Notes:

1. All the dimensions are in mm until unless specified.


2. Cable bending radius as per cables voltage grade as per IS
1255.
3. Maximum 40% pipe filling criteria to be maintained as per
standard industry practice.
4. Cable tray shall be ladder type and hot dip galvanized with
2mm thickness shall be used. Brackets, elbows, bends,
reducers, ties, crosses etc will be used wherever required.
18205
Water Drainage 5. Power cable to communication cable and power to control
2230 3230 3230 2825 3430 3030 Pipe Ø110,4Nos.
EXT-1 cable spacing shall be as per IS 1255.
W1 W2 W1 W1 TYPE-2
0
W1 6. All wall opening and pipe sleeves opening shall be properly
4 sealed with water tight and fire proof compound after
FILE 5kVA UPS & FILE

12mm THK. POLISHED


AC-1 AC-1
EL + 1.778
T.O.C
EXT-1 RACK PRINTER UPS DB RACK installation.

ALMIRA

GRANITE SLAB
PIGEON

7. Grade of concrete shall be M25 with 10 & 20mm nominal size


CCTV Panel

STAIR CASE
of aggregate as per IS 456:2000.
8. All reinforcement shall be high strength deformed TMT steel

RACK-1
SCADA ROOM
STORE ROOM PANTRY MEETING ROOM 3200X3200 bar of grade Fe500 confirming to IS 1786(Latest)
3000X3200 3725X3200 OFFICE ROOM
1870x3200 9. Lap length shall be 50D where D is the dia of the largest bar.

W1

3430
FALSE CEILING AREA 2800X3200

RACK-2
FALSE CEILING AREA FALSE CEILING AREA 10. Lapping of bars shall be suitably staggered and in no case
B B more then 50% bars shall be lapped at any section.
FRONT 11. Existing strata should be properly compacted.

RACK-3
UP 180
12. Minimum concrete cover : 40mm

D2
D2

D2
13. A slopes of 1:1000 shall be provided along the run of the

D2
SCADA

350
PANEL SERVER PANEL
FIRE 530
cable trench.
D4 530

3 14. A slopes of 1:1000 shall be given in the direction


perpendicular to the run of the cable trench.

ROLLING SHUTTER
15. Checker plate shall be anti skid type with 5 mm thickness.

8090
1300

TYPE-B
20Ø CPVC PIPE RUNNING
@600MM Above FFL IN WALL
1000
SLOPE1:6

D1

2030
PLATFORM
RS1

2000x1500
4725 3030

+0.600EL
(+)0.60M FFL

LEGENDS:

D2
63Ø UPVC PIPE DROP
TO WB AT 450 AFFL

3 CABLE TRAY 300MM


Y 1
PANEL AREA Y
PVC PIPE ( DIA 200MM)

EMERGENCY GATE
2 D4 TOWEL
D4 TYPE-A A FRONT
X
SOAP
RAIL
HOLDER

PRECAST SLAB
1 C CONTROL CABLE

D-1A
PLATFORM
FEMALE 200 ACDB NIFPS DCDB
200X500 110 kV 1500x1000
BATTERY
HOLDER
SOAP

MALE TOILET BATTERY ROOM 350X1000 320X500


TOWEL

RTCC
RAIL

TOILET CRP PORTION OF P


3000X2170 POWER CABLE

VITREOUS CHINA
C_URINALS
DARFIELD
K-5024-T
1685x2170 CHARGER 800X600 TRENCH REMOVED
1200x2170 1300X800 1000X800
D3 1500
CL SOAK PIT

SOAK

2400
INPECTION CHAMBER GULLY TRAP

PIT SEPTIC TANK


INLET
SIZE-450 X450 SIZE-300X300 200 1487 CABLE TRAY
FIXED ON WALL 200 X PLATFORM * CT/PT/CVT CABLES
WC

WC
IL-400MM IL-350MM 940
150Ø RCC SOIL PIPE
1200 3030
A

920
BATTERY
DFCBD BATTERY

405

407
1000x1000

UPS

150
110Ø UPVC WASTE

570
PIPE L-900MM,
SLOPE -1:150
PIPE INLET RACK
LEVEL-100

IC GT 150Ø RCC SOIL PIPE


EXT-1 EXT-1 EXT-1 EXT-1 EXT-1
1 PIPE OUTLET
LEVEL-100
PIPE INLET 63Ø UPVC WASTE PIPE

200
LEVEL-150
L-900MM,SLOPE -1:150

W2 W2 W1 TYPE-1 W1 W1
100
Water Drainage Pipe
20Ø CPVC PIPE RUNNING
@600MM Above FFL IN WALL

