Professional Documents
Culture Documents
~\
0
SECTION 15080:
KINGDOM
OFSAUDIARABIA ~~~I 4J.}!J1~I
RoyalCommissionlor Jubail & Yanbu ~ ~~ 46loJ Iri4+J1
SECTION 15080
MECHANICAL INSULATION
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 2
1.05 DEFINITIONS....................................................................................................... 5
1.06 SUBMITTALS....................................................................................................... 6
3.02 INSTALLATION.................................................................................................. 47
PART 1 GENERAL
A. This Section covers the furnishing and installation of acceptable insulation materials
in the location and quantities shown in the drawings. It shall include labor, tools and
equipment required to complete the work. The Contractor shall include the following:
2. Insulate exposed, bare or stripped off insulation materials for hot water line in
plumbing system.
3. Provide duct sound insulation or acoustic duct lining where necessary to meet
noise criteria described in SECTION 15070.
5. Refrigerant piping.
7. Waste water drain piping (partial from F.D) when used as A/C condensate with
indirect waste funnel discharge point.
3. Air conditioning plenums, housings, and cold sections that are not factory
insulated.
F. Acoustic liner.
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials, products and workmanship. In case of conflict between these
standards and the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment, materials and
processes conforming to one group of codes and standards.
Thermal Insulation
15. ASTM C585 Standard Practice for Inner and Outer Diameters of
Rigid Thermal Insulation for Nominal Sizes of Pipe
and Tubing (NPS System)
19. ASTM C612 Standard Specification for Mineral Fiber Block and
Board Thermal Insulation
20. ASTM C795 Standard Specification for Thermal Insulation for Use
in Contact with Austenitic Stainless Steel
22. ASTM C1071 Standard Specification for Fibrous Glass Duct Lining
Insulation (Thermal and Sound Absorbing Material)
27. ASTM D2842 Standard Test Method for Water Absorption of Rigid
Cellular Plastics
2. NFPA 90B Standard for the Installation of Warm Air Heating and
Air Conditioning Systems
3. NFPA 101 Code for Safety to Life from Fire in Buildings and
Structures
1.05 DEFINITIONS
A. concealed spaces: Spaces out of sight. For example, above ceilings; below floors;
between double walls; furred-in areas; pipe and duct shafts; and similar spaces.
B. conditioned space: An area, room or space normally occupied and being heated or
cooled for human habitation by any equipment.
C. exposed: Open to view. For example, pipe running through a room and not covered by
other construction.
D. finished spaces: Spaces used for habitation of occupancy where rough surfaces are
plastered, paneled, or otherwise treated to provide a pleasing appearance.
F. outside: Open to view up to 1.5 m (5 ft.) beyond the exterior side of walls, above the
roof, and unexcavated or crawl spaces.
G. recirculating domestic hot water and heating hot water piping: Piping in which
water flows when the circulating pump is running. Piping runs which are not part of the
recirculating system are considered run-outs and are not required to be insulated.
H. unfinished spaces: Spaces used for storage or work areas where appearance is not a
factor, such as unexcavated spaces and crawl space.
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
3. Catalog data for each type of insulation system including the following
information:
a) Density in kg/m3.
d) Perm rating.
g) Description of:
1) Adhesives.
2) Mechanical fasteners.
3) Application, finishing, and flashing materials and methods.
4. Product Data
5. Shop Drawings
6. Verification Samples
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing to achieve the specified
quality to the approval of the Royal Commission in accordance with
SECTION 01450.
1. All insulation, jackets, facings, and adhesive used shall have fire and smoke
hazard ratings as tested by procedure ASTM E84, not exceeding flame spread
of 25 and smoke developed of 50. Accessories such as adhesives, mastics,
cements, tapes and cloths for fittings shall have similar component ratings.
C. Installer's Qualifications
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
1. All piping shall be insulated unless otherwise noted. Pipe insulation shall be
continuous and installed on all fittings and appurtenances unless specified
otherwise. Installation shall be with full length units of insulation and using a
single cut piece to complete a run. Cut pieces or scraps abutting each other
shall not be used. Pipe insulation shall be omitted on the following:
b) Sanitary drain lines and vent piping that does not pass through
conditioned plenum space.
c) Unions.
d) Strainers.
4. Where penetrating floors, the aluminum jacket shall extend from a point below
the backup material to a point 250 mm (10 in.) above the floor with one band at
the floor and one not more than 25 mm (1 in.) from the end of the aluminum
jacket.
5. Where penetrating waterproofed floors, the aluminum jacket shall extend from
below the backup material to a point 50 mm (2 in.) above the flashing with a
band 25 mm (1 in.) from the end of the aluminum jacket.
a) Where penetrating exterior walls, the aluminum jacket required for pipe
exposed to weather shall continue through the sleeve to a point 50 mm
(2 in.) beyond the interior surface of the wall.
8. The insulations for exterior application shall butt tightly to the top of flashing
and interior insulation.
9. The exterior aluminum jacket shall extend 50 mm (2 in.) down beyond the end
of the insulation to form a counterflashing.
10. The flashing and counterflashing shall be sealed underneath with caulking.
d) The insert shall cover not less than the bottom 180° arc of the pipe.
e) Inserts shall be the same thickness as the insulation, and shall extend
50 mm (2 in.) on each end beyond the protection shield. Inserts are not
required with Type 39 pipe saddles.
1. Flexible cellular pipe insulation shall be tubular form for pipe sizes 125 mm
(5 in.) and less.
2. Sweat fittings shall be insulated with miter-cut pieces the same size as on
adjacent piping.
3. Screwed fittings shall be insulated with sleeved fitting covers fabricated from
miter cut pieces and shall be overlapped and sealed to the adjacent pipe
insulation.
2. Insulation Thickness
- 18.3 to - 34.4 (- 1
75 75 75 90 90 100
to -3 0) (Cellular -
(3) (3) (3) (3½) (3½) (4)
Glass)
- 18.3 to - 34.4 (- 1
38 50 65 65 75 75
to - 30) (Mineral -
(1½) (2) (2½) (2½) (3) (3)
Fiber)
Domestic (Flexible 50 50 50
- - - -
Cellular) (2) (2) (2)
Interior (Mineral 50 50 50 25 25 25
-
Fiber) (2) (2) (2) (1) (1) (1)
3. Vapor Barrier Jacket for Fibrous and Cellular Glass Insulated Pipe
4. Insulation for Straight Runs on Fibrous and Cellular Glass Insulated Pipe
Inside Building
a) Insulation shall be applied to the pipe with joints tightly butted. The ends
of fibrous insulation shall be sealed off with vapor barrier coating at
intervals not to exceed 4.6 m (15 ft.).
b) Longitudinal laps of the jacket material shall overlap not less than
38 mm (1½ in.). Butt strips 75 mm (3 in.) wide shall be provided for
circumferential joints.
c) Laps and butt strips shall be secured with adhesive and stapled on
100 mm (4 in.) centers if not factory self-sealing.
a) Pipe insulation shall have tapered ends thoroughly coated with a vapor
barrier coating not more than 150 mm (6 in.) from each flange, union,
valve, anchor, or fitting in all directions. Insulation may be premolded or
segmented. Insulation of the same thickness and conductivity as the
adjoining pipe insulation shall be used. If nesting size insulation is used,
the insulation should be overlapped 50 mm (2 in.) or one pipe diameter.
Loose fill mineral fiber or insulating cement shall be used to fill the voids.
Insulation for elbows less than 75 mm (3 in.) size shall be remolded.
Insulation for elbows 75 mm (3 in.) size and larger shall be either
premolded or segmented. Elbows insulated using segments shall not
have less than 3 segments per elbow. Insulation may be secured by
wire until finish is applied.
inserts shall be used under the fitting covers for elbows. Insulation
thickness for inserts shall be as recommended by the insulation
manufacturer for the prescribed application temperatures. Elsewhere
field cut inserts may be used. The covers shall be secured by PVC
vapor barrier tape or adhesive or with tacks made for securing PVC
covers. All tape seams and tacks shall then be coated with vapor barrier
coating.
1. Aboveground hot water pipeline shall be insulated as per the Table 1C.
Steamed or hot Mineral fiber with all service jacket except mechanical room
water heating which shall have aluminum jacket.
2. Insulation Thickness
Mineral 25 25 25 25 38 38 38
Fiber (1) (1) (1) (1) (1.5) (1.5) (1.5)
Cellular 38 38 38 38 50 50 50
Glass (1.5) (1.5) (1.5) (1.5) (2) (2) (2)
Flexible 6.5 25 25 25 25
Cellular (½) (1) (1) (1) (1)
4. Insulation for Straight Runs on Fibrous and Cellular Glass Insulated Pipe
Longitudinal laps of the jacket material shall overlap not less than
38 mm (1½ in.), and butt strips 75 mm (3 in.) wide shall be provided for
circumferential joints. Laps and butt strips shall be secured with
adhesive and stapled on 100 mm (4 in.) centers if not factory self-
sealing. Adhesive may be omitted where pipe is concealed.
a) The run of the line pipe insulation shall have the ends brought up to the
item. Insulation of the same thickness and conductivity as the adjoining
pipe insulation, either premolded or segmented, shall be placed around
the item abutting the adjoining pipe insulation, or if nesting size
insulation is used, overlapping 50 mm (2 in.) or one pipe diameter.
Loose fill mineral fiber or insulating cement shall be used to fill the voids.
Insulation for elbows less than 75 mm (3 in.) size shall be premolded.
Insulation for elbows 75 mm (3 in.) size and larger shall be either
premolded or segmented. Elbows insulated using segments shall have
not less than 3 segments per elbow. Insulation may be wired or taped on
until finish is applied.
1. The Contractor shall supply and install pre-insulated chilled water piping
system with the following requirements:
a) Core Pipe
1) The core pipe shall be made from extruded, rigid high-density
polyethylene (HDPE) pipe to DIN 8074/8075 with material
designation of PE 100 with MRS of 10 MPa at 20°C, 50 years of
service and pressure rating of PN 16 SDR 11. All pipes shall be
with straight plain ends with standard length of 12 m.
2. Aluminum Jacket
a) The jacket for hot piping may be factory applied. The jacket shall overlap
not less than 50 mm (2 in.) at longitudinal and circumferential joints and
shall be secured with bands at not more than 300 mm (12 in.) centers.
Longitudinal joints shall be overlapped down to shed water and located
at 4 or 8 o'clock positions. Joints on piping 15.6°C (60°F) and below
shall be sealed with caulking while overlapping to prevent moisture
penetration. Where jacketing on piping 15.6°C (60°F) and below abuts
an un-insulated surface, joints shall be sealed with caulking. Joints on
piping above 15.6°C (60°F) shall be sealed with a moisture barrier.
a) Fuel oil.
b) Water line between new central control station and new well house.
2. Type of Insulation
a) All below ground pipe shall be insulated with cellular 75 mm (3 in.) glass.
b) Insulation applied to the pipe shall have all joints tightly butted and
bedded together with bedding compound. Butt joints shall be staggered.
i) At termination points, other than building entrances, the mastic and cloth
or tape shall cover the ends of insulation and extend 50 mm (2 in.) along
the bare pipe.
1. All duct and equipment shall be externally insulated unless otherwise noted.
Corner angles shall be installed on external corners of insulation on ductwork
in exposed finished spaces before covering with jacket. Duct insulation shall
be omitted on the following:
d) In ceilings used as return air plenum, the supply duct always requires
insulation. Return duct and exhaust duct may not need insulation.
L. Insulation and Vapor Barrier for Cold Air Duct Below 15.6°C (60°F)
a) Supply ducts.
3. Vapor Barrier
4. Duct Insulation
Class 2 adhesive around the entire perimeter of the duct in 150 mm (6 in.)
wide strips on 300 mm (12 in.) centers. For rectangular and oval ducts,
600 mm (24 in.) and larger insulation shall be additionally secured to bottom of
ducts by the use of mechanical fasteners. Fasteners shall be spaced on
450 mm (18 in.) centers and not more than 450 mm (18 in.) from duct corners.
2. For rectangular, oval and round ducts, mechanical fasteners shall be provided
on sides of duct risers for all duct sizes. Fasteners shall be spaced on 450 mm
(18 in.) centers and not more than 450 mm (18 in.) from duct corners.
Insulation shall be impaled on the mechanical fasteners where used and shall
be pressed thoroughly into the adhesive. Care shall be taken to insure vapor
barrier jacket joints overlap 50 mm (2 in.). The insulation shall not be
compressed to a thickness less than that specified. Insulation shall be carried
over standing seams and trapeze-type duct hanger.
4. Jacket overlaps shall be secured under the overlap with Class 2 adhesive and
stapled on 100 mm (4 in.) centers. Staples and seams shall be coated with a
vapor barrier coating. Breaks in the jacket material shall be covered with
patches of the same material as the vapor barrier. The patches shall extend
not less than 50 mm (2 in.) beyond the break or penetration in all directions
and shall be secured with Class 2 adhesive and staples. Staples and joints
shall be sealed with a brush coat of vapor barrier coating.
6. Insulation terminations and pin punctures shall be sealed and flashed with a
reinforced vapor barrier coating finish. The coating shall overlap the adjoining
insulation and un-insulated surface 50 mm (2 in.). Pin puncture coatings shall
extend 50 mm (2 in.) from the puncture in all directions.
2. Duct insulation shall be formed with minimum jacket seams, and in no case
shall a jacket seam be allowed on or within 75 mm (3 in.) of the duct corner.
Insulation shall be brought up to standing seams, reinforcing, and other vertical
projections and shall not be carried over. Vapor barrier jacket shall be
continuous across seams, reinforcing, and projections. When height of
projections is greater than the insulation thickness, insulation and jacket shall
be carried over.
4. Breaks and ribs or standing seam penetrations in the jacket material shall be
covered with a patch of the same material as the jacket. Patches shall extend
not less than 50 mm (2 in.) beyond the break or penetration and shall be
secured with Class 2 adhesive and stapled. Staples and joints shall be sealed
with a brush coat of vapor barrier coating.
6. Insulation terminations and pin punctures shall be sealed and flashed with a
reinforced vapor barrier coating finish. The coating shall overlap the adjoining
insulation and uninsulated surface 50 mm (2 in.). Pin puncture coatings shall
extend 50 mm (2 in.) from the puncture in all directions.
a) Supply ducts.
e) Filter boxes.
f) Mixing boxes.
3. Adhesive Finish
4. Duct Insulation
1. For rectangular, oval and round ducts, insulation shall be attached by applying
Class 2 adhesive around the entire perimeter of the duct in 150 mm (6 in.)
wide strips on 300 mm (12 in.) centers. For rectangular and oval ducts 600 mm
(24 in.) and larger, insulation shall be secured to the bottom of ducts by the
use of mechanical fasteners. Fasteners shall be spaced on 450 mm (18 in.)
centers and not more than 450 mm (18 in.) from duct corner.
2. For rectangular, oval and round ducts, mechanical fasteners shall be provided
on sides of duct risers for all duct sizes. Fasteners shall be spaced on 450 mm
(18 in.) centers and not more than 450 mm (18 in.) from duct corners.
3. The insulation shall be impaled on the mechanical fasteners where used and
shall be pressed thoroughly into the adhesive. The insulation shall not be
compressed to a thickness less than that specified. Insulation shall be carried
over standing seams and trapeze-type hangers.
5. Insulation shall overlap not less than 50 mm (2 in.) at joints and the laps shall
be secured with staples on 100 mm (4 in.) centers.
1. For rectangular ducts, the rigid insulation shall be secured to the duct by the
use of mechanical fasteners on all 4 sides of the duct, spaced not more than
300 mm (12 in.) apart and not more than 75 mm (3 in.) from the edges of the
insulation joints. A minimum of 2 rows of fasteners shall be provided for each
side of duct 300 mm (12 in.) and larger and a minimum of one row for each
side of duct less than 300 mm (12 in.).
a) Handholes.
b) Cleanouts.
c) ASME stamps.
d) Manufacturer's nameplates.
2. Insulation
3. Installation
4. Coating
5. Penetrations
2. Insulation
3. Installation
4. Equipment Handling Dual Temperature Media Below and Above 15.6°C (60°F)
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
5. All products shall be inspected at time of delivery for damage and for
compliance with specifications.
6. Any products that are damaged or found not to be in accordance with the
specifications shall be immediately repaired or replaced.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
A. Use the specified molded pipe insulation on all piping unless otherwise indicated.
2. Finish insulation located indoors with ASJ (All Service Jacket) jacket, unless
otherwise indicated.
3. Finish insulation exposed outdoors and in mechanical rooms and high traffic
areas with the following jacketing, unless otherwise indicated:
a) Jacket
1) PVC jacketing and fitting covers.
b) Where PVC jacketing cannot be used, use specified metal jacketing and
fitting covers.
4. Do not use PVC jacketing where exposed to direct sunlight and insulation is
more than 500 mm (20 in.) outside diameter, or where insulation thickness is
not adequate to ensure that the surface temperature of PVC does not exceed
51°C (125°F).
1. Fiber glass pipe insulation, meeting ASTM C547, C585, and C795; rigid,
molded, non-combustible.
2. Vapor retardant all service jacket complying with ASTM C1136 Type I.
1. Molded PVC high-impact jacketing, fitting covers, and accessories, with fiber
glass inserts.
c) PVC
1) Minimum thickness of 0.508 mm (0.020 in.), outdoor weatherable.
d) Insulation Inserts
1) Fiber glass; thermal conductivity (K-value) of 0.033 W/m °K
(0.23 Btu in/hr ft2 °F) 24°C (75°F).
e) Closures
1) Stainless steel tacks, matching PVC tape, or PVC adhesive as
recommended by manufacturer.
a) Overlap
1) 50 mm (2 in.), minimum.
b) Fittings
1) Die-shaped with factory-applied moisture barrier.
F. Fitting Insulation
1. Where molded PVC fitting covers are not used, provide preformed fitting
insulation made of molded or mitered fiber glass board and protected with
field-applied fitting covers or metal fittings.
G. Glass Fiber
1. Insulation
a) White Kraft paper with glass fiber yarn, bonded to aluminized film;
moisture vapor transmission when tested in accordance with ASTM E96
of 0.029 ng/Pa s m (0.02 perm in.).
3. Tie Wire
5. Insulating Cement/Mastic
a) Cloth
1) Untreated; 305 g/m² (9 oz/yd²) weight.
b) Blanket
1) 16 kg/m³ (1 lb/ft³) density.
c) Weave
1) 5 x 5.
a) Cloth
1) Untreated; 305 g/m² (9 oz/yd²) weight.
9. Insulating Cement
a) ASTM C449M.
H. Cellular Glass
1. Insulation
2. Tie Wire
3. Insulating Cement
a) ASTM C449M.
1. Insulation Material
J. Polyethylene
1. Insulation
1. Insulation
L. Jackets
1. PVC Plastic
a) Jacket
1) One piece molded type fitting covers and sheet material, off-white
color.
(a) Minimum Service Temperature
(i) - 18°C (0°F).
(b) Maximum Service Temperature
(i) 66°C (150°F).
(c) Moisture Vapor Permeability
(i) 0.00029 ng/Pa s m² (0.002 perm in.), maximum,
when tested in accordance with ASTM E96.
(d) Thickness
(i) 0.25 mm (10 mil).
(e) Connections
(i) Brush on welding adhesive.
2. ABS Plastic
a) Jacket
1) One piece molded type fitting covers and sheet material, off-white
color.
3. Canvas Jacket
a) UL listed 220 g/m² (6 oz/yd²) plain weave cotton fabric treated with dilute
fire retardant lagging adhesive.
1) Lagging Adhesive
(a) Compatible with insulation.
4. Aluminum Jacket
2) Finish
(a) Smooth.
3) Metal Jacket Bands
(a) 10 mm (3/8 in.) wide; 0.25 mm (0.010 in.) thick stainless
steel.
1. Insulation
b) The leak detection system consists of the following main parts and
equipment:
1) Alarm wires installed in the insulation of the pipes and fittings. The
wire of the individual pipes are field-connected to each other.
2) Megger for field measurement.
3) Monitoring unit.
4) Matching boxes.
5) Connected cables.
A. Use the specified rigid insulation on all equipment indicated to be insulated, unless
otherwise indicated.
2. Where equipment shape does not accommodate rigid boards, use elevated
temperature insulation, either semi-rigid or flexible.
6. Finish
a) PVC jacketing.
4. Finish
a) PVC jacketing.
D. Rigid Insulation
1. Fiber glass insulation board meeting ASTM C612 Type IA and IB; rigid.
c) Medium Density
1) 48 kg/m³ (3 lb/ft³), minimum.
(a) Thermal Conductivity (K-Value)
(i) 0.033 W/m °K (0.23 Btu in/hr ft2 °F), when tested in
accordance with ASTM C177 at 24°C (75°F).
(b) ASJ (All Service Jacket) Facing
(i) Vapor retardant all service jacket conforming to
ASTM C1136 Type I.
(c) FSK (Foil Scrim Kraft) Facing
(i) Vapor retardant foil scrim Kraft conforming to
ASTM C1136 Type II.
E. Semi-Rigid Insulation
1. Pipe and Tank Insulation; semi-rigid fiber glass board, limited combustible.
1. Elevated temperature board; ASTM C612 Type IA, IB, and II; rigid fiber glass
board, noncombustible.
b) Density
1) 45 kg/m³ (2.8 lb/ft³).
1. Elevated temperature panel 1000°; ASTM C612 Type II and III; semi-rigid fiber
glass board, noncombustible.
b) Density
1) 38 kg/m³ (2.4 lb/ft³).
b) Density
1) 26 kg/m³ (1.6 lb/ft³).
b) Density
1) 18 kg/m³ (1.1 lb/ft³).
J. PVC Jacketing
K. Metal Jacketing
1. Insulation
a) Kraft paper reinforced with glass fiber yarn and bonded to aluminized
film.
1) Moisture Vapor Permeability
(a) 0.029 ng/Pa s m² (0.02 perm in.), when tested in
accordance with ASTM E96.
2) Secure with self-sealing longitudinal laps and butt strips.
3) Secure with outward clinch expanding staples and vapor barrier
mastic.
3. Tie Wire
5. Insulating Cement/Mastic
1. Insulation
a) Kraft paper reinforced with glass fiber yarn and bonded to aluminized
film.
d) Secure with outward clinch expanding staples and vapor barrier mastic.
3. Facing
5. Insulating Cement/Mastic
N. Cellular Glass
1. Insulation
2. Tie Wire
3. Insulating Cement
a) ASTM C449M.
1. Insulation
P. Jackets
1. PVC Plastic
a) Jacket
1) Sheet material, off-white color.
(a) Minimum Service Temperature
(i) - 40°C (- 40°F).
(b) Maximum Service Temperature
(i) 66°C (150°F).
(c) Moisture Vapor Permeability
(i) 0.029 ng/Pa s m² (0.02 perm in.), when tested in
accordance with ASTM E96.
(d) Thickness
(i) 0.25 mm (10 mil).
(e) Connections
(i) Brush on welding adhesive.
2. Canvas Jacket
a) UL listed 220 g/m² (6 oz/yd²) plain weave cotton fabric treated with dilute
fire retardant lagging adhesive.
1) Lagging Adhesive
3. Aluminum Jacket
A. Use one of the following materials on exterior of ducts, unless otherwise indicated:
1. Flexible insulation.
2. Rigid insulation.
3. R-Value
B. Use same insulation as specified for high temperature equipment on ducts operating
at over 177°C (350°F).
D. Flexible Insulation
1. Duct Wrap; flexible fiber glass blanket insulation meeting ASTM C553 Types I,
II and III, and ASTM C1290; limited combustible.
b) Density
1) Concealed Areas
(a) Minimum 12 kg/m³ (0.75 lb/ft³).
2) Exposed Areas
(a) Minimum 16 kg/m³ (1 lb/ft³).
c) No Facing
1) Maximum service temperature 177°C (350°F).
E. Rigid Insulation
1. Insulation Board; fiber glass insulation board meeting ASTM C612 Type IA and
IB; rigid.
c) Medium Density
1) 48 kg/m³ (3 lb/ft³), minimum.
(a) Thermal Conductivity (K-Value)
(i) 0.033 W/m °K (0.23 Btu in/hr ft² °F), when tested in
accordance with ASTM C177 at 24°C (75°F).
(b) Facing
(i) Vapor retarder all service jacket (ASJ) conforming to
ASTM C1136 Type I.
(c) Facing
(i) Vapor retarder foil scrim Kraft (FSK) conforming to
ASTM C1136 Type II.
F. Duct Liner
1. Duct Liner E-M, complying with ASTM C1071 Type I and NFPA 90A and 90B;
or Rigid Plenum Liner, complying with ASTM C1071 Type II and NFPA 90A
and 90B.
a) Insulation
1) Incombustible glass fiber, flexible blanket, rigid board, and
preformed round liner board; impregnated surface and edges
coated with poly vinyl acetate polymer, or acrylic polymer shown
to be fungus and bacteria resistant by testing to ASTM G21.
c) Service Temperature
1) Up to 121°C (250°F).
f) Adhesive
1) ASTM C916. Waterproof, fire-retardant type.
g) Liner Fasteners
1) Galvanized steel, self-adhesive pad with integral head.
G. Aluminum Jacketing
H. PVC Jacketing
1. Insulation
a) Kraft paper with glass fiber yarn and bonded to aluminized film.
a) Kraft paper reinforced with glass fiber yarn and bonded to aluminized
film, with pressure sensitive rubber based adhesive.
5. Tie Wire
1. Insulation
a) Kraft paper with glass fiber yarn and bonded to aluminized film.
a) Kraft paper reinforced with glass fiber yarn and bonded to aluminized
film, with pressure sensitive rubber based adhesive.
a) Cloth
1) Untreated; 305 g/m² (9 oz/yd²) weight, glass fabric.
K. Jackets
1. Canvas Jacket
a) UL listed 220 g/m² (6 oz/yd²) plain weave cotton fabric treated with dilute
fire retardant lagging adhesive.
1) Lagging Adhesive
(a) Compatible with insulation.
3. Aluminum Jacket
a) ASTM B209M.
1) Thickness
(a) 0.40 mm (0.016 in.) sheet.
2) Finish
(a) Smooth.
3) Joining
(a) Longitudinal slip joints and 50 mm (2 in.) laps.
4) Fittings
(a) 0.4 mm (0.016 in.) thick die shaped fitting covers with
factory attached protective liner.
5) Metal Jacket Bands
(a) 10 mm (3/8 in.) wide; 0.38 mm (0.015 in.) thick aluminum.
6) Metal Jacket Bands
(a) 10 mm (3/8 in.) wide; 0.25 mm (0.010 in.) thick stainless
steel.
A. Joint Tape
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that piping has been tested before applying insulation materials.
B. Verify that surfaces are clean and dry, with foreign material removed.
3.02 INSTALLATION
A. Piping Insulation
3. Exposed Piping
b) Insulate fittings, joints, and valves with molded insulation of like material
and thickness as adjacent pipe. Finish with glass cloth and vapor barrier
adhesive or PVC fitting covers.
1. Installation Procedures
c) Connect both the cables from the megger to the pre-insulated HDPE
pipe. Set the megger to Mega Ohms, press TEST button. The readout
shall be Ohms, if not, check the connection to the pipe.
d) Insulation Test
1) Leave the black cable connected to the HDPE pipe and connect
the red cable of the megger to the tinned wire. Press the TEST
button. The reading shall be infinity. Similarly, do the same test to
the copper wire.
e) Form a loop at the start point of the pipeline by crimping the copper and
tinned wires. Repeat step as in par. 3.02 B.1.d.
f) Repeat steps as in pars. 3.02 B.1.c, d and e. The reading will increase
at a rate of 2.2 Ohms/100 m pipe.
C. Equipment Insulation
a) Do not insulate.
3. Exposed Equipment
5. Fill joints, cracks, seams, and depressions with bedding compound to form
smooth surface. On cold equipment, use vapor barrier cement.
8. For hot equipment containing fluids 60°C (140°F) or less, do not insulate
flanges and unions, but bevel and seal ends of insulation.
9. For hot equipment containing fluids over 60°C (140°F), insulate flanges and
unions with removable sections and jackets.
a) Application
1) Equipment 40 mm (1½ in.) diameter or larger.
b) Shields
1) Galvanized steel between hangers and inserts.
c) Insert Location
1) Between support shield and equipment and under the finish
jacket.
d) Insert Configuration
1) Minimum 150 mm (6 in.) long, of same thickness and contour as
adjoining insulation; may be factory fabricated.
e) Insert Material
1) Hydrous calcium silicate insulation or other heavy density
insulating material suitable for the planned temperature range.
a) Provide vapor barrier jacket or finish with glass mesh reinforced vapor
barrier cement. Cover with aluminum jacket with seams located on
bottom side of horizontal equipment.
15. Cover glass fiber insulation with metal mesh and finish with heavy coat of
insulating cement aluminum jacket.
D. Duct Insulation
b) Insulate fittings and joints. Where service access is required, bevel and
seal ends of insulation.
6. Exterior Applications
a) Provide insulation with vapor barrier jacket. Cover with outdoor finished
jacket.
a) Secure insulation with vapor barrier with wires and seal jacket joints with
vapor barrier adhesive or tape to match jacket.
e) Stop and point insulation around access doors and damper operators to
allow operation without disturbing wrapping.
e) Duct dimensions indicated are net inside dimensions required for air
flow. Increase duct size to allow for insulation thickness.
END OF SECTION