CLIENT

PLUMBING LEGEND & ABBREVIATIONS GENERAL NOTES BOOK SPECIFICATION


SUPERCEDE ANY NOTES BELOW

DISREGARD LEGEND ITEMS NOT INDICATED ON DRAWINGS


1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL OFFSETS. INSTALL PIPING AS
NEW PLUMBING FIXTURE CLOSE AS POSSIBLE TO LOCATIONS SHOWN. WHERE INTERFERENCE'S WITH COMPONENTS OF OTHER TRADE'S WORK
(STRUCTURAL FOUNDATIONS OR OTHER BUILDING ELEMENTS) REQUIRE ROUTINGS AND LOCATIONS THAT VARY FROM
SAN / S SANITARY WASTE THOSE SHOWN, THE CONTRACTOR SHALL OBTAIN PROJECT ENGINEER'S APPROVAL PRIOR TO INSTALLATION. NO
STORM / ST STORM DRAINAGE LINE ADDITIONAL COST SHALL BE GRANTED FOR THESE CHANGES.

C.D. CONDENSATE DRAIN LINE 2. BEFORE BEGINNING EXCAVATIONS OR DEMOLITION OF ANY NATURE WHATSOEVER, CONTRACTOR SHALL LOCATE ALL City of Richmond
SERVICES AND UTILITIES OCCURRING WITHIN THE BOUNDS OF THE PROJECT. THE CONTRACTOR SHALL THEN
GW GREASE WASTE PROCEED WITH CAUTION IN HIS WORK SO THAT NO UTILITY OR LINE SERVING AREAS THAT ARE TO REMAIN BE
1116 Myrtle Street
AW ACID WASTE DAMAGED WITH A RESULTANT LOSS OF SERVICE. VERIFY THE SOURCE AND SERVICE OF EACH AND EVERY LINE Richmond, TX 77469
ENCOUNTERED AND RECORD SERVICE, SIZE AND LOCATION ON RECORD DRAWINGS. T 281-342-0559
CHEM−W CHEMICAL WASTE
V VENT 3. ROUGH-IN PLUMBING PIPING USING DIMENSIONS SHOWN ON ARCHITECTURAL DRAWINGS. LOCATION OF ALL PIPING
SHALL ALLOW INSTALLATION OF FIXTURES WITHOUT THE NEED TO FURR-OUT WALLS.
FIRE FIRE LINE
4. PROVIDE CLEANOUTS IN EXCESS OF THOSE SHOWN WHICH ARE REQUIRED BY THE PLUMBING CODE. CONTRACTOR
DIS DEIONIZED WATER SUPPLY SHALL PROVIDE A COVER STATING WHAT SYSTEM IT IS SERVING. (CLEANOUT SANITARY, CLEANOUT GREASE WASTE,
DIR DEIONIZED WATER RETURN CLEANOUT ACID WASTE.) ARCHITECT
SW SOFT WATER 5. INDIVIDUAL FIXTURE SUPPLY AND DRAIN SERVICES ARE NOT SHOWN DUE TO DRAWING SPACE LIMITATIONS. THIS
CW DOMESTIC COLD WATER PIPING CONTRACTOR SHALL PROVIDE ALL SERVICES FOR A COMPLETE FIRST CLASS INSTALLATION.

HW DOMESTIC HOT WATER PIPING 6. FURNISH AND INSTALL ALL NECESSARY VALVES, TRAPS, GAUGES, STRAINERS, UNIONS, ETC. FOR EACH PIECE OF

PGAL
EQUIPMENT HAVING PLUMBING CONNECTIONS TO FACILITATE PROPER FUNCTIONING AND SERVICING.
HWR DOMESTIC HOT WATER RETURN PIPING
TW TEMPERED WATER PIPING 7. SEAL ALL PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS WITH A UL LISTED ASSEMBLY TO PROVIDE
A RATING EQUAL TO OR GREATER THAN THE RATING OF THE WALL, FLOOR OR CEILING.
TWR TEMPERED WATER RETURN PIPING
8. EACH CONTRACTOR SHALL VISIT THE SITE AND ASCERTAIN FOR HIMSELF THE CONDITIONS TO BE MET THERE IN
NPW(C) NON POTABLE WATER (COLD) IMPLEMENTING HIS WORK AND MAKE DUE PROVISIONS FOR THE SAME. IT IS ASSUMED THAT THE CONTRACTOR HAS
HPW(H) NON POTABLE WATER (HOT) VISITED THE PREMISES AND THAT HIS COST ESTIMATE COVERS ALL NECESSARY LABOR AND MATERIALS TO
PROPERLY ACCOMPLISH HIS WORK. FAILURE ON THE PART OF THE CONTRACTOR TO COMPLY WITH THIS REQUIREMENT
DI DEIONIZED WATER SHALL NOT BE CONSIDERED JUSTIFICATION FOR OMISSIONS OR FAULTY WORK OR FOR THE PAYMENT OF ADDITIONAL
COMPENSATION.
NG / G NATURAL GAS
PGAL, LLC
LA NATURAL GAS 9. FIELD VERIFY EXISTING AND FUTURE GRADES WITHIN AREAS WHERE WORK IS BEING DONE.
3131 BRIARPARK DR.
VAC NATURAL GAS 10. VERIFY EXACT LOCATION OF EQUIPMENT PRIOR TO INSTALLATION OF FLOOR DRAINS AND FLOOR SINKS. RELOCATION SUITE 200
DUE TO MISPLACEMENT SHALL BE AT CONTRACTORS EXPENSE.
N2 NATURAL GAS HOUSTON, TX 77042
FCO FLOOR CLEAN OUT 11. PROVIDE A KEYED ACCESS PANELS FOR ALL VALVES AND APPARATUSES THAT REQUIRE MAINTENANCE. T 713 622 1444
ECO EXTERIOR CLEANOUT 12. A WATER HAMMER ARRESTOR SHALL BE INSTALLED FOR ALL SINGLE AND MULTIPLE FIXTURE BRANCH LINES. WATER F 713 968 9333
HAMMER ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS AND
WCO WALL CLEANOUT TBPE REG. No. F-2742
CONFORM TO ASSE 1010. PROVIDE FOR HOT WATER AND COLD WATER LINES AND REFER TO WATER HAMMER
FD FLOOR DRAIN ARRESTOR DETAIL FOR MORE INFORMATION AND SIZING. www.pgal.com
FS FLOOR SINK 13. INSULATE PIPING AS FOLLOWS:
# RISER IDENTIFICATION
# DOMESTIC COLD WATER PIPING:
ELBOW UP INSULATE AND VAPOR SEAL ALL COLD AND SOFTENED WATER PIPE WITH GLASS FIBER PIPE INSULATION.
(EXCEPTION : ALL PIPING EXPOSED TO THE EXTERIOR SHALL BE PROVIDED WITH ALUMINUM).
ELBOW DOWN
DOMESTIC HOT WATER PIPING:
CAP AND SEAL INSULATE ALL HOT WATER PIPE WITH GLASS FIBER PIPE INSULATION WITH FACTORY−APPLIED WHITE JACKET.
INFRASTRUCTURE ASSOCIATES, INC.
BALL VALVE DRAINS: 6117 RICHMOND AVENUE, SUITE 200
HOUSTON, TEXAS 77057-6267
B.V. BALANCING VALVE INSULATE AND VAPOR SEAL ALL ABOVEGROUND P−TRAPS AND HORIZONTAL DRAIN PIPING RECEIVING (713) 622-0120 PH (713) 622-0557
CONDENSATE OR ICE MAKER DRAINAGE WITH 1/2" GLASS PER FIBER INSULATION. FAX
GAS VALVE INSULATE AND VAPOR SEAL ROOF DRAIN AND OVERFLOW ROOF DRAIN SUMP, PIPING AND FITTINGS FROM TBPE FIRM REGISTRATION #F-4506
C.V. CHECK VALVE DRAIN TO VERTICAL LEADER WITH 1/2" GLASS FIBER INSULATION. WWW.IAHOUSTON.COM
S A.D.A. ACCESSIBLE LAVATORIES AND SINKS:
SOLENOID VALVE
INSULATE ALL EXPOSED DRAIN PIPING AND WATER SUPPLY PIPING BENEATH A.D.A. COMPLIANT LAVATORIES
FLOW SWITCH & SINKS WITH FULLY MOLDED CLOSED CELL VINYL INSULATION KIT AS MANUFACTURED BY TRUEBRO, BROCAR
TP AUTOMATIC TRAP PRIMER OR MCGUIRE.

