NOTES

1. ALL ELECTRICAL INSTALLATIONS SHALL CONFORM TO NATIONAL ELECTRICAL


CODE AND PROJECT SPECIFICATIONS.
2. MINIMUM SIZE OF BRANCH CIRCUIT REQUIRED SHALL BE 2X1C-4mm 2 Cu/XLPE/PVC
2
+1C-4mm Cu/PVC (G)
3. PANEL BOARD MOUNTING HEIGHT SHALL BE 1800mm FROM FINISHED FLOOR
LEVEL TO TOP OF PANELBOARD.
4. ALL BUILDING WIRES AND CABLES SHALL BE SINGLE CORE

BRANCH PANEL: PP-HVAC-R1 BRANCH PANEL: PP-HVAC-R2 BRANCH PANEL: PP-HVAC-R3


LOCATION: STORAGE-2 F-31 VOLTS: 400/230 Wye A.I.C. RATING: 25 KA LOCATION: STORAGE-2 F-31 VOLTS: 400/230 Wye A.I.C. RATING: 25 KA LOCATION: STORAGE-2 F-31 VOLTS: 400/230 Wye A.I.C. RATING: 25 KA
SUPPLY FROM: MCC-1 PHASES: 3 MAINS TYPE: MCCB BREAKER SUPPLY FROM: MCC-1 PHASES: 3 MAINS TYPE: MCCB BREAKER SUPPLY FROM: MCC-1 PHASES: 3 MAINS TYPE: MCCB BREAKER
MOUNTING: Recessed WIRES: 4 MAINS... 250 A MOUNTING: Recessed WIRES: 4 MAINS... 100 A MOUNTING: Recessed WIRES: 4 MAINS... 150 A
ENCLOSURE: NEMA-12 MCB RATING: 250 A ENCLOSURE: NEMA-12 MCB RATING: 50 A ENCLOSURE: NEMA-12 MCB RATING: 125 A
FEEDER: 4x1C-150 mm² Cu, XLPE/PVC+1C-95 mm² Cu, PVC (G) FEEDER: 4x1C-50 mm² Cu, XLPE/PVC+1C-25 mm² Cu, PVC (G) FEEDER: 4x1C-95 mm² Cu, XLPE/PVC+1C-50 mm² Cu, PVC (G)
NOTES: NOTES: NOTES:

