Professional Documents
Culture Documents
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 2
1.05 SUBMITTALS....................................................................................................... 5
3.03 INSTALLATION.................................................................................................. 18
3.07 TESTING............................................................................................................ 27
PART 1 GENERAL
A. The Contractor shall provide all labor, materials, equipment and services required for
the furnishing, installation and testing of the residential sanitary waste and vent
piping; and storm drainage piping.
C. Interceptors
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials, products and workmanship. In case of conflict between these
standards and the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment, materials and
processes conforming to one group of codes and standards.
1. ASTM A74 Standard Specification for Cast Iron Soil Pipe and
Fittings
10. ASTM C564 Standard Specification for Rubber Gaskets for Cast
Iron Soil Pipe and Fittings
27. ASTM D3212 Standard Specification for Joints for Drain and Sewer
Plastic Pipes Using Flexible Elastomeric Seals
34. ASTM F656 Standard Specification for Primers for Use in Solvent
Cement Joints of Poly Vinyl Chloride (PVC) Plastic
Pipe and Fittings
1.05 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
1. Product Data
a) For pipe, tube, fittings, and couplings. Include rated capacities and
shipping, installed, and operating weights. Indicate materials, finishes,
dimensions, required clearances, and methods of assembly of
components; and piping and wiring connections for the following:
1) Floor drains and trench drains.
2) Air-admittance valves, vent caps, vent terminals, and roof flashing
assemblies.
3) Sleeve penetration systems.
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing to achieve the specified
quality to the approval of the Royal Commission in accordance with
SECTION 01450.
B. Drainage system shall be left unconcealed and uncovered until it has been
inspected, tested and approved by the Royal Commission.
C. Piping materials shall bear label, stamp or other markings of specified testing
agency.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
A. General
2. Where sanitary sewer lines cross water mains, the water main pipe shall have
a minimum 450 mm (18 in.) clear distance vertically above the sanitary sewer
pipe. If this clear distance is not feasible or the sanitary sewer line is above the
water line, the crossing must be designed and constructed, using pipe
encasement on the sanitary sewer main, to protect the water main. Where the
sanitary sewer main is already constructed, the pipe encasement shall be
placed on the water main.
3. Storm sewers shall have the same restrictions as sanitary sewer and other
utilities.
4. Each structure and each subdivided lot shall be served by separate service
lines.
5. All lots shall have separate sewer services without crossing any adjacent
properties.
7. The service line shall flow maximum half full at peak design flow.
9. The minimum horizontal distance required from building sewers shall be as per
Table 7-7 of IPC. The bottom of the water pipe, at all points shall be at least
305 mm (12 in.) above the top of the sewer or drain line.
10. Service lines may not be installed in trenches with other conduits. A service
line shall be separated from other conduits a minimum 3 m (10 ft.) horizontally.
11. Clean-outs shall be located at all points of deflection (i.e. bends) and every
30 m (100 ft.) in a service or in a straight pipeline with the following exception:
12. Each lot or separate building site shall have tees or tapping saddles for service
connections.
14. All service lines greater than 150 mm (6 in.) diameter shall be connected at a
manhole. This service connection shall channel the flow through the manhole
bench to the invert unless the difference in invert elevations are greater than
600 mm (24 in.).
B. Design Flow
1. The sanitary sewer collection system design shall include consideration for
providing service for the entire area tributary to the outfall point. Estimates for
sanitary sewage flows shall use the following guidelines:
A. Provide components and installation capable of producing piping systems with the
following minimum working-pressure ratings, unless otherwise indicated:
B. The sanitary sewerage system shall provide an adequate circulation of air in all pipes
with no danger of siphonage, aspiration, or forcing of trap seals under conditions of
ordinary use.
C. Sanitary sewerage systems in the desert area shall be so installed, that soil water
containing excreta is kept separate from the other waste water, and therefore a split-
pipe system is necessary.
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
3. Load and unload pipe, fittings, valves and accessories by lifting with hoists or
skidding so as to avoid shock or damage. Do not skid or roll pipe on skid ways
against pipe already on the ground.
5. When socketed pipes are stacked, the sockets shall be placed at alternate
ends of the stack with the sockets protruding so that pipes are evenly
supported along their entire length.
7. No piping shall be exposed to the direct sunlight for more than 2 weeks during
storage, transportation, handling or installation.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
B. All Drainage piping shall be sized at 50 mm minimum and larger in accordance with
the Royal Commission requirements.
1. PVC Pipe
c) Joints shall be solvent welded, with ASTM D2564 solvent cement and
ASTM F656 Primer.