BFP BACKFLOW PREVENTER 14. SUPPORT UNBURIED PIPE AS FOLLOWS:


HORIZONTAL PIPING:
VTR VENT THROUGH ROOF
HUBLESS CAST IRON SOIL PIPING SHALL BE SUPPORTED AT LEAST AT EVERY OTHER JOINT EXCEPT THAT WHEN THE
F.F.L. FINISHED FLOOR LEVEL DEVELOPED LENGTH BETWEEN SUPPORTS EXCEEDS FOUR FEET, THEY SHALL BE PROVIDED AT EACH JOINT.
SUPPORTS SHALL ALSO BE PROVIDED AT EACH HORIZONTAL BRANCH CONNECTION. SUPPORTS SHALL BE PLACED REGISTRATION
I.L. INVERT LEVEL
IMMEDIATELY ADJACENT TO THE COUPLING. SUSPENDED LINES SHALL BE BRACED TO PREVENT HORIZONTAL Copyright © 2016
A.R.F. ABOVE FINISHED ROOF MOVEMENT.
(E) EXISTING TO REMAIN COPPER TUBING SHALL BE SUPPORTED AT NOT MORE THAN SIX FOOT INTERVALS FOR PIPING 1-1/2" AND SMALLER AND
NINE FOOT INTERVALS FOR PIPING 2" AND LARGER IN DIAMETER. F
(OF) OVERFLOW STORM DRAINAGE TE O T EXA
HANGERS FOR NON-INSULATED COPPER PIPING SHALL HAVE A COPPER FINISH. IN POTENTIALLY DAMP LOCATIONS, TA
(P) PRIMARY STORM DRAINAGE

S
NON-INSULATED COPPER PIPING HANGERS OR SUPPORTS SHALL BE PLASTIC-COATED.
T.A.S TEXAS ACCESSIBILITY STANDARDS STEEL PIPING SHALL BE SUPPORTED AT INTERVALS OF NO GREATER THAN 6 FEET FOR 1/2" PIPING, 8 FEET FOR 3/4" &
1" PIPING AND 10 FEET FOR 1-1/4" AND LARGER PIPING. ANWAR HASSAN
64671

PR

R
VERTICAL PIPING: LIC

EE
FE E N SE D N

O
PROVIDE RISER CLAMP AT BASE AND AT EACH FLOOR LEVEL SS I
IO N A L EN G
15. MARKING AND IDENTIFICATION:
IDENTIFY EACH PIPE WITH LABELING AT THE FOLLOWING LOCATIONS: 2023-02-17
DRAWING HISTORY
−AT EACH BRANCH TAKE−OFF FROM A MAIN
№. DATE DESCRIPTION
−ON EACH SIDE OF A WALL PENETRATION
−EVERY 20’ OF STRAIGHT RUN OF PIPE
−AT EQUIPMENT CONNECTIONS IF MORE THAN 10’ FROM A BRANCH TAKE−OFF

DOMESTIC HOT WATER:


INDICATE DELIVERED WATER TEMPERATURE ON DOMESTIC HOT WATER SUPPLY AND RETURN LINES.
PROJECT NAME
INDICATE FLOW DIRECTION WITH ARROWS ON DOMESTIC HOT WATER SUPPLY AND RETURN LINES.
MEDIUM PRESSURE GAS PIPING:
City of Richmond
MEDIUM PRESSURE GAS PIPING (14" WIC TO 5 PI) SHALL BE IDENTIFIED BY THE STATEMENT, "WARNING TO 5 PI Economic
NATURAL GAS." THESE LABELS SHALL BE PLACED AT INTERVALS NOT EXCEEDING 30 FEET. ALL REGULATORS IN Development Dept.
MEDIUM PRESSURE LINES SHALL HAVE IDENTIFICATION TAGS IN ACCORDANCE WITH APPLICABLE CODES.
Buildout
16. SLEEVES:
FLOORS: PROVIDE UL FIRE RATED ASSEMBLIES WERE PIPES PENETRATE ABOVE GRADE FLOORS.
WALLS: PROVIDE UL FIRE RATED ASSEMBLIES WERE PIPES PENETRATE FIRE RATED WALLS.
WHERE PIPING PASSES THROUGH NON CEILING OR WALL, CLOSE OFF SPACE BETWEEN PIPE OR DUCT AND PROJECT LOCATION
CONSTRUCTION WITH NORMAL GYPSUM WALLBOARD, REPAIR PLASTER SMOOTHED AND FINISHED TO MATCH
REMAINDER OF WALL. 1116 Myrtle St.
INSTALL CHROME OR STAINLESS STEEL ESCUTCHEONS WHERE PIPING PASSES THROUGH FINISHED SURFACES. Richmond, TX 77469

