ARCHITECTURAL
A.800 MILLWORK
A.801 MILLWORK
A.802 SERVERY/BAR MILLWORK
A.803 MILLWORK
STRUCTURAL
ESC
HAPA COLLABORATIVE
1400-1185 West Georgia Street 403-375 West 5th Avenue
Vancouver, BC V6E 4E6 L1.1 MATERIALS LAYOUT
Vancouver, BC V5Y 1J6 L1.2 GRADING PLAN
604-687-1821 604-909-4150 L1.3 PLANTING PLAN
L1.4 ROOF PLAN UBC ENGINEERING
Contact: Willie Perez Contact: Joseph Fry L1.5 IRRIGATION PLAN STUDENT CENTRE
Sarah Siegel L2.6 DETAILS PAVING AND SITE FURNISHINGS
L2.7 DETAILS DECKING
L2.8 DETAILS DECKING AND SWALE
L2.9 PLANTING DETAILS
CIVIL
C1 KEY PLAN
COVER SHEET
C2 UTILITY DEMOLITION PLAN
C3 PAVING PLAN
C4 SERVICING PLAN
C5 SERVICING PLAN
C6 SERVICING PLAN
C7 EROSION AND SEDIMENT CONTROL PLAN
A.001
GENERAL NOTES
KEY PLAN
1. ALL LABOUR, MATERIALS, AND PRODUCTS TO COMPLY WITH THE REQUIREMENTS OF
N
THE BRITISH COLUMBIA BUILDING CODE 2012 EDITION (BCBC) AND ALL OTHER
APPLICABLE CODES, STANDARDS AND BY-LAWS, INCLUDING, BUT NOT LIMITED TO:
401 - 134 Abbott Street
• CAN/CSA-B651-M90 BARRIER FREE DESIGN Vancouver, BC
• CSA STANDARD C2 EMERGENCY LIGHTING Canada V6B 2K4
t: 604-683-5060
2. BUILDING CODE, SAFETY STANDARDS, AND REGULATORY STATUTE REFERENCES ON e: info@urban-arts.ca
DRAWINGS ARE FOR AUTHORITY REVIEW PURPOSES ONLY. THE PRESENCE OF THE
AFOREMENTIONED NOTES DOES NOT RELEASE THE CONTRACTOR AND ALL OTHERS SEAL:
INVOLVED IN THE CONSTRUCTION OF THE PROJECT FROM THEIR LEGAL AND
STATUTORY RESPONSIBILITY TO CONFORM TO THE LAW OF THE LAND IN
CONSTRUCTING AND THE CONSTRUCTION OF THE BUILDING.
are for use on the specified project only and shall not be used otherwise
5. without written permission of this office.
SITE CONTRACTOR SHALL VERIFY DIMENSIONS, REQUIRED CLEARANCES, AND POWER AND The Contractor shall check and verify all dimensions and report any
IN
LOCATION
PLUMBING REQUIREMENTS. NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO discrepancies before proceeding.
COMMENCEMENT OF WORK. Do not scale drawings.
6.
MA
ALL DOOR PROVIDING ACCESS TO EXIT TO BE READILY OPENABLE FROM THE INSIDE
WITH NO MORE THAN ONE RELEASING OPERATION, WHEN TRAVELLING IN DIRECTION
LL
AC ASPHALTIC CONCRETE D DEPTH FOM FACE OF MASONRY LB POUND PRCST PRECAST SQ SQUARE
ACOUT ACOUSTICAL DEG DEGREES FOS FACE OF STUD LF LINEAR FOOT PREFAB PREFABRICATED SS SOLID SURFACE A F1 ASSEMBLY TYPES
ACM ASBESTOS CONTAINING DEMO DEMOLITION FOW FACE OF WALL LT LIGHT PREFIN PREFINISHED SST STAINLESS STEEL
MATERIAL DET DETAIL L LEFT MAN MANUAL PRV PRESSURE RELEASE VALVE ST STAIN
ACP ALUMINUM COMPOSITE PANEL DF DRINKING FOUNTAIN LAM LAMINATE MATL MATERIAL PWC PRESENTATION WALL STD STANDARD
ACT ACOUSTICAL CEILING TILE DIA DIAMETER LAV LAVATORY MAX MAXIMUM COVERING STL STEEL 1 STRUCTURAL OR REVISION SYMBOL &
ADDN ADDITION / ADDITIONAL DIFF DIFFUSER FPRF FIRE PROOFING MB MACHINE BOLT PSF POUNDS PER SQUARE FOOT STOR STORAGE REFERENCE GRIDS 1 BUBBLE TO INDICATE
AFF ABOVE FINISHED FLOOR DIM DIMENSION FR FIRE RATING MDF MEDIUM DENSITY FIBERBOARD PT PRESSURE TREATED STRUC STRUCTURAL AFFECTED AREA
ALUM ALUMINUM DN DOWN FRR FIRE RESISTANCE RATING MDO MEDIUM DENSITY OVERLAY PTD PAINTED / PAPER TOWEL SUBST SUBSTRATE
ALT ALTERNATE DR DOOR FRP FIBERGLASS REINFORCED MECH MECHANICAL DISPENSER SUSP SUSPENDED
ANOD ANODIZED DS DOWN SPOUT PANEL MEMB MEMBRANE PTR PAPER TOWEL RECEPTOR TB THERMAL BREAK/TACK BOARD
CUT TITLE
APPROX APPROXIMATELY DWG DRAWING FRT FIRE RETARDANT TREATED MEZZ MEZZANINE PVC POLYVINYLCHLORIDE TEMP TEMPERATURE 1
ARCH ARCHITECT / ARCHITECTURAL E EAST FT FOOT / FEET MFG MANUFACTURER (ED) PTN PARTITION T&G TONGUE AND GROVE LINE 1'-0" = 1'-0"
BD BOARD EA EACH FTG FOOTING MH MANHOLE QT QUARRY TILE THK THICK
BET BETWEEN E/A EXHAUST AIR FXTR FIXTURE MHK MOP HOOK R RIGHT THOLD THRESHOLD
BLK BLOCK EIFS EXTERIOR INSULATION FINISH GA GAUGE MO MASONRY OPENING RA RETURN AIR THRU THROUGH xxx.xx FINISHED
BLKG BLOCKING SYSTEM GALV GALVANIZED MTL METAL RAD RADIUS T/O TOP OF GRADE OR
BM BEAM EL ELEVATION GB GRAB BAR MTR BD MORTAR BED RB RUBBER TOM TOP OF MASONRY ELEVATION 0 DETAIL TITLE
BRG BEARING ELEV ELEVATOR GEN GENERAL MILWK MILLWORK RBL ROLLER BLIND TOS TOP OF STEEL A000 1'-0" = 1'-0"
BO BOTTOM OF ELEC ELECTRICAL GL GLASS MIN MINIMUM RCP REFLECTED CEILING PLAN TOW TOP OF WALL EXISTING
BOD BOTTOM OF DECK EPDM ETHYLENE PROPYLENE DIENE GLB GLUE LAM BEAM MIR MIRROR RD ROOF DRAIN TPD TOILET PAPER DISPENSER xx.xx
GRADE OR
BUR BUILT-UP ROOF MONOMER GLU-LAM GLUE LAMINATED MISC MISCELLANEOUS REF REFERENCE TS TUBE STEEL ELEVATION
C CELCIUS EQUIP EQUIPMENT GLT GLUE LAMINATED TIMBER MLDG MOLDING REINF REINFORCE (D) (ING) (MENT) TSTAT THERMOSTAT BUILDING
CAB CABINET EW EACH WAY GOV GOVERNMENT MTD MOUNTED REQD REQUIRED TFRV TRANSFER VENT 0
SECTIONS
CB CHALK BOARD EXH EXHAUST GM GLASS MESH N NORTH RESIL RESILIENT TRKV TRICKLE VENT A000
CBB CEMENT BACKER BOARD EXP EXPANDED / EXPANSION GWB GYPSUM WALL BOARD NA NOT APPLICABLE REV REVISE / REVISION TYP TYPICAL 000
CG CORNER GUARD EXP JT EXPANSION JOINT GR GRADE NAT FIN NATURAL FINISH RFG ROOFING UG UNDERGROUND ROOM NAME 03 25 2014: Issued for Construction
ROOM TITLE 12 20 2013: Revised for B.P.
CHKRD CHECKERED EXST EXISTING GRTG GRATING NFS NON FROST SUSCEPTIBLE RFS RAISED FLOOR SYSTEM U/S UNDERSIDE WALL 11 19 2013: Issued for Tender and B.P.
CL CENTER LINE EXT EXTERIOR GSP GALVANIZED STEEL PIPE NIC NOT IN CONTRACT RHK ROBE HOOK UH UNIT HEATER 0 10 18 2013: 100% Complete - Issued for Client Review
SECTIONS
CLT CROSS LAMINATED TIMBER EXTR EXTRUDED GWB GYPSUM WALL BOARD NLB NON LOAD BEARING RHMS ROUND HEAD MACHINE UL UNDERWRITERS LIBRATORY A000 08 16 2013: 99% Complete - Issued for Client Review
CLG CEILING F FAHRENHEIT HB HOSE BIB NLT NAIL LAMINATED TIMBER SCREW UNFIN UNFINISHED GLAZING 07 30 2013: 95% Coordination
B TYPE
CJ CONTROL JOINT FA FIRE ALARM HC HANDICAPPED NO NUMBER RHWS ROUND HEAD WOOD SCREW UNO UNLESS OTHERWISE NOTED 05 14 2013: Issued to Consultants
CLR CLEAR FAB FABRICATE(D) HDO HIGH DENSITY OVERLAY NOM NOMINAL RWL RAIN WATER LEADER VAC VACUUM
CMP CORRUGATED METAL PIPE FD FLOOR DRAIN HDWD HARDWOOD NR NON-RATED RM ROOM VAR VARIES 0 DATE ISSUE
DETAILS
CMU CONCRETE MASONRY UNIT FDC FIRE DEPARTMENT CONNECTION HDWR HARDWARE NTS NOT TO SCALE RND ROUND VERT VERTICAL A000
CP CEMENT PANEL FDN FOUNDATION HM HOLLOW METAL O/A OUTSIDE AIR RO ROUGH OPENING VB VAPOR BARRIER D 100 A DOORS
CO CLEAN OUT FE FIRE EXTINGUISHER HORIZ HORIZONTAL OC ON CENTER RTR RUBBER TREAD & RISER VP VAPOR PROOF
ESC
COL COLUMN FEC FIRE EXTINGUISHER CABINET HR HOUR OFCI OWNER FURNISHED-CONTRACTOR S SOUTH VTR VENT THROUGH ROOF
COMM COMMUNICATION FF FACTORY FINISHED HT/H HEIGHT INSTALLED S/A SUPPLY AIR W WEST / WIDTH
MW 100
100.1 MILLWORK 0 EXTERIOR
CONC CONCRETE FG FIBERGLASS HTG HEATING OFOI OWNER FURNISHED-OWNER INSTALLED SC SOLID CORE W/ WITH
CONST CONSTRUCTION FHC FIRE HOSE CABINET IBC INTERNATIONAL BUILDING OH OVERHEAD SCHED SCHEDULE W/O WITHOUT A000 ELEVATIONS
CONT CONTINUOUS FHWS FLAT HEAD WOOD SCREW CODE OPP OPPOSITE SCW SOLID CORE WOOD WD WOOD
CONTR CONTRACT(OR) FHMS FLAT HEAD MACHINE SCREW IN INCH OPNG OPENING SD STORM DRAIN/SOAP WDO WINDOW UBC ENGINEERING
1
CONV CONVECTOR FIG FIGURE ID INSIDE DIAMETER ORD OVERFLOW ROOF DRAIN DISPENSER WF WIDE FLANGE PROJECT
NORTH STUDENT CENTRE
COORD COORDINATE FIN FINISH INSUL INSULATION ORIG ORIGINAL SECT SECTION WR WASTE RECEPTACLE
NORTH
CSK COUNTERSINK FIN GR FINISH GRADE IHM INSULATED HOLLOW METAL PBD PARTICLE BOARD SF SQUARE FOOT / FEET WP WATERPROOF
4 A000 2 INTERIOR ELEVATIONS
CSMT CASEMENT FIN FLR FINISH FLOOR INT INTERIOR PER PERFORATED SHT SHEET WT WEIGHT REFERENCE
CT CERAMIC TILE FL FLASHING INV INVERT PL PLATE / PLASTIC LAMINATE SHTHG SHEATHING WWF WELDED WIRE FABRIC NORTH
CTR CENTER(ED) FLR FLOOR JT JOINT PLAM PLASTIC LAMINATE SIM SIMILAR XPS EXTRUDED POLYSTYRENE 3
CU
CUH
CUBIC
CABINET UNIT HEATER
FLRG
FOC
FLOORING
FACE OF CONCRETE
JST
KD
JOIST
KNOCK DOWN
PLYWD PLYWOOD
PNL PANEL
SLR
SND
SEALER
SANITARY NAPKIN DISPENSER
GENERAL NOTES,
C/W COMPLETE WITH FOF FACE OF FINISH KPL KICK PLATE PR PAIR SNR
SPEC
SANITARY NAPKIN RECEPTOR
SPECIFICATION(S)
KEY PLAN, LEGEND,
ABBREVIATIONS
A.002
FIRE ACCESS
EXIT
133
SEAL:
5 1
1 2
EXIT
EXIT 178
385
NOTES:
CODE ANALYSIS
62 This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
without written permission of this office.
ITEM BRITISH COLUMBIA 2012 BUILDING CODE BCBC REFERENCE NOTES The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
17 37 23
2 MAJOR OCCUPANCY
Group A, Division 2 "Assembly Occupancy"
17 WC REQUIREMENTS
1 universal, 3 male, 5 female
24
18 BARRIER FREE conform to 3.8
24.4m
LEGEND
SECOND FLOOR PLAN
03 25 2014: Issued for Construction
11 19 2013: Issued for Tender and B.P.
10 18 2013: 100% Complete - Issued for Client Review
X.XXm TRAVEL DISTANCE IN METERS (BCBC 2.4.25) 12 13 08 16 2013: 99% Complete - Issued for Client Review
07 30 2013: 95% Coordination
05 14 2013: Issued to Consultants
EXIT LOCATION AND EXIT CAPACITY IN 9 9 19 DATE ISSUE
EXIT
PERSONS (BCBC 3.4.3.2)
XX
3 1 5
1 HR FRR
3/4 HR FRR
ESC
UBC ENGINEERING
0 HR FRR STUDENT CENTRE
A.003
SECOND FLOOR PLAN
TYP. U/S OF CEILING
2490mm
NOTE: MINIMUM CLEARANCE
NOTE: ALIGN GRAB BAR SPACE INDICATED IN GREY
BEND WITH FRONT EDGE NOTE: FAUCETS TO BE OPERATED
OF TOILET SHOWER
HEAD AUTOMATICALLY
MIRROR NOTE: INSTALL P-TRAPS TIGHT
T/O WC PARTITIONS
AGAINST WALL
1778mm GRAB BARS SEE 10/A.803
H.C. ONLY
CL CL SOAP
COAT HOOK 200
DISPENSER
CL PAPER TOWEL 401 - 134 Abbott Street
CL
MAX. TO USER FUNCTIONS DISP. Vancouver, BC
2044
1100mm CL 900 Canada V6B 2K4
120
45
300 300
t: 604-683-5060
1200 MAXIMUM
GRAB BAR DYSON
1100 MAXIMUM
NAPKIN DISPOSAL e: info@urban-arts.ca
AIRBLADE
962 MAXIMUM
WOMEN'S ONLY 450
1315
1200
FOLDING SEAT DRYER
1100 MAX.
1050
1000
T/O TOILET FIXTURES - 480mm SEAL:
860
840
840
780
765
U/S WC PARTITIONS
660
500
480
475
305mm
TOILET PAPER 380 MAX.
250
DISPENSER
T/O F.F.
0mm 750
465 465 460 250 250
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
without written permission of this office.
The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
1175
FIRE ALARM
STROBE LIGHT
FIRE
ELEVATOR CONTROLS EXTINGUISHER
CABINET DOOR TO COAT HOOKS
CABINET
EXTEND 38mm BELOW LIGHT SWITCH
CABINET TO COVER ACCESSIBLE
LIGHT FIXTURE FIRE PULL
U/S CABINET COAT HOOKS
1365mm THERMOSTAT
2490
FIRE
635
635
CO2 CONTROLS
T/O COUNTER
1570 MAX.
1520 MAX.
38
38
915mm
RECEPTACLE
1219 MAX.
38
1220
VOICE/DATA
774
915
356
T/O KICK
102
KITCHEN
NOTES:
SEE INTERIOR ELEVATIONS FOR VINYL GRAPHICS AND THEIR LOCATIONS
T/O DOOR FRAME
2490mm NOTES:
2mm THICK
118
FACEPLATE 1. FIX PANELS TO WALL WITH DOUBLE SIDED TAPE, SET
10MM IN FROM ALL EDGES.
2. SIGN TO BE LOCATED CENTRED 1350MM A.F.F.
MAXIMUM OF 150MM FROM EDGE OF SIGN TO LATCH
50
50
ROOM SIGNAGE, TYP. ROOM SIGNAGE ON SIGN OF DOOR.
- SEE DETAIL GLAZING TYP. 32mm HIGH 3. IF CANNOT BE MOUNTED IN THE ABOVE POSITION
ADHERE TO GLASS 1mm THICK, LOCATE ON NEAREST PARALLEL WALL LOCATION.
MAX 150 MAX 150 C/W SINTRA BACK VERTICALLY 4. AT DOUBLE DOORS LOCATE TO RIGHT OF DOORS.
PANEL CENTERED
TACTILE TACTILE LETTERING
LETTERING
1MM THICK SINGLE PLY NON-GLARE MATT ADA
ROWMARK, ALTNERATE APPLIQUE, WHITE
TYPEFACE
LOUNGE
13mm HIGH
1350
1350
50
50
VERTICALLY
CENTERED
TACTILE
LETTERING
T/O F.F.
0mm
BACK PANEL
3mm WHITE, SINTRA,
3mm THICK
SIGNAGE MOUNTING HEIGHT BACKING PLATE
50
50
03 25 2014: Issued for Construction
LETTERING APPLIQUE ON
11 19 2013: Issued for Tender and B.P.
2mm FACEPLATE
TYPICAL DOOR SIGNAGE AND MOUNTING HEIGHT 10 18 2013: 100% Complete - Issued for Client Review
3 Scale 1:25
MATTE FINISH, BLACK, ADA
ROWMARK, ALTERNATIVE
08 16 2013: 99% Complete - Issued for Client Review
07 30 2013: 95% Coordination
SUBSTRATE
05 14 2013: Issued to Consultants
DATE ISSUE
GRADE 2 BRAILLE
25
25
NUMBER, LETTER
HEIGHT 9.5mm
THICKNESS 1.5mm
A.004
EXTERIOR WALL ASSEMBLIES: INTERIOR WALL ASSEMBLIES: FLOOR ASSEMBLIES: ROOF ASSEMBLIES:
F1
172
185
62
GL FF R1
89
76
169
25
114-229
P1 TYPICAL INTERIOR WALL
51
102
GL
16mm GWB both sides (painted) over
38 x 140mm wood studs @ 400mm o.c. U.N.O. by Structural
169
100
W1D TYPICAL EXTERIOR FRAME WALL ASSEMBLY WITH CFIP (c/w thermal batt insulation sized to fill cavity where noted on plan)
(Effective R-28) 401 - 134 Abbott Street
153
NOTES:
Vancouver, BC
51mm concrete-faced insulated panel (R-7) on Canada V6B 2K4
Air / moisture barrier over 1. Plywood sheathing behind GWB where noted at shear wall locations.
W1A TYPICAL EXTERIOR FRAME WALL ASSEMBLY W/ BRICK VENEER t: 604-683-5060
13mm plywood sheathing on See Structural Drawings.
(Effective R-25.5)
38 x 140 wood studs @ 400mm o.c. c/w 2. Provide plywood backing or blocking behind all accessories and e: info@urban-arts.ca
139mm thermal batt Insulation (R-21) with wall-mounted elements.
