED CONCRETE TO BE EXPOSED CONCRETE TO BE w/ CONT. ACOUSTIC CAULKING (TYP.) OAKVILLE, ON L6J 7W5
PARGED SMOOTH PARGED SMOOTH PARGED SMOOTH 1/2" EXPANSION JOINT
8"
8"
8"
1/2" EXPANSION JOINT 1/2" EXPANSION JOINT ARCHITECT
0'-0" 0'-0" 0'-0"
SAPLYS ARCHITECTS INC.
T/O GR. FLOOR 35 8" T/O GR. FLOOR 35 8" T/O GR. FLOOR 35 8"
55 ST CLAIR AVE W, STE. 205
TORONTO, ON M4V 1N5
NORTH PROFESSIONAL CERTIFICATION
7" 4" 4'-0" 7" 4" 4'-0" 105 8" 4" 4'-0"
2" RIGID INSULATION EXTENDED 4' BELOW 2" RIGID INSULATION EXTENDED 4' BELOW 2" RIGID INSULATION EXTENDED 4' BELOW PROJECT NAME
GRADE, TYP. AROUND FOUNDATION GRADE, TYP. AROUND FOUNDATION GRADE, TYP. AROUND FOUNDATION
PERIMETER PERIMETER PERIMETER UPPER CENTENNIAL
GC TO COORDINATE ANY WEEPING GC TO COORDINATE ANY WEEPING GC TO COORDINATE ANY WEEPING COMMERCIAL DEVELOPMENT
CONC. FOUNDATION AND FOOTING , CONC. FOUNDATION AND FOOTING , CONC. FOUNDATION AND FOOTING ,
TILE REQUREMENTS WITH THE
REFER TO STRUCT. DWGS
TILE REQUREMENTS WITH THE
REFER TO STRUCT. DWGS
TILE REQUREMENTS WITH THE
REFER TO STRUCT. DWGS
BUILDING 1
GEOTECH REPORT AND MECH DWG'S GEOTECH REPORT AND MECH DWG'S GEOTECH REPORT AND MECH DWG'S PROJECT ADDRESS
UPPER CENTENNIAL PKWY & MUD ST W
HAMILTON, ON
DRAWING TITLE
WALL SECTIONS
A4.01
S20-031
SCALE: 1/2"=1'-0" A4.01 SCALE: 1/2"=1'-0" A4.01 SCALE: 1/2"=1'-0" A4.01 SCALE
1
1/2"=1'-0"
C1 8 C
AIR/MOISTURE BARRIER LAPPED UP OVER AIR/MOISTURE BARRIER LAPPED UP OVER
PREFINISHED METAL SIDING (TYPE: CL-725-R PREFINISHED METAL SIDING (TYPE: CL-725-R AIR/MOISTURE BARRIER LAPPED UP OVER PREFINISHED METAL SIDING (TYPE: CL-725-R
PARAPET & UNDER METAL FLASHING PARAPET & UNDER METAL FLASHING
OR CL-622-RBY VICWEST OR APPROVED EQ, OR CL-622-RBY VICWEST OR APPROVED EQ, PARAPET & UNDER METAL FLASHING OR CL-622-RBY VICWEST OR APPROVED EQ,
SLOPE SLOPE SLOPE
20'-6" COLOR: STONE GREY) 20'-6" COLOR: STONE GREY) 20'-6" COLOR: STONE GREY)
T/O LOW PARAPET - ON 78" FURRING CHANEL @ 24" O.C. MAX T/O LOW PARAPET - ON 78" FURRING CHANEL @ 24" O.C. MAX T/O LOW PARAPET - ON 78" FURRING CHANEL @ 24" O.C. MAX
(HORIZONT.) (HORIZONT.) PREFINISHED METAL CAP (HORIZONT.)
PREFINISHED METAL CAP - ON PEEL AND STICK MEMBRANE PREFINISHED METAL CAP - ON PEEL AND STICK MEMBRANE - ON PEEL AND STICK MEMBRANE
FLASHING C/W STARTER STRIP
FLASHING C/W STARTER STRIP - ON 1/2" EXTERIOR SHEATHING FLASHING C/W STARTER STRIP - ON 1/2" EXTERIOR SHEATHING - ON 1/2" EXTERIOR SHEATHING
SEALANT
SEALANT CONT. METAL FLASHING UPSTAND MIN. 8" CONT. METAL FLASHING UPSTAND MIN. 8" CONT. METAL FLASHING UPSTAND MIN. 8"
SEALANT
CONU. SEAL UNDER MEMBRANE CONU. SEAL UNDER MEMBRANE PROVIDE LOUVER VENT AS NEEDED CONU. SEAL UNDER MEMBRANE
PROVIDE LOUVER VENT AS NEEDED PROVIDE LOUVER VENT AS NEEDED
R1 R1 FILL CAVITY WITH MEDIUM R1
6'-2"
FILL CAVITY WITH MEDIUM CONT. FIBRE CANT STRIP FILL CAVITY WITH MEDIUM CONT. FIBRE CANT STRIP DENSITY SPRAY FOAM INSULATION CONT. FIBRE CANT STRIP
DENSITY SPRAY FOAM INSULATION DENSITY SPRAY FOAM INSULATION TO LEVEL THAT MATCHES
TO LEVEL THAT MATCHES TO LEVEL THAT MATCHES ROOF R INSULATION VALUE
ROOF R INSULATION VALUE ROOF R INSULATION VALUE
16'-5" 16'-5" 16'-5"
U/S OF DECK U/S OF DECK U/S OF DECK
WE1b
WE1b
SEALANT C/W WEEPS @ 2' O/C SEALANT C/W WEEPS @ 2' O/C
1'-4"
1'-4"
COLOUR TO MATCH ADJACENT FINISH COLOUR TO MATCH ADJACENT FINISH
SEALANT C/W WEEPS @ 2' O/C SEALANT C/W WEEPS @ 2' O/C
WE2
2'-111 2"
STEEL ANGLE
19'-10"
REFER TO STRUCTURAL
10'-0 1/2"
WE2 WE2
U/S HSS HEADER
PREFINISHED METAL FLASHING RETURN GYPSUM BOARD
C/W DRIP EDGE
SEALANT
6"
BACKER ROD & SEALANT
C/W WEEPS @ 600 O/C
12'-4"
AL WINDOW 2 NZ ISSUED FOR CONSTRUCTION 01-NOV-2021
DATE
ISSUE BY DESCRIPTION [DD-MMM-YYYY]
9'-41 2"
LOW EXPANSION SPRAY FOAM GENERAL NOTES
ALL AROUND WINDOW FRAME
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-400 WALL SECTIONS B1 | PLOT DATE: November 8, 2021
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS
M AR KED " ISSUED FOR C ON STR U C TION " . VERIFY
SEALANT CONFIGURATIONS & DIMENSIONS ON SITE BEFORE
BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF
RETURN GYPSUM BOARD
ANY ERRORS, OMISSIONS OR DISCREPANCIES.
6 MIL POLY VAPOUR BARRIER
WEEP HOLES IN BASE STONE WEEP HOLES IN BASE STONE BACKER ROD & SEALANT CLIENT
@ 2'-4" O/C @ 2'-4" O/C C/W WEEPS @ 2' O/C 2354538 ONTARIO INC.
METAL CORNER
C/O 3245 HARVESTER RD., UNIT 14
THROUGH WALL FLASHING MEMBRANE. SILL PLATE GASKET BETWEEN THROUGH WALL FLASHING MEMBRANE. SILL PLATE GASKET BETWEEN PREFINISHED METAL SILL SILL PLATE GASKET BETWEEN BURLINGTON, ON L7N 3T7
TO EXTEND UP WALL MIN 12" FOUNDATION & STEEL STUD TO EXTEND UP WALL MIN 12" FOUNDATION & STEEL STUD C/W WATER DRIP EDGE. FOUNDATION & STEEL STUD DEVELOPMENT CONSULTANT
BEHIND AIR BARRIER BEHIND AIR BARRIER COLOUR TO MATCH WINDOW FRAME API DEVELOPMENT CONSULTANTS INC.
SEAL VAPOUR BARRIER INTO FLOOR SLAB SEAL VAPOUR BARRIER INTO FLOOR SLAB SEAL VAPOUR BARRIER INTO FLOOR SLAB
1464 UNIT #7 CORNWALL ROAD
w/ CONT. ACOUSTIC CAULKING (TYP.) w/ CONT. ACOUSTIC CAULKING (TYP.) w/ CONT. ACOUSTIC CAULKING (TYP.)
EXPOSED CONCRETE TO BE EXPOSED CONCRETE TO BE EXPOSED CONCRETE TO BE OAKVILLE, ON L6J 7W5
PARGED SMOOTH PARGED SMOOTH PARGED SMOOTH
8"
8"
8"
1/2" EXPANSION JOINT 1/2" EXPANSION JOINT 1/2" EXPANSION JOINT ARCHITECT
0'-0" 0'-0" 0'-0"
SAPLYS ARCHITECTS INC.
T/O GR. FLOOR 35 8" T/O GR. FLOOR 35 8" T/O GR. FLOOR 35 8"
55 ST CLAIR AVE W, STE. 205
TORONTO, ON M4V 1N5
NORTH PROFESSIONAL CERTIFICATION
105 8" 4" 4'-0" 105 8" 4" 4'-0" 105 8" 4" 4'-0"
2" RIGID INSULATION EXTENDED 4' BELOW 2" RIGID INSULATION EXTENDED 4' BELOW 2" RIGID INSULATION EXTENDED 4' BELOW PROJECT NAME
GRADE, TYP. AROUND FOUNDATION GRADE, TYP. AROUND FOUNDATION GRADE, TYP. AROUND FOUNDATION
PERIMETER PERIMETER PERIMETER UPPER CENTENNIAL
GC TO COORDINATE ANY WEEPING GC TO COORDINATE ANY WEEPING GC TO COORDINATE ANY WEEPING COMMERCIAL DEVELOPMENT
CONC. FOUNDATION AND FOOTING , CONC. FOUNDATION AND FOOTING , CONC. FOUNDATION AND FOOTING ,
TILE REQUREMENTS WITH THE
REFER TO STRUCT. DWGS
TILE REQUREMENTS WITH THE
REFER TO STRUCT. DWGS
TILE REQUREMENTS WITH THE
REFER TO STRUCT. DWGS
BUILDING 1
GEOTECH REPORT AND MECH DWG'S GEOTECH REPORT AND MECH DWG'S GEOTECH REPORT AND MECH DWG'S PROJECT ADDRESS
UPPER CENTENNIAL PKWY & MUD ST W
HAMILTON, ON
DRAWING TITLE
WALL SECTIONS
A4.01
S20-031
SCALE: 1/2"=1'-0" A4.02 SCALE: 1/2"=1'-0" A4.02 SCALE: 1/2"=1'-0" A4.02 SCALE
1
1/2"=1'-0"
ABBREVIATION LEGEND DOOR NOTES
AL ANODIZED ALUMINUM 1. ALL EXTERIOR HOLLOW METAL DOORS SHALL BE
CL CLEAR GALVANIZED & INSULATED.
DG DOUBLE GLASS 2. ALL DOORS SHALL BE PRE-FINISHED (SHOP OR
EXIST EXISTING FACTORY). TOPS, BOTTOMS AND SIDES OF ALL DOORS
SHALL BE PAINTED OR STAINED TO MATCH DOOR
GL GLAZED
FINISH/COLOR.
HM HOLLOW METAL
3. OUT-SWINGING EXTERIOR DOORS MUST HAVE CLOSED
IHM INSULATED HOLLOW METAL TOPS
IST INSULATED STEEL
4. EXTERIOR DOORS MUST HAVE WEATHER STRIPPING
PF PRE-FINISHED WITH THE APPROPRIATE TYPE OF THRESHOLD.
PH PANIC HARDWARE 5. PROVIDE CONSTRUCTION CYLINDERS DURING
PS PRESSED STEEL CONSTRUCTION. FOR DOORS REQUIRED TO BE LOCKED 20 196379 000 00 C3
PT PAINT REPLACE CONSTRUCTION CYLINDERS PRIOR TO HOTEL
OPENING (COORDINATE WITH GENERAL CONTRACTOR). 05/18/21
SCD SELF CLOSING DEVICE
TB THERMALLY BROKEN 6. ALL DOOR CYLINDERS SHALL BE FORMAT TO MATCH Joyanne Beckett
TG TEMPERED GLASS PROPERTY STANDARDS. ALL LOCK SETS AND
CYLINDERS ARE SUPPLIED WITH FINAL CORES.
WS WEATHER STRIPPING
7. ALL DOORS SHALL BE MASTER KEYED. COORDINATE
KEYING WITH OWNER. PERMANENT KEYING BY DOOR
SUBCONTRACTOR.
HARDWARE SCHEDULE 8. ALL FULL/HALF VISION DOORS SHALL BE A MEDIUM
SET #1 ALLUMINUM GLASS EXTERIOR DOOR C/W BF STILE (U.N.O.)
OPERATOR 9. ALL INTERIOR DOOR GLAZING AND SIDELIGHTS SHALL
· HINGES BE CLEAR TEMPERED GLASS (U.N.O.). ALL EXTERIOR
· LOCK SET DOOR GLAZING AND SIDELIGHTS SHALL BE INSULATED
TEMPERED GLASS.
· DOOR SWEEP
· CONCEALED DOOR CLOSER 10. ALL RATED DOORS SHALL BE PROVIDED W/ MIN.
REQUIRED DOOR HARDWARE REGARDLESS IF NOT
· PULL /PUSH BARS
SHOWN ON SCHEDULE. IF DIRECTION INDICATED OR
· PANIC HARDWARE NOTED IS SPECIFICALLY IN CONTRADICTION TO WHAT IS
· THRESHOLD REQUIRED IN RATED DOORS, CONTACT ARCHITECT.
· WEATHERSTRIP 11. WHERE UNDERCUT NOT SPECIFIED, PROVIDE
· BARRIER FREE OPERATION AS INDICATED IN THE STANDARD UNDERCUT OF 3/4" FOR HM & WOOD DOORS
DOOR NOTES
12.PROVIDE 1 1/2" PAIR BUTT HINGES PER DOOR LEAF UP
TO 7'-0". PROVIDE 2 PAIR BUTT HINGES PER DOOR LEAF
SET # 2 ALLUMINUM GLASS EXIT DOOR FOR SOLID CORE WOOD OR HM DOORS FROM 7'-0" TO
· HINGES 10'-0”.
· LOCK SET 13.PROVIDE (3) SILENCERS IN SINGLE LEAF DOORS, (2)
· DOOR SWEEP SILENCERS IN DOUBLE LEAF DOORS
· CONCEALED DOOR CLOSER 14.LOCKSET SHALL OPERATE WHERE TURNING KEY
· PULL /PUSH BARS UNLATCHES DOOR WHEN PUSHBUTTON IS ENGAGED &
· PANIC HARDWARE TURNED, KEY OPERATION WILL BE REQUIRED AT ALL
TIMES. RELEASING PUSHBUTTON UNLOCKS DOOR.
· THRESHOLD
· WEATHERSTRIP 15. ALL EXTERIOR DOORS SHALL BE PROVIDED WITH AN
ALUMINUM DRIP EDGE ANCHORED TO UNDERSIDE OF
WALL CONSTRUCTION (DOORS AS PART OF AN
SET # 3 HM EXTERIOR EXIT DOOR ALUMINUM STOREFRONT SYSTEM WITH A TRANSOM
· HINGES DOES NOT REQUIRE DRIP EDGE, NOR DO DOORS THAT
· LOCK SET ARE PROTECTED UNDER CANOPIES.
· KICKPLATE 16. ALL EXTERIOR DOORS SHALL HAVE THE TOP OF THE
· DOOR SWEEP DOOR SLAB CONSTRUCTED IN SUCH A WAY TO SHED
· DOOR CLOSER AND THEREFORE PREVENT WATER FROM
· THRESHOLD COLLECTING/SITTING WITHIN THE TOP OF THE DOOR
SLAB. JOINTS SHALL BE MINIMIZED AT THE TOP OF
· FLOOR STOP
DOOR SLAB. ANY CONSTRUCTION JOINTS SHALL BE
· WEATHERSTRIP FULLY WEATHER TIGHT.
17.THRESHOLDS AT ACCESSIBLE DOORS TO MEET ALL
APPLICABLE ACCESSIBILITY REQUIREMENTS.
ACCESSIBLE DOORS INCLUDE ALL PUBLIC ACCESS
SPACES, ALL PUBLIC EXTERIOR DOORS, ALL EGRESS
DOORS, AND EMPLOYEE DOORS THAT ARE INDICATED
WITH A CLEAR FLOOR AREA.
18. ALL DOOR HARDWARE SHALL COMPLY WITH
REQUIREMENTS FOR ACCESSIBILITY AS PER OBC
19.PROVIDE PUSH BUTTON (ON BOTH SIDES OF DOOR) W/
AUTOMATIC OPENER FOR ACCESSIBLE DOOR
20.ALL 'EXIT' DOORS MUST BE OPERABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY, SPECIAL KNOWLEDGE OR
EFFORT.
21.ALL WELDED CONSTRUCTION AT HOLLOW METAL DOOR
FRAMES.
22.ALL FIRE RATED DOORS TO HAVE CLOSERS AND
PER SCHEDULE LATCHING HARDWARE.
1 AF ISSUED FOR BUILDING PERMIT 20-12-07
23.PANIC EXIT HARDWARE REQUIRED.
DATE
2" TYP.
DWG NAME: A-600 Door and Window schedule B1.dwg PLOT DATE: December/11/20
ISSUE BY DESCRIPTION
2" TYP. 24.ALL GLAZING TO BE 12MM TEMPERED GLASS, UNLESS YY-MM-DD
PER SCHEDULE
25.ENSURE CONFORMITY WITH THE OBC DATA MATRIX, DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
SB-10 TABLE, WINDOW SCHEDULE AND OTHER "ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
VERTICAL FENESTRATION INSULATION VALUES DRAWINGS
ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
DISCREPANCIES.
METAL FRAMING, FIXED Max U-Value: U-0.38, Max SHGC: 0.40, Min VT/SHGC 1.10
METAL FRAMING, ENTRANCE DOORS Max U-Value: U-0.69, Max SHGC: 0.40, Min VT/SHGC 1.10 OWNER
FRAME TYPES
ARCHITECT
PATH: S:\2020\31. S20-031 Hamilton - Centennial Pkwy Retail\3.0 - Drawings\3.3 - Working Drawings\Building 1\
PER SCHEDULE PER SCHEDULE
GROUND FLOOR
3'-2"
101 UNIT 1-1 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM
102 UNIT 1-2 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM
103 UNIT 1-3 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM
104 UNIT 1-4 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM
PER SCHEDULE
PER SCHEDULE
PROJECT
105 UNIT 1-5 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM UPPER CENTENNIAL
106 UNIT 1-6 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM
7'-0 8"
COMMERCIAL DEVELOPMENT
5
107 UNIT 1-7 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM
108 UNIT 1-7 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM BUILDING 1
109 UNIT 1-6 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
110 UNIT 1-5 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
DRAWING TITLE
0.0m 111 UNIT 1-4 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
T.O. GROUND FLOOR 112 UNIT 1-3 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
D1 D2 D3 113 UNIT 1-2 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM DOOR SCHEDULE
THERMALLY BROKEN THERMALLY BROKEN THERMALLY BROKEN
114 UNIT 1-1 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM AND DETAILS
ALUMINUM DOOR ALUMINUM DOOR HOLLOW METAL DOOR 115 MECH. ROOM EXTERIOR 3'-0" 7'-0" 1 3/4" HM PT #3 D3 - - F1 HM BY CHECKED ISSUED FOR
3 1 S20-031
AS NOTED A6.01 1
ABBREVIATION LEGEND DOOR NOTES
AL ANODIZED ALUMINUM 1. ALL EXTERIOR HOLLOW METAL DOORS SHALL BE
CL CLEAR GALVANIZED & INSULATED.