PROJECT STATUS

100%
CONSTRUCTION
FILE NAME: C:\Revit\CRED_MEP_R22_aa1ZLRQM.rvt

DOCUMENTS
DATE OF ISSUE

02/17/2023
PROJECT NUMBER

1006083.00
DATE STAMP:2/16/2023 11:37:01 AM

SHEET TITLE

SYMBOL LEGEND,
SCHEDULES

SHEET NUMBER

P0.01
CLIENT
PLUMBING FIXTURE SCHEDULE PLUMBING FIXTURE SCHEDULE
SIZE OF CONNECTION SIZE OF CONNECTION
MARK DESCRIPTION REMARKS MARK DESCRIPTION REMARKS
TRAP SS SV CW HW TRAP SS SV CW HW
1A
S
T
U
.R
7
C
Y
6
H
IN
D
F
E
M
,V
X
J
O
:5
B
0
P

T
E
U
N
.V
C
J
IM
A
H
D
R
O
7
6
1S
P
,:Y
5
0
B
X
F

SK−1 SINGLE BOWL 1 1/2" 3" 2" 1/2" 1/2" K−8689−5U−0 KOHLER 33"x22"x5−7/8" UNDERMOUNT SINGLE−BOWL KITCHEN SINK. ENAMELED WC−1 WATER CLOSET − 4" 2" 1" − 2257.528 AMERICAN STANDARD "AFWALL", WALL-MOUNTED FLUSHOMETER VALVE TOILET,
SINK CAST IRON MATERIAL. (WALL MOUNTED) VITREOUS CHINA, HIGH EFFICIENCY, LOW CONSUMPTION. OPERATES IN THE RANGE OF 1.28 GPF,
(A.D.A) (A.D.A.) CONDENSATION CHANNEL, ELONGATED BOWL, POWERFUL DIRECT-FED SIPHON JET ACTION, 1-1/2"
7185ORB MOEN OIL RUBBED BRONZE, SINGLE HANDLE FAUCET. PULL DOWN 68" HOSE FURNISHED. INLET SPUD, FULLY-GLAZED 2-1/8" TRAPWAY, 10" X 12" WATER SURFACE AREA.
LEVER TYPE HANDLE, DURALOCK QUICK CONNECT SYSTEM FOR INSTALLATION. ADA COMPLIANT.
1.5 GPM MAX FLOW RATE AND 1255 DURALAST CARTRIDGE FOR SINGLE HANDED FAUCETS. 111-1.28-ES-S-TMO SLOAN "OPTIMA", 1” I.P.S. SCREWDRIVER BAK-CHEK® ANGLE STOP, FREE City of Richmond
SPINNING VANDAL RESISTANT STOP CAP, HIGH BACK PRESSURE VACUUM BREAKER FLUSH 1116 Myrtle Street
K−8799−2BZ KOHLER DUOSTRAINER, SINK DRAIN AND STRAINER BASKET. SOLID BRASS CONNECTION WITH ONE-PIECE BOTTOM HEX COUPLING NUT, SPUD COUPLING AND FLANGE FOR 1 ½” Richmond, TX 77469
CONSTRUCTION, WITH OPEN/CLOSE STOPPER THAT SEALS TIGHTLY. FITS STANDARD 3−1/2" OR 17" TOP SPUD, EL-154 TRANSFORMER (120 VAC/24 VAC 50 VA). THE PLUMBING CONTRACTOR IS
RESPONSIBLE FOR THE CONCEALED LOW VOLTAGE WIRING BETWEEN THE MULTI USE TRANSFORMER FOR T 281-342-0559
4" INCH OUTLET.
THE WATER CLOSETS, URINALS AND FACULTY LAVATORIES. LOCATE THE TRANSFORMERS ABOVE
ACCESSIBLE CEILINGS OR PROVIDE ACCESS PANEL FOR HARD CEILINGS. UP TO 6 FIXTURE PER
1151WC MCGUIRE, 1 1/2" ADA COMPLIANT OFFSET STAINER/DRAIN ASSEMBLY AND TAILPIECE, TRANSFORMER.
C8912 MCGUIRE, 1 1/2" CAST BODY P−TRAP AND CLEANOUT. INSULATE P−TRAP, TAILPIECE 9500C CHURCH, SEATS SHALL BE EXTRA HEAVY WEIGHT AND INJECTION MOLDED OF SOLID
ASSEMBLY. PLASTIC. SEATS SHALL BE OPEN FRONT LESS COVER FOR ELONGATED BOWL AND FEATURE LARGE
MOLDED-IN BUMPERS. CONCEALED CHECK HINGES TO FEATURE 300 SERIES STAINLESS STEEL ARCHITECT
BV02 MCGUIRE, 1/2 IPS X 3/8 OD, QUARTER−TURN BRASS BALL VALVE ANGLE STOP, CHROME POSTS THAT STOP SEAT 11 DEGREES BEYOND VERTICAL. USES 300 SERIES STAINLESS STEEL
PLATED, CONVERTIBLE LOOSE KEY HANDLE. SUPPLY STOP VALVE SHALL BE CERTIFIED BY CSA HARDWARE.
OR OTHER RECOGNIZED TESTING AUTHORITY AND SHALL BEAR MANUFACTURER AND TESTING
MARK. STOP TO BE CERTIFIED TO 200 PSI LINE PRESSURE. WALL HUNG WATER CLOSET CARRIERS AND FACE PLATE SHALL BE BY JR SMITH.

PGAL
270-RF-STSTL-REC LEONARD, POINT OF USE THERMOSTATIC VALVE MIXING VALVE, BRONZE
WATER CLOSET RIM HEIGHT SHALL BE 17" ABOVE FINISHED FLOOR LEVEL PER A.D.A.
BODY, LOCKED TEMPERATURE ADJUSTMENT CAP (VANDAL RESISTANT), COPPER ENCAPSULATED REQUIREMENTS.
THERMOSTAT ASSEMBLY WITH POLYMER THERMOPLASTIC SHUTTLE, STAINLESS STEEL SPRINGS, E
:T
1A
7
−0
,IS
U2
D
P
Y
9
N
L
R
F
C
B
O
X
5
H
.J
6
V
M

BUNA-N O'RINGS, INTEGRAL CHECK VALVES ON HOT AND COLD INLETS. SET TEMPERATURE TO L−1 LAVATORY 1 1/4" 2" 2" 1/2" 1/2" Z5350 ZURN, 19" x 17" WALL HUNG LAVATORY, VITREOUS CHINA WITH FAUCET HOLES SINGLE, 4"
105°F (WALL MOUNTED) OR 8" CENTERS. FRONT OVERFLOW AND WALL HANGER PROVIDED. WASTE SIZE: 1−1/4" O.D.
(A.D.A.)
Z6950−XL−S ZURN HYDRO−X POWER, SELF−SUSTAINING, BATTERY POWERED, SENSOR FAUCET.
SELF−SUSTAINING HYDROPOWER AND BATTERY BACKUP. INFRARED CONVERGENCE−TYPE