0 A B C D E Ø110,4Nos. F
Mount With U-Clamp

CHEQUERED
PLATE 5MM THK.
150
75 75

EDGE ANGLE
ISA75X75X6
ISMC-75 75

125 50

300
8Ø LUG WELDED
TO ANGLE C

1850

300
450
P
DETAIL AT 'D'
Slope
(1:100)

1300 03 06.04.21 REVISED AS MKD


FOR APPROVAL

200

300
50x8 GI EARTH 02 11.09.20

200
ISA 75x75x6 FRONT STRIP
TRENCH TYPE-A TO TYPE-B
Mount with Hole Concrete M25
ISA 75x75x6
Mount with Hole
FRONT Weld Hold Brick PANELS SECTION Y-Y
01 09.09.20 FOR APPROVAL
PANELS Trench Corner
Weld Hold Brick Checker Plate
Trench Corner 00 28.08.20 FOR APPROVAL

400
VIEW-D Checker Plate EL.(+)0.6m 150 5mm Thk. 200mm Dia Pipe
Type-B Trench
EL.(+)0.6m 5mm Thk. Base Frame Channel PLINTH BEAM

REV. DATE REVISION HISTORY


505

Base Frame Channel ISMC 75 EL.(+)0.56m CABLE TRAY FIXING ON WALL


Cable Tray
50x8 GI EARTH 150
T.O.PB
505

STRIP ISA 75x75x6


ISMC 75
185

620

C PLINTH BEAM Power cable PROJECT TITLE :


200

50x8 GI EARTH EL.(+)0.21m


300

C STRIP 150MM THK 300


RCC TRENCH WALL C 232 50x8 GI EARTH
110 kV 50MW(AC) SOLAR PV PLANT, RAICHUR,
300

C STRIP RTCC
300

C 450 CRP
200mm Dia Pipe 800X600 Type-A Trench
KARNATAKA, INDIA
300
1850

* 300 200 1000X800


R2
853

1660
300

450 C 03 1Cx16sqmm Cu Cable


265 300

P
1550

150MM THK
750 450
300

RCC TRENCH WALL


P 450 OWNER : KONDAPURAM SOLAR PRIVATE LTD
1810

EL.(-)0.8m * Cable Tray

620
Slope EL.(-)1.1m
265 300

(1:100) Slope 750 450 TYPICAL TOP VIEW OF


75 (1:100) TRENCH TYPE-A TO TYPE-B
150

CLIENT :
200

75 P R2 SECTION Y-Y
03
150

75MM THK
PCC 1:3:6 Slope
COMPACTED SOIL 75MM THK
(1:100)

1850
PCC 1:3:6 COMPACTED SOIL 75 2125
ISA 75x75x6 AMP ENERGY INDIA PVT. LTD.
1000 Mount with Hole
150

1200
1300 COMPACTED SOIL Weld Hold Brick Checker Plate
1500
Trench Corner
TRENCH TYPE-B-B
TRENCH TYPE-A-A 5mm Thk. EPC CONTRACTOR:
1500
EL.(+)0.6m RAYS POWER INFRA PVT. LTD., D-43,

75
SECTION X-X

200
12Ø 150mm JANPATH, SHYAM NAGAR, JAIPUR -
SIDE VIEW OF X-X long

10Ø
302019
10Ø
@150mm c/c @150mm c/c

Checker Plate
DRAWING TITLE :
PLINTH BEAM EL.(+)0.6m
C 5mm Thk.

