You are on page 1of 3

TEXAS INSTRUMENT

GENERAL NOTES: not the same as SLD

1.0 ALL ELECTRONICS WORKS HERE IN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE
LATEST EDITION OF THE PHILIPPINE ELECTRONICS CODE, THE RULES AND REGULATIONS OF THE
LOCAL ENFORCING AUTHORITIES AND THE REQUIREMENTS OF THE UTILITY TELEPHONE COMPANY. NOTES :
2.0 ALL ELECTRONICS WORKS HERE IN INCLUDED SHALL BE EXECUTED BY PERSONNEL WITH ELECTRICAL 1.) THIS DRAWING IS SCHEMATIC REPRESENTATION OF SYSTEM ONLY.
TENDERS TO DETAIL COMPLIANT OFFER BASED ON MANUFACTURER'S
EXPERIENCE UNDER THE DIRECT SUPERVISION OF A FULL TIME LICENSED ELECTRONICS ENGINEER, SYSTEM & WIRING METHODS RECOMMENDATION.
WORKS SHALL BE NEATLY PLACED, SECURELY FASTENED AND PROPERLY FINISHED. 2.) POWER SUPPLY TO EACH LDC MUST BE CONNECTED TO EMERGENCY POWER EC-501
ENGINEERING SG
I NATURE DATE COMMENTS
3.0 THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF TAPPING POINT FOR 3.) WIRING INSTALLATION (CEILING CONCEALED, EMBEDDED, EXPOSED OR
CONNECTION TO COMMUNICATION SUPPLY. SURFACED) SHALL BE USED RSC, 15mmØ MINIMUM.
4.0 ALL MATERIALS SHALL BE BRAND NEW & SHALL CONFORM WITH THE PROVISIONS OF THE UNDER 4.) WIRING FROM TEL/DATA PORT TO LDC MUST BE CAT6e NEATLY BUNDLED IN
WRITERS LABORATORIES INC., IN EVERY CASE WHERE SUCH A STANDARD HAS BEEN ESTABLISHED. CABLE TRAY USING NYLON CABLE TIE
5.0 ALL CONDUITS MUST BE PROTECTED AGAINST DAMAGES BY THE ENTRANCE OF WATER & FOREIGN 5.) LDC's ARE WALL MOUNTED LOCATED 2 FEET BELOW CEILING.
MATTERS DURING CONSTRUCTION. ALL ENDS OF CONDUITS SHALL BE PLUGGED TO EXCLUDE
MOISTURE AND DUST IMMEDIATELY AFTER THE CONDUITS ARE PLACED.
ENS SYSTEM SHALL BE HONEYWELL BRAND
6.0 UNLESS OTHERWISE SPECIFIED, ALL ELECTRONICS WIRING INSTALLATION SHALL BE USED RSC. PROVIDE MODEL NO. CONTROL SIGNALS FROM
THE MINIMUM SIZE OF CONDUIT SHALL BE 15mmØ. FIRE ALARM SYSTEM
7.0 ALL RACEWAYS, WALL & FLOOR PENETRATIONS SHALL BE PROVIDED WITH FIRE BARRIER OF THE FIRE MAN'S MICROPHONE
APPROVED TYPE. LOCATED AT RECEPTION AREA (SECOND FLOOR)