ELECTRIC WATER HEATER SCHEDULE PROXIMITY SENSOR. IN−LINE FILTER AND STANDARD CHROME−PLATED CAST BRASS BODY. ADA,
ASME A112.18/CSA B125.1 COMPLIANT.
PGAL, LLC
ELEMENT(S) RECOVERY GPH TANK CAPACITY BV02 MCGUIRE, 1/2 IPS X 3/8 OD, QUARTER−TURN BRASS BALL VALVE ANGLE STOP, CHROME 3131 BRIARPARK DR.
MARK MFR MODEL VOLTS ø LOCATION PLATED, CONVERTIBLE LOOSE KEY HANDLE. SUPPLY STOP VALVE SHALL BE CERTIFIED BY CSA
QTY kW @ 100°F RISE GALLONS
OR OTHER RECOGNIZED TESTING AUTHORITY AND SHALL BEAR MANUFACTURER AND TESTING SUITE 200
EWH−1 A.O. SMITH DEL−30 208 3 2 3 23 30 JAN. 110 MARK. STOP TO BE CERTIFIED TO 200 PSI LINE PRESSURE. HOUSTON, TX 77042
NOTES: 149 MCGUIRE, FLAT GRID STRAINER WITH 4" TAILPIECE. WROUGHT BRASS SINK STRAINER WITH T 713 622 1444
1. OUTLET TEMPERATURE SHALL BE 140°F. 20 GA TAILPIECE AND BRASS LOCK AND COUPLING NUTS. FITS SINK DEPTH UP TO 3/4". CHROME F 713 968 9333
2. PROVIDE SIMULTANEOUS ELEMENT OPERATION. PLATED.
TBPE REG. No. F-2742
8872 MCGUIRE, HEAVY CAST BRASS 1 1/4 X 1 1/4 ADJUSTABLE TRAP WITH CLEANOUT PLUG AND www.pgal.com
11INCH CENTER TO END. FURNISHED WITH SLIP NUTS, 17 GAUGE SEAMLESS TUBULAR BRASS

HOT WATER CIRCULATING PUMP SCHEDULE WALL BEND, AND STEEL SHALLOW FLANGE.

102−EZ−W TRUEBRO, "P" TRAP AND SUPPLY INSULATION KIT.


MODEL MOTOR
MARK MFR. TYPE G.P.M. HEAD H.P. VOLTAGE LOCATION 0700 J.R. SMITH, LAVATORY SUPPORTS WITH CONCEALED ARMS.
NO. R.P.M.
HWCP−1 BELL & GOSSETT PL−55 IN LINE BRONZE 15 40 1/12 120 / 1ø 1725 JAN. 110 270−LF−STSTL−REC−BV−DT LEONARD, ASSE 1070 COMPLIANT, POINT OF USE THERMOSTATIC
INFRASTRUCTURE ASSOCIATES, INC.
VALVE MIXING VALVE, BRONZE BODY, LOCKED TEMPERATURE ADJUSTMENT CAP (VANDAL
NOTES: 6117 RICHMOND AVENUE, SUITE 200
RESISTANT), COPPER ENCAPSULATED THERMOSTAT ASSEMBLY WITH POLYMER THERMOPLASTIC HOUSTON, TEXAS 77057-6267
1. HOT WATER CIRCULATION PUMP SHALL BE PROVIDED WITH TIMER TO DE-ENERGIZE THE PUMP UNDER SHUTTLE, STAINLESS STEEL SPRINGS, BUNA−N O’RINGS, INTEGRAL CHECK VALVES ON HOT AND (713) 622-0120 PH (713) 622-0557
DURING UNOCCUPIED PERIODS PER THE CURRENT IECC. COLD INLETS. SET TEMPERATURE TO 105°F. − STSTL−REC: STAINLESS STEEL CABINET #4 FAX
FINISH RECESSED, BV: INLET BALL VALVES, DT: DIAL THERMOMETER TBPE FIRM REGISTRATION #F-4506
T
.1A
S
L
U
R
7
C
Y
6
H
IN
D
F
E
,X
:J
M
V
-
5
B
2
0
O
P
9

WWW.IAHOUSTON.COM
EDF−1 ELECTRIC 1 1/2" 2" 2" 1/2" − HTHB-HACG8BLPV-NF HALSEY TAYLOR, WALL MOUNT WATER COLLER, BARRIER-FREE ACCESS

PIPING MATERIALS DRINKING


FOUNTAIN
(BI-LEVEL)
BI-LEVEL, NO LEAD DRINKING FOUNTAIN, LIGHT TOUCH PUSHBAR ON FRONT, BOTTLE FILLING
STATION, NON-FILTERED, PLATINUM VINYL FINISH. COMPLETE WITH DOUBLE-BUBBLER AND REAL
DRAIN. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS AND LOCATION.
(A.D.A.)
1. SANITARY WASTE AND VENT PIPING : (BELOW GRADE) BV02 MCGUIRE'S, 1/2 IPS X 3/8 OD, QUARTER-TURN BRASS BALL VALVE ANGLE STOP, CHROME
SCHEDULE 40 PVC, CONFORM TO ASTM D-1785 SOIL AND WASTE VENT PIPING. FITTINGS SHALL BE COMPATIBLE PLATED, CONVERTIBLE LOOSE KEY HANDLE. SUPPLY STOP VALVE SHALL BE CERTIFIED BY CSA OR
MATERIAL WITH SOLVENT CEMENT TYPE JOINTS. OTHER RECOGNIZED TESTING AUTHORITY AND SHALL BEAR MANUFACTURER AND TESTING MARK.
STOP TO BE CERTIFIED TO 200 PSI LINE PRESSURE.
2. SANITARY WASTE AND VENT PIPING : (ABOVE SLAB ONLY)
PIPE: CAST IRON ASTM A 74, HUBLESS, SERVICE WEIGHT. 8872 MCGUIRE, HEAVY CAST BRASS 1 1/4 X 1 1/4 ADJUSTABLE TRAP WITH CLEANOUT PLUG AND REGISTRATION
11INCH CENTER TO END. FURNISHED WITH SLIP NUTS, 17 GAUGE SEAMLESS TUBULAR BRASS WALL Copyright © 2016
JOINTS: NO HUB, ASTM C 564 NEOPRENE GASKETS AND STANDARD STAINLESS STEEL CLAMP AND SOLID SHIELD BEND, AND STEEL SHALLOW FLANGE.
ASSEMBLIES CONSTRUCTED OF TYPE 300 SERIES STAINLESS STEEL. CLAMP ASSEMBLIES SHALL CONFORM TO FM
1680 WHERE REQUIRED BY THE ADMINISTRATIVE AUTHORITY.
MLP200 HALSEY TAYLOR, IN WALL CARRIER MOUNTING SYSTEM.
F
FITTINGS: CAST IRON, ASTM A 888 DRAINAGE PATTERN. TE O T EXA
98312C HALSEY TAYLOR, PLATINUM VINYL APRON. PROVIDE APRON ONLY FOR UNITS MOUNTED AT TA