DG DOUBLE GLASS 2. ALL DOORS SHALL BE PRE-FINISHED (SHOP OR
EXIST EXISTING FACTORY). TOPS, BOTTOMS AND SIDES OF ALL DOORS
SHALL BE PAINTED OR STAINED TO MATCH DOOR
GL GLAZED
FINISH/COLOR.
HM HOLLOW METAL
3. OUT-SWINGING EXTERIOR DOORS MUST HAVE CLOSED
IHM INSULATED HOLLOW METAL TOPS
IST INSULATED STEEL
4. EXTERIOR DOORS MUST HAVE WEATHER STRIPPING
PF PRE-FINISHED WITH THE APPROPRIATE TYPE OF THRESHOLD.
PH PANIC HARDWARE 5. PROVIDE CONSTRUCTION CYLINDERS DURING
PS PRESSED STEEL CONSTRUCTION. FOR DOORS REQUIRED TO BE LOCKED
PT PAINT REPLACE CONSTRUCTION CYLINDERS PRIOR TO HOTEL
SCD SELF CLOSING DEVICE OPENING (COORDINATE WITH GENERAL CONTRACTOR).
TB THERMALLY BROKEN 6. ALL DOOR CYLINDERS SHALL BE FORMAT TO MATCH
TG TEMPERED GLASS PROPERTY STANDARDS. ALL LOCK SETS AND
CYLINDERS ARE SUPPLIED WITH FINAL CORES.
WS WEATHER STRIPPING
7. ALL DOORS SHALL BE MASTER KEYED. COORDINATE
KEYING WITH OWNER. PERMANENT KEYING BY DOOR
SUBCONTRACTOR.
HARDWARE SCHEDULE 8. ALL FULL/HALF VISION DOORS SHALL BE A MEDIUM
SET #1 ALLUMINUM GLASS EXTERIOR DOOR C/W BF STILE (U.N.O.)
OPERATOR 9. ALL INTERIOR DOOR GLAZING AND SIDELIGHTS SHALL
· HINGES BE CLEAR TEMPERED GLASS (U.N.O.). ALL EXTERIOR
· LOCK SET DOOR GLAZING AND SIDELIGHTS SHALL BE INSULATED
TEMPERED GLASS.
· DOOR SWEEP
· CONCEALED DOOR CLOSER 10. ALL RATED DOORS SHALL BE PROVIDED W/ MIN.
REQUIRED DOOR HARDWARE REGARDLESS IF NOT
· PULL /PUSH BARS
SHOWN ON SCHEDULE. IF DIRECTION INDICATED OR
· PANIC HARDWARE NOTED IS SPECIFICALLY IN CONTRADICTION TO WHAT IS
· THRESHOLD REQUIRED IN RATED DOORS, CONTACT ARCHITECT.
· WEATHERSTRIP 11. WHERE UNDERCUT NOT SPECIFIED, PROVIDE
· BARRIER FREE OPERATION AS INDICATED IN THE STANDARD UNDERCUT OF 3/4" FOR HM & WOOD DOORS
DOOR NOTES
12. PROVIDE 1 1/2" PAIR BUTT HINGES PER DOOR LEAF UP
TO 7'-0". PROVIDE 2 PAIR BUTT HINGES PER DOOR LEAF
SET # 2 ALLUMINUM GLASS EXIT DOOR FOR SOLID CORE WOOD OR HM DOORS
· HINGES FROM 7'-0" TO 10'-0”.
· LOCK SET 13. PROVIDE (3) SILENCERS IN SINGLE LEAF DOORS, (2)
· DOOR SWEEP SILENCERS IN DOUBLE LEAF DOORS
· CONCEALED DOOR CLOSER 14. LOCKSET SHALL OPERATE WHERE TURNING KEY
· PULL /PUSH BARS UNLATCHES DOOR WHEN PUSHBUTTON IS ENGAGED &
· PANIC HARDWARE TURNED, KEY OPERATION WILL BE REQUIRED AT ALL
TIMES. RELEASING PUSHBUTTON UNLOCKS DOOR.
· THRESHOLD
· WEATHERSTRIP 15. ALL EXTERIOR DOORS SHALL BE PROVIDED WITH AN
ALUMINUM DRIP EDGE ANCHORED TO UNDERSIDE OF
WALL CONSTRUCTION (DOORS AS PART OF AN
SET # 3 HM EXTERIOR EXIT DOOR ALUMINUM STOREFRONT SYSTEM WITH A TRANSOM
· HINGES DOES NOT REQUIRE DRIP EDGE, NOR DO DOORS THAT
· LOCK SET ARE PROTECTED UNDER CANOPIES.
· KICKPLATE 16. ALL EXTERIOR DOORS SHALL HAVE THE TOP OF THE
· DOOR SWEEP DOOR SLAB CONSTRUCTED IN SUCH A WAY TO SHED
· DOOR CLOSER AND THEREFORE PREVENT WATER FROM
· THRESHOLD COLLECTING/SITTING WITHIN THE TOP OF THE DOOR
SLAB. JOINTS SHALL BE MINIMIZED AT THE TOP OF
· FLOOR STOP
DOOR SLAB. ANY CONSTRUCTION JOINTS SHALL BE
· WEATHERSTRIP FULLY WEATHER TIGHT.
17. THRESHOLDS AT ACCESSIBLE DOORS TO MEET ALL
APPLICABLE ACCESSIBILITY REQUIREMENTS.
ACCESSIBLE DOORS INCLUDE ALL PUBLIC ACCESS
SPACES, ALL PUBLIC EXTERIOR DOORS, ALL EGRESS
DOORS, AND EMPLOYEE DOORS THAT ARE INDICATED
WITH A CLEAR FLOOR AREA.
18. ALL DOOR HARDWARE SHALL COMPLY WITH
REQUIREMENTS FOR ACCESSIBILITY AS PER OBC
19. PROVIDE PUSH BUTTON (ON BOTH SIDES OF DOOR) W/
AUTOMATIC OPENER FOR ACCESSIBLE DOOR
20. ALL 'EXIT' DOORS MUST BE OPERABLE FROM THE INSIDE
WITHOUT THE USE OF A KEY, SPECIAL KNOWLEDGE OR
EFFORT.
21. ALL WELDED CONSTRUCTION AT HOLLOW METAL DOOR
FRAMES. 2 NZ ISSUED FOR CONSTRUCTION 01-NOV-2021
22. ALL FIRE RATED DOORS TO HAVE CLOSERS AND 1 AF ISSUED FOR BUILDING PERMIT 07-DEC-2020
PER SCHEDULE LATCHING HARDWARE.
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-600 DOOR AND WINDOW SCHEDULE B1 | PLOT DATE: November 8, 2021
DATE
ISSUE BY DESCRIPTION [DD-MMM-YYYY]
23. PANIC EXIT HARDWARE REQUIRED.
2" TYP.
24. ALL GLAZING TO BE 12MM TEMPERED GLASS, UNLESS GENERAL NOTES
2" TYP.
OTHERWISE NOTED DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS
M AR KED " ISSUED FOR C ON STR U C TION " . VERIFY
PER SCHEDULE
25. ENSURE CONFORMITY WITH THE OBC DATA MATRIX,
SB-10 TABLE, WINDOW SCHEDULE AND OTHER CONFIGURATIONS & DIMENSIONS ON SITE BEFORE
BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF
VERTICAL FENESTRATION INSULATION VALUES DRAWINGS
ANY ERRORS, OMISSIONS OR DISCREPANCIES.
METAL FRAMING, FIXED Max U-Value: U-0.38, Max SHGC: 0.40, Min VT/SHGC 1.10
CLIENT
METAL FRAMING, ENTRANCE DOORS Max U-Value: U-0.69, Max SHGC: 0.40, Min VT/SHGC 1.10 2354538 ONTARIO INC.
C/O 3245 HARVESTER RD., UNIT 14
0.0m
BURLINGTON, ON L7N 3T7
T.O. GROUND FLOOR
F1 SB-10 ENVELOPE REQUIREMENTS 2 DEVELOPMENT CONSULTANT
PER SCHEDULE
PROJECT NAME
105 UNIT 1-5 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM ACCESSIBLE
106 UNIT 1-6 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM ACCESSIBLE
UPPER CENTENNIAL
7'-0 8"
COMMERCIAL DEVELOPMENT
5
107 UNIT 1-7 ENTR. EXTERIOR 6'-4" 8'-0" PER MANUF. AL ANOD. #1 D1 DG - - ALUM ACCESSIBLE
108 UNIT 1-7 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM BUILDING 1
109 UNIT 1-6 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM PROJECT ADDRESS
UPPER CENTENNIAL PKWY & MUD ST W
110 UNIT 1-5 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
HAMILTON, ON
0.0m 111 UNIT 1-4 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM DRAWING TITLE
T.O. GROUND FLOOR 112 UNIT 1-3 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
D1 D2 D3 DOOR SCHEDULE
113 UNIT 1-2 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
AND DETAILS
114 UNIT 1-1 EXIT EXTERIOR 3'-2" 8'-0" PER MANUF. AL ANOD. #2 D2 DG - - ALUM
THERMALLY BROKEN THERMALLY BROKEN THERMALLY BROKEN
ALUMINUM DOOR ALUMINUM DOOR HOLLOW METAL DOOR 115 MECH. ROOM EXTERIOR 3'-0" 7'-0" 1 3/4" HM PT #3 D3 - - F1 HM
BY CHECK ISSUED FOR
NZ - SEE TABLE ABOVE
A6.02
S20-031
SCALE: 1/4"=1'-0" A6.01 SCALE: 3"=1'-0" A6.01 SCALE
1
AS NOTED
SPANDREL PANEL LEGEND
CLEAR TEMPERED GLASS SPANDREL PANEL |
SP LIGHT GRAY
WINDOW NOTES
1. OWNER/CONTRACTOR TO ENSURE SHOP DRAWING
SUBMITTALS ARE PREPARED BY THE WINDOW SYSTEMS
DESIGNER AND SUBMITTED FOR ARCHITECT'S REVIEW
2. CONTRACTOR TO REVIEW AND APPROVE THE ABOVE
MENTIONED SHOP DRAWINGS PRIOR TO SUBMISSION TO
THE ARCHITECT. THE WINDOW AND SCREEN DRAWINGS
SHOW HERE ARE FOR REFERENCE AND DESIGN INTENT
ONLY, AND NOT INTENDED FOR FABRICATION.
VAPOUR BARRIER TO WRAP AROUND 3. STANDARD WINDOW DETAILS ARE PROPOSED FOR
INTENT ONLY. FINAL DETAILING MAY VARY BASED ON
STUD AND SEAL TO TAPE FLASHING MANUFACTURER AND/OR TRADE'S SPECS AND
6" TYP.
SEALANT STANDARDS.
4. ENSURE CONFORMITY WITH THE OBC DATA MATRIX,
VAPOUR BARRIER TO WRAP AROUND EXPANDING FOAM SEALANT TO SB-10 TABLE, WINDOW SCHEDULE AND OTHER
STUD AND SEAL TO TAPE FLASHING SEAL FRAME TO AIR BARRIER DRAWINGS
5. DIMENSIONS SHOWN ARE PROPOSED WINDOW FRAME.
WINDOW SUPPLIER AND FRAMER TO COORDINATE SIZE
OF ROUGH OPENING
7. WINDOW SUPPLIER TO CONFIRM SIZE OF OPENING ON
SEALANT
6" TYP.
SITE BEFORE MFG
SB-10 ENVELOPE REQUIREMENTS 6 DETAIL @ WINDOW JAMB @ BRICK WALL 5 DETAIL @ WINDOW JAMB @ EIFS WALL 3
A6.02 SCALE: 3"=1'-0" A6.02 SCALE: 3"=1'-0" A6.02
DRAWING LOCATION: S:\2020\31. S20-031 HAMILTON, ON - CENTENNIAL PKWY RETAIL\3.0 - DRAWINGS\3.3 - WORKING DRAWINGS\BUILDING 1 | DRAWING FILENAME: A-600 DOOR AND WINDOW SCHEDULE B1 | PLOT DATE: November 8, 2021
DATE
BRICK STL LEDGE/LINTEL ISSUE BY DESCRIPTION [DD-MMM-YYYY]
EXPANDING FOAM SEALANT TO
1'-103 4"
DETAIL @ WINDOW HEAD AT BRICK WALL 4 DETAIL @ WINDOW HEAD AT EIFS WALL 2
1464 UNIT #7 CORNWALL ROAD
8"
SP SP SP
1'-103 4"
1'-103 4"
1'-103 4"
1'-103 4"
1'-103 4"
1'-103 4"
2'-0"
6'-4" 3'-2" 3'-51 4" 2'-2"
3'-61 2" PROJECT NAME
UPPER CENTENNIAL
9'-4"
9'-4"
9'-4"
9'-4"
9'-4"
9'-4"
10'-0"
COMMERCIAL DEVELOPMENT
7'-51 4"
7'-51 4"
7'-5 4"
7'-51 4"
7'-51 4"
7'-5 4"
7'-4"
1
1
8'-0"
BUILDING 1
PROJECT ADDRESS
UPPER CENTENNIAL PKWY & MUD ST W
HAMILTON, ON
DRAWING TITLE
WINDOW SCHEDULE
8"
8"
8"
8"
8"
8"
8"
0.0m
T.O. GROUND FLOOR AND DETAILS
W1 W2 W3 W4 W5 W6 W7
BY CHECK ISSUED FOR
NZ - SEE TABLE ABOVE
WINDOW TYPES 1
PROJECT No. SHEET No. SHEET REVISION
A6.02
S20-031
SCALE: 1/4"=1'-0" A6.02 SCALE
1
AS NOTED
20 196379 000 00 C3
05/18/21
Joyanne Beckett
© exp, 2012
GENERAL NOTES:
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
"ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
DISCREPANCIES.
OWNER
DEVELOPMENT CONSULTANT
PROJECT
UPPER CENTENNIAL
COMMERCIAL DEVELOPMENT
BUILDING 1
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
DRAWING TITLE
COVER SHEET
12/8/2020 3:18:50 PM
AS NOTED S0.01 2
NON-STRUCTURAL ELEMENTS GN-011CS ABBREVIATIONS GN-010CS FOUNDATIONS NOTES GN-005CS
AB ANCHOR BOLT F’c COMPRESSIVE STRENGTH Pf;Cf;Tf,Mf.Vf,Rf FACTORED LOADS
ADD ADDITIONAL OF CONCRETE P,T,C,V,M,R UNFACTORED LOADS
AESS ARCHITECTURALLY FF FAR FACE PC PRECAST THE FOLLOWING NOTES ARE IN ADDITION TO THE GENERAL NOTES, THE SPECIFICATION AND PLAN NOTES.
1. "NON-STRUCTURAL" OR "SECONDARY STRUCTURAL" ELEMENTS ARE NOT PART OF THE STRUCTURAL DESIGN SHOWN ON
EXPOSED STRUCTURAL PL PLATE
THESE 1. SEE FOUNDATION PLAN NOTES FOR ASSUMED BEARING CONDITIONS. IF ACTUAL SITE OR SOIL CONDITIONS
STEEL GALV GALVANIZED PSL PARALLEL STRAND
DRAWINGS. SUCH ELEMENTS ARE DESIGNED, DETAILED AND REVIEWED IN THE FIELD BY OTHERS. THEY APPEAR ON DRAWINGS VARY FROM THOSE ASSUMED, OBTAIN WRITTEN INSTRUCTIONS FROM THE CONSULTANT BEFORE
AIFB ASPHALT IMPREGNATED LUMBER
OTHER THAN THESE STRUCTURAL DRAWINGS BY exp. WHERE STRUCTURAL ENGINEERING RESPONSIBILITY IS REQUIRED FOR PROCEEDING WITH THE WORK.
FIBREBOARD HB HIGH BEAM PVC POLYVINYL CHLORIDE
THESE ELEMENTS, THIS SHALL BE PROVIDED BY SPECIALTY STRUCTURAL ENGINEERS, WHO SHALL ALSO PROVIDE ANY 2. CARRY EXTERIOR FOOTINGS DOWN MINIMUM 1200 mm (4’) BELOW FINISHED GRADE. PROTECT FOOTINGS
ALT ALTERNATIVE HD HANGER DOWN
DOCUMENTATION REQUIRED BY BUILDING PERMIT AUTHORITIES. EXPOSED TO FROST DURING CONSTRUCTION WITH 1200 mm (4’) OF EARTH OR ITS EQUIVALENT TO PREVENT
AR ANCHOR ROD HEF HORIZONTAL EACH FACE REINF REINFORCEMENT
ARCH ARCHITECTURAL HH HOOK-HOOK RE RIGHT END FREEZING OF SOIL UNDER FOOTINGS. DO NOT PLACE FOOTINGS ON FROZEN SOIL.
2. EXAMPLES OF NON-STRUCTURAL ELEMENTS INCLUDE, BUT ARE NOT LIMITED TO: 3. KEEP EXCAVATIONS CONTINUOUSLY DRY BEFORE CONCRETE IS PLACED. IF SOIL IS SOFTENED BY WATER,
(HOOK EACH END) RTU ROOF TOP UNIT
a. ARCHITECTURAL COMPONENTS SUCH AS GUARDRAILS, HANDRAILS, MISCELLANEOUS STEEL STAIRS, FLAG POLES, EXTEND EXCAVATION BELOW SOFTENED MATERIAL AND LOWER FOOTINGS TO SUIT.
B, BOTT BOTTOM HIF HORIZONTAL INSIDE FACE
CANOPIES, CEILINGS, MILLWORK, ETC. 4. DO NOT EXCEED A RISE OF 7 IN RUN OF 10 IN THE LINE OF SLOPE BETWEEN ADJACENT EXCAVATIONS. 20 196379 000 00 C3
BC BOTTOM ELEVATION OF HL HIGH LINE S STANDARD BEAM
b. LANDSCAPE ELEMENTS SUCH AS BENCHES, LIGHT POSTS, PLANTERS, ETC. MAXIMUM STEP 600 mm (24”) APPROXIMATELY.