8.0 ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16, DEEP TYPE WITH FACTORY KNOCKOUTS.
ZONE PAGING MICROPHONE LOCATED AT RECEPTION
PULLBOXES SHALL BE USED WHEN APPLICABLE FOR EASY PULLING OF WIRES AND SHALL BE IN AREA (SECOND FLOOR)
ACCORDANCE WITH THE PHILIPPINE ELECTRICAL CODE REQUIREMENT.
PREFERRED BRAND FOR JUNCTION, PULLBOX OR UTILITY SQUARE BOXES SHALL BE FUMACO, AMCO,
TIMO OR APPROVED EQUAL.
SECOND FLOOR
9.0 MOUNTING HEIGHTS OF DEVICES SHALL BE:
(SUBJECT TO ARCHITECT'S APPROVAL PRIOR TO INSTALLATION) 1. is the network controller interface capable of providing
the desired power amplification for the Microphones? if not
DATA OUTLET- 0.30M ABOVE FINISHED FLOOR TO CENTER OF DEVICE pre-amplifier for the remote microphones at the reception
are to be provided.
10.0 ALL SPEAKER WIRING SHALL BE 2-0.75 SQ.MM SHIELDED SPEAKER WIRE. 2. wall mounted speaker does not have the wattage as well as
the amplifiers. contractor to provide data for proper identification UPPER G/F
11.0 NETWORK CABLES/CONDUIT SHALL HAVE A MINIMUM DISTANCE OF 0.3M FROM POWER CONDUIT to be used in the quantifications of all devices to be used.
WHEN LAID PARALLEL & MUST RUN PERPENDICULAR TO THE STEEL CONDUIT WHEN CUTTING
ACROSS A POWER LINE.
12.0 THE PLANS AS DRAWN ARE BASED UPON THE ARCHITECTURAL PLANS & THE DETAILS & SHOWN
LOWER G/F
CONDITION AS ACCURATELY AS IT IS POSSIBLE TO INDICATE THEM IN SCALE. THE PLANS ARE ESH
DIAGRAMMATICAL AND DOES NOT NECESSARILY SHOW ALL FITTINGS NECESSARY TO FIT TO THE
BUILDING CONDITIONS. THE LOCATIONS OF OUTLETS, APPARATUS AND APPLIANCES SHOWN ON 1 PA & BGM RISER DIAGRAM
THE PLANS ARE APPROXIMATE. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THEIR ECE-1 SCALE: NTS
PROPER LOCATION IN ORDER TO MAKE THEM FIT WITH THE ARCHITECTURAL DETAILS AND
INSTRUCTIONS FROM THE ENGINEER'S REPRESENTATIVE AT THE SITE. LDC1
PB
LDC2
POE SWITCH

LEGENDS & SYMBOLS 1-CAT.7e UTP, 4-PAIRS


CATV PB

1. based on the connection, camera are IP based since


LDC3
LDC4
LDC5
CABLE IN 25mm dia. all are connected to a PoE switch.
SYMBOL/ PVC CONDUIT 2. specify the intent of the design as to where the conversion
LDC6

ABBREV. DESCRIPTION of video signal are to processed, 44 NO.S TEL/DATA CONNECTED


a. DVR systems process data at the recorder TO EACH LDC. A TOTAL OF 255 NO. OF
1-CAT.7e UTP, 4-PAIRS
b. NVR systems encode and process data at the camera
LDC LOCAL DISTRIBUTION CABINET FOR TEL/DATA DVR CABLE EACH IN CABLE TEL/DATA @ IT ACE/P2P/FAST TEAM/WPL
before transmitting it to the recorder for storage and remote viewing. OTHERS
TRAY CONFERENCE ROOM/FINANCE AREA/
3. Any specific frequency requirement to justify the usage of CAT7E?
Is video streaming a stringent requirement of the client? MANAGERS RM/PAYROL AREA
IDF INTERMEDIATE DISTRIBUTION FRAME DATA CABINET/ 4. CATV pullbox?
ADMIN OFFICE 5. where does the DVR signals being monitored and stored? 1. provide details of LDC for more stringent review of the system.
TO TELCO
6. Per TIA, For furniture pathways, the maximum pathway fill shall 2. Any specific frequency requirement to justify the usage of CAT7E?
M CONVENTIONAL MONITOR MODULE be 40%. SERVICE
3. How does the telephone cables terminated? via RJ11 or RJ45 since
ENTRANCE
7. Ensure that the max cable length shall be as required by EIA/TIA we are using Cat7E cables.
not to exceed 100 meters with the inclusion of the patch cord. IDF SERVER ROOM 4. provide IDF device details for more stringent review
WALL MOUNTED DATA/VOICE 5. Ensure that the max cable length shall be as required by EIA/TIA
not to exceed 100 meters with the inclusion of the patch cord.
PB PULL BOX 5. Per TIA, For furniture pathways, the maximum pathway fill shall
1-CAT.7e UTP, 4-PAIRS CABLE
be 40%.
IN 25mm PVC CONDUIT SECOND FLOOR
INT INTERCOM OUTLET
tel or data? PB LDC7

