Professional Documents
Culture Documents
~\
~I~\
.. 0-.JIJ)uW~1
<"" w~I--t\~
SECTION 16510:
KINGDOM
OFSAUDIARABIA ~~~1 ~f!J1~1
forJubail&Yanbu
RoyalCommission ~4 ~ ~1.14fJ1
SECTION 16510
INTERIOR LUMINAIRES
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 1
1.05 DEFINITIONS....................................................................................................... 4
1.06 SUBMITTALS....................................................................................................... 5
PART 1 GENERAL
A. Luminaires
B. Luminaire Control
E. Lighting Calculations
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials and products. In case of conflict between these standards and
the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, manufacturer shall propose equipment confirming to
Rev 0
1 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
Rev 0
2 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
12. ASTM D635 Standard Test Method for Rate of Burning and/or
Extent and Time of Burning of Plastics in a
Horizontal Position
1. IEC 60061-1 Lamp Caps and Holders Together with Gages for
the Control of Interchangeability and Safety
Rev 0
3 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
1.05 DEFINITIONS
A. ballast: A device used with an electric discharge lamp to obtain necessary circuit
conditions (voltage, current and wave form) for starting and operating.
D. high bay area: An industrial building is classified as high bay area if ceiling height of
building is more than 7.5 m above the finished floor.
E. lamp lumen depreciation (LLD): A factor used in lighting calculation to account for
light loss that takes place in a lamp due to the gradual decay in lumen output over a
designated period of time.
F. low bay area: An industrial building is classified as low bay area if ceiling height of
building is less than 7.5 m above the finished floor.
Rev 0
4 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
G. luminaires: A complete lighting fixture including one or more lamps and a means for
connecting to power source.
J. working surface/plane: The plane at which work is usually performed and at which
the illumination is specified and measured.
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
c) Installation instructions.
d) Part list.
B. The Contractor shall submit Field Test Report after completion of testing and
commissioning.
Rev 0
5 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing such as to achieve the
specified quality to the approval of the Royal Commission in accordance with
SECTION 01450.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
A. All equipment and material shall be tested at factory in accordance with latest
applicable codes and standards. All type tests as per applicable codes and standards
shall be performed on first unit of every new design. The Contractor shall notify the
Royal Commission in writing not less than 30 days prior to the scheduled starting
date of the factory tests.
B. The Royal Commission reserves the right of deputing their representative for
witnessing the factory test.
C. Upon completion of factory test and before shipment of the equipment/material, the
Contractor shall submit 5 certified copies of test reports not latter than 10 days after
completion of all factory tests for review/approval by the Royal Commission.
A. Luminaires installed indoors shall be suitable for continuous operation under the
following service conditions:
Rev 0
6 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
a) A maximum of 40°C.
b) A minimum of 0°C.
c) Average temperature measured over a period of 1 month is 35°C.
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
2. Store all units protected from weather and protect all units from physical
damage from work of other trades.
Rev 0
7 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by this Specification shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
B. All parts and materials shall be new, good quality and shall be selected by the
Contractor and the manufacturer to perform as specified herein.
2.02 EQUIPMENT
B. Equipment shall have been in commercial production for at least 8 years prior to
supply with an established historical database of good performance.
C. Equipment shall be factory assembled and tested to the greatest extent practical to
minimize field erection.
2.03 LUMINAIRES
A. Watt and voltage rating, shape, size, housing, reflector, material and type of Lighting
Luminaires shall be as shown on the Contract Drawings/Documents.
B. Lamps used for indoor installations shall be Incandescent, Fluorescent and High
Intensity Discharge lamps. All lamps shall conform to relevant standards as
specified in par. 1.03.
1. Incandescent Lamps
2. Fluorescent Lamps
Rev 0
8 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
c) Energy saving warm white color lamp shall be used in public areas while
cool white color lamp shall be used for tunnels and ancillary spaces.
b) High Pressure Sodium Vapor Lamp shall be used in areas where color
rendering effect is not important.
1. Incandescent Lamps
2. Fluorescent Lamp
1. Incandescent Lamps
Rev 0
9 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
2. Lamp holders for fluorescent lamps shall conform to UL 542/IEC 60400 and
shall be:
3. Lamp holders for mercury vapor lamp shall be as specified in par. 2.02 D.1.a
except voltage rating which shall be 600 V.