S
NON-ADA HEIGHT TO MEET A.D.A. REQUIREMENTS OF 24" A.F.F.
3. DOMESTIC WATER: CANE TOUCH − − − − −
TYPE "L" COPPER TUBING WITH WROUGHT COPPER FITTINGS AND 95/5 (TIN/ANTIMONY) SOLDER JOINTS. APRON HWF3000 HALSEY TAYLOR WATERSENTRY PLUS FILTER KIT (BOTTLE FILLERS). ANWAR HASSAN
E
:T
,I1A
U Y
8
N
0
2
S
−D
B
7
R
6
F
O
C
X
5
H
P
.J
V
M

4. FIRE PROTECTION SYSTEM: MS−1 MOP SINK 3" 3" 2" 3/4" 3/4" HL−1800 STERN WILLIAMS HIlow, 24"X24"X12" DRAIN SHALL CAST BRASS WITH STAINLESS STEEL 64671

PR

R
LIC

EE
SCHEDULE 40 BLACK STEEL PIPE WITH CLASS 150 BLACK MALLEABLE IRON SCREWED FITTINGS. PIPING 2 1/2" AND (FLOOR STRAINER CAST INTEGRAL AND SHALL PROVIDE FOR CAULKED LEAD CONNECTION NOT LES FE E N SE D N

O
SS I
LARGER SHALL BE JOINED WITH VICTAULIC FITTINGS UTILIZING ROLL GROOVES. VICTAULIC REDUCING COUPLINGS MOUNTED) THAN 1" DEEP TO A 3" PIPE. TERRAZZO RECEPTOR COMPOSED OF PEARL GREY MARBLE CHIPS IO N A L EN G
"FIT" OR "PRESS FIT" SYSTEMS AND STRAP TYPE MECHANICAL TEES SHALL NOT BE USED. AND WHITE PORTLAND CEMENT GROUND SMOOTH, GROUTED AND SEALED TO RESIST STAINS.
STAINLESS STEEL CAP OF ONE PIECE 20 GA. 302 STAINLESS STEEL CAST INTEGRAL ON FROM 2023-02-17
DROP. DRAWING HISTORY
№. DATE DESCRIPTION
540−LD897SWXFABCP CHICAGO FAUCETS, 8" FIXED CENTERS, 6GPM, 897−SJKCP − 5 3/4" RIGID
VACUUM BREAKER SPOUT WITH 3/4" MALE HOSE THREAD AND PAIL HOOK, 369−PR − 2 3/8"
LEVER HANDLE, XT − QUATURN COMPRESSION OPERATING CARTRIDGE, WXF − STRAIGHT 2"
INLET SUPPLY ARM WITH WALL FLANGE WITH 1/2" NPT FEMALE THREAD INLET, ATMOSPHERIC
VACUUM BREAKER, NOT INTENDED FOR CONTINUOUS PRESSURE APPLICATIONS, CHROME PLATE
FINISH. PROJECT NAME
T−35 STERN WILLIAMS, HOSE AND WALL HOOK. HOSE 36" LONG, WITH 3/4" CHROME COUPLINGS. City of Richmond
WALL BRACKET OF STAINLESS STEEL.
Economic
T−40 STERN WILLIAMS, STAINLESS STEEL MOP HANGER OF STAINLESS STEEL WITH #4 FINISH. Development Dept.
24" LONG, WITH 3 RUBBER SPRING LOADED GRIPS.
Buildout
BP STERN WILLIAMS, SPLASH CATCHER PANELS OF 20 GA. TYPE 304 STAINLESS STEEL.
:e1t
E
7
0
,I2
U−a
Y
9
S
N
D
R
F
C
A
B
T
O
X
5
H
P
.J
6
V
M

RVB−1 REFRIGERATOR/ − − − 1/2" − BIM875 − GUY GRAY − REFRIGERATOR/ ICE MAKER VALVE BOX, FURNISHED WITH 1/2" FIP INLET
ICE MAKER X 1/4" OD OUTLET COMPERSSION ANGLE VALVE. PROVIDE FILTER WHEN MAKING FINAL PROJECT LOCATION
VALVE BOX CONNECTION.
(FURNISH AND INSTALL AT ALL REFRIGERATORS AND ICE MACHINES) 1116 Myrtle St.
:e1t
E
7
0
,I2
U−a
Y
9
S
N
D
R
F
C
A
B
T
O
X
5
H
P
.J
6
V
M

FD−1 FLOOR DRAIN 3"−4" 3"−4" 2" − − 2005−B−NB. J.R. SMITH, DUCO CAST IRON BODY WITH FLASHING COLLAR AND ADJUSTABLE
Richmond, TX 77469
STRAINER HEAD 6" DIAMETER TYPE "A" NICKEL BRONZE STRAINER.
PROJECT STATUS
INSTALL COMPLETE WITH PROSET TRAP GUARD, EXCEPT FOR SHOWER DRAIN.
FS−1 FLOOR SINK 3"−4" 3" 2" − − 3200−PDBS JR SMITH, CAST IRON FLANGED RECEPTOR WITH SEEPAGE HOLES, ACID RESISTANT 100%
(KITCHEN) COATED INTERIOR, NICKEL BRONZE RIM AND SECURED GRATE. ALUMINUM DOME BOTTOM
STRAINER OR SEDIMENT BUCKET AS INDICATED BY FIGURE NUMBER. −PDBS POLISHED ALUMINUM
CONSTRUCTION
FILE NAME: C:\Revit\CRED_MEP_R22_aa1ZLRQM.rvt

DOME BOTTOM STRAINER. REFER TO KITCHEN CONSULATANT WHAT GRATE SHALL BE UTILIZED DOCUMENTS
1/2 GRATE, 3/4 GRATE, OR FULL GRATE. INSTALL COMPLETE WITH PROSET TRAP GUARD.
DATE OF ISSUE
E
,IY
US
N
R
F
C
A
B
7
T
O
:X
5
0
1H
P
.J
6
V
M
D