CAISSON HOF HORIZONTAL OUTSIDE SECT SECTION 05/18/21
c. CLADDING, GLAZING, WINDOW MULLIONS, INTERIOR STUD WALLS AND EXTERIOR STUD WALLS. 5. FOUND NEW FOOTINGS WHICH ARE LOCATED IMMEDIATELY ADJACENT TO EXISTING FOOTINGS AT THE SAME
BEW BOTTOM EACH WAY FACE SF SPRAY FIRE PROOFED
d. ARCHITECTURAL PRECAST, PRECAST CLADDING. ELEVATION AS THE EXISTING FOOTING UNLESS NOTED OTHERWISE. AT LOCATIONS WHERE MECHANICAL
BLL BOTTOM LOWER LAYER HOR HORIZONTAL SFD STEP FOOTING DOWN Joyanne Beckett
e. SKYLIGHTS. SERVICES INTERFERE WITH FOOTINGS ESTABLISH TOP OF FOOTING A MINIMUM 200 mm (8”) BELOW INVERT
BM BEAM HP HIGH POINT SFU STEP FOOTING UP
f. MECHANICAL AND ELECTRICAL EQUIPMENT, COMPONENTS, AND THEIR ATTACHMENT DETAILS. CONNECTIONS ELEVATION. REFER TO MECHANICAL DRAWINGS FOR LOCATION OF SERVICES.
BMB BENDING MOMENT BAR HSC HORIZONTALLY SLOTTED SIM SIMILAR
DESIGNED SEISMIC RESTRAINT ACCORDING TO OBC 2012 CLAUSE 4.1.8.18.
BPL BEARING/BASE PLATE CONNECTION SJ STEEL JOIST
g. WINDOW WASHING EQUIPMENT, FALL ARREST ANCHORS AND THEIR ATTACHMENTS.
BRG BEARING HSS HOLLOW STRUCTURAL SL SLAB
h. ESCALATORS, ELEVATORS, AND CONVEYING SYSTEMS.
BSMT BASEMENT SECTION SOG SLAB ON GRADE
i. GLASS BLOCK AND ITS ATTACHMENTS.
BUL BOTTOM UPPER LAYER HU HANGER UP SP SPANDREL, SPRUCE
j. BRICK OR BLOCK VENEERS AND THEIR ATTACHMENTS.
SPF SPRUCE PINE FIR
k. NON-LOAD BEARING MASONRY.
C STANDARD CHANNEL ID INSIDE DIAMETER ST STRAIGHT
l. NON-STRUCTURAL CONCRETE TOPPINGS.
C/C CENTRE TO CENTRE IF INSIDE FACE STIRR STIRRUP
C/W COMPLETE WITH STRUCT STRUCTURAL
3. SUBMIT SHOP DRAWINGS FOR NON-STRUCTURAL ELEMENTS WHICH MAY AFFECT THE PRIMARY STRUCTURAL SYSTEM TO exp.
CA COLUMN ABOVE KB KNEE BRACE
THESE DRAWINGS WILL BE REVIEWED ONLY FOR THE LOAD EFFECT OF THE ELEMENT ON THE PRIMARY STRUCTURAL SYSTEM.
CB COLUMN BELOW kN KILOWNEWTON t THICKNESS
CANT/CANTIL CANTILEVER kPa KILOPASCAL T TOP
4. SINCE IeFaSa(0.2)<0.35, SEISMIC LATERAL FORCES OF THE ELEMENT/COMPONENTS OUTLINED IN CATEGORIES 6 THROUGH 21
CF CONCRETE TC TOP ELEVATION OF
OF TABLE 4.1.8.18 OF OBC 2012 CAN BE NEGLECTED.
FIREPROOFED L SINGLE ANGLE CAISSON
CJ CONTROL JOINT 2L DOUBLE ANGLES TCAP TOP ELEVATION OF CAP
CL CLEAR LB LOWER BEAM TEW TOP EACH WAY
C.L. CENTRE LINE LE LEFT END T&J TONGUE AND GROOVE
COMP COMPOSITE LG LONG/LENGTH TJ TIE JOIST
COL COLUMN LL LIVE LOAD TLE TOP LEFT END
CONC CONCRETE LL LOW LINE TLL TOP LOWER LAYER
CONN CONNECTION LLV LONG LEG VERTICAL TOC TOP OF CONCRETE
CONST JT CONSTRUCTION JOINT LLH LONG LEG HORIZONTAL TOS TOP OF STEEL
CONT CONTINUOUS LP LOW POINT TRE TOP RIGHT END
LSSJ LONG SPAN STEEL JOIST TUL TOP UPPER LAYER
DET DETAIL LVL LAMINATED VENEER TYP TYPICAL
D FIR DOUGLAS FIR LUMBER
DIA DIAMETER UB UPPER BEAM
DIM DIMENSION MAX MAXIMUM U/S UNDERSIDE EXP Services Inc.
DL DEAD LOAD MC MOMENT CONNECTION USD UNDERSIDE OF DECK
DP DEEP MC MISCELLANEOUS CHANNEL UL UPPER LAYER t: +1.905.695.3217 f: +1.905.470.7700
DWG DRAWING MIN MINIMUM U/N UNLESS NOTED 220 Commerce Valley Drive West, Suite 500
DWL DOWEL m METRE UNO UNLESS NOTED Markham, ON L3T 0A8
m2 SQUARE METRE OTHERWISE CANADA
EA EACH mm MILLIMETRE UPT UPTURNED www.exp.com
ECR EPOXY COATED mm2 SQUARE MILLIMETRE
REINFORCEMENT MECH MECHANICAL VERT VERTICAL
EE EACH END MPa MEGAPASCAL VBF VERTICAL BRACED
EF EACH FACE FRAME
EJ, EXP. JT EXPANSION JOINT NBCC NATIONAL BUILDING CODE VEF VERTICAL EACH FACE
EL, ELEV ELEVATION OF CANADA VIF VERTICAL INSIDE FACE
ELECT ELECTRICAL NCB NO COLUMN BELOW VOF VERTICAL OUTSIDE FACE • BUILDINGS • EARTH & ENVIRONMENT •
EMBED EMBEDMENT NF NEAR FACE VSC VERTICAL SLOTTED
• ENERGY • INDUSTRIAL •
EQ EQUAL NIC NOT IN CONTRACT CONNECTION
EW EACH WAY No NUMBER • INFRASTRUCTURE • SUSTAINABILITY •
EX, EXIST EXISTING NTS NOT TO SCALE W WIDE FLANGE BEAM
WP WALL PLATE CAUTION: DO NOT SCALE DRAWINGS.
THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
FIN FINISHED OBC ONTARIO BUILDING CODE WT STRUCTURAL TEE ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
FL FLOOR OC ON CENTRE WWF WELDED WIRE FABRIC FOR INCORRECT SCALING. UNAUTHORIZED
REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
FTG FOOTING OD OUTSIDE DIAMETER WWF WELDED WIDE FLANGE PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
FMC FULL MOMENT OF OUTSIDE FACE DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
CONNECTION OPNG OPENING MUST BE IN WRITING.
Fy YIELD STRENGTH OWSJ OPEN WEB STEEL JOIST
© exp, 2012
EXCAVATION AND BACKFILL GN-004CS DESIGN LOAD - BUILDING 8 GN-002CS GENERAL NOTES GN-001CS
1 GENERAL 1. UNIT FLOOR AND ROOF LOADINGS, SOIL BEARING PRESSURES AND FOUNDATION LOADS
1 GENERAL
GIVEN ON PLANS ARE UNFACTORED. MEMBER FORCES GIVEN ON DRAWINGS ARE FACTORED.
1.1 THE FOLLOWING REFERENCE STANDARDS SHALL GOVERN THE WORK OF THIS SECTION:
1.1.1 OPSS 1010, MATERIAL SPECIFICATION FOR AGGREGATES –BASE, SUBBASE, SELECT SUBGRADE 1.1 CHECK DIMENSIONS ON STRUCTURAL DRAWINGS AGAINST ARCHITECTURAL DRAWINGS AND EXISTING
2. GRAVITY LOADS: SUPERIMPOSED DEAD LOADS AND LIVE LOADS ARE GIVEN ON PLANS.
AND BACKFILL MATERIALS SITE CONDITIONS. REPORT INCONSISTENCIES TO CONSULTANT BEFORE PROCEEDING WITH THE WORK.
1.2 READ DRAWINGS IN CONJUNCTION WITH SPECIFICATIONS.
3. SNOW LOAD PARAMETERS, OBC 2012(R2019) –HAMILTON (ABOVE ESCARPMENT - EAST OF JOHN C. MUNRO INT'L AIRPORT), ONTARIO
2 PRODUCTS: 1.3 DO NOT EXCEED DURING CONSTRUCTION DESIGN LOADS SHOWN ON PLANS REDUCED AS NECESSARY
Ss = 1.3 kPa
UNTIL MATERIALS REACH DESIGN STRENGTH.
Sr = 0.4 kPa
2.1 MATERIAL 1.4 DO NOT SCALE DRAWINGS. 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
Is ULS = 1
2.1.1 BACKFILL AROUND FOOTINGS, FOUNDATION WALLS, RETAINING WALLS 1.5 DIMENSIONS ARE IN INCHES UNLESS NOTED OTHERWISE. ELEVATIONS ARE IN FEET AND INCHES UNLESS NOTED 1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
Is SLS = 0.9
.1 TO OPSS GRANULAR B TYPE II OTHERWISE. DATE
ISSUE BY DESCRIPTION YY-MM-DD
2.1.2 GRANULAR UNDERBED FOR SLABS-ON-GRADE 4. RAIN LOAD PARAMETER, OBC 2012(R2019) –HAMILTON (ABOVE ESCARPMENT - EAST OF JOHN C. MUNRO INT'L AIRPORT), ONTARIO
.1 19 mm CLEAR STONE 2 DESIGN GENERAL NOTES:
ONE DAY RAINFALL = 108 mm
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
2.1 DESIGN IS IN ACCORDANCE WITH THE ONTARIO BUILDING CODE, 2012(R2019) EDITION. "ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
5. WIND LOAD PARAMETERS, OBC, 2012(R2019) –HAMILTON (ABOVE ESCARPMENT - EAST OF JOHN C. MUNRO INT'L AIRPORT), ONTARIO
3 EXECUTION 2.2 DESIGN STANDARDS DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
q (1/10) = 0.36 kPa
2.2.1 CONCRETE MEMBERS ARE DESIGNED IN ACCORDANCE WITH CSA STANDARD A23.3-14. ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
q (1/50) = 0.46 kPa
3.1 EXCAVATE TO FOOTING ELEVATIONS INDICATED ON DRAWINGS AND OBTAIN VERIFICATION FROM INSPECTION AND TESTING 2.2.2 STRUCTURAL STEEL IS DESIGNED IN ACCORDANCE WITH CSA STANDARD S16-14. DISCREPANCIES.
Iw ULS = 1
COMPANY THAT BEARING MATERIAL IS AS ANTICIPATED. REMOVE UNSUITABLE MATERIAL AS INSTRUCTED. Iw SLS = 0.75
3.2 BACKFILL 3 MATERIALS
WIND LOAD APPLIED AS PER OBC(R2019) FIGURE 4.1.7.6.A OWNER
3.2.1 PLACE GRANULAR MATERIAL SPECIFIED IN 2.1.1.1 FACTORED HORIZONTAL FORCE AT BASE IN NORTH-SOUTH DIRECTION, VF =165 kN
3.2.2 EXCAVATED MATERIAL MAY BE USED AS BACKFILL PROVIDED THAT IT IS TESTED TO VERIFY THAT IT MEETS THE 3.1 CONCRETE: SEE SCHEDULE OF CONCRETE PROPERTIES AND SPECIFICATION.
FACTORED HORIZONTAL FORCE AT BASE IN EAST-WEST DIRECTION, VF =250 kN
3.2 STRUCTURAL STEEL: UNLESS NOTED OTHERWISE TO CSA G40.20/G40.21-13 OR ASTM STANDARD A992/A992M-15. BROOKLYN CONTRACTING INC
REQUIREMENTS FOR GRADING AND CLEANLINESS ACCORDING TO THE GEOTECHNICAL REPORT.
3.2.3 PLACE BACKFILL IN 200 mm (8") LAYERS AND COMPACT TO 98% SPMDD. W AND WWF SHAPES: GRADE 350W 3245 HARVESTER ROAD #14
6. SEISMIC LOAD PARAMETERS, OBC, 2012(R2019) –HAMILTON (ABOVE ESCARPMENT - EAST OF JOHN C. MUNRO INT'L AIRPORT), ONTARIO
3.3 GRANULAR UNDERBED FOR SLAB-ON-GRADE PLATES: GRADE 350 W
Sa (0.2) = 0.26 Sa (5.0) = 0.0068 BURLINGTON, ON, L7N 3T7
3.3.1 OBTAIN GEOTECHNICAL CONSULTANT’S WRITTEN CONFIRMATION THAT PREPARED SUBGRADE IS CHANNELS AND ANGLES: GRADE 300W
Sa (0.5) = 0.128 Sa (10.0) = 0.0027
ACCEPTABLE FOR PLACEMENT OF GRANULAR UNDERBED. HOLLOW STRUCTURAL SECTIONS: 350W CLASS C OR ASTM STANDARD A1085-15
Sa (1.0) = 0.061 PGA = 0.168
3.3.2 PLACE GRANULAR MATERIAL SPECIFIED IN PER 2.1.2.1 ANCHOR RODS: ASTM F1554 GRADE 36 DEVELOPMENT CONSULTANT
Sa (2.0) = 0.028 PGV = 0.101
3.3.3 PLACE 200 mm (8") THICK UNDERBED AND COMPACT TO 100% SPMDD. 3.3 REINFORCING STEEL: TO CONFORM TO CSA G30.18-09(R2014) GRADE 400W UNLESS NOTED OTHERWISE API DEVELOPMENT CONSULTANTS INC.
SITE CLASSIFICATION = C
3.3.1 REINFORCING BAR AREAS ARE 100, 200, 300, 500, 700, 1000, 1500 AND 2500 SQ. MM 1464 CORNWALL ROAD, UNIT 7
Ie = 1.0
4 FIELD QUALITY CONTROL FOR BAR DESIGNATIONS 10M, 15M, 20M, 25M, 30M, 35M, 45M AND 55M RESPECTIVELY.
Fa=1.0 OAKVILLE, ON L6J 7W5, CANADA
3.3.2 STRENGTH:
Fv=1.0
4.1 INSPECTION AND TESTING COMPANY SHALL PERFORM: DEFORMED REINFORCING BARS: 400 MPa. ARCHITECT
IeFaSa(0.2)=0.26
4.1.1 VERIFICATION OF FOUNDATION BEARING MATERIAL; WELDED WIRE FABRIC: 440 MPa SAPLYS ARCHITECTS INC.
4.1.2 TESTING OF GRANULAR MATERIALS TO CONFIRM THEY MEET GRADING AND COMPACTION REQUIREMENTS. TYPE OF IRREGULARITIES AS PER OBC TABLE 4.1.8.6 610 FORD DRIVE SUITE 338
NONE OAKVILLE, ON L6J 7W4, CANADA
NORTH PROFESSIONAL
CERTIFICATION
METHOD OF ANALYSIS: EQUIVALENT STATIC FORCE PROCEDURE
SCALE
2020-215
AS NOTED S0.02 2
20 196379 000 00 C3
05/18/21
Joyanne Beckett
2.2.1 ANCHOR ROD: PROVIDE ANCHOR RODS OF SIZE, TYPE AND EMBEDMENT LENGTH SHOWN ON DRAWINGS DATE
2.3 REINFORCING BARS: TO CAN/CSA-G30.18, GRADE 400W .3 REINFORCING STEEL IS PROPERLY CHAIRED AND HELD SECURELY IN PLACE; ISSUE BY DESCRIPTION YY-MM-DD
INCLUDING MATCHING NUTS AND MATCHING WASHERS. 2.4 WELDED WIRE FABRIC: TO ASTM A1064/A1064M AND IN FLAT SHEETS NOT ROLLS .4 ALL EQUIPMENT FOR THE FINISHING OF CONCRETE AND THE SAW CUTTING OF CONTROL JOINTS IS ON SITE AND WORKING
2.2.2 REINFORCING BAR: PROVIDE REINFORCING BAR AS ANCHOR ROD WHERE SPECIFIED ON DRAWING. 2.5 CEMENTING MATERIALS PROPERLY; GENERAL NOTES:
2.2.3 CORROSION PROTECTION: PROVIDE CORROSION PROTECTION SPECIFIED ON DRAWINGS 2.5.1 PORTLAND CEMENT: TO CSA A3000 TYPE GU OR GUL .5 USE EARLY ENTRY SAW (SOFF-CUT, BY HUSQVARNA). COMMENCE SAWCUTTING AS SOON AS CONCRETE CAN SUPPORT WEIGHT OF DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
2.2.4 ADHESIVE: PROVIDE THE ADHESIVE SPECIFIED ON THE DRAWINGS. 2.5.2 CEMENTITIOUS HYDRAULIC SLAG AND FLY ASH: TO CSA A3000 SAW AND OPERATOR WITHOUT MARRING CONCRETE SURFACE AND WITHIN 2 HOURS OF COMPLETION OF FINAL FINISHING; "ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
2.6 AGGREGATE 3.9 FLOOR FINISH: HARD, SMOOTH, DENSE TROWELED SURFACE FREE FROM BLEMISHES. DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
3 EXECUTION 2.6.1 FINE AGGREGATE FOR SLABS ON GRADE: FINENESS MODULUS BETWEEN 2.6 AND 3.1 ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
2.6.2 COARSE AGGREGATE: 5mm TO 20 mm UNLESS OTHERWISE SPECIFIED DISCREPANCIES.
4 FIELD QUALITY CONTROL
3.1 DRILLED-IN ANCHORS 2.7 CONTROL JOINT FILLER: SEMI-RIGID JOINT FILLER
3.1.1 ARRANGE FOR MANUFACTURER’S TECHNICAL REPRESENTATIVE TO BE PRESENT DURING INSTALLATION OF FIRST : QWIKJOINT UVR, BY EUCLID CANADA INC., TORONTO, ON. 4.1 INSPECTION AND TESTING COMPANY SHALL PERFORM: OWNER
FEW ANCHORS OF EACH TYPE. SUBMIT SITE REPORTS BY MANUFACTURER TO CONSULTANT WITHIN ONE WEEK : LOADFLEX, BY SIKA CANADA INC., MISSISSAUGA, ON. 4.1.1 SAMPLING, INSPECTION AND TESTING IN ACCORDANCE WITH CSA A23.2 AND TO INCLUDE:
OF EACH VISIT. INDICATE IN REPORTS ANCHOR SIZES AND TYPES INSTALLED, LOCATIONS, AND WHETHER : PLANIBOND JF, BY MAPEI INC., BRAMPTON, ON. .1 MAKING STANDARD SLUMP TESTS; BROOKLYN CONTRACTING INC
INSTALLATION PROCEDURES WERE IN ACCORDANCE WITH MANUFACTURER’S PRINTED INSTRUCTIONS. 2.8 PREMIXED GROUT: DRYPACK NON-SHRINK NON-METALLIC .2 OBTAINING OF THREE STANDARD SPECIMENS FOR STRENGTH TESTS FROM EACH 100 CUBIC METRES OF CONCRETE, OR FRACTION
3.1.2 INSTALL ANCHORS IN STRICT ACCORDANCE WITH MANUFACTURER’S PRINTED INSTRUCTIONS. THEREOF, OF EACH MIX DESIGN OF CONCRETE PLACED IN ANY ONE DAY; 3245 HARVESTER ROAD #14
3.1.3 INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER. 3 EXECUTION .3 MAKING COMPRESSION TESTS OF EACH SET OF THREE SPECIMENS, ONE AT 7DAYS AND TWO AT 28 DAYS; BURLINGTON, ON, L7N 3T7
3.1.4 DO NOT DRILL HOLES LARGER IN DIAMETER THAN INDICATED IN MANUFACTURER’S PRINTED INSTRUCTIONS. .4 VERIFICATION OF AIR CONTENT OF AIR-ENTRAINED CONCRETE;
3.1.5 PROVIDE MANUFACTURER’S STANDARD EMBEDMENT LENGTH INTO SOLID CONCRETE, UNLESS OTHERWISE 3.1 CONCRETE TO BE IN ACCORDANCE WITH SCHEDULE OF CONCRETE PROPERTIES C-001 .5 INSPECTION OF TOLERANCES. DEVELOPMENT CONSULTANT
NOTED ON DRAWINGS.