2. PVC Pipe
3. ABS Pipe
4. ABS Pipe
5. Fiberglass Pipe
6. Fiberglass Pipe
1. PVC Pipe
2. PVC Pipe
3. PVC Pipe
4. ABS Pipe
5. ABS Pipe
6. Fiberglass Pipe
7. Fiberglass Pipe
1. Concrete Pipe
2. ABS Pipe
3. PVC Pipe
4. PVC Pipe
1. ABS Pipe
2. PVC Pipe
2. Polyvinyl Chloride (PVC) Plastic pipe may be used for above ground when
piping is enclosed in 1 hour fire rated pipe chase.
A. Cleanouts
1. General
c) Size
1) Cleanouts shall be the same nominal size as the pipes they serve;
except where cleanouts are required in pipes 100 mm and larger,
provide 100 mm cleanouts.
d) Accessibility
1) Cleanouts must be accessible. Adequate clearance for drain
cleaning shall be maintained.
e) Locations
2. Floor Cleanouts
3. Wall Cleanouts
a) Wall cleanouts shall be suitable for installation in PVC or other pipe and
shall be supplied with:
1) Ferrule with brass plug.
2) 150 mm diameter secured stainless steel access cover.
4. Cleanout Plugs
B. Floor Drains
1. General
d) Floor drains serving water heater areas shall be of deep seal type or
shall be discharged to the indirect waste funnel (IWF).
d) Outlet: Bottom.
i) Inlet Fitting: Gray iron, with threaded inlet and threaded or spigot outlet.
o) Leveling adjustment.
C. Roof Drains
1. Coated cast iron roof drain with sealing gasket, large vandalproof cast iron
locking dome, non-puncturing clamp ring with internal gravel stop, adjustable
top with wide roof flange, under deck clamp assembly, large sump with anchor
flange and bottom outlet inside caulk connection.
2.04 INTERCEPTORS
A. Grease Interceptors
1. Construction
a) Material
1) Epoxy coated fabricated steel.
b) Rough-In
1) On floor.
c) Accessories
1) Multi-weir baffle assembly, integral deep seal trap, removable
integral flow control, sediment bucket.
d) Cover
1) Steel, epoxy coated, non-skid with gasket, securing handle, hinge
typed cover, recessed for floor finish and enzyme injection port.
B. Oil Interceptors
1. Construction
a) Material
1) Epoxy coated fabricated steel.
b) Rough-In
1) On floor.
c) Accessories
1) Integral deep seal trap, removable integral flow control, adjustable
draw-off assembly, sediment bucket.
d) Cover
1) Steel, epoxy coated, non-skid with gasket, securing handle, and
enzyme injection port, recessed for floor finish.
A. Waste food grinders shall be small freestanding type disposers for both continuous
and batch feeding that allows continuous feeding of food waste into the disposer. The
cover shall prevent accidental contact with the rotary shedder by the operator. If the
cover is lifted, a limit switch in the control circuit shall stop the motor rotating the
shredder.
B. Series disposer parts shall be made of alloys suitable for use with salt seawater for
flushing ground food waste and disposer housing or cabinet manufactured with an
7. Average Amps 3 to 4.
PART 3 EXECUTION
3.01 INSPECTION
A. Verify that excavations are to required grade, dry and not over-excavated.
B. Immediately before laying, examine accessories, each pipe and joint again for
soundness and cleanliness and make sure that material and surfaces which form
part of a joint are clean and dry before commencing their assembly. All defective
material shall be replaced.
C. Check that the position and levels of existing drains and services have been
established.
3.02 PREPARATION
A. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe.
3.03 INSTALLATION
A. General
3. Horizontal sanitary drainage piping outside the building shall be sloped in the
direction of flow by 1%, unless otherwise indicated.
6. Drain piping for condensate waste from air conditioning cooling coils shall be
indirectly connected to a floor drain, or shall be indirectly connected into the
inlet side of a P-trap or indirect waste funnel.
7. All floor drains and cleanouts location shall be installed as shown on the
Contract Drawings and on the approved Shop Drawings.
8. Install cleanouts at grade and extend to where building sanitary drains connect
to building sanitary sewers.
9. Install cleanout fitting with closure plug inside the building in sanitary force-
main piping.
10. Install cast-iron sleeve with waterstop and mechanical sleeve seal at each
service pipe penetration through foundation wall. Select number of interlocking
rubber links required to make installation watertight. Refer to SECTION 15092
for sleeves and mechanical sleeve seals.
11. The top of each floor drain shall be leveled flush with finished floor and drain
shall be at the lowest point if floor is sloped to drain.
12. Floor cleanouts shall be adjusted for level flush with finished floor or slabs and
secured.