WALL MOUNTED TELEPHONE OUTLET POE SWITCH


CATV PB
WALL MOUNTED DATA OUTLET 1-CAT.7e UTP,
are this IP based PROVISION @ STORAGE AREA
1-CAT.7e UTP, 4-PAIRS CABLE 4-PAIRS CABLE
DOME TYPE CCTV CAMERA, 720 TV LINES, cameras? IN 25mm PVC
IN 25mm PVC CONDUIT
D VANDAL-PROOF WITH IR LED'S CONDUIT
UPPER G/F
BULLET TYPE WEATHER-PROOF CCTV CAMERA
B 720 TV LINES, VANDAL-PROOF W/ IR LED'S PB
LDC8
CIRCUIT HOME RUN POE SWITCH
CATV PB
LDC9
J JUNCTION BOX FOR PROVISION

CATVPB CATV PULLBOX EACH CCTV (IPCAM) SERVER AREA


48 NO.S TEL/DATA CONNECTED
CONNECTED TO NETWORK TO EACH LDC. A TOTAL OF 73 NO. OF
SWITCH OF ADMIN OFFICE TEL/DATA@ PLANNING AREA/CONFERENCE
CCTV CCTV PULLBOX LOWER G/F
ROOM/FACILITIES/ESH

TTC TELEPHONE CABINET


2 CCTV SYSTEM RISER DIAGRAM 3 TELEPHONE SYSTEM RISER DIAGRAM
CATV OUTLET ECE-1 SCALE: NTS ECE-1 SCALE: NTS
TV

WALL MOUNTER SPEAKER

Electronics Plans shall be signed and sealed by a Professional Electronics Engineer per R.A. 9292. FOR APPROVAL
SUSALUM CORPORATION PHILIP P. PANGILINAN, PEE / CEA TIPI TIPI
SAL - Bldg. Sta Rosa - Tagaytay Highway
Sitio Muzon, Brgy. Putingkahoy, Silang, Cavite
PROFESSIONAL ELECTRICAL ENGINEER
DESIGN AND BUILD FOR OFFICE AND AUXILIARY GENERAL NOTES,
Philippines 4118
4895 5566791 STOCKROOM BUILDING SYMBOLS & LEGENDS, & RISER ECE-1
Trunkline No. 63-49-502-9931 to 32
Direct Line: 63-49-502-9924 400-321-713 Quezon City DIAGRAMS
Fax No. 63-49-502-9925 RICHARD CACAL
Email: susalum@susalum.com.ph 01/08/2024 LOAKAN ROAD, PEZA, BAGUIO CITY FACILITIES DIRECTOR

all electronics plans


shall be signed and
sealed by PECE as
per RA 9292
provide conduit schedule, this is to identify the
conduit size and numbers of cables that will TEXAS INSTRUMENT

X8 X9 X10
passing a certain size. this is to allow reviewer
idea if the conduits size to be used is still X11 X12 X13
acceptable in the work area.
GENERAL NOTES:

= TELEPHONE AND DATA OUTLET


6000 6000 6000 6000 6000 EC-502
ENGINEERING SG
I NATURE DATE COMMENTS
= TELEPHONE OUTLET

TTC is not
shown in = CCTV CAMERA
the SLD
= WALL- MOUNTED SPEAKER

Y5
ELECTRICAL ROOM

VENDO
AREA
5000

LEGAL COM.