3.1.6 DO NOT CUT REINFORCEMENT TO ACCOMMODATE ANCHORS. 3.2 ALL REINFORCEMENT SHALL BE SECURELY HELD IN PROPER POSITION WHILE PLACING CONCRETE. PROVIDE CHAIRS, TIES, SPACERS, ADDITIONAL API DEVELOPMENT CONSULTANTS INC.
3.1.7 RELOCATE ANCHORS, AT NO ADDITIONAL COST TO CONTRACT, WHEN OBSTRUCTIONS PREVENT DRILLING SUPPORT BARS AND STIRRUPS AS MAY BE REQUIRED. 1464 CORNWALL ROAD, UNIT 7
HOLES TO REQUIRED DEPTH IN LOCATIONS INDICATED ON DRAWINGS. OAKVILLE, ON L6J 7W5, CANADA
3.1.8 OBTAIN CONSULTANT’S APPROVAL OF NEW LOCATION BEFORE DRILLING HOLE. FILL ABANDONED HOLES
ARCHITECT
WITH SPECIFIED GROUT.
3.1.9 TIGHTEN EXPANSION ANCHORS USING TORQUE WRENCH UNLESS FINGER-TIGHT IS INDICATED ON DRAWINGS. SAPLYS ARCHITECTS INC.
610 FORD DRIVE SUITE 338
OAKVILLE, ON L6J 7W4, CANADA
NORTH PROFESSIONAL
CERTIFICATION
PROJECT
UPPER CENTENNIAL
COMMERCIAL DEVELOPMENT
BUILDING 1
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
DRAWING TITLE
GENERAL NOTES
12/8/2020 3:18:51 PM
SCALE
2020-215
AS NOTED S0.03 2
20 196379 000 00 C3
05/18/21
Joyanne Beckett
STEEL DECK NOTES GN-008CS STEEL JOIST NOTES GN-007CS STRUCTURAL STEEL NOTES GN-006CS www.exp.com
1 GENERAL 1 GENERAL
1 GENERAL
1.1 THE FOLLOWING REFERENCE STANDARDS SHALL GOVERN THE WORK OF THIS SECTION: 1.1 THE FOLLOWING REFERENCE STANDARDS SHALL GOVERN THE WORK OF THIS SECTION:
1.1 THE FOLLOWING REFERENCE STANDARDS SHALL GOVERN THE WORK OF THIS SECTION:
1.1.1 CSA S16-14, DESIGN OF STEEL STRUCTURES 1.1.1 ASTM A108-13, SPECIFICATION FOR STEEL BAR, CARBON AND ALLOY, COLD FINISHED
1.1.1 CSA S136-16 PACKAGE, COLD-FORMED STEEL STRUCTURAL MEMBERS • BUILDINGS • EARTH & ENVIRONMENT •
1.1.2 CSA S136-16 PACKAGE, COLD-FORMED STEEL STRUCTURAL MEMBERS 1.1.2 CSA S16-14, DESIGN OF STEEL STRUCTURES
1.1.2 CSSBI 10M-13, STANDARD FOR STEEL ROOF DECK • ENERGY • INDUSTRIAL •
1.1.3 CSA W47.1-09(R2 014), CERTIFICATION OF COMPANIES FOR FUSION WELDING OF STEEL 1.1.3 CSA S136-16, NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS
1.1.3 CSSBI 12 M-15 , STANDARD FOR COMPOSITE STEEL DECK
1.1.4 CSA W5 9-13, WELDED STEEL CONSTRUCTION 1.1.4 CSA W47.1-09(R2 014), CERTIFICATION OF COMPANIES FOR FUSION WELDING OF STEEL • INFRASTRUCTURE • SUSTAINABILITY •
1.1.4 ASTM A108-13, SPECIFICATION FOR STEEL BAR, CARBON AND ALLOY, COLD FINISHED
1.1.5 CSA W178.1-14, CERTIFICATION OF WELDING INSPECTION ORGANIZATIONS 1.1.5 CSA W5 9-13, WELDED STEEL CONSTRUCTION
1.1.5 ASTM A65 3/A65 3M-15 , STEEL SHEET, ZINC-COATED (GALVANIZED) OR ZINC-IRON
1.1.6 CSA W178.2 -14, CERTIFICATION OF WELDING INSPECTORS 1.1.6 CSA W178.1-14, CERTIFICATION OF WELDING INSPECTION ORGANIZATIONS CAUTION: DO NOT SCALE DRAWINGS.
COATED (GALVANNEALED) BY HOT-DIP PROCESS THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
1.2 DESIGN OF JOISTS SHALL BE BY A PROFESSIONAL ENGINEER LICENSED IN THE PROVINCE OF ONTARIO 1.1.7 CSA W178.2 -14, CERTIFICATION OF WELDING INSPECTORS
1.1.6 CSA W47.1(R2 014), CERTIFICATION OF COMPANIES FOR FUSION WELDING OF STEEL ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
EXPERIENCED IN STEEL JOIST DESIGN. 1.2 DESIGN OF CONNECTIONS SHALL BE BY A PROFESSIONAL ENGINEER LICENSED IN THE PROVINCE OF ONTARIO. FOR INCORRECT SCALING. UNAUTHORIZED
1.1.7 CSA W5 9-13, WELDED STEEL CONSTRUCTION REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
1.3 DESIGN CRITERIA 1.3 DESIGN CRITERIA
1.1.8 CSA W178.1-14, CERTIFICATION OF WELDING INSPECTION ORGANIZATIONS PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
1.3.1 DESIGN JOISTS FOR GRAVITY LOADS NOTED ON PLANS, CONCENTRATED LOADS NOTED IN 1.3.1 AXIAL LOADED MEMBERS THAT MEET AT A JOINT SHALL HAVE THEIR CENTROIDAL AXES INTERSECT DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
1.1.9 CSA W178.2 -14, CERTIFICATION OF WELDING INSPECTORS USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
OBC AND WIND UPLIFT. AT A COMMON POINT UNLESS SHOWN OTHERWISE.
1.2 DESIGN OF STEEL DECK SHALL BE BY A PROFESSIONAL ENGINEER LICENSED IN THE MUST BE IN WRITING.
1.3.2 DESIGN FOR DEFLECTIONS NOT EXCEEDING LIMITS GIVEN IN ANNEX D OF CSA S16. 1.3.2 DESIGN AND DETAIL ALL CONNECTIONS AS FLEXIBLE EXCEPT WHERE NOTED OTHERWISE ON THE DRAWINGS.
PROVINCE OF ONTARIO EXPERIENCED IN THE DESIGN OF METAL DECK.
1.4 SUBMITTALS CONNECTIONS MAY BE WELDED OR BOLTED.
1.3 DESIGN CRITERIA: © exp, 2012
1.4.1 SUBMIT JOIST DESIGN DRAWINGS AND ERECTION DRAWINGS. 1.3.3 PROVIDE CONNECTIONS ADEQUATE TO RESIST REACTION OF BEAM, WHEN IT IS LOADED TO MAXIMUM
1.3.1 WHEREVER STRUCTURAL FRAMING PERMITS, DESIGN AND FABRICATE DECK TO SPAN
.1 EACH SHOP DRAWING SUBMITTED SHALL BEAR THE SIGNATURE AND SEAL OF FLEXURAL CAPACITY UNDER UNIFORMLY DISTRIBUTED LOAD, UNLESS REACTION OR CONNECTION DETAIL
OVER AT LEAST 4 SUPPORTS (3 SPANS).
THE PROFESSIONAL ENGINEER RESPONSIBLE FOR JOIST DESIGN. IS SHOWN ON DRAWINGS.
1.3.2 ROOF DECK
.2 INDICATE: ALL LOADS FOR WHICH LOADS HAVE BEEN DESIGNED, DIMENSIONED 1.3.4 WHERE MOMENT CONNECTIONS ARE CALLED FOR BUT DESIGN FORCES ARE NOT INDICATED, DESIGN MOMENT
.1 DESIGN ROOF DECK IN ACCORDANCE WITH CSSBI 10M FOR GRAVITY LOADS NOTED
INTERSECTIONS OF MEMBERS, BRIDGING LOCATIONS, JOIST SPACING, SLOPES, CONNECTION FOR THE FULL MOMENT CAPACITY OF THE WEAKER MEMBER JOINED.
ON PLANS, CONCENTRATED LOADS NOTED IN OBC AND WIND UPLIFT. MINIMUM
JOIST BEARING. 1.3.5 FOR BOLTED CONNECTIONS USE SNUG TIGHT HIGH STRENGTH BOLTS, ASTM F312 5GRADES A325OR A490 EXCEPT
FACTORED UNIFORM GRAVITY LOAD FOR STRENGTH IS 3.5kPa (75psf).
USE PRETENSIONED HIGH STRENGTH BOLTS IN LOCATIONS SPECIFIED IN CSA-S16 CLAUSE 2 2 .2
.2
.2 MAXIMUM DEFLECTION SHALL NOT EXCEED OF 1/2 40 OF SPAN UNDER UNIFORM LIVE
2 PRODUCTS .1 SLIP-CRITICAL CONNECTIONS WHERE SLIPPAGE CANNOT BE TOLERATED;
OR SNOW LOAD BUT NOT LESS THAN 1.9 kPa (40 psf).
.2 SHEAR CONNECTIONS PROPORTIONED IN ACCORDANCE WITH SEISMIC REQUIREMENTS;
.3 DESIGN DECK AND FASTENING TO RESIST DIAPHRAGM SHEARS NOTED ON DRAWINGS.
2
.1 MATERIAL .3 ALL ELEMENTS RESISTING CRANE LOADS;
1.3.3 DO NOT SUSPEND CEILINGS, LIGHTS, DUCTS, PIPES OR ANY OTHER ITEMS FROM STEEL DECK.
2.1.1 PROVIDE NEW MATERIALS IN ACCORDANCE WITH REFERENCE STANDARDS, OF STRENGTH .4 CONNECTIONS SUBJECT TO IMPACT OR CYCLIC LOADING;
1.4 SUBMITALS
AND QUALITY NOTED IN GENERAL NOTES. .5 CONNECTIONS WHERE THE BOLTS ARE SUBJECT TO TENSILE LOADING;
1.4.1 SUBMIT STEEL DECK SHOP DRAWINGS.
2.1.2 PAINT: .6 CONNECTIONS USING OVERSIZE OR LONG SLOTTED HOLES (UNLESS SPECIFICALLY DESIGNED
.1 EACH SHOP DRAWING SUBMITTED SHALL BEAR THE SIGNATURE AND SEAL OF
.1 INTERIOR: SHOP COAT FOR STEEL THAT WILL NOT RECEIVE A FINISH COAT: TO CISC/CPMA TO ACCOMMODATE MOVEMENT).
THE PROFESSIONAL ENGINEER RESPONSIBLE FOR DECK DESIGN.
Standard 1-73A, A QUICK-DRYING ONE-COAT PAINT FOR USE ON STRUCTURAL STEEL. 1.3.6 PROVIDE CONNECTIONS FOR MEMBERS THAT ARE PART OF THE LATERAL LOAD RESISTING SYSTEM ADEQUATE TO RESIST
.2 INDICATE DESIGN LOADING, DECK PROFILE, THICKNESS, STEEL GRADE,
.2 INTERIOR: PRIME PAINT: TO MEET THE REQUIREMENTS OF CISC/CPMA 2 -75
, A QUICK DRYING FORCES SHOWN ON DRAWINGS. WHERE SEISMIC DESIGN GOVERNS, THE FORCES HAVE BEEN ADJUST TO MEET THE
ZINC COATING, LAYOUT OF UNITS, SIZE AND SPACING OF FASTENING TO MEET 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
PRIMER FOR USE ON STRUCTURAL STEEL REQUIREMENTS OF CLAUSE 2 7. 1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
UPLIFT AND DIAPHRAGM REQUIREMENTS.
.3 EXTERIOR: ZINC-RICH PAINT READY MIX TO SPCC-PAINT 2 0 STANDARD 1.4 SUBMITTALS DATE
ISSUE BY DESCRIPTION
1.4.1 SUBMIT STRUCTURAL SHOP DRAWINGS. YY-MM-DD
2 PRODUCTS
3 EXECUTION .1 EACH SHOP DRAWING SUBMITTED SHALL BEAR THE SIGNATURE AND SEAL OF THE GENERAL NOTES:
PROFESSIONAL ENGINEER RESPONSIBLE FOR CONNECTION DESIGN. DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
2
.1 MATERIAL: ASTM A65 3/A65 3M, GRADE 2 30 MIN, MINIMUM ZINC COATING ZF75
, MINIMUM THICKNESS 0.76 mm.
2
.2 SHEET STEEL ANGLES, COVER PLATES, CLOSURES, FLASHINGS, AND REINFORCING SHALL BE OF 3.1 EXTEND BOTTOM CHORDS OF JOISTS WHERE REQUIRED TO SUPPORT CEILING. "ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
3.2 PROVIDE EXTENDED TOP CHORDS, REINFORCED CONTINUOUSLY FROM END OF JOIST TO SECOND PANEL POINT 2 PRODUCTS DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
SIMILAR MATERIAL AND ZINC COATING AS DECK.
2
.3 PRIME PAINT FOR TOUCH-UP: ZINC-RICH PAINT READY MIX TO SPCC-PAINT 2 0 STANDARD WHERE JOISTS CANTILEVER BEYOND BEARING. ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
3.3 PROVIDE TOP CHORDS OF SUFFICIENT WIDTH AND MATERIAL THICKNESS TO PERMIT 2 0 mm DIAMETER WELDS 2
.1 MATERIAL DISCREPANCIES.
2
.4 REINFORCEMENT FOR OPENINGS:
OF DECK TO JOIST. 2.1.1 PROVIDE NEW MATERIALS IN ACCORDANCE WITH REFERENCE STANDARDS, OF STRENGTH AND QUALITY
2.4.1 REINFORCE OPENINGS 45 0 mm (18”) (IF ROOF) ACROSS
3.4 PROVIDE CAMBER TO JOISTS FOR FULL DEAD LOAD DEFLECTION. ADJUST CAMBER TO JOISTS ADJACENT TO NOTED IN GENERAL NOTES.
FLUTES, WITH 5 1 X51 X 6.4 (2X 2X ¼) STRUCTURAL STEEL ANGLES IN DIRECTION PERPENDICULAR TO
WALLS, JOISTS WITH SHORTER SPAN AND SIMILAR STIFFER ELEMENTS TO ALLOW ATTACHMENT OF DECK. 2.1.2 GALVANIZING: HOT-DIP TO ASTM A15 3 / A15
3M-16 STANDARD SPECIFICATION FOR ZINC COATING OWNER
FLUTES EXTENDING 45 0 mm (18”) PAST OPENING. WELD TO DECK WITH 2 5mm (1”) LONG WELDS AT
LIMIT DIFFERENCE IN CAMBER BETWEEN ADJACENT SUPPORTS TO DECK SPAN/100. (HOT-DIP) ON IRON AND STEEL HARDWARE.
15 0 mm (6”) CENTRES. BROOKLYN CONTRACTING INC
3.5 IN ORDER TO FACILITATE THE PASSAGE OF MECHANICAL DUCTS AND PIPES THROUGH JOISTS, LOCATE WEB 2.1.3 PAINT:
MEMBERS TO LINE UP FROM JOIST TO JOIST. .1 INTERIOR: SHOP COAT FOR STEEL THAT WILL NOT RECEIVE A FINISH COAT: TO CISC/CPMA
3 EXECUTION 3245 HARVESTER ROAD #14
3.6 T.J. DENOTES TIE JOIST WITH AT LEAST ONE END CONNECTED TO A COLUMN WITH FULL SIZE OF BOTTOM CHORD STANDARD 1-73A, A QUICK-DRYING ONE-COAT PAINT FOR USE ON STRUCTURAL STEEL.
.2 INTERIOR: PRIME PAINT: TO MEET THE REQUIREMENTS OF CISC/CPMA STANDARD 2 -75
, BURLINGTON, ON, L7N 3T7
3.1 PLACEMENT: CONNECTED TO COLUMN. DESIGN AND CONNECT TIE JOIST FOR A NEGATIVE SPECIFIED MOMENT OF 10kN-m
(ERECTION LOADS) AT COLUMN IN ADDITION TO GRAVITY LOADS. PROVIDE MINIMUM SIZE BOTTOM CHORD FOR TIE A QUICK DRYING PRIMER FOR USE ON STRUCTURAL STEEL
3.1.1 MINIMUM BEARING ON STRUCTURAL STEEL SUPPORTS: 45mm (1 ¾”).
JOISTS, 2L’s 44X44X4.8 (1 ¾ X 1 ¾ X3/16). EITHER TOP OR BOTTOM CONNECTION SHALL UTILIZE A BOLTED .3 EXTERIOR: ZINC-RICH PAINT READY MIX TO SPCC-PAINT 20 STANDARD DEVELOPMENT CONSULTANT
3.1.2 LAP ENDS OF PANELS NOT LESS THAN 45mm (1 ¾”).
3.2 FASTENING: CONNECTION. API DEVELOPMENT CONSULTANTS INC.
3.7 BRIDGING SHOWN ON DRAWINGS IS A GUIDELINE ONLY. PROVIDE BRIDGING IN ACCORDANCE WITH CSA S16 AND IN 3 EXECUTION 1464 CORNWALL ROAD, UNIT 7
3.2.1 WELD FLUTES TO STEEL SUPPORTS WITH 2 0 mm (3/4”) DIAMETER WELD AT MAXIMUM 300 mm (12
”) CENTRES.
3.2.2 PROVIDE WELD AT END LAPS AT 400 mm (16”) CENTRES MAXIMUM. ADDITION PROVIDE ONE ROW OF HORIZONTAL BRIDGING AT FIRST BOTTOM CHORD PANEL POINT AT END OF EACH OAKVILLE, ON L6J 7W5, CANADA
JOIST. 3.1 PROVIDE WELDED STIFFENER PLATES MINIMUM 10 mm THICK ON BOTH SIDES OF WEB OF BEAMS AT POINTS OF
3.2.3 SECURE PANELS TO EACH OTHER BY BUTTON PUNCHING AT 600 mm (2 4”) CENTRES MAXIMUM.
3.8 ALL PIPES MUST BE HUNG FROM TOP CHORD OF JOISTS. IF A CONCENTRATED LOAD (APPROVED BY THE CONCENTRATED LOADS INCLUDING BEAMS SUPPORTING COLUMNS OR BEAMS SUPPORTED ON TOP OF COLUMNS. ARCHITECT
3.2.4 WELD STUD SHEAR CONNECTORS THROUGH DECK WHERE INDICATED ON DRAWINGS.
STRUCTURAL ENGINEER) IS HUNG FROM A JOIST AT A LOCATION OTHER THAN A PANEL POINT, PROVIDE 3.2 ALL EXPOSED WELDS SHALL BE CONTINUOUS AND GROUND SMOOTH. SAPLYS ARCHITECTS INC.