FCO−1 FLOOR − − − − − 4040 J.R. SMITH, WITH SCREWED PLUG AND FLASHING RING AND COVER PLATE WITH SECURING
CLEANOUT SCREW. COVER PLATE SHALL BE FLUSH TO FINISH FLOOR, AND SUITABLE FOR FLOOR
COVERING INSTALLED.
02/17/2023
PROJECT NUMBER
DW−1 DISHWASHING 2" 2" 2" 1/2" 1/2" B−200 GUY GRAY, DISHWASHING MACHINE DRAIN BOX;
MACHINE FINISH: MINIMUM SPANGLE G90 HOT DIPPED GALVANIZED STEEL (UNPAINTED) 1006083.00
DATE STAMP:2/16/2023 11:37:07 AM

DRAIN BOX
VALVES: FURNISHED WITH DOMESTIC VALVES AND COMBINATION MIP OR SWEAT CONNECTION SHEET TITLE
DRAIN: MALE THREAD FITTING AND LOCKNUT INCLUDED
SCHEDULES

SHEET NUMBER

P0.02
CLIENT

KEYED NOTE LEGEND


1 CONTRACTOR SHALL FOLLOW THE MANUFACTURE INSTALLATION GUIDE FOR CONNECTING THE DISHWASHER AT
THIS LOCATION. ROUTE WATER AND WASTE TO AND FROM SINK PROVIDE AIR GAP AT THE SINK.

City of Richmond
1116 Myrtle Street
Richmond, TX 77469
T 281-342-0559

ARCHITECT

PGAL
PGAL, LLC
3131 BRIARPARK DR.
SUITE 200
HOUSTON, TX 77042
T 713 622 1444
F 713 968 9333
RVB-1
UNISEX
TBPE REG. No. F-2742
BREAK AREA
110
www.pgal.com
1 103 L-1
DW-1 HWCP-1 WC-1 OFFICE ELEC.
120 121
VEST.
CONFERENCE RM.
104A
JANITOR MS-1
SK-1 108 111

OFFICE
118

B.V.

1/2"HWR

1/2"HWR
WC-1
INFRASTRUCTURE ASSOCIATES, INC.
L-1 EWH-1: LOCATED
OFFICE
6117 RICHMOND AVENUE, SUITE 200

3/4"CW
119

ABOVE MS-1 HOUSTON, TEXAS 77057-6267


MECH. EDF-1 UNISEX
(713) 622-0120 PH (713) 622-0557

1/2"HW
102 112

1/2"HW
FAX

2"CW
TBPE FIRM REGISTRATION #F-4506
NOT IN SCOPE 1/2"HWR CORRIDOR
WWW.IAHOUSTON.COM

1/2"HW 104

3/4"CW
2"CW
AC CLOSET CLOSET
119A 117A

2" DOMESTIC CW LINE TO CONNECT


OFFICE
101
BACK TO UTILITY MAIN, REFER TO
OFFICE CIVIL FOR CONTINUATION.
OFFICE OFFICE OFFICE 117
105 107 113

REGISTRATION
Copyright © 2016

F
TE O T EXA
TA

S
ANWAR HASSAN
64671

PR

R
LIC

EE
FLOOR PLAN - DOMESTIC FE E N SE D N

O
SS I
2 IO N A L EN G
1/8" = 1'-0"
2023-02-17
DRAWING HISTORY
№. DATE DESCRIPTION

4" SANITARY LINE TO BE CONNECTED 4" SANITARY LINE TO BE CONNECTED PROJECT NAME
TO UTILITY MAIN. REFER TO CIVIL TO UTILITY MAIN. REFER TO CIVIL
FOR CONTINUATION. FOR CONTINUATION. City of Richmond
Economic
Development Dept.
UNISEX
Buildout

4"SAN
110

3"SAN

3"SAN
BREAK AREA
103 WC-1
OFFICE ELEC.
L-1 FD-1 120 121
PROPOSED SAW CUT VEST.
4" VTR PROJECT LOCATION
SK-1 CONFERENCE RM.
108
104A
MS-1
FS-1 1116 Myrtle St.

4"SAN
4" VTR JANITOR

PROPOSED SAW CUT 111 OFFICE


118
2"V Richmond, TX 77469
PROPOSED SAW CUT
WC-1
L-1
FS-1 4"SAN FD-1 PROJECT STATUS

2"V
EDF-1
MECH.
FCO-1 UNISEX

100%

3"SAN
102 112

FS-1
NOT IN SCOPE 2"V OFFICE
CONSTRUCTION
FILE NAME: C:\Revit\CRED_MEP_R22_aa1ZLRQM.rvt

CORRIDOR
104 FS-1
119
DOCUMENTS
AC CLOSET
119A
CLOSET DATE OF ISSUE
117A

02/17/2023
OFFICE
FCO-1
101 PROJECT NUMBER
OFFICE
OFFICE OFFICE OFFICE

1006083.00
117
105 107 113
DATE STAMP:2/16/2023 11:37:14 AM

SHEET TITLE

FLOOR PLAN -
PLUMBING

SHEET NUMBER
FLOOR PLAN - SANITARY
1
1/8" = 1'-0"
P2.01
CLIENT

City of Richmond
1116 Myrtle Street
Richmond, TX 77469
T 281-342-0559

CLAMP TO 4LB STAINLESS STEEL SHEET,


24"x24", AND WATERPROOFING MEMBRANE STRAINER
ATTACH TO STRUCTURE
FINISH FLOOR (TYPICAL)
A.S.M.E. RATED TEMP. AND ARCHITECT
VACUUM RELIEF VALVE
PRESSURE RELIEF VALVE.
WATTS NO. 36A−3/4"
PIPE DISCHARGE FULL SIZE
TO EXISTING DRAIN. BALL VALVE
3/4"
PROVIDE AND INSTALL FOR ALL
FLOOR DRAINS, ODOR TRAP
GUARDS AS MANUFACTURED MY
PRO−SET SYSTEMS, SUITABLE TO
DRAIN INSTALLED, FIELD VERIFY
EXACT LOCATION AND QUANTITY
CLAMP TO 4"
LEAD SHEET
HWCP−1
EXPANSI ON TANK

HEAT TRAP (TYPICAL)


EXPANSION TANK
A.O. SMITH PMC−2
PGAL
(24"x24") AND
4" DEEP AUXILIARY EWH−1 PGAL, LLC
SUPPORT AT WATERPROOFING BALL VALVE (TYPICAL)
3" DIA. MEMBRANE DRAIN PAN 18 GAUGE 3131 BRIARPARK DR.
THIS POINT
COMPRESSION CHAMBER GALVANIZED STEEL. UNION (TYPICAL) SUITE 200
FINISH FLOOR HOUSTON, TX 77042
1" AUXILIARY DRAIN LINE
CEILING
TO FLOOR DRAIN. T 713 622 1444
DEEP SEAL
F 713 968 9333
SHELL
"P" TRAP 2" UNISTRUT SUPPORT, TBPE REG. No. F-2742
BELLOWS ROUTE 1" T&P DRAIN
1/2" ALL THREADED www.pgal.com
LINE TO NEAREST
RODS COMPLETE WITH
FLOOR DRAIN.
DOUBLE NUTS AND LOCK
NIPPLES
WASHERS.
B CONCRETE