14. Access covers for wall cleanouts shall be adjusted to fit tightly to finished wall.
15. Install wall penetration system at each service pipe penetration through
foundation wall. Make installation watertight.
16. Make changes in direction for soil and waste drainage and vent piping using
appropriate branches, bends, and long-sweep bends. Straight tees, elbows,
and crosses may be used on vent lines. Do not change direction of flow more
than 90°. Use proper size of standard increasers and reducers if pipes of
different sizes are connected. Reducing size of drainage piping in direction of
flow is prohibited.
17. Lay buried building drainage piping beginning at low point of each system.
Install true to grades and alignment indicated, with unbroken continuity of
invert. Place hub ends of piping upstream. Install required gaskets according
to manufacturer's written instructions for use of lubricants, cements, and other
installation requirements. Maintain swab in piping and pull past each joint as
completed.
18. Install soil and waste drainage and vent piping at the following minimum
slopes, unless otherwise indicated:
c) Vent Piping
1) 1% down toward vertical fixture vent or toward vent stack.
19. Install engineered soil and waste drainage and vent piping systems in
locations indicated and as follows:
20. Sleeves are not required for cast-iron soil piping passing through concrete
slabs-on-grade if slab is without membrane waterproofing.
21. Do not enclose, cover, or put piping into operation until it is inspected and
approved by the Royal Commission.
B. Vents
1. Trap seals shall be protected from siphonage or back pressure by the use of
vents.
2. All vent and branch vent pipes shall be graded and connected so they drip
back into the sewerage pipe by gravity.
3. All the vent pipes shall be located at a minimum of 1.5 m apart from the fresh
air intake of the air conditioning systems installed on the roof top.
4. Where vent pipes connect to a horizontal sanitary sewerage pipe, the vent
shall be taken off above the center line of the soil pipe or at an angle not more
than 45° from the vertical and the vent pipe shall rise vertically.
5. Vents shall extend (full size) 300 mm above roof and flash with approved
material. Return flashing in to pipe section minimum 50 mm.
7. Vents from chemical and acid waste systems shall not be connected to any
waste venting system, unless otherwise approved.
C. Roof Ventilators
insulation.
4. Airflow Requirements
5. Common Venting
b) A common vent may be used for two fixtures set on the same floor level
but connecting at different levels in the stack, provided the vertical drain
is one pipe diameter larger than the upper fixture drain but in no case
smaller than the lower fixture drain.
d) The diameter of an individual vent shall be not less than 50 mm nor less
than one-half of the diameter of the drain to which it is connected.
a) A wet vent is a stack which receives the discharge from wastes other
than water closets.
c) Not more than one fixture unit is drained into a 40 mm diameter wet vent
or not more-than 4 fixture units drain into a 50 mm diameter wet vent.
d) The horizontal branch connects to the stack at the same level as the
water closet drain or below the water closet drain when installed on the
top floor. It may also connect to the water closet bend.
e) The wet vent and its extension to the vent stack is 50 mm in diameter.
a) A branch soil or waste pipe to which 2 but not more than 8 water closets
(except blowout type), pedestal urinals, standard floor traps, shower
stalls, or floor drains are connected in battery shall be vented by a circuit
or loop vent which shall take off in front of the last fixture connection. In
addition, lower-floor branches serving more than 3 water closets shall be
provided with a relief vent taken off in front of the first fixture connection.
When lavatories or similar fixtures discharge above such branches, each
vertical branch shall be provided with a continuous vent.
c) When the circuit, loop, or relief vent connections are taken off the
horizontal branch, the vent branch connection shall be taken off at a
vertical angle or from the top of the horizontal branch.
b) The lower end of each relief vent shall connect to the sewerage stack
through a "Y" branch below the horizontal branch serving the floor, and
the upper end shall connect to the vent stack through a "Y" branch not
less than 1 m above the floor level.
D. Traps
1. Traps shall be installed in waste system for each floor drain, hub drain, and
basin drain and connected to drains (unless trap is an integrated part of the
plumbing product).
2. Trap Seals used in pressurized buildings shall have a minimum trap seal of
110 mm.
E. Pipe Identification/Labelling
F. Piping Installation
2. Route piping in orderly manner and maintain gradient. Route parallel and
perpendicular to walls.
3. Install piping to maintain headroom, conserve space, and not interfere with use
of space.
5. Install piping to allow for expansion and contraction without stressing pipe,
joints, or connected equipment.
7. Provide clearance in hangers and from structure and other equipment for
installation of insulation and access to valves and fittings.
9. Establish elevations of buried piping outside the building to ensure not less
than required length of cover.
10. Install vent piping penetrating roofed areas to maintain integrity of roof
assembly.