3.2.5 INSTALL SHEET STEEL COVER PLATES AS MAY BE REQUIRED TO SUPPORT CANTS, INSULATION AND
A JOIST DIAGONAL FROM THE HANGER LOCATION TO THE NEAREST PANEL POINT ON THE BOTTOM CHORD. 3.3 PROVIDE STRUCTURAL STEEL FOR LATERAL SUPPORT OF MASONRY WALLS. 610 FORD DRIVE SUITE 338
OTHER ROOFING COMPONENTS. SECURE WITH WELDS OR CORROSION RESISTANT SHEET METAL
3.9 PROVIDE MINIMUM 65mm (2½”) BEARING ON STEEL BEAMS. WHERE JOISTS ARE ON BOTH SIDES OF BEAM AND 3.4 CLEAN STEEL, IN ACCORDANCE WITH PAINT SYSTEM SPECIFIED. ZINC-RICH PAINT REQUIRES CLEANING TO SSPC-SP6,
SCREWS. OAKVILLE, ON L6J 7W4, CANADA
MINIMUM BEARING CANNOT BE ACHIEVED, STAGGER JOISTS. COMMERCIAL BLAST CLEANING.
3.2.6 CLEAN AND WIRE BRUSH WELDS, SCRATCHES AND OTHER DAMAGED AREAS AND APPLY TWO
3.10 CLEAN STEEL, IN ACCORDANCE WITH PAINT SYSTEM SPECIFIED. ZINC-RICH PAINT REQUIRES CLEANING TO 3.5 PAINTING: NORTH PROFESSIONAL
COATS OF PRIME PAINT. CERTIFICATION
SSPC-SP6, COMMERCIAL BLAST CLEANING. 3.5.1 PAINT INTERIOR STEEL SURFACES WITH INTERIOR PAINT SPECIFIED
3.3 WHERE MECHANICAL EQUIPMENT IS SUPPORTED ON TIMBER SLEEPERS OR CURBS DIRECTLY ON
3.11 PAINTING: 3.5.2 PAINT EXTERIOR STEEL SURFACES WITH EXTERIOR PAINT SPECIFIED.
ROOF DECK, PROVIDE WEDGES IN FLUTES OF DECK UNDER SLEEPER AT STRUCTURAL SUPPORT (BEAMS,
3.11.1 PAINT INTERIOR STEEL SURFACES WITH INTERIOR PAINT SPECIFIED 3.5.3 DO NOT PAINT:
JOISTS, WALLS).
3.11.2 PAINT EXTERIOR STEEL SURFACES WITH EXTERIOR PAINT SPECIFIED. .1 SURFACES AND EDGES WITHIN 5 0 mm OF FIELD WELDS
3.11.3 DO NOT PAINT: .2 SURFACES ENCASED IN OR IN CONTACT WITH CONCRETE
4 FIELD QUALITY CONTROL
.1 SURFACES AND EDGES WITHIN 5 0 MM OF FIELD WELDS .3 SURFACES TO BE SPRAY FIREPROOFED.
.2 SURFACES ENCASED IN OR IN CONTACT WITH CONCRETE 3.5.4 AFTER ERECTION IS COMPLETE GIVE ONE COAT TOUCH-UP PAINT TO FIELD BOLTS, FIELD CONNECTIONS,
4.1 INSPECTION AND TESTING COMPANY SHALL PERFORM:
.3 SURFACES TO BE SPRAY FIREPROOFED. BURNT AREAS AND DAMAGED AREAS. USE SAME PAINT AS SHOP PAINT.
4.1.1 VERIFICATION OF MATERIAL THICKNESS, DEPTH, PROFILE AND ZINC COATING;
3.11.4 AFTER ERECTION IS COMPLETE GIVE ONE COAT TOUCH-UP PAINT TO FIELD BOLTS, 3.6 GALVANIZE LINTELS, BRICK SUPPORT ANGLES, ARCHITECTURAL BLOCK SUPPORT ANGLES AND OTHER
4.1.2 VERIFICATION OF ERECTION AND FASTENING;
FIELD CONNECTIONS, BURNTAREAS AND DAMAGED AREAS. USE SAME PAINT AS SHOP PAINT. MEMBERS INDICATED AS GALVANIZED ON DRAWINGS AFTER SHOP WELDING IS COMPLETE.
4.1.3 GENERAL INSPECTION OF COATING TOUCH-UP. PROJECT
3.12 COMPLY WITH THE REQUIREMENTS OF REFERENCE STANDARDS AND REQUIREMENTS OF REGULATORY 3.7 COMPLY WITH THE REQUIREMENTS OF REFERENCE STANDARDS AND REQUIREMENTS OF REGULATORY AUTHORITIES IN
ERECTION OF STRUCTURAL STEEL.
UPPER CENTENNIAL
AUTHORITIES IN ERECTION OF JOISTS.
3.8 PROVIDE MINIMUM BEARING FOR ALL STEEL BEAMS: COMMERCIAL DEVELOPMENT
4 FIELD QUALITY CONTROL 3.8.1 100 mm (4”) ON STEEL
BUILDING 1
4.1 INSPECTION AND TESTING COMPANY SHALL PERFORM: 4 FIELD QUALITY CONTROL
4.1.1 INSPECTION OF JOIST BEARING; UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
4.1.2 INSPECTION OF ERECTION AND FIT-UP INCLUDING PLACING, PLUMBING AND LEVELLING; 4.1 INSPECTION AND TESTING COMPANY SHALL PERFORM:
DRAWING TITLE
4.1.3 INSPECTION OF WELDED AND BOLTED CONNECTIONS; 4.1.1 INSPECTION OF ERECTION AND FIT-UP INCLUDING PLACING, PLUMBING AND LEVELLING;
4.1.4 GENERAL INSPECTION OF FIELD CUTTING AND ALTERATIONS; 4.1.2 INSPECTION OF BOLTED CONNECTIONS INCLUDING VERIFICATION OF BOLT GRADE AND IF
4.1.5 GENERAL INSPECTION OF COATING TOUCH-UP. SNUG TIGHT AND PRETENSIONED BOLTS HAVE BEEN USED APPROPRIATELY;
4.1.3 INSPECTION OF WELDED JOINTS; GENERAL NOTES
12/8/2020 3:18:51 PM
SCALE
2020-215
AS NOTED S0.04 2
TENSION DEVELOPMENT LENGTH AND TENSION LAP SPLICES (Fy=400 MPa AND 500 MPa) C-017
SPLICE CLASS A OR Ld CLASS B = 1.3*Ld CLASS A OR Ld CLASS B = 1.3*Ld CLASS A OR Ld CLASS B = 1.3*Ld CLASS A OR Ld CLASS B = 1.3*Ld CLASS A OR Ld CLASS B = 1.3*Ld CLASS A OR Ld CLASS B = 1.3*Ld SPLICE
10M 300 (12) 380 (15) 300 (12) 350 (14) 300 (12) 320 (13) 300 (12) 300 (12) 300 (12) 300 (12) 300 (12) 300 (12) 10M 05/18/21
15M 440 (18) 570 (23) 400 (16) 520 (21) 370 (15) 480 (19) 350 (14) 450 (18) 330 (13) 420 (17) 310 (12) 400 (16) 15M
20M 580 (23) 750 (30) 530 (21) 690 (28) 490 (20) 640 (26) 460 (19) 600 (24) 430 (17) 560 (23) 410 (16) 530 (21) 20M Joyanne Beckett
25M 900 (36) 1170 (47) 830 (33) 1070 (43) 760 (30) 990 (39) 720 (29) 930 (37) 670 (27) 880 (35) 640 (26) 830 (33) 25M
30M 1080 (43) 1410 (56) 990 (39) 1290 (51) 920 (37) 1190 (47) 860 (34) 1110 (44) 810 (32) 1050 (42) 770 (31) 1000 (40) 30M
35M 1260 (50) 1640 (65) 1150 (46) 1500 (60) 1070 (43) 1390 (55) 1000 (40) 1300 (52) 940 (38) 1220 (49) 890 (36) 1160 (46) 35M
1. USE TABULATED TENSION LAP SPLICE LENGTHS UNLESS NOTED OTHERWISE ON DRAWINGS.
2. TENSION DEVELOPMENT LENGTHS, Ld DENOTED AS TENSION LAP SPLICE CLASS A.
3. FOR COLUMNS, USE COLUMN TENSION SPLICE TYPICAL DETAIL C-018.
4. TOP BARS ARE BARS WITH MORE THAN 300 (12") OF CONCRETE BELOW.
5. CLEAR COVER NOT LESS THAN db, CLEAR SPACING NOT LESS THAN 1.4 db.
6. DIMENSIONS ARE MILLIMETRES, EXCEPT DIMENSIONS IN BRACKETS ARE INCHES.
© exp, 2012
ARRANGEMENT OF REINFORCEMENT IN
MECHANICAL HOUSEKEEPING PADS C-028 C-015 SCHEDULE OF CONCRETE PROPERTIES C-001
COLUMN/PIERS
STRUCTURAL ELEMENTS CLASS OF EXPOSURE COMPRESSIVE STRENGTH (MPa) LOCATION/REMARKS
FOUNDATION
BAR BELOW
UPSTAND WALL AND CURB ABOVE 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
TRENCH FOOTING C-1 35 u/n LOADING DOCKS, GAS 1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
(CORROSIVE ENVIRONMENTS) STATIONS
20 (3/4") CHAMFER, TYP. 10@300 (12") TOP EACH WAY 4 BAR 6 BAR 8 BAR ISSUE BY DESCRIPTION
DATE
YY-MM-DD
DOSAGE: 20l/m3
REINFORCEMENT DOES NOT PASS THROUGH
COLUMN REINFORCEMENT CAGE OWNER
75 (3")
APRON SLABS AND EQUIPMENT C-1 35 CORROSION INHIBITOR BROOKLYN CONTRACTING INC
SITEWORKS
40 (1 1/2") CLEAR PADS DOSAGE: 20l/m3
3245 HARVESTER ROAD #14
PLACE 10@600 (18") DOWELS (MINIMUM 2 EACH SIDE). BURLINGTON, ON, L7N 3T7
DRILL AND SET IN HILTI HIT HY-200 ADHESIVE OR C-2
CURBS AND SIDEWALKS 32 u/n
EQUIVALENT WHERE EXISTING SLAB.
SEE TIE ARRANGEMENTS DEVELOPMENT CONSULTANT
ABOVE FOR COLUMN API DEVELOPMENT CONSULTANTS INC.
NOTES: PLACED MONOLITHICALLY 1464 CORNWALL ROAD, UNIT 7
OAKVILLE, ON L6J 7W5, CANADA
1. SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR SIZES AND LOCATIONS.
2. DIMENSIONS ARE MILLIMETRES, EXCEPT DIMENSIONS IN BRACKETS ARE INCHES. ARCHITECT
NOTES:
COLUMNS PLACED MONOLITHICALLY SAPLYS ARCHITECTS INC.
1 THIS SCHEDULE IS A PERFORMANCE-BASED SPECIFICATION IN ACCORDANCE WITH CSA A23.1, TABLE 5 ALTERNATIVE (1). NOTHING ON 610 FORD DRIVE SUITE 338
WITH FOUNDATION WALLS THE DRAWINGS OR SCHEDULES SHALL BE CONSTRUED OR INTERPRETED AS RENDERING THE SPECIFICATION TO BE ALTERNATIVE (2). OAKVILLE, ON L6J 7W4, CANADA
2. READ THIS SCHEDULE IN CONJUNCTION WITH THE SEPARATELY BOUND SPECIFICATIONS. FOR EXPOSURE CLASSIFICATION OF
NOTES: BUILDING ELEMENTS NOT SHOWN IN SCHEDULE AND FOR OTHER CONCRETE PROPERTIES AND REQUIREMENTS INCLUDING BUT NOT NORTH PROFESSIONAL
CERTIFICATION
LIMITED TO SUPPLEMENTARY CEMENTITIOUS MATERIALS AND AGGREGATE SIZE, REFER TO THE SEPARATELY BOUND
1. OMIT INTERIOR TIE WHERE CLEAR SPACING BETWEEN ANY TWO ADJACENT LONGITUDINAL REINFORCEMENT BARS, "R," IS SPECIFICATIONS.
150 (6") OR LESS. ALTERNATING AND CORNER LONGITUDINAL BARS REQUIRE INTERIOR TIE REGARDLESS OF SPACING 3. CONCRETE STRENGTHS SHOWN ARE MINIMUMS. PROVIDE THE GREATER OF THE STRENGTH SHOWN ABOVE AND THE STRENGTHS
DIMENSION, "R". SHOWN ON PLANS AND OTHER SCHEDULES ON DRAWINGS.
2. PROVIDE 10M TIES UNLESS OTHERWISE NOTED. 4. WHERE ELEMENTS OF DIFFERENT EXPOSURE CLASSIFICATIONS, STRENGTHS, CORROSION INHIBITOR DOSAGES, AND SHRINKAGE
3. ALTERNATE 90 DEG. HOOK ALONG DEPTH AND IN SUCCESSIVE SETS LONGITUDINALLY. LIMITS ARE PLACED MONOLITHICALLY, USE THE MOST SEVERE EXPOSURE CLASSIFICATION, AND RESPECTIVE STRENGTH AND
4. ARRANGE VERTICAL BARS AS SHOWN UNLESS NOTED OTHERWISE IN PIER SCHEDULE. CORROSION INHIBITOR DOSAGE.
5. SEE PIER SCHEDULE FOR SPECIFIED REINFORCEMENT.
6. SEE TYPICAL DETAIL C-002 FOR CONCRETE COVER.
7. DIMENSIONS ARE MILLIMETRES, EXCEPT DIMENSIONS IN BRACKETS ARE INCHES.
PROJECT
UPPER CENTENNIAL
COMMERCIAL DEVELOPMENT
BUILDING 1
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
DRAWING TITLE
TYPICAL DETAILS
12/8/2020 3:18:53 PM
SCALE
2020-215
AS NOTED S0.05 2
SLAB ON GRADE - STEPS, TRENCHES & SHALLOW
MASONRY PARTITION SUPPORT ON SLAB ON GRADE SG-007 SUPPORT OF STAIRS AT GRADE SG-006 SG-004
PITS
900 MAX
200
(36")
(8")
MASONRY WALL SLAB ON GRADE 1
SEE PLAN FOR SIZE SEE PLAN 20 196379 000 00 C3
2
STEEL STAIR AND 200 05/18/21
CLEAR
STRINGER
75
(8")
Joyanne Beckett
MIN.
200
(8")
CONNECTION BY STEEL 450 450
STAIR SUPPLIER
(18") (18")
200
(8")
POURED IN PLACE
CONC. FTG. STEP
ORIGINAL UNDISTURBED SOIL 10M@250 300
2-15 CONT + 10@1200 FOR BEARING PRESSURE (12")
(48")TRANSVERSE 100 100 SEE SOIL REPORT.
(4") (4") 10@300 FOR COVER & FRAME SEE MECH
(12")
300
SPACER
EACH WAY & ARCH. DWGS.
(3") TYP.
SAWCUT
1-15 CONT.
75
(12") (12") JOINT
OR 150 (6") IN THICKNESS t TYP.
t
STEEL STAIRS
1
t
2
1 50
6"
1 Markham, ON L3T 0A8
CANADA
1
MAX DEPTH
300 300 www.exp.com
600 (24")
2-15 CONT 2-10M CONT.
(1'-0") (1'-0")
+ 10@1200 (48")
TRANSVERSE 1
SPACER 1
CONT. 38mmx50mm
1 50
(6")
(1 1/2"x2") SHEAR KEY
THICKENING AT MASONRY PARTITIONS NOT EXCEEDING 150 10M@300mm
• BUILDINGS • EARTH & ENVIRONMENT •
COVER
75 (3")
(6") IN THICKNESS AND 3600 (12'-0") IN HEIGHT (12") EACH WAY 200 • ENERGY • INDUSTRIAL •
(8") ORIGINAL • INFRASTRUCTURE • SUSTAINABILITY •
UNDISTURBED SOIL
CAUTION: DO NOT SCALE DRAWINGS.
TYPICAL SHALLOW PITS, THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
FOR INCORRECT SCALING. UNAUTHORIZED
REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
MUST BE IN WRITING.
© exp, 2012
SLAB ON GRADE - JOINT DETAILS SG-003 SLAB ON GRADE - AREA PLACEMENT SG-001 CONCRETE CURBS ON SLABS C-029
50 (2")
t/4
50 (2")
10@300 (12") VERT.
t
1200 (4'-0")
15@300 (12") HOR. (1 MIN. 10@300 (12") VEF
MAX
FOR CURBS 150 (6") HIGH, 2 15@300 (12") HEF 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
450 (18")
MIN. FOR CURBS 151 (6") TO
MAX
50 (2")
DATE
200 (8") HIGH)
50 (2")
ISSUE BY DESCRIPTION YY-MM-DD
GENERAL NOTES:
'X'
ADD 10M HOR. MIN. AT
HOOK, WHERE NO
BOTTOM REINF. IN SLAB
OWNER
'X' 100 (4") TO 190 (7.5") MAX 200 (8") OR GREATER BROOKLYN CONTRACTING INC
SAWCUT OR KEYED 3245 HARVESTER ROAD #14
CONSTRUCTION JOINTS BURLINGTON, ON, L7N 3T7
FOR EXPOSED SURFACES
EDGE EACH SIDE WITH 3
REFER TO DETAIL SG-003 CURBS (NON-VEHICULAR GUARD) ON UNREINFORCED SLAB
(1/8") RADIUS. 20 SAWCUT FOR BAYS EXCEEDING 'X' DEVELOPMENT CONSULTANT
PLAN 1. SEE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS AND ARCHITECT
DIMENSIONS OF CURBS NOT SHOWN ON STRUCTURAL DRAWINGS.
"H" SHAPED COLUMN SAPLYS ARCHITECTS INC.
2. AT TOP OF CURB, PROVIDE 20 (3/4") CHAMFERS OR ROUNDED CORNERS EACH SIDE, TYPICAL
N.
N.
610 FORD DRIVE SUITE 338
MI WHERE NO MASONRY ABOVE -SEE ARCHITECTURAL DRAWINGS.
MI
)
")
6" COLUMN BASE 3. PLACED HOOKED VERTICAL REINFORCEMENT BEFORE PLACING CONCRETE SLAB. OAKVILLE, ON L6J 7W4, CANADA
(3
0(
75
1 5 PLATE 4. COVER IN ACCORDANCE WITH TYPICAL DETAIL C-002: NORTH PROFESSIONAL
5. FOR BARS IN CURB: AS FOR TYPICAL WALLS. CERTIFICATION
KEYED CONSTRUCTION JOINT FOR FOR HOOK IN SLAB: AS FOR SLABS.
SLAB GREATER THAN 100 (4") 6. DIMENSIONS ARE MILLIMETRES, EXCEPT DIMENSIONS IN BRACKETS ARE FEET AND INCHES.