White concrete brick on
25mm airspace on Vapour retarder with R1 LOW SLOPE MEMBRANE ROOF ASSEMBLY, INSULATED (R-30.4 AVG.) SEAL:
51mm semi-rigid mineral wool insulation (R-7.6) on 16mm GWB, painted (Type X where noted as 3/4 HR FRR in Code Report)
Air / moisture barrier on
NOTES: F1 GROUND FLOOR - CONCRETE TOPPING ON SLAB ON GRADE (R-20) 2-ply SBS roofing membrane on
13mm plywood sheathing on
38 x 140 wood studs @ 400mm o.c. c/w 1. Provide ULC listed fire stopping at floor/roof connections and penetrations as Protection board, adhered, on
required to maintain 3/4 HR FRR from interior where indicated in Code Diagram 76mm concrete topping c/w 51mm roof insulation (R-11.4), adhered, on
139mm thermal batt insulation (R-24) on
Vapour retarder on and Code Report. Radiant in-floor system where indicated by Mechanical c/w 2 64-178mm tapered insulation (min. R-7 to R-28; avg. over occupied areas
2. Located within 200mm of grade and at exterior ground floor deck & roof deck. Reinforcing mesh (see Structural Drawings) on R-16.6), mechanically fastened, sloped min.1:50 to drain on
16mm GWB, painted (Type X where noted as 3/4 HR FRR in Code Report)
172
185
102mm XPS insulation (R-20) over Self-adhesive vapour retarder on
100mm reinforced concrete slab-on-grade (see Structural Drawings) over 13mm plywood (primed) on
NOTES:
Vapour retarder over 140mm NLT solid wood roof (see Structural Drawings), clear fin. at u/s ceiling
1. See Architectural Drawings for furred out finish areas
150mm compacted granular fill as per Geotechnical report
2. Masonry veneer supported on steel angles on standoffs.
3. Provide ULC listed fire stopping at floor/roof connections and penetrations as ALIGN WITH FACE OF BRICK AT ASSEMBLY W1A ADJACENT P2A 0-HR FRR (SMOKE SEPARATION) INTERIOR WALL NOTES:
required to maintain 3/4 HR FRR from interior where indicated in Code Diagram
NOTES: 1. No FRR required at unoccupied roof areas.
and Code Report.
89
16mm GWB both sides (painted) over 1. Slab sloped to drain minimum 1% at all floors with drains, including but not
38 x 140mm wood studs @ 400mm o.c. U.N.O. by Structural limited to Washrooms, Servery, Bar, and Janitor's Room.
(c/w thermal batt insulation sized to fill cavity where noted on plan) NOTES:
76
GL This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
NOTES: their name. All designs and all other information shown on this drawing
1. Mud or seal all penetrations and interfaces with floor and underside of
51
200
are for use on the specified project only and shall not be used otherwise
GL roof/floor decking to provide smoke-tight separation. without written permission of this office.
2. Plywood sheathing behind GWB where noted at shear wall locations. R2
The Contractor shall check and verify all dimensions and report any
See Structural Drawings.
169
51
wall-mounted elements. Do not scale drawings.
114-229 varies
W2A TYPICAL EXTERIOR CONCRETE WALL ASSEMBLY W/BRICK VENEER F2
(Uninsulated) FF
W1B TYPICAL EXTERIOR FRAME WALL ASSEMBLY WITH EIFS
White concrete brick on
(Effective R-28)
76mm airspace on
200mm poured-in-place reinforced concrete
172
Exterior Insulated Finish System (EIFS) w/ 51mm EPS insulation (R-7.6) on
260
185
2 Air / moisture barrier on
NOTES:
13mm plywood sheathing on
1. Masonry veneer supported at base and headers by steel angles with knife
38 x 140 wood studs @ 400mm o.c. c/w
plates to reduce thermal bridging.
139mm thermal batt insulation (R-24) on
2. Refer to Specifications for exposed concrete finish standard.
Vapour retarder on P2B 3/4-HR FRR INTERIOR WALL
3. Provide ULC listed fire stopping penetrations as required to maintain 3/4 HR
347
16mm GWB, painted (Type X where noted as 3/4 HR FRR in Code Report) ULC Design W301 - 1 hour fire-resistance rated assembly
FRR from interior where indicated in Code Diagram and Code Report.
F2 45-min. FRR SECOND FLOOR - NLT
NOTES: 16mm Type 'X' fire-rated GWB both sides (painted) over
1. Provide ULC listed fire stopping at floor/roof connections and penetrations as 38 x 140mm wood studs @ 400mm o.c. U.N.O. by Structural with Finish flooring on
required to maintain 3/4 HR FRR from interior where indicated in Code Diagram FIRESTOP SPRINKLER AND (c/w thermal batt insulation sized to fill cavity where noted on plan) 38mm concrete topping c/w
and Code Report. OTHER PENETRATIONS AT
RATED EXTERIOR WALLS, TYP. Radiant in-floor system c/w
Reinforcing mesh (see Structural Drawings) on
NOTES: Vapour retarder on R2 45-min. FRR LOW SLOPE (FLAT) MEMBRANE ROOF FRAME
1. Rating to extend from top of floor to underside of roof/floor decking. 25mm rigid insulation (R-5) on ASSEMBLY, INSULATED (R-28)
102
2. Plywood sheathing behind GWB where noted at shear wall locations. 13mm plywood on Ceiling Membrane Rating based on Assembly Number M2 (1hr FRR) per
See Structural Drawings. 184mm NLT Solid Wood Floor (see Structural Drawings), clear finish at u/s BCBC Table A-9.10.3.1.B, as permitted by 3.1.7.1.4).
GL 3. Provide plywood backing or blocking behind all accessories and Ceiling finish as noted
wall-mounted elements. 51mm thick 600mm sq. concrete pavers on
2 Adjustable pedestals on
1
200
NOTES: 2-ply SBS roofing membrane on
1. 45-min. FRR provided through Heavy Timber. Protection board, adhered, on
2. Provide fire-rated firestop at penetrations as required. 51mm roof insulation (R-11.4), adhered, on
64-178mm tapered insulation (min. R-7 to R-28; avg. over occupied areas
105 R-16.6), mechanically fastened, sloped min.1:50 to drain on
172
185
Self-adhesive vapour retarder on
13mm plywood (primed) on
11-7/8" TJIs @ 400 mm o.c. (see Structural Drawings) on
W2B TYPICAL EXTERIOR CONCRETE WALL ASSEMBLY WITH EIFS 2 layers 16mm fire-rated Type 'X' GWB (painted)
(Effective R-28) P2C 1-HR FRR INTERIOR WALL
ULC Design W301 - 1 hour fire-resistance rated assembly NOTES:
51
63
16mm GWB (painted)
NOTES: R3
NOTES: 1. Rating to extend from top of floor to underside of roof/floor decking.
1. See Architectural Drawings for furred out finish areas 2. Plywood sheathing behind GWB where noted at shear wall locations.
2. Coordinate with Structural for coring locations as required for sprinklers, etc. See Structural Drawings.
5. Provide ULC listed fire stopping penetrations as required to maintain 3/4 HR
114-229
3. Provide plywood backing or blocking behind all accessories and
W1B2 1-HR FRR EXTERIOR ELEVATOR SHAFT WALL ASSEMBLY WITH EIFS FRR from interior where indicated in Code Diagram and Code Report.
347
wall-mounted elements.
(Efective R-28 min.)
W2B-NC NON COMBUSTIBLE EXTERIOR CONCRETE WALL ASSEMBLY
ULC Design W301 - 1 hour fire-resistance rated assembly WITH EIFS, (Effective R-28)
2
Exterior Insulated Finish System (EIFS) w/ 51mm EPS insulation (R-7.6) on
153
Similar to above, replace 102mm EPS insulation w/ 102 non combustible rigid
Air / moisture barrier on mineral fibre insulation (R-15.2)
16mm Type 'X' fire-rated exterior gypsum sheathing on
200
13mm plywood sheathing on F3 45-min. FRR SECOND FLOOR - TJI FRAMING
16
38 x 184 wood studs @ 400mm o.c. c/w Ceiling Membrane Rating based on Assembly Number M2 (1hr FRR)
178mm thermal batt insulation (R-28) on per BCBC Table A-9.10.3.1.B, as permitted by 3.1.7.1.4).
13mm plywood sheathing on R3 LOW SLOPE (FLAT) MEMBRANE ROOF FRAME ASSEMBLY,
Vapour retarder on INSULATED (AVERAGE R-28), UNRATED
105
Finish flooring on
16mm Type 'X' fire-rated GWB (painted) 38mm concrete topping c/w 2-ply SBS roofing membrane on
Radiant in-floor system on Protection board, adhered, on
200
NOTES: Reinforcing mesh (see Structural Drawings) on 51mm roof insulation (R-11.4), adhered, on
1. Provide ULC listed fire stopping at floor/roof connections and penetrations as P3 CONCRETE WALLS + FURRING Vapour retarder on 2 64-178mm tapered insulation (min. R-7 to R-28; avg. over occupied areas
required to maintain 1 HR FRR from interior where indicated in Code Diagram 25mm rigid insulation (R-5) on
and Code Report. R-16.6), mechanically fastened, sloped min.1:50 to drain on
16mm GWB finish (painted) over 13mm 48/24 T+G span-rated plywood sheathing (Exposure 1) on Self-adhesive vapour retarder on
38 x 13mm wood furring @ 400mm O.C. with 11-7/8" TJIs @ 400 mm o.c. (see Structural Drawings) on 13mm plywood (primed) on
W3 EXTERIOR CONCRETE WALL 76mm rigid insulation over 2 layers 16mm fire-rated Type 'X' GWB (painted) 38 x 140mm wood studs @ 400 mm o.c., (see Structural Drawings) on
200mm poured in place concrete
16mm GWB (painted)
200mm poured-in-place reinforced concrete, sandblasted
NOTES:
NOTES: NOTES: 1. 45-min. FRR required at occupied 2nd Floor. NOTES:
1. See Structural Drawings 1. See Structural Drawings 2. See Mechanical for radiant floor system. 1. No FRR required at unoccupied roof areas.
2. Refer to Specifications for exposed concrete finish standard. 2. Refer to Specifications for exposed concrete finish standard.
1. Provide sealant at top of all walls between vapour retarder and wood
decking.
GL
2. Provide fire-rated caulking at termination of all fire-rated membranes 03 25 2014: Issued for Construction
±300-400
between concrete or wood structure and fire-rated GWB. 2 03 24 2014: Issued for Value Engineering
169
300-400 +/-
req'd
W1C TYPICAL EXTERIOR FRAME WALL ASSEMBLY WITH METAL PANEL
as
marking, angles, clips, or fasteners so they are not visible from the interior. 05 14 2013: Issued to Consultants
SYSTEM (Effective R-28)
Refer to Reflected Ceiling Plans for exposed areas.
46
44
DATE ISSUE
38mm Aluminum Panel System on
25mm vertical track (included in AP System) on 5. Conceal all conduit and piping within concrete walls, wood-framed walls, or
C3 ACOUSTIC CEILING SUSPENDED IN T-BAR CEILING GRID SYSTEM S1 EXTERIOR WOOD SOFFIT non-visible side of NLT panels, including at top of roof deck for conduits
300-400 +/-
ESC
Air / moisture barrier on
13mm plywood sheathing on 16mm Acoustic ceiling tiles on 25mm resilient channels (spacing as required) on
38 x 140 wood studs @ 400mm o.c. c/w 46mm suspension system with integrated electrical conductors on 38 x 140mm wood framing as required on 6. NLT panels are to be oriented as required to meet structural requirements
139mm thermal batt Insulation (R-24) on underside of Floor / Roof assembly 150mm airspace maximum on and facilitate constructibility.
Vapour retarder on Rigid insulation (R-20 min.) on
16mm GWB, painted (Type X where noted as 3/4 HR FRR in Code Report) NOTES: Air / moisture barrier on underside of 7. Refer to Structural Drawings for all shear wall locations.
UBC ENGINEERING
58
A.005
2
2
365
127
± 3150 AFF
MECH PANEL OR
127
750
750
METAL PANEL W/ MECH PANEL
127 LIGHT FIXTURE
± 2440 AFF ± 2440 AFF ± 2440 AFF 1'-2"
127
127
± 2135 AFF ± 2135 AFF ± 2135 AFF ± 2135 AFF
127
3740
DOOR PANEL
ROUTED W/ FLUSH
SOUND SOAK INLAY
305
305
T T
610
610
Canada V6B 2K4
t: 604-683-5060
W
305
305
305
e: info@urban-arts.ca
260
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
PS.A PS.B PS.C PS.D PS.E SF.A SF.B SF.C SF.D SF.E SF.F
A1 W1 W2 W3 W4 M1 M2, M3
SEAL:
STOREFRONT DOOR FRAME SCHEDULE
PRESSED STEEL DOOR FRAME SCHEDULE
3 SCALE 1:50
DOOR TYPES 2
1 SCALE 1:50 SCALE 1:50
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
ESC UBC ENGINEERING STUDENT CENTRE December 09, 2013
DOOR SCHEDULE are for use on the specified project only and shall not be used otherwise
Issued for Addendum without written permission of this office.
DOOR FRAME GLASS HARDWARE REMARKS
The Contractor shall check and verify all dimensions and report any
FIRE RATING
DOOR TYPE
THICKNESS
UNDERCUT
REQUIRED
(INCHES)
(HOURS)
DOOR #
Hollow Metal
ROOM NAME DOOR SIZE (MM) SC WOOD
PRSD STEEL
FRAME TYP
TEMPERED.
TRANSOM
GROUP Do not scale drawings.
SIDELITE
WOOD
FINISH
FINISH
ALUM:
FROM
ALUM
STD.
TO
D100 A ENTRY 2 - 1220 x 3050 100 EXT 1 3/4" A1 X CA CW X CA X X E-AL-10 Insulated Door and Frame, card reader
D101 A COMMONS 1070 x 2440 101 EXT 1 3/4" A1 X CA CW X CA X X E-AL-01 Insulated Door and Frame
D101 B COMMONS 2-1070 x 2440 101 EXT 1 3/4" A1 X CA CW X CA X X AL-10 Insulated Door and Frame
D101 C COMMONS 2-1070 x 2440 101 EXT 1 3/4" A1 X CA CW X CA X X AL-10 Insulated Door and Frame
1 D102 A FIRST YEAR 915 x 2440 100 102 1 3/4" W4 X PT SF (B) X CA X X OF-01 Tempered safety glass at sidelite, std. at porthole, Rough-in for card reader
D102 B FIRST YEAR 915 x 2440 102 ELEV 1 3/4" 3/4 M3 X PT PS2 (B) X PT SR-01 Elevator Door, self closing and locking, disconnect mounting panel
D103 A FLEX ROOM 915 x 2440 100 103 1 3/4" W4 X PT SF (A) X CA X PA-01
D103 B FLEX ROOM 2- 2180 x 3300 103 101 2 1/2" W1 X PT SL-01 Recessed ceiling track / floor guide, acoustic panel 1 side
D103 C FLEX ROOM 2200 x 3300 103 101 2 1/2" W1 X PT SL-01 Recessed ceiling track / floor guide, acoustic panel 1 side
D103 D FLEX ROOM 2- 1070 x 2440 103 EXT 1 3/4" A1 X CA CW X CA X X X AL-10 Insulated Door and Frame
D103 E FLEX ROOM 915 x 2440 103 EXT 1 3/4" A1 X CA CW X CA X X X AL-02 Insulated Door and Frame
D105 A STORAGE 1067 x 2440 101 105 1 3/4" M2 X PT PS1 (B) X PT SR-02
D106 A STORAGE 2-1125 x 2440 106 EXT 1 3/4" M2 X PT PS1 (C) X PT SR-10 Insulated Door and Frame not required
1 2 D107 A GARBAGE 1067 x 3290 EXT 107 1 3/4" M3 X PT PS1 (E) X PT SR-03 Insulated Door and Frame, Wall has 3/4 FRR
D107 B GARBAGE 915 x 2440 122 107 1 3/4" 3/4 M3 X PT PS2 (B) X PT X PA-02
1 2 D108 A MECHANICAL 1067 x 3290 108 EXT 1 3/4" M3 X PT PS1 (A) X PT X X SR-04 Firelite at rated door, Insulated Door and Frame, wall has 3/4 HR FRR
D109 A JANITOR 915 x 2440 122 109 1 3/4" M2 X PT PS1 (B) X PT SR-03
1 2 D110 A HALL 915 x 3290 110 EXT 1 3/4" M3 X PT PS1 (A) X PT X EX-01 Firelite at rated door, Insulated Door and Frame, wall has 3/4 HR FRR
D111 A ELECTRICAL 915 x 2440 110 111 1 3/4" 0 M1 X PT PS1 (B) X PT X SR-03
1 D112 A DRY STORAGE 915 x 2440 110 112 1 3/4" M1 X PT PS1 (B) X PT X SR-05 Rough-in for card reader
D113 A COMMUNICATIONS 915 x 2440 111 113 1 3/4" M1 X PT PS1 (B) X PT SR-03
D116 A MEN 915 x 2440 123 116 1 3/4" W3 X PL PS1 (B) X PT WR-01 P.Lam both sides of door
D117 A MEN'S SHOWER 915 x 2440 116 117 1 3/4" X M1 X PT PS1 (B) X PT X WR-02 Obscure Glass
D118 A LOUNGE 915 x 2440 123 118 1 3/4" W3 X PL PS1 (B) X PT WR-01 P.Lam both sides of door
D120 A WOMEN'S SHOWER 915 x 2440 119 120 1 3/4" X M1 X PT PS1 (B) X PT X WR-02 Obscure Glass
D121 A RED SALES 915 x 2440 100 121 1 3/4" W2 X PT SF (B) X CA X X CL-01 Alum SF system, single glazed, sidelite
D121 B RED SALES 915 x 2440 121 122 1 3/4" W2 X PT PS1 (B) X CA SR-05
D201 A DIGITAL 915 x 2135 200 201 1 3/4" W2 X PT SF (C) X CA X X OF-02 Alum SF system, single glazed, sidelite
D202 B DIGITAL 915 x 2135 201 202 1 3/4" X M2 X PT PS1 (D) X PT SR-07 Ian to confirm
D203 A ROOF ACCESS 915 x 2135 200A 203 1 3/4" W3 X PL PS1 (D) X PT SR-06 P.Lam both sides of door
D204 A WC 915 x 2135 200A 204 1 3/4" X W3 X PL PS1 (D) X PT WR-03 P.Lam both sides of door
1 D206 A VICE PRESIDENTS 915 x 2135 205 206 1 3/4" W2 X PT SF (D) X CA X X OF-02 Alum SF system, single glazed, sidelite ,Rough-in for card reader
D207 A PRESIDENT 915 x 2135 205 207 1 3/4" W2 X PT SF (D) X CA X X OF-02 Alum SF system, single glazed, sidelite
D208 A SOCIETY 915 x 2135 205 208 1 3/4" W2 X PT SF (D) X CA X X OF-02 Alum SF system, single glazed, sidelite
D209 A GROUP STUDY 915 x 2135 200A 209 1 3/4" W2 X PT SF (C) X CA X X OF-02 Alum SF system, single glazed, sidelite
D210 A GROUP STUDY 915 x 2135 200A 210 1 3/4" W2 X PT SF (C) X CA X X OF-02 Alum SF system, single glazed, sidelite
D211 A PRINT SHOP 915 x 2135 200A 211 1 3/4" W2 X PT SF (C) X CA X X X OF-02 Alum SF system, single glazed, sidelite
D212 A ARCHIVE 915 x 2135 211 212 1 3/4" W2 X PT PS1 (B) X PT SR-06 Alum SF system, single glazed, sidelite
DATE ISSUE
ESC
UBC ENGINEERING
STUDENT CENTRE
DOOR SCHEDULE
A.006
EL 94.00
CW 200 CW 215-1
2540
EQ EQ
2270
e: info@urban-arts.ca
SEAL:
1360
T/O SECOND FLOOR SLAB 5615 4255 1500 1000 1500 1500 1500 1500 1500 1500 1500 1500 1550 1590
EL 98.00
EQ EQ 1140 455 1045 1045 455 585
EQ EQ EQ 585 585
200
+/- 3050 AFF BRAKE FORM ALUM
D-100A This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
D-101C D-101B D-101C D 103-D D 103-E their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
A A A without written permission of this office.
