1200
C-1 C-1 C-1 C-1 C-1 C-1
01 01 Engineer before concrete blinding is laid.
2 200mm Thick RC Retaining wall 200mm Thick RC Retaining wall 200mm Thick RC Retaining wall 200mm Thick RC Retaining wall 200mm Thick RC Retaining wall
2
01 01
Weak pockets of bearing strata to be dug
600
3700
3700
T16-02-150 B2
Reinforced concrete to have a minimum/
10 10 characteristic cube strength of 30N/mm²
F-1 F-1
T16-02-150 B1
TYPICAL SECTION THROUGH SLAB at 28 days with 20mm max.aggregate size
10 10 (scale 1:25)
1600
400
A2
C-1 C-1 S2 S2
3' 200mm Thick Plinth
200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth
3'
F-1 F-1
3. REINFORCEMENT
A2
(a) High Tensile Ribbed bars to BS4461and
1500
1500
SECTION A3 - A3(Scale 1:10) are marked"T" on these dwgs
1000
600
C-1 C-1 C-1
C-1
(b) Mild steel marked "R" on these dwgs to
10400
10400
3 3
ROOF SLAB be round bars to BS4483
1475
1475
675 250 675
1600 4. MINIMUM COVER TO ALL STEEL IN
TYPICAL LAYOUT FOR 1600x1600x600mm
(Ground Floor) 250
3" 3" FOOTING F2, 04 No. (a) Foundations = 50mm
200mm Thick RC Retaining wall
200
SCALE 1:25
(b) Beams = 30mm
2425
BRC Mesh REF No. A142 6T16
5. ABBREVIATIONS
3150
A2
18T8-(50-52)-200
6T20 1000 Gauge DPM M.C = Mass Concrete
4 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth
4
F-2 F-2 F-2 F-2 200mm Thick RC Solid Slab R.C = Reinforced Concrete
A2
1300
1300
50mm Thick Sand Blinding 25mm water proof plaster T = Top
A1
3700
3175 325 1150 2325 725 2200 700 2350 1150 3500
T8-04-150
17600 Compacted to 98% MDD SECOND FLOOR This drawing must be read in conjunction with
in Layers n.e 200mm 25mm plaster and 2 layers the relevant architectural,Mechanical,Electrical
F E" E E' G D C H B' B A of APP water proofing drawings.
FOUNDATION LAYOUT
(Scale: 1:75)
675 250 675 Any discrepancy MUST be brought to attention
F E" E E' G D C H B' B A of the project manager.
600
T16-02-150 B1 Well graded marram
1 1 compacted to 98% MDD 6T20
REVISIONS
3150
17600
18T8-(50-52)-200
150mm Kicker
4650 3050 2200 3050 4650
50mm Thick Concrete Blinding
1200
1200
02 02 02 02 02 02 02
2 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth
2 TYPICAL SECTION S2-S2 THROUGH No. Date: Descriptions:
FOOTING F2, 04 No. (Basement Level)
SCALE 1:25
200mm Thick Plinth
75mm kicker
200mm Thick Plinth
3700
200mm Thick Plinth
A142
200mm Thick Plinth
A142 A142
A142
A142
FIRST FLOOR
A2
800
A2
op m
n t 50m T16-02-150 B2
1500
1500
e d o r of
rc ve
nfo co
b rei Min TYPICAL SECTION THROUGH THE
sla ith a
18T8-(50-52)-200
10400
10400
3 lid
so 42 w
3
RETAINING WALL
3150
T16-02-150 B1
RC A1
ick o.
Th ref.N
2000
1475
1475
400
m h
A142 A142 0m es
20 M A142
A142
A142 S1 S1
250 6T20
3" 3"
200mm Thick Plinth
01
200mm Thick Plinth
75mm kicker
800
2425
2425
200mm Thick Plinth
A2
2000
1300
1300
5 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth 200mm Thick Plinth
5
TYPICAL LAYOUT FOR 2000x2000x600mm T12-11-200 F2
A1
3175 325 1150 2325 725 2200 700 2350 1150 3500
17600 FOOTING F1, 04 No.
2/22T12-02 - 200
SCALE 1:25
T12-12-200 N1
Project Title:
3150
14T8-(50-52)-200
F E" E E' G D C H B' B A T12-12-200 F1
PROPOSED DEVELOPMENT AS TO BE BUILT
BASEMENT FLOOR SLAB LAYOUT ON BLOCK ........ PLOT ............