.
IN DO NOT PLACE INFILL CONCRETE
")M
75(3 AT COLUMN UNTIL AT LEAST 21
DAYS AFTER PLACING ADJACENT
PROJECT
SLABS. POUR INFILL DOWN TO
TOP OF CAP OR PIER.
UPPER CENTENNIAL
FORM CIRCULAR CONSTRUCTION
JOINT. REMOVE FORM BEFORE ALTERNATIVE DIAMOND COMMERCIAL DEVELOPMENT
PLACING INFILL. JOINT AT COLUMNS CONSTRUCTION JOINT BUILDING 1
NOTES UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
1. FORM AROUND COLUMNS.
2. PLACE SLAB AREA NO LARGER THAN CAN BE FINISHED IN ONE DAY. DRAWING TITLE
3. SAWCUTCONTROL JOINTS AS SOON AS CONCRETE HAS SET SUFFICIENTLY TO AVOID RAVELING EDGES. USE EARLY
ENTRY SAW (SOFF-CUT, BY HUSQVARNA). COMMENCE SAWCUTTING AS SOON AS CONCRETE CAN SUPPORT WEIGHT
OF SAW AND OPERATOR WITHOUT MARRING CONCRETE SURFACE AND WITH 2 HOURS COMPLETION OF FINAL TYPICAL DETAILS
12/8/2020 3:18:53 PM
FINISHING.
4. SAWCUT AT COLUMN CENTRELINES. FOR BAYS EXCEEDING 'X' SAWCUT ALSO INTO PANELS NOT EXCEEDING 'X,'
UNLESS OTHERWISE NOTED ON PLANS. BY CHECKED ISSUED FOR
5. LIMIT RATIO OF LENGTH TO WIDTH OF ANY SAWCUT PANEL TO 1.5 MAXIMUM. D.J. A.T. SEE TABLE ABOVE
6. FILL SAWCUT JOINTS WITH SEMI-RIGID EPOXY, IN ACCORDANCE WITH SPECIFICATION. PROJECT No. SHEET NO. SHEET REV
7. DIMENSIONS ARE mm, EXCEPT DIMENSIONS IN BRACKETS ARE INCHES.
8. SUBMIT PROPOSED CONTROL AND SAWCUT JOINT LOCATIONS IN DRAWING FORMAT FOR REVIEW PRIOR TO
CONSTRUCTION. SCALE
2020-215
AS NOTED S0.06 2
TYPICAL WALL FOOTING ADJACENT TO
F-011 STRIP FOOTING OVER BURIED SERVICE F-010 TYPICAL STEPPED FOOTING DETAIL F-009
EXCAVATIONS
20 196379 000 00 C3
05/18/21
Joyanne Beckett
WALL FOOTING
T
7 7
MINIMUM
BOTTOM OF PROVIDE 50mm (2") THICK MAX SLOPE 10
BEFORE CONSTRUCTION OF FOOTINGS, EXAMINE EXCAVATION COMPRESSIBLE MATERIAL
D
INVERT ELEVATIONS OF UNDERGROUND SERVICES, ETC. AROUND UNDERGROUND 45° MAX.
FOOTINGS IN THE VICINITY SHALL BE LOWERED TO SERVICE.
SATISFY THE MAX. SLOPE OF 7 TO 10
PROVIDE 10 MPa CONCRETE BACKFILL EXP Services Inc.
WHERE EXCAVATION RUNS UNDER THE t: +1.905.695.3217 f: +1.905.470.7700
LINE OF FOOTINGS 220 Commerce Valley Drive West, Suite 500
Markham, ON L3T 0A8
CANADA
www.exp.com
© exp, 2012
TYPICAL EXTERIOR COLUMN FOUNDATION DETAIL, TYPICAL INTERIOR COLUMN DETAIL, STEEL COLUMN
FOUNDATION WALLS WITH TRENCH FOOTING F-005 F-003 F-001
STEEL COLUMN WITH TRENCH FOOTING WITH TRENCH FOOTING
CURB WIDTH
8"
50 (2") MIN.
AND GROUTED STEEL COLUMN SEE PLAN, AND SCHEDULE
8" MIN.
8"
GENERAL NOTES:
UNLESS NOTED OTHERWISE
2 LAYERS OF 6-MIL POLY SUP-SHEET DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
OR 6MM THICK AFIB AS BOND BREAK OR POUR No.1 POUR No.2 POUR No.1 "ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
8"
DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
PACK GROUT
MINIMUM 4'0" FOR FROST PROTECTION
OWNER
TRENCH AND POUR CONC. CONSTRUCTION JOINT AROUND COLUMN
FOOTING. TYP SEE TYP. DETAIL SG-001, SG-002 BROOKLYN CONTRACTING INC
TRENCH WIDTH SLAB-ON-GRADE 3245 HARVESTER ROAD #14
BURLINGTON, ON, L7N 3T7
8" U.N.O.
DEVELOPMENT CONSULTANT
DOWELS NOT REQUIRED IF
WALLS POURED MONOLITHIC. API DEVELOPMENT CONSULTANTS INC.
1464 CORNWALL ROAD, UNIT 7
75 (3") CLEAR
CLEAR COVER
BOTTOM REINFORCING IF REQUIRED. SEE OR 6MM THICK AFIB AS BOND BREAK
(BOTH SIDES) TYP
75 (3")
50 x 100 FOOTING SCHEDULE. HOOK BAR IF NOTED
75 (3")
(2" x 4") KEY CLEAR COVER
EXTERIOR UNDISTURBED SOIL OR APPROVED
PLAN 2 LAYERS OF 6-MIL POLY ENGINEERING FILL. SEE SOIL REPORT BOTTOM REINFORCING IF REQUIRED. SEE
SUP-SHEET OR 6MM FOOTING SCHEDULE. HOOK BAR IF NOTED
CONC. COVER
MINIMUM COVER TO REINFORCING STEEL
BASEPLATE
50 (2") MIN
THICK AFIB AS BOND
COVER 'C' 25mm (1") 75mm (3") 25mm (1") BREAK (BOTH SIDES) TYP UNDISTURBED SOIL OR APPROVED PROJECT
COVER 'C'
ENGINEERING FILL. SEE SOIL REPORT UPPER CENTENNIAL
EXPOSURE CLASS BAR SIZE COMMERCIAL DEVELOPMENT
≤ 25 30 35 BUILDING 1
N 25 30 35 INSIDE FACE INSIDE FACE
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
F-1, F-2, S-1, S-2 40 45 55 DRAWING TITLE
AS NOTED S0.07 2
JOIST BEARING ON EXTERIOR BEAM S-006 BEAM TO COLUMN CONNECTION DETAIL S-005 STRUCTURAL STEEL JOIST DETAILS S-004
© exp, 2012
STEEL DECK AND HORIZONTAL BRIDGING DETAIL S-003 JOISTS BEARING ON BEAMS AT COLUMN LOCATIONS S-002 FROST SLAB DETAIL F-030
OPEN WEB STEEL JOIST SEE ARCH. DWG. FOR LOCATIONS. GENERAL NOTES:
DESIGNED BY JOIST ADDITIONAL BOTTOM CHORD PANEL POINT DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
SUPPLIER TYPICAL CONTINUOUS HORIZONTAL BRIDGING AT BOTH INSTALL 6mil SLIP SHEET
DOOR "ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
ENDS OF ALL JOISTS, DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
COLUMN SEE ARCH. DWG.
TYPICAL. THIS BRIDGING IS IN ADDITION TO MINIMUM 0.5 MPa LEAN MIX ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
BRIDGING REQUIRED BY THE JOIST DESIGNER, DISCREPANCIES.
AND IS TO BE SUPPLIED AND SIDEWALK, SEE ARCH
INSTALLED BY JOIST SUPPLIER.
SLAB ON GRADE OWNER
SEE ARCH. DWG. SLOPE SEE PLAN
EXTEND FULL SIZE BOTTOM CHORD OF
WELD STEEL DECK TO ALL SUPPORTING STEEL ROOF JOIST AND CONNECT TO STEEL COLUMN BROOKLYN CONTRACTING INC
FOR LOADS AS PER NOTES. TYPICAL IN SLIP RESISTANT
STEEL BY MEANS OF 20Ø FUSION DECK
ALL CASES WHERE JOISTS FRAME INTO SLOTTED CONNECTION 3245 HARVESTER ROAD #14
WELDS @ 300 MAX. c/c. TYPICAL U.N.O.
BURLINGTON, ON, L7N 3T7
DENOTED AS "T.J.".
BY CHECKED ISSUED FOR
JOISTS BEARING BEAMS AT COLUMN LOCATIONS D.J. A.T. SEE TABLE ABOVE
(WHERE JOIST DEEPER THAN BEAM) PROJECT No. SHEET NO. SHEET REV
SCALE
2020-215
AS NOTED S0.08 2
SPANDREL BEAM CONNECTION S-016 DOOR LINTEL DETAIL S-012 VERTICAL BRACE DETAILS S-010
BEAM
COL.
2-200x18Ga STEEL STUDS 1900 MAX. OPENING
PROVIDE TOP AND BOTTOM CONNECTED TOGETHER
FLANGE ANGLES TO RESIST (ALSO SPANNING HORIZ.
TWISTING. AT ROOF, ABOVE DOOR) HEADER
ORIENTATE TOP FLANGE ABOVE DOOR
ANGLE VERTICAL LEG DOWN SLOT COLUMN AS REQUIRED TO
INSTALL GUSSET PLATE THROUGH BEAM
CENTER LINE OF COLUMN. WELD
GUSSET PLATE TO EACH FACE OF
COLUMN. WELD GUSSET TO 20 196379 000 00 C3
ROOF BEAM.
05/18/21
GUSSET PLATE
Joyanne Beckett
150 150
STUD LOOSE LINTEL SEE
WALL MIN. MIN.
PLAN & SCHEDULE
SPANDREL BELOW. BRACE
FACE BRICKWHERE APPLICABLE
BEAM
TYPICAL BRACE CONNECTION
COL. BRACE TO COLUMN & ROOF BEAM
OPENING SIZE LINTEL
NOTES:
BRACE.
1. SPANDREL BEAM IS DEFINED AS AN EXTERIOR PERIMETER BEAM. SEE ELEV.
• BUILDINGS • EARTH & ENVIRONMENT •
2. SUPPORT SHOW IS AN "HSS" COLUMN. PROVIDE SIMILAR CONNECTION AT OTHER TYPES OF SUPPORT, SUCH AS "HSS"
SLOT HSS AS REQUIRED • ENERGY • INDUSTRIAL •
COLUMN, OR GIRDER SUPPORT.
FOR CONT. GUSSET PLATE. • INFRASTRUCTURE • SUSTAINABILITY •
WELD GUSSET PLATE TO
EACH FACE OF HSS. (TYP.) CAUTION: DO NOT SCALE DRAWINGS.
THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
FOR INCORRECT SCALING. UNAUTHORIZED
TYPICAL BRACE CONNECTION REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
GUSSET PL. USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
MUST BE IN WRITING.
© exp, 2012
VERTICAL BRACE ELEVATION DETAIL S-009 TRIMMING AT OPENINGS IN DECK S-008 CANTILEVERED BEAM DETAIL S-007
COLUMN SPLICE
SEE PLAN FOR DIMENSION
GRID GRID
DECKSPAN
VERTICAL BRACE 2000mm (6'-8") CONSULT
SCHEDULE STRUCTURAL CONSULTANT
FOR REQUIRED EN BEFORE PROCEEDING OWNER
EN OP
CONNECTION
BROOKLYN CONTRACTING INC
OP
STRENGTHS.
3245 HARVESTER ROAD #14
SEE DETAIL 2-12mm STIFF. PLATES EACH STEEL JOIST BURLINGTON, ON, L7N 3T7
S-010 SIDE OF WEB. TYPICAL FOR TYPICAL WHERE SHOWN
ALL CANTILEVERED BEAMS.
DEVELOPMENT CONSULTANT
CONNECTION BETWEEN CANTILEVERED BEAM
AND CONNECTION CAP PLATE TO HAVE MIN. 4 API DEVELOPMENT CONSULTANTS INC.
FOR JOIST SPACING UP TO 2000mm FOR OPENINGS LENGTHS UP TO
BOLTS. SLOPE CONNECTION CAP PLATE AS 1464 CORNWALL ROAD, UNIT 7
FILL CONCRETE PIER (6'-8") - C100X8 FOR LARGER 900mm (3'-0") - L64X64X4.8 FROM
POCKET WITH SPACING SEE PLAN. STEEL COLUMN REQUIRED TO ACCOMMODATE ROOF SLOPES. OAKVILLE, ON L6J 7W5, CANADA
900mm (3'-0") TO 1800mm (6'-0") -
20 MPa CONCRETE C100X8 SEE PLAN. ARCHITECT
AFTER BASEPLATE CONNECT BOTTOM CHORD OF THE JOIST TO
COLUMN/BEAM FOR MOMENT SPECIFIED IN SAPLYS ARCHITECTS INC.
ARE GROUTED 610 FORD DRIVE SUITE 338
STRUCTURAL SPECIFICATION OR ON DRAWINGS.
OAKVILLE, ON L6J 7W4, CANADA
NOTES:
NORTH PROFESSIONAL
CERTIFICATION
1. TOP OF ALL TRIMMING TO BE INSTALLED TIGHT TO UNDERSIDE OF STEEL DECKUNLESS OTHERWISE NOTED
SEE DETAIL S-010
2. LOCATION OF MECHANICAL UNITS AND OPENINGS THROUGH ROOF IS BASED ON INFORMATION SHOWN ON MECHANICAL
DRAWINGS. THE STRUCTURAL STEEL SUB-CONTRACTOR MUST CONFIRM ALL THESE DIMENSIONS AND SIZES WITH THE
MECHANICAL CONTRACTOR
SCALE
2020-215
AS NOTED S0.09 2
1 2a 2 2b 3 1 2a 2 2b 3
A A A A
C S C
Z
Z
S 20 196379 000 00 C3
B1 B1 05/18/21
Z
a
3X Joyanne Beckett
kP
1 .5
B C B B B
B2 Y B2 Y
4 6 8 4 6 8
a
1 .5 kP
S
R S
Z
C C
1X C C 1X
Z
S
1 .5
C
3X
kP
R
a
D2 D2 1 .5 kPa a
kP
Z
1 .5
D D
S R Z
1
1 kP
a
1 .5
EXP Services Inc.
t: +1.905.695.3217 f: +1.905.470.7700
Y Y
Z
Z
C S S C
Z
CANADA
F F www.exp.com
F F
X X
3a 4a 4 6 8 4a 4 6 8
• BUILDINGS • EARTH & ENVIRONMENT •
• ENERGY • INDUSTRIAL •
• INFRASTRUCTURE • SUSTAINABILITY •
WIND PRESSURE TABLE (kPa)
CAUTION: DO NOT SCALE DRAWINGS.
THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
WIND UPLIFT WIND PRESSURE
4 WIND UPLIFT KEY PLAN 3 RAIN LOAD KEY PLAN ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
FOR INCORRECT SCALING. UNAUTHORIZED
REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
1/16" = 1'-0" C -0.83 0.14 1/16" = 1'-0" PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
MUST BE IN WRITING.
1. DESIGN WIND UPLIFT AS NOTED. AND NOT LESS THAN THAT REQUIRED BY OBC2012(R2019) S -0.64 0.13
2. POSITIVE COEFFICIENTS DENOTE FORCES TOWARD THE SURFACE, NEGATIVE © exp, 2012
COEFFICIENTS DENOTE FORCES AWAY FROM THE SURFACE
R -0.48 0.13
3. WIND UPLIFT LOADS SHOWN ARE UNFACTORED
Z 8' - 10"
1 2a 2 2b 3 1 2a 2 2b 1.29 kPa
3
V.B.
190 kN
A A A A 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
13' - 7"
DATE
ISSUE BY DESCRIPTION YY-MM-DD
23' - 6"
GENERAL NOTES:
2.98 kPa DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
1.29 kPa
"ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
13' - 7"
B1 B1 ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
DISCREPANCIES.
V.B.
B B B B OWNER
2.98 kPa
2.9
4 6 8 8k
Pa
4 6 8 3245 HARVESTER ROAD #14
BURLINGTON, ON, L7N 3T7
23' - 6"
1.29 kPa DEVELOPMENT CONSULTANT
6"
1X 1X OAKVILLE, ON L6J 7W5, CANADA
'-
23
13' - 7"
ARCHITECT
3X 3X SAPLYS ARCHITECTS INC.
35 kN 35 kN
610 FORD DRIVE SUITE 338
OAKVILLE, ON L6J 7W4, CANADA
NORTH PROFESSIONAL
D2 D2 CERTIFICATION
1.29 kPa
7"
'-
13
13' - 7"
D D
1 1 1 .2
9k
Pa
6"
'-
V.B.
23
23' - 6"
PROJECT
UPPER CENTENNIAL
13' - 7"
Y COMMERCIAL DEVELOPMENT
E
2.9
8k
Pa
E
BUILDING 1
385 kN
F F UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
V.B. F 2.98 kPa
1.29 kPa F
X
DRAWING TITLE
35 kN
248 kN
3a 4a 4 6 8
171 kN
LOADING PLANS
35 kN
12/8/2020 3:18:58 PM
AS NOTED S1.01 2
1 2a 2 2b 3
S2.02
4
TF-2 TF-2 TF-2
F3
F2
F1
F1
TF-3
A A
20 196379 000 00 C3
TF-2
FROST SLAB. SEE 05/18/21
TYP. DETAIL.
Joyanne Beckett
TF-1
TF-2a
FROST SLAB. SEE
1 S2.02
TYP. DETAIL.
TF-1a
F2
TF-2
B1
S2.01 10
3X FROST SLAB. SEE
TYP. DETAIL.
F8
F4
TF-1
B B
TF
-2
F2
S2.02 FROST SLAB. SEE
T.O.F. -1' - 8" TYP. DETAIL.
TF
B2 2
Y
-2
a
4 6 8 EXP Services Inc.
TF
-2
PROVIDE SAWCUTS IN SLAB FROST SLAB. SEE S2.02 FROST SLAB. SEE t: +1.905.695.3217 f: +1.905.470.7700
ON GRADE AS PER SG-001 TYP. DETAIL. TYP. DETAIL. 220 Commerce Valley Drive West, Suite 500
Markham, ON L3T 0A8
TF
5 CANADA
-2
a
www.exp.com
F3
F4
F4
F2
TF
C
-2
TF-3 TF-2 TF-2a TF-2 TF-2a TF-2 TF-2a TF-2 TF-2a
1X
TF-1
TF-2
CAUTION: DO NOT SCALE DRAWINGS.
THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
FOR INCORRECT SCALING. UNAUTHORIZED
REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
MUST BE IN WRITING.
F4
F9
SOIL REPORT FOR RECOMMENDED SUB-GRADE
AND SUB-GRADE PREPARATIONS. F.F.E = 0.00
9
TF
F8
-2
F9
F4
S2.01
8
1 D
S2.01
TF
-2
a
TF
-1
DATE
7 ISSUE BY DESCRIPTION
TF
YY-MM-DD
TF-2
-1
GENERAL NOTES:
ON GRADE AS PER SG-001
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
"ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
Y 6
DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
TF
DISCREPANCIES.