+/- 760 AFF
The Contractor shall check and verify all dimensions and report any
CW 102-1 CW 102-2 discrepancies before proceeding.
CW 103-1
T/O GROUND FLOOR SLAB Do not scale drawings.
EL 94.00
CW 100-1 CW 101-1 CW 101-2 CW 103-2
BREAK FORM ALUM. CORNER BREAK FORM ALUM. CORNER BREAK FORM ALUM. CORNER
T/O SECOND FLOOR SLAB 1315 1500 1500 1500 1500 1500 1630 1250 1500 1500
EL 98.00 BREAK FORM ALUM. 2115 2660
585
585 585 2190 1680 1390 1390 EQ EQ
625
OBSCURE GLASS OBSCURE GLASS
+/- 2440 AFF +/- 2440 AFF
CW 116 CW 118
A A A
+/- 760 AFF +/- 760 AFF
CW 121-1 CW 121-2
CW 104-1 CW 104-2
T/O GROUND FLOOR SLAB FINISHED FLOOR
EL 94.00
CW 103-2 CW 100-1
D218A
A A A A A
+/- 760 AFF
2540
03 25 2014: Issued for Construction
2 03 24 2014: Issued for Value Engineering
1 12 03 2013: Issued for Addendum #2
11 19 2013: Issued for Tender and B.P.
T/O SECOND FLOOR SLAB 10 18 2013: 100% Complete - Issued for Client Review
EL 98.00 1500 1500 600 975 13000 08 16 2013: 99% Complete - Issued for Client Review
07 30 2013: 95% Coordination
585 585 1705 955 1500 1570 1575 1500 1500 1500 1195 05 14 2013: Issued to Consultants
GENERAL NOTES:
585 585 585
+/- 2940 AFF +/- 2940 AFF DATE ISSUE
1. REFER TO PLAN TO CONFIRM DOOR SWING.
3.
OPERATION.
WINDOW SCHEDULE
SECOND FLOOR CURTAIN WALLS
2 Scale 1:50
A.007
ENGINEERING STUDENT CENTRE 2013 11 19 ENGINEERING STUDENT CENTRE 2013 11 19
FINISH SCHEDULE Issued for BP and Tender Issued for BP and Tender
FINISH SCHEDULE
Room # Room Name Floor Base Walls Ceiling NOTES Room # Room Name Floor Base Walls Ceiling NOTES
GROUND FLOOR N E S W Material
SECOND FLOOR N E S W Material
100 ENTRY SPCS B1 GWB, PT GWB, PT --- GWB, PT Open to above Floor Mat NIC
Glazing Glazing NLT, CF+GWB, PT Doner Panel West Elev., NIC
101 COMMONS SPCS B1 AWP Glazing GWB, PT Open to above, NLT, CF AWP's from 2440 mm AFF to underside of sill @ 2nd floor glazing
200 WAITING RF B1 GWB, PT Guard rail Guard rail '--- NLT, CF No Base at Guard Rail 401 - 134 Abbott Street
--- GWB, PT WD Soffit, Stain Fin 200A HALL RF B1 GWB, PT Guard rail Truss (top chord) GWB, PT NLT, CF No Base at Guard Rail Vancouver, BC
102 FIRST YEAR SPCS B1 GWB, PT GWB, PT PWC, TB GWB, PT WD Soffit, Stain Fin See Elev for MDF Vent Panel and Trickle Vent Panel Truss Canada V6B 2K4
Glazing Glazing GWB, PT GWB, PT 201 DIGITAL CPT B1 GWB, PT GWB, PT GWB, PT GWB, PT ACT See Elev for MDF Vent Panel and Trickle Vent Panel t: 604-683-5060
103 FLEX ROOM SPCS B1 PWC GWB, PT GWB, PT Glazing WD Soffit, Stain Fin See Elev for MDF Vent Panel and Trickle Vent Panel PWC e: info@urban-arts.ca
GWB, PT Glazing GWB, PT NLT, CF 202 ELEC. CLOSET RF B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT
104 COMMONS ANNEX SPCS B1 GWB, PT --- Glazing GWB, PT WD Soffit, Stain Fin See Elev for MDF Vent Panel and Trickle Vent Panel
SEAL:
GWB, PT Glazing NLT, CF 203 ROOF ACCESS RF B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT
105 INT. STORAGE SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT
204 UNISEX W/C RF B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT
106 EXT. STORAGE Conc Slab --- CONC CONC CONC EXT GWB, PT CONC
107 GARBAGE SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT Plastic Laminate Panel to 1220 mm AFF 205 MUTLI-PURPOSE RF B1 GWB, PT --- GWB, PT GWB, PT ACT Back painted glass backsplash North elev.
PLP PLP PLP PLP PWC Glazing
108 MECHANICAL SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT Plywood Backing where required for mech equipment 206 VICE PRESIDENTS CPT B1 GWB, PT GWB, PT GWB, PT GWB, PT ACT See Elev for MDF Vent Panel and Trickle Vent Panel
Glazing, TB Glazing NLT, CF
109 JANITOR SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT Stainless steel splash panel at Janitor sink 207 PRESIDENT CPT B1 GWB, PT Glazing GWB, PT Glazing ACT See Elev for MDF Vent Panel and Trickle Vent Panel
PLP PLP PLP PLP Plastic Laminate Panel to 1220 mm AFF TB GWB, PT GWB, PT NLT, CF
110 HALL SPCS B1 GWB, PT Glazing GWB, PT --- GWB, PT 208 SOCIETY CPT B1 GWB, PT Glazing GWB, PT Glazing ACT See Elev for MDF Vent Panel and Trickle Vent Panel
PLAM Soffit TB GWB, PT PWC GWB, PT NLT, CF
111 ELECTRICAL SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT 209 GROUP STUDY CPT B1 GWB, PT GWB, PT GWB, PT Glazing ACT See Elev for MDF Vent Panel and Trickle Vent Panel
P.P P.P P.P P.P Plywood panels, painted finish to 2440 mm AFF
Glazing PWC GWB, PT NLT, CF
112 DRY STORAGE SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT Plywood Backing to 2440mm AFF NOTES:
210 GROUP STUDY CPT B1 GWB, PT GWB, PT GWB, PT Glazing ACT See Elev for MDF Vent Panel and Trickle Vent Panel
113 COMMUNICATIONS SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT PWC Glazing GWB, PT NLT, CF This drawing is the property of Urban Arts Architecture and may not be
P.P P.P P.P P.P Plywood panels, painted finish to 2440 mm AFF 211 PRINT ROOM RF B1 GWB, PT GWB, PT GWB, PT GWB, PT ACT See Elev for MDF Vent Panel reproduced without their permission and unless the reproduction carries
2 their name. All designs and all other information shown on this drawing
114 BAR SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT PLAM Soffit Bulkhead at 2490mm, Back painted glass backsplash Glazing TB are for use on the specified project only and shall not be used otherwise
BPG GWB, PT See Elevation for Vinyl Graphic 212 ARCHIVE RF B1 GWB, PT GWB, PT GWB, PT GWB, PT ACT without written permission of this office.
115 SERVERY SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT PLAM Soffit Bulkhead at 2490mm, Back painted glass backsplash 2 Plywood Backing to 2440mm AFF
The Contractor shall check and verify all dimensions and report any
BPG BPG GWB, PT See Elevation for Vinyl Graphic 213 CONFERENCE/STUDY CPT B1 GWB, PT GWB, PT GWB, PT GWB, PT ACT See Elev for MDF Vent Panel and Trickle Vent Panel discrepancies before proceeding.
116 MEN'S W/C SPCS B2 TILE 2 GWB, PT GWB, PT GWB, PT, TILE 2GWB, PT GWB, PT Truss Glazing Truss PWC NLT, CF PWC on 12 mm MDF, Align with ACT dropped ceiling
TILE 2 MIRROR TILE 2 Do not scale drawings.
214 STUDY RF B1 Truss + GWB, PT Truss, GWB, PT GWB, PT ACT See Elev for Trickle Vent Panel
117 MEN'S SHOWER TILE 1 B2 TILE 2 TILE 2 TILE 2 TILE 2 TILE 2 GWB, PT Glazing Glazing PWC NLT, CF
215 STUDY LOUNGE RF B1 GWB, PT GWB, PT GWB, PT GWB, PT ACT See Elev for Trickle Vent Panel
118 LOUNGE SPCS B2 TILE 2 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT
Glazing PWC NLT, CF
MIRROR
119 WOMEN'S W/C SPCS B2 TILE 2 GWB, PT GWB, PT GWB PT TILE 2, GWB PT GWB, PT 301 LANTERN --- --- GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT
TILE 2 MIRROR
120 WOMEN'S SHOWER TILE 1 B2 TILE 2 TILE 2 TILE 2 TILE 2 TILE 2 GWB, PT
121 RED SALES SPCS B1 GWB, PT SLAT WALL GWB, PT GWB, PT GWB, PT Slat wall display system East elev.
PLAM GWB, PT MIRROR Glazing, PLAM
122 RED SALES STORAGE SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB, PT Plywood Backing to 2440mm AFF, all walls
123 WC HALL SPCS B1 GWB, PT GWB, PT GWB, PT GWB, PT GWB. PT See Elevation for Vinyl Graphic
LEGEND
ACT Acoustic Ceiling Tile PLAM Plastic laminate
AFF Above Finish Floor P.P Plywood panel ALIGN SEAMS WITH CL OF MULLIONS
AWP Acoustic Wall Panel, CASH ALLOWANCE PLP Plastic laminate Panel AND DOOR FRAMES BELOW
B1 Rubber Base, 100mm high RF Resilient Flooring
B2 Tile Base SPCS Sealed Polymer Concrete Slab, Retroplate Polishing System
CONC Concrete TBD To be determined
CF Clear Finish TILE 1 Floor Tile MDF PT. FIN. TO MATCH GWB
290
CPT Carpet Tile TILE 2 Wall Tile MDF PT. FIN. TO MATCH GWB
GWB Gypsum Wall Board TB Tack Board Surface 1/2" DIA. PERFORATIONS
515
NLT Nail Laminated Timber Truss Wood Truss See Structural @ 19MM O.C.
PT Paint WD Soffit Cedar T&G Soffit, Stain Fin
1
PWC Presentation Wall Covering, SEPARATE PRICE
160
65
VARIES
160 45
515
1/2" DIA. PERFORATIONS
MDF PT. FIN. TO MATCH GWB @ 19MM O.C.
355
MDF PT. FIN. TO MATCH GWB
VARIES
TYP. PERFORATED MDF TRICKLE VENT PANEL @ 200A HALL TYP.
8 Scale 1:10
CL OF DOOR
03 25 2014: Issued for Construction
2 12 09 2013: Issued for Addendum #3
1 12 03 2013: Issued for Addendum #2
11 19 2013: Issued for Tender and B.P.
10 18 2013: 100% Complete - Issued for Client Review
08 16 2013: 99% Complete - Issued for Client Review
07 30 2013: 95% Coordination
05 14 2013: Issued to Consultants
DATE ISSUE
TRANSITION
ESC
SCHLUTER JOLLY
TRANSITION
TOPPING SLOPED TRANSITION
MIRROR TILE ON GROUT
TO DRAIN 1:100
GROUT B/T
INSET TILE, MED SET CONC. CARPET TILE RES. FL.
TRANSISTION AND TILE UBC ENGINEERING
PWC STUDENT CENTRE
32
76
76
MUD
102
102
ROOM FINISH
9 SCHEDULE
102
102
16MM MDF
SLAB DEPRESSION
2
TYP. MDF TRIM
Scale 1:5 3
TYP.TILE/CONCRETE SECTION DETAIL
Scale 1:5 4
TYP.CARPET TILE / RES. FL. SECTION DETAIL
Scale 1:5 5
TYP.TILE / MIRROR WALL TRANSISTION
Scale 1:5 6
TYP.VENT PANEL @ 2ND FLOOR DOORS
Scale 1:5
A.008
1 2 3 4 5 6 7 8 9 10 11 12 13
33695
EL 94.152 401 - 134 Abbott Street
T/O CONC. 3170 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 525 Vancouver, BC
700
Canada V6B 2K4
1180 1270 1240 t: 604-683-5060
e: info@urban-arts.ca
A A
SEAL:
T/O CONC.
T/O CONC. T/O CONC. EL 94.000
EL 93.968
SLAB EL 93.925 EL 94.000 T/O CONC.
1025
2915
DEPRESSION
T/O CONC.
EL 93.925
905
1390
B B
695 110
T/O CONC.
EL 3.925
T/O CONC.
NOTES:
EL 93.925
T/O CONC.
EL 93.925 This drawing is the property of Urban Arts Architecture and may not be
815 900 EL 93.968 T/O CONC. reproduced without their permission and unless the reproduction carries
T/O CONC. their name. All designs and all other information shown on this drawing
SLAB 700 700 EL 93.925 1630 are for use on the specified project only and shall not be used otherwise
T/O CONC. DEPRESSION without written permission of this office.
EL 94.152
The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
EL 93.925
1870
5195
170
2400 MM O.C., SEE STRUCTURAL
3000
AND MECHANICAL
2850
T/O CONC. T/O CONC.
T/O CONC. EL 93.925
EL 93.925
1445
EL 94.722
1010 740 740
89 357
130 1350 2020 525
300
C C
218
226
EL 94.152
1
T/O CONC.
T/O CONC.
EL 94.000
CONFIRM ON SITE
W/ CONSULTANT
PRIOR TO FORMING
EL 94.000
T/O CONC.
21535
5925
T/O CONC.
EL 94.000
557
DIMENSIONS OF ELEVATOR
SHAFT TO BE CONFIRMED 1330 40
EL 94.152
BY MANUFACTURER AND
T/O CONC. CONSULTANT PRIOR TO CONTROL JOINT TYP.,
FORMING OF ELEVATOR PIT SEE STRUCTURAL
CONFIRM ON SITE
1210
W/ CONSULTANT 1130
PRIOR TO FORMING
1
150
58
240
D D
139
1570
EL 94.722
T/O CONC.
E E
EL 93.925
T/O CONC. T/O CONC. EL 94.722
2720
86
EL 94.722
COORDINATE
EXTENT OF E'
CONCRETE
UPSTANDS W/
T/O CONC. T/O CONC. EL 94.152
1310
ELEVATIONS
1068
AND WINDOW EL 94.152 EL 94.000 T/O CONC. T/O CONC.
SCHEDULE, TYP.
EL 94.000
F F
400
G
150 88 1 EXTERIOR CONCRETE PIERS COORDINATE EXTENT OF
440 440 TO BE BELOW FINISHED CONCRETE UPSTANDS W/
1500
T/O CONC. T/O CONC. T/O CONC. GRADE COORDINATE W/ ELEVATIONS AND WINDOW
SLOPED PAVING/DECK AT SCHEDULE, TYP.
EL 94.152 EL 94.722 EL 94.152 EXTERIOR SEE LANDSCAPE
DRAWINGS FOR GRADING
H H
COORDINATE EXTENT OF
CONCRETE UPSTANDS W/
ELEVATIONS AND WINDOW
SCHEDULE, TYP.
1619 1335
365
ESC
UBC ENGINEERING
STUDENT CENTRE
A.100.1
1 1
A.405 A.301
1 2 3 4 5 6 7 8 9 10 11 12 13
401 - 134 Abbott Street
33695
Vancouver, BC
Canada V6B 2K4
3170 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 525 1710
t: 604-683-5060
e: info@urban-arts.ca
1
OBSCURE GLASS @ TRK VENT,
CLERESTORY WINDOWS, HIGH IN WALL A.303 SEAL:
TYP. @ (3) LOCATIONS SEE ELEV.
1 EXIT 3 4
D 110 A
D 108 A
A.604 A.604 A.604
W1A sim. W1A W1A
CW 118 CW 116 W3
A A
TRK
SPRINKLER D 106 A
MW 118
D 107 A
TREE TRASH
ANNUNC. 635 545
2 1525 1025 111 635 PANEL 21-24 2
A.301
118 P2A ELECTRICAL FLOOR MAT N.I.C.
A.701
Storage for 106 A.301
P1 P2A
P1 108 COMPOST
2915
PLUMBING 1 P2B are for use on the specified project only and shall not be used otherwise
HALL MANIFOLD PAPER
D 107 B
without written permission of this office.
405
CHASE BELOW A.706 RWL
D 120 A COUNTER 945
B P2C 1020 P2C B The Contractor shall check and verify all dimensions and report any
480
340
1 7-10 discrepancies before proceeding.
P1
805
610
610
MW 120.1 MW 119.1 A.705 ELEC. RISER
P2B P2B A.705 113 W2B
RWL Do not scale drawings.
COMMUNICATIONS 9-12 P2C
TRF P2C
D 113 A D 112 A D 109 A
D 117 A 16-18
A.701
109 1645
116 610 SEE ELEC/ TELECOM. VENDING
360
A.700
TILE
RWL
RWL
P1 DRAWINGS JANITOR MACHINE
MW 116.1
2005
MW 121.3 P1 11-14
MEN'S W/C 5-8 112 13-16
2 A.701
D 122 A MANIFOLD A.705 DRY STORAGE P2A A.701
A.606 P2A
105
380
SIM C/W P1
16 RISERS @ 160mm
117 FURRED P1
P2B 19-20
Bottle Filler INT. STORAGE
PREVENTER A.700
MEN'S SHWR. PLUMBING
MW 121.2
PROVIDE
1700
WALL
STAIR 2
P1 ROUGH-IN FOR
5195
850
D 118 A
D 116 A
MW 121.4 STORAGE 2
A.700 MW 115.1 MW 114.2
610 610 A.503
121 SHELVING N.I.C.
2710
2000
Station
CW 121-1
1830
W/C HALL 1460 11 12
D 121 A
P1
D 105 A
8 A.604 A.604
460 MW 115.2 MW 115.3
MW 121.1 870 900 740 740 1345 MW 114.1 A.606
330 305
RWL UP
C CW 121-2 DASHBOARD P2B P2B C
W1B
5 1 TRF 6 P1
700 700 P3
A.604 7 D 101 A W2B
CW 101-2
A.606
D 100 A OPEN TO
ABOVE A.606 SIM 4
AUTOMATIC DOOR VENT PIPE, EXPOSED CONCRETE,
6 A.802 EXIT
OPENER CENTERED SEE MECH. 101 POLISHED, SEALED
ON BRAKE SHAPE A.604 100
CW 100-1
9+10 FO FO FO
CW 101-1
FO
A.604 UP
1 2 5
1
P2B D 101 C
A.302 A.405 A.503 A.302
SIM
ELEV.
MW 101-2
F.D BELOW
TROPHY CASE
W1B2 10
RESILIENT STAIR 1
MW 101.1
13 A.606
A.604 FLOOR PLATFORM 23 RISERS TOTAL
1550 @ 175mm EA.
11
W/ 280mm TREADS
TRF TRF A.606
TYP.
CW 102-2
D D
D 102 B
D 102 A
D 103 A
D 103 C
E DOOR WITH ELEVATOR E
MANUFACTURER
470
P1
CW 104-2
CW 102-1
12-15
SIM C/W
FURRED A.700 104
MECH.