CONDUIT/ CONDUIT/ CONDUIT/ CONDUIT/ CONDUIT/ CONDUIT/


CABLE CABLE / CIRCUIT POLE POLE CIRCUIT CABLE / CABLE CABLE CABLE / CIRCUIT POLE POLE CIRCUIT CABLE / CABLE CABLE CABLE / CIRCUIT POLE POLE CIRCUIT CABLE / CABLE
CKT TRAY WIRE (MM²) DESCRIPTION TRIP S A B C S TRIP DESCRIPTION WIRE (MM²) TRAY CKT CKT TRAY WIRE (MM²) DESCRIPTION TRIP S A B C S TRIP DESCRIPTION WIRE (MM²) TRAY CKT CKT TRAY WIRE (MM²) DESCRIPTION TRIP S A B C S TRIP DESCRIPTION WIRE (MM²) TRAY CKT ABBREVIATIONS
32mm DIA. CONDENSING CONDENSING 32mm DIA. 32mm DIA. A : AMPERE
2X1C-6+1C-6 2X1C-6+1C-6 2X1C-6+1C-6 CONDENSING CONDENSING 2X1C-6+1C-6 PH : PHASE
1 2778 VA 5556 VA 2 1 RGS/CABL SPLIT UNIT 20 A 1 0 VA 0 VA 1 20 A SPLIT UNIT RGS/CABL 2 1 20 A 1 0 VA 0 VA 1 20 A RGS/CABL 2
(G) (G) (G) SPLIT UNIT SPLIT UNIT (G)
E TRAY (STAND-BY) (STAND-BY) E TRAY E TRAY AF : AMPERE FRAME PP : POWER PANELBOARD
AT : AMPERE TRIP SPD : SURGE PROTECTION DEVICE
50mm DIA. 50mm DIA. 32mm DIA. 25mm DIA. 32mm DIA.
4X1C-16+1C- 4X1C-25+1C- 2X1C-6+1C-6 CONDENSING 2X1C-4+1C-4 CONDENSING 2X1C-6+1C-6 kA : KILO-AMPERE
3 RGS/CABL
16(G)
AHU 30 A 3 2778 VA 5556 VA 3 40 A AHU
16(G)
RGS/CABL 4 3 RGS/CABL
(G) SPLIT UNIT
20 A 1 2222 VA 0 VA 1 20 A SPARE -- -- 4 3 RGS/CABL
(G)
BLEED FAN 20 A 1 833 VA 2222 VA 1 20 A
SPLIT UNIT (G)
RGS/CABL 4 TCL : TOTAL CONNECTED LOAD
E TRAY E TRAY E TRAY E TRAY E TRAY AIC : CURRENT INTERRUPTING V : VOLT
CAPACITY
VA : VOLT-AMPERE
32mm DIA. 25mm DIA. 32mm DIA. TDL : TOTAL CONNECTED LOAD
2X1C-6+1C-6 CONDENSING 2X1C-4+1C-4 CONDENSING 2X1C-6+1C-6
5 2778 VA 5556 VA 6 5 RGS/CABL 20 A 1 2778 VA 0 VA 1 20 A SPARE -- -- 6 5 RGS/CABL BLEED FAN 20 A 1 833 VA 2222 VA 1 20 A RGS/CABL 6 DDC : DIRECT DIGITAL CONTROL
(G) SPLIT UNIT (G) SPLIT UNIT (G) LPP : LIGHTING/POWER PANELBOARD
E TRAY E TRAY E TRAY
MDB : MAIN DISTRIBUTION PANEL WH : WAREHOUSE
25mm DIA. 25mm DIA.
7 4074 VA 5556 VA 8 7 RGS/CABL
2X1C-4+1C-4
EXHAUST FAN 20 A 1 555 VA 2222 VA 1 20 A
CONDENSING 2X1C-6+1C-6
8 7 -- -- SPARE 20 A 1 0 VA 555 VA 1 20 A EXHAUST FAN
2X1C-4+1C-4
RGS/CABL 8
MCC : MOTOR CONTROL CENTER
(G) SPLIT UNIT (G) (G)
E TRAY E TRAY FACP : FIRE ALARM CONTROL PANEL
CU-1 : CONDENSING UNIT – 1
50mm DIA. 50mm DIA.
4X1C-25+1C- 4X1C-25+1C- SEF : SMOKE EXHAUST FAN
9 RGS/CABL AHU 30 A 3 4074 VA 5556 VA 3 40 A AHU RGS/CABL 10 9 926 VA 926 VA 10 9 -- -- SPARE 20 A 1 0 VA 926 VA 10
16(G) 16(G)
E TRAY E TRAY
LCP : LIGHTING CONTROL PANEL
25mm DIA. HVAC : HEATING, VENTILATION, AND AIR-CONDITIONING
32mm DIA. 4X1C-4+1C-4 4X1C-4+1C-4 32mm DIA. 2X1C-4+1C-4 4X1C-4+1C-4 32mm DIA.
11 4074 VA 5556 VA 12 11 SEF 20 A 3 926 VA 926 VA 3 20 A SEF 12 11 RGS/CABL BLEED FAN 20 A 1 2222 VA 926 VA 3 20 A SEF 12 PVC : POLYVINYL CHLORIDE
RGS/EMT (G) (G) RGS/EMT (G) (G) RGS/EMT
E TRAY

13 5556 VA 2222 VA 14 13 926 VA 926 VA 14 13 926 VA 926 VA 14

50mm DIA. 50mm DIA.


4X1C-25+1C- 4X1C-16+1C- 32mm DIA. 4X1C-4+1C-4
15 RGS/CABL AHU 40 A 3 5556 VA 2222 VA 3 40 A FAHU RGS/CABL 16 15 926 VA 926 VA 16 15 SEF 20 A 3 926 VA 926 VA 16
16(G) 16(G) RGS/EMT (G)
E TRAY E TRAY

32mm DIA. 4X1C-4+1C-4 4X1C-4+1C-4 32mm DIA. 4X1C-4+1C-4 32mm DIA.