J.R. SMITH P.D.I. FIXTURE UNIT A B


FIG. NO SYMB. RATING SIZE
PROVIDE AND INSTALL FOR ALL FLOOR
FLOOR DRAIN DETAIL WITH TRAP GUARD not to scale 0 90 5005 A 1 − 11 3/4" 4" DRAINS, ODOR TRAP GUARDS AS INFRASTRUCTURE ASSOCIATES, INC.
6117 RICHMOND AVENUE, SUITE 200
MANUFACTURED MY PRO−SET SYSTEMS, HOUSTON, TEXAS 77057-6267
5010 B 12 − 32 1" 5" SUITABLE TO DRAIN INSTALLED, FIELD (713) 622-0120 PH (713) 622-0557
VERIFY EXACT LOCATION AND FAX
GRADE LEVEL FLOOR
SLAB
EXTERIOR
WALL
5020 C 33 − 60 1" 6" QUANTITY ELECTRIC WATER HEATER DETAIL not to scale 0 TBPE FIRM REGISTRATION #F-4506
WWW.IAHOUSTON.COM
12"
A 5030 D 61 − 113 1" 7"
FINAL FINAL
BACKFILL BACKFILL
UNDISTURBED 5040 E 114 − 154 1" 8"
SECONDARY NATIVE SOIL
CROWN NOTES: 5050 F 155 − 330 1" 9" 1’’ MIN. STAINLESS STEAL FLASHING −
INITIAL BACKFILL
CRIMP INTO TOP OF PIPE
PRIMARY INITIAL +MIN. 6" 1. ALWAYS INSTALL IN UPRIGHT POSITION MINIMUM 1’’ − PRIME FLANGE
CLAY SOIL SEAL
BACKFILL. 2. INSTALL AT AN ACCESSIBLE LOCATION. PROVIDE AND SET IN PLASTIC CEMENT
75% OF NOTE: CONTRACTOR SHALL ACCESS PANEL WHERE REQUIRED. DEEP SEAL "P"
EMBEDMENT PIPE DIAM. COORDINATE WITH STRUCTURAL TRAP
3. COMPLY WITH THE LATEST UNIFORM PLUMBING CODE REGISTRATION
ENGINEER PRIOR TO PENETRATING OR VENT PIPE
MIN. 6" MODIFICATION TO THE FOUNDATION. Copyright © 2016
8’’ MINIMUM REFER TO ARCHITECTURAL
STABILIZED
DEPTH AS AND STRUCTURAL PLANS
SAND BEDDING.
HAUNCH EMBEDMENT REQUIRED. FOR PROPER PENETRATION
F
DETAIL AND FLASHING. TE O T EXA
TA
WATER HAMMER ARRESTERS not to scale 0 FLOOR SINK WITH TRAP GUARD (FS−1) not to scale 0

S
UNDERGROUND INSTALLATION OF PLASTIC PIPE
PLASTIC PIPE SHOULD ALWAYS BE BURIED IN STRICT ACCORDANCE WITH THE ASTM STANDARD RELEVANT TO THE TYPE OF ANWAR HASSAN
PLASTIC PIPING SYSTEM BEING INSTALLED. THOSE STANDARDS ARE:
PROVIDE ADEQUATE PIPE 64671
ASTM D2321 STANDARD PRACTICE FOR UNDERGROUND INSTALLATION OF SUPPORTS TO PREVENT

PR

R
LIC

EE
THERMOPLASTIC PIPE FOR SEWERS AND OTHER GRAVITY−FLOW FE E N SE D N

O
ANY MOVEMENT, SS I
APPLICATIONS. IO N A L EN G

EXTERIOR WALL
TYPE "L" COPPER COLD
ASTM D2774 STANDARD PRACTICE FOR UNDERGROUND INSTALLATION OF WATER RISER SIZE AS 2023-02-17
THERMOPLASTIC PRESSURE PIPING. INDICATED ON PLAN DRAWING HISTORY
NOTE: IN ADDITION TO THESE STANDARDS, PIPE SHOULD ALWAYS BE INSTALLED IN №. DATE DESCRIPTION

ACCORDANCE WITH ALL LOCAL CODE REQUIREMENTS. SEAL WITH


FULL−OPEN VALVE NON−HARDENING
RECOMMENDATIONS FOR UNDERGROUND INSTALLATION OF PLASTIC DRAINAGE PIPE: SEALANT
1. THE MINIMUM WIDTH OF THE TRENCH SHOULD BE THE PIPE OD (OUTSIDE DIAMETER) PLUS 16 INCHES THIS
J.R. SMITH 5519, NON−FREZZE
WILL ALLOW ADEQUATE ROOM FOR JOINING THE PIPE, SNAKING THE PIPE IN THE TRENCH TO ALLOW FOR 3/4" BALL VALVE
STAINLESS STEEL FLUSH MOUNT
VENT THROUGH ROOF DETAIL not to scale 0 PROJECT NAME
EXPANSION AND CONTRACTION WHERE APPROPRIATE AND SPACE FOR BACKFILLING AND COMPACTION OF
BOX, BRASS HOSE BIBB WITH WALL
City of Richmond

3’−0"
BACKFILL. THE SPACE BETWEEN THE PIPE AND TRENCH WALL MUST BE WIDER THAN THE COMPACTION
FLANGE AND VACUUM BREAKER.
EQUIPMENT USED TO COMPACT THE BACKFILL. Economic
2. PROVIDE A MINIMUM OF 4 INCHES OF FIRM, STABLE AND UNIFORM BEDDING MATERIAL IN THE TRENCH PROVIDE FLOOR CLAMP TO 4" (24"x24")
STAINLESS STEEL SHEET AND
CLEANOUT REFER
TO SPECS.
Development Dept.
MOUNTED SUPPORT
BOTTOM. IF ROCK OR UNYIELDING MATERIAL IS ENCOUNTERED, A MINIMUM OF 6 INCHES OF BEDDING Buildout