8-11
WALL COMMONS ANNEX
LINE OF 2ND
FLOOR ABOVE A.700 FO FO FO FO FO FO
P1
102 103
2720
PWC
WINDOW SILL
3
A.405
E'
TRK
CW 104-1 TRK
D 103 E
5
1310
TRK
A.604 SIM
CW 103-2
EXIT
F F
400
G CW 103-1
TRK CW 103-1 TRK
D 103 D
1
03 25 2014: Issued for Construction
W1B 1 03 24 2014: Issued for Value Engineering
1500
15 16 A.303
14 A.604
11 19 2013: Issued for Tender and B.P
A.604
A.604 10 18 2013: 100% Complete - Issued for Client Review
08 16 2013: 99% Complete - Issued for Client review
07 31 2013: 95% Coordination
H H 07 16 2013: Client Review
06 26 2013: Issued to Consultants
05 14 2013: Issued to Consultants
1 1
A.301
DATE ISSUE
A.405
1335
365
MOUNTED
WALL LIGHT
(SEE ELEC.)
5B
1 2
T/O 2nd FLOOR PARAPET FRAMING
101.68m
U/S ROOF STRUCTURE S S
101.20m
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
TRV B SIM reproduced without their permission and unless the reproduction carries
1 1115X460 their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
FFL - SECOND FLOOR without written permission of this office.
98.00m The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
2
S S Do not scale drawings.
5B
T/O FRAMING 2
94.760m
DOOR OPERATOR TRV A
TRV A
FFL - GROUND FLOOR 2
94.00m
2 ALIGN JOINTS W/ CL
OF MULLIONS TYP.
HB
MATERIAL LEGEND
1 DOUBLE GLAZED, THERMALLY BROKEN ALUMINUM
CURTAIN WALL
5B EIFS
2
6 PERFORATED ALUMINUM
101.20m
T/O FRAMING
98.760m TRV B SIM
TRV B TRV B TRV B TRV B
1220X460
T/O FRAMING
ESC
EQ EQ
94.760m
TRV A TRV A TRV A TRV A
FFL - GROUND FLOOR
94.00m UBC ENGINEERING
2 STUDENT CENTRE
HB HB
WEST ELEVATION
4 Scale: 1:50 ELEVATIONS
A.203
1 1 1
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
TYP. GUARD are for use on the specified project only and shall not be used otherwise
AND HANDRAIL without written permission of this office.
The Contractor shall check and verify all dimensions and report any
T/O FRAMING discrepancies before proceeding.
98.760m POURED IN PLACE
TRV B TRV B TRV B Do not scale drawings.
CONCRETE STAIR 3
FFL - SECOND FLOOR FFL - SECOND FLOOR
98.00m 3 98.00m
T/O FRAMING
94.760m
3
MATERIAL LEGEND
FFL - GROUND FLOOR
94.00m
1 DOUBLE GLAZED, THERMALLY BROKEN ALUMINUM
CURTAIN WALL
5B EIFS
3
6 PERFORATED ALUMINUM
S SPRINKLER HEAD
101.20m
1
T/O FRAMING
98.760m MASONRY EXPANSION JOINTS 03 25 2014: Issued for Construction
3 3 03 24 2014: Issued for Value Engineering
2 12 09 2013: Issued for Addendum #3
FFL - SECOND FLOOR 1 12 03 2013: Issued for Addendum #2
98.00m 11 19 2013: Issued for Tender and B.P.
10 18 2013: 100% - Issued for Client Review
08 16 2013: 99% Complete - For Client Review
07 31 2013: 95% Coordination
07 16 2013: Client Review
GRILLE,
SEE MECH. DATE ISSUE
U/S SLAB
96.490m
T/O FRAMING
ESC
94.760m UBC ENGINEERING
STUDENT CENTRE
FFL - GROUND FLOOR
94.00m
U/S OF CONCRETE 1 MASONRY EXPANSION JOINTS
STAIR BEYOND FIRE DEPARTMENT METAL PANEL HB
GAS METER
ENCLOSURE CONNECTION WITH LIGHT
FIXTURE
ABOVE
ELEVATIONS
EAST ELEVATION
2 Scale 1:50
A.204
1 2 3 4 5 6 7 8 9 10 11 12 13
R1
RD
3
4 1
A.402
A.402 A.402
214 NOTES:
F2 ELEC., TYP. GLASS PANEL F2 The Contractor shall check and verify all dimensions and report any
T/O SECOND FLOOR SLAB discrepancies before proceeding.
EL 98.00
Do not scale drawings.
100 ALUM. ANGLE ACOUSTIC PANELS
ENTRY 2270X1220
101 POURED-IN
AV/ TV PLACE CONCRETE
COMMONS GWB, PT. STAIR BEYOND
4
A.802
F1 F1
T/O GROUND FLOOR SLAB
EL 94.00
2
LEGEND
A.402 45 MIN FIRE SEPARATION
13 12 11' 10 9 8 7 6 5 4 3 2 1
EL 103.48
T/O LANTERN
3
A.403 EL 102.32
MECH
EQUIP T/O FEATURE WALL BEYOND
RD R1
1
A.402 SIM. TRUSS 1
- SEE STRUCT. A.403
STEEL GUARD
W/ PERFORATED
UNISEX ROOF
METAL INFILL
W/C ACCESS
T/O SILL
EL 98.76
F2 F2
T/O SECOND FLOOR SLAB
EL 98.00
ESC
UBC ENGINEERING
STUDENT CENTRE
2
A.403
A.302
401 - 134 Abbott Street
Vancouver, BC
H G F E' E D C A Canada V6B 2K4
t: 604-683-5060
e: info@urban-arts.ca
SEAL:
9
A.607
T/O LANTERN PARAPET T/O LANTERN PARAPET
103.45m 103.48m
342
U/S ROOF STRUCTURE U/S ROOF STRUCTURE
101.20m 101.20m
WALL SPRINKLER,
SEE MECHANICAL
3
T/O WINDOW SILL (2nd Floor) PERF. METAL GUARD
A.505
98.76m 7
SIM.
A.608
TRICKLE VENT
1 12
T/O PARAPET FRAMING
1 98.09m
F2 F2 R2
T/O SECOND FLOOR TOPPING T/O SECOND FLOOR TOPPING
98.00m 98.00m
W1C
U/S NLT STRUCTURE
T/O ROOF PLYWOOD SHEATHING
97.74m
BLOCKING AT END CUSTOM 97.655m
BULKHEAD 45 MIN FRR
OF NLT - SEE
STRUCT. DWGS. 1 FASCIA W/
U/S SOFFIT TYP. CONCEALED
97.30m LIGHTING LINEAR SURFACE SPRAY FOAM INSULATION AND
S1 C4 MOUNT WALL VAPOUR RETARDER TO LAP
PRE-FINISHED METAL VENT LIGHTS, SEE
STRIP C/W INSECT SCREEN ELECTRICAL.
T&G SOFFIT BOARDS W/ CLEAR FINISH HEIGHT AND
ON RESILIENT CHANNELS LOCATIONS TO BE
6
MIN. 5" RIGID INSULATION @ U/S OF NLTs COORDINATED ON
- INSULATE CAVITY SUCH THAT CONCEALED A.608 SITE WITH
SPACE <150mm DEEP CONSULTANT
RECESSED LIGHT FIXTURES
U/S MULLION + T/O DOOR U.O.N.
- SEE ELECT. DWGS.
96.44m
PRE-FINISHED METAL INSECT SCREEN
ROLLER BLIND + RECESS
1 x 4 CEDAR T&G SOFFIT BOARDS COILING GRILLE
W/ CLEAR FINISH c/w ACOUSTICAL
LINER & INSULATION 103 111
FLEX ROOM ELECTRICAL
DOUBLE GLAZED CURTAIN WALL SYSTEM
101 100 115
GLULAM COLUMN (CLEAR FINISH) C/W COMMONS ENTRY SERVERY
STEEL BASE, PT. FIN. TYP. @ INTERIOR ROOF DRAIN IN PARTITION WALL
10
BEYOND TO BE TIED INTO
A.608 EXISTING STORM WATER SYSTEM
6
A.803
P1 P2B W1A
03 25 2014: Issued for Construction
T/O WINDOW SILL (Ground Floor)
SIM. 1 03 24 2014: Issued for Value Engineering
250 11 19 2013: Issued for Tender and B.P.
94.76m 10 18 2013: 100% - Issued for Client Review
10 10 08 16 2013: 99% Complete - Issued for Client Review
A.609 A.609 07 31 2013: 95% Coordination
TRICKLE VENT 07 16 2013: Client Review
12 05 14 2013: Issued to Consultants
A.608
2x6 WOOD DECK ON CONCRETE PILES, 1 DATE ISSUE
SEE LANDSCAPE F1 F1
FFL - GROUND FLOOR FFL - GROUND FLOOR
94.00m 94.00m
ESC
UBC ENGINEERING
STUDENT CENTRE
WALL SECTIONS
5
SECTION AT VP OFFICE CANTILEVER (GL 4+)
Scale 1:20 4
SECTION AT FLEX ROOM / VP OFFICE (GL 4+)
Scale 1:20 3
SECTION AT ATRIUM / STAIR (GL 4+)
Scale 1:20 2
SECTION AT ATRIUM / ROOF DECK (GL 4+)
Scale 1:20 1
SECTION AT ELECTRICAL ROOM (GL 4+)
Scale 1:20
A.401
401 - 134 Abbott Street
Vancouver, BC
Canada V6B 2K4
t: 604-683-5060
e: info@urban-arts.ca
2 3 4 10 11 12 13 SEAL:
191
RECESSED LINEAR COVE The Contractor shall check and verify all dimensions and report any
LIGHT FIXTURE 1 discrepancies before proceeding.
253
Do not scale drawings.
SIDEWALL SPRINKLER
SIDEWALL SPRINKLER COVERAGE AT ALL
IN WALL BEYOND OVERHANGS >1200mm
C3
(NO SPRINKLERS ABOVE - SEE MECH. DWGS.
ENTRY GLAZING)
BEAM BEYOND PROVIDE CLOSER FLAP
GLULAM COLUMN BEYOND 2 - SEE STRUCT. @ ROLLER BLIND RECESS
A.609
<W1B> WALL TYPE SIM. 3
AT WALL BEYOND
1 GLASS
A.609
PARTITIONS ON
STAND-OFFS, SEE
LINE OF SPRINKLER
DETAIL 17-A.702
RISER BEYOND
214
HOT-DIPPED GALVANIZED STUDY
STEEL GUARD @ ROOF 7
DECK W/PERFORATED A.609
METAL INFILL PANEL
215 STUDY
BEYOND
T/O WINDOW SILL (2nd Floor)
TYP. TRK VENT 98.76m
BRIDGE @ 2nd FLR
450x450x200 ZONE BOX FOR WAP, DETAIL
PROVIDE FLUSH ACCESS PANEL IN
1 CEILING BELOW W/ FINISH TO
MATCH T+G CEILING
100
ENTRY 101
COMMONS
DASHBOARD
INTERIOR
STORAGE
BEYOND
12
A.602
F1
T/O GROUND FLOOR TOPPING T/O GROUND FLOOR TOPPING
03 25 2014: Issued for Construction
94.00m 94.00m 1 03 24 2014: Issued for Value Engineering
11 19 2013: Issued for Tender and B.P.
10 18 2013: 100% - Issued for Client Review
08 16 2013: 99% Complete - Issued for Client Review
07 31 2013: 95% Coordination
07 16 2013: Client Review
BOTTOM OF FOOTING BOTTOM OF FOOTING 05 14 2013: Issued to Consultants
SEE STRUCTURAL SEE STRUCTURAL
DATE ISSUE
ESC
UBC ENGINEERING
STUDENT CENTRE
WALL SECTIONS
SECTION AT ENTRY (GL C+) SECTION AT BRIDGE (GL C+) SECTION AT ATRIUM / STUDY ROOM / COMMONS (GL C+) SECTION AT STUDY ROOM CANTILEVER (GL C+)
4 Scale 1:20 3 Scale 1:20 2 Scale 1:20 1 Scale 1:20 A.402
6 5 4 3 2 1
406
EDGE OF GREEN ROOF SEE STRUCTURAL reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
SPLASH PAD ALONG GL '2' 6 are for use on the specified project only and shall not be used otherwise
1
4 T/O MAIN ROOF PARAPET FRAMING without written permission of this office.
R1 A.609
200
R1 R1 101.68m The Contractor shall check and verify all dimensions and report any
GREEN ROOF ALTERNATE PRICE GREEN ROOF ALTERNATE PRICE discrepancies before proceeding.
P2B
SIM.
W1B2
200
WAITING
ELEVATOR
UNISEX ROOF SHAFT
WASHROOM ACCESS
BEYOND BEYOND
F2
T/O SECOND FLOOR TOPPING
98.00m
1
U/S GROUND FLR. SOFFIT, TYP.
97.30m
PROVIDE CONTINUOUS
FIRE RATING AT ELEVATOR
SHAFT AND DOORS
101
COMMONS STAIR 1 P2B
SIM.
W1B2
ELEVATOR SHOP
DRAWINGS TO BE
APPROVED PRIOR
ESC
TO FORMING OF
1222
SEE STRUCTURAL
BOTTOM OF FOOTING
WALL SECTIONS
CL 3
300 300 300 300 300 95
A.608 LINE OF PARAPET LINE OF PARAPET
100
6 SIM. BEYOND BEYOND 6
1 1 1
T/O MAIN ROOF PARAPET FRAMING T/O MAIN ROOF PARAPET FRAMING
1:50 TYP. 1:50 TYP.
101.68m GREEN ROOF ALTERNATE PRICE R1 R1 101.68m NOTES:
GREEN ROOF ALTERNATE PRICE GREEN ROOF ALTERNATE PRICE
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
U/S ROOF STRUCTURE U/S ROOF STRUCTURE are for use on the specified project only and shall not be used otherwise
without written permission of this office.
101.20m 101.20m
The Contractor shall check and verify all dimensions and report any
SIDE WALL SPRINKLER
SIDE WALL SPRINKLER discrepancies before proceeding.
1 REVEAL
1 COVERAGE @ COVERAGE @
A.609 OVERHANG DEPTH OVERHANG DEPTH Do not scale drawings.
A.608 101.00m
1200mm OR GREATER1200mm OR GREATER
- SEE MECH. DWGS. - SEE MECH. DWGS.
C3 LINE OF LIGHTS C3
EQ1
BEYOND, TYP.
EXTERIOR LIGHT FIXTURE, SEE ELECTRICAL. SPRINKLER 2
COORDINATE MOUNTING HEIGHT AND LOCATION ELECTRICAL LINE IN A.609
WITH CONSULTANT PRIOR TO INSTALLATION RISER IN WALL DROPPED
TYPICAL CEILING ABOVE
ROOF DRAIN IN
EQ2
SHEAR WALL
PARTITION
- SEE STRUCT.
215 + MECH. DWGS
W1C
W2B
STUDY
LOUNGE P1
214 213
STUDY CONFERENCE/STUDY
EQ1
T/O GUARDRAIL
99.07m
1
1 218
EQ2
A.507 ROOF DECK 5
A.609
1
DOUBLE SILL PLATE TO
DOUBLE SILL PLATE TO
F3 F2
T/O SECOND FLOOR TOPPING FORM EDGE OF CONC. FORM EDGE OF CONC. T/O SECOND FLOOR TOPPING
TOPPING TOPPING
98.00m 98.00m
EQ3
U/S STRUCTURE
97.75m
CONCRETE STAIR, SEE
STRUCTURAL AND
LANDSCAPING
U/S SOFFIT TYP.
97.30m
C4 S1
T/O WINDOW
W3 NO SPRINKLERS REQ'D @ 6 97.08m
400
CONCEALED SPACE <150mm DEEP A.609
125 MM RIGID INSULATION @ U/S OF NLTs
SLOPED U/S OF
CONC. STAIR 2 1 x 4 CEDAR T&G W/CLEAR FINISH
T/O OPENING IN CONCRETE FURRED OUT TO ALIGN WITH
DUCT, SEE MECHANICAL
96.49m FACE OF EXTERIOR CLADDING
SIDE WALL SPRINKLER COVERAGE
OPENING AT OVERHANG DEPTH >1200mm
400
F1B F1 F1
T/O GROUND FLOOR FRAMING T/O GROUND FLOOR TOPPING
03 25 2014: Issued for Construction
94.00m 94.00m 1 03 24 2014: Issued for Value Engineering
11 19 2013: Issued for Tender and B.P.
10 18 2013: 100% - Issued for Client Review
08 16 2013: 99% Complete - Issued for Client Review
07 31 2013: 95% Coordination
07 16 2013: Client Review
05 14 2013: Issued to Consultants
DATE ISSUE
12 11
A.609 A.609
ESC
SIM.
UBC ENGINEERING
STUDENT CENTRE
WALL SECTIONS
SECTION AT LANDING / EXTERIOR STORAGE (GL 10+) STUDY / STORAGE (GL 10+) SECTION AT CONFERENCE / COMMONS ANNEX (GL 10+)
3 Scale 1:20 2 Scale 1:20 1 Scale 1:20 A.404
401 - 134 Abbott Street
Vancouver, BC
Canada V6B 2K4
t: 604-683-5060
e: info@urban-arts.ca
SEAL:
1 2 D E F G
NOTES:
6 This drawing is the property of Urban Arts Architecture and may not be
1 reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
without written permission of this office.
3
2 The Contractor shall check and verify all dimensions and report any
A.608 SEALANT FILM, discrepancies before proceeding.
A.608 TYPICAL
6 SIM. Do not scale drawings.
1 SIM.
T/O MAIN ROOF PARAPET FRAMING T/O MAIN ROOF PARAPET FRAMING
101.68m R1 1:50 TYP. 1:50 TYP. 101.68m 1:50 TYP. 1:50 TYP. R1 1:50 TYP. 1
EQ1
C3
12" EXTRUDED ALUMINUM PERIMETER TRIM
PERIMETER TRIM AT CEILING FACE OF
@ DROPPED <C3>
GRID, TYP. PERIMETER TRIM CEILING BEYOND
@ DROPPED <C3>
CEILING BEYOND
EQ2
201 201 FEATURE WALL
W1B EXTERIOR WALL
DIGITAL DIGITAL ASSEMBLY W/
ADDITIONAL FRAMING
201 + PLYWOOD FOR SHEAR
W1C WALL
DIGITAL - SEE STRUCT. DWGS.
EQ1
1
T/O WINDOW SILL TYP. T/O WINDOW SILL TYP. W1B
98.76m 98.76m
EQ2
EQ2
W1C
5+6
A.609
F2 F2 F2
T/O SECOND FLOOR TOPPING SIM. T/O SECOND FLOOR TOPPING
98.00m 98.00m
EQ3
EQ3
8
A.609
104
FIRST YEAR 102 102
CORNER OF FIRST YEAR FIRST YEAR
ELEVATOR BEYOND
(INTERIOR WALL)
W1B
ESC
UBC ENGINEERING
STUDENT CENTRE
WIDER STRIP
FOUNDATION WALL
@ FEATURE WALL
- SEE STRUCT. DWGS.
WALL SECTIONS
SECTION AT DIGITAL (GL E+) SECTION AT DIGITAL / FIRST YEAR (GL 1+) SECTION AT FEATURE WALL (GL 2+)
3 Scale 1:20 2 Scale 1:20 1 Scale 1:20 A.405
6 5 4
EQ EQ 1
SET WOOD TREAD
LINE OF STRINGER FLUSH W/ FIN. FLOOR
BELOW
19 MAX
5
TRUSS (2ND FLOOR) 401 - 134 Abbott Street
A.505
90
Vancouver, BC
125
WOOD TREAD
1200
3 UP 19 R @ 175MM
18 T @ 305MM
1730
A.504
TACTILE WARNING SURFACE
2
4
90
ALIGN UPRIGHTS TYP.
4 A.504
65 MM O.C. STEEL TO
19 MAX
A.504
MATCH RISER
MW 101.2 BELOW 1
305 745 INSET WOOD
TREAD BEYOND NOTES:
19 MAX.
5 1120 1120 1120 835 This drawing is the property of Urban Arts Architecture and may not be
5 reproduced without their permission and unless the reproduction carries
A.505
7 A.505
TRUSS their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
A.505
without written permission of this office.
The Contractor shall check and verify all dimensions and report any
UP 3 R @ 175MM discrepancies before proceeding.
1015
300
2 T @ 305MM
Do not scale drawings.