17 5556 VA 2222 VA 18 17 SEF 20 A 3 926 VA 926 VA 3 20 A SEF 18 17 926 VA 926 VA 3 20 A SEF 18
RGS/EMT (G) (G) RGS/EMT (G) RGS/EMT

19 5556 VA 1333 VA 20 19 926 VA 926 VA 20 19 926 VA 926 VA 20

50mm DIA. 50mm DIA.


4X1C-25+1C- 4X1C-6+1C-6 32mm DIA. 4X1C-4+1C-4
21 RGS/CABL AHU 40 A 3 5556 VA 1333 VA 3 20 A WATER HEATER RGS/CABL 22 21 926 VA 926 VA 22 21 SEF 20 A 3 926 VA 2037 VA 22
16(G) (G) RGS/EMT (G)
E TRAY E TRAY

50mm DIA.
32mm DIA. 4X1C-4+1C-4 4X1C-4+1C-4 32mm DIA. 4X1C-16+1C-
23 5556 VA 1333 VA 24 23 SEF 20 A 3 926 VA 926 VA 3 20 A SEF 24 23 926 VA 2037 VA 3 20 A AHU RGS/CABL 24
RGS/EMT (G) (G) RGS/EMT 16(G)
E TRAY

25 5556 VA 1333 VA 26 25 926 VA 926 VA 26 25 3704 VA 2037 VA 26

50mm DIA. 32mm DIA. 50mm DIA.


4X1C-25+1C- 4X1C-6+1C-6 4X1C-16+1C-
27 RGS/CABL AHU 40 A 3 5556 VA 1333 VA 3 20 A WATER HEATER RGS/CABL 28 27 926 VA 1333 VA 28 27 RGS/CABL FAHU 30 A 3 3704 VA 5556 VA 28
16(G) (G) 16(G)
E TRAY E TRAY E TRAY

32mm DIA. 50mm DIA.


25mm DIA. 4X1C-4+1C-4 4X1C-6+1C-6 4X1C-25+1C-
29 5556 VA 1333 VA 30 29 SEF 20 A 3 926 VA 1333 VA 3 20 A WATER HEATER RGS/CABL 30 29 3704 VA 5556 VA 3 40 A AHU RGS/CABL 30
RGS/EMT (G) (G) 16(G)
E TRAY E TRAY

31 0 VA 0 VA 32 31 926 VA 1333 VA 32 31 7037 VA 5556 VA 32

50mm DIA.
4X1C-35+1C-
33 -- -- SPARE 40 A 3 0 VA 0 VA 3 20 A SPARE -- -- 34 33 -- -- SPARE 20 A 1 0 VA -- 1 -- SPACE -- -- 34 33 RGS/CABL AHU 40 A 3 7037 VA 0 VA 1 20 A SPARE -- -- 34
16(G)
E TRAY

35 0 VA 0 VA 36 35 -- -- SPARE 20 A 1 0 VA -- 1 -- SPACE -- -- 36 35 7037 VA -- 1 -- SPARE -- -- 36

37 -- -- 38 37 0 VA -- 38 37 0 VA -- 38
This Drawing and the design it covers are the property of the Royal
Commission for Jubail and Yanbu / Royal Commission at Jazan. These
drawings are loaned on the borrower's express agreement that they will
not be reproduced, copied, loaned, exhibited or used except in the limited
39 -- -- SPACE -- 3 -- -- 3 -- SPACE -- -- 40 39 -- -- SPARE 20 A 3 0 VA -- 3 -- SPACE -- -- 40 39 -- -- SPARE 20 A 3 0 VA -- 3 -- SPACE -- -- 40
way, if any, permitted by written consent of the Royal Commission.