1. Ballasts for fluorescent lamps shall be high frequency electronic ballast and
shall comply with UL 935 and relevant standards as specified in par. 1.03.
High frequency electronic ballast shall have following features:
c) The ballast shall operate the lamps in a manner that will not adversely
curtail the normal life of the lamp. The light output shall not vary by more
than ± 5% for a ± 10% variation of the input voltage about the center
design voltage. Light output shall remain constant for a ± 5% variation of
the input voltage.
d) Ballast shall check proper functioning of light source and disengage any
failed lamp. The ballast shall ignite new lamp after replacement.
e) The ballasts shall be "A" sound rated. Where an "A" rating is not
available, use the next higher rating. The noise level, 600 mm from the
installed fixture, shall not exceed 30 db.
f) The flicker of ballast shall be less than 5% and shall not be visible.
g) The ballast shall have high power factor and shall not be less than 95%.
2. Ballasts for High Intensity Discharge Lamp shall comply with UL 1029 and
relevant standards as specified in par. 1.03. The ballast shall:
Rev 0
10 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
c) Have not less than Class B sound ratings for interior fixtures, when
available. Ballasts which are not available with Class B ratings shall be
of the next standard rating.
1. The diffuser shall be made of one piece virgin acrylic, clear acrylic, or
polycarbonate plastic or as specified on Contract Drawings/Documents, and
shall have the following characteristics:
a) Inner surface of the diffuser shall be diffusing type while outer surface
shall be smooth.
c) The color of diffuser material shall not change when used with 4500 K
fluorescent lamp.
a) The minimum thickness of globe shall be 3.2 mm. Its surface shall be
free from visible mold seam.
b) Reduction in globe strength shall not be more than 10% after 5 years of
its use.
Rev 0
11 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
I. Construction of Luminaires
1. The metal parts of luminaires shall be formed to prevent warping and sagging.
Housing, trim and lens frame shall be true, straight (unless intentionally
curved), and parallel to each other as designed.
2. Wireways and fittings shall be free of burrs and sharp edges and shall
accommodate internal and branch circuit wiring without damage to the wiring.
4. When installed, any exposed fixture housing surface, trim frame, door frame
and lens frame shall be free of light leaks; lens doors shall close in a light tight
manner.
7. Hinged door closure frames shall operate smoothly without bending when the
fixture is in the installed position, and latches shall function easily by finger
action without the use of tools.
a) All metal surfaces shall be thoroughly cleaned to make it free from rust,
grease, dust and other deposits. After cleaning the surface, apply a coat
of corrosion resistant primer followed by final finish.
c) Interior light reflecting finishes shall be white with not less than 88%
reflectance.
Rev 0
12 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
10. Provide all lighting fixtures with a specific means for grounding their metallic
wire ways and housings to an equipment grounding conductor.
A. Switching of Luminaires
a) The dimmer switches used for controlling light levels shall be of solid-
state design incorporating triac. The dimmer switch shall be wall-
mounted type with “OFF” position. The switch shall:
1) Raise or lower the light level from completely off at extreme
counter-clockwise rotation to full intensity.
2) Withstand in rush current during switching on of the lamp.
3) Withstand radio frequency interference.
Rev 0
13 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
d) Sensor switches can have an optional ambient light sensing feature with
an adjustment range to result in a lighting system not being turned "ON"
during occupancy with generous daylight contribution.
f) All sensors shall have a sensitivity adjustment feature to "tune in" for
proper operation for a variation of room or area geometrics. This
measure accepts the use of 2 or more sensor switches suitably
interconnected as a system for situations such as highly irregular areas,
partitioned workstation areas, very large areas, etc.
A. These buildings are classified as “High Bay” and “Low Bay” areas depending upon
height of the ceiling.
Rev 0
14 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
A. Mostly incandescent and fluorescent luminaires shall be used for indoor illumination
of commercial buildings. These areas require both general and specific task lighting.
1. Lighting in Offices
2. Task Lighting
A. The most effective method for calculating illumination level for large indoor areas is
the Lumen Method. This method is frequently used as it gives uniform distribution of
light over large areas using any type of luminaires.