1015
10
A.505
5
A.505
6 5 4
SIM
TYPICAL 1
UPRIGHT
1015
900
300
MANIFOLDS
900
ALIGN UPRIGHTS TYP. SEE MECH
STEEL UPRIGHT
WELDED TO STEEL NLT
PLATE AND BOLTED 700 AFF
TO U/S OF NLT 12MM PLYWOOD PANEL
CLEAR FINISH
211
1015
311
FILL CAVITY WITH INSULATION
30MM DIA STEEL
HANDRAIL WAX FIN.
SEE STRUCTURAL
STAIR SECTION
STAIR AND BRIDGE PLAN 4 Scale 1:20
1 Scale 1:20
3 6 5 4
A.505 840 3 EQUAL 870
7
A505
SIM.
DATE ISSUE
TYP. HANDRAIL
BOTH SIDES
1 ESC
TYP. HANDRAIL
BOTH SIDES UBC ENGINEERING
420 1
420 STUDENT CENTRE
1 300
300
90.00
900
900
NLT PLATFORM
STAIR SECTION THROUGH LANDING STAIR 1 NORTH ELEVATION @ MILLWORK STAIR WEST ELEVATION
A.504
2 Scale 1:20 3 Scale 1:20 5 Scale 1:20
305
TYP TREAD: 38 MM DEEP RECYCLED WOOD,
PLANED AND GLUED W/ BISCUIT, CLEAR FIN. ON TYP TREAD: 38 MM DEEP RECYCLED WOOD,
280 FOLDED STEEL PLATE: SEE STRUCTURAL PLANED AND GLUED W/ BISCUIT, CLEAR FIN. ON
WOOD STRINGER TO SUIT
NON-SLIP SAFETY STRIP ALUMINUM INSERT
175
NON-SLIP SAFETY STRIP ALUMINUM INSERT
30MM DIA STEEL 25
8mm RADIUS ON LEADING EDGE, TYP. 8mm RADIUS ON LEADING EDGE, TYP.
HANDRAIL WAX FIN. 25
6MM X 6MM REVEAL - TYP.
CL OF TYP RISER: 12 MM DEEP RECYCLED WOOD,
38
38
HANDRAIL ATTACHED W/
COLUMN CONCEALED PIN CONNECTION ANGLE EDGE OF WOOD TREAD TO ALIGN WITH PLANED AND GLUED W/ BISCUIT, CLEAR FIN. ON
@ WOOD COLUMN FOLDED STEEL PLATE WOOD FRAMING TO SUIT
175
6 MM X 6 MM REVEAL 305
ALIGN CL OF GUARD UPRIGHT W/
TYP. RISER: FOLDED STEEL PLATE, 280
CL OF TRUSS VERTICAL
SEE STRUCTURAL
401 - 134 Abbott Street
TYP. GUARD RAIL Vancouver, BC
TYP. RAIL: STEEL PLATE
TYP. UPRIGHT WAX FIN., 64MM X 12MM Canada V6B 2K4
t: 604-683-5060
76 TYP.
e: info@urban-arts.ca
76 TYP.
SEAL:
25 TYP.
Scale 1:5 Scale 1:5 Scale 1:5
1070 TYP.
2 TYP. GUARDRAIL 3
TYP. PERF. GUARD
A.505 A.505
EQ TYP.
78
BOTTOM ALUM. GUARD 6MM
ABOVE TOP OF TRUSS
NOTES:
BOTTOM CHORD OF TRUSS FACE OF FOLDED PERF. ALUM SHEET
This drawing is the property of Urban Arts Architecture and may not be
FLUSH WITH OUTSIDE FACE OF STEEL reproduced without their permission and unless the reproduction carries
UPRIGHT (IE: TIGHT TO TRUSS FACE) 900 ABOVE STAIR TREAD AT NOSING their name. All designs and all other information shown on this drawing
TYP. UPRIGHT are for use on the specified project only and shall not be used otherwise
6
1070 TYP.
HANDRAIL ATTACHMENT The Contractor shall check and verify all dimensions and report any
1070 TYP.
discrepancies before proceeding.
30 MM DIA. STEEL HANDRAIL Do not scale drawings.
WELDED TO UPRIGHT W/ 8 MM
X 12MM S.S PLATE
GUARD AT TRUSS: TYP. BAY ELEVATION CONNECTION
1 Scale 1:10 1 PERFORATED GUARD FOLDED 2
AND BOLTED TO STEEL UPRIGHT 2 STEEL UPSTAND BOLTED TO STEEL
STRINGER 12MM EXPOSED END GRAIN
OF NLT
GUARD 6MM ABOVE TOP OF BOTTOM 38MM WOOD TREAD ON FOLDED STEEL
CHORD PLATE: SEE STRUCTURAL
3 LINE OF FIN. FL. BEYOND
EQ TYP.
STEEL UPRIGHT BOLTED TO NLT
A.505
LINE OF
STEEL ANGLE BEHIND
51
60 TYP
51
TYP. GUARD RAIL TYP. GUARD RAIL FOLDED PERFORATED ALUM. GUARD
OFFSET 6MM FROM BOTH FACE OF
TYP. GUARD UPRIGHT TYP. GUARD UPRIGHT FLOOR ASSEMBLY STRINGER AND BOLTED BASE PLATE
25 TYP.
76 TYP
HANDRAIL WAX FIN. 60 TYP GWB/BOTTOM CHORD OF NLT BRIDGE STUCTURE BEYOND
6
12MM GWB REVEAL AT U/S OF BOTTOM CHORD FOLDED PERFORATED GUARD BOLTED
CONTINUOUS STEEL ANGLE (COUNTERSUNK) TO STEEL STRINGER
12MM X 12MM STEEL AT FACE OF NLT ALIGN W/ EDGE OF TRUSS TYP.
30MM DIA STEEL RUBBER GASKET B/T STEEL STRINGER
SUPPORT WELDED TO HANDRAIL WAX FIN. AND ALUMINUM GUARD
12MM X 64MM STEEL TAB PERFORATED ALUM. GUARD
60 TYP
IA. STEEL SUPPORT AND HANDRAIL 9MM DIA. STEEL SUPPORT OFFSET 6MM PROUD OF
12MM X 12MM STEEL SUPPORT ANGLE AND FACE OF NLT, 6MM REVEAL B/T WOOD PANEL AND
144
ED TO STEEL TAB AND WELDED TO 12MM X 64MM WELDED TO STEEL TAB AND
RAIL HANDRAIL PROVIDE 12 MM DIA. X 6 MM STEEL STRINGER (BOTH SIDES)
STEEL TAB AND HANDRAIL THICK NEOPRENE BUMPER
12MM X 64MM STEEL TAB
AT STEEL ANGLE
64
12
ED TO 12MM X 64MM STEEL PLATE WELDED TO 12MM X 64MM ALUM. ANGLE AT BLOCKING AS
TAB WELDED TO U/S OF NLT REVEALING
TAB STEEL TAB 6MM REVEAL REQUIRED FOR WOOD PANELS
STEEL UPRIGHT PROVIDE BLOCKING LINE OF END GRAIN, TYP
IN WALL AT BRIDGE
TYP. STAIR HANDRAIL SECTION DETAIL TYP. STAIR HANDRAIL SUPPORT TYP. HANDRAIL SUPPORT:
@ STEEL UPRIGHT @ GWB WALL: SECTION DETAIL AXONOMETRIC VIEW BRIDGE GUARD RAIL: SECTION DETAIL STAIR DETAIL SECTION
2 Scale 1:5 4 Scale 1:5 10 Scale 1:5 3 Scale 1:5 7 Scale 1:10
76 TYP.
STEEL FASTENING PLATE,
INSET WOOD TREAD INSET WOOD TREAD (BOLTS COUNTERSUNK) SEE
STRUCTURAL
EDGE OF EXPOSED
60 TYP.
12
1070 TYP.
55 55 CL OF BRIDGE
6
1070 TYP.
2 03 24 2014: Issued for Value Engineering
FOLDED PERFORATED ALUM. GUARD TYP. UPRIGHT 1 12 09 2013: Issued for Addendum #3
BOLTED TO TYP. STEEL UPRIGHT
900 TYP.
PROVIDE RUBBER GASKET TO 3 11 19 2013: Issued for Tender and B.P.
SEPARATE ALUM. FROM STEEL, TYP. 10 18 2013: 100% Complete - - For Client Review
A.505
08 16 2013: 99% Complete - - For Client Review
TYP. HANDRAIL SUPPORT
BELOW STEEL UPRIGHT WELDED TO 07 31 2013: 95% Coordination
STEEL PLATE BOLTED TO STEEL
50 75 50
60 TYP. 05 14 2013: Issued to Consultants
6 MM REVEAL STRINGER
60 TYP. SPRINKLER
S.S. NOSING STRIP (BOTH SIDES) TYP. TREAD DATE ISSUE
GWB, PT. FIN. ON
435
FRAMING TO SUIT HWR DHWR DHW
HWS DCW
ESC
LINE OF RECESSED
30 MM DIA. STEEL HANDRAIL
2 LIGHT BEYOND
5
TYP. STAIR + BRIDGE GUARD RAIL PLAN DETAIL
8
STAIR AND BRIDGE DETAIL SECTION
A.505
Scale 1:5 (FIN. FL. NOTES NOT SHOWN FOR CLARITY) Scale 1:10
10 11 12 13
13
76
BOLTED TO FACE OF
CONCRETE SLAB A
STEEL TAB BELOW BOLTED TO FACE OF
CONC. SLAB , PROVIDE NEOPRENE
GASKETS TYP. AT ALL LOCATIONS A
401 - 134 Abbott Street
CLOSURE STEEL PLATE/ ANGLE 76
BOLTED TO CONCRETE WALL 300 305 300 Vancouver, BC
CONTINUOUS SEALANT
Canada V6B 2K4
TYP. GUARD RAIL t: 604-683-5060
25
CONTINUOUS ABOVE e: info@urban-arts.ca
SEAL:
CONCRETE LANDING
CAST IN PLACE
EXTERIOR STAIR PLAN DETAIL @ SOUTHWEST CONCRETE EL. 96.740
1
CORNER, LANDING + BASE OF STAIR PAVERS LANDING
1 Scale 1:10 UP 9 RISERS @ 143MM A.506
TREADS AT 305MM
SLOPE 1:50
4 750 305
A.506
W2B-NC NON COMBUSTIBLE
1 EIFS CONSTRUCTION AT EAST
ONE
TREAD ELEVATION ONLY
WIDTH 4
CAST IN PLACE
METAL TACTILE A.507
2497
WARNING SYSTEM NOTES:
300
This drawing is the property of Urban Arts Architecture and may not be
TYP. NOSING STRIP: reproduced without their permission and unless the reproduction carries
CAST IN PLACE METAL their name. All designs and all other information shown on this drawing
NOSING are for use on the specified project only and shall not be used otherwise
without written permission of this office.
TYP. EXTERIOR HANDRAIL 1
The Contractor shall check and verify all dimensions and report any
A.506
76 discrepancies before proceeding.
305
PANEL BEHIND
1
TYP. STEEL UPRIGHT
A.507
76
150MM X 64MM STEEL
PLATE PINNED TO EXTERIOR STAIR PLAN
CONCRETE STAIR 5 Scale 1:20
LINE OF BOTTOM
EDGE OF PERFORATED
100
PANEL BEHIND
150 4
A.507
450
ATTACHMENT @ CONCRETE STAIR UP 16 RISERS @ 171MM
305
305
6 Scale 1:10
TREADS AT 305MM
C
305
3
ALIGN W/ FACE A.507
OF CLADDING
10 11 12
TYP. EXTERIOR GUARD
1
T/O GUARDRAIL
99.07m TYP. EXTERIOR STAIR:
W2B
POURED IN PLACE CONCRETE
STAIR W/ METAL NOSING MIN.
50MM, SBS MEMBRANE, 200MM
CONCRETE SLAB
83
30mm DIA. STEEL GALVANIZED
PAINTED HANDRAIL @ INSTALL PERF. ALUM. TYP. EXTERIOR HANDRAIL SLOPED STEEL PARAPET EXTERIOR STAIR LANDING:
EXTERIOR GRAVEL STOP AT TOP CAP - SEE DETAIL #1 ON CONCRETE TOPPING (MIN. 50MM)
OF STAIR BEYOND SHEET A.507 SBS MEMBRANE ON 200MM
R2 CONCRETE SLAB
9MM DIA. STEEL SUPPORT SLOPE 1:50 T/O STAIR
T/O PAVERS RETURN STEEL PARAPET
WELDED TO 12MM X 64MM
98.025m
STEEL TAB AND HANDRAIL 98.00m CAP DOWN TO CONC.SLAB
T/O SLAB
305 300
12MM X 64MM STEEL TAB 97.925m
WELDED TO STEEL PLATE T/O DECK
1070 TYP.
SAM OR B.P. BETWEEN CONC.
AND WOOD
REGLET @ CONCRETE
SPRAY INSULATION WALL
4
A.507
03 25 2014: Issued for Construction
SEAL VB TO TOP OF PLATE METAL FLASHING
SIM 1 03 24 2014: Issued for Value Engineering
11 19 2013: Issued for Tender and B.P.
T/O SLAB
96.740m 10 18 2013: 100% Complete - - For Client Review
08 16 2013: 99% Complete - - For Client Review
U/S SLAB
07 31 2013: 95% Coordination
96.490m
SECTION DETAIL - EXT. HANDRAIL ATTACHMENT 05 14 2013: Issued to Consultants
2 Scale 1:5
DATE ISSUE
FOLD GUARD BACK 25MM
AT 90 DEGREES TYP. AT
EXT. STAIR AND LANDING
9MM X 9MM DRIP
ESC
SBS MEMBRANE
POURED IN PLACE
PERFORATED
CONCRETE TREADS
305 ALUMINUM UBC ENGINEERING
FIXED PANEL STUDENT CENTRE
171
CAST IN PLACE 25
METAL NOSING
50
MI
N.
ALUMINUM FLASHING
LINE OF SBS
MEMBRANE
EXTERIOR STAIR DETAILS
20
0
T/O GUARDRAIL
99.07m
A PARAPET CAP:
3MM GALVANIZED PAINTED STEEL
W/ DRIP EDGE AS SHOWN ON BUILT-UP
PLYWOOD SLOPED TO DRAIN C B A
2
STEEL PLATE CAP BOLTED TO CONC.
WALL, SEPARATE STEEL PLATE FROM 401 - 134 Abbott Street
465 CONCRETE WITH WATERPROOF W2B-NC Vancouver, BC
MEMBRANE Canada V6B 2K4
38 19
60 TYP. STEEL HANDRAIL 101
t: 604-683-5060
38 TYP. STEEL HANDRAIL
e: info@urban-arts.ca
6 12
1 INSTALL HANDRAIL SUPPORTS PRIOR
T/O CONC. WALL SEAL:
70
IN WALL DRIVE- LOCK REGLET C/W LAP AVM OVER SBS ROOFING, SEAL
BACKER ROD + SEALANT OVER TOP OF WITH SAM, CONTINUOUS FLASHING TO
SURFACE REGLET PINNED TO TERMINATE UNDER STAIR TOPPING
CONCRETE W/ POLYURETHANE
SEALANT - FILL TO TOP + CROWN TO ALUM. PERF. INSECT SCREEN CLOSER
PROMOTE DRAINAGE NOTES:
ALUM. FLASHING AND DRIP EDGE
ALUM. FLASHING METAL 'E' LOGO SIGN,
This drawing is the property of Urban Arts Architecture and may not be
PROVIDE SEPARATE PRICE reproduced without their permission and unless the reproduction carries
W2A SBS ROOFING MEMBRANE TO
SEE 6/A.507 their name. All designs and all other information shown on this drawing
EXTEND MIN. 200MM UP WALL
are for use on the specified project only and shall not be used otherwise
VARIES 50 MIN.
TYP. EXTERIOR STAIR
100
without written permission of this office.
200
200
The Contractor shall check and verify all dimensions and report any
CONC. STAIR 99.07m discrepancies before proceeding.
1 2
200
SLOPED CONC.
U/S SLAB
STEEL HANDRAIL ATTACHMENT
C/W STEEL PLATE CONCEALED 96.490m
BEHIND CLADDING + ATTACHED TO PERF. GUARD TO U/S OF
CONCRETE WALL. CONFIRM CONC. SLAB, FOLD BACK 25
METHOD OF ATTACHMENT W/ MM AT 90 DEGREES
E' STRUCTURAL
ALIGN
PRE-ENGINEERED
ALUMINUM SHIP'S 3
LADDER A.506
900
R
1
U/S CEILING
EXTERIOR STAIR SECTION
101.20 3 Scale 1:20
203
ROOF ACCESS
180
FIXED PERF. METAL PANEL 08 16 2013: 99% Complete - - For Client Review
WELDED TO FRAME W2B
07 31 2013: 95% Coordination
75° 05 14 2013: Issued to Consultants
2 F1B
LAP AVM OVER SBS ROOFING, SEAL
DATE ISSUE
WITH SAM, CONTINUOUS
360
GROUND FLOOR
2300
94.00m
91 ALUM. PERF. INSECT SCREEN AND
CLOSER
COORDINATE BOLTED
ESC
1000
645
+/- 50 MIN.
UBC ENGINEERING
200
STUDENT CENTRE
64
T/O TOPPING
360
98.00
180
200
76
1960
9MM X 9MM DRIP
EXTERIOR STAIR
FOLD PERFORATED GUARD
2 2 BACK 25MM AT 90 DEGREES + ROOF HATCH
DETAILS
9 6
TYP. BREAK SHAPE HEADER ASSEMBLY: LAP AND SEAL AIR BARRIER TO
PERF. MTL. INSECT SCREEN THROUGH-WALL FLASHING
ANOD. ALUM. CONTINUOUS CLEAT SEALANT BETWEEN NLT AND
RESILIENT CHANNEL
SEPARATE FROM ANY PRESSURE TOP PLATE OF WALLS, TYP. STAINLESS STEEL THROUGH-
TREATED WOOD THROUGHOUT WALL FLASHING LAP SEAMS W1A
25mm AND SOLDER
SEALANT
TYPICAL BRAKE SHAPE 150x150x12.5 METAL PLATE C/W
MECHANICALLY FASTEN AIR/MOISTURE 100X60 OFFSET WELDED KNIFE
HEADER ASSEMBLY T&G WOOD SOFFIT
BARRIER TO UNDERSIDE OF DECK T&G CEILING, ALIGN W/ PLATE DRILLED PRIOR TO
THROUGH CONTINUOUS PRESSURE AIR / MOISTURE BARRIER LINE OF NLT PANELS ABOVE ANOD. ALUM. THROUGH-WALL EXTERIOR SOFFIT GALVANIZING
223
TREATED PLYWOOD TERMINATION BAR FLASHING C/W DRIP AND CLEAT SEAL AIR BARRIER TO PLATE
SELF-ADHESIVE MEMBRANE HEADER - SEE STRUCTURAL
CONTINUOUS BEAD OF ACOUSTIC LAPPING AIR BARRIER HEADER - SEE STRUCTURAL AIR / MOISTURE BARRIER
210
MORTAR COLLECTION MESH
SEALANT OR FOAM GASKET TO PROVIDE TRANSMISSION MEMBRANE AND
SPRAY FOAM INSULATION TYPICAL BRAKE SHAPE HEADER - SEE STRUCTURAL
VAPOUR RETARDER CONTINUITY 19 52 THROUGH-WALL FLASHING METAL TAB WELDED TO LINTEL 401 - 134 Abbott Street
HEADER ASSEMBLY
ANOD. ALUM. BRAKE SHAPE ANOD. ALUM. THROUGH-WALL VAPOUR RETARDER LAPPED AND DRILLED PRIOR TO
19
Vancouver, BC
FLASHING C/W DRIP AND SEALED TO AIR/MOISTURE ANOD. ALUM. THROUGH-WALL GALVANIZING VAPOUR RETARDER Canada V6B 2K4
SEMI-RIGID MINERAL WOOL INSULATION
TYP.