(Scale: 1:75)
6T20
BRC Mesh REF No. A142
75mm kicker
BRC Mesh REF No. A142 BRC Mesh REF No. A142
1000 Gauge DPM 6T20 1000 Gauge DPM
1000 Gauge DPM
200mm Thick RC Solid Slab 200mm Thick RC Solid Slab Client:
200mm Thick RC Solid Slab 50mm Thick Sand Blinding BASEMENT FLOOR
50mm Thick Sand Blinding Mr. ....................
50mm Thick Sand Blinding
150mm Thick Well Compacted
BE CONFIRMED ON SITE BY THE S.E.
min 1200mm FOUNDATION DEPTH TO
2T16 Designed:
200 200 200 200
K.P Dwg No.:
200 200 200 01
3T16
Drawn by:
275
200
600
400
200 T16-02-150 B1 2/14T20-03-150 T2&B2
350
350
50mm Thick Concrete Date: S-01
50mm Thick Concrete
TYPICAL SECTION THROUGH DEC, 2021
125
Blinding
Blinding 50mm Thick Concrete Blinding
TYPICAL SECTION A2-A2 THROUGH 600x200mm 200
1B33 500/250
1B36 500/250
1B32 500/250
1B34 500/250
3B36 500/250
3B38 500/250
3B39 500/250
3B40 500/250
b Slab b lab
d Sla d Sla
C So
li
C So
lid 325 Soli C So
lid S Engineer before concrete blinding is laid.
1200
1200
1200
1200
kR hick
R RC R
Thic mT hick hick
mT mT
X1
m
200m 200m 200m 200m
C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1
2 1B1 500/250 1B2 500/250 1B3 500/250 1B4 500/250 1B5 500/250
2 2 3B1 500/250 3B2 500/250 3B3 500/250 3B4 500/250 3B5 500/250
2 Weak pockets of bearing strata to be dug
out and filled with C20 mass concrete.
X1
1B31 500/250
1B35 500/250
3B20 500/250
REINFORCED ON TOP WITH BRC
ab
lab
ab
2. CONCRETE MIXES
200mm THICK MAXPAN SLAB
d Sl
d Sl
d
Soli
Soli
Soli
11 11
Reinforced concrete to have a minimum/
C So
3B29 500/250
3B31 500/250
1B41 500/250
1B40 500/250
8 8
1B15 500/250
1B17 500/250
3B22 500/250
REINFORCED ON TOP WITH BRC
WITH 150mm MAXPANS, 150mm
RC
k RC
RC
3700
3700
3700
12 12
hick
hick
hick
3B18 500/250
1B14 500/250
3B14 500/250
3B19 500/250
Thic
1B6 500/250
3B6 500/250
13 13
T
6 6
at 28 days with 20mm max.aggregate size
mm
mm
14 14
m
m
5 5
200
200
200
200
15 15
4 4
16 16
3 3
17 17
X4
C-1
2 C-1 C-1
2 C-1
18 18
1 3. REINFORCEMENT
3' 1
3' 3' 3'
1B19 500/250 3B32 500/250
1B20 500/250 1B21 500/250 1B22 500/250 1B23 500/250 3B30 500/250 3B28 500/250
3B23 500/250
(a) High Tensile Ribbed bars to BS4461and
X4
3B21 500/250
are marked"T" on these dwgs
1500
1500
1500
1500
11600
11600
11600
11600
(b) Mild steel marked "R" on these dwgs to
ab
X2
Sl
C-1 C-1
lid
C-1 C-1 C-1 C-1
C-1 C-1
So
be round bars to BS4483
RC
3 3 3 3
3B15 500/250
3B16 500/250 3B17 500/250
k
ic
Th
m
Slab ab
0m
X2
d d Sl
Soli Soli
20
k RC RC 4. MINIMUM COVER TO ALL STEEL IN
1475
1475
1475
1475
hic hick
mT mT
00m 200
m
2
(a) Foundations = 50mm
ab ab
3B25 500/250
3B27 500/250
3B13 500/250
Sl Sl
(b) Beams = 30mm
3B26 500/250
REINFORCED ON TOP WITH BRC
3" 3" 3" 3"