3’−0"
VIBRATION ISOLATORS WATERPROOFING MEMBRANE
FINISHED FLOOR
SHALL BE USED. BLOCKING SHOULD NOT BE USED TO CHANGE PIPE GRADE OR TO INTERMITTENTLY WHERE REQUIRED
SUPPORT PIPE OVER LOW SECTIONS IN THE TRENCH. (TYP.)
FINISHED FLOOR
REFER TO CIVIL FOR
HANGER RODS CONTINUATION.
3. THE PIPE SHOULD BE SURROUNDED WITH AN AGGREGATE MATERIAL WHICH CAN BE EASILY WORKED (TYP.) INSULATED PIPE PROJECT LOCATION
AROUND THE SIDES OF THE PIPE. BACKFILLING SHOULD BE PERFORMED IN LAYERS OF 6 INCHES WITH EACH SHIELD (TYP.)
NON−INSULATED INSULATED FINISHED GRADE 1116 Myrtle St.
LAYER BEING SUFFICIENTLY COMPACTED TO 85% TO 95% COMPACTION. PIPE (TYP.) PIPE (TYP.)
Richmond, TX 77469
4. A MECHANICAL TAMPER IS RECOMMENDED FOR COMPACTING SAND AND GRAVEL. THESE MATERIALS PROVIDE ADJUSTABLE
CLAMPING COLLAR
CONTAIN FINE−GRAINS, SUCH AS SILT AND CLAY. IF A TAMPER IS NOT AVAILABLE, COMPACTING SHOULD BE LINK SEAL.
DONE BY HAND. PROJECT STATUS

5. THE TRENCH SHOULD BE COMPLETELY FILLED. THE BACKFILL SHOULD BE PLACED AND SPREAD IN UNIFORM
SLEEVE AND CAULK
PENETRATIONS
12" MIN. 100%
LAYERS TO PREVENT ANY UNFILLED SPACES OR VOIDS. LARGE ROCKS, STONES, FROZEN CLODS, OR OTHER
REFER TO DOMESTIC PLAN FOR SIZE
CAST IRON PIPE
CONSTRUCTION
LARGE DEBRIS SHOULD BE REMOVED. STONE BACKFILL SHALL PASS THROUGH AN 1−1/2" SIEVE. ROCK SIZE ANGLE IRON OR SEMI−CYLINDRICAL GALV.
FILE NAME: C:\Revit\CRED_MEP_R22_aa1ZLRQM.rvt

SHOULD BE ABOUT ONE−TENTH OF THE PIPE OUTSIDE DIAMETER. HEAVY TAMPERS OR ROLLING EQUIPMENT UNISTRUT IRON SHEILD W/LOAD DOCUMENTS
SHOULD ONLY BE USED TO CONSOLIDATE THE FINAL BACKFILL. SUPPORT (TYP.) BEARING INSULATION AT
ALL HANGER POINTS REFER 5’−0" DATE OF ISSUE
TO SPECS FOR ADDITIONAL
6. TO PREVENT DAMAGE TO THE PIPE AND DISTURBANCE TO PIPE EMBEDMENT, A MINIMUM DEPTH OF INFORMATION SEAMLESS 316
STAINLESS STEEL OR
THRUST BLOCK
(PER NFPA 24)
PROVIDE MANUFACTURE
RECOMMEND BACKFILL. FOR
02/17/2023
BACKFILL ABOVE THE PIPE SHOULD BE MAINTAINED. PIPE SHOULD ALWAYS BE INSTALLED BELOW THE BRASS WATER ENTRY. UNDERGROUND PIPING. PROJECT NUMBER
FROST LEVEL. TYPICALLY, IT IS NOT ADVISABLE TO ALLOW VEHICULAR TRAFFIC OR HEAVY CONSTRUCTION
EQUIPMENT TO TRAVERSE THE PIPE TRENCH. 1006083.00
DATE STAMP:2/16/2023 11:37:20 AM

SHEET TITLE
BACKFILL PIPING DETAIL not to scale 1 PIPE HANGER DETAIL not to scale 0 DOMESTIC WATER ENTRY DETAIL not to scale 0 FLOOR CLEANOUT DETAIL (FCO−1) not to scale 0 DETAILS

SHEET NUMBER

P3.01
CLIENT

B.V.

City of Richmond
1116 Myrtle Street
Richmond, TX 77469
RVB-1 T 281-342-0559
SK-1
DW-1

1/2 ARCHITECT
"HW
R

1/2 HWCP-1
"HW

PGAL
3/
4"C
W
"HW
R 1/2
2"HW L-1
1/
W
2"C

EDF-1 PGAL, LLC


EWH-1: LOCATED 3131 BRIARPARK DR.
ABOVE MS-1
SUITE 200
HOUSTON, TX 77042
WC-1
T 713 622 1444
F 713 968 9333
L-1 WC-1
2"C TBPE REG. No. F-2742
W
www.pgal.com
MS-1

INFRASTRUCTURE ASSOCIATES, INC.


6117 RICHMOND AVENUE, SUITE 200
HOUSTON, TEXAS 77057-6267
(713) 622-0120 PH (713) 622-0557
FAX
TBPE FIRM REGISTRATION #F-4506
2" DOMESTIC CW LINE TO CONNECT WWW.IAHOUSTON.COM
BACK TO UTILITY MAIN, REFER TO
CIVIL FOR CONTINUATION.

REGISTRATION
Copyright © 2016
RISER DIAGRAM - DOMESTIC
1

F
TE O T EX A
TA

S
4" VTR
4" SANITARY LINE TO BE CONNECTED ANWAR HASSAN
TO UTILITY MAIN. REFER TO CIVIL
64671
FOR CONTINUATION.

PR

R
LI C

EE
FE E N SE D N

O
SS I
ION A L ENG

2023-02-17
DRAWING HISTORY
2"V

№. DATE DESCRIPTION

SK-1
AN
3"S
FS-1
PROJECT NAME
City of Richmond
FCO-1
Economic
L-1 Development Dept.
4" VTR Buildout
FILE NAME: C:\Users\MarlonL\Documents\CRED_MEP_R22_ml1@iahouston.com.rvt

2"V 4" SANITARY LINE TO BE CONNECTED


TO UTILITY MAIN. REFER TO CIVIL
FOR CONTINUATION.
PROJECT LOCATION
1116 Myrtle St.
Richmond, TX 77469
FS-1 EDF-1 FD-1
2"V
PROJECT STATUS

100%
4"S
AN
4" SANITARY LINE TO BE CONNECTED
CONSTRUCTION
WC-1
TO UTILITY MAIN. REFER TO CIVIL DOCUMENTS
FOR CONTINUATION.
MS-1 FD-1 2"V DATE OF ISSUE

02/17/2023
FS-1 PROJECT NUMBER
AN
3"S
1006083.00
DATE STAMP:2/16/2023 12:03:13 PM

SHEET TITLE

RISER DIAGRAMS
FS-1
AN
3"S

FCO-1

SHEET NUMBER
RISER DIAGRAM - SANITARY
2
P4.01