MEMBRANE WITH SPRAY FOAM FLASHING C/W DRIP MASONRY WEEP 780mm t: 604-683-5060
25
HORIZONTAL PRESSURE-TREATED ANOD. ALUM. CONTINUOUS INSULATION
9
ANOD. ALUM. CONTINUOUS O/C. CORNER BEAD e: info@urban-arts.ca
PLYWOOD FURRING CLEAT CLAMPED INTO 6mm STEEL ROD DRIP
CURTAINWALL POCKET CORNER BEAD CLEAT CLAMPED INTO CORNER BEAD SEALANT- TYP.
WELDED TO LINTEL PRIOR
SELF-ADHESIVE MEMBRANE SEPARATING SEALANT CURTAINWALL POCKET SEALANT TO GALVANIZING SPRAY FOAM INSULATION SEAL:
PT WOOD FROM METAL AIR BARRIER TRANSITION
MEMBRANE ON CONTINUOUS T OR F SLIP ANCHOR @ HEAD OF AIR BARRIER TRANSITION T OR F SLIP ANCHOR @ HEAD OF STEEL LINTEL, HOT-DIPPED
ANOD. ALUM. CONTINUOUS CLEAT VERTICAL MEMBERS, TYP. VERTICAL MEMBERS, TYP. T OR F SLIP ANCHOR @ HEAD OF
KINKED METAL FLASHING MEMBRANE ON CONTINUOUS GALVANIZED VERTICAL MEMBERS, TYP.
KINKED METAL FLASHING
ANOD. ALUM CLOSURE
PERFORATED METAL INSECT SCREEN LINE OF ALUM. PANEL BEYOND LINE OF GWB BEYOND LINE OF ALUM. CLUSURE LINE OF GWB BEYOND STRIP CLAMPED INTO
FLASHING BEYOND GLAZING POCKET
WEEP OPENING
6
9
TYP. SEALANT
9
TYPICAL BRAKE SHAPE HEADER ASSEMBLY SECTION DETAIL: TYP. CURTAIN WALL HEAD @ W1C (ALUM. PANEL) SECTION DETAIL: TYP. CURTAIN WALL HEAD @ W1B (EIFS) SECTION DETAIL: TYP. CURTAIN WALL HEAD @ W1A (BRICK VENEER)
1 Scale 1:2 2 Scale 1:5 3 Scale 1:5 1 4 Scale 1:5
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
76X76 HOT-DIPPED GALVANIZED AIR BARRIER TRANSITION their name. All designs and all other information shown on this drawing
GENERAL NOTES FOR CURTAIN WALL: are for use on the specified project only and shall not be used otherwise
ANGLE CLIPS, 75 LONG, 900 O/C. MEMBRANE SUPPORTED OVER GAP
without written permission of this office.
1. ACCOMMODATE DEFLECTION WITH SLIP CONNECTIONS AS REQUIRED. DRILL, CUT AND DEBURR PRIOR BY FOAM BACKER ROD AND
TO GALVANIZING. CLAMPED INTO GLAZING POCKET The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
2. RECESS SEALANT TO INTERIOR FROM FACE OF WINDOW FRAME AS SHOWN, TYPICAL. AIR / MOISTURE BARRIER SEALANT AND BACKER ROD
AIR BARRIER TRANSITION Do not scale drawings.
AIR BARRIER TRANSITION GALVANIZED STEEL JAMB -
MEMBRANE MEMBRANE SUPPORTED OVER HOT-DIPPED GALVANIZED METAL
ANOD. ALUM. CLOSURE GAP BY FOAM BACKER ROD AND W1A PLATE, BOLTED TO ANGLE CLIPS
19 TYP CLAMPED INTO GLAZING POCKET DRILL, CUT AND DEBURR PRIOR TO
W1C GALVANIZING
PREFIN. ALUM. CLOSURE
SELF-ADHESIVE MEMBRANE
INSULATION INSULATION THERMAL BREAK
ANOD. ALUM. CLOSURE
ALUM. PANEL SILL BELOW 1 W1B 19 TYP.
19 TYP.
TYP.
TYP.
SPRAY FOAM INSULATION FRAMING
19
19
VAPOUR RETARDER SPRAY FOAM INSULATION
SPRAY FOAM INSULATION
INTERIOR WALL FINISH TO WRAP F.O. GWB BELOW INTERIOR WALL FINISH TO WRAP
BEHIND WINDOW FRAME - TYP. BEHIND WINDOW FRAME - TYP.
INTERIOR WALL FINISH TO WRAP
F.O. GWB BELOW BEHIND WINDOW FRAME - TYP. F.O. GWB BELOW
MDF SILL, PAINTED, TYP. CORNER BEAD MDF SILL, PAINTED, TYP.
CORNER BEAD MDF SILL, PAINTED, TYP. CORNER BEAD
LAP VAPOUR BARRIER TO AIR / LAP VAPOUR BARRIER TO AIR /
MOISTURE BARRIER AND SEAL MOISTURE BARRIER AND SEAL
PLAN DETAIL: TYP. CURTAIN WALL JAMB @ W1C (ALUM. PANEL) PLAN DETAIL: TYP. CURTAIN WALL JAMB @ W1B (EIFS) PLAN DETAIL: TYP. CURTAIN WALL JAMB @ W1A (BRICK VENEER)
6 Scale 1:5 7 Scale 1:5 8 Scale 1:5
W1C W1A
SECTION DETAIL: TYP. CURTAIN WALL SILL @ W1C (ALUM. PANEL) SECTION DETAIL: TYP. CURTAIN WALL SILL @ W1A (BRICK VENEER)
10 Scale 1:5 12 Scale 1:5
GL
LINE OF BRICK BELOW 03 25 2014: Issued for Construction
SILL BELOW 1 03 24 2014: Issued for Value Engineering
ANOD. ALUM. BREAKSHAPE GL CLEAR ANODIZED ALUM. METAL 11 19 2013: Issued for Tender and B.P.
BREAKSHAPE 10 17 2013: 100% Complete - Issued for Client Review
GL 08 16 2013 99% Complete - Issued for Client Review
MINERAL FIBRE INSULATION ANOD. ALUM. CLOSURE MINERAL FIBRE INSULATION 07 31 2013: 95% Coordination
INSULATION CLEAR ANODIZED ALUM. BREAKSHAPE
TO MATCH WINDOW SYSTEM AIR / MOISTURE BARRIER DATE ISSUE
(REFER TO ELEVATIONS)
ESC
MINERAL FIBRE INSULATION INTO GLAZING POCKET
GL GL GL GL
CURTAIN WALL FRAME SPRAY FOAM INSULATION CURTAIN WALL FRAME
19 TYP.
19 TYP.
+ GLAZING
19 TYP.
PREFINISHED METAL SILL BELOW + GLAZING
TYP.
19
13
PLAN DETAIL: TYP. CW JAMB AT PARTITION @ W1C (AL. PNL.)
Scale 1:5 14
PLAN DETAIL: TYP. CURTAIN WALL CORNER JAMB @ W1C (ALUM. PANEL)
Scale 1:5 15
PLAN DETAIL: TYP. CURTAIN WALL CORNER JAMB DETAIL @ W1B (CEMENT PANEL)
Scale 1:5 16
PLAN DETAIL: CW JAMB AT COLUMN @ W1A (BRICK VENEER)
Scale 1:5
A.601
INSULATION RETENTION WASHER ON
MASONRY TIE
AIR SPACE
INSULATION
5
TO PROVIDE CONTINUOUS e: info@urban-arts.ca
METAL PLATE BEYOND AIR BARRIER
SECTION DETAIL: PRESSED STEEL FRAME DOOR HEAD, MASONRY WALL PLAN DETAIL: PRESSED STEEL FRAME JAMB DETAIL @ SIDELITE SECTION DETAIL: CURTAIN WALL HEAD, ENTRY
1 Scale 1:5 2 Scale 1:5 4 Scale 1:5
---
EXTERIOR
EXTERIOR MASONRY CLADDING
AIR SPACE
SELF-ADHESIVE MEMBRANE
76X51 HOT-DIPPED GALVANIZED ANGLE CLIPS,
75 LONG, 900 O/C. DRILL, CUT AND DEBURR ---
PRIOR TO GALVANIZING.
--- ---
EXTERIOR EXTERIOR EXTERIOR
SEALANT AND BACKER ROD (12mm THERMAL GLAZING
JOINT)
HOT-DIPPED GALVANIZED METAL PLATE, ANOD. ALUM. CURTAINWALL
BOLTED TO ANGLE CLIPS AIR BARRIER TRANSITION AIR BARRIER TRANSITION FRAME BELOW
DRILL, CUT AND DEBURR PRIOR TO MEMBRANE MEMBRANE
GALVANIZING. ALUM. THRESHOLD BELOW
PREFIN. ALUM. CLOSURE PREFIN. ALUM. CLOSURE ALIGNED WITH FACE OF
ALUM. THRESHOLD BELOW ALUM. THRESHOLD BELOW EXTERIOR CLADDING
19
W1A BELOW
19 TYP.
SELF-ADHESIVE MEMBRANE THERMAL BREAK THERMALLY BROKEN THERMALLY BROKEN
W1C THERMALLY BROKEN
ALUMINUM ENTRANCE ALUMINUM ENTRANCE
SEALANT AND BACKER ROD ALUMINUM ENTRANCE
DOOR DOOR
DOOR
THRESHOLD 19
2
INSULATED HOLLOW METAL DOOR IN W1B
19
PRESSED STEEL FRAME C/W WEATHERSTRIPPING
PLAN DETAIL: PRESSED STEEL FRAME DOOR JAMB, MASONRY WALL PLAN DETAIL: CURTAIN WALL SILL, LOWER LEVEL TYP. PLAN DETAIL: CURTAIN WALL JAMB, UPPER LEVEL TYP. PLAN DETAIL: CURTAIN WALL JAMB, ENTRY
5 Scale 1:5 6 Scale 1:5 7 Scale 1:5 8 Scale 1:5
--- ---
A --- ---
INTERIOR
C EXTERIOR --- ---
INTERIOR EXTERIOR INTERIOR EXTERIOR
EXTERIOR CLADDING EDGE OF GWB BEYOND
--- --- THERMALLY BROKEN EDGE OF CURTAIN WALL
INTERIOR EXTERIOR RUBBER BASE ALUMINUM ENTRANCE DOOR BEYOND
DOOR FRAME BEYOND THRESHOLD TO COVER 12mm RUBBER BASE EDGE OF CLADDING BEYOND
ASPHALT IMPREGNATED
METAL PLATE BEYOND FIBERBOARD CONTROL JOINT ALUMINUM THRESHOLD FULLY THRESHOLD TO COVER 12mm
SET IN SEALANT ASPHALT IMPREGNATED
12mm ASPHALT IMPREGNATED FIBERBOARD THERMALLY BROKEN FIBERBOARD CONTROL JOINT
CONTROL JOINT ALUMINUM ENTRANCE DOOR GALVANIZED METAL FLASHING
RUBBER BASE
INSULATED HOLLOW METAL DOOR C/W FOIL-FACED SELF-ADHERED MEMBRANE MEMBRANE FLASHING C/W
WEATHERSTRIPPING OVER TOP OF CONCRETE AT EXTERIOR END DAMS AND MEMBRANE
GUSSETS AT DOORSILL THERMALLY BROKEN
SOLDERED STAINLESS STEEL SILL PAN DOORS ON GRADE, TYPICAL. ALUMINUM ENTRANCE DOOR
CORNERS
FASTENED THROUGH END DAMS TO R.O. ON FOIL-FACED SELF-ADHERED 03 25 2014: Issued for Construction
THERMALLY BROKEN ALUMINUM GALVANIZED STEEL ANGLE ON
EITHER SIDE OF DOOR FRAME MEMBRANE OVER TOP OF 2 03 24 2014: Issued for Value Engineering
THRESHOLD FULLY SET IN SEALANT 12mm GALVANIZED METAL
FOIL-FACED SELF-ADHERED MEMBRANE OVER AND SEALED TO MEMBRANE CONCRETE AT EXTERIOR DOORS 1 12 09 2013: Issued for Addendum #3
SHIMS TYPICAL TO EXTERIOR 11 19 2013: Issued for Tender and B.P.
TOP OF CONCRETE AT EXTERIOR DOORS ON DOORS, SEE STRUCTURAL ON GRADE, TYPICAL.
GRADE, TYPICAL. GALVANIZED STEEL ANGLE ON 12mm 10 17 2013: 100% Complete - Issued for Client Review
F2 F3 PRECAST CONCRETE PAVERS THERMALLY-BROKEN ALUMINUM 08 16 2013: 99% Complete - Issued for Client Review
THERMALLY-BROKEN ALUMINUM THRESHOLD GALVANIZED METAL SHIMS TYPICAL TO ON PEDESTALS
98.00m THRESHOLD FULLY SET IN 07 31 2013: 95% COORDINATION
FULLY SET IN SEALANT EXTERIOR DOORS, SEE STRUCTURAL
T.O.SLAB - 2ND FLOOR SEALANT AND SEALED TO
ALIGN THERMAL BREAK WITH DOOR SWEEP MEMBRANE DATE ISSUE
WOOD DECK ON SLEEPERS,
SEE LANDSCAPE SEALED AND BOLTED REINFORCED CONCRETE
SLOPE 2% REINFORCED CONCRETE ON COMPACTED
94.00m CONNECTION ON COMPACTED GRAVEL
GRAVEL BASE, SEE STRUCTURAL CONCRETE-FACED
FFL - GROUND FLOOR F1 F1 SLOPE 2% BASE, SEE STRUCTURAL
94.00m INSULATION 94.00m
ESC
FFL - GROUND FLOOR FFL - GROUND FLOOR GALVANIZED STEEL ANGLE
76X51 GALVANIZED STEEL ANGLE ON 12mm ON 12mm GALVANIZED
GALVANIZED METAL DRAINAGE SHIMS TYPICAL
200
200
STRUCTURAL
SEAL MEMBRANE PENETRATION MEMBRANE
SEAL MEMBRANE
UBC ENGINEERING
PENETRATIONS
CONCRETE-FACED INSULATION
PENETRATION STUDENT CENTRE
CONCRETE-
97.655m
FACED
INSULATION T.O.PLYWOOD CONCRETE-FACED
INSULATION
FREE-DRAINING
FILL, SEE GEOTECH. FREE-DRAINING
150 FILL, SEE GEOTECH.
DOOR DETAILS
9
SECTION DETAIL: PRESSED STEEL FRAME DOOR SILL, MASONRY WALL
Scale 1:5 10
SECTION DETAIL: CURTAIN WALL SILL, LOWER LEVEL TYP.
Scale 1:5 11
SECTION DETAIL: CURTAIN WALL SILL, UPPER LEVEL TYP.
Scale 1:5 12
SECTION DETAIL: CURTAIN WALL SILL, ENTRY
Scale 1:5
A.602
1 POURED IN PLACE CONCRETE WALL
F.O. WORK
PLY. POINT
LINE OF STEEL PLATE ABOVE
PRESSED STL. DOOR FRAME FILLED FACE OF BRICK ABOVE
WITH SPRAY FOAM INSULATION LINE OF STEEL PLATE ABOVE
EXTERIOR W1A
EXTERIOR WALL METAL FASCIA FLASHING
169 ASSEMBLY AIR/MOISTURE BARRIER
19
59
25
A A A
19
100 50
401 - 134 Abbott Street
Vancouver, BC
Canada V6B 2K4
W1A t: 604-683-5060
EXTERIOR WALL GALVANIZED AND PAINTED e: info@urban-arts.ca
THIN-SET WALL TILE EPOXIED BOLTED PRESSED STEEL FRAME
ASSEMBLY OVER CEMENT CONNECTION C/W GROUTED SOLID
120 BOARD SEAL:
GALVANIZED AND PAINTED
WOMEN'S STAND-OFF SLEEVE
SHOWER HOLLOW METAL DOOR
PERFORATED ALUMINUM SHEET,
FOLDED ALONG ALL FOUR EDGES
WITH WELDED CORNERS,
GALVANIZED AND PAINTED
106
W2B SIM. W/ 75 EPS EXT. STORAGE
107 W2B SIM. 106
GARBAGE EXT. STORAGE
1
BRICK CORNER DETAIL -- W1A: BRICK VENEER + WOOD FRAMING PLAN DETAIL PLAN DETAIL
1 Scale 1:10 3 Scale 1:10 4 Scale 1:10
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
1 106 are for use on the specified project only and shall not be used otherwise
RED SALES
2 The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
9 SIM.
PLY.
F.O.
A.601 Do not scale drawings.
357
PLYWOOD BLOCKING LINE OF GWB
W1A EXTERIOR FOR MILLWORK ABOVE SCREEN HOLLOW METAL DOOR
WALL ASSEMBLY - REFER TO INT. ELEVS
FOR LOCATIONS PRESSED STEEL FRAME
1 GROUTED SOLID
120
EXTENT OF <W1A> A.601
218
FINISH ABOVE
FULL-HEIGHT GALV.
95
STL. ANGLE AT
TERMINATION OF
C
BRICK FINISH MDF SILL BELOW 100
LINE OF BRICK ABOVE ENTRY
7 SIM. W1B
A.601
LINE OF STEEL
PLATE ABOVE
B
GLULAM COLUMN
- SEE STRUCT.
DWGS.
F.O.
EXTEND
PLY.
THRESHOLD TO
EXTERIOR 7 FACE OF GWB
105
218
INT. STORAGE
A.602
SIM
C
RED SALES EXT. DETAIL -- W1C: ALUM. PANEL + WOOD FRAMING ENTRY/RED SALES WALL -- W1C: ALUM. PANEL + WOOD FRAMING PLAN DETAIL
5 Scale 1:10 6 Scale 1:10 8 Scale 1:10
2 100 12 13
ENTRY 11
PLY.
PLY.
F.O.
F.O.
70
CLEAR ANODIZED ALUM. ALIGN ASSEMBLY 105 1
BREAKSHAPE, CLIP 100 70 LINE OF TRUSS 'C'
MOUNTED OVER 1" RIGID
INT. STORAGE
19mm MDF, PAINTED FURR OUT WALL AS VERTICAL ABOVE
INSULATION BOARD 1 CL OF RWL RWL RWL REQUIRED FOR INSULATED RWL CONC. WALL
RETURN EIFS AT JAMB - SEE STRUCT. DWGS.
170
72
100
EXTERIOR 9mm REVEAL
C C
100
45-min. FRR @ 365
ELEVATOR SHAFT
- SEE SHEET G.103 P2B, SIM.
19
W2B
ELEV.SHAFT WALL: 1
W1B2 EXTERIOR P2B SIM. 76 MIN.
ELEVATOR ELEVATOR TYPE X GWB BOTH SIDES ON
WALL ASSEMBLY STRUCTURAL PLY ON W2B EXTERIOR WALL
WOOD FRAMING. SEE STRUCTURAL ASSEMBLY
PLAN DETAIL - GROUND FLOOR ELEVATOR PLAN DETAIL - GROUND FLOOR ELEVATOR PLAN DETAIL GROUND FLOOR DETAIL @ GL C/12 -- W2B: CEMENT PANEL + CONC.
9 Scale 1:10 10 Scale 1:10 11 Scale 1:10 12 Scale 1:10
102 103
2
PLY.
F.O.
EXTEND VAPOUR RETARDER AND INFILL W/ BATT FIRST YEAR FLEX ROOM 03 25 2014: Issued for Construction
1 557
INSULATION FOR 300 TO MAKE CONTINUOUS W/
ADJACENT WALL BELOW WINDOW
1 03 24 2014: Issued for Value Engineering
11 19 2013: Issued for Tender and B.P.
ELECTRICAL RISERS LOCATED 3 102 10 17 2013: 100% Complete - Issued for Client Review
PER ELECTRICAL, FIRESTOP FIRST YEAR 6 08 16 2013: 99% Complete - Issued for Client Review
102 FLOOR PENETRATIONS, TYP. 07 31 2013: 95% Coordination
W1B2 FIRST YEAR 9 MM REVEAL PT. FIN.
WOOD COLUMN DATE ISSUE
TO MATCH GWB (BOTH SIDES) P1 SIM.