Y4 MR-6

ESH
5000

MR-7

20000
Y3
MR-5 PLANNING

OTHERS
5000

Y2
PAYROLL & FINANCE

minimal speakers are


provided in the area, if this
5000

speaker will be used also for


evac during Fire alarm
evacuation, sound pressure
level shall be considered and
Y1
evaluated in the design. this
is to ensure voice
inteliigibility in all part f the
area

EXIT

AUXILIARY LAYOUT PLAN - LOWER GND FLR


1 SCALE: 1:75M
FOR APPROVAL
Electronics Plans shall be signed and sealed by a Professional Electronics Engineer per R.A. 9292.

SUSALUM CORPORATION
SAL - Bldg. Sta Rosa - Tagaytay Highway
PHILIP P. PANGILINAN, PEE / CEA
PROFESSIONAL ELECTRICAL ENGINEER
TIPI TIPI
Sitio Muzon, Brgy. Putingkahoy, Silang, Cavite DESIGN AND BUILD FOR OFFICE AND
Philippines 4118
4895 5566791 STOCKROOM BUILDING AUXILIARY LAYOUT PLAN - LOWER GND FLR ECE-2
Trunkline No. 63-49-502-9931 to 32
Direct Line: 63-49-502-9924 400-321-713 Quezon City
Fax No. 63-49-502-9925 RICHARD CACAL
Email: susalum@susalum.com.ph 01/08/2024 LOAKAN ROAD, PEZA, BAGUIO CITY FACILITIES DIRECTOR
same comments

TEXAS INSTRUMENT
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10GENERAL NOTES: X11 X12 X13
75000

= TELEPHONE AND
DATA OUTLET = WALL-MOUNTED
6000 6000 6000 6000 6000 6000 6000
6000 6000 6000 6000
SPEAKER 6000

30TR 30TR = TELEPHONE


OUTLET
EC-503
= CCTV CAMERA ENGINEERING SG
I NATURE DATE COMMENTS
Y5 6700 6100 7400

TRANSFORMER
TRANSFORMER

UNREG
UPS
5000

Y4
5000

Y3

20000
5000

Y2
5000

Y1
WALKWAY
ESH

AUXILIARY LAYOUT - UPPER GROUND FLOOR


1 SCALE: 1:150M
GENERAL NOTES:
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13
75600 = TELEPHONE AND
DATA OUTLET = WALL-MOUNTED
SPEAKER
= TELEPHONE
6000 6000 6000 6000 6000 6000 6000 6000 6000 6000 6000 6000
OUTLET

= CCTV CAMERA
OTHERS

Y5
IDF ROOM
IT ACE VENDO
VENDO AREA AREA
ELECTRICAL ROOM MR-4
P2P
5000

P2P

Y4 MR-2

EXIT
5000

STAIR
MR-1

Y3

133.27
5000

MR-3

LOCAL IT

Y2
GENDER
NEUTRAL

IT ACE

XID/FAST

LOBBY
5000

Y1
STAIR

AUXILIARY LAYOUT PLAN - SECOND FLOOR


2
Electronics Plans shall be signed and sealed by a Professional Electronics Engineer per R.A. 9292.
SCALE: 1:150M FOR APPROVAL
SUSALUM CORPORATION
SAL - Bldg. Sta Rosa - Tagaytay Highway
PHILIP P. PANGILINAN, PEE / CEA
PROFESSIONAL ELECTRICAL ENGINEER
TIPI TIPI
Sitio Muzon, Brgy. Putingkahoy, Silang, Cavite DESIGN AND BUILD FOR OFFICE AND AUXILIARY LAYOUT PLAN UPPER
Philippines 4118
4895 5566791 STOCKROOM BUILDING ECE-3
Trunkline No. 63-49-502-9931 to 32
400-321-713 Quezon City
GROUND FLOOR & SECOND FLOOR
Direct Line: 63-49-502-9924
Fax No. 63-49-502-9925 RICHARD CACAL
Email: susalum@susalum.com.ph 01/08/2024 LOAKAN ROAD, PEZA, BAGUIO CITY FACILITIES DIRECTOR