1B18 500/250
C C
Th Th
0m
m
0m
m
(d) Ground slab = 30mm
1B25 500/250
3B24 500/250
2425
2425
2425
3B7 500/250
2425
MESH REF No. A142
3B34 500/250
X3 X3
1B7 500/250
M.C = Mass Concrete
4 1B26 500/250 1B27 500/250 1B28 500/250 1B29 500/250 1B30 500/250
4 4 4 R.C = Reinforced Concrete
T = Top
B = Bottom
1300
1300
1300
1300
C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1
C-1 C-1
5 1B12 500/250 1B11 500/250 1B10 500/250 1B9 500/250 1B8 500/250
5 5 3B12 500/250 3B11 500/250 3B10 500/250 3B9 500/250 3B8 500/250
5 All dimensions to be confirmed on site.
ab
3B42 500/250
3B41 500/250
3B43 500/250
3B44 500/250
3175 325 1150 2325 725 2200 700 2350 1150 325 3175 d Sl Slab
Soli Soli
d
17600 RC RC
hick hick
mT mT
200
m 200m This drawing must be read in conjunction with
F E" E E' G D C H B' B B" A 3175 325 1150 2325 725 2200 700 2350 1150 325 3175 the relevant architectural,Mechanical,Electrical
GROUND FLOOR SLAB LAYOUT 17600
drawings.
(Scale: 1:75)
F E" E E' G D C H B' B B" A Any discrepancy MUST be brought to attention
TYPICAL FIRST & SECOND FLOOR SLAB LAYOUT of the project manager.
(Scale: 1:75)
REVISIONS
2/5T12-07-200T2&B2
2/5T12-07-200T2&B2
2/5T12-07-200T2&B2
2/5T12-07-200T2&B2
F E" E E' G D C H B' B B" A F E" E E' G D C H B' B B" A No. Date: Descriptions:
2/6T12-13-200T2&B2
2/6T12-13-200T2&B2
1 1 1 1
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
2/14T12-08-200T1&B1 2/14T12-08-200T1&B1 2/14T12-08-200T1&B1 2/14T12-08-200T1&B1
X1
C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1
2 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam
2 2 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam
2
2/6T12-05-200T2&B2 2/6T12-05-200T2&B2 2/6T12-05-200T2&B2 2/6T12-05-200T2&B2
X1
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
10 10
18T12-11B1, 2@RIB
18T12-11B1, 2@RIB
18T12-11B1, 2@RIB
18T12-11B1, 2@RIB
9 9
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
2/17T12-06-200T1
2/17T12-06-200T1
2/17T12-06-200T1
2/17T12-06-200T1
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
11 11
8 8
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
12 12
250x500mm RC Beam
7 7
13 13
6 6
14 14
5 5
15 15
4 4
16 16
3 3
17 17
(4) (4) (4) (4) (4) (4) (4) (4) 32T12-04 (4) (4) (4) (4) (4) (4) (4) (4) 32T12-04
C-1
2 C-1 C-1
2 C-1
18 18
250x500mm RC Beam
1
3' 3' 3' 1
3'
250x500mm RC Beam 250x500mm RC Beam
250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam
10T12-03B1, 2@RIB
10T12-03B1, 2@RIB
250x500mm RC Beam
2/6T12-14 200T2&B2
2/22T12-03 200 T1&B1
X2
C-1 C-1
C-1 C-1 C-1 C-1
C-1 C-1
3 3 3 250x500mm RC Beam
250x500mm RC Beam 250x500mm RC Beam
3
2/6T12-15-200T2&B2
X2
8T12-02B1, 2@RIB
8T12-02B1, 2@RIB
2/26T12-10-200T1&B1
2/26T12-10-200T1&B1
2/17T12-16 200T1&B1
Structural Engineers:
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
3" 3" 3" 3"
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
2/16T12-01-200T2&B2 2/20T12-02-200T2&B2 2/10T12-03-200T2&B2 2/20T12-02-200T2&B2 2/16T12-01-200T2&B2
250x500mm RC Beam
26T12-01B1, 2@RIB
26T12-01B1, 2@RIB
250x500mm RC Beam
X3 X3
4 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam
4 4 (4) (4) (4) (4) (4) (4) (4) (4) (4) (4) (4) (4) 48T12-05
4
Project Title:
C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 C-1 PROPOSED RESIDENTIAL DEVELOPMENT AS
C-1 C-1
TO BE BUILT ON BLOCK 273 PLOT 4393,
5 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam
5 5 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam 250x500mm RC Beam
5
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
250x500mm RC Beam
MASSAJJA, NAMASUBA, MAKINDYE
2/5T12-09-200T1&B1
2/5T12-09-200T1&B1
2/6T12-12-200T2&B2
2/6T12-12-200T2&B2
2/14T12-17-200T1&B1 2/14T12-17-200T1&B1
SSABAGABO, WAKISO DISTRICT
2/6T12-18-200T2&B2
2/6T12-18-200T2&B2
GROUND FLOOR SLAB REINFORCEMENT LAYOUT
(Scale: 1:75) Client:
F E" E E' G D C H B' B B" A
MARTIN MBAZIRA MAKESA
TYPICAL FIRST & SECOND FLOOR SLAB REINFORCEMENT LAYOUT P.O.BOX 31281 K'LA
(Scale: 1:75)
Drawing Title:
A142 BRC MESH FLOOR SLAB LAYOUTS AND DETAILS
T12-13-200T1 A142 BRC MESH
T12-08-200T2 A142 BRC MESH 05 05 05 05
07 07 07 07 11 11
150 50
03 03 02 02
200
Designed:
200
05 05 05 05
K.P Dwg No.:
02
150 300 300 07 07 07 07 11 11 11 11 Drawn by:
03 03 03 03 02 02 02 02
300
300
T12-13-200B1
300
Date: S-02
DEC, 2021
200
SECTION X3 - X3 200 Scale:
200
SECTION X2 - X2
(Scale 1:10) SECTION X1 - X1
(Scale 1:10) AS SHOWN(A1)
(Scale 1:10)
NOTES
1. FOUNDATIONS
They shall generally be taken 1200mm
min. below existing ground level after
removal of organic layer and all
excavations to be confirmed by the
Engineer before concrete blinding is laid.
2/5T12-07-200T2&B2
2/5T12-07-200T2&B2
F E" E E' G D C H B' B B" A C-1 C-1 Reinforced concrete to have a minimum/
characteristic cube strength of 30N/mm²
3B3 500/250 at 28 days with 20mm max.aggregate size
X1
1 1
10 T12-02-200 T2
10 T12-02-200 B2
10 T12-02-200 B2
8 T12-02-200 T2
3B36 500/250
3B38 500/250
3B39 500/250
3B40 500/250
C-1 C-1
2/14T12-08-200T1&B1
C-1 C-1 2/14T12-08-200T1&B1 C-1 C-1
3. REINFORCEMENT
2 3B1 500/250 3B2 500/250 3B3 500/250 3B4 500/250 3B5 500/250
2 (a) High Tensile Ribbed bars to BS4461and
C-1 C-1 are marked"T" on these dwgs
(b) Mild steel marked "R" on these dwgs to
3B20 500/250
200x500mm RC Beam be round bars to BS4483
3B31 500/250
3B22 500/250
2/18T12-04-200T1&B1
2/18T12-04-200T1&B1
10
11 9
3B29 500/250
5T12-01-200 B2&T2
12
7 4. MINIMUM COVER TO ALL STEEL IN
3B18 500/250
3B14 500/250
3B19 500/250
6T12-08-200T1
3B6 500/250
13
lab la b
So
li dS 14
6
So
li dS
2/10T12-01-150T2&B2 (a) Foundations = 50mm
RC 5 C
kR
m
Th
ick 2/14T12-03-200T2&B2 15
4
2/14T12-03-200T2&B2
T hic (b) Beams = 30mm
mm
6T12-12-200B1
3B18 500/250
0m
2/30T12-02-150T1&B1
16
0
(c) Columns = 30mm
6T12-06-200B1
3B19 500/250
20 3 20
17
10
6T12-13-200T1
C-1
2 C-1 (d) Ground slab = 30mm
200x500mm RC Beam
9
18
1
3' 3B32 500/250
3B30 500/250 3B28 500/250
3'
3B23 500/250
11
6T12-11-200T1
5. ABBREVIATIONS
3B21 500/250
2/22T12-03-200T2&B2 2/22T12-03-200T2&B2 8
5200
200x500mm RC Beam
12 M.C = Mass Concrete
(4)
(4)
C-1 C-1
C-1
7 R.C = Reinforced Concrete
6T12-07-200B1
C-1
3 3 13
3B15 500/250
3B16 500/250 3B17 500/250
T = Top
14 6 B = Bottom
5
6T12-10-200B1
All dimensions to be confirmed on site.