W1B EXTERIOR WALL F F LINE OF SILL BELOW
6 SIM. ASSEMBLY BELOW
300
ESC
A.601 RAIN WATER LEADER
F.O. WALL THICKNESS TO
6 SIM. ACCOMODATE THROW OF
PLY.
58
F.O.
UBC ENGINEERING
PLY. G G G STUDENT CENTRE
96
153
13
PLAN DETAIL - GROUND FLOOR ELEVATOR
Scale 1:10 14
GROUND FLOOR FEATURE WALL CORNER -- W2A: C.P. + WD. FRAMING
Scale 1:10 15
CW JAMB @ FEATURE WALL & ELECTRICAL RISER
Scale 1:10 16
PLAN DETAIL
Scale 1:10
A.604
2 12 13
10 HATCH DENOTES EXTENT
OF NON-COMBUSTIBLE 325
105 RIGID MINERAL FIBRE
W2B-NC 1 INSULATION W2B-NC 1 EXTEND W2B EPS
357 EXTEND W2B EPS
INSULATION TO INSULATION TO
PARAPET CAP BELOW OUTSIDE CORNER, TYP.
51 OUTSIDE CORNER, TYP.
PLY.
F.O.
METAL GUARD BELOW
PLY.
- SEE STRUCT. DWGS.
F.O.
W1B W2B
36
F.O.
PLY. B B
95
W2B 401 - 134 Abbott Street
LINE OF CURTAIN WALL ANOD. ALUM. CLOSURE, TYP.
BELOW
Vancouver, BC
19
Canada V6B 2K4
384
KNIFE PLATE t: 604-683-5060
SPRINKLER RISER 215
e: info@urban-arts.ca
CURTAIN WALL FRAME + GLAZING ELECTRICAL RISERS STUDY LOUNGE
- SEE ELECT. DWGS.
C SEAL:
GLULAM COLUMN 12mm PLYWOOD TO 2440 AFF
- SEE STRUCT. DWGS. 215 EAST AND SOUTH ELEVATION
LINE OF BRICK BELOW
W1B STUDY LOUNGE FOR MOUNTING CLASS PHOTOS
CONTINUOUS ALUM. CLOSURE RETAIN 89mm CLEARANCE TO
CLIP AT JAMBS, TYP. 100 CONC. WALL
ENTRY BELOW
19
9 SPRINKLER
A.601
CORNER DETAIL @ GL C/2 -- W1C: ALUM. PANEL + WOOD FRAME CORNER DETAIL @ RM 215 -- W2B: CEMENT PANEL + CONC. CORNER DETAIL @ RM 215 -- W2B: CEMENT PANEL + CONC.
1 Scale: 1:10 3 Scale: 1:10 4 Scale: 1:10
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
2 10 12 13
without written permission of this office.
The Contractor shall check and verify all dimensions and report any
PLY.
PLY.
F.O.
PLY.
F.O.
200 357 218 Do not scale drawings.
81
F.O. C
PLY.
F.O.
100
PLY.
300
9mm REVEAL
CURTAIN WALL 1
45-min. FRR @
384
83
ELEVATOR SHAFT 200 WRAP STUCCO AROUND
139
TYPICAL WINDOW SILL ALIGN JAMB DETAIL @ 8
- SEE SHEET G.103 WAITING CORNER TO WINDOW JAMB
W2B CORNER (SIM.) A.601
FACE OF WALL BELOW W1C EXTERIOR WALL
76
SHOWN DASHED ASSEMBLY BELOW
ELEV.SHAFT WALL:
ELEVATOR
SHAFT
ELEVATOR P2B 1-HR. FRR
INTERIOR WALL
C
76
W1B2 EXTERIOR SHAFT LINE OF BLIND RECESS ABOVE
ASSEMBLY WOOD COLUMN
WALL ASSEMBLY
1
LAM. SAFETY GLASS ON STANDOFF CL OF
TRUSS
BELOW
EDGE OF FLOOR BELOW
PLAN DETAIL PLAN DETAIL: ELEVATOR + DONOR WALL PLAN DETAIL @ TRUSS/CURTAIN WALL GL C + 1000 MM AFF SECOND FLOOR DETAIL @ GL C-12 -- W2B: CEMENT PANEL + CONC.
5 Scale: 1:10 6 Scale: 1:10 7 Scale: 1:10 8 Scale: 1:10
12 13
1
LINE OF GWB BELOW
W1B2
214 W1C EXTERIOR WALL
ELEVATOR ASSEMBLY BELOW
STUDY 152
W1C SHAFT
BLIND RECESS ABOVE
9 MM REVEAL BOTH SIDES
PAINT PLY TO MATCH GWB.
P2B, SIM.
58
D
E
139
F.O.
45
3
03 25 2014: Issued for Construction
1 03 24 2014: Issued for Value Engineering
1 1' 213 LINE OF TRUSS BELOW
11
10
19
17
2013:
2013:
Issued for Tender and B.P.
100% Complete - Issued for Client Review
CONF./STUDY 08 16 2013: 99% Complete - Issued for Client Review
ELECTRICAL PANELS BLIND RECESS ABOVE 07 31 2013: 95% Coordination
- SEE ELECT. DWGS. LINE OF WOOD FRAMING
F ELECTRICAL RISERS
F BELOW DATE ISSUE
ESC
VP TRUSS + GWB
11 TYP. CW JAMB
RWL
A.601 DETAIL @ W1C CORNER
F.O.
G PLY. G UBC ENGINEERING
STUDENT CENTRE
153
F.O. PLY.
F.O.
H
PLY.
PLY.
F.O.
RETURN EIFS TO
WINDOW JAMB 9 SIM.
19
PLY.
LAP AND SEAL
F.O.
PANEL JOINT WITH GRIDLINE-12
AIR / MOISTURE BARRIER
29 124 CONTINUE GWB + V.B. EXTERIOR PLAN
455
STUD
F.O.
- SECOND FLOOR
12 13
13
PLAN DETAIL - 2ND FLOOR FEATURE WALL
Scale: 1:10 14
PLAN DETAIL - 2ND FLOOR FEATURE WALL
Scale: 1:10 16
SE CORNER @ TRUSS C -- W1C: ALUM. PANEL + WOOD FRAMING
Scale: 1:10
A.605
LINE OF FOOTING BELOW
450
Canada V6B 2K4
t: 604-683-5060
e: info@urban-arts.ca
SEAL:
75
380
CL OF RWL RWL
165
121 122
RED SALES STORAGE
WOOD DOOR IN
STOREFRONT FRAME
PLAN DETAIL PLAN DETAIL: RED SALES DOOR PLAN DETAIL PLAN DETAIL
1 Scale 1:5 2 Scale 1:10 3 Scale 1:5 4 Scale 1:5
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
without written permission of this office.
10 The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
CL OF
3 5 TRUSS ABOVE Do not scale drawings.
51
P.LAM BOTH SIDES WHERE EXPOSED FACE OF TRUSS ABOVE
38 MM APPLE PLY
INSIDE FACE OF WALL ABOVE
85
51
51
P.LAM BOTH SIDES
72 64
38 LINE OF SOFFIT ABOVE 38 LINE OF SOFFIT ABOVE 101
EXPOSED PLY EDGE COMMONS
TYP. SERVICE SOFFIT / DOOR FRAME
C C TYP. BOTH SIDES OF OPENING
C
101
COMMONS
PLAN DETAIL PLAN DETAIL: RED SALES DOOR PLAN DETAIL: WASHROOM FOYER JAMB PLAN DETAIL: CONCRETE WALL AT ENTRY TO HALL 124
5 Scale 1:5 6 Scale 1:10 7 Scale 1:10 8 Scale 1:10
101
D COMMONS
D
PLAN DETAIL PLAN DETAIL: 102/103 WALL PLAN DETAIL PLAN DETAIL
9 Scale 1:5 10 Scale 1:10 11 Scale 1:5 12 Scale 1:5
19
CEILING ABOVE
19MM PLY ON 6 MM CAULK AND SHIM SPACE
213 UBC ENGINEERING
50 CONF./STUDY
FURRING TO SUIT (RECESS CAULK), TYP. 211 STUDENT CENTRE
G 210 PRINT LINE OF
TRUSS BELOW
METAL EDGE TRIM
GROUP STUDY
204 TACKBOARD P2
205
WC MULTI-PURPOSE
INTERIOR PLAN DETAILS
13
PLAN DETAIL
Scale 1:5 14
PLAN DETAIL
Scale 1:10 15
PLAN DETAIL: VENDING/RECYLING AREA
Scale 1:10 16
PLAN DETAIL
Scale 1:5
A.606
5 4 3 2 D
A.607
7
1220 X 1635 PERF. METAL PANELS BOLTED TO GALV. STEEL
STEEL BEAMS, SEE STRUCTURAL ANGLES BEYOND SEE STRUCTURAL
1200 X 1200 VENT: SEE MECH CONTINUOUS METAL FLASHING OVER BEAM AND PANELS 1200 X 1200 VENT: SEE MECH
100
ALIGN FLASHING SEAMS WITH PANEL REVEALS AS SHOWN
TOP OF FRAMING TOP OF FRAMING
100
103.48 103.48
1730
1730
t: 604-683-5060
EIFS EIFS EIFS EIFS EIFS EIFS
PERF. METAL PANELS e: info@urban-arts.ca
SEAL:
2 2
VARIES
101.70 OPEN TO BEYOND
VARIES
ROOFTOP MECH ENCLOSURE EAST ELEVATION ROOFTOP MECH. ENCLOSURE SOUTH ELEVATION
1 Scale 1:20 2 Scale 1:20
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
2 3 4 5 4 152 X152 HSS 3 without written permission of this office.
A.607 A.607 LINE OF FLASHING The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
8 9 76 X 76 HSS WELDED 12MM BARRELL
GATE FRAME HINGES (3) WELDED Do not scale drawings.
TO STRUCTURAL
STEEL ANGLE STEEL ANGLE AND
GATE FRAME
100
STEEL ANGLE
SEE STRUCTURAL
PERF. METAL PANELS
1730
100
EIFS
PERF. METAL PANELS
865 O.C.
2
ROOFTOP MECH. ENCLOSURE NORTH ELEVATION INTERIOR ELEVATION IN ROOFTOP MECH. ENCLOSURE
3 Scale 1:20 4 Scale 1:20
40
40
W1B 2 TOP OF PARAPET FRAMING 103.48 T.O. LANTERN TOP OF PARAPET FRAMING T.O. LANTERN
100
100
100
89
100
T.O. LANTERN 103.48 103.48
100
FLASHING BEYOND FLASHING BEYOND
150
150
VENT LOUVRE
12
TYP. ALUM FLASHING W/ DRIP EDGE, LAP
152X152 HSS BEAM BELOW AND ABOVE: CONTINUOUS
CONTINUOUS OVER ALUM. VENT FRAME
SEE STRUCTURAL ROD
ROD AND
AND CAULK
CAULK ALUM. FRAME FASTENED TO PARAPET
12
2 2 FRAMING, MEMBRANE CONTINUOUS BEHIND
MDF
MDF SILL
SILL BELOW
BELOW
LINE OF BEAM BELOW AND ABOVE
TYP. FASTENING LOCATION
FOR HARDWARE REFER TO TYP. PERF. METAL PANEL ON
REFER TO STRUCTURAL FOR STEEL 16 MM PLY AT VERTICAL HSS ONLY ON
PRODUCT INSTALLATION ALUM. BACKING AT FRAMING
PLATE CONNECTION DETAIL 76MM X 76MM HSS GATE FRAME
GUIDELINES FOR DIMENSIONS
LAP
LAP MEMBRANE
MEMBRANE AND
AND
MOISTURE BARRIER CONTINUOUS
VAPOUR
VAPOUR BARRIER
BARRIER
UNDER GALV. STEEL ANGLE
BEHIND
BEHIND MDF
MDF TRIM
TRIM STEEL T-SECTION BEYOND VERTICAL HSS BEYOND
SEE STRUCTURAL
W1B
12
PLATE CONNECTION DETAIL 1
MDF SILL, PT. FIN.
6MM STEEL PLATE WELDED TO ISSUE
TYP STEEL ANGLE
D
VENT, SEE MECH.
STEEL ANGLE WELDING
TO BEAM BEYOND
85
LINE
LINE OF
OF BEAM
BEAM BELOW
BELOW AND
AND ABOVE
ABOVE LINE OF STUCCO
152X152 HSS BEAM BELOW AND ABOVE:
ESC
LINE OF STUCCO BEYOND BEYOND ALUM. VENT FRAME, PROVIDE NEOPRENE
SEE STRUCTURAL STEEL ANGLE WELDED TO T.O. PARAPET GASKET B/T FRAME AND STEEL ANGLE
19
19
6
PLAN DETAIL AT ROOFTOP MECH. ENCLOSURE GATE
Scale 1:5
A.607
WRAP ROOFING MEMBRANE SEALANT BETWEEN NLT
UP + OVER CURB H AND TOP PLATE OF WALLS,
PRE-FINISHED METAL CAP
G F E TYP. THROUGHOUT
FLASHING C/W CLEAT + HEMMED 6 PROVIDE CONDUIT SPACE WHERE C
DRIP EDGES 1 REQUIRED TYP. 2ND LEVEL ROOF
DRAIN SPRINKLER LINE
T/O PARAPET FRAMING
52
SEALANT BETWEEN NLT AND SPRINKLERS TO EXTEND THROUGH
GLULAM BEAM 300
101.68m TOP PLATE OF WALLS, BEAM @ PREDRILLED HOLES CENTRED
TYP. THROUGHOUT IN STRUCTURAL BAYS, TYPICAL. SEE
320
SLOPE 1:50 TYP. R1 GREEN ROOF ALTERNATE PRICE WALL SECTION 3-A.402
BUILT-UP PARAPET
- SEE STRUCT. DWGS.
25
WRAP AIR/MOISTURE MEMBRANE
OVER PLY. + NLT FRAMING AND
SEAL TO ROOFING MEMBRANE
152
U/S ROOF STRUCTURE 401 - 134 Abbott Street
101.20m Vancouver, BC
100
100
MDF, PAINTED, VALENCE FOR Canada V6B 2K4
PRE-FINISHED METAL 150mm SQ. ROLLER BLIND BOX t: 604-683-5060
239
FASCIA FLASHING C/W SPRINKLER LINE BETWEEN e: info@urban-arts.ca
100
100
CLEAT + DRIP EDGES BLINDS AT MULLIONS
SEAL:
R1 ROOF ASSEMBLY
ALIGN BOTTOM EDGE W/
GWB @ WINDOW OPENING
255
169
38
2 SPRINKLER WATER CURTAIN, ALIGN
TYP. W1C U/S OF SPRINKLER HEAD W/ TOP OF
A.601 HEAD DETAIL ROOF DRAIN SLOPE
MULLION, TYPICAL
1:100, SEE MECHANICAL
175
RECESSED LIGHT FIXTURES MDFMDF
PT. FIN.
PT. FIN. 221
CL OF SPRINKLER TO GLASS
175
C3 CEILING ASSEMBLY REFER TO A.008 ROOM FINISH NOTES:
SCHEDULE 95 117 64 100±
This drawing is the property of Urban Arts Architecture and may not be
38
MDF PT. FIN. reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
without written permission of this office.
RETURN MDF BEHIND STOREFRONT
FRAME The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
SECTION DETAIL: TYPICAL ROOF PARAPET SECTION DETAIL: TYP. CW + ROOF INTERFACE @ OFFICE SECTION DETAIL: DROPPED CEILING AND TYP. ROOF DRAIN SECTION DETAIL: TYPICAL TRANSFER VENT SECTION DETAIL: CURTAIN WALL AT GL 'C' @ WATER CURTAIN Do not scale drawings.
1 Scale 1:10 2 Scale 1:10 3 Scale 1:10 4 Scale 1:10 13 Scale 1:10
H G F ACOUSTIC PANEL
207
(CASH ALLOWANCE)
A
PRES. OFFICE EXTEND TYP. MDF SILL TO
T/O ACOUSTIC PANEL
10 TYP. W1C
A.601 SILL DETAIL 1
GUARD RAIL
RAINWATER LEADER FROM
T/O WINDOW SILL (2nd Floor) UPPER ROOF, FIX TO PLANTER.
38
38
PROVIDE 200MM STRIPS OF 38MM EITHER END OF PLANTER, SLOPED GALVANIZED STEEL PLATE CAP
RIGID INSULATION TO EITHER 2 CONTINUOUS, WELDED TO STEEL (PTD.) BOLTED TO PARAPET, REFER TO
305
SIDE OF SPRINKLER LINE. UPRIGHTS, GALVANIZED AND PAINTED DETAIL 1-A.507 FOR DIMENSIONS
WATER SUPPLY + RETURN PREDRILL HOLES AT BEAMS 11 STEEL PAVER
203mm DEEP - SEE MECH. DWGS. ROOF DECK PLANTER
200 MIN.
TRK VENT WHERE REQUIRED RETENTION STRIP,
A.601 - SEE LNDSCP. DWGS. CONTINUOUS,
- SEE MECH. DWGS. F2 FLOOR ASSEMBLY CONTINUOUS CAULK B/T STEEL
35
38X38 K.D. CEDAR SLATS ON TYP. W1B WELDED TO STEEL 12 PLATE PARAPET CAP AND BRICK
SEAL V.B. TO TOP OF NLT AND TO NOTE: BLINDS @ FLEX UPRIGHTS, 1
BOTTOM OF FRAMING AT CONC. ROOM ONLY BLACK FILTER CLOTH ON SILL DETAIL
W1C EXTERIOR 19X89 STRAPPING W/ ACOUSTIC GALVANIZED AND 98.09m
WALL ASSEMBLY TOPPING, CONTINUOUS SEAL
100
12 MAX.
OVER PARAPET FRAMING/BLOCKING
WRAP AIR BARRIER UP AND OVER
PARAPET FRAMING
FLUORESCENT LINEAR FIXTURES T/O ROOF CONTINUOUS CAULK B/T ALUM. FLASHING
U/S NLT STRUCTURE
910
12 5 EQ. 19
97.74m 152 CEILING FRAMING TO SUIT
SHEATHING T/O ROOF PLYWOOD SHEATHING
PROVIDE 2x6 FRAMED 97.655m 97.655m
WALL C/W PLY. BOTH RECESSED FIXTURE
2 RIVER ROCK SPLASH PAD IN FILL 152MM WIDE GRAVEL STRIP TO U/S OF
445
152
225
REINFORCED PARAPET, TYP.
- SEE STRUCT. DWGS.
U/S SOFFIT TYP.
51
6
97.30m 50 C4
ALUM. PANEL SOFFIT KNIFE PLATE CONNECTION
EDGE, TYP. 8 25 51 x 25 BRUSHED ALUMINUM TRIM ON 115 W1A EXTERIOR WALL
INSULATED BOX @ CONTINUOUS 8mm SPACER AT ALL - SEE STRUCT. DWGS.
ASSEMBLY
50mm PRE-FINISHED PERFORATED LIGHT FIXTURE AT SIDES OF COLUM WHERE PENETRATES NOTCH GWB OVER BOLT HEADS.
CONTINUOUS METAL VENT STRIP EXTERIOR, PROVIDE THROUGH T+G CEILING
LINE OF COLUMN BEYOND
MIN. CLEARANCE TRIM TO MATCH T+G SOFFIT
9 MM REVEAL, TYP. FROM INSULATION AS
PER BCBC TRIM AND T+G SOFFIT
S1 SOFFIT ASSEMBLY 3
TYP. W1B BEYOND BLIND RECESS
FILL ALL VOIDS W/ INSULATION TO AVOID HEAD DETAIL A.601
SPINKLERING REQUIREMENTS
SECTION DETAIL: TRICKLE VENT @ 2ND FLOOR SECTION DETAIL: DROPPED CEILING + WINDOW HEAD SECTION DETAIL: ROOF DECK @ UPPER ATRIUM SECTION DETAIL: ROOF DECK @ PARAPET
5 Scale 1:10 6 Scale 1:10 7 Scale 1:10 8 Scale 1:10
FLASHING W/ DRIP CL
EDGE OVER LOUVER 13 PLY SURROUND, AT TRICKLE 19 x 13 RABBET EDGE OF CONCRETE FOUNDATION
AND CLIP ANGLE VENTS, ON 2x FRAMING INFILL, TYP. 260 WALL FOR OVERLAP OF SHEATHING, TYPICAL 03 25 2014: Issued for Construction
GWB, PT. FIN. 2 03 24 2014: Issued for Value Engineering
PROVIDE ADHESIVE MEMBRANE TO SEAL A.M.