11. Where pipe support members are welded to structural building framing,
scrape, brush clean, and apply 1 coat of zinc rich primer to welding.
12. Prepare exposed, unfinished pipe, fittings, supports, and accessories ready for
finish painting.
13. Install bell and spigot pipe with bell end upstream.
14. Pipe vents from gas pressure reducing valves to outdoors and terminate in
weatherproof hood.
G. Cleanouts
2. Install cleanout deck plates with top flush with finished floor, for floor cleanouts
for piping below floors.
3. Install cleanout wall access covers, of types indicated, with frame and cover
flush with finished wall, for cleanouts located in concealed piping.
H. Floor Drains
1. Install floor drains at low points of surface areas to be drained. Set grates of
drains flush with finished floor, unless otherwise indicated.
I. Roof Drains
2. Roof Drain (General Purpose) Cast-iron body with combined flashing collar
and gravel stop, cast-iron dome.
3. Roof Drain (controlled flow) Cast-iron body, combined flashing collar and
gravel stop, cast-iron dome with adjustable flow rate control assembly.
4. Roof Drain (steel roof decks) Cast-iron body, combined flashing collar and
gravel stop, cast-iron dome.
5. Roof Drain (parapet roofs) Cast-iron body, flashing device, loose set grate.
J. Inserts
2. Provide inserts for suspending hangers from reinforced concrete slabs and
sides of reinforced concrete beams.
3. Provide hooked rod to concrete reinforcement section for inserts carrying pipe
over 100 mm (4 in.).
4. Where concrete slabs form finished ceiling, locate inserts flush with slab
surface.
5. Where inserts are omitted, drill through concrete slab from below and provide
through-bolt with recessed square steel plate and nut above slab.
A. Fabricate flashing from single piece unless large pans, sumps, or other drainage
shapes are required. Join flashing according to the following if required:
1. Lead Sheets
1. Pipe Flashing
2. Sleeve Flashing
a) Flat sheet, with skirt or flange extending at least 200 mm (8 in.) around
sleeve.
a) Flat sheet, with skirt or flange extending at least 200 mm (8 in.) around
specialty.
7. Vertical Support
8. Floor Support
a) Floor support shall be Cast iron adjustable pipe saddle, lock nut, nipple,
floor flange, and concrete pier or steel support.
F. Use hangers with 40 mm (1½ in.) minimum vertical adjustment. Design hangers for
pipe movement without disengagement of supported pipe.
G. Support vertical piping at every other floor. Support riser piping independently of
H. Where several pipes can be installed in parallel and at same elevation, provide
multiple or trapeze hangers.
J. Prime coat exposed steel hangers and supports. Refer to SECTION 15060. Hangers
and supports located in crawl spaces, pipe shafts and suspended ceiling spaces are
not considered exposed.
K. Provide hangers adjacent to motor driven equipment with vibration isolation; refer to
SECTION 15070.
B. Plugs
1. All open pipe ends or fitting openings shall be plugged or capped immediately
during construction.
C. The Contractor shall clear the interior of the pipe of dirt and other material as the
work progresses.
D. Protect drains during remainder of construction period to avoid clogging with dirt and
debris and to prevent damage from traffic and construction work.
3.07 TESTING
B. Test sanitary drainage and vent piping according to procedures of authorities having
jurisdiction or, in absence of published procedures, as follows:
1. Test for leaks and defects in new piping and parts of existing piping that have
been altered, extended, or repaired. If testing is performed in segments,
submit separate report for each test, complete with diagram of portion of piping
tested.
of overflow, but not less than 30 kPa (10 ft. head of water) at 15.5°C
(60°F). From 15 minutes before inspection starts to completion of
inspection, water level must not drop. Water to stand in piping for a
period of 24 hour. Inspect joints for leaks.
a) After plumbing fixtures have been set and traps filled with water, test
connections and prove they are gastight and watertight. Plug vent-stack
openings on roof and building drains where they leave building.
Introduce air into piping system equal to pressure of 250 Pa (1 in. wg).
Use U-tube or manometer inserted in trap of water closet to measure
this pressure. Air pressure must remain constant without introducing
additional air throughout period of inspection. Inspect plumbing fixture
connections for gas and water leaks.
5. Repair leaks and defects with new materials and retest piping, or portion
thereof, until satisfactory results are obtained.
3.08 SCHEDULES
1. Metal Piping
2. Plastic Piping
a) All Sizes
1) Maximum hanger spacing shall be 1.8 m (6 ft.).
2) Hanger rod diameter shall be 9 mm (3/8 in.).
7. Vertical Support
8. Floor Support
a) Cast iron adjustable pipe saddle, lock nut, nipple, floor flange and
concrete pier or steel support.
END OF SECTION