(10)
(10)
15
3B25 500/250
3B27 500/250
3B13 500/250
3B26 500/250
3" 3"
725
728
3B37 500/250 3B35 500/250 3B33 500/250
6T12-10-200B1
16
Sla
b
dS
lab
3B30 500/250 This drawing must be read in conjunction with
RC
S olid
RC
S oli 3 the relevant architectural,Mechanical,Electrical
6T12-16-200B1
3B24 500/250
3B7 500/250
k ick
hic Th
17
mT
200
m
20
0 mm drawings.
2
3B34 500/250
(4)
(4)
18 Any discrepancy MUST be brought to attention
1 Beam of the project manager.
4 2/16T12-01-200T2&B2 2/16T12-01-200T2&B2 2/8T12-200T2&B2 2/8T12-200T2&B2 2/16T12-01-200T2&B2 2/16T12-01-200T2&B2 4 200x500mm RC
6T12-15-200B1
6T12-04-200T1
6T12-05-200T1
C-1 C-1 C-1 C-1 C-1
C-1 C-1
6T12-03-200B1
REVISIONS
15T12-01-200 B2&T2
C-1
6T12-14-200T1
5 3B12 500/250 3B11 500/250 3B10 500/250 3B9 500/250 3B8 500/250
5
2/14T12-17-200T1&B1 2/14T12-17-200T1&B1
3B42 500/250
3B41 500/250
3B43 500/250
3B44 500/250
3B16 500/250 No. Date: Descriptions:
C-1 C-1
2/6T12-18-200T2&B2
2/6T12-18-200T2&B2
F E' D C B' A
4650 3050 2200 3050 4650
X1
800
850 850 1250
650
700 700 1000
1250 850 3T16-7(T1) 800 850
3T16-1(T1) 1000 3T16-4(T1) 3T16-5(T1) 700 3T16-6(T1) 650 3T16-6(T1) 3T16-5(T1) 700 3T16-4(T1) 3T16-1(T1) STAIRCASE REINF. LAYOUT
SCALE: 1:25
50
14 01 01 01 01 01 01 01
5 3 2 200 15 02
5200 5200 02 05 20 15
02 02 03
02 10
1350 A 02
Structural Engineers:
1000 02
16
1350 02
3T16-13(T1) 3T16-15(T1) 3T16-13(T1) 02
1000 13
02 02
02
900
02
02 02
T8 - 3 - 200 T8 - 3 - 200 08
02 02
07
20
02 STAIRCASE DETAILS
11 02 02
3T16-14(B1) 2/2T12
02 02
12 TREADS: 267mm
0202
1002
11
08 RISERS: 167mm
02
02
02
06 WAIST: 200mm Project Title:
200
06 20 02
a-a-a a-a-a 12 10
02 02
400
200
1450 b=T12 b=T12 02 TO BE BUILT ON BLOCK 273 PLOT 4393,
3T16-40(T1) 3T16-42(T1) 07 02 MASSAJJA, NAMASUBA, MAKINDYE
1000
b b c=T8-200 b b 02 05
02 SSABAGABO, WAKISO DISTRICT
500
500
02
02 02
T8 - 3 - 200 T8 - 3 - 200 b b b b 02 02
02 02
02 04
2/2T12 400 200 02 16 20 14 Client:
3T16-41(B1) 03
02
a-a-a a-a-a 04 02
01 01 01 01 01 01 01
Mr.
250 T8 - 3 - 200 250 T8 - 3 - 200 GUTTER SECTION (Scale 1:10) 02
1
02 0
TYPICAL MIDSPAN SECTION TYPICAL SUPPORT SECTION 01 01 01 01 01 01 01
02
SCALE, 1:20 SCALE, 1:20 05 20 15
02 03
02
02
Drawing Title:
BEAMS & STAIRCASE DETAILS
TYPICAL SECTION X1-X1 THROUGH THE STAIRCASE
SCALE: 1:25
Designed:
K.P Dwg No.:
03
Drawn by:
K.P Sheet No.
Date: S-03
DEC, 2021
Scale:
AS SHOWN(A1)