12 09 2013: Issued for Addendum #3
160
TRICKLE VENT, FOAM AND SEAL BARRIER TO FLASHING OVER STL. ANGLE
1
LAP AND CONTINUOUS SEAL AT ALL SIDES, TYP. W1B 11 19 2013: Issued for Tender and B.P.
INTEGRAL METAL AIR/MOISTURE BARRIER AND GALVANIZED STEEL ANGLE BOLTED TO 10 17 2013: 100% Complete - Issued for Client Review
19 x 13 RABBET EDGE OF
BACKING TO EXTEND VAPOUR RETARDER AT ALL CONCRETE FOUNDATION WALL 08 16 2013: 99% Complete - Issued for Client Review
CONCRETE FOUNDATION LAP VAPOUR RETARDER
TO TRV OPENING, SIDES, TYPICAL 2x6 WOOD DECK ON CONCRETE PILES, SEE 07 31 2013: 95% Coordination
WALL FOR OVERLAP OF UP FOUNDATION WALL WEEP HOLES
LANDSCAPE. COORDINATE LOCATION OF 2 SHEATHING, TYPICAL AND UNDER SILL, TYPICAL
WEEP HOLE, 300 PILES WITH FOUNDATION DRAINAGE WORK 51mm CONCRETE-FACED DATE ISSUE
PROVIDE ADHESIVE
MM O.C. CONTINUOUS SPRAY - SEE LANDSCAPE FASTEN GWB TO INSULATED PANELS OVER
MEMBRANE TO SEAL A.M.
305 +/- (SEE MECH)
336 FOAM, ALL SIDES BARRIER TO FLASHING CONCRETE BASE, 51mm XPS INSULATION OVER
TRICKLE VENT SUPPLY AND RETURN PIPING, SHIM AS REQUIRED, FLUID-APPLIED DAMPPROOFING
COORDINATE MECH. W/ 2x3 FURRING SPACE ROD AND SEALANT TYPICAL TO 600mm BELOW GRADE
152
152
ESC
SLOPE 2% F1 - TYP. @ W1A FOUNDATIONS
T/O GROUND FLOOR TOPPING 94.00m
51
TRICKLE VENT
HOT WATER SUPPLY
- SEE MECH. DWGS. 94.00m T/O GROUND FLOOR TOPPING
ADMIXTURE PLANTING BED, SEE LANDSCAPE
INTERIOR LOUVER AND WATERPROOFING IN UBC ENGINEERING
760
LANDSCAPE UNIT
TRIM, COLOUR TO BE CONCRETE MIX @
SELECTED BY ELEVATOR PIT (HATCHED)
PAVERS, SEE
LANDSCAPE AND CIVIL PERFORATED PERIMETER DRAIN IN
STUDENT CENTRE
CONSULTANT FROM GRAVEL C/W FILTER CLOTH, TYP.
FULL COLOUR RANGE ELEVATOR PIT - SEE MECH. DWGS.
INTEGRAL METAL 51mm CONCRETE-FACED
600
BE APPROVED PRIOR TO
SIDES, TYPICAL DAMPPROOFING TO
WRAP AIR BARRIER FOOTING BEYOND SHOWN FORMING OF ELEVATOR PIT
TRANSITION MEMBRANE DASHED 600mm BELOW GRADE.
GWB, PT. FIN. 200
CONTINUOUS TO
CONCRETE FACE AND REFER TO STRUCTURAL
SEE STRUCTURAL
51mm XPS INSULATION REFER TO STRUCTURAL SECTION DETAILS
152
9
SECTION DETAIL: TRICKLE VENT @ GROUND FLOOR
Scale 1:5 10
SECTION DETAIL: TRICKLE VENT @ GROUND FLOOR
Scale 1:10 11
SECTION DETAIL: FOUNDATION WALL @ ELEVATOR PIT
Scale 1:10 12
SECTION DETAIL: TYP. FOUNDATION @ W1A WALL
Scale 1:10
A.608
12
B H 12 TURN ROOF MEMBRANE OVER PARAPET AND
BUILT-UP ROOFING AS SHOWN. REFER TO
1 SCUPPER
MEMBRANE
MANUFACTURER'S REQUIREMENTS FOR FLASHING
101.68m SEALANT BETWEEN NLT AND 101.68m SEALANT BETWEEN NLT AND INTERMEDIATE FASTENERS AND SEAM DETAILS.
MEMBRANE FLASHING
SEALANT BETWEEN NLT AND TOP PLATE OF WALLS, TYP. SPRINKLER LINE AT TOP PLATE OF WALLS, TYP. OVER ROOF MEMBRANE
TOP PLATE OF WALLS, TYP.
T/O ROOF PARAPET FRAMING T/O ROOF PARAPET FRAMING CAULKING SEALANT ALL
THROUGHOUT PREDRILLED HOLES THROUGHOUT R1 1:50 TYP.
THROUGHOUT R1 IN TRUSS SIDES AT SCUPPER AND
38
R1 GREEN ROOF SEPARATE PRICE EIFS, TYPICAL
235 +/-
Vancouver, BC
TYP. PRE-FINISHED METAL
REVEAL 2 Canada V6B 2K4
SPRINKLER LINE: SEALANT OR TAPE TYP. W1C RAINWATER LEADER
t: 604-683-5060
19
PENETRATIONS THROUGH VAPOUR A.601 HEAD DETAIL
EXTERIOR LIGHT FIXTURE, e: info@urban-arts.ca
RETARDER AND AIR / MOISTURE ROD AND SEALANT
SEE ELECTRICAL.
BARRIER, TYP. ALIGN WITH FLASHING
COORDINATE MOUNTING
HEIGHT AND LOCATION FASCIA OVER WINDOWS, TYP. 13 EXTERIOR GRADE PLYWOOD SEAL:
WITH CONSULTANT PRIOR SURROUND TO LOUVER HEAD,
PRE-FINISHED METAL REVEAL TRUSS TOP ± 64 SILL AND JAMBS, TYPICAL
TO INSTALLATION C/W SIDEWALL SPRINKLER CHORD
C3 C3
W1C EXTERIOR MECHANICAL LOUVER,
WALL ASSEMBLY RECESS FOR REFER TO MECHANICAL
150mm SQ. DRAWINGS
SEALANT OR GASKET TO PROVIDE AIR C3 CEILING ASSEMBLY
ROLLER BLIND
BARRIER CONTINUITY FROM AIR /
BOX TURN ROOF MEMBRANE OVER
MOISTURE MEMBRANE TO UNDERSIDE
FACE OF
P.LAM. FINISH LOUVER SILL AT LOCATIONS OF
STUDS
OF PLYWOOD
200
1 ON PLY. TRIM MECHANICAL LOUVERS, TYPICAL
TRUSS BEYOND 301 R1
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
1 are for use on the specified project only and shall not be used otherwise
without written permission of this office.
The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
SECTION DETAIL: NLT SOFFIT AT W2B ASSEMBLY SECTION DETAIL: NLT SOFFIT AT W1C ASSEMLY SECTION DETAIL: NLT SOFFIT / CURTAIN WALL AT TRUSS SECTION DETAIL: ELEVATOR SHAFT PARAPET
1 Scale 1:10 2 Scale 1:10 3 Scale 1:10 4 Scale 1:10
E' 12 D
10 TYP. W1C T/O WINDOW SILL (2nd Floor)
EXTEND MDF A.601 SILL DETAIL
SILL (PTD.) 98.76m
MDF PT. FINISH ABOVE
TRV LOCATIONS ONLY
BOTTOM TRUSS
W1C
CHORD TRUSS PERFORATED
BEYOND
629
MDF PANEL @
TRK VENT 1
100
F2 F2 F2 F2
98.00m T/O SECOND FLOOR TOPPING
1
FFL - SECOND FLOOR 98.00m
S1 S1 S1 C4
C4 WALL HEAD CENTERED IN
INSECT SCREEN ADDITIONAL FRAMING EXTEND AIR / MOISTURE ALUM. PANEL
PREFINISHED METAL REVEAL, TYP.
+ STRAPS REQUIRED BARRIER AROUND PARAPET SOFFIT TRIM SHAPE
3 TYP. W1C @ CURTAIN WALL AND SEL TO AIR / MOISTURE
- SEE STRUCT. DWGS. BARRIER AT U/S OF NLT TYP. PRE-FINISHED
A.601 HEAD DETAIL
METAL REVEAL
H C4 INTERIOR SOFFIT
SECTION DETAIL: SOFFIT DETAIL @ COMMONS ANNEX SECTION DETAIL: W1C WALL + SOFFIT SECTION DETAIL: 2nd LEVEL TRICKLE VENT @ TRUSS SECTION DETAIL: CURTAIN WALL + INTERIOR SOFFIT @ W1C
5 Scale 1:10 6 Scale 1:10 7 Scale 1:10 8 Scale 1:10
1
1
94.00m
ESC
94.00m
T/O GROUND FLOOR TOPPING
SEE STRUCTURAL
BOTTOM OF FOOTING
REFER TO STRUCTURAL
SECTION DETAILS
B D
F
9
SECTION DETAIL: FOUNDATION @ EXTERIOR STORAGE
Scale 1:10 10
SECTION DETAIL - TYP. INTERIOR FOOTING
Scale 1:10 11
SECTION DETAIL: EXTERIOR FOOTING
Scale 1:10 12
SECTION DETAIL: FOUNDATION @ W1B
Scale 1:10
A.609
ENGINEERING STUDENT CENTRE
ADDENDUM 4 2013 12 11
GWB, PT.
BEYOND 8
SEE 5/A706 FOR ELEVATOR ELEVATION TYP. COLUMN A.505
GLASS PANEL
FIRST YEAR
RED SALES
GWB, PT. 4
ENTRY DASHBOARD OPEN GWB, PT. 1 SERVERY BAR
FIRE
FIRE ALARM SEE ELEC. TO W/C BEYOND HALL BEYOND HALL FIRE ALARM FIRE
FLEX
1 BEYOND
A.801
FINISHED FLOOR B1
B1 B1 B1 B1 B1 B1
TYP. ROOM SIGN TYP. SERVICE SOFTI/ TYP. COLUMN, CLR. FIN. WITH
100 NORTH ENTRY ELEVATION 100 ENTRY WEST ELEVATION 100 ENTRY AND 101 COMMONS EAST
122
EMERGENCY W/C SIGN
1 Scale 1:50 2 Scale 1:50 3 Scale 1:50
LIGHT DOOR FRAME STEEL PL. BASE, PT. FIN. NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
without written permission of this office.
The Contractor shall check and verify all dimensions and report any
8 5 discrepancies before proceeding.
A.801 A.801
SLAT WALL
P.LAM MIRROR
M121-2
M121-3
P.LAM
1
7 A.801
200
1220
P.LAM MW 121-3 6 P.LAM
A.801
A.801 GWB, PT. 1
760
D TRV GWB, PT. D D D MW 121-2
FINISHED FLOOR
B2 B1 B2 B1 B1 B1 B2 B1 FINISHED FLOOR
THERMOSTAT THERMOSTAT
CO2 CONTROLS AND CO2 CONTROLS AND
HUMISTATE
121
HUMISTATE
121 RED SALES NORTH ELEV. 121 RED SALES EAST ELEVATION 121 RED SALES SOUTH ELEVATION 121 RED SALES WEST ELEV. 104 COMMONS ANNEX SOUTH
4 Scale 1:50 5 Scale 1:50 6 Scale 1:50 7 Scale 1:50
21 Scale 1:50
METAL TRIM
2490 AFF 2490 AFF
104 COMMONS ANNEX WEST 102 1ST YEAR NORTH ELEVATION 102 1ST YEAR EAST ELEVATION
22
102
8 9 102 1ST YEAR SOUTH ELEVATION 102 1ST YEAR WEST ELEVATION
Scale 1:50 Scale 1:50 Scale 1:50 10 Scale 1:50 11 Scale 1:50
3740 AFF
SLIDER TRACK RECESSED INTO NLT STRUCTURE SLIDER TRACK RECESSED INTO NLT STRUCTURE
3675 AFF
CEILING MOUNTED
EXIT SIGN
RBL TYP. MDF,
MDF,TRV
TRVPANEL
PANEL RBL TYP. RBL TYP.
3300 AFF 3300 AFF
EXIT RBL
GWB, PT. 1
METAL TRIM
2490 AFF 2490 AFF
SLIDING WOOD DOORS
ALIGN WITH WOOD
CEILING ABOVE
POWER
POWER AND
AND ACCOUSTIC PANEL ACCOUSTIC PANEL ACCOUSTIC PANEL
GWB, PT. 1
MDF, PT. COMM.
COMM.FOR
FORTVTV GWB PT. 1
TV
N.I.C.
1600
PWC
101
12
103 FLEX ROOM NORTH ELEVATION
Scale 1:50
13
103 FLEX ROOM EAST ELEVATION
Scale 1:50 14
103 FLEX ROOM SOUTH ELEVATION
Scale 1:50 15
103 FLEX ROOM WEST ELEVATION
Scale 1:50
10
08
07
18
16
31
2013:
2013:
2013:
100% - Issued for Client Review
99% Complete - Issued for Client Review
95% Coordination
07 22 2013: Issued to Consultants
06 13 2013: Progress Set
05 14 2013: Issued to Consultants
DATE ISSUE
ESC
SEE 1/A.802 FOR 5
FIRE ALARM BELL EMERGENCY LIGHT SEE 5/A.803
SERVERY BEYOND A.803
CORNER GUARD CEILING CEILING CORNER GUARD sim. CORNER GUARD 2750 AFF
2750 AFF ANNUNCIATOR MOUNTED MOUNTED
PANEL, SEE ELEC. EXIT SIGN EXIT SIGN 2490 AFF
2490 AFF
EXIT MW 124-1
OPEN
SHELF
UBC ENGINEERING
ELEC.
PANEL
P.LAM
STUDENT CENTRE
GWB, PT.1 GWB, PT. (SEE OPEN TO BAR P.LAM P.LAM OPEN TO BAR GWB, PT.1
ON GWB
PLAM GWB PT.1 GWB, PT. 1 ELEC.) BEYOND
FIRE FIRE
FIRE ALARM VENDING
PULL STATION MACHINE
GWB, PT. 1
BOTTLE RECYCLING MDF, PT.
FILLER
FINISHED FLOOR
B1 B1 B1 B1 B1 B1 B1 FINISHED FLOOR
INTERIOR
ELEVATIONS
110 CAFE / HALL NORTH ELEVATION 110 HALL EAST ELEVATION 110 HALL SOUTH ELEVATION 124 HALL NORTH ELEVATION 124 HALL SOUTH ELEVATION
16 Scale 1:50 17 Scale 1:50 18 Scale 1:50 19 Scale 1:50 20 Scale 1:50
A.700
3310 AFF 3310 AFF
PT. FIN. PT. FIN. PT. FIN. PT. FIN. PT. FIN. PT. FIN.
PLYWOOD ON ELEC. PLYWOOD ON FIRE ALARM ELEC. PLYWOOD PLYWOOD ON PLYWOOD PLYWOOD ON
GWB PANELS GWB CONTROL PANEL ON GWB GWB ON GWB GWB
PANEL
401 - 134 Abbott Street
Vancouver, BC
PT. FIN. PT FIN.
Canada V6B 2K4
PLYWOOD ON PLYWOOD ON t: 604-683-5060
GWB GWB
FINISHED FLOOR
e: info@urban-arts.ca
B1 B1 B1 B1 B1 B1 B1 B1 FINISHED FLOOR
SEAL:
111 ELEC. ROOM SOUTH ELEV. 111 ELEC. ROOM WEST ELEV. 113 COMM. NORTH ELEV. 113 COMM. EAST ELEV. 113 COMM. SOUTH ELEV. 113 COMM. WEST ELEVATION
1
111 ELEC. ROOM NORTH ELEV.
Scale 1:50 2
111 ELEC. ROOM EAST ELEV.
Scale 1:50
3 Scale 1:50 4 Scale 1:50 5 Scale 1:50 6 Scale 1:50 7 Scale 1:50 8 Scale 1:50
NOTE: REFER TO ELEC. ROOM PLAN FOR EXACT ELECTRICAL PANEL LOCATIONS. REFER TO ELECTRICAL PLAN FOR EQUIPMENT LAYOUT
NOTES:
This drawing is the property of Urban Arts Architecture and may not be
reproduced without their permission and unless the reproduction carries
their name. All designs and all other information shown on this drawing
are for use on the specified project only and shall not be used otherwise
without written permission of this office.
The Contractor shall check and verify all dimensions and report any
discrepancies before proceeding.
500
SHIELD ON SHIELD ON SHIELD ON MW 109-1
1220
SHIELD SHIELD SHIELD SHIELD
FINISHED FLOOR B1
B1 B1 B1 B1 B1 B1 B1 FINISHED FLOOR
BACK FLOW
PREVENTER
112 DRY STOR. RM. NORTH ELEV. 112 DRY STOR. RM. EAST ELEV. 112 DRY STOR. RM. SOUTH ELEV. 112 DRY STOR. RM. WEST ELEV. 109 JAN. ROOM NORTH ELEV. 109 JAN. ROOM EAST ELEV. 109 JAN. ROOM SOUTH ELEV. 109 JAN. ROOM WEST ELEV.
(SEE MECH.)
9 Scale 1:50 10 Scale 1:50 11 Scale 1:50 12 Scale 1:50 13 Scale 1:50 14 Scale 1:50 15 Scale 1:50 16 Scale 1:50
P.LAM
1220
1220
1220
1220
P.LAM P.LAM P.LAM
FINISHED FLOOR
B1 B1 B1 B1 B1 B1 B1 B1 FINISHED FLOOR
SLOPED TO SLOPED TO SLOPED TO SLOPED TO
DRAIN DRAIN DRAIN DRAIN
108 MECH
108 MECH NORTH
RM NORTH ELEV. 108108
MECH EAST
MECH RM. EAST ELEV. 108 108
MECH SOUTH
MECH RM. SOUTH ELEV. 108 108
MECH WEST
MECH ROOM WEST ELEV. 107
107 GARBAGE NORTH
GARBAGE ROOM NORTH ELEV. 107 GARBAGE
107 GARBAGE EAST
ROOM EAST ELEV. 107107GARBAGE
GARBAGE ROOMSOUTH
SOUTH ELEV. 107
107 GARBAGE WEST
GARBAGE ROOM WEST ELEV.
17 Scale 1:50 18 Scale 1:50 19 Scale 1:50 20 Scale 1:50 21 Scale 1:50 22 Scale 1:50 23 Scale 1:50 24 Scale 1:50
2490 AFF
DATE ISSUE
2490 AFF
GWB, PT. 1
MANIFOLD
MANIFOLD
(SEE(SEE
MECH.)
MECH.)
GWB, PT.1 FIRE ALARM
PULL STATION
GWB, PT. 1 GWB, PT. 1 ESC
UBC ENGINEERING
FINISHED FLOOR
STUDENT CENTRE
B1 B1 B1 B1 B1 FINISHED FLOOR
122
122 RED SALES STOR. NORTH ELEV. 122 RED SALES STOR. EAST ELEV. 122 RED SALES STOR. SOUTH ELEV. 122 RED SALES STOR. WEST ELEV.
25 Scale 1:50 26 Scale 1:50 27 Scale 1:50 28 Scale 1:50
INTERIOR
NOTE: RED SALES STORAGE - PLYWOOD BACKING TO 2440 AFF ALL ELEVATIONS ELEVATIONS
A.701