B. The mathematical equation used in Lumen Method for calculating no. of luminaires to
obtain desired level of illumination is as follows:
c) A = Area in m²
Rev 0
15 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
e) CU = Coefficient of utilization
2. In most lighting design, the required maintained Lux intensity will be a known
quantity. It can be obtained from standard tables. Most frequently used
illumination levels are listed in Table 2A.
3. Initial lamp lumen for specified luminaire can be obtained from manufacturer’s
catalogs.
5. The output of lamp depreciates during service mainly due to loss of lumens
resulting from aging of luminaires. It also decreases due to accumulation of
dust, dirt and insects as well as chemical changes in reflecting surfaces.
C. Frequently used values of illumination level for calculating no. of luminaires for indoor
installations are indicated in Table 2A.
Rev 0
16 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
Rev 0
17 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
PART 3 EXECUTION
3.01 GENERAL
A. The Contractor shall provide all materials, equipment and labor as deemed
necessary for complete and proper execution of the work.
B. After the installation is complete and properly adjusted, the Contractor shall conduct
operating tests. The various equipment and systems shall be demonstrated to
operate in accordance with the requirements of the specifications. Tests shall be
performed in the presence of the Royal Commission's representative. The Contractor
shall provide electric power, instruments and personnel necessary for performing the
various tests.
A. General
1. All installation details, write up on handling of the equipment, instruction
manuals and latest revised drawings furnished by manufacturer shall be
available at site prior to installation of the equipment. These details shall be
reviewed by the Royal Commission’s representative. The details and
instructions furnished in these documents shall be followed carefully during
installation of the equipment.
2. Ensure that all buildings and rooms for the installation of the equipment are
ready, complete and clean. All embedded channels and anchor bolts shall be
in place as per layout drawings.
3. All the facilities required for transportation of electrical equipment from store to
site such as competent manpower, crane and trucks of adequate capacities
shall be supplied by the Contractor.
4. All equipment moved to the site shall be inspected for damage or deterioration
during storage. Tag numbers and nameplates shall be verified with the details
given on the Contract Drawings.
B. Installation of Luminaires
2. Align, mount and level the lighting luminaires uniformly. Avoid interference with
other equipment by providing sufficient clearances from them.
3. For suspended lighting fixtures, the mounting heights shall provide the
clearances between the bottoms of the fixtures and the finished floors as
shown on the Contract Drawings.
Rev 0
18 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
A. General
1. The Contractor shall carry out all site tests in accordance with approved test
procedure to ensure that the equipment and materials comply with the
specifications and operational requirements. All tests are subject to witnessing
by the Royal Commission’s representatives.
Rev 0
19 of 20 Contract No:
SECTION 16510
INTERIOR LUMINAIRES
2. At least 4 weeks prior to scheduled tests, the Contractor shall submit to the
Royal Commission an outline of the plan and procedures to be used in
performing the site inspection and site tests. This outline shall include a brief
description of the test equipment, connection diagrams, proposed tests and
procedures, test sheets, calculations, reference drawings and
minimum/maximum test and performance values in conformance with
applicable standards which will be used to determine conformance with the
specification and acceptability of the equipment and installation.
3. All testing equipment shall be calibrated by approved authorities and
calibration certificate shall be provided to the Royal Commission for their
review and approval.
4. Upon completion of installation and prior to final acceptance, each component
of each system shall be tested to the complete satisfaction of the Royal
Commission. The Contractor shall provide all test instrumentation, equipment
and accessories necessary for demonstration and putting the equipment into
operation.
B. Upon completion of all testing, the Contractor shall submit 5 certified copies of a
report attesting that each test has been performed in accordance with the approved
test procedures. The report for each test shall include the name of the person in-
charge of test and the date of performance. All factory and field test reports shall be
included in Operation and Maintenance Manuals.
2. Check the insulation of the cable at the point where it enters luminaires.
4. Check the signs of damages, if any, within the luminaires due to over heating.
7. Manually operate switches and contactor minimum for 10 times and check for
the freedom of all moving parts.
8. Test that the operation of automatic controls for switching of luminaires are as
per control schematics shown on the Contract Drawings.
9. Check that the initial illumination levels on working plane in various areas are
in conformance with the design.
END OF SECTION
Rev 0
20 of 20 Contract No: