SECTION 15150

SANITARY WASTE AND VENT PIPING

PART 1 GENERAL

1.1 SUMMARY

A. Section includes pipe, pipe fittings, connections and equipment for sanitary sewer
piping systems. This section also includes floor drains, cleanouts, interceptors,
manholes and sewage ejectors.

B. Related Sections:
1. Pipes and Tubes
2. Concrete Forms and Accessories: Execution requirements for placement
of inserts and sleeves specified by this section.
3. Cast-in-Place Concrete: Execution requirements for placement of concrete
specified by this section.
4. Paints and Coatings: Execution requirements for painting material
specified by this section.
5. Mechanical Identification: Product requirements for pipe identification for
placement by this section.
6. Wiring Connections: Execution requirements for electric connections to
equipment specified by this section.
7. Motors: Product requirements for motors for placement by this section.

1.2 REFERENCES

A. SME B13 (American Society of Mechanical Engineers) - Malleable Iron


Threaded Fittings.

B. ASME B123 (American Society of Mechanical Engineers) - Cast Copper Alloy


Solder Joint Drainage Fittings - DWV.

C. ASME B129 (American Society of Mechanical Engineers) - Wrought Copper and


Wrought Copper Alloy Solder Joint Drainage Fittings - DWV.

D. ASME B132 (American Society of Mechanical Engineers) - Cast Copper Alloy


Solder Joint Fittings for Sovent Drainage Systems.

E. ASME B31.9 (American Society of Mechanical Engineers) - Building Services


Piping.

F. ASTM A53 - Pipe, Steel, Black and Hot-Dipped Zinc Coated, Welded and
Seamless.

Sanitary Waste And Vent Piping 15150 – Page 1


of 15
G. ASTM A74 - Cast Iron Soil Pipe and Fittings.

H. ASTM B32 - Solder Metal.

I. ASTM B306 - Copper Drainage Tube (DWV).

J. ASTM C14 - Concrete Sewer, Storm Drain, and Culvert Pipe (ASTM C14M -
Concrete Sewer, Storm Drain, and Culvert Pipe Metric).

K. ASTM C425 - Compression Joints for Vitrified Clay Pipe and Fittings.

L. ASTM C564 - Rubber Gaskets for Cast Iron Soil Pipe and Fittings.

M. ASTM C1053 - Borosilicate Glass Pipe and fittings for Drain, Waste, and Vent
(DWV) Applications.

N. ASTM D2235 - Solvent Cement for Acrylonitrile - Butadiene - Styrene (ABS)


Plastic Pipe and Fittings.

O. ASTM D2564 - Solvent Cements for Poly (Vinyl Chloride) (PVC) Plastic Pipe
and Fittings.

P. ASTM D2661 - Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic


Drain, Waste, and Vent Pipe and Fittings.

Q. ASTM D2662 - Polybutylene (PB) Plastic Pipe (SIDR-PR) Based on Controlled


Inside Diameter.

R. ASTM D2665 - Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe
and Fittings.

S. ASTM D2729 - Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings.

T. ASTM D2751 - Acrylonitrile-Butadiene-Styrene (ABS) Sewer Pipe and Fittings.

U. ASTM D2855 - Making Solvent-Cemented Joints with Poly (Vinyl Chloride)


(PVC) Pipe and Fittings.

V. ASTM D2996 - Filament-Wound 'Fiberglass' (Glass-Fiber-Reinforced


Thermosetting-Resin) Pipe.

W. ASTM D2997 - Centrifugally Cast 'Fiberglass' (Glass-Fiber-Reinforced


Thermosetting-Resin) Pipe.

X. ASTM D3034 - Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings.

Y. ASTM D3262 - 'Fiberglass' (Glass-Fiber-Reinforced Thermosetting-Resin)


Sewer Pipe.

Sanitary Waste And Vent Piping 15150 – Page 2


of 15
Z. ASTM D3840 - 'Fiberglass' (Glass-Fiber-Reinforced Thermosetting-Resin)
Sewer Pipe Fittings for Non-Pressure Applications.

AA. ASTM D4160 - Reinforced Thermosetting Resin Pipe (RTRP) Fittings for Non-
Pressure Applications.

BB. ASTM E814 - Fire Tests of Through-Penetration Fire Stops.

CC. ASTM F477 - Elastomeric Seals (Gaskets) for Joining Plastic Pipe.

DD. ASTM F628 - Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain,


Waste, and Vent Pipe with a Cellular Core.

EE. ASTM F679 - Poly (Vinyl Chloride) (PVC) Large-Diameter Plastic Gravity
Sewer Pipe and Fittings.

FF. ASTM F708 - Design and Installation of Rigid Pipe Hangers.

GG. ASME A1121.1 (American Society of Mechanical Engineers) - Floor Drains.

HH. CISPI 301 (Cast Iron Soil Pipe Institute) - Cast Iron Soil Pipe and Fittings for
Hubless Cast Iron Sanitary Systems.

II. CISPI 310 (Cast Iron Soil Pipe Institute) - Joints for Hubless Cast Iron Sanitary
Systems.

JJ. MSS SP58 (Manufacturers Standardization Society of the Valve and Fittings
Industry) - Pipe Hangers and Supports - Materials, Design and Manufacturer.

KK. SP89 - Pipe Hangers and Supports - Fabrication and Installation Practices.

LL. ASTM C478/C478M - Pre-cast Reinforced Concrete Sections.

MM. PDI G-101 (Plumbing and Drainage Institute) - Testing and Rating Procedure for
Grease Interceptors with Appendix of Sizing and Installation Dat

NN. UL 1479 (Underwriters Laboratories, Inc.) - Fire Tests of Through-Penetration


Firestops.

1.3 SUBMITTALS

A. Shop Drawings: Indicate dimensions, weights, and placement of openings and


holes for sewage-ejectors, and manholes.

B. Product Data: Submit data on pipe materials, fittings, and accessories. Submit
manufacturers catalog information. Indicate component sizes, rough-in
requirements, service sizes, and finishes. Indicate pump type, capacity, power
requirements, certified pump curves showing pump performance characteristics

Sanitary Waste And Vent Piping 15150 – Page 3


of 15
with pump and system operating point plotted. Include NPSH curve when
applicable. Indicate electrical characteristics and connection requirements.

C. Manufacturer's Installation Instructions: Submit installation instructions for


material and equipment.

D. Manufacturer's Certificate: Certify products meet or exceed specified


requirements.

1.4 CLOSEOUT SUBMITTALS

A. Execution Requirements: Closeout procedures.

B. Project Record Documents: Record actual locations of equipment and clean-outs.

C. Operation and Maintenance Data: Submit frequency of treatment required for


interceptors. Include, spare parts lists, exploded assembly views for pumps and
equipment.

1.5 QUALIFICATIONS

A. Manufacturer: Company specializing in manufacturing products specified in this


section with minimum three years experience, and with sewage ejector service
facilities within 100 miles of Project.

B. Installer: Company specializing in performing Work of this section with


minimum three years experience

1.6 PRE-INSTALLATION MEETING

A. Administrative Requirements: Preinstallation meeting.

B. Convene minimum one week prior to commencing Work of this section.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Product Requirements: Product storage and handling requirements.

B. Protect piping systems from entry of foreign materials by temporary covers,


completing sections of the work, and isolating parts of completed system.

1.8 ENVIRONMENTAL REQUIREMENTS

A. Product Requirements.

B. Do not install underground piping when bedding is wet or frozen.

Sanitary Waste And Vent Piping 15150 – Page 4


of 15
1.9 FIELD MEASUREMENTS

A. Verify field measurements prior to fabrication.

1.10 WARRANTY

A. Execution Requirements: Product warranties and product bonds.

B. Furnish five year manufacturer warranty for sanitary waste and vent piping.

1.11 EXTRA MATERIALS

A. Execution Requirements: Spare parts and maintenance products.

B. Furnish two sets of pump seals

PART 2 PRODUCTS

2.1 SANITARY SEWER PIPING, BURIED BEYOND 5 FEET OF BUILDING

A. Cast Iron Pipe: ASTM A74 extra heavy service weight.


1. Fittings: Cast iron.
2. Joints: ASTM C564, neoprene gasket system or lead and oakum.

B. ABS Pipe: ASTM D2751 or ASTM F628.


1. Fittings: ABS.
2. Joints: ASTM D2235, solvent weld.

C. ABS Pipe: ASTM D2661 or ASTM D2751.


1. Fittings: ABS.
2. Joints: ASTM D2235, solvent weld.

D. PVC Pipe: ASTM D3034 SDR 3


1. Fittings: PV
2. Joints: ASTM F477, elastomeric gaskets.

E. PVC Pipe: ASTM D2665 or ASTM D3034.


1. Fittings: PV
2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement.

F. Concrete Pipe: ASTM C14 (ASTM C14M) or ASTM C7


1. Fittings: ASTM C14 (ASTM C14M) or ASTM C7
2. Joints: Elastomeric gaskets.

G. Copper Tube: (ASTM B251M) Type K


1. Fittings: ASME B123, cast bronze, or ASME B129, wrought copper.
2. Joints: ASTM B32, solder, Grade 50B.

Sanitary Waste And Vent Piping 15150 – Page 5


of 15
2.2 SANITARY SEWER PIPING, BURIED OF BUILDING

A. PVC Pipe: ASTM D2665 or ASTM D3034.


1. Fittings: PVC.
2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement.

B. PVC Pipe: ASTM D2665, ASTM D3034, or ASTM F679.


1. Fittings: PVC.
2. Joints: ASTM F477, elastomeric gaskets.

2.3 SANITARY SEWER PIPING, ABOVE GRADE

A. PVC Pipe: ASTM D2729.


1. Fittings: PVC.
2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement.

B. PVC Pipe: ASTM D2665.


1. Fittings: PVC.
2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement.

C. PVC Pipe: ASTM D1785 Schedule 40, or ASTM D2241 SDR-26 for not less than
150 psi pressure rating.
1. Fittings: ASTM D2466, PVC.
2. Joints: ASTM D2855, solvent weld with ASTM D2564 Solvent cement.

2.4 CHEMICAL RESISTANT SEWER PIPING

A. PVC Pipe: ASTM D2729 or ASTM D2665.


1. Fittings: PVC.
2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement.

2.5 PIPE HANGERS AND SUPPORTS

A. Drain, Waste, and Vent: Conform to ASME B31.9, ASTM F708,MSS SP58,MSS
SP69,MSS SP89.

B. Hangers for Pipe Sizes 1/2 to 1-1/2 inch malleable iron, Carbon steel, adjustable
swivel, split ring.

C. Hangers for Pipe Sizes 2 inches and Over: Carbon steel, adjustable, clevis.

D. Multiple or Trapeze Hangers: Steel channels with welded spacers and hanger
rods.

E. Wall Support for Pipe Sizes to 3 inches Cast iron hooks.

F. Wall Support for Pipe Sizes over 3 inches Welded steel bracket and wrought steel
clamp.

Sanitary Waste And Vent Piping 15150 – Page 6


of 15
G. Vertical Support: Steel riser clamp.

H. Floor Support: Cast iron adjustable pipe saddle, lock nut, nipple, floor flange, and
concrete pier or steel support.

I. Copper Pipe Support: Carbon-steel, copper-plated adjustable ring.

2.6 FIRE STOP SYSTEMS

A. General Purpose Fire Stopping Sealant: Water based non-slumping, premixed


sealant with in tumescent properties, rated for 3 hours in accordance with ASTM
E814 and UL 1479.

B. General Purpose Vibration Resistant Fire Stopping Sealant: Silicone based, non-
slumping, premixed sealant with in tumescent properties, vibration and moisture
resistant, rated for 3 hours in accordance with ASTM E814 and UL 1479.

C. DWV Plastic Pipe Systems Fire Stopping Sealant: Silicone based, premixed
sealant with in tumescent properties, vibration and moisture resistant, rated for 3
hours in accordance with ASTM E814 and UL 1479 with metal collars.

2.7 FLOOR DRAINS

A. Manufacturers:
1. Terain
2. Jason
Or approved equal

B. Floor Drain (FD-1): ANSI A1121.1; galvanized cast iron two piece body with
double drainage flange, weep holes, reversible clamping collar, and round,
adjustable nickel-bronze strainer.

C. Floor Drain (FD-2): ANSI A1121.1; galvanized cast iron two piece body with
double drainage flange, weep holes, [reversible clamping collar, and round,
adjustable round or square nickel-bronze strainer with removable perforated
sediment bucket.

D. Floor Drain (FD-3): ANSI A1121.1; galvanized cast iron two piece body with
double drainage flange, weep holes, reversible clamping collar, and round,
adjustable nickel-bronze strainer with polished bronze funnel

E. Floor Drain (FD-4): ANSI A1121.1; galvanized cast iron two piece body with
double drainage flange, weep holes, reversible clamping collar, and round,
adjustable nickel-bronze extra heavy duty strainer.

F. Floor Drain (FD-5): ANSI A1121.1; galvanized cast iron two piece body with
double drainage flange, weep holes, reversible clamping collar, and round,

Sanitary Waste And Vent Piping 15150 – Page 7


of 15
adjustable nickel-bronze extra heavy duty strainer with hinged grate and sediment
bucket.

G. Floor Drain (FD-6): Galvanized cast iron two piece body with drainage flange,
heavy duty grate 6 inches -12 inches wide, 12 inches -24 inches long, dome
strainer, end plates with gaskets.

2.8 FLOOR SINKS

A. Manufacturers:
1. Ideal Standard
2. Duravit
Approved or equal

B. Floor Sink (FS-1): Galvanized cast iron body with dome strainer and seepage
flange.

C. Floor Sink (FS-2): Square lacquered cast iron body with integral seepage pan,
epoxy coated interior, aluminum dome strainer, clamp collar, sediment bucket,
epoxy coated, nickel bronze frame and full grate.

2.9 PLANTER DRAINS

A. Manufacturers:
1. Terain
2. Jason
Approved or equal

B. ANSI A1121.2; galvanized cast iron body with sump.

C. Strainer: Removable polyethylene, cast metal ,cast aluminum, cast bronze, cast
iron dome with stainless steel, bronze screen.

D. Accessories: Membrane flange and membrane clamp with integral gravel stops.

2.10 CLEANOUTS

A. Manufacturers:
1. Terain
2. Jason
Approved or equal

B. Exterior Surfaced Areas (CO-1): Round or Square cast nickel bronze access frame
and non-skid cover.

C. Exterior Unsurfaced Areas (CO-2): Line type with lacquered cast iron body and
round epoxy coated cover with gasket.

Sanitary Waste And Vent Piping 15150 – Page 8


of 15
D. Interior Finished Floor Areas (CO-3): Galvanized cast iron body with anchor
flange, [reversible clamping collar,] threaded top assembly, and round scored
cover with gasket in service areas and round or square depressed cover with
gasket to accept floor finish in finished floor areas.

E. Interior Finished Wall Areas (CO-4): Line type with lacquered cast iron body and
round epoxy coated cover with gasket, and round stainless steel access cover
secured with machine screw.

F. Interior Unfinished Accessible Areas (CO-5): Calked or threaded type. Provide


bolted stack cleanouts on vertical rainwater leaders.

2.11 SUMPS

A. Precast concrete specified in Section Precast concrete Epoxy coated fabricated


steel, Glass fiber reinforced encased with 8 inches concrete with required
openings and drainage fittings.

2.12 GREASE INTERCEPTORS

A. Manufacturers:
1. Terain
2. Jason
Approved or equal

B. Construction:
1. Material: Epoxy coated fabricated steel
2. Rough in: Fully recessed in floor installation with anchor flange

C. Accessories: Multi-weir baffle assembly, integral deep seal trap, removable


integral flow control, sediment bucket

D. Cover: Steel, epoxy coated, non-skid with gasket, securing handle, and enzyme
injection port, recessed for floor finish, tile, terrazzo

E. Unit Rating: gpm flow and grease capacity.

2.13 OIL INTERCEPTORS

A. Manufacturers:
1. Jason
2. Terain
Approved or equal

B. Construction:
1. Material: Epoxy coated fabricated steel
2. Rough in: Fully recessed in floor installation with anchor flange.

Sanitary Waste And Vent Piping 15150 – Page 9


of 15
C. Accessories: Integral deep seal trap, removable integral flow control, adjustable
draw-off assembly, sediment bucket.

D. Cover: Steel, epoxy coated, with gasket, securing handle, and enzyme injection
port , recessed for floor finish

E. Unit Rating: gpm flow and oil capacity in kg.

2.14 SEDIMENT INTERCEPTORS

A. Manufacturers:
1. Jason
2. Terain
Approved or equal

B. Epoxy coated cast iron, Stainless steel or Precast concrete body and secured cover
with removable stainless steel sediment bucket.

2.15 MANHOLES

A. Formed Bottom Manholes: ASTM C478 (ASTM C478M); concrete masonry


units or reinforced precast concrete sections laid on cast-in-place reinforced
concrete foundation pad as specified in Section 03300.
1. Size: inch diameter.
2. Cover: Standard cast iron with minimum sized pick hole, and frame. Use
heavy-duty cover and frame in vehicular traffic areas.
3. Steps: 3/4 inch diameter galvanized steel on 16 inch centers.

2.16 SEWAGE EJECTORS

A. Manufacturers:
1. Jason
2. Terain
Approved or equal

B. Type: Vertical centrifugal, direct connected, simplex, duplex arrangement.

C. Casing: Cast iron volute with radial clearance around impeller, slide away
couplings

D. Impeller: Cast iron, Bronze; open non-clog, keyed to corrosion resistant alloy
steel stainless steel shaft.

E. Support: Cast iron pedestal motor support on steel floor plate with gas tight
gaskets.

F. Bearings: Oil lubricated bronze sleeve spaced maximum 48 inches and grease
lubricated ball thrust at floor plate.

Sanitary Waste And Vent Piping 15150 – Page 10


of 15
G. Drive: Flexible coupling to vertical, solid shaft ball bearing electric motor.

H. Sump: Steel cover plate with steel curb frame for grouting into concrete sump
with inspection opening and cover, and alarm fittings.

I. Controls Float operated mechanical alternator with float rod, stops, and corrosion
resistant float to alternate operation of pumps. Cut-in second pump on rising level
or lead pump failure. Furnish separate pressure switch high level alarm with
transformer, alarm bell, and stand pipe ,and extra set of wired terminals for
remote alarm circuit and emergency float switch with float rod, stops, and
corrosion resistant float to operate both pumps on failure of alternator.

2.17 SUBMERSIBLE SEWAGE EJECTORS

A. Manufacturers:
1. Jason
2. Terian
Or Approved equal

B. Casing: Cast iron or Bronze pump body and oil filled motor chamber.

C. Impeller: Cast iron; Bronze; open non-clog, stainless steel corrosion resistant
alloy steel] shaft.

D. Bearings: Ball bearings.

E. Sump: Fiberglass basin with steel cover plate

F. Accessories: Oil resistant 6 foot cord and plug with three-prong connector for
connection to electric wiring system including grounding connector.

G. Servicing: Slide-away coupling consisting of discharge elbow secure to sump


floor, movable bracket, guide pipe system, lifting chain and chain hooks.

H. Controls: Integral diaphragm, mercury switch, type level controls with separate,
liquid-level, and control high level alarm.

I. Controls: Motor control panel containing across-the-line electric motor starters


with ambient compensated quick trip overloads in each phase with manual trip
button and reset button, circuit breaker, control transformer, electro-mechanical
alternator, hand-off-automatic selector switches, pilot lights, high water alarm
pilot light, reset button and alarm horn. Furnish mercury switch liquid level
controls, steel shell switch encased in polyurethane foam with cast iron weight for
pump on (each pump), pump off (common), and alarm.

Sanitary Waste And Vent Piping 15150 – Page 11


of 15
PART 3 EXECUTION

3.1 EXAMINATION

A. Administrative Requirements: Coordination and project conditions.

B. Verify excavations are to required grade, dry, and not over-excavated.

3.2 PREPARATION

A. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe.

B. Remove scale and dirt , on inside and outside, before assembly.

C. Prepare piping connections to equipment with flanges or unions.

3.3 INSTALLATION

A. Extend cleanouts to finished floor or wall surface. Lubricate threaded cleanout


plugs with mixture of graphite and linseed oil. Provide clearances at cleanout for
snaking drainage system.

B. Encase exterior cleanouts in concrete flush with grade.

C. Install floor cleanouts at elevation to accommodate finished floor.

D. Provide non-conducting dielectric connections wherever jointing dissimilar


metals.

E. Route piping in orderly manner and maintain gradient. Route parallel and
perpendicular to walls.

F. Install piping to maintain headroom. Do not spread piping, conserving space.

G. Group piping whenever practical at common elevations.

H. Install piping to allow for expansion and contraction without stressing pipe,
joints, or connected equipment.

I. Provide clearance in hangers and from structure and other equipment for
installation of insulation and access to valves and fittings.

J. Provide access where valves and fittings are not exposed. Coordinate size and
location of access doors

K. Establish elevations of buried piping outside building to provide not less than ft
of cover.

L. Install piping penetrating roofed areas to maintain integrity of roof assembly.

Sanitary Waste And Vent Piping 15150 – Page 12


of 15
M. Where pipe support members are welded to structural building framing, scrape,
brush clean, and apply one coat of zinc rich primer to welding.

N. Prepare exposed, unfinished pipe, fittings, supports, and accessories ready for
finish painting.

O. Excavate and backfill in accordance with Section 02315.

P. Install bell and spigot pipe with bell end upstream.

Q. Sleeve pipes passing through partitions, walls and floors.

R. Inserts:
1. Provide inserts for placement in concrete forms.
2. Provide inserts for suspending hangers from reinforced concrete slabs and
sides of reinforced concrete beams.
3. Provide hooked rod to concrete reinforcement section for inserts carrying
pipe over 4 inches
4. Where concrete slabs form finished ceiling, locate inserts flush with slab
surface.
5. Where inserts are omitted, drill through concrete slab from below and
provide through-bolt with recessed square steel plate and nut above flush
with top of recessed into and grouted flush with slab.

S. Pipe Hangers and Supports:


1. Install in accordance with ASME B3 1.9, ASTM F708 and MSS SP89.
2. Support horizontal piping as scheduled.
3. Install hangers to provide minimum 1/2 inch space between finished
covering and adjacent work.
4. Place hangers within 12 inches of each horizontal elbow.
5. Use hangers with 1-1/2 inch minimum vertical adjustment. Design
hangers for pipe movement without disengagement of supported pipe.
6. Support vertical piping at every floor. Support riser piping independently
of connected horizontal piping.
7. Where installing several pipes in parallel and at same elevation, provide
multiple pipe hangers or trapeze hangers.
8. Provide copper plated hangers and supports for copper piping , sheet lead
packing between hanger or support and piping.

9. Prime coat exposed steel hangers and supports. Hangers and supports
located in crawl spaces, pipe shafts, and suspended ceiling spaces are not
considered expose
10. Install hangers adjacent to motor driven equipment with vibration
isolation; refer to Section 15070.
11. Support cast iron drainage piping at every joint.

T. Pumps:

Sanitary Waste And Vent Piping 15150 – Page 13


of 15
1. Provide shaft length allowing ejector pumps to be located minimum 24
inches below lowest invert into sump pit and minimum 6 inches clearance
from bottom of sump pit.
2. Provide air cock and drain connection on horizontal pump casings.
3. Provide line sized isolating valve on suction and line sized soft seated
check valve and balancing valve on discharge.
4. Decrease from line size with long radius reducing elbows or reducers.
Support piping adjacent to pump independently of pump casings. Install
supports under elbows on pump suction and discharge line sizes 4 inches
and over.
5. Provide pumps operating at specified system fluid temperatures without
vapor binding and cavitation , non-overloading in parallel or individual
operation, and operating within 25 percent of midpoint of published
maximum efficiency curve.

3.4 ERECTION TOLERANCES

A. Quality Requirements: Tolerances.

B. Establish invert elevations, slopes for drainage to ¼ inch per foot percent
minimum. Maintain gradients.

3.5 SCHEDULES

METAL-PIPE HANGER SPACING:

A. Pipe size: 1/2 to 1-1/4 inches


1. Maximum hanger spacing: 5 ft
2. Hanger rod diameter: 3/8 inches

B. Pipe size: 1-1/2 to 2 inches


1. Maximum hanger spacing: 10 ft
2. Hanger rod diameter: 3/8 inch

C. Pipe size: 2-1/2 to 3 inches


1. Maximum hanger spacing: 10 ft
2. Hanger rod diameter: 1/2 inch

D. Pipe size: 4 to 6 inches


1. Maximum hanger spacing: 10 ft
2. Hanger rod diameter: 5/8 inch

E. Pipe size: 8 to 12 inches


1. Maximum hanger spacing: 14 ft
2. Hanger rod diameter: 7/8 inch

Sanitary Waste And Vent Piping 15150 – Page 14


of 15
F. Pipe size: 14 inches and over
1. Maximum hanger spacing: 20 ft
2. Hanger rod diameter: 1 inch

PLASTIC-PIPE HANGER SPACING:

G. All Sizes:
1. Maximum hanger spacing: 6 ft
2. Hanger rod diameter: 3/8 inch

END OF SECTION 15150