GENERAL NOTES:

1. CONTRACTOR SHALL MAINTAIN ALL WORKING


207 208 CLEARANCES AND DEDICATED ELECTRICAL SPACES PER
1 CEC 2-308.

Sport EF-1.1
2
2. REFER TO THE MECHANICAL DRAWINGS FOR QUANTITY
AND LOCATION OF ALL DUCT-MOUNTED SMOKE
Store DETECTORS. CONTRACTOR IS RESPONSIBLE FOR ALL
CONDUIT, WIRING, AND CONNECTION OF DUCT-MOUNTED
SMOKE DETECTORS.
NOTES:
1. The design on this drawing is copyright and remains
the property of Century Property Developments.
3. REFER TO THE MECHANICAL DRAWINGS FOR QUANTITY 2. All work to be carried out in strict accordance
4 4 17 17 AND LOCATION OF ALL SMOKE AND FIRE-SMOKE with local authority requirements, National Building
GFI/WP GFI/WP 4 GFI/WP GFI/WP DAMPERS. CONTRACTOR IS RESPONSIBLE FOR ALL Regulations, and the S.A.B.S standards.
CONDUIT, WIRING, AND CONNECTION OF CONTROL 3. This drawing may not be scaled. Only figured
dimensions and levels may be used.
3 POWER TO SMOKE AND FIRE-SMOKE DAMPERS.
4. All relevant details, levels, dimensions must be
8 E 33 checked on site before commencement of work. Any
EF-1.3 23
F GFI TP-1 222 222
(TYPLABORATORY
222
(TYP 4) 2 (TYP 4) GFI 222 (TYP 4) 1222 222 4. CONTRACTOR TO REFER TO ARCHITECTURAL AND discrepenies to be reported to the Architects office
PUMP ROOM
15cd 8
33 33 4)
39
30
27
GFI LABORATORY (TYP 4) (TYP 4) 23 23 13 13 11 17 INTERIOR DESIGNER'S (ID) DRAWINGS FOR ADDITIONAL immediately.
41
GFI
37
GFI 31 27 HEAD DEPUTY GFI/WP INFORMATION FOR DEVICE LOCATIONS AND
GFI GFI GFI GFI REV DATE DESCRIPTION
DSSI-1.10 HWRP-1 EF-1.2 30 29 DIMMENSIONS.
CO/SB DWBP-1 GFI EF-1.4 11
GFI 27 27
E GWH-1 41 37 31 19 13 FCU-1.4B
31 39 29 GFI 29 GFI 222 FCU-1.4C
GFI GFI GFI 30cd 13
JOCKEY PUMP 43 30cd
GFI
30cd 29
21
222 30cd
GFI FCU-1.3B
25 13 20 229 KEY NOTES
CONTROLLER 222 203 FCU-1.2 203 19 J 201 FOR INFORMATION REGARDING POWER REQUIREMENTS
31 222 21
35 FCU-1.3A FOR EQUIPMENT IN THIS AREA, REFER TO KITCHEN
JP-1 236 33 203
203 41 39 GFI 30 PREP GFI 29 27
16
7 9 EQUIPMENT CONNECTION SCHEDULES ON SHEET 'E603'.
GFI GFI 30cd 40 31 GFI EF-1.5 +48" FOR DETAILED INFORMATION CONCERNING EXACT
FIRE PUMP ROOM 37 GFI ROOM FEMALE EF-1.6 RECEPTION/

E
FCU-1.1A FCU-1.1B SSV-1 GFI SSV-1 GFI GFI
GFI KITCHEN EQUIPMENT CONNECTION REQUIREMENTS,

E
GFI 38 TEACHERS 7
DSSI-1.1 FP-1 38
27 15cd
ADMINISTRATION MOUNTING HEIGHTS, ETC. REFER TO KITCHEN VENDOR
41 39 31 29 MALE 222 DRAWINGS.
GFI 23
15cd GFI GFI 37 GFI GFI 16 15cd
TEACHERS 4 203 RECEPTACLE TO SERVE MONITOR/TELEVISION.
8 15cd
33 GFI 27 +48" 6
GFI F WP COORDINATE EXACT LOCATION AND ELEVATION WITH
GFI 203 M
FIRE PUMP 5 ARCHITECT/OWNER PRIOR TO ROUGH-IN.
F WP CONTROLLER F WP 204 ALL 120V RECEPTACLES AND JUNCTION BOXES IN THIS
15 8 7 30cd
2 2 16 EWC E501 32 AREA SHALL BE CIRCUITED TO PANEL 'LBK', UNO.
GFI/WP
COVERED WALKWAY
GFI/WP GFI/WP
7

FCU-1.4D
COVERED 207 ALL 120V RECEPTACLES AND JUNCTION BOXES ON THIS
SIDE OF BOUNDARY SHALL BE CIRCUITED TO PANEL 'LB2',
COVERED WALKWAY WP UNO. 6 06/03/22 Revision 6
15cd
WP
2
E301
WP WP 15cd
WP
WP 15cd
WP
F FAA
231
7
PIAZZA6 208 ALL 120V RECEPTACLES AND JUNCTION BOXES ON THIS
SIDE OF BOUNDARY SHALL BE CIRCUITED TO PANEL 'LB3',
5
4
3
05/03/22
03/16/22
02/16/22
Revision 5
Revision 4
Revision 3
UNO.
1 12/10/21 Revision 1
2 16 FCU-1.4A 210 PROVIDE DUPLEX RECEPTACLE TO SERVE
GFI/WP GFI/WP 7 MULTI-FUNCTION COPIER.
6
DSSI-1.2 75cd 75cd 218 PROVIDE WALL DEEP ENOUGH FOR FLUSH MOUNTED
23 WP WP
Finance 22 M PANEL.
25 8
GFI 220 PROVIDE 120V POWER FOR FUTURE CEILING FANS.
6 WP
22 Admin 1
F

16 5 221 RECPTACLE SHALL PROVIDE POWER CONNECTION FOR


ELECTRICAL FCU-1.5A 2 GFI/WP 22 SIGN LIGHTING. COORDINATE EXACT LOCATION WITH
203 5
ROOM 3 GFI/WP ARCHITECT/INTERIOR DESIGNER/SIGNAGE CONSULTANT.
75cd 15cd 5 222 RECEPTACLE SHALL BE MOUNTED WITHIN MILLWORK.
6 COORDINATE THE EXACT LOCATION WITH MILLWORK
WP
30cd 18 CONTRACTOR.
24 Sick GFI/WP 223 PROVIDE (4) WEATHER PROOF JUNCTION BOXES FOR
23 Admin262
GFI SENIOR ART FUTURE FAN CONTROLLERS PROVIDED BY OTHERS.
WP COORDINATE EXACT REQUIREMENTS AND LOCATION
24
26 WITH OWNER PRIOR TO ROUGH-IN. BOXES SHALL BE
LANDSCAPED AND GRASSED

COVERED WALKWAY
LOCATED AT 48" AFF TO THE TOP OF THE BOX. PROVIDE
21 PLAY AREA AN EMPTY 3/4" CONDUIT FROM EACH BOX TO (1) OF THE
GFI/WP 18 CEILING MOUNTED FUTURE FAN OUTLET BOXES.
49' X 101' +48" 34

600x1000 MIRROR
26 229 PROVIDE 120V POWER TO BAS CONTROLLER.
GFI
9 COORDINATE EXACT LOCATION AND REQUIREMENTS
15cd

GRAB RAIL TRH


15cd EF-1.13 210 WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
WP

F
UNISEX
WC

WP 231 PROVIDE REMOTE ANNUNCIATOR PANEL FOR 'INV/EHA'.