CONTROL ROOM - TRENCH SECTION & LAYOUT


380

475 Concrete M25


D Concrete M25
535

475 75MM THK


380

380

Concrete M25 PCC 1:3:6


535

535

100x800mm, 6mm 100x1100mm, 6mm


Insert Plate
300

Insert Plate
300 100x1100mm, 6mm
300 300 300 300 Insert Plate
10Ø
DRAWING NO. : RPIPL-K-OA-AMP-CE-DWG-MCR-008
1400
300

300

@200mm c/c
300

ISA 60X60X6 ISA 60X60X6


1400 1500mm C/C
1700

1500mm C/C ISA 60X60X6


welded(6mm thk.) welded(6mm thk.) 1500mm C/C
300 300 1700
300

with inserted plate 300


300
300

with inserted plate welded(6mm thk.) COMPACTED SOIL


300 with inserted plate
300 SECTION TYPICAL SITE CO-ORDINATE.:
300

300
450 300 STRUCTURAL DETAIL FOR ALL TRENCH
325
SHEET NO. 1 OF 2 SCALE N.T.S.
265

220
220
265

C
370

325
D
75

450
Detail: C-C Detail: D-D DETAIL OF TRENCH & CABLE
TRAY CROSSING THE PLINTH
DRAWN AD PAPER SIZE A0
DETAIL-B BEAMS.
DETAIL-A CABLE TRAY AT BEND
INSERT PLATE DETAIL
INSERT PLATE DETAIL SECTION 1-1 CHECKED AG REV NO. R3
REFERENCE DRAWINGS:
1. CONTROLROOM PLAN RPIPL-K-OA-AMP-CE-DWG-MCR-002 APPROVED NSG DATE 06.04.2021
750 mm HIGH, 115 THK. BRICK WALL 75 THK. PCC EL.(+)5.15m
T.O.P
COPING 1:2:4

EL.(+)4.30m

EL.(+)4.0m
B.O.B
ROOF BEAM ROOF BEAM ROOF BEAM

1800 1800
1200 1200

4000
1200

1200
W1 W1

Ø200MM

900

900
Ø200MM PVC PIPE
PVC PIPE EL.(+)0.6m
FFL
550

EL.(+)0.45m
COMPACTED SOIL FILLING COMPACTED SOIL FILLING
300

C D D E F

550
300
300

CABLE ENTRY & EXIT CABLE ENTRY & EXIT


DETAIL : TYPE 1 DETAIL : TYPE 2

16NOS x 200MM DIA. PVC/HDPE PIPE

EL.(+)0.6m
75MM PRECAST 75MM GROOVING
250

COVER SLAB INSIDE THE WALL


10Ø
550

@150mm c/c 75

NGL
03 06.04.21 REVISED AS MKD
300

SWITCHYARD SWITCHYARD INSIDE MCR

1200

1200
FOR APPROVAL
1925

INSIDE MCR 02 11.09.20


1350

300

TRENCH TRENCH TRENCH TRENCH


01 09.09.20 FOR APPROVAL
1450

300

00 28.08.20 FOR APPROVAL


250

REV. DATE REVISION HISTORY


PROJECT TITLE :
50MW(AC) SOLAR PV PLANT, RAICHUR,
125

KARNATAKA, INDIA

TYP. SECTION ENTRY AT TYPE 1 TYP. PLAN ENTRY AT TYPE 1 OWNER : KONDAPURAM SOLAR PRIVATE LTD
CLIENT :
AMP ENERGY INDIA PVT. LTD.
3NOS x 200MM DIA. PVC/HDPE PIPE
FOR AUXILIARY AND
COMMUNICATION CABLES EPC CONTRACTOR:
RAYS POWER INFRA PVT. LTD., D-43,
JANPATH, SHYAM NAGAR, JAIPUR -
923

300

3x 200MM HDPE PIPE 75MM PRECAST 75MM GROOVING


EL.(+)0.6m 302019
COVER SLAB INSIDE THE WALL
FOR AUXILIARY AND
COMMUNICATION CABLES
10Ø
@150mm c/c 75
DRAWING TITLE :
CONTROL ROOM - TRENCH SECTION & LAYOUT
300

NGL INSIDE MCR


1625

1500

1500 TRENCH
DRAWING NO. : RPIPL-K-OA-AMP-CE-DWG-MCR-008
800

800
1050

650

225

FROM PV FIELD SITE CO-ORDINATE.:


300

1500
SHEET NO. 2 OF 2 SCALE N.T.S.
CABLE PULL PIT DRAWN AD PAPER SIZE A0
25

TYP. SECTION (INSPECION CHAMBER) ENTRY AT TYPE 2 TYP. PLAN ENTRY (INSPECTION CHAMBER) AT TYPE 2 CHECKED AG REV NO. R3
APPROVED NSG DATE 06.04.2021