S2.01
FROST SLAB. SEE
TYP. DETAIL. OWNER
E
F4
F4
F4
F2
F1
TF-1 TF-1 TF-2 TF-2a TF-2 TF-2a TF-2 TF-2 TF-2a TF-2 TF-2a TF-2
BROOKLYN CONTRACTING INC
1/8" = 1'-0" 2. BOTTOM OF TRENCH/PAD FOOTINGS AT ELEVATION -5'8" (205.6 GEODETIC) ON UNDISTURBED SOIL ELEVATION OR APPROVED
ENGINEERED FILL. REFER TO SOIL REPORT. ENSURE MIN 4'0" BELOW EXTERIOR GRADE FOR PERIMETER FOOTINGS.
TRENCH FOOTING AND FOUNDATION WALL SCHEDULE 3 CARRY FOOTINGS DOWN TO NATURAL UNDISTURBED SOIL OF BEARING CAPACITY:
FOOTING SCHEDULE
SERVICEABILITY LIMIT STATES (SLS): 200 kPa
TYPE MARK FOOTING WIDTH WALL WIDTH CURB WIDTH SIZE REINFORCING ULTIMATE LIMIT STATES (ULS): 300 kPa
TF-1 1' - 8" 0' - 11" 0' - 7 3/8" MARK L W EACH WAY BOTTOM, UNO EACH WAY TOP, UNO REMARKS
4 FOOTING ELEVATIONS, AND BEARING VALUE OF SOIL UNDER FOOTINGS AND SLAB ON GRADE ARE BASED ON INFORMATION
F1 2' - 6" 2' - 6" NO REINFORCING NO REINFORCING PROJECT
TF-1a 1' - 8" 0' - 11" 0' - 0" F2 3' - 0" 3' - 0" NO REINFORCING NO REINFORCING
AVAILABLE AT THE TIME DRAWINGS ARE ISSUED. REFER TO GEOTECHNICAL INVESTIGATION PREPARED BY EXP SERVICES INC.REPORT
UPPER CENTENNIAL
NUMBER HAM-00801949-A0 DATED JULY 29, 2020 . REPORT ADJUSTMENTS NECESSARY DUE TO ACTUAL CONDITIONS TO THE CONSULTANT
TF-2 1' - 10" 1' - 2 5/8" 0' - 6 5/8" F3 3' - 6" 3' - 6" NO REINFORCING NO REINFORCING BEFORE PROCEEDING WITH THE WORK. COMMERCIAL DEVELOPMENT
F4 4' - 0" 4' - 0" NO REINFORCING NO REINFORCING
TF-2a 1' - 10" 1' - 2 5/8" 0' - 0" F8 6' - 0" 6' - 0" NO REINFORCING NO REINFORCING 5 BEFORE PLACING SLAB ON GRADE VERIFY THAT BEARING CAPACITY OF SUBGRADE AND COMPACTION OF SUB-BASE ARE ADEQUATE BUILDING 1
F9 6' - 6" 6' - 6" NO REINFORCING NO REINFORCING TO SUPPORT 25 kPa UNIFORMLY DISTRIBUTED LOAD ON SLAB ON GRADE WITHOUT SIGNIFICANT DIFFERENTIAL SETTLEMENT BETWEEN
TF-3 2' - 2" 1' - 5" 0' - 9" SLAB AND BUILDING FOOTINGS. UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
NOTE: REFER TO TYPICAL DETAIL F-005 6 FOR ALL TRENCH FOOTINGS REFER TO FOUNDATION WALL DETAILS ON S0 SERIES DRAWINGS. DRAWING TITLE
7 LOWER FOOTINGS BELOW ALL INCOMING SERVICES. SEE TYPICAL DETAIL ON S0 SERIES DRAWINGS.
FOUNDATION PLAN
12/8/2020 3:18:59 PM
8 “SFU”DENOTES STEP FOOTING UP, “SFD”DENOTES STEP FOOTING DOWN. SEE TYPICAL DETAIL ON S0 SERIES DRAWINGS.
9 CENTRE ALL BASEPLATES AND FOOTINGS UNDER COLUMNS UNLESS OTHERWISE NOTED ON PLANS. BY CHECKED ISSUED FOR
D.J. A.T. SEE TABLE ABOVE
10 CONCRETE PROPERTIES: SEE SCHEDULE OF CONCRETE PROPERTIES ON S0 SERIES DRAWINGS.
PROJECT No. SHEET NO. SHEET REV
11
12
SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR DEPRESSIONS IN SLAB ON GRADE. MAINTAIN SLAB THICKNESS SPECIFIED
ON PLAN.
AS NOTED S1.02 2
1 2a 2 2b 3
S2.02
HIGHLINE
4
L.
L.
L.
L.
<25KN> <60KN> <40KN>
CO
CO
CO
CO
W410x39 W360x33 W360x33
A A
V.B.
T.J.
T.J.
T.J.
20 196379 000 00 C3
RTU 1-1 ADDITIONAL X-BRIDGING
MAX WEIGHT= L38X38X3.2 @ 6’-8”C/C MAX. WHERE SHOWN 05/18/21
3.6 KN (800 lbs)
HIGHLINE
Joyanne Beckett
W310x28
N1 B N2 B N1
A
B
22" OWSJ
22" OWSJ
22" OWSJ
22" OWSJ
26" OWSJ
26" OWSJ
B
W360x39
A A N1 1 S2.02
COLUMN TIE B
L76x76x6.4 (TYP.) N1 N2 B
HIGHLINE
RD1
<25 KN>
26" OWSJ
22" OWSJ
22" OWSJ
B1
<30KN>
S2.01 10 4' - 0"
3X
V.B.
T.J.
W410x46
L.
L.
CO
CO
W530x66 W530x66 (CANT.)
B B
T.J.
LP
S2.02
B2 2
Y
L.
<60 KN> CO
RD1
W
W360x33
31
W
4 6 8
36
0x
0x
21
39
22" OWSJ
S2.02 EXP Services Inc.
N2 B N2
W
24" OWSJ
t: +1.905.695.3217 f: +1.905.470.7700
8
20
x2
0x
220 Commerce Valley Drive West, Suite 500
0
5
31
19
W
Markham, ON L3T 0A8
<6
28" OWSJ
A
31
5K
CANADA
0x2
28" OWSJ
N>
28" OWSJ
28" OWSJ
28" OWSJ
28" OWSJ
28" OWSJ
B
W
A
1
20
HIGHLINE www.exp.com
0x
A <30KN> <20KN>
L.
L.
L.
19
CO
CO
CO
W360x33 W410x39 W410x39
L.
C
CO
W410x39
B
N2 N2
1X 22" OWSJ 28" OWSJ
RTU 1-2
28" OWSJ • BUILDINGS • EARTH & ENVIRONMENT •
MAX WEIGHT=
5.8 KN (1300 lbs) • ENERGY • INDUSTRIAL •
60
0x
• INFRASTRUCTURE • SUSTAINABILITY •
46
24" OWSJ 28" OWSJ 28" OWSJ
W
CAUTION: DO NOT SCALE DRAWINGS.
W530x66
THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
FOR INCORRECT SCALING. UNAUTHORIZED
REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
28" OWSJ N1 N1 28" OWSJ N1 N1 N1 N1 28" OWSJ N1 N1 PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
W
W530x66
W530x66
DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
20
0x
L.
19
CO
0k
D2 A A A A
N>
B
L.
W
CO
© exp, 2012
N2 N2 N2 N2 N2 N2 N2 N2
20
A
28" OWSJ 28" OWSJ 28" OWSJ
0x
<40KN>
9
19
W
31
0 x2
1
B B B B
W
B
31
S2.01
20
0x
0x
W
L.
L.
L.
1 28" OWSJ T.J. T.J. 28" OWSJ T.J. T.J. 28" OWSJ T.J.
21
CO
CO
CO
31
19
39
D
0x
RD1
RD1
RD1
0x
24
41
HIGHLINE
N1 N1 N1 N1 N1 N1 N1 N1
W
4' - 0"
4' - 0"
MAX WEIGHT= RTU 1-4 RTU 1-5 LP RTU 1-6 RTU 1-7
5.8 KN (1300 lbs) LP MAX WEIGHT= MAX WEIGHT= MAX WEIGHT= MAX WEIGHT=
N2 N2
W
3.4 kN (750 lbs) 3.4 kN (750 lbs) 3.4 kN (750 lbs) 28" OWSJ 3.4 kN (750 lbs)
0x2
B
1
<3
0K
A
N>
B
B
A
S2.01
W200
W610x101
L.
W
CO
31
<3
x1 9
7 N2
0K
>
N2
x2
W530x66
1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
N>
W530x74 (CANT.)
W530x66 (CANT.)
ISSUE BY DESCRIPTION YY-MM-DD
28" OWSJ 28" OWSJ 28" OWSJ
INDICATES BEAM GENERAL NOTES:
FRAMING OVER W COLUMN.
Y A
W
6
0x
B
24
26" OWSJ 28" OWSJ 26" OWSJ DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
HI
<40KN>
INDICATES BEAM FRAMING DISCREPANCIES.
LIN
W2
E
0x1 9 <55 00x1 9
OWNER
W20 5kN> W410x39
L.
kN>
<5
CO
W310x28 W310x28 W410x39 BROOKLYN CONTRACTING INC
F <55KN>
L.
F
CO
L.
L.
L.
CO
CO
CO
5 3 1 BURLINGTON, ON, L7N 3T7
4 S2.01 S2.01 2 ADDITIONAL X-BRIDGING
T/BEAM C/L
L38X38X3.2 @ 6’-8”C/C MAX. WHERE SHOWN
INDICATES AXIAL
X S2.01 S2.01 S2.01 DEVELOPMENT CONSULTANT
ARCHITECT
REQUIRED IF OMITTED) ROOF FRAMING PLAN NOTES OAKVILLE, ON L6J 7W4, CANADA
W12x22 ( C=1")
- INDICATED COMPRESSION
+ INDICATES TENSION 6. DESIGN OWSJ SUPERIMPOSED DEAD LOAD, JOIST SELF WEIGHT, WEIGHT OF EQUIPMENT SHOWN ON PLAN, LIVE LOAD, BY CHECKED ISSUED FOR
SNOW LOADS, RAIN LOAD AND WIND UPLIFT. DEAD LOAD FOR UPLIFT CALCULATIONS IS 0.3 kPa + SELF WEIGHT. SEE TABLE ABOVE
D.J. A.T.
PROJECT No. SHEET NO. SHEET REV
7. STEEL DECK IS DESIGNED TO ACT AS A DIAPHRAGM. REFER TO ROOF DIAPHRAGM DETAILS ON S0 SERIES DRAWINGS.
AS NOTED S1.03 2
20 196379 000 00 C3
05/18/21
Joyanne Beckett
T/O GIRT (AT H. PAR) C200x17 C200x17 C200x28 C200x17 C200x17 C200x17 T/O GIRT (AT H. PAR) • BUILDINGS • EARTH & ENVIRONMENT •
23' - 2 1/2" 23' - 2 1/2" • ENERGY • INDUSTRIAL •
T/O GIRT (AT L. PAR)
C100X7
C100X7
C200x17
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
• INFRASTRUCTURE • SUSTAINABILITY •
20' - 3 1/2"
C100X7
C100X7
CAUTION: DO NOT SCALE DRAWINGS.
U/S ROOF DECK(HP) U/S ROOF DECK(HP) THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
16' - 5" 16' - 5" FOR INCORRECT SCALING. UNAUTHORIZED
REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
.
V.
.
C.
V.
.C
PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
.C
.C
.C
V.
S.
S.
S.
S
S
S
S
C.
V.
V.
V.
V.
C.
V.
.C
HSS152x152x6.4
USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
.
MUST BE IN WRITING.
HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8
© exp, 2012
C150X12
C150X12
HSS152x152x6.4
HSS152x152x6.4
HSS152x152x6.4
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
HS
.4
S1
x6
52
Cf
52
=T
x1
N
x1
0k
52
f=
52
x6
22
22
S1
.4
0k
f=
HS
=T
N
Cf
F.F.E. F.F.E.
0' - 0" 0' - 0"
10 ELEV ON GRIDLINE 1 8 ELEV ON GRIDLINE 1X 7 ELEV ON GRIDLINE Y BTW 1X& X 6 ELEV ON GRIDLINE X 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
1/8" = 1'-0"
9 ELEV ON GRIDLINE D2 1/8" = 1'-0" 1/8" = 1'-0" 1/8" = 1'-0"
1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
DATE
ISSUE BY DESCRIPTION YY-MM-DD
1/8" = 1'-0"
GENERAL NOTES:
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
"ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
DISCREPANCIES.
OWNER
DEVELOPMENT CONSULTANT
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
OAKVILLE, ON L6J 7W4, CANADA
9' - 10" 8' - 5"
U/S ROOF DECK(HP) SIGNAGE U/S ROOF DECK(HP) NORTH PROFESSIONAL
CERTIFICATION
16' - 5" 16' - 5"
1" THICK STIFFENER
C.
HSS178x178x6.4
C.
C.
V.
V.
.
.
V.
V.
C
C
BOTH SIDES
S.
S.
S.
S.
S.
S.
S.
S.
S.
V.
C.
C.
V.
V.
C.
C.
V.
V.
STEEL LINTEL,
HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8
SEE GENERAL DETAILS
4
HS
x6.
S15
152
Cf=
kN
2x1
52x
220
Tf=
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
52x
S1
220
Tf=
C150X12
HS
6.4
Cf=
PROJECT
kN
UPPER CENTENNIAL
COMMERCIAL DEVELOPMENT
F.F.E. F.F.E. BUILDING 1
0' - 0" 0' - 0"
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
DRAWING TITLE
ELEVATIONS
12/8/2020 3:19:04 PM
5 ELEV ON GRIDLINE F BTW 2X& 4 4 ELEV ON GRIDLINE 4 BTW E & F 3 ELE ALONG GRIDLINE E BTW 4 & 6 2 ELEV ON GRIDLINE 6 BTW E & F 1 ELEV ON GRIDLINE F BTW 6 & 8
BY CHECKED ISSUED FOR
1/8" = 1'-0" 1/8" = 1'-0" 1/8" = 1'-0" 1/8" = 1'-0" 1/8" = 1'-0" D.J. A.T. SEE TABLE ABOVE
PROJECT No. SHEET NO. SHEET REV
SCALE
2020-215
AS NOTED S2.01 2
20 196379 000 00 C3
05/18/21
Joyanne Beckett
T/O GIRT (AT H. PAR) T/O GIRT (AT H. PAR) C200x17 C200x17 C200x17 T/O GIRT (AT H. PAR)
23' - 2 1/2" 23' - 2 1/2" 23' - 2 1/2"
T/O GIRT (AT L. PAR) C200x28 C200x28 T/O GIRT (AT L. PAR) C200x17
C100X7
C100X7
C100X7
C100X7
C100X7
20' - 3 1/2" 20' - 3 1/2"
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
U/S ROOF DECK(HP)
16' - 5"
U/S ROOF DECK(HP)
16' - 5"
U/S ROOF DECK(HP)
16' - 5"
SIGN U/S ROOF DECK(HP)
16' - 5"
• BUILDINGS • EARTH& ENVIRONMENT •
• ENERGY • INDUSTRIAL •
• INFRASTRUCTURE • SUSTAINABILITY •
V.
V.
V.
V.
.
V.
.
C
.C
.C
.C
.C
S
S.
S.
S.
S
S
.C
.C
.C
.C
C.
V.
V.
V.
V.
V.
V.
CAUTION: DO NOT SCALE DRAWINGS.
.
.
THIS REPRODUCTION MAY BE AT A SIZE DIFFERENT THAN
HSS178x178x4.8 HSS178x178x4.8 ORIGINALLY DRAWN. EXP ASSUMES NO RESPONSIBILITY
FOR INCORRECT SCALING. UNAUTHORIZED
REPRODUCTION OR REUSE IS STRICTLY PROHIBITED. NOT
HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8 HSS178x178x4.8 PUBLISHED - ALL RIGHTS RESERVED. EXP EXPRESSLY
DISCLAIMS RESPONSIBILITY ARISING FROM UNAUTHORIZED
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
USE OF THESE DRAWINGS AND NOTES. AUTHORIZATION
C150X12
MUST BE IN WRITING.
.4
HS
x6
1
52
S1
N
x1
52
Cf
0k
© exp, 2012
52
x1
=T
S3.01
18
S1
52
f=
f=
HS
x6
18
=T
.4
0k
Cf
N
F.F.E. F.F.E. F.F.E. F.F.E.
0' - 0" 0' - 0" 0' - 0" 0' - 0"
5 ELEV ON GRIDLINE C 4 ELEV ON GRIDLINE A 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
1/8" = 1'-0" 1/8" = 1'-0" DATE
ISSUE BY DESCRIPTION YY-MM-DD
GENERAL NOTES:
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
"ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
DISCREPANCIES.
OWNER
DEVELOPMENT CONSULTANT
C100X7
20' - 3 1/2" 20' - 3 1/2" 20' - 3 1/2" 20' - 3 1/2" SAPLYS ARCHITECTS INC.
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C100X7
C.
V.
V.
C.
C.
S.
S.
S.
S.
S.
S.
C.
C.
C.
C.
V.
V.
V.
V.
S.
S.
V.
V.
HSS152x152x6.4
HSS152x152x6.4
HSS178x178x6.4
C150X12
C150X12
C150X12
C150X12
C150X12
C150X12
HSS152x152x6.4
C150X12
C150X12
4
x6. HS
2 x1 52 S1
52
5 kN Cf= x1 5
S1 2
HS 1 50 Tf= x6. PROJECT
Cf=
T f= 1 50
kN
4 UPPER CENTENNIAL
COMMERCIAL DEVELOPMENT
F.F.E. F.F.E. F.F.E. F.F.E. F.F.E. F.F.E.
0' - 0" 0' - 0" 0' - 0" 0' - 0" 0' - 0" 0' - 0" BUILDING 1
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
DRAWING TITLE
ELEVATIONS
NORTH
3 ELEV ON GRIDLINE 8 2 ELEV ON GRIDLINE 3X 1 ELEV ON GRIDLINE 3
12/8/2020 3:19:06 PM
SCALE
2020-215
AS NOTED S2.02 2
LIST OF DRAWINGS UPPER CENTENNIAL COMMERCIAL PROJECT CONTACTS
S20-031
07 NOV 2021
CONSTRUCTION
ISSUED FOR:
PROJECT NUMBER:
ISSUE DATE:
ARCHITECTURAL
A0.01
A001
COVER SHEET
PROPOSED SITE PLAN
DEVELOPMENT - BUILDING 1 OWNER
2354538 ONTARIO INC.
A0.02 OBC DATA MATRIX AND CODE COMPLIANCE PLAN C/O 3245 HARVESTER RD., UNIT 14
A0.03 WALL TYPES
UPPER CENTENNIAL PKWY & MUD ST W
BURLINGTON, ON L7N 3T7
A1.01
A1.02
GROUND FLOOR PLAN
ROOF PLAN
HAMILTON, ON
A2.01 ELEVATIONS
A4.01 WALL SECTIONS ARCHITECT
A4.02 WALL SECTIONS SAPLYS ARCHITECTS INC.