EF-1.14 30cd 3 ADA Restroom PROVIDE LOW VOLTAGE WIRING, IN CONDUIT, BETWEEN
UNCOVERED GFI/WP 6 PANEL AND INVERTER.
18 236 PROVIDE 120V POWER CONNECTION TO MOBILE FUME
ART YARD
F

WP
STORE CUPBOARD. COORDINATE EXACT REQUIREMENTS PRIOR
FCU-1.5B LB3 TO ROUGH-IN.
6
25 238 PROVIDE COMBINATION USB/RECEPTACLE WITHIN EACH
M LOCKER. JUNCTION BOXES TO BE LOCATED BEHIND THE
21 WP LOCKERS. PROVIDE ONE CIRCUIT FOR EVERY TEN
GFI/WP 25 25 18
203
75cd
STAIR 1 GFI/WP
LOCKERS. COORDINATE EXACT JUNCTION BOX AND
RECEPTACLE LOCATIONS WITH LOCKER
WP MANUFACTURER/INSTALLER.
3
UNROOFED STORE WP
GFI/WP
F

TRASH/BIN
21 YARD 25 3
WP/GFI KILN GFI/WP
E 30cd 75cd 75cd
KILN WP WP 3 10
3
GFI/WP GFI/WP
E E E E E E E E 11
238 238 238 238 238 238 238 238
42 44 45 46 47 48 49 51

COVERED WALKWAY COVERED WALKWAY


15cd 3 WP WP 15cd WP 35 WP 3 15cd 15cd exp U.S. Services Inc.
WP WP GFI/WP GFI/WP 204 WP WP
GFI/WP t: +1.414.221.0088 f: +1.414.221.0537
221 241 North Broadway, Suite 203
F WP F WP F WP Milwaukee, WI 53202
12 USA

30cd www.exp.com
7 29 6 3 Project #: 21008941-00
GFI/WP

Counter
Beverage
GFI Cert of Auth: 29701

SERVERY by CATERING SPECIALIST


15cd 201
3 FCU-1.9C
30cd 30cd 30cd KITCHENCO/SB
GIRLS

GFI/WP FCU-1.10A FCU-1.10B


11
19 15
3 DINING ROOM
FCU-1.9B 218
17 SENIOR YEAR 6 203 15 SENIOR YEAR 5 11 SENIOR YEAR 4 9
GFI/WP 5
CP OPERATIONS
19 13 EWC LBK 30cd
203 203 30cd 30cd 13 Architects Division
29
BOYS

8 29 5 Lynx Road, Treesbank


EF-2.1 GFI
15cd E501 FCU-1.10C MIDRAND
6 WP FCU-1.9A
FCU-1.6 FCU-1.7 FCU-1.8 CO/SB P.O. Box 70406
BRYANSTON, 2021

Trash & Tray Drop


15cd 6
201 Tel:+27(11) 300-8700
19 15 11 HT-1 29 michael@century.co.za
17 13 9 7
x;EVAP
EVAP

M M M E 3
GFI G
G www.century.co.za
GFI/WP
14
F WP CLIENT
1 1 223 J J 40
3
GFI/WP
GFI/WP GFI/WP J J
Trash & Tray Drop

40 CENTURY PROPERTY
30cd
30cd DEVELOPMENTS
FCU-1.10E
220 220 220 220
15
J 8 J 10 J 12 J 14 PROJECT NAME
FCU-1.10F FCU-1.10D
16 KING'S COLLEGE SCHOOL
COVERED EXTERNAL F NASSAU, BAHAMAS

F
DINING
75cd AREA 40
15cd WP ERF:
WP 1 TOWNSHIP:
GFI/WP
1 17 DRAWING TITLE

GFI/WP ELECTRICAL FIRST FLOOR PLAN -


POWER - AREA 1 - PHASE 1
PHASE

X W V U T S R Q P O N M 100% CONSTRUCTION DOCUMENTS


6/3/2022 1:53:13 PM

SCALE DATE DRAWN

As Noted 11/12/2021 TKS

1 ELECTRICAL FIRST FLOOR PLAN - POWER - AREA 1


1/8" = 1'-0"
CPD COST
CENTER:

0000
CPD DRAW ING NUMER

E211P
REVISION