41 -- -- 42 41 0 VA -- 42 41 0 VA -- 42 REFERENCE DRAWINGS
DRAWING NO. DRAWING TITLE
TOTAL... 39519 VA 39519 VA 39519 VA TOTAL... 10592 VA 10037 VA 10593 VA TOTAL... 22592 VA 25093 VA 27315 VA
2031-EE-A1-100 OVERALL LOW VOLTAGE SINGLE LINE DIAGRAM
TOTAL... 172 A 172 A 172 A TOTAL... 46 A 44 A 46 A TOTAL... 98 A 111 A 120 A
REMARKS: REMARKS: REMARKS: 2031-EE-A0-200 POWER SINGLE LINE DIAGRAM
2031-EE-A0-280 CABLE SCHEDULE
2031-EE-A0-210 GROUND FLOOR LIGHTING LAYOUT MASTER PLAN
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
2031-EE-A0-215 FIRST FLOOR LIGHTING LAYOUT MASTER PLAN
WATER HEATER 8000 VA 20.00% 1600 VA WATER HEATER 4000 VA 20.00% 800 VA EXHAUST FAN 555 VA 20.00% 111 VA
AHU 103889 VA 90.00% 93500 VA TOTAL CONNECTED LOAD: 118556 VA EXHAUST FAN 555 VA 20.00% 111 VA TOTAL CONNECTED LOAD: 31222 VA AHU 43889 VA 90.00% 39500 VA TOTAL CONNECTED LOAD: 74999 VA 2031-EE-A0-220 ROOF LIGHTING LAYOUT MASTER PLAN
FAHU 6667 VA 90.00% 6000 VA TOTAL CONNECTED (+20%)... 142267 VA SEF 19444 VA 0.01% 2 VA TOTAL CONNECTED (+20%)... 37466 VA FAHU 11111 VA 90.00% 10000 VA TOTAL CONNECTED (+20%)... 89999 VA 2031-EE-A0-225 GROUND FLOOR POWER LAYOUT MASTER PLAN
TOTAL DEMAND FACTOR: 85.28% CONDENSING SPLIT UNIT 7222 VA 60.00% 4333 VA TOTAL DEMAND FACTOR: 16.80% SEF 11111 VA 0.01% 1 VA TOTAL DEMAND FACTOR: 74.37% 2031-EE-A0-230 FIRST FLOOR POWER LAYOUT MASTER PLAN
TOTAL DEMAND LOAD 121320 VA TOTAL DEMAND LOAD 6296 VA BLEED FAN 3889 VA 90.00% 3500 VA TOTAL DEMAND LOAD 66935 VA
TOTAL DEMAND CURRENT 175 A TOTAL DEMAND CURRENT 9A CONDENSING SPLIT UNIT 4444 VA 60.00% 2667 VA TOTAL DEMAND CURRENT 97 A 2031-EE-A0-235 ROOF POWER LAYOUT MASTER PLAN
GROUND FLOOR HVAC POWER AND CABLE TRAY LAYOUT
2031-EE-A0-240
MASTER PLAN
FIRST FLOOR HVAC POWER AND CABLE TRAY LAYOUT
2031-EE-A0-245
MASTER PLAN
ROOF FLOOR HVAC POWER AND CABLE TRAY LAYOUT
2031-EE-A0-250
MASTER PLAN

0 MAY.'23 FAEC ISSUED FOR BIDDING O. KHUSHAIM


NO. DATE BY DESCRIPTION APPROVED BY

KINGDOM OF SAUDI ARABIA

Royal Commission for Jubail and Yanbu

Royal Commission at Jazan

JAZAN CITY FOR PRIMARY AND


DOWNSTREAM INDUSTRIES
DRAWING TITLE::
DEVELOPMENT OF JCPDI SUPPORT SERVICES WAREHOUSE
WAREHOUSE BUILDING

PANELBOARD LOAD SCHEDULE (SHEET 5 OF 5)

DESIGNED BY: AI HEAD OFFICE:


PO Box 4549
DRAWN BY: AH 7545 King Khalid Road, Al
Tahliyah,
CHECKED BY: SS Al Khobar 34716, Saudi Arabia
Tel.:+966 13 887 8838
PROJ ENGR. : GAUTAM . T Fahd Abdullah Alireza & Partenrs Engineering Consultants Co.
Fax:+966 13 887 0574
‫ﺷﺭﻛﺔ ﻓﻬﺩ ﻋﺑﺩﷲ ﻋﻠﻲ ﺭﺿﺎ ﻭﺷﺭﻛﺎﺅﻩ ﻟﻼﺳﺗﺷﺎﺭﺍﺕ ﺍﻟﻬﻧﺩﺳﻳﺔ‬ www.FAEC.com
DU SUPV :

A/E APPROVAL : O. KHUSHAIM WBS NO : DRAWING NO.

R. C. APPROVAL: CONT. NO : JCPDI I-2031 2031-EE-A0-279


DATE: MARCH 2023 SCALE: NTS REV. NO. 0