A6.01 DOOR SCHEDULE
A6.02 WINDOW SCHEDULE
55 ST CLAIR AVE W, STE. 205
TORONTO, ON M4V 1N5
STRUCTURAL
S-000 COVER SHEET DEVELOPMENT CONSULTANT
DEVELOPMENT - BUILDING 1
S-103 TYPICAL DETAILS OAKVILLE, ON L6J 7W5
S-104 TYPICAL DETAILS
S-105 TYPICAL DETAILS 07 NOV 2021 TEL: 905-337-7249
S-106 TYPICAL DETAILS URL: APIDEVELOPMENTCONSULTANTS.COM
S-107 TYPICAL DETAILS
S-108 LOADING PLANS
S-200 FOUNDATION PLAN STRUCTURAL ENGINEER
S-201 ROOF FRAMING PLAN
S-300 ELEVATIONS
EXP SERVICES INC.
S-301 ELEVATIONS 499 KING ST E, SUITE 200
S-400 SCHEDULES HAMILTON, ON L8N 1C9
ELECTRICAL
E01 ELECTRICAL SITE PLAN
E02 GROUND FLOOR POWER AND LIGHTING PLAN
E03 ELECTRICAL ROOF PLAN
E04 ELECTRICAL SPECIFICATION, LEGEND AND NOTES
UPPER CENTENNIAL
PKWY & MUD ST W
HAMILTON, ON
PROJECT ADDRESS:
COLUMN SCHEDULE
Joyanne Beckett
VERTICAL BRACE
VERTICAL BRACE
VERTICAL BRACE
VERTICAL BRACE
VERTICAL BRACE
VERTICAL BRACE
VERTICAL BRACE
HSS178x178x9.5
HSS178x178x9.5
HSS178x178x9.5
HSS203x203x9.5
HSS152x152x6.4
HSS152x152x6.4
HSS152x152x6.4
HSS152x152x6.4
HSS178x178x6.4
HSS152x152x6.4
HSS152x152x6.4
HSS178x178x6.4
HSS178x178x6.4
HSS152x152x6.4
HSS152x152x6.4
HSS152x152x6.4
HSS152x152x6.4
HSS178x178x6.4
HSS152x152x6.4
HSS178x178x6.4
F.F.E. F.F.E.
A-1 A-2a A-2b A-3 B-2 B-3 B1-1 B2-1 C-3 C-4 C-6 C-8 D-4 D-6 D-8 D2-1 D2-3a F-3a F-4 F-4a
4-3/4" DIA. ANCHOR BOLTS 4-3/4" DIA. ANCHOR BOLTS 4-3/4" DIA. ANCHOR BOLTS 2 A.T. ISSUED FOR BUILDING PERMIT 2020-12-08
MIN. 10" EMBEDMENT. MIN. 10" EMBEDMENT. MIN. 10" EMBEDMENT. 1 A.T. ISSUED FOR BUILDING PERMIT 2020-08-04
DATE
1" 6" C150 ISSUE BY DESCRIPTION YY-MM-DD
4" 4" 4"
1' - 3"
1' - 3"
1'-3"
GENERAL NOTES:
1"
9"
DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED
1"
1"
"ISSUED FOR CONSTRUCTION". VERIFY CONFIGURATIONS &
3" 3" 3" DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY
ARCHITECT IMMEDIATELY OF ANY ERRORS, OMISSIONS OR
7"
4" DISCREPANCIES.
BASE PL. FOR VERTICAL BRACES
- ANCHOR BOLTS TO BE
1"
1"
4 - 1 1/4" DIA. BOLTS 32" LONG 1/2" OWNER
4"
MIN. 20" EMBEDMENT. BROOKLYN CONTRACTING INC
4"
HSS COLUMN TYP.
3245 HARVESTER ROAD #14
2'-2"
BURLINGTON, ON, L7N 3T7
7"X1/2"X6" BASEPLATE +
6" 2 - 5/8" KWIK HUS-EZ SCREW ANCHOR DEVELOPMENT CONSULTANT
VERTICAL BRACE
HSS178x178x6.4
HSS152x152x6.4
HSS152x152x6.4
CONT. L102X102X6.4 LINTEL 3. BASE PLATE DIMENSION GIVEN LAST IS PARALLEL TO COLUMN WEB.
F-6 F-8 X-Y LINTEL, SEE ELEVATION PROJECT
TYP ABOVE WINDOWS/DOORS
4. PROVIDE 1/4" CAP PLATE TO ALL HSS COLUMNS.
UPPER CENTENNIAL
COMMERCIAL DEVELOPMENT
5. PROVIDE 3/8" DRAIN HOLE AT BASE OF ALL HSS COLUMNS.
BUILDING 1
6. SEE GENERAL NOTES AND TYPICAL DETAILS.
UPPER CENTENNIAL & MUD ROAD, HAMILTON, ONTARIO
DRAWING TITLE
SCHEDULES
12/8/2020 3:19:07 PM
AS NOTED S3.01 2
SIN BEAM SIZES AND BOLT GAUGE SB-001
1 2a 2 2b 3 ORIGINAL FULL SIZE DRAWINGS ARE ARCH D - 24" x 36"
t
ALL CONSTRUCTION MUST CONFORM TO ALL APPLICABLE
LOCAL CODES, BY LAWS AND ALL REQUIREMENTS OF THE
WHERE
1 2a 2 2b 3 w = WEB THICKNESS (A, B, C, D)
2w = 155mm
AUTHORITIES HAVING JURISDICTION
a3 = 40 TO 43mm
D = WEB DEPTH (IN mm)
b = FLANGE WIDTH (IN mm) THESE DRAWINGS ARE NOT TO BE USED FOR
CONSTRUCTION UNTIL THE DRAWING IS LABELED ISSUED
b
D
t = FLANGE THICKNESS (IN mm)
FOR CONSTRUCTION AND THE ENGINEERING SEAL IS
THE SINUSOIDAL WEB OF THE BEAM HAS A WAVE LENGTH a3 SIGNED BY THE ENGINEER OF RECORD
L.
L.
L.
L.
i.e. WTA - 610 / 178 x 10 : INDICATES ACCURACY OF SURVEY, ARCHITECTURAL, MECHANICAL,
O
W410x39 W360x33 W360x33
AA A
C
C
A ELECTRICAL, ETC. INFORMATION SHOWN ON THESE
t
WEB THICKNESS A (1.90mm) 21 155494 000 00 C9
V.B. WEB HEIGHT 610mm DRAWINGS. INFORMATION FOR OTHER DISCIPLINES IS
T.J.
T.J.
T.J.
FLANGE WIDTH 178mm SHOWN FOR REFERENCE ONLY. REFER TO02/25/22
THE
FLANGE THICKNESS 10mm APPROPRIATE DRAWINGS BEFORE PROCEEDING WITH ANY
WORK. Malak Rezek
TOTAL BEAM DEPTH 630mm (10 + 610 +10) FLANGE GAUGE
WIDTH (b) mm [in]
THESE DRAWINGS ARE COPYRIGHT AND PROPERTY OF
WTA_333/127x6
22" OWSJ
22" OWSJ
22" OWSJ
26" OWSJ
26" OWSJ
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
WTA_500/127x6
A
FLANGE (I.E. FOR JOIST SHOES) IS DEPENDENT 279 to 330 178 [7"]
W360x39
B
B
A A N1 ON THE FLANGE WIDTH AS FOLLOWS: 356 plus 203 [8"]
B
HIGHLINE
N1 N2 B
RD1
SIN BEAM TYPICAL SHEAR CONNECTIONS SB-002
26" OWSJ
22" OWSJ
22" OWSJ
B1 B1 L
. B1 END PLATE OR ANGLE END PLATE WELD TO
O
<30KN>
C
WELD TO T&B FLANGE T&B FLANGE AND WEB
4' - 0" AND WEB 3/4" [19mm] A325
3X
3X BOLTS
V.B.
WTA_610/152x8
W410x46
WTB_610/178x13 WTC_610/178x13
T.J.
L.
L.
O
O
W530x66 W530x66 (CANT.)
B B
C
C
B T.J. B HSS COLUMN OR WF COLUMN
LP WF COLUMN
B2 B2 L
. Y B2
O
C
W360x33
W 31
W
WTA_333/127x6
TA 0
TA
W
_3 x2
_6
3
3a 60
4 6 8
33 1
10
/12
/15
x3 T PLATE OR ANGLE AND
22" OWSJ
WTA_500/127x6
7x
2x
9
8
3/4" [19mm] A325 BOLTS
6
7x
N2 N2
8 12
x2 33/
B SHEAR TAB OR
24" OWSJ
W
WTA_500/127x6
10 _3
TA
2 SINGLE ANGLE
3 TA
00
_3
W W
33
x1 CONNECTION
W
/12
WTA_500/127x6
TA 31
<
28" OWSJ
7x
65
_3 0x
W
6
A
33 2
K
W
28" OWSJ
WTA_610/152x10
28" OWSJ
28" OWSJ
28" OWSJ
28" OWSJ
28" OWSJ
WTA_610/127x6
WTA_610/152x6
WTA_610/127x6
WTA_610/127x6
WTA_610/152x8
/12 1
N
TA
W
>
B
_3
7x
2
A
6
33
00
HIGHLINE
/12
A x1 WTA_333/127x6 WTA_610/152x10 WTA_610/152x10
L.
L.
L.
. <30KN>
7x
L 9
O
6
O W360x33 W410x39 W410x39
C
C
C C
WTA_500/152x8
W410x39
B
N2 N2
WTA_500/127x6 3X WTA_610/152x6
SHEAR TAB CONNECTION END PLATE CONNECTION
1X
1X 22" OWSJ WTA_610/152x6 28" OWSJ
28" OWSJ
SIN BEAM CANTILEVER BEAM CONNETION SB-003
0 0
x6 2x1
60 5
4 0/1
WTA_500/127x6 WTA_610/127x6
W _61
WTA_610/127x6
TA
WTC_610/178x13
WTA_610/152x10
WTB_610/178x13
W530x66
WTA_610/127x6 WTA_610/127x6 WTA_610/127x6
W
W530x66
W530x66
_3
2
00
3 3/1
x1 WTC_610/152x19 .
27
9 W610x101 O
C
D2
D2 D2 A A A A SLOTTED THRU WEB
W W2
B
TA 0
N2 N2 N2 N2 N2 N2 N2 N2
A
C
33 x1
7x
_3 0
W W2
STIFFENERS
TA 31
7x
TA
6
_3 0
B B B
_3 00
W
B
W W
33 x2
33 x1
. WTA_610/127x6
TA 3
WTA_610/127x6 WTA_610/127x6
x6
L
/12 1
/12 9
L.
L.
_3 10
1
27
7x
O
33 x
0/1
C
6
D
C
C
0x
/12 24
D D
0
CONNECTION
RD1
RD1
_5
7x
HIGHLINE
4a
TA
4
6
4' - 0"
4' - 0"
W
W N1 N1 N1 N1 N1 N1
LP SEE PLAN
W W3
LP WTA_610/127x6
TA 1
N2 N2 WTA_610/127x6
_3 0
B
6
A
B
WTA
A
W610x101
A
_333
W2 27x6
W
L.
3
O
/1
00x
10
3
C
WTB_610/152x13
WTA_610/152x10
WTF_610/178x13
3/1
W530x66
x2 N2 N2 CANTILEVER BEAM
27
19
x6
1
W530x74 (CANT.)
W530x66 (CANT.)
28" OWSJ 28" OWSJ 28" OWSJ
WTA_610/152x8 WTA_610/152x6 WTA_610/127x6
W
TA 31
Y
Y
A
W
_5 0x
00 2
/12 4
B
SIN BEAM TO SIN BEAM CONNECTIONS SB-004
7x
6
<40KN>
WTA_610/152x10 WTA_610/152x6 WTA_610/152x6
E X TA_3
33/1
27x
1
6
9 WTA_610/152x10 W2
E E SIN BEAM GIRDER ANGLE OR T PLATE SIN BEAM GIRDER
W WELD TO T&B FLANGE
WTA_333/127x6 WTA_333/127x6 00x W410x39 S IN 00x1 WTA_610/152x10 ANGLE OR T PLATE
W2 5kN>
L.
B EA 9 AND WEB
O
W310x28 W310x28 <5 M W410x39 WELD TO T&B FLANGE
F
C
<55KN> AND WEB
L.
. .
L L
F
O
L.
O O
C
F C <50KN> C <70KN>
F
O
HIGHLINE <25KN>
C
X SIN BEAM
SECONDARY
BEAM
3a 4a 4 6 8 SIN BEAM
SECONDARY
3/4" [19mm] 1 2021-11-09 REVISION TO PERMIT DVE
BEAM
A325 BOLTS # DATE DESCRIPTION BY
3/4" [19mm]
A325 BOLTS ANGLE WELDED TO CONNECTION
GIRDER TOP AND PLATE SLOTTED ANGLE WELDED CONNECTION VAN EE ENGINEERING
1 2a 2 3a 2b 3 4a 4 6 8 BOTTOM FLANGE THROUGH BEAM TO GIRDER TOP PLATE SLOTTED STRUCTURAL CONSULTANT
NOT WELDED TO WEB AND BOTTOM THROUGH BEAM 416-659-2222
GIRDER WEB FLANGE NOT TO WEB VANEEENGINEERING.CA
GIRDER WEB
S200 1 : 100
PLAN VIEW SECTION VIEW 62 Progress Ct, Brampton, ON L6S 5X2
416.798.3343 steelcon.ca
PROJECT
SIN BEAM VXB CONNECTIONS SB-005
BUILDING 1
SHEAR WEB REINF SHEAR TAB OR
WHEN REQUIRED SINGLE ANGLE COLUMN UPPER CENTENNIAL COMMERCIAL DEVELOPMENT
CONNECTION UPPER CENTENNIAL & MUD ROAD
HAMILTON, ONTARIO
SIN BEAM NOTES DRAWING
THE SIN BEAM IS A MANUFACTURED WELDED WIDE FLANGE SECTION MANUFACTURED BY STEELCON FABRICATION SHEAR WEB REINF
1. GENERAL WHEN REQUIRED
A. ALL SIN BEAM MEMBERS COMPLY WITH THE ONTARIO MINISTERS RULING MR-21-01-01A DATED JUNE 15, 2021 ROOF FRAMING PLAN
B. SIN BEAM MEMBERS AND THEIR CONNECTIONS SHALL BE DESIGNED ACCORDING TO CSA STANDARD S16 AND S136 3/4" [19mm]
C. ALL WELDING OF SIN BEAM MEMBERS AND THEIR CONNECTIONS SHALL CONFORM TO CSA STANDARD W59 AND BE A325 BOLTS
STIFFENER
PERFORMED BY A WELDED CERTIFIED TO CSA W47.1
PLATE THRU
D. SIN BEAM CONNECTIONS SHALL BE DESIGNED FOR THE FULL SHEAR CAPACITY OF THE SIN BEAM MEMBER UNLESS
BEAM WEB
NOTED OTHERWISE. SIN BEAM FRAMING NOTES WHERE PROJECT NO.
E. FOR MORE INFORMATION ON THE SIN BEAM SEE THE SIN BEAM TECHNICAL GUIDE PREPARED BY STEELCON
FABRICATION
REQ'D SFJ00449
2. PRODUCTS 1. WHERE SHOWN PROPOSED SIN BEAM MEMBERS ARE TO REPLACE WIDE FLANGE BEAMS THAT WERE SHOWN ON PROJECT DATE
A. SIN BEAM MATERIAL IS TO BE STRUCTURAL STEEL CONFORMING TO CSA G40.20/G40.21 - STRUCTURAL DRAWINGS PREPARED BY EXP. ALL OTHER MEMBERS TO REMAIN AS THE SIZES SHOWN ON STRUCTURAL
JUNE 2021
B. WEB AND FLANGE TO BE - GRADE 350W DRAWINGS
C. CONNECTION HARDWARE (ANGLES AND PLATES) - GRADE 300W 2. SIN BEAM MEMBERS ARE A WELDED WIDE FLANGE SECTION WITH A CORRUGATED STEEL WEB MANUFACTURED BY STEELCON DRAWN BY
D. BOLTS FOR CONNECTIONS SHALL BE ASTM A325 UNLESS NOTED OTHERWISE FABRICATION, MORE INFORMATION IS AVAILABLE IN THE SIN BEAM TECHNICAL GUIDE AND CODE COMPLIANCE REPORT
Author
E. ANCHOR RODS CAST INTO CONCRETE OR BLOCK SHALL BE ASTM A1554-36 UNLESS NOTED AVAILABLE ON STEELCON'S WEBSITE: www.steelcon.ca BRACING MEMBER GUSSET PLATE
F. PRIMER PAINT TO CONFORM TO CAN/CGSB- 1.40 OR CISC/CPMA 1 OR CISC/CPMA 2. 3. DEFLECTION REQUIREMENTS ARE AS FOLLOWS: CHECKED BY 2021/11/09
G. HOT DIP GALVANIZING WITH A MINIMUM ZINC COATING OF 600g/sq.m UNLESS OTHERWISE SPECIFIED. 1. LIVE: L/360, Checker
3. FABRICATION 2. DEAD + LIVE: L/240
A. FABRICATION AND ERECTION SHALL CONFORM TO CSA STANDARD S16. 4. DESIGN LOADS BRACING MEMBER SCALE
B. CLEAN, PREPARE SURFACES AND SHOP PRIME ALL SIN BEAM MEMBERS WITH ONE COAT OF SPECIFIED PRIMER PAINT IN 1. SUPERIMPOSED DEAD LOAD: 0.95 kPa As indicated
CCORDANCE WITH CAN/CSA - S16, EXCEPT WHERE MEMBERS ARE TO BE ENCASED IN CONCRETE, OR TO RECEIVE SPRAY 2. LIVE LOAD: 1.0 kPa
PPLIED FIRE PROOFING. FIELD " TOUCH-UP" BOLTS, WELDS, BURNED OR SCRAPED SURFACES AFTER ERECTION AS 3. SNOW LOAD: 1.44 kPa + DRIFT 0 5 10 20 30 40 50 mm
REQUIRED.
C. NO HOLES OTHER THAN THOSE SHOWN ON THE REVIEWED SHOP DRAWINGS SHALL BE MADE IN ANY SIN BEAM MEMBER 0" 1/4" 1/2" 1" 2"
ITHOUT AN APPROVED SKETCH REVIEWED BY THE SIN BEAM DESIGNER.
4. QUALITY CONTROL DRAWING NO.
A. ALL SIN BEAM MEMBER SHALL BE REVIEWED ON SITE AND INSPECTED WITH THE SAME CRITERIA USED FOR
CONVENTIONAL IDE FLANGE STEEL BEAMS.
S200
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
M0.01
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
M0.02
20 196379 000 00 C3
05/18/21
Joyanne Beckett
1
M1.01
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
M1.02
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
M3.01
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
1'-0" min.
1'-0" min.
UPPER CENTENNIAL & MUD
ROAD, HAMILTON, ONTARIO
M3.02
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
M6.01
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
P1.01
UNDERGROUND PLUMBING LAYOUT
SCALE : 1/8" = 1'-0"
20 196379 000 00 C3
05/18/21
Joyanne Beckett
MECHANICAL & ELECTRICAL CONSULTANTS
P1.02
GROUND FLOOR PLUMBING LAYOUT
SCALE : 1/8" = 1'-0"