50mm DIA.
32mm DIA. 4X1C-4+1C-4 4X1C-4+1C-4 32mm DIA. 4X1C-16+1C-
23 5556 VA 1333 VA 24 23 SEF 20 A 3 926 VA 926 VA 3 20 A SEF 24 23 926 VA 2037 VA 3 20 A AHU RGS/CABL 24
RGS/EMT (G) (G) RGS/EMT 16(G)
E TRAY
50mm DIA.
4X1C-35+1C-
33 -- -- SPARE 40 A 3 0 VA 0 VA 3 20 A SPARE -- -- 34 33 -- -- SPARE 20 A 1 0 VA -- 1 -- SPACE -- -- 34 33 RGS/CABL AHU 40 A 3 7037 VA 0 VA 1 20 A SPARE -- -- 34
16(G)
E TRAY
37 -- -- 38 37 0 VA -- 38 37 0 VA -- 38
This Drawing and the design it covers are the property of the Royal
Commission for Jubail and Yanbu / Royal Commission at Jazan. These
drawings are loaned on the borrower's express agreement that they will
not be reproduced, copied, loaned, exhibited or used except in the limited
39 -- -- SPACE -- 3 -- -- 3 -- SPACE -- -- 40 39 -- -- SPARE 20 A 3 0 VA -- 3 -- SPACE -- -- 40 39 -- -- SPARE 20 A 3 0 VA -- 3 -- SPACE -- -- 40
way, if any, permitted by written consent of the Royal Commission.
41 -- -- 42 41 0 VA -- 42 41 0 VA -- 42 REFERENCE DRAWINGS
DRAWING NO. DRAWING TITLE
TOTAL... 39519 VA 39519 VA 39519 VA TOTAL... 10592 VA 10037 VA 10593 VA TOTAL... 22592 VA 25093 VA 27315 VA
2031-EE-A1-100 OVERALL LOW VOLTAGE SINGLE LINE DIAGRAM
TOTAL... 172 A 172 A 172 A TOTAL... 46 A 44 A 46 A TOTAL... 98 A 111 A 120 A
REMARKS: REMARKS: REMARKS: 2031-EE-A0-200 POWER SINGLE LINE DIAGRAM
2031-EE-A0-280 CABLE SCHEDULE
2031-EE-A0-210 GROUND FLOOR LIGHTING LAYOUT MASTER PLAN
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
2031-EE-A0-215 FIRST FLOOR LIGHTING LAYOUT MASTER PLAN
WATER HEATER 8000 VA 20.00% 1600 VA WATER HEATER 4000 VA 20.00% 800 VA EXHAUST FAN 555 VA 20.00% 111 VA
AHU 103889 VA 90.00% 93500 VA TOTAL CONNECTED LOAD: 118556 VA EXHAUST FAN 555 VA 20.00% 111 VA TOTAL CONNECTED LOAD: 31222 VA AHU 43889 VA 90.00% 39500 VA TOTAL CONNECTED LOAD: 74999 VA 2031-EE-A0-220 ROOF LIGHTING LAYOUT MASTER PLAN
FAHU 6667 VA 90.00% 6000 VA TOTAL CONNECTED (+20%)... 142267 VA SEF 19444 VA 0.01% 2 VA TOTAL CONNECTED (+20%)... 37466 VA FAHU 11111 VA 90.00% 10000 VA TOTAL CONNECTED (+20%)... 89999 VA 2031-EE-A0-225 GROUND FLOOR POWER LAYOUT MASTER PLAN
TOTAL DEMAND FACTOR: 85.28% CONDENSING SPLIT UNIT 7222 VA 60.00% 4333 VA TOTAL DEMAND FACTOR: 16.80% SEF 11111 VA 0.01% 1 VA TOTAL DEMAND FACTOR: 74.37% 2031-EE-A0-230 FIRST FLOOR POWER LAYOUT MASTER PLAN
TOTAL DEMAND LOAD 121320 VA TOTAL DEMAND LOAD 6296 VA BLEED FAN 3889 VA 90.00% 3500 VA TOTAL DEMAND LOAD 66935 VA
TOTAL DEMAND CURRENT 175 A TOTAL DEMAND CURRENT 9A CONDENSING SPLIT UNIT 4444 VA 60.00% 2667 VA TOTAL DEMAND CURRENT 97 A 2031-EE-A0-235 ROOF POWER LAYOUT MASTER PLAN
GROUND FLOOR HVAC POWER AND CABLE TRAY LAYOUT
2031-EE-A0-240
MASTER PLAN
FIRST FLOOR HVAC POWER AND CABLE TRAY LAYOUT
2031-EE-A0-245
MASTER PLAN
ROOF FLOOR HVAC POWER AND CABLE TRAY LAYOUT
2031-EE-A0-250
